Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:20
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2020-06-03 19:20:53
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:53
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1482.99 | 709.46 | 709.46 |
Net Site Energy | 1482.99 | 709.46 | 709.46 |
Total Source Energy | 4687.29 | 2242.38 | 2242.38 |
Net Source Energy | 4687.29 | 2242.38 | 2242.38 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 4.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 509.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 550.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 139.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 58.61 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1478.50 | 4.49 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 4.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 509.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 550.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 91.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 139.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 58.61 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 307.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 338.55 | 2.15 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 707.31 | 2.15 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 307.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 338.55 | 2.15 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 707.31 | 2.15 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1478.505 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1478.505 | 100.00 |
Total On-Site and Utility Electric Sources | 1478.505 | 100.00 |
Total Electricity End Uses | 1478.505 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 6.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1185.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Meter |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:53
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.75 | 20.75 | 20.0855 | 11.61 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.37 | 10.37 | 22.9594 | 11.61 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 20.8066 | 11.61 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 20.8066 | 11.61 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 20.8066 | 11.61 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.70 | 20.70 | 13.4441 | 11.61 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 13.4441 | 11.61 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 13.4441 | 11.61 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 13.4441 | 11.61 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.35 | 10.35 | 13.4441 | 11.61 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 17.1846 | 11.61 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 17.1846 | 11.61 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:53
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUN-15:50 | 02-JAN-08:09 | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 98898.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 86608.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 34106.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 16126.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5413.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 150314.14 | 98898.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 98898.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 86608.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 34106.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 16126.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5413.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:53
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 4.86 | 0.00 | 0.00 | 0.00 |
Cooling | 1614.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1744.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 290.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 441.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 185.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4682.43 | 4.86 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2.33 | 0.00 | 0.00 | 0.00 |
Cooling | 772.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 834.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 139.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 211.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 88.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2240.05 | 2.33 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2.33 | 0.00 | 0.00 | 0.00 |
Cooling | 772.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 834.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 139.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 211.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 88.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2240.05 | 2.33 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:53
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.69 |
SMSTORE1 DIRECT AIR | 1.41 |
SMSTORE2 DIRECT AIR | 1.40 |
SMSTORE3 DIRECT AIR | 1.41 |
SMSTORE4 DIRECT AIR | 1.40 |
LGSTORE2 DIRECT AIR | 2.46 |
SMSTORE5 DIRECT AIR | 1.30 |
SMSTORE6 DIRECT AIR | 1.29 |
SMSTORE7 DIRECT AIR | 1.30 |
SMSTORE8 DIRECT AIR | 1.46 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.69 | 2.69 | 2.69 | 2.69 | 2.69 | 2.69 | 1.00 | 1.00 | 2.69 |
PSZ-AC_2:2 | 1.41 | 1.41 | 1.41 | 1.41 | 1.41 | 1.41 | 1.00 | 1.00 | 1.41 |
PSZ-AC_3:3 | 1.40 | 1.40 | 1.40 | 1.40 | 1.40 | 1.40 | 1.00 | 1.00 | 1.40 |
PSZ-AC_4:4 | 1.41 | 1.41 | 1.41 | 1.41 | 1.41 | 1.41 | 1.00 | 1.00 | 1.41 |
PSZ-AC_5:5 | 1.40 | 1.40 | 1.40 | 1.40 | 1.40 | 1.40 | 1.00 | 1.00 | 1.40 |
PSZ-AC_6:6 | 2.46 | 2.46 | 2.46 | 2.46 | 2.46 | 2.46 | 1.00 | 1.00 | 2.46 |
PSZ-AC_7:7 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.00 | 1.00 | 1.30 |
PSZ-AC_8:8 | 1.29 | 1.29 | 1.29 | 1.29 | 1.29 | 1.29 | 1.00 | 1.000000 | 1.29 |
PSZ-AC_9:9 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.00 | 1.000000 | 1.30 |
PSZ-AC_10:10 | 1.46 | 1.46 | 1.46 | 1.46 | 1.46 | 1.46 | 1.00 | 1.00 | 1.46 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.69 | 0.411453 |
PSZ-AC_2:2_OA_CONTROLLER | 1.41 | 0.205727 |
PSZ-AC_3:3_OA_CONTROLLER | 1.40 | 0.205727 |
PSZ-AC_4:4_OA_CONTROLLER | 1.41 | 0.205727 |
PSZ-AC_5:5_OA_CONTROLLER | 1.40 | 0.205727 |
PSZ-AC_6:6_OA_CONTROLLER | 2.46 | 0.411453 |
PSZ-AC_7:7_OA_CONTROLLER | 1.30 | 0.205727 |
PSZ-AC_8:8_OA_CONTROLLER | 1.29 | 0.205727 |
PSZ-AC_9:9_OA_CONTROLLER | 1.30 | 0.205727 |
PSZ-AC_10:10_OA_CONTROLLER | 1.46 | 0.205727 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.69 | 2.69 | 2.69 | 1.78 | 54950.02 | 67231.47 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.41 | 1.41 | 1.41 | 0.929692 | 28546.08 | 34980.17 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.40 | 1.40 | 1.40 | 0.925857 | 28442.80 | 34850.73 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.41 | 1.41 | 1.41 | 0.927596 | 28489.84 | 34909.44 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.40 | 1.40 | 1.40 | 0.921800 | 28333.49 | 34713.75 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.46 | 2.46 | 2.46 | 1.62 | 50716.37 | 61933.67 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.30 | 1.30 | 1.30 | 0.858017 | 26613.04 | 32560.40 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.29 | 1.29 | 1.29 | 0.854487 | 26517.81 | 32441.25 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.30 | 1.30 | 1.30 | 0.857334 | 26594.74 | 32537.35 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.46 | 1.46 | 1.46 | 0.966032 | 29315.18 | 36207.07 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 2.69 | 1.35 | 1.80 | 44608.34 | 54950.02 | 27475.01 | 27475.01 | 0.729462 | 0.729460 | 0.729460 | 0.729460 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 1.41 | 0.704310 | 0.939080 | 23317.66 | 28546.08 | 14273.04 | 14273.04 | 0.731317 | 0.731320 | 0.731320 | 0.731320 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 1.40 | 0.701405 | 0.935207 | 23221.49 | 28442.80 | 14221.40 | 14221.40 | 0.731164 | 0.731160 | 0.731160 | 0.731160 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 1.41 | 0.702725 | 0.936967 | 23265.19 | 28489.84 | 14244.92 | 14244.92 | 0.731232 | 0.731230 | 0.731230 | 0.731230 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 1.40 | 0.698335 | 0.931113 | 23119.85 | 28333.49 | 14166.75 | 14166.75 | 0.731003 | 0.731000 | 0.731000 | 0.731000 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 2.46 | 1.23 | 1.64 | 41388.46 | 50716.37 | 25358.19 | 25358.19 | 0.725845 | 0.725840 | 0.725840 | 0.725840 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 1.30 | 0.650015 | 0.866687 | 21625.41 | 26613.04 | 13306.52 | 13306.52 | 0.728297 | 0.728300 | 0.728300 | 0.728300 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 1.29 | 0.647340 | 0.863120 | 21563.26 | 26517.81 | 13258.91 | 13258.91 | 0.728137 | 0.728140 | 0.728140 | 0.728140 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 1.30 | 0.649495 | 0.865993 | 21613.56 | 26594.74 | 13297.37 | 13297.37 | 0.728264 | 0.728260 | 0.728260 | 0.728260 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 1.46 | 0.731840 | 0.975787 | 24229.10 | 29315.18 | 14657.59 | 14657.59 | 0.734868 | 0.734870 | 0.734870 | 0.734870 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.69 | 2883.55 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.41 | 1559.57 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.40 | 1553.14 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.41 | 1556.06 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.40 | 1546.33 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.46 | 2629.13 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.30 | 1439.33 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.29 | 1433.41 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.30 | 1438.19 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.46 | 1566.21 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | 67231.47 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | 34980.17 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | 34850.73 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | 34909.44 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | 34713.75 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | 61933.67 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | 32560.40 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | 32441.25 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | 32537.35 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | 36207.07 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:53
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:53
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:53
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.76 | 20.75 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.67 | 10.37 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.43 | 20.70 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.13 | 10.35 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 20.085 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.385 | No |
2 | SMSTORE1 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 22.959 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 27.259 | No |
3 | SMSTORE2 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 20.807 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.107 | No |
4 | SMSTORE3 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 20.807 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.107 | No |
5 | SMSTORE4 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 20.807 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.107 | No |
6 | LGSTORE2 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
7 | SMSTORE5 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
8 | SMSTORE6 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
9 | SMSTORE7 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
10 | SMSTORE8 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 4683.750 | 13.444 | 156.145 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4683.750 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 2313.749 | 6.641 | 77.135 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2313.749 |
3 | SMSTORE1_LIGHTS | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1657.501 | 9.515 | 110.515 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1657.501 |
5 | SMSTORE2_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 1282.497 | 7.363 | 85.511 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1282.497 |
7 | SMSTORE3_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 1282.497 | 7.363 | 85.511 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1282.497 |
9 | SMSTORE4_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 1282.497 | 7.363 | 85.511 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1282.497 |
11 | LGSTORE2_LIGHTS | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 4683.750 | 13.444 | 156.145 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4683.750 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL | 20 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 30 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 31 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9750000 | 3.9750000 | 3.9750000 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
19 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
20 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
21 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
22 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
23 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
24 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
25 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
26 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
27 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
28 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
29 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 29 | 1 | VerySmooth | 3.241 | 0.252 | 0.162 | 0.276 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 30.0 | 0.159 | 4.569E-004 | 2.517E-004 | 0.317 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 15.0 | 4.561E-002 | 2.619E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 30.0 | 9.122E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 15.0 | 0.113 | 6.514E-004 | 3.022E-004 | 0.453 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 29747.58023 | 35697.09628 | 2.24566 | 2.69479 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 42.00000 | 9.11023E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
2 | LGSTORE1 | Heating | 14512.32302 | 17414.78762 | 0.64182 | 0.77019 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
3 | SMSTORE1 | Cooling | 15549.61580 | 18659.53895 | 1.17385 | 1.40862 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 42.00000 | 9.11023E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
4 | SMSTORE1 | Heating | 7293.64475 | 8752.37370 | 0.32257 | 0.38708 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
5 | SMSTORE2 | Cooling | 15485.48509 | 18582.58211 | 1.16901 | 1.40281 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.11022E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
6 | SMSTORE2 | Heating | 7378.94161 | 8854.72993 | 0.32634 | 0.39161 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
7 | SMSTORE3 | Cooling | 15514.57217 | 18617.48660 | 1.17121 | 1.40545 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.11022E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
8 | SMSTORE3 | Heating | 7448.92876 | 8938.71452 | 0.32944 | 0.39532 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
9 | SMSTORE4 | Cooling | 15417.62724 | 18501.15268 | 1.16389 | 1.39667 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.11022E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
10 | SMSTORE4 | Heating | 7592.46989 | 9110.96386 | 0.33578 | 0.40294 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
11 | LGSTORE2 | Cooling | 27122.97460 | 32547.56952 | 2.04752 | 2.45703 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.11022E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
12 | LGSTORE2 | Heating | 14353.88689 | 17224.66427 | 0.63482 | 0.76178 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
13 | SMSTORE5 | Cooling | 14350.81854 | 17220.98225 | 1.08335 | 1.30003 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.11022E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
14 | SMSTORE5 | Heating | 7789.30773 | 9347.16928 | 0.34449 | 0.41339 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
15 | SMSTORE6 | Cooling | 14291.78998 | 17150.14797 | 1.07890 | 1.29468 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.11022E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
16 | SMSTORE6 | Heating | 7789.59095 | 9347.50914 | 0.34450 | 0.41340 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
17 | SMSTORE7 | Cooling | 14339.39836 | 17207.27803 | 1.08249 | 1.29899 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.11022E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
18 | SMSTORE7 | Heating | 8007.10120 | 9608.52144 | 0.35412 | 0.42494 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
19 | SMSTORE8 | Cooling | 16158.14495 | 19389.77394 | 1.21974 | 1.46368 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 41.51500 | 9.11022E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
20 | SMSTORE8 | Heating | 9184.60351 | 11021.52421 | 0.40620 | 0.48744 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 44031.45 | 2.69479 | 2.69479 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 24348.00 | 0.77019 | 0.77019 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 22816.38 | 1.40862 | 1.40862 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 12218.30 | 0.38708 | 0.38708 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 22739.49 | 1.40281 | 1.40281 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 12319.16 | 0.39161 | 0.39161 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 22773.24 | 1.40545 | 1.40545 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 12401.92 | 0.39532 | 0.39532 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 22658.47 | 1.39667 | 1.39667 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 12571.66 | 0.40294 | 0.40294 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 40917.77 | 2.45703 | 2.45703 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 24160.64 | 0.76178 | 0.76178 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 21393.20 | 1.30003 | 1.30003 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 12804.43 | 0.41339 | 0.41339 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 21323.26 | 1.29468 | 1.29468 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 12804.76 | 0.41340 | 0.41340 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 21379.05 | 1.29899 | 1.29899 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 13061.97 | 0.42494 | 0.42494 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 23431.16 | 1.46368 | 1.46368 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 14454.39 | 0.48744 | 0.48744 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.69479 |
2 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.40862 |
3 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.40281 |
4 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.40545 |
5 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.39667 |
6 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.45703 |
7 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.30003 |
8 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.29468 |
9 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.29899 |
10 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.46368 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.69479 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.69479 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.69479 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.69479 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.69479 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.69479 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.40862 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.40862 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.40862 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.40862 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.40862 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.40862 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.40281 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.40281 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.40281 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.40281 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.40281 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.40281 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.40545 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.40545 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.40545 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.40545 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.40545 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.40545 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.39667 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.39667 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.39667 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.39667 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.39667 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.39667 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.45703 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.45703 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.45703 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.45703 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.45703 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.45703 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.30003 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.30003 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.30003 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.30003 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.30003 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.30003 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.29468 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.29468 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.29468 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.29468 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.29468 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.29468 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.29899 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.29899 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.29899 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.29899 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.29899 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.29899 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.46368 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.46368 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.46368 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.46368 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.46368 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.46368 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.69479 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.40862 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.40281 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.40545 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.39667 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.45703 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.30003 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.29468 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.29899 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.46368 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.69479 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.69479 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.69479 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.69479 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.77856 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.69479 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.34740 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.79653 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 44608.34299 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 54950.02000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 27475.01000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 27475.01000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72946 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72946 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72946 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72946 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 54950.02000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 67231.47009 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
122 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.69479 |
123 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2883.55377 |
124 | Coil:Heating:Fuel | PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 67231.47009 |
125 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.40862 |
126 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.40862 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.40862 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.40862 |
130 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.92969 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.40862 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.70431 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.93908 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 23317.66264 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 28546.08000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14273.04000 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 14273.04000 |
138 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73132 |
139 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73132 |
140 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73132 |
141 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73132 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28546.08000 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34980.17154 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
146 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.40862 |
147 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1559.57084 |
148 | Coil:Heating:Fuel | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 34980.17154 |
149 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.40281 |
150 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
151 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.40281 |
152 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.40281 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.40281 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.92586 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.40281 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.70141 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.93521 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 23221.48651 |
159 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 28442.80000 |
160 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14221.40000 |
161 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 14221.40000 |
162 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73116 |
163 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73116 |
164 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73116 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73116 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28442.80000 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34850.72723 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
170 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.40281 |
171 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1553.13796 |
172 | Coil:Heating:Fuel | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 34850.72723 |
173 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.40545 |
174 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.40545 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.40545 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.40545 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.92760 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.40545 |
180 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.70273 |
181 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.93697 |
182 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 23265.18788 |
183 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 28489.84000 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14244.92000 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 14244.92000 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73123 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73123 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73123 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73123 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28489.84000 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34909.44021 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
194 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.40545 |
195 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1556.05527 |
196 | Coil:Heating:Fuel | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 34909.44021 |
197 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.39667 |
198 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.39667 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.39667 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.39667 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.92180 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.39667 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.69834 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.93111 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 23119.84771 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 28333.49000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14166.74500 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 14166.74500 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73100 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73100 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73100 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73100 |
214 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28333.49000 |
215 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34713.75337 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
218 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.39667 |
219 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1546.33189 |
220 | Coil:Heating:Fuel | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 34713.75337 |
221 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.45703 |
222 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.45703 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.45703 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.45703 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.62164 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.45703 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.22852 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.63802 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 41388.45675 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 50716.37000 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 25358.18500 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 25358.18500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72585 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72584 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72584 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72584 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 50716.37000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 61933.67132 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
241 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
242 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.45703 |
243 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2629.13386 |
244 | Coil:Heating:Fuel | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 61933.67132 |
245 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.30003 |
246 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.30003 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.30003 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.30003 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.85802 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.30003 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65002 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.86669 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21625.40750 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 26613.04000 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13306.52000 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 13306.52000 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72830 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72830 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72830 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72830 |
262 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26613.04000 |
263 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32560.40339 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
266 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.30003 |
267 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1439.33434 |
268 | Coil:Heating:Fuel | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 32560.40339 |
269 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.29468 |
270 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
271 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.29468 |
272 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.29468 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.29468 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.85449 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.29468 |
276 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.64734 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.86312 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21563.26260 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 26517.81000 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13258.90500 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 13258.90500 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72814 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72814 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72814 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72814 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26517.81000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32441.25401 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.29468 |
291 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1433.41399 |
292 | Coil:Heating:Fuel | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 32441.25401 |
293 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.29899 |
294 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.29899 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.29899 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.29899 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.85733 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.29899 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.64950 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.86599 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21613.56381 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 26594.74000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13297.37000 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 13297.37000 |
306 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72826 |
307 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72826 |
308 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72826 |
309 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72826 |
310 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26594.74000 |
311 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32537.34834 |
312 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
313 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
314 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.29899 |
315 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1438.18877 |
316 | Coil:Heating:Fuel | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 32537.34834 |
317 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.46368 |
318 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
319 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.46368 |
320 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.46368 |
321 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.46368 |
322 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96603 |
323 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.46368 |
324 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.73184 |
325 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.97579 |
326 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 24229.10114 |
327 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 29315.18000 |
328 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14657.59000 |
329 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 14657.59000 |
330 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73487 |
331 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73487 |
332 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73487 |
333 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73487 |
334 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29315.18000 |
335 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36207.06555 |
336 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
337 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
338 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.46368 |
339 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1566.21120 |
340 | Coil:Heating:Fuel | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 36207.06555 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 52831.6 | 11.40 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 27438.8 | 33.81 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 27340.1 | 45.49 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 27385.1 | 56.97 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 27235.6 | 68.85 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 48784.5 | 49.42 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 25591.0 | 107.05 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 25500.0 | 119.02 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 25573.5 | 130.25 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 28164.9 | 129.33 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 58.20 | 78.94 | 58.20 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.10 | 39.47 | 29.10 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 58.24 | 78.94 | 58.24 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 10 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 4.6406942458E-002 | 5.9414123068E-002 | Pass | Pass | 0.9850131894 | 9.1424096303 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 5.6951268028E-002 | 0.1030704260 | Pass | Pass | 7.8536912155E-002 | 0.3089104179 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 4.2092876003E-002 | 6.3961355888E-002 | Pass | Pass | 0.2324246661 | 1.4821631549 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.9468075840E-002 | 8.8534554152E-002 | Pass | Pass | 0.2314225675 | 0.9293680905 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.5868591000E-002 | 0.1171312173 | Pass | Pass | 0.2936663879 | 1.4851981490 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 3.4396916267E-002 | 0.1656611970 | Pass | Pass | 0.1342381616 | 0.3880132893 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 3.4570412982E-002 | 0.1734802991 | Pass | Pass | 0.2852813811 | 1.0607539818 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 3.5052427179E-002 | 0.1803960851 | Pass | Pass | 0.2330196023 | 0.7113027819 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 3.7352859170E-002 | 0.2018197817 | Pass | Pass | 0.3420946905 | 1.3320083160 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 4.6762495393E-002 | 0.2456297439 | Pass | Pass | 0.3981027950 | 1.7960900200 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:53
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:53
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 78.94 | 58.20 | 180.00 | 90.00 | S |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.10 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 78.94 | 58.24 | 180.00 | 90.00 | S |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 3.241 | 0.252 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 3.241 | 0.252 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 3.241 | 0.252 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
Total or Average | 124.29 | 3.241 | 0.252 | 0.276 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 124.29 | 3.241 | 0.252 | 0.276 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE8_WALL_3 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:53
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:53
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | 13.4441 | 348.39 | 4683.75 | LightsWired | TYPE1_LIGHT_SCH | 98.22 | 168.00 | 98.21 | 0.0000 | Y | 86.34 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | 6.6413 | 348.39 | 2313.75 | LightsWired | TYPE1_LIGHT_SCH | 98.22 | 168.00 | 98.21 | 0.0000 | Y | 42.65 |
SMSTORE1_LIGHTS | SMSTORE1 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE1_LIGHT_SCH | 98.22 | 168.00 | 98.21 | 0.0000 | Y | 43.17 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | 9.5153 | 174.19 | 1657.50 | LightsWired | TYPE1_LIGHT_SCH | 98.22 | 168.00 | 98.21 | 0.0000 | Y | 30.56 |
SMSTORE2_LIGHTS | SMSTORE2 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 34.27 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | 7.3625 | 174.19 | 1282.50 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.77 |
SMSTORE3_LIGHTS | SMSTORE3 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 34.27 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | 7.3625 | 174.19 | 1282.50 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.77 |
SMSTORE4_LIGHTS | SMSTORE4 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 34.27 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | 7.3625 | 174.19 | 1282.50 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.77 |
LGSTORE2_LIGHTS | LGSTORE2 | 13.4441 | 348.39 | 4683.75 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 63.00 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | 0.0000 | 348.39 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 31.50 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 31.50 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 31.50 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 31.50 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 8.5923 | 4180.64 | 35921.24 | 550.85 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 418.40 | AstronomicalClock | - | 41.75 | 41.75 | 3.28 | |
EXTERIOR_LIGHTS_B | 6630.02 | AstronomicalClock | - | 83.75 | 71.15 | 88.55 | |
Exterior Lighting Total | 7048.42 | 91.83 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:53
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 54950.02 | 40083.84 | 14866.18 | 0.73 | 3.73 | |||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 28546.08 | 20876.32 | 7669.76 | 0.73 | 3.80 | |||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 28442.80 | 20796.24 | 7646.56 | 0.73 | 3.80 | |||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 28489.84 | 20832.63 | 7657.21 | 0.73 | 3.80 | |||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 28333.49 | 20711.78 | 7621.71 | 0.73 | 3.80 | |||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 50716.37 | 36811.97 | 13904.40 | 0.73 | 3.73 | |||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 26613.04 | 19382.28 | 7230.76 | 0.73 | 3.80 | |||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 26517.81 | 19308.68 | 7209.13 | 0.73 | 3.80 | |||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 26594.74 | 19367.89 | 7226.85 | 0.73 | 3.80 | |||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 29315.18 | 21542.85 | 7772.33 | 0.73 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 52831.6 | 11.40 | ||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 27438.8 | 33.81 | ||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 27340.1 | 45.49 | ||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 27385.1 | 56.97 | ||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 27235.6 | 68.85 | ||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 48784.5 | 49.42 | ||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 25591.0 | 107.05 | ||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 25500.0 | 119.02 | ||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 25573.5 | 130.25 | ||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 28164.9 | 129.33 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 67231.47 | 0.80 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 34980.17 | 0.80 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 34850.73 | 0.80 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 34909.44 | 0.80 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 34713.75 | 0.80 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 61933.67 | 0.80 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 32560.40 | 0.80 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 32441.25 | 0.80 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 32537.35 | 0.80 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 36207.07 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.69 | 2883.55 | 1070.05 | 1.00 | 1.28 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.41 | 1559.57 | 1107.16 | 1.00 | 1.33 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.40 | 1553.14 | 1107.16 | 1.00 | 1.33 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.41 | 1556.06 | 1107.16 | 1.00 | 1.33 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.40 | 1546.33 | 1107.16 | 1.00 | 1.33 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.46 | 2629.13 | 1070.05 | 1.00 | 1.29 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.30 | 1439.33 | 1107.16 | 1.00 | 1.34 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.29 | 1433.41 | 1107.16 | 1.00 | 1.34 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.30 | 1438.19 | 1107.16 | 1.00 | 1.34 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.46 | 1566.21 | 1070.05 | 1.00 | 1.37 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:53
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 29747.58 | 35697.10 | 102.46 | 2.246 | 2.695 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 23.89 | 23.89 | 0.00749 | 42.00 | 0.00911 | 0.411 | 0.00 |
SMSTORE1 | 15549.62 | 18659.54 | 107.12 | 1.174 | 1.409 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 23.89 | 23.89 | 0.00750 | 42.00 | 0.00911 | 0.206 | 0.00 |
SMSTORE2 | 15485.49 | 18582.58 | 106.68 | 1.169 | 1.403 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00750 | 41.92 | 0.00911 | 0.206 | 0.00 |
SMSTORE3 | 15514.57 | 18617.49 | 106.88 | 1.171 | 1.405 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00750 | 41.92 | 0.00911 | 0.206 | 0.00 |
SMSTORE4 | 15417.63 | 18501.15 | 106.21 | 1.164 | 1.397 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00750 | 41.92 | 0.00911 | 0.206 | 0.00 |
LGSTORE2 | 27122.97 | 32547.57 | 93.42 | 2.048 | 2.457 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00752 | 41.92 | 0.00911 | 0.411 | 0.00 |
SMSTORE5 | 14350.82 | 17220.98 | 98.86 | 1.083 | 1.300 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00753 | 41.92 | 0.00911 | 0.206 | 0.00 |
SMSTORE6 | 14291.79 | 17150.15 | 98.45 | 1.079 | 1.295 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00753 | 41.92 | 0.00911 | 0.206 | 0.00 |
SMSTORE7 | 14339.40 | 17207.28 | 98.78 | 1.082 | 1.299 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00753 | 41.92 | 0.00911 | 0.206 | 0.00 |
SMSTORE8 | 16158.14 | 19389.77 | 111.31 | 1.220 | 1.464 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 23.89 | 23.89 | 0.00749 | 41.52 | 0.00911 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 14512.32 | 17414.79 | 49.99 | 0.642 | 0.770 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00735 | 6.30 | 0.00607 | 0.411 | 0.00 |
SMSTORE1 | 7293.64 | 8752.37 | 50.25 | 0.323 | 0.387 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00728 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE2 | 7378.94 | 8854.73 | 50.83 | 0.326 | 0.392 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00729 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE3 | 7448.93 | 8938.71 | 51.31 | 0.329 | 0.395 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00729 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE4 | 7592.47 | 9110.96 | 52.30 | 0.336 | 0.403 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00730 | 6.30 | 0.00607 | 0.206 | 0.00 |
LGSTORE2 | 14353.89 | 17224.66 | 49.44 | 0.635 | 0.762 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00735 | 6.30 | 0.00607 | 0.411 | 0.00 |
SMSTORE5 | 7789.31 | 9347.17 | 53.66 | 0.344 | 0.413 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00731 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE6 | 7789.59 | 9347.51 | 53.66 | 0.345 | 0.413 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00731 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE7 | 8007.10 | 9608.52 | 55.16 | 0.354 | 0.425 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00732 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE8 | 9184.60 | 11021.52 | 63.27 | 0.406 | 0.487 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00736 | 6.30 | 0.00607 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.69 | 2.69 | 0.77 | 0.77 | 2.6948 | 2.6948 | 2.6948 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.41 | 1.41 | 0.39 | 0.39 | 1.4086 | 1.4086 | 1.4086 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.40 | 1.40 | 0.39 | 0.39 | 1.4028 | 1.4028 | 1.4028 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.41 | 1.41 | 0.40 | 0.40 | 1.4054 | 1.4054 | 1.4054 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.40 | 1.40 | 0.40 | 0.40 | 1.3967 | 1.3967 | 1.3967 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.46 | 2.46 | 0.76 | 0.76 | 2.4570 | 2.4570 | 2.4570 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.30 | 1.30 | 0.41 | 0.41 | 1.3000 | 1.3000 | 1.3000 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.29 | 1.29 | 0.41 | 0.41 | 1.2947 | 1.2947 | 1.2947 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.30 | 1.30 | 0.42 | 0.42 | 1.2990 | 1.2990 | 1.2990 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.46 | 1.46 | 0.49 | 0.49 | 1.4637 | 1.4637 | 1.4637 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 27475.010 | 0.000 | 2.694790 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 27475.01 | 27475.01 | 2.694790 | 26.65 | 16.38 | 0.00773441 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 15.2685 | 23.89 | 0.00748650 | 39.6138 | 29747.58 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 67231.470 | 67231.470 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 67231.47 | 67231.47 | 2.694791 | 13.20 | 10.15 | 0.00666764 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.2685 | 21.11 | 0.00735043 | 46.0592 | 14512.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 14273.040 | 0.000 | 1.408620 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 14273.04 | 14273.04 | 1.408620 | 26.53 | 16.34 | 0.00773238 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 14.6048 | 23.89 | 0.00749673 | 39.6675 | 15549.62 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 34980.172 | 34980.172 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34980.17 | 34980.17 | 1.408624 | 13.24 | 10.14 | 0.00664032 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.6048 | 21.11 | 0.00728463 | 45.6521 | 7293.64 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 14221.400 | 0.000 | 1.402810 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 14221.40 | 14221.40 | 1.402810 | 26.54 | 16.35 | 0.00773491 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 14.6653 | 23.89 | 0.00749850 | 39.6767 | 15484.72 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 34850.727 | 34850.727 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34850.73 | 34850.73 | 1.402814 | 13.33 | 10.19 | 0.00664915 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.6653 | 21.11 | 0.00728754 | 45.6701 | 7378.94 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 14244.920 | 0.000 | 1.405450 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 14244.92 | 14244.92 | 1.405450 | 26.54 | 16.34 | 0.00773382 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 14.6378 | 23.89 | 0.00749771 | 39.6726 | 15513.20 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 34909.440 | 34909.440 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34909.44 | 34909.44 | 1.405449 | 13.40 | 10.23 | 0.00665679 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.6378 | 21.11 | 0.00729096 | 45.6913 | 7448.93 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 14166.745 | 0.000 | 1.396670 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 14166.75 | 14166.75 | 1.396670 | 26.56 | 16.35 | 0.00773757 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 14.7298 | 23.89 | 0.00750037 | 39.6864 | 15416.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 34713.753 | 34713.753 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34713.75 | 34713.75 | 1.396667 | 13.55 | 10.31 | 0.00667232 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.7298 | 21.11 | 0.00729820 | 45.7362 | 7592.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 25358.185 | 0.000 | 2.457030 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 25358.19 | 25358.19 | 2.457030 | 26.92 | 16.53 | 0.00779008 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 16.7460 | 23.89 | 0.00752438 | 39.8118 | 27119.30 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 61933.671 | 61933.671 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 61933.67 | 61933.67 | 2.457026 | 13.11 | 10.10 | 0.00665820 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 16.7460 | 21.11 | 0.00734629 | 46.0335 | 14353.89 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 13306.520 | 0.000 | 1.300030 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 13306.52 | 13306.52 | 1.300030 | 26.75 | 16.46 | 0.00778156 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 15.8248 | 23.89 | 0.00753160 | 39.8497 | 14348.30 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 32560.403 | 32560.403 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32560.40 | 32560.40 | 1.300025 | 13.74 | 10.41 | 0.00669260 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.8248 | 21.11 | 0.00730709 | 45.7913 | 7789.31 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 13258.905 | 0.000 | 1.294680 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 13258.91 | 13258.91 | 1.294680 | 26.77 | 16.47 | 0.00778414 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 15.8902 | 23.89 | 0.00753344 | 39.8594 | 14289.26 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 32441.254 | 32441.254 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32441.25 | 32441.25 | 1.294678 | 13.74 | 10.41 | 0.00669266 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.8902 | 21.11 | 0.00730715 | 45.7917 | 7789.59 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 13297.370 | 0.000 | 1.298990 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 13297.37 | 13297.37 | 1.298990 | 26.76 | 16.46 | 0.00778209 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 15.8374 | 23.89 | 0.00753196 | 39.8516 | 14336.36 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 32537.348 | 32537.348 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32537.35 | 32537.35 | 1.298991 | 13.94 | 10.52 | 0.00671453 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.8374 | 21.11 | 0.00731719 | 45.8539 | 8007.10 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 14657.590 | 0.000 | 1.463680 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 14657.59 | 14657.59 | 1.463680 | 26.39 | 16.28 | 0.00771312 | 12.80 | 11.87 | 0.00850000 | 41.68 | 0.00911023 | 22.11 | 14.0554 | 23.89 | 0.00748507 | 39.6064 | 16092.64 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 36207.066 | 36207.066 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36207.07 | 36207.07 | 1.463684 | 14.86 | 11.02 | 0.00681817 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.0554 | 21.11 | 0.00736284 | 46.1368 | 9184.60 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:20:53
