Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:20
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Honolulu Intl Arpt HI USA TMY3 WMO#=911820
Simulation Timestamp: 2020-06-03 19:20:44
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:44
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1401.46 | 670.45 | 670.45 |
Net Site Energy | 1401.46 | 670.45 | 670.45 |
Total Source Energy | 4438.43 | 2123.33 | 2123.33 |
Net Source Energy | 4438.43 | 2123.33 | 2123.33 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 474.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 550.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 97.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 58.55 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1401.46 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 474.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 550.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 91.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 97.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 58.55 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 307.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 301.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 670.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 307.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 301.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 670.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1401.460 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1401.460 | 100.00 |
Total On-Site and Utility Electric Sources | 1401.460 | 100.00 |
Total Electricity End Uses | 1401.460 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 240.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_HI_HONOLULU
| Meter |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:44
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Honolulu Intl Arpt HI USA TMY3 WMO#=911820 |
Latitude [deg] | 21.32 |
Longitude [deg] | -157.9 |
Elevation [m] | 2.00 |
Time Zone | -10.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.75 | 20.75 | 20.0855 | 11.61 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.37 | 10.37 | 22.9594 | 11.61 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 20.8066 | 11.61 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 20.8066 | 11.61 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 20.8066 | 11.61 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.70 | 20.70 | 13.4441 | 11.61 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 13.4441 | 11.61 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 13.4441 | 11.61 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 13.4441 | 11.61 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.35 | 10.35 | 13.4441 | 11.61 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 17.1846 | 11.61 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 17.1846 | 11.61 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:44
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 19-AUG-13:30 | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 52631.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 34106.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9080.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 9654.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 113532.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 52631.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 34106.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 9080.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 9654.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:44
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1501.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1744.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 291.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 309.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 185.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4438.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 718.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 834.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 139.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 148.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 88.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2123.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 718.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 834.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 139.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 148.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 88.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2123.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:44
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.00 |
SMSTORE1 DIRECT AIR | 1.06 |
SMSTORE2 DIRECT AIR | 1.05 |
SMSTORE3 DIRECT AIR | 1.06 |
SMSTORE4 DIRECT AIR | 1.05 |
LGSTORE2 DIRECT AIR | 1.82 |
SMSTORE5 DIRECT AIR | 0.948258 |
SMSTORE6 DIRECT AIR | 0.942838 |
SMSTORE7 DIRECT AIR | 0.944309 |
SMSTORE8 DIRECT AIR | 1.08 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.00 | 2.00 | 2.00 | 2.00 | 2.00 | 2.00 | 1.00 | 1.00 | 2.00 |
PSZ-AC_2:2 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.00 | 1.000000 | 1.06 |
PSZ-AC_3:3 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.00 | 1.000000 | 1.05 |
PSZ-AC_4:4 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.00 | 1.00 | 1.06 |
PSZ-AC_5:5 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.00 | 1.00 | 1.05 |
PSZ-AC_6:6 | 1.82 | 1.82 | 1.82 | 1.82 | 1.82 | 1.82 | 1.00 | 1.00 | 1.82 |
PSZ-AC_7:7 | 0.948258 | 0.948258 | 0.948258 | 0.948258 | 0.948258 | 0.948258 | 1.00 | 1.00 | 0.948258 |
PSZ-AC_8:8 | 0.942838 | 0.942838 | 0.942838 | 0.942838 | 0.942838 | 0.942838 | 1.00 | 1.00 | 0.942838 |
PSZ-AC_9:9 | 0.944309 | 0.944309 | 0.944309 | 0.944309 | 0.944309 | 0.944309 | 1.00 | 1.000000 | 0.944309 |
PSZ-AC_10:10 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.00 | 1.00 | 1.08 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.00 | 0.411453 |
PSZ-AC_2:2_OA_CONTROLLER | 1.06 | 0.205727 |
PSZ-AC_3:3_OA_CONTROLLER | 1.05 | 0.205727 |
PSZ-AC_4:4_OA_CONTROLLER | 1.06 | 0.205727 |
PSZ-AC_5:5_OA_CONTROLLER | 1.05 | 0.205727 |
PSZ-AC_6:6_OA_CONTROLLER | 1.82 | 0.411453 |
PSZ-AC_7:7_OA_CONTROLLER | 0.948258 | 0.205727 |
PSZ-AC_8:8_OA_CONTROLLER | 0.942838 | 0.205727 |
PSZ-AC_9:9_OA_CONTROLLER | 0.944309 | 0.205727 |
PSZ-AC_10:10_OA_CONTROLLER | 1.08 | 0.205727 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.00 | 2.00 | 2.00 | 1.32 | 45931.79 | 48083.77 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 0.697988 | 24159.64 | 25391.63 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 0.695560 | 24098.42 | 25307.20 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 0.697319 | 24144.06 | 25368.09 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 0.690725 | 23974.00 | 25139.62 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.82 | 1.82 | 1.82 | 1.20 | 42773.34 | 43951.37 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.948258 | 0.948258 | 0.948258 | 0.625850 | 22288.66 | 23151.84 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.942838 | 0.942838 | 0.942838 | 0.622273 | 22194.93 | 23026.25 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.944309 | 0.944309 | 0.944309 | 0.623244 | 22221.55 | 22803.09 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.08 | 1.08 | 1.08 | 0.713007 | 24460.19 | 26291.29 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 2.00 | 0.998500 | 1.33 | 43497.86 | 45931.79 | 22965.90 | 22965.90 | 0.695604 | 0.695600 | 0.695600 | 0.695600 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 1.06 | 0.528780 | 0.705040 | 22868.13 | 24159.64 | 12079.82 | 12079.82 | 0.697408 | 0.697410 | 0.697410 | 0.697410 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 1.05 | 0.526940 | 0.702587 | 22811.71 | 24098.42 | 12049.21 | 12049.21 | 0.697155 | 0.697150 | 0.697150 | 0.697150 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 1.06 | 0.528270 | 0.704360 | 22853.76 | 24144.06 | 12072.03 | 12072.03 | 0.697322 | 0.697320 | 0.697320 | 0.697320 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 1.05 | 0.523275 | 0.697700 | 22696.80 | 23974.00 | 11987.00 | 11987.00 | 0.696675 | 0.696680 | 0.696680 | 0.696680 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 1.82 | 0.908105 | 1.21 | 40575.22 | 42773.34 | 21386.67 | 21386.67 | 0.689419 | 0.689420 | 0.689420 | 0.689420 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 0.948260 | 0.474130 | 0.632173 | 21140.28 | 22288.66 | 11144.33 | 11144.33 | 0.689926 | 0.689930 | 0.689930 | 0.689930 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 0.942840 | 0.471420 | 0.628560 | 21053.63 | 22194.93 | 11097.47 | 11097.47 | 0.689533 | 0.689530 | 0.689530 | 0.689530 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 0.944310 | 0.472155 | 0.629540 | 21078.35 | 22221.55 | 11110.77 | 11110.77 | 0.689626 | 0.689630 | 0.689630 | 0.689630 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 1.08 | 0.540155 | 0.720207 | 23139.37 | 24460.19 | 12230.09 | 12230.09 | 0.699795 | 0.699800 | 0.699800 | 0.699800 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.00 | 2136.88 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.06 | 1170.88 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1166.81 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.06 | 1169.76 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1158.70 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.82 | 1943.43 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.948258 | 1049.87 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.942838 | 1043.87 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.944309 | 1045.50 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.08 | 1196.08 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | 48083.77 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | 25391.63 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | 25307.20 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | 25368.09 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | 25139.62 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | 43951.37 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | 23151.84 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | 23026.25 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | 22803.09 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | 26291.29 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:44
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:44
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:44
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.20 | 24.80 | 23.70 | 22.50 | 22.80 | 23.20 | 23.80 | 25.20 | 25.90 | 26.90 | 27.10 | 26.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Honolulu Intl Arpt HI USA TMY3 WMO#=911820 | 21.32 | -157.93 | -10.00 | 2.00 | 101301 | 1.2040 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.92 | 4.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.76 | 20.75 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.67 | 10.37 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.43 | 20.70 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.13 | 10.35 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 20.085 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.385 | No |
2 | SMSTORE1 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 22.959 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 27.259 | No |
3 | SMSTORE2 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 20.807 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.107 | No |
4 | SMSTORE3 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 20.807 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.107 | No |
5 | SMSTORE4 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 20.807 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.107 | No |
6 | LGSTORE2 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
7 | SMSTORE5 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
8 | SMSTORE6 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
9 | SMSTORE7 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
10 | SMSTORE8 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 4683.750 | 13.444 | 156.145 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4683.750 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 2313.749 | 6.641 | 77.135 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2313.749 |
3 | SMSTORE1_LIGHTS | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1657.501 | 9.515 | 110.515 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1657.501 |
5 | SMSTORE2_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 1282.497 | 7.363 | 85.511 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1282.497 |
7 | SMSTORE3_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 1282.497 | 7.363 | 85.511 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1282.497 |
9 | SMSTORE4_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 1282.497 | 7.363 | 85.511 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1282.497 |
11 | LGSTORE2_LIGHTS | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 4683.750 | 13.444 | 156.145 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4683.750 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL | 20 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 30 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 31 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9750000 | 3.9750000 | 3.9750000 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
19 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
20 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
21 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
22 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
23 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
24 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
25 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
26 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
27 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
28 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
29 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 29 | 1 | VerySmooth | 3.241 | 0.252 | 0.162 | 0.276 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 30.0 | 0.159 | 4.569E-004 | 2.517E-004 | 0.317 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 15.0 | 4.561E-002 | 2.619E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 30.0 | 9.122E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 15.0 | 0.113 | 6.514E-004 | 3.022E-004 | 0.453 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 22669.10527 | 27202.92632 | 1.66416 | 1.99700 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 32.05800 | 1.43490E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
2 | LGSTORE1 | Heating | 6475.87934 | 7771.05521 | 0.27013 | 0.41145 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 16.20000 | 1.15180E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
3 | SMSTORE1 | Cooling | 12004.77779 | 14405.73335 | 0.88130 | 1.05756 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 32.20000 | 1.43490E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
4 | SMSTORE1 | Heating | 2954.05058 | 3544.86069 | 0.12384 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 16.20000 | 1.15180E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
5 | SMSTORE2 | Cooling | 11963.07105 | 14355.68526 | 0.87823 | 1.05388 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 32.14083 | 1.43490E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
6 | SMSTORE2 | Heating | 2764.80972 | 3317.77166 | 0.11922 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 13:00:00 | 16.20000 | 1.15180E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
7 | SMSTORE3 | Cooling | 11993.31488 | 14391.97786 | 0.88045 | 1.05654 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 32.14083 | 1.43490E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
8 | SMSTORE3 | Heating | 2798.11621 | 3357.73945 | 0.12066 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 13:00:00 | 16.20000 | 1.15180E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
9 | SMSTORE4 | Cooling | 11879.92682 | 14255.91218 | 0.87213 | 1.04655 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 32.14083 | 1.43490E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
10 | SMSTORE4 | Heating | 2906.80553 | 3488.16664 | 0.12534 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 13:00:00 | 16.20000 | 1.15180E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
11 | LGSTORE2 | Cooling | 20617.21592 | 24740.65910 | 1.51351 | 1.81621 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 32.14083 | 1.43490E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
12 | LGSTORE2 | Heating | 6749.49333 | 8099.39200 | 0.28091 | 0.41145 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 16.20000 | 1.15180E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
13 | SMSTORE5 | Cooling | 10764.18772 | 12917.02527 | 0.79022 | 0.94826 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 32.14083 | 1.43490E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
14 | SMSTORE5 | Heating | 3494.44190 | 4193.33028 | 0.14603 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 16.20000 | 1.15180E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
15 | SMSTORE6 | Cooling | 10702.66658 | 12843.19989 | 0.78570 | 0.94284 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 32.14083 | 1.43490E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
16 | SMSTORE6 | Heating | 3501.37522 | 4201.65027 | 0.14632 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 16.20000 | 1.15180E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
17 | SMSTORE7 | Cooling | 10719.46408 | 12863.35690 | 0.78692 | 0.94431 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 32.08167 | 1.43490E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
18 | SMSTORE7 | Heating | 3760.61694 | 4512.74033 | 0.15688 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 16.20000 | 1.15180E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
19 | SMSTORE8 | Cooling | 12264.97406 | 14717.96887 | 0.90026 | 1.08031 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 31.84500 | 1.43490E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
20 | SMSTORE8 | Heating | 4429.47268 | 5315.36722 | 0.18425 | 0.22109 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 16.20000 | 1.15180E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 30898.04 | 1.99700 | 1.99700 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 11847.79 | 0.41145 | 0.41145 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 16252.68 | 1.05756 | 1.05756 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 5923.90 | 0.20573 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:40:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 16200.61 | 1.05388 | 1.05388 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 5923.90 | 0.20573 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 16235.61 | 1.05654 | 1.05654 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 5923.90 | 0.20573 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 16101.95 | 1.04655 | 1.04655 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 5923.90 | 0.20573 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:50:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 28492.36 | 1.81621 | 1.81621 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 11847.79 | 0.41145 | 0.41145 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 14783.42 | 0.94826 | 0.94826 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 5923.90 | 0.20573 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:20:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 14710.76 | 0.94284 | 0.94284 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 5923.90 | 0.20573 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:20:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 14727.94 | 0.94431 | 0.94431 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 5923.90 | 0.20573 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 16471.30 | 1.08031 | 1.08031 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 6281.78 | 0.22109 | 0.22109 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.99700 |
2 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05756 |
3 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05388 |
4 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05654 |
5 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.04655 |
6 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.81621 |
7 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.94826 |
8 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.94284 |
9 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.94431 |
10 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.08031 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.99700 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.99700 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.99700 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.99700 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.99700 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.99700 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05756 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05756 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05756 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05756 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05756 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05756 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05388 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05388 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05388 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05388 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05388 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05388 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05654 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05654 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05654 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05654 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05654 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05654 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.04655 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.04655 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.04655 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.04655 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04655 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04655 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.81621 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.81621 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.81621 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.81621 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.81621 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.81621 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.94826 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.94826 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.94826 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.94826 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.94826 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.94826 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.94284 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.94284 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.94284 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.94284 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.94284 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.94284 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.94431 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.94431 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.94431 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.94431 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.94431 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.94431 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.08031 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.08031 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.08031 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.08031 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.08031 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.08031 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.99700 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.05756 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.05388 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.05654 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.04655 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.81621 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.94826 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.94284 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.94431 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.08031 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.99700 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.99700 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.99700 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.99700 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.31802 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.99700 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.99850 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.33133 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 43497.85562 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 45931.79000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 22965.89500 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 22965.89500 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69560 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69560 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69560 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69560 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 45931.79000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 48083.77105 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
122 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.99700 |
123 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2136.88144 |
124 | Coil:Heating:Fuel | PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 48083.77105 |
125 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05756 |
126 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05756 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05756 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05756 |
130 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69799 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05756 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52878 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70504 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22868.12570 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 24159.64000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12079.82000 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 12079.82000 |
138 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69741 |
139 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69741 |
140 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69741 |
141 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69741 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24159.64000 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25391.63440 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
146 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05756 |
147 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1170.88347 |
148 | Coil:Heating:Fuel | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 25391.63440 |
149 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05388 |
150 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
151 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05388 |
152 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05388 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05388 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69556 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05388 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52694 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70259 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22811.70733 |
159 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 24098.42000 |
160 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12049.21000 |
161 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 12049.21000 |
162 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69715 |
163 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69715 |
164 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69715 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69715 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24098.42000 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25307.19988 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
170 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05388 |
171 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1166.81123 |
172 | Coil:Heating:Fuel | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 25307.19988 |
173 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05654 |
174 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05654 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05654 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05654 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69732 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05654 |
180 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52827 |
181 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70436 |
182 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22853.75870 |
183 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 24144.06000 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12072.03000 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 12072.03000 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69732 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69732 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69732 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69732 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24144.06000 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25368.08672 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
194 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05654 |
195 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1169.76115 |
196 | Coil:Heating:Fuel | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 25368.08672 |
197 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04655 |
198 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04655 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04655 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04655 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69073 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04655 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52328 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69770 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22696.79959 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 23974.00000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11987.00000 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 11987.00000 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69668 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69668 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69668 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69668 |
214 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23974.00000 |
215 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25139.62181 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
218 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04655 |
219 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1158.70116 |
220 | Coil:Heating:Fuel | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 25139.62181 |
221 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.81621 |
222 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.81621 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.81621 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.81621 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.19870 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.81621 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.90811 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.21081 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 40575.21513 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 42773.34000 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 21386.67000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 21386.67000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68942 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68942 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68942 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68942 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 42773.34000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 43951.37225 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
241 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
242 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.81621 |
243 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1943.42656 |
244 | Coil:Heating:Fuel | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 43951.37225 |
245 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.94826 |
246 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.94826 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.94826 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.94826 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.62585 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.94826 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47413 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.63217 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21140.28183 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22288.66000 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11144.33000 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 11144.33000 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68993 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68993 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68993 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68993 |
262 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22288.66000 |
263 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 23151.83684 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
266 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.94826 |
267 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1049.87239 |
268 | Coil:Heating:Fuel | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 23151.83684 |
269 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.94284 |
270 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
271 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.94284 |
272 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.94284 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.94284 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.62227 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.94284 |
276 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47142 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.62856 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21053.62961 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22194.93000 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11097.46500 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 11097.46500 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68953 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68953 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68953 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68953 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22194.93000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 23026.25203 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.94284 |
291 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1043.87168 |
292 | Coil:Heating:Fuel | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 23026.25203 |
293 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.94431 |
294 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.94431 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.94431 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.94431 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.62324 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.94431 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47216 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.62954 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21078.34891 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22221.55000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11110.77500 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 11110.77500 |
306 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68963 |
307 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68963 |
308 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68963 |
309 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68963 |
310 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22221.55000 |
311 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 22803.09226 |
312 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
313 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
314 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.94431 |
315 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1045.49957 |
316 | Coil:Heating:Fuel | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 22803.09226 |
317 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.08031 |
318 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
319 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.08031 |
320 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.08031 |
321 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.08031 |
322 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.71301 |
323 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.08031 |
324 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.54016 |
325 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.72021 |
326 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 23139.36709 |
327 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 24460.19000 |
328 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12230.09500 |
329 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 12230.09500 |
330 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69979 |
331 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69980 |
332 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69980 |
333 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69980 |
334 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24460.19000 |
335 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26291.28521 |
336 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
337 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
338 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.08031 |
339 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1196.07830 |
340 | Coil:Heating:Fuel | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 26291.28521 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 44358.6 | 11.63 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 23326.6 | 34.22 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 23268.3 | 46.11 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 23311.9 | 57.82 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 23149.6 | 70.05 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 41342.0 | 50.48 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 21541.4 | 110.17 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 21451.9 | 122.51 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 21477.3 | 134.21 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 23609.4 | 133.12 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 58.20 | 78.94 | 58.20 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.10 | 39.47 | 29.10 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 58.24 | 78.94 | 58.24 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 7 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 2.6497653688E-002 | 0.1140930285 | Pass | Pass | 1.3839186613 | 16.1669251421 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 2.7600014356E-002 | 0.1346309639 | Pass | Pass | 1.4911913724 | 17.4904383329 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 4.2372925704E-002 | 0.1875796995 | Pass | Pass | 2.3438130974 | 24.6147063857 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 4.2576448380E-002 | 0.1891696183 | Pass | Pass | 1.7761678912 | 17.9504351070 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 4.1339603176E-002 | 0.1811348403 | Pass | Pass | 0.7973976349 | 5.9322788499 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 4.2005010050E-002 | 0.1765381856 | Pass | Pass | 0.3136094109 | 1.9670400656 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.0924890750E-002 | 0.1756702287 | Pass | Pass | 0.2309818091 | 1.6459672335 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.0653179310E-002 | 0.1731923930 | Pass | Pass | 0.2146875889 | 1.5740798209 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 4.0089302285E-002 | 0.1665914479 | Pass | Pass | 0.6388698727 | 5.4730641829 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 4.6791325010E-002 | 0.1715634343 | Pass | Pass | 0.2720162283 | 1.7670887865 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:44
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 16.20 | 0.00 | 16.20 | Wetbulb [C] | 1.90 | 320.00 |
HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 32.20 | 7.10 | 23.30 | Wetbulb [C] | 6.70 | 60.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:44
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 78.94 | 58.20 | 180.00 | 90.00 | S |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.10 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 78.94 | 58.24 | 180.00 | 90.00 | S |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 3.241 | 0.252 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 3.241 | 0.252 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 3.241 | 0.252 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
Total or Average | 124.29 | 3.241 | 0.252 | 0.276 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 124.29 | 3.241 | 0.252 | 0.276 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE8_WALL_3 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:44
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:44
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | 13.4441 | 348.39 | 4683.75 | LightsWired | TYPE1_LIGHT_SCH | 98.22 | 168.00 | 98.21 | 0.0000 | Y | 86.34 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | 6.6413 | 348.39 | 2313.75 | LightsWired | TYPE1_LIGHT_SCH | 98.22 | 168.00 | 98.21 | 0.0000 | Y | 42.65 |
SMSTORE1_LIGHTS | SMSTORE1 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE1_LIGHT_SCH | 98.22 | 168.00 | 98.21 | 0.0000 | Y | 43.17 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | 9.5153 | 174.19 | 1657.50 | LightsWired | TYPE1_LIGHT_SCH | 98.22 | 168.00 | 98.21 | 0.0000 | Y | 30.56 |