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27475.010 | 0.000 | 2.694790 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2179 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 27475.01 | 27475.01 | 1.0000 | 3.16310532 | 2.694790 | 26.65 | 16.38 | 0.00773441 | 46508.5 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27475.01 | 42.00 | 0.00911023 | 22.20 | 0.41145340 | 15.2685 | 23.89 | 0.00748650 | 23.89 | 0.00748650 | 39.6138 | 29747.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 67231.470 | 67231.470 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.694791 | 3.16310651 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 67231.47 | 67231.47 | 1.0000 | 3.16310651 | 2.694791 | 13.20 | 10.15 | 0.00666764 | 30100.5 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 67231.47 | 6.30 | 0.00607234 | 6.30 | 0.41145340 | 15.2685 | 21.11 | 0.00735043 | 21.11 | 0.00735043 | 46.0592 | 14512.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 14273.040 | 0.000 | 1.408620 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2141 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 14273.04 | 14273.04 | 1.0000 | 1.65341767 | 1.408620 | 26.53 | 16.34 | 0.00773238 | 46380.8 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14273.04 | 42.00 | 0.00911023 | 22.20 | 0.20572670 | 14.6048 | 23.89 | 0.00749673 | 23.89 | 0.00749673 | 39.6675 | 15549.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34980.172 | 34980.172 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.408624 | 1.65342287 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34980.17 | 34980.17 | 1.0000 | 1.65342287 | 1.408624 | 13.24 | 10.14 | 0.00664032 | 30072.8 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34980.17 | 6.30 | 0.00607234 | 6.30 | 0.20572670 | 14.6048 | 21.11 | 0.00728463 | 21.11 | 0.00728463 | 45.6521 | 7293.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 14221.400 | 0.000 | 1.402810 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2188 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 14221.40 | 14221.40 | 1.0000 | 1.64659798 | 1.402810 | 26.54 | 16.35 | 0.00773491 | 46398.5 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14221.40 | 42.00 | 0.00911023 | 22.20 | 0.20572670 | 14.6653 | 23.89 | 0.00749854 | 23.89 | 0.00749850 | 39.6767 | 15484.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34850.727 | 34850.727 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.402814 | 1.64660287 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34850.73 | 34850.73 | 1.0000 | 1.64660287 | 1.402814 | 13.33 | 10.19 | 0.00664915 | 30187.6 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34850.73 | 6.30 | 0.00607234 | 6.30 | 0.20572670 | 14.6653 | 21.11 | 0.00728754 | 21.11 | 0.00728754 | 45.6701 | 7378.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 14244.920 | 0.000 | 1.405450 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2168 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 14244.92 | 14244.92 | 1.0000 | 1.64969678 | 1.405450 | 26.54 | 16.34 | 0.00773382 | 46390.8 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14244.92 | 42.00 | 0.00911023 | 22.20 | 0.20572670 | 14.6378 | 23.89 | 0.00749777 | 23.89 | 0.00749771 | 39.6726 | 15513.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34909.440 | 34909.440 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.405449 | 1.64969574 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34909.44 | 34909.44 | 1.0000 | 1.64969574 | 1.405449 | 13.40 | 10.23 | 0.00665679 | 30281.2 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34909.44 | 6.30 | 0.00607234 | 6.30 | 0.20572670 | 14.6378 | 21.11 | 0.00729096 | 21.11 | 0.00729096 | 45.6913 | 7448.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 14166.745 | 0.000 | 1.396670 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2238 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 14166.75 | 14166.75 | 1.0000 | 1.63939094 | 1.396670 | 26.56 | 16.35 | 0.00773757 | 46417.3 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14166.75 | 42.00 | 0.00911023 | 22.20 | 0.20572670 | 14.7298 | 23.89 | 0.00750043 | 23.89 | 0.00750037 | 39.6864 | 15416.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34713.753 | 34713.753 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.396667 | 1.63938723 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34713.75 | 34713.75 | 1.0000 | 1.63938723 | 1.396667 | 13.55 | 10.31 | 0.00667232 | 30468.7 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34713.75 | 6.30 | 0.00607234 | 6.30 | 0.20572670 | 14.7298 | 21.11 | 0.00729820 | 21.11 | 0.00729820 | 45.7362 | 7592.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25358.185 | 0.000 | 2.457030 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3214 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 25358.19 | 25358.19 | 1.0000 | 2.88402609 | 2.457030 | 26.92 | 16.53 | 0.00779008 | 46923.7 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25358.19 | 42.00 | 0.00911023 | 22.20 | 0.41145340 | 16.7460 | 23.89 | 0.00752450 | 23.89 | 0.00752438 | 39.8118 | 27119.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 61933.671 | 61933.671 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.457026 | 2.88402128 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 61933.67 | 61933.67 | 1.0000 | 2.88402128 | 2.457026 | 13.11 | 10.10 | 0.00665820 | 29987.8 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 61933.67 | 6.30 | 0.00607234 | 6.30 | 0.41145340 | 16.7460 | 21.11 | 0.00734629 | 21.11 | 0.00734629 | 46.0335 | 14353.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 13306.520 | 0.000 | 1.300030 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3055 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 13306.52 | 13306.52 | 1.0000 | 1.52595631 | 1.300030 | 26.75 | 16.46 | 0.00778156 | 46732.0 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13306.52 | 42.00 | 0.00911023 | 22.20 | 0.20572670 | 15.8248 | 23.89 | 0.00753172 | 23.89 | 0.00753160 | 39.8497 | 14348.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32560.403 | 32560.403 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.300025 | 1.52595076 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32560.40 | 32560.40 | 1.0000 | 1.52595076 | 1.300025 | 13.74 | 10.41 | 0.00669260 | 30714.3 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32560.40 | 6.30 | 0.00607234 | 6.30 | 0.20572670 | 15.8248 | 21.11 | 0.00730709 | 21.11 | 0.00730709 | 45.7913 | 7789.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 13258.905 | 0.000 | 1.294680 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3103 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 13258.91 | 13258.91 | 1.0000 | 1.51967656 | 1.294680 | 26.77 | 16.47 | 0.00778414 | 46750.6 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13258.91 | 42.00 | 0.00911023 | 22.20 | 0.20572670 | 15.8902 | 23.89 | 0.00753356 | 23.89 | 0.00753344 | 39.8594 | 14289.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32441.254 | 32441.254 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.294678 | 1.51967414 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32441.25 | 32441.25 | 1.0000 | 1.51967414 | 1.294678 | 13.74 | 10.41 | 0.00669266 | 30714.7 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32441.25 | 6.30 | 0.00607234 | 6.30 | 0.20572670 | 15.8902 | 21.11 | 0.00730715 | 21.11 | 0.00730715 | 45.7917 | 7789.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 13297.370 | 0.000 | 1.298990 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3065 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 13297.37 | 13297.37 | 1.0000 | 1.52473557 | 1.298990 | 26.76 | 16.46 | 0.00778209 | 46735.7 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13297.37 | 42.00 | 0.00911023 | 22.20 | 0.20572670 | 15.8374 | 23.89 | 0.00753210 | 23.89 | 0.00753196 | 39.8516 | 14336.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32537.348 | 32537.348 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.298991 | 1.52473625 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32537.35 | 32537.35 | 1.0000 | 1.52473625 | 1.298991 | 13.94 | 10.52 | 0.00671453 | 30973.6 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32537.35 | 6.30 | 0.00607234 | 6.30 | 0.20572670 | 15.8374 | 21.11 | 0.00731719 | 21.11 | 0.00731719 | 45.8539 | 8007.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 14657.590 | 0.000 | 1.463680 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.1783 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 14657.59 | 14657.59 | 1.0000 | 1.71804630 | 1.463680 | 26.39 | 16.28 | 0.00771312 | 46187.7 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14657.59 | 41.68 | 0.00911023 | 22.11 | 0.20572670 | 14.0554 | 23.89 | 0.00748426 | 23.89 | 0.00748507 | 39.6064 | 16092.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36207.066 | 36207.066 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.463684 | 1.71805114 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36207.07 | 36207.07 | 1.0000 | 1.71805114 | 1.463684 | 14.86 | 11.02 | 0.00681817 | 32170.7 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36207.07 | 6.30 | 0.00607234 | 6.30 | 0.20572670 | 14.0554 | 21.11 | 0.00736284 | 21.11 | 0.00736284 | 46.1368 | 9184.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:53
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 4434.33 | 1449.67 | 951.67 |
SMSTORE1 | 4412.67 | 1112.50 | 801.83 |
SMSTORE2 | 3383.33 | 1200.33 | 890.33 |
SMSTORE3 | 3350.67 | 1218.67 | 881.17 |
SMSTORE4 | 3277.67 | 1285.17 | 895.67 |
LGSTORE2 | 2839.67 | 1371.17 | 878.00 |
SMSTORE5 | 2738.67 | 1426.00 | 885.50 |
SMSTORE6 | 2718.17 | 1449.17 | 890.00 |
SMSTORE7 | 2705.50 | 1479.67 | 883.67 |
SMSTORE8 | 2764.50 | 1420.67 | 792.00 |
Facility | 4605.50 | 2094.33 | 1185.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 9.50 | 0.00 | 6.67 |
SMSTORE1 | 0.00 | 4.17 | 0.00 | 3.00 |
SMSTORE2 | 0.00 | 14.83 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 17.17 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 13.83 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 12.00 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 9.50 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 9.00 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 9.00 | 0.00 | 0.00 |
SMSTORE8 | 0.00 | 12.83 | 0.00 | 0.00 |
Facility | 0.00 | 31.50 | 0.00 | 6.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:53
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.848 | 0.333 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.703 | 0.375 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 0.848 | 0.494 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 0.848 | 0.494 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 0.848 | 0.494 | 0.000 | 0.000 |
LGSTORE2 | 13.22 | 30.00 | 1805.20 | 0.848 | 0.462 | 0.000 | 0.000 |
SMSTORE5 | 6.61 | 15.00 | 902.60 | 0.848 | 0.527 | 0.000 | 0.000 |
SMSTORE6 | 6.61 | 15.00 | 902.60 | 0.848 | 0.527 | 0.000 | 0.000 |
SMSTORE7 | 6.61 | 15.00 | 902.60 | 0.848 | 0.527 | 0.000 | 0.000 |
SMSTORE8 | 6.61 | 15.00 | 902.60 | 0.848 | 0.536 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.779 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 0.778 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 0.777 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 0.777 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 13.22 | 30.00 | 1805.20 | 0.778 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 6.61 | 15.00 | 902.60 | 0.778 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 6.61 | 15.00 | 902.60 | 0.778 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 6.61 | 15.00 | 902.60 | 0.777 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 6.61 | 15.00 | 902.60 | 0.777 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:53
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:20:53
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1478.50 | 3448.90 | 15-JAN-07:20 | 150314.14 | 22-JUN-15:50 |
Electricity:Building | 679.00 | 2237.90 | 01-JAN-00:10 | 42165.88 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 155.25 | 423.51 | 01-JAN-00:10 | 7978.91 | 01-JAN-10:10 |
InteriorLights:Electricity | 550.85 | 1795.07 | 01-JAN-08:10 | 34106.38 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 129.00 | 349.25 | 01-JAN-08:10 | 6635.66 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 550.85 | 1795.07 | 01-JAN-08:10 | 34106.38 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 86.85 | 236.79 | 01-JAN-00:10 | 4464.19 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 73.73 | 199.61 | 01-JAN-08:10 | 3792.57 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 63.46 | 218.04 | 01-JAN-00:10 | 4114.78 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 53.04 | 181.22 | 01-JAN-00:10 | 3443.15 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 63.46 | 218.04 | 01-JAN-00:10 | 4114.78 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 53.04 | 181.22 | 01-JAN-00:10 | 3443.15 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 63.46 | 218.04 | 01-JAN-00:10 | 4114.78 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 53.04 | 181.22 | 01-JAN-00:10 | 3443.15 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 82.18 | 307.83 | 01-JAN-00:10 | 5792.81 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 63.00 | 234.19 | 01-JAN-00:10 | 4449.56 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 41.09 | 153.91 | 01-JAN-00:10 | 2896.41 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 31.50 | 117.09 | 01-JAN-00:10 | 2224.78 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 41.09 | 153.91 | 01-JAN-00:10 | 2896.41 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 31.50 | 117.09 | 01-JAN-00:10 | 2224.78 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 41.09 | 153.91 | 01-JAN-00:10 | 2896.41 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 31.50 | 117.09 | 01-JAN-00:10 | 2224.78 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 41.09 | 153.91 | 01-JAN-00:10 | 2896.41 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 31.50 | 117.09 | 01-JAN-00:10 | 2224.78 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
Electricity:Plant | 58.61 | 1211.00 | 01-JAN-09:10 | 11810.53 | 06-JAN-13:50 |
WaterSystems:Electricity | 58.61 | 1211.00 | 01-JAN-09:10 | 11810.53 | 06-JAN-13:50 |
Water Heater:WaterSystems:Electricity | 58.61 | 1211.00 | 01-JAN-09:10 | 11810.53 | 06-JAN-13:50 |
ElectricityPurchased:Facility | 1478.50 | 3448.90 | 15-JAN-07:20 | 150314.14 | 22-JUN-15:50 |
ElectricityPurchased:Plant | 1478.50 | 3448.90 | 15-JAN-07:20 | 150314.14 | 22-JUN-15:50 |
Cogeneration:ElectricityPurchased | 1478.50 | 3448.90 | 15-JAN-07:20 | 150314.14 | 22-JUN-15:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1478.50 | 3448.90 | 15-JAN-07:20 | 150314.14 | 22-JUN-15:50 |
ElectricityNet:Plant | 1478.50 | 3448.90 | 15-JAN-07:20 | 150314.14 | 22-JUN-15:50 |
Cogeneration:ElectricityNet | 1478.50 | 3448.90 | 15-JAN-07:20 | 150314.14 | 22-JUN-15:50 |
Electricity:HVAC | 649.06 | 0.00 | 01-JAN-00:10 | 103721.65 | 22-JUN-16:10 |
Fans:Electricity | 139.36 | 0.00 | 01-JAN-00:10 | 16552.50 | 01-JUL-15:00 |
General:Fans:Electricity | 139.36 | 0.00 | 01-JAN-00:10 | 16552.50 | 01-JUL-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 509.69 | 0.00 | 01-JAN-00:10 | 87401.99 | 22-JUN-16:10 |
ExteriorLights:Electricity | 91.83 | 0.00 | 01-JAN-07:20 | 7048.42 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 91.83 | 0.00 | 01-JAN-07:20 | 7048.42 | 01-JAN-06:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 4.49 | 0.00 | 01-JAN-00:10 | 98898.98 | 02-JAN-08:10 |
Gas:HVAC | 4.49 | 0.00 | 01-JAN-00:10 | 98898.98 | 02-JAN-08:10 |
Heating:Gas | 4.49 | 0.00 | 01-JAN-00:10 | 98898.98 | 02-JAN-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 3033.26 | 0.00 | 01-JAN-00:10 | 451858.69 | 01-JUL-15:00 |
EnergyTransfer:Building | 1076.33 | 0.00 | 01-JAN-00:10 | 157322.39 | 12-JUN-14:40 |
EnergyTransfer:Zone:LGSTORE1 | 223.39 | 0.00 | 01-JAN-00:10 | 26518.01 | 08-JUN-16:10 |
Heating:EnergyTransfer | 7.07 | 0.00 | 01-JAN-00:10 | 51273.25 | 02-JAN-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.19 | 0.00 | 01-JAN-00:10 | 4886.06 | 02-JAN-08:10 |
Cooling:EnergyTransfer | 1069.26 | 0.00 | 01-JAN-00:10 | 157322.39 | 12-JUN-14:40 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 223.20 | 0.00 | 01-JAN-00:10 | 26518.01 | 08-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE1 | 118.39 | 0.00 | 01-JAN-00:10 | 13245.44 | 08-JUN-16:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.07 | 0.00 | 01-JAN-00:10 | 1178.26 | 14-APR-07:20 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 118.32 | 0.00 | 01-JAN-00:10 | 13245.44 | 08-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE2 | 92.54 | 0.00 | 01-JAN-00:10 | 13378.53 | 12-JUN-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 1.19 | 0.00 | 01-JAN-00:10 | 4213.35 | 10-JUN-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 91.35 | 0.00 | 01-JAN-00:10 | 13378.53 | 12-JUN-14:00 |
EnergyTransfer:Zone:SMSTORE3 | 92.57 | 0.00 | 01-JAN-00:10 | 13524.54 | 12-JUN-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 1.20 | 0.00 | 01-JAN-00:10 | 4211.15 | 10-JUN-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 91.38 | 0.00 | 01-JAN-00:10 | 13524.54 | 12-JUN-14:00 |
EnergyTransfer:Zone:SMSTORE4 | 90.16 | 0.00 | 01-JAN-00:10 | 13468.49 | 12-JUN-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 1.23 | 0.00 | 01-JAN-00:10 | 5702.71 | 01-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 88.93 | 0.00 | 01-JAN-00:10 | 13468.49 | 12-JUN-14:00 |
EnergyTransfer:Zone:LGSTORE2 | 147.16 | 0.00 | 01-JAN-00:10 | 24462.52 | 12-JUN-14:20 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 0.98 | 0.00 | 01-JAN-00:10 | 12517.18 | 01-JAN-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 146.18 | 0.00 | 01-JAN-00:10 | 24462.52 | 12-JUN-14:20 |
EnergyTransfer:Zone:SMSTORE5 | 76.22 | 0.00 | 01-JAN-00:10 | 13051.18 | 12-JUN-14:20 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 0.51 | 0.00 | 01-JAN-00:10 | 6748.82 | 01-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 75.71 | 0.00 | 01-JAN-00:10 | 13051.18 | 12-JUN-14:20 |
EnergyTransfer:Zone:SMSTORE6 | 75.49 | 0.00 | 01-JAN-00:10 | 13010.58 | 12-JUN-14:20 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 0.52 | 0.00 | 01-JAN-00:10 | 6983.25 | 01-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 74.97 | 0.00 | 01-JAN-00:10 | 13010.58 | 12-JUN-14:20 |
EnergyTransfer:Zone:SMSTORE7 | 75.08 | 0.00 | 01-JAN-00:10 | 13126.36 | 12-JUN-14:20 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 0.54 | 0.00 | 01-JAN-00:10 | 7930.76 | 01-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 74.54 | 0.00 | 01-JAN-00:10 | 13126.36 | 12-JUN-14:20 |
EnergyTransfer:Zone:SMSTORE8 | 85.34 | 0.00 | 01-JAN-00:10 | 15343.69 | 12-JUN-12:30 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 0.65 | 0.00 | 01-JAN-00:10 | 10468.84 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 84.69 | 0.00 | 01-JAN-00:10 | 15343.69 | 12-JUN-12:30 |
EnergyTransfer:HVAC | 1956.93 | 0.00 | 01-JAN-00:10 | 327222.12 | 01-JUL-16:00 |
HeatingCoils:EnergyTransfer | 3.59 | 0.00 | 01-JAN-00:10 | 79119.18 | 02-JAN-08:10 |
CoolingCoils:EnergyTransfer | 1953.34 | 0.00 | 01-JAN-00:10 | 327222.12 | 01-JUL-16:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:53
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.186 | -223.199 | 0.000 | 0.000 | 12.421 | 128.996 | 26.249 | 20.320 | 0.000 | 25.289 | 19.918 | 0.000 | -5.090 | 0.000 | -5.090 | -0.002 |
SMSTORE1 | 0.000 | 0.000 | 0.075 | -118.317 | 0.000 | 0.000 | 6.199 | 73.727 | 13.125 | 10.186 | 0.000 | 14.232 | 6.188 | 0.000 | -2.603 | 0.000 | -2.812 | -0.001 |
SMSTORE2 | 0.000 | 0.000 | 1.193 | -91.344 | 0.000 | 0.000 | 3.727 | 53.039 | 10.421 | 10.008 | 0.000 | 14.024 | 4.460 | 0.000 | -2.683 | 0.000 | -2.844 | -0.001 |
SMSTORE3 | 0.000 | 0.000 | 1.196 | -91.373 | 0.000 | 0.000 | 3.728 | 53.039 | 10.421 | 10.000 | 0.000 | 14.020 | 4.470 | 0.000 | -2.674 | 0.000 | -2.827 | -0.001 |
SMSTORE4 | 0.000 | 0.000 | 1.226 | -88.931 | 0.000 | 0.000 | 3.731 | 53.039 | 10.421 | 10.026 | 0.000 | 14.025 | 1.890 | 0.000 | -2.631 | 0.000 | -2.797 | -0.001 |
LGSTORE2 | 0.000 | 0.000 | 0.977 | -146.182 | 0.000 | 0.000 | 12.828 | 63.003 | 19.173 | 20.159 | 0.000 | 24.615 | 15.247 | 0.000 | -5.027 | 0.000 | -4.793 | -0.002 |
SMSTORE5 | 0.000 | 0.000 | 0.510 | -75.704 | 0.000 | 0.000 | 6.417 | 31.501 | 9.586 | 10.123 | 0.000 | 14.041 | 8.702 | 0.000 | -2.484 | 0.000 | -2.693 | -0.001 |
SMSTORE6 | 0.000 | 0.000 | 0.521 | -74.969 | 0.000 | 0.000 | 6.419 | 31.501 | 9.586 | 10.134 | 0.000 | 14.043 | 7.913 | 0.000 | -2.470 | 0.000 | -2.678 | -0.000 |
SMSTORE7 | 0.000 | 0.000 | 0.541 | -74.536 | 0.000 | 0.000 | 6.424 | 31.501 | 9.586 | 10.135 | 0.000 | 14.042 | 7.398 | 0.000 | -2.447 | 0.000 | -2.645 | -0.001 |
SMSTORE8 | 0.000 | 0.000 | 0.649 | -84.686 | 0.000 | 0.000 | 6.428 | 31.501 | 9.586 | 10.038 | 0.000 | 14.379 | 17.350 | 0.000 | -2.388 | 0.000 | -2.857 | -0.001 |
Total Facility | 0.000 | 0.000 | 7.074 | -1069.242 | 0.000 | 0.000 | 68.322 | 550.849 | 128.154 | 121.129 | 0.000 | 162.709 | 93.536 | 0.000 | -30.498 | 0.000 | -32.035 | -0.009 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-MAY-07:01 | 0.00 | 0.00 | 0.00 | -46408.72 | 0.00 | 0.00 | 0.00 | 349.87 | 73.64 | 325.13 | 0.00 | 271.06 | 45389.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 08-APR-07:02 | 0.00 | 0.00 | 0.00 | -24091.05 | 0.00 | 0.00 | 0.00 | 199.97 | 36.82 | 27.17 | 0.00 | 9.47 | 23817.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 20-APR-06:01 | 0.00 | 0.00 | 0.00 | -24783.31 | 0.00 | 0.00 | 0.00 | 181.22 | 36.82 | 0.00 | 0.00 | 1.59 | 24594.74 | 0.00 | -31.06 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 20-APR-06:01 | 0.00 | 0.00 | 0.00 | -24841.92 | 0.00 | 0.00 | 0.00 | 181.22 | 36.82 | 0.00 | 0.00 | 1.46 | 24654.87 | 0.00 | -32.44 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 20-APR-06:01 | 0.00 | 0.00 | 0.00 | -24610.43 | 0.00 | 0.00 | 0.00 | 181.22 | 36.82 | 0.00 | 0.00 | 1.86 | 24419.87 | 0.00 | -29.35 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 20-APR-07:01 | 0.00 | 0.00 | 0.00 | -43401.86 | 0.00 | 0.00 | 0.00 | 234.19 | 73.64 | 183.09 | 0.00 | 100.40 | 42810.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 20-APR-07:01 | 0.00 | 0.00 | 0.00 | -22707.18 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 94.45 | 0.00 | 61.97 | 22396.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 20-APR-07:01 | 0.00 | 0.00 | 0.00 | -22592.28 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 95.31 | 0.00 | 63.19 | 22279.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 20-APR-07:01 | 0.00 | 0.00 | 0.00 | -22580.43 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 95.90 | 0.00 | 66.41 | 22264.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | -25024.07 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 301.04 | 0.00 | 260.91 | 24308.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-MAY-07:01 | 0.00 | 0.00 | 0.00 | -219090.55 | 0.00 | 0.00 | 157.58 | 6688.96 | 1450.75 | 2090.90 | 0.00 | 2006.66 | 206695.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 02-JAN-08:61 | 0.00 | 0.00 | 25875.15 | 0.00 | 0.00 | 0.00 | 126.19 | 349.25 | 74.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -45.73 | 0.00 | -957.86 | -25421.63 |
SMSTORE1 | 12-JUN-07:05 | 0.00 | 0.00 | 3789.74 | 0.00 | 0.00 | 0.00 | 38.07 | 199.61 | 37.31 | 331.16 | 0.00 | 464.98 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4860.87 |
SMSTORE2 | 01-JAN-08:62 | 0.00 | 0.00 | 6595.77 | 0.00 | 0.00 | 0.00 | 0.00 | 181.22 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -67.59 | 0.00 | -513.64 | -6233.07 |
SMSTORE3 | 01-JAN-08:62 | 0.00 | 0.00 | 13090.07 | 0.00 | 0.00 | 0.00 | 0.00 | 181.22 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -54.76 | 0.00 | -511.74 | -12742.10 |
SMSTORE4 | 01-JAN-08:62 | 0.00 | 0.00 | 18111.55 | 0.00 | 0.00 | 0.00 | 0.00 | 181.22 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -45.39 | 0.00 | -510.13 | -17774.57 |
LGSTORE2 | 01-JAN-09:01 | 0.00 | 0.00 | 57019.97 | 0.00 | 0.00 | 0.00 | 0.00 | 234.19 | 73.64 | 571.64 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -751.80 | -57147.64 |
SMSTORE5 | 01-JAN-09:01 | 0.00 | 0.00 | 30098.30 | 0.00 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 287.58 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -427.32 | -30112.48 |
SMSTORE6 | 01-JAN-09:01 | 0.00 | 0.00 | 30004.41 | 0.00 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 289.67 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -423.93 | -30024.06 |
SMSTORE7 | 01-JAN-09:01 | 0.00 | 0.00 | 30155.02 | 0.00 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 295.48 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -414.03 | -30190.37 |
SMSTORE8 | 01-JAN-09:01 | 0.00 | 0.00 | 33732.23 | 0.00 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 312.42 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -394.59 | -33803.97 |
Total Facility | 02-JAN-08:61 | -2736.53 | 2736.53 | 206138.99 | -2736.53 | 0.00 | 0.00 | 371.28 | 6687.98 | 1452.23 | 122.25 | 0.00 | 0.00 | 0.00 | 0.00 | -134.06 | 0.00 | -6049.89 | -205852.25 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:53
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.6948 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.6948 | 0.1527 | 1.0000 | 0.4115 | 0.1527 | ||
PSZ-AC_2:2 | 1.4086 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.4086 | 0.1460 | 1.0000 | 0.2057 | 0.1460 | ||
PSZ-AC_3:3 | 1.4028 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.4028 | 0.1467 | 1.0000 | 0.2057 | 0.1467 | ||
PSZ-AC_4:4 | 1.4054 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.4054 | 0.1464 | 1.0000 | 0.2057 | 0.1464 | ||
PSZ-AC_5:5 | 1.3967 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3967 | 0.1473 | 1.0000 | 0.2057 | 0.1473 | ||
PSZ-AC_6:6 | 2.4570 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.4570 | 0.1675 | 1.0000 | 0.4115 | 0.1675 | ||
PSZ-AC_7:7 | 1.3000 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3000 | 0.1582 | 1.0000 | 0.2057 | 0.1582 | ||
PSZ-AC_8:8 | 1.2947 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.2947 | 0.1589 | 1.0000 | 0.2057 | 0.1589 | ||
PSZ-AC_9:9 | 1.2990 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.2990 | 0.1584 | 1.0000 | 0.2057 | 0.1584 | ||
PSZ-AC_10:10 | 1.4637 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.4637 | 0.1406 | 1.0000 | 0.2057 | 0.1406 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.6948 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.6948 | 1.0000 | 1.0000 | 0.4115 | 0.1527 | ||
PSZ-AC_2:2 | 1.4086 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.4086 | 1.0000 | 1.0000 | 0.2057 | 0.1460 | ||
PSZ-AC_3:3 | 1.4028 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.4028 | 1.0000 | 1.0000 | 0.2057 | 0.1467 | ||
PSZ-AC_4:4 | 1.4054 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.4054 | 1.0000 | 1.0000 | 0.2057 | 0.1464 | ||
PSZ-AC_5:5 | 1.3967 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3967 | 1.0000 | 1.0000 | 0.2057 | 0.1473 | ||
PSZ-AC_6:6 | 2.4570 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.4570 | 1.0000 | 1.0000 | 0.4115 | 0.1675 | ||
PSZ-AC_7:7 | 1.3000 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3000 | 1.0000 | 1.0000 | 0.2057 | 0.1582 | ||
PSZ-AC_8:8 | 1.2947 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.2947 | 1.0000 | 1.0000 | 0.2057 | 0.1589 | ||
PSZ-AC_9:9 | 1.2990 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.2990 | 1.0000 | 1.0000 | 0.2057 | 0.1584 | ||
PSZ-AC_10:10 | 1.4637 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.4637 | 1.0000 | 1.0000 | 0.2057 | 0.1406 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 2.6948 | 2.6948 | 2.6948 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.4086 | 1.4086 | 1.4086 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.4028 | 1.4028 | 1.4028 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.4054 | 1.4054 | 1.4054 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.3967 | 1.3967 | 1.3967 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 2.4570 | 2.4570 | 2.4570 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 1.3000 | 1.3000 | 1.3000 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 1.2947 | 1.2947 | 1.2947 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 1.2990 | 1.2990 | 1.2990 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.4637 | 1.4637 | 1.4637 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.6948 | 2.6948 | 2.6948 | 2.6948 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.4086 | 1.4086 | 1.4086 | 1.4086 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.4028 | 1.4028 | 1.4028 | 1.4028 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.4054 | 1.4054 | 1.4054 | 1.4054 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.3967 | 1.3967 | 1.3967 | 1.3967 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.4570 | 2.4570 | 2.4570 | 2.4570 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.3000 | 1.3000 | 1.3000 | 1.3000 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.2947 | 1.2947 | 1.2947 | 1.2947 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.2990 | 1.2990 | 1.2990 | 1.2990 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.4637 | 1.4637 | 1.4637 | 1.4637 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 2.6948 | 2.6948 | 2.6948 | 0.4115 | 0.5342 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.4086 | 1.4086 | 1.4086 | 0.2057 | 0.5315 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.4028 | 1.4028 | 1.4028 | 0.2057 | 0.5253 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.4054 | 1.4054 | 1.4054 | 0.2057 | 0.5204 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.3967 | 1.3967 | 1.3967 | 0.2057 | 0.5106 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 2.4570 | 2.4570 | 2.4570 | 0.4115 | 0.5401 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 1.3000 | 1.3000 | 1.3000 | 0.2057 | 0.4977 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 1.2947 | 1.2947 | 1.2947 | 0.2057 | 0.4976 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 1.2990 | 1.2990 | 1.2990 | 0.2057 | 0.4841 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.4637 | 1.4637 | 1.4637 | 0.2057 | 0.4221 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.6948 | 2.6948 | 2.6948 | 2.6948 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.4086 | 1.4086 | 1.4086 | 1.4086 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.4028 | 1.4028 | 1.4028 | 1.4028 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.4054 | 1.4054 | 1.4054 | 1.4054 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.3967 | 1.3967 | 1.3967 | 1.3967 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.4570 | 2.4570 | 2.4570 | 2.4570 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.3000 | 1.3000 | 1.3000 | 1.3000 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.2947 | 1.2947 | 1.2947 | 1.2947 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.2990 | 1.2990 | 1.2990 | 1.2990 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.4637 | 1.4637 | 1.4637 | 1.4637 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:53
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 6.67 |
Number of hours not met | 6.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 4.49 | 98898.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 509.69 | 87401.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 550.85 | 34106.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 91.83 | 7048.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 139.36 | 16552.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 58.61 | 11810.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 1478.50 |
Natural Gas | 0.00 | 4.49 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1482.99 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 263.52 |
Space Heating | 0.00 |
Space Cooling | 243.84 |
Fans (All) | 66.67 |
Service Water Heating | 28.04 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 707.31 |
Subtotal | 707.31 |
Natural Gas [MJ/m2] | |
Space Heating | 2.15 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 2.15 |
Subtotal | 2.15 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 37.14 |
Space Heating | 0.30 |
Space Cooling | 34.37 |
Fans (All) | 9.40 |
Service Water Heating | 3.95 |
Receptacle Equipment | 8.64 |
Miscellaneous | 6.19 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
TYPE1_LIGHT_SCH | 5122. | 8760. |
TYPE2_LIGHT_SCH | 4096. | 8760. |
TYPE3_LIGHT_SCH | 3767. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUALSPSCHED | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.368209E+10 |
February | 0.000 | 0.322072E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.482229E+09 |
Annual Sum or Average | 0.448639E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.368209E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.368209E+10 |
February | 0.000 | 0.322072E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.482229E+09 |
Annual Sum or Average | 0.448639E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.368209E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Meter
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.368209E+10 |
February | 0.000 | 0.322072E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.482229E+09 |
Annual Sum or Average | 0.448639E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.368209E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.368209E+10 |
February | 0.000 | 0.322072E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.482229E+09 |
Annual Sum or Average | 0.448639E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.368209E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Meter
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.368209E+10 |
February | 0.000 | 0.322072E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.482229E+09 |
Annual Sum or Average | 0.448639E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.368209E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.368209E+10 |
February | 0.000 | 0.322072E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.482229E+09 |
Annual Sum or Average | 0.448639E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.368209E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.368209E+10 |
February | 0.000 | 0.322072E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.482229E+09 |
Annual Sum or Average | 0.448639E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.368209E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Meter
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.368209E+10 |
February | 0.000 | 0.322072E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.482229E+09 |
Annual Sum or Average | 0.448639E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.368209E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Meter
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.368209E+10 |
February | 0.000 | 0.322072E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.482229E+09 |
Annual Sum or Average | 0.448639E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.368209E+10 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.711995E+10 | 8292.26 | 12-JAN-15:00 | 23.60 | 14.18 | 0.728403E+09 | 899.04 | 08-JAN-17:10 | 20.12 | 13.89 |
February | 0.915090E+10 | 12115.68 | 22-FEB-15:00 | 27.10 | 16.17 | 0.673241E+09 | 899.05 | 20-FEB-18:00 | 20.60 | 13.90 |
March | 0.151574E+11 | 40057.61 | 30-MAR-07:02 | 21.65 | 17.02 | 0.744585E+09 | 899.05 | 05-MAR-17:00 | 26.20 | 17.75 |
April | 0.212396E+11 | 46352.73 | 08-APR-07:02 | 24.45 | 14.69 | 0.726403E+09 | 899.14 | 28-APR-12:50 | 37.40 | 20.46 |
May | 0.263299E+11 | 46408.13 | 06-MAY-07:01 | 30.00 | 17.73 | 0.747564E+09 | 899.11 | 07-MAY-17:49 | 39.42 | 22.06 |
June | 0.264052E+11 | 43070.47 | 07-JUN-07:01 | 34.92 | 19.60 | 0.722180E+09 | 898.99 | 04-JUN-16:19 | 42.13 | 22.31 |
July | 0.259229E+11 | 37180.38 | 07-JUL-07:01 | 33.33 | 24.38 | 0.753704E+09 | 898.97 | 02-JUL-16:19 | 40.37 | 26.41 |
August | 0.247536E+11 | 34658.54 | 03-AUG-07:01 | 28.70 | 23.40 | 0.743170E+09 | 898.94 | 06-AUG-16:30 | 36.15 | 26.33 |
September | 0.225970E+11 | 37695.40 | 26-SEP-07:01 | 25.87 | 19.86 | 0.728292E+09 | 898.94 | 03-SEP-17:00 | 26.80 | 24.76 |
October | 0.209310E+11 | 43101.40 | 23-OCT-07:02 | 20.23 | 14.64 | 0.751750E+09 | 899.11 | 01-OCT-16:10 | 35.32 | 20.14 |
November | 0.147056E+11 | 28089.97 | 09-NOV-08:62 | 19.90 | 16.69 | 0.726503E+09 | 899.07 | 11-NOV-17:10 | 25.85 | 18.08 |
December | 0.888750E+10 | 9956.38 | 02-DEC-14:00 | 24.10 | 13.12 | 0.744480E+09 | 899.05 | 03-DEC-17:10 | 19.32 | 13.77 |
Annual Sum or Average | 0.223200E+12 | 0.879027E+10 | ||||||||
Minimum of Months | 0.711995E+10 | 8292.26 | 19.90 | 13.12 | 0.673241E+09 | 898.94 | 19.32 | 13.77 | ||
Maximum of Months | 0.264052E+11 | 46408.13 | 34.92 | 24.38 | 0.753704E+09 | 899.14 | 42.13 | 26.41 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.400990E+10 | 4739.46 | 12-JAN-15:00 | 23.60 | 14.18 | 0.370810E+09 | 449.52 | 08-JAN-17:19 | 19.73 | 13.78 |
February | 0.532470E+10 | 8309.59 | 25-FEB-08:63 | 18.73 | 15.94 | 0.338125E+09 | 449.53 | 05-FEB-18:40 | 19.63 | 12.56 |
March | 0.850307E+10 | 21725.23 | 30-MAR-07:02 | 21.65 | 17.02 | 0.372405E+09 | 449.52 | 05-MAR-17:00 | 26.20 | 17.75 |
April | 0.113116E+11 | 24090.58 | 08-APR-07:02 | 24.45 | 14.69 | 0.363210E+09 | 449.57 | 28-APR-12:39 | 37.20 | 20.33 |
May | 0.137314E+11 | 24012.83 | 06-MAY-07:01 | 30.00 | 17.73 | 0.373779E+09 | 449.56 | 27-MAY-12:20 | 40.10 | 20.27 |
June | 0.136087E+11 | 22528.27 | 07-JUN-07:01 | 34.92 | 19.60 | 0.361082E+09 | 449.49 | 04-JUN-16:19 | 42.13 | 22.31 |
July | 0.133506E+11 | 20206.64 | 07-JUL-07:01 | 33.33 | 24.38 | 0.376839E+09 | 449.47 | 04-JUL-16:30 | 39.80 | 24.46 |
August | 0.127063E+11 | 19381.22 | 03-AUG-07:01 | 28.70 | 23.40 | 0.371572E+09 | 449.47 | 06-AUG-16:30 | 36.15 | 26.33 |
September | 0.116761E+11 | 20986.00 | 26-SEP-07:01 | 25.87 | 19.86 | 0.364137E+09 | 449.47 | 24-SEP-16:30 | 34.45 | 25.39 |
October | 0.110242E+11 | 23074.73 | 25-OCT-07:02 | 20.13 | 15.93 | 0.375879E+09 | 449.54 | 01-OCT-16:10 | 35.32 | 20.14 |
November | 0.804937E+10 | 16325.94 | 09-NOV-08:62 | 19.90 | 16.69 | 0.363344E+09 | 449.52 | 26-NOV-17:10 | 22.25 | 14.81 |
December | 0.502202E+10 | 5650.22 | 02-DEC-14:00 | 24.10 | 13.12 | 0.375368E+09 | 449.52 | 03-DEC-17:10 | 19.32 | 13.77 |
Annual Sum or Average | 0.118318E+12 | 0.440655E+10 | ||||||||
Minimum of Months | 0.400990E+10 | 4739.46 | 18.73 | 13.12 | 0.338125E+09 | 449.47 | 19.32 | 12.56 | ||
Maximum of Months | 0.137314E+11 | 24090.58 | 34.92 | 24.38 | 0.376839E+09 | 449.57 | 42.13 | 26.33 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.274722E+10 | 4341.46 | 12-JAN-15:00 | 23.60 | 14.18 | 0.217672E+09 | 449.51 | 07-JAN-13:39 | 20.73 | 13.24 |
February | 0.376635E+10 | 7863.99 | 25-FEB-07:03 | 18.20 | 15.79 | 0.201804E+09 | 449.49 | 04-FEB-13:09 | 22.38 | 12.53 |
March | 0.639093E+10 | 21576.12 | 29-MAR-06:02 | 21.15 | 17.30 | 0.230112E+09 | 449.50 | 04-MAR-13:09 | 26.57 | 15.78 |
April | 0.878985E+10 | 24782.37 | 20-APR-06:01 | 26.07 | 17.11 | 0.219610E+09 | 449.54 | 29-APR-12:09 | 37.25 | 19.97 |
May | 0.110459E+11 | 24327.05 | 06-MAY-06:01 | 29.38 | 17.54 | 0.227966E+09 | 449.53 | 06-MAY-12:00 | 41.10 | 20.00 |
June | 0.109820E+11 | 22191.72 | 07-JUN-06:01 | 33.87 | 19.42 | 0.223093E+09 | 449.42 | 24-JUN-12:30 | 24.85 | 24.21 |
July | 0.104307E+11 | 18179.60 | 01-JUL-06:01 | 29.62 | 23.94 | 0.224599E+09 | 449.36 | 01-JUL-12:50 | 37.90 | 28.36 |
August | 0.100953E+11 | 16026.10 | 03-AUG-06:01 | 28.43 | 23.35 | 0.230640E+09 | 449.33 | 05-AUG-12:09 | 35.03 | 26.47 |
September | 0.905476E+10 | 18761.10 | 27-SEP-06:01 | 23.70 | 20.39 | 0.219519E+09 | 449.38 | 09-SEP-12:00 | 27.10 | 25.75 |
October | 0.848330E+10 | 23818.87 | 23-OCT-06:02 | 19.08 | 14.20 | 0.224523E+09 | 449.49 | 21-OCT-12:09 | 29.33 | 18.35 |
November | 0.605070E+10 | 15786.25 | 09-NOV-07:03 | 18.42 | 16.26 | 0.216351E+09 | 449.50 | 18-NOV-13:09 | 26.42 | 17.17 |
December | 0.350933E+10 | 5385.46 | 02-DEC-14:00 | 24.10 | 13.12 | 0.220565E+09 | 449.51 | 09-DEC-13:39 | 19.23 | 12.72 |
Annual Sum or Average | 0.913464E+11 | 0.265645E+10 | ||||||||
Minimum of Months | 0.274722E+10 | 4341.46 | 18.20 | 13.12 | 0.201804E+09 | 449.33 | 19.23 | 12.53 | ||
Maximum of Months | 0.110459E+11 | 24782.37 | 33.87 | 23.94 | 0.230640E+09 | 449.54 | 41.10 | 28.36 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.257201E+10 | 4211.84 | 12-JAN-15:00 | 23.60 | 14.18 | 0.216724E+09 | 449.51 | 07-JAN-13:39 | 20.73 | 13.24 |
February | 0.366527E+10 | 7444.04 | 25-FEB-07:03 | 18.20 | 15.79 | 0.201647E+09 | 449.49 | 04-FEB-13:09 | 22.38 | 12.53 |
March | 0.636178E+10 | 21625.36 | 29-MAR-06:02 | 21.15 | 17.30 | 0.230100E+09 | 449.50 | 04-MAR-13:09 | 26.57 | 15.78 |
April | 0.883359E+10 | 24840.98 | 20-APR-06:01 | 26.07 | 17.11 | 0.219611E+09 | 449.54 | 29-APR-12:09 | 37.25 | 19.97 |
May | 0.111463E+11 | 24412.40 | 06-MAY-06:01 | 29.38 | 17.54 | 0.227970E+09 | 449.53 | 06-MAY-12:00 | 41.10 | 20.00 |
June | 0.110771E+11 | 22364.19 | 12-JUN-06:01 | 34.87 | 19.37 | 0.223096E+09 | 449.42 | 24-JUN-12:30 | 24.85 | 24.21 |
July | 0.105336E+11 | 18303.65 | 01-JUL-06:01 | 29.62 | 23.94 | 0.224603E+09 | 449.36 | 01-JUL-12:50 | 37.90 | 28.36 |
August | 0.101688E+11 | 16133.54 | 03-AUG-06:01 | 28.43 | 23.35 | 0.230642E+09 | 449.33 | 05-AUG-12:09 | 35.03 | 26.47 |
September | 0.911303E+10 | 18855.77 | 27-SEP-06:01 | 23.70 | 20.39 | 0.219521E+09 | 449.38 | 09-SEP-12:00 | 27.10 | 25.75 |
October | 0.852119E+10 | 23920.45 | 23-OCT-06:02 | 19.08 | 14.20 | 0.224523E+09 | 449.49 | 21-OCT-12:09 | 29.33 | 18.35 |
November | 0.600309E+10 | 15617.60 | 09-NOV-07:03 | 18.42 | 16.26 | 0.216331E+09 | 449.51 | 18-NOV-13:09 | 26.42 | 17.17 |
December | 0.337962E+10 | 5305.92 | 02-DEC-14:00 | 24.10 | 13.12 | 0.220248E+09 | 449.51 | 09-DEC-13:50 | 19.47 | 12.75 |
Annual Sum or Average | 0.913754E+11 | 0.265502E+10 | ||||||||
Minimum of Months | 0.257201E+10 | 4211.84 | 18.20 | 13.12 | 0.201647E+09 | 449.33 | 19.47 | 12.53 | ||
Maximum of Months | 0.111463E+11 | 24840.98 | 34.87 | 23.94 | 0.230642E+09 | 449.54 | 41.10 | 28.36 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.229714E+10 | 3951.66 | 12-JAN-15:00 | 23.60 | 14.18 | 0.215162E+09 | 449.51 | 07-JAN-13:00 | 20.90 | 13.27 |
February | 0.343151E+10 | 6043.38 | 22-FEB-14:00 | 27.00 | 16.30 | 0.201280E+09 | 449.49 | 11-FEB-13:09 | 20.65 | 13.77 |
March | 0.612212E+10 | 21372.56 | 29-MAR-06:02 | 21.15 | 17.30 | 0.230050E+09 | 449.51 | 04-MAR-13:09 | 26.57 | 15.78 |
April | 0.863838E+10 | 24609.53 | 20-APR-06:01 | 26.07 | 17.11 | 0.219593E+09 | 449.54 | 29-APR-12:09 | 37.25 | 19.97 |
May | 0.109737E+11 | 24198.30 | 06-MAY-06:01 | 29.38 | 17.54 | 0.227953E+09 | 449.53 | 06-MAY-12:00 | 41.10 | 20.00 |
June | 0.109101E+11 | 22189.86 | 12-JUN-06:01 | 34.87 | 19.37 | 0.223080E+09 | 449.42 | 24-JUN-12:50 | 24.88 | 24.25 |
July | 0.103806E+11 | 18013.45 | 01-JUL-06:01 | 29.62 | 23.94 | 0.224587E+09 | 449.36 | 01-JUL-12:50 | 37.90 | 28.36 |
August | 0.999652E+10 | 15858.24 | 03-AUG-06:01 | 28.43 | 23.35 | 0.230626E+09 | 449.33 | 05-AUG-12:09 | 35.03 | 26.47 |
September | 0.894133E+10 | 18609.73 | 27-SEP-06:01 | 23.70 | 20.39 | 0.219504E+09 | 449.39 | 09-SEP-12:09 | 27.27 | 25.68 |
October | 0.832964E+10 | 23696.37 | 23-OCT-06:02 | 19.08 | 14.20 | 0.224505E+09 | 449.49 | 21-OCT-12:09 | 29.33 | 18.35 |
November | 0.578240E+10 | 14047.12 | 09-NOV-07:03 | 18.42 | 16.26 | 0.216276E+09 | 449.51 | 18-NOV-13:09 | 26.42 | 17.17 |
December | 0.312944E+10 | 5111.44 | 02-DEC-14:00 | 24.10 | 13.12 | 0.219636E+09 | 449.51 | 09-DEC-13:00 | 19.70 | 12.77 |
Annual Sum or Average | 0.889329E+11 | 0.265225E+10 | ||||||||
Minimum of Months | 0.229714E+10 | 3951.66 | 18.42 | 13.12 | 0.201280E+09 | 449.33 | 19.70 | 12.77 | ||
Maximum of Months | 0.109737E+11 | 24609.53 | 34.87 | 23.94 | 0.230626E+09 | 449.54 | 41.10 | 28.36 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.317950E+10 | 6917.69 | 03-JAN-08:03 | 6.40 | 5.70 | 0.722543E+09 | 1198.69 | 07-JAN-15:20 | 20.57 | 13.36 |
February | 0.502911E+10 | 10120.15 | 22-FEB-15:10 | 27.00 | 16.13 | 0.687127E+09 | 1198.65 | 11-FEB-15:00 | 21.20 | 14.71 |
March | 0.979006E+10 | 37519.11 | 30-MAR-07:02 | 21.65 | 17.02 | 0.788708E+09 | 1198.67 | 04-MAR-15:00 | 26.70 | 15.70 |
April | 0.143592E+11 | 43401.29 | 20-APR-07:01 | 26.55 | 16.61 | 0.752689E+09 | 1198.78 | 15-APR-14:09 | 40.22 | 20.59 |
May | 0.185628E+11 | 42691.54 | 29-MAY-08:61 | 32.12 | 19.76 | 0.778485E+09 | 1198.74 | 06-MAY-14:00 | 41.70 | 19.93 |
June | 0.185201E+11 | 39452.28 | 07-JUN-07:01 | 34.92 | 19.60 | 0.763236E+09 | 1198.57 | 10-JUN-14:00 | 42.70 | 25.56 |
July | 0.175094E+11 | 33867.66 | 07-JUL-07:01 | 33.33 | 24.38 | 0.767902E+09 | 1198.22 | 22-JUL-14:09 | 29.58 | 26.97 |
August | 0.168552E+11 | 30910.77 | 08-AUG-07:01 | 30.50 | 24.41 | 0.789654E+09 | 1198.23 | 19-AUG-14:00 | 27.10 | 25.89 |
September | 0.149146E+11 | 34724.04 | 27-SEP-07:02 | 24.98 | 20.38 | 0.752433E+09 | 1198.34 | 09-SEP-14:09 | 26.78 | 25.72 |
October | 0.138676E+11 | 41273.80 | 23-OCT-07:02 | 20.23 | 14.64 | 0.766030E+09 | 1198.62 | 28-OCT-14:00 | 29.30 | 18.42 |
November | 0.915710E+10 | 22770.38 | 09-NOV-08:62 | 19.90 | 16.69 | 0.736509E+09 | 1198.70 | 18-NOV-15:20 | 26.20 | 17.22 |
December | 0.443975E+10 | 8277.22 | 02-DEC-14:20 | 24.03 | 13.14 | 0.748829E+09 | 1198.69 | 09-DEC-15:39 | 19.17 | 13.13 |
Annual Sum or Average | 0.146184E+12 | 0.905415E+10 | ||||||||
Minimum of Months | 0.317950E+10 | 6917.69 | 6.40 | 5.70 | 0.687127E+09 | 1198.22 | 19.17 | 13.13 | ||
Maximum of Months | 0.185628E+11 | 43401.29 | 34.92 | 24.41 | 0.789654E+09 | 1198.78 | 42.70 | 26.97 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146774E+10 | 3458.49 | 03-JAN-08:03 | 6.40 | 5.70 | 0.359444E+09 | 599.34 | 07-JAN-15:20 | 20.57 | 13.36 |
February | 0.248247E+10 | 5260.42 | 22-FEB-15:10 | 27.00 | 16.13 | 0.343208E+09 | 599.32 | 11-FEB-15:00 | 21.20 | 14.71 |
March | 0.503172E+10 | 18435.75 | 30-MAR-07:02 | 21.65 | 17.02 | 0.394341E+09 | 599.33 | 04-MAR-15:00 | 26.70 | 15.70 |
April | 0.750668E+10 | 22706.81 | 20-APR-07:01 | 26.55 | 16.61 | 0.376328E+09 | 599.38 | 15-APR-14:30 | 40.25 | 20.61 |
May | 0.975614E+10 | 22332.37 | 29-MAY-08:61 | 32.12 | 19.76 | 0.389227E+09 | 599.37 | 06-MAY-14:00 | 41.70 | 19.93 |
June | 0.971364E+10 | 20617.68 | 07-JUN-07:01 | 34.92 | 19.60 | 0.381600E+09 | 599.26 | 10-JUN-14:00 | 42.70 | 25.56 |
July | 0.915885E+10 | 17713.43 | 07-JUL-07:01 | 33.33 | 24.38 | 0.383927E+09 | 599.10 | 22-JUL-14:09 | 29.58 | 26.97 |
August | 0.878891E+10 | 16163.28 | 08-AUG-07:01 | 30.50 | 24.41 | 0.394808E+09 | 599.10 | 19-AUG-14:00 | 27.10 | 25.89 |
September | 0.777325E+10 | 18114.23 | 27-SEP-07:02 | 24.98 | 20.38 | 0.376194E+09 | 599.17 | 09-SEP-14:09 | 26.78 | 25.72 |
October | 0.720734E+10 | 21534.99 | 23-OCT-07:02 | 20.23 | 14.64 | 0.383004E+09 | 599.31 | 28-OCT-14:00 | 29.30 | 18.42 |
November | 0.468607E+10 | 10405.51 | 09-NOV-08:62 | 19.90 | 16.69 | 0.368249E+09 | 599.35 | 18-NOV-15:20 | 26.20 | 17.22 |
December | 0.213254E+10 | 4237.26 | 02-DEC-14:30 | 24.00 | 13.14 | 0.373781E+09 | 599.34 | 09-DEC-15:39 | 19.17 | 13.13 |
Annual Sum or Average | 0.757053E+11 | 0.452411E+10 | ||||||||
Minimum of Months | 0.146774E+10 | 3458.49 | 6.40 | 5.70 | 0.343208E+09 | 599.10 | 19.17 | 13.13 | ||
Maximum of Months | 0.975614E+10 | 22706.81 | 34.92 | 24.41 | 0.394808E+09 | 599.38 | 42.70 | 26.97 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140857E+10 | 3439.12 | 03-JAN-08:03 | 6.40 | 5.70 | 0.358190E+09 | 599.34 | 07-JAN-15:20 | 20.57 | 13.36 |
February | 0.241197E+10 | 5190.00 | 22-FEB-15:10 | 27.00 | 16.13 | 0.342871E+09 | 599.32 | 11-FEB-15:00 | 21.20 | 14.71 |
March | 0.495495E+10 | 17903.19 | 30-MAR-07:02 | 21.65 | 17.02 | 0.394315E+09 | 599.33 | 04-MAR-15:00 | 26.70 | 15.70 |
April | 0.744246E+10 | 22591.93 | 20-APR-07:01 | 26.55 | 16.61 | 0.376325E+09 | 599.39 | 15-APR-14:39 | 40.27 | 20.62 |
May | 0.969678E+10 | 22246.75 | 29-MAY-08:61 | 32.12 | 19.76 | 0.389225E+09 | 599.37 | 06-MAY-14:00 | 41.70 | 19.93 |
June | 0.965451E+10 | 20513.72 | 07-JUN-07:01 | 34.92 | 19.60 | 0.381598E+09 | 599.26 | 10-JUN-14:00 | 42.70 | 25.56 |
July | 0.910586E+10 | 17615.22 | 07-JUL-07:01 | 33.33 | 24.38 | 0.383924E+09 | 599.10 | 22-JUL-14:09 | 29.58 | 26.97 |
August | 0.873485E+10 | 16074.19 | 08-AUG-07:01 | 30.50 | 24.41 | 0.394805E+09 | 599.10 | 19-AUG-14:00 | 27.10 | 25.89 |
September | 0.772169E+10 | 18014.13 | 27-SEP-07:02 | 24.98 | 20.38 | 0.376190E+09 | 599.17 | 09-SEP-14:09 | 26.78 | 25.72 |
October | 0.714911E+10 | 21440.87 | 23-OCT-07:02 | 20.23 | 14.64 | 0.383000E+09 | 599.31 | 28-OCT-14:00 | 29.30 | 18.42 |
November | 0.462125E+10 | 9981.32 | 09-NOV-08:62 | 19.90 | 16.69 | 0.368229E+09 | 599.35 | 18-NOV-15:20 | 26.20 | 17.22 |
December | 0.206869E+10 | 4171.16 | 02-DEC-14:30 | 24.00 | 13.14 | 0.373219E+09 | 599.34 | 09-DEC-15:30 | 19.35 | 13.12 |
Annual Sum or Average | 0.749707E+11 | 0.452189E+10 | ||||||||
Minimum of Months | 0.140857E+10 | 3439.12 | 6.40 | 5.70 | 0.342871E+09 | 599.10 | 19.35 | 13.12 | ||
Maximum of Months | 0.969678E+10 | 22591.93 | 34.92 | 24.41 | 0.394805E+09 | 599.39 | 42.70 | 26.97 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128484E+10 | 3336.84 | 04-JAN-08:04 | 6.42 | 5.61 | 0.355723E+09 | 599.34 | 07-JAN-15:09 | 20.73 | 13.39 |
February | 0.225551E+10 | 5069.53 | 22-FEB-15:10 | 27.00 | 16.13 | 0.342000E+09 | 599.33 | 11-FEB-15:00 | 21.20 | 14.71 |
March | 0.481011E+10 | 16464.55 | 11-MAR-08:62 | 24.43 | 17.40 | 0.394229E+09 | 599.33 | 04-MAR-15:00 | 26.70 | 15.70 |
April | 0.740549E+10 | 22580.11 | 20-APR-07:01 | 26.55 | 16.61 | 0.376322E+09 | 599.38 | 15-APR-14:30 | 40.25 | 20.61 |
May | 0.973083E+10 | 22311.95 | 29-MAY-08:61 | 32.12 | 19.76 | 0.389226E+09 | 599.37 | 06-MAY-14:00 | 41.70 | 19.93 |
June | 0.970752E+10 | 20608.65 | 07-JUN-07:01 | 34.92 | 19.60 | 0.381599E+09 | 599.28 | 10-JUN-14:00 | 42.70 | 25.56 |
July | 0.917884E+10 | 17727.45 | 07-JUL-07:01 | 33.33 | 24.38 | 0.383927E+09 | 599.10 | 22-JUL-14:09 | 29.58 | 26.97 |
August | 0.880569E+10 | 16194.03 | 08-AUG-07:01 | 30.50 | 24.41 | 0.394807E+09 | 599.10 | 19-AUG-14:00 | 27.10 | 25.89 |
September | 0.776633E+10 | 18075.62 | 27-SEP-07:02 | 24.98 | 20.38 | 0.376192E+09 | 599.17 | 09-SEP-14:09 | 26.78 | 25.72 |
October | 0.714303E+10 | 21469.54 | 23-OCT-07:02 | 20.23 | 14.64 | 0.382999E+09 | 599.31 | 28-OCT-14:00 | 29.30 | 18.42 |
November | 0.451947E+10 | 8761.96 | 09-NOV-08:62 | 19.90 | 16.69 | 0.368172E+09 | 599.35 | 18-NOV-15:09 | 26.30 | 17.20 |
December | 0.192995E+10 | 4038.84 | 02-DEC-14:30 | 24.00 | 13.14 | 0.371884E+09 | 599.34 | 09-DEC-15:30 | 19.35 | 13.12 |
Annual Sum or Average | 0.745376E+11 | 0.451708E+10 | ||||||||
Minimum of Months | 0.128484E+10 | 3336.84 | 6.42 | 5.61 | 0.342000E+09 | 599.10 | 19.35 | 13.12 | ||
Maximum of Months | 0.973083E+10 | 22580.11 | 34.92 | 24.41 | 0.394807E+09 | 599.38 | 42.70 | 26.97 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116141E+10 | 3685.32 | 04-JAN-08:04 | 6.42 | 5.61 | 0.354462E+09 | 599.34 | 07-JAN-15:09 | 20.73 | 13.39 |
February | 0.220735E+10 | 5507.26 | 22-FEB-14:00 | 27.00 | 16.30 | 0.340631E+09 | 599.33 | 11-FEB-15:00 | 21.20 | 14.71 |
March | 0.508171E+10 | 12711.40 | 11-MAR-08:62 | 24.43 | 17.40 | 0.394002E+09 | 599.34 | 04-MAR-15:00 | 26.70 | 15.70 |
April | 0.840538E+10 | 24253.16 | 20-APR-07:01 | 26.55 | 16.61 | 0.376367E+09 | 599.39 | 15-APR-14:30 | 40.25 | 20.61 |
May | 0.112817E+11 | 25023.54 | 29-MAY-08:61 | 32.12 | 19.76 | 0.389273E+09 | 599.37 | 06-MAY-14:00 | 41.70 | 19.93 |
June | 0.112890E+11 | 23543.11 | 12-JUN-07:01 | 35.90 | 20.10 | 0.381641E+09 | 599.24 | 03-JUN-14:00 | 40.80 | 22.30 |
July | 0.107558E+11 | 20108.23 | 07-JUL-07:01 | 33.33 | 24.38 | 0.384001E+09 | 599.10 | 22-JUL-14:09 | 29.58 | 26.97 |
August | 0.103967E+11 | 17758.31 | 09-AUG-07:01 | 30.30 | 25.36 | 0.394865E+09 | 599.09 | 19-AUG-14:00 | 27.10 | 25.89 |
September | 0.910769E+10 | 20323.95 | 27-SEP-07:02 | 24.98 | 20.38 | 0.376263E+09 | 599.22 | 09-SEP-14:09 | 26.78 | 25.72 |
October | 0.822779E+10 | 23269.21 | 23-OCT-07:02 | 20.23 | 14.64 | 0.383064E+09 | 599.31 | 28-OCT-14:00 | 29.30 | 18.42 |
November | 0.491713E+10 | 7894.56 | 04-NOV-14:10 | 30.28 | 17.21 | 0.368083E+09 | 599.36 | 18-NOV-15:20 | 26.20 | 17.22 |
December | 0.185639E+10 | 4288.72 | 01-DEC-14:00 | 23.50 | 13.04 | 0.370704E+09 | 599.34 | 09-DEC-15:20 | 19.53 | 13.10 |
Annual Sum or Average | 0.846880E+11 | 0.451336E+10 | ||||||||
Minimum of Months | 0.116141E+10 | 3685.32 | 6.42 | 5.61 | 0.340631E+09 | 599.09 | 19.53 | 13.10 | ||
Maximum of Months | 0.112890E+11 | 25023.54 | 35.90 | 25.36 | 0.394865E+09 | 599.39 | 41.70 | 26.97 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21628304.42 | 25875.48 | 02-JAN-08:61 | 7.38 |
February | 183093.59 | 915.47 | 02-FEB-08:13 | 8.43 |
March | 4018373.96 | 2523.94 | 11-MAR-08:04 | 24.43 |
April | 40559942.72 | 5066.98 | 27-APR-07:04 | 30.20 |
May | 28737310.66 | 6695.66 | 04-MAY-07:05 | 34.62 |
June | 21421663.34 | 6990.80 | 07-JUN-07:05 | 34.92 |
July | 12410208.95 | 6055.23 | 02-JUL-07:07 | 33.57 |
August | 17569296.85 | 4746.34 | 08-AUG-07:06 | 30.50 |
September | 23763179.68 | 3933.00 | 22-SEP-07:05 | 28.37 |
October | 15612202.71 | 3188.24 | 04-OCT-07:04 | 26.28 |
November | 41780.04 | 278.53 | 09-NOV-08:05 | 19.90 |
December | 474040.16 | 1719.16 | 23-DEC-08:10 | 7.55 |
Annual Sum or Average | 0.186419E+09 | |||
Minimum of Months | 41780.04 | 278.53 | 7.38 | |
Maximum of Months | 40559942.72 | 25875.48 | 34.92 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1127996.47 | 1906.02 | 02-JAN-08:05 | 7.38 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.73 |
March | 2431787.27 | 1389.01 | 11-MAR-08:04 | 24.43 |
April | 17527005.30 | 2673.08 | 27-APR-07:04 | 30.20 |
May | 10451810.15 | 3133.37 | 01-MAY-07:04 | 33.43 |
June | 9142526.49 | 3790.03 | 12-JUN-07:05 | 35.90 |
July | 6663687.89 | 3205.02 | 02-JUL-07:06 | 33.57 |
August | 8855821.13 | 2454.20 | 07-AUG-07:05 | 30.33 |
September | 9849704.51 | 1940.29 | 22-SEP-07:05 | 28.37 |
October | 8674128.34 | 1782.72 | 04-OCT-07:04 | 26.28 |
November | 59618.32 | 305.99 | 09-NOV-08:05 | 19.90 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 74784085.86 | |||
Minimum of Months | 0.00 | 0.00 | 7.38 | |
Maximum of Months | 17527005.30 | 3790.03 | 35.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8500331.78 | 6596.14 | 01-JAN-08:62 | 8.17 |
February | 332028.54 | 302.11 | 20-FEB-17:03 | 24.33 |
March | 33819483.26 | 1942.05 | 12-MAR-16:02 | 31.18 |
April | 0.177937E+09 | 3825.43 | 16-APR-16:01 | 39.13 |
May | 0.220813E+09 | 4550.12 | 07-MAY-16:01 | 42.17 |
June | 0.236867E+09 | 4874.11 | 11-JUN-16:01 | 43.35 |
July | 0.175328E+09 | 4179.70 | 02-JUL-16:01 | 40.38 |
August | 0.142007E+09 | 3186.22 | 06-AUG-16:01 | 36.25 |
September | 0.125288E+09 | 2772.08 | 24-SEP-16:01 | 34.68 |
October | 65937766.90 | 2880.83 | 01-OCT-16:01 | 35.32 |
November | 5850661.19 | 1110.02 | 04-NOV-17:03 | 27.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.119268E+10 | |||
Minimum of Months | 0.00 | 0.00 | 8.17 | |
Maximum of Months | 0.236867E+09 | 6596.14 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19677073.94 | 13090.81 | 01-JAN-08:62 | 8.17 |
February | 359258.78 | 309.85 | 20-FEB-17:03 | 24.33 |
March | 33906582.28 | 1943.27 | 12-MAR-16:02 | 31.18 |
April | 0.177243E+09 | 3823.95 | 16-APR-16:01 | 39.13 |
May | 0.219246E+09 | 4547.89 | 07-MAY-16:01 | 42.17 |
June | 0.234362E+09 | 4871.46 | 11-JUN-16:01 | 43.35 |
July | 0.173974E+09 | 4177.41 | 02-JUL-16:01 | 40.38 |