SMSTORE2_LIGHTS | SMSTORE2 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 34.27 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | 7.3625 | 174.19 | 1282.50 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.77 |
SMSTORE3_LIGHTS | SMSTORE3 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 34.27 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | 7.3625 | 174.19 | 1282.50 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.77 |
SMSTORE4_LIGHTS | SMSTORE4 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 34.27 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | 7.3625 | 174.19 | 1282.50 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.77 |
LGSTORE2_LIGHTS | LGSTORE2 | 13.4441 | 348.39 | 4683.75 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 63.00 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | 0.0000 | 348.39 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 31.50 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 31.50 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 31.50 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 31.50 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 8.5923 | 4180.64 | 35921.24 | 550.85 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 418.40 | AstronomicalClock | - | 41.86 | 41.86 | 3.29 | |
EXTERIOR_LIGHTS_B | 6630.02 | AstronomicalClock | - | 83.86 | 71.26 | 88.69 | |
Exterior Lighting Total | 7048.42 | 91.97 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:44
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 45931.79 | 31950.15 | 13981.64 | 0.70 | 3.73 | |||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 24159.64 | 16849.17 | 7310.47 | 0.70 | 3.80 | |||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 24098.42 | 16800.21 | 7298.21 | 0.70 | 3.80 | |||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 24144.06 | 16836.14 | 7307.92 | 0.70 | 3.80 | |||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 23974.00 | 16702.21 | 7271.79 | 0.70 | 3.80 | |||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 42773.34 | 29488.80 | 13284.54 | 0.69 | 3.73 | |||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 22288.66 | 15377.62 | 6911.04 | 0.69 | 3.80 | |||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 22194.93 | 15304.07 | 6890.86 | 0.69 | 3.80 | |||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 22221.55 | 15324.65 | 6896.90 | 0.69 | 3.80 | |||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 24460.19 | 17117.24 | 7342.95 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 44358.6 | 11.63 | ||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 23326.6 | 34.22 | ||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 23268.3 | 46.11 | ||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 23311.9 | 57.82 | ||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 23149.6 | 70.05 | ||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 41342.0 | 50.48 | ||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 21541.4 | 110.17 | ||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 21451.9 | 122.51 | ||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 21477.3 | 134.21 | ||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 23609.4 | 133.12 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 48083.77 | 0.80 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 25391.63 | 0.80 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 25307.20 | 0.80 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 25368.09 | 0.80 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 25139.62 | 0.80 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 43951.37 | 0.80 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 23151.84 | 0.80 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 23026.25 | 0.80 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 22803.09 | 0.80 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 26291.29 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.00 | 2136.88 | 1070.05 | 1.00 | 1.32 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.06 | 1170.88 | 1107.16 | 1.00 | 1.39 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1166.81 | 1107.16 | 1.00 | 1.39 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.06 | 1169.76 | 1107.16 | 1.00 | 1.39 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1158.70 | 1107.16 | 1.00 | 1.39 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.82 | 1943.43 | 1070.05 | 1.00 | 1.33 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.95 | 1049.87 | 1107.16 | 1.00 | 1.42 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.94 | 1043.87 | 1107.16 | 1.00 | 1.42 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.94 | 1045.50 | 1107.16 | 1.00 | 1.42 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.08 | 1196.08 | 1107.16 | 1.00 | 1.38 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:44
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 22669.11 | 27202.93 | 78.08 | 1.664 | 1.997 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 23.89 | 23.88 | 0.00983 | 32.06 | 0.01435 | 0.411 | 0.00 |
SMSTORE1 | 12004.78 | 14405.73 | 82.70 | 0.881 | 1.058 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 23.89 | 23.88 | 0.00986 | 32.20 | 0.01435 | 0.206 | 0.00 |
SMSTORE2 | 11963.07 | 14355.69 | 82.41 | 0.878 | 1.054 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.00987 | 32.14 | 0.01435 | 0.206 | 0.00 |
SMSTORE3 | 11993.31 | 14391.98 | 82.62 | 0.880 | 1.057 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.00986 | 32.14 | 0.01435 | 0.206 | 0.00 |
SMSTORE4 | 11879.93 | 14255.91 | 81.84 | 0.872 | 1.047 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.00987 | 32.14 | 0.01435 | 0.206 | 0.00 |
LGSTORE2 | 20617.22 | 24740.66 | 71.01 | 1.514 | 1.816 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.00992 | 32.14 | 0.01435 | 0.411 | 0.00 |
SMSTORE5 | 10764.19 | 12917.03 | 74.15 | 0.790 | 0.948 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.00998 | 32.14 | 0.01435 | 0.206 | 0.00 |
SMSTORE6 | 10702.67 | 12843.20 | 73.73 | 0.786 | 0.943 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.00999 | 32.14 | 0.01435 | 0.206 | 0.00 |
SMSTORE7 | 10719.46 | 12863.36 | 73.85 | 0.787 | 0.944 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.88 | 0.00999 | 32.08 | 0.01435 | 0.206 | 0.00 |
SMSTORE8 | 12264.97 | 14717.97 | 84.49 | 0.900 | 1.080 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 23.89 | 23.88 | 0.00986 | 31.85 | 0.01435 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 6475.88 | 7771.06 | 22.31 | 0.270 | 0.411 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 21.11 | 21.11 | 0.00918 | 16.20 | 0.01152 | 0.411 | 0.00 |
SMSTORE1 | 2954.05 | 3544.86 | 20.35 | 0.124 | 0.206 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 21.11 | 21.11 | 0.00912 | 16.20 | 0.01152 | 0.206 | 0.00 |
SMSTORE2 | 2764.81 | 3317.77 | 19.05 | 0.119 | 0.206 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 13:00:00 | 21.11 | 21.11 | 0.00991 | 16.20 | 0.01152 | 0.206 | 0.00 |
SMSTORE3 | 2798.12 | 3357.74 | 19.28 | 0.121 | 0.206 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 13:00:00 | 21.11 | 21.11 | 0.00990 | 16.20 | 0.01152 | 0.206 | 0.00 |
SMSTORE4 | 2906.81 | 3488.17 | 20.02 | 0.125 | 0.206 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 13:00:00 | 21.11 | 21.11 | 0.00986 | 16.20 | 0.01152 | 0.206 | 0.00 |
LGSTORE2 | 6749.49 | 8099.39 | 23.25 | 0.281 | 0.411 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 21.11 | 21.11 | 0.00950 | 16.20 | 0.01152 | 0.411 | 0.00 |
SMSTORE5 | 3494.44 | 4193.33 | 24.07 | 0.146 | 0.206 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 21.11 | 21.11 | 0.00951 | 16.20 | 0.01152 | 0.206 | 0.00 |
SMSTORE6 | 3501.38 | 4201.65 | 24.12 | 0.146 | 0.206 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 21.11 | 21.11 | 0.00951 | 16.20 | 0.01152 | 0.206 | 0.00 |
SMSTORE7 | 3760.62 | 4512.74 | 25.91 | 0.157 | 0.206 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 21.11 | 21.11 | 0.00945 | 16.20 | 0.01152 | 0.206 | 0.00 |
SMSTORE8 | 4429.47 | 5315.37 | 30.51 | 0.184 | 0.221 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 21.11 | 21.11 | 0.00960 | 16.20 | 0.01152 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.00 | 2.00 | 0.41 | 0.41 | 1.9970 | 1.9970 | 1.9970 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.06 | 1.06 | 0.21 | 0.21 | 1.0576 | 1.0576 | 1.0576 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.05 | 1.05 | 0.21 | 0.21 | 1.0539 | 1.0539 | 1.0539 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.06 | 1.06 | 0.21 | 0.21 | 1.0565 | 1.0565 | 1.0565 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.05 | 1.05 | 0.21 | 0.21 | 1.0466 | 1.0466 | 1.0466 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.82 | 1.82 | 0.41 | 0.41 | 1.8162 | 1.8162 | 1.8162 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 0.95 | 0.95 | 0.21 | 0.21 | 0.9483 | 0.9483 | 0.9483 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 0.94 | 0.94 | 0.21 | 0.21 | 0.9428 | 0.9428 | 0.9428 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 0.94 | 0.94 | 0.21 | 0.21 | 0.9443 | 0.9443 | 0.9443 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.08 | 1.08 | 0.22 | 0.22 | 1.0803 | 1.0803 | 1.0803 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 22965.895 | 0.000 | 1.997000 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 22965.90 | 16365.89 | 1.997000 | 25.60 | 18.77 | 0.01076155 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 20.6036 | 23.88 | 0.00982822 | 53.1552 | 22649.16 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 48083.771 | 48083.771 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 48083.77 | 48083.77 | 1.996997 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 20.6036 | 21.11 | 0.00918426 | 58.8520 | 2693.31 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 12079.820 | 0.000 | 1.057560 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 12079.82 | 8620.17 | 1.057560 | 25.50 | 18.72 | 0.01073522 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 19.4530 | 23.88 | 0.00986245 | 53.3380 | 12004.78 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 25391.634 | 25391.634 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:40:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:40:00 | 25391.63 | 25391.63 | 1.057557 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 19.4530 | 21.11 | 0.00911587 | 58.4207 | 1221.13 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 12049.210 | 0.000 | 1.053880 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 12049.21 | 8592.22 | 1.053880 | 25.51 | 18.73 | 0.01074172 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 19.5209 | 23.88 | 0.00986566 | 53.3551 | 11960.71 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 25307.200 | 25307.200 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 25307.20 | 25307.20 | 1.053879 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 19.5209 | 21.11 | 0.00991031 | 63.4282 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 12072.030 | 0.000 | 1.056540 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 12072.03 | 8612.57 | 1.056540 | 25.50 | 18.72 | 0.01073738 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 19.4717 | 23.88 | 0.00986291 | 53.3404 | 11990.33 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 25368.087 | 25368.087 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 25368.09 | 25368.09 | 1.056543 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 19.4717 | 21.11 | 0.00990074 | 63.3679 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 11987.000 | 0.000 | 1.046550 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 11987.00 | 8536.37 | 1.046550 | 25.52 | 18.74 | 0.01075407 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 19.6576 | 23.88 | 0.00987332 | 53.3958 | 11877.20 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 25139.622 | 25139.622 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:50:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:50:00 | 25139.62 | 25139.62 | 1.046554 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 19.6575 | 21.11 | 0.00986427 | 63.1381 | 1920.84 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 21386.670 | 0.000 | 1.816210 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 21386.67 | 14990.04 | 1.816210 | 25.77 | 18.95 | 0.01092172 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 22.6545 | 23.88 | 0.00991633 | 53.6238 | 20613.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 43951.372 | 43951.372 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 43951.37 | 43951.37 | 1.816206 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 22.6546 | 21.11 | 0.00949679 | 60.8234 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 11144.330 | 0.000 | 0.948260 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 11144.33 | 7787.24 | 0.948260 | 25.69 | 18.94 | 0.01093291 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 21.6952 | 23.88 | 0.00998487 | 53.9894 | 10761.18 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 23151.837 | 23151.837 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:20:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:20:00 | 23151.84 | 23151.84 | 0.948258 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 21.6952 | 21.11 | 0.00951461 | 60.9355 | 1473.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 11097.465 | 0.000 | 0.942840 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 11097.47 | 7745.96 | 0.942840 | 25.70 | 18.95 | 0.01094359 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 21.8199 | 23.88 | 0.00999155 | 54.0250 | 10699.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 23026.252 | 23026.252 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:20:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:20:00 | 23026.25 | 23026.25 | 0.942838 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 21.8199 | 21.11 | 0.00951457 | 60.9352 | 1475.16 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 11110.775 | 0.000 | 0.944310 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 11110.77 | 7757.27 | 0.944310 | 25.70 | 18.94 | 0.01094106 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 21.7859 | 23.88 | 0.00998776 | 54.0048 | 10714.22 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 22803.092 | 22803.092 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 22803.09 | 22803.09 | 0.944309 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 21.7860 | 21.11 | 0.00944602 | 60.5026 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 12230.095 | 0.000 | 1.080310 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 12230.09 | 8735.05 | 1.080310 | 25.40 | 18.67 | 0.01071248 | 12.80 | 12.10 | 0.00850000 | 31.85 | 0.01434902 | 23.20 | 19.0433 | 23.88 | 0.00985707 | 53.3090 | 12264.97 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 26291.285 | 26291.285 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 26291.29 | 26291.29 | 1.080313 | 16.52 | 16.20 | 0.01138484 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 19.0432 | 21.11 | 0.00960261 | 61.4885 | 4429.47 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:20:44
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22965.895 | 0.000 | 1.997000 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8452 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 22965.90 | 16365.89 | 1.0000 | 2.40443431 | 1.997000 | 25.60 | 18.77 | 0.01076155 | 53149.6 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22965.90 | 32.20 | 0.01434902 | 23.30 | 0.41145340 | 20.6036 | 23.88 | 0.00982956 | 23.88 | 0.00982822 | 53.1552 | 22649.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 48083.771 | 48083.771 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.996997 | 2.40443098 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 48083.77 | 48083.77 | 1.0000 | 2.40443098 | 1.996997 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 48083.77 | 16.20 | 0.01151798 | 16.20 | 0.41145340 | 20.6036 | 21.11 | 0.00870954 | 21.11 | 0.00918426 | 58.8520 | 2693.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12079.820 | 0.000 | 1.057560 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.7962 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 12079.82 | 8620.17 | 1.0000 | 1.27332676 | 1.057560 | 25.50 | 18.72 | 0.01073522 | 52982.8 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12079.82 | 32.20 | 0.01434902 | 23.30 | 0.20572670 | 19.4530 | 23.88 | 0.00986245 | 23.88 | 0.00986245 | 53.3380 | 12004.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25391.634 | 25391.634 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.057557 | 1.27332315 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:40:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:40:00 | 25391.63 | 25391.63 | 1.0000 | 1.27332315 | 1.057557 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25391.63 | 16.20 | 0.01151798 | 16.20 | 0.20572670 | 19.4530 | 21.11 | 0.00874752 | 21.11 | 0.00911587 | 58.4207 | 1221.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12049.210 | 0.000 | 1.053880 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8083 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 12049.21 | 8592.22 | 1.0000 | 1.26889596 | 1.053880 | 25.51 | 18.73 | 0.01074172 | 53005.5 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12049.21 | 32.20 | 0.01434902 | 23.30 | 0.20572670 | 19.5209 | 23.88 | 0.00986653 | 23.88 | 0.00986566 | 53.3551 | 11960.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25307.200 | 25307.200 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.053879 | 1.26889463 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 25307.20 | 25307.20 | 1.0000 | 1.26889463 | 1.053879 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25307.20 | 16.20 | 0.01151798 | 16.20 | 0.20572670 | 19.5209 | 21.11 | 0.00000000 | 21.11 | 0.00991031 | 63.4282 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12072.030 | 0.000 | 1.056540 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8003 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 12072.03 | 8612.57 | 1.0000 | 1.27209866 | 1.056540 | 25.50 | 18.72 | 0.01073738 | 52990.3 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12072.03 | 32.20 | 0.01434902 | 23.30 | 0.20572670 | 19.4717 | 23.88 | 0.00986383 | 23.88 | 0.00986291 | 53.3404 | 11990.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25368.087 | 25368.087 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.056543 | 1.27210264 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 25368.09 | 25368.09 | 1.0000 | 1.27210264 | 1.056543 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25368.09 | 16.20 | 0.01151798 | 16.20 | 0.20572670 | 19.4717 | 21.11 | 0.00000000 | 21.11 | 0.00990074 | 63.3679 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 11987.000 | 0.000 | 1.046550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8313 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 11987.00 | 8536.37 | 1.0000 | 1.26007047 | 1.046550 | 25.52 | 18.74 | 0.01075407 | 53048.6 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11987.00 | 32.20 | 0.01434902 | 23.30 | 0.20572670 | 19.6576 | 23.88 | 0.00987423 | 23.88 | 0.00987332 | 53.3958 | 11877.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25139.622 | 25139.622 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.046554 | 1.26007502 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:50:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:50:00 | 25139.62 | 25139.62 | 1.0000 | 1.26007502 | 1.046554 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25139.62 | 16.20 | 0.01151798 | 16.20 | 0.20572670 | 19.6575 | 21.11 | 0.00919416 | 21.11 | 0.00986427 | 63.1381 | 1920.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21386.670 | 0.000 | 1.816210 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.1429 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 21386.67 | 14990.04 | 1.0000 | 2.18675896 | 1.816210 | 25.77 | 18.95 | 0.01092172 | 53731.6 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21386.67 | 32.20 | 0.01434902 | 23.30 | 0.41145340 | 22.6545 | 23.89 | 0.00991760 | 23.88 | 0.00991633 | 53.6238 | 20613.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 43951.372 | 43951.372 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.816206 | 2.18675446 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 43951.37 | 43951.37 | 1.0000 | 2.18675446 | 1.816206 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 43951.37 | 16.20 | 0.01151798 | 16.20 | 0.41145340 | 22.6546 | 21.11 | 0.00000000 | 21.11 | 0.00949679 | 60.8234 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 11144.330 | 0.000 | 0.948260 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.1637 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 11144.33 | 7787.24 | 1.0000 | 1.14172703 | 0.948260 | 25.69 | 18.94 | 0.01093291 | 53678.3 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11144.33 | 32.20 | 0.01434902 | 23.30 | 0.20572670 | 21.6952 | 23.88 | 0.00998611 | 23.88 | 0.00998487 | 53.9894 | 10761.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23151.837 | 23151.837 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.948258 | 1.14172490 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:20:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:20:00 | 23151.84 | 23151.84 | 1.0000 | 1.14172490 | 0.948258 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23151.84 | 16.20 | 0.01151798 | 16.20 | 0.20572670 | 21.6952 | 20.82 | 0.00972539 | 21.11 | 0.00951461 | 60.9355 | 1473.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 11097.465 | 0.000 | 0.942840 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.1836 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 11097.47 | 7745.96 | 1.0000 | 1.13520122 | 0.942840 | 25.70 | 18.95 | 0.01094359 | 53716.1 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11097.47 | 32.20 | 0.01434902 | 23.30 | 0.20572670 | 21.8199 | 23.88 | 0.00999280 | 23.88 | 0.00999155 | 54.0250 | 10699.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23026.252 | 23026.252 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.942838 | 1.13519920 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:20:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:20:00 | 23026.25 | 23026.25 | 1.0000 | 1.13519920 | 0.942838 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23026.25 | 16.20 | 0.01151798 | 16.20 | 0.20572670 | 21.8199 | 20.82 | 0.00972644 | 21.11 | 0.00951457 | 60.9352 | 1475.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 11110.775 | 0.000 | 0.944310 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.1789 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 11110.77 | 7757.27 | 1.0000 | 1.13697114 | 0.944310 | 25.70 | 18.94 | 0.01094106 | 53707.1 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11110.77 | 32.20 | 0.01434902 | 23.30 | 0.20572670 | 21.7859 | 23.88 | 0.00999122 | 23.88 | 0.00998776 | 54.0048 | 10714.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 22803.092 | 22803.092 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.944309 | 1.13696951 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 22803.09 | 22803.09 | 1.0000 | 1.13696951 | 0.944309 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22803.09 | 16.20 | 0.01151798 | 16.20 | 0.20572670 | 21.7860 | 21.11 | 0.00000000 | 21.11 | 0.00944602 | 60.5026 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12230.095 | 0.000 | 1.080310 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.7540 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 12230.09 | 8735.05 | 1.0000 | 1.30071829 | 1.080310 | 25.40 | 18.67 | 0.01071248 | 52822.0 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12230.09 | 31.85 | 0.01434902 | 23.20 | 0.20572670 | 19.0433 | 23.89 | 0.00985707 | 23.88 | 0.00985707 | 53.3090 | 12264.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26291.285 | 26291.285 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.080313 | 1.30072225 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 26291.29 | 26291.29 | 1.0000 | 1.30072225 | 1.080313 | 16.52 | 16.20 | 0.01138484 | 45418.7 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26291.29 | 16.20 | 0.01151798 | 16.20 | 0.20572670 | 19.0432 | 20.75 | 0.00960261 | 21.11 | 0.00960261 | 61.4885 | 4429.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:44
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 5789.33 | 76.00 | 74.50 |
SMSTORE1 | 5733.83 | 40.83 | 39.17 |
SMSTORE2 | 4379.33 | 99.67 | 99.67 |
SMSTORE3 | 4378.33 | 101.33 | 101.33 |
SMSTORE4 | 4375.67 | 111.67 | 111.67 |
LGSTORE2 | 3992.33 | 137.17 | 137.17 |
SMSTORE5 | 3970.50 | 153.33 | 153.33 |
SMSTORE6 | 3966.83 | 159.00 | 159.00 |
SMSTORE7 | 3966.17 | 167.50 | 167.33 |
SMSTORE8 | 3983.50 | 157.00 | 156.33 |
Facility | 5906.50 | 243.50 | 240.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.67 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.67 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.67 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 1.00 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.83 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 0.67 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 0.67 | 0.00 | 0.00 |
SMSTORE8 | 0.00 | 1.33 | 0.00 | 0.00 |
Facility | 0.00 | 2.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:44
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.02 | 30.00 | 1805.20 | 0.842 | 0.352 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.710 | 0.387 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 0.843 | 0.506 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 0.843 | 0.506 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 0.843 | 0.506 | 0.000 | 0.000 |
LGSTORE2 | 13.23 | 30.00 | 1805.20 | 0.843 | 0.474 | 0.000 | 0.000 |
SMSTORE5 | 6.62 | 15.00 | 902.60 | 0.843 | 0.540 | 0.000 | 0.000 |
SMSTORE6 | 6.62 | 15.00 | 902.60 | 0.843 | 0.540 | 0.000 | 0.000 |
SMSTORE7 | 6.62 | 15.00 | 902.60 | 0.843 | 0.540 | 0.000 | 0.000 |
SMSTORE8 | 6.62 | 15.00 | 902.60 | 0.843 | 0.565 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.02 | 30.00 | 1805.20 | 0.826 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.148 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 0.825 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 0.825 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 0.825 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 13.23 | 30.00 | 1805.20 | 0.829 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 6.62 | 15.00 | 902.60 | 0.829 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 6.62 | 15.00 | 902.60 | 0.829 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 6.62 | 15.00 | 902.60 | 0.829 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 6.62 | 15.00 | 902.60 | 0.829 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:44
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:20:44
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1401.46 | 3448.90 | 01-JAN-07:20 | 113532.44 | 19-AUG-13:30 |
Electricity:Building | 679.00 | 2237.90 | 01-JAN-00:10 | 42165.88 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 155.25 | 423.51 | 01-JAN-00:10 | 7978.91 | 01-JAN-10:10 |
InteriorLights:Electricity | 550.85 | 1795.07 | 01-JAN-08:10 | 34106.38 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 129.00 | 349.25 | 01-JAN-08:10 | 6635.66 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 550.85 | 1795.07 | 01-JAN-08:10 | 34106.38 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 86.85 | 236.79 | 01-JAN-00:10 | 4464.19 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 73.73 | 199.61 | 01-JAN-08:10 | 3792.57 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 63.46 | 218.04 | 01-JAN-00:10 | 4114.78 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 53.04 | 181.22 | 01-JAN-00:10 | 3443.15 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 63.46 | 218.04 | 01-JAN-00:10 | 4114.78 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 53.04 | 181.22 | 01-JAN-00:10 | 3443.15 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 63.46 | 218.04 | 01-JAN-00:10 | 4114.78 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 53.04 | 181.22 | 01-JAN-00:10 | 3443.15 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 82.18 | 307.83 | 01-JAN-00:10 | 5792.81 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 63.00 | 234.19 | 01-JAN-00:10 | 4449.56 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 41.09 | 153.91 | 01-JAN-00:10 | 2896.41 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 31.50 | 117.09 | 01-JAN-00:10 | 2224.78 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 41.09 | 153.91 | 01-JAN-00:10 | 2896.41 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 31.50 | 117.09 | 01-JAN-00:10 | 2224.78 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 41.09 | 153.91 | 01-JAN-00:10 | 2896.41 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 31.50 | 117.09 | 01-JAN-00:10 | 2224.78 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 41.09 | 153.91 | 01-JAN-00:10 | 2896.41 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 31.50 | 117.09 | 01-JAN-00:10 | 2224.78 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
Electricity:Plant | 58.55 | 1211.00 | 07-MAY-08:10 | 11786.11 | 06-JAN-13:10 |
WaterSystems:Electricity | 58.55 | 1211.00 | 07-MAY-08:10 | 11786.11 | 06-JAN-13:10 |
Water Heater:WaterSystems:Electricity | 58.55 | 1211.00 | 07-MAY-08:10 | 11786.11 | 06-JAN-13:10 |
ElectricityPurchased:Facility | 1401.46 | 3448.90 | 01-JAN-07:20 | 113532.44 | 19-AUG-13:30 |
ElectricityPurchased:Plant | 1401.46 | 3448.90 | 01-JAN-07:20 | 113532.44 | 19-AUG-13:30 |
Cogeneration:ElectricityPurchased | 1401.46 | 3448.90 | 01-JAN-07:20 | 113532.44 | 19-AUG-13:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1401.46 | 3448.90 | 01-JAN-07:20 | 113532.44 | 19-AUG-13:30 |
ElectricityNet:Plant | 1401.46 | 3448.90 | 01-JAN-07:20 | 113532.44 | 19-AUG-13:30 |
Cogeneration:ElectricityNet | 1401.46 | 3448.90 | 01-JAN-07:20 | 113532.44 | 19-AUG-13:30 |
Electricity:HVAC | 571.94 | 0.00 | 01-JAN-00:10 | 64419.82 | 03-SEP-13:00 |
Fans:Electricity | 97.70 | 0.00 | 01-JAN-00:10 | 9396.42 | 03-SEP-13:00 |
General:Fans:Electricity | 97.70 | 0.00 | 01-JAN-00:10 | 9396.42 | 03-SEP-13:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 474.23 | 0.00 | 01-JAN-00:10 | 55023.40 | 03-SEP-13:00 |
ExteriorLights:Electricity | 91.97 | 0.00 | 01-JAN-07:20 | 7048.42 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 91.97 | 0.00 | 01-JAN-07:20 | 7048.42 | 01-JAN-06:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Gas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 3019.92 | 0.00 | 01-JAN-00:10 | 326379.41 | 03-SEP-13:00 |
EnergyTransfer:Building | 1048.49 | 0.00 | 01-JAN-00:10 | 109134.67 | 11-OCT-13:00 |
EnergyTransfer:Zone:LGSTORE1 | 220.00 | 0.00 | 01-JAN-00:10 | 18859.94 | 03-SEP-16:10 |
Heating:EnergyTransfer | 3.05 | 0.00 | 01-JAN-00:10 | 16971.42 | 03-SEP-16:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.19 | 0.00 | 01-JAN-00:10 | 1711.80 | 28-JUN-07:20 |
Cooling:EnergyTransfer | 1045.44 | 0.00 | 01-JAN-00:10 | 109134.67 | 11-OCT-13:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 219.81 | 0.00 | 01-JAN-00:10 | 18859.94 | 03-SEP-16:10 |
EnergyTransfer:Zone:SMSTORE1 | 117.12 | 0.00 | 01-JAN-00:10 | 9774.95 | 01-OCT-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.10 | 0.00 | 01-JAN-00:10 | 881.65 | 24-JUN-07:20 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 117.02 | 0.00 | 01-JAN-00:10 | 9774.95 | 01-OCT-13:00 |
EnergyTransfer:Zone:SMSTORE2 | 89.29 | 0.00 | 01-JAN-00:10 | 9587.97 | 01-OCT-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 0.35 | 0.00 | 01-JAN-00:10 | 1862.03 | 03-SEP-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 88.94 | 0.00 | 01-JAN-00:10 | 9587.97 | 01-OCT-13:00 |
EnergyTransfer:Zone:SMSTORE3 | 89.29 | 0.00 | 01-JAN-00:10 | 9603.20 | 01-OCT-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 0.35 | 0.00 | 01-JAN-00:10 | 1860.86 | 03-SEP-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 88.94 | 0.00 | 01-JAN-00:10 | 9603.20 | 01-OCT-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 86.99 | 0.00 | 01-JAN-00:10 | 9471.42 | 01-OCT-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 0.36 | 0.00 | 01-JAN-00:10 | 1868.21 | 03-SEP-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 86.63 | 0.00 | 01-JAN-00:10 | 9471.42 | 01-OCT-13:00 |
EnergyTransfer:Zone:LGSTORE2 | 142.41 | 0.00 | 01-JAN-00:10 | 16647.67 | 03-SEP-14:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 0.56 | 0.00 | 01-JAN-00:10 | 3804.17 | 03-SEP-16:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 141.84 | 0.00 | 01-JAN-00:10 | 16647.67 | 03-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE5 | 73.53 | 0.00 | 01-JAN-00:10 | 8761.92 | 03-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 0.29 | 0.00 | 01-JAN-00:10 | 1910.20 | 03-SEP-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 73.24 | 0.00 | 01-JAN-00:10 | 8761.92 | 03-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE6 | 72.81 | 0.00 | 01-JAN-00:10 | 8716.39 | 03-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 0.29 | 0.00 | 01-JAN-00:10 | 1912.79 | 03-SEP-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 72.52 | 0.00 | 01-JAN-00:10 | 8716.39 | 03-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE7 | 72.45 | 0.00 | 01-JAN-00:10 | 8766.04 | 03-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 0.29 | 0.00 | 01-JAN-00:10 | 1911.07 | 03-SEP-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 72.16 | 0.00 | 01-JAN-00:10 | 8766.04 | 03-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE8 | 84.59 | 0.00 | 01-JAN-00:10 | 10324.49 | 11-OCT-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 0.26 | 0.00 | 01-JAN-00:10 | 1842.09 | 03-SEP-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 84.33 | 0.00 | 01-JAN-00:10 | 10324.49 | 11-OCT-13:00 |
EnergyTransfer:HVAC | 1971.43 | 0.00 | 01-JAN-00:10 | 223096.50 | 19-AUG-15:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 1971.43 | 0.00 | 01-JAN-00:10 | 223096.50 | 19-AUG-15:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:44
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.185 | -219.810 | 0.000 | 0.000 | 12.381 | 128.996 | 26.249 | 16.118 | 0.000 | 17.146 | 23.754 | 0.000 | -3.448 | 0.000 | -1.573 | -0.001 |
SMSTORE1 | 0.000 | 0.000 | 0.102 | -117.015 | 0.000 | 0.000 | 6.191 | 73.727 | 13.125 | 8.075 | 0.000 | 9.511 | 8.581 | 0.000 | -1.732 | 0.000 | -0.564 | -0.000 |
SMSTORE2 | 0.000 | 0.000 | 0.354 | -88.936 | 0.000 | 0.000 | 3.718 | 53.039 | 10.421 | 8.046 | 0.000 | 9.319 | 6.783 | 0.000 | -1.942 | 0.000 | -0.802 | -0.000 |
SMSTORE3 | 0.000 | 0.000 | 0.354 | -88.937 | 0.000 | 0.000 | 3.718 | 53.039 | 10.421 | 8.046 | 0.000 | 9.318 | 6.796 | 0.000 | -1.948 | 0.000 | -0.806 | -0.000 |
SMSTORE4 | 0.000 | 0.000 | 0.364 | -86.625 | 0.000 | 0.000 | 3.718 | 53.039 | 10.421 | 8.058 | 0.000 | 9.320 | 4.392 | 0.000 | -1.910 | 0.000 | -0.778 | -0.000 |
LGSTORE2 | 0.000 | 0.000 | 0.563 | -141.840 | 0.000 | 0.000 | 12.762 | 63.003 | 19.173 | 16.114 | 0.000 | 16.382 | 18.833 | 0.000 | -3.572 | 0.000 | -1.417 | -0.001 |
SMSTORE5 | 0.000 | 0.000 | 0.289 | -73.241 | 0.000 | 0.000 | 6.381 | 31.501 | 9.586 | 8.075 | 0.000 | 9.329 | 10.539 | 0.000 | -1.741 | 0.000 | -0.719 | -0.000 |
SMSTORE6 | 0.000 | 0.000 | 0.291 | -72.522 | 0.000 | 0.000 | 6.381 | 31.501 | 9.586 | 8.081 | 0.000 | 9.330 | 9.792 | 0.000 | -1.729 | 0.000 | -0.713 | -0.001 |
SMSTORE7 | 0.000 | 0.000 | 0.289 | -72.162 | 0.000 | 0.000 | 6.381 | 31.501 | 9.586 | 8.081 | 0.000 | 9.331 | 9.412 | 0.000 | -1.720 | 0.000 | -0.699 | -0.000 |
SMSTORE8 | 0.000 | 0.000 | 0.259 | -84.326 | 0.000 | 0.000 | 6.381 | 31.501 | 9.586 | 8.000 | 0.000 | 9.721 | 21.948 | 0.000 | -1.717 | 0.000 | -1.354 | -0.000 |
Total Facility | 0.000 | 0.000 | 3.052 | -1045.413 | 0.000 | 0.000 | 68.014 | 550.849 | 128.154 | 96.693 | 0.000 | 108.706 | 120.830 | 0.000 | -21.459 | 0.000 | -9.426 | -0.004 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 25-DEC-08:62 | 0.00 | 0.00 | 0.00 | -34665.81 | 0.00 | 0.00 | 94.19 | 349.25 | 74.62 | 1098.09 | 0.00 | 0.00 | 33258.91 | 0.00 | -0.00 | 0.00 | -209.25 | 0.00 |
SMSTORE1 | 21-JAN-08:62 | 0.00 | 0.00 | 0.00 | -19043.88 | 0.00 | 0.00 | 0.00 | 199.97 | 36.82 | 618.73 | 0.00 | 0.00 | 18313.45 | 0.00 | -0.00 | 0.00 | -125.09 | 0.00 |
SMSTORE2 | 20-DEC-07:02 | 0.00 | 0.00 | 0.00 | -18447.02 | 0.00 | 0.00 | 0.00 | 181.22 | 36.82 | 1676.86 | 0.00 | 0.00 | 16572.54 | 0.00 | -0.00 | 0.00 | -20.42 | 0.00 |
SMSTORE3 | 20-DEC-07:02 | 0.00 | 0.00 | 0.00 | -18474.11 | 0.00 | 0.00 | 0.00 | 181.22 | 36.82 | 1677.24 | 0.00 | 0.00 | 16599.18 | 0.00 | -0.00 | 0.00 | -20.35 | 0.00 |
SMSTORE4 | 20-DEC-07:02 | 0.00 | 0.00 | 0.00 | -18242.08 | 0.00 | 0.00 | 0.00 | 181.22 | 36.82 | 1681.44 | 0.00 | 0.00 | 16362.25 | 0.00 | -0.00 | 0.00 | -19.66 | 0.00 |
LGSTORE2 | 20-DEC-08:62 | 0.00 | 0.00 | 0.00 | -32383.60 | 0.00 | 0.00 | 0.00 | 234.19 | 73.64 | 1186.60 | 0.00 | 0.00 | 31140.40 | 0.00 | -0.00 | 0.00 | -251.24 | 0.00 |
SMSTORE5 | 20-DEC-08:62 | 0.00 | 0.00 | 0.00 | -16776.16 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 593.96 | 0.00 | 0.00 | 16163.96 | 0.00 | -0.00 | 0.00 | -135.68 | 0.00 |
SMSTORE6 | 20-DEC-08:62 | 0.00 | 0.00 | 0.00 | -16665.54 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 594.99 | 0.00 | 0.00 | 16050.89 | 0.00 | -0.00 | 0.00 | -134.25 | 0.00 |
SMSTORE7 | 20-DEC-08:62 | 0.00 | 0.00 | 0.00 | -16608.37 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 597.15 | 0.00 | 0.00 | 15986.92 | 0.00 | -0.00 | 0.00 | -129.62 | 0.00 |
SMSTORE8 | 24-DEC-09:02 | 0.00 | 0.00 | 0.00 | -17703.08 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 1269.91 | 0.00 | 0.00 | 16347.87 | 0.00 | -0.00 | 0.00 | -68.61 | 0.00 |
Total Facility | 20-DEC-08:62 | 0.00 | 0.00 | 0.00 | -159226.59 | 0.00 | 0.00 | 297.78 | 6687.98 | 1452.23 | 7178.88 | 0.00 | 0.00 | 145193.94 | 0.00 | 0.00 | 0.00 | -1584.21 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 03-SEP-07:17 | 0.00 | 0.00 | 2934.90 | 0.00 | 0.00 | 0.00 | 105.06 | 349.25 | 74.62 | 239.23 | 0.00 | 309.97 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4013.02 |
SMSTORE1 | 03-SEP-07:05 | 0.00 | 0.00 | 1592.74 | 0.00 | 0.00 | 0.00 | 43.14 | 199.61 | 37.31 | 76.26 | 0.00 | 154.15 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2103.22 |
SMSTORE2 | 03-SEP-16:02 | 0.00 | 0.00 | 2277.68 | 0.00 | 0.00 | 0.00 | 52.54 | 1812.19 | 373.13 | 452.26 | 0.00 | 2185.69 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7153.49 |
SMSTORE3 | 03-SEP-16:02 | 0.00 | 0.00 | 2277.11 | 0.00 | 0.00 | 0.00 | 52.54 | 1812.19 | 373.13 | 452.08 | 0.00 | 2185.47 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7152.51 |
SMSTORE4 | 03-SEP-16:02 | 0.00 | 0.00 | 2280.65 | 0.00 | 0.00 | 0.00 | 52.54 | 1812.19 | 373.13 | 452.58 | 0.00 | 2186.73 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7157.82 |
LGSTORE2 | 03-SEP-16:02 | 0.00 | 0.00 | 4586.80 | 0.00 | 0.00 | 0.00 | 231.18 | 2341.87 | 746.25 | 904.47 | 0.00 | 3860.08 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -12670.66 |
SMSTORE5 | 03-SEP-16:02 | 0.00 | 0.00 | 2298.91 | 0.00 | 0.00 | 0.00 | 115.59 | 1170.94 | 373.13 | 456.14 | 0.00 | 2194.93 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6609.63 |
SMSTORE6 | 03-SEP-16:02 | 0.00 | 0.00 | 2299.97 | 0.00 | 0.00 | 0.00 | 115.59 | 1170.94 | 373.13 | 456.48 | 0.00 | 2195.45 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6611.55 |
SMSTORE7 | 03-SEP-16:02 | 0.00 | 0.00 | 2298.98 | 0.00 | 0.00 | 0.00 | 115.59 | 1170.94 | 373.13 | 455.90 | 0.00 | 2195.06 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6609.60 |
SMSTORE8 | 03-SEP-16:02 | 0.00 | 0.00 | 2267.50 | 0.00 | 0.00 | 0.00 | 115.59 | 1170.94 | 373.13 | 448.29 | 0.00 | 2259.26 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6634.71 |
Total Facility | 03-SEP-16:02 | -28060.87 | 28060.87 | 20587.61 | -28060.87 | 0.00 | 0.00 | 2742.71 | 22890.41 | 5373.00 | 5452.13 | 0.00 | 25719.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -54704.09 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:44
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9970 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.9970 | 0.2060 | 1.0000 | 0.4115 | 0.2060 | ||
PSZ-AC_2:2 | 1.0576 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0576 | 0.1945 | 1.0000 | 0.2057 | 0.1945 | ||
PSZ-AC_3:3 | 1.0539 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0539 | 0.1952 | 1.0000 | 0.2057 | 0.1952 | ||
PSZ-AC_4:4 | 1.0565 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0565 | 0.1947 | 1.0000 | 0.2057 | 0.1947 | ||
PSZ-AC_5:5 | 1.0466 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0466 | 0.1966 | 1.0000 | 0.2057 | 0.1966 | ||
PSZ-AC_6:6 | 1.8162 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.8162 | 0.2265 | 1.0000 | 0.4115 | 0.2265 | ||
PSZ-AC_7:7 | 0.9483 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9483 | 0.2170 | 1.0000 | 0.2057 | 0.2170 | ||
PSZ-AC_8:8 | 0.9428 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9428 | 0.2182 | 1.0000 | 0.2057 | 0.2182 | ||
PSZ-AC_9:9 | 0.9443 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9443 | 0.2179 | 1.0000 | 0.2057 | 0.2179 | ||
PSZ-AC_10:10 | 1.0803 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0803 | 0.1904 | 1.0000 | 0.2057 | 0.1904 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9970 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.9970 | 1.0000 | 1.0000 | 0.4115 | 0.2060 | ||
PSZ-AC_2:2 | 1.0576 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0576 | 1.0000 | 1.0000 | 0.2057 | 0.1945 | ||
PSZ-AC_3:3 | 1.0539 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0539 | 1.0000 | 1.0000 | 0.2057 | 0.1952 | ||
PSZ-AC_4:4 | 1.0565 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0565 | 1.0000 | 1.0000 | 0.2057 | 0.1947 | ||
PSZ-AC_5:5 | 1.0466 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0466 | 1.0000 | 1.0000 | 0.2057 | 0.1966 | ||
PSZ-AC_6:6 | 1.8162 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.8162 | 1.0000 | 1.0000 | 0.4115 | 0.2265 | ||
PSZ-AC_7:7 | 0.9483 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9483 | 1.0000 | 1.0000 | 0.2057 | 0.2170 | ||
PSZ-AC_8:8 | 0.9428 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9428 | 1.0000 | 1.0000 | 0.2057 | 0.2182 | ||
PSZ-AC_9:9 | 0.9443 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9443 | 1.0000 | 1.0000 | 0.2057 | 0.2179 | ||