August | 0.141142E+09 | 3184.19 | 06-AUG-16:01 | 36.25 |
September | 0.124634E+09 | 2770.37 | 24-SEP-16:01 | 34.68 |
October | 65603038.86 | 2879.41 | 01-OCT-16:01 | 35.32 |
November | 5886951.91 | 1112.40 | 04-NOV-17:03 | 27.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.119603E+10 | |||
Minimum of Months | 0.00 | 0.00 | 8.17 | |
Maximum of Months | 0.234362E+09 | 13090.81 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 29968023.16 | 18112.56 | 01-JAN-08:62 | 8.17 |
February | 413069.96 | 324.75 | 20-FEB-17:03 | 24.33 |
March | 34981148.40 | 1949.05 | 12-MAR-16:02 | 31.18 |
April | 0.179485E+09 | 3827.90 | 16-APR-16:01 | 39.13 |
May | 0.221950E+09 | 4550.97 | 07-MAY-16:01 | 42.17 |
June | 0.239223E+09 | 4873.79 | 11-JUN-16:01 | 43.35 |
July | 0.176304E+09 | 4180.19 | 02-JUL-16:01 | 40.38 |
August | 0.143990E+09 | 3187.19 | 06-AUG-16:01 | 36.25 |
September | 0.126537E+09 | 2774.41 | 24-SEP-16:01 | 34.68 |
October | 67078642.12 | 2883.73 | 01-OCT-16:01 | 35.32 |
November | 6110226.58 | 1121.63 | 04-NOV-17:03 | 27.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.122604E+10 | |||
Minimum of Months | 0.00 | 0.00 | 8.17 | |
Maximum of Months | 0.239223E+09 | 18112.56 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 91744878.54 | 57021.03 | 01-JAN-09:01 | 9.20 |
February | 1173696.25 | 1580.00 | 02-FEB-08:10 | 8.07 |
March | 33536300.47 | 3921.82 | 12-MAR-16:02 | 31.18 |
April | 0.150463E+09 | 7692.97 | 16-APR-16:01 | 39.13 |
May | 0.135511E+09 | 9135.70 | 07-MAY-16:01 | 42.17 |
June | 0.121005E+09 | 9771.78 | 11-JUN-16:01 | 43.35 |
July | 0.132482E+09 | 8384.83 | 02-JUL-16:01 | 40.38 |
August | 94619159.56 | 6391.85 | 06-AUG-16:01 | 36.25 |
September | 0.110213E+09 | 5578.47 | 24-SEP-16:01 | 34.68 |
October | 93337885.48 | 5804.70 | 01-OCT-16:01 | 35.32 |
November | 11887058.29 | 2279.40 | 04-NOV-17:03 | 27.72 |
December | 595777.37 | 2978.89 | 23-DEC-08:07 | 7.55 |
Annual Sum or Average | 0.976569E+09 | |||
Minimum of Months | 595777.37 | 1580.00 | 7.55 | |
Maximum of Months | 0.150463E+09 | 57021.03 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58532908.15 | 30098.84 | 01-JAN-09:01 | 9.20 |
February | 1037148.15 | 1258.67 | 02-FEB-08:10 | 8.07 |
March | 18211331.99 | 1974.25 | 12-MAR-16:02 | 31.18 |
April | 74283741.74 | 3849.85 | 16-APR-16:01 | 39.13 |
May | 68836149.10 | 4569.83 | 07-MAY-16:01 | 42.17 |
June | 62700137.07 | 4888.86 | 11-JUN-16:01 | 43.35 |
July | 67278763.12 | 4196.94 | 02-JUL-16:01 | 40.38 |
August | 47415759.59 | 3204.49 | 06-AUG-16:01 | 36.25 |
September | 55297810.08 | 2796.89 | 24-SEP-16:01 | 34.68 |
October | 49296835.40 | 2907.91 | 01-OCT-16:01 | 35.32 |
November | 6803612.84 | 1162.80 | 04-NOV-17:03 | 27.72 |
December | 386862.28 | 1123.73 | 23-DEC-08:07 | 7.55 |
Annual Sum or Average | 0.510081E+09 | |||
Minimum of Months | 386862.28 | 1123.73 | 7.55 | |
Maximum of Months | 74283741.74 | 30098.84 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 64903197.90 | 30004.94 | 01-JAN-09:01 | 9.20 |
February | 1110675.59 | 1061.92 | 02-FEB-08:10 | 8.07 |
March | 18268450.96 | 1975.92 | 12-MAR-16:02 | 31.18 |
April | 74428690.31 | 3851.23 | 16-APR-16:01 | 39.13 |
May | 70608984.54 | 4570.96 | 07-MAY-16:01 | 42.17 |
June | 62491796.10 | 4889.80 | 11-JUN-16:01 | 43.35 |
July | 67459727.45 | 4197.96 | 02-JUL-16:01 | 40.38 |
August | 47662321.81 | 3205.39 | 06-AUG-16:01 | 36.25 |
September | 55603695.97 | 2798.05 | 24-SEP-16:01 | 34.68 |
October | 49580740.14 | 2909.17 | 01-OCT-16:01 | 35.32 |
November | 6853792.70 | 1165.16 | 04-NOV-17:03 | 27.72 |
December | 1653890.54 | 2333.97 | 23-DEC-09:00 | 10.30 |
Annual Sum or Average | 0.520626E+09 | |||
Minimum of Months | 1110675.59 | 1061.92 | 8.07 | |
Maximum of Months | 74428690.31 | 30004.94 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 84691235.18 | 30155.55 | 01-JAN-09:01 | 9.20 |
February | 1578136.69 | 913.78 | 02-FEB-08:07 | 8.07 |
March | 18450786.47 | 1978.62 | 12-MAR-16:02 | 31.18 |
April | 74012693.14 | 3850.54 | 16-APR-16:01 | 39.13 |
May | 70900402.31 | 4569.29 | 07-MAY-16:01 | 42.17 |
June | 62590980.58 | 4887.51 | 11-JUN-16:01 | 43.35 |
July | 67259047.54 | 4195.24 | 02-JUL-16:01 | 40.38 |
August | 47601739.83 | 3202.60 | 06-AUG-16:01 | 36.25 |
September | 54932196.69 | 2795.84 | 24-SEP-16:01 | 34.68 |
October | 49565152.17 | 2907.33 | 01-OCT-16:01 | 35.32 |
November | 6989448.95 | 1168.60 | 04-NOV-17:03 | 27.72 |
December | 2689767.73 | 2609.49 | 23-DEC-08:63 | 7.55 |
Annual Sum or Average | 0.541262E+09 | |||
Minimum of Months | 1578136.69 | 913.78 | 7.55 | |
Maximum of Months | 84691235.18 | 30155.55 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.198622E+09 | 33732.82 | 01-JAN-09:01 | 9.20 |
February | 24826748.15 | 10492.09 | 11-FEB-08:63 | 11.12 |
March | 18932121.44 | 1951.48 | 12-MAR-16:02 | 31.18 |
April | 70628606.21 | 3794.06 | 16-APR-16:01 | 39.13 |
May | 61191095.32 | 4506.96 | 07-MAY-16:01 | 42.17 |
June | 53767089.66 | 4823.90 | 11-JUN-16:01 | 43.35 |
July | 59049436.47 | 4124.71 | 02-JUL-16:01 | 40.38 |
August | 40218887.71 | 3131.95 | 06-AUG-16:01 | 36.25 |
September | 49791829.36 | 2726.39 | 24-SEP-16:01 | 34.68 |
October | 47361662.37 | 2839.10 | 01-OCT-16:01 | 35.32 |
November | 6763335.36 | 1137.96 | 04-NOV-17:03 | 27.72 |
December | 17517690.76 | 11378.20 | 23-DEC-08:63 | 7.55 |
Annual Sum or Average | 0.648671E+09 | |||
Minimum of Months | 6763335.36 | 1137.96 | 7.55 | |
Maximum of Months | 0.198622E+09 | 33732.82 | 43.35 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.109389E+11 | 6635.66 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.989784E+10 | 6635.66 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.109616E+11 | 6635.66 | 01-MAR-10:09 | 0.223053E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.106145E+11 | 6635.66 | 01-APR-09:09 | 0.215990E+10 | 1343.25 | 01-APR-09:09 |
May | 0.109389E+11 | 6635.66 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.106145E+11 | 6635.66 | 01-JUN-09:09 | 0.215990E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.109616E+11 | 6635.66 | 01-JUL-09:09 | 0.223053E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.109389E+11 | 6635.66 | 01-AUG-09:09 | 0.222596E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.106372E+11 | 6635.66 | 01-SEP-09:09 | 0.216447E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.109389E+11 | 6635.66 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.105693E+11 | 6635.66 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.109842E+11 | 6635.66 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.128996E+12 | 0.262491E+11 | ||||
Minimum of Months | 0.989784E+10 | 6635.66 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.109842E+11 | 6635.66 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.625207E+10 | 3792.57 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.565704E+10 | 3792.57 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.626500E+10 | 3792.57 | 01-MAR-10:09 | 0.111526E+10 | 671.63 | 01-MAR-10:09 |
April | 0.606666E+10 | 3792.57 | 01-APR-09:09 | 0.107995E+10 | 671.63 | 01-APR-09:09 |
May | 0.625207E+10 | 3792.57 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.606666E+10 | 3792.57 | 01-JUN-09:09 | 0.107995E+10 | 671.63 | 01-JUN-09:09 |
July | 0.626500E+10 | 3792.57 | 01-JUL-09:09 | 0.111526E+10 | 671.63 | 01-JUL-09:09 |
August | 0.625207E+10 | 3792.57 | 01-AUG-09:09 | 0.111298E+10 | 671.63 | 01-AUG-09:09 |
September | 0.607960E+10 | 3792.57 | 01-SEP-09:09 | 0.108223E+10 | 671.63 | 01-SEP-09:09 |
October | 0.625207E+10 | 3792.57 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.604079E+10 | 3792.57 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.627794E+10 | 3792.57 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.737270E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.565704E+10 | 3792.57 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.627794E+10 | 3792.57 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.447798E+10 | 3443.15 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.405524E+10 | 3443.15 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.457193E+10 | 3443.15 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.434490E+10 | 3443.15 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.452496E+10 | 3443.15 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.441536E+10 | 3443.15 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.445450E+10 | 3443.15 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.457193E+10 | 3443.15 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.434490E+10 | 3443.15 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.447798E+10 | 3443.15 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.434490E+10 | 3443.15 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.445450E+10 | 3443.15 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.530391E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.405524E+10 | 3443.15 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.457193E+10 | 3443.15 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.447798E+10 | 3443.15 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.405524E+10 | 3443.15 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.457193E+10 | 3443.15 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.434490E+10 | 3443.15 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.452496E+10 | 3443.15 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.441536E+10 | 3443.15 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.445450E+10 | 3443.15 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.457193E+10 | 3443.15 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.434490E+10 | 3443.15 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.447798E+10 | 3443.15 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.434490E+10 | 3443.15 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.445450E+10 | 3443.15 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.530391E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.405524E+10 | 3443.15 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.457193E+10 | 3443.15 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.447798E+10 | 3443.15 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.405524E+10 | 3443.15 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.457193E+10 | 3443.15 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.434490E+10 | 3443.15 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.452496E+10 | 3443.15 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.441536E+10 | 3443.15 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.445450E+10 | 3443.15 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.457193E+10 | 3443.15 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.434490E+10 | 3443.15 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.447798E+10 | 3443.15 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.434490E+10 | 3443.15 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.445450E+10 | 3443.15 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.530391E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.405524E+10 | 3443.15 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.457193E+10 | 3443.15 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.531643E+10 | 4449.56 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.481564E+10 | 4449.56 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.543783E+10 | 4449.56 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.515962E+10 | 4449.56 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.537713E+10 | 4449.56 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.525067E+10 | 4449.56 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.528608E+10 | 4449.56 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.543783E+10 | 4449.56 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.515962E+10 | 4449.56 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.531643E+10 | 4449.56 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.515962E+10 | 4449.56 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.528608E+10 | 4449.56 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.630030E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.481564E+10 | 4449.56 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.543783E+10 | 4449.56 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.265822E+10 | 2224.78 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.240782E+10 | 2224.78 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.271892E+10 | 2224.78 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.257981E+10 | 2224.78 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.268857E+10 | 2224.78 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.262534E+10 | 2224.78 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.264304E+10 | 2224.78 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.271892E+10 | 2224.78 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.257981E+10 | 2224.78 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.265822E+10 | 2224.78 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.257981E+10 | 2224.78 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.264304E+10 | 2224.78 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.315015E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.240782E+10 | 2224.78 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.271892E+10 | 2224.78 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.265822E+10 | 2224.78 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.240782E+10 | 2224.78 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.271892E+10 | 2224.78 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.257981E+10 | 2224.78 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.268857E+10 | 2224.78 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.262534E+10 | 2224.78 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.264304E+10 | 2224.78 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.271892E+10 | 2224.78 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.257981E+10 | 2224.78 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.265822E+10 | 2224.78 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.257981E+10 | 2224.78 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.264304E+10 | 2224.78 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.315015E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.240782E+10 | 2224.78 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.271892E+10 | 2224.78 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.265822E+10 | 2224.78 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.240782E+10 | 2224.78 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.271892E+10 | 2224.78 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.257981E+10 | 2224.78 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.268857E+10 | 2224.78 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.262534E+10 | 2224.78 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.264304E+10 | 2224.78 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.271892E+10 | 2224.78 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.257981E+10 | 2224.78 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.265822E+10 | 2224.78 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.257981E+10 | 2224.78 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.264304E+10 | 2224.78 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.315015E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.240782E+10 | 2224.78 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.271892E+10 | 2224.78 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.265822E+10 | 2224.78 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.240782E+10 | 2224.78 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.271892E+10 | 2224.78 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.257981E+10 | 2224.78 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.268857E+10 | 2224.78 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.262534E+10 | 2224.78 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.264304E+10 | 2224.78 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.271892E+10 | 2224.78 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.257981E+10 | 2224.78 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.265822E+10 | 2224.78 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.257981E+10 | 2224.78 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.264304E+10 | 2224.78 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.315015E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.240782E+10 | 2224.78 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.271892E+10 | 2224.78 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.180574E+10 | 0.109389E+11 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200731E+10 |
February | 0.163016E+10 | 0.989784E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120694E+09 | 0.843940E+09 |
March | 0.178954E+10 | 0.109616E+11 | 0.223053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122902E+10 | 0.206890E+09 |
April | 0.174484E+10 | 0.106145E+11 | 0.215990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329608E+10 | 11846828.79 |
May | 0.179537E+10 | 0.109389E+11 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466043E+10 | 3792442.27 |
June | 0.173447E+10 | 0.106145E+11 | 0.215990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422948E+10 | 1745291.64 |
July | 0.181028E+10 | 0.109616E+11 | 0.223053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340750E+10 | 1166515.69 |
August | 0.178501E+10 | 0.109389E+11 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288926E+10 | 1645656.47 |
September | 0.174937E+10 | 0.106372E+11 | 0.216447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252503E+10 | 3902021.62 |
October | 0.180574E+10 | 0.109389E+11 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218267E+10 | 38480152.64 |
November | 0.174613E+10 | 0.105693E+11 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.743602E+09 | 0.256709E+09 |
December | 0.181481E+10 | 0.109842E+11 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5217231.93 | 0.171292E+10 |
Annual Sum or Average | 0.212115E+11 | 0.128996E+12 | 0.262491E+11 | 0.252890E+11 | 0.509035E+10 | ||||
Minimum of Months | 0.163016E+10 | 0.989784E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1166515.69 |
Maximum of Months | 0.181481E+10 | 0.109842E+11 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466043E+10 | 0.200731E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.902868E+09 | 0.625207E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113664E+10 |
February | 0.815075E+09 | 0.565704E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68423887.93 | 0.454554E+09 |
March | 0.894769E+09 | 0.626500E+10 | 0.111526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695460E+09 | 95779817.15 |
April | 0.872416E+09 | 0.606666E+10 | 0.107995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185746E+10 | 4629580.83 |
May | 0.897684E+09 | 0.625207E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261064E+10 | 1205222.58 |
June | 0.867232E+09 | 0.606666E+10 | 0.107995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237921E+10 | 532940.56 |
July | 0.905135E+09 | 0.626500E+10 | 0.111526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190346E+10 | 339031.81 |
August | 0.892501E+09 | 0.625207E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162461E+10 | 461943.67 |
September | 0.874683E+09 | 0.607960E+10 | 0.108223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142706E+10 | 1100449.94 |
October | 0.902868E+09 | 0.625207E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123944E+10 | 19223181.01 |
November | 0.873064E+09 | 0.604079E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423062E+09 | 0.137729E+09 |
December | 0.907403E+09 | 0.627794E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2963352.65 | 0.959321E+09 |
Annual Sum or Average | 0.106057E+11 | 0.737270E+11 | 0.131245E+11 | 0.142318E+11 | 0.281151E+10 | ||||
Minimum of Months | 0.815075E+09 | 0.565704E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339031.81 |
Maximum of Months | 0.907403E+09 | 0.627794E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261064E+10 | 0.113664E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.447798E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112434E+10 |
February | 0.487879E+09 | 0.405524E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68332646.37 | 0.469803E+09 |
March | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683067E+09 | 0.107321E+09 |
April | 0.524810E+09 | 0.434490E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183138E+10 | 6152898.82 |
May | 0.544247E+09 | 0.452496E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258094E+10 | 1519319.73 |
June | 0.532585E+09 | 0.441536E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235691E+10 | 711983.33 |
July | 0.536472E+09 | 0.445450E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186936E+10 | 438015.74 |
August | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160180E+10 | 1427139.18 |
September | 0.524810E+09 | 0.434490E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140112E+10 | 2114760.76 |
October | 0.537120E+09 | 0.447798E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121028E+10 | 20209891.73 |
November | 0.518979E+09 | 0.434490E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417973E+09 | 0.148099E+09 |
December | 0.536472E+09 | 0.445450E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2963165.82 | 0.961574E+09 |
Annual Sum or Average | 0.638324E+10 | 0.530391E+11 | 0.104207E+11 | 0.140241E+11 | 0.284371E+10 | ||||
Minimum of Months | 0.487879E+09 | 0.405524E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438015.74 |
Maximum of Months | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258094E+10 | 0.112434E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.447798E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111375E+10 |
February | 0.487879E+09 | 0.405524E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68333818.00 | 0.467805E+09 |
March | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683043E+09 | 0.107150E+09 |
April | 0.524810E+09 | 0.434490E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183109E+10 | 6236566.00 |
May | 0.544247E+09 | 0.452496E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257994E+10 | 1627686.06 |
June | 0.532585E+09 | 0.441536E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235624E+10 | 775897.25 |
July | 0.536472E+09 | 0.445450E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186819E+10 | 492722.15 |
August | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160124E+10 | 1514168.87 |
September | 0.524810E+09 | 0.434490E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140082E+10 | 2269180.54 |
October | 0.537120E+09 | 0.447798E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121008E+10 | 20261122.10 |
November | 0.518979E+09 | 0.434490E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417978E+09 | 0.147788E+09 |
December | 0.536472E+09 | 0.445450E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2963129.60 | 0.957688E+09 |
Annual Sum or Average | 0.638324E+10 | 0.530391E+11 | 0.104207E+11 | 0.140199E+11 | 0.282736E+10 | ||||
Minimum of Months | 0.487879E+09 | 0.405524E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492722.15 |
Maximum of Months | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257994E+10 | 0.111375E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.447798E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109751E+10 |
February | 0.487879E+09 | 0.405524E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68334956.82 | 0.463441E+09 |
March | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683254E+09 | 0.105835E+09 |
April | 0.524810E+09 | 0.434490E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183154E+10 | 5982257.67 |
May | 0.544247E+09 | 0.452496E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258082E+10 | 1480724.61 |
June | 0.532585E+09 | 0.441536E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235690E+10 | 724196.76 |
July | 0.536472E+09 | 0.445450E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186924E+10 | 419616.22 |
August | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160191E+10 | 1338617.43 |
September | 0.524810E+09 | 0.434490E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140124E+10 | 1992044.60 |
October | 0.537120E+09 | 0.447798E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121045E+10 | 20108660.30 |
November | 0.518979E+09 | 0.434490E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418008E+09 | 0.146817E+09 |
December | 0.536472E+09 | 0.445450E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2963076.55 | 0.950910E+09 |
Annual Sum or Average | 0.638324E+10 | 0.530391E+11 | 0.104207E+11 | 0.140247E+11 | 0.279656E+10 | ||||
Minimum of Months | 0.487879E+09 | 0.405524E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419616.22 |
Maximum of Months | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258082E+10 | 0.109751E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.183632E+10 | 0.531643E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184773E+10 |
February | 0.167188E+10 | 0.481564E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119706E+09 | 0.801863E+09 |
March | 0.189386E+10 | 0.543783E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119875E+10 | 0.189048E+09 |
April | 0.180380E+10 | 0.515962E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321326E+10 | 11249265.64 |
May | 0.186509E+10 | 0.537713E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453369E+10 | 2760934.70 |
June | 0.182945E+10 | 0.525067E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413764E+10 | 1661708.56 |
July | 0.183943E+10 | 0.528608E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328531E+10 | 646538.20 |
August | 0.189386E+10 | 0.543783E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281140E+10 | 2008478.84 |
September | 0.180380E+10 | 0.515962E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245535E+10 | 3791807.45 |
October | 0.183632E+10 | 0.531643E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212221E+10 | 38149129.23 |
November | 0.176881E+10 | 0.515962E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732133E+09 | 0.256600E+09 |
December | 0.183943E+10 | 0.528608E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5188642.08 | 0.163722E+10 |
Annual Sum or Average | 0.218821E+11 | 0.630030E+11 | 0.191729E+11 | 0.246146E+11 | 0.479273E+10 | ||||
Minimum of Months | 0.167188E+10 | 0.481564E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 646538.20 |
Maximum of Months | 0.189386E+10 | 0.543783E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453369E+10 | 0.184773E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103865E+10 |
February | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68342693.22 | 0.448989E+09 |
March | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684445E+09 | 0.102816E+09 |
April | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183326E+10 | 5803452.37 |
May | 0.932542E+09 | 0.268857E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258417E+10 | 1288944.41 |
June | 0.914724E+09 | 0.262534E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235971E+10 | 795713.92 |
July | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187219E+10 | 279392.73 |
August | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160377E+10 | 922584.87 |
September | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140174E+10 | 1696465.89 |
October | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121230E+10 | 21107049.60 |
November | 0.884402E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418203E+09 | 0.144600E+09 |
December | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2963131.07 | 0.925792E+09 |
Annual Sum or Average | 0.109410E+11 | 0.315015E+11 | 0.958644E+10 | 0.140411E+11 | 0.269275E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279392.73 |
Maximum of Months | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258417E+10 | 0.103865E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103109E+10 |
February | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68342893.16 | 0.446657E+09 |
March | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684525E+09 | 0.102269E+09 |
April | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183344E+10 | 5735516.39 |
May | 0.932542E+09 | 0.268857E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258441E+10 | 1259964.24 |
June | 0.914724E+09 | 0.262534E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235992E+10 | 782108.68 |
July | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187247E+10 | 270233.12 |
August | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160396E+10 | 898631.78 |
September | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140188E+10 | 1641873.86 |
October | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121242E+10 | 21038825.14 |
November | 0.884402E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418217E+09 | 0.144207E+09 |
December | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2963216.06 | 0.922140E+09 |
Annual Sum or Average | 0.109410E+11 | 0.315015E+11 | 0.958644E+10 | 0.140425E+11 | 0.267799E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270233.12 |
Maximum of Months | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258441E+10 | 0.103109E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101600E+10 |
February | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68343161.84 | 0.440518E+09 |
March | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684651E+09 | 0.100561E+09 |
April | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183359E+10 | 5583425.77 |
May | 0.932542E+09 | 0.268857E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258443E+10 | 1205448.63 |
June | 0.914724E+09 | 0.262534E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235989E+10 | 772601.92 |
July | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187220E+10 | 261925.64 |
August | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160381E+10 | 898533.66 |
September | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140182E+10 | 1602417.17 |
October | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121241E+10 | 20943788.01 |
November | 0.884402E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418233E+09 | 0.143182E+09 |
December | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2963186.15 | 0.913566E+09 |
Annual Sum or Average | 0.109410E+11 | 0.315015E+11 | 0.958644E+10 | 0.140423E+11 | 0.264510E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261925.64 |
Maximum of Months | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258443E+10 | 0.101600E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106057E+10 |
February | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69181312.47 | 0.493659E+09 |
March | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694548E+09 | 0.137556E+09 |
April | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187439E+10 | 9029267.11 |
May | 0.932542E+09 | 0.268857E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266746E+10 | 2953772.08 |
June | 0.914724E+09 | 0.262534E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242206E+10 | 1816596.53 |
July | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193904E+10 | 843028.93 |
August | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164201E+10 | 2293524.24 |
September | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142384E+10 | 4737027.49 |
October | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122224E+10 | 26010581.28 |
November | 0.884402E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421047E+09 | 0.157918E+09 |
December | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2991532.98 | 0.959211E+09 |
Annual Sum or Average | 0.109410E+11 | 0.315015E+11 | 0.958644E+10 | 0.143788E+11 | 0.285660E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 843028.93 |
Maximum of Months | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266746E+10 | 0.106057E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2159.72 | 01-JAN-13:09 | 6635.66 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4264.98 | 15-JAN-18:00 |
February | 2159.72 | 03-FEB-13:09 | 6635.66 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1447.29 | 22-FEB-15:00 | 3837.16 | 10-FEB-18:00 |
March | 2159.72 | 03-MAR-13:09 | 6635.66 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5081.45 | 28-MAR-15:00 | 1577.58 | 18-MAR-17:00 |
April | 2159.72 | 01-APR-12:09 | 6635.66 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7288.68 | 15-APR-15:00 | 295.52 | 10-APR-07:03 |
May | 2159.72 | 05-MAY-12:09 | 6635.66 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8781.49 | 03-MAY-15:00 | 75.38 | 13-MAY-05:00 |
June | 2159.72 | 02-JUN-12:09 | 6635.66 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8808.75 | 06-JUN-15:00 | 89.34 | 18-JUN-05:00 |
July | 2159.72 | 01-JUL-12:09 | 6635.66 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7083.44 | 07-JUL-15:00 | 79.41 | 19-JUL-03:00 |
August | 2159.72 | 04-AUG-12:09 | 6635.66 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5871.58 | 07-AUG-15:00 | 103.85 | 16-AUG-07:01 |
September | 2159.72 | 01-SEP-12:09 | 6635.66 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5407.50 | 29-SEP-13:00 | 95.41 | 07-SEP-07:01 |
October | 2159.72 | 01-OCT-12:09 | 6635.66 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5500.06 | 02-OCT-14:00 | 505.39 | 11-OCT-16:00 |
November | 2159.72 | 03-NOV-12:09 | 6635.66 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2858.31 | 04-NOV-14:00 | 2233.40 | 30-NOV-18:00 |
December | 2159.72 | 01-DEC-13:09 | 6635.66 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 323.80 | 28-DEC-14:00 | 5033.52 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2159.72 | 6635.66 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.38 | |||||
Maximum of Months | 2159.72 | 6635.66 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8808.75 | 5033.52 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 01-JAN-13:09 | 3792.57 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2500.36 | 15-JAN-18:00 |
February | 1079.86 | 03-FEB-13:09 | 3792.57 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.26 | 22-FEB-15:00 | 2302.02 | 10-FEB-18:00 |
March | 1079.86 | 03-MAR-13:09 | 3792.57 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.54 | 28-MAR-15:00 | 894.16 | 18-MAR-17:00 |
April | 1079.86 | 01-APR-12:09 | 3792.57 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4078.49 | 15-APR-15:00 | 163.32 | 10-APR-07:03 |
May | 1079.86 | 05-MAY-12:09 | 3792.57 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4974.18 | 03-MAY-15:00 | 41.69 | 13-MAY-07:02 |
June | 1079.86 | 02-JUN-12:09 | 3792.57 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.68 | 07-JUN-16:00 | 27.13 | 18-JUN-05:00 |
July | 1079.86 | 01-JUL-12:09 | 3792.57 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4020.11 | 07-JUL-15:00 | 23.28 | 19-JUL-03:00 |
August | 1079.86 | 04-AUG-12:09 | 3792.57 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3323.84 | 07-AUG-15:00 | 52.04 | 16-AUG-07:01 |
September | 1079.86 | 01-SEP-12:09 | 3792.57 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3058.20 | 29-SEP-13:00 | 48.39 | 07-SEP-07:01 |
October | 1079.86 | 01-OCT-12:09 | 3792.57 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3125.50 | 02-OCT-14:00 | 286.44 | 11-OCT-16:00 |
November | 1079.86 | 03-NOV-12:09 | 3792.57 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.96 | 04-NOV-14:00 | 1272.87 | 30-NOV-18:00 |
December | 1079.86 | 01-DEC-13:09 | 3792.57 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.43 | 28-DEC-14:00 | 2906.28 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3792.57 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.28 | |||||
Maximum of Months | 1079.86 | 3792.57 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.68 | 2906.28 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3443.15 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2403.11 | 15-JAN-17:00 |
February | 1079.86 | 04-FEB-13:09 | 3443.15 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.24 | 22-FEB-15:00 | 2270.45 | 10-FEB-12:10 |
March | 1079.86 | 04-MAR-13:09 | 3443.15 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.55 | 28-MAR-15:00 | 894.19 | 18-MAR-17:00 |
April | 1079.86 | 01-APR-12:09 | 3443.15 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4078.48 | 15-APR-15:00 | 187.17 | 22-APR-19:00 |
May | 1079.86 | 06-MAY-12:09 | 3443.15 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4974.16 | 03-MAY-15:00 | 27.76 | 15-MAY-03:00 |
June | 1079.86 | 03-JUN-12:09 | 3443.15 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.67 | 07-JUN-16:00 | 45.76 | 18-JUN-07:01 |
July | 1079.86 | 01-JUL-12:09 | 3443.15 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4020.10 | 07-JUL-15:00 | 25.16 | 19-JUL-03:00 |
August | 1079.86 | 05-AUG-12:09 | 3443.15 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3323.84 | 07-AUG-15:00 | 227.78 | 20-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 3443.15 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3058.16 | 29-SEP-13:00 | 119.54 | 03-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 3443.15 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3125.49 | 02-OCT-14:00 | 286.45 | 11-OCT-16:00 |
November | 1079.86 | 04-NOV-12:09 | 3443.15 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.96 | 04-NOV-14:00 | 1272.87 | 30-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3443.15 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.42 | 28-DEC-14:00 | 2867.23 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.16 | |||||
Maximum of Months | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.67 | 2867.23 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3443.15 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2379.67 | 15-JAN-17:00 |
February | 1079.86 | 04-FEB-13:09 | 3443.15 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.24 | 22-FEB-15:00 | 2253.88 | 10-FEB-12:10 |
March | 1079.86 | 04-MAR-13:09 | 3443.15 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.55 | 28-MAR-15:00 | 894.19 | 18-MAR-17:00 |
April | 1079.86 | 01-APR-12:09 | 3443.15 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4078.48 | 15-APR-15:00 | 187.39 | 22-APR-19:00 |
May | 1079.86 | 06-MAY-12:09 | 3443.15 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4974.16 | 03-MAY-15:00 | 29.54 | 15-MAY-03:00 |
June | 1079.86 | 03-JUN-12:09 | 3443.15 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.68 | 07-JUN-16:00 | 50.43 | 18-JUN-07:01 |
July | 1079.86 | 01-JUL-12:09 | 3443.15 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4020.10 | 07-JUL-15:00 | 25.66 | 19-JUL-03:00 |
August | 1079.86 | 05-AUG-12:09 | 3443.15 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3323.85 | 07-AUG-15:00 | 232.85 | 20-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 3443.15 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3058.16 | 29-SEP-13:00 | 126.07 | 03-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 3443.15 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3125.49 | 02-OCT-14:00 | 286.45 | 11-OCT-16:00 |
November | 1079.86 | 04-NOV-12:09 | 3443.15 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.96 | 04-NOV-14:00 | 1272.86 | 30-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3443.15 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.42 | 28-DEC-14:00 | 2848.43 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 | |||||
Maximum of Months | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.68 | 2848.43 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3443.15 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2334.18 | 15-JAN-17:00 |
February | 1079.86 | 04-FEB-13:09 | 3443.15 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.23 | 22-FEB-15:00 | 2200.91 | 10-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3443.15 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.56 | 28-MAR-15:00 | 894.20 | 18-MAR-17:00 |
April | 1079.86 | 01-APR-12:09 | 3443.15 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4078.49 | 15-APR-15:00 | 182.09 | 22-APR-19:00 |
May | 1079.86 | 06-MAY-12:09 | 3443.15 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4974.16 | 03-MAY-15:00 | 28.29 | 15-MAY-03:00 |
June | 1079.86 | 03-JUN-12:09 | 3443.15 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.68 | 07-JUN-16:00 | 47.11 | 18-JUN-07:01 |
July | 1079.86 | 01-JUL-12:09 | 3443.15 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4020.10 | 07-JUL-15:00 | 24.66 | 19-JUL-03:00 |
August | 1079.86 | 05-AUG-12:09 | 3443.15 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3323.84 | 07-AUG-15:00 | 219.76 | 20-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 3443.15 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3058.16 | 29-SEP-13:00 | 113.88 | 03-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 3443.15 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3125.49 | 02-OCT-14:00 | 286.46 | 11-OCT-16:00 |
November | 1079.86 | 04-NOV-12:09 | 3443.15 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.96 | 04-NOV-14:00 | 1272.86 | 30-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3443.15 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.42 | 28-DEC-14:00 | 2803.61 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.66 | |||||
Maximum of Months | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.68 | 2803.61 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2879.63 | 07-JAN-15:09 | 4449.56 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3843.94 | 15-JAN-17:00 |
February | 2879.63 | 04-FEB-15:09 | 4449.56 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1441.23 | 22-FEB-15:00 | 3590.65 | 10-FEB-18:00 |
March | 2879.63 | 04-MAR-15:09 | 4449.56 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5081.52 | 28-MAR-15:00 | 1566.32 | 18-MAR-17:00 |
April | 2879.63 | 01-APR-14:09 | 4449.56 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7157.75 | 15-APR-15:00 | 305.31 | 22-APR-19:00 |
May | 2879.63 | 06-MAY-14:09 | 4449.56 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8713.69 | 03-MAY-15:00 | 71.70 | 13-MAY-07:02 |
June | 2879.63 | 03-JUN-14:09 | 4449.56 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8729.82 | 07-JUN-16:00 | 129.61 | 18-JUN-07:01 |
July | 2879.63 | 01-JUL-14:09 | 4449.56 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7040.35 | 07-JUL-15:00 | 44.64 | 19-JUL-03:00 |
August | 2879.63 | 05-AUG-14:09 | 4449.56 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5823.14 | 07-AUG-15:00 | 317.89 | 20-AUG-17:00 |
September | 2879.63 | 02-SEP-14:09 | 4449.56 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5358.42 | 29-SEP-13:00 | 128.61 | 03-SEP-17:00 |
October | 2879.63 | 07-OCT-14:09 | 4449.56 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5472.60 | 02-OCT-14:00 | 515.64 | 29-OCT-07:03 |
November | 2879.63 | 04-NOV-14:09 | 4449.56 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2849.60 | 04-NOV-14:00 | 2227.78 | 30-NOV-18:00 |
December | 2879.63 | 02-DEC-15:09 | 4449.56 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 321.30 | 28-DEC-14:00 | 4693.44 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2879.63 | 4449.56 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | |||||
Maximum of Months | 2879.63 | 4449.56 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8729.82 | 4693.44 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2224.78 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2178.07 | 01-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2224.78 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.23 | 22-FEB-15:00 | 2021.41 | 10-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2224.78 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.60 | 28-MAR-15:00 | 894.22 | 18-MAR-17:00 |
April | 1439.81 | 01-APR-14:09 | 2224.78 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4078.75 | 15-APR-15:00 | 163.17 | 22-APR-19:00 |
May | 1439.81 | 06-MAY-14:09 | 2224.78 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4974.22 | 03-MAY-15:00 | 35.84 | 13-MAY-07:02 |
June | 1439.81 | 03-JUN-14:09 | 2224.78 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.74 | 07-JUN-16:00 | 68.24 | 18-JUN-07:01 |
July | 1439.81 | 01-JUL-14:09 | 2224.78 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4020.17 | 07-JUL-15:00 | 21.54 | 19-JUL-03:00 |
August | 1439.81 | 05-AUG-14:09 | 2224.78 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3323.92 | 07-AUG-15:00 | 156.59 | 20-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 2224.78 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3058.19 | 29-SEP-13:00 | 54.52 | 03-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 2224.78 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3125.52 | 02-OCT-14:00 | 289.95 | 29-OCT-07:03 |
November | 1439.81 | 04-NOV-14:09 | 2224.78 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.98 | 04-NOV-14:00 | 1272.86 | 30-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2224.78 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.42 | 28-DEC-14:00 | 2660.10 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.54 | |||||
Maximum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.74 | 2660.10 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2224.78 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2178.07 | 01-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2224.78 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.23 | 22-FEB-15:00 | 2000.16 | 10-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2224.78 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.60 | 28-MAR-15:00 | 894.23 | 18-MAR-17:00 |
April | 1439.81 | 01-APR-14:09 | 2224.78 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4078.75 | 15-APR-15:00 | 162.58 | 10-APR-07:03 |
May | 1439.81 | 06-MAY-14:09 | 2224.78 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4974.22 | 03-MAY-15:00 | 34.70 | 13-MAY-07:02 |
June | 1439.81 | 03-JUN-14:09 | 2224.78 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.74 | 07-JUN-16:00 | 67.18 | 18-JUN-07:01 |
July | 1439.81 | 01-JUL-14:09 | 2224.78 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4020.17 | 07-JUL-15:00 | 21.35 | 19-JUL-03:00 |
August | 1439.81 | 05-AUG-14:09 | 2224.78 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3323.92 | 07-AUG-15:00 | 152.47 | 20-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 2224.78 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3058.19 | 29-SEP-13:00 | 53.42 | 04-SEP-07:01 |
October | 1439.81 | 07-OCT-14:09 | 2224.78 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3125.52 | 02-OCT-14:00 | 288.65 | 29-OCT-07:03 |
November | 1439.81 | 04-NOV-14:09 | 2224.78 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.98 | 04-NOV-14:00 | 1272.86 | 30-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2224.78 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.42 | 28-DEC-14:00 | 2645.44 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.35 | |||||
Maximum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.74 | 2645.44 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2224.78 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2178.07 | 01-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2224.78 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.23 | 22-FEB-15:00 | 1951.43 | 10-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2224.78 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.60 | 28-MAR-15:00 | 894.23 | 18-MAR-17:00 |
April | 1439.81 | 01-APR-14:09 | 2224.78 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4078.75 | 15-APR-15:00 | 162.15 | 10-APR-07:03 |
May | 1439.81 | 06-MAY-14:09 | 2224.78 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4974.22 | 03-MAY-15:00 | 31.33 | 13-MAY-07:02 |
June | 1439.81 | 03-JUN-14:09 | 2224.78 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.74 | 07-JUN-16:00 | 65.92 | 18-JUN-07:01 |
July | 1439.81 | 01-JUL-14:09 | 2224.78 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4020.17 | 07-JUL-15:00 | 21.07 | 19-JUL-03:00 |
August | 1439.81 | 05-AUG-14:09 | 2224.78 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3323.93 | 07-AUG-15:00 | 154.12 | 20-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 2224.78 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3058.19 | 29-SEP-13:00 | 53.09 | 03-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 2224.78 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3125.52 | 02-OCT-14:00 | 286.47 | 11-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 2224.78 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.98 | 04-NOV-14:00 | 1272.86 | 30-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2224.78 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.41 | 28-DEC-14:00 | 2609.19 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.07 | |||||
Maximum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.74 | 2609.19 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2224.78 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2182.34 | 01-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2224.78 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 829.25 | 22-FEB-15:00 | 1854.70 | 10-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2224.78 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.60 | 28-MAR-15:00 | 905.56 | 18-MAR-17:00 |
April | 1439.81 | 01-APR-14:09 | 2224.78 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4209.97 | 15-APR-15:00 | 210.83 | 22-APR-18:10 |
May | 1439.81 | 06-MAY-14:09 | 2224.78 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5041.96 | 03-MAY-15:00 | 60.33 | 15-MAY-03:00 |
June | 1439.81 | 03-JUN-14:09 | 2224.78 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5082.36 | 06-JUN-15:00 | 81.51 | 18-JUN-07:01 |
July | 1439.81 | 01-JUL-14:09 | 2224.78 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4063.30 | 07-JUL-15:00 | 53.89 | 19-JUL-03:00 |
August | 1439.81 | 05-AUG-14:09 | 2224.78 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3372.46 | 07-AUG-15:00 | 244.26 | 20-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 2224.78 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3107.22 | 29-SEP-13:00 | 131.10 | 03-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 2224.78 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3152.98 | 02-OCT-14:00 | 294.50 | 29-OCT-07:03 |
November | 1439.81 | 04-NOV-14:09 | 2224.78 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1636.73 | 04-NOV-14:00 | 1278.46 | 30-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2224.78 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 185.91 | 28-DEC-14:00 | 2584.81 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.89 | |||||
Maximum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5082.36 | 2584.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8292.26 | 12-JAN-15:00 | 1439.81 | 6635.66 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.35 |
February | 12115.68 | 22-FEB-15:00 | 1439.81 | 6635.66 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1447.29 | 0.00 |
March | 40057.61 | 30-MAR-07:02 | 899.88 | 1746.23 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.11 |
April | 46352.73 | 08-APR-07:02 | 0.00 | 1749.37 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 28.82 | 0.00 |
May | 46408.13 | 06-MAY-07:01 | 0.00 | 2799.00 | 589.11 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | 0.00 |
June | 43070.47 | 07-JUN-07:01 | 1799.77 | 3492.45 | 746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 584.55 | 0.00 |
July | 37180.38 | 07-JUL-07:01 | 0.00 | 3498.75 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 442.91 | 0.00 |
August | 34658.54 | 03-AUG-07:01 | 1619.79 | 3143.21 | 671.62 | 0.00 | 0.00 | 0.00 | 0.00 | 145.80 | 0.00 |
September | 37695.40 | 26-SEP-07:01 | 1259.84 | 2444.72 | 522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 21.41 | 0.00 |
October | 43101.40 | 23-OCT-07:02 | 899.88 | 1746.23 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.72 |
November | 28089.97 | 09-NOV-08:62 | 719.91 | 1396.98 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.17 |
December | 9956.38 | 02-DEC-14:00 | 2159.72 | 6635.66 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 92.90 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 8292.26 | 0.00 | 1396.98 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46408.13 | 2159.72 | 6635.66 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1447.29 | 276.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4739.46 | 12-JAN-15:00 | 719.90 | 3792.57 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.11 |
February | 8309.59 | 25-FEB-08:63 | 0.00 | 599.91 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.47 |
March | 21725.23 | 30-MAR-07:02 | 449.94 | 998.04 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.60 |
April | 24090.58 | 08-APR-07:02 | 0.00 | 999.84 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.47 | 0.00 |
May | 24012.83 | 06-MAY-07:01 | 0.00 | 1599.75 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 152.31 | 0.00 |
June | 22528.27 | 07-JUN-07:01 | 899.88 | 1996.09 | 373.13 | 0.00 | 0.00 | 0.00 | 0.00 | 317.21 | 0.00 |
July | 20206.64 | 07-JUL-07:01 | 0.00 | 1999.69 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 247.85 | 0.00 |
August | 19381.22 | 03-AUG-07:01 | 809.89 | 1796.48 | 335.81 | 0.00 | 0.00 | 0.00 | 0.00 | 87.71 | 0.00 |
September | 20986.00 | 26-SEP-07:01 | 629.92 | 1397.26 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 16.34 | 0.00 |
October | 23074.73 | 25-OCT-07:02 | 449.94 | 998.04 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.20 |
November | 16325.94 | 09-NOV-08:62 | 359.95 | 798.44 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.37 |
December | 5650.22 | 02-DEC-14:00 | 1079.86 | 3792.57 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 52.96 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4739.46 | 0.00 | 599.91 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24090.58 | 1079.86 | 3792.57 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 317.21 | 208.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4341.46 | 12-JAN-15:00 | 539.93 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.12 |
February | 7863.99 | 25-FEB-07:03 | 0.00 | 543.66 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.22 |
March | 21576.12 | 29-MAR-06:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
April | 24782.37 | 20-APR-06:01 | 0.00 | 1268.53 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 | 0.00 |
May | 24327.05 | 06-MAY-06:01 | 0.00 | 1630.97 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 | 0.00 |
June | 22191.72 | 07-JUN-06:01 | 0.00 | 1812.19 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 16.93 | 0.00 |
July | 18179.60 | 01-JUL-06:01 | 0.00 | 1630.97 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 4.73 | 0.00 |
August | 16026.10 | 03-AUG-06:01 | 0.00 | 1630.97 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 2.80 | 0.00 |
September | 18761.10 | 27-SEP-06:01 | 0.00 | 1268.53 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 |
October | 23818.87 | 23-OCT-06:02 | 0.00 | 1087.31 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.55 |
November | 15786.25 | 09-NOV-07:03 | 0.00 | 724.87 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.55 |
December | 5385.46 | 02-DEC-14:00 | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 52.97 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4341.46 | 0.00 | 543.66 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24782.37 | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 52.97 | 78.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4211.84 | 12-JAN-15:00 | 539.93 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.12 |
February | 7444.04 | 25-FEB-07:03 | 0.00 | 543.66 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.21 |
March | 21625.36 | 29-MAR-06:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
April | 24840.98 | 20-APR-06:01 | 0.00 | 1268.53 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 | 0.00 |
May | 24412.40 | 06-MAY-06:01 | 0.00 | 1630.97 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 3.66 | 0.00 |