PSZ-AC_10:10 | 1.0803 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0803 | 1.0000 | 1.0000 | 0.2057 | 0.1904 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 1.9970 | 1.9970 | 1.9970 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.0576 | 1.0576 | 1.0576 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.0539 | 1.0539 | 1.0539 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.0565 | 1.0565 | 1.0565 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.0466 | 1.0466 | 1.0466 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 1.8162 | 1.8162 | 1.8162 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 0.9483 | 0.9483 | 0.9483 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 0.9428 | 0.9428 | 0.9428 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 0.9443 | 0.9443 | 0.9443 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.0803 | 1.0803 | 1.0803 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9970 | 1.9970 | 1.9970 | 1.9970 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0576 | 1.0576 | 1.0576 | 1.0576 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0539 | 1.0539 | 1.0539 | 1.0539 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0565 | 1.0565 | 1.0565 | 1.0565 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0466 | 1.0466 | 1.0466 | 1.0466 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8162 | 1.8162 | 1.8162 | 1.8162 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9483 | 0.9483 | 0.9483 | 0.9483 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9428 | 0.9428 | 0.9428 | 0.9428 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9443 | 0.9443 | 0.9443 | 0.9443 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0803 | 1.0803 | 1.0803 | 1.0803 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 1.9970 | 1.9970 | 1.9970 | 0.4115 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.0576 | 1.0576 | 1.0576 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.0539 | 1.0539 | 1.0539 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.0565 | 1.0565 | 1.0565 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.0466 | 1.0466 | 1.0466 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 1.8162 | 1.8162 | 1.8162 | 0.4115 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 0.9483 | 0.9483 | 0.9483 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 0.9428 | 0.9428 | 0.9428 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 0.9443 | 0.9443 | 0.9443 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.0803 | 1.0803 | 1.0803 | 0.2057 | 0.9305 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9970 | 1.9970 | 1.9970 | 1.9970 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0576 | 1.0576 | 1.0576 | 1.0576 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0539 | 1.0539 | 1.0539 | 1.0539 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0565 | 1.0565 | 1.0565 | 1.0565 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0466 | 1.0466 | 1.0466 | 1.0466 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8162 | 1.8162 | 1.8162 | 1.8162 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9483 | 0.9483 | 0.9483 | 0.9483 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9428 | 0.9428 | 0.9428 | 0.9428 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9443 | 0.9443 | 0.9443 | 0.9443 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0803 | 1.0803 | 1.0803 | 1.0803 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:44
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Honolulu Intl Arpt HI USA TMY3 WMO#=911820 |
Total gross floor area [m2] | 2090.32 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 474.23 | 55023.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 550.85 | 34106.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 91.97 | 7048.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 97.70 | 9396.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 58.55 | 11786.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 1401.46 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1401.46 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 263.52 |
Space Heating | 0.00 |
Space Cooling | 226.87 |
Fans (All) | 46.74 |
Service Water Heating | 28.01 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 670.45 |
Subtotal | 670.45 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 39.31 |
Space Heating | 0.00 |
Space Cooling | 33.84 |
Fans (All) | 6.97 |
Service Water Heating | 4.18 |
Receptacle Equipment | 9.14 |
Miscellaneous | 6.56 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
TYPE1_LIGHT_SCH | 5122. | 8760. |
TYPE2_LIGHT_SCH | 4096. | 8760. |
TYPE3_LIGHT_SCH | 3767. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUALSPSCHED | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Meter
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Meter
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Meter
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_HI_HONOLULU
For: Meter
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.159931E+11 | 34617.77 | 21-JAN-08:62 | 21.47 | 15.79 | 0.751677E+09 | 899.01 | 20-JAN-13:00 | 25.00 | 16.56 |
February | 0.149063E+11 | 29050.73 | 01-FEB-08:62 | 22.15 | 19.31 | 0.678539E+09 | 899.02 | 11-FEB-13:00 | 23.90 | 16.33 |
March | 0.166804E+11 | 31588.89 | 19-MAR-07:02 | 21.88 | 17.44 | 0.744896E+09 | 899.01 | 26-MAR-12:09 | 26.78 | 19.06 |
April | 0.161088E+11 | 32344.80 | 30-APR-07:02 | 22.15 | 17.80 | 0.726322E+09 | 899.01 | 01-APR-12:39 | 25.20 | 17.05 |
May | 0.185551E+11 | 32580.95 | 02-MAY-07:02 | 22.15 | 18.54 | 0.747410E+09 | 899.00 | 07-MAY-17:00 | 26.70 | 21.73 |
June | 0.186915E+11 | 30420.10 | 04-JUN-07:01 | 24.67 | 20.27 | 0.722077E+09 | 898.98 | 11-JUN-17:00 | 26.50 | 20.77 |
July | 0.208096E+11 | 29132.20 | 08-JUL-07:02 | 25.37 | 20.63 | 0.753633E+09 | 898.97 | 30-JUL-16:30 | 29.15 | 21.02 |
August | 0.210392E+11 | 29581.23 | 24-AUG-07:02 | 23.27 | 19.94 | 0.743117E+09 | 898.95 | 20-AUG-17:30 | 29.45 | 22.45 |
September | 0.206733E+11 | 29340.36 | 18-SEP-07:02 | 23.35 | 20.65 | 0.728247E+09 | 898.94 | 10-SEP-17:00 | 28.30 | 22.83 |
October | 0.205615E+11 | 30599.08 | 26-OCT-07:02 | 21.23 | 19.48 | 0.751703E+09 | 898.95 | 08-OCT-16:30 | 29.75 | 21.78 |
November | 0.183118E+11 | 32672.16 | 26-NOV-08:62 | 21.38 | 17.99 | 0.726923E+09 | 898.96 | 11-NOV-17:30 | 25.25 | 20.29 |
December | 0.174832E+11 | 34671.80 | 25-DEC-08:62 | 21.85 | 16.27 | 0.755488E+09 | 899.00 | 22-DEC-13:09 | 25.77 | 17.26 |
Annual Sum or Average | 0.219814E+12 | 0.883003E+10 | ||||||||
Minimum of Months | 0.149063E+11 | 29050.73 | 21.23 | 15.79 | 0.678539E+09 | 898.94 | 23.90 | 16.33 | ||
Maximum of Months | 0.210392E+11 | 34671.80 | 25.37 | 20.65 | 0.755488E+09 | 899.02 | 29.75 | 22.83 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.880537E+10 | 19046.31 | 21-JAN-08:62 | 21.47 | 15.79 | 0.375847E+09 | 449.50 | 20-JAN-13:00 | 25.00 | 16.56 |
February | 0.807191E+10 | 17405.85 | 01-FEB-08:62 | 22.15 | 19.31 | 0.339278E+09 | 449.51 | 11-FEB-13:09 | 24.82 | 16.23 |
March | 0.897920E+10 | 17886.57 | 19-MAR-07:02 | 21.88 | 17.44 | 0.372456E+09 | 449.50 | 24-MAR-12:39 | 25.53 | 17.48 |
April | 0.866635E+10 | 18239.30 | 30-APR-07:02 | 22.15 | 17.80 | 0.363167E+09 | 449.52 | 30-APR-17:40 | 24.97 | 18.77 |
May | 0.988150E+10 | 18104.11 | 02-MAY-07:02 | 22.15 | 18.54 | 0.373709E+09 | 449.47 | 29-MAY-16:30 | 26.15 | 21.01 |
June | 0.985138E+10 | 17287.37 | 04-JUN-07:01 | 24.67 | 20.27 | 0.361041E+09 | 449.48 | 18-JUN-16:30 | 29.10 | 21.62 |
July | 0.108944E+11 | 16677.15 | 08-JUL-07:02 | 25.37 | 20.63 | 0.376817E+09 | 449.48 | 30-JUL-16:30 | 29.15 | 21.02 |
August | 0.109762E+11 | 16882.68 | 24-AUG-07:02 | 23.27 | 19.94 | 0.371559E+09 | 449.48 | 06-AUG-16:30 | 28.30 | 21.99 |
September | 0.106934E+11 | 16869.80 | 18-SEP-07:02 | 23.35 | 20.65 | 0.364124E+09 | 449.48 | 17-SEP-16:19 | 28.70 | 21.46 |
October | 0.109167E+11 | 17449.84 | 26-OCT-07:02 | 21.23 | 19.48 | 0.375854E+09 | 449.47 | 29-OCT-16:40 | 28.33 | 21.73 |
November | 0.978147E+10 | 18213.03 | 26-NOV-08:62 | 21.38 | 17.99 | 0.363464E+09 | 449.48 | 11-NOV-17:30 | 25.25 | 20.29 |
December | 0.949928E+10 | 18970.26 | 25-DEC-08:62 | 21.85 | 16.27 | 0.377748E+09 | 449.49 | 22-DEC-13:09 | 25.77 | 17.26 |
Annual Sum or Average | 0.117017E+12 | 0.441506E+10 | ||||||||
Minimum of Months | 0.807191E+10 | 16677.15 | 21.23 | 15.79 | 0.339278E+09 | 449.47 | 24.82 | 16.23 | ||
Maximum of Months | 0.109762E+11 | 19046.31 | 25.37 | 20.65 | 0.377748E+09 | 449.52 | 29.15 | 21.99 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.658600E+10 | 18112.54 | 21-JAN-07:02 | 20.18 | 16.12 | 0.224087E+09 | 449.49 | 21-JAN-13:09 | 25.68 | 17.07 |
February | 0.600697E+10 | 16515.74 | 01-FEB-07:03 | 20.78 | 18.49 | 0.203566E+09 | 449.51 | 11-FEB-13:00 | 23.90 | 16.33 |
March | 0.676268E+10 | 17112.41 | 07-MAR-07:03 | 19.50 | 14.61 | 0.230084E+09 | 449.49 | 25-MAR-12:09 | 26.52 | 17.81 |
April | 0.641573E+10 | 17447.75 | 02-APR-07:03 | 21.38 | 15.93 | 0.219031E+09 | 449.50 | 01-APR-12:09 | 25.50 | 17.03 |
May | 0.752668E+10 | 16516.76 | 02-MAY-06:02 | 21.70 | 18.37 | 0.227251E+09 | 449.45 | 06-MAY-12:39 | 30.20 | 21.52 |
June | 0.756699E+10 | 15489.22 | 04-JUN-07:01 | 24.67 | 20.27 | 0.222413E+09 | 449.43 | 10-JUN-12:20 | 29.40 | 20.95 |
July | 0.829696E+10 | 14794.95 | 04-JUL-07:01 | 25.37 | 20.83 | 0.224163E+09 | 449.40 | 08-JUL-12:09 | 31.20 | 21.97 |
August | 0.860674E+10 | 15145.87 | 24-AUG-06:02 | 21.38 | 19.31 | 0.230351E+09 | 449.38 | 05-AUG-12:00 | 30.00 | 21.62 |
September | 0.815105E+10 | 15146.96 | 19-SEP-06:02 | 22.30 | 20.24 | 0.219295E+09 | 449.41 | 16-SEP-12:00 | 27.20 | 23.26 |
October | 0.840421E+10 | 15366.63 | 19-OCT-06:02 | 19.40 | 17.64 | 0.224382E+09 | 449.38 | 28-OCT-12:09 | 30.18 | 22.21 |
November | 0.749618E+10 | 16435.10 | 09-NOV-07:02 | 18.77 | 17.50 | 0.216652E+09 | 449.37 | 25-NOV-13:09 | 28.30 | 22.38 |
December | 0.711780E+10 | 18450.22 | 20-DEC-07:02 | 21.10 | 15.88 | 0.223884E+09 | 449.47 | 23-DEC-13:09 | 25.77 | 17.78 |
Annual Sum or Average | 0.889380E+11 | 0.266516E+10 | ||||||||
Minimum of Months | 0.600697E+10 | 14794.95 | 18.77 | 14.61 | 0.203566E+09 | 449.37 | 23.90 | 16.33 | ||
Maximum of Months | 0.860674E+10 | 18450.22 | 25.37 | 20.83 | 0.230351E+09 | 449.51 | 31.20 | 23.26 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.655791E+10 | 18127.27 | 21-JAN-07:02 | 20.18 | 16.12 | 0.224083E+09 | 449.49 | 21-JAN-13:09 | 25.68 | 17.07 |
February | 0.598572E+10 | 16536.93 | 01-FEB-07:03 | 20.78 | 18.49 | 0.203563E+09 | 449.51 | 11-FEB-13:00 | 23.90 | 16.33 |
March | 0.674417E+10 | 16882.84 | 07-MAR-07:03 | 19.50 | 14.61 | 0.230081E+09 | 449.50 | 25-MAR-12:09 | 26.52 | 17.81 |
April | 0.639457E+10 | 17337.29 | 02-APR-07:03 | 21.38 | 15.93 | 0.219028E+09 | 449.50 | 01-APR-12:09 | 25.50 | 17.03 |
May | 0.752634E+10 | 16539.62 | 02-MAY-06:02 | 21.70 | 18.37 | 0.227249E+09 | 449.45 | 06-MAY-12:50 | 30.40 | 21.62 |
June | 0.757206E+10 | 15534.34 | 04-JUN-07:01 | 24.67 | 20.27 | 0.222411E+09 | 449.44 | 17-JUN-12:09 | 29.12 | 22.29 |
July | 0.832113E+10 | 14856.47 | 04-JUL-07:01 | 25.37 | 20.83 | 0.224162E+09 | 449.40 | 08-JUL-12:09 | 31.20 | 21.97 |
August | 0.862735E+10 | 15189.85 | 24-AUG-06:02 | 21.38 | 19.31 | 0.230351E+09 | 449.38 | 05-AUG-12:00 | 30.00 | 21.62 |
September | 0.818290E+10 | 15202.78 | 19-SEP-06:02 | 22.30 | 20.24 | 0.219295E+09 | 449.41 | 16-SEP-12:00 | 27.20 | 23.26 |
October | 0.843030E+10 | 15401.72 | 19-OCT-06:02 | 19.40 | 17.64 | 0.224382E+09 | 449.38 | 28-OCT-12:09 | 30.18 | 22.21 |
November | 0.749378E+10 | 16470.49 | 09-NOV-07:02 | 18.77 | 17.50 | 0.216650E+09 | 449.37 | 25-NOV-13:09 | 28.30 | 22.38 |
December | 0.710318E+10 | 18477.32 | 20-DEC-07:02 | 21.10 | 15.88 | 0.223881E+09 | 449.47 | 23-DEC-13:09 | 25.77 | 17.78 |
Annual Sum or Average | 0.889394E+11 | 0.266514E+10 | ||||||||
Minimum of Months | 0.598572E+10 | 14856.47 | 18.77 | 14.61 | 0.203563E+09 | 449.37 | 23.90 | 16.33 | ||
Maximum of Months | 0.862735E+10 | 18477.32 | 25.37 | 20.83 | 0.230351E+09 | 449.51 | 31.20 | 23.26 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.635168E+10 | 17883.71 | 21-JAN-07:02 | 20.18 | 16.12 | 0.224064E+09 | 449.49 | 21-JAN-13:09 | 25.68 | 17.07 |
February | 0.579600E+10 | 16135.58 | 01-FEB-07:03 | 20.78 | 18.49 | 0.203545E+09 | 449.51 | 11-FEB-13:00 | 23.90 | 16.33 |
March | 0.652812E+10 | 15905.99 | 19-MAR-07:02 | 21.88 | 17.44 | 0.230061E+09 | 449.50 | 25-MAR-12:09 | 26.52 | 17.81 |
April | 0.619031E+10 | 16569.46 | 30-APR-07:02 | 22.15 | 17.80 | 0.219009E+09 | 449.50 | 01-APR-12:00 | 25.00 | 17.06 |
May | 0.732971E+10 | 16304.84 | 02-MAY-06:02 | 21.70 | 18.37 | 0.227231E+09 | 449.45 | 06-MAY-12:50 | 30.40 | 21.62 |
June | 0.738570E+10 | 15293.66 | 04-JUN-07:01 | 24.67 | 20.27 | 0.222394E+09 | 449.43 | 17-JUN-12:09 | 29.12 | 22.29 |
July | 0.814109E+10 | 14631.50 | 04-JUL-07:01 | 25.37 | 20.83 | 0.224145E+09 | 449.40 | 08-JUL-12:09 | 31.20 | 21.97 |
August | 0.843524E+10 | 14961.70 | 24-AUG-06:02 | 21.38 | 19.31 | 0.230333E+09 | 449.38 | 05-AUG-12:00 | 30.00 | 21.62 |
September | 0.800714E+10 | 14981.64 | 19-SEP-06:02 | 22.30 | 20.24 | 0.219279E+09 | 449.40 | 16-SEP-12:00 | 27.20 | 23.26 |
October | 0.824389E+10 | 15173.45 | 19-OCT-06:02 | 19.40 | 17.64 | 0.224365E+09 | 449.38 | 28-OCT-12:09 | 30.18 | 22.21 |
November | 0.730980E+10 | 16243.94 | 09-NOV-07:02 | 18.77 | 17.50 | 0.216633E+09 | 449.37 | 25-NOV-13:09 | 28.30 | 22.38 |
December | 0.690828E+10 | 18245.30 | 20-DEC-07:02 | 21.10 | 15.88 | 0.223863E+09 | 449.47 | 23-DEC-13:09 | 25.77 | 17.78 |
Annual Sum or Average | 0.866270E+11 | 0.266492E+10 | ||||||||
Minimum of Months | 0.579600E+10 | 14631.50 | 18.77 | 15.88 | 0.203545E+09 | 449.37 | 23.90 | 16.33 | ||
Maximum of Months | 0.843524E+10 | 18245.30 | 25.37 | 20.83 | 0.230333E+09 | 449.51 | 31.20 | 23.26 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101930E+11 | 32051.28 | 21-JAN-08:62 | 21.47 | 15.79 | 0.764996E+09 | 1198.62 | 21-JAN-15:09 | 22.98 | 17.97 |
February | 0.931982E+10 | 26221.62 | 13-FEB-08:62 | 23.98 | 19.24 | 0.696569E+09 | 1198.56 | 11-FEB-15:00 | 23.90 | 16.33 |
March | 0.105366E+11 | 27661.82 | 19-MAR-08:62 | 23.27 | 17.70 | 0.788980E+09 | 1198.53 | 25-MAR-14:09 | 26.10 | 17.78 |
April | 0.994643E+10 | 29403.12 | 06-APR-07:02 | 22.48 | 16.83 | 0.751699E+09 | 1198.62 | 29-APR-14:00 | 27.20 | 18.09 |
May | 0.120148E+11 | 29301.07 | 02-MAY-07:02 | 22.15 | 18.54 | 0.777321E+09 | 1198.51 | 06-MAY-14:30 | 30.00 | 21.62 |
June | 0.121707E+11 | 26554.41 | 27-JUN-07:02 | 24.93 | 21.00 | 0.762423E+09 | 1198.46 | 10-JUN-14:09 | 29.32 | 21.13 |
July | 0.134806E+11 | 26816.25 | 18-JUL-07:01 | 26.28 | 19.61 | 0.767118E+09 | 1198.39 | 01-JUL-14:00 | 31.10 | 21.52 |
August | 0.139859E+11 | 27026.62 | 24-AUG-07:02 | 23.27 | 19.94 | 0.789371E+09 | 1198.35 | 05-AUG-14:09 | 31.60 | 22.39 |
September | 0.132782E+11 | 27165.65 | 19-SEP-07:02 | 22.98 | 20.28 | 0.752170E+09 | 1198.42 | 16-SEP-14:20 | 27.77 | 23.42 |
October | 0.136865E+11 | 27469.93 | 19-OCT-07:02 | 20.23 | 18.38 | 0.765609E+09 | 1198.33 | 21-OCT-14:00 | 28.90 | 22.67 |
November | 0.120169E+11 | 28606.23 | 09-NOV-08:62 | 21.75 | 19.08 | 0.737049E+09 | 1198.46 | 25-NOV-15:00 | 26.10 | 20.73 |
December | 0.112140E+11 | 32388.70 | 20-DEC-08:62 | 21.28 | 16.29 | 0.766422E+09 | 1198.63 | 23-DEC-15:09 | 25.27 | 17.49 |
Annual Sum or Average | 0.141843E+12 | 0.911973E+10 | ||||||||
Minimum of Months | 0.931982E+10 | 26221.62 | 20.23 | 15.79 | 0.696569E+09 | 1198.33 | 22.98 | 16.33 | ||
Maximum of Months | 0.139859E+11 | 32388.70 | 26.28 | 21.00 | 0.789371E+09 | 1198.63 | 31.60 | 23.42 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.522285E+10 | 16604.90 | 21-JAN-08:62 | 21.47 | 15.79 | 0.382487E+09 | 599.31 | 21-JAN-15:09 | 22.98 | 17.97 |
February | 0.477866E+10 | 13578.92 | 13-FEB-08:62 | 23.98 | 19.24 | 0.348273E+09 | 599.28 | 11-FEB-15:00 | 23.90 | 16.33 |
March | 0.541090E+10 | 14314.12 | 19-MAR-08:62 | 23.27 | 17.70 | 0.394480E+09 | 599.26 | 25-MAR-14:09 | 26.10 | 17.78 |
April | 0.511401E+10 | 15226.80 | 06-APR-07:02 | 22.48 | 16.83 | 0.375838E+09 | 599.31 | 29-APR-14:00 | 27.20 | 18.09 |
May | 0.621272E+10 | 15198.46 | 02-MAY-07:02 | 22.15 | 18.54 | 0.388648E+09 | 599.25 | 06-MAY-14:39 | 29.80 | 21.58 |
June | 0.628689E+10 | 13786.36 | 27-JUN-07:02 | 24.93 | 21.00 | 0.381199E+09 | 599.22 | 03-JUN-14:00 | 28.30 | 20.42 |
July | 0.699358E+10 | 13899.12 | 18-JUL-07:01 | 26.28 | 19.61 | 0.383541E+09 | 599.19 | 01-JUL-14:00 | 31.10 | 21.52 |
August | 0.726383E+10 | 14005.90 | 24-AUG-07:02 | 23.27 | 19.94 | 0.394668E+09 | 599.17 | 05-AUG-14:09 | 31.60 | 22.39 |
September | 0.688048E+10 | 14094.99 | 19-SEP-07:02 | 22.98 | 20.28 | 0.376068E+09 | 599.20 | 16-SEP-14:20 | 27.77 | 23.42 |
October | 0.710685E+10 | 14227.26 | 19-OCT-07:02 | 20.23 | 18.38 | 0.382789E+09 | 599.15 | 21-OCT-14:00 | 28.90 | 22.67 |
November | 0.620288E+10 | 14816.52 | 09-NOV-08:62 | 21.75 | 19.08 | 0.368512E+09 | 599.22 | 25-NOV-15:00 | 26.10 | 20.73 |
December | 0.576905E+10 | 16778.89 | 20-DEC-08:62 | 21.28 | 16.29 | 0.383198E+09 | 599.31 | 23-DEC-15:09 | 25.27 | 17.49 |
Annual Sum or Average | 0.732427E+11 | 0.455970E+10 | ||||||||
Minimum of Months | 0.477866E+10 | 13578.92 | 20.23 | 15.79 | 0.348273E+09 | 599.15 | 22.98 | 16.33 | ||
Maximum of Months | 0.726383E+10 | 16778.89 | 26.28 | 21.00 | 0.394668E+09 | 599.31 | 31.60 | 23.42 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.515839E+10 | 16493.58 | 21-JAN-08:62 | 21.47 | 15.79 | 0.382484E+09 | 599.31 | 21-JAN-15:09 | 22.98 | 17.97 |
February | 0.471832E+10 | 13481.58 | 13-FEB-08:62 | 23.98 | 19.24 | 0.348269E+09 | 599.28 | 11-FEB-15:00 | 23.90 | 16.33 |
March | 0.534553E+10 | 14221.76 | 19-MAR-08:62 | 23.27 | 17.70 | 0.394476E+09 | 599.27 | 25-MAR-14:09 | 26.10 | 17.78 |
April | 0.505531E+10 | 15124.96 | 06-APR-07:02 | 22.48 | 16.83 | 0.375835E+09 | 599.31 | 29-APR-14:00 | 27.20 | 18.09 |
May | 0.615378E+10 | 15096.30 | 02-MAY-07:02 | 22.15 | 18.54 | 0.388644E+09 | 599.25 | 06-MAY-14:39 | 29.80 | 21.58 |
June | 0.622892E+10 | 13688.31 | 27-JUN-07:02 | 24.93 | 21.00 | 0.381196E+09 | 599.22 | 03-JUN-14:00 | 28.30 | 20.42 |
July | 0.693621E+10 | 13805.10 | 18-JUL-07:01 | 26.28 | 19.61 | 0.383538E+09 | 599.19 | 01-JUL-14:00 | 31.10 | 21.52 |
August | 0.720712E+10 | 13907.83 | 24-AUG-07:02 | 23.27 | 19.94 | 0.394665E+09 | 599.17 | 05-AUG-14:09 | 31.60 | 22.39 |
September | 0.682383E+10 | 13997.05 | 19-SEP-07:02 | 22.98 | 20.28 | 0.376064E+09 | 599.20 | 16-SEP-14:20 | 27.77 | 23.42 |
October | 0.704863E+10 | 14129.03 | 19-OCT-07:02 | 20.23 | 18.38 | 0.382785E+09 | 599.15 | 21-OCT-14:00 | 28.90 | 22.67 |
November | 0.614151E+10 | 14711.49 | 09-NOV-08:62 | 21.75 | 19.08 | 0.368509E+09 | 599.23 | 25-NOV-15:00 | 26.10 | 20.73 |
December | 0.570546E+10 | 16668.27 | 20-DEC-08:62 | 21.28 | 16.29 | 0.383193E+09 | 599.32 | 23-DEC-15:09 | 25.27 | 17.49 |
Annual Sum or Average | 0.725230E+11 | 0.455966E+10 | ||||||||
Minimum of Months | 0.471832E+10 | 13481.58 | 20.23 | 15.79 | 0.348269E+09 | 599.15 | 22.98 | 16.33 | ||
Maximum of Months | 0.720712E+10 | 16668.27 | 26.28 | 21.00 | 0.394665E+09 | 599.32 | 31.60 | 23.42 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.508376E+10 | 15332.62 | 21-JAN-08:62 | 21.47 | 15.79 | 0.382479E+09 | 599.31 | 21-JAN-15:09 | 22.98 | 17.97 |
February | 0.463974E+10 | 13400.26 | 13-FEB-08:62 | 23.98 | 19.24 | 0.348264E+09 | 599.28 | 11-FEB-15:00 | 23.90 | 16.33 |
March | 0.526885E+10 | 14180.31 | 19-MAR-08:62 | 23.27 | 17.70 | 0.394471E+09 | 599.27 | 25-MAR-14:09 | 26.10 | 17.78 |
April | 0.500754E+10 | 15074.45 | 06-APR-07:02 | 22.48 | 16.83 | 0.375831E+09 | 599.31 | 29-APR-14:00 | 27.20 | 18.09 |
May | 0.613964E+10 | 15040.19 | 02-MAY-07:02 | 22.15 | 18.54 | 0.388642E+09 | 599.25 | 06-MAY-14:39 | 29.80 | 21.58 |
June | 0.621991E+10 | 13646.70 | 27-JUN-07:02 | 24.93 | 21.00 | 0.381194E+09 | 599.22 | 03-JUN-14:00 | 28.30 | 20.42 |
July | 0.694431E+10 | 13766.31 | 18-JUL-07:01 | 26.28 | 19.61 | 0.383536E+09 | 599.19 | 01-JUL-14:00 | 31.10 | 21.52 |
August | 0.722853E+10 | 13888.79 | 24-AUG-07:02 | 23.27 | 19.94 | 0.394665E+09 | 599.17 | 05-AUG-14:09 | 31.60 | 22.39 |
September | 0.682713E+10 | 13970.55 | 19-SEP-07:02 | 22.98 | 20.28 | 0.376063E+09 | 599.20 | 16-SEP-14:20 | 27.77 | 23.42 |
October | 0.705182E+10 | 14092.84 | 19-OCT-07:02 | 20.23 | 18.38 | 0.382784E+09 | 599.15 | 21-OCT-14:00 | 28.90 | 22.67 |
November | 0.610396E+10 | 14659.68 | 09-NOV-08:62 | 21.75 | 19.08 | 0.368506E+09 | 599.23 | 25-NOV-15:00 | 26.10 | 20.73 |
December | 0.564809E+10 | 16611.12 | 20-DEC-08:62 | 21.28 | 16.29 | 0.383189E+09 | 599.32 | 23-DEC-15:09 | 25.27 | 17.49 |
Annual Sum or Average | 0.721633E+11 | 0.455962E+10 | ||||||||
Minimum of Months | 0.463974E+10 | 13400.26 | 20.23 | 15.79 | 0.348264E+09 | 599.15 | 22.98 | 16.33 | ||
Maximum of Months | 0.722853E+10 | 16611.12 | 26.28 | 21.00 | 0.394665E+09 | 599.32 | 31.60 | 23.42 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.574262E+10 | 14652.70 | 12-JAN-08:62 | 22.88 | 18.16 | 0.382504E+09 | 599.30 | 21-JAN-15:09 | 22.98 | 17.97 |
February | 0.511295E+10 | 12730.22 | 23-FEB-08:62 | 22.85 | 21.36 | 0.348289E+09 | 599.29 | 11-FEB-15:00 | 23.90 | 16.33 |
March | 0.591085E+10 | 15384.30 | 19-MAR-08:62 | 23.27 | 17.70 | 0.394496E+09 | 599.33 | 25-MAR-14:00 | 26.10 | 17.92 |
April | 0.587694E+10 | 15080.67 | 30-APR-08:62 | 24.60 | 18.07 | 0.375873E+09 | 599.33 | 01-APR-14:09 | 25.60 | 17.37 |
May | 0.737076E+10 | 15610.81 | 31-MAY-07:02 | 23.58 | 18.09 | 0.388691E+09 | 599.25 | 06-MAY-14:39 | 29.80 | 21.58 |
June | 0.744467E+10 | 15075.47 | 04-JUN-08:61 | 25.15 | 20.78 | 0.381236E+09 | 599.23 | 10-JUN-14:09 | 29.32 | 21.13 |
July | 0.834911E+10 | 14541.61 | 04-JUL-08:61 | 27.38 | 20.84 | 0.383604E+09 | 599.18 | 01-JUL-14:00 | 31.10 | 21.52 |
August | 0.877969E+10 | 14483.76 | 24-AUG-07:02 | 23.27 | 19.94 | 0.394720E+09 | 599.16 | 05-AUG-14:09 | 31.60 | 22.39 |
September | 0.799150E+10 | 14724.25 | 19-SEP-07:02 | 22.98 | 20.28 | 0.376127E+09 | 599.19 | 16-SEP-14:30 | 28.05 | 23.49 |
October | 0.838209E+10 | 15033.20 | 26-OCT-07:02 | 21.23 | 19.48 | 0.382845E+09 | 599.15 | 21-OCT-14:00 | 28.90 | 22.67 |
November | 0.698028E+10 | 15902.38 | 15-NOV-08:62 | 23.98 | 18.53 | 0.368540E+09 | 599.24 | 25-NOV-15:00 | 26.10 | 20.73 |
December | 0.638662E+10 | 17706.68 | 24-DEC-09:02 | 23.50 | 17.22 | 0.383219E+09 | 599.32 | 23-DEC-15:09 | 25.27 | 17.49 |
Annual Sum or Average | 0.843281E+11 | 0.456014E+10 | ||||||||
Minimum of Months | 0.511295E+10 | 12730.22 | 21.23 | 17.22 | 0.348289E+09 | 599.15 | 22.98 | 16.33 | ||
Maximum of Months | 0.877969E+10 | 17706.68 | 27.38 | 21.36 | 0.394720E+09 | 599.33 | 31.60 | 23.49 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3925934.30 | 1270.99 | 02-JAN-08:05 | 23.48 |
February | 7462440.71 | 1573.90 | 28-FEB-08:06 | 24.50 |
March | 7981096.92 | 1226.42 | 02-MAR-08:05 | 23.48 |
April | 7223104.75 | 1366.86 | 25-APR-07:06 | 24.18 |
May | 24127636.34 | 2214.25 | 17-MAY-07:05 | 25.28 |
June | 26721200.78 | 2678.04 | 21-JUN-07:06 | 26.78 |
July | 24089659.33 | 2467.22 | 23-JUL-07:06 | 26.28 |
August | 20244576.81 | 2462.23 | 08-AUG-07:06 | 26.10 |
September | 20969371.77 | 2935.34 | 03-SEP-07:17 | 27.77 |
October | 13626273.57 | 2309.13 | 07-OCT-07:06 | 26.05 |
November | 18701374.40 | 2556.89 | 06-NOV-08:06 | 26.47 |
December | 10397790.12 | 2177.23 | 03-DEC-08:06 | 26.10 |
Annual Sum or Average | 0.185470E+09 | |||
Minimum of Months | 3925934.30 | 1226.42 | 23.48 | |
Maximum of Months | 26721200.78 | 2935.34 | 27.77 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2373336.29 | 750.50 | 02-JAN-08:05 | 23.48 |
February | 4489806.97 | 946.45 | 18-FEB-08:05 | 24.60 |
March | 4429325.42 | 679.12 | 02-MAR-08:05 | 23.48 |
April | 4150609.78 | 717.63 | 25-APR-07:06 | 24.18 |
May | 12926470.63 | 1195.40 | 09-MAY-07:05 | 25.28 |
June | 14743705.32 | 1293.09 | 21-JUN-07:06 | 26.78 |
July | 12618268.33 | 1396.09 | 20-JUL-07:06 | 26.60 |
August | 12458030.00 | 1318.66 | 07-AUG-07:05 | 25.78 |
September | 11282146.34 | 1592.75 | 03-SEP-07:05 | 27.48 |
October | 7327177.45 | 1326.35 | 06-OCT-07:05 | 25.97 |
November | 9352593.52 | 1244.34 | 06-NOV-08:06 | 26.47 |
December | 5621309.50 | 1227.59 | 06-DEC-08:05 | 25.72 |
Annual Sum or Average | 0.101773E+09 | |||
Minimum of Months | 2373336.29 | 679.12 | 23.48 | |
Maximum of Months | 14743705.32 | 1592.75 | 27.48 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3124972.35 | 846.72 | 29-JAN-17:03 | 26.83 |
February | 4937973.46 | 717.25 | 26-FEB-17:03 | 26.32 |
March | 8085378.28 | 913.33 | 12-MAR-16:03 | 27.12 |
April | 10091370.29 | 1207.10 | 09-APR-16:02 | 28.12 |
May | 31040860.68 | 1247.84 | 21-MAY-16:02 | 28.30 |
June | 39621548.27 | 1452.62 | 18-JUN-16:02 | 29.23 |
July | 59952021.52 | 1719.26 | 09-JUL-16:02 | 30.40 |
August | 58638776.32 | 2012.10 | 20-AUG-16:02 | 31.42 |
September | 59622162.48 | 2277.24 | 03-SEP-16:02 | 32.62 |
October | 48609051.67 | 2130.35 | 01-OCT-16:02 | 31.93 |
November | 20179128.43 | 1427.96 | 05-NOV-16:02 | 29.22 |
December | 9875725.51 | 1189.80 | 03-DEC-08:06 | 26.10 |
Annual Sum or Average | 0.353779E+09 | |||
Minimum of Months | 3124972.35 | 717.25 | 26.10 | |
Maximum of Months | 59952021.52 | 2277.24 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3167802.78 | 849.06 | 29-JAN-17:03 | 26.83 |
February | 4970279.14 | 719.11 | 26-FEB-17:03 | 26.32 |
March | 8166967.14 | 915.36 | 12-MAR-16:03 | 27.12 |
April | 10211846.48 | 1208.28 | 09-APR-16:02 | 28.12 |
May | 31033574.99 | 1248.55 | 21-MAY-16:02 | 28.30 |
June | 39578359.36 | 1452.95 | 18-JUN-16:02 | 29.23 |
July | 60093793.30 | 1719.32 | 09-JUL-16:02 | 30.40 |
August | 58660922.71 | 2012.11 | 20-AUG-16:02 | 31.42 |
September | 59589709.58 | 2276.66 | 03-SEP-16:02 | 32.62 |
October | 48670364.40 | 2130.44 | 01-OCT-16:02 | 31.93 |
November | 20223119.47 | 1427.86 | 05-NOV-16:02 | 29.22 |
December | 9944195.37 | 1194.88 | 03-DEC-08:06 | 26.10 |
Annual Sum or Average | 0.354311E+09 | |||
Minimum of Months | 3167802.78 | 719.11 | 26.10 | |
Maximum of Months | 60093793.30 | 2276.66 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3399329.79 | 855.22 | 29-JAN-17:03 | 26.83 |
February | 4912280.74 | 725.14 | 26-FEB-17:03 | 26.32 |
March | 8421280.06 | 921.75 | 12-MAR-16:03 | 27.12 |
April | 10562998.71 | 1212.67 | 09-APR-16:02 | 28.12 |
May | 31994040.27 | 1252.90 | 21-MAY-16:02 | 28.30 |
June | 41418156.62 | 1457.12 | 18-JUN-16:02 | 29.23 |
July | 61521608.93 | 1723.88 | 09-JUL-16:02 | 30.40 |
August | 59947218.12 | 2015.58 | 20-AUG-16:02 | 31.42 |
September | 60828229.06 | 2280.21 | 03-SEP-16:02 | 32.62 |
October | 49839437.94 | 2134.01 | 01-OCT-16:02 | 31.93 |
November | 20670878.40 | 1432.15 | 05-NOV-16:02 | 29.22 |
December | 10850024.96 | 1143.88 | 03-DEC-08:06 | 26.10 |
Annual Sum or Average | 0.364365E+09 | |||
Minimum of Months | 3399329.79 | 725.14 | 26.10 | |
Maximum of Months | 61521608.93 | 2280.21 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9319980.99 | 1811.63 | 08-JAN-09:06 | 24.87 |
February | 14853735.99 | 1494.49 | 05-FEB-09:05 | 24.50 |
March | 19685959.65 | 1875.36 | 12-MAR-16:03 | 27.12 |
April | 26328930.86 | 2432.68 | 09-APR-16:02 | 28.12 |
May | 57662102.44 | 2514.84 | 21-MAY-16:02 | 28.30 |
June | 63241899.50 | 2931.74 | 18-JUN-16:02 | 29.23 |
July | 93334221.43 | 3476.45 | 09-JUL-16:02 | 30.40 |
August | 74888666.55 | 4044.35 | 20-AUG-16:02 | 31.42 |
September | 78758104.07 | 4585.97 | 03-SEP-16:02 | 32.62 |
October | 66346591.51 | 4286.01 | 01-OCT-16:02 | 31.93 |
November | 39300172.64 | 2889.96 | 05-NOV-16:02 | 29.22 |
December | 18758364.27 | 2131.69 | 03-DEC-09:07 | 26.10 |
Annual Sum or Average | 0.562479E+09 | |||
Minimum of Months | 9319980.99 | 1494.49 | 24.50 | |
Maximum of Months | 93334221.43 | 4585.97 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5255385.62 | 909.05 | 01-JAN-09:06 | 24.78 |
February | 7983217.82 | 822.18 | 05-FEB-09:05 | 24.50 |
March | 10615231.09 | 948.77 | 12-MAR-16:03 | 27.12 |
April | 14493523.86 | 1228.76 | 09-APR-16:02 | 28.12 |
May | 29763219.28 | 1269.24 | 21-MAY-16:02 | 28.30 |
June | 31686046.79 | 1475.67 | 18-JUN-16:02 | 29.23 |
July | 47475035.11 | 1745.57 | 09-JUL-16:02 | 30.40 |
August | 39052305.39 | 2030.43 | 20-AUG-16:02 | 31.42 |
September | 39780505.97 | 2298.48 | 03-SEP-16:02 | 32.62 |
October | 33911260.09 | 2149.88 | 01-OCT-16:02 | 31.93 |
November | 19654490.86 | 1489.12 | 23-NOV-09:06 | 27.38 |
December | 9634617.00 | 1092.02 | 06-DEC-08:05 | 25.72 |
Annual Sum or Average | 0.289305E+09 | |||
Minimum of Months | 5255385.62 | 822.18 | 24.50 | |
Maximum of Months | 47475035.11 | 2298.48 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5354074.28 | 896.34 | 01-JAN-09:06 | 24.78 |
February | 8154919.25 | 824.84 | 05-FEB-09:05 | 24.50 |
March | 10693449.95 | 950.36 | 12-MAR-16:03 | 27.12 |
April | 14590185.50 | 1229.72 | 09-APR-16:02 | 28.12 |
May | 29978041.35 | 1270.15 | 21-MAY-16:02 | 28.30 |
June | 31743875.73 | 1476.80 | 18-JUN-16:02 | 29.23 |
July | 47348621.64 | 1746.75 | 09-JUL-16:02 | 30.40 |
August | 39476211.67 | 2031.13 | 20-AUG-16:02 | 31.42 |
September | 40063268.68 | 2299.54 | 03-SEP-16:02 | 32.62 |
October | 34226388.27 | 2150.89 | 01-OCT-16:02 | 31.93 |
November | 19954766.05 | 1477.38 | 23-NOV-09:06 | 27.38 |
December | 9671789.94 | 1089.49 | 06-DEC-08:05 | 25.72 |
Annual Sum or Average | 0.291256E+09 | |||
Minimum of Months | 5354074.28 | 824.84 | 24.50 | |
Maximum of Months | 47348621.64 | 2299.54 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5337908.94 | 884.27 | 29-JAN-17:03 | 26.83 |
February | 8620744.57 | 839.51 | 05-FEB-09:05 | 24.50 |
March | 10946021.73 | 952.39 | 12-MAR-16:03 | 27.12 |
April | 14731103.73 | 1230.68 | 09-APR-16:02 | 28.12 |
May | 29450143.47 | 1270.48 | 21-MAY-16:02 | 28.30 |
June | 31589473.81 | 1476.89 | 18-JUN-16:02 | 29.23 |
July | 46474018.34 | 1746.32 | 09-JUL-16:02 | 30.40 |
August | 39431580.94 | 2030.23 | 20-AUG-16:02 | 31.42 |
September | 39438573.70 | 2298.54 | 03-SEP-16:02 | 32.62 |
October | 34021352.10 | 2150.92 | 01-OCT-16:02 | 31.93 |
November | 19345755.23 | 1454.40 | 05-NOV-16:02 | 29.22 |
December | 9786437.68 | 1125.97 | 06-DEC-08:05 | 25.72 |
Annual Sum or Average | 0.289173E+09 | |||
Minimum of Months | 5337908.94 | 839.51 | 24.50 | |
Maximum of Months | 46474018.34 | 2298.54 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5751208.99 | 943.23 | 08-JAN-09:06 | 24.87 |
February | 9609841.78 | 924.21 | 05-FEB-09:05 | 24.50 |
March | 11551757.71 | 938.67 | 12-MAR-16:03 | 27.12 |
April | 15157212.02 | 1223.99 | 09-APR-16:02 | 28.12 |
May | 24772689.62 | 1276.98 | 14-MAY-08:06 | 26.28 |
June | 24564680.54 | 1458.93 | 18-JUN-16:02 | 29.23 |
July | 39919137.71 | 1717.12 | 09-JUL-16:02 | 30.40 |
August | 34181433.90 | 2006.71 | 20-AUG-16:02 | 31.42 |
September | 37232673.87 | 2267.06 | 03-SEP-16:02 | 32.62 |
October | 32577770.01 | 2129.09 | 01-OCT-16:02 | 31.93 |
November | 15567692.28 | 1522.39 | 23-NOV-09:06 | 27.38 |
December | 8535515.50 | 1233.02 | 06-DEC-08:05 | 25.72 |
Annual Sum or Average | 0.259422E+09 | |||
Minimum of Months | 5751208.99 | 924.21 | 24.50 | |
Maximum of Months | 39919137.71 | 2267.06 | 32.62 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.109389E+11 | 6635.66 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.989784E+10 | 6635.66 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.109616E+11 | 6635.66 | 01-MAR-10:09 | 0.223053E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.106145E+11 | 6635.66 | 01-APR-09:09 | 0.215990E+10 | 1343.25 | 01-APR-09:09 |
May | 0.109389E+11 | 6635.66 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.106145E+11 | 6635.66 | 01-JUN-09:09 | 0.215990E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.109616E+11 | 6635.66 | 01-JUL-09:09 | 0.223053E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.109389E+11 | 6635.66 | 01-AUG-09:09 | 0.222596E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.106372E+11 | 6635.66 | 01-SEP-09:09 | 0.216447E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.109389E+11 | 6635.66 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.105693E+11 | 6635.66 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.109842E+11 | 6635.66 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.128996E+12 | 0.262491E+11 | ||||
Minimum of Months | 0.989784E+10 | 6635.66 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.109842E+11 | 6635.66 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.625207E+10 | 3792.57 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.565704E+10 | 3792.57 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.626500E+10 | 3792.57 | 01-MAR-10:09 | 0.111526E+10 | 671.63 | 01-MAR-10:09 |
April | 0.606666E+10 | 3792.57 | 01-APR-09:09 | 0.107995E+10 | 671.63 | 01-APR-09:09 |
May | 0.625207E+10 | 3792.57 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.606666E+10 | 3792.57 | 01-JUN-09:09 | 0.107995E+10 | 671.63 | 01-JUN-09:09 |
July | 0.626500E+10 | 3792.57 | 01-JUL-09:09 | 0.111526E+10 | 671.63 | 01-JUL-09:09 |
August | 0.625207E+10 | 3792.57 | 01-AUG-09:09 | 0.111298E+10 | 671.63 | 01-AUG-09:09 |
September | 0.607960E+10 | 3792.57 | 01-SEP-09:09 | 0.108223E+10 | 671.63 | 01-SEP-09:09 |
October | 0.625207E+10 | 3792.57 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.604079E+10 | 3792.57 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.627794E+10 | 3792.57 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.737270E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.565704E+10 | 3792.57 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.627794E+10 | 3792.57 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.447798E+10 | 3443.15 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.405524E+10 | 3443.15 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.457193E+10 | 3443.15 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.434490E+10 | 3443.15 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.452496E+10 | 3443.15 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.441536E+10 | 3443.15 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.445450E+10 | 3443.15 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.457193E+10 | 3443.15 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.434490E+10 | 3443.15 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.447798E+10 | 3443.15 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.434490E+10 | 3443.15 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.445450E+10 | 3443.15 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.530391E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.405524E+10 | 3443.15 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.457193E+10 | 3443.15 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.447798E+10 | 3443.15 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.405524E+10 | 3443.15 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.457193E+10 | 3443.15 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.434490E+10 | 3443.15 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.452496E+10 | 3443.15 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.441536E+10 | 3443.15 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.445450E+10 | 3443.15 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.457193E+10 | 3443.15 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.434490E+10 | 3443.15 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.447798E+10 | 3443.15 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.434490E+10 | 3443.15 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.445450E+10 | 3443.15 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.530391E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.405524E+10 | 3443.15 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.457193E+10 | 3443.15 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.447798E+10 | 3443.15 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.405524E+10 | 3443.15 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.457193E+10 | 3443.15 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.434490E+10 | 3443.15 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.452496E+10 | 3443.15 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.441536E+10 | 3443.15 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.445450E+10 | 3443.15 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.457193E+10 | 3443.15 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.434490E+10 | 3443.15 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.447798E+10 | 3443.15 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.434490E+10 | 3443.15 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.445450E+10 | 3443.15 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.530391E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.405524E+10 | 3443.15 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.457193E+10 | 3443.15 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.531643E+10 | 4449.56 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.481564E+10 | 4449.56 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.543783E+10 | 4449.56 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.515962E+10 | 4449.56 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.537713E+10 | 4449.56 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.525067E+10 | 4449.56 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.528608E+10 | 4449.56 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.543783E+10 | 4449.56 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.515962E+10 | 4449.56 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.531643E+10 | 4449.56 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.515962E+10 | 4449.56 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.528608E+10 | 4449.56 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.630030E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.481564E+10 | 4449.56 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.543783E+10 | 4449.56 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.265822E+10 | 2224.78 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.240782E+10 | 2224.78 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.271892E+10 | 2224.78 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.257981E+10 | 2224.78 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.268857E+10 | 2224.78 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.262534E+10 | 2224.78 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.264304E+10 | 2224.78 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.271892E+10 | 2224.78 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.257981E+10 | 2224.78 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.265822E+10 | 2224.78 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.257981E+10 | 2224.78 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.264304E+10 | 2224.78 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.315015E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.240782E+10 | 2224.78 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.271892E+10 | 2224.78 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.265822E+10 | 2224.78 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.240782E+10 | 2224.78 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.271892E+10 | 2224.78 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.257981E+10 | 2224.78 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.268857E+10 | 2224.78 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.262534E+10 | 2224.78 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.264304E+10 | 2224.78 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.271892E+10 | 2224.78 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.257981E+10 | 2224.78 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.265822E+10 | 2224.78 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.257981E+10 | 2224.78 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.264304E+10 | 2224.78 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.315015E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.240782E+10 | 2224.78 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.271892E+10 | 2224.78 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.265822E+10 | 2224.78 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.240782E+10 | 2224.78 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.271892E+10 | 2224.78 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.257981E+10 | 2224.78 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.268857E+10 | 2224.78 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.262534E+10 | 2224.78 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.264304E+10 | 2224.78 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.271892E+10 | 2224.78 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.257981E+10 | 2224.78 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.265822E+10 | 2224.78 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.257981E+10 | 2224.78 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.264304E+10 | 2224.78 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.315015E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.240782E+10 | 2224.78 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.271892E+10 | 2224.78 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.265822E+10 | 2224.78 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.240782E+10 | 2224.78 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.271892E+10 | 2224.78 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.257981E+10 | 2224.78 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.268857E+10 | 2224.78 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.262534E+10 | 2224.78 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.264304E+10 | 2224.78 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.271892E+10 | 2224.78 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.257981E+10 | 2224.78 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.265822E+10 | 2224.78 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.257981E+10 | 2224.78 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.264304E+10 | 2224.78 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.315015E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.240782E+10 | 2224.78 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.271892E+10 | 2224.78 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.180574E+10 | 0.109389E+11 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574148E+09 | 0.353913E+09 |
February | 0.163016E+10 | 0.989784E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624224E+09 | 0.186658E+09 |
March | 0.178954E+10 | 0.109616E+11 | 0.223053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.947812E+09 | 0.190967E+09 |
April | 0.174484E+10 | 0.106145E+11 | 0.215990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103389E+10 | 0.163868E+09 |
May | 0.179537E+10 | 0.109389E+11 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162731E+10 | 94162374.82 |
June | 0.173447E+10 | 0.106145E+11 | 0.215990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159647E+10 | 74276201.93 |
July | 0.181028E+10 | 0.109616E+11 | 0.223053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220428E+10 | 58398821.37 |
August | 0.178501E+10 | 0.109389E+11 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240604E+10 | 50390361.57 |
September | 0.174937E+10 | 0.106372E+11 | 0.216447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198943E+10 | 40600580.06 |
October | 0.180574E+10 | 0.109389E+11 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210594E+10 | 56889738.23 |
November | 0.174613E+10 | 0.105693E+11 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123657E+10 | 0.123391E+09 |
December | 0.181481E+10 | 0.109842E+11 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.799969E+09 | 0.179105E+09 |
Annual Sum or Average | 0.212115E+11 | 0.128996E+12 | 0.262491E+11 | 0.171461E+11 | 0.157262E+10 | ||||
Minimum of Months | 0.163016E+10 | 0.989784E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574148E+09 | 40600580.06 |
Maximum of Months | 0.181481E+10 | 0.109842E+11 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240604E+10 | 0.353913E+09 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.902868E+09 | 0.625207E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321538E+09 | 0.149823E+09 |
February | 0.815075E+09 | 0.565704E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349728E+09 | 71545754.87 |
March | 0.894769E+09 | 0.626500E+10 | 0.111526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529155E+09 | 66428908.09 |
April | 0.872416E+09 | 0.606666E+10 | 0.107995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576203E+09 | 55458886.60 |
May | 0.897684E+09 | 0.625207E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905971E+09 | 29140977.34 |
June | 0.867232E+09 | 0.606666E+10 | 0.107995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.880853E+09 | 22829566.69 |
July | 0.905135E+09 | 0.626500E+10 | 0.111526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121597E+10 | 17959778.81 |