June | 22364.19 | 12-JUN-06:01 | 0.00 | 1812.19 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 | 0.00 |
July | 18303.65 | 01-JUL-06:01 | 0.00 | 1630.97 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 4.60 | 0.00 |
August | 16133.54 | 03-AUG-06:01 | 0.00 | 1630.97 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 2.68 | 0.00 |
September | 18855.77 | 27-SEP-06:01 | 0.00 | 1268.53 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 |
October | 23920.45 | 23-OCT-06:02 | 0.00 | 1087.31 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.60 |
November | 15617.60 | 09-NOV-07:03 | 0.00 | 724.87 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 |
December | 5305.92 | 02-DEC-14:00 | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 52.97 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4211.84 | 0.00 | 543.66 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24840.98 | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 52.97 | 78.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3951.66 | 12-JAN-15:00 | 539.93 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.12 |
February | 6043.38 | 22-FEB-14:00 | 719.90 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 797.56 | 0.00 |
March | 21372.56 | 29-MAR-06:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
April | 24609.53 | 20-APR-06:01 | 0.00 | 1268.53 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 1.86 | 0.00 |
May | 24198.30 | 06-MAY-06:01 | 0.00 | 1630.97 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 3.86 | 0.00 |
June | 22189.86 | 12-JUN-06:01 | 0.00 | 1812.19 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 15.98 | 0.00 |
July | 18013.45 | 01-JUL-06:01 | 0.00 | 1630.97 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 | 0.00 |
August | 15858.24 | 03-AUG-06:01 | 0.00 | 1630.97 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 2.92 | 0.00 |
September | 18609.73 | 27-SEP-06:01 | 0.00 | 1268.53 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 |
October | 23696.37 | 23-OCT-06:02 | 0.00 | 1087.31 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.53 |
November | 14047.12 | 09-NOV-07:03 | 0.00 | 724.87 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 |
December | 5111.44 | 02-DEC-14:00 | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 52.96 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3951.66 | 0.00 | 724.87 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24609.53 | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 797.56 | 78.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6917.69 | 03-JAN-08:03 | 0.00 | 1639.31 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1061.73 |
February | 10120.15 | 22-FEB-15:10 | 2483.68 | 4449.56 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1397.58 | 0.00 |
March | 37519.11 | 30-MAR-07:02 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.16 |
April | 43401.29 | 20-APR-07:01 | 0.00 | 1639.31 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 100.40 | 0.00 |
May | 42691.54 | 29-MAY-08:61 | 0.00 | 2341.87 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 394.17 | 0.00 |
June | 39452.28 | 07-JUN-07:01 | 0.00 | 2341.87 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 555.80 | 0.00 |
July | 33867.66 | 07-JUL-07:01 | 0.00 | 2341.87 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 427.75 | 0.00 |
August | 30910.77 | 08-AUG-07:01 | 0.00 | 2341.87 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 239.72 | 0.00 |
September | 34724.04 | 27-SEP-07:02 | 0.00 | 1405.12 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.22 |
October | 41273.80 | 23-OCT-07:02 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.03 |
November | 22770.38 | 09-NOV-08:62 | 0.00 | 936.75 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.99 |
December | 8277.22 | 02-DEC-14:20 | 2771.64 | 4449.56 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 62.29 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6917.69 | 0.00 | 936.75 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43401.29 | 2771.64 | 4449.56 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1397.58 | 1061.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3458.49 | 03-JAN-08:03 | 0.00 | 819.66 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 605.79 |
February | 5260.42 | 22-FEB-15:10 | 1241.83 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 798.23 | 0.00 |
March | 18435.75 | 30-MAR-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.43 |
April | 22706.81 | 20-APR-07:01 | 0.00 | 819.66 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 61.97 | 0.00 |
May | 22332.37 | 29-MAY-08:61 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 223.27 | 0.00 |
June | 20617.68 | 07-JUN-07:01 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 319.74 | 0.00 |
July | 17713.43 | 07-JUL-07:01 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 248.24 | 0.00 |
August | 16163.28 | 08-AUG-07:01 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 140.69 | 0.00 |
September | 18114.23 | 27-SEP-07:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
October | 21534.99 | 23-OCT-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.34 |
November | 10405.51 | 09-NOV-08:62 | 0.00 | 468.37 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.01 |
December | 4237.26 | 02-DEC-14:30 | 1385.82 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 26.89 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3458.49 | 0.00 | 468.37 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22706.81 | 1385.82 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 798.23 | 605.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3439.12 | 03-JAN-08:03 | 0.00 | 819.66 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 602.51 |
February | 5190.00 | 22-FEB-15:10 | 1241.83 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 798.23 | 0.00 |
March | 17903.19 | 30-MAR-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.24 |
April | 22591.93 | 20-APR-07:01 | 0.00 | 819.66 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 63.19 | 0.00 |
May | 22246.75 | 29-MAY-08:61 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 223.86 | 0.00 |
June | 20513.72 | 07-JUN-07:01 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 320.66 | 0.00 |
July | 17615.22 | 07-JUL-07:01 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 248.96 | 0.00 |
August | 16074.19 | 08-AUG-07:01 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 141.33 | 0.00 |
September | 18014.13 | 27-SEP-07:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 0.00 |
October | 21440.87 | 23-OCT-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.59 |
November | 9981.32 | 09-NOV-08:62 | 0.00 | 468.37 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.85 |
December | 4171.16 | 02-DEC-14:30 | 1385.82 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 26.89 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3439.12 | 0.00 | 468.37 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22591.93 | 1385.82 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 798.23 | 602.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3336.84 | 04-JAN-08:04 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 597.54 |
February | 5069.53 | 22-FEB-15:10 | 1241.83 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 798.23 | 0.00 |
March | 16464.55 | 11-MAR-08:62 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.07 | 0.00 |
April | 22580.11 | 20-APR-07:01 | 0.00 | 819.66 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 66.41 | 0.00 |
May | 22311.95 | 29-MAY-08:61 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 223.71 | 0.00 |
June | 20608.65 | 07-JUN-07:01 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 319.49 | 0.00 |
July | 17727.45 | 07-JUL-07:01 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 247.53 | 0.00 |
August | 16194.03 | 08-AUG-07:01 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 139.69 | 0.00 |
September | 18075.62 | 27-SEP-07:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 0.00 |
October | 21469.54 | 23-OCT-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.18 |
November | 8761.96 | 09-NOV-08:62 | 0.00 | 468.37 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.52 |
December | 4038.84 | 02-DEC-14:30 | 1385.82 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 26.89 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3336.84 | 0.00 | 468.37 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22580.11 | 1385.82 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 798.23 | 597.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3685.32 | 04-JAN-08:04 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 607.56 |
February | 5507.26 | 22-FEB-14:00 | 1277.83 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 801.85 | 0.00 |
March | 12711.40 | 11-MAR-08:62 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.59 | 0.00 |
April | 24253.16 | 20-APR-07:01 | 0.00 | 819.66 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 79.35 | 0.00 |
May | 25023.54 | 29-MAY-08:61 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 260.91 | 0.00 |
June | 23543.11 | 12-JUN-07:01 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 324.30 | 0.00 |
July | 20108.23 | 07-JUL-07:01 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 251.23 | 0.00 |
August | 17758.31 | 09-AUG-07:01 | 0.00 | 1053.84 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 128.40 | 0.00 |
September | 20323.95 | 27-SEP-07:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 |
October | 23269.21 | 23-OCT-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.37 |
November | 7894.56 | 04-NOV-14:10 | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1631.64 | 0.00 |
December | 4288.72 | 01-DEC-14:00 | 1277.83 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.76 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3685.32 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25023.54 | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1631.64 | 607.56 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.850718E+11 | 69417.89 | 12-JAN-15:20 | 0.368209E+10 | 98898.98 | 02-JAN-08:09 |
February | 0.841368E+11 | 78721.08 | 22-FEB-14:00 | 0.322072E+09 | 22070.77 | 02-FEB-08:20 |
March | 0.108304E+12 | 97902.46 | 28-MAR-15:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.123496E+12 | 121905.82 | 16-APR-15:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.150797E+12 | 137565.35 | 30-MAY-16:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.155440E+12 | 150314.14 | 22-JUN-15:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.159475E+12 | 149343.53 | 01-JUL-14:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.158723E+12 | 143090.56 | 27-AUG-14:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.140593E+12 | 129684.40 | 14-SEP-16:19 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.122658E+12 | 112525.67 | 03-OCT-13:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.101449E+12 | 88556.93 | 08-NOV-13:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.883599E+11 | 73444.40 | 28-DEC-17:40 | 0.482229E+09 | 33398.29 | 23-DEC-08:09 |
Annual Sum or Average | 0.147850E+13 | 0.448639E+10 | ||||
Minimum of Months | 0.841368E+11 | 69417.89 | 0.00 | 0.00 | ||
Maximum of Months | 0.159475E+12 | 150314.14 | 0.368209E+10 | 98898.98 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.465742E+11 | 0.903676E+10 | 0.108325E+11 | 0.00 | 0.103174E+11 | 0.00 | 0.00 | 0.308865E+10 | 0.00 | 0.00 | 0.00 | 0.522235E+10 | 0.00 |
February | 0.421675E+11 | 0.775911E+10 | 0.980803E+10 | 0.00 | 0.930126E+10 | 0.00 | 0.00 | 0.104087E+11 | 0.00 | 0.00 | 0.00 | 0.469217E+10 | 0.00 |
March | 0.472558E+11 | 0.793720E+10 | 0.110038E+11 | 0.00 | 0.104701E+11 | 0.00 | 0.00 | 0.265095E+11 | 0.00 | 0.00 | 0.00 | 0.512767E+10 | 0.00 |
April | 0.451947E+11 | 0.704190E+10 | 0.105115E+11 | 0.00 | 0.105781E+11 | 0.00 | 0.00 | 0.453461E+11 | 0.00 | 0.00 | 0.00 | 0.482346E+10 | 0.00 |
May | 0.468973E+11 | 0.671501E+10 | 0.109147E+11 | 0.00 | 0.130031E+11 | 0.00 | 0.00 | 0.684015E+11 | 0.00 | 0.00 | 0.00 | 0.486515E+10 | 0.00 |
June | 0.456793E+11 | 0.619609E+10 | 0.106349E+11 | 0.00 | 0.138252E+11 | 0.00 | 0.00 | 0.744721E+11 | 0.00 | 0.00 | 0.00 | 0.463278E+10 | 0.00 |
July | 0.464483E+11 | 0.656699E+10 | 0.107982E+11 | 0.00 | 0.145230E+11 | 0.00 | 0.00 | 0.764132E+11 | 0.00 | 0.00 | 0.00 | 0.472537E+10 | 0.00 |
August | 0.472203E+11 | 0.701950E+10 | 0.109970E+11 | 0.00 | 0.144308E+11 | 0.00 | 0.00 | 0.742755E+11 | 0.00 | 0.00 | 0.00 | 0.478001E+10 | 0.00 |
September | 0.452303E+11 | 0.740559E+10 | 0.105184E+11 | 0.00 | 0.121416E+11 | 0.00 | 0.00 | 0.606074E+11 | 0.00 | 0.00 | 0.00 | 0.469012E+10 | 0.00 |
October | 0.465742E+11 | 0.831782E+10 | 0.108325E+11 | 0.00 | 0.105670E+11 | 0.00 | 0.00 | 0.414106E+11 | 0.00 | 0.00 | 0.00 | 0.495621E+10 | 0.00 |
November | 0.451236E+11 | 0.860242E+10 | 0.104978E+11 | 0.00 | 0.997550E+10 | 0.00 | 0.00 | 0.223337E+11 | 0.00 | 0.00 | 0.00 | 0.491635E+10 | 0.00 |
December | 0.464839E+11 | 0.923552E+10 | 0.108050E+11 | 0.00 | 0.102318E+11 | 0.00 | 0.00 | 0.642615E+10 | 0.00 | 0.00 | 0.00 | 0.517753E+10 | 0.00 |
Annual Sum or Average | 0.550849E+12 | 0.918339E+11 | 0.128154E+12 | 0.139365E+12 | 0.00 | 0.509693E+12 | 0.586092E+11 | ||||||
Minimum of Months | 0.421675E+11 | 0.619609E+10 | 0.980803E+10 | 0.00 | 0.930126E+10 | 0.00 | 0.00 | 0.308865E+10 | 0.00 | 0.00 | 0.00 | 0.463278E+10 | 0.00 |
Maximum of Months | 0.472558E+11 | 0.923552E+10 | 0.110038E+11 | 0.00 | 0.145230E+11 | 0.00 | 0.00 | 0.764132E+11 | 0.00 | 0.00 | 0.00 | 0.522235E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.368209E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.322072E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.482229E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.448639E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.368209E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 34106.38 | 01-JAN-11:09 | 7048.42 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 9110.74 | 02-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 34106.38 | 01-FEB-10:09 | 7048.42 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 7502.40 | 02-FEB-08:20 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 34106.38 | 01-MAR-10:09 | 7048.42 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 8452.71 | 11-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 34106.38 | 01-APR-09:09 | 7048.42 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 10913.80 | 16-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 34106.38 | 01-MAY-09:09 | 7048.42 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 13647.65 | 03-MAY-14:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 34106.38 | 01-JUN-09:09 | 7048.42 | 01-JUN-05:10 | 8059.50 | 01-JUN-09:09 | 0.00 | 16319.67 | 22-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 34106.38 | 01-JUL-09:09 | 7048.42 | 01-JUL-05:10 | 8059.50 | 01-JUL-09:09 | 0.00 | 16552.50 | 01-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 34106.38 | 01-AUG-09:09 | 7048.42 | 01-AUG-05:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 15997.66 | 27-AUG-14:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 34106.38 | 01-SEP-09:09 | 7048.42 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 13612.84 | 14-SEP-16:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 34106.38 | 01-OCT-10:09 | 7048.42 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 10040.62 | 04-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 34106.38 | 01-NOV-09:09 | 7048.42 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 7495.43 | 09-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 34106.38 | 01-DEC-10:09 | 7048.42 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 7740.88 | 23-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 34106.38 | 7048.42 | 8059.50 | 0.00 | 7495.43 | 0.00 | 0.00 | |||||
Maximum of Months | 34106.38 | 7048.42 | 8059.50 | 0.00 | 16552.50 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 13773.93 | 12-JAN-15:09 | 0.00 | 0.00 | 0.00 | 11810.53 | 06-JAN-13:50 | 0.00 |
February | 24066.88 | 22-FEB-14:50 | 0.00 | 0.00 | 0.00 | 7550.58 | 17-FEB-15:20 | 0.00 |
March | 42499.25 | 28-MAR-14:00 | 0.00 | 0.00 | 0.00 | 7564.97 | 01-MAR-13:30 | 0.00 |
April | 62443.50 | 16-APR-14:00 | 0.00 | 0.00 | 0.00 | 9666.29 | 15-APR-12:39 | 0.00 |
May | 77835.36 | 03-MAY-14:00 | 0.00 | 0.00 | 0.00 | 9656.58 | 06-MAY-12:20 | 0.00 |
June | 87401.99 | 22-JUN-16:10 | 0.00 | 0.00 | 0.00 | 9641.84 | 17-JUN-12:20 | 0.00 |
July | 86245.33 | 01-JUL-14:00 | 0.00 | 0.00 | 0.00 | 7934.43 | 13-JUL-12:20 | 0.00 |
August | 81734.00 | 27-AUG-14:09 | 0.00 | 0.00 | 0.00 | 9623.85 | 09-AUG-14:50 | 0.00 |
September | 70140.54 | 14-SEP-16:10 | 0.00 | 0.00 | 0.00 | 7540.44 | 18-SEP-12:30 | 0.00 |
October | 55859.96 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 7278.58 | 01-OCT-15:20 | 0.00 |
November | 32887.48 | 09-NOV-13:39 | 0.00 | 0.00 | 0.00 | 9638.70 | 16-NOV-19:10 | 0.00 |
December | 17589.44 | 28-DEC-13:00 | 0.00 | 0.00 | 0.00 | 8959.77 | 02-DEC-10:50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13773.93 | 0.00 | 0.00 | 0.00 | 7278.58 | 0.00 | ||
Maximum of Months | 87401.99 | 0.00 | 0.00 | 0.00 | 11810.53 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 69417.89 | 12-JAN-15:20 | 34106.38 | 8059.50 | 0.00 | 0.00 | 7041.97 | 0.00 | 0.00 | 13714.15 | 0.00 |
February | 78721.08 | 22-FEB-14:00 | 34106.38 | 8059.50 | 0.00 | 0.00 | 7041.97 | 0.00 | 0.00 | 24066.86 | 0.00 |
March | 97902.46 | 28-MAR-15:50 | 34106.38 | 8059.50 | 0.00 | 0.00 | 7054.37 | 0.00 | 0.00 | 41947.28 | 0.00 |
April | 121905.82 | 16-APR-15:30 | 34106.38 | 8059.50 | 0.00 | 0.00 | 10714.23 | 0.00 | 0.00 | 61509.09 | 0.00 |
May | 137565.35 | 30-MAY-16:10 | 34106.38 | 8059.50 | 0.00 | 0.00 | 13330.38 | 0.00 | 0.00 | 74548.14 | 0.00 |
June | 150314.14 | 22-JUN-15:50 | 34106.38 | 8059.50 | 0.00 | 0.00 | 16126.71 | 0.00 | 0.00 | 86608.05 | 0.00 |
July | 149343.53 | 01-JUL-14:30 | 34106.38 | 8059.50 | 0.00 | 0.00 | 16505.27 | 0.00 | 0.00 | 86097.01 | 0.00 |
August | 143090.56 | 27-AUG-14:50 | 34106.38 | 8059.50 | 0.00 | 0.00 | 15988.71 | 0.00 | 0.00 | 81626.00 | 0.00 |
September | 129684.40 | 14-SEP-16:19 | 34106.38 | 8059.50 | 0.00 | 0.00 | 13595.17 | 0.00 | 0.00 | 70037.17 | 0.00 |
October | 112525.67 | 03-OCT-13:30 | 34106.38 | 8059.50 | 0.00 | 0.00 | 9837.07 | 0.00 | 0.00 | 55090.20 | 0.00 |
November | 88556.93 | 08-NOV-13:00 | 34106.38 | 8059.50 | 0.00 | 0.00 | 7041.97 | 0.00 | 0.00 | 31791.94 | 0.00 |
December | 73444.40 | 28-DEC-17:40 | 34106.38 | 8059.50 | 7048.42 | 0.00 | 7041.97 | 0.00 | 0.00 | 11756.13 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 69417.89 | 34106.38 | 8059.50 | 0.00 | 0.00 | 7041.97 | 0.00 | 0.00 | 11756.13 | 0.00 | |
Maximum of Months | 150314.14 | 34106.38 | 8059.50 | 7048.42 | 0.00 | 16505.27 | 0.00 | 0.00 | 86608.05 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 98898.98 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 22070.77 | 02-FEB-08:20 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 33398.29 | 23-DEC-08:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 98898.98 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.45 | 0.33 | 24.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.54 | 1.50 | 24.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.63 | 2.50 | 24.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.53 | 2.33 | 24.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.50 | 24.57 | 6.67 | 24.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.63 | 2.50 | 24.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.48 | 0.50 | 24.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.51 | 1.83 | 24.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.48 | 0.67 | 24.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.17 | 24.50 | 3.00 | 24.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.51 | 1.83 | 24.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.47 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.62 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.79 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.70 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.58 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 14.83 | 24.69 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.79 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.50 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.62 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.82 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.72 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.59 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 17.17 | 24.70 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.82 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.49 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.60 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.84 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.69 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.58 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 13.83 | 24.69 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.84 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.55 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.58 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.87 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.67 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.65 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.00 | 24.69 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.87 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.50 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.58 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.84 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.72 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.60 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.50 | 24.69 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.84 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.51 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.59 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.86 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.72 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.60 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.00 | 24.70 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.86 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.50 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.57 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.85 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.72 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.62 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.00 | 24.70 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.85 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.52 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.62 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.93 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.71 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.67 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.83 | 24.75 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.93 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 224.00 | 22.52 | 45.67 | 23.88 | 0.00 | 0.00 |
February | 90.00 | 22.74 | 162.50 | 23.89 | 0.00 | 0.00 |
March | 21.50 | 23.35 | 353.83 | 23.89 | 0.00 | 0.00 |
April | 1.67 | 23.75 | 445.17 | 23.89 | 0.00 | 0.00 |
May | 18.33 | 23.92 | 496.00 | 23.89 | 18.33 | 23.92 |
June | 104.50 | 23.90 | 480.00 | 23.89 | 104.50 | 23.90 |
July | 286.67 | 23.90 | 496.00 | 23.89 | 286.67 | 23.90 |
August | 332.33 | 23.89 | 496.00 | 23.89 | 332.33 | 23.89 |
September | 206.17 | 23.89 | 480.00 | 23.89 | 206.17 | 23.89 |
October | 3.67 | 23.90 | 485.67 | 23.89 | 3.67 | 23.90 |
November | 18.33 | 23.27 | 373.50 | 23.89 | 0.00 | 0.00 |
December | 142.50 | 22.75 | 120.00 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 1449.67 | 23.48 | 4434.33 | 23.89 | 951.67 | 23.90 |
Minimum of Months | 1.67 | 22.52 | 45.67 | 23.88 | 0.00 | 0.00 |
Maximum of Months | 332.33 | 23.92 | 496.00 | 23.89 | 332.33 | 23.92 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 132.17 | 22.71 | 56.33 | 23.87 | 0.00 | 0.00 |
February | 53.17 | 22.94 | 170.17 | 23.89 | 0.00 | 0.00 |
March | 13.33 | 23.54 | 349.00 | 23.89 | 0.00 | 0.00 |
April | 0.67 | 23.75 | 433.33 | 23.89 | 0.00 | 0.00 |
May | 10.00 | 23.91 | 496.00 | 23.89 | 10.00 | 23.91 |
June | 86.50 | 23.90 | 480.00 | 23.89 | 86.50 | 23.90 |
July | 251.50 | 23.89 | 496.00 | 23.89 | 251.50 | 23.89 |
August | 282.67 | 23.89 | 496.00 | 23.89 | 282.67 | 23.89 |
September | 171.17 | 23.89 | 480.00 | 23.89 | 171.17 | 23.89 |
October | 0.00 | 0.00 | 479.67 | 23.89 | 0.00 | 0.00 |
November | 12.33 | 23.41 | 355.00 | 23.89 | 0.00 | 0.00 |
December | 99.00 | 23.07 | 121.17 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 1112.50 | 23.62 | 4412.67 | 23.89 | 801.83 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 56.33 | 23.87 | 0.00 | 0.00 |
Maximum of Months | 282.67 | 23.91 | 496.00 | 23.89 | 282.67 | 23.91 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 143.17 | 22.50 | 33.67 | 23.91 | 0.00 | 0.00 |
February | 53.83 | 22.79 | 136.50 | 24.03 | 0.00 | 0.00 |
March | 10.17 | 23.84 | 293.67 | 24.08 | 0.67 | 28.32 |
April | 7.33 | 28.52 | 332.67 | 24.17 | 7.33 | 28.52 |
May | 27.00 | 26.77 | 375.00 | 24.20 | 27.00 | 26.77 |
June | 108.67 | 24.73 | 366.00 | 24.20 | 108.67 | 24.73 |
July | 254.33 | 24.29 | 369.00 | 24.18 | 254.33 | 24.29 |
August | 292.67 | 24.21 | 379.00 | 24.15 | 292.67 | 24.21 |
September | 191.00 | 24.30 | 360.00 | 24.14 | 191.00 | 24.30 |
October | 8.67 | 26.43 | 366.17 | 24.11 | 8.67 | 26.43 |
November | 9.50 | 23.25 | 290.17 | 24.02 | 0.00 | 0.00 |
December | 94.00 | 22.87 | 81.50 | 23.95 | 0.00 | 0.00 |
Annual Sum or Average | 1200.33 | 24.00 | 3383.33 | 24.13 | 890.33 | 24.45 |
Minimum of Months | 7.33 | 22.50 | 33.67 | 23.91 | 0.00 | 0.00 |
Maximum of Months | 292.67 | 28.52 | 379.00 | 24.20 | 292.67 | 28.52 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 159.00 | 22.50 | 24.83 | 23.92 | 0.00 | 0.00 |
February | 59.00 | 22.77 | 128.33 | 24.03 | 0.00 | 0.00 |
March | 10.83 | 23.80 | 291.50 | 24.08 | 0.67 | 28.32 |
April | 7.33 | 28.53 | 333.67 | 24.17 | 7.33 | 28.53 |
May | 27.17 | 26.78 | 375.00 | 24.20 | 27.17 | 26.78 |
June | 108.00 | 24.74 | 366.00 | 24.20 | 108.00 | 24.74 |
July | 250.67 | 24.30 | 369.00 | 24.18 | 250.67 | 24.30 |
August | 289.67 | 24.21 | 379.00 | 24.15 | 289.67 | 24.21 |
September | 189.00 | 24.30 | 360.00 | 24.15 | 189.00 | 24.30 |
October | 8.67 | 26.44 | 366.33 | 24.11 | 8.67 | 26.44 |
November | 10.67 | 23.25 | 286.17 | 24.02 | 0.00 | 0.00 |
December | 98.67 | 22.82 | 70.83 | 23.94 | 0.00 | 0.00 |
Annual Sum or Average | 1218.67 | 23.97 | 3350.67 | 24.13 | 881.17 | 24.46 |
Minimum of Months | 7.33 | 22.50 | 24.83 | 23.92 | 0.00 | 0.00 |
Maximum of Months | 289.67 | 28.53 | 379.00 | 24.20 | 289.67 | 28.53 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 188.00 | 22.53 | 13.50 | 23.97 | 0.00 | 0.00 |
February | 68.33 | 22.74 | 110.83 | 24.02 | 0.00 | 0.00 |
March | 13.33 | 23.70 | 281.67 | 24.08 | 0.67 | 28.27 |
April | 6.50 | 28.56 | 330.67 | 24.17 | 6.50 | 28.56 |
May | 27.67 | 26.67 | 375.00 | 24.19 | 27.67 | 26.67 |
June | 110.00 | 24.72 | 366.00 | 24.20 | 110.00 | 24.72 |
July | 256.00 | 24.28 | 369.00 | 24.18 | 256.00 | 24.28 |
August | 294.17 | 24.20 | 379.00 | 24.14 | 294.17 | 24.20 |
September | 192.17 | 24.29 | 360.00 | 24.14 | 192.17 | 24.29 |
October | 8.50 | 26.33 | 365.83 | 24.11 | 8.50 | 26.33 |
November | 13.17 | 23.23 | 271.67 | 24.02 | 0.00 | 0.00 |
December | 107.33 | 22.75 | 54.50 | 23.94 | 0.00 | 0.00 |
Annual Sum or Average | 1285.17 | 23.91 | 3277.67 | 24.13 | 895.67 | 24.44 |
Minimum of Months | 6.50 | 22.53 | 13.50 | 23.94 | 0.00 | 0.00 |
Maximum of Months | 294.17 | 28.56 | 379.00 | 24.20 | 294.17 | 28.56 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 268.50 | 22.74 | 6.67 | 23.94 | 0.00 | 0.00 |
February | 74.67 | 22.83 | 56.50 | 23.96 | 0.00 | 0.00 |
March | 13.00 | 23.59 | 220.00 | 23.96 | 0.50 | 28.25 |
April | 3.50 | 28.82 | 288.83 | 24.01 | 3.50 | 28.82 |
May | 20.67 | 25.42 | 344.00 | 24.00 | 20.67 | 25.42 |
June | 106.83 | 24.16 | 336.00 | 23.99 | 106.83 | 24.16 |
July | 261.00 | 24.05 | 338.00 | 24.02 | 261.00 | 24.05 |
August | 296.50 | 23.98 | 348.00 | 23.97 | 296.50 | 23.98 |
September | 182.50 | 24.06 | 330.00 | 23.99 | 182.50 | 24.06 |
October | 6.50 | 25.83 | 335.00 | 23.98 | 6.50 | 25.83 |
November | 9.17 | 23.31 | 218.17 | 23.95 | 0.00 | 0.00 |
December | 128.33 | 22.84 | 18.50 | 23.90 | 0.00 | 0.00 |
Annual Sum or Average | 1371.17 | 23.64 | 2839.67 | 23.99 | 878.00 | 24.11 |
Minimum of Months | 3.50 | 22.74 | 6.67 | 23.90 | 0.00 | 0.00 |
Maximum of Months | 296.50 | 28.82 | 348.00 | 24.02 | 296.50 | 28.82 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 287.00 | 22.76 | 0.50 | 24.42 | 0.00 | 0.00 |
February | 86.33 | 22.93 | 43.33 | 23.97 | 0.00 | 0.00 |
March | 15.50 | 23.62 | 194.17 | 23.97 | 0.50 | 28.13 |
April | 3.33 | 28.78 | 269.33 | 24.01 | 3.33 | 28.78 |
May | 20.00 | 25.26 | 344.00 | 24.00 | 20.00 | 25.26 |
June | 107.67 | 24.14 | 336.00 | 23.99 | 107.67 | 24.14 |
July | 263.67 | 24.05 | 338.00 | 24.02 | 263.67 | 24.05 |
August | 300.67 | 23.98 | 348.00 | 23.97 | 300.67 | 23.98 |
September | 183.00 | 24.05 | 330.00 | 23.99 | 183.00 | 24.05 |
October | 6.67 | 25.46 | 331.33 | 23.98 | 6.67 | 25.46 |
November | 11.50 | 23.40 | 195.00 | 23.95 | 0.00 | 0.00 |
December | 140.67 | 22.89 | 9.00 | 23.91 | 0.00 | 0.00 |
Annual Sum or Average | 1426.00 | 23.62 | 2738.67 | 23.99 | 885.50 | 24.10 |
Minimum of Months | 3.33 | 22.76 | 0.50 | 23.91 | 0.00 | 0.00 |
Maximum of Months | 300.67 | 28.78 | 348.00 | 24.42 | 300.67 | 28.78 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 290.33 | 22.72 | 0.33 | 24.40 | 0.00 | 0.00 |
February | 93.00 | 22.94 | 39.33 | 23.97 | 0.00 | 0.00 |
March | 16.83 | 23.60 | 190.67 | 23.97 | 0.50 | 28.11 |
April | 3.33 | 28.53 | 265.83 | 24.01 | 3.17 | 28.77 |
May | 20.17 | 25.25 | 344.00 | 24.00 | 20.17 | 25.25 |
June | 108.50 | 24.14 | 336.00 | 23.99 | 108.50 | 24.14 |
July | 265.17 | 24.05 | 338.00 | 24.02 | 265.17 | 24.05 |
August | 301.83 | 23.98 | 348.00 | 23.97 | 301.83 | 23.98 |
September | 184.00 | 24.05 | 330.00 | 23.99 | 184.00 | 24.05 |
October | 6.67 | 25.46 | 330.67 | 23.98 | 6.67 | 25.46 |
November | 12.50 | 23.41 | 189.50 | 23.95 | 0.00 | 0.00 |
December | 146.83 | 22.88 | 5.83 | 23.91 | 0.00 | 0.00 |
Annual Sum or Average | 1449.17 | 23.61 | 2718.17 | 23.99 | 890.00 | 24.09 |
Minimum of Months | 3.33 | 22.72 | 0.33 | 23.91 | 0.00 | 0.00 |
Maximum of Months | 301.83 | 28.53 | 348.00 | 24.40 | 301.83 | 28.77 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 298.00 | 22.66 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 105.33 | 22.91 | 36.33 | 23.96 | 0.00 | 0.00 |
March | 20.00 | 23.52 | 187.33 | 23.97 | 0.50 | 28.09 |
April | 3.50 | 28.53 | 266.67 | 24.01 | 3.33 | 28.76 |
May | 20.50 | 25.27 | 344.00 | 24.00 | 20.50 | 25.27 |
June | 107.50 | 24.14 | 336.00 | 23.99 | 107.50 | 24.14 |
July | 263.33 | 24.05 | 338.00 | 24.02 | 263.33 | 24.05 |
August | 298.83 | 23.98 | 348.00 | 23.97 | 298.83 | 23.98 |
September | 183.00 | 24.05 | 330.00 | 23.99 | 183.00 | 24.05 |
October | 6.67 | 25.46 | 330.83 | 23.98 | 6.67 | 25.46 |
November | 14.67 | 23.37 | 184.50 | 23.95 | 0.00 | 0.00 |
December | 158.33 | 22.84 | 3.83 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 1479.67 | 23.57 | 2705.50 | 23.99 | 883.67 | 24.10 |
Minimum of Months | 3.50 | 22.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 298.83 | 28.53 | 348.00 | 24.02 | 298.83 | 28.76 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 301.17 | 22.60 | 1.17 | 21.11 | 1.17 | 21.11 |
February | 117.00 | 22.82 | 36.83 | 23.96 | 0.00 | 0.00 |
March | 27.33 | 23.37 | 195.50 | 23.97 | 0.67 | 28.14 |
April | 4.33 | 28.41 | 292.33 | 24.01 | 4.00 | 28.79 |
May | 20.67 | 25.47 | 344.00 | 24.01 | 20.67 | 25.47 |
June | 94.33 | 24.21 | 336.00 | 23.99 | 94.33 | 24.21 |
July | 235.67 | 24.08 | 338.00 | 24.02 | 235.67 | 24.08 |
August | 260.00 | 24.00 | 348.00 | 23.97 | 260.00 | 24.00 |
September | 168.00 | 24.09 | 330.00 | 23.99 | 168.00 | 24.09 |
October | 7.50 | 25.99 | 333.00 | 23.99 | 7.50 | 25.99 |
November | 18.00 | 23.29 | 206.33 | 23.95 | 0.00 | 0.00 |
December | 166.67 | 22.76 | 3.33 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 1420.67 | 23.52 | 2764.50 | 23.99 | 792.00 | 24.15 |
Minimum of Months | 4.33 | 22.60 | 1.17 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 301.17 | 28.41 | 348.00 | 24.02 | 260.00 | 28.79 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.24728 | 39.38960 | 0.21312 | 6.95474 |
February | 448.00000 | 23.64539 | 40.88150 | 0.35189 | 8.08874 |
March | 496.00000 | 23.86517 | 41.41800 | 0.46028 | 9.58822 |
April | 480.00000 | 23.89937 | 41.57903 | 0.53337 | 11.08042 |
May | 496.00000 | 23.91264 | 50.44557 | -0.1801 | 5.82152 |
June | 480.00000 | 23.91488 | 56.57033 | -0.1177 | 5.45001 |
July | 496.00000 | 23.91773 | 62.89050 | -0.0820 | 5.29295 |
August | 496.00000 | 23.91667 | 64.36168 | -0.0839 | 5.29932 |
September | 480.00000 | 23.90906 | 61.35419 | -0.1289 | 5.47093 |
October | 496.00000 | 23.89998 | 47.54003 | 0.57477 | 12.02010 |
November | 480.00000 | 23.86377 | 41.16432 | 0.46358 | 9.62501 |
December | 496.00000 | 23.55062 | 38.24315 | 0.30400 | 7.58907 |
Annual Sum or Average | 5840.00000 | 23.79533 | 48.87031 | 0.19111 | 7.68444 |
Minimum of Months | 448.00000 | 23.24728 | 38.24315 | -0.1801 | 5.29295 |
Maximum of Months | 496.00000 | 23.91773 | 64.36168 | 0.57477 | 12.02010 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.54407 | 38.47881 | 0.28355 | 7.31079 |
February | 448.00000 | 23.76332 | 39.60250 | 0.37884 | 8.27938 |
March | 496.00000 | 23.88313 | 40.51406 | 0.45797 | 9.48781 |
April | 480.00000 | 23.90114 | 41.14262 | 0.51480 | 10.64206 |
May | 496.00000 | 23.91282 | 49.64072 | -0.2218 | 6.14398 |
June | 480.00000 | 23.91377 | 55.60785 | -0.1673 | 5.71802 |
July | 496.00000 | 23.91560 | 61.75955 | -0.1310 | 5.49083 |
August | 496.00000 | 23.91464 | 63.24089 | -0.1326 | 5.50898 |
September | 480.00000 | 23.90817 | 59.89149 | -0.1748 | 5.75952 |
October | 496.00000 | 23.90097 | 46.31620 | 0.54851 | 11.38990 |
November | 480.00000 | 23.87955 | 40.03447 | 0.45445 | 9.40796 |
December | 496.00000 | 23.71831 | 37.21180 | 0.34094 | 7.79091 |
Annual Sum or Average | 5840.00000 | 23.84638 | 47.83887 | 0.17790 | 7.73827 |
Minimum of Months | 448.00000 | 23.54407 | 37.21180 | -0.2218 | 5.49083 |
Maximum of Months | 496.00000 | 23.91560 | 63.24089 | 0.54851 | 11.38990 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.31858 | 38.25619 | 0.22714 | 7.04388 |
February | 336.00000 | 23.73679 | 39.73870 | 0.36972 | 8.32896 |
March | 379.00000 | 23.99724 | 40.46502 | 0.48096 | 10.05891 |
April | 360.00000 | 24.09327 | 40.74393 | 0.55410 | 11.80566 |
May | 375.00000 | 24.12928 | 50.05447 | -0.1504 | 6.32069 |
June | 366.00000 | 24.13197 | 56.39232 | -0.0928 | 6.09161 |
July | 369.00000 | 24.11796 | 63.45275 | -0.0556 | 5.94013 |
August | 379.00000 | 24.08813 | 65.32308 | -0.0635 | 5.77948 |
September | 360.00000 | 24.08834 | 61.92937 | -0.1050 | 5.88708 |
October | 371.00000 | 24.05963 | 47.08144 | 0.59241 | 12.62235 |
November | 360.00000 | 23.95355 | 40.07846 | 0.47395 | 9.85489 |
December | 369.00000 | 23.62017 | 36.82801 | 0.31532 | 7.63564 |
Annual Sum or Average | 4395.00000 | 23.94586 | 48.44378 | 0.21031 | 8.10554 |
Minimum of Months | 336.00000 | 23.31858 | 36.82801 | -0.1504 | 5.77948 |
Maximum of Months | 379.00000 | 24.13197 | 65.32308 | 0.59241 | 12.62235 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.25806 | 38.45800 | 0.20638 | 6.93307 |
February | 336.00000 | 23.71656 | 39.83778 | 0.36139 | 8.24344 |
March | 379.00000 | 23.99507 | 40.47983 | 0.47961 | 10.03486 |
April | 360.00000 | 24.09344 | 40.72415 | 0.55533 | 11.83624 |
May | 375.00000 | 24.12992 | 49.99853 | -0.1468 | 6.30701 |
June | 366.00000 | 24.13256 | 56.31522 | -0.0895 | 6.08840 |
July | 369.00000 | 24.11856 | 63.33869 | -0.0524 | 5.94342 |
August | 379.00000 | 24.08853 | 65.23135 | -0.0613 | 5.78012 |
September | 360.00000 | 24.08866 | 61.85220 | -0.1031 | 5.88393 |
October | 371.00000 | 24.05969 | 47.05255 | 0.59332 | 12.64615 |
November | 360.00000 | 23.94964 | 40.10791 | 0.47161 | 9.81471 |
December | 369.00000 | 23.59122 | 36.94074 | 0.30428 | 7.54489 |
Annual Sum or Average | 4395.00000 | 23.93650 | 48.44248 | 0.20804 | 8.07982 |
Minimum of Months | 336.00000 | 23.25806 | 36.94074 | -0.1468 | 5.78012 |
Maximum of Months | 379.00000 | 24.13256 | 65.23135 | 0.59332 | 12.64615 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.16116 | 38.77273 | 0.17541 | 6.75016 |
February | 336.00000 | 23.67547 | 40.06618 | 0.34533 | 8.06755 |
March | 379.00000 | 23.98624 | 40.61541 | 0.47245 | 9.89739 |
April | 360.00000 | 24.09042 | 40.79220 | 0.55063 | 11.71921 |
May | 375.00000 | 24.12726 | 50.10550 | -0.1515 | 6.31308 |
June | 366.00000 | 24.12993 | 56.46556 | -0.0938 | 6.07843 |
July | 369.00000 | 24.11605 | 63.52282 | -0.0557 | 5.92914 |
August | 379.00000 | 24.08580 | 65.45793 | -0.0651 | 5.76819 |
September | 360.00000 | 24.08567 | 62.08931 | -0.1074 | 5.88107 |
October | 371.00000 | 24.05657 | 47.20145 | 0.58947 | 12.54322 |
November | 360.00000 | 23.93924 | 40.24386 | 0.46443 | 9.68208 |
December | 369.00000 | 23.53999 | 37.15113 | 0.28586 | 7.39675 |
Annual Sum or Average | 4395.00000 | 23.91761 | 48.62121 | 0.19903 | 7.99472 |
Minimum of Months | 336.00000 | 23.16116 | 37.15113 | -0.1515 | 5.76819 |
Maximum of Months | 379.00000 | 24.12993 | 65.45793 | 0.58947 | 12.54322 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.96130 | 40.13750 | 0.11031 | 6.26006 |
February | 308.00000 | 23.61439 | 40.95374 | 0.31328 | 7.57871 |
March | 348.00000 | 23.90270 | 41.31099 | 0.44407 | 9.30143 |
April | 330.00000 | 23.97015 | 41.52251 | 0.52345 | 10.98730 |
May | 344.00000 | 23.98061 | 51.25134 | -0.1901 | 6.20287 |
June | 336.00000 | 23.96677 | 57.78641 | -0.1348 | 5.78400 |
July | 338.00000 | 23.99018 | 64.91795 | -0.0877 | 5.71040 |
August | 348.00000 | 23.95107 | 66.99134 | -0.1006 | 5.55807 |
September | 330.00000 | 23.96531 | 63.46737 | -0.1419 | 5.78288 |
October | 340.00000 | 23.96152 | 47.98311 | 0.56859 | 11.94788 |
November | 330.00000 | 23.89781 | 40.76455 | 0.44437 | 9.25103 |
December | 338.00000 | 23.46194 | 38.38689 | 0.25188 | 7.04038 |
Annual Sum or Average | 4030.00000 | 23.80299 | 49.70885 | 0.16481 | 7.61043 |
Minimum of Months | 308.00000 | 22.96130 | 38.38689 | -0.1901 | 5.55807 |
Maximum of Months | 348.00000 | 23.99018 | 66.99134 | 0.56859 | 11.94788 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.91648 | 40.19458 | 0.08830 | 6.16972 |
February | 308.00000 | 23.60256 | 40.99783 | 0.29685 | 7.38210 |
March | 348.00000 | 23.90173 | 41.35134 | 0.42716 | 8.98532 |
April | 330.00000 | 23.96937 | 41.51015 | 0.50163 | 10.50837 |
May | 344.00000 | 23.97993 | 51.29170 | -0.2240 | 6.48580 |
June | 336.00000 | 23.96602 | 57.92011 | -0.1693 | 5.99375 |
July | 338.00000 | 23.98928 | 65.20500 | -0.1199 | 5.83756 |
August | 348.00000 | 23.95041 | 67.35073 | -0.1312 | 5.69928 |
September | 330.00000 | 23.96419 | 63.75981 | -0.1713 | 5.96566 |
October | 340.00000 | 23.96112 | 48.08852 | 0.54818 | 11.46168 |
November | 330.00000 | 23.89741 | 40.81688 | 0.42784 | 8.94270 |
December | 338.00000 | 23.44674 | 38.41480 | 0.23599 | 6.90316 |
Annual Sum or Average | 4030.00000 | 23.79647 | 49.82867 | 0.14052 | 7.52295 |
Minimum of Months | 308.00000 | 22.91648 | 38.41480 | -0.2240 | 5.69928 |
Maximum of Months | 348.00000 | 23.98928 | 67.35073 | 0.54818 | 11.46168 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.87633 | 40.30283 | 0.07577 | 6.13573 |
February | 308.00000 | 23.58545 | 41.07913 | 0.28958 | 7.31980 |
March | 348.00000 | 23.89904 | 41.39050 | 0.42386 | 8.93058 |
April | 330.00000 | 23.96904 | 41.52573 | 0.49938 | 10.46018 |
May | 344.00000 | 23.97974 | 51.32352 | -0.2266 | 6.50837 |
June | 336.00000 | 23.96583 | 57.96903 | -0.1718 | 6.00938 |
July | 338.00000 | 23.98901 | 65.26968 | -0.1220 | 5.84547 |
August | 348.00000 | 23.95021 | 67.42307 | -0.1332 | 5.70839 |
September | 330.00000 | 23.96390 | 63.82941 | -0.1734 | 5.97847 |
October | 340.00000 | 23.96078 | 48.12595 | 0.54636 | 11.41877 |
November | 330.00000 | 23.89528 | 40.85225 | 0.42500 | 8.89449 |
December | 338.00000 | 23.42386 | 38.49381 | 0.22783 | 6.85462 |
Annual Sum or Average | 4030.00000 | 23.78930 | 49.88552 | 0.13642 | 7.50074 |
Minimum of Months | 308.00000 | 22.87633 | 38.49381 | -0.2266 | 5.70839 |
Maximum of Months | 348.00000 | 23.98901 | 67.42307 | 0.54636 | 11.41877 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.79613 | 40.51959 | 0.05315 | 6.10646 |
February | 308.00000 | 23.54001 | 41.28359 | 0.27436 | 7.22033 |
March | 348.00000 | 23.88995 | 41.50191 | 0.41908 | 8.86684 |
April | 330.00000 | 23.96882 | 41.55352 | 0.50040 | 10.48427 |
May | 344.00000 | 23.97981 | 51.32582 | -0.2221 | 6.46874 |
June | 336.00000 | 23.96592 | 57.94512 | -0.1667 | 5.97638 |
July | 338.00000 | 23.98924 | 65.19120 | -0.1166 | 5.82451 |
August | 348.00000 | 23.95035 | 67.33043 | -0.1280 | 5.68361 |
September | 330.00000 | 23.96404 | 63.78319 | -0.1688 | 5.94870 |
October | 340.00000 | 23.96063 | 48.15395 | 0.54837 | 11.46740 |
November | 330.00000 | 23.88888 | 40.93819 | 0.42226 | 8.85916 |
December | 338.00000 | 23.36714 | 38.68084 | 0.21116 | 6.77980 |
Annual Sum or Average | 4030.00000 | 23.77302 | 49.93626 | 0.13365 | 7.46960 |
Minimum of Months | 308.00000 | 22.79613 | 38.68084 | -0.2221 | 5.68361 |
Maximum of Months | 348.00000 | 23.98924 | 67.33043 | 0.54837 | 11.46740 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.73416 | 40.69745 | 0.03037 | 6.17734 |
February | 308.00000 | 23.46543 | 41.55037 | 0.25398 | 7.20984 |
March | 348.00000 | 23.86522 | 41.67135 | 0.42302 | 9.04285 |
April | 330.00000 | 23.97256 | 41.45169 | 0.53515 | 11.28320 |
May | 344.00000 | 23.98375 | 50.89210 | -0.1567 | 6.01158 |
June | 336.00000 | 23.96956 | 57.15871 | -0.1013 | 5.67233 |
July | 338.00000 | 23.99556 | 63.90280 | -0.0551 | 5.71096 |
August | 348.00000 | 23.95570 | 65.74765 | -0.0688 | 5.51956 |
September | 330.00000 | 23.97038 | 62.50602 | -0.1133 | 5.70116 |
October | 340.00000 | 23.96596 | 47.74173 | 0.58394 | 12.35904 |
November | 330.00000 | 23.87826 | 40.95113 | 0.43570 | 9.16460 |
December | 338.00000 | 23.29944 | 38.82314 | 0.19289 | 6.79941 |
Annual Sum or Average | 4030.00000 | 23.75632 | 49.50425 | 0.16178 | 7.54895 |
Minimum of Months | 308.00000 | 22.73416 | 38.82314 | -0.1567 | 5.51956 |
Maximum of Months | 348.00000 | 23.99556 | 65.74765 | 0.58394 | 12.35904 |
Report: DXReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.266016E+10 | 0.728633E+09 | 224.33 | 0.240801E+10 | 0.252140E+09 | 0.00 | 0.44 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 9743.82 | 12-JAN-15:00 | 9317.70 | 12-JAN-15:00 | 1516.59 | 13-JAN-15:00 | 2615.07 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.839323E+10 | 0.225347E+10 | 338.14 | 0.738936E+10 | 0.100387E+10 | 0.00 | 0.67 | 22-FEB-15:00 | 0.00 | 01-FEB-00:05 | 15940.32 | 22-FEB-15:00 | 14881.57 | 22-FEB-15:00 | 4071.26 | 25-FEB-18:05 | 4252.89 | 22-FEB-15:00 | 0.00 | 01-FEB-00:05 |
March | 0.203461E+11 | 0.547114E+10 | 470.95 | 0.178249E+11 | 0.252120E+10 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 | 56760.97 | 11-MAR-08:62 | 45283.28 | 30-MAR-07:02 | 11981.82 | 11-MAR-08:62 | 12765.49 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.328961E+11 | 0.933215E+10 | 483.15 | 0.298566E+11 | 0.303951E+10 | 0.00 | 1.00 | 02-APR-07:02 | 0.00 | 01-APR-00:05 | 57162.15 | 26-APR-07:02 | 53254.02 | 08-APR-07:02 | 13379.28 | 26-APR-07:02 | 13824.84 | 27-APR-07:01 | 0.00 | 01-APR-00:05 |
May | 0.480699E+11 | 0.137495E+11 | 502.67 | 0.390797E+11 | 0.899023E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 60607.00 | 24-MAY-07:01 | 53725.84 | 06-MAY-07:01 | 25850.27 | 24-MAY-07:03 | 14565.87 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.546933E+11 | 0.150751E+11 | 488.43 | 0.394534E+11 | 0.152398E+11 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 61710.16 | 26-JUN-07:01 | 51696.74 | 07-JUN-07:01 | 29702.49 | 26-JUN-07:13 | 15038.21 | 10-JUN-16:20 | 0.00 | 01-JUN-00:10 |
July | 0.623264E+11 | 0.157690E+11 | 504.52 | 0.375673E+11 | 0.247591E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 62443.96 | 25-JUL-07:01 | 45125.37 | 07-JUL-07:01 | 31910.94 | 25-JUL-07:13 | 14755.46 | 01-JUL-16:10 | 0.00 | 01-JUL-00:03 |
August | 0.616763E+11 | 0.150554E+11 | 503.21 | 0.348947E+11 | 0.267816E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 62124.13 | 10-AUG-07:01 | 40747.95 | 03-AUG-07:01 | 30057.16 | 10-AUG-07:06 | 14021.99 | 08-AUG-07:13 | 0.00 | 01-AUG-00:10 |
September | 0.510516E+11 | 0.125768E+11 | 488.64 | 0.310073E+11 | 0.200443E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 61498.97 | 03-SEP-07:01 | 43362.01 | 26-SEP-07:01 | 28842.40 | 03-SEP-07:13 | 13652.67 | 22-SEP-07:01 | 0.00 | 01-SEP-00:10 |
October | 0.326817E+11 | 0.853227E+10 | 496.25 | 0.262009E+11 | 0.648074E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:03 | 59220.56 | 12-OCT-07:02 | 47722.41 | 23-OCT-07:02 | 21443.68 | 12-OCT-07:02 | 13223.66 | 04-OCT-07:01 | 0.00 | 01-OCT-00:03 |
November | 0.173593E+11 | 0.459009E+10 | 450.36 | 0.151383E+11 | 0.222106E+10 | 0.00 | 0.84 | 08-NOV-15:00 | 0.00 | 01-NOV-00:10 | 41216.48 | 09-NOV-08:62 | 30462.32 | 09-NOV-08:62 | 10754.16 | 09-NOV-08:62 | 8894.07 | 09-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.529295E+10 | 0.143416E+10 | 323.33 | 0.465873E+10 | 0.634224E+09 | 0.00 | 0.53 | 28-DEC-15:00 | 0.00 | 01-DEC-00:10 | 12339.84 | 28-DEC-15:00 | 11416.23 | 03-DEC-14:00 | 1698.81 | 16-DEC-14:00 | 3268.49 | 28-DEC-15:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.397447E+12 | 0.104568E+12 | 5273.99 | 0.285479E+12 | 0.111968E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.266016E+10 | 0.728633E+09 | 224.33 | 0.240801E+10 | 0.252140E+09 | 0.00 | 0.44 | 0.00 | 9743.82 | 9317.70 | 1516.59 | 2615.07 | 0.00 | |||||||
Maximum of Months | 0.623264E+11 | 0.157690E+11 | 504.52 | 0.394534E+11 | 0.267816E+11 | 0.00 | 1.00 | 0.00 | 62443.96 | 53725.84 | 31910.94 | 15038.21 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.272248E+10 | 0.746300E+09 | 357.97 | 0.247428E+10 | 0.248198E+09 | 0.00 | 0.47 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 5518.28 | 12-JAN-15:00 | 5299.38 | 12-JAN-15:00 | 1297.10 | 15-JAN-18:10 | 1440.83 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.556966E+10 | 0.148042E+10 | 390.31 | 0.497632E+10 | 0.593342E+09 | 0.00 | 0.79 | 25-FEB-08:63 | 0.00 | 01-FEB-00:05 | 10535.48 | 25-FEB-08:63 | 8407.07 | 25-FEB-08:63 | 2193.58 | 25-FEB-18:05 | 2404.86 | 25-FEB-08:63 | 0.00 | 01-FEB-00:05 |
March | 0.111569E+11 | 0.296798E+10 | 482.20 | 0.995762E+10 | 0.119926E+10 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 | 29147.75 | 30-MAR-07:02 | 24715.61 | 11-MAR-08:62 | 4510.46 | 30-MAR-07:02 | 6467.58 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.166038E+11 | 0.469327E+10 | 484.17 | 0.152497E+11 | 0.135412E+10 | 0.00 | 1.00 | 02-APR-07:02 | 0.00 | 01-APR-00:05 | 29263.29 | 03-APR-07:02 | 27803.03 | 08-APR-07:02 | 4981.10 | 26-APR-07:02 | 7017.95 | 27-APR-07:01 | 0.00 | 01-APR-00:05 |
May | 0.237649E+11 | 0.678638E+10 | 502.81 | 0.195837E+11 | 0.418116E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 30784.67 | 24-MAY-07:01 | 27907.20 | 06-MAY-07:01 | 10544.59 | 24-MAY-07:03 | 7427.32 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.267784E+11 | 0.736374E+10 | 488.29 | 0.195987E+11 | 0.717965E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 31146.05 | 26-JUN-07:01 | 27107.34 | 07-JUN-07:01 | 12529.02 | 28-JUN-12:50 | 7598.36 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.303753E+11 | 0.766823E+10 | 504.52 | 0.186863E+11 | 0.116890E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 31490.62 | 25-JUL-07:01 | 24443.73 | 07-JUL-07:01 | 13241.10 | 25-JUL-07:04 | 7450.13 | 05-JUL-07:01 | 0.00 | 01-JUL-00:03 |
August | 0.300944E+11 | 0.733138E+10 | 503.30 | 0.174163E+11 | 0.126781E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 31422.63 | 10-AUG-07:01 | 22691.77 | 03-AUG-07:01 | 13131.48 | 10-AUG-07:13 | 7147.93 | 08-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.249144E+11 | 0.613790E+10 | 488.79 | 0.155505E+11 | 0.936390E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 31088.19 | 03-SEP-07:01 | 24118.03 | 26-SEP-07:01 | 11671.73 | 03-SEP-07:04 | 6936.36 | 22-SEP-07:01 | 0.00 | 01-SEP-00:10 |
October | 0.165841E+11 | 0.431303E+10 | 497.37 | 0.136077E+11 | 0.297639E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:03 | 30059.45 | 12-OCT-07:02 | 25750.91 | 16-OCT-07:02 | 7925.31 | 12-OCT-07:02 | 6696.22 | 04-OCT-07:01 | 0.00 | 01-OCT-00:03 |
November | 0.981406E+10 | 0.256880E+10 | 464.61 | 0.872483E+10 | 0.108923E+10 | 0.00 | 0.88 | 11-NOV-08:63 | 0.00 | 01-NOV-00:10 | 21623.17 | 09-NOV-08:62 | 17872.74 | 09-NOV-08:62 | 3750.43 | 09-NOV-08:62 | 4599.21 | 09-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.428481E+10 | 0.115532E+10 | 409.22 | 0.382367E+10 | 0.461142E+09 | 0.00 | 0.55 | 28-DEC-14:40 | 0.00 | 01-DEC-01:05 | 6700.89 | 28-DEC-14:50 | 6405.69 | 03-DEC-14:00 | 1091.14 | 10-DEC-18:05 | 1733.81 | 28-DEC-14:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.202663E+12 | 0.532127E+11 | 5573.56 | 0.149650E+12 | 0.530135E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.272248E+10 | 0.746300E+09 | 357.97 | 0.247428E+10 | 0.248198E+09 | 0.00 | 0.47 | 0.00 | 5518.28 | 5299.38 | 1091.14 | 1440.83 | 0.00 | |||||||
Maximum of Months | 0.303753E+11 | 0.766823E+10 | 504.52 | 0.195987E+11 | 0.126781E+11 | 0.00 | 1.00 | 0.00 | 31490.62 | 27907.20 | 13241.10 | 7598.36 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.127239E+10 | 0.341336E+09 | 188.25 | 0.117240E+10 | 99989036.61 | 0.00 | 0.44 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 5094.41 | 12-JAN-15:00 | 4898.21 | 12-JAN-15:00 | 801.84 | 14-JAN-14:00 | 1341.77 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.365745E+10 | 0.961783E+09 | 248.81 | 0.327864E+10 | 0.378812E+09 | 0.00 | 0.80 | 25-FEB-07:03 | 0.00 | 01-FEB-00:05 | 10944.12 | 25-FEB-07:03 | 7795.45 | 25-FEB-07:03 | 3148.67 | 25-FEB-07:03 | 2480.26 | 25-FEB-07:03 | 0.00 | 01-FEB-00:05 |
March | 0.852284E+10 | 0.224992E+10 | 348.42 | 0.758649E+10 | 0.936345E+09 | 0.00 | 1.00 | 11-MAR-07:02 | 0.00 | 01-MAR-00:05 | 30024.79 | 11-MAR-07:02 | 24316.51 | 29-MAR-06:02 | 8266.49 | 11-MAR-07:02 | 6520.65 | 11-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.132968E+11 | 0.370636E+10 | 356.09 | 0.121549E+11 | 0.114194E+10 | 0.00 | 1.00 | 02-APR-07:02 | 0.00 | 01-APR-00:05 | 30104.78 | 17-APR-06:01 | 28074.12 | 20-APR-06:01 | 7809.02 | 17-APR-06:02 | 7056.12 | 27-APR-06:01 | 0.00 | 01-APR-00:05 |
May | 0.197200E+11 | 0.556544E+10 | 377.78 | 0.161078E+11 | 0.361213E+10 | 0.00 | 1.00 | 01-MAY-06:01 | 0.00 | 01-MAY-00:10 | 31748.45 | 23-MAY-06:01 | 27932.08 | 28-MAY-07:01 | 14475.74 | 23-MAY-06:04 | 7250.12 | 04-MAY-06:01 | 0.00 | 01-MAY-00:10 |
June | 0.223076E+11 | 0.603918E+10 | 368.92 | 0.160680E+11 | 0.623969E+10 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 32704.99 | 26-JUN-06:01 | 26472.11 | 07-JUN-06:01 | 19226.41 | 26-JUN-06:05 | 7484.62 | 12-JUN-06:01 | 0.00 | 01-JUN-00:10 |
July | 0.249171E+11 | 0.616953E+10 | 371.20 | 0.148712E+11 | 0.100459E+11 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:03 | 32733.58 | 23-JUL-07:01 | 21710.15 | 07-JUL-06:01 | 19296.56 | 24-JUL-06:06 | 7409.40 | 02-JUL-07:14 | 0.00 | 01-JUL-00:03 |
August | 0.252486E+11 | 0.604667E+10 | 379.75 | 0.141591E+11 | 0.110895E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 32804.82 | 21-AUG-06:01 | 19164.73 | 03-AUG-06:01 | 20171.71 | 21-AUG-06:04 | 7104.16 | 08-AUG-06:12 | 0.00 | 01-AUG-00:10 |
September | 0.204100E+11 | 0.492930E+10 | 359.78 | 0.123526E+11 | 0.805741E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:10 | 32812.95 | 10-SEP-07:01 | 21263.95 | 27-SEP-06:01 | 20269.23 | 11-SEP-06:05 | 6885.82 | 22-SEP-06:01 | 0.00 | 01-SEP-00:10 |
October | 0.132065E+11 | 0.339348E+10 | 364.89 | 0.107228E+11 | 0.248362E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:03 | 30923.96 | 12-OCT-06:02 | 25748.01 | 23-OCT-06:02 | 12040.83 | 13-OCT-06:02 | 6687.52 | 04-OCT-06:01 | 0.00 | 01-OCT-00:03 |
November | 0.736228E+10 | 0.191308E+10 | 323.46 | 0.657571E+10 | 0.786571E+09 | 0.00 | 0.91 | 11-NOV-08:63 | 0.00 | 01-NOV-00:10 | 23769.16 | 09-NOV-07:03 | 17139.88 | 09-NOV-07:03 | 6629.28 | 09-NOV-07:03 | 5031.19 | 09-NOV-07:03 | 0.00 | 01-NOV-00:10 |
December | 0.248364E+10 | 0.659237E+09 | 249.25 | 0.223285E+10 | 0.250790E+09 | 0.00 | 0.53 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 6291.37 | 28-DEC-14:00 | 6057.14 | 02-DEC-14:00 | 900.51 | 29-DEC-18:10 | 1643.42 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.162405E+12 | 0.419753E+11 | 3936.58 | 0.117283E+12 | 0.451226E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.127239E+10 | 0.341336E+09 | 188.25 | 0.117240E+10 | 99989036.61 | 0.00 | 0.44 | 0.00 | 5094.41 | 4898.21 | 801.84 | 1341.77 | 0.00 | |||||||
Maximum of Months | 0.252486E+11 | 0.616953E+10 | 379.75 | 0.161078E+11 | 0.110895E+11 | 0.00 | 1.00 | 0.00 | 32812.95 | 28074.12 | 20269.23 | 7484.62 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.114530E+10 | 0.307842E+09 | 175.00 | 0.105617E+10 | 89128600.55 | 0.00 | 0.43 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 4961.53 | 12-JAN-15:00 | 4769.64 | 12-JAN-15:00 | 784.49 | 14-JAN-14:00 | 1310.79 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.355543E+10 | 0.936852E+09 | 246.56 | 0.318738E+10 | 0.368047E+09 | 0.00 | 0.76 | 25-FEB-07:03 | 0.00 | 01-FEB-00:05 | 10322.43 | 25-FEB-07:03 | 7654.73 | 22-FEB-15:00 | 2980.41 | 25-FEB-07:03 | 2367.00 | 25-FEB-07:03 | 0.00 | 01-FEB-00:05 |
March | 0.849360E+10 | 0.224373E+10 | 347.03 | 0.755977E+10 | 0.933831E+09 | 0.00 | 1.00 | 11-MAR-07:02 | 0.00 | 01-MAR-00:05 | 30075.62 | 11-MAR-07:02 | 24375.31 | 29-MAR-06:02 | 8285.58 | 11-MAR-07:02 | 6531.56 | 11-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.133473E+11 | 0.371928E+10 | 356.03 | 0.122013E+11 | 0.114597E+10 | 0.00 | 1.00 | 02-APR-07:02 | 0.00 | 01-APR-00:05 | 30178.07 | 17-APR-06:01 | 28130.17 | 20-APR-06:01 | 7720.48 | 17-APR-06:02 | 7068.39 | 27-APR-06:01 | 0.00 | 01-APR-00:05 |
May | 0.198397E+11 | 0.559636E+10 | 377.79 | 0.162146E+11 | 0.362504E+10 | 0.00 | 1.00 | 01-MAY-06:01 | 0.00 | 01-MAY-00:10 | 31805.34 | 23-MAY-06:01 | 28003.29 | 28-MAY-07:01 | 14430.64 | 23-MAY-06:04 | 7263.18 | 04-MAY-06:01 | 0.00 | 01-MAY-00:10 |
June | 0.224289E+11 | 0.607077E+10 | 369.38 | 0.161712E+11 | 0.625774E+10 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 32759.05 | 26-JUN-06:01 | 26715.26 | 12-JUN-06:01 | 19170.06 | 26-JUN-06:05 | 7499.91 | 12-JUN-06:01 | 0.00 | 01-JUN-00:10 |
July | 0.250592E+11 | 0.620561E+10 | 371.74 | 0.149838E+11 | 0.100754E+11 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:03 | 32787.69 | 23-JUL-07:01 | 21853.41 | 07-JUL-06:01 | 19247.30 | 24-JUL-06:06 | 7430.19 | 02-JUL-07:16 | 0.00 | 01-JUL-00:03 |
August | 0.253518E+11 | 0.607150E+10 | 379.75 | 0.142386E+11 | 0.111132E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 32859.05 | 21-AUG-06:01 | 19264.68 | 03-AUG-06:01 | 20136.61 | 21-AUG-06:04 | 7115.90 | 08-AUG-06:12 | 0.00 | 01-AUG-00:10 |
September | 0.204897E+11 | 0.494761E+10 | 359.87 | 0.124147E+11 | 0.807500E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:10 | 32867.19 | 10-SEP-07:01 | 21359.40 | 27-SEP-06:01 | 20265.95 | 11-SEP-06:05 | 6897.23 | 22-SEP-06:01 | 0.00 | 01-SEP-00:10 |
October | 0.132527E+11 | 0.340484E+10 | 364.84 | 0.107631E+11 | 0.248960E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:03 | 30977.53 | 12-OCT-06:02 | 25847.35 | 23-OCT-06:02 | 12052.81 | 13-OCT-06:02 | 6699.08 | 04-OCT-06:01 | 0.00 | 01-OCT-00:03 |
November | 0.731322E+10 | 0.190218E+10 | 322.40 | 0.653115E+10 | 0.782068E+09 | 0.00 | 0.90 | 02-NOV-06:03 | 0.00 | 01-NOV-00:10 | 23513.20 | 09-NOV-07:03 | 16931.83 | 09-NOV-07:03 | 6581.37 | 09-NOV-07:03 | 4977.21 | 09-NOV-07:03 | 0.00 | 01-NOV-00:10 |
December | 0.235847E+10 | 0.627571E+09 | 245.92 | 0.212008E+10 | 0.238384E+09 | 0.00 | 0.52 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 6162.18 | 28-DEC-14:00 | 5978.79 | 02-DEC-14:00 | 874.79 | 29-DEC-18:10 | 1614.39 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.162635E+12 | 0.420341E+11 | 3916.32 | 0.117442E+12 | 0.451934E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.114530E+10 | 0.307842E+09 | 175.00 | 0.105617E+10 | 89128600.55 | 0.00 | 0.43 | 0.00 | 4961.53 | 4769.64 | 784.49 | 1310.79 | 0.00 | |||||||
Maximum of Months | 0.253518E+11 | 0.620561E+10 | 379.75 | 0.162146E+11 | 0.111132E+11 | 0.00 | 1.00 | 0.00 | 32867.19 | 28130.17 | 20265.95 | 7499.91 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.935964E+09 | 0.252452E+09 | 151.17 | 0.863598E+09 | 72365385.32 | 0.00 | 0.41 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 4689.86 | 12-JAN-15:00 | 4505.36 | 12-JAN-15:00 | 745.47 | 14-JAN-14:00 | 1245.67 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.330883E+10 | 0.875397E+09 | 238.64 | 0.296785E+10 | 0.340986E+09 | 0.00 | 0.65 | 22-FEB-14:50 | 0.00 | 01-FEB-00:05 | 8159.81 | 25-FEB-07:03 | 7461.53 | 22-FEB-15:00 | 2394.72 | 25-FEB-07:03 | 2099.83 | 22-FEB-14:50 | 0.00 | 01-FEB-00:05 |
March | 0.822395E+10 | 0.217893E+10 | 343.66 | 0.731660E+10 | 0.907345E+09 | 0.00 | 1.00 | 11-MAR-07:02 | 0.00 | 01-MAR-00:05 | 29891.55 | 11-MAR-07:02 | 24101.00 | 29-MAR-06:02 | 8387.21 | 11-MAR-07:02 | 6493.69 | 11-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.131295E+11 | 0.366399E+10 | 355.73 | 0.119972E+11 | 0.113226E+10 | 0.00 | 1.00 | 02-APR-07:02 | 0.00 | 01-APR-00:05 | 30000.61 | 17-APR-06:01 | 27899.76 | 20-APR-06:01 | 7742.17 | 17-APR-06:02 | 7027.74 | 27-APR-06:01 | 0.00 | 01-APR-00:05 |
May | 0.196295E+11 | 0.553970E+10 | 377.69 | 0.160295E+11 | 0.359996E+10 | 0.00 | 1.00 | 01-MAY-06:01 | 0.00 | 01-MAY-00:10 | 31622.39 | 23-MAY-06:01 | 27829.10 | 28-MAY-07:01 | 14308.15 | 23-MAY-06:04 | 7221.45 | 04-MAY-06:01 | 0.00 | 01-MAY-00:10 |
June | 0.222085E+11 | 0.601162E+10 | 368.92 | 0.159881E+11 | 0.622043E+10 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 32579.26 | 26-JUN-06:01 | 26527.61 | 12-JUN-06:01 | 19176.88 | 26-JUN-06:05 | 7458.29 | 12-JUN-06:01 | 0.00 | 01-JUN-00:10 |
July | 0.248426E+11 | 0.615078E+10 | 371.17 | 0.148169E+11 | 0.100257E+11 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:03 | 32607.74 | 23-JUL-07:01 | 21590.78 | 07-JUL-06:01 | 19235.71 | 24-JUL-06:06 | 7380.42 | 02-JUL-07:14 | 0.00 | 01-JUL-00:03 |
August | 0.251038E+11 | 0.601086E+10 | 379.66 | 0.140512E+11 | 0.110526E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 32678.71 | 21-AUG-06:01 | 18999.91 | 03-AUG-06:01 | 20116.62 | 21-AUG-06:04 | 7076.88 | 08-AUG-06:12 | 0.00 | 01-AUG-00:10 |
September | 0.202503E+11 | 0.489088E+10 | 359.78 | 0.122304E+11 | 0.801988E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:10 | 32686.81 | 10-SEP-07:01 | 21103.10 | 27-SEP-06:01 | 20261.90 | 11-SEP-06:05 | 6859.33 | 22-SEP-06:01 | 0.00 | 01-SEP-00:10 |
October | 0.130219E+11 | 0.335078E+10 | 363.99 | 0.105640E+11 | 0.245781E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:03 | 30799.56 | 12-OCT-06:02 | 25606.35 | 23-OCT-06:02 | 12141.48 | 13-OCT-06:02 | 6661.40 | 04-OCT-06:01 | 0.00 | 01-OCT-00:03 |
November | 0.706683E+10 | 0.184362E+10 | 318.40 | 0.630860E+10 | 0.758233E+09 | 0.00 | 0.84 | 09-NOV-13:40 | 0.00 | 01-NOV-00:10 | 21055.61 | 09-NOV-07:03 | 14963.62 | 09-NOV-07:03 | 6091.99 | 09-NOV-07:03 | 4459.04 | 09-NOV-07:03 | 0.00 | 01-NOV-00:10 |
December | 0.210545E+10 | 0.562555E+09 | 238.42 | 0.189209E+10 | 0.213363E+09 | 0.00 | 0.50 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 | 5898.89 | 28-DEC-14:00 | 5780.44 | 02-DEC-14:00 | 835.64 | 16-DEC-14:00 | 1552.93 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.159827E+12 | 0.413316E+11 | 3867.22 | 0.115026E+12 | 0.448010E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.935964E+09 | 0.252452E+09 | 151.17 | 0.863598E+09 | 72365385.32 | 0.00 | 0.41 | 0.00 | 4689.86 | 4505.36 | 745.47 | 1245.67 | 0.00 | |||||||
Maximum of Months | 0.251038E+11 | 0.615078E+10 | 379.66 | 0.160295E+11 | 0.110526E+11 | 0.00 | 1.00 | 0.00 | 32686.81 | 27899.76 | 20261.90 | 7458.29 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.985215E+09 | 0.272903E+09 | 104.83 | 0.893751E+09 | 91464221.99 | 0.00 | 0.37 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 7441.44 | 12-JAN-15:10 | 7015.45 | 12-JAN-15:10 | 1269.54 | 14-JAN-15:10 | 2033.94 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.492718E+10 | 0.134147E+10 | 223.97 | 0.437761E+10 | 0.549573E+09 | 0.00 | 0.63 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 13820.62 | 24-FEB-15:20 | 12734.83 | 22-FEB-15:10 | 3239.37 | 25-FEB-16:00 | 3712.33 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.138995E+11 | 0.377518E+10 | 336.04 | 0.122358E+11 | 0.166372E+10 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 | 52892.60 | 11-MAR-08:62 | 41953.96 | 30-MAR-07:02 | 13663.77 | 11-MAR-08:62 | 11844.44 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.230189E+11 | 0.656847E+10 | 345.32 | 0.209979E+11 | 0.202105E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 53524.75 | 17-APR-07:01 | 49109.23 | 20-APR-07:01 | 14053.70 | 17-APR-07:03 | 12790.07 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.350061E+11 | 0.100639E+11 | 368.48 | 0.284147E+11 | 0.659146E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 56161.53 | 21-MAY-08:61 | 49487.03 | 29-MAY-08:61 | 23510.21 | 21-MAY-08:05 | 13472.71 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.397521E+11 | 0.109588E+11 | 359.96 | 0.284004E+11 | 0.113517E+11 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 58295.26 | 25-JUN-08:62 | 47582.83 | 07-JUN-07:01 | 34452.78 | 26-JUN-07:06 | 13790.98 | 10-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.442347E+11 | 0.111259E+11 | 360.12 | 0.259288E+11 | 0.183059E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 58283.44 | 23-JUL-08:61 | 41311.54 | 07-JUL-07:01 | 34582.74 | 23-JUL-08:06 | 13696.89 | 01-JUL-15:00 | 0.00 | 01-JUL-00:03 |
August | 0.449097E+11 | 0.109115E+11 | 371.24 | 0.245827E+11 | 0.203269E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 58466.80 | 21-AUG-07:01 | 37038.02 | 08-AUG-07:01 | 36255.95 | 21-AUG-07:06 | 12991.60 | 27-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.357301E+11 | 0.877166E+10 | 349.16 | 0.211935E+11 | 0.145366E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 58493.31 | 04-SEP-08:61 | 39786.01 | 27-SEP-07:02 | 36359.39 | 11-SEP-07:05 | 12659.21 | 24-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.227455E+11 | 0.597033E+10 | 352.76 | 0.182459E+11 | 0.449964E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:03 | 54667.56 | 12-OCT-07:02 | 45073.91 | 25-OCT-07:02 | 20408.04 | 12-OCT-07:02 | 12180.27 | 04-OCT-07:01 | 0.00 | 01-OCT-00:03 |
November | 0.117236E+11 | 0.313606E+10 | 317.56 | 0.103239E+11 | 0.139970E+10 | 0.00 | 0.83 | 09-NOV-13:40 | 0.00 | 01-NOV-00:10 | 33328.88 | 09-NOV-08:62 | 23935.46 | 09-NOV-08:62 | 9393.42 | 09-NOV-08:62 | 7195.56 | 09-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.259357E+10 | 0.711479E+09 | 194.25 | 0.231158E+10 | 0.281986E+09 | 0.00 | 0.47 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 9772.57 | 28-DEC-14:00 | 9406.99 | 02-DEC-14:10 | 1451.32 | 16-DEC-14:40 | 2642.88 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.279526E+12 | 0.736076E+11 | 3683.69 | 0.197907E+12 | 0.816197E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.985215E+09 | 0.272903E+09 | 104.83 | 0.893751E+09 | 91464221.99 | 0.00 | 0.37 | 0.00 | 7441.44 | 7015.45 | 1269.54 | 2033.94 | 0.00 | |||||||
Maximum of Months | 0.449097E+11 | 0.111259E+11 | 371.24 | 0.284147E+11 | 0.203269E+11 | 0.00 | 1.00 | 0.00 | 58493.31 | 49487.03 | 36359.39 | 13790.98 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.453290E+09 | 0.123635E+09 | 96.67 | 0.411717E+09 | 41573132.73 | 0.00 | 0.36 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 3773.42 | 12-JAN-15:10 | 3572.84 | 12-JAN-15:10 | 624.56 | 14-JAN-15:10 | 1016.45 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.248706E+10 | 0.666840E+09 | 220.31 | 0.221836E+10 | 0.268693E+09 | 0.00 | 0.62 | 22-FEB-15:10 | 0.00 | 01-FEB-00:05 | 7145.94 | 24-FEB-15:20 | 6617.75 | 22-FEB-15:10 | 1625.44 | 25-FEB-16:00 | 1891.27 | 22-FEB-15:10 | 0.00 | 01-FEB-00:05 |
March | 0.716014E+10 | 0.191509E+10 | 335.68 | 0.632105E+10 | 0.839083E+09 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 | 27753.83 | 11-MAR-08:62 | 20689.32 | 30-MAR-07:02 | 7131.43 | 11-MAR-08:62 | 6106.20 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.119307E+11 | 0.335351E+10 | 345.79 | 0.108958E+11 | 0.103495E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 28101.89 | 17-APR-07:01 | 25849.44 | 20-APR-07:01 | 7393.72 | 17-APR-07:03 | 6592.87 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.181736E+11 | 0.514884E+10 | 368.26 | 0.147688E+11 | 0.340473E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 29473.22 | 21-MAY-08:61 | 25968.55 | 29-MAY-08:61 | 12283.99 | 21-MAY-08:13 | 6942.42 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.206120E+11 | 0.559842E+10 | 359.38 | 0.147435E+11 | 0.586846E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 30589.99 | 25-JUN-08:62 | 24932.72 | 07-JUN-07:01 | 18147.46 | 26-JUN-07:06 | 7124.13 | 10-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.229377E+11 | 0.568066E+10 | 359.76 | 0.134654E+11 | 0.947234E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 30583.79 | 23-JUL-08:61 | 21679.35 | 07-JUL-07:01 | 18186.84 | 23-JUL-08:06 | 7062.31 | 01-JUL-15:00 | 0.00 | 01-JUL-00:03 |
August | 0.232627E+11 | 0.556555E+10 | 371.40 | 0.127508E+11 | 0.105119E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 30680.01 | 21-AUG-07:01 | 19461.70 | 08-AUG-07:01 | 19131.79 | 21-AUG-07:06 | 6710.77 | 27-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.185078E+11 | 0.447571E+10 | 349.34 | 0.109961E+11 | 0.751176E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 30693.92 | 04-SEP-08:61 | 20935.67 | 27-SEP-07:02 | 19212.82 | 11-SEP-07:03 | 6526.37 | 24-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.117674E+11 | 0.304216E+10 | 353.39 | 0.946325E+10 | 0.230417E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:03 | 28672.26 | 12-OCT-07:02 | 23726.29 | 23-OCT-07:02 | 10604.34 | 12-OCT-07:02 | 6277.39 | 04-OCT-07:01 | 0.00 | 01-OCT-00:03 |
November | 0.603593E+10 | 0.158989E+10 | 316.47 | 0.533289E+10 | 0.703043E+09 | 0.00 | 0.91 | 10-NOV-08:62 | 0.00 | 01-NOV-00:10 | 15133.89 | 09-NOV-08:62 | 10826.15 | 09-NOV-08:62 | 4307.74 | 09-NOV-08:62 | 3211.73 | 09-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.127035E+10 | 0.343098E+09 | 187.75 | 0.113778E+10 | 0.132570E+09 | 0.00 | 0.46 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 4987.56 | 28-DEC-14:00 | 4848.61 | 02-DEC-14:10 | 723.57 | 16-DEC-14:40 | 1329.42 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.144599E+12 | 0.375034E+11 | 3664.18 | 0.102505E+12 | 0.420933E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.453290E+09 | 0.123635E+09 | 96.67 | 0.411717E+09 | 41573132.73 | 0.00 | 0.36 | 0.00 | 3773.42 | 3572.84 | 624.56 | 1016.45 | 0.00 | |||||||
Maximum of Months | 0.232627E+11 | 0.568066E+10 | 371.40 | 0.147688E+11 | 0.105119E+11 | 0.00 | 1.00 | 0.00 | 30693.92 | 25968.55 | 19212.82 | 7124.13 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.418369E+09 | 0.114252E+09 | 90.50 | 0.379392E+09 | 38977405.49 | 0.00 | 0.35 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 3680.71 | 12-JAN-15:10 | 3482.83 | 12-JAN-15:10 | 610.01 | 14-JAN-15:10 | 993.34 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.241552E+10 | 0.648548E+09 | 217.47 | 0.215447E+10 | 0.261051E+09 | 0.00 | 0.62 | 22-FEB-15:10 | 0.00 | 01-FEB-00:05 | 7076.45 | 24-FEB-15:20 | 6544.93 | 22-FEB-15:10 | 1600.50 | 25-FEB-16:00 | 1873.45 | 22-FEB-15:10 | 0.00 | 01-FEB-00:05 |
March | 0.707345E+10 | 0.189348E+10 | 334.26 | 0.624176E+10 | 0.831686E+09 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 | 27652.03 | 11-MAR-08:62 | 20499.00 | 11-MAR-08:62 | 7153.04 | 11-MAR-08:62 | 6084.06 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.118597E+11 | 0.333455E+10 | 345.65 | 0.108279E+11 | 0.103177E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 27998.89 | 17-APR-07:01 | 25722.99 | 20-APR-07:01 | 7385.60 | 17-APR-07:03 | 6568.91 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.181006E+11 | 0.512807E+10 | 368.01 | 0.147035E+11 | 0.339712E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 29365.18 | 21-MAY-08:61 | 25872.35 | 29-MAY-08:61 | 12253.44 | 21-MAY-08:13 | 6917.29 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.205371E+11 | 0.557758E+10 | 359.44 | 0.146800E+11 | 0.585709E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 30480.55 | 25-JUN-08:62 | 24820.49 | 07-JUN-07:01 | 18100.66 | 26-JUN-07:06 | 7103.51 | 10-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.228642E+11 | 0.566136E+10 | 359.78 | 0.134077E+11 | 0.945648E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 30474.37 | 23-JUL-08:61 | 21572.36 | 07-JUL-07:01 | 18142.64 | 23-JUL-08:06 | 7042.14 | 01-JUL-15:00 | 0.00 | 01-JUL-00:03 |
August | 0.231859E+11 | 0.554594E+10 | 371.29 | 0.126918E+11 | 0.104941E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 30570.24 | 21-AUG-07:01 | 19363.68 | 08-AUG-07:01 | 19082.04 | 21-AUG-07:06 | 6693.27 | 27-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.184359E+11 | 0.445772E+10 | 349.36 | 0.109401E+11 | 0.749579E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 30584.10 | 04-SEP-08:61 | 20826.29 | 27-SEP-07:02 | 19167.85 | 11-SEP-07:03 | 6503.03 | 24-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.116973E+11 | 0.302477E+10 | 353.27 | 0.940127E+10 | 0.229600E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:03 | 28571.31 | 12-OCT-07:02 | 23615.63 | 23-OCT-07:02 | 10615.98 | 12-OCT-07:02 | 6254.98 | 04-OCT-07:01 | 0.00 | 01-OCT-00:03 |
November | 0.596238E+10 | 0.157170E+10 | 315.81 | 0.526562E+10 | 0.696758E+09 | 0.00 | 0.88 | 10-NOV-08:62 | 0.00 | 01-NOV-00:10 | 14495.37 | 09-NOV-08:62 | 10314.70 | 09-NOV-08:62 | 4180.67 | 09-NOV-08:62 | 3076.65 | 09-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.120813E+10 | 0.326640E+09 | 181.25 | 0.108265E+10 | 0.125479E+09 | 0.00 | 0.45 | 02-DEC-14:10 | 0.00 | 01-DEC-00:10 | 4901.26 | 28-DEC-14:00 | 4779.39 | 02-DEC-14:10 | 710.41 | 16-DEC-14:40 | 1308.46 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.143758E+12 | 0.372846E+11 | 3646.10 | 0.101776E+12 | 0.419823E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.418369E+09 | 0.114252E+09 | 90.50 | 0.379392E+09 | 38977405.49 | 0.00 | 0.35 | 0.00 | 3680.71 | 3482.83 | 610.01 | 993.34 | 0.00 | |||||||
Maximum of Months | 0.231859E+11 | 0.566136E+10 | 371.29 | 0.147035E+11 | 0.104941E+11 | 0.00 | 1.00 | 0.00 | 30584.10 | 25872.35 | 19167.85 | 7103.51 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.360276E+09 | 98671930.81 | 82.00 | 0.326197E+09 | 34079110.85 | 0.00 | 0.33 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 3507.24 | 12-JAN-15:10 | 3318.64 | 12-JAN-15:10 | 577.60 | 14-JAN-15:10 | 950.68 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.227222E+10 | 0.612216E+09 | 213.08 | 0.202885E+10 | 0.243371E+09 | 0.00 | 0.61 | 22-FEB-15:10 | 0.00 | 01-FEB-00:05 | 6957.81 | 24-FEB-15:20 | 6426.18 | 22-FEB-15:10 | 1549.76 | 25-FEB-16:00 | 1845.55 | 22-FEB-15:10 | 0.00 | 01-FEB-00:05 |
March | 0.691370E+10 | 0.185561E+10 | 329.73 | 0.610194E+10 | 0.811755E+09 | 0.00 | 0.99 | 28-MAR-15:00 | 0.00 | 01-MAR-00:05 | 26232.10 | 11-MAR-08:62 | 19319.97 | 11-MAR-08:62 | 6912.13 | 11-MAR-08:62 | 5774.02 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.118193E+11 | 0.332645E+10 | 345.84 | 0.107928E+11 | 0.102648E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 28072.34 | 17-APR-07:01 | 25749.14 | 20-APR-07:01 | 7429.69 | 17-APR-07:03 | 6587.13 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.181361E+11 | 0.514016E+10 | 368.22 | 0.147404E+11 | 0.339572E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 29444.78 | 21-MAY-08:61 | 25948.28 | 29-MAY-08:61 | 12309.67 | 21-MAY-08:13 | 6937.42 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.205984E+11 | 0.559660E+10 | 359.38 | 0.147374E+11 | 0.586100E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 30568.98 | 25-JUN-08:62 | 24922.72 | 07-JUN-07:01 | 18199.33 | 26-JUN-07:06 | 7132.51 | 10-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.229610E+11 | 0.568796E+10 | 359.74 | 0.134873E+11 | 0.947370E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 30562.79 | 23-JUL-08:61 | 21687.49 | 07-JUL-07:01 | 18215.38 | 23-JUL-08:06 | 7072.59 | 01-JUL-15:00 | 0.00 | 01-JUL-00:03 |
August | 0.232840E+11 | 0.557109E+10 | 371.30 | 0.127687E+11 | 0.105153E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 30658.94 | 21-AUG-07:01 | 19485.63 | 08-AUG-07:01 | 19141.56 | 21-AUG-07:04 | 6724.13 | 27-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.184940E+11 | 0.447301E+10 | 349.34 | 0.109890E+11 | 0.750503E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 30672.84 | 04-SEP-08:61 | 20895.37 | 27-SEP-07:02 | 19263.76 | 11-SEP-07:03 | 6521.90 | 24-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.116881E+11 | 0.302398E+10 | 352.68 | 0.939754E+10 | 0.229055E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:03 | 28648.23 | 12-OCT-07:02 | 23664.03 | 23-OCT-07:02 | 10693.49 | 12-OCT-07:02 | 6272.48 | 04-OCT-07:01 | 0.00 | 01-OCT-00:03 |
November | 0.585025E+10 | 0.154515E+10 | 311.94 | 0.516813E+10 | 0.682120E+09 | 0.00 | 0.94 | 09-NOV-08:62 | 0.00 | 01-NOV-00:10 | 12669.65 | 09-NOV-08:62 | 9326.10 | 04-NOV-14:10 | 3723.17 | 09-NOV-08:62 | 2741.08 | 09-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.109041E+10 | 0.295588E+09 | 168.00 | 0.979643E+09 | 0.110767E+09 | 0.00 | 0.44 | 02-DEC-14:20 | 0.00 | 01-DEC-00:10 | 4746.00 | 28-DEC-14:00 | 4646.55 | 02-DEC-14:10 | 680.77 | 16-DEC-14:40 | 1271.93 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.143468E+12 | 0.372265E+11 | 3611.26 | 0.101518E+12 | 0.419499E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.360276E+09 | 98671930.81 | 82.00 | 0.326197E+09 | 34079110.85 | 0.00 | 0.33 | 0.00 | 3507.24 | 3318.64 | 577.60 | 950.68 | 0.00 | |||||||
Maximum of Months | 0.232840E+11 | 0.568796E+10 | 371.30 | 0.147404E+11 | 0.105153E+11 | 0.00 | 1.00 | 0.00 | 30672.84 | 25948.28 | 19263.76 | 7132.51 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.373752E+09 | 0.102625E+09 | 80.50 | 0.341966E+09 | 31786561.51 | 0.00 | 0.31 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 3621.78 | 12-JAN-15:10 | 3456.67 | 12-JAN-15:10 | 558.40 | 14-JAN-15:00 | 986.93 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.233371E+10 | 0.631742E+09 | 209.50 | 0.210358E+10 | 0.230123E+09 | 0.00 | 0.59 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 7426.10 | 22-FEB-14:00 | 6915.93 | 22-FEB-14:00 | 1496.06 | 25-FEB-16:00 | 1984.57 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.725268E+10 | 0.195845E+10 | 324.17 | 0.644858E+10 | 0.804099E+09 | 0.00 | 0.97 | 28-MAR-15:00 | 0.00 | 01-MAR-00:05 | 20351.78 | 11-MAR-08:62 | 14761.46 | 11-MAR-08:62 | 5590.31 | 11-MAR-08:62 | 4485.75 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.129318E+11 | 0.364811E+10 | 346.94 | 0.118633E+11 | 0.106857E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 30984.80 | 17-APR-07:01 | 28144.71 | 09-APR-08:62 | 8383.60 | 17-APR-07:03 | 7260.19 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.199750E+11 | 0.568315E+10 | 368.89 | 0.163950E+11 | 0.358000E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 32718.85 | 24-MAY-07:01 | 28948.76 | 29-MAY-08:61 | 15485.20 | 24-MAY-07:03 | 7654.23 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.225847E+11 | 0.618029E+10 | 360.64 | 0.164351E+11 | 0.614962E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 33695.98 | 25-JUN-08:62 | 28107.19 | 12-JUN-07:01 | 20663.10 | 26-JUN-07:06 | 7832.79 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.252173E+11 | 0.629415E+10 | 361.04 | 0.151920E+11 | 0.100253E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 33689.15 | 23-JUL-08:61 | 24306.48 | 07-JUL-07:01 | 20527.64 | 23-JUL-08:06 | 7770.49 | 10-JUL-13:00 | 0.00 | 01-JUL-00:03 |
August | 0.255840E+11 | 0.616564E+10 | 371.83 | 0.144838E+11 | 0.111002E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 33795.13 | 21-AUG-07:01 | 21407.01 | 09-AUG-07:01 | 20872.19 | 21-AUG-07:04 | 7353.93 | 27-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.203303E+11 | 0.494678E+10 | 349.62 | 0.124284E+11 | 0.790193E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 33810.46 | 04-SEP-08:61 | 23604.30 | 27-SEP-07:02 | 21116.62 | 11-SEP-07:05 | 7189.02 | 24-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.129620E+11 | 0.335500E+10 | 352.42 | 0.105567E+11 | 0.240530E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:03 | 31856.78 | 12-OCT-07:02 | 25995.09 | 23-OCT-07:02 | 12843.71 | 12-OCT-07:02 | 6911.48 | 04-OCT-07:01 | 0.00 | 01-OCT-00:03 |
November | 0.632146E+10 | 0.167309E+10 | 308.61 | 0.563415E+10 | 0.687307E+09 | 0.00 | 0.82 | 09-NOV-13:20 | 0.00 | 01-NOV-00:10 | 11034.06 | 09-NOV-13:10 | 10105.58 | 04-NOV-14:10 | 2303.10 | 09-NOV-08:62 | 2857.42 | 09-NOV-13:20 | 0.00 | 01-NOV-00:10 |
December | 0.114334E+10 | 0.310512E+09 | 162.67 | 0.103893E+10 | 0.104404E+09 | 0.00 | 0.42 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 4988.45 | 28-DEC-14:00 | 4860.52 | 02-DEC-14:10 | 688.35 | 16-DEC-14:30 | 1343.73 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.157010E+12 | 0.409495E+11 | 3596.82 | 0.112921E+12 | 0.440886E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.373752E+09 | 0.102625E+09 | 80.50 | 0.341966E+09 | 31786561.51 | 0.00 | 0.31 | 0.00 | 3621.78 | 3456.67 | 558.40 | 986.93 | 0.00 | |||||||
Maximum of Months | 0.255840E+11 | 0.629415E+10 | 371.83 | 0.164351E+11 | 0.111002E+11 | 0.00 | 1.00 | 0.00 | 33810.46 | 28948.76 | 21116.62 | 7832.79 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 103.32 | 64.99 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.36 | 51.84 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 98.30 | 30.87 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 87.39 | 10.63 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 88.26 | 1.90 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 90.52 | 1.47 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 84.39 | 0.49 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 76.80 | 1.47 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 84.77 | 5.40 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 129.75 | 24.55 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 146.43 | 46.64 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.24 | 64.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 100.75 | 25.25 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 76.80 | 0.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 146.43 | 64.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 103.32 | 64.99 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.36 | 51.84 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 98.30 | 30.87 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 87.39 | 10.63 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 88.26 | 1.90 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 90.52 | 1.47 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 84.39 | 0.49 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 76.80 | 1.47 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 84.77 | 5.40 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 129.75 | 24.55 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 146.43 | 46.64 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.24 | 64.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 100.75 | 25.25 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 76.80 | 0.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 146.43 | 64.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 103.32 | 64.99 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.36 | 51.84 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 98.30 | 30.87 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 87.39 | 10.63 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 88.26 | 1.90 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 90.52 | 1.47 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 84.39 | 0.49 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 76.80 | 1.47 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 84.77 | 5.40 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 129.75 | 24.55 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 146.43 | 46.64 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.24 | 64.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 100.75 | 25.25 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 76.80 | 0.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 146.43 | 64.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 103.32 | 64.99 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.36 | 51.84 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 98.30 | 30.87 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 87.39 | 10.63 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 88.26 | 1.90 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 90.52 | 1.47 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 84.39 | 0.49 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 76.80 | 1.47 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 84.77 | 5.40 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 129.75 | 24.55 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 146.43 | 46.64 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.24 | 64.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 100.75 | 25.25 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 76.80 | 0.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 146.43 | 64.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.66 | 56.31 | 36.35 | 124.19 | 77.62 | 0.00 | 0.00 | 744.00 |
February | 88.09 | 48.93 | 39.16 | 125.39 | 61.94 | 0.00 | 0.00 | 672.00 |
March | 75.30 | 33.25 | 42.05 | 117.94 | 36.95 | 0.00 | 0.00 | 744.00 |
April | 52.88 | 14.91 | 37.97 | 104.53 | 12.74 | 0.00 | 0.00 | 720.00 |
May | 38.02 | 2.79 | 35.23 | 105.24 | 2.29 | 0.00 | 0.00 | 744.00 |
June | 34.79 | 0.58 | 34.21 | 107.94 | 1.76 | 0.00 | 0.00 | 720.00 |
July | 36.29 | 0.49 | 35.80 | 100.66 | 0.60 | 0.00 | 0.00 | 744.00 |
August | 38.50 | 2.05 | 36.45 | 91.72 | 1.78 | 0.00 | 0.00 | 744.00 |
September | 51.61 | 13.39 | 38.22 | 101.41 | 6.48 | 0.00 | 0.00 | 720.00 |
October | 88.80 | 49.59 | 39.22 | 155.54 | 29.43 | 0.00 | 0.00 | 744.00 |
November | 110.95 | 73.35 | 37.61 | 175.76 | 55.80 | 0.00 | 0.00 | 720.00 |
December | 99.02 | 62.06 | 36.96 | 138.46 | 76.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 67.12 | 29.70 | 37.42 | 120.67 | 30.20 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.79 | 0.49 | 34.21 | 91.72 | 0.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.95 | 73.35 | 42.05 | 175.76 | 77.62 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.66 | 56.31 | 36.35 | 124.19 | 77.62 | 0.00 | 0.00 | 744.00 |
February | 88.09 | 48.93 | 39.16 | 125.39 | 61.94 | 0.00 | 0.00 | 672.00 |
March | 75.30 | 33.25 | 42.05 | 117.94 | 36.95 | 0.00 | 0.00 | 744.00 |
April | 52.88 | 14.91 | 37.97 | 104.53 | 12.74 | 0.00 | 0.00 | 720.00 |
May | 38.02 | 2.79 | 35.23 | 105.24 | 2.29 | 0.00 | 0.00 | 744.00 |
June | 34.79 | 0.58 | 34.21 | 107.94 | 1.76 | 0.00 | 0.00 | 720.00 |
July | 36.29 | 0.49 | 35.80 | 100.66 | 0.60 | 0.00 | 0.00 | 744.00 |
August | 38.50 | 2.05 | 36.45 | 91.72 | 1.78 | 0.00 | 0.00 | 744.00 |
September | 51.61 | 13.39 | 38.22 | 101.41 | 6.48 | 0.00 | 0.00 | 720.00 |
October | 88.80 | 49.59 | 39.22 | 155.54 | 29.43 | 0.00 | 0.00 | 744.00 |
November | 110.95 | 73.35 | 37.61 | 175.76 | 55.80 | 0.00 | 0.00 | 720.00 |
December | 99.02 | 62.06 | 36.96 | 138.46 | 76.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 67.12 | 29.70 | 37.42 | 120.67 | 30.20 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.79 | 0.49 | 34.21 | 91.72 | 0.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.95 | 73.35 | 42.05 | 175.76 | 77.62 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 102.13 | 67.55 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.51 | 53.44 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 98.04 | 31.62 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 87.89 | 10.88 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 89.34 | 1.90 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 91.89 | 1.47 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 85.74 | 0.47 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 77.95 | 1.37 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 85.55 | 5.19 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 130.05 | 24.55 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 146.17 | 47.13 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 114.33 | 65.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 101.01 | 25.83 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 77.95 | 0.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 146.17 | 67.55 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 102.13 | 67.55 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.51 | 53.44 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 98.04 | 31.62 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 87.89 | 10.88 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 89.34 | 1.90 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 91.89 | 1.47 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 85.74 | 0.47 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 77.95 | 1.37 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 85.55 | 5.19 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 130.05 | 24.55 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 146.17 | 47.13 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 114.33 | 65.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 101.01 | 25.83 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 77.95 | 0.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 146.17 | 67.55 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.66 | 56.31 | 36.35 | 122.78 | 80.66 | 0.00 | 0.00 | 744.00 |
February | 88.09 | 48.93 | 39.16 | 124.37 | 63.83 | 0.00 | 0.00 | 672.00 |
March | 75.30 | 33.25 | 42.05 | 117.63 | 37.85 | 0.00 | 0.00 | 744.00 |
April | 52.88 | 14.91 | 37.97 | 105.12 | 13.04 | 0.00 | 0.00 | 720.00 |
May | 38.02 | 2.79 | 35.23 | 106.53 | 2.30 | 0.00 | 0.00 | 744.00 |
June | 34.79 | 0.58 | 34.21 | 109.58 | 1.77 | 0.00 | 0.00 | 720.00 |
July | 36.29 | 0.49 | 35.80 | 102.28 | 0.56 | 0.00 | 0.00 | 744.00 |
August | 38.50 | 2.05 | 36.45 | 93.11 | 1.65 | 0.00 | 0.00 | 744.00 |
September | 51.61 | 13.39 | 38.22 | 102.36 | 6.23 | 0.00 | 0.00 | 720.00 |
October | 88.80 | 49.59 | 39.22 | 155.91 | 29.42 | 0.00 | 0.00 | 744.00 |
November | 110.95 | 73.35 | 37.61 | 175.45 | 56.38 | 0.00 | 0.00 | 720.00 |
December | 99.02 | 62.06 | 36.96 | 137.38 | 78.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 67.12 | 29.70 | 37.42 | 120.99 | 30.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.79 | 0.49 | 34.21 | 93.11 | 0.56 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.95 | 73.35 | 42.05 | 175.45 | 80.66 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 102.67 | 66.22 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.71 | 53.68 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 97.83 | 33.17 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 85.95 | 12.51 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 85.47 | 2.71 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 87.78 | 2.16 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 81.15 | 0.78 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 74.94 | 2.25 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 83.79 | 7.13 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 129.52 | 27.08 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 146.21 | 48.51 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 114.70 | 65.50 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 99.43 | 26.69 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 74.94 | 0.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 146.21 | 66.22 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 102.67 | 66.22 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.71 | 53.68 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 97.83 | 33.17 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 85.95 | 12.51 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 85.47 | 2.71 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 87.78 | 2.16 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 81.15 | 0.78 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 74.94 | 2.25 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 83.79 | 7.13 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 129.52 | 27.08 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 146.21 | 48.51 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 114.70 | 65.50 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 99.43 | 26.69 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 74.94 | 0.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 146.21 | 66.22 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 122.76 | 78.62 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 123.94 | 63.74 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 116.75 | 39.43 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 102.29 | 14.89 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 101.45 | 3.24 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 104.19 | 2.56 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 96.37 | 0.94 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 89.10 | 2.69 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 99.76 | 8.49 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 154.45 | 32.22 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 174.55 | 57.66 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 137.08 | 77.79 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 118.49 | 31.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 89.10 | 0.94 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 174.55 | 78.62 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 103.01 | 65.20 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.87 | 53.20 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 97.86 | 33.09 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 85.85 | 12.70 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 85.13 | 2.90 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 87.36 | 2.28 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 80.67 | 0.86 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 74.67 | 2.39 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 83.70 | 7.41 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 129.49 | 27.27 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 146.26 | 48.35 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 114.92 | 64.89 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 99.35 | 26.59 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 74.67 | 0.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 146.26 | 65.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 103.01 | 65.20 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.87 | 53.20 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 97.86 | 33.09 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 85.85 | 12.70 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 85.13 | 2.90 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 87.36 | 2.28 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 80.67 | 0.86 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 74.67 | 2.39 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 83.70 | 7.41 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 129.49 | 27.27 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 146.26 | 48.35 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 114.92 | 64.89 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 99.35 | 26.59 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 74.67 | 0.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 146.26 | 65.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 123.17 | 77.41 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 124.13 | 63.16 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 116.78 | 39.34 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 102.17 | 15.11 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 101.04 | 3.47 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 103.69 | 2.71 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 95.80 | 1.03 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 88.78 | 2.85 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 99.65 | 8.82 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 154.40 | 32.45 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 174.61 | 57.48 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 137.35 | 77.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 118.40 | 31.60 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 88.78 | 1.03 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 174.61 | 77.41 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 103.50 | 64.04 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.17 | 52.46 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 98.03 | 32.61 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 86.05 | 12.36 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 85.41 | 2.74 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 87.72 | 2.18 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 80.97 | 0.77 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 74.93 | 2.22 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 83.84 | 7.08 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 129.59 | 26.90 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 146.43 | 47.89 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.27 | 64.12 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 99.61 | 26.16 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 74.93 | 0.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 146.43 | 64.12 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 103.50 | 64.04 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.17 | 52.46 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 98.03 | 32.61 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 86.05 | 12.36 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 85.41 | 2.74 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 87.72 | 2.18 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 80.97 | 0.77 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 74.93 | 2.22 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 83.84 | 7.08 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 129.59 | 26.90 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 146.43 | 47.89 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.27 | 64.12 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 99.61 | 26.16 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 74.93 | 0.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 146.43 | 64.12 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 123.75 | 76.03 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 124.49 | 62.29 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 116.99 | 38.77 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 102.41 | 14.72 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 101.38 | 3.28 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 104.11 | 2.59 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 96.15 | 0.93 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 89.09 | 2.66 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 99.81 | 8.43 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 154.53 | 32.01 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 174.81 | 56.93 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 137.77 | 76.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 118.71 | 31.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 89.09 | 0.93 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 174.81 | 76.15 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 104.74 | 61.33 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.98 | 50.54 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 98.45 | 31.11 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 86.42 | 11.33 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 85.92 | 2.28 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 88.51 | 1.91 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 81.37 | 0.54 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 75.32 | 1.72 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 83.94 | 6.09 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 129.64 | 25.70 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 146.77 | 46.56 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 116.18 | 62.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 100.13 | 25.00 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 75.32 | 0.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 146.77 | 62.21 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 104.74 | 61.33 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.98 | 50.54 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 98.45 | 31.11 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 86.42 | 11.33 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 85.92 | 2.28 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 88.51 | 1.91 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 81.37 | 0.54 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 75.32 | 1.72 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 83.94 | 6.09 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 129.64 | 25.70 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 146.77 | 46.56 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 116.18 | 62.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 100.13 | 25.00 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 75.32 | 0.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 146.77 | 62.21 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 104.74 | 61.33 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.98 | 50.54 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 98.45 | 31.11 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 86.42 | 11.33 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 85.92 | 2.28 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 88.51 | 1.91 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 81.37 | 0.54 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 75.32 | 1.72 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 83.94 | 6.09 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 129.64 | 25.70 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 146.77 | 46.56 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 116.18 | 62.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 100.13 | 25.00 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 75.32 | 0.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 146.77 | 62.21 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 104.74 | 61.33 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.98 | 50.54 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 98.45 | 31.11 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 86.42 | 11.33 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 85.92 | 2.28 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 88.51 | 1.91 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 81.37 | 0.54 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 75.32 | 1.72 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 83.94 | 6.09 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 129.64 | 25.70 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 146.77 | 46.56 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 116.18 | 62.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 100.13 | 25.00 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 75.32 | 0.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 146.77 | 62.21 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 125.23 | 72.81 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 125.46 | 60.01 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 117.50 | 37.00 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 102.87 | 13.48 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 102.00 | 2.73 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 105.08 | 2.27 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 96.66 | 0.65 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 89.57 | 2.06 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 99.95 | 7.25 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 154.60 | 30.58 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 175.22 | 55.35 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 138.85 | 73.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 119.35 | 29.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 89.57 | 0.65 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 175.22 | 73.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 125.23 | 72.81 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 125.46 | 60.01 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 117.50 | 37.00 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 102.87 | 13.48 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 102.00 | 2.73 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 105.08 | 2.27 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 96.66 | 0.65 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 89.57 | 2.06 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 99.95 | 7.25 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 154.60 | 30.58 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 175.22 | 55.35 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 138.85 | 73.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 119.35 | 29.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 89.57 | 0.65 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 175.22 | 73.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 104.76 | 60.95 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.94 | 50.28 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 98.55 | 30.76 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 86.93 | 10.97 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 86.92 | 2.08 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 89.63 | 1.79 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 82.42 | 0.45 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 76.09 | 1.52 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 84.37 | 5.65 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 129.81 | 25.24 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 146.76 | 46.23 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 116.15 | 61.97 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 100.56 | 24.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 76.09 | 0.45 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 146.76 | 61.97 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 104.76 | 60.95 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.94 | 50.28 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 98.55 | 30.76 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 86.93 | 10.97 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 86.92 | 2.08 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 89.63 | 1.79 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 82.42 | 0.45 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 76.09 | 1.52 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 84.37 | 5.65 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 129.81 | 25.24 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 146.76 | 46.23 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 116.15 | 61.97 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 100.56 | 24.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 76.09 | 0.45 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 146.76 | 61.97 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 125.28 | 72.36 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 125.44 | 59.69 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 117.63 | 36.57 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 103.48 | 13.06 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 103.18 | 2.49 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 106.40 | 2.12 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 97.90 | 0.54 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 90.49 | 1.81 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 100.47 | 6.72 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 154.81 | 30.03 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 175.23 | 54.95 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 138.83 | 73.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 119.87 | 29.36 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 90.49 | 0.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 175.23 | 73.59 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 104.96 | 60.54 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 105.09 | 49.98 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 98.64 | 30.58 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 87.03 | 10.88 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 87.04 | 2.04 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 89.76 | 1.76 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 82.55 | 0.44 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 76.20 | 1.48 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 84.44 | 5.57 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 129.86 | 25.14 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 146.84 | 46.09 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 116.31 | 61.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 100.67 | 24.57 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 76.20 | 0.44 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 146.84 | 61.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 104.96 | 60.54 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 105.09 | 49.98 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 98.64 | 30.58 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 87.03 | 10.88 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 87.04 | 2.04 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 89.76 | 1.76 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 82.55 | 0.44 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 76.20 | 1.48 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 84.44 | 5.57 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 129.86 | 25.14 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 146.84 | 46.09 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 116.31 | 61.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 100.67 | 24.57 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 76.20 | 0.44 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 146.84 | 61.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 125.51 | 71.87 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 125.61 | 59.34 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 117.73 | 36.37 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 103.60 | 12.94 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 103.32 | 2.45 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 106.56 | 2.09 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 98.05 | 0.53 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 90.61 | 1.77 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 100.55 | 6.63 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 154.88 | 29.90 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 175.32 | 54.78 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 139.02 | 73.25 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 120.00 | 29.19 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 90.61 | 0.53 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 175.32 | 73.25 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 105.32 | 59.65 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 105.40 | 49.26 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 98.79 | 30.20 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 87.01 | 10.78 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 86.88 | 2.06 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 89.52 | 1.78 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 82.22 | 0.45 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 75.94 | 1.54 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 84.31 | 5.67 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 129.82 | 25.14 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 146.95 | 45.82 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 116.65 | 61.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 100.68 | 24.33 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 75.94 | 0.45 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 146.95 | 61.00 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 105.32 | 59.65 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 105.40 | 49.26 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 98.79 | 30.20 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 87.01 | 10.78 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 86.88 | 2.06 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 89.52 | 1.78 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 82.22 | 0.45 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 75.94 | 1.54 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 84.31 | 5.67 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 129.82 | 25.14 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 146.95 | 45.82 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 116.65 | 61.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 100.68 | 24.33 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 75.94 | 0.45 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 146.95 | 61.00 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 125.95 | 70.82 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 125.99 | 58.48 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 117.91 | 35.91 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 103.58 | 12.83 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 103.13 | 2.47 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 106.27 | 2.11 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 97.66 | 0.55 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 90.30 | 1.84 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 100.40 | 6.76 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 154.83 | 29.91 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 175.45 | 54.46 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 139.43 | 72.44 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 120.01 | 28.92 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 90.30 | 0.55 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 175.45 | 72.44 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 105.83 | 57.09 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 105.90 | 46.81 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 98.82 | 28.75 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 86.04 | 10.55 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 84.87 | 2.26 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 87.02 | 1.93 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 79.35 | 0.62 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 73.60 | 2.05 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 82.88 | 6.69 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 129.00 | 25.62 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 146.86 | 44.99 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 117.18 | 58.84 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 99.72 | 23.75 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 73.60 | 0.62 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 146.86 | 58.84 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 105.83 | 57.09 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 105.90 | 46.81 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 98.82 | 28.75 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 86.04 | 10.55 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 84.87 | 2.26 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 87.02 | 1.93 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 79.35 | 0.62 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 73.60 | 2.05 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 82.88 | 6.69 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 129.00 | 25.62 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 146.86 | 44.99 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 117.18 | 58.84 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 99.72 | 23.75 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 73.60 | 0.62 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 146.86 | 58.84 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 126.56 | 67.78 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 126.59 | 55.58 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 117.95 | 34.20 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 102.41 | 12.56 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 100.72 | 2.72 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 103.27 | 2.29 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 94.23 | 0.75 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 87.49 | 2.45 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 98.68 | 7.97 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 153.83 | 30.49 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 175.34 | 53.48 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 140.06 | 69.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 118.85 | 28.22 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 87.49 | 0.75 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 175.34 | 69.88 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.276720E+09 | 0.174060E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.252464E+09 | 0.125413E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.263295E+09 | 82673691.11 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.226528E+09 | 27541885.34 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.236394E+09 | 5076179.83 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.234640E+09 | 3801767.73 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.226020E+09 | 1323794.23 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.205690E+09 | 3946201.96 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.219728E+09 | 13986748.16 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.347512E+09 | 65766947.61 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.379556E+09 | 0.120895E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.308652E+09 | 0.171920E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.317720E+10 | 0.796406E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.205690E+09 | 1323794.23 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.379556E+09 | 0.174060E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.276720E+09 | 0.174060E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.252464E+09 | 0.125413E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.263295E+09 | 82673691.11 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.226528E+09 | 27541885.34 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.236394E+09 | 5076179.83 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.234640E+09 | 3801767.73 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.226020E+09 | 1323794.23 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.205690E+09 | 3946201.96 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.219728E+09 | 13986748.16 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.347512E+09 | 65766947.61 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.379556E+09 | 0.120895E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.308652E+09 | 0.171920E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.317720E+10 | 0.796406E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.205690E+09 | 1323794.23 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.379556E+09 | 0.174060E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.276720E+09 | 0.174060E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.252464E+09 | 0.125413E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.263295E+09 | 82673691.11 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.226528E+09 | 27541885.34 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.236394E+09 | 5076179.83 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.234640E+09 | 3801767.73 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.226020E+09 | 1323794.23 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.205690E+09 | 3946201.96 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.219728E+09 | 13986748.16 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.347512E+09 | 65766947.61 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.379556E+09 | 0.120895E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.308652E+09 | 0.171920E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.317720E+10 | 0.796406E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.205690E+09 | 1323794.23 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.379556E+09 | 0.174060E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.276720E+09 | 0.174060E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.252464E+09 | 0.125413E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.263295E+09 | 82673691.11 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.226528E+09 | 27541885.34 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.236394E+09 | 5076179.83 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.234640E+09 | 3801767.73 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.226020E+09 | 1323794.23 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.205690E+09 | 3946201.96 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.219728E+09 | 13986748.16 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.347512E+09 | 65766947.61 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.379556E+09 | 0.120895E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.308652E+09 | 0.171920E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.317720E+10 | 0.796406E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.205690E+09 | 1323794.23 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.379556E+09 | 0.174060E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248181E+09 | 0.150827E+09 | 97354518.97 | 0.332637E+09 | 0.207888E+09 |