August | 0.892501E+09 | 0.625207E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133089E+10 | 15279697.93 |
September | 0.874683E+09 | 0.607960E+10 | 0.108223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109682E+10 | 12172118.43 |
October | 0.902868E+09 | 0.625207E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117324E+10 | 17763171.09 |
November | 0.873064E+09 | 0.604079E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683948E+09 | 40542342.48 |
December | 0.907403E+09 | 0.627794E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446442E+09 | 64594602.78 |
Annual Sum or Average | 0.106057E+11 | 0.737270E+11 | 0.131245E+11 | 0.951076E+10 | 0.563539E+09 | ||||
Minimum of Months | 0.815075E+09 | 0.565704E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321538E+09 | 12172118.43 |
Maximum of Months | 0.907403E+09 | 0.627794E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133089E+10 | 0.149823E+09 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.447798E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318096E+09 | 0.180986E+09 |
February | 0.487879E+09 | 0.405524E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344593E+09 | 96247871.85 |
March | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521435E+09 | 90706438.21 |
April | 0.524810E+09 | 0.434490E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565919E+09 | 83724354.77 |
May | 0.544247E+09 | 0.452496E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.888948E+09 | 46657993.79 |
June | 0.532585E+09 | 0.441536E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.861493E+09 | 38536949.59 |
July | 0.536472E+09 | 0.445450E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118371E+10 | 31072978.15 |
August | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130702E+10 | 24687275.81 |
September | 0.524810E+09 | 0.434490E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106743E+10 | 21460096.54 |
October | 0.537120E+09 | 0.447798E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114650E+10 | 28455816.45 |
November | 0.518979E+09 | 0.434490E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670997E+09 | 63308069.92 |
December | 0.536472E+09 | 0.445450E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442356E+09 | 96431585.36 |
Annual Sum or Average | 0.638324E+10 | 0.530391E+11 | 0.104207E+11 | 0.931850E+10 | 0.802276E+09 | ||||
Minimum of Months | 0.487879E+09 | 0.405524E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318096E+09 | 21460096.54 |
Maximum of Months | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130702E+10 | 0.180986E+09 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.447798E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318098E+09 | 0.180687E+09 |
February | 0.487879E+09 | 0.405524E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344593E+09 | 96123246.40 |
March | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521441E+09 | 90688922.03 |
April | 0.524810E+09 | 0.434490E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565927E+09 | 83617198.77 |
May | 0.544247E+09 | 0.452496E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.888939E+09 | 46940069.43 |
June | 0.532585E+09 | 0.441536E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.861470E+09 | 39134171.95 |
July | 0.536472E+09 | 0.445450E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118357E+10 | 32167877.50 |
August | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130692E+10 | 25526961.24 |
September | 0.524810E+09 | 0.434490E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106714E+10 | 22439325.35 |
October | 0.537120E+09 | 0.447798E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114641E+10 | 29082750.24 |
November | 0.518979E+09 | 0.434490E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670990E+09 | 63606636.65 |
December | 0.536472E+09 | 0.445450E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442355E+09 | 96422869.74 |
Annual Sum or Average | 0.638324E+10 | 0.530391E+11 | 0.104207E+11 | 0.931785E+10 | 0.806437E+09 | ||||
Minimum of Months | 0.487879E+09 | 0.405524E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318098E+09 | 22439325.35 |
Maximum of Months | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130692E+10 | 0.180687E+09 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.447798E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318109E+09 | 0.178318E+09 |
February | 0.487879E+09 | 0.405524E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344605E+09 | 94268213.91 |
March | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521486E+09 | 88543384.11 |
April | 0.524810E+09 | 0.434490E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566000E+09 | 81164228.35 |
May | 0.544247E+09 | 0.452496E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.889125E+09 | 44814451.18 |
June | 0.532585E+09 | 0.441536E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.861666E+09 | 36317540.43 |
July | 0.536472E+09 | 0.445450E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118398E+10 | 29120784.50 |
August | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130720E+10 | 23058734.73 |
September | 0.524810E+09 | 0.434490E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106758E+10 | 20063499.81 |
October | 0.537120E+09 | 0.447798E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114669E+10 | 27327539.68 |
November | 0.518979E+09 | 0.434490E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671063E+09 | 61117688.88 |
December | 0.536472E+09 | 0.445450E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442373E+09 | 93887338.98 |
Annual Sum or Average | 0.638324E+10 | 0.530391E+11 | 0.104207E+11 | 0.931989E+10 | 0.778002E+09 | ||||
Minimum of Months | 0.487879E+09 | 0.405524E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318109E+09 | 20063499.81 |
Maximum of Months | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130720E+10 | 0.178318E+09 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.183632E+10 | 0.531643E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558326E+09 | 0.327201E+09 |
February | 0.167188E+10 | 0.481564E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604716E+09 | 0.174731E+09 |
March | 0.189386E+10 | 0.543783E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.915972E+09 | 0.166627E+09 |
April | 0.180380E+10 | 0.515962E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.994477E+09 | 0.152215E+09 |
May | 0.186509E+10 | 0.537713E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156268E+10 | 82648774.63 |
June | 0.182945E+10 | 0.525067E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151523E+10 | 62231973.71 |
July | 0.183943E+10 | 0.528608E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208240E+10 | 47019302.82 |
August | 0.189386E+10 | 0.543783E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229936E+10 | 37264721.02 |
September | 0.180380E+10 | 0.515962E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187915E+10 | 31842076.36 |
October | 0.183632E+10 | 0.531643E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201509E+10 | 49252429.41 |
November | 0.176881E+10 | 0.515962E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117873E+10 | 0.111685E+09 |
December | 0.183943E+10 | 0.528608E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776115E+09 | 0.174403E+09 |
Annual Sum or Average | 0.218821E+11 | 0.630030E+11 | 0.191729E+11 | 0.163823E+11 | 0.141712E+10 | ||||
Minimum of Months | 0.167188E+10 | 0.481564E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558326E+09 | 31842076.36 |
Maximum of Months | 0.189386E+10 | 0.543783E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229936E+10 | 0.327201E+09 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318195E+09 | 0.174848E+09 |
February | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344665E+09 | 91352989.18 |
March | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521821E+09 | 84994161.15 |
April | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566432E+09 | 76927592.53 |
May | 0.932542E+09 | 0.268857E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.890087E+09 | 40355391.97 |
June | 0.914724E+09 | 0.262534E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862280E+09 | 29138699.46 |
July | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118541E+10 | 21460235.64 |
August | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130906E+10 | 17038161.57 |
September | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106972E+10 | 14337629.45 |
October | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114835E+10 | 23875883.82 |
November | 0.884402E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670783E+09 | 55549238.99 |
December | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442171E+09 | 89549648.97 |
Annual Sum or Average | 0.109410E+11 | 0.315015E+11 | 0.958644E+10 | 0.932897E+10 | 0.719428E+09 | ||||
Minimum of Months | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318195E+09 | 14337629.45 |
Maximum of Months | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130906E+10 | 0.174848E+09 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318201E+09 | 0.174148E+09 |
February | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344674E+09 | 90797068.47 |
March | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521839E+09 | 84408228.07 |
April | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566467E+09 | 76287569.01 |
May | 0.932542E+09 | 0.268857E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.890158E+09 | 39861899.65 |
June | 0.914724E+09 | 0.262534E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862378E+09 | 28530998.64 |
July | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118562E+10 | 20877889.44 |
August | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130921E+10 | 16617053.36 |
September | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106995E+10 | 13906909.36 |
October | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114850E+10 | 23525081.68 |
November | 0.884402E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670833E+09 | 54901947.26 |
December | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442182E+09 | 88812070.39 |
Annual Sum or Average | 0.109410E+11 | 0.315015E+11 | 0.958644E+10 | 0.933001E+10 | 0.712675E+09 | ||||
Minimum of Months | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318201E+09 | 13906909.36 |
Maximum of Months | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130921E+10 | 0.174148E+09 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318206E+09 | 0.172508E+09 |
February | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344689E+09 | 89463628.43 |
March | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521856E+09 | 83101153.10 |
April | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566496E+09 | 74901121.09 |
May | 0.932542E+09 | 0.268857E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.890189E+09 | 38918006.87 |
June | 0.914724E+09 | 0.262534E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862465E+09 | 27367324.32 |
July | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118573E+10 | 19865662.74 |
August | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130928E+10 | 15978569.99 |
September | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107002E+10 | 13198002.92 |
October | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114858E+10 | 22993907.36 |
November | 0.884402E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670887E+09 | 53585821.32 |
December | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442194E+09 | 87246445.98 |
Annual Sum or Average | 0.109410E+11 | 0.315015E+11 | 0.958644E+10 | 0.933060E+10 | 0.699128E+09 | ||||
Minimum of Months | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318206E+09 | 13198002.92 |
Maximum of Months | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130928E+10 | 0.172508E+09 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328031E+09 | 0.268930E+09 |
February | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355042E+09 | 0.154946E+09 |
March | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540072E+09 | 0.163285E+09 |
April | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587636E+09 | 0.151776E+09 |
May | 0.932542E+09 | 0.268857E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.924011E+09 | 88727731.91 |
June | 0.914724E+09 | 0.262534E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904694E+09 | 67622596.35 |
July | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124220E+10 | 52700253.39 |
August | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136877E+10 | 43448754.68 |
September | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112190E+10 | 35763791.12 |
October | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118891E+10 | 54038519.68 |
November | 0.884402E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702706E+09 | 0.111620E+09 |
December | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457519E+09 | 0.161517E+09 |
Annual Sum or Average | 0.109410E+11 | 0.315015E+11 | 0.958644E+10 | 0.972149E+10 | 0.135438E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328031E+09 | 35763791.12 |
Maximum of Months | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136877E+10 | 0.268930E+09 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2159.72 | 01-JAN-13:09 | 6635.66 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2594.94 | 06-JAN-13:00 | 2205.18 | 25-JAN-12:10 |
February | 2159.72 | 03-FEB-13:09 | 6635.66 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2357.75 | 25-FEB-13:00 | 1074.68 | 06-FEB-18:00 |
March | 2159.72 | 03-MAR-13:09 | 6635.66 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2913.06 | 29-MAR-13:00 | 815.87 | 03-MAR-15:00 |
April | 2159.72 | 01-APR-12:09 | 6635.66 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2928.00 | 09-APR-14:00 | 825.43 | 11-APR-14:00 |
May | 2159.72 | 05-MAY-12:09 | 6635.66 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3458.46 | 17-MAY-13:00 | 305.67 | 31-MAY-04:00 |
June | 2159.72 | 02-JUN-12:09 | 6635.66 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3240.11 | 29-JUN-11:20 | 209.42 | 13-JUN-05:00 |
July | 2159.72 | 01-JUL-12:09 | 6635.66 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3937.62 | 09-JUL-12:00 | 218.61 | 13-JUL-06:00 |
August | 2159.72 | 04-AUG-12:09 | 6635.66 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4201.05 | 11-AUG-14:00 | 173.89 | 13-AUG-03:00 |
September | 2159.72 | 01-SEP-12:09 | 6635.66 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4517.87 | 03-SEP-13:00 | 187.83 | 30-SEP-06:00 |
October | 2159.72 | 01-OCT-12:09 | 6635.66 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4429.09 | 01-OCT-13:00 | 307.59 | 19-OCT-07:02 |
November | 2159.72 | 03-NOV-12:09 | 6635.66 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3261.33 | 04-NOV-13:00 | 1082.33 | 25-NOV-18:00 |
December | 2159.72 | 01-DEC-13:09 | 6635.66 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3178.62 | 13-DEC-14:00 | 1005.32 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2159.72 | 6635.66 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2357.75 | 173.89 | |||||
Maximum of Months | 2159.72 | 6635.66 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4517.87 | 2205.18 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 01-JAN-13:09 | 3792.57 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1463.03 | 03-JAN-14:00 | 1242.67 | 25-JAN-12:10 |
February | 1079.86 | 03-FEB-13:09 | 3792.57 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.20 | 25-FEB-13:00 | 602.29 | 06-FEB-18:00 |
March | 1079.86 | 03-MAR-13:09 | 3792.57 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.02 | 29-MAR-13:00 | 457.87 | 03-MAR-15:00 |
April | 1079.86 | 01-APR-12:09 | 3792.57 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1635.90 | 09-APR-14:00 | 464.00 | 11-APR-14:00 |
May | 1079.86 | 05-MAY-12:09 | 3792.57 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1926.75 | 17-MAY-13:00 | 161.03 | 15-MAY-17:00 |
June | 1079.86 | 02-JUN-12:09 | 3792.57 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1801.77 | 29-JUN-11:10 | 64.11 | 13-JUN-05:00 |
July | 1079.86 | 01-JUL-12:09 | 3792.57 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2206.80 | 09-JUL-12:00 | 66.46 | 13-JUL-06:00 |
August | 1079.86 | 04-AUG-12:09 | 3792.57 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2354.42 | 11-AUG-14:00 | 90.50 | 26-AUG-07:02 |
September | 1079.86 | 01-SEP-12:09 | 3792.57 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.20 | 03-SEP-13:00 | 71.56 | 19-SEP-07:02 |
October | 1079.86 | 01-OCT-12:09 | 3792.57 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2482.23 | 01-OCT-13:00 | 170.35 | 19-OCT-07:02 |
November | 1079.86 | 03-NOV-12:09 | 3792.57 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1807.89 | 04-NOV-13:00 | 603.77 | 25-NOV-18:00 |
December | 1079.86 | 01-DEC-13:09 | 3792.57 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1784.19 | 13-DEC-14:00 | 568.87 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3792.57 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.20 | 64.11 | |||||
Maximum of Months | 1079.86 | 3792.57 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.20 | 1242.67 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3443.15 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1463.02 | 03-JAN-14:00 | 1242.67 | 25-JAN-12:10 |
February | 1079.86 | 04-FEB-13:09 | 3443.15 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.24 | 25-FEB-13:00 | 800.53 | 12-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3443.15 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.04 | 29-MAR-13:00 | 728.79 | 05-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 3443.15 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1635.94 | 09-APR-14:00 | 501.66 | 16-APR-17:00 |
May | 1079.86 | 06-MAY-12:09 | 3443.15 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1926.41 | 17-MAY-13:00 | 653.18 | 14-MAY-17:00 |
June | 1079.86 | 03-JUN-12:09 | 3443.15 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1801.77 | 29-JUN-11:10 | 108.48 | 25-JUN-17:00 |
July | 1079.86 | 01-JUL-12:09 | 3443.15 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2206.80 | 09-JUL-12:00 | 86.63 | 22-JUL-18:10 |
August | 1079.86 | 05-AUG-12:09 | 3443.15 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2354.39 | 11-AUG-14:00 | 122.60 | 06-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 3443.15 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.15 | 03-SEP-13:00 | 86.49 | 30-SEP-18:10 |
October | 1079.86 | 07-OCT-12:09 | 3443.15 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2482.18 | 01-OCT-13:00 | 568.82 | 22-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 3443.15 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1807.88 | 04-NOV-13:00 | 757.07 | 26-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3443.15 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1784.18 | 13-DEC-14:00 | 965.44 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.24 | 86.49 | |||||
Maximum of Months | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.15 | 1242.67 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3443.15 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1463.02 | 03-JAN-14:00 | 1242.68 | 25-JAN-12:10 |
February | 1079.86 | 04-FEB-13:09 | 3443.15 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.23 | 25-FEB-13:00 | 796.87 | 12-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3443.15 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.05 | 29-MAR-13:00 | 726.75 | 05-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 3443.15 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1635.95 | 09-APR-14:00 | 500.53 | 16-APR-17:00 |
May | 1079.86 | 06-MAY-12:09 | 3443.15 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1926.41 | 17-MAY-13:00 | 654.17 | 14-MAY-17:00 |
June | 1079.86 | 03-JUN-12:09 | 3443.15 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1801.48 | 29-JUN-11:20 | 112.11 | 25-JUN-17:00 |
July | 1079.86 | 01-JUL-12:09 | 3443.15 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2206.80 | 09-JUL-12:00 | 87.38 | 22-JUL-18:10 |
August | 1079.86 | 05-AUG-12:09 | 3443.15 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2354.38 | 11-AUG-14:00 | 127.01 | 06-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 3443.15 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.15 | 03-SEP-13:00 | 88.08 | 30-SEP-19:00 |
October | 1079.86 | 07-OCT-12:09 | 3443.15 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2482.18 | 01-OCT-13:00 | 570.76 | 22-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 3443.15 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1807.88 | 04-NOV-13:00 | 754.76 | 26-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3443.15 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1784.18 | 13-DEC-14:00 | 962.56 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.23 | 87.38 | |||||
Maximum of Months | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.15 | 1242.68 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3443.15 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1463.01 | 03-JAN-14:00 | 1242.68 | 25-JAN-12:10 |
February | 1079.86 | 04-FEB-13:09 | 3443.15 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.23 | 25-FEB-13:00 | 778.93 | 12-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3443.15 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.07 | 29-MAR-13:00 | 710.11 | 05-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 3443.15 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1635.97 | 09-APR-14:00 | 483.57 | 16-APR-17:00 |
May | 1079.86 | 06-MAY-12:09 | 3443.15 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1926.42 | 17-MAY-13:00 | 639.49 | 14-MAY-17:00 |
June | 1079.86 | 03-JUN-12:09 | 3443.15 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1801.49 | 29-JUN-11:20 | 97.89 | 25-JUN-17:00 |
July | 1079.86 | 01-JUL-12:09 | 3443.15 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2206.79 | 09-JUL-12:00 | 83.07 | 22-JUL-18:10 |
August | 1079.86 | 05-AUG-12:09 | 3443.15 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2354.38 | 11-AUG-14:00 | 112.51 | 06-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 3443.15 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.15 | 03-SEP-13:00 | 82.49 | 30-SEP-18:10 |
October | 1079.86 | 07-OCT-12:09 | 3443.15 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2482.17 | 01-OCT-13:00 | 555.35 | 22-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 3443.15 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1807.88 | 04-NOV-13:00 | 738.73 | 26-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3443.15 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1784.17 | 13-DEC-14:00 | 945.54 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.23 | 82.49 | |||||
Maximum of Months | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.15 | 1242.68 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2879.63 | 07-JAN-15:09 | 4449.56 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2564.38 | 03-JAN-14:00 | 2178.49 | 25-JAN-12:10 |
February | 2879.63 | 04-FEB-15:09 | 4449.56 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2334.58 | 25-FEB-13:00 | 1255.45 | 12-FEB-18:00 |
March | 2879.63 | 04-MAR-15:09 | 4449.56 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2860.65 | 29-MAR-13:00 | 1145.45 | 05-MAR-18:00 |
April | 2879.63 | 01-APR-14:09 | 4449.56 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2871.64 | 09-APR-14:00 | 813.88 | 11-APR-14:00 |
May | 2879.63 | 06-MAY-14:09 | 4449.56 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3382.99 | 17-MAY-13:00 | 1054.10 | 14-MAY-17:00 |
June | 2879.63 | 03-JUN-14:09 | 4449.56 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3164.46 | 29-JUN-11:20 | 139.10 | 08-JUN-23:00 |
July | 2879.63 | 01-JUL-14:09 | 4449.56 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3871.67 | 09-JUL-12:00 | 129.35 | 22-JUL-18:10 |
August | 2879.63 | 05-AUG-14:09 | 4449.56 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4130.66 | 11-AUG-14:00 | 192.68 | 06-AUG-07:10 |
September | 2879.63 | 02-SEP-14:09 | 4449.56 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4406.50 | 03-SEP-13:00 | 138.08 | 10-SEP-07:01 |
October | 2879.63 | 07-OCT-14:09 | 4449.56 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4354.86 | 01-OCT-13:00 | 890.37 | 22-OCT-17:00 |
November | 2879.63 | 04-NOV-14:09 | 4449.56 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3176.95 | 04-NOV-13:00 | 1192.68 | 26-NOV-18:00 |
December | 2879.63 | 02-DEC-15:09 | 4449.56 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3129.60 | 13-DEC-14:00 | 1550.00 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2879.63 | 4449.56 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2334.58 | 129.35 | |||||
Maximum of Months | 2879.63 | 4449.56 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4406.50 | 2178.49 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2224.78 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1463.05 | 03-JAN-14:00 | 1242.67 | 25-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 2224.78 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.26 | 25-FEB-13:00 | 697.49 | 12-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2224.78 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.14 | 29-MAR-13:00 | 632.54 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 2224.78 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1636.04 | 09-APR-14:00 | 464.08 | 11-APR-14:00 |
May | 1439.81 | 06-MAY-14:09 | 2224.78 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1926.48 | 17-MAY-13:00 | 574.80 | 14-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 2224.78 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1801.82 | 29-JUN-11:10 | 67.45 | 08-JUN-23:00 |
July | 1439.81 | 01-JUL-14:09 | 2224.78 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2206.78 | 09-JUL-12:00 | 64.17 | 22-JUL-18:10 |
August | 1439.81 | 05-AUG-14:09 | 2224.78 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2354.39 | 11-AUG-14:00 | 102.03 | 06-AUG-07:01 |
September | 1439.81 | 02-SEP-14:09 | 2224.78 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.14 | 03-SEP-13:00 | 75.16 | 10-SEP-07:01 |
October | 1439.81 | 07-OCT-14:09 | 2224.78 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2482.18 | 01-OCT-13:00 | 486.22 | 22-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 2224.78 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1807.88 | 04-NOV-13:00 | 661.93 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2224.78 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1784.21 | 13-DEC-14:00 | 862.91 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.26 | 64.17 | |||||
Maximum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.14 | 1242.67 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2224.78 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1463.05 | 03-JAN-14:00 | 1242.67 | 25-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 2224.78 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.26 | 25-FEB-13:00 | 691.30 | 12-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2224.78 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.13 | 29-MAR-13:00 | 627.17 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 2224.78 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1636.00 | 09-APR-14:00 | 464.09 | 11-APR-14:00 |
May | 1439.81 | 06-MAY-14:09 | 2224.78 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1926.48 | 17-MAY-13:00 | 570.65 | 14-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 2224.78 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1801.82 | 29-JUN-11:10 | 66.99 | 08-JUN-23:00 |
July | 1439.81 | 01-JUL-14:09 | 2224.78 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2206.78 | 09-JUL-12:00 | 62.94 | 22-JUL-18:10 |
August | 1439.81 | 05-AUG-14:09 | 2224.78 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2354.39 | 11-AUG-14:00 | 100.56 | 06-AUG-07:03 |
September | 1439.81 | 02-SEP-14:09 | 2224.78 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.14 | 03-SEP-13:00 | 74.13 | 10-SEP-07:01 |
October | 1439.81 | 07-OCT-14:09 | 2224.78 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2482.18 | 01-OCT-13:00 | 482.16 | 22-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 2224.78 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1807.88 | 04-NOV-13:00 | 656.50 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2224.78 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1784.21 | 13-DEC-14:00 | 857.17 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.26 | 62.94 | |||||
Maximum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.14 | 1242.67 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2224.78 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1463.05 | 03-JAN-14:00 | 1242.67 | 25-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 2224.78 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.25 | 25-FEB-13:00 | 680.94 | 12-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2224.78 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.12 | 29-MAR-13:00 | 621.48 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 2224.78 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1636.02 | 09-APR-14:00 | 464.09 | 11-APR-14:00 |
May | 1439.81 | 06-MAY-14:09 | 2224.78 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1926.78 | 17-MAY-13:00 | 567.38 | 14-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 2224.78 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1801.84 | 29-JUN-11:10 | 66.13 | 08-JUN-23:00 |
July | 1439.81 | 01-JUL-14:09 | 2224.78 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2206.78 | 09-JUL-12:00 | 62.22 | 22-JUL-18:10 |
August | 1439.81 | 05-AUG-14:09 | 2224.78 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2354.39 | 11-AUG-14:00 | 97.93 | 06-AUG-07:01 |
September | 1439.81 | 02-SEP-14:09 | 2224.78 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.15 | 03-SEP-13:00 | 71.87 | 18-SEP-07:02 |
October | 1439.81 | 07-OCT-14:09 | 2224.78 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2482.18 | 01-OCT-13:00 | 479.64 | 22-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 2224.78 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1807.88 | 04-NOV-13:00 | 650.03 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2224.78 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1784.21 | 13-DEC-14:00 | 850.97 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.25 | 62.22 | |||||
Maximum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.15 | 1242.67 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2224.78 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1494.07 | 06-JAN-13:00 | 1269.32 | 25-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 2224.78 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1355.56 | 25-FEB-13:00 | 715.98 | 12-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2224.78 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1682.54 | 29-MAR-13:00 | 686.37 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 2224.78 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1692.50 | 09-APR-14:00 | 475.71 | 11-APR-14:00 |
May | 1439.81 | 06-MAY-14:09 | 2224.78 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2002.38 | 17-MAY-13:00 | 651.33 | 14-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 2224.78 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1877.50 | 29-JUN-11:10 | 161.74 | 08-JUN-23:00 |
July | 1439.81 | 01-JUL-14:09 | 2224.78 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2272.68 | 09-JUL-12:00 | 129.77 | 13-JUL-06:00 |
August | 1439.81 | 05-AUG-14:09 | 2224.78 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2424.64 | 11-AUG-14:00 | 137.92 | 06-AUG-07:10 |
September | 1439.81 | 02-SEP-14:09 | 2224.78 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2619.30 | 03-SEP-13:00 | 121.09 | 30-SEP-18:10 |
October | 1439.81 | 07-OCT-14:09 | 2224.78 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2556.23 | 01-OCT-13:00 | 565.97 | 22-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 2224.78 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1892.15 | 04-NOV-13:00 | 692.18 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2224.78 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1833.21 | 13-DEC-14:00 | 891.05 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1355.56 | 121.09 | |||||
Maximum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2619.30 | 1269.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 34617.77 | 21-JAN-08:62 | 0.00 | 1749.37 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.38 |
February | 29050.73 | 01-FEB-08:62 | 719.91 | 1396.98 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.44 |
March | 31588.89 | 19-MAR-07:02 | 1079.86 | 2095.47 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.32 |
April | 32344.80 | 30-APR-07:02 | 899.88 | 1746.23 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.83 |
May | 32580.95 | 02-MAY-07:02 | 899.88 | 1746.23 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.47 |
June | 30420.10 | 04-JUN-07:01 | 1259.84 | 2444.72 | 522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.51 |
July | 29132.20 | 08-JUL-07:02 | 0.00 | 2099.25 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 18.08 | 0.00 |
August | 29581.23 | 24-AUG-07:02 | 1079.86 | 2095.47 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.02 |
September | 29340.36 | 18-SEP-07:02 | 1079.86 | 2095.47 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.72 |
October | 30599.08 | 26-OCT-07:02 | 899.88 | 1746.23 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.92 |
November | 32672.16 | 26-NOV-08:62 | 899.88 | 1746.23 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.37 |
December | 34671.80 | 25-DEC-08:62 | 899.88 | 1746.23 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.25 |
Annual Sum or Average | |||||||||||
Minimum of Months | 29050.73 | 0.00 | 1396.98 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34671.80 | 1259.84 | 2444.72 | 522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 18.08 | 241.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19046.31 | 21-JAN-08:62 | 0.00 | 999.84 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.09 |
February | 17405.85 | 01-FEB-08:62 | 359.95 | 798.44 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.89 |
March | 17886.57 | 19-MAR-07:02 | 539.93 | 1197.65 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.68 |
April | 18239.30 | 30-APR-07:02 | 449.94 | 998.04 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.53 |
May | 18104.11 | 02-MAY-07:02 | 449.94 | 998.04 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.08 |
June | 17287.37 | 04-JUN-07:01 | 629.92 | 1397.26 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.26 |
July | 16677.15 | 08-JUL-07:02 | 0.00 | 1199.81 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 9.22 | 0.00 |
August | 16882.68 | 24-AUG-07:02 | 539.93 | 1197.65 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.61 |
September | 16869.80 | 18-SEP-07:02 | 539.93 | 1197.65 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.86 |
October | 17449.84 | 26-OCT-07:02 | 449.94 | 998.04 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.52 |
November | 18213.03 | 26-NOV-08:62 | 449.94 | 998.04 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.59 |
December | 18970.26 | 25-DEC-08:62 | 449.94 | 998.04 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.57 |
Annual Sum or Average | |||||||||||
Minimum of Months | 16677.15 | 0.00 | 798.44 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19046.31 | 629.92 | 1397.26 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 9.22 | 132.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18112.54 | 21-JAN-07:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.61 |
February | 16515.74 | 01-FEB-07:03 | 0.00 | 724.87 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 |
March | 17112.41 | 07-MAR-07:03 | 0.00 | 724.87 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.76 |
April | 17447.75 | 02-APR-07:03 | 0.00 | 724.87 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.00 |
May | 16516.76 | 02-MAY-06:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 |
June | 15489.22 | 04-JUN-07:01 | 0.00 | 1268.53 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.89 |
July | 14794.95 | 04-JUL-07:01 | 0.00 | 1268.53 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.45 |
August | 15145.87 | 24-AUG-06:02 | 0.00 | 1087.31 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.98 |
September | 15146.96 | 19-SEP-06:02 | 0.00 | 1087.31 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.31 |
October | 15366.63 | 19-OCT-06:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.12 |
November | 16435.10 | 09-NOV-07:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.80 |
December | 18450.22 | 20-DEC-07:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.42 |
Annual Sum or Average | |||||||||||
Minimum of Months | 14794.95 | 0.00 | 724.87 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.31 | |
Maximum of Months | 18450.22 | 0.00 | 1268.53 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18127.27 | 21-JAN-07:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.56 |
February | 16536.93 | 01-FEB-07:03 | 0.00 | 724.87 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 |
March | 16882.84 | 07-MAR-07:03 | 0.00 | 724.87 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.76 |
April | 17337.29 | 02-APR-07:03 | 0.00 | 724.87 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.72 |
May | 16539.62 | 02-MAY-06:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.15 |
June | 15534.34 | 04-JUN-07:01 | 0.00 | 1268.53 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.59 |
July | 14856.47 | 04-JUL-07:01 | 0.00 | 1268.53 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.95 |
August | 15189.85 | 24-AUG-06:02 | 0.00 | 1087.31 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.01 |
September | 15202.78 | 19-SEP-06:02 | 0.00 | 1087.31 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 |
October | 15401.72 | 19-OCT-06:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.15 |
November | 16470.49 | 09-NOV-07:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.81 |
December | 18477.32 | 20-DEC-07:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.35 |
Annual Sum or Average | |||||||||||
Minimum of Months | 14856.47 | 0.00 | 724.87 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 | |
Maximum of Months | 18477.32 | 0.00 | 1268.53 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17883.71 | 21-JAN-07:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.24 |
February | 16135.58 | 01-FEB-07:03 | 0.00 | 724.87 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.43 |
March | 15905.99 | 19-MAR-07:02 | 0.00 | 1087.31 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.24 |
April | 16569.46 | 30-APR-07:02 | 0.00 | 906.09 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.10 |
May | 16304.84 | 02-MAY-06:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.84 |
June | 15293.66 | 04-JUN-07:01 | 0.00 | 1268.53 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.66 |
July | 14631.50 | 04-JUL-07:01 | 0.00 | 1268.53 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.68 |
August | 14961.70 | 24-AUG-06:02 | 0.00 | 1087.31 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.78 |
September | 14981.64 | 19-SEP-06:02 | 0.00 | 1087.31 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.27 |
October | 15173.45 | 19-OCT-06:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.87 |
November | 16243.94 | 09-NOV-07:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.66 |
December | 18245.30 | 20-DEC-07:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.66 |
Annual Sum or Average | |||||||||||
Minimum of Months | 14631.50 | 0.00 | 724.87 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.27 | |
Maximum of Months | 18245.30 | 0.00 | 1268.53 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 32051.28 | 21-JAN-08:62 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.55 |
February | 26221.62 | 13-FEB-08:62 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.11 |
March | 27661.82 | 19-MAR-08:62 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.20 |
April | 29403.12 | 06-APR-07:02 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.11 |
May | 29301.07 | 02-MAY-07:02 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.33 |
June | 26554.41 | 27-JUN-07:02 | 0.00 | 1405.12 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.56 |
July | 26816.25 | 18-JUL-07:01 | 0.00 | 1639.31 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 56.90 | 0.00 |
August | 27026.62 | 24-AUG-07:02 | 0.00 | 1405.12 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.44 |
September | 27165.65 | 19-SEP-07:02 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.89 |
October | 27469.93 | 19-OCT-07:02 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.53 |
November | 28606.23 | 09-NOV-08:62 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.09 |
December | 32388.70 | 20-DEC-08:62 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.24 |
Annual Sum or Average | |||||||||||
Minimum of Months | 26221.62 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32388.70 | 0.00 | 1639.31 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 56.90 | 291.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16604.90 | 21-JAN-08:62 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.88 |
February | 13578.92 | 13-FEB-08:62 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.53 |
March | 14314.12 | 19-MAR-08:62 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.64 |
April | 15226.80 | 06-APR-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.66 |
May | 15198.46 | 02-MAY-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.72 |
June | 13786.36 | 27-JUN-07:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 |
July | 13899.12 | 18-JUL-07:01 | 0.00 | 819.66 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 35.85 | 0.00 |
August | 14005.90 | 24-AUG-07:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.98 |
September | 14094.99 | 19-SEP-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.60 |
October | 14227.26 | 19-OCT-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.32 |
November | 14816.52 | 09-NOV-08:62 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.79 |
December | 16778.89 | 20-DEC-08:62 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.68 |
Annual Sum or Average | |||||||||||
Minimum of Months | 13578.92 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16778.89 | 0.00 | 819.66 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 35.85 | 161.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16493.58 | 21-JAN-08:62 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.53 |
February | 13481.58 | 13-FEB-08:62 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.85 |
March | 14221.76 | 19-MAR-08:62 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.41 |
April | 15124.96 | 06-APR-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.44 |
May | 15096.30 | 02-MAY-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.82 |
June | 13688.31 | 27-JUN-07:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.03 | 0.00 |
July | 13805.10 | 18-JUL-07:01 | 0.00 | 819.66 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 36.92 | 0.00 |
August | 13907.83 | 24-AUG-07:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.93 |