February | 0.213112E+09 | 0.118378E+09 | 94734419.52 | 0.303332E+09 | 0.149833E+09 |
March | 0.201672E+09 | 89050731.45 | 0.112622E+09 | 0.315896E+09 | 98969878.24 |
April | 0.137055E+09 | 38635516.98 | 98419012.29 | 0.270934E+09 | 33021343.74 |
May | 0.101831E+09 | 7480702.62 | 94349914.59 | 0.281862E+09 | 6123121.15 |
June | 90170610.98 | 1510838.69 | 88659772.29 | 0.279788E+09 | 4562501.63 |
July | 97206536.27 | 1321397.98 | 95885138.30 | 0.269596E+09 | 1601208.56 |
August | 0.103116E+09 | 5491590.03 | 97624287.37 | 0.245657E+09 | 4757845.45 |
September | 0.133773E+09 | 34703279.05 | 99069922.65 | 0.262843E+09 | 16800577.50 |
October | 0.237848E+09 | 0.132810E+09 | 0.105039E+09 | 0.416586E+09 | 78821129.43 |
November | 0.287593E+09 | 0.190121E+09 | 97472814.23 | 0.455566E+09 | 0.144638E+09 |
December | 0.265225E+09 | 0.166225E+09 | 98999985.37 | 0.370856E+09 | 0.205407E+09 |
Annual Sum or Average | 0.211678E+10 | 0.936554E+09 | 0.118023E+10 | 0.380555E+10 | 0.952425E+09 |
Minimum of Months | 90170610.98 | 1321397.98 | 88659772.29 | 0.245657E+09 | 1601208.56 |
Maximum of Months | 0.287593E+09 | 0.190121E+09 | 0.112622E+09 | 0.455566E+09 | 0.207888E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248181E+09 | 0.150827E+09 | 97354518.97 | 0.332637E+09 | 0.207888E+09 |
February | 0.213112E+09 | 0.118378E+09 | 94734419.52 | 0.303332E+09 | 0.149833E+09 |
March | 0.201672E+09 | 89050731.45 | 0.112622E+09 | 0.315896E+09 | 98969878.24 |
April | 0.137055E+09 | 38635516.98 | 98419012.29 | 0.270934E+09 | 33021343.74 |
May | 0.101831E+09 | 7480702.62 | 94349914.59 | 0.281862E+09 | 6123121.15 |
June | 90170610.98 | 1510838.69 | 88659772.29 | 0.279788E+09 | 4562501.63 |
July | 97206536.27 | 1321397.98 | 95885138.30 | 0.269596E+09 | 1601208.56 |
August | 0.103116E+09 | 5491590.03 | 97624287.37 | 0.245657E+09 | 4757845.45 |
September | 0.133773E+09 | 34703279.05 | 99069922.65 | 0.262843E+09 | 16800577.50 |
October | 0.237848E+09 | 0.132810E+09 | 0.105039E+09 | 0.416586E+09 | 78821129.43 |
November | 0.287593E+09 | 0.190121E+09 | 97472814.23 | 0.455566E+09 | 0.144638E+09 |
December | 0.265225E+09 | 0.166225E+09 | 98999985.37 | 0.370856E+09 | 0.205407E+09 |
Annual Sum or Average | 0.211678E+10 | 0.936554E+09 | 0.118023E+10 | 0.380555E+10 | 0.952425E+09 |
Minimum of Months | 90170610.98 | 1321397.98 | 88659772.29 | 0.245657E+09 | 1601208.56 |
Maximum of Months | 0.287593E+09 | 0.190121E+09 | 0.112622E+09 | 0.455566E+09 | 0.207888E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.273532E+09 | 0.180924E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.250402E+09 | 0.129282E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.262592E+09 | 84699458.38 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.227821E+09 | 28205825.59 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.239299E+09 | 5101959.26 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.238185E+09 | 3818582.85 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.229645E+09 | 1246416.30 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.208788E+09 | 3669596.10 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.221756E+09 | 13440382.13 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.348313E+09 | 65752736.09 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.378871E+09 | 0.122152E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.306216E+09 | 0.176322E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.318542E+10 | 0.814616E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.208788E+09 | 1246416.30 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.378871E+09 | 0.180924E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.273532E+09 | 0.180924E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.250402E+09 | 0.129282E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.262592E+09 | 84699458.38 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.227821E+09 | 28205825.59 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.239299E+09 | 5101959.26 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.238185E+09 | 3818582.85 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.229645E+09 | 1246416.30 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.208788E+09 | 3669596.10 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.221756E+09 | 13440382.13 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.348313E+09 | 65752736.09 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.378871E+09 | 0.122152E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.306216E+09 | 0.176322E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.318542E+10 | 0.814616E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.208788E+09 | 1246416.30 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.378871E+09 | 0.180924E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248181E+09 | 0.150827E+09 | 97354518.97 | 0.328846E+09 | 0.216035E+09 |
February | 0.213112E+09 | 0.118378E+09 | 94734419.52 | 0.300885E+09 | 0.154425E+09 |
March | 0.201672E+09 | 89050731.45 | 0.112622E+09 | 0.315067E+09 | 0.101375E+09 |
April | 0.137055E+09 | 38635516.98 | 98419012.29 | 0.272480E+09 | 33810269.80 |
May | 0.101831E+09 | 7480702.62 | 94349914.59 | 0.285331E+09 | 6153359.73 |
June | 90170610.98 | 1510838.69 | 88659772.29 | 0.284039E+09 | 4582258.97 |
July | 97206536.27 | 1321397.98 | 95885138.30 | 0.273941E+09 | 1508196.07 |
August | 0.103116E+09 | 5491590.03 | 97624287.37 | 0.249390E+09 | 4425276.20 |
September | 0.133773E+09 | 34703279.05 | 99069922.65 | 0.265308E+09 | 16143804.26 |
October | 0.237848E+09 | 0.132810E+09 | 0.105039E+09 | 0.417578E+09 | 78788843.08 |
November | 0.287593E+09 | 0.190121E+09 | 97472814.23 | 0.454778E+09 | 0.146125E+09 |
December | 0.265225E+09 | 0.166225E+09 | 98999985.37 | 0.367969E+09 | 0.210630E+09 |
Annual Sum or Average | 0.211678E+10 | 0.936554E+09 | 0.118023E+10 | 0.381561E+10 | 0.974002E+09 |
Minimum of Months | 90170610.98 | 1321397.98 | 88659772.29 | 0.249390E+09 | 1508196.07 |
Maximum of Months | 0.287593E+09 | 0.190121E+09 | 0.112622E+09 | 0.454778E+09 | 0.216035E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.274999E+09 | 0.177368E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.250889E+09 | 0.129871E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.262031E+09 | 88839943.18 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.222779E+09 | 32423469.84 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.228932E+09 | 7247839.76 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.227523E+09 | 5589264.77 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.217360E+09 | 2084163.75 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.200726E+09 | 6027190.94 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.217181E+09 | 18483922.88 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.346918E+09 | 72541983.70 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.378988E+09 | 0.125740E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.307218E+09 | 0.175446E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.313554E+10 | 0.841663E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.200726E+09 | 2084163.75 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.378988E+09 | 0.177368E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.274999E+09 | 0.177368E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.250889E+09 | 0.129871E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.262031E+09 | 88839943.18 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.222779E+09 | 32423469.84 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.228932E+09 | 7247839.76 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.227523E+09 | 5589264.77 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.217360E+09 | 2084163.75 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.200726E+09 | 6027190.94 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.217181E+09 | 18483922.88 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.346918E+09 | 72541983.70 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.378988E+09 | 0.125740E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.307218E+09 | 0.175446E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.313554E+10 | 0.841663E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.200726E+09 | 2084163.75 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.378988E+09 | 0.177368E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.328809E+09 | 0.210574E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.299831E+09 | 0.154193E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.312693E+09 | 0.105620E+09 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.265135E+09 | 38590058.39 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.271713E+09 | 8685969.29 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.270048E+09 | 6642359.21 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.258130E+09 | 2507003.30 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.238646E+09 | 7196181.79 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.258574E+09 | 22015425.03 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.413671E+09 | 86302369.20 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.452434E+09 | 0.149460E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.367161E+09 | 0.208352E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.373685E+10 | 0.100014E+10 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.238646E+09 | 2507003.30 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.452434E+09 | 0.210574E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.275914E+09 | 0.174634E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.251282E+09 | 0.128696E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.262101E+09 | 88637036.39 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.222527E+09 | 32908515.73 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.228018E+09 | 7766387.10 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.226437E+09 | 5917939.83 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.216059E+09 | 2290215.74 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.200006E+09 | 6401596.61 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.216954E+09 | 19205036.76 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.346822E+09 | 73045568.99 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.379118E+09 | 0.125335E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.307810E+09 | 0.173790E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.313305E+10 | 0.838628E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.200006E+09 | 2290215.74 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.379118E+09 | 0.174634E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.275914E+09 | 0.174634E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.251282E+09 | 0.128696E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.262101E+09 | 88637036.39 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.222527E+09 | 32908515.73 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.228018E+09 | 7766387.10 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.226437E+09 | 5917939.83 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.216059E+09 | 2290215.74 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.200006E+09 | 6401596.61 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.216954E+09 | 19205036.76 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.346822E+09 | 73045568.99 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.379118E+09 | 0.125335E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.307810E+09 | 0.173790E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.313305E+10 | 0.838628E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.200006E+09 | 2290215.74 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.379118E+09 | 0.174634E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.329907E+09 | 0.207326E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.300303E+09 | 0.152798E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.312778E+09 | 0.105380E+09 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.264834E+09 | 39166491.03 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.270624E+09 | 9304831.69 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.268753E+09 | 7033537.88 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.256584E+09 | 2755554.90 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.237789E+09 | 7642590.89 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.258302E+09 | 22871750.80 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.413555E+09 | 86901447.43 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.452591E+09 | 0.148978E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.367872E+09 | 0.206385E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.373389E+10 | 0.996543E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.237789E+09 | 2755554.90 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.452591E+09 | 0.207326E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.277205E+09 | 0.171531E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.252008E+09 | 0.126909E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.262565E+09 | 87332922.81 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.223038E+09 | 32044598.44 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.228775E+09 | 7328458.92 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.227363E+09 | 5654314.70 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.216866E+09 | 2064162.54 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.200693E+09 | 5956908.62 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.217302E+09 | 18349023.86 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.347107E+09 | 72061975.06 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.379545E+09 | 0.124137E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.308752E+09 | 0.171743E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.314122E+10 | 0.825112E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.200693E+09 | 2064162.54 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.379545E+09 | 0.171743E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.277205E+09 | 0.171531E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.252008E+09 | 0.126909E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.262565E+09 | 87332922.81 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.223038E+09 | 32044598.44 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.228775E+09 | 7328458.92 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.227363E+09 | 5654314.70 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.216866E+09 | 2064162.54 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.200693E+09 | 5956908.62 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.217302E+09 | 18349023.86 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.347107E+09 | 72061975.06 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.379545E+09 | 0.124137E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.308752E+09 | 0.171743E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.314122E+10 | 0.825112E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.200693E+09 | 2064162.54 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.379545E+09 | 0.171743E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.331454E+09 | 0.203646E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.301177E+09 | 0.150684E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.313340E+09 | 0.103839E+09 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.265449E+09 | 38145017.02 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.271524E+09 | 8784807.20 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.269854E+09 | 6721128.07 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.257539E+09 | 2485932.57 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.238607E+09 | 7115972.67 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.258720E+09 | 21860538.03 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.413901E+09 | 85738101.03 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.453107E+09 | 0.147559E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.369002E+09 | 0.203959E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.374367E+10 | 0.980538E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.238607E+09 | 2485932.57 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.453107E+09 | 0.203959E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.280533E+09 | 0.164253E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.253973E+09 | 0.122274E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.263692E+09 | 83335661.69 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.223999E+09 | 29363047.05 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.230119E+09 | 6116059.59 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.229430E+09 | 4958542.77 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.217953E+09 | 1450424.80 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.201739E+09 | 4615142.99 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.217577E+09 | 15776563.33 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.347222E+09 | 68837903.28 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.380425E+09 | 0.120689E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.311171E+09 | 0.166630E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.315783E+10 | 0.788300E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.201739E+09 | 1450424.80 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.380425E+09 | 0.166630E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.280533E+09 | 0.164253E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.253973E+09 | 0.122274E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.263692E+09 | 83335661.69 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.223999E+09 | 29363047.05 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.230119E+09 | 6116059.59 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.229430E+09 | 4958542.77 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.217953E+09 | 1450424.80 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.201739E+09 | 4615142.99 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.217577E+09 | 15776563.33 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.347222E+09 | 68837903.28 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.380425E+09 | 0.120689E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.311171E+09 | 0.166630E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.315783E+10 | 0.788300E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.201739E+09 | 1450424.80 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.380425E+09 | 0.166630E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.280533E+09 | 0.164253E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.253973E+09 | 0.122274E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.263692E+09 | 83335661.69 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.223999E+09 | 29363047.05 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.230119E+09 | 6116059.59 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.229430E+09 | 4958542.77 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.217953E+09 | 1450424.80 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.201739E+09 | 4615142.99 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.217577E+09 | 15776563.33 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.347222E+09 | 68837903.28 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.380425E+09 | 0.120689E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.311171E+09 | 0.166630E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.315783E+10 | 0.788300E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.201739E+09 | 1450424.80 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.380425E+09 | 0.166630E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.280533E+09 | 0.164253E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.253973E+09 | 0.122274E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.263692E+09 | 83335661.69 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.223999E+09 | 29363047.05 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.230119E+09 | 6116059.59 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.229430E+09 | 4958542.77 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.217953E+09 | 1450424.80 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.201739E+09 | 4615142.99 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.217577E+09 | 15776563.33 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.347222E+09 | 68837903.28 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.380425E+09 | 0.120689E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.311171E+09 | 0.166630E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.315783E+10 | 0.788300E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.201739E+09 | 1450424.80 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.380425E+09 | 0.166630E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.335417E+09 | 0.195013E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.303521E+09 | 0.145188E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.314710E+09 | 99094284.33 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.266641E+09 | 34945373.07 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.273184E+09 | 7323494.11 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.272369E+09 | 5886002.15 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.258895E+09 | 1745706.39 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.239896E+09 | 5512433.97 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.259077E+09 | 18786441.54 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.414068E+09 | 81898508.49 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.454169E+09 | 0.143461E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.371884E+09 | 0.197885E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.376383E+10 | 0.936739E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.239896E+09 | 1745706.39 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.454169E+09 | 0.197885E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.335417E+09 | 0.195013E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.303521E+09 | 0.145188E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.314710E+09 | 99094284.33 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.266641E+09 | 34945373.07 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.273184E+09 | 7323494.11 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.272369E+09 | 5886002.15 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.258895E+09 | 1745706.39 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.239896E+09 | 5512433.97 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.259077E+09 | 18786441.54 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.414068E+09 | 81898508.49 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.454169E+09 | 0.143461E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.371884E+09 | 0.197885E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.376383E+10 | 0.936739E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.239896E+09 | 1745706.39 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.454169E+09 | 0.197885E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.280602E+09 | 0.163258E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.253880E+09 | 0.121627E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.263946E+09 | 82376167.97 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.225332E+09 | 28442181.37 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.232802E+09 | 5576176.98 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.232313E+09 | 4637384.82 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.220764E+09 | 1210477.04 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.203807E+09 | 4060880.18 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.218688E+09 | 14633631.54 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.347681E+09 | 67610565.37 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.380405E+09 | 0.119840E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.311105E+09 | 0.165985E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.317133E+10 | 0.779258E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.203807E+09 | 1210477.04 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.380405E+09 | 0.165985E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.280602E+09 | 0.163258E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.253880E+09 | 0.121627E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.263946E+09 | 82376167.97 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.225332E+09 | 28442181.37 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.232802E+09 | 5576176.98 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.232313E+09 | 4637384.82 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.220764E+09 | 1210477.04 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.203807E+09 | 4060880.18 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.218688E+09 | 14633631.54 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.347681E+09 | 67610565.37 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.380405E+09 | 0.119840E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.311105E+09 | 0.165985E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.317133E+10 | 0.779258E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.203807E+09 | 1210477.04 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.380405E+09 | 0.165985E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.335551E+09 | 0.193807E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.303459E+09 | 0.144402E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.315053E+09 | 97946926.88 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.268233E+09 | 33851247.92 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.276354E+09 | 6682193.37 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.275787E+09 | 5502815.60 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.262221E+09 | 1457939.21 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.242361E+09 | 4850446.49 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.260426E+09 | 17425450.10 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.414653E+09 | 80433316.21 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.454196E+09 | 0.142441E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.371855E+09 | 0.197098E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.378015E+10 | 0.925898E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.242361E+09 | 1457939.21 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.454196E+09 | 0.197098E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.281116E+09 | 0.162157E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.254230E+09 | 0.120922E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.264185E+09 | 81917355.03 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.225572E+09 | 28188567.27 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.233125E+09 | 5473531.99 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.232670E+09 | 4571081.89 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.221099E+09 | 1172931.70 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.204082E+09 | 3972261.52 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.218862E+09 | 14432080.99 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.347820E+09 | 67326312.79 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.380597E+09 | 0.119456E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.311526E+09 | 0.165220E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.317489E+10 | 0.774809E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.204082E+09 | 1172931.70 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.380597E+09 | 0.165220E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.281116E+09 | 0.162157E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.254230E+09 | 0.120922E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.264185E+09 | 81917355.03 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.225572E+09 | 28188567.27 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.233125E+09 | 5473531.99 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.232670E+09 | 4571081.89 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.221099E+09 | 1172931.70 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.204082E+09 | 3972261.52 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.218862E+09 | 14432080.99 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.347820E+09 | 67326312.79 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.380597E+09 | 0.119456E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.311526E+09 | 0.165220E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.317489E+10 | 0.774809E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.204082E+09 | 1172931.70 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.380597E+09 | 0.165220E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.336167E+09 | 0.192500E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.303880E+09 | 0.143564E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.315340E+09 | 97401584.69 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.268522E+09 | 33549468.30 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.276740E+09 | 6559489.93 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.276214E+09 | 5423534.32 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.262622E+09 | 1413033.90 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.242691E+09 | 4744878.45 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.260636E+09 | 17185028.51 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.414822E+09 | 80095295.46 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.454429E+09 | 0.141983E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.372360E+09 | 0.196190E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.378442E+10 | 0.920610E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.242691E+09 | 1413033.90 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.454429E+09 | 0.196190E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.282091E+09 | 0.159776E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.254994E+09 | 0.119160E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.264586E+09 | 80879803.79 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.225540E+09 | 27936537.18 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.232689E+09 | 5521805.51 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.232047E+09 | 4604242.46 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.220217E+09 | 1214368.52 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.203390E+09 | 4112748.36 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.218531E+09 | 14707634.61 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.347721E+09 | 67339035.24 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.380887E+09 | 0.118765E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.312446E+09 | 0.163388E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.317514E+10 | 0.767404E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.203390E+09 | 1214368.52 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.380887E+09 | 0.163388E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.282091E+09 | 0.159776E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.254994E+09 | 0.119160E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.264586E+09 | 80879803.79 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.225540E+09 | 27936537.18 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.232689E+09 | 5521805.51 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.232047E+09 | 4604242.46 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.220217E+09 | 1214368.52 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.203390E+09 | 4112748.36 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.218531E+09 | 14707634.61 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.347721E+09 | 67339035.24 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.380887E+09 | 0.118765E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.312446E+09 | 0.163388E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.317514E+10 | 0.767404E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.203390E+09 | 1214368.52 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.380887E+09 | 0.163388E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.337333E+09 | 0.189682E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.304795E+09 | 0.141480E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.315823E+09 | 96177308.18 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.268482E+09 | 33255583.64 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.276212E+09 | 6620867.49 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.275461E+09 | 5465354.02 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.261561E+09 | 1463514.31 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.241858E+09 | 4916022.35 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.260235E+09 | 17520229.16 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.414702E+09 | 80117974.11 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.454775E+09 | 0.141168E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.373458E+09 | 0.194019E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.378470E+10 | 0.911886E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.241858E+09 | 1463514.31 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.454775E+09 | 0.194019E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.283454E+09 | 0.152920E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.256202E+09 | 0.113239E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.264667E+09 | 77009365.25 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.223024E+09 | 27348306.22 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.227328E+09 | 6065412.69 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.225555E+09 | 4996249.14 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.212535E+09 | 1672382.73 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.197120E+09 | 5485451.89 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.214837E+09 | 17350769.15 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.345512E+09 | 68633863.96 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.380656E+09 | 0.116607E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.313846E+09 | 0.157610E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.314473E+10 | 0.748937E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.197120E+09 | 1672382.73 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.380656E+09 | 0.157610E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.283454E+09 | 0.152920E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.256202E+09 | 0.113239E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.264667E+09 | 77009365.25 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.223024E+09 | 27348306.22 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.227328E+09 | 6065412.69 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.225555E+09 | 4996249.14 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.212535E+09 | 1672382.73 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.197120E+09 | 5485451.89 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.214837E+09 | 17350769.15 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.345512E+09 | 68633863.96 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.380656E+09 | 0.116607E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.313846E+09 | 0.157610E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.314473E+10 | 0.748937E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.197120E+09 | 1672382.73 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.380656E+09 | 0.157610E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.338978E+09 | 0.181553E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.306238E+09 | 0.134464E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.315909E+09 | 91592448.99 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.265441E+09 | 32557692.56 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.269771E+09 | 7272340.90 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.267672E+09 | 5933902.90 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.252374E+09 | 2016976.82 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.234334E+09 | 6555863.09 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.255774E+09 | 20665908.23 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.412019E+09 | 81662717.74 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.454479E+09 | 0.138611E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.375128E+09 | 0.187167E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.374812E+10 | 0.890054E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.234334E+09 | 2016976.82 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.454479E+09 | 0.187167E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 661.65 | 415.18 | 493.18 | 299.72 | 193.46 | 0.00 | 0.00 |
February | 668.20 | 331.23 | 468.86 | 260.44 | 208.42 | 0.00 | 0.00 |
March | 629.10 | 197.37 | 400.76 | 176.96 | 223.80 | 0.00 | 0.00 |
April | 558.63 | 67.98 | 281.43 | 79.33 | 202.09 | 0.00 | 0.00 |
May | 563.51 | 12.15 | 202.35 | 14.87 | 187.49 | 0.00 | 0.00 |
June | 577.99 | 9.39 | 185.16 | 3.10 | 182.05 | 0.00 | 0.00 |
July | 538.86 | 3.17 | 193.16 | 2.63 | 190.54 | 0.00 | 0.00 |
August | 490.62 | 9.45 | 204.91 | 10.91 | 193.99 | 0.00 | 0.00 |
September | 541.90 | 34.55 | 274.69 | 71.26 | 203.43 | 0.00 | 0.00 |
October | 830.05 | 157.07 | 472.64 | 263.91 | 208.73 | 0.00 | 0.00 |
November | 937.25 | 298.17 | 590.54 | 390.39 | 200.15 | 0.00 | 0.00 |
December | 737.87 | 410.13 | 527.04 | 330.31 | 196.73 | 0.00 | 0.00 |
Annual Sum or Average | 644.34 | 161.42 | 357.25 | 158.06 | 199.19 | 0.00 | 0.00 |
Minimum of Months | 490.62 | 3.17 | 185.16 | 2.63 | 182.05 | 0.00 | 0.00 |
Maximum of Months | 937.25 | 415.18 | 590.54 | 390.39 | 223.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 327.03 | 215.76 | 246.59 | 149.86 | 96.73 | 0.00 | 0.00 |
February | 331.39 | 170.71 | 234.43 | 130.22 | 104.21 | 0.00 | 0.00 |
March | 313.71 | 101.10 | 200.38 | 88.48 | 111.90 | 0.00 | 0.00 |
April | 280.91 | 34.81 | 140.71 | 39.67 | 101.05 | 0.00 | 0.00 |
May | 285.22 | 6.11 | 101.18 | 7.43 | 93.74 | 0.00 | 0.00 |
June | 293.37 | 4.71 | 92.58 | 1.55 | 91.03 | 0.00 | 0.00 |
July | 273.76 | 1.49 | 96.58 | 1.31 | 95.27 | 0.00 | 0.00 |
August | 249.02 | 4.39 | 102.45 | 5.46 | 97.00 | 0.00 | 0.00 |
September | 273.46 | 16.60 | 137.34 | 35.63 | 101.71 | 0.00 | 0.00 |
October | 416.00 | 78.51 | 236.32 | 131.96 | 104.36 | 0.00 | 0.00 |
November | 467.79 | 150.63 | 295.27 | 195.20 | 100.08 | 0.00 | 0.00 |
December | 366.04 | 210.30 | 263.52 | 165.16 | 98.36 | 0.00 | 0.00 |
Annual Sum or Average | 323.01 | 82.55 | 178.63 | 79.03 | 99.60 | 0.00 | 0.00 |
Minimum of Months | 249.02 | 1.49 | 92.58 | 1.31 | 91.03 | 0.00 | 0.00 |
Maximum of Months | 467.79 | 215.76 | 295.27 | 195.20 | 111.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 328.11 | 211.06 | 246.08 | 149.55 | 96.53 | 0.00 | 0.00 |
February | 331.35 | 171.10 | 233.95 | 129.95 | 104.00 | 0.00 | 0.00 |
March | 312.41 | 105.77 | 199.97 | 88.30 | 111.67 | 0.00 | 0.00 |
April | 274.19 | 39.91 | 140.42 | 39.59 | 100.84 | 0.00 | 0.00 |
May | 272.39 | 8.65 | 100.97 | 7.42 | 93.55 | 0.00 | 0.00 |
June | 279.74 | 6.88 | 92.39 | 1.55 | 90.84 | 0.00 | 0.00 |
July | 258.68 | 2.49 | 96.38 | 1.31 | 95.07 | 0.00 | 0.00 |
August | 238.99 | 7.19 | 102.24 | 5.45 | 96.80 | 0.00 | 0.00 |
September | 267.34 | 22.76 | 137.06 | 35.56 | 101.51 | 0.00 | 0.00 |
October | 413.50 | 86.39 | 235.84 | 131.69 | 104.15 | 0.00 | 0.00 |
November | 466.98 | 154.68 | 294.67 | 194.80 | 99.87 | 0.00 | 0.00 |
December | 366.49 | 208.80 | 262.98 | 164.82 | 98.16 | 0.00 | 0.00 |
Annual Sum or Average | 317.35 | 85.09 | 178.26 | 78.87 | 99.39 | 0.00 | 0.00 |
Minimum of Months | 238.99 | 2.49 | 92.39 | 1.31 | 90.84 | 0.00 | 0.00 |
Maximum of Months | 466.98 | 211.06 | 294.67 | 194.80 | 111.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 329.20 | 207.81 | 246.08 | 149.55 | 96.53 | 0.00 | 0.00 |
February | 331.87 | 169.56 | 233.95 | 129.95 | 104.00 | 0.00 | 0.00 |
March | 312.49 | 105.53 | 199.97 | 88.30 | 111.67 | 0.00 | 0.00 |
April | 273.88 | 40.50 | 140.42 | 39.59 | 100.84 | 0.00 | 0.00 |
May | 271.30 | 9.27 | 100.97 | 7.42 | 93.55 | 0.00 | 0.00 |
June | 278.41 | 7.28 | 92.39 | 1.55 | 90.84 | 0.00 | 0.00 |
July | 257.13 | 2.74 | 96.38 | 1.31 | 95.07 | 0.00 | 0.00 |
August | 238.13 | 7.63 | 102.24 | 5.45 | 96.80 | 0.00 | 0.00 |
September | 267.06 | 23.64 | 137.06 | 35.56 | 101.51 | 0.00 | 0.00 |
October | 413.38 | 86.99 | 235.84 | 131.69 | 104.15 | 0.00 | 0.00 |
November | 467.14 | 154.19 | 294.67 | 194.80 | 99.87 | 0.00 | 0.00 |
December | 367.19 | 206.83 | 262.98 | 164.82 | 98.16 | 0.00 | 0.00 |
Annual Sum or Average | 317.10 | 84.79 | 178.26 | 78.87 | 99.39 | 0.00 | 0.00 |
Minimum of Months | 238.13 | 2.74 | 92.39 | 1.31 | 90.84 | 0.00 | 0.00 |
Maximum of Months | 467.14 | 207.81 | 294.67 | 194.80 | 111.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 330.74 | 204.12 | 246.08 | 149.55 | 96.53 | 0.00 | 0.00 |
February | 332.83 | 167.20 | 233.95 | 129.95 | 104.00 | 0.00 | 0.00 |
March | 313.05 | 103.98 | 199.97 | 88.30 | 111.67 | 0.00 | 0.00 |
April | 274.51 | 39.44 | 140.42 | 39.59 | 100.84 | 0.00 | 0.00 |
May | 272.21 | 8.75 | 100.97 | 7.42 | 93.55 | 0.00 | 0.00 |
June | 279.54 | 6.96 | 92.39 | 1.55 | 90.84 | 0.00 | 0.00 |
July | 258.09 | 2.47 | 96.38 | 1.31 | 95.07 | 0.00 | 0.00 |
August | 238.95 | 7.10 | 102.24 | 5.45 | 96.80 | 0.00 | 0.00 |
September | 267.49 | 22.59 | 137.06 | 35.56 | 101.51 | 0.00 | 0.00 |
October | 413.72 | 85.82 | 235.84 | 131.69 | 104.15 | 0.00 | 0.00 |
November | 467.67 | 152.71 | 294.67 | 194.80 | 99.87 | 0.00 | 0.00 |
December | 368.32 | 204.39 | 262.98 | 164.82 | 98.16 | 0.00 | 0.00 |
Annual Sum or Average | 317.93 | 83.42 | 178.26 | 78.87 | 99.39 | 0.00 | 0.00 |
Minimum of Months | 238.95 | 2.47 | 92.39 | 1.31 | 90.84 | 0.00 | 0.00 |
Maximum of Months | 467.67 | 204.39 | 294.67 | 194.80 | 111.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 669.42 | 390.92 | 492.16 | 299.10 | 193.06 | 0.00 | 0.00 |
February | 670.86 | 322.20 | 467.90 | 259.90 | 207.99 | 0.00 | 0.00 |
March | 628.80 | 198.45 | 399.93 | 176.59 | 223.34 | 0.00 | 0.00 |
April | 551.42 | 72.28 | 280.85 | 79.17 | 201.68 | 0.00 | 0.00 |
May | 547.66 | 14.60 | 201.94 | 14.83 | 187.10 | 0.00 | 0.00 |
June | 564.22 | 12.19 | 184.78 | 3.10 | 181.68 | 0.00 | 0.00 |
July | 518.82 | 3.47 | 192.77 | 2.62 | 190.15 | 0.00 | 0.00 |
August | 480.42 | 11.01 | 204.49 | 10.89 | 193.60 | 0.00 | 0.00 |
September | 535.67 | 38.84 | 274.13 | 71.11 | 203.01 | 0.00 | 0.00 |
October | 827.74 | 163.96 | 471.67 | 263.37 | 208.30 | 0.00 | 0.00 |
November | 937.52 | 296.94 | 589.33 | 389.59 | 199.74 | 0.00 | 0.00 |
December | 742.40 | 396.61 | 525.96 | 329.64 | 196.32 | 0.00 | 0.00 |
Annual Sum or Average | 639.24 | 159.39 | 356.52 | 157.74 | 198.78 | 0.00 | 0.00 |
Minimum of Months | 480.42 | 3.47 | 184.78 | 2.62 | 181.68 | 0.00 | 0.00 |
Maximum of Months | 937.52 | 396.61 | 589.33 | 389.59 | 223.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 334.81 | 194.27 | 246.08 | 149.55 | 96.53 | 0.00 | 0.00 |
February | 335.33 | 160.24 | 233.95 | 129.95 | 104.00 | 0.00 | 0.00 |
March | 314.72 | 98.08 | 199.97 | 88.30 | 111.67 | 0.00 | 0.00 |
April | 277.35 | 35.01 | 140.42 | 39.59 | 100.84 | 0.00 | 0.00 |
May | 277.02 | 6.66 | 100.97 | 7.42 | 93.55 | 0.00 | 0.00 |
June | 285.65 | 5.70 | 92.39 | 1.55 | 90.84 | 0.00 | 0.00 |
July | 262.75 | 1.45 | 96.38 | 1.31 | 95.07 | 0.00 | 0.00 |
August | 242.67 | 4.84 | 102.24 | 5.45 | 96.80 | 0.00 | 0.00 |
September | 269.21 | 18.01 | 137.06 | 35.56 | 101.51 | 0.00 | 0.00 |
October | 414.43 | 80.52 | 235.84 | 131.69 | 104.15 | 0.00 | 0.00 |
November | 468.75 | 147.42 | 294.67 | 194.80 | 99.87 | 0.00 | 0.00 |
December | 371.14 | 197.53 | 262.98 | 164.82 | 98.16 | 0.00 | 0.00 |
Annual Sum or Average | 320.99 | 78.78 | 178.26 | 78.87 | 99.39 | 0.00 | 0.00 |
Minimum of Months | 242.67 | 1.45 | 92.39 | 1.31 | 90.84 | 0.00 | 0.00 |
Maximum of Months | 468.75 | 197.53 | 294.67 | 194.80 | 111.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 335.42 | 192.96 | 246.08 | 149.55 | 96.53 | 0.00 | 0.00 |
February | 335.79 | 159.31 | 233.95 | 129.95 | 104.00 | 0.00 | 0.00 |
March | 315.01 | 97.53 | 199.97 | 88.30 | 111.67 | 0.00 | 0.00 |
April | 277.65 | 34.69 | 140.42 | 39.59 | 100.84 | 0.00 | 0.00 |
May | 277.40 | 6.54 | 100.97 | 7.42 | 93.55 | 0.00 | 0.00 |
June | 286.09 | 5.62 | 92.39 | 1.55 | 90.84 | 0.00 | 0.00 |
July | 263.15 | 1.40 | 96.38 | 1.31 | 95.07 | 0.00 | 0.00 |
August | 243.00 | 4.74 | 102.24 | 5.45 | 96.80 | 0.00 | 0.00 |
September | 269.43 | 17.77 | 137.06 | 35.56 | 101.51 | 0.00 | 0.00 |
October | 414.60 | 80.18 | 235.84 | 131.69 | 104.15 | 0.00 | 0.00 |
November | 468.99 | 146.95 | 294.67 | 194.80 | 99.87 | 0.00 | 0.00 |
December | 371.64 | 196.62 | 262.98 | 164.82 | 98.16 | 0.00 | 0.00 |
Annual Sum or Average | 321.35 | 78.33 | 178.26 | 78.87 | 99.39 | 0.00 | 0.00 |
Minimum of Months | 243.00 | 1.40 | 92.39 | 1.31 | 90.84 | 0.00 | 0.00 |
Maximum of Months | 468.99 | 196.62 | 294.67 | 194.80 | 111.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 336.59 | 190.13 | 246.08 | 149.55 | 96.53 | 0.00 | 0.00 |
February | 336.80 | 156.99 | 233.95 | 129.95 | 104.00 | 0.00 | 0.00 |
March | 315.49 | 96.30 | 199.97 | 88.30 | 111.67 | 0.00 | 0.00 |
April | 277.61 | 34.39 | 140.42 | 39.59 | 100.84 | 0.00 | 0.00 |
May | 276.88 | 6.60 | 100.97 | 7.42 | 93.55 | 0.00 | 0.00 |
June | 285.32 | 5.66 | 92.39 | 1.55 | 90.84 | 0.00 | 0.00 |
July | 262.10 | 1.45 | 96.38 | 1.31 | 95.07 | 0.00 | 0.00 |
August | 242.17 | 4.91 | 102.24 | 5.45 | 96.80 | 0.00 | 0.00 |
September | 269.02 | 18.11 | 137.06 | 35.56 | 101.51 | 0.00 | 0.00 |
October | 414.48 | 80.20 | 235.84 | 131.69 | 104.15 | 0.00 | 0.00 |
November | 469.35 | 146.10 | 294.67 | 194.80 | 99.87 | 0.00 | 0.00 |
December | 372.74 | 194.44 | 262.98 | 164.82 | 98.16 | 0.00 | 0.00 |
Annual Sum or Average | 321.38 | 77.58 | 178.26 | 78.87 | 99.39 | 0.00 | 0.00 |
Minimum of Months | 242.17 | 1.45 | 92.39 | 1.31 | 90.84 | 0.00 | 0.00 |
Maximum of Months | 469.35 | 194.44 | 294.67 | 194.80 | 111.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 338.22 | 181.97 | 246.08 | 149.55 | 96.53 | 0.00 | 0.00 |
February | 338.39 | 149.20 | 233.95 | 129.95 | 104.00 | 0.00 | 0.00 |
March | 315.58 | 91.70 | 199.97 | 88.30 | 111.67 | 0.00 | 0.00 |
April | 274.49 | 33.66 | 140.42 | 39.59 | 100.84 | 0.00 | 0.00 |
May | 270.47 | 7.24 | 100.97 | 7.42 | 93.55 | 0.00 | 0.00 |
June | 277.31 | 6.14 | 92.39 | 1.55 | 90.84 | 0.00 | 0.00 |
July | 252.93 | 2.00 | 96.38 | 1.31 | 95.07 | 0.00 | 0.00 |
August | 234.68 | 6.54 | 102.24 | 5.45 | 96.80 | 0.00 | 0.00 |
September | 264.45 | 21.36 | 137.06 | 35.56 | 101.51 | 0.00 | 0.00 |
October | 411.83 | 81.74 | 235.84 | 131.69 | 104.15 | 0.00 | 0.00 |
November | 469.06 | 143.45 | 294.67 | 194.80 | 99.87 | 0.00 | 0.00 |
December | 374.41 | 187.57 | 262.98 | 164.82 | 98.16 | 0.00 | 0.00 |
Annual Sum or Average | 318.29 | 75.72 | 178.26 | 78.87 | 99.39 | 0.00 | 0.00 |
Minimum of Months | 234.68 | 2.00 | 92.39 | 1.31 | 90.84 | 0.00 | 0.00 |
Maximum of Months | 469.06 | 187.57 | 294.67 | 194.80 | 111.67 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.177215E+10 | 0.111202E+10 | 0.132092E+10 | 0.802760E+09 | 0.518160E+09 | 0.00 | 0.00 |
February | 0.161652E+10 | 0.801319E+09 | 0.113427E+10 | 0.630055E+09 | 0.504215E+09 | 0.00 | 0.00 |
March | 0.168497E+10 | 0.528634E+09 | 0.107338E+10 | 0.473964E+09 | 0.599418E+09 | 0.00 | 0.00 |
April | 0.144798E+10 | 0.176209E+09 | 0.729460E+09 | 0.205634E+09 | 0.523826E+09 | 0.00 | 0.00 |
May | 0.150930E+10 | 32550063.77 | 0.541984E+09 | 39815324.31 | 0.502168E+09 | 0.00 | 0.00 |
June | 0.149814E+10 | 24331855.76 | 0.479924E+09 | 8041294.43 | 0.471883E+09 | 0.00 | 0.00 |
July | 0.144327E+10 | 8496904.40 | 0.517372E+09 | 7033014.36 | 0.510339E+09 | 0.00 | 0.00 |
August | 0.131407E+10 | 25299404.86 | 0.548824E+09 | 29228462.76 | 0.519596E+09 | 0.00 | 0.00 |
September | 0.140459E+10 | 89547048.59 | 0.711995E+09 | 0.184705E+09 | 0.527290E+09 | 0.00 | 0.00 |
October | 0.222322E+10 | 0.420710E+09 | 0.126592E+10 | 0.706866E+09 | 0.559059E+09 | 0.00 | 0.00 |
November | 0.242936E+10 | 0.772855E+09 | 0.153069E+10 | 0.101190E+10 | 0.518790E+09 | 0.00 | 0.00 |
December | 0.197632E+10 | 0.109850E+10 | 0.141163E+10 | 0.884714E+09 | 0.526918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.203199E+11 | 0.509046E+10 | 0.112664E+11 | 0.498472E+10 | 0.628166E+10 | 0.00 | 0.00 |
Minimum of Months | 0.131407E+10 | 8496904.40 | 0.479924E+09 | 7033014.36 | 0.471883E+09 | 0.00 | 0.00 |
Maximum of Months | 0.242936E+10 | 0.111202E+10 | 0.153069E+10 | 0.101190E+10 | 0.599418E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.875909E+09 | 0.577883E+09 | 0.660460E+09 | 0.401380E+09 | 0.259080E+09 | 0.00 | 0.00 |
February | 0.801688E+09 | 0.412988E+09 | 0.567135E+09 | 0.315028E+09 | 0.252107E+09 | 0.00 | 0.00 |