September | 13997.05 | 19-SEP-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.70 |
October | 14129.03 | 19-OCT-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.26 |
November | 14711.49 | 09-NOV-08:62 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.61 |
December | 16668.27 | 20-DEC-08:62 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.25 |
Annual Sum or Average | |||||||||||
Minimum of Months | 13481.58 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16668.27 | 0.00 | 819.66 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 36.92 | 160.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15332.62 | 21-JAN-08:62 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.77 |
February | 13400.26 | 13-FEB-08:62 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 |
March | 14180.31 | 19-MAR-08:62 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.10 |
April | 15074.45 | 06-APR-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.78 |
May | 15040.19 | 02-MAY-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.21 |
June | 13646.70 | 27-JUN-07:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 3.06 | 0.00 |
July | 13766.31 | 18-JUL-07:01 | 0.00 | 819.66 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 39.93 | 0.00 |
August | 13888.79 | 24-AUG-07:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.93 |
September | 13970.55 | 19-SEP-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.31 |
October | 14092.84 | 19-OCT-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.54 |
November | 14659.68 | 09-NOV-08:62 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.16 |
December | 16611.12 | 20-DEC-08:62 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.62 |
Annual Sum or Average | |||||||||||
Minimum of Months | 13400.26 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16611.12 | 0.00 | 819.66 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 39.93 | 157.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14652.70 | 12-JAN-08:62 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.39 |
February | 12730.22 | 23-FEB-08:62 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.99 |
March | 15384.30 | 19-MAR-08:62 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.96 |
April | 15080.67 | 30-APR-08:62 | 0.00 | 468.37 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 29.15 | 0.00 |
May | 15610.81 | 31-MAY-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.93 |
June | 15075.47 | 04-JUN-08:61 | 0.00 | 819.66 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 |
July | 14541.61 | 04-JUL-08:61 | 0.00 | 819.66 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 83.67 | 0.00 |
August | 14483.76 | 24-AUG-07:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.68 |
September | 14724.25 | 19-SEP-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.21 |
October | 15033.20 | 26-OCT-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.32 |
November | 15902.38 | 15-NOV-08:62 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.43 |
December | 17706.68 | 24-DEC-09:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.61 |
Annual Sum or Average | |||||||||||
Minimum of Months | 12730.22 | 0.00 | 468.37 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17706.68 | 0.00 | 819.66 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 83.67 | 110.32 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.109015E+12 | 100957.17 | 04-JAN-13:50 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.102026E+12 | 97661.59 | 21-FEB-14:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.112283E+12 | 96035.35 | 13-MAR-14:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.106771E+12 | 94666.12 | 24-APR-14:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.118205E+12 | 95467.95 | 18-MAY-15:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.116444E+12 | 96954.26 | 29-JUN-14:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.125333E+12 | 103837.86 | 15-JUL-14:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.129044E+12 | 113532.44 | 19-AUG-13:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.124233E+12 | 110341.78 | 03-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.127322E+12 | 108862.09 | 14-OCT-12:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.116207E+12 | 102455.65 | 06-NOV-14:20 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.114577E+12 | 97027.52 | 12-DEC-13:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.140146E+13 | 0.00 | ||||
Minimum of Months | 0.102026E+12 | 94666.12 | 0.00 | 0.00 | ||
Maximum of Months | 0.129044E+12 | 113532.44 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.465742E+11 | 0.872381E+10 | 0.108325E+11 | 0.00 | 0.778209E+10 | 0.00 | 0.00 | 0.300891E+11 | 0.00 | 0.00 | 0.00 | 0.501374E+10 | 0.00 |
February | 0.421675E+11 | 0.756457E+10 | 0.980803E+10 | 0.00 | 0.715968E+10 | 0.00 | 0.00 | 0.307931E+11 | 0.00 | 0.00 | 0.00 | 0.453348E+10 | 0.00 |
March | 0.472558E+11 | 0.791606E+10 | 0.110038E+11 | 0.00 | 0.791569E+10 | 0.00 | 0.00 | 0.331662E+11 | 0.00 | 0.00 | 0.00 | 0.502513E+10 | 0.00 |
April | 0.451947E+11 | 0.718145E+10 | 0.105115E+11 | 0.00 | 0.750413E+10 | 0.00 | 0.00 | 0.315623E+11 | 0.00 | 0.00 | 0.00 | 0.481642E+10 | 0.00 |
May | 0.468973E+11 | 0.702796E+10 | 0.109147E+11 | 0.00 | 0.805116E+10 | 0.00 | 0.00 | 0.403579E+11 | 0.00 | 0.00 | 0.00 | 0.495612E+10 | 0.00 |
June | 0.456793E+11 | 0.661476E+10 | 0.106349E+11 | 0.00 | 0.789425E+10 | 0.00 | 0.00 | 0.408333E+11 | 0.00 | 0.00 | 0.00 | 0.478700E+10 | 0.00 |
July | 0.464483E+11 | 0.688840E+10 | 0.107982E+11 | 0.00 | 0.874140E+10 | 0.00 | 0.00 | 0.475523E+11 | 0.00 | 0.00 | 0.00 | 0.490448E+10 | 0.00 |
August | 0.472203E+11 | 0.725210E+10 | 0.109970E+11 | 0.00 | 0.908325E+10 | 0.00 | 0.00 | 0.495477E+11 | 0.00 | 0.00 | 0.00 | 0.494392E+10 | 0.00 |
September | 0.452303E+11 | 0.746480E+10 | 0.105184E+11 | 0.00 | 0.874931E+10 | 0.00 | 0.00 | 0.474901E+11 | 0.00 | 0.00 | 0.00 | 0.477993E+10 | 0.00 |
October | 0.465742E+11 | 0.817403E+10 | 0.108325E+11 | 0.00 | 0.895284E+10 | 0.00 | 0.00 | 0.478305E+11 | 0.00 | 0.00 | 0.00 | 0.495840E+10 | 0.00 |
November | 0.451236E+11 | 0.833176E+10 | 0.104978E+11 | 0.00 | 0.795492E+10 | 0.00 | 0.00 | 0.394719E+11 | 0.00 | 0.00 | 0.00 | 0.482673E+10 | 0.00 |
December | 0.464839E+11 | 0.883376E+10 | 0.108050E+11 | 0.00 | 0.791201E+10 | 0.00 | 0.00 | 0.355403E+11 | 0.00 | 0.00 | 0.00 | 0.500231E+10 | 0.00 |
Annual Sum or Average | 0.550849E+12 | 0.919735E+11 | 0.128154E+12 | 0.977007E+11 | 0.00 | 0.474235E+12 | 0.585477E+11 | ||||||
Minimum of Months | 0.421675E+11 | 0.661476E+10 | 0.980803E+10 | 0.00 | 0.715968E+10 | 0.00 | 0.00 | 0.300891E+11 | 0.00 | 0.00 | 0.00 | 0.453348E+10 | 0.00 |
Maximum of Months | 0.472558E+11 | 0.883376E+10 | 0.110038E+11 | 0.00 | 0.908325E+10 | 0.00 | 0.00 | 0.495477E+11 | 0.00 | 0.00 | 0.00 | 0.502513E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 34106.38 | 01-JAN-11:09 | 7048.42 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 7105.68 | 02-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 34106.38 | 01-FEB-10:09 | 7048.42 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 7368.16 | 19-FEB-13:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 34106.38 | 01-MAR-10:09 | 7048.42 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 7075.17 | 13-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 34106.38 | 01-APR-09:09 | 7048.42 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 6400.58 | 20-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 34106.38 | 01-MAY-09:09 | 7048.42 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 7150.02 | 10-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 34106.38 | 01-JUN-09:09 | 7048.42 | 01-JUN-05:10 | 8059.50 | 01-JUN-09:09 | 0.00 | 7150.02 | 26-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 34106.38 | 01-JUL-09:09 | 7048.42 | 01-JUL-05:10 | 8059.50 | 01-JUL-09:09 | 0.00 | 8274.12 | 15-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 34106.38 | 01-AUG-09:09 | 7048.42 | 01-AUG-05:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 9248.10 | 19-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 34106.38 | 01-SEP-09:09 | 7048.42 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 9396.42 | 03-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 34106.38 | 01-OCT-10:09 | 7048.42 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 9140.94 | 14-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 34106.38 | 01-NOV-09:09 | 7048.42 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 8111.87 | 06-NOV-13:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 34106.38 | 01-DEC-10:09 | 7048.42 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 7397.54 | 13-DEC-13:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 34106.38 | 7048.42 | 8059.50 | 0.00 | 6400.58 | 0.00 | 0.00 | |||||
Maximum of Months | 34106.38 | 7048.42 | 8059.50 | 0.00 | 9396.42 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 40642.75 | 01-JAN-13:39 | 0.00 | 0.00 | 0.00 | 11786.11 | 06-JAN-13:09 | 0.00 |
February | 43025.40 | 19-FEB-13:00 | 0.00 | 0.00 | 0.00 | 9666.89 | 03-FEB-14:20 | 0.00 |
March | 41517.30 | 13-MAR-14:09 | 0.00 | 0.00 | 0.00 | 9666.20 | 16-MAR-12:20 | 0.00 |
April | 38173.27 | 24-APR-13:00 | 0.00 | 0.00 | 0.00 | 9647.08 | 18-APR-11:30 | 0.00 |
May | 43161.99 | 13-MAY-13:00 | 0.00 | 0.00 | 0.00 | 9610.35 | 22-MAY-19:10 | 0.00 |
June | 41921.19 | 29-JUN-12:00 | 0.00 | 0.00 | 0.00 | 9643.54 | 02-JUN-11:20 | 0.00 |
July | 48887.37 | 15-JUL-13:00 | 0.00 | 0.00 | 0.00 | 10584.84 | 12-JUL-16:19 | 0.00 |
August | 53411.46 | 19-AUG-14:00 | 0.00 | 0.00 | 0.00 | 9654.47 | 19-AUG-13:30 | 0.00 |
September | 55023.40 | 03-SEP-12:00 | 0.00 | 0.00 | 0.00 | 9642.79 | 06-SEP-14:39 | 0.00 |
October | 53035.09 | 15-OCT-12:00 | 0.00 | 0.00 | 0.00 | 7550.43 | 24-OCT-12:50 | 0.00 |
November | 47315.60 | 06-NOV-13:00 | 0.00 | 0.00 | 0.00 | 7553.09 | 10-NOV-13:50 | 0.00 |
December | 44102.27 | 13-DEC-13:00 | 0.00 | 0.00 | 0.00 | 7551.60 | 06-DEC-14:30 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 38173.27 | 0.00 | 0.00 | 0.00 | 7550.43 | 0.00 | ||
Maximum of Months | 55023.40 | 0.00 | 0.00 | 0.00 | 11786.11 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 100957.17 | 04-JAN-13:50 | 34106.38 | 8059.50 | 0.00 | 0.00 | 6736.17 | 0.00 | 0.00 | 40271.84 | 0.00 |
February | 97661.59 | 21-FEB-14:00 | 34106.38 | 8059.50 | 0.00 | 0.00 | 6888.27 | 0.00 | 0.00 | 40632.07 | 0.00 |
March | 96035.35 | 13-MAR-14:30 | 34106.38 | 8059.50 | 0.00 | 0.00 | 7002.15 | 0.00 | 0.00 | 41437.31 | 0.00 |
April | 94666.12 | 24-APR-14:20 | 34106.38 | 8059.50 | 0.00 | 0.00 | 6119.52 | 0.00 | 0.00 | 37700.94 | 0.00 |
May | 95467.95 | 18-MAY-15:09 | 34106.38 | 8059.50 | 0.00 | 0.00 | 6712.39 | 0.00 | 0.00 | 41168.88 | 0.00 |
June | 96954.26 | 29-JUN-14:20 | 34106.38 | 8059.50 | 0.00 | 0.00 | 6627.24 | 0.00 | 0.00 | 40630.56 | 0.00 |
July | 103837.86 | 15-JUL-14:20 | 34106.38 | 8059.50 | 0.00 | 0.00 | 8131.57 | 0.00 | 0.00 | 48117.25 | 0.00 |
August | 113532.44 | 19-AUG-13:30 | 34106.38 | 8059.50 | 0.00 | 0.00 | 9080.28 | 0.00 | 0.00 | 52631.81 | 0.00 |
September | 110341.78 | 03-SEP-12:00 | 34106.38 | 8059.50 | 0.00 | 0.00 | 9396.42 | 0.00 | 0.00 | 55023.40 | 0.00 |
October | 108862.09 | 14-OCT-12:30 | 34106.38 | 8059.50 | 0.00 | 0.00 | 9052.88 | 0.00 | 0.00 | 52207.79 | 0.00 |
November | 102455.65 | 06-NOV-14:20 | 34106.38 | 8059.50 | 0.00 | 0.00 | 7947.93 | 0.00 | 0.00 | 46465.91 | 0.00 |
December | 97027.52 | 12-DEC-13:50 | 34106.38 | 8059.50 | 0.00 | 0.00 | 7074.15 | 0.00 | 0.00 | 42097.38 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 94666.12 | 34106.38 | 8059.50 | 0.00 | 0.00 | 6119.52 | 0.00 | 0.00 | 37700.94 | 0.00 | |
Maximum of Months | 113532.44 | 34106.38 | 8059.50 | 0.00 | 0.00 | 9396.42 | 0.00 | 0.00 | 55023.40 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.49 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.49 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.67 | 24.49 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.49 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.50 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.55 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.67 | 24.53 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.55 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.49 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.67 | 24.48 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.49 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.58 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.50 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.58 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 24.55 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.58 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.53 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.54 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.83 | 24.52 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.54 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.52 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.53 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.67 | 24.53 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.53 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.50 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.52 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.67 | 24.51 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.52 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.66 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.57 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.53 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.33 | 24.56 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.66 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 23.84 | 477.50 | 23.89 | 0.33 | 23.91 |
February | 32.50 | 23.88 | 438.17 | 23.89 | 31.50 | 23.89 |
March | 9.17 | 23.88 | 481.83 | 23.89 | 9.00 | 23.89 |
April | 0.00 | 0.00 | 474.83 | 23.89 | 0.00 | 0.00 |
May | 1.83 | 23.93 | 495.83 | 23.89 | 1.83 | 23.93 |
June | 0.67 | 24.11 | 480.00 | 23.89 | 0.67 | 24.11 |
July | 9.17 | 23.96 | 496.00 | 23.89 | 9.17 | 23.96 |
August | 3.67 | 24.07 | 496.00 | 23.89 | 3.67 | 24.07 |
September | 12.50 | 23.94 | 480.00 | 23.89 | 12.50 | 23.94 |
October | 0.50 | 24.09 | 496.00 | 23.89 | 0.50 | 24.09 |
November | 3.33 | 23.99 | 479.67 | 23.89 | 3.33 | 23.99 |
December | 2.00 | 23.96 | 493.50 | 23.89 | 2.00 | 23.96 |
Annual Sum or Average | 76.00 | 23.92 | 5789.33 | 23.89 | 74.50 | 23.93 |
Minimum of Months | 0.00 | 0.00 | 438.17 | 23.89 | 0.00 | 0.00 |
Maximum of Months | 32.50 | 24.11 | 496.00 | 23.89 | 31.50 | 24.11 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 23.78 | 466.67 | 23.89 | 0.00 | 0.00 |
February | 23.67 | 23.88 | 429.33 | 23.89 | 22.83 | 23.89 |
March | 6.83 | 23.88 | 467.33 | 23.89 | 6.33 | 23.89 |
April | 0.00 | 0.00 | 464.00 | 23.89 | 0.00 | 0.00 |
May | 0.17 | 23.89 | 495.00 | 23.89 | 0.17 | 23.89 |
June | 0.00 | 0.00 | 480.00 | 23.89 | 0.00 | 0.00 |
July | 3.67 | 23.90 | 496.00 | 23.89 | 3.67 | 23.90 |
August | 0.00 | 0.00 | 496.00 | 23.89 | 0.00 | 0.00 |
September | 5.83 | 23.89 | 480.00 | 23.89 | 5.83 | 23.89 |
October | 0.17 | 23.89 | 495.83 | 23.89 | 0.17 | 23.89 |
November | 0.00 | 0.00 | 477.50 | 23.89 | 0.00 | 0.00 |
December | 0.17 | 24.35 | 486.17 | 23.89 | 0.17 | 24.35 |
Annual Sum or Average | 40.83 | 23.88 | 5733.83 | 23.89 | 39.17 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 429.33 | 23.89 | 0.00 | 0.00 |
Maximum of Months | 23.67 | 24.35 | 496.00 | 23.89 | 22.83 | 24.35 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 25.24 | 365.33 | 24.02 | 1.83 | 25.24 |
February | 38.33 | 24.24 | 331.50 | 24.03 | 38.33 | 24.24 |
March | 9.00 | 24.28 | 374.17 | 24.03 | 9.00 | 24.28 |
April | 1.17 | 25.81 | 359.33 | 24.04 | 1.17 | 25.81 |
May | 3.33 | 26.07 | 375.00 | 24.06 | 3.33 | 26.07 |
June | 1.67 | 27.46 | 366.00 | 24.07 | 1.67 | 27.46 |
July | 11.17 | 25.73 | 369.00 | 24.10 | 11.17 | 25.73 |
August | 4.67 | 27.57 | 379.00 | 24.09 | 4.67 | 27.57 |
September | 16.33 | 25.57 | 360.00 | 24.10 | 16.33 | 25.57 |
October | 7.00 | 26.37 | 371.00 | 24.08 | 7.00 | 26.37 |
November | 2.00 | 26.75 | 360.00 | 24.05 | 2.00 | 26.75 |
December | 3.17 | 25.95 | 369.00 | 24.03 | 3.17 | 25.95 |
Annual Sum or Average | 99.67 | 25.19 | 4379.33 | 24.06 | 99.67 | 25.19 |
Minimum of Months | 1.17 | 24.24 | 331.50 | 24.02 | 1.17 | 24.24 |
Maximum of Months | 38.33 | 27.57 | 379.00 | 24.10 | 38.33 | 27.57 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 25.12 | 364.83 | 24.02 | 2.00 | 25.12 |
February | 39.17 | 24.24 | 331.33 | 24.03 | 39.17 | 24.24 |
March | 9.17 | 24.30 | 374.17 | 24.03 | 9.17 | 24.30 |
April | 1.33 | 25.99 | 359.00 | 24.04 | 1.33 | 25.99 |
May | 3.33 | 26.07 | 375.00 | 24.06 | 3.33 | 26.07 |
June | 1.67 | 27.47 | 366.00 | 24.07 | 1.67 | 27.47 |
July | 11.33 | 25.70 | 369.00 | 24.10 | 11.33 | 25.70 |
August | 4.67 | 27.57 | 379.00 | 24.09 | 4.67 | 27.57 |
September | 16.33 | 25.57 | 360.00 | 24.10 | 16.33 | 25.57 |
October | 7.00 | 26.46 | 371.00 | 24.08 | 7.00 | 26.46 |
November | 2.17 | 26.53 | 360.00 | 24.05 | 2.17 | 26.53 |
December | 3.17 | 25.94 | 369.00 | 24.03 | 3.17 | 25.94 |
Annual Sum or Average | 101.33 | 25.19 | 4378.33 | 24.06 | 101.33 | 25.19 |
Minimum of Months | 1.33 | 24.24 | 331.33 | 24.02 | 1.33 | 24.24 |
Maximum of Months | 39.17 | 27.57 | 379.00 | 24.10 | 39.17 | 27.57 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 24.99 | 363.83 | 24.01 | 2.17 | 24.99 |
February | 42.67 | 24.22 | 330.83 | 24.02 | 42.67 | 24.22 |
March | 10.17 | 24.28 | 373.50 | 24.02 | 10.17 | 24.28 |
April | 1.33 | 25.53 | 358.67 | 24.03 | 1.33 | 25.53 |
May | 3.67 | 25.77 | 375.00 | 24.05 | 3.67 | 25.77 |
June | 1.67 | 27.41 | 366.00 | 24.06 | 1.67 | 27.41 |
July | 12.50 | 25.55 | 369.00 | 24.09 | 12.50 | 25.55 |
August | 5.17 | 27.25 | 379.00 | 24.08 | 5.17 | 27.25 |
September | 17.67 | 25.41 | 360.00 | 24.09 | 17.67 | 25.41 |
October | 7.33 | 26.27 | 371.00 | 24.08 | 7.33 | 26.27 |
November | 2.33 | 26.29 | 360.00 | 24.04 | 2.33 | 26.29 |
December | 5.00 | 25.37 | 368.83 | 24.03 | 5.00 | 25.37 |
Annual Sum or Average | 111.67 | 25.06 | 4375.67 | 24.05 | 111.67 | 25.06 |
Minimum of Months | 1.33 | 24.22 | 330.83 | 24.01 | 1.33 | 24.22 |
Maximum of Months | 42.67 | 27.41 | 379.00 | 24.09 | 42.67 | 27.41 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 25.15 | 326.67 | 23.93 | 1.67 | 25.15 |
February | 51.67 | 24.05 | 300.00 | 23.94 | 51.67 | 24.05 |
March | 14.83 | 24.12 | 338.67 | 23.93 | 14.83 | 24.12 |
April | 1.17 | 25.45 | 326.50 | 23.95 | 1.17 | 25.45 |
May | 4.67 | 24.92 | 344.00 | 23.95 | 4.67 | 24.92 |
June | 0.83 | 27.34 | 336.00 | 23.95 | 0.83 | 27.34 |
July | 14.50 | 24.84 | 338.00 | 23.98 | 14.50 | 24.84 |
August | 4.17 | 27.02 | 348.00 | 23.95 | 4.17 | 27.02 |
September | 24.83 | 24.75 | 330.00 | 23.97 | 24.83 | 24.75 |
October | 7.17 | 25.90 | 340.00 | 23.97 | 7.17 | 25.90 |
November | 3.83 | 24.82 | 330.00 | 23.94 | 3.83 | 24.82 |
December | 7.83 | 24.77 | 334.50 | 23.94 | 7.83 | 24.77 |
Annual Sum or Average | 137.17 | 24.59 | 3992.33 | 23.95 | 137.17 | 24.59 |
Minimum of Months | 0.83 | 24.05 | 300.00 | 23.93 | 0.83 | 24.05 |
Maximum of Months | 51.67 | 27.34 | 348.00 | 23.98 | 51.67 | 27.34 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 25.07 | 319.17 | 23.93 | 2.00 | 25.07 |
February | 56.00 | 24.03 | 295.00 | 23.94 | 56.00 | 24.03 |
March | 16.50 | 24.11 | 335.17 | 23.93 | 16.50 | 24.11 |
April | 1.67 | 24.97 | 322.83 | 23.95 | 1.67 | 24.97 |
May | 5.00 | 24.89 | 344.00 | 23.95 | 5.00 | 24.89 |
June | 0.67 | 27.29 | 336.00 | 23.95 | 0.67 | 27.29 |
July | 16.17 | 24.65 | 338.00 | 23.98 | 16.17 | 24.65 |
August | 5.83 | 25.98 | 348.00 | 23.95 | 5.83 | 25.98 |
September | 28.67 | 24.60 | 330.00 | 23.97 | 28.67 | 24.60 |
October | 7.33 | 25.81 | 340.00 | 23.96 | 7.33 | 25.81 |
November | 4.50 | 24.66 | 330.00 | 23.94 | 4.50 | 24.66 |
December | 9.00 | 24.71 | 332.33 | 23.94 | 9.00 | 24.71 |
Annual Sum or Average | 153.33 | 24.49 | 3970.50 | 23.95 | 153.33 | 24.49 |
Minimum of Months | 0.67 | 24.03 | 295.00 | 23.93 | 0.67 | 24.03 |
Maximum of Months | 56.00 | 27.29 | 348.00 | 23.98 | 56.00 | 27.29 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 24.89 | 318.17 | 23.93 | 2.33 | 24.89 |
February | 57.50 | 24.02 | 294.50 | 23.94 | 57.50 | 24.02 |
March | 17.17 | 24.10 | 334.33 | 23.93 | 17.17 | 24.10 |
April | 1.67 | 24.96 | 322.00 | 23.95 | 1.67 | 24.96 |
May | 5.17 | 24.92 | 344.00 | 23.95 | 5.17 | 24.92 |
June | 0.83 | 27.13 | 336.00 | 23.95 | 0.83 | 27.13 |
July | 16.67 | 24.63 | 338.00 | 23.98 | 16.67 | 24.63 |
August | 6.67 | 25.71 | 348.00 | 23.95 | 6.67 | 25.71 |
September | 29.33 | 24.56 | 330.00 | 23.97 | 29.33 | 24.56 |
October | 7.67 | 25.71 | 340.00 | 23.96 | 7.67 | 25.71 |
November | 4.67 | 24.63 | 330.00 | 23.94 | 4.67 | 24.63 |
December | 9.33 | 24.69 | 331.83 | 23.94 | 9.33 | 24.69 |
Annual Sum or Average | 159.00 | 24.47 | 3966.83 | 23.95 | 159.00 | 24.47 |
Minimum of Months | 0.83 | 24.02 | 294.50 | 23.93 | 0.83 | 24.02 |
Maximum of Months | 57.50 | 27.13 | 348.00 | 23.98 | 57.50 | 27.13 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.00 | 24.65 | 318.17 | 23.93 | 3.00 | 24.65 |
February | 61.33 | 24.02 | 294.17 | 23.94 | 61.33 | 24.02 |
March | 18.83 | 24.08 | 333.83 | 23.93 | 18.67 | 24.08 |
April | 2.00 | 24.77 | 322.17 | 23.94 | 2.00 | 24.77 |
May | 5.50 | 24.86 | 344.00 | 23.95 | 5.50 | 24.86 |
June | 0.83 | 27.12 | 336.00 | 23.95 | 0.83 | 27.12 |
July | 16.83 | 24.62 | 338.00 | 23.98 | 16.83 | 24.62 |
August | 6.50 | 25.76 | 348.00 | 23.95 | 6.50 | 25.76 |
September | 30.17 | 24.54 | 330.00 | 23.97 | 30.17 | 24.54 |
October | 7.67 | 25.71 | 340.00 | 23.96 | 7.67 | 25.71 |
November | 4.83 | 24.60 | 330.00 | 23.94 | 4.83 | 24.60 |
December | 10.00 | 24.67 | 331.83 | 23.94 | 10.00 | 24.67 |
Annual Sum or Average | 167.50 | 24.44 | 3966.17 | 23.95 | 167.33 | 24.45 |
Minimum of Months | 0.83 | 24.02 | 294.17 | 23.93 | 0.83 | 24.02 |
Maximum of Months | 61.33 | 27.12 | 348.00 | 23.98 | 61.33 | 27.12 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 24.82 | 324.00 | 23.93 | 2.67 | 24.82 |
February | 59.17 | 24.03 | 297.00 | 23.94 | 59.00 | 24.03 |
March | 19.83 | 24.11 | 337.17 | 23.94 | 19.33 | 24.12 |
April | 1.17 | 25.73 | 326.50 | 23.95 | 1.17 | 25.73 |
May | 5.67 | 24.99 | 344.00 | 23.95 | 5.67 | 24.99 |
June | 2.00 | 26.52 | 336.00 | 23.95 | 2.00 | 26.52 |
July | 14.00 | 25.18 | 338.00 | 23.98 | 14.00 | 25.18 |
August | 5.50 | 26.74 | 348.00 | 23.96 | 5.50 | 26.74 |
September | 25.17 | 24.83 | 330.00 | 23.98 | 25.17 | 24.83 |
October | 7.83 | 26.06 | 340.00 | 23.97 | 7.83 | 26.06 |
November | 5.33 | 24.69 | 330.00 | 23.94 | 5.33 | 24.69 |
December | 8.67 | 24.82 | 332.83 | 23.94 | 8.67 | 24.82 |
Annual Sum or Average | 157.00 | 24.63 | 3983.50 | 23.95 | 156.33 | 24.63 |
Minimum of Months | 1.17 | 24.03 | 297.00 | 23.93 | 1.17 | 24.03 |
Maximum of Months | 59.17 | 26.74 | 348.00 | 23.98 | 59.00 | 26.74 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.89601 | 50.31129 | 0.55036 | 11.43450 |
February | 448.00000 | 23.89402 | 54.95327 | 0.58610 | 12.31603 |
March | 496.00000 | 23.89427 | 51.80790 | 0.56358 | 11.75195 |
April | 480.00000 | 23.89602 | 50.88562 | 0.55679 | 11.55576 |
May | 496.00000 | 23.90164 | 53.25092 | -0.2515 | 6.40974 |
June | 480.00000 | 23.90428 | 53.63789 | -0.2351 | 6.23507 |
July | 496.00000 | 23.90660 | 54.84906 | -0.2092 | 6.00519 |
August | 496.00000 | 23.90683 | 54.79460 | -0.2078 | 5.99300 |
September | 480.00000 | 23.90490 | 56.03347 | -0.1903 | 5.86580 |
October | 496.00000 | 23.90286 | 55.25043 | 0.62589 | 13.28390 |
November | 480.00000 | 23.90423 | 54.16160 | 0.60682 | 12.79671 |
December | 496.00000 | 23.90060 | 52.78386 | 0.58326 | 12.22391 |
Annual Sum or Average | 5840.00000 | 23.90107 | 53.54723 | 0.24617 | 9.64005 |
Minimum of Months | 448.00000 | 23.89402 | 50.31129 | -0.2515 | 5.86580 |
Maximum of Months | 496.00000 | 23.90683 | 56.03347 | 0.62589 | 13.28390 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.89821 | 48.47213 | 0.53298 | 11.03959 |
February | 448.00000 | 23.89649 | 52.74322 | 0.56256 | 11.75620 |
March | 496.00000 | 23.89640 | 50.00901 | 0.54147 | 11.23987 |
April | 480.00000 | 23.89783 | 49.17779 | 0.53473 | 11.05572 |
May | 496.00000 | 23.90325 | 51.58398 | -0.2824 | 6.75743 |
June | 480.00000 | 23.90519 | 52.14181 | -0.2690 | 6.59675 |
July | 496.00000 | 23.90716 | 53.34755 | -0.2470 | 6.37028 |
August | 496.00000 | 23.90702 | 53.37676 | -0.2467 | 6.36377 |
September | 480.00000 | 23.90517 | 54.63325 | -0.2320 | 6.23267 |
October | 496.00000 | 23.90395 | 53.50050 | 0.59820 | 12.57779 |
November | 480.00000 | 23.90554 | 52.35057 | 0.58151 | 12.16933 |
December | 496.00000 | 23.90214 | 50.88711 | 0.56183 | 11.71139 |
Annual Sum or Average | 5840.00000 | 23.90240 | 51.84219 | 0.21759 | 9.47581 |
Minimum of Months | 448.00000 | 23.89640 | 48.47213 | -0.2824 | 6.23267 |
Maximum of Months | 496.00000 | 23.90716 | 54.63325 | 0.59820 | 12.57779 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.98988 | 50.41649 | 0.56906 | 11.90618 |
February | 336.00000 | 23.99585 | 55.39965 | 0.60414 | 12.82295 |
March | 379.00000 | 23.99824 | 52.19130 | 0.57827 | 12.15604 |
April | 360.00000 | 24.00448 | 51.20753 | 0.57114 | 11.96123 |
May | 375.00000 | 24.02197 | 53.49913 | -0.2324 | 6.40016 |
June | 366.00000 | 24.02734 | 54.02931 | -0.2185 | 6.26959 |
July | 369.00000 | 24.05025 | 55.15488 | -0.1895 | 6.13107 |
August | 379.00000 | 24.04478 | 55.04944 | -0.1922 | 6.13814 |
September | 360.00000 | 24.05191 | 56.54443 | -0.1738 | 6.06860 |
October | 371.00000 | 24.04077 | 55.51349 | 0.64583 | 13.95655 |
November | 360.00000 | 24.01408 | 54.41418 | 0.62348 | 13.29221 |
December | 369.00000 | 24.00251 | 52.98591 | 0.60147 | 12.72836 |
Annual Sum or Average | 4395.00000 | 24.02033 | 53.85192 | 0.26220 | 9.95833 |
Minimum of Months | 336.00000 | 23.98988 | 50.41649 | -0.2324 | 6.06860 |
Maximum of Months | 379.00000 | 24.05191 | 56.54443 | 0.64583 | 13.95655 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.98914 | 50.45823 | 0.56830 | 11.88744 |
February | 336.00000 | 23.99514 | 55.44360 | 0.60355 | 12.80738 |
March | 379.00000 | 23.99760 | 52.22032 | 0.57776 | 12.14282 |
April | 360.00000 | 24.00387 | 51.23945 | 0.57054 | 11.94597 |
May | 375.00000 | 24.02164 | 53.50526 | -0.2325 | 6.40041 |
June | 366.00000 | 24.02708 | 54.02924 | -0.2184 | 6.26826 |
July | 369.00000 | 24.05018 | 55.12969 | -0.1888 | 6.12594 |
August | 379.00000 | 24.04467 | 55.02970 | -0.1916 | 6.13368 |
September | 360.00000 | 24.05192 | 56.50425 | -0.1728 | 6.06309 |
October | 371.00000 | 24.04073 | 55.48262 | 0.64633 | 13.97085 |
November | 360.00000 | 24.01371 | 54.42697 | 0.62337 | 13.28909 |
December | 369.00000 | 24.00200 | 53.01250 | 0.60108 | 12.71804 |
Annual Sum or Average | 4395.00000 | 24.01997 | 53.85801 | 0.26220 | 9.95190 |
Minimum of Months | 336.00000 | 23.98914 | 50.45823 | -0.2325 | 6.06309 |
Maximum of Months | 379.00000 | 24.05192 | 56.50425 | 0.64633 | 13.97085 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.98558 | 50.69815 | 0.56441 | 11.79063 |
February | 336.00000 | 23.99143 | 55.75798 | 0.60005 | 12.71453 |
March | 379.00000 | 23.99390 | 52.48879 | 0.57380 | 12.04248 |
April | 360.00000 | 24.00041 | 51.49239 | 0.56652 | 11.84431 |
May | 375.00000 | 24.01847 | 53.73337 | -0.2380 | 6.44237 |
June | 366.00000 | 24.02400 | 54.25092 | -0.2237 | 6.30329 |
July | 369.00000 | 24.04717 | 55.33273 | -0.1937 | 6.14959 |
August | 379.00000 | 24.04163 | 55.24364 | -0.1967 | 6.15957 |
September | 360.00000 | 24.04893 | 56.72658 | -0.1775 | 6.08201 |
October | 371.00000 | 24.03769 | 55.70390 | 0.64321 | 13.87829 |
November | 360.00000 | 24.01053 | 54.65801 | 0.62016 | 13.19872 |
December | 369.00000 | 23.99869 | 53.25524 | 0.59765 | 12.62640 |
Annual Sum or Average | 4395.00000 | 24.01670 | 54.09578 | 0.25797 | 9.90901 |
Minimum of Months | 336.00000 | 23.98558 | 50.69815 | -0.2380 | 6.08201 |
Maximum of Months | 379.00000 | 24.04893 | 56.72658 | 0.64321 | 13.87829 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.92146 | 51.93351 | 0.54514 | 11.31667 |
February | 308.00000 | 23.92660 | 57.18642 | 0.58273 | 12.24621 |
March | 348.00000 | 23.92210 | 53.76549 | 0.55408 | 11.53449 |
April | 330.00000 | 23.93330 | 52.70570 | 0.54605 | 11.32618 |
May | 344.00000 | 23.93652 | 54.91564 | -0.2703 | 6.68367 |
June | 336.00000 | 23.93419 | 55.50959 | -0.2564 | 6.51080 |
July | 338.00000 | 23.95772 | 56.53240 | -0.2241 | 6.27764 |
August | 348.00000 | 23.93929 | 56.38396 | -0.2313 | 6.31021 |
September | 330.00000 | 23.95471 | 57.94631 | -0.2072 | 6.17337 |
October | 340.00000 | 23.94879 | 56.76179 | 0.62360 | 13.28865 |
November | 330.00000 | 23.92989 | 55.91085 | 0.60054 | 12.64507 |
December | 338.00000 | 23.92854 | 54.54973 | 0.57861 | 12.11771 |
Annual Sum or Average | 4030.00000 | 23.93612 | 55.32395 | 0.23322 | 9.67736 |
Minimum of Months | 308.00000 | 23.92146 | 51.93351 | -0.2703 | 6.17337 |
Maximum of Months | 348.00000 | 23.95772 | 57.94631 | 0.62360 | 13.28865 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.92075 | 52.10811 | 0.52849 | 10.93645 |
February | 308.00000 | 23.92584 | 57.44317 | 0.56623 | 11.84412 |
March | 348.00000 | 23.92150 | 53.95886 | 0.53715 | 11.14112 |
April | 330.00000 | 23.93259 | 52.87195 | 0.52910 | 10.93969 |
May | 344.00000 | 23.93585 | 55.10872 | -0.2966 | 6.99056 |
June | 336.00000 | 23.93355 | 55.71102 | -0.2837 | 6.81303 |
July | 338.00000 | 23.95695 | 56.73203 | -0.2527 | 6.55717 |
August | 348.00000 | 23.93845 | 56.56746 | -0.2599 | 6.59642 |
September | 330.00000 | 23.95388 | 58.18325 | -0.2360 | 6.43200 |
October | 340.00000 | 23.94810 | 56.96778 | 0.60386 | 12.77371 |
November | 330.00000 | 23.92920 | 56.12969 | 0.58207 | 12.17986 |
December | 338.00000 | 23.92769 | 54.76309 | 0.56113 | 11.69394 |
Annual Sum or Average | 4030.00000 | 23.93539 | 55.52708 | 0.21131 | 9.55259 |
Minimum of Months | 308.00000 | 23.92075 | 52.10811 | -0.2966 | 6.43200 |
Maximum of Months | 348.00000 | 23.95695 | 58.18325 | 0.60386 | 12.77371 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.92038 | 52.18598 | 0.52663 | 10.89457 |
February | 308.00000 | 23.92545 | 57.54768 | 0.56447 | 11.80190 |
March | 348.00000 | 23.92118 | 54.04059 | 0.53532 | 11.09898 |
April | 330.00000 | 23.93224 | 52.94312 | 0.52734 | 10.89980 |
May | 344.00000 | 23.93558 | 55.17247 | -0.2992 | 7.02092 |
June | 336.00000 | 23.93330 | 55.77542 | -0.2862 | 6.84161 |
July | 338.00000 | 23.95662 | 56.78906 | -0.2552 | 6.58146 |
August | 348.00000 | 23.93821 | 56.62040 | -0.2623 | 6.62093 |
September | 330.00000 | 23.95357 | 58.24759 | -0.2385 | 6.45390 |
October | 340.00000 | 23.94780 | 57.02764 | 0.60221 | 12.73042 |
November | 330.00000 | 23.92890 | 56.20507 | 0.58035 | 12.13673 |
December | 338.00000 | 23.92729 | 54.84296 | 0.55934 | 11.65113 |
Annual Sum or Average | 4030.00000 | 23.93507 | 55.59788 | 0.20923 | 9.53907 |
Minimum of Months | 308.00000 | 23.92038 | 52.18598 | -0.2992 | 6.45390 |
Maximum of Months | 348.00000 | 23.95662 | 58.24759 | 0.60221 | 12.73042 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.91990 | 52.31206 | 0.52703 | 10.90398 |
February | 308.00000 | 23.92491 | 57.72871 | 0.56475 | 11.80961 |
March | 348.00000 | 23.92060 | 54.18086 | 0.53571 | 11.10921 |
April | 330.00000 | 23.93188 | 53.03288 | 0.52840 | 10.92352 |
May | 344.00000 | 23.93539 | 55.20642 | -0.2966 | 6.98844 |
June | 336.00000 | 23.93315 | 55.80092 | -0.2834 | 6.80784 |
July | 338.00000 | 23.95652 | 56.78521 | -0.2517 | 6.54434 |
August | 348.00000 | 23.93822 | 56.60173 | -0.2584 | 6.57950 |
September | 330.00000 | 23.95348 | 58.25882 | -0.2353 | 6.42391 |
October | 340.00000 | 23.94769 | 57.03955 | 0.60452 | 12.78990 |
November | 330.00000 | 23.92862 | 56.28033 | 0.58163 | 12.16840 |
December | 338.00000 | 23.92686 | 54.94647 | 0.56019 | 11.67167 |
Annual Sum or Average | 4030.00000 | 23.93480 | 55.66167 | 0.21114 | 9.53788 |
Minimum of Months | 308.00000 | 23.91990 | 52.31206 | -0.2966 | 6.42391 |
Maximum of Months | 348.00000 | 23.95652 | 58.25882 | 0.60452 | 12.78990 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.92206 | 51.99299 | 0.54905 | 11.41960 |
February | 308.00000 | 23.92719 | 57.56052 | 0.58354 | 12.28130 |
March | 348.00000 | 23.92256 | 54.05095 | 0.55851 | 11.65245 |
April | 330.00000 | 23.93572 | 52.47868 | 0.55751 | 11.60259 |
May | 344.00000 | 23.93963 | 54.32413 | -0.2444 | 6.42926 |
June | 336.00000 | 23.93692 | 54.92482 | -0.2312 | 6.27771 |
July | 338.00000 | 23.96249 | 55.83694 | -0.1929 | 6.04048 |
August | 348.00000 | 23.94301 | 55.52342 | -0.1957 | 6.03243 |
September | 330.00000 | 23.95920 | 57.54424 | -0.1829 | 6.01967 |
October | 340.00000 | 23.95300 | 56.10106 | 0.64295 | 13.82938 |
November | 330.00000 | 23.93158 | 55.79384 | 0.60821 | 12.85422 |
December | 338.00000 | 23.92939 | 54.51335 | 0.58324 | 12.24244 |
Annual Sum or Average | 4030.00000 | 23.93860 | 55.03044 | 0.24958 | 9.69714 |
Minimum of Months | 308.00000 | 23.92206 | 51.99299 | -0.2444 | 6.01967 |
Maximum of Months | 348.00000 | 23.96249 | 57.56052 | 0.64295 | 13.82938 |
Report: DXReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.253538E+11 | 0.622767E+10 | 494.62 | 0.175468E+11 | 0.780701E+10 | 0.00 | 1.00 | 01-JAN-08:62 | 0.00 | 01-JAN-00:05 | 49730.85 | 31-JAN-08:62 | 37457.70 | 21-JAN-08:62 | 20444.97 | 31-JAN-08:62 | 10784.88 | 02-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.269437E+11 | 0.643916E+10 | 447.70 | 0.168324E+11 | 0.101113E+11 | 0.00 | 1.00 | 03-FEB-08:62 | 0.00 | 01-FEB-00:05 | 51465.37 | 17-FEB-08:62 | 32508.61 | 13-FEB-08:62 | 26115.37 | 17-FEB-08:03 | 10984.10 | 18-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.282279E+11 | 0.688136E+10 | 494.94 | 0.191509E+11 | 0.907699E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 50209.19 | 03-MAR-08:62 | 34108.78 | 19-MAR-07:02 | 23154.77 | 03-MAR-08:62 | 10753.42 | 15-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.269309E+11 | 0.662918E+10 | 480.17 | 0.187873E+11 | 0.814358E+10 | 0.00 | 1.00 | 05-APR-07:02 | 0.00 | 01-APR-00:05 | 49154.11 | 25-APR-07:02 | 35500.93 | 06-APR-07:02 | 17721.64 | 18-APR-07:02 | 10822.48 | 25-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.341366E+11 | 0.830608E+10 | 497.13 | 0.229686E+11 | 0.111680E+11 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 50493.79 | 10-MAY-07:02 | 35740.23 | 02-MAY-07:02 | 22138.02 | 10-MAY-07:03 | 11002.25 | 09-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.347307E+11 | 0.840776E+10 | 484.83 | 0.232292E+11 | 0.115015E+11 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 50075.29 | 14-JUN-07:02 | 33880.16 | 04-JUN-07:01 | 20314.40 | 14-JUN-07:03 | 11189.93 | 21-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.405988E+11 | 0.985500E+10 | 502.89 | 0.267674E+11 | 0.138313E+11 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 51453.62 | 20-JUL-07:01 | 33166.18 | 08-JUL-07:02 | 24631.09 | 20-JUL-07:04 | 11205.06 | 20-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.412058E+11 | 0.100742E+11 | 501.09 | 0.273660E+11 | 0.138398E+11 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 50704.30 | 08-AUG-07:01 | 32655.86 | 24-AUG-07:02 | 22127.84 | 08-AUG-07:04 | 11154.55 | 27-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.414529E+11 | 0.995422E+10 | 487.07 | 0.264502E+11 | 0.150027E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 51084.98 | 30-SEP-07:02 | 32525.70 | 19-SEP-07:02 | 24033.33 | 30-SEP-07:03 | 11303.72 | 03-SEP-07:01 | 0.00 | 01-SEP-00:10 |
October | 0.402688E+11 | 0.977721E+10 | 499.09 | 0.262957E+11 | 0.139731E+11 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:03 | 50388.48 | 13-OCT-07:01 | 33163.21 | 26-OCT-07:02 | 21005.25 | 13-OCT-07:03 | 11111.45 | 07-OCT-07:01 | 0.00 | 01-OCT-00:03 |
November | 0.336379E+11 | 0.810343E+10 | 482.70 | 0.220178E+11 | 0.116202E+11 | 0.00 | 1.00 | 01-NOV-07:01 | 0.00 | 01-NOV-00:10 | 50514.69 | 01-NOV-07:01 | 35427.81 | 26-NOV-08:62 | 21744.29 | 01-NOV-07:03 | 11154.44 | 06-NOV-08:61 | 0.00 | 01-NOV-00:10 |
December | 0.306341E+11 | 0.739040E+10 | 499.28 | 0.201556E+11 | 0.104785E+11 | 0.00 | 1.00 | 01-DEC-08:61 | 0.00 | 01-DEC-01:05 | 50830.03 | 03-DEC-08:61 | 37657.95 | 25-DEC-08:62 | 22283.66 | 03-DEC-08:04 | 11141.74 | 03-DEC-08:61 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.404122E+12 | 0.980457E+11 | 5871.50 | 0.267568E+12 | 0.136554E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.253538E+11 | 0.622767E+10 | 447.70 | 0.168324E+11 | 0.780701E+10 | 0.00 | 1.00 | 0.00 | 49154.11 | 32508.61 | 17721.64 | 10753.42 | 0.00 | |||||||
Maximum of Months | 0.414529E+11 | 0.100742E+11 | 502.89 | 0.273660E+11 | 0.150027E+11 | 0.00 | 1.00 | 0.00 | 51465.37 | 37657.95 | 26115.37 | 11303.72 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.135970E+11 | 0.331278E+10 | 494.89 | 0.974433E+10 | 0.385267E+10 | 0.00 | 1.00 | 01-JAN-08:62 | 0.00 | 01-JAN-00:05 | 25629.05 | 31-JAN-08:62 | 20703.30 | 21-JAN-08:62 | 8305.20 | 31-JAN-08:62 | 5525.23 | 02-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.140749E+11 | 0.334712E+10 | 449.32 | 0.915271E+10 | 0.492217E+10 | 0.00 | 1.00 | 01-FEB-08:62 | 0.00 | 01-FEB-00:05 | 26354.18 | 17-FEB-08:62 | 19531.36 | 01-FEB-08:62 | 10905.23 | 17-FEB-08:03 | 5651.31 | 18-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.147404E+11 | 0.357552E+10 | 496.72 | 0.103248E+11 | 0.441566E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 25764.38 | 03-MAR-08:62 | 19359.96 | 19-MAR-07:02 | 9252.78 | 03-MAR-08:62 | 5506.64 | 15-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.139862E+11 | 0.342744E+10 | 480.70 | 0.100619E+11 | 0.392432E+10 | 0.00 | 1.00 | 05-APR-07:02 | 0.00 | 01-APR-00:05 | 25335.89 | 14-APR-07:02 | 20055.87 | 30-APR-07:02 | 7294.71 | 14-APR-07:02 | 5534.85 | 25-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.173809E+11 | 0.421358E+10 | 497.83 | 0.120431E+11 | 0.533777E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 25956.92 | 10-MAY-07:02 | 19923.29 | 02-MAY-07:02 | 9211.52 | 10-MAY-07:03 | 5644.34 | 09-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.174993E+11 | 0.422498E+10 | 485.19 | 0.120266E+11 | 0.547264E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 25846.19 | 14-JUN-07:02 | 19212.04 | 04-JUN-07:01 | 8726.82 | 14-JUN-07:03 | 5756.40 | 21-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.202437E+11 | 0.490862E+10 | 502.47 | 0.137188E+11 | 0.652491E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 26448.74 | 20-JUL-07:01 | 18918.83 | 08-JUL-07:02 | 10581.40 | 20-JUL-07:03 | 5782.59 | 20-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.205420E+11 | 0.501287E+10 | 500.27 | 0.139953E+11 | 0.654662E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 26107.84 | 08-AUG-07:01 | 18646.49 | 24-AUG-07:02 | 9389.37 | 08-AUG-07:03 | 5735.41 | 08-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.204440E+11 | 0.490590E+10 | 486.99 | 0.134035E+11 | 0.704050E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 26246.43 | 30-SEP-07:02 | 18666.73 | 19-SEP-07:02 | 10188.83 | 30-SEP-07:03 | 5819.19 | 03-SEP-07:01 | 0.00 | 01-SEP-00:10 |
October | 0.203298E+11 | 0.492050E+10 | 499.09 | 0.136709E+11 | 0.665897E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:03 | 25934.81 | 13-OCT-07:01 | 18996.59 | 26-OCT-07:02 | 8883.57 | 13-OCT-07:03 | 5710.90 | 07-OCT-07:01 | 0.00 | 01-OCT-00:03 |
November | 0.172087E+11 | 0.412654E+10 | 483.23 | 0.116276E+11 | 0.558110E+10 | 0.00 | 1.00 | 01-NOV-07:01 | 0.00 | 01-NOV-00:10 | 26032.21 | 01-NOV-07:01 | 19824.58 | 26-NOV-08:62 | 9294.67 | 01-NOV-07:03 | 5736.63 | 22-NOV-08:61 | 0.00 | 01-NOV-00:10 |
December | 0.159566E+11 | 0.382779E+10 | 499.51 | 0.108850E+11 | 0.507153E+10 | 0.00 | 1.00 | 01-DEC-08:61 | 0.00 | 01-DEC-01:05 | 26251.43 | 03-DEC-08:61 | 20692.47 | 25-DEC-08:62 | 9966.82 | 03-DEC-08:04 | 5742.41 | 03-DEC-08:61 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.206003E+12 | 0.498036E+11 | 5876.20 | 0.140655E+12 | 0.653489E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.135970E+11 | 0.331278E+10 | 449.32 | 0.915271E+10 | 0.385267E+10 | 0.00 | 1.00 | 0.00 | 25335.89 | 18646.49 | 7294.71 | 5506.64 | 0.00 | |||||||
Maximum of Months | 0.205420E+11 | 0.501287E+10 | 502.47 | 0.139953E+11 | 0.704050E+10 | 0.00 | 1.00 | 0.00 | 26448.74 | 20703.30 | 10905.23 | 5819.19 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.105871E+11 | 0.254426E+10 | 362.17 | 0.739336E+10 | 0.319371E+10 | 0.00 | 1.00 | 01-JAN-08:62 | 0.00 | 01-JAN-00:05 | 26516.91 | 02-JAN-07:02 | 19571.79 | 11-JAN-07:03 | 11773.07 | 01-JAN-08:62 | 5556.04 | 02-JAN-07:02 | 0.00 | 01-JAN-00:05 |
February | 0.110483E+11 | 0.258751E+10 | 327.31 | 0.695612E+10 | 0.409217E+10 | 0.00 | 1.00 | 01-FEB-07:03 | 0.00 | 01-FEB-00:05 | 27267.53 | 18-FEB-07:02 | 18216.85 | 01-FEB-07:03 | 14388.77 | 18-FEB-07:03 | 5653.07 | 17-FEB-07:02 | 0.00 | 01-FEB-00:05 |
March | 0.116268E+11 | 0.278439E+10 | 368.64 | 0.793897E+10 | 0.368785E+10 | 0.00 | 1.00 | 01-MAR-07:02 | 0.00 | 01-MAR-00:05 | 26903.15 | 13-MAR-06:02 | 18511.41 | 07-MAR-07:03 | 13175.69 | 13-MAR-06:03 | 5547.39 | 14-MAR-06:02 | 0.00 | 01-MAR-00:05 |
April | 0.108936E+11 | 0.263559E+10 | 351.98 | 0.764237E+10 | 0.325118E+10 | 0.00 | 1.00 | 01-APR-06:02 | 0.00 | 01-APR-00:05 | 26426.97 | 24-APR-06:02 | 19341.62 | 02-APR-07:03 | 11873.80 | 24-APR-06:02 | 5554.63 | 25-APR-06:02 | 0.00 | 01-APR-00:05 |
May | 0.139667E+11 | 0.333935E+10 | 368.48 | 0.946721E+10 | 0.449951E+10 | 0.00 | 1.00 | 01-MAY-06:02 | 0.00 | 01-MAY-00:10 | 26936.59 | 15-MAY-06:02 | 18144.17 | 02-MAY-06:02 | 13572.30 | 15-MAY-06:03 | 5638.91 | 09-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.142163E+11 | 0.337783E+10 | 362.92 | 0.951972E+10 | 0.469656E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 26467.26 | 18-JUN-07:01 | 17338.75 | 04-JUN-07:01 | 10961.53 | 09-JUN-06:02 | 5738.48 | 21-JUN-06:01 | 0.00 | 01-JUN-00:10 |
July | 0.163066E+11 | 0.389696E+10 | 367.38 | 0.107963E+11 | 0.551031E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 27297.59 | 23-JUL-07:01 | 16786.89 | 04-JUL-07:01 | 13591.95 | 23-JUL-07:04 | 5766.92 | 23-JUL-07:13 | 0.00 | 01-JUL-00:05 |
August | 0.169179E+11 | 0.407845E+10 | 376.15 | 0.113079E+11 | 0.561005E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 27099.17 | 20-AUG-07:01 | 16715.31 | 23-AUG-06:01 | 13059.46 | 20-AUG-07:04 | 5762.34 | 27-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.164142E+11 | 0.388105E+10 | 357.69 | 0.104987E+11 | 0.591551E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:10 | 27452.31 | 25-SEP-06:01 | 16631.58 | 29-SEP-06:01 | 14714.82 | 25-SEP-06:01 | 5846.25 | 03-SEP-07:13 | 0.00 | 01-SEP-00:10 |
October | 0.164230E+11 | 0.392323E+10 | 366.27 | 0.108186E+11 | 0.560440E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:03 | 26916.64 | 10-OCT-06:01 | 16546.40 | 28-OCT-06:02 | 13657.16 | 23-OCT-06:03 | 5706.70 | 07-OCT-06:01 | 0.00 | 01-OCT-00:03 |
November | 0.139083E+11 | 0.328467E+10 | 354.87 | 0.916063E+10 | 0.474766E+10 | 0.00 | 1.00 | 01-NOV-06:01 | 0.00 | 01-NOV-00:10 | 26736.63 | 24-NOV-07:02 | 17787.63 | 15-NOV-07:02 | 12484.81 | 24-NOV-07:03 | 5722.23 | 23-NOV-08:61 | 0.00 | 01-NOV-00:10 |
December | 0.125832E+11 | 0.296859E+10 | 363.20 | 0.833793E+10 | 0.424527E+10 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 26906.67 | 03-DEC-08:61 | 19961.82 | 20-DEC-07:02 | 12657.68 | 10-DEC-08:03 | 5745.80 | 03-DEC-08:61 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.164892E+12 | 0.393019E+11 | 4327.05 | 0.109838E+12 | 0.550542E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.105871E+11 | 0.254426E+10 | 327.31 | 0.695612E+10 | 0.319371E+10 | 0.00 | 1.00 | 0.00 | 26426.97 | 16546.40 | 10961.53 | 5547.39 | 0.00 | |||||||
Maximum of Months | 0.169179E+11 | 0.407845E+10 | 376.15 | 0.113079E+11 | 0.591551E+10 | 0.00 | 1.00 | 0.00 | 27452.31 | 19961.82 | 14714.82 | 5846.25 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.105501E+11 | 0.253714E+10 | 361.92 | 0.736677E+10 | 0.318337E+10 | 0.00 | 1.00 | 01-JAN-08:62 | 0.00 | 01-JAN-00:05 | 26570.51 | 02-JAN-07:02 | 19604.40 | 11-JAN-07:03 | 11777.99 | 01-JAN-08:62 | 5566.76 | 02-JAN-07:02 | 0.00 | 01-JAN-00:05 |
February | 0.110182E+11 | 0.258193E+10 | 327.26 | 0.693593E+10 | 0.408224E+10 | 0.00 | 1.00 | 01-FEB-07:03 | 0.00 | 01-FEB-00:05 | 27320.08 | 18-FEB-07:02 | 18250.33 | 01-FEB-07:03 | 14422.65 | 18-FEB-07:03 | 5663.78 | 17-FEB-07:02 | 0.00 | 01-FEB-00:05 |
March | 0.116022E+11 | 0.278004E+10 | 368.61 | 0.792185E+10 | 0.368034E+10 | 0.00 | 1.00 | 01-MAR-07:02 | 0.00 | 01-MAR-00:05 | 26957.30 | 13-MAR-06:02 | 18234.16 | 07-MAR-07:03 | 13188.92 | 13-MAR-06:03 | 5558.05 | 14-MAR-06:02 | 0.00 | 01-MAR-00:05 |
April | 0.108661E+11 | 0.263077E+10 | 351.91 | 0.762265E+10 | 0.324347E+10 | 0.00 | 1.00 | 01-APR-06:02 | 0.00 | 01-APR-00:05 | 26477.50 | 24-APR-06:02 | 19211.69 | 02-APR-07:03 | 11896.31 | 24-APR-06:02 | 5565.26 | 25-APR-06:02 | 0.00 | 01-APR-00:05 |
May | 0.139659E+11 | 0.333994E+10 | 368.48 | 0.946803E+10 | 0.449784E+10 | 0.00 | 1.00 | 01-MAY-06:02 | 0.00 | 01-MAY-00:10 | 26991.33 | 15-MAY-06:02 | 18177.37 | 02-MAY-06:02 | 13578.73 | 15-MAY-06:03 | 5649.73 | 09-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.142223E+11 | 0.337986E+10 | 362.90 | 0.952607E+10 | 0.469619E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 26521.74 | 18-JUN-07:01 | 17387.20 | 04-JUN-07:01 | 10983.58 | 09-JUN-06:02 | 5749.46 | 21-JUN-06:01 | 0.00 | 01-JUN-00:10 |
July | 0.163376E+11 | 0.390412E+10 | 367.40 | 0.108219E+11 | 0.551567E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 27353.86 | 23-JUL-07:01 | 16847.12 | 04-JUL-07:01 | 13598.06 | 23-JUL-07:04 | 5777.84 | 23-JUL-07:13 | 0.00 | 01-JUL-00:05 |
August | 0.169443E+11 | 0.408465E+10 | 376.12 | 0.113300E+11 | 0.561429E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 27156.68 | 20-AUG-07:01 | 16768.22 | 23-AUG-06:01 | 13059.29 | 20-AUG-07:04 | 5773.29 | 27-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.164567E+11 | 0.389073E+10 | 357.69 | 0.105326E+11 | 0.592407E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:10 | 27512.67 | 25-SEP-06:01 | 16676.46 | 29-SEP-06:01 | 14698.23 | 25-SEP-06:01 | 5857.36 | 03-SEP-07:13 | 0.00 | 01-SEP-00:10 |
October | 0.164574E+11 | 0.393115E+10 | 366.37 | 0.108464E+11 | 0.561101E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:03 | 26975.48 | 10-OCT-06:01 | 16590.06 | 28-OCT-06:02 | 13663.70 | 23-OCT-06:03 | 5717.63 | 07-OCT-06:01 | 0.00 | 01-OCT-00:03 |
November | 0.139040E+11 | 0.328457E+10 | 354.89 | 0.915951E+10 | 0.474444E+10 | 0.00 | 1.00 | 01-NOV-06:01 | 0.00 | 01-NOV-00:10 | 26792.44 | 24-NOV-07:02 | 17821.53 | 15-NOV-07:02 | 12483.45 | 24-NOV-07:03 | 5733.14 | 23-NOV-08:61 | 0.00 | 01-NOV-00:10 |
December | 0.125632E+11 | 0.296521E+10 | 363.08 | 0.832458E+10 | 0.423860E+10 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 26959.44 | 03-DEC-08:61 | 20000.04 | 20-DEC-07:02 | 12680.29 | 10-DEC-08:03 | 5756.69 | 03-DEC-08:61 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.164888E+12 | 0.393101E+11 | 4326.63 | 0.109856E+12 | 0.550315E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.105501E+11 | 0.253714E+10 | 327.26 | 0.693593E+10 | 0.318337E+10 | 0.00 | 1.00 | 0.00 | 26477.50 | 16590.06 | 10983.58 | 5558.05 | 0.00 | |||||||
Maximum of Months | 0.169443E+11 | 0.408465E+10 | 376.12 | 0.113300E+11 | 0.592407E+10 | 0.00 | 1.00 | 0.00 | 27512.67 | 20000.04 | 14698.23 | 5857.36 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.102813E+11 | 0.247773E+10 | 361.33 | 0.715349E+10 | 0.312784E+10 | 0.00 | 1.00 | 01-JAN-08:62 | 0.00 | 01-JAN-00:05 | 26371.94 | 02-JAN-07:02 | 19190.91 | 21-JAN-07:02 | 11769.34 | 01-JAN-08:62 | 5526.90 | 02-JAN-07:02 | 0.00 | 01-JAN-00:05 |
February | 0.107563E+11 | 0.252492E+10 | 326.76 | 0.673911E+10 | 0.401720E+10 | 0.00 | 1.00 | 02-FEB-07:03 | 0.00 | 01-FEB-00:05 | 27119.04 | 18-FEB-07:02 | 17790.44 | 01-FEB-07:03 | 14439.47 | 18-FEB-07:03 | 5623.87 | 17-FEB-07:02 | 0.00 | 01-FEB-00:05 |
March | 0.113162E+11 | 0.271669E+10 | 366.63 | 0.769813E+10 | 0.361811E+10 | 0.00 | 1.00 | 01-MAR-07:02 | 0.00 | 01-MAR-00:05 | 26754.75 | 13-MAR-06:02 | 17280.95 | 19-MAR-07:02 | 13177.62 | 13-MAR-06:03 | 5518.17 | 14-MAR-06:02 | 0.00 | 01-MAR-00:05 |
April | 0.106001E+11 | 0.257203E+10 | 351.71 | 0.741165E+10 | 0.318847E+10 | 0.00 | 1.00 | 01-APR-06:02 | 0.00 | 01-APR-00:05 | 26278.10 | 24-APR-06:02 | 18313.11 | 30-APR-07:02 | 11905.37 | 24-APR-06:02 | 5525.45 | 25-APR-06:02 | 0.00 | 01-APR-00:05 |
May | 0.137079E+11 | 0.328219E+10 | 368.26 | 0.926204E+10 | 0.444582E+10 | 0.00 | 1.00 | 01-MAY-06:02 | 0.00 | 01-MAY-00:10 | 26790.46 | 15-MAY-06:02 | 17934.51 | 02-MAY-06:02 | 13555.73 | 15-MAY-06:03 | 5609.50 | 09-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.139754E+11 | 0.332470E+10 | 362.50 | 0.932956E+10 | 0.464580E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 26319.34 | 18-JUN-07:01 | 17149.34 | 04-JUN-07:01 | 11021.41 | 09-JUN-06:02 | 5708.37 | 21-JUN-06:01 | 0.00 | 01-JUN-00:10 |
July | 0.160993E+11 | 0.384902E+10 | 367.29 | 0.106305E+11 | 0.546888E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 27148.70 | 23-JUL-07:01 | 16620.47 | 04-JUL-07:01 | 13587.83 | 23-JUL-07:04 | 5737.25 | 23-JUL-07:13 | 0.00 | 01-JUL-00:05 |
August | 0.166909E+11 | 0.402575E+10 | 376.04 | 0.111262E+11 | 0.556467E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 26952.57 | 20-AUG-07:01 | 16535.50 | 23-AUG-06:01 | 13046.47 | 20-AUG-07:04 | 5732.52 | 27-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.162199E+11 | 0.383641E+10 | 357.62 | 0.103454E+11 | 0.587448E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:10 | 27308.55 | 25-SEP-06:01 | 16446.18 | 29-SEP-06:01 | 14667.27 | 25-SEP-06:01 | 5816.12 | 03-SEP-07:13 | 0.00 | 01-SEP-00:10 |
October | 0.162096E+11 | 0.387391E+10 | 366.14 | 0.106488E+11 | 0.556087E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:03 | 26775.83 | 10-OCT-06:01 | 16350.87 | 28-OCT-06:02 | 13640.15 | 23-OCT-06:03 | 5676.94 | 07-OCT-06:01 | 0.00 | 01-OCT-00:03 |
November | 0.136593E+11 | 0.323069E+10 | 355.06 | 0.896694E+10 | 0.469236E+10 | 0.00 | 1.00 | 01-NOV-06:01 | 0.00 | 01-NOV-00:10 | 26592.18 | 24-NOV-07:02 | 17582.54 | 15-NOV-07:02 | 12467.68 | 24-NOV-07:03 | 5692.42 | 23-NOV-08:61 | 0.00 | 01-NOV-00:10 |
December | 0.123045E+11 | 0.290883E+10 | 362.75 | 0.812127E+10 | 0.418324E+10 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 26755.39 | 03-DEC-08:61 | 19757.76 | 20-DEC-07:02 | 12675.94 | 10-DEC-08:03 | 5716.08 | 03-DEC-08:61 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.161821E+12 | 0.386229E+11 | 4322.11 | 0.107433E+12 | 0.543877E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.102813E+11 | 0.247773E+10 | 326.76 | 0.673911E+10 | 0.312784E+10 | 0.00 | 1.00 | 0.00 | 26278.10 | 16350.87 | 11021.41 | 5518.17 | 0.00 | |||||||
Maximum of Months | 0.166909E+11 | 0.402575E+10 | 376.04 | 0.111262E+11 | 0.587448E+10 | 0.00 | 1.00 | 0.00 | 27308.55 | 19757.76 | 14667.27 | 5816.12 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.173056E+11 | 0.425994E+10 | 351.92 | 0.117286E+11 | 0.557698E+10 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 47069.30 | 01-JAN-09:02 | 34409.68 | 21-JAN-08:62 | 21000.31 | 01-JAN-09:04 | 10225.63 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.183219E+11 | 0.438283E+10 | 319.37 | 0.111154E+11 | 0.720646E+10 | 0.00 | 1.00 | 04-FEB-08:62 | 0.00 | 01-FEB-00:05 | 47976.64 | 18-FEB-08:62 | 29656.91 | 13-FEB-08:62 | 24886.80 | 17-FEB-08:03 | 10229.86 | 18-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.193335E+11 | 0.473598E+10 | 359.61 | 0.128140E+11 | 0.651944E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 47670.94 | 13-MAR-07:02 | 30627.51 | 19-MAR-08:62 | 23999.86 | 13-MAR-07:03 | 10032.33 | 13-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.179868E+11 | 0.445347E+10 | 340.86 | 0.122776E+11 | 0.570915E+10 | 0.00 | 1.00 | 05-APR-07:02 | 0.00 | 01-APR-00:05 | 46920.39 | 24-APR-07:02 | 32631.53 | 30-APR-08:62 | 21744.68 | 24-APR-07:02 | 10124.57 | 09-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.237589E+11 | 0.579002E+10 | 359.62 | 0.156914E+11 | 0.806748E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 47801.21 | 15-MAY-07:02 | 31942.93 | 02-MAY-07:02 | 24373.55 | 15-MAY-07:03 | 10386.69 | 14-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.242565E+11 | 0.586960E+10 | 353.33 | 0.158159E+11 | 0.844062E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 46948.93 | 18-JUN-08:61 | 29960.45 | 27-JUN-07:02 | 19766.56 | 25-JUN-08:04 | 10453.28 | 18-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.281321E+11 | 0.683184E+10 | 355.12 | 0.181734E+11 | 0.995868E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 48484.88 | 23-JUL-08:61 | 30672.56 | 04-JUL-08:61 | 24227.57 | 23-JUL-08:04 | 10524.67 | 23-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.293005E+11 | 0.718500E+10 | 367.57 | 0.191403E+11 | 0.101602E+11 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 48105.25 | 20-AUG-08:61 | 30066.48 | 23-AUG-07:02 | 23064.50 | 20-AUG-08:05 | 10629.79 | 27-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.283754E+11 | 0.681885E+10 | 346.72 | 0.176973E+11 | 0.106781E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 48687.52 | 25-SEP-07:02 | 29973.84 | 19-SEP-07:02 | 26509.75 | 25-SEP-07:02 | 10726.24 | 03-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.285052E+11 | 0.692544E+10 | 356.62 | 0.183282E+11 | 0.101770E+11 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:03 | 47746.63 | 10-OCT-07:02 | 29508.20 | 28-OCT-07:02 | 24575.67 | 23-OCT-07:02 | 10544.04 | 08-OCT-08:61 | 0.00 | 01-OCT-00:03 |
November | 0.236158E+11 | 0.568597E+10 | 346.38 | 0.151184E+11 | 0.849736E+10 | 0.00 | 1.00 | 01-NOV-07:01 | 0.00 | 01-NOV-00:10 | 47522.63 | 24-NOV-08:62 | 31451.50 | 15-NOV-08:62 | 22243.98 | 24-NOV-08:03 | 10496.26 | 23-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.210129E+11 | 0.506194E+10 | 351.32 | 0.134906E+11 | 0.752231E+10 | 0.00 | 1.00 | 01-DEC-08:61 | 0.00 | 01-DEC-00:10 | 47940.26 | 03-DEC-09:01 | 34570.16 | 20-DEC-08:62 | 22963.98 | 03-DEC-09:04 | 10380.68 | 03-DEC-09:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.279905E+12 | 0.680009E+11 | 4208.45 | 0.181391E+12 | 0.985138E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.173056E+11 | 0.425994E+10 | 319.37 | 0.111154E+11 | 0.557698E+10 | 0.00 | 1.00 | 0.00 | 46920.39 | 29508.20 | 19766.56 | 10032.33 | 0.00 | |||||||
Maximum of Months | 0.293005E+11 | 0.718500E+10 | 367.57 | 0.191403E+11 | 0.106781E+11 | 0.00 | 1.00 | 0.00 | 48687.52 | 34570.16 | 26509.75 | 10726.24 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.889326E+10 | 0.215515E+10 | 352.07 | 0.603437E+10 | 0.285889E+10 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 24536.09 | 01-JAN-09:02 | 17964.95 | 21-JAN-08:62 | 10924.09 | 02-JAN-08:03 | 5235.39 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.941646E+10 | 0.221754E+10 | 319.43 | 0.571740E+10 | 0.369905E+10 | 0.00 | 1.00 | 04-FEB-08:62 | 0.00 | 01-FEB-00:05 | 24988.21 | 18-FEB-08:62 | 15463.48 | 13-FEB-08:62 | 12934.84 | 17-FEB-08:03 | 5237.09 | 18-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.994140E+10 | 0.239726E+10 | 360.02 | 0.659424E+10 | 0.334716E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 24864.26 | 13-MAR-07:02 | 15966.01 | 19-MAR-08:62 | 12562.27 | 13-MAR-07:03 | 5137.00 | 13-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.925194E+10 | 0.225510E+10 | 341.14 | 0.632129E+10 | 0.293066E+10 | 0.00 | 1.00 | 05-APR-07:02 | 0.00 | 01-APR-00:05 | 24461.72 | 24-APR-07:02 | 16998.39 | 30-APR-08:62 | 11355.25 | 24-APR-07:02 | 5183.63 | 09-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.122515E+11 | 0.293881E+10 | 360.37 | 0.809673E+10 | 0.415472E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 24931.80 | 15-MAY-07:02 | 16699.34 | 02-MAY-07:02 | 12769.78 | 15-MAY-07:03 | 5317.65 | 14-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.124970E+11 | 0.297725E+10 | 354.77 | 0.815515E+10 | 0.434184E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 24467.08 | 18-JUN-08:61 | 15649.41 | 27-JUN-07:02 | 10319.42 | 25-JUN-08:04 | 5351.65 | 18-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.145260E+11 | 0.347269E+10 | 355.13 | 0.939076E+10 | 0.513521E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 25270.96 | 23-JUL-08:61 | 15973.64 | 04-JUL-08:61 | 12678.70 | 23-JUL-08:04 | 5388.14 | 23-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.151347E+11 | 0.365392E+10 | 367.09 | 0.989407E+10 | 0.524061E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 25073.46 | 20-AUG-08:61 | 15688.33 | 23-AUG-07:02 | 12056.07 | 20-AUG-08:04 | 5441.85 | 27-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.146456E+11 | 0.346445E+10 | 347.49 | 0.914091E+10 | 0.550468E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 25405.84 | 25-SEP-07:02 | 15673.67 | 19-SEP-07:02 | 13935.60 | 25-SEP-07:02 | 5491.29 | 03-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.147335E+11 | 0.352341E+10 | 356.51 | 0.948046E+10 | 0.525304E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:03 | 24908.63 | 10-OCT-07:02 | 15417.81 | 28-OCT-07:02 | 12853.86 | 23-OCT-07:02 | 5398.05 | 08-OCT-08:61 | 0.00 | 01-OCT-00:03 |
November | 0.121708E+11 | 0.288485E+10 | 347.31 | 0.779991E+10 | 0.437085E+10 | 0.00 | 1.00 | 01-NOV-07:01 | 0.00 | 01-NOV-00:10 | 24776.23 | 24-NOV-08:62 | 16410.88 | 15-NOV-08:62 | 11636.22 | 24-NOV-08:03 | 5373.33 | 23-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.108172E+11 | 0.256560E+10 | 351.47 | 0.695280E+10 | 0.386443E+10 | 0.00 | 1.00 | 01-DEC-08:61 | 0.00 | 01-DEC-00:10 | 24981.11 | 03-DEC-09:01 | 18055.90 | 20-DEC-08:62 | 11985.33 | 03-DEC-09:04 | 5314.43 | 03-DEC-09:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.144279E+12 | 0.345060E+11 | 4212.80 | 0.935781E+11 | 0.507011E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.889326E+10 | 0.215515E+10 | 319.43 | 0.571740E+10 | 0.285889E+10 | 0.00 | 1.00 | 0.00 | 24461.72 | 15417.81 | 10319.42 | 5137.00 | 0.00 | |||||||
Maximum of Months | 0.151347E+11 | 0.365392E+10 | 367.09 | 0.989407E+10 | 0.550468E+10 | 0.00 | 1.00 | 0.00 | 25405.84 | 18055.90 | 13935.60 | 5491.29 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.880684E+10 | 0.213525E+10 | 351.87 | 0.596600E+10 | 0.284084E+10 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 24430.19 | 01-JAN-09:02 | 17843.86 | 21-JAN-08:62 | 10904.53 | 02-JAN-08:03 | 5213.27 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.933007E+10 | 0.219796E+10 | 319.15 | 0.565316E+10 | 0.367691E+10 | 0.00 | 1.00 | 04-FEB-08:62 | 0.00 | 01-FEB-00:05 | 24884.89 | 18-FEB-08:62 | 15358.58 | 13-FEB-08:62 | 12921.74 | 17-FEB-08:03 | 5215.09 | 18-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.985261E+10 | 0.237677E+10 | 359.41 | 0.652486E+10 | 0.332775E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 24756.58 | 13-MAR-07:02 | 15864.45 | 19-MAR-08:62 | 12535.58 | 13-MAR-07:03 | 5115.28 | 13-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.917379E+10 | 0.223693E+10 | 340.94 | 0.625892E+10 | 0.291487E+10 | 0.00 | 1.00 | 05-APR-07:02 | 0.00 | 01-APR-00:05 | 24356.19 | 24-APR-07:02 | 16889.79 | 30-APR-08:62 | 11336.54 | 24-APR-07:02 | 5161.65 | 09-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.121735E+11 | 0.292048E+10 | 360.52 | 0.803368E+10 | 0.413978E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 24824.35 | 15-MAY-07:02 | 16584.26 | 02-MAY-07:02 | 12740.37 | 15-MAY-07:03 | 5295.23 | 14-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.124202E+11 | 0.295934E+10 | 354.80 | 0.809321E+10 | 0.432701E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 24361.73 | 18-JUN-08:61 | 15542.19 | 27-JUN-07:02 | 10299.45 | 25-JUN-08:04 | 5329.09 | 18-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.144513E+11 | 0.345479E+10 | 355.40 | 0.932944E+10 | 0.512182E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 25162.63 | 23-JUL-08:61 | 15871.28 | 04-JUL-08:61 | 12648.81 | 23-JUL-08:04 | 5365.48 | 23-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.150608E+11 | 0.363589E+10 | 366.89 | 0.983280E+10 | 0.522798E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24966.59 | 20-AUG-08:61 | 15584.96 | 23-AUG-07:02 | 12025.21 | 20-AUG-08:04 | 5419.01 | 27-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.145695E+11 | 0.344632E+10 | 347.27 | 0.907983E+10 | 0.548972E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 25296.82 | 25-SEP-07:02 | 15565.21 | 19-SEP-07:02 | 13897.40 | 25-SEP-07:02 | 5468.21 | 03-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.146569E+11 | 0.350496E+10 | 356.50 | 0.941781E+10 | 0.523905E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:03 | 24801.34 | 10-OCT-07:02 | 15308.10 | 28-OCT-07:02 | 12824.43 | 23-OCT-07:02 | 5375.35 | 08-OCT-08:61 | 0.00 | 01-OCT-00:03 |
November | 0.120876E+11 | 0.286574E+10 | 347.23 | 0.773420E+10 | 0.435342E+10 | 0.00 | 1.00 | 01-NOV-07:01 | 0.00 | 01-NOV-00:10 | 24669.46 | 24-NOV-08:62 | 16298.99 | 15-NOV-08:62 | 11613.31 | 24-NOV-08:03 | 5350.73 | 23-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.107313E+11 | 0.254606E+10 | 351.44 | 0.688528E+10 | 0.384602E+10 | 0.00 | 1.00 | 01-DEC-08:61 | 0.00 | 01-DEC-00:10 | 24873.72 | 03-DEC-09:01 | 17935.45 | 20-DEC-08:62 | 11958.85 | 03-DEC-09:04 | 5292.08 | 03-DEC-09:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.143314E+12 | 0.342805E+11 | 4211.41 | 0.928092E+11 | 0.505052E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.880684E+10 | 0.213525E+10 | 319.15 | 0.565316E+10 | 0.284084E+10 | 0.00 | 1.00 | 0.00 | 24356.19 | 15308.10 | 10299.45 | 5115.28 | 0.00 | |||||||
Maximum of Months | 0.150608E+11 | 0.363589E+10 | 366.89 | 0.983280E+10 | 0.548972E+10 | 0.00 | 1.00 | 0.00 | 25296.82 | 17935.45 | 13897.40 | 5468.21 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.870363E+10 | 0.211292E+10 | 351.11 | 0.589098E+10 | 0.281265E+10 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 24449.43 | 01-JAN-09:02 | 16959.04 | 12-JAN-08:62 | 10955.43 | 02-JAN-08:03 | 5219.13 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.921351E+10 | 0.217316E+10 | 318.04 | 0.557329E+10 | 0.364022E+10 | 0.00 | 1.00 | 04-FEB-08:62 | 0.00 | 01-FEB-00:05 | 24909.77 | 18-FEB-08:62 | 15305.83 | 13-FEB-08:62 | 12998.37 | 17-FEB-08:62 | 5221.29 | 18-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.974368E+10 | 0.235324E+10 | 358.62 | 0.644759E+10 | 0.329609E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 24778.93 | 13-MAR-07:02 | 15842.19 | 19-MAR-08:62 | 12585.49 | 13-MAR-07:03 | 5121.13 | 13-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.910725E+10 | 0.222261E+10 | 340.63 | 0.621109E+10 | 0.289616E+10 | 0.00 | 1.00 | 06-APR-07:02 | 0.00 | 01-APR-00:05 | 24376.60 | 24-APR-07:02 | 16655.58 | 06-APR-07:02 | 11389.36 | 24-APR-07:02 | 5167.14 | 09-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.121540E+11 | 0.291682E+10 | 361.02 | 0.802059E+10 | 0.413342E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 24846.72 | 15-MAY-07:02 | 16550.14 | 02-MAY-07:02 | 12784.39 | 15-MAY-07:03 | 5301.33 | 14-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.124069E+11 | 0.295704E+10 | 354.89 | 0.808488E+10 | 0.432199E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 24384.26 | 18-JUN-08:61 | 15522.85 | 27-JUN-07:02 | 10336.77 | 25-JUN-08:04 | 5335.32 | 18-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.144616E+11 | 0.345803E+10 | 355.56 | 0.933944E+10 | 0.512215E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 25188.35 | 23-JUL-08:61 | 15858.12 | 04-JUL-08:61 | 12682.00 | 23-JUL-08:04 | 5371.91 | 23-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.150889E+11 | 0.364308E+10 | 367.12 | 0.985608E+10 | 0.523284E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24991.83 | 20-AUG-08:61 | 15571.60 | 23-AUG-07:02 | 12055.22 | 20-AUG-08:04 | 5425.55 | 27-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.145740E+11 | 0.344826E+10 | 347.34 | 0.908470E+10 | 0.548928E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 25323.14 | 25-SEP-07:02 | 15552.62 | 19-SEP-07:02 | 13931.54 | 25-SEP-07:02 | 5474.77 | 03-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.146607E+11 | 0.350663E+10 | 356.46 | 0.942240E+10 | 0.523826E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:03 | 24826.50 | 10-OCT-07:02 | 15292.85 | 28-OCT-07:02 | 12865.24 | 23-OCT-07:02 | 5381.80 | 08-OCT-08:61 | 0.00 | 01-OCT-00:03 |
November | 0.120345E+11 | 0.285526E+10 | 347.41 | 0.769703E+10 | 0.433745E+10 | 0.00 | 1.00 | 01-NOV-07:01 | 0.00 | 01-NOV-00:10 | 24691.25 | 24-NOV-08:62 | 16255.49 | 15-NOV-08:62 | 11656.68 | 24-NOV-08:03 | 5356.92 | 23-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.106506E+11 | 0.252927E+10 | 351.34 | 0.682753E+10 | 0.382309E+10 | 0.00 | 1.00 | 01-DEC-08:61 | 0.00 | 01-DEC-00:10 | 24897.07 | 03-DEC-09:01 | 17901.21 | 20-DEC-08:62 | 12000.12 | 03-DEC-09:04 | 5298.44 | 03-DEC-09:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.142799E+12 | 0.341763E+11 | 4209.53 | 0.924556E+11 | 0.503436E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.870363E+10 | 0.211292E+10 | 318.04 | 0.557329E+10 | 0.281265E+10 | 0.00 | 1.00 | 0.00 | 24376.60 | 15292.85 | 10336.77 | 5121.13 | 0.00 | |||||||
Maximum of Months | 0.150889E+11 | 0.364308E+10 | 367.12 | 0.985608E+10 | 0.548928E+10 | 0.00 | 1.00 | 0.00 | 25323.14 | 17901.21 | 13931.54 | 5474.77 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.957608E+10 | 0.232623E+10 | 352.24 | 0.663157E+10 | 0.294451E+10 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 26894.49 | 02-JAN-08:62 | 16798.77 | 29-JAN-09:02 | 12156.02 | 31-JAN-08:62 | 5743.99 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.988330E+10 | 0.234097E+10 | 317.09 | 0.612069E+10 | 0.376260E+10 | 0.00 | 1.00 | 17-FEB-08:62 | 0.00 | 01-FEB-00:05 | 27846.95 | 18-FEB-08:62 | 14885.27 | 26-FEB-09:02 | 15819.73 | 18-FEB-08:62 | 5747.97 | 18-FEB-08:03 | 0.00 | 01-FEB-00:05 |
March | 0.105992E+11 | 0.256497E+10 | 356.58 | 0.717355E+10 | 0.342565E+10 | 0.00 | 1.00 | 02-MAR-08:62 | 0.00 | 01-MAR-00:05 | 27335.53 | 13-MAR-07:02 | 17481.32 | 19-MAR-08:62 | 13992.18 | 13-MAR-07:02 | 5644.54 | 15-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.102610E+11 | 0.249919E+10 | 341.44 | 0.716125E+10 | 0.309979E+10 | 0.00 | 1.00 | 07-APR-07:02 | 0.00 | 01-APR-00:05 | 26815.61 | 24-APR-07:02 | 17606.49 | 30-APR-08:62 | 12409.33 | 24-APR-07:02 | 5698.30 | 09-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.138123E+11 | 0.331063E+10 | 362.61 | 0.935410E+10 | 0.445820E+10 | 0.00 | 1.00 | 04-MAY-07:02 | 0.00 | 01-MAY-00:10 | 27343.12 | 15-MAY-07:02 | 17837.48 | 31-MAY-07:02 | 13919.30 | 15-MAY-07:03 | 5838.62 | 14-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.140929E+11 | 0.335496E+10 | 356.68 | 0.941509E+10 | 0.467781E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 26976.03 | 25-JUN-08:61 | 17077.54 | 04-JUN-08:61 | 11976.73 | 14-JUN-07:02 | 5874.86 | 18-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.163950E+11 | 0.392127E+10 | 356.59 | 0.108629E+11 | 0.553208E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 27902.03 | 23-JUL-08:61 | 17046.11 | 04-JUL-08:61 | 14334.10 | 20-JUL-07:04 | 5912.97 | 23-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.172036E+11 | 0.415388E+10 | 369.01 | 0.115347E+11 | 0.566894E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 27646.25 | 20-AUG-08:61 | 16446.80 | 23-AUG-07:02 | 13196.68 | 20-AUG-08:04 | 5972.99 | 27-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.162088E+11 | 0.384395E+10 | 348.32 | 0.103571E+11 | 0.585171E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 27913.39 | 25-SEP-07:02 | 16708.61 | 19-SEP-07:02 | 15326.17 | 25-SEP-07:02 | 6026.69 | 03-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.164616E+11 | 0.394406E+10 | 356.36 | 0.108672E+11 | 0.559443E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:03 | 27395.94 | 10-OCT-07:02 | 16665.69 | 26-OCT-07:02 | 13966.13 | 10-OCT-07:03 | 5923.97 | 08-OCT-08:03 | 0.00 | 01-OCT-00:03 |
November | 0.132492E+11 | 0.315022E+10 | 348.74 | 0.866623E+10 | 0.458297E+10 | 0.00 | 1.00 | 01-NOV-07:01 | 0.00 | 01-NOV-00:10 | 27244.35 | 24-NOV-08:62 | 17863.22 | 15-NOV-08:62 | 12946.53 | 24-NOV-08:03 | 5907.88 | 23-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.116644E+11 | 0.277662E+10 | 352.48 | 0.765276E+10 | 0.401161E+10 | 0.00 | 1.00 | 01-DEC-08:61 | 0.00 | 01-DEC-00:10 | 27530.51 | 03-DEC-09:01 | 19651.95 | 25-DEC-09:02 | 13311.13 | 03-DEC-09:04 | 5832.21 | 03-DEC-09:03 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.159407E+12 | 0.381869E+11 | 4218.15 | 0.105797E+12 | 0.536103E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.957608E+10 | 0.232623E+10 | 317.09 | 0.612069E+10 | 0.294451E+10 | 0.00 | 1.00 | 0.00 | 26815.61 | 14885.27 | 11976.73 | 5644.54 | 0.00 | |||||||
Maximum of Months | 0.172036E+11 | 0.415388E+10 | 369.01 | 0.115347E+11 | 0.585171E+10 | 0.00 | 1.00 | 0.00 | 27913.39 | 19651.95 | 15819.73 | 6026.69 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.53 | 26.68 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 102.84 | 25.35 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 71.93 | 24.95 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.29 | 20.90 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.00 | 15.24 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.46 | 11.83 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.06 | 8.74 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.15 | 10.01 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.71 | 9.09 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.14 | 14.66 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.22 | 17.48 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.38 | 20.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 79.89 | 17.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.29 | 8.74 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.38 | 26.68 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.53 | 26.68 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 102.84 | 25.35 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 71.93 | 24.95 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.29 | 20.90 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.00 | 15.24 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.46 | 11.83 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.06 | 8.74 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.15 | 10.01 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.71 | 9.09 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.14 | 14.66 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.22 | 17.48 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.38 | 20.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 79.89 | 17.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.29 | 8.74 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.38 | 26.68 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.53 | 26.68 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 102.84 | 25.35 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 71.93 | 24.95 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.29 | 20.90 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.00 | 15.24 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.46 | 11.83 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.06 | 8.74 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.15 | 10.01 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.71 | 9.09 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.14 | 14.66 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.22 | 17.48 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.38 | 20.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 79.89 | 17.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.29 | 8.74 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.38 | 26.68 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.53 | 26.68 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 102.84 | 25.35 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 71.93 | 24.95 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.29 | 20.90 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.00 | 15.24 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.46 | 11.83 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.06 | 8.74 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.15 | 10.01 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.71 | 9.09 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.14 | 14.66 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.22 | 17.48 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.38 | 20.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 79.89 | 17.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.29 | 8.74 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.38 | 26.68 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.84 | 57.67 | 34.17 | 148.30 | 31.98 | 0.00 | 0.00 | 744.00 |
February | 77.79 | 41.47 | 36.32 | 123.45 | 30.37 | 0.00 | 0.00 | 672.00 |
March | 56.44 | 19.34 | 37.10 | 86.29 | 29.89 | 0.00 | 0.00 | 744.00 |
April | 36.49 | 3.51 | 32.98 | 53.09 | 25.07 | 0.00 | 0.00 | 720.00 |
May | 30.89 | 0.08 | 30.81 | 53.84 | 18.31 | 0.00 | 0.00 | 744.00 |
June | 30.55 | 0.00 | 30.55 | 53.18 | 14.25 | 0.00 | 0.00 | 720.00 |
July | 29.63 | 0.08 | 29.55 | 57.43 | 10.55 | 0.00 | 0.00 | 744.00 |
August | 32.41 | 1.99 | 30.42 | 61.14 | 12.07 | 0.00 | 0.00 | 744.00 |
September | 48.98 | 11.89 | 37.09 | 84.68 | 10.97 | 0.00 | 0.00 | 720.00 |
October | 69.44 | 33.53 | 35.91 | 123.63 | 17.63 | 0.00 | 0.00 | 744.00 |
November | 87.68 | 50.26 | 37.42 | 149.05 | 21.01 | 0.00 | 0.00 | 720.00 |
December | 94.88 | 61.13 | 33.75 | 156.51 | 24.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 57.15 | 23.34 | 33.81 | 95.77 | 20.51 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.63 | 0.00 | 29.55 | 53.09 | 10.55 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.88 | 61.13 | 37.42 | 156.51 | 31.98 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.84 | 57.67 | 34.17 | 148.30 | 31.98 | 0.00 | 0.00 | 744.00 |
February | 77.79 | 41.47 | 36.32 | 123.45 | 30.37 | 0.00 | 0.00 | 672.00 |
March | 56.44 | 19.34 | 37.10 | 86.29 | 29.89 | 0.00 | 0.00 | 744.00 |
April | 36.49 | 3.51 | 32.98 | 53.09 | 25.07 | 0.00 | 0.00 | 720.00 |
May | 30.89 | 0.08 | 30.81 | 53.84 | 18.31 | 0.00 | 0.00 | 744.00 |
June | 30.55 | 0.00 | 30.55 | 53.18 | 14.25 | 0.00 | 0.00 | 720.00 |
July | 29.63 | 0.08 | 29.55 | 57.43 | 10.55 | 0.00 | 0.00 | 744.00 |
August | 32.41 | 1.99 | 30.42 | 61.14 | 12.07 | 0.00 | 0.00 | 744.00 |
September | 48.98 | 11.89 | 37.09 | 84.68 | 10.97 | 0.00 | 0.00 | 720.00 |
October | 69.44 | 33.53 | 35.91 | 123.63 | 17.63 | 0.00 | 0.00 | 744.00 |
November | 87.68 | 50.26 | 37.42 | 149.05 | 21.01 | 0.00 | 0.00 | 720.00 |
December | 94.88 | 61.13 | 33.75 | 156.51 | 24.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 57.15 | 23.34 | 33.81 | 95.77 | 20.51 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.63 | 0.00 | 29.55 | 53.09 | 10.55 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.88 | 61.13 | 37.42 | 156.51 | 31.98 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.28 | 27.03 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 102.69 | 25.63 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 71.95 | 25.23 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.40 | 21.10 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.26 | 15.34 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.79 | 11.80 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.52 | 8.63 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.67 | 9.86 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 71.22 | 8.87 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.36 | 14.66 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.20 | 17.53 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.19 | 20.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.04 | 17.16 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.40 | 8.63 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.19 | 27.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.28 | 27.03 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 102.69 | 25.63 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 71.95 | 25.23 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.40 | 21.10 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.26 | 15.34 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.79 | 11.80 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.52 | 8.63 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.67 | 9.86 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 71.22 | 8.87 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.36 | 14.66 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.20 | 17.53 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.19 | 20.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.04 | 17.16 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.40 | 8.63 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.19 | 27.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.84 | 57.67 | 34.17 | 148.01 | 32.39 | 0.00 | 0.00 | 744.00 |
February | 77.79 | 41.47 | 36.32 | 123.30 | 30.70 | 0.00 | 0.00 | 672.00 |
March | 56.44 | 19.34 | 37.10 | 86.33 | 30.21 | 0.00 | 0.00 | 744.00 |
April | 36.49 | 3.51 | 32.98 | 53.22 | 25.30 | 0.00 | 0.00 | 720.00 |
May | 30.89 | 0.08 | 30.81 | 54.15 | 18.41 | 0.00 | 0.00 | 744.00 |
June | 30.55 | 0.00 | 30.55 | 53.59 | 14.20 | 0.00 | 0.00 | 720.00 |
July | 29.63 | 0.08 | 29.55 | 57.99 | 10.42 | 0.00 | 0.00 | 744.00 |
August | 32.41 | 1.99 | 30.42 | 61.75 | 11.89 | 0.00 | 0.00 | 744.00 |
September | 48.98 | 11.89 | 37.09 | 85.28 | 10.70 | 0.00 | 0.00 | 720.00 |
October | 69.44 | 33.53 | 35.91 | 123.90 | 17.63 | 0.00 | 0.00 | 744.00 |
November | 87.68 | 50.26 | 37.42 | 149.04 | 21.07 | 0.00 | 0.00 | 720.00 |
December | 94.88 | 61.13 | 33.75 | 156.30 | 24.86 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 57.15 | 23.34 | 33.81 | 95.97 | 20.60 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.63 | 0.00 | 29.55 | 53.22 | 10.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.88 | 61.13 | 37.42 | 156.30 | 32.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.41 | 28.84 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 102.70 | 27.44 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 71.80 | 26.92 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.34 | 22.85 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.13 | 17.43 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.69 | 14.02 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.17 | 11.15 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.47 | 12.30 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.61 | 11.32 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.11 | 17.21 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.30 | 19.75 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.35 | 22.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 79.92 | 19.30 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.34 | 11.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.35 | 28.84 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.41 | 28.84 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 102.70 | 27.44 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 71.80 | 26.92 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.34 | 22.85 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.13 | 17.43 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.69 | 14.02 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.17 | 11.15 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.47 | 12.30 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.61 | 11.32 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.11 | 17.21 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.30 | 19.75 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.35 | 22.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 79.92 | 19.30 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.34 | 11.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.35 | 28.84 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 147.36 | 34.31 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 122.62 | 32.63 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 85.68 | 32.02 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 52.85 | 27.20 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 53.70 | 20.75 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 53.17 | 16.71 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 57.27 | 13.30 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 61.18 | 14.67 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 84.12 | 13.51 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 122.93 | 20.51 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 148.35 | 23.53 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 155.63 | 27.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 95.30 | 22.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 52.85 | 13.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 155.63 | 34.31 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.44 | 28.78 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 102.71 | 27.41 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 71.81 | 26.91 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.35 | 22.83 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.12 | 17.49 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.68 | 14.11 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.14 | 11.32 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.45 | 12.45 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.58 | 11.52 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.08 | 17.37 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.30 | 19.80 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.36 | 22.81 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 79.91 | 19.36 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.35 | 11.32 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.36 | 28.78 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.44 | 28.78 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 102.71 | 27.41 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 71.81 | 26.91 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.35 | 22.83 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.12 | 17.49 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.68 | 14.11 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.14 | 11.32 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.45 | 12.45 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.58 | 11.52 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.08 | 17.37 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.30 | 19.80 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.36 | 22.81 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 79.91 | 19.36 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.35 | 11.32 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.36 | 28.78 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 147.39 | 34.24 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 122.65 | 32.59 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 85.70 | 32.00 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 52.87 | 27.17 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 53.70 | 20.83 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 53.16 | 16.82 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 57.23 | 13.49 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 61.16 | 14.85 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 84.07 | 13.74 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 122.90 | 20.69 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 148.34 | 23.60 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 155.64 | 27.16 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 95.29 | 23.05 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 52.87 | 13.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 155.64 | 34.24 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.56 | 28.39 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 102.85 | 27.00 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 71.94 | 26.49 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.49 | 22.43 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.25 | 17.12 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.81 | 13.74 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.26 | 10.96 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.57 | 12.08 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.68 | 11.16 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.19 | 17.00 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.42 | 19.44 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.48 | 22.42 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.04 | 18.98 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.49 | 10.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.48 | 28.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.56 | 28.39 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 102.85 | 27.00 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 71.94 | 26.49 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.49 | 22.43 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.25 | 17.12 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.81 | 13.74 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.26 | 10.96 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.57 | 12.08 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.68 | 11.16 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.19 | 17.00 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.42 | 19.44 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.48 | 22.42 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.04 | 18.98 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.49 | 10.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.48 | 28.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 147.54 | 33.78 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 122.81 | 32.10 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 85.85 | 31.50 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 53.03 | 26.69 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 53.85 | 20.39 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 53.32 | 16.39 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 57.38 | 13.08 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 61.30 | 14.41 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 84.21 | 13.32 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 123.03 | 20.26 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 148.49 | 23.17 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 155.78 | 26.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 95.44 | 22.60 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 53.03 | 13.