March | 0.840250E+09 | 0.270774E+09 | 0.536691E+09 | 0.236982E+09 | 0.299709E+09 | 0.00 | 0.00 |
April | 0.728121E+09 | 90221607.62 | 0.364730E+09 | 0.102817E+09 | 0.261913E+09 | 0.00 | 0.00 |
May | 0.763929E+09 | 16357133.64 | 0.270992E+09 | 19907662.15 | 0.251084E+09 | 0.00 | 0.00 |
June | 0.760408E+09 | 12219251.42 | 0.239962E+09 | 4020647.22 | 0.235942E+09 | 0.00 | 0.00 |
July | 0.733230E+09 | 4000983.80 | 0.258686E+09 | 3516507.18 | 0.255170E+09 | 0.00 | 0.00 |
August | 0.666966E+09 | 11763874.06 | 0.274412E+09 | 14614231.38 | 0.259798E+09 | 0.00 | 0.00 |
September | 0.708820E+09 | 43023979.06 | 0.355998E+09 | 92352442.07 | 0.263645E+09 | 0.00 | 0.00 |
October | 0.111420E+10 | 0.210294E+09 | 0.632962E+09 | 0.353433E+09 | 0.279529E+09 | 0.00 | 0.00 |
November | 0.121252E+10 | 0.390429E+09 | 0.765344E+09 | 0.505950E+09 | 0.259395E+09 | 0.00 | 0.00 |
December | 0.980401E+09 | 0.563274E+09 | 0.705816E+09 | 0.442357E+09 | 0.263459E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101864E+11 | 0.260323E+10 | 0.563319E+10 | 0.249236E+10 | 0.314083E+10 | 0.00 | 0.00 |
Minimum of Months | 0.666966E+09 | 4000983.80 | 0.239962E+09 | 3516507.18 | 0.235942E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121252E+10 | 0.577883E+09 | 0.765344E+09 | 0.505950E+09 | 0.299709E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.878807E+09 | 0.565310E+09 | 0.659104E+09 | 0.400556E+09 | 0.258548E+09 | 0.00 | 0.00 |
February | 0.801610E+09 | 0.413935E+09 | 0.565971E+09 | 0.314381E+09 | 0.251590E+09 | 0.00 | 0.00 |
March | 0.836756E+09 | 0.283300E+09 | 0.535589E+09 | 0.236495E+09 | 0.299094E+09 | 0.00 | 0.00 |
April | 0.710692E+09 | 0.103437E+09 | 0.363981E+09 | 0.102606E+09 | 0.261375E+09 | 0.00 | 0.00 |
May | 0.729576E+09 | 23181274.44 | 0.270435E+09 | 19866784.00 | 0.250569E+09 | 0.00 | 0.00 |
June | 0.725094E+09 | 17820811.03 | 0.239469E+09 | 4012391.27 | 0.235457E+09 | 0.00 | 0.00 |
July | 0.692850E+09 | 6675314.41 | 0.258155E+09 | 3509286.43 | 0.254646E+09 | 0.00 | 0.00 |
August | 0.640098E+09 | 19250485.08 | 0.273849E+09 | 14584222.69 | 0.259265E+09 | 0.00 | 0.00 |
September | 0.692937E+09 | 58983178.41 | 0.355267E+09 | 92162806.66 | 0.263104E+09 | 0.00 | 0.00 |
October | 0.110751E+10 | 0.231386E+09 | 0.631663E+09 | 0.352707E+09 | 0.278955E+09 | 0.00 | 0.00 |
November | 0.121041E+10 | 0.400941E+09 | 0.763773E+09 | 0.504911E+09 | 0.258862E+09 | 0.00 | 0.00 |
December | 0.981596E+09 | 0.559243E+09 | 0.704367E+09 | 0.441449E+09 | 0.262918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100079E+11 | 0.268346E+10 | 0.562162E+10 | 0.248724E+10 | 0.313438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.640098E+09 | 6675314.41 | 0.239469E+09 | 3509286.43 | 0.235457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121041E+10 | 0.565310E+09 | 0.763773E+09 | 0.504911E+09 | 0.299094E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.881735E+09 | 0.556595E+09 | 0.659104E+09 | 0.400556E+09 | 0.258548E+09 | 0.00 | 0.00 |
February | 0.802866E+09 | 0.410189E+09 | 0.565971E+09 | 0.314381E+09 | 0.251590E+09 | 0.00 | 0.00 |
March | 0.836980E+09 | 0.282654E+09 | 0.535589E+09 | 0.236495E+09 | 0.299094E+09 | 0.00 | 0.00 |
April | 0.709888E+09 | 0.104983E+09 | 0.363981E+09 | 0.102606E+09 | 0.261375E+09 | 0.00 | 0.00 |
May | 0.726660E+09 | 24837410.21 | 0.270435E+09 | 19866784.00 | 0.250569E+09 | 0.00 | 0.00 |
June | 0.721627E+09 | 18869416.74 | 0.239469E+09 | 4012391.27 | 0.235457E+09 | 0.00 | 0.00 |
July | 0.688703E+09 | 7335941.27 | 0.258155E+09 | 3509286.43 | 0.254646E+09 | 0.00 | 0.00 |
August | 0.637801E+09 | 20445766.59 | 0.273849E+09 | 14584222.69 | 0.259265E+09 | 0.00 | 0.00 |
September | 0.692210E+09 | 61281733.03 | 0.355267E+09 | 92162806.66 | 0.263104E+09 | 0.00 | 0.00 |
October | 0.110720E+10 | 0.232993E+09 | 0.631663E+09 | 0.352707E+09 | 0.278955E+09 | 0.00 | 0.00 |
November | 0.121083E+10 | 0.399649E+09 | 0.763773E+09 | 0.504911E+09 | 0.258862E+09 | 0.00 | 0.00 |
December | 0.983493E+09 | 0.553966E+09 | 0.704367E+09 | 0.441449E+09 | 0.262918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.999999E+10 | 0.267380E+10 | 0.562162E+10 | 0.248724E+10 | 0.313438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.637801E+09 | 7335941.27 | 0.239469E+09 | 3509286.43 | 0.235457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121083E+10 | 0.556595E+09 | 0.763773E+09 | 0.504911E+09 | 0.299094E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.885863E+09 | 0.546707E+09 | 0.659104E+09 | 0.400556E+09 | 0.258548E+09 | 0.00 | 0.00 |
February | 0.805193E+09 | 0.404502E+09 | 0.565971E+09 | 0.314381E+09 | 0.251590E+09 | 0.00 | 0.00 |
March | 0.838471E+09 | 0.278504E+09 | 0.535589E+09 | 0.236495E+09 | 0.299094E+09 | 0.00 | 0.00 |
April | 0.711525E+09 | 0.102234E+09 | 0.363981E+09 | 0.102606E+09 | 0.261375E+09 | 0.00 | 0.00 |
May | 0.729074E+09 | 23441465.93 | 0.270435E+09 | 19866784.00 | 0.250569E+09 | 0.00 | 0.00 |
June | 0.724580E+09 | 18029500.28 | 0.239469E+09 | 4012391.27 | 0.235457E+09 | 0.00 | 0.00 |
July | 0.691272E+09 | 6614011.05 | 0.258155E+09 | 3509286.43 | 0.254646E+09 | 0.00 | 0.00 |
August | 0.639993E+09 | 19029620.19 | 0.273849E+09 | 14584222.69 | 0.259265E+09 | 0.00 | 0.00 |
September | 0.693325E+09 | 58558554.12 | 0.355267E+09 | 92162806.66 | 0.263104E+09 | 0.00 | 0.00 |
October | 0.110811E+10 | 0.229862E+09 | 0.631663E+09 | 0.352707E+09 | 0.278955E+09 | 0.00 | 0.00 |
November | 0.121220E+10 | 0.395832E+09 | 0.763773E+09 | 0.504911E+09 | 0.258862E+09 | 0.00 | 0.00 |
December | 0.986507E+09 | 0.547446E+09 | 0.704367E+09 | 0.441449E+09 | 0.262918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100261E+11 | 0.263076E+10 | 0.562162E+10 | 0.248724E+10 | 0.313438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.639993E+09 | 6614011.05 | 0.239469E+09 | 3509286.43 | 0.235457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121220E+10 | 0.547446E+09 | 0.763773E+09 | 0.504911E+09 | 0.299094E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.179297E+10 | 0.104704E+10 | 0.131821E+10 | 0.801112E+09 | 0.517096E+09 | 0.00 | 0.00 |
February | 0.162294E+10 | 0.779471E+09 | 0.113194E+10 | 0.628762E+09 | 0.503180E+09 | 0.00 | 0.00 |
March | 0.168419E+10 | 0.531531E+09 | 0.107118E+10 | 0.472991E+09 | 0.598188E+09 | 0.00 | 0.00 |
April | 0.142928E+10 | 0.187343E+09 | 0.727962E+09 | 0.205212E+09 | 0.522750E+09 | 0.00 | 0.00 |
May | 0.146684E+10 | 39111158.87 | 0.540871E+09 | 39733568.00 | 0.501137E+09 | 0.00 | 0.00 |
June | 0.146246E+10 | 31605978.08 | 0.478939E+09 | 8024782.53 | 0.470914E+09 | 0.00 | 0.00 |
July | 0.138960E+10 | 9292699.49 | 0.516310E+09 | 7018572.86 | 0.509292E+09 | 0.00 | 0.00 |
August | 0.128675E+10 | 29485144.40 | 0.547697E+09 | 29168445.38 | 0.518529E+09 | 0.00 | 0.00 |
September | 0.138846E+10 | 0.100679E+09 | 0.710533E+09 | 0.184326E+09 | 0.526207E+09 | 0.00 | 0.00 |
October | 0.221702E+10 | 0.439148E+09 | 0.126333E+10 | 0.705415E+09 | 0.557911E+09 | 0.00 | 0.00 |
November | 0.243004E+10 | 0.769679E+09 | 0.152755E+10 | 0.100982E+10 | 0.517724E+09 | 0.00 | 0.00 |
December | 0.198845E+10 | 0.106229E+10 | 0.140873E+10 | 0.882898E+09 | 0.525836E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.201590E+11 | 0.502667E+10 | 0.112432E+11 | 0.497448E+10 | 0.626876E+10 | 0.00 | 0.00 |
Minimum of Months | 0.128675E+10 | 9292699.49 | 0.478939E+09 | 7018572.86 | 0.470914E+09 | 0.00 | 0.00 |
Maximum of Months | 0.243004E+10 | 0.106229E+10 | 0.152755E+10 | 0.100982E+10 | 0.598188E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.896756E+09 | 0.520324E+09 | 0.659104E+09 | 0.400556E+09 | 0.258548E+09 | 0.00 | 0.00 |
February | 0.811219E+09 | 0.387655E+09 | 0.565971E+09 | 0.314381E+09 | 0.251590E+09 | 0.00 | 0.00 |
March | 0.842945E+09 | 0.262699E+09 | 0.535589E+09 | 0.236495E+09 | 0.299094E+09 | 0.00 | 0.00 |
April | 0.718897E+09 | 90735520.81 | 0.363981E+09 | 0.102606E+09 | 0.261375E+09 | 0.00 | 0.00 |
May | 0.741959E+09 | 17834398.54 | 0.270435E+09 | 19866784.00 | 0.250569E+09 | 0.00 | 0.00 |
June | 0.740412E+09 | 14777585.02 | 0.239469E+09 | 4012391.27 | 0.235457E+09 | 0.00 | 0.00 |
July | 0.703748E+09 | 3878690.56 | 0.258155E+09 | 3509286.43 | 0.254646E+09 | 0.00 | 0.00 |
August | 0.649976E+09 | 12972140.45 | 0.273849E+09 | 14584222.69 | 0.259265E+09 | 0.00 | 0.00 |
September | 0.697801E+09 | 46692697.89 | 0.355267E+09 | 92162806.66 | 0.263104E+09 | 0.00 | 0.00 |
October | 0.111001E+10 | 0.215654E+09 | 0.631663E+09 | 0.352707E+09 | 0.278955E+09 | 0.00 | 0.00 |
November | 0.121500E+10 | 0.382122E+09 | 0.763773E+09 | 0.504911E+09 | 0.258862E+09 | 0.00 | 0.00 |
December | 0.994066E+09 | 0.529066E+09 | 0.704367E+09 | 0.441449E+09 | 0.262918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101228E+11 | 0.248441E+10 | 0.562162E+10 | 0.248724E+10 | 0.313438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.649976E+09 | 3878690.56 | 0.239469E+09 | 3509286.43 | 0.235457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121500E+10 | 0.529066E+09 | 0.763773E+09 | 0.504911E+09 | 0.299094E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.898400E+09 | 0.516814E+09 | 0.659104E+09 | 0.400556E+09 | 0.258548E+09 | 0.00 | 0.00 |
February | 0.812340E+09 | 0.385408E+09 | 0.565971E+09 | 0.314381E+09 | 0.251590E+09 | 0.00 | 0.00 |
March | 0.843710E+09 | 0.261236E+09 | 0.535589E+09 | 0.236495E+09 | 0.299094E+09 | 0.00 | 0.00 |
April | 0.719666E+09 | 89926487.17 | 0.363981E+09 | 0.102606E+09 | 0.261375E+09 | 0.00 | 0.00 |
May | 0.742991E+09 | 17506389.56 | 0.270435E+09 | 19866784.00 | 0.250569E+09 | 0.00 | 0.00 |
June | 0.741553E+09 | 14565568.02 | 0.239469E+09 | 4012391.27 | 0.235457E+09 | 0.00 | 0.00 |
July | 0.704819E+09 | 3758844.47 | 0.258155E+09 | 3509286.43 | 0.254646E+09 | 0.00 | 0.00 |
August | 0.650855E+09 | 12689390.21 | 0.273849E+09 | 14584222.69 | 0.259265E+09 | 0.00 | 0.00 |
September | 0.698360E+09 | 46049141.58 | 0.355267E+09 | 92162806.66 | 0.263104E+09 | 0.00 | 0.00 |
October | 0.111046E+10 | 0.214748E+09 | 0.631663E+09 | 0.352707E+09 | 0.278955E+09 | 0.00 | 0.00 |
November | 0.121562E+10 | 0.380895E+09 | 0.763773E+09 | 0.504911E+09 | 0.258862E+09 | 0.00 | 0.00 |
December | 0.995413E+09 | 0.526630E+09 | 0.704367E+09 | 0.441449E+09 | 0.262918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101342E+11 | 0.247023E+10 | 0.562162E+10 | 0.248724E+10 | 0.313438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.650855E+09 | 3758844.47 | 0.239469E+09 | 3509286.43 | 0.235457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121562E+10 | 0.526630E+09 | 0.763773E+09 | 0.504911E+09 | 0.299094E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.901516E+09 | 0.509234E+09 | 0.659104E+09 | 0.400556E+09 | 0.258548E+09 | 0.00 | 0.00 |
February | 0.814783E+09 | 0.379799E+09 | 0.565971E+09 | 0.314381E+09 | 0.251590E+09 | 0.00 | 0.00 |
March | 0.844996E+09 | 0.257937E+09 | 0.535589E+09 | 0.236495E+09 | 0.299094E+09 | 0.00 | 0.00 |
April | 0.719561E+09 | 89128521.16 | 0.363981E+09 | 0.102606E+09 | 0.261375E+09 | 0.00 | 0.00 |
May | 0.741590E+09 | 17664337.09 | 0.270435E+09 | 19866784.00 | 0.250569E+09 | 0.00 | 0.00 |
June | 0.739554E+09 | 14673692.00 | 0.239469E+09 | 4012391.27 | 0.235457E+09 | 0.00 | 0.00 |
July | 0.701995E+09 | 3892077.98 | 0.258155E+09 | 3509286.43 | 0.254646E+09 | 0.00 | 0.00 |
August | 0.648639E+09 | 13141448.83 | 0.273849E+09 | 14584222.69 | 0.259265E+09 | 0.00 | 0.00 |
September | 0.697297E+09 | 46935483.41 | 0.355267E+09 | 92162806.66 | 0.263104E+09 | 0.00 | 0.00 |
October | 0.111014E+10 | 0.214796E+09 | 0.631663E+09 | 0.352707E+09 | 0.278955E+09 | 0.00 | 0.00 |
November | 0.121655E+10 | 0.378697E+09 | 0.763773E+09 | 0.504911E+09 | 0.258862E+09 | 0.00 | 0.00 |
December | 0.998351E+09 | 0.520794E+09 | 0.704367E+09 | 0.441449E+09 | 0.262918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101350E+11 | 0.244669E+10 | 0.562162E+10 | 0.248724E+10 | 0.313438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.648639E+09 | 3892077.98 | 0.239469E+09 | 3509286.43 | 0.235457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121655E+10 | 0.520794E+09 | 0.763773E+09 | 0.504911E+09 | 0.299094E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.905885E+09 | 0.487392E+09 | 0.659104E+09 | 0.400556E+09 | 0.258548E+09 | 0.00 | 0.00 |
February | 0.818641E+09 | 0.360942E+09 | 0.565971E+09 | 0.314381E+09 | 0.251590E+09 | 0.00 | 0.00 |
March | 0.845242E+09 | 0.245611E+09 | 0.535589E+09 | 0.236495E+09 | 0.299094E+09 | 0.00 | 0.00 |
April | 0.711489E+09 | 87254063.53 | 0.363981E+09 | 0.102606E+09 | 0.261375E+09 | 0.00 | 0.00 |
May | 0.724427E+09 | 19402810.45 | 0.270435E+09 | 19866784.00 | 0.250569E+09 | 0.00 | 0.00 |
June | 0.718782E+09 | 15926401.18 | 0.239469E+09 | 4012391.27 | 0.235457E+09 | 0.00 | 0.00 |
July | 0.677444E+09 | 5361505.87 | 0.258155E+09 | 3509286.43 | 0.254646E+09 | 0.00 | 0.00 |
August | 0.628573E+09 | 17526502.53 | 0.273849E+09 | 14584222.69 | 0.259265E+09 | 0.00 | 0.00 |
September | 0.685447E+09 | 55367320.27 | 0.355267E+09 | 92162806.66 | 0.263104E+09 | 0.00 | 0.00 |
October | 0.110304E+10 | 0.218930E+09 | 0.631663E+09 | 0.352707E+09 | 0.278955E+09 | 0.00 | 0.00 |
November | 0.121579E+10 | 0.371825E+09 | 0.763773E+09 | 0.504911E+09 | 0.258862E+09 | 0.00 | 0.00 |
December | 0.100282E+10 | 0.502386E+09 | 0.704367E+09 | 0.441449E+09 | 0.262918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100376E+11 | 0.238793E+10 | 0.562162E+10 | 0.248724E+10 | 0.313438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.628573E+09 | 5361505.87 | 0.239469E+09 | 3509286.43 | 0.235457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121579E+10 | 0.502386E+09 | 0.763773E+09 | 0.504911E+09 | 0.299094E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.37 | 7.87 | 1.20 | 0.37 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.77 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.59 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.31 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.95 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.37 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.28 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.69 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.73 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.45 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.87 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.75 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.37 | 7.87 | 0.66 | 0.37 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.18 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.17 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.47 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.63 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.60 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.49 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.34 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.56 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.67 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.02 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.14 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.28 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.18 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.67 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.55 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.57 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.73 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.61 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.36 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.40 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.17 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.16 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.05 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.91 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.61 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.17 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.47 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.24 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.03 | 0.00 | 15.60 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.69 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.40 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.58 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.47 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.302808E+09 | -186924334.7 | 0.00 | 0.00 | 744.00 | 0.00 | -115883959.9 | 58.99 | 0.00 | 0.00 |
February | 0.269209E+09 | -166093925.7 | 0.00 | 0.00 | 672.00 | 0.00 | -103115105.7 | 58.99 | 0.00 | 0.00 |
March | 0.287028E+09 | -174340231.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112687676.7 | 58.99 | 0.00 | 0.00 |
April | 0.257674E+09 | -149624654.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108048878.6 | 58.99 | 0.00 | 0.00 |
May | 0.247342E+09 | -136561943.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110779596.5 | 58.99 | 0.00 | 0.00 |
June | 0.226665E+09 | -119747837.7 | 0.00 | 0.00 | 720.00 | 0.00 | -106917444.3 | 58.99 | 0.00 | 0.00 |
July | 0.226127E+09 | -115768629.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110358041.0 | 58.99 | 0.00 | 0.00 |
August | 0.232685E+09 | -122175835.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110509588.8 | 58.99 | 0.00 | 0.00 |
September | 0.236726E+09 | -129446814.8 | 0.00 | 0.00 | 720.00 | 0.00 | -107279383.5 | 58.99 | 0.00 | 0.00 |
October | 0.261701E+09 | -150075974.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111624988.5 | 58.99 | 0.00 | 0.00 |
November | 0.271230E+09 | -162148702.5 | 0.00 | 0.00 | 720.00 | 0.00 | -109081158.7 | 58.99 | 0.00 | 0.00 |
December | 0.296334E+09 | -181751070.8 | 0.00 | 0.00 | 744.00 | 0.00 | -114582591.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.311553E+10 | -.179466E+10 | 8760.00 | -.132087E+10 | 58.99 | |||||
Minimum of Months | 0.226127E+09 | -186924334.7 | 0.00 | 0.00 | 672.00 | 0.00 | -115883959.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.302808E+09 | -115768629.6 | 0.00 | 0.00 | 744.00 | 0.00 | -103115105.7 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.301461E+09 | -186913137.4 | 0.00 | 0.00 | 744.00 | 0.00 | -114547938.3 | 58.99 | 0.00 | 0.00 |
February | 0.268515E+09 | -166094426.8 | 0.00 | 0.00 | 672.00 | 0.00 | -102420839.9 | 58.99 | 0.00 | 0.00 |
March | 0.286657E+09 | -174344415.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112312544.7 | 58.99 | 0.00 | 0.00 |
April | 0.257529E+09 | -149625436.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107903505.6 | 58.99 | 0.00 | 0.00 |
May | 0.247326E+09 | -136562401.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110763488.0 | 58.99 | 0.00 | 0.00 |
June | 0.226722E+09 | -119747484.5 | 0.00 | 0.00 | 720.00 | 0.00 | -106974978.6 | 58.99 | 0.00 | 0.00 |
July | 0.226223E+09 | -115774417.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110448230.6 | 58.99 | 0.00 | 0.00 |
August | 0.232778E+09 | -122183752.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110593847.4 | 58.99 | 0.00 | 0.00 |
September | 0.236771E+09 | -129448549.0 | 0.00 | 0.00 | 720.00 | 0.00 | -107322675.8 | 58.99 | 0.00 | 0.00 |
October | 0.261631E+09 | -150069608.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111561321.4 | 58.99 | 0.00 | 0.00 |
November | 0.270962E+09 | -162151441.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108810639.7 | 58.99 | 0.00 | 0.00 |
December | 0.295450E+09 | -181758011.7 | 0.00 | 0.00 | 744.00 | 0.00 | -113692353.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.311203E+10 | -.179467E+10 | 8760.00 | -.131735E+10 | 58.99 | |||||
Minimum of Months | 0.226223E+09 | -186913137.4 | 0.00 | 0.00 | 672.00 | 0.00 | -114547938.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.301461E+09 | -115774417.0 | 0.00 | 0.00 | 744.00 | 0.00 | -102420839.9 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.279640E+09 | -164384640.0 | 0.00 | 0.00 | 744.00 | 0.00 | -115255780.5 | 58.99 | 0.00 | 0.00 |
February | 0.248367E+09 | -146173543.2 | 0.00 | 0.00 | 672.00 | 0.00 | -102193172.1 | 59.00 | 0.00 | 0.00 |
March | 0.266746E+09 | -155697078.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111048926.3 | 58.99 | 0.00 | 0.00 |
April | 0.237122E+09 | -131494030.9 | 0.00 | 0.00 | 720.00 | 0.00 | -105628203.8 | 58.99 | 0.00 | 0.00 |
May | 0.229131E+09 | -121151890.3 | 0.00 | 0.00 | 744.00 | 0.00 | -107979472.0 | 58.99 | 0.00 | 0.00 |
June | 0.210973E+09 | -106686399.8 | 0.00 | 0.00 | 720.00 | 0.00 | -104286512.2 | 59.00 | 0.00 | 0.00 |
July | 0.208632E+09 | -101116204.5 | 0.00 | 0.00 | 744.00 | 0.00 | -107516262.7 | 58.99 | 0.00 | 0.00 |
August | 0.217344E+09 | -109244752.8 | 0.00 | 0.00 | 744.00 | 0.00 | -108098866.5 | 58.98 | 0.00 | 0.00 |
September | 0.218683E+09 | -113743020.0 | 0.00 | 0.00 | 720.00 | 0.00 | -104939747.6 | 58.98 | 0.00 | 0.00 |
October | 0.241515E+09 | -131992968.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109521824.3 | 58.99 | 0.00 | 0.00 |
November | 0.251053E+09 | -143145744.9 | 0.00 | 0.00 | 720.00 | 0.00 | -107906968.7 | 58.99 | 0.00 | 0.00 |
December | 0.272523E+09 | -158640867.9 | 0.00 | 0.00 | 744.00 | 0.00 | -113881727.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.288173E+10 | -.158347E+10 | 8760.00 | -.129826E+10 | 58.99 | |||||
Minimum of Months | 0.208632E+09 | -164384640.0 | 0.00 | 0.00 | 672.00 | 0.00 | -115255780.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.279640E+09 | -101116204.5 | 0.00 | 0.00 | 744.00 | 0.00 | -102193172.1 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.280084E+09 | -164354922.5 | 0.00 | 0.00 | 744.00 | 0.00 | -115729293.1 | 59.00 | 0.00 | 0.00 |
February | 0.248554E+09 | -146214630.8 | 0.00 | 0.00 | 672.00 | 0.00 | -102339256.5 | 58.98 | 0.00 | 0.00 |
March | 0.266776E+09 | -155692073.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111084416.5 | 58.99 | 0.00 | 0.00 |
April | 0.237027E+09 | -131513938.0 | 0.00 | 0.00 | 720.00 | 0.00 | -105512766.2 | 58.99 | 0.00 | 0.00 |
May | 0.228944E+09 | -121187485.6 | 0.00 | 0.00 | 744.00 | 0.00 | -107756519.3 | 58.98 | 0.00 | 0.00 |
June | 0.210798E+09 | -106747814.6 | 0.00 | 0.00 | 720.00 | 0.00 | -104050572.7 | 58.98 | 0.00 | 0.00 |
July | 0.208435E+09 | -101114199.9 | 0.00 | 0.00 | 744.00 | 0.00 | -107320842.6 | 58.99 | 0.00 | 0.00 |
August | 0.217193E+09 | -109256639.9 | 0.00 | 0.00 | 744.00 | 0.00 | -107935989.1 | 58.98 | 0.00 | 0.00 |
September | 0.218561E+09 | -113746700.2 | 0.00 | 0.00 | 720.00 | 0.00 | -104813920.2 | 58.99 | 0.00 | 0.00 |
October | 0.241436E+09 | -131995000.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109440562.4 | 58.99 | 0.00 | 0.00 |
November | 0.251113E+09 | -143142994.9 | 0.00 | 0.00 | 720.00 | 0.00 | -107969690.0 | 59.00 | 0.00 | 0.00 |
December | 0.272794E+09 | -158648198.2 | 0.00 | 0.00 | 744.00 | 0.00 | -114145871.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.288171E+10 | -.158361E+10 | 8760.00 | -.129810E+10 | 58.99 | |||||
Minimum of Months | 0.208435E+09 | -164354922.5 | 0.00 | 0.00 | 672.00 | 0.00 | -115729293.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.280084E+09 | -101114199.9 | 0.00 | 0.00 | 744.00 | 0.00 | -102339256.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.272979E+09 | -155351906.6 | 0.00 | 0.00 | 744.00 | 0.00 | -117627517.9 | 58.99 | 0.00 | 0.00 |
February | 0.241708E+09 | -138248576.9 | 0.00 | 0.00 | 672.00 | 0.00 | -103459553.2 | 58.99 | 0.00 | 0.00 |
March | 0.259362E+09 | -147286211.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112075846.3 | 59.00 | 0.00 | 0.00 |
April | 0.230836E+09 | -124453103.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106382660.3 | 58.99 | 0.00 | 0.00 |
May | 0.223156E+09 | -114567602.9 | 0.00 | 0.00 | 744.00 | 0.00 | -108588139.0 | 58.99 | 0.00 | 0.00 |
June | 0.205855E+09 | -101014486.9 | 0.00 | 0.00 | 720.00 | 0.00 | -104840020.5 | 58.98 | 0.00 | 0.00 |
July | 0.203514E+09 | -95627842.1 | 0.00 | 0.00 | 744.00 | 0.00 | -107886279.3 | 58.99 | 0.00 | 0.00 |
August | 0.212005E+09 | -103347647.7 | 0.00 | 0.00 | 744.00 | 0.00 | -108657619.8 | 58.99 | 0.00 | 0.00 |
September | 0.213151E+09 | -107631583.8 | 0.00 | 0.00 | 720.00 | 0.00 | -105519286.1 | 58.99 | 0.00 | 0.00 |
October | 0.234921E+09 | -124773249.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110147880.4 | 58.99 | 0.00 | 0.00 |
November | 0.243914E+09 | -135177907.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108736121.8 | 59.00 | 0.00 | 0.00 |
December | 0.265474E+09 | -150030830.3 | 0.00 | 0.00 | 744.00 | 0.00 | -115442995.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.280687E+10 | -.149751E+10 | 8760.00 | -.130936E+10 | 58.99 | |||||
Minimum of Months | 0.203514E+09 | -155351906.6 | 0.00 | 0.00 | 672.00 | 0.00 | -117627517.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.272979E+09 | -95627842.1 | 0.00 | 0.00 | 744.00 | 0.00 | -103459553.2 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.273184E+09 | -155350167.6 | 0.00 | 0.00 | 744.00 | 0.00 | -117833368.3 | 58.99 | 0.00 | 0.00 |
February | 0.241805E+09 | -138240682.3 | 0.00 | 0.00 | 672.00 | 0.00 | -103564010.6 | 58.99 | 0.00 | 0.00 |
March | 0.259484E+09 | -147306578.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112177105.5 | 59.00 | 0.00 | 0.00 |
April | 0.230992E+09 | -124443092.7 | 0.00 | 0.00 | 720.00 | 0.00 | -106549392.8 | 58.99 | 0.00 | 0.00 |
May | 0.223375E+09 | -114607565.9 | 0.00 | 0.00 | 744.00 | 0.00 | -108767323.5 | 58.99 | 0.00 | 0.00 |
June | 0.206062E+09 | -100989655.5 | 0.00 | 0.00 | 720.00 | 0.00 | -105072554.8 | 58.99 | 0.00 | 0.00 |
July | 0.203744E+09 | -95654533.9 | 0.00 | 0.00 | 744.00 | 0.00 | -108089004.2 | 58.99 | 0.00 | 0.00 |
August | 0.212212E+09 | -103340362.6 | 0.00 | 0.00 | 744.00 | 0.00 | -108871224.3 | 58.99 | 0.00 | 0.00 |
September | 0.213344E+09 | -107641971.0 | 0.00 | 0.00 | 720.00 | 0.00 | -105702321.8 | 58.99 | 0.00 | 0.00 |
October | 0.235080E+09 | -124751140.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110328600.7 | 58.99 | 0.00 | 0.00 |
November | 0.244031E+09 | -135211679.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108819360.9 | 58.99 | 0.00 | 0.00 |
December | 0.265578E+09 | -150045127.0 | 0.00 | 0.00 | 744.00 | 0.00 | -115532426.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.280889E+10 | -.149758E+10 | 8760.00 | -.131131E+10 | 58.99 | |||||
Minimum of Months | 0.203744E+09 | -155350167.6 | 0.00 | 0.00 | 672.00 | 0.00 | -117833368.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.273184E+09 | -95654533.9 | 0.00 | 0.00 | 744.00 | 0.00 | -103564010.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.273381E+09 | -155354681.2 | 0.00 | 0.00 | 744.00 | 0.00 | -118026167.5 | 58.99 | 0.00 | 0.00 |
February | 0.241928E+09 | -138252968.3 | 0.00 | 0.00 | 672.00 | 0.00 | -103674552.1 | 58.99 | 0.00 | 0.00 |
March | 0.259542E+09 | -147350365.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112191326.3 | 58.98 | 0.00 | 0.00 |
April | 0.231058E+09 | -124454602.1 | 0.00 | 0.00 | 720.00 | 0.00 | -106603483.0 | 58.99 | 0.00 | 0.00 |
May | 0.223400E+09 | -114587106.6 | 0.00 | 0.00 | 744.00 | 0.00 | -108812746.9 | 58.99 | 0.00 | 0.00 |
June | 0.206110E+09 | -101010493.1 | 0.00 | 0.00 | 720.00 | 0.00 | -105099932.3 | 58.98 | 0.00 | 0.00 |
July | 0.203772E+09 | -95627231.8 | 0.00 | 0.00 | 744.00 | 0.00 | -108145158.0 | 58.99 | 0.00 | 0.00 |
August | 0.212258E+09 | -103349894.0 | 0.00 | 0.00 | 744.00 | 0.00 | -108908582.4 | 58.99 | 0.00 | 0.00 |
September | 0.213356E+09 | -107612563.6 | 0.00 | 0.00 | 720.00 | 0.00 | -105743104.9 | 58.99 | 0.00 | 0.00 |
October | 0.235136E+09 | -124774795.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110361448.9 | 58.99 | 0.00 | 0.00 |
November | 0.244082E+09 | -135186191.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108895643.8 | 59.00 | 0.00 | 0.00 |
December | 0.265726E+09 | -150028418.7 | 0.00 | 0.00 | 744.00 | 0.00 | -115697272.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.280975E+10 | -.149759E+10 | 8760.00 | -.131216E+10 | 58.99 | |||||
Minimum of Months | 0.203772E+09 | -155354681.2 | 0.00 | 0.00 | 672.00 | 0.00 | -118026167.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.273381E+09 | -95627231.8 | 0.00 | 0.00 | 744.00 | 0.00 | -103674552.1 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 319.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 364.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 386.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 372.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 317.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 315.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4237.50 | ||||||||||
Minimum of Months | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.280945E+09 | 31613.01 | 02-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14461925.92 | 5234.55 | 02-FEB-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36208912.36 | 6915.87 | 23-DEC-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.331616E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.280945E+09 | 31613.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 44248496.50 | 4522.41 | 02-JAN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2173683.46 | 1029.92 | 21-DEC-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46422179.96 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44248496.50 | 4522.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.123674E+09 | 9327.39 | 01-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1671071.58 | 626.61 | 02-FEB-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8132926.54 | 1823.48 | 23-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133478E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.123674E+09 | 9327.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.169333E+09 | 16253.03 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3071450.11 | 1189.19 | 02-FEB-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12295089.51 | 2004.56 | 23-DEC-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184700E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.169333E+09 | 16253.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.231139E+09 | 21629.49 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8311278.80 | 1744.93 | 02-FEB-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20565562.67 | 2204.17 | 23-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.260016E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.231139E+09 | 21629.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.553241E+09 | 61933.67 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 40093211.03 | 6638.50 | 02-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 66071602.02 | 8330.53 | 23-DEC-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.659406E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.553241E+09 | 61933.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.296978E+09 | 32560.40 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20195293.43 | 3753.92 | 02-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 33750682.23 | 3760.69 | 23-DEC-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.350924E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.296978E+09 | 32560.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.319808E+09 | 32441.25 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24433258.86 | 3575.43 | 02-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 39032103.76 | 4461.08 | 23-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.383273E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.319808E+09 | 32441.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.380577E+09 | 32537.35 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 39899821.24 | 3383.01 | 02-FEB-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 54121029.60 | 5374.98 | 23-DEC-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.474598E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.380577E+09 | 32537.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.545730E+09 | 36207.07 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105521E+09 | 12996.18 | 11-FEB-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113432E+09 | 14780.35 | 23-DEC-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.764683E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.545730E+09 | 36207.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.266016E+10 | 0.240801E+10 | 9743.82 | 12-JAN-15:00 | 9317.70 | 0.00 |
February | 0.00 | 0.00 | 0.839323E+10 | 0.738936E+10 | 15940.32 | 22-FEB-15:00 | 14881.57 | 0.00 |
March | 0.00 | 0.00 | 0.203461E+11 | 0.178249E+11 | 56760.97 | 11-MAR-08:62 | 44779.15 | 0.00 |
April | 0.00 | 0.00 | 0.328961E+11 | 0.298566E+11 | 57162.15 | 26-APR-07:02 | 43782.87 | 0.00 |
May | 0.00 | 0.00 | 0.480699E+11 | 0.390797E+11 | 60607.00 | 24-MAY-07:01 | 35200.27 | 0.00 |
June | 0.00 | 0.00 | 0.546933E+11 | 0.394534E+11 | 61710.16 | 26-JUN-07:01 | 32902.03 | 0.00 |
July | 0.00 | 0.00 | 0.623264E+11 | 0.375673E+11 | 62443.96 | 25-JUL-07:01 | 31540.23 | 0.00 |
August | 0.00 | 0.00 | 0.616763E+11 | 0.348947E+11 | 62124.13 | 10-AUG-07:01 | 33703.10 | 0.00 |
September | 0.00 | 0.00 | 0.510516E+11 | 0.310073E+11 | 61498.97 | 03-SEP-07:01 | 34242.44 | 0.00 |
October | 0.00 | 0.00 | 0.326817E+11 | 0.262009E+11 | 59220.56 | 12-OCT-07:02 | 37776.88 | 0.00 |
November | 0.00 | 0.00 | 0.173593E+11 | 0.151383E+11 | 41216.48 | 09-NOV-08:62 | 30462.32 | 0.00 |
December | 0.00 | 0.00 | 0.529295E+10 | 0.465873E+10 | 12339.84 | 28-DEC-15:00 | 11265.63 | 0.00 |
Annual Sum or Average | 0.397447E+12 | 0.285479E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.266016E+10 | 0.240801E+10 | 9743.82 | 9317.70 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.623264E+11 | 0.394534E+11 | 62443.96 | 44779.15 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.272248E+10 | 0.247428E+10 | 5518.28 | 12-JAN-15:00 | 5299.38 | 0.00 |
February | 0.00 | 0.00 | 0.556966E+10 | 0.497632E+10 | 10535.48 | 25-FEB-08:63 | 8407.07 | 0.00 |
March | 0.00 | 0.00 | 0.111569E+11 | 0.995762E+10 | 29147.75 | 30-MAR-07:02 | 24637.29 | 0.00 |
April | 0.00 | 0.00 | 0.166038E+11 | 0.152497E+11 | 29263.29 | 03-APR-07:02 | 24387.81 | 0.00 |
May | 0.00 | 0.00 | 0.237649E+11 | 0.195837E+11 | 30784.67 | 24-MAY-07:01 | 20631.24 | 0.00 |
June | 0.00 | 0.00 | 0.267784E+11 | 0.195987E+11 | 31146.05 | 26-JUN-07:01 | 19735.34 | 0.00 |
July | 0.00 | 0.00 | 0.303753E+11 | 0.186863E+11 | 31490.62 | 25-JUL-07:01 | 18979.90 | 0.00 |
August | 0.00 | 0.00 | 0.300944E+11 | 0.174163E+11 | 31422.63 | 10-AUG-07:01 | 19689.17 | 0.00 |
September | 0.00 | 0.00 | 0.249144E+11 | 0.155505E+11 | 31088.19 | 03-SEP-07:01 | 20316.15 | 0.00 |
October | 0.00 | 0.00 | 0.165841E+11 | 0.136077E+11 | 30059.45 | 12-OCT-07:02 | 22134.14 | 0.00 |
November | 0.00 | 0.00 | 0.981406E+10 | 0.872483E+10 | 21623.17 | 09-NOV-08:62 | 17872.74 | 0.00 |
December | 0.00 | 0.00 | 0.428481E+10 | 0.382367E+10 | 6700.89 | 28-DEC-14:50 | 6152.76 | 0.00 |
Annual Sum or Average | 0.202663E+12 | 0.149650E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.272248E+10 | 0.247428E+10 | 5518.28 | 5299.38 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.303753E+11 | 0.195987E+11 | 31490.62 | 24637.29 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.127239E+10 | 0.117240E+10 | 5094.41 | 12-JAN-15:00 | 4898.21 | 0.00 |
February | 0.00 | 0.00 | 0.365745E+10 | 0.327864E+10 | 10944.12 | 25-FEB-07:03 | 7795.45 | 0.00 |
March | 0.00 | 0.00 | 0.852284E+10 | 0.758649E+10 | 30024.79 | 11-MAR-07:02 | 21758.30 | 0.00 |
April | 0.00 | 0.00 | 0.132968E+11 | 0.121549E+11 | 30104.78 | 17-APR-06:01 | 22661.17 | 0.00 |
May | 0.00 | 0.00 | 0.197200E+11 | 0.161078E+11 | 31748.45 | 23-MAY-06:01 | 17583.23 | 0.00 |
June | 0.00 | 0.00 | 0.223076E+11 | 0.160680E+11 | 32704.99 | 26-JUN-06:01 | 13769.90 | 0.00 |
July | 0.00 | 0.00 | 0.249171E+11 | 0.148712E+11 | 32733.58 | 23-JUL-07:01 | 13952.31 | 0.00 |
August | 0.00 | 0.00 | 0.252486E+11 | 0.141591E+11 | 32804.82 | 21-AUG-06:01 | 12766.12 | 0.00 |
September | 0.00 | 0.00 | 0.204100E+11 | 0.123526E+11 | 32812.95 | 10-SEP-07:01 | 13729.85 | 0.00 |
October | 0.00 | 0.00 | 0.132065E+11 | 0.107228E+11 | 30923.96 | 12-OCT-06:02 | 19064.57 | 0.00 |
November | 0.00 | 0.00 | 0.736228E+10 | 0.657571E+10 | 23769.16 | 09-NOV-07:03 | 17139.88 | 0.00 |
December | 0.00 | 0.00 | 0.248364E+10 | 0.223285E+10 | 6291.37 | 28-DEC-14:00 | 5836.88 | 0.00 |
Annual Sum or Average | 0.162405E+12 | 0.117283E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.127239E+10 | 0.117240E+10 | 5094.41 | 4898.21 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.252486E+11 | 0.161078E+11 | 32812.95 | 22661.17 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.114530E+10 | 0.105617E+10 | 4961.53 | 12-JAN-15:00 | 4769.64 | 0.00 |
February | 0.00 | 0.00 | 0.355543E+10 | 0.318738E+10 | 10322.43 | 25-FEB-07:03 | 7342.02 | 0.00 |
March | 0.00 | 0.00 | 0.849360E+10 | 0.755977E+10 | 30075.62 | 11-MAR-07:02 | 21790.04 | 0.00 |
April | 0.00 | 0.00 | 0.133473E+11 | 0.122013E+11 | 30178.07 | 17-APR-06:01 | 22833.76 | 0.00 |
May | 0.00 | 0.00 | 0.198397E+11 | 0.162146E+11 | 31805.34 | 23-MAY-06:01 | 17700.50 | 0.00 |
June | 0.00 | 0.00 | 0.224289E+11 | 0.161712E+11 | 32759.05 | 26-JUN-06:01 | 13917.81 | 0.00 |
July | 0.00 | 0.00 | 0.250592E+11 | 0.149838E+11 | 32787.69 | 23-JUL-07:01 | 14066.14 | 0.00 |
August | 0.00 | 0.00 | 0.253518E+11 | 0.142386E+11 | 32859.05 | 21-AUG-06:01 | 12869.85 | 0.00 |
September | 0.00 | 0.00 | 0.204897E+11 | 0.124147E+11 | 32867.19 | 10-SEP-07:01 | 13774.07 | 0.00 |
October | 0.00 | 0.00 | 0.132527E+11 | 0.107631E+11 | 30977.53 | 12-OCT-06:02 | 19124.04 | 0.00 |
November | 0.00 | 0.00 | 0.731322E+10 | 0.653115E+10 | 23513.20 | 09-NOV-07:03 | 16931.83 | 0.00 |
December | 0.00 | 0.00 | 0.235847E+10 | 0.212008E+10 | 6162.18 | 28-DEC-14:00 | 5715.28 | 0.00 |
Annual Sum or Average | 0.162635E+12 | 0.117442E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.114530E+10 | 0.105617E+10 | 4961.53 | 4769.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.253518E+11 | 0.162146E+11 | 32867.19 | 22833.76 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.935964E+09 | 0.863598E+09 | 4689.86 | 12-JAN-15:00 | 4505.36 | 0.00 |
February | 0.00 | 0.00 | 0.330883E+10 | 0.296785E+10 | 8159.81 | 25-FEB-07:03 | 5765.09 | 0.00 |
March | 0.00 | 0.00 | 0.822395E+10 | 0.731660E+10 | 29891.55 | 11-MAR-07:02 | 21504.34 | 0.00 |
April | 0.00 | 0.00 | 0.131295E+11 | 0.119972E+11 | 30000.61 | 17-APR-06:01 | 22624.37 | 0.00 |
May | 0.00 | 0.00 | 0.196295E+11 | 0.160295E+11 | 31622.39 | 23-MAY-06:01 | 17452.18 | 0.00 |
June | 0.00 | 0.00 | 0.222085E+11 | 0.159881E+11 | 32579.26 | 26-JUN-06:01 | 13714.95 | 0.00 |
July | 0.00 | 0.00 | 0.248426E+11 | 0.148169E+11 | 32607.74 | 23-JUL-07:01 | 13853.48 | 0.00 |
August | 0.00 | 0.00 | 0.251038E+11 | 0.140512E+11 | 32678.71 | 21-AUG-06:01 | 12686.53 | 0.00 |
September | 0.00 | 0.00 | 0.202503E+11 | 0.122304E+11 | 32686.81 | 10-SEP-07:01 | 13540.31 | 0.00 |
October | 0.00 | 0.00 | 0.130219E+11 | 0.105640E+11 | 30799.56 | 12-OCT-06:02 | 18865.10 | 0.00 |
November | 0.00 | 0.00 | 0.706683E+10 | 0.630860E+10 | 21055.61 | 09-NOV-07:03 | 14963.62 | 0.00 |
December | 0.00 | 0.00 | 0.210545E+10 | 0.189209E+10 | 5898.89 | 28-DEC-14:00 | 5465.65 | 0.00 |
Annual Sum or Average | 0.159827E+12 | 0.115026E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.935964E+09 | 0.863598E+09 | 4689.86 | 4505.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.251038E+11 | 0.160295E+11 | 32686.81 | 22624.37 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.985215E+09 | 0.893751E+09 | 7441.44 | 12-JAN-15:10 | 7015.45 | 0.00 |
February | 0.00 | 0.00 | 0.492718E+10 | 0.437761E+10 | 13820.62 | 24-FEB-15:20 | 11551.67 | 0.00 |
March | 0.00 | 0.00 | 0.138995E+11 | 0.122358E+11 | 52892.60 | 11-MAR-08:62 | 39228.83 | 0.00 |
April | 0.00 | 0.00 | 0.230189E+11 | 0.209979E+11 | 53524.75 | 17-APR-07:01 | 40089.46 | 0.00 |
May | 0.00 | 0.00 | 0.350061E+11 | 0.284147E+11 | 56161.53 | 21-MAY-08:61 | 33778.25 | 0.00 |
June | 0.00 | 0.00 | 0.397521E+11 | 0.284004E+11 | 58295.26 | 25-JUN-08:62 | 25677.01 | 0.00 |
July | 0.00 | 0.00 | 0.442347E+11 | 0.259288E+11 | 58283.44 | 23-JUL-08:61 | 24172.98 | 0.00 |
August | 0.00 | 0.00 | 0.449097E+11 | 0.245827E+11 | 58466.80 | 21-AUG-07:01 | 22432.24 | 0.00 |
September | 0.00 | 0.00 | 0.357301E+11 | 0.211935E+11 | 58493.31 | 04-SEP-08:61 | 24728.58 | 0.00 |
October | 0.00 | 0.00 | 0.227455E+11 | 0.182459E+11 | 54667.56 | 12-OCT-07:02 | 34259.53 | 0.00 |
November | 0.00 | 0.00 | 0.117236E+11 | 0.103239E+11 | 33328.88 | 09-NOV-08:62 | 23935.46 | 0.00 |
December | 0.00 | 0.00 | 0.259357E+10 | 0.231158E+10 | 9772.57 | 28-DEC-14:00 | 8888.56 | 0.00 |
Annual Sum or Average | 0.279526E+12 | 0.197907E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.985215E+09 | 0.893751E+09 | 7441.44 | 7015.45 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.449097E+11 | 0.284147E+11 | 58493.31 | 40089.46 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.453290E+09 | 0.411717E+09 | 3773.42 | 12-JAN-15:10 | 3572.84 | 0.00 |
February | 0.00 | 0.00 | 0.248706E+10 | 0.221836E+10 | 7145.94 | 24-FEB-15:20 | 5987.53 | 0.00 |
March | 0.00 | 0.00 | 0.716014E+10 | 0.632105E+10 | 27753.83 | 11-MAR-08:62 | 20622.41 | 0.00 |
April | 0.00 | 0.00 | 0.119307E+11 | 0.108958E+11 | 28101.89 | 17-APR-07:01 | 21052.98 | 0.00 |
May | 0.00 | 0.00 | 0.181736E+11 | 0.147688E+11 | 29473.22 | 21-MAY-08:61 | 17697.29 | 0.00 |
June | 0.00 | 0.00 | 0.206120E+11 | 0.147435E+11 | 30589.99 | 25-JUN-08:62 | 13354.88 | 0.00 |
July | 0.00 | 0.00 | 0.229377E+11 | 0.134654E+11 | 30583.79 | 23-JUL-08:61 | 12601.19 | 0.00 |
August | 0.00 | 0.00 | 0.232627E+11 | 0.127508E+11 | 30680.01 | 21-AUG-07:01 | 11622.87 | 0.00 |
September | 0.00 | 0.00 | 0.185078E+11 | 0.109961E+11 | 30693.92 | 04-SEP-08:61 | 12849.20 | 0.00 |
October | 0.00 | 0.00 | 0.117674E+11 | 0.946325E+10 | 28672.26 | 12-OCT-07:02 | 18067.92 | 0.00 |
November | 0.00 | 0.00 | 0.603593E+10 | 0.533289E+10 | 15133.89 | 09-NOV-08:62 | 10826.15 | 0.00 |
December | 0.00 | 0.00 | 0.127035E+10 | 0.113778E+10 | 4987.56 | 28-DEC-14:00 | 4552.26 | 0.00 |
Annual Sum or Average | 0.144599E+12 | 0.102505E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.453290E+09 | 0.411717E+09 | 3773.42 | 3572.84 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.232627E+11 | 0.147688E+11 | 30693.92 | 21052.98 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.418369E+09 | 0.379392E+09 | 3680.71 | 12-JAN-15:10 | 3482.83 | 0.00 |
February | 0.00 | 0.00 | 0.241552E+10 | 0.215447E+10 | 7076.45 | 24-FEB-15:20 | 5924.69 | 0.00 |
March | 0.00 | 0.00 | 0.707345E+10 | 0.624176E+10 | 27652.03 | 11-MAR-08:62 | 20499.00 | 0.00 |
April | 0.00 | 0.00 | 0.118597E+11 | 0.108279E+11 | 27998.89 | 17-APR-07:01 | 20954.41 | 0.00 |
May | 0.00 | 0.00 | 0.181006E+11 | 0.147035E+11 | 29365.18 | 21-MAY-08:61 | 17606.17 | 0.00 |
June | 0.00 | 0.00 | 0.205371E+11 | 0.146800E+11 | 30480.55 | 25-JUN-08:62 | 13269.86 | 0.00 |
July | 0.00 | 0.00 | 0.228642E+11 | 0.134077E+11 | 30474.37 | 23-JUL-08:61 | 12529.10 | 0.00 |
August | 0.00 | 0.00 | 0.231859E+11 | 0.126918E+11 | 30570.24 | 21-AUG-07:01 | 11555.61 | 0.00 |
September | 0.00 | 0.00 | 0.184359E+11 | 0.109401E+11 | 30584.10 | 04-SEP-08:61 | 12780.38 | 0.00 |
October | 0.00 | 0.00 | 0.116973E+11 | 0.940127E+10 | 28571.31 | 12-OCT-07:02 | 17955.33 | 0.00 |
November | 0.00 | 0.00 | 0.596238E+10 | 0.526562E+10 | 14495.37 | 09-NOV-08:62 | 10314.70 | 0.00 |
December | 0.00 | 0.00 | 0.120813E+10 | 0.108265E+10 | 4901.26 | 28-DEC-14:00 | 4470.30 | 0.00 |
Annual Sum or Average | 0.143758E+12 | 0.101776E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.418369E+09 | 0.379392E+09 | 3680.71 | 3482.83 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.231859E+11 | 0.147035E+11 | 30584.10 | 20954.41 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.360276E+09 | 0.326197E+09 | 3507.24 | 12-JAN-15:10 | 3318.64 | 0.00 |
February | 0.00 | 0.00 | 0.227222E+10 | 0.202885E+10 | 6957.81 | 24-FEB-15:20 | 5822.99 | 0.00 |
March | 0.00 | 0.00 | 0.691370E+10 | 0.610194E+10 | 26232.10 | 11-MAR-08:62 | 19319.97 | 0.00 |
April | 0.00 | 0.00 | 0.118193E+11 | 0.107928E+11 | 28072.34 | 17-APR-07:01 | 20982.47 | 0.00 |
May | 0.00 | 0.00 | 0.181361E+11 | 0.147404E+11 | 29444.78 | 21-MAY-08:61 | 17635.07 | 0.00 |
June | 0.00 | 0.00 | 0.205984E+11 | 0.147374E+11 | 30568.98 | 25-JUN-08:62 | 13239.57 | 0.00 |
July | 0.00 | 0.00 | 0.229610E+11 | 0.134873E+11 | 30562.79 | 23-JUL-08:61 | 12553.88 | 0.00 |
August | 0.00 | 0.00 | 0.232840E+11 | 0.127687E+11 | 30658.94 | 21-AUG-07:01 | 11583.42 | 0.00 |
September | 0.00 | 0.00 | 0.184940E+11 | 0.109890E+11 | 30672.84 | 04-SEP-08:61 | 12813.99 | 0.00 |
October | 0.00 | 0.00 | 0.116881E+11 | 0.939754E+10 | 28648.23 | 12-OCT-07:02 | 17954.74 | 0.00 |
November | 0.00 | 0.00 | 0.585025E+10 | 0.516813E+10 | 12669.65 | 09-NOV-08:62 | 8946.48 | 0.00 |
December | 0.00 | 0.00 | 0.109041E+10 | 0.979643E+09 | 4746.00 | 28-DEC-14:00 | 4327.76 | 0.00 |
Annual Sum or Average | 0.143468E+12 | 0.101518E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.360276E+09 | 0.326197E+09 | 3507.24 | 3318.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.232840E+11 | 0.147404E+11 | 30672.84 | 20982.47 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.373752E+09 | 0.341966E+09 | 3621.78 | 12-JAN-15:10 | 3456.67 | 0.00 |
February | 0.00 | 0.00 | 0.233371E+10 | 0.210358E+10 | 7426.10 | 22-FEB-14:00 | 6915.93 | 0.00 |
March | 0.00 | 0.00 | 0.725268E+10 | 0.644858E+10 | 20351.78 | 11-MAR-08:62 | 14761.46 | 0.00 |
April | 0.00 | 0.00 | 0.129318E+11 | 0.118633E+11 | 30984.80 | 17-APR-07:01 | 23017.86 | 0.00 |
May | 0.00 | 0.00 | 0.199750E+11 | 0.163950E+11 | 32718.85 | 24-MAY-07:01 | 17393.82 | 0.00 |
June | 0.00 | 0.00 | 0.225847E+11 | 0.164351E+11 | 33695.98 | 25-JUN-08:62 | 14303.66 | 0.00 |
July | 0.00 | 0.00 | 0.252173E+11 | 0.151920E+11 | 33689.15 | 23-JUL-08:61 | 13334.73 | 0.00 |
August | 0.00 | 0.00 | 0.255840E+11 | 0.144838E+11 | 33795.13 | 21-AUG-07:01 | 13044.33 | 0.00 |
September | 0.00 | 0.00 | 0.203303E+11 | 0.124284E+11 | 33810.46 | 04-SEP-08:61 | 14154.43 | 0.00 |
October | 0.00 | 0.00 | 0.129620E+11 | 0.105567E+11 | 31856.78 | 12-OCT-07:02 | 19013.07 | 0.00 |
November | 0.00 | 0.00 | 0.632146E+10 | 0.563415E+10 | 11034.06 | 09-NOV-13:10 | 9686.42 | 0.00 |
December | 0.00 | 0.00 | 0.114334E+10 | 0.103893E+10 | 4988.45 | 28-DEC-14:00 | 4587.56 | 0.00 |
Annual Sum or Average | 0.157010E+12 | 0.112921E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.373752E+09 | 0.341966E+09 | 3621.78 | 3456.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.255840E+11 | 0.164351E+11 | 33810.46 | 23017.86 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.210000E+10 | 0.37 | 1966.95 | 02-JAN-08:61 | 0.75 |
February | 0.189383E+10 | 0.37 | 1288.13 | 02-FEB-08:13 | 0.58 |
March | 0.209779E+10 | 0.37 | 2883.55 | 11-MAR-08:62 | 0.89 |
April | 0.212164E+10 | 0.38 | 2883.55 | 02-APR-07:02 | 0.89 |
May | 0.251666E+10 | 0.41 | 2883.55 | 01-MAY-07:01 | 0.89 |
June | 0.266112E+10 | 0.42 | 2883.55 | 01-JUN-07:01 | 0.89 |
July | 0.282177E+10 | 0.43 | 2883.55 | 01-JUL-07:01 | 0.89 |
August | 0.277169E+10 | 0.42 | 2883.55 | 01-AUG-07:01 | 0.88 |
September | 0.239550E+10 | 0.40 | 2883.55 | 01-SEP-07:01 | 0.88 |
October | 0.213214E+10 | 0.37 | 2883.55 | 01-OCT-07:01 | 0.89 |
November | 0.202234E+10 | 0.37 | 1933.99 | 09-NOV-08:62 | 0.73 |
December | 0.210200E+10 | 0.37 | 1331.39 | 23-DEC-08:10 | 0.60 |
Annual Sum or Average | 0.276365E+11 | 0.39 | |||
Minimum of Months | 0.189383E+10 | 0.37 | 1288.13 | 0.58 | |
Maximum of Months | 0.282177E+10 | 0.43 | 2883.55 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.909273E+09 | 0.40 | 744.81 | 02-JAN-08:05 | 0.63 |
February | 0.845161E+09 | 0.40 | 623.83 | 01-FEB-11:00 | 0.56 |
March | 0.976870E+09 | 0.40 | 1559.57 | 11-MAR-08:62 | 0.92 |
April | 0.102955E+10 | 0.40 | 1559.57 | 02-APR-07:02 | 0.92 |
May | 0.127276E+10 | 0.43 | 1559.57 | 01-MAY-07:01 | 0.93 |
June | 0.135685E+10 | 0.44 | 1559.57 | 01-JUN-07:01 | 0.92 |
July | 0.144143E+10 | 0.44 | 1559.57 | 01-JUL-07:01 | 0.92 |
August | 0.141498E+10 | 0.44 | 1559.57 | 01-AUG-07:01 | 0.92 |
September | 0.120750E+10 | 0.42 | 1559.57 | 01-SEP-07:01 | 0.92 |
October | 0.102443E+10 | 0.40 | 1559.57 | 01-OCT-07:01 | 0.92 |
November | 0.928367E+09 | 0.40 | 1084.62 | 09-NOV-08:62 | 0.78 |
December | 0.919216E+09 | 0.41 | 651.38 | 21-DEC-08:30 | 0.58 |
Annual Sum or Average | 0.133264E+11 | 0.42 | |||
Minimum of Months | 0.845161E+09 | 0.40 | 623.83 | 0.56 | |
Maximum of Months | 0.144143E+10 | 0.44 | 1559.57 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.902387E+09 | 0.30 | 870.66 | 01-JAN-08:62 | 0.69 |
February | 0.814137E+09 | 0.30 | 638.01 | 02-FEB-07:30 | 0.57 |
March | 0.917820E+09 | 0.31 | 1553.14 | 11-MAR-07:02 | 0.92 |
April | 0.920946E+09 | 0.31 | 1553.14 | 02-APR-07:02 | 0.92 |
May | 0.112658E+10 | 0.34 | 1553.14 | 01-MAY-06:01 | 0.93 |
June | 0.119303E+10 | 0.36 | 1553.14 | 01-JUN-06:01 | 0.92 |
July | 0.124161E+10 | 0.36 | 1553.14 | 01-JUL-06:01 | 0.92 |
August | 0.124560E+10 | 0.36 | 1553.14 | 01-AUG-06:01 | 0.91 |
September | 0.104944E+10 | 0.33 | 1553.14 | 01-SEP-06:01 | 0.91 |
October | 0.919197E+09 | 0.31 | 1553.14 | 01-OCT-07:01 | 0.92 |
November | 0.872433E+09 | 0.30 | 1187.07 | 09-NOV-07:03 | 0.81 |
December | 0.894825E+09 | 0.30 | 670.01 | 23-DEC-07:30 | 0.59 |
Annual Sum or Average | 0.120980E+11 | 0.33 | |||
Minimum of Months | 0.814137E+09 | 0.30 | 638.01 | 0.57 | |
Maximum of Months | 0.124560E+10 | 0.36 | 1553.14 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.905298E+09 | 0.30 | 1057.10 | 02-JAN-07:03 | 0.77 |
February | 0.815704E+09 | 0.30 | 654.23 | 02-FEB-07:30 | 0.58 |
March | 0.919543E+09 | 0.31 | 1556.06 | 11-MAR-07:02 | 0.92 |
April | 0.922939E+09 | 0.31 | 1556.06 | 02-APR-07:02 | 0.92 |
May | 0.113109E+10 | 0.34 | 1556.06 | 01-MAY-06:01 | 0.93 |
June | 0.119836E+10 | 0.36 | 1556.06 | 01-JUN-06:01 | 0.92 |
July | 0.124930E+10 | 0.36 | 1556.06 | 01-JUL-06:01 | 0.92 |
August | 0.125034E+10 | 0.36 | 1556.06 | 01-AUG-06:01 | 0.91 |
September | 0.105231E+10 | 0.33 | 1556.06 | 01-SEP-06:01 | 0.91 |
October | 0.921183E+09 | 0.31 | 1556.06 | 01-OCT-07:01 | 0.92 |
November | 0.874067E+09 | 0.30 | 1170.85 | 09-NOV-07:03 | 0.81 |
December | 0.896617E+09 | 0.30 | 676.03 | 23-DEC-07:13 | 0.59 |
Annual Sum or Average | 0.121367E+11 | 0.33 | |||
Minimum of Months | 0.815704E+09 | 0.30 | 654.23 | 0.58 | |
Maximum of Months | 0.125034E+10 | 0.36 | 1556.06 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.901318E+09 | 0.30 | 1196.63 | 02-JAN-07:03 | 0.82 |
February | 0.810747E+09 | 0.30 | 665.17 | 02-FEB-07:30 | 0.59 |
March | 0.913715E+09 | 0.31 | 1546.33 | 11-MAR-07:02 | 0.92 |
April | 0.915247E+09 | 0.31 | 1546.33 | 02-APR-07:02 | 0.92 |
May | 0.112080E+10 | 0.34 | 1546.33 | 01-MAY-06:01 | 0.93 |
June | 0.118696E+10 | 0.36 | 1546.33 | 01-JUN-06:01 | 0.92 |
July | 0.123781E+10 | 0.36 | 1546.33 | 01-JUL-06:01 | 0.92 |
August | 0.123806E+10 | 0.36 | 1546.33 | 01-AUG-06:01 | 0.91 |
September | 0.104168E+10 | 0.33 | 1546.33 | 01-SEP-06:01 | 0.91 |
October | 0.914331E+09 | 0.31 | 1546.33 | 01-OCT-07:01 | 0.92 |
November | 0.868541E+09 | 0.30 | 1018.63 | 09-NOV-07:03 | 0.75 |
December | 0.891237E+09 | 0.30 | 677.44 | 23-DEC-07:10 | 0.60 |
Annual Sum or Average | 0.120404E+11 | 0.33 | |||
Minimum of Months | 0.810747E+09 | 0.30 | 665.17 | 0.59 | |
Maximum of Months | 0.123806E+10 | 0.36 | 1546.33 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.141868E+10 | 0.27 | 2629.13 | 01-JAN-09:01 | 0.89 |
February | 0.127310E+10 | 0.27 | 1220.74 | 02-FEB-08:10 | 0.60 |
March | 0.143574E+10 | 0.28 | 2629.13 | 11-MAR-08:62 | 0.89 |
April | 0.144434E+10 | 0.28 | 2629.13 | 02-APR-08:62 | 0.89 |
May | 0.180499E+10 | 0.31 | 2629.13 | 01-MAY-07:01 | 0.90 |
June | 0.193084E+10 | 0.33 | 2629.13 | 01-JUN-07:01 | 0.89 |
July | 0.202626E+10 | 0.33 | 2629.13 | 01-JUL-07:01 | 0.89 |
August | 0.202166E+10 | 0.33 | 2629.13 | 01-AUG-07:01 | 0.88 |
September | 0.167206E+10 | 0.30 | 2629.13 | 01-SEP-07:01 | 0.88 |
October | 0.143961E+10 | 0.27 | 2629.13 | 01-OCT-08:61 | 0.89 |
November | 0.136302E+10 | 0.27 | 1482.65 | 09-NOV-08:62 | 0.67 |
December | 0.139870E+10 | 0.27 | 1263.84 | 23-DEC-08:07 | 0.61 |
Annual Sum or Average | 0.192290E+11 | 0.29 | |||
Minimum of Months | 0.127310E+10 | 0.27 | 1220.74 | 0.60 | |
Maximum of Months | 0.202626E+10 | 0.33 | 2629.13 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.776827E+09 | 0.28 | 1439.33 | 01-JAN-09:01 | 0.93 |
February | 0.696943E+09 | 0.28 | 675.30 | 02-FEB-08:10 | 0.62 |
March | 0.785916E+09 | 0.29 | 1439.33 | 11-MAR-08:62 | 0.92 |
April | 0.790139E+09 | 0.29 | 1439.33 | 02-APR-08:62 | 0.92 |
May | 0.986689E+09 | 0.32 | 1439.33 | 01-MAY-07:01 | 0.93 |
June | 0.105096E+10 | 0.34 | 1439.33 | 01-JUN-07:01 | 0.92 |
July | 0.110035E+10 | 0.34 | 1439.33 | 01-JUL-07:01 | 0.92 |
August | 0.109741E+10 | 0.34 | 1439.33 | 01-AUG-07:01 | 0.91 |
September | 0.911127E+09 | 0.31 | 1439.33 | 01-SEP-07:01 | 0.91 |
October | 0.787221E+09 | 0.28 | 1439.33 | 01-OCT-08:61 | 0.92 |
November | 0.746164E+09 | 0.28 | 664.90 | 09-NOV-08:62 | 0.61 |
December | 0.765700E+09 | 0.28 | 675.48 | 23-DEC-08:07 | 0.62 |
Annual Sum or Average | 0.104955E+11 | 0.30 | |||
Minimum of Months | 0.696943E+09 | 0.28 | 664.90 | 0.61 | |
Maximum of Months | 0.110035E+10 | 0.34 | 1439.33 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.774266E+09 | 0.28 | 1433.41 | 01-JAN-09:01 | 0.93 |
February | 0.694191E+09 | 0.28 | 668.15 | 02-FEB-08:10 | 0.62 |
March | 0.782656E+09 | 0.29 | 1433.41 | 11-MAR-08:62 | 0.92 |
April | 0.786686E+09 | 0.29 | 1433.41 | 02-APR-08:62 | 0.92 |
May | 0.982704E+09 | 0.32 | 1433.41 | 01-MAY-07:01 | 0.93 |
June | 0.104675E+10 | 0.34 | 1433.41 | 01-JUN-07:01 | 0.92 |
July | 0.109629E+10 | 0.34 | 1433.41 | 01-JUL-07:01 | 0.92 |
August | 0.109324E+10 | 0.34 | 1433.41 | 01-AUG-07:01 | 0.91 |
September | 0.907366E+09 | 0.31 | 1433.41 | 01-SEP-07:01 | 0.91 |
October | 0.783907E+09 | 0.28 | 1433.41 | 01-OCT-08:61 | 0.92 |
November | 0.743090E+09 | 0.28 | 625.70 | 09-NOV-08:62 | 0.59 |
December | 0.762694E+09 | 0.28 | 691.63 | 23-DEC-09:00 | 0.63 |
Annual Sum or Average | 0.104538E+11 | 0.30 | |||
Minimum of Months | 0.694191E+09 | 0.28 | 625.70 | 0.59 | |
Maximum of Months | 0.109629E+10 | 0.34 | 1433.41 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.778431E+09 | 0.28 | 1438.19 | 01-JAN-09:01 | 0.93 |
February | 0.696911E+09 | 0.28 | 665.00 | 02-FEB-08:07 | 0.62 |
March | 0.785181E+09 | 0.29 | 1346.19 | 11-MAR-08:62 | 0.89 |
April | 0.788600E+09 | 0.29 | 1438.19 | 02-APR-08:62 | 0.92 |
May | 0.986016E+09 | 0.32 | 1438.19 | 01-MAY-07:01 | 0.93 |
June | 0.105122E+10 | 0.34 | 1438.19 | 01-JUN-07:01 | 0.92 |
July | 0.110247E+10 | 0.34 | 1438.19 | 01-JUL-07:01 | 0.92 |
August | 0.109881E+10 | 0.34 | 1438.19 | 01-AUG-07:01 | 0.91 |
September | 0.910926E+09 | 0.31 | 1438.19 | 01-SEP-07:01 | 0.91 |
October | 0.786498E+09 | 0.28 | 1438.19 | 01-OCT-08:61 | 0.92 |
November | 0.745557E+09 | 0.28 | 575.28 | 01-NOV-14:40 | 0.56 |
December | 0.765631E+09 | 0.28 | 717.82 | 23-DEC-08:63 | 0.65 |
Annual Sum or Average | 0.104963E+11 | 0.30 | |||
Minimum of Months | 0.696911E+09 | 0.28 | 575.28 | 0.56 | |
Maximum of Months | 0.110247E+10 | 0.34 | 1438.19 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.850897E+09 | 0.27 | 1566.21 | 01-JAN-09:01 | 0.89 |
February | 0.760534E+09 | 0.27 | 963.79 | 11-FEB-08:63 | 0.70 |
March | 0.854821E+09 | 0.28 | 942.26 | 11-MAR-08:62 | 0.69 |
April | 0.858061E+09 | 0.28 | 1566.21 | 02-APR-08:62 | 0.89 |
May | 0.107482E+10 | 0.31 | 1566.21 | 01-MAY-07:01 | 0.90 |
June | 0.114908E+10 | 0.33 | 1566.21 | 01-JUN-07:01 | 0.89 |
July | 0.120575E+10 | 0.33 | 1566.21 | 01-JUL-07:01 | 0.88 |
August | 0.119906E+10 | 0.33 | 1566.21 | 01-AUG-07:01 | 0.88 |
September | 0.993730E+09 | 0.30 | 1566.21 | 01-SEP-07:01 | 0.88 |
October | 0.858475E+09 | 0.27 | 1566.21 | 01-OCT-08:61 | 0.89 |
November | 0.811924E+09 | 0.27 | 626.48 | 10-NOV-18:20 | 0.54 |
December | 0.835166E+09 | 0.27 | 1010.10 | 23-DEC-08:63 | 0.72 |
Annual Sum or Average | 0.114523E+11 | 0.29 | |||
Minimum of Months | 0.760534E+09 | 0.27 | 626.48 | 0.54 | |
Maximum of Months | 0.120575E+10 | 0.33 | 1566.21 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.06 | 1.50 |
February | 0.36 | 0.58 |
March | 0.31 | 0.82 |
April | 0.94 | 0.53 |
May | 1.12 | 0.00 |
June | 1.25 | 0.00 |
July | 1.67 | 0.00 |
August | 2.00 | 0.00 |
September | 1.21 | 0.00 |
October | 0.94 | 0.66 |
November | 0.17 | 0.75 |
December | 0.00 | 0.00 |