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 155.78 | 33.78 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.73 | 27.13 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.11 | 25.71 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.17 | 25.22 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.57 | 21.19 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.16 | 15.91 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.63 | 12.50 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 47.99 | 9.76 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.33 | 10.77 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.56 | 10.02 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.11 | 15.80 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.41 | 18.25 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.57 | 21.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.02 | 17.75 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.57 | 9.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.57 | 27.13 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.73 | 27.13 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.11 | 25.71 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.17 | 25.22 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.57 | 21.19 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.16 | 15.91 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.63 | 12.50 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 47.99 | 9.76 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.33 | 10.77 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.56 | 10.02 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.11 | 15.80 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.41 | 18.25 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.57 | 21.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.02 | 17.75 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.57 | 9.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.57 | 27.13 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.73 | 27.13 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.11 | 25.71 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.17 | 25.22 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.57 | 21.19 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.16 | 15.91 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.63 | 12.50 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 47.99 | 9.76 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.33 | 10.77 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.56 | 10.02 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.11 | 15.80 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.41 | 18.25 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.57 | 21.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.02 | 17.75 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.57 | 9.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.57 | 27.13 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.73 | 27.13 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.11 | 25.71 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.17 | 25.22 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.57 | 21.19 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.16 | 15.91 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.63 | 12.50 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 47.99 | 9.76 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.33 | 10.77 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.56 | 10.02 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.11 | 15.80 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.41 | 18.25 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.57 | 21.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.02 | 17.75 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.57 | 9.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.57 | 27.13 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 147.75 | 32.29 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 123.12 | 30.58 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 86.14 | 30.00 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 53.15 | 25.22 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 53.76 | 18.95 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 53.13 | 14.92 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 57.08 | 11.65 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 61.05 | 12.86 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 84.08 | 11.96 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 122.95 | 18.83 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 148.49 | 21.76 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 155.90 | 25.26 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 95.44 | 21.14 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 53.13 | 11.65 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 155.90 | 32.29 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 147.75 | 32.29 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 123.12 | 30.58 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 86.14 | 30.00 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 53.15 | 25.22 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 53.76 | 18.95 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 53.13 | 14.92 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 57.08 | 11.65 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 61.05 | 12.86 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 84.08 | 11.96 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 122.95 | 18.83 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 148.49 | 21.76 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 155.90 | 25.26 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 95.44 | 21.14 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 53.13 | 11.65 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 155.90 | 32.29 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.70 | 26.75 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.11 | 25.31 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.27 | 24.82 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.76 | 20.78 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.44 | 15.48 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.94 | 12.03 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.35 | 9.27 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.70 | 10.27 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.85 | 9.50 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.29 | 15.31 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.46 | 17.78 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.54 | 20.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.19 | 17.30 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.76 | 9.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.54 | 26.75 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.70 | 26.75 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.11 | 25.31 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.27 | 24.82 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.76 | 20.78 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.44 | 15.48 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.94 | 12.03 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.35 | 9.27 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.70 | 10.27 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.85 | 9.50 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.29 | 15.31 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.46 | 17.78 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.54 | 20.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.19 | 17.30 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.76 | 9.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.54 | 26.75 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 147.73 | 31.83 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 123.14 | 30.11 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 86.27 | 29.52 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 53.38 | 24.74 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 54.10 | 18.44 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 53.50 | 14.36 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 57.51 | 11.08 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 61.49 | 12.27 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 84.43 | 11.35 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 123.17 | 18.25 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 148.57 | 21.19 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 155.89 | 24.72 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 95.66 | 20.61 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 53.38 | 11.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 155.89 | 31.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.77 | 26.62 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.18 | 25.18 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.34 | 24.68 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.82 | 20.66 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.50 | 15.38 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 45.00 | 11.93 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.42 | 9.18 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.76 | 10.18 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.91 | 9.40 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.34 | 15.20 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.53 | 17.66 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.60 | 20.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.26 | 17.18 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.82 | 9.18 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.60 | 26.62 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.77 | 26.62 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.18 | 25.18 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.34 | 24.68 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.82 | 20.66 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.50 | 15.38 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 45.00 | 11.93 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.42 | 9.18 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.76 | 10.18 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.91 | 9.40 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.34 | 15.20 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.53 | 17.66 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.60 | 20.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.26 | 17.18 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.82 | 9.18 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.60 | 26.62 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 147.81 | 31.68 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 123.23 | 29.94 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 86.35 | 29.36 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 53.46 | 24.60 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 54.17 | 18.31 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 53.58 | 14.24 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 57.59 | 10.96 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 61.56 | 12.15 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 84.50 | 11.23 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 123.24 | 18.12 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 148.64 | 21.05 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 155.97 | 24.57 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 95.73 | 20.47 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 53.46 | 10.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 155.97 | 31.68 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.82 | 26.43 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.24 | 24.97 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.37 | 24.50 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.84 | 20.52 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.48 | 15.31 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.98 | 11.88 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.37 | 9.17 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.69 | 10.19 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.86 | 9.40 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.30 | 15.18 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.54 | 17.56 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.64 | 20.49 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.25 | 17.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.84 | 9.17 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.64 | 26.43 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.82 | 26.43 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.24 | 24.97 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.37 | 24.50 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.84 | 20.52 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.48 | 15.31 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.98 | 11.88 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.37 | 9.17 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.69 | 10.19 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.86 | 9.40 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.30 | 15.18 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.54 | 17.56 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.64 | 20.49 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.25 | 17.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.84 | 9.17 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.64 | 26.43 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 147.88 | 31.46 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 123.30 | 29.70 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 86.39 | 29.14 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 53.47 | 24.43 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 54.15 | 18.24 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 53.54 | 14.18 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 57.53 | 10.96 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 61.48 | 12.17 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 84.43 | 11.24 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 123.19 | 18.11 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 148.66 | 20.94 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 156.01 | 24.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 95.73 | 20.37 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 53.47 | 10.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 156.01 | 31.46 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.40 | 25.90 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 102.91 | 24.36 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 71.88 | 23.95 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.13 | 20.17 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 44.48 | 15.35 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.96 | 12.02 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 47.20 | 9.55 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 50.43 | 10.67 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 69.87 | 9.89 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 102.29 | 15.56 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 123.90 | 17.52 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.14 | 20.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 79.46 | 17.06 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.96 | 9.55 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.14 | 25.90 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.40 | 25.90 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 102.91 | 24.36 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 71.88 | 23.95 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.13 | 20.17 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 44.48 | 15.35 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.96 | 12.02 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 47.20 | 9.55 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 50.43 | 10.67 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 69.87 | 9.89 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 102.29 | 15.56 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 123.90 | 17.52 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.14 | 20.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 79.46 | 17.06 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.96 | 9.55 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.14 | 25.90 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 147.37 | 30.84 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 122.90 | 28.98 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 85.79 | 28.49 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 52.61 | 24.02 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 52.94 | 18.29 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 52.32 | 14.35 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 56.12 | 11.41 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 59.96 | 12.75 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 83.24 | 11.82 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 121.96 | 18.56 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 147.89 | 20.90 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 155.40 | 24.11 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 94.76 | 20.33 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 52.32 | 11.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 155.40 | 30.84 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.330869E+09 | 71451180.03 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.248780E+09 | 61319373.98 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.192647E+09 | 66823337.30 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.114811E+09 | 54174296.60 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.120527E+09 | 40826607.00 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.115239E+09 | 30664821.07 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.128715E+09 | 23410085.69 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.136998E+09 | 26801473.99 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183293E+09 | 23556777.64 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276247E+09 | 39261810.58 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.321984E+09 | 45305215.99 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349197E+09 | 54975361.04 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.251931E+10 | 0.538570E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.114811E+09 | 23410085.69 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349197E+09 | 71451180.03 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.330869E+09 | 71451180.03 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.248780E+09 | 61319373.98 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.192647E+09 | 66823337.30 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.114811E+09 | 54174296.60 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.120527E+09 | 40826607.00 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.115239E+09 | 30664821.07 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.128715E+09 | 23410085.69 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.136998E+09 | 26801473.99 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183293E+09 | 23556777.64 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276247E+09 | 39261810.58 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.321984E+09 | 45305215.99 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349197E+09 | 54975361.04 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.251931E+10 | 0.538570E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.114811E+09 | 23410085.69 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349197E+09 | 71451180.03 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.330869E+09 | 71451180.03 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.248780E+09 | 61319373.98 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.192647E+09 | 66823337.30 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.114811E+09 | 54174296.60 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.120527E+09 | 40826607.00 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.115239E+09 | 30664821.07 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.128715E+09 | 23410085.69 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.136998E+09 | 26801473.99 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183293E+09 | 23556777.64 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276247E+09 | 39261810.58 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.321984E+09 | 45305215.99 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349197E+09 | 54975361.04 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.251931E+10 | 0.538570E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.114811E+09 | 23410085.69 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349197E+09 | 71451180.03 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.330869E+09 | 71451180.03 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.248780E+09 | 61319373.98 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.192647E+09 | 66823337.30 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.114811E+09 | 54174296.60 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.120527E+09 | 40826607.00 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.115239E+09 | 30664821.07 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.128715E+09 | 23410085.69 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.136998E+09 | 26801473.99 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183293E+09 | 23556777.64 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276247E+09 | 39261810.58 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.321984E+09 | 45305215.99 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349197E+09 | 54975361.04 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.251931E+10 | 0.538570E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.114811E+09 | 23410085.69 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349197E+09 | 71451180.03 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.245987E+09 | 0.154472E+09 | 91515107.98 | 0.397213E+09 | 85651326.95 |
February | 0.188197E+09 | 0.100323E+09 | 87874414.35 | 0.298651E+09 | 73466481.28 |
March | 0.151158E+09 | 51789298.46 | 99368896.28 | 0.231121E+09 | 80052025.01 |
April | 94588372.98 | 9109605.43 | 85478767.55 | 0.137597E+09 | 64977620.24 |
May | 82733628.79 | 213615.15 | 82520013.64 | 0.144197E+09 | 49030554.35 |
June | 79197287.84 | 0.00 | 79197287.84 | 0.137854E+09 | 36926468.10 |
July | 79352611.83 | 216935.24 | 79135676.59 | 0.153822E+09 | 28253781.10 |
August | 86805029.55 | 5330716.79 | 81474312.76 | 0.163745E+09 | 32324572.83 |
September | 0.126953E+09 | 30810433.11 | 96142796.74 | 0.219481E+09 | 28423617.26 |
October | 0.185985E+09 | 89814394.78 | 96170710.31 | 0.331120E+09 | 47219982.69 |
November | 0.227268E+09 | 0.130278E+09 | 96989683.65 | 0.386349E+09 | 54457694.70 |
December | 0.254120E+09 | 0.163736E+09 | 90383919.63 | 0.419184E+09 | 66006873.93 |
Annual Sum or Average | 0.180234E+10 | 0.736093E+09 | 0.106625E+10 | 0.302033E+10 | 0.646791E+09 |
Minimum of Months | 79197287.84 | 0.00 | 79135676.59 | 0.137597E+09 | 28253781.10 |
Maximum of Months | 0.254120E+09 | 0.163736E+09 | 99368896.28 | 0.419184E+09 | 85651326.95 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.245987E+09 | 0.154472E+09 | 91515107.98 | 0.397213E+09 | 85651326.95 |
February | 0.188197E+09 | 0.100323E+09 | 87874414.35 | 0.298651E+09 | 73466481.28 |
March | 0.151158E+09 | 51789298.46 | 99368896.28 | 0.231121E+09 | 80052025.01 |
April | 94588372.98 | 9109605.43 | 85478767.55 | 0.137597E+09 | 64977620.24 |
May | 82733628.79 | 213615.15 | 82520013.64 | 0.144197E+09 | 49030554.35 |
June | 79197287.84 | 0.00 | 79197287.84 | 0.137854E+09 | 36926468.10 |
July | 79352611.83 | 216935.24 | 79135676.59 | 0.153822E+09 | 28253781.10 |
August | 86805029.55 | 5330716.79 | 81474312.76 | 0.163745E+09 | 32324572.83 |
September | 0.126953E+09 | 30810433.11 | 96142796.74 | 0.219481E+09 | 28423617.26 |
October | 0.185985E+09 | 89814394.78 | 96170710.31 | 0.331120E+09 | 47219982.69 |
November | 0.227268E+09 | 0.130278E+09 | 96989683.65 | 0.386349E+09 | 54457694.70 |
December | 0.254120E+09 | 0.163736E+09 | 90383919.63 | 0.419184E+09 | 66006873.93 |
Annual Sum or Average | 0.180234E+10 | 0.736093E+09 | 0.106625E+10 | 0.302033E+10 | 0.646791E+09 |
Minimum of Months | 79197287.84 | 0.00 | 79135676.59 | 0.137597E+09 | 28253781.10 |
Maximum of Months | 0.254120E+09 | 0.163736E+09 | 99368896.28 | 0.419184E+09 | 85651326.95 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.330186E+09 | 72393123.67 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.248436E+09 | 62005865.75 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.192710E+09 | 67568074.84 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.115090E+09 | 54678938.73 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.121212E+09 | 41079765.10 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116098E+09 | 30581175.36 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.129965E+09 | 23127929.63 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.138380E+09 | 26413326.28 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.184598E+09 | 22998924.40 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276831E+09 | 39276640.16 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.321926E+09 | 45435012.38 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.348701E+09 | 55460424.52 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.252413E+10 | 0.541019E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.115090E+09 | 22998924.40 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.348701E+09 | 72393123.67 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.330186E+09 | 72393123.67 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.248436E+09 | 62005865.75 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.192710E+09 | 67568074.84 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.115090E+09 | 54678938.73 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.121212E+09 | 41079765.10 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116098E+09 | 30581175.36 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.129965E+09 | 23127929.63 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.138380E+09 | 26413326.28 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.184598E+09 | 22998924.40 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276831E+09 | 39276640.16 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.321926E+09 | 45435012.38 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.348701E+09 | 55460424.52 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.252413E+10 | 0.541019E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.115090E+09 | 22998924.40 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.348701E+09 | 72393123.67 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.245987E+09 | 0.154472E+09 | 91515107.98 | 0.396441E+09 | 86760725.40 |
February | 0.188197E+09 | 0.100323E+09 | 87874414.35 | 0.298276E+09 | 74268777.84 |
March | 0.151158E+09 | 51789298.46 | 99368896.28 | 0.231222E+09 | 80924429.31 |
April | 94588372.98 | 9109605.43 | 85478767.55 | 0.137941E+09 | 65565114.32 |
May | 82733628.79 | 213615.15 | 82520013.64 | 0.145025E+09 | 49319902.37 |
June | 79197287.84 | 0.00 | 79197287.84 | 0.138894E+09 | 36817112.90 |
July | 79352611.83 | 216935.24 | 79135676.59 | 0.155325E+09 | 27906440.52 |
August | 86805029.55 | 5330716.79 | 81474312.76 | 0.165404E+09 | 31848297.67 |
September | 0.126953E+09 | 30810433.11 | 96142796.74 | 0.221057E+09 | 27739050.34 |
October | 0.185985E+09 | 89814394.78 | 96170710.31 | 0.331849E+09 | 47226100.67 |
November | 0.227268E+09 | 0.130278E+09 | 96989683.65 | 0.386324E+09 | 54603373.02 |
December | 0.254120E+09 | 0.163736E+09 | 90383919.63 | 0.418643E+09 | 66575079.29 |
Annual Sum or Average | 0.180234E+10 | 0.736093E+09 | 0.106625E+10 | 0.302640E+10 | 0.649554E+09 |
Minimum of Months | 79197287.84 | 0.00 | 79135676.59 | 0.137941E+09 | 27739050.34 |
Maximum of Months | 0.254120E+09 | 0.163736E+09 | 99368896.28 | 0.418643E+09 | 86760725.40 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.330549E+09 | 77238264.48 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.248440E+09 | 66386907.17 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.192307E+09 | 72112318.90 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.114920E+09 | 59237339.45 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.120868E+09 | 46682579.08 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.115834E+09 | 36331673.54 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.129024E+09 | 29866610.41 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.137851E+09 | 32953947.47 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183028E+09 | 29344522.02 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276161E+09 | 46092022.90 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322196E+09 | 51190187.70 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349129E+09 | 61074065.58 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.252031E+10 | 0.608510E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.114920E+09 | 29344522.02 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349129E+09 | 77238264.48 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.330549E+09 | 77238264.48 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.248440E+09 | 66386907.17 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.192307E+09 | 72112318.90 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.114920E+09 | 59237339.45 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.120868E+09 | 46682579.08 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.115834E+09 | 36331673.54 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.129024E+09 | 29866610.41 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.137851E+09 | 32953947.47 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183028E+09 | 29344522.02 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276161E+09 | 46092022.90 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322196E+09 | 51190187.70 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349129E+09 | 61074065.58 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.252031E+10 | 0.608510E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.114920E+09 | 29344522.02 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349129E+09 | 77238264.48 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.394688E+09 | 91893149.05 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.296650E+09 | 78936587.06 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.229487E+09 | 85752570.16 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.136989E+09 | 70497175.43 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.143828E+09 | 55572047.60 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.137820E+09 | 43309261.46 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.153383E+09 | 35618119.52 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.163877E+09 | 39302849.17 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.218038E+09 | 35014375.69 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.329253E+09 | 54924874.50 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.384512E+09 | 60992446.94 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.416838E+09 | 72722167.32 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.300536E+10 | 0.724536E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.136989E+09 | 35014375.69 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.416838E+09 | 91893149.05 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.330608E+09 | 77088472.20 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.248486E+09 | 66301253.75 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.192338E+09 | 72065961.40 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.114964E+09 | 59173377.25 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.120860E+09 | 46857967.81 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.115811E+09 | 36568038.13 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.128947E+09 | 30307044.38 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.137792E+09 | 33355631.50 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.182931E+09 | 29856023.29 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276095E+09 | 46516795.95 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322191E+09 | 51330809.00 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349152E+09 | 61082490.19 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.252017E+10 | 0.610504E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.114964E+09 | 29856023.29 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349152E+09 | 77088472.20 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.330608E+09 | 77088472.20 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.248486E+09 | 66301253.75 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.192338E+09 | 72065961.40 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.114964E+09 | 59173377.25 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.120860E+09 | 46857967.81 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.115811E+09 | 36568038.13 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.128947E+09 | 30307044.38 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.137792E+09 | 33355631.50 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.182931E+09 | 29856023.29 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276095E+09 | 46516795.95 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322191E+09 | 51330809.00 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349152E+09 | 61082490.19 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.252017E+10 | 0.610504E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.114964E+09 | 29856023.29 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349152E+09 | 77088472.20 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.394760E+09 | 91715874.43 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.296705E+09 | 78835034.33 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.229526E+09 | 85697110.74 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.137042E+09 | 70421342.50 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.143818E+09 | 55779891.24 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.137791E+09 | 43587706.09 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.153290E+09 | 36140286.31 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.163806E+09 | 39779092.58 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.217922E+09 | 35621164.76 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.329173E+09 | 55429032.67 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.384505E+09 | 61159838.27 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.416866E+09 | 72731976.44 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.300520E+10 | 0.726898E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.137042E+09 | 35621164.76 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.416866E+09 | 91715874.43 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.330947E+09 | 76030165.32 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.248808E+09 | 65309638.34 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.192689E+09 | 70952727.81 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.115308E+09 | 58127197.06 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.121204E+09 | 45866397.39 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116143E+09 | 35622938.83 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.129268E+09 | 29361954.69 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.138114E+09 | 32353316.76 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183211E+09 | 28924346.53 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276381E+09 | 45533823.01 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322500E+09 | 50388184.50 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349473E+09 | 60062567.67 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.252405E+10 | 0.598533E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.115308E+09 | 28924346.53 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349473E+09 | 76030165.32 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.330947E+09 | 76030165.32 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.248808E+09 | 65309638.34 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.192689E+09 | 70952727.81 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.115308E+09 | 58127197.06 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.121204E+09 | 45866397.39 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116143E+09 | 35622938.83 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.129268E+09 | 29361954.69 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.138114E+09 | 32353316.76 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183211E+09 | 28924346.53 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276381E+09 | 45533823.01 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322500E+09 | 50388184.50 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349473E+09 | 60062567.67 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.252405E+10 | 0.598533E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.115308E+09 | 28924346.53 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349473E+09 | 76030165.32 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.395171E+09 | 90466191.70 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.297095E+09 | 77664886.78 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.229949E+09 | 84382875.94 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.137460E+09 | 69187401.21 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.144234E+09 | 54610556.66 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.138193E+09 | 42474985.44 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.153678E+09 | 35027559.99 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.164195E+09 | 38597420.73 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.218260E+09 | 34522104.26 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.329519E+09 | 54268879.43 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.384878E+09 | 60047101.65 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.417253E+09 | 71528322.92 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.300989E+10 | 0.712778E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.137460E+09 | 34522104.26 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.417253E+09 | 90466191.70 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.331410E+09 | 72666558.73 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.249442E+09 | 62204356.19 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193308E+09 | 67553539.96 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.115536E+09 | 54916021.66 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.120949E+09 | 42601987.61 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.115692E+09 | 32404636.85 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.128538E+09 | 26131284.09 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.137478E+09 | 28849080.20 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.182898E+09 | 25970314.64 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276182E+09 | 42316131.21 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322477E+09 | 47303719.66 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349715E+09 | 56789195.65 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.252362E+10 | 0.559707E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.115536E+09 | 25970314.64 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349715E+09 | 72666558.73 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.331410E+09 | 72666558.73 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.249442E+09 | 62204356.19 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193308E+09 | 67553539.96 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.115536E+09 | 54916021.66 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.120949E+09 | 42601987.61 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.115692E+09 | 32404636.85 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.128538E+09 | 26131284.09 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.137478E+09 | 28849080.20 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.182898E+09 | 25970314.64 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276182E+09 | 42316131.21 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322477E+09 | 47303719.66 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349715E+09 | 56789195.65 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.252362E+10 | 0.559707E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.115536E+09 | 25970314.64 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349715E+09 | 72666558.73 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.331410E+09 | 72666558.73 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.249442E+09 | 62204356.19 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193308E+09 | 67553539.96 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.115536E+09 | 54916021.66 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.120949E+09 | 42601987.61 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.115692E+09 | 32404636.85 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.128538E+09 | 26131284.09 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.137478E+09 | 28849080.20 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.182898E+09 | 25970314.64 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276182E+09 | 42316131.21 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322477E+09 | 47303719.66 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349715E+09 | 56789195.65 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.252362E+10 | 0.559707E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.115536E+09 | 25970314.64 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349715E+09 | 72666558.73 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.331410E+09 | 72666558.73 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.249442E+09 | 62204356.19 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193308E+09 | 67553539.96 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.115536E+09 | 54916021.66 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.120949E+09 | 42601987.61 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.115692E+09 | 32404636.85 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.128538E+09 | 26131284.09 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.137478E+09 | 28849080.20 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.182898E+09 | 25970314.64 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276182E+09 | 42316131.21 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322477E+09 | 47303719.66 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349715E+09 | 56789195.65 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.252362E+10 | 0.559707E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.115536E+09 | 25970314.64 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349715E+09 | 72666558.73 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.395738E+09 | 86484712.04 