Annual Sum or Average | 10.03 | 0.18 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.00 | 1.50 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.44 | 3.47 |
February | 0.36 | 0.29 |
March | 0.22 | 0.28 |
April | 0.78 | 0.00 |
May | 0.29 | 0.00 |
June | 0.67 | 0.00 |
July | 0.75 | 0.00 |
August | 0.83 | 0.00 |
September | 0.12 | 0.00 |
October | 1.36 | 0.23 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 5.83 | 0.35 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.36 | 3.47 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.31 | 0.00 |
February | 0.28 | 0.37 |
March | 2.36 | 0.59 |
April | 5.11 | 0.67 |
May | 5.21 | 0.70 |
June | 5.32 | 0.67 |
July | 5.48 | 0.67 |
August | 5.03 | 0.68 |
September | 3.88 | 0.72 |
October | 2.97 | 0.69 |
November | 0.28 | 0.75 |
December | 0.00 | 0.00 |
Annual Sum or Average | 36.23 | 0.67 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 5.48 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.14 | 0.00 |
February | 0.19 | 0.54 |
March | 2.20 | 0.64 |
April | 5.03 | 0.68 |
May | 5.21 | 0.70 |
June | 5.32 | 0.67 |
July | 5.48 | 0.67 |
August | 4.94 | 0.68 |
September | 3.88 | 0.72 |
October | 2.97 | 0.69 |
November | 0.28 | 0.75 |
December | 0.00 | 0.00 |
Annual Sum or Average | 35.65 | 0.68 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 5.48 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 0.00 |
February | 0.19 | 0.54 |
March | 2.28 | 0.53 |
April | 5.20 | 0.67 |
May | 5.12 | 0.71 |
June | 5.38 | 0.67 |
July | 5.53 | 0.67 |
August | 4.97 | 0.68 |
September | 3.88 | 0.72 |
October | 2.83 | 0.68 |
November | 0.36 | 0.58 |
December | 0.00 | 0.00 |
Annual Sum or Average | 35.84 | 0.67 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 5.53 | 0.72 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 0.00 |
February | 0.11 | 0.00 |
March | 0.81 | 2.96 |
April | 2.29 | 2.14 |
May | 1.77 | 2.00 |
June | 1.44 | 1.96 |
July | 2.11 | 2.54 |
August | 1.86 | 1.92 |
September | 1.91 | 2.27 |
October | 2.02 | 2.48 |
November | 0.31 | 1.50 |
December | 0.00 | 0.00 |
Annual Sum or Average | 14.71 | 2.20 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.29 | 2.96 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 0.00 |
February | 0.11 | 0.00 |
March | 0.64 | 1.44 |
April | 1.96 | 1.18 |
May | 1.52 | 1.08 |
June | 1.44 | 0.88 |
July | 2.33 | 1.21 |
August | 1.61 | 1.03 |
September | 1.66 | 1.30 |
October | 2.19 | 1.15 |
November | 0.22 | 1.03 |
December | 0.00 | 0.00 |
Annual Sum or Average | 13.76 | 1.13 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.33 | 1.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 0.00 |
February | 0.00 | 0.00 |
March | 0.56 | 1.65 |
April | 1.88 | 1.23 |
May | 1.52 | 1.08 |
June | 1.44 | 0.88 |
July | 1.99 | 1.27 |
August | 1.61 | 1.03 |
September | 1.66 | 1.30 |
October | 2.30 | 1.05 |
November | 0.22 | 1.03 |
December | 0.00 | 0.00 |
Annual Sum or Average | 13.26 | 1.14 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.30 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 0.00 |
February | 0.00 | 0.00 |
March | 0.56 | 1.65 |
April | 1.88 | 1.23 |
May | 1.52 | 1.08 |
June | 1.44 | 0.88 |
July | 2.33 | 1.21 |
August | 1.67 | 0.99 |
September | 1.66 | 1.30 |
October | 2.30 | 1.05 |
November | 0.14 | 1.65 |
December | 0.00 | 0.00 |
Annual Sum or Average | 13.57 | 1.14 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.33 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.64 | 1.65 |
April | 1.49 | 1.50 |
May | 1.38 | 0.92 |
June | 1.21 | 0.97 |
July | 1.82 | 1.26 |
August | 1.92 | 0.79 |
September | 1.94 | 1.00 |
October | 2.85 | 0.83 |
November | 0.14 | 1.65 |
December | 0.00 | 0.00 |
Annual Sum or Average | 13.40 | 1.05 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.85 | 1.65 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.282863E+10 | 0.351182E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.414730E+10 | 18077407.40 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.756893E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.114538E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.162661E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.177362E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.185908E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.178271E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.149723E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.106644E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.661244E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.353616E+10 | 45261140.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.132204E+12 | 0.414520E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.282863E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.185908E+11 | 0.351182E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.165557E+10 | 55310620.63 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.232558E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.394485E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.572282E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.805914E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.872059E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.910966E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.874636E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.734540E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.533746E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.349716E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.207453E+10 | 2717104.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.665391E+11 | 58027724.95 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.165557E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.910966E+10 | 55310620.63 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.124372E+10 | 0.154593E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.177592E+10 | 2088839.48 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.316774E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.462731E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.669202E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.723221E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.741114E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.729227E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.597874E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.431267E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.278552E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.155406E+10 | 10166158.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.540733E+11 | 0.166848E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.124372E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.741114E+10 | 0.154593E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.121314E+10 | 0.211667E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.175256E+10 | 3839312.63 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.316327E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.464222E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.672745E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.726912E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.745491E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.732183E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.599992E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.432603E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.277625E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.152419E+10 | 15368861.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.541709E+11 | 0.230875E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.121314E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.745491E+10 | 0.211667E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.115377E+10 | 0.288924E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.168614E+10 | 10389098.50 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.309265E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.457924E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.666050E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.719859E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.738859E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.724892E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.593256E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.426511E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.271216E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.145379E+10 | 25706953.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.533720E+11 | 0.325020E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.115377E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.738859E+10 | 0.288924E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.169158E+10 | 0.691551E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.261458E+10 | 50116513.78 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.521092E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.801281E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.118689E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.128896E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.131522E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.129331E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.104437E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.740994E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.449908E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.211018E+10 | 82589502.53 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.928366E+11 | 0.824257E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.169158E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.131522E+11 | 0.691551E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.900462E+09 | 0.371223E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.136378E+10 | 25244116.79 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.270100E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.414364E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.613553E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.664938E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.678101E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.666296E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.538684E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.382938E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.233606E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.110880E+10 | 42188352.79 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.479988E+11 | 0.438655E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.900462E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.678101E+10 | 0.371223E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.888518E+09 | 0.399760E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.134274E+10 | 30541573.57 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.267614E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.412124E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.611078E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.662433E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.675765E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.663918E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.536508E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.380868E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.231479E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.108933E+10 | 48790129.70 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.477384E+11 | 0.479092E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.888518E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.675765E+10 | 0.399760E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.877103E+09 | 0.475721E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.130913E+10 | 49874776.55 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.264079E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.411505E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.612618E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.664782E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.679043E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.666990E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.538394E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.381047E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.229071E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.106122E+10 | 67651286.99 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.477228E+11 | 0.593247E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.877103E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.679043E+10 | 0.475721E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.953522E+09 | 0.682163E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.139228E+10 | 0.131901E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.281328E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.450617E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.675797E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.732937E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.749990E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.736469E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.594051E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.421348E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.248502E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.114568E+10 | 0.141789E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.524018E+11 | 0.955853E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.953522E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.749990E+10 | 0.682163E+09 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.210000E+10 | 0.266016E+10 | 0.280945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.189383E+10 | 0.839323E+10 | 14461925.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.209779E+10 | 0.203461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.212164E+10 | 0.328961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.251666E+10 | 0.480699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.266112E+10 | 0.546933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.282177E+10 | 0.623264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.277169E+10 | 0.616763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.239550E+10 | 0.510516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.213214E+10 | 0.326817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.202234E+10 | 0.173593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.210200E+10 | 0.529295E+10 | 36208912.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.276365E+11 | 0.397447E+12 | 0.331616E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.189383E+10 | 0.266016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.282177E+10 | 0.623264E+11 | 0.280945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.909273E+09 | 0.272248E+10 | 44248496.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.845161E+09 | 0.556966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.976870E+09 | 0.111569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102955E+10 | 0.166038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.127276E+10 | 0.237649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135685E+10 | 0.267784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144143E+10 | 0.303753E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141498E+10 | 0.300944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.120750E+10 | 0.249144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102443E+10 | 0.165841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.928367E+09 | 0.981406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.919216E+09 | 0.428481E+10 | 2173683.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133264E+11 | 0.202663E+12 | 46422179.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.845161E+09 | 0.272248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144143E+10 | 0.303753E+11 | 44248496.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.902387E+09 | 0.127239E+10 | 0.123674E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.814137E+09 | 0.365745E+10 | 1671071.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.917820E+09 | 0.852284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.920946E+09 | 0.132968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112658E+10 | 0.197200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119303E+10 | 0.223076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.124161E+10 | 0.249171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124560E+10 | 0.252486E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104944E+10 | 0.204100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.919197E+09 | 0.132065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.872433E+09 | 0.736228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.894825E+09 | 0.248364E+10 | 8132926.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120980E+11 | 0.162405E+12 | 0.133478E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.814137E+09 | 0.127239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124560E+10 | 0.252486E+11 | 0.123674E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.905298E+09 | 0.114530E+10 | 0.169333E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.815704E+09 | 0.355543E+10 | 3071450.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.919543E+09 | 0.849360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.922939E+09 | 0.133473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113109E+10 | 0.198397E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119836E+10 | 0.224289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.124930E+10 | 0.250592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.125034E+10 | 0.253518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105231E+10 | 0.204897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.921183E+09 | 0.132527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.874067E+09 | 0.731322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.896617E+09 | 0.235847E+10 | 12295089.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121367E+11 | 0.162635E+12 | 0.184700E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.815704E+09 | 0.114530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.125034E+10 | 0.253518E+11 | 0.169333E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.901318E+09 | 0.935964E+09 | 0.231139E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.810747E+09 | 0.330883E+10 | 8311278.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.913715E+09 | 0.822395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.915247E+09 | 0.131295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112080E+10 | 0.196295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.118696E+10 | 0.222085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123781E+10 | 0.248426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.123806E+10 | 0.251038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104168E+10 | 0.202503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.914331E+09 | 0.130219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.868541E+09 | 0.706683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.891237E+09 | 0.210545E+10 | 20565562.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120404E+11 | 0.159827E+12 | 0.260016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.810747E+09 | 0.935964E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.123806E+10 | 0.251038E+11 | 0.231139E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.141868E+10 | 0.985215E+09 | 0.553241E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127310E+10 | 0.492718E+10 | 40093211.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143574E+10 | 0.138995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144434E+10 | 0.230189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.180499E+10 | 0.350061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.193084E+10 | 0.397521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.202626E+10 | 0.442347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.202166E+10 | 0.449097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167206E+10 | 0.357301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143961E+10 | 0.227455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136302E+10 | 0.117236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139870E+10 | 0.259357E+10 | 66071602.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192290E+11 | 0.279526E+12 | 0.659406E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127310E+10 | 0.985215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.202626E+10 | 0.449097E+11 | 0.553241E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.776827E+09 | 0.453290E+09 | 0.296978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.696943E+09 | 0.248706E+10 | 20195293.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.785916E+09 | 0.716014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.790139E+09 | 0.119307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.986689E+09 | 0.181736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.105096E+10 | 0.206120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110035E+10 | 0.229377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109741E+10 | 0.232627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.911127E+09 | 0.185078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.787221E+09 | 0.117674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.746164E+09 | 0.603593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.765700E+09 | 0.127035E+10 | 33750682.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104955E+11 | 0.144599E+12 | 0.350924E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.696943E+09 | 0.453290E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110035E+10 | 0.232627E+11 | 0.296978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.774266E+09 | 0.418369E+09 | 0.319808E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.694191E+09 | 0.241552E+10 | 24433258.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.782656E+09 | 0.707345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.786686E+09 | 0.118597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.982704E+09 | 0.181006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104675E+10 | 0.205371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109629E+10 | 0.228642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109324E+10 | 0.231859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.907366E+09 | 0.184359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.783907E+09 | 0.116973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.743090E+09 | 0.596238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.762694E+09 | 0.120813E+10 | 39032103.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104538E+11 | 0.143758E+12 | 0.383273E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.694191E+09 | 0.418369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109629E+10 | 0.231859E+11 | 0.319808E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.778431E+09 | 0.360276E+09 | 0.380577E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.696911E+09 | 0.227222E+10 | 39899821.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.785181E+09 | 0.691370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.788600E+09 | 0.118193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.986016E+09 | 0.181361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.105122E+10 | 0.205984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110247E+10 | 0.229610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109881E+10 | 0.232840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.910926E+09 | 0.184940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.786498E+09 | 0.116881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.745557E+09 | 0.585025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.765631E+09 | 0.109041E+10 | 54121029.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104963E+11 | 0.143468E+12 | 0.474598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.696911E+09 | 0.360276E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110247E+10 | 0.232840E+11 | 0.380577E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.850897E+09 | 0.373752E+09 | 0.545730E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.760534E+09 | 0.233371E+10 | 0.105521E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.854821E+09 | 0.725268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.858061E+09 | 0.129318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107482E+10 | 0.199750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.114908E+10 | 0.225847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.120575E+10 | 0.252173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119906E+10 | 0.255840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.993730E+09 | 0.203303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.858475E+09 | 0.129620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.811924E+09 | 0.632146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.835166E+09 | 0.114334E+10 | 0.113432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114523E+11 | 0.157010E+12 | 0.764683E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.760534E+09 | 0.373752E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.120575E+10 | 0.255840E+11 | 0.545730E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.210000E+10 | 0.00 | 0.00 | 0.00 | 0.728633E+09 | 0.00 | 0.351182E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.189383E+10 | 0.00 | 0.00 | 0.00 | 0.225347E+10 | 0.00 | 18077407.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.209779E+10 | 0.00 | 0.00 | 0.00 | 0.547114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.212164E+10 | 0.00 | 0.00 | 0.00 | 0.933215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.251666E+10 | 0.00 | 0.00 | 0.00 | 0.137495E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.266112E+10 | 0.00 | 0.00 | 0.00 | 0.150751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.282177E+10 | 0.00 | 0.00 | 0.00 | 0.157690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.277169E+10 | 0.00 | 0.00 | 0.00 | 0.150554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.239550E+10 | 0.00 | 0.00 | 0.00 | 0.125768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.213214E+10 | 0.00 | 0.00 | 0.00 | 0.853227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.202234E+10 | 0.00 | 0.00 | 0.00 | 0.459009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.210200E+10 | 0.00 | 0.00 | 0.00 | 0.143416E+10 | 0.00 | 45261140.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.276365E+11 | 0.00 | 0.00 | 0.00 | 0.104568E+12 | 0.00 | 0.414520E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.189383E+10 | 0.00 | 0.00 | 0.00 | 0.728633E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.282177E+10 | 0.00 | 0.00 | 0.00 | 0.157690E+11 | 0.00 | 0.351182E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.909273E+09 | 0.00 | 0.00 | 0.00 | 0.746300E+09 | 0.00 | 55310620.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.845161E+09 | 0.00 | 0.00 | 0.00 | 0.148042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.976870E+09 | 0.00 | 0.00 | 0.00 | 0.296798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102955E+10 | 0.00 | 0.00 | 0.00 | 0.469327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.127276E+10 | 0.00 | 0.00 | 0.00 | 0.678638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135685E+10 | 0.00 | 0.00 | 0.00 | 0.736374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144143E+10 | 0.00 | 0.00 | 0.00 | 0.766823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141498E+10 | 0.00 | 0.00 | 0.00 | 0.733138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.120750E+10 | 0.00 | 0.00 | 0.00 | 0.613790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102443E+10 | 0.00 | 0.00 | 0.00 | 0.431303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.928367E+09 | 0.00 | 0.00 | 0.00 | 0.256880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.919216E+09 | 0.00 | 0.00 | 0.00 | 0.115532E+10 | 0.00 | 2717104.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133264E+11 | 0.00 | 0.00 | 0.00 | 0.532127E+11 | 0.00 | 58027724.95 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.845161E+09 | 0.00 | 0.00 | 0.00 | 0.746300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144143E+10 | 0.00 | 0.00 | 0.00 | 0.766823E+10 | 0.00 | 55310620.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.902387E+09 | 0.00 | 0.00 | 0.00 | 0.341336E+09 | 0.00 | 0.154593E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.814137E+09 | 0.00 | 0.00 | 0.00 | 0.961783E+09 | 0.00 | 2088839.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.917820E+09 | 0.00 | 0.00 | 0.00 | 0.224992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.920946E+09 | 0.00 | 0.00 | 0.00 | 0.370636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112658E+10 | 0.00 | 0.00 | 0.00 | 0.556544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119303E+10 | 0.00 | 0.00 | 0.00 | 0.603918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.124161E+10 | 0.00 | 0.00 | 0.00 | 0.616953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124560E+10 | 0.00 | 0.00 | 0.00 | 0.604667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104944E+10 | 0.00 | 0.00 | 0.00 | 0.492930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.919197E+09 | 0.00 | 0.00 | 0.00 | 0.339348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.872433E+09 | 0.00 | 0.00 | 0.00 | 0.191308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.894825E+09 | 0.00 | 0.00 | 0.00 | 0.659237E+09 | 0.00 | 10166158.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120980E+11 | 0.00 | 0.00 | 0.00 | 0.419753E+11 | 0.00 | 0.166848E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.814137E+09 | 0.00 | 0.00 | 0.00 | 0.341336E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124560E+10 | 0.00 | 0.00 | 0.00 | 0.616953E+10 | 0.00 | 0.154593E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.905298E+09 | 0.00 | 0.00 | 0.00 | 0.307842E+09 | 0.00 | 0.211667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.815704E+09 | 0.00 | 0.00 | 0.00 | 0.936852E+09 | 0.00 | 3839312.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.919543E+09 | 0.00 | 0.00 | 0.00 | 0.224373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.922939E+09 | 0.00 | 0.00 | 0.00 | 0.371928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113109E+10 | 0.00 | 0.00 | 0.00 | 0.559636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119836E+10 | 0.00 | 0.00 | 0.00 | 0.607077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.124930E+10 | 0.00 | 0.00 | 0.00 | 0.620561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.125034E+10 | 0.00 | 0.00 | 0.00 | 0.607150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105231E+10 | 0.00 | 0.00 | 0.00 | 0.494761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.921183E+09 | 0.00 | 0.00 | 0.00 | 0.340484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.874067E+09 | 0.00 | 0.00 | 0.00 | 0.190218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.896617E+09 | 0.00 | 0.00 | 0.00 | 0.627571E+09 | 0.00 | 15368861.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121367E+11 | 0.00 | 0.00 | 0.00 | 0.420341E+11 | 0.00 | 0.230875E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.815704E+09 | 0.00 | 0.00 | 0.00 | 0.307842E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.125034E+10 | 0.00 | 0.00 | 0.00 | 0.620561E+10 | 0.00 | 0.211667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.901318E+09 | 0.00 | 0.00 | 0.00 | 0.252452E+09 | 0.00 | 0.288924E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.810747E+09 | 0.00 | 0.00 | 0.00 | 0.875397E+09 | 0.00 | 10389098.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.913715E+09 | 0.00 | 0.00 | 0.00 | 0.217893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.915247E+09 | 0.00 | 0.00 | 0.00 | 0.366399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112080E+10 | 0.00 | 0.00 | 0.00 | 0.553970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.118696E+10 | 0.00 | 0.00 | 0.00 | 0.601162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123781E+10 | 0.00 | 0.00 | 0.00 | 0.615078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.123806E+10 | 0.00 | 0.00 | 0.00 | 0.601086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104168E+10 | 0.00 | 0.00 | 0.00 | 0.489088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.914331E+09 | 0.00 | 0.00 | 0.00 | 0.335078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.868541E+09 | 0.00 | 0.00 | 0.00 | 0.184362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.891237E+09 | 0.00 | 0.00 | 0.00 | 0.562555E+09 | 0.00 | 25706953.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120404E+11 | 0.00 | 0.00 | 0.00 | 0.413316E+11 | 0.00 | 0.325020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.810747E+09 | 0.00 | 0.00 | 0.00 | 0.252452E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.123806E+10 | 0.00 | 0.00 | 0.00 | 0.615078E+10 | 0.00 | 0.288924E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.141868E+10 | 0.00 | 0.00 | 0.00 | 0.272903E+09 | 0.00 | 0.691551E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127310E+10 | 0.00 | 0.00 | 0.00 | 0.134147E+10 | 0.00 | 50116513.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143574E+10 | 0.00 | 0.00 | 0.00 | 0.377518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144434E+10 | 0.00 | 0.00 | 0.00 | 0.656847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.180499E+10 | 0.00 | 0.00 | 0.00 | 0.100639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.193084E+10 | 0.00 | 0.00 | 0.00 | 0.109588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.202626E+10 | 0.00 | 0.00 | 0.00 | 0.111259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.202166E+10 | 0.00 | 0.00 | 0.00 | 0.109115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167206E+10 | 0.00 | 0.00 | 0.00 | 0.877166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143961E+10 | 0.00 | 0.00 | 0.00 | 0.597033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136302E+10 | 0.00 | 0.00 | 0.00 | 0.313606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139870E+10 | 0.00 | 0.00 | 0.00 | 0.711479E+09 | 0.00 | 82589502.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192290E+11 | 0.00 | 0.00 | 0.00 | 0.736076E+11 | 0.00 | 0.824257E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.127310E+10 | 0.00 | 0.00 | 0.00 | 0.272903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.202626E+10 | 0.00 | 0.00 | 0.00 | 0.111259E+11 | 0.00 | 0.691551E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.776827E+09 | 0.00 | 0.00 | 0.00 | 0.123635E+09 | 0.00 | 0.371223E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.696943E+09 | 0.00 | 0.00 | 0.00 | 0.666840E+09 | 0.00 | 25244116.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.785916E+09 | 0.00 | 0.00 | 0.00 | 0.191509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.790139E+09 | 0.00 | 0.00 | 0.00 | 0.335351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.986689E+09 | 0.00 | 0.00 | 0.00 | 0.514884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.105096E+10 | 0.00 | 0.00 | 0.00 | 0.559842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110035E+10 | 0.00 | 0.00 | 0.00 | 0.568066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109741E+10 | 0.00 | 0.00 | 0.00 | 0.556555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.911127E+09 | 0.00 | 0.00 | 0.00 | 0.447571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.787221E+09 | 0.00 | 0.00 | 0.00 | 0.304216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.746164E+09 | 0.00 | 0.00 | 0.00 | 0.158989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.765700E+09 | 0.00 | 0.00 | 0.00 | 0.343098E+09 | 0.00 | 42188352.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104955E+11 | 0.00 | 0.00 | 0.00 | 0.375034E+11 | 0.00 | 0.438655E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.696943E+09 | 0.00 | 0.00 | 0.00 | 0.123635E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110035E+10 | 0.00 | 0.00 | 0.00 | 0.568066E+10 | 0.00 | 0.371223E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.774266E+09 | 0.00 | 0.00 | 0.00 | 0.114252E+09 | 0.00 | 0.399760E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.694191E+09 | 0.00 | 0.00 | 0.00 | 0.648548E+09 | 0.00 | 30541573.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.782656E+09 | 0.00 | 0.00 | 0.00 | 0.189348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.786686E+09 | 0.00 | 0.00 | 0.00 | 0.333455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.982704E+09 | 0.00 | 0.00 | 0.00 | 0.512807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104675E+10 | 0.00 | 0.00 | 0.00 | 0.557758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109629E+10 | 0.00 | 0.00 | 0.00 | 0.566136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109324E+10 | 0.00 | 0.00 | 0.00 | 0.554594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.907366E+09 | 0.00 | 0.00 | 0.00 | 0.445772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.783907E+09 | 0.00 | 0.00 | 0.00 | 0.302477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.743090E+09 | 0.00 | 0.00 | 0.00 | 0.157170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.762694E+09 | 0.00 | 0.00 | 0.00 | 0.326640E+09 | 0.00 | 48790129.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104538E+11 | 0.00 | 0.00 | 0.00 | 0.372846E+11 | 0.00 | 0.479092E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.694191E+09 | 0.00 | 0.00 | 0.00 | 0.114252E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109629E+10 | 0.00 | 0.00 | 0.00 | 0.566136E+10 | 0.00 | 0.399760E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.778431E+09 | 0.00 | 0.00 | 0.00 | 98671930.81 | 0.00 | 0.475721E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.696911E+09 | 0.00 | 0.00 | 0.00 | 0.612216E+09 | 0.00 | 49874776.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.785181E+09 | 0.00 | 0.00 | 0.00 | 0.185561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.788600E+09 | 0.00 | 0.00 | 0.00 | 0.332645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.986016E+09 | 0.00 | 0.00 | 0.00 | 0.514016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.105122E+10 | 0.00 | 0.00 | 0.00 | 0.559660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110247E+10 | 0.00 | 0.00 | 0.00 | 0.568796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109881E+10 | 0.00 | 0.00 | 0.00 | 0.557109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.910926E+09 | 0.00 | 0.00 | 0.00 | 0.447301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.786498E+09 | 0.00 | 0.00 | 0.00 | 0.302398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.745557E+09 | 0.00 | 0.00 | 0.00 | 0.154515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.765631E+09 | 0.00 | 0.00 | 0.00 | 0.295588E+09 | 0.00 | 67651286.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104963E+11 | 0.00 | 0.00 | 0.00 | 0.372265E+11 | 0.00 | 0.593247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.696911E+09 | 0.00 | 0.00 | 0.00 | 98671930.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110247E+10 | 0.00 | 0.00 | 0.00 | 0.568796E+10 | 0.00 | 0.475721E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.850897E+09 | 0.00 | 0.00 | 0.00 | 0.102625E+09 | 0.00 | 0.682163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.760534E+09 | 0.00 | 0.00 | 0.00 | 0.631742E+09 | 0.00 | 0.131901E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.854821E+09 | 0.00 | 0.00 | 0.00 | 0.195845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.858061E+09 | 0.00 | 0.00 | 0.00 | 0.364811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107482E+10 | 0.00 | 0.00 | 0.00 | 0.568315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.114908E+10 | 0.00 | 0.00 | 0.00 | 0.618029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.120575E+10 | 0.00 | 0.00 | 0.00 | 0.629415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119906E+10 | 0.00 | 0.00 | 0.00 | 0.616564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.993730E+09 | 0.00 | 0.00 | 0.00 | 0.494678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.858475E+09 | 0.00 | 0.00 | 0.00 | 0.335500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.811924E+09 | 0.00 | 0.00 | 0.00 | 0.167309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.835166E+09 | 0.00 | 0.00 | 0.00 | 0.310512E+09 | 0.00 | 0.141789E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114523E+11 | 0.00 | 0.00 | 0.00 | 0.409495E+11 | 0.00 | 0.955853E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.760534E+09 | 0.00 | 0.00 | 0.00 | 0.102625E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.120575E+10 | 0.00 | 0.00 | 0.00 | 0.629415E+10 | 0.00 | 0.682163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.386089E+10 | 281718.27 | 0.00 | 6875411.12 | 0.00 | 87910728.50 | 0.347702E+10 | 0.00 | 0.57 |
February | 0.139471E+10 | 0.203790E+09 | 0.00 | 9652722.45 | 0.00 | 1251020.81 | 0.218375E+10 | 0.00 | 0.57 |
March | 0.251494E+09 | 0.281362E+10 | 0.00 | 5584806.08 | 5980868.81 | 0.00 | 0.590543E+09 | 0.00 | 0.57 |
April | 3218268.88 | 0.838126E+10 | 0.00 | 580170.92 | 70176013.19 | 0.00 | 17739809.82 | 0.00 | 0.58 |
May | 0.00 | 0.163393E+11 | 0.00 | 105709.83 | 93307692.60 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.210652E+11 | 0.00 | 0.00 | 93139998.44 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.260458E+11 | 0.00 | 0.00 | 62331061.63 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.260302E+11 | 0.00 | 0.00 | 93636866.19 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.200099E+11 | 0.00 | 0.00 | 0.123877E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
October | 12427318.20 | 0.759005E+10 | 0.00 | 1213822.27 | 47541761.98 | 0.00 | 84391884.92 | 0.00 | 0.57 |
November | 0.306707E+09 | 0.144030E+10 | 0.00 | 9145123.47 | 34845.52 | 0.00 | 0.157422E+10 | 0.00 | 0.57 |
December | 0.252639E+10 | 9916165.94 | 0.00 | 11127154.31 | 0.00 | 1472448.18 | 0.397274E+10 | 0.00 | 0.57 |
Annual Sum or Average | 0.835584E+10 | 0.129930E+12 | 0.00 | 44284920.45 | 0.590026E+09 | 90634197.50 | 0.119004E+11 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 281718.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.386089E+10 | 0.260458E+11 | 0.00 | 11127154.31 | 0.123877E+09 | 87910728.50 | 0.397274E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.103738E+10 | 151567.52 | 0.00 | 5470973.36 | 0.00 | 9915792.53 | 0.149841E+10 | 0.00 | 0.44 |
February | 0.412465E+09 | 0.108332E+09 | 0.00 | 6139080.82 | 277715.28 | 0.00 | 0.692124E+09 | 0.00 | 0.45 |
March | 67191894.28 | 0.130587E+10 | 0.00 | 3124840.91 | 7473195.31 | 0.00 | 0.172101E+09 | 0.00 | 0.47 |
April | 1264396.20 | 0.363675E+10 | 0.00 | 328283.78 | 37842467.17 | 0.00 | 5947969.07 | 0.00 | 0.48 |
May | 0.00 | 0.721730E+10 | 0.00 | 11722.45 | 39300850.13 | 0.00 | 0.00 | 0.00 | 0.50 |
June | 0.00 | 0.934002E+10 | 0.00 | 0.00 | 52587361.81 | 0.00 | 0.00 | 0.00 | 0.51 |
July | 0.00 | 0.115341E+11 | 0.00 | 0.00 | 45786424.77 | 0.00 | 0.00 | 0.00 | 0.51 |
August | 0.00 | 0.115600E+11 | 0.00 | 0.00 | 64370169.83 | 0.00 | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.871921E+10 | 0.00 | 0.00 | 76399850.99 | 0.00 | 0.00 | 0.00 | 0.50 |
October | 1375129.71 | 0.338068E+10 | 0.00 | 349028.48 | 37583677.73 | 0.00 | 10187152.59 | 0.00 | 0.47 |
November | 90841034.71 | 0.728181E+09 | 0.00 | 4803058.88 | 1615415.91 | 0.00 | 0.361213E+09 | 0.00 | 0.46 |
December | 0.702446E+09 | 5476151.05 | 0.00 | 7241392.60 | 0.00 | 0.00 | 0.135968E+10 | 0.00 | 0.44 |
Annual Sum or Average | 0.231296E+10 | 0.575361E+11 | 0.00 | 27468381.29 | 0.363237E+09 | 9915792.53 | 0.409966E+10 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 151567.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.103738E+10 | 0.115600E+11 | 0.00 | 7241392.60 | 76399850.99 | 9915792.53 | 0.149841E+10 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.155756E+10 | 202704.34 | 0.00 | 2712092.92 | 0.00 | 63790033.93 | 0.104036E+10 | 0.00 | 0.45 |
February | 0.728297E+09 | 0.105690E+09 | 0.00 | 3217665.53 | 517770.61 | 0.00 | 0.546328E+09 | 0.00 | 0.45 |
March | 0.147762E+09 | 0.112762E+10 | 0.00 | 1972627.46 | 56973187.51 | 0.00 | 0.220990E+09 | 0.00 | 0.46 |
April | 1429611.14 | 0.312674E+10 | 0.00 | 295674.79 | 0.214565E+09 | 0.00 | 5807863.61 | 0.00 | 0.46 |
May | 9403.96 | 0.610754E+10 | 0.00 | 175901.94 | 0.400641E+09 | 0.00 | 36716.11 | 0.00 | 0.47 |
June | 0.00 | 0.766174E+10 | 0.00 | 0.00 | 0.523609E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.916255E+10 | 0.00 | 0.00 | 0.602429E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.938166E+10 | 0.00 | 0.00 | 0.623819E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.698147E+10 | 0.00 | 13837.36 | 0.485968E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 8906828.71 | 0.283627E+10 | 0.00 | 1016061.00 | 0.172472E+09 | 0.00 | 67979524.86 | 0.00 | 0.46 |
November | 0.269093E+09 | 0.678614E+09 | 0.00 | 2502504.55 | 11295411.14 | 0.00 | 0.389617E+09 | 0.00 | 0.46 |
December | 0.125844E+10 | 5820314.34 | 0.00 | 4082282.34 | 0.00 | 0.00 | 0.932122E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.397150E+10 | 0.471759E+11 | 0.00 | 15988647.87 | 0.309229E+10 | 63790033.93 | 0.320324E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 202704.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.155756E+10 | 0.938166E+10 | 0.00 | 4082282.34 | 0.623819E+09 | 63790033.93 | 0.104036E+10 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.158967E+10 | 190535.55 | 0.00 | 2430202.13 | 0.00 | 80954524.34 | 0.975473E+09 | 0.00 | 0.45 |
February | 0.738230E+09 | 0.104520E+09 | 0.00 | 3092203.56 | 514534.95 | 0.00 | 0.533919E+09 | 0.00 | 0.45 |
March | 0.152910E+09 | 0.112697E+10 | 0.00 | 1953983.84 | 56958318.27 | 0.00 | 0.215919E+09 | 0.00 | 0.46 |
April | 1427586.22 | 0.312992E+10 | 0.00 | 309067.52 | 0.214424E+09 | 0.00 | 5761521.42 | 0.00 | 0.46 |
May | 10912.33 | 0.612107E+10 | 0.00 | 181806.52 | 0.396598E+09 | 0.00 | 38047.01 | 0.00 | 0.47 |
June | 0.00 | 0.767854E+10 | 0.00 | 1851.65 | 0.520167E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.918283E+10 | 0.00 | 0.00 | 0.602287E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.940205E+10 | 0.00 | 0.00 | 0.620254E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.699665E+10 | 0.00 | 17379.95 | 0.484234E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 8916567.87 | 0.284214E+10 | 0.00 | 1040242.78 | 0.171317E+09 | 0.00 | 67767252.85 | 0.00 | 0.46 |
November | 0.278289E+09 | 0.677485E+09 | 0.00 | 2462956.70 | 11282711.78 | 0.00 | 0.380773E+09 | 0.00 | 0.46 |
December | 0.127242E+10 | 5669147.44 | 0.00 | 3907114.40 | 0.00 | 0.00 | 0.913709E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.404188E+10 | 0.472680E+11 | 0.00 | 15396809.05 | 0.307804E+10 | 80954524.34 | 0.309336E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 190535.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.158967E+10 | 0.940205E+10 | 0.00 | 3907114.40 | 0.620254E+09 | 80954524.34 | 0.975473E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.167384E+10 | 167621.79 | 0.00 | 1954894.52 | 0.00 | 0.101310E+09 | 0.846418E+09 | 0.00 | 0.45 |
February | 0.778908E+09 | 0.101382E+09 | 0.00 | 2792229.96 | 498347.45 | 0.00 | 0.492033E+09 | 0.00 | 0.45 |
March | 0.170962E+09 | 0.111537E+10 | 0.00 | 1817649.89 | 57167531.87 | 0.00 | 0.202259E+09 | 0.00 | 0.46 |
April | 1430863.75 | 0.312013E+10 | 0.00 | 275901.24 | 0.215382E+09 | 0.00 | 5851371.51 | 0.00 | 0.46 |
May | 8126.79 | 0.610149E+10 | 0.00 | 168555.99 | 0.399242E+09 | 0.00 | 36999.05 | 0.00 | 0.47 |
June | 0.00 | 0.765004E+10 | 0.00 | 619.71 | 0.524153E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.915209E+10 | 0.00 | 0.00 | 0.602208E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.935774E+10 | 0.00 | 0.00 | 0.625463E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.695788E+10 | 0.00 | 15021.43 | 0.484664E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 9635910.23 | 0.282105E+10 | 0.00 | 974399.58 | 0.171871E+09 | 0.00 | 69611484.82 | 0.00 | 0.46 |
November | 0.303200E+09 | 0.669354E+09 | 0.00 | 2295417.73 | 11257484.20 | 0.00 | 0.361273E+09 | 0.00 | 0.46 |
December | 0.130320E+10 | 5422341.31 | 0.00 | 3518079.90 | 0.00 | 0.00 | 0.878279E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.424118E+10 | 0.470521E+11 | 0.00 | 13812769.93 | 0.309191E+10 | 0.101310E+09 | 0.285576E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 167621.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.167384E+10 | 0.935774E+10 | 0.00 | 3518079.90 | 0.625463E+09 | 0.101310E+09 | 0.878279E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.323594E+10 | 0.00 | 0.00 | 2057339.11 | 0.00 | 0.261331E+09 | 0.104455E+10 | 0.00 | 0.42 |
February | 0.123576E+10 | 0.146929E+09 | 0.00 | 4505351.89 | 380500.56 | 1288063.58 | 0.899044E+09 | 0.00 | 0.42 |
March | 0.245333E+09 | 0.215329E+10 | 0.00 | 2917581.07 | 45130628.47 | 0.00 | 0.266048E+09 | 0.00 | 0.43 |
April | 1791744.21 | 0.613239E+10 | 0.00 | 210558.22 | 0.198321E+09 | 0.00 | 5059888.83 | 0.00 | 0.42 |
May | 0.00 | 0.119475E+11 | 0.00 | 93182.47 | 0.242200E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.149506E+11 | 0.00 | 0.00 | 0.277417E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.175646E+11 | 0.00 | 0.00 | 0.406522E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.182697E+11 | 0.00 | 0.00 | 0.362256E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.134358E+11 | 0.00 | 24249.05 | 0.374572E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 12177566.14 | 0.551431E+10 | 0.00 | 887230.02 | 0.161291E+09 | 0.00 | 57695112.33 | 0.00 | 0.42 |
November | 0.335072E+09 | 0.119782E+10 | 0.00 | 3857634.24 | 17362735.93 | 0.00 | 0.606280E+09 | 0.00 | 0.42 |
December | 0.218979E+10 | 6360799.26 | 0.00 | 4701035.40 | 0.00 | 5543893.61 | 0.171562E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.725586E+10 | 0.913192E+11 | 0.00 | 19254161.46 | 0.208545E+10 | 0.268163E+09 | 0.459430E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.323594E+10 | 0.182697E+11 | 0.00 | 4701035.40 | 0.406522E+09 | 0.261331E+09 | 0.171562E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.163784E+10 | 0.00 | 0.00 | 900653.30 | 0.00 | 0.148755E+09 | 0.462441E+09 | 0.00 | 0.42 |
February | 0.632921E+09 | 72709275.85 | 0.00 | 2204034.87 | 186093.85 | 2169537.40 | 0.430415E+09 | 0.00 | 0.42 |
March | 0.125992E+09 | 0.107205E+10 | 0.00 | 1456683.14 | 22275357.91 | 0.00 | 0.130707E+09 | 0.00 | 0.43 |
April | 913895.04 | 0.306741E+10 | 0.00 | 101829.66 | 99566536.89 | 0.00 | 2549455.38 | 0.00 | 0.42 |
May | 0.00 | 0.597569E+10 | 0.00 | 41551.91 | 0.113975E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.746069E+10 | 0.00 | 0.00 | 0.135096E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.874328E+10 | 0.00 | 0.00 | 0.201754E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.908443E+10 | 0.00 | 0.00 | 0.177879E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.667807E+10 | 0.00 | 25043.08 | 0.185788E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 5697886.91 | 0.274127E+10 | 0.00 | 427407.77 | 81005808.80 | 0.00 | 29920694.43 | 0.00 | 0.42 |
November | 0.175271E+09 | 0.593509E+09 | 0.00 | 1920312.69 | 8471549.14 | 0.00 | 0.297461E+09 | 0.00 | 0.42 |
December | 0.111428E+10 | 3122968.12 | 0.00 | 2226580.89 | 0.00 | 7648754.16 | 0.828877E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.369292E+10 | 0.454922E+11 | 0.00 | 9304097.30 | 0.102600E+10 | 0.158573E+09 | 0.218237E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.163784E+10 | 0.908443E+10 | 0.00 | 2226580.89 | 0.201754E+09 | 0.148755E+09 | 0.828877E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.164714E+10 | 0.00 | 0.00 | 822696.33 | 0.00 | 0.167540E+09 | 0.422418E+09 | 0.00 | 0.42 |
February | 0.641822E+09 | 72108337.71 | 0.00 | 2125392.53 | 187386.28 | 2163380.52 | 0.419747E+09 | 0.00 | 0.42 |
March | 0.126327E+09 | 0.106881E+10 | 0.00 | 1416333.03 | 22263042.56 | 0.00 | 0.130922E+09 | 0.00 | 0.43 |
April | 916409.77 | 0.306507E+10 | 0.00 | 99129.53 | 99686563.37 | 0.00 | 2572289.92 | 0.00 | 0.42 |
May | 0.00 | 0.596969E+10 | 0.00 | 40893.12 | 0.114739E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.745254E+10 | 0.00 | 0.00 | 0.135573E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.872940E+10 | 0.00 | 0.00 | 0.205326E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.907269E+10 | 0.00 | 0.00 | 0.177697E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.666721E+10 | 0.00 | 25267.59 | 0.185808E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 5805580.77 | 0.273558E+10 | 0.00 | 423182.58 | 81333202.74 | 0.00 | 30260382.49 | 0.00 | 0.42 |
November | 0.181209E+09 | 0.591418E+09 | 0.00 | 1874505.05 | 8498099.10 | 0.00 | 0.293068E+09 | 0.00 | 0.42 |
December | 0.114601E+10 | 3089866.64 | 0.00 | 2105882.83 | 0.00 | 12753098.93 | 0.787983E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.374923E+10 | 0.454276E+11 | 0.00 | 8933282.60 | 0.103111E+10 | 0.182457E+09 | 0.208697E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.164714E+10 | 0.907269E+10 | 0.00 | 2125392.53 | 0.205326E+09 | 0.167540E+09 | 0.787983E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.159754E+10 | 0.00 | 0.00 | 692226.75 | 0.00 | 0.249942E+09 | 0.365381E+09 | 0.00 | 0.42 |
February | 0.654273E+09 | 70567472.11 | 0.00 | 1939400.52 | 190241.66 | 9603897.60 | 0.393161E+09 | 0.00 | 0.42 |
March | 0.136494E+09 | 0.105977E+10 | 0.00 | 1323022.95 | 22519276.64 | 0.00 | 0.121099E+09 | 0.00 | 0.43 |
April | 931721.57 | 0.306086E+10 | 0.00 | 94627.02 | 99550680.05 | 0.00 | 2649915.84 | 0.00 | 0.42 |
May | 0.00 | 0.596731E+10 | 0.00 | 40183.98 | 0.116211E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.745323E+10 | 0.00 | 0.00 | 0.138159E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.874286E+10 | 0.00 | 0.00 | 0.204012E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.908678E+10 | 0.00 | 0.00 | 0.178524E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.667291E+10 | 0.00 | 25206.97 | 0.187077E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 6846398.15 | 0.273189E+10 | 0.00 | 403698.90 | 81395201.73 | 0.00 | 29909794.27 | 0.00 | 0.42 |
November | 0.195589E+09 | 0.586407E+09 | 0.00 | 1770025.06 | 8521743.99 | 0.00 | 0.280810E+09 | 0.00 | 0.42 |
December | 0.119541E+10 | 2998955.37 | 0.00 | 1860319.18 | 0.00 | 13640660.33 | 0.725199E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.378708E+10 | 0.454356E+11 | 0.00 | 8148711.31 | 0.103616E+10 | 0.273187E+09 | 0.191821E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.159754E+10 | 0.908678E+10 | 0.00 | 1939400.52 | 0.204012E+09 | 0.249942E+09 | 0.725199E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.146651E+10 | 0.00 | 0.00 | 673542.37 | 0.00 | 0.376929E+09 | 0.347030E+09 | 0.00 | 0.42 |
February | 0.591066E+09 | 69748229.67 | 0.00 | 1921986.98 | 194280.92 | 66315349.02 | 0.374609E+09 | 0.00 | 0.42 |
March | 0.142749E+09 | 0.105201E+10 | 0.00 | 1309278.85 | 21333384.88 | 0.00 | 0.111851E+09 | 0.00 | 0.43 |
April | 688372.79 | 0.307230E+10 | 0.00 | 90243.43 | 92873357.82 | 0.00 | 3482936.46 | 0.00 | 0.42 |
May | 0.00 | 0.602236E+10 | 0.00 | 41642.29 | 99574253.36 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.756592E+10 | 0.00 | 37863.58 | 0.117543E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.891091E+10 | 0.00 | 0.00 | 0.183970E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.932252E+10 | 0.00 | 0.00 | 0.155229E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.685891E+10 | 0.00 | 52924.14 | 0.171163E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 8965405.39 | 0.279014E+10 | 0.00 | 379038.28 | 78585683.78 | 0.00 | 27732530.04 | 0.00 | 0.42 |
November | 0.212835E+09 | 0.591057E+09 | 0.00 | 1789127.89 | 8205617.13 | 0.00 | 0.256301E+09 | 0.00 | 0.42 |
December | 0.117515E+10 | 2947255.08 | 0.00 | 1840738.13 | 0.00 | 65659192.72 | 0.656018E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.359796E+10 | 0.462588E+11 | 0.00 | 8136385.95 | 0.928671E+09 | 0.508904E+09 | 0.177703E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.146651E+10 | 0.932252E+10 | 0.00 | 1921986.98 | 0.183970E+09 | 0.376929E+09 | 0.656018E+09 | 0.00 | 0.44 |