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.297862E+09 | 73988209.73 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.230713E+09 | 80351050.47 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.137770E+09 | 65375795.62 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.143985E+09 | 50743097.98 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.137718E+09 | 38663515.34 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.152878E+09 | 31201598.30 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.163506E+09 | 34441825.92 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.217928E+09 | 31008362.08 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.329314E+09 | 50444521.27 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.384882E+09 | 56390419.26 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.417562E+09 | 67650615.82 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.300986E+10 | 0.666744E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.137718E+09 | 31008362.08 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.417562E+09 | 86484712.04 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.395738E+09 | 86484712.04 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.297862E+09 | 73988209.73 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.230713E+09 | 80351050.47 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.137770E+09 | 65375795.62 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.143985E+09 | 50743097.98 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.137718E+09 | 38663515.34 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.152878E+09 | 31201598.30 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.163506E+09 | 34441825.92 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.217928E+09 | 31008362.08 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.329314E+09 | 50444521.27 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.384882E+09 | 56390419.26 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.417562E+09 | 67650615.82 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.300986E+10 | 0.666744E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.137718E+09 | 31008362.08 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.417562E+09 | 86484712.04 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.331318E+09 | 71646034.57 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.249438E+09 | 61237802.11 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193578E+09 | 66471019.41 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.116021E+09 | 53868963.76 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.121695E+09 | 41464944.30 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116481E+09 | 31189877.91 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.129511E+09 | 24838534.53 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.138465E+09 | 27515445.16 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183642E+09 | 24636140.99 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276640E+09 | 40998582.58 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322602E+09 | 46080852.37 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349634E+09 | 55592332.93 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.252902E+10 | 0.545541E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.116021E+09 | 24636140.99 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349634E+09 | 71646034.57 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.331318E+09 | 71646034.57 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.249438E+09 | 61237802.11 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193578E+09 | 66471019.41 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.116021E+09 | 53868963.76 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.121695E+09 | 41464944.30 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116481E+09 | 31189877.91 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.129511E+09 | 24838534.53 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.138465E+09 | 27515445.16 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183642E+09 | 24636140.99 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276640E+09 | 40998582.58 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322602E+09 | 46080852.37 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349634E+09 | 55592332.93 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.252902E+10 | 0.545541E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.116021E+09 | 24636140.99 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349634E+09 | 71646034.57 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.395689E+09 | 85264967.53 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.297907E+09 | 72833723.30 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.231068E+09 | 79058492.02 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.138368E+09 | 64127890.90 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.144890E+09 | 49389599.89 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.138671E+09 | 37224048.93 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.154047E+09 | 29669128.38 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.164688E+09 | 32860449.81 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.218834E+09 | 29424556.32 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.329899E+09 | 48878709.85 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.385082E+09 | 54933906.77 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.417529E+09 | 66221940.62 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.301667E+10 | 0.649887E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.138368E+09 | 29424556.32 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.417529E+09 | 85264967.53 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.331494E+09 | 71298043.30 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.249605E+09 | 60906086.40 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193745E+09 | 66114655.08 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.116181E+09 | 53555203.54 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.121866E+09 | 41182637.46 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116652E+09 | 30923629.62 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.129685E+09 | 24575537.55 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.138624E+09 | 27259358.25 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183794E+09 | 24367914.70 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276789E+09 | 40714192.75 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322771E+09 | 45774537.76 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349810E+09 | 55254270.10 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.253101E+10 | 0.541926E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.116181E+09 | 24367914.70 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349810E+09 | 71298043.30 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.331494E+09 | 71298043.30 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.249605E+09 | 60906086.40 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193745E+09 | 66114655.08 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.116181E+09 | 53555203.54 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.121866E+09 | 41182637.46 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116652E+09 | 30923629.62 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.129685E+09 | 24575537.55 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.138624E+09 | 27259358.25 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183794E+09 | 24367914.70 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276789E+09 | 40714192.75 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322771E+09 | 45774537.76 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349810E+09 | 55254270.10 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.253101E+10 | 0.541926E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.116181E+09 | 24367914.70 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349810E+09 | 71298043.30 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.395901E+09 | 84851406.54 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.298110E+09 | 72439394.21 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.231270E+09 | 78635322.93 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.138562E+09 | 63754571.26 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.145096E+09 | 49054695.38 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.138878E+09 | 36907140.31 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.154257E+09 | 29356404.20 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.164880E+09 | 32555813.28 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.219017E+09 | 29105494.42 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.330080E+09 | 48540351.79 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.385285E+09 | 54569710.42 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.417740E+09 | 65820825.20 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.301907E+10 | 0.645591E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.138562E+09 | 29105494.42 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.417740E+09 | 84851406.54 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.331643E+09 | 70795771.26 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.249750E+09 | 60396756.03 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193834E+09 | 65610288.99 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.116216E+09 | 53180928.17 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.121808E+09 | 41006809.86 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116579E+09 | 30795436.30 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.129543E+09 | 24561026.45 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.138446E+09 | 27291110.90 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183659E+09 | 24373699.33 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276682E+09 | 40670068.77 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322814E+09 | 45520985.70 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349906E+09 | 54878369.19 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.253088E+10 | 0.539081E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.116216E+09 | 24373699.33 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349906E+09 | 70795771.26 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.331643E+09 | 70795771.26 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.249750E+09 | 60396756.03 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193834E+09 | 65610288.99 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.116216E+09 | 53180928.17 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.121808E+09 | 41006809.86 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116579E+09 | 30795436.30 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.129543E+09 | 24561026.45 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.138446E+09 | 27291110.90 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183659E+09 | 24373699.33 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276682E+09 | 40670068.77 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322814E+09 | 45520985.70 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349906E+09 | 54878369.19 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.253088E+10 | 0.539081E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.116216E+09 | 24373699.33 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349906E+09 | 70795771.26 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.396078E+09 | 84262680.59 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.298284E+09 | 71843199.63 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.231377E+09 | 78045128.07 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.138604E+09 | 63318010.49 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.145024E+09 | 48853855.63 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.138789E+09 | 36762737.29 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.154085E+09 | 29347767.03 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.164664E+09 | 32602630.92 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.218854E+09 | 29121299.70 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.329949E+09 | 48496681.28 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.385333E+09 | 54276286.51 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.417855E+09 | 65381625.18 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.301890E+10 | 0.642312E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.138604E+09 | 29121299.70 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.417855E+09 | 84262680.59 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.330527E+09 | 69379574.19 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.248960E+09 | 58919991.41 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.192527E+09 | 64136883.10 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.114372E+09 | 52275278.73 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.119148E+09 | 41103531.32 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.113947E+09 | 31158418.64 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.126416E+09 | 25578675.87 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.135073E+09 | 28580735.44 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.181092E+09 | 25635545.44 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.273972E+09 | 41687615.08 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.321159E+09 | 45420705.43 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.348560E+09 | 54192313.26 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.250575E+10 | 0.538069E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.113947E+09 | 25578675.87 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.348560E+09 | 69379574.19 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.330527E+09 | 69379574.19 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.248960E+09 | 58919991.41 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.192527E+09 | 64136883.10 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.114372E+09 | 52275278.73 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.119148E+09 | 41103531.32 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.113947E+09 | 31158418.64 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.126416E+09 | 25578675.87 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.135073E+09 | 28580735.44 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.181092E+09 | 25635545.44 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.273972E+09 | 41687615.08 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.321159E+09 | 45420705.43 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.348560E+09 | 54192313.26 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.250575E+10 | 0.538069E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.113947E+09 | 25578675.87 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.348560E+09 | 69379574.19 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.394716E+09 | 82594544.29 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.297321E+09 | 70100964.76 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.229792E+09 | 76309796.48 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.136370E+09 | 62255130.44 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.141807E+09 | 48979835.79 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.135603E+09 | 37203175.50 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.150304E+09 | 30564112.02 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.160585E+09 | 34143441.17 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.215752E+09 | 30628495.63 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.326664E+09 | 49713930.29 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.383321E+09 | 54168453.77 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.416213E+09 | 64581059.04 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.298845E+10 | 0.641243E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.135603E+09 | 30564112.02 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.416213E+09 | 82594544.29 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 790.73 | 170.66 | 488.81 | 306.96 | 181.85 | 0.00 | 0.00 |
February | 658.24 | 162.12 | 414.05 | 220.72 | 193.33 | 0.00 | 0.00 |
March | 460.29 | 159.57 | 300.38 | 102.91 | 197.46 | 0.00 | 0.00 |
April | 283.35 | 133.74 | 194.23 | 18.71 | 175.52 | 0.00 | 0.00 |
May | 287.67 | 97.58 | 164.40 | 0.42 | 163.98 | 0.00 | 0.00 |
June | 284.21 | 75.81 | 162.62 | 0.00 | 162.62 | 0.00 | 0.00 |
July | 307.09 | 56.06 | 157.69 | 0.43 | 157.26 | 0.00 | 0.00 |
August | 326.87 | 64.16 | 172.50 | 10.59 | 161.90 | 0.00 | 0.00 |
September | 452.21 | 58.28 | 260.69 | 63.27 | 197.42 | 0.00 | 0.00 |
October | 659.81 | 93.89 | 369.58 | 178.48 | 191.11 | 0.00 | 0.00 |
November | 795.00 | 111.94 | 466.67 | 267.51 | 199.16 | 0.00 | 0.00 |
December | 834.51 | 131.39 | 504.98 | 325.37 | 179.61 | 0.00 | 0.00 |
Annual Sum or Average | 511.09 | 109.33 | 304.19 | 124.23 | 179.95 | 0.00 | 0.00 |
Minimum of Months | 283.35 | 56.06 | 157.69 | 0.00 | 157.26 | 0.00 | 0.00 |
Maximum of Months | 834.51 | 170.66 | 504.98 | 325.37 | 199.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 394.57 | 86.45 | 244.41 | 153.48 | 90.93 | 0.00 | 0.00 |
February | 328.68 | 81.96 | 207.02 | 110.36 | 96.66 | 0.00 | 0.00 |
March | 230.23 | 80.67 | 150.19 | 51.46 | 98.73 | 0.00 | 0.00 |
April | 142.02 | 67.49 | 97.11 | 9.35 | 87.76 | 0.00 | 0.00 |
May | 144.66 | 49.09 | 82.20 | 0.21 | 81.99 | 0.00 | 0.00 |
June | 143.17 | 37.80 | 81.31 | 0.00 | 81.31 | 0.00 | 0.00 |
July | 155.04 | 27.69 | 78.84 | 0.22 | 78.63 | 0.00 | 0.00 |
August | 165.08 | 31.61 | 86.25 | 5.30 | 80.95 | 0.00 | 0.00 |
September | 227.72 | 28.45 | 130.34 | 31.63 | 98.71 | 0.00 | 0.00 |
October | 330.61 | 46.96 | 184.79 | 89.24 | 95.55 | 0.00 | 0.00 |
November | 397.44 | 56.12 | 233.34 | 133.76 | 99.58 | 0.00 | 0.00 |
December | 416.68 | 66.27 | 252.49 | 162.68 | 89.80 | 0.00 | 0.00 |
Annual Sum or Average | 256.05 | 54.91 | 152.09 | 62.12 | 89.98 | 0.00 | 0.00 |
Minimum of Months | 142.02 | 27.69 | 78.84 | 0.00 | 78.63 | 0.00 | 0.00 |
Maximum of Months | 416.68 | 86.45 | 252.49 | 162.68 | 99.58 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 394.19 | 91.98 | 243.91 | 153.16 | 90.74 | 0.00 | 0.00 |
February | 328.01 | 87.51 | 206.60 | 110.13 | 96.47 | 0.00 | 0.00 |
March | 229.28 | 85.86 | 149.88 | 51.35 | 98.53 | 0.00 | 0.00 |
April | 141.52 | 72.91 | 96.91 | 9.33 | 87.58 | 0.00 | 0.00 |
May | 143.95 | 55.61 | 82.03 | 0.21 | 81.82 | 0.00 | 0.00 |
June | 142.55 | 44.74 | 81.14 | 0.00 | 81.14 | 0.00 | 0.00 |
July | 153.61 | 35.60 | 78.68 | 0.22 | 78.47 | 0.00 | 0.00 |
August | 164.12 | 39.28 | 86.07 | 5.29 | 80.78 | 0.00 | 0.00 |
September | 225.35 | 36.15 | 130.08 | 31.57 | 98.51 | 0.00 | 0.00 |
October | 329.14 | 54.92 | 184.41 | 89.05 | 95.36 | 0.00 | 0.00 |
November | 396.95 | 63.03 | 232.86 | 133.48 | 99.37 | 0.00 | 0.00 |
December | 416.33 | 72.76 | 251.97 | 162.35 | 89.62 | 0.00 | 0.00 |
Annual Sum or Average | 255.14 | 61.57 | 151.78 | 61.99 | 89.79 | 0.00 | 0.00 |
Minimum of Months | 141.52 | 35.60 | 78.68 | 0.00 | 78.47 | 0.00 | 0.00 |
Maximum of Months | 416.33 | 91.98 | 251.97 | 162.35 | 99.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 394.26 | 91.81 | 243.91 | 153.16 | 90.74 | 0.00 | 0.00 |
February | 328.07 | 87.40 | 206.60 | 110.13 | 96.47 | 0.00 | 0.00 |
March | 229.32 | 85.81 | 149.88 | 51.35 | 98.53 | 0.00 | 0.00 |
April | 141.58 | 72.83 | 96.91 | 9.33 | 87.58 | 0.00 | 0.00 |
May | 143.94 | 55.82 | 82.03 | 0.21 | 81.82 | 0.00 | 0.00 |
June | 142.52 | 45.03 | 81.14 | 0.00 | 81.14 | 0.00 | 0.00 |
July | 153.52 | 36.12 | 78.68 | 0.22 | 78.47 | 0.00 | 0.00 |
August | 164.05 | 39.76 | 86.07 | 5.29 | 80.78 | 0.00 | 0.00 |
September | 225.23 | 36.78 | 130.08 | 31.57 | 98.51 | 0.00 | 0.00 |
October | 329.06 | 55.43 | 184.41 | 89.05 | 95.36 | 0.00 | 0.00 |
November | 396.95 | 63.20 | 232.86 | 133.48 | 99.37 | 0.00 | 0.00 |
December | 416.36 | 72.77 | 251.97 | 162.35 | 89.62 | 0.00 | 0.00 |
Annual Sum or Average | 255.12 | 61.77 | 151.78 | 61.99 | 89.79 | 0.00 | 0.00 |
Minimum of Months | 141.58 | 36.12 | 78.68 | 0.00 | 78.47 | 0.00 | 0.00 |
Maximum of Months | 416.36 | 91.81 | 251.97 | 162.35 | 99.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 394.66 | 90.55 | 243.91 | 153.16 | 90.74 | 0.00 | 0.00 |
February | 328.50 | 86.10 | 206.60 | 110.13 | 96.47 | 0.00 | 0.00 |
March | 229.74 | 84.49 | 149.88 | 51.35 | 98.53 | 0.00 | 0.00 |
April | 142.00 | 71.54 | 96.91 | 9.33 | 87.58 | 0.00 | 0.00 |
May | 144.36 | 54.64 | 82.03 | 0.21 | 81.82 | 0.00 | 0.00 |
June | 142.93 | 43.87 | 81.14 | 0.00 | 81.14 | 0.00 | 0.00 |
July | 153.90 | 35.00 | 78.68 | 0.22 | 78.47 | 0.00 | 0.00 |
August | 164.44 | 38.57 | 86.07 | 5.29 | 80.78 | 0.00 | 0.00 |
September | 225.57 | 35.64 | 130.08 | 31.57 | 98.51 | 0.00 | 0.00 |
October | 329.41 | 54.26 | 184.41 | 89.05 | 95.36 | 0.00 | 0.00 |
November | 397.33 | 62.05 | 232.86 | 133.48 | 99.37 | 0.00 | 0.00 |
December | 416.74 | 71.56 | 251.97 | 162.35 | 89.62 | 0.00 | 0.00 |
Annual Sum or Average | 255.52 | 60.56 | 151.78 | 61.99 | 89.79 | 0.00 | 0.00 |
Minimum of Months | 142.00 | 35.00 | 78.68 | 0.00 | 78.47 | 0.00 | 0.00 |
Maximum of Months | 416.74 | 90.55 | 251.97 | 162.35 | 99.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 790.44 | 173.10 | 487.81 | 306.33 | 181.48 | 0.00 | 0.00 |
February | 658.69 | 164.02 | 413.20 | 220.26 | 192.93 | 0.00 | 0.00 |
March | 460.97 | 160.89 | 299.76 | 102.70 | 197.06 | 0.00 | 0.00 |
April | 284.60 | 135.19 | 193.83 | 18.67 | 175.16 | 0.00 | 0.00 |
May | 288.14 | 101.51 | 164.07 | 0.42 | 163.64 | 0.00 | 0.00 |
June | 284.80 | 79.84 | 162.29 | 0.00 | 162.29 | 0.00 | 0.00 |
July | 306.12 | 62.32 | 157.36 | 0.43 | 156.93 | 0.00 | 0.00 |
August | 327.41 | 68.80 | 172.14 | 10.57 | 161.57 | 0.00 | 0.00 |
September | 450.40 | 64.00 | 260.15 | 63.14 | 197.01 | 0.00 | 0.00 |
October | 658.36 | 100.86 | 368.82 | 178.11 | 190.71 | 0.00 | 0.00 |
November | 794.63 | 116.51 | 465.71 | 266.96 | 198.75 | 0.00 | 0.00 |
December | 834.07 | 135.33 | 503.94 | 324.70 | 179.24 | 0.00 | 0.00 |
Annual Sum or Average | 510.98 | 113.28 | 303.56 | 123.98 | 179.58 | 0.00 | 0.00 |
Minimum of Months | 284.60 | 62.32 | 157.36 | 0.00 | 156.93 | 0.00 | 0.00 |
Maximum of Months | 834.07 | 173.10 | 503.94 | 324.70 | 198.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 395.13 | 85.33 | 243.91 | 153.16 | 90.74 | 0.00 | 0.00 |
February | 329.36 | 80.73 | 206.60 | 110.13 | 96.47 | 0.00 | 0.00 |
March | 230.82 | 79.15 | 149.88 | 51.35 | 98.53 | 0.00 | 0.00 |
April | 142.91 | 66.31 | 96.91 | 9.33 | 87.58 | 0.00 | 0.00 |
May | 144.97 | 49.40 | 82.03 | 0.21 | 81.82 | 0.00 | 0.00 |
June | 143.38 | 38.43 | 81.14 | 0.00 | 81.14 | 0.00 | 0.00 |
July | 154.22 | 29.62 | 78.68 | 0.22 | 78.47 | 0.00 | 0.00 |
August | 164.88 | 32.81 | 86.07 | 5.29 | 80.78 | 0.00 | 0.00 |
September | 226.13 | 30.36 | 130.08 | 31.57 | 98.51 | 0.00 | 0.00 |
October | 329.74 | 48.86 | 184.41 | 89.05 | 95.36 | 0.00 | 0.00 |
November | 397.49 | 56.75 | 232.86 | 133.48 | 99.37 | 0.00 | 0.00 |
December | 416.96 | 66.24 | 251.97 | 162.35 | 89.62 | 0.00 | 0.00 |
Annual Sum or Average | 256.05 | 55.21 | 151.78 | 61.99 | 89.79 | 0.00 | 0.00 |
Minimum of Months | 142.91 | 29.62 | 78.68 | 0.00 | 78.47 | 0.00 | 0.00 |
Maximum of Months | 416.96 | 85.33 | 251.97 | 162.35 | 99.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 395.34 | 84.92 | 243.91 | 153.16 | 90.74 | 0.00 | 0.00 |
February | 329.58 | 80.30 | 206.60 | 110.13 | 96.47 | 0.00 | 0.00 |
March | 231.02 | 78.73 | 149.88 | 51.35 | 98.53 | 0.00 | 0.00 |
April | 143.10 | 65.92 | 96.91 | 9.33 | 87.58 | 0.00 | 0.00 |
May | 145.17 | 49.07 | 82.03 | 0.21 | 81.82 | 0.00 | 0.00 |
June | 143.59 | 38.10 | 81.14 | 0.00 | 81.14 | 0.00 | 0.00 |
July | 154.43 | 29.31 | 78.68 | 0.22 | 78.47 | 0.00 | 0.00 |
August | 165.07 | 32.51 | 86.07 | 5.29 | 80.78 | 0.00 | 0.00 |
September | 226.31 | 30.03 | 130.08 | 31.57 | 98.51 | 0.00 | 0.00 |
October | 329.92 | 48.52 | 184.41 | 89.05 | 95.36 | 0.00 | 0.00 |
November | 397.70 | 56.37 | 232.86 | 133.48 | 99.37 | 0.00 | 0.00 |
December | 417.17 | 65.83 | 251.97 | 162.35 | 89.62 | 0.00 | 0.00 |
Annual Sum or Average | 256.25 | 54.84 | 151.78 | 61.99 | 89.79 | 0.00 | 0.00 |
Minimum of Months | 143.10 | 29.31 | 78.68 | 0.00 | 78.47 | 0.00 | 0.00 |
Maximum of Months | 417.17 | 84.92 | 251.97 | 162.35 | 99.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 395.52 | 84.32 | 243.91 | 153.16 | 90.74 | 0.00 | 0.00 |
February | 329.77 | 79.63 | 206.60 | 110.13 | 96.47 | 0.00 | 0.00 |
March | 231.12 | 78.13 | 149.88 | 51.35 | 98.53 | 0.00 | 0.00 |
April | 143.15 | 65.46 | 96.91 | 9.33 | 87.58 | 0.00 | 0.00 |
May | 145.10 | 48.86 | 82.03 | 0.21 | 81.82 | 0.00 | 0.00 |
June | 143.50 | 37.95 | 81.14 | 0.00 | 81.14 | 0.00 | 0.00 |
July | 154.26 | 29.30 | 78.68 | 0.22 | 78.47 | 0.00 | 0.00 |
August | 164.86 | 32.55 | 86.07 | 5.29 | 80.78 | 0.00 | 0.00 |
September | 226.15 | 30.04 | 130.08 | 31.57 | 98.51 | 0.00 | 0.00 |
October | 329.79 | 48.48 | 184.41 | 89.05 | 95.36 | 0.00 | 0.00 |
November | 397.75 | 56.06 | 232.86 | 133.48 | 99.37 | 0.00 | 0.00 |
December | 417.29 | 65.39 | 251.97 | 162.35 | 89.62 | 0.00 | 0.00 |
Annual Sum or Average | 256.24 | 54.56 | 151.78 | 61.99 | 89.79 | 0.00 | 0.00 |
Minimum of Months | 143.15 | 29.30 | 78.68 | 0.00 | 78.47 | 0.00 | 0.00 |
Maximum of Months | 417.29 | 84.32 | 251.97 | 162.35 | 99.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 394.18 | 82.64 | 243.91 | 153.16 | 90.74 | 0.00 | 0.00 |
February | 328.72 | 77.69 | 206.60 | 110.13 | 96.47 | 0.00 | 0.00 |
March | 229.56 | 76.38 | 149.88 | 51.35 | 98.53 | 0.00 | 0.00 |
April | 140.86 | 64.35 | 96.91 | 9.33 | 87.58 | 0.00 | 0.00 |
May | 141.91 | 48.98 | 82.03 | 0.21 | 81.82 | 0.00 | 0.00 |
June | 140.24 | 38.39 | 81.14 | 0.00 | 81.14 | 0.00 | 0.00 |
July | 150.51 | 30.51 | 78.68 | 0.22 | 78.47 | 0.00 | 0.00 |
August | 160.82 | 34.09 | 86.07 | 5.29 | 80.78 | 0.00 | 0.00 |
September | 222.97 | 31.60 | 130.08 | 31.57 | 98.51 | 0.00 | 0.00 |
October | 326.54 | 49.69 | 184.41 | 89.05 | 95.36 | 0.00 | 0.00 |
November | 395.69 | 55.95 | 232.86 | 133.48 | 99.37 | 0.00 | 0.00 |
December | 415.67 | 64.58 | 251.97 | 162.35 | 89.62 | 0.00 | 0.00 |
Annual Sum or Average | 253.68 | 54.46 | 151.78 | 61.99 | 89.79 | 0.00 | 0.00 |
Minimum of Months | 140.24 | 30.51 | 78.68 | 0.00 | 78.47 | 0.00 | 0.00 |
Maximum of Months | 415.67 | 82.64 | 251.97 | 162.35 | 99.37 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.211790E+10 | 0.457107E+09 | 0.130924E+10 | 0.822161E+09 | 0.487080E+09 | 0.00 | 0.00 |
February | 0.159242E+10 | 0.392210E+09 | 0.100166E+10 | 0.533957E+09 | 0.467703E+09 | 0.00 | 0.00 |
March | 0.123283E+10 | 0.427397E+09 | 0.804525E+09 | 0.275644E+09 | 0.528881E+09 | 0.00 | 0.00 |
April | 0.734438E+09 | 0.346652E+09 | 0.503438E+09 | 48485003.77 | 0.454953E+09 | 0.00 | 0.00 |
May | 0.770501E+09 | 0.261367E+09 | 0.440342E+09 | 1136946.20 | 0.439205E+09 | 0.00 | 0.00 |
June | 0.736662E+09 | 0.196512E+09 | 0.421520E+09 | 0.00 | 0.421520E+09 | 0.00 | 0.00 |
July | 0.822503E+09 | 0.150147E+09 | 0.422347E+09 | 1154617.08 | 0.421192E+09 | 0.00 | 0.00 |
August | 0.875481E+09 | 0.171854E+09 | 0.462011E+09 | 28372230.32 | 0.433639E+09 | 0.00 | 0.00 |
September | 0.117213E+10 | 0.151073E+09 | 0.675696E+09 | 0.163986E+09 | 0.511711E+09 | 0.00 | 0.00 |
October | 0.176723E+10 | 0.251486E+09 | 0.989888E+09 | 0.478029E+09 | 0.511859E+09 | 0.00 | 0.00 |
November | 0.206064E+10 | 0.290136E+09 | 0.120961E+10 | 0.693393E+09 | 0.516218E+09 | 0.00 | 0.00 |
December | 0.223515E+10 | 0.351915E+09 | 0.135253E+10 | 0.871468E+09 | 0.481060E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.161179E+11 | 0.344786E+10 | 0.959281E+10 | 0.391779E+10 | 0.567502E+10 | 0.00 | 0.00 |
Minimum of Months | 0.734438E+09 | 0.150147E+09 | 0.421520E+09 | 0.00 | 0.421192E+09 | 0.00 | 0.00 |
Maximum of Months | 0.223515E+10 | 0.457107E+09 | 0.135253E+10 | 0.871468E+09 | 0.528881E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105681E+10 | 0.231547E+09 | 0.654621E+09 | 0.411081E+09 | 0.243540E+09 | 0.00 | 0.00 |
February | 0.795149E+09 | 0.198281E+09 | 0.500830E+09 | 0.266978E+09 | 0.233852E+09 | 0.00 | 0.00 |
March | 0.616642E+09 | 0.216061E+09 | 0.402263E+09 | 0.137822E+09 | 0.264441E+09 | 0.00 | 0.00 |
April | 0.368121E+09 | 0.174923E+09 | 0.251719E+09 | 24242501.89 | 0.227476E+09 | 0.00 | 0.00 |
May | 0.387449E+09 | 0.131479E+09 | 0.220171E+09 | 568473.10 | 0.219602E+09 | 0.00 | 0.00 |
June | 0.371090E+09 | 97979298.02 | 0.210760E+09 | 0.00 | 0.210760E+09 | 0.00 | 0.00 |
July | 0.415254E+09 | 74161540.32 | 0.211173E+09 | 577308.54 | 0.210596E+09 | 0.00 | 0.00 |
August | 0.442163E+09 | 84674524.64 | 0.231006E+09 | 14186115.16 | 0.216820E+09 | 0.00 | 0.00 |
September | 0.590252E+09 | 73736057.72 | 0.337848E+09 | 81992791.92 | 0.255855E+09 | 0.00 | 0.00 |
October | 0.885510E+09 | 0.125779E+09 | 0.494944E+09 | 0.239014E+09 | 0.255930E+09 | 0.00 | 0.00 |
November | 0.103018E+10 | 0.145473E+09 | 0.604806E+09 | 0.346697E+09 | 0.258109E+09 | 0.00 | 0.00 |
December | 0.111605E+10 | 0.177496E+09 | 0.676264E+09 | 0.435734E+09 | 0.240530E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.807466E+10 | 0.173159E+10 | 0.479640E+10 | 0.195889E+10 | 0.283751E+10 | 0.00 | 0.00 |
Minimum of Months | 0.368121E+09 | 73736057.72 | 0.210760E+09 | 0.00 | 0.210596E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111605E+10 | 0.231547E+09 | 0.676264E+09 | 0.435734E+09 | 0.264441E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105579E+10 | 0.246370E+09 | 0.653277E+09 | 0.410236E+09 | 0.243040E+09 | 0.00 | 0.00 |
February | 0.793531E+09 | 0.211710E+09 | 0.499802E+09 | 0.266430E+09 | 0.233371E+09 | 0.00 | 0.00 |
March | 0.614100E+09 | 0.229977E+09 | 0.401437E+09 | 0.137539E+09 | 0.263898E+09 | 0.00 | 0.00 |
April | 0.366829E+09 | 0.188972E+09 | 0.251202E+09 | 24192722.62 | 0.227009E+09 | 0.00 | 0.00 |
May | 0.385564E+09 | 0.148937E+09 | 0.219719E+09 | 567305.80 | 0.219152E+09 | 0.00 | 0.00 |
June | 0.369488E+09 | 0.115973E+09 | 0.210327E+09 | 0.00 | 0.210327E+09 | 0.00 | 0.00 |
July | 0.411430E+09 | 95351306.93 | 0.210740E+09 | 576123.10 | 0.210164E+09 | 0.00 | 0.00 |
August | 0.439579E+09 | 0.105211E+09 | 0.230531E+09 | 14156985.56 | 0.216374E+09 | 0.00 | 0.00 |
September | 0.584095E+09 | 93703270.20 | 0.337154E+09 | 81824428.90 | 0.255330E+09 | 0.00 | 0.00 |
October | 0.881574E+09 | 0.147109E+09 | 0.493928E+09 | 0.238523E+09 | 0.255404E+09 | 0.00 | 0.00 |
November | 0.102890E+10 | 0.163373E+09 | 0.603564E+09 | 0.345985E+09 | 0.257579E+09 | 0.00 | 0.00 |
December | 0.111510E+10 | 0.194870E+09 | 0.674875E+09 | 0.434839E+09 | 0.240036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.804598E+10 | 0.194156E+10 | 0.478656E+10 | 0.195487E+10 | 0.283168E+10 | 0.00 | 0.00 |
Minimum of Months | 0.366829E+09 | 93703270.20 | 0.210327E+09 | 0.00 | 0.210164E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111510E+10 | 0.246370E+09 | 0.674875E+09 | 0.434839E+09 | 0.263898E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105598E+10 | 0.245893E+09 | 0.653277E+09 | 0.410236E+09 | 0.243040E+09 | 0.00 | 0.00 |
February | 0.793676E+09 | 0.211438E+09 | 0.499802E+09 | 0.266430E+09 | 0.233371E+09 | 0.00 | 0.00 |
March | 0.614201E+09 | 0.229829E+09 | 0.401437E+09 | 0.137539E+09 | 0.263898E+09 | 0.00 | 0.00 |
April | 0.366970E+09 | 0.188768E+09 | 0.251202E+09 | 24192722.62 | 0.227009E+09 | 0.00 | 0.00 |
May | 0.385539E+09 | 0.149496E+09 | 0.219719E+09 | 567305.80 | 0.219152E+09 | 0.00 | 0.00 |
June | 0.369412E+09 | 0.116724E+09 | 0.210327E+09 | 0.00 | 0.210327E+09 | 0.00 | 0.00 |
July | 0.411184E+09 | 96754346.93 | 0.210740E+09 | 576123.10 | 0.210164E+09 | 0.00 | 0.00 |
August | 0.439390E+09 | 0.106490E+09 | 0.230531E+09 | 14156985.56 | 0.216374E+09 | 0.00 | 0.00 |
September | 0.583785E+09 | 95333145.37 | 0.337154E+09 | 81824428.90 | 0.255330E+09 | 0.00 | 0.00 |
October | 0.881363E+09 | 0.148463E+09 | 0.493928E+09 | 0.238523E+09 | 0.255404E+09 | 0.00 | 0.00 |
November | 0.102889E+10 | 0.163821E+09 | 0.603564E+09 | 0.345985E+09 | 0.257579E+09 | 0.00 | 0.00 |
December | 0.111517E+10 | 0.194897E+09 | 0.674875E+09 | 0.434839E+09 | 0.240036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.804555E+10 | 0.194791E+10 | 0.478656E+10 | 0.195487E+10 | 0.283168E+10 | 0.00 | 0.00 |
Minimum of Months | 0.366970E+09 | 95333145.37 | 0.210327E+09 | 0.00 | 0.210164E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111517E+10 | 0.245893E+09 | 0.674875E+09 | 0.434839E+09 | 0.263898E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105707E+10 | 0.242527E+09 | 0.653277E+09 | 0.410236E+09 | 0.243040E+09 | 0.00 | 0.00 |
February | 0.794712E+09 | 0.208284E+09 | 0.499802E+09 | 0.266430E+09 | 0.233371E+09 | 0.00 | 0.00 |
March | 0.615327E+09 | 0.226288E+09 | 0.401437E+09 | 0.137539E+09 | 0.263898E+09 | 0.00 | 0.00 |
April | 0.368077E+09 | 0.185442E+09 | 0.251202E+09 | 24192722.62 | 0.227009E+09 | 0.00 | 0.00 |
May | 0.386642E+09 | 0.146343E+09 | 0.219719E+09 | 567305.80 | 0.219152E+09 | 0.00 | 0.00 |
June | 0.370478E+09 | 0.113721E+09 | 0.210327E+09 | 0.00 | 0.210327E+09 | 0.00 | 0.00 |
July | 0.412214E+09 | 93751137.00 | 0.210740E+09 | 576123.10 | 0.210164E+09 | 0.00 | 0.00 |
August | 0.440423E+09 | 0.103304E+09 | 0.230531E+09 | 14156985.56 | 0.216374E+09 | 0.00 | 0.00 |
September | 0.584682E+09 | 92370392.23 | 0.337154E+09 | 81824428.90 | 0.255330E+09 | 0.00 | 0.00 |
October | 0.882280E+09 | 0.145336E+09 | 0.493928E+09 | 0.238523E+09 | 0.255404E+09 | 0.00 | 0.00 |
November | 0.102988E+10 | 0.160823E+09 | 0.603564E+09 | 0.345985E+09 | 0.257579E+09 | 0.00 | 0.00 |
December | 0.111620E+10 | 0.191653E+09 | 0.674875E+09 | 0.434839E+09 | 0.240036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.805798E+10 | 0.190984E+10 | 0.478656E+10 | 0.195487E+10 | 0.283168E+10 | 0.00 | 0.00 |
Minimum of Months | 0.368077E+09 | 92370392.23 | 0.210327E+09 | 0.00 | 0.210164E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111620E+10 | 0.242527E+09 | 0.674875E+09 | 0.434839E+09 | 0.263898E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.211712E+10 | 0.463636E+09 | 0.130655E+10 | 0.820473E+09 | 0.486080E+09 | 0.00 | 0.00 |
February | 0.159349E+10 | 0.396794E+09 | 0.999603E+09 | 0.532861E+09 | 0.466743E+09 | 0.00 | 0.00 |
March | 0.123466E+10 | 0.430916E+09 | 0.802873E+09 | 0.275078E+09 | 0.527795E+09 | 0.00 | 0.00 |
April | 0.737682E+09 | 0.350415E+09 | 0.502404E+09 | 48385445.24 | 0.454018E+09 | 0.00 | 0.00 |
May | 0.771764E+09 | 0.271894E+09 | 0.439438E+09 | 1134611.60 | 0.438303E+09 | 0.00 | 0.00 |
June | 0.738205E+09 | 0.206945E+09 | 0.420654E+09 | 0.00 | 0.420654E+09 | 0.00 | 0.00 |
July | 0.819908E+09 | 0.166928E+09 | 0.421479E+09 | 1152246.21 | 0.420327E+09 | 0.00 | 0.00 |
August | 0.876923E+09 | 0.184280E+09 | 0.461063E+09 | 28313971.12 | 0.432749E+09 | 0.00 | 0.00 |
September | 0.116745E+10 | 0.165897E+09 | 0.674309E+09 | 0.163649E+09 | 0.510660E+09 | 0.00 | 0.00 |
October | 0.176335E+10 | 0.270154E+09 | 0.987855E+09 | 0.477047E+09 | 0.510808E+09 | 0.00 | 0.00 |
November | 0.205967E+10 | 0.301996E+09 | 0.120713E+10 | 0.691970E+09 | 0.515158E+09 | 0.00 | 0.00 |
December | 0.223398E+10 | 0.362458E+09 | 0.134975E+10 | 0.869679E+09 | 0.480072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.161142E+11 | 0.357231E+10 | 0.957311E+10 | 0.390974E+10 | 0.566337E+10 | 0.00 | 0.00 |
Minimum of Months | 0.737682E+09 | 0.165897E+09 | 0.420654E+09 | 0.00 | 0.420327E+09 | 0.00 | 0.00 |
Maximum of Months | 0.223398E+10 | 0.463636E+09 | 0.134975E+10 | 0.869679E+09 | 0.527795E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105833E+10 | 0.228557E+09 | 0.653277E+09 | 0.410236E+09 | 0.243040E+09 | 0.00 | 0.00 |
February | 0.796782E+09 | 0.195309E+09 | 0.499802E+09 | 0.266430E+09 | 0.233371E+09 | 0.00 | 0.00 |
March | 0.618224E+09 | 0.212001E+09 | 0.401437E+09 | 0.137539E+09 | 0.263898E+09 | 0.00 | 0.00 |
April | 0.370410E+09 | 0.171866E+09 | 0.251202E+09 | 24192722.62 | 0.227009E+09 | 0.00 | 0.00 |
May | 0.388280E+09 | 0.132319E+09 | 0.219719E+09 | 567305.80 | 0.219152E+09 | 0.00 | 0.00 |
June | 0.371633E+09 | 99603777.00 | 0.210327E+09 | 0.00 | 0.210327E+09 | 0.00 | 0.00 |
July | 0.413068E+09 | 79346060.78 | 0.210740E+09 | 576123.10 | 0.210164E+09 | 0.00 | 0.00 |
August | 0.441618E+09 | 87890999.06 | 0.230531E+09 | 14156985.56 | 0.216374E+09 | 0.00 | 0.00 |
September | 0.586118E+09 | 78696663.08 | 0.337154E+09 | 81824428.90 | 0.255330E+09 | 0.00 | 0.00 |
October | 0.883179E+09 | 0.130876E+09 | 0.493928E+09 | 0.238523E+09 | 0.255404E+09 | 0.00 | 0.00 |
November | 0.103029E+10 | 0.147096E+09 | 0.603564E+09 | 0.345985E+09 | 0.257579E+09 | 0.00 | 0.00 |
December | 0.111680E+10 | 0.177406E+09 | 0.674875E+09 | 0.434839E+09 | 0.240036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.807472E+10 | 0.174097E+10 | 0.478656E+10 | 0.195487E+10 | 0.283168E+10 | 0.00 | 0.00 |
Minimum of Months | 0.370410E+09 | 78696663.08 | 0.210327E+09 | 0.00 | 0.210164E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111680E+10 | 0.228557E+09 | 0.674875E+09 | 0.434839E+09 | 0.263898E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105889E+10 | 0.227447E+09 | 0.653277E+09 | 0.410236E+09 | 0.243040E+09 | 0.00 | 0.00 |
February | 0.797320E+09 | 0.194252E+09 | 0.499802E+09 | 0.266430E+09 | 0.233371E+09 | 0.00 | 0.00 |
March | 0.618759E+09 | 0.210865E+09 | 0.401437E+09 | 0.137539E+09 | 0.263898E+09 | 0.00 | 0.00 |
April | 0.370923E+09 | 0.170865E+09 | 0.251202E+09 | 24192722.62 | 0.227009E+09 | 0.00 | 0.00 |
May | 0.388828E+09 | 0.131420E+09 | 0.219719E+09 | 567305.80 | 0.219152E+09 | 0.00 | 0.00 |
June | 0.372181E+09 | 98754397.18 | 0.210327E+09 | 0.00 | 0.210327E+09 | 0.00 | 0.00 |
July | 0.413626E+09 | 78507390.03 | 0.210740E+09 | 576123.10 | 0.210164E+09 | 0.00 | 0.00 |
August | 0.442127E+09 | 87074479.25 | 0.230531E+09 | 14156985.56 | 0.216374E+09 | 0.00 | 0.00 |
September | 0.586604E+09 | 77841275.81 | 0.337154E+09 | 81824428.90 | 0.255330E+09 | 0.00 | 0.00 |
October | 0.883658E+09 | 0.129969E+09 | 0.493928E+09 | 0.238523E+09 | 0.255404E+09 | 0.00 | 0.00 |
November | 0.103083E+10 | 0.146119E+09 | 0.603564E+09 | 0.345985E+09 | 0.257579E+09 | 0.00 | 0.00 |
December | 0.111736E+10 | 0.176329E+09 | 0.674875E+09 | 0.434839E+09 | 0.240036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.808110E+10 | 0.172944E+10 | 0.478656E+10 | 0.195487E+10 | 0.283168E+10 | 0.00 | 0.00 |
Minimum of Months | 0.370923E+09 | 77841275.81 | 0.210327E+09 | 0.00 | 0.210164E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111736E+10 | 0.227447E+09 | 0.674875E+09 | 0.434839E+09 | 0.263898E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105936E+10 | 0.225854E+09 | 0.653277E+09 | 0.410236E+09 | 0.243040E+09 | 0.00 | 0.00 |
February | 0.797784E+09 | 0.192637E+09 | 0.499802E+09 | 0.266430E+09 | 0.233371E+09 | 0.00 | 0.00 |
March | 0.619045E+09 | 0.209266E+09 | 0.401437E+09 | 0.137539E+09 | 0.263898E+09 | 0.00 | 0.00 |
April | 0.371035E+09 | 0.169680E+09 | 0.251202E+09 | 24192722.62 | 0.227009E+09 | 0.00 | 0.00 |
May | 0.388640E+09 | 0.130867E+09 | 0.219719E+09 | 567305.80 | 0.219152E+09 | 0.00 | 0.00 |
June | 0.371947E+09 | 98353609.88 | 0.210327E+09 | 0.00 | 0.210327E+09 | 0.00 | 0.00 |
July | 0.413172E+09 | 78469656.22 | 0.210740E+09 | 576123.10 | 0.210164E+09 | 0.00 | 0.00 |
August | 0.441555E+09 | 87184384.29 | 0.230531E+09 | 14156985.56 | 0.216374E+09 | 0.00 | 0.00 |
September | 0.586172E+09 | 77868501.96 | 0.337154E+09 | 81824428.90 | 0.255330E+09 | 0.00 | 0.00 |
October | 0.883313E+09 | 0.129837E+09 | 0.493928E+09 | 0.238523E+09 | 0.255404E+09 | 0.00 | 0.00 |
November | 0.103096E+10 | 0.145318E+09 | 0.603564E+09 | 0.345985E+09 | 0.257579E+09 | 0.00 | 0.00 |
December | 0.111767E+10 | 0.175138E+09 | 0.674875E+09 | 0.434839E+09 | 0.240036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.808066E+10 | 0.172047E+10 | 0.478656E+10 | 0.195487E+10 | 0.283168E+10 | 0.00 | 0.00 |
Minimum of Months | 0.371035E+09 | 77868501.96 | 0.210327E+09 | 0.00 | 0.210164E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111767E+10 | 0.225854E+09 | 0.674875E+09 | 0.434839E+09 | 0.263898E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105577E+10 | 0.221354E+09 | 0.653277E+09 | 0.410236E+09 | 0.243040E+09 | 0.00 | 0.00 |
February | 0.795240E+09 | 0.187941E+09 | 0.499802E+09 | 0.266430E+09 | 0.233371E+09 | 0.00 | 0.00 |
March | 0.614846E+09 | 0.204584E+09 | 0.401437E+09 | 0.137539E+09 | 0.263898E+09 | 0.00 | 0.00 |
April | 0.365115E+09 | 0.166806E+09 | 0.251202E+09 | 24192722.62 | 0.227009E+09 | 0.00 | 0.00 |
May | 0.380103E+09 | 0.131187E+09 | 0.219719E+09 | 567305.80 | 0.219152E+09 | 0.00 | 0.00 |
June | 0.363498E+09 | 99519731.41 | 0.210327E+09 | 0.00 | 0.210327E+09 | 0.00 | 0.00 |
July | 0.403135E+09 | 81721316.96 | 0.210740E+09 | 576123.10 | 0.210164E+09 | 0.00 | 0.00 |
August | 0.430730E+09 | 91304045.47 | 0.230531E+09 | 14156985.56 | 0.216374E+09 | 0.00 | 0.00 |
September | 0.577936E+09 | 81899128.46 | 0.337154E+09 | 81824428.90 | 0.255330E+09 | 0.00 | 0.00 |
October | 0.874608E+09 | 0.133089E+09 | 0.493928E+09 | 0.238523E+09 | 0.255404E+09 | 0.00 | 0.00 |
November | 0.102564E+10 | 0.145010E+09 | 0.603564E+09 | 0.345985E+09 | 0.257579E+09 | 0.00 | 0.00 |
December | 0.111333E+10 | 0.172966E+09 | 0.674875E+09 | 0.434839E+09 | 0.240036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.799995E+10 | 0.171738E+10 | 0.478656E+10 | 0.195487E+10 | 0.283168E+10 | 0.00 | 0.00 |
Minimum of Months | 0.363498E+09 | 81721316.96 | 0.210327E+09 | 0.00 | 0.210164E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111333E+10 | 0.221354E+09 | 0.674875E+09 | 0.434839E+09 | 0.263898E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 22.49 | 18.25 | 15.90 | 4.15 | 13.31 | 59.87 | 181.51 | 0.00 |
February | 22.80 | 19.74 | 18.20 | 3.70 | 14.21 | 74.30 | 182.84 | 0.03 |
March | 23.17 | 18.99 | 16.85 | 4.23 | 14.23 | 89.51 | 186.76 | 0.02 |
April | 23.76 | 19.01 | 16.50 | 4.83 | 14.94 | 95.22 | 199.35 | 0.00 |
May | 25.23 | 20.49 | 18.23 | 4.38 | 17.08 | 98.73 | 213.00 | 0.00 |
June | 25.87 | 20.89 | 18.70 | 5.87 | 17.20 | 99.16 | 227.55 | 0.00 |
July | 26.90 | 21.77 | 19.49 | 5.98 | 18.80 | 89.26 | 241.04 | 0.00 |
August | 27.06 | 21.88 | 19.61 | 5.21 | 18.26 | 83.09 | 253.22 | 0.00 |
September | 26.87 | 22.30 | 20.37 | 5.44 | 18.71 | 93.82 | 214.78 | 0.00 |
October | 26.22 | 21.67 | 19.68 | 3.78 | 17.26 | 74.41 | 199.79 | 0.00 |
November | 24.76 | 20.57 | 18.62 | 5.17 | 16.20 | 67.97 | 175.93 | 0.00 |
December | 23.69 | 19.64 | 17.67 | 4.42 | 14.96 | 56.37 | 177.80 | 0.00 |
Annual Sum or Average | 24.91 | 20.44 | 18.32 | 4.77 | 16.27 | 81.79 | 204.64 | 0.00 |
Minimum of Months | 22.49 | 18.25 | 15.90 | 3.70 | 13.31 | 56.37 | 175.93 | 0.00 |
Maximum of Months | 27.06 | 22.30 | 20.37 | 5.98 | 18.80 | 99.16 | 253.22 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.40 | 03-JAN-12:00 | 22.05 | 18.90 | 3.60 | 19.35 | 145.50 | 575.00 |
February | 28.90 | 19-FEB-10:00 | 22.34 | 19.40 | 3.10 | 18.28 | 204.00 | 595.50 |
March | 30.00 | 29-MAR-12:00 | 20.05 | 15.00 | 6.70 | 20.22 | 350.50 | 543.50 |
April | 30.00 | 09-APR-13:00 | 20.06 | 15.00 | 7.20 | 17.39 | 126.00 | 778.50 |
May | 31.10 | 17-MAY-13:20 | 21.31 | 16.70 | 7.87 | 22.12 | 283.17 | 716.50 |
June | 30.60 | 26-JUN-13:00 | 21.72 | 17.80 | 6.70 | 20.40 | 162.00 | 756.50 |
July | 32.20 | 09-JUL-11:00 | 23.42 | 20.00 | 6.20 | 23.49 | 235.00 | 733.00 |
August | 32.80 | 11-AUG-13:00 | 23.28 | 19.40 | 6.20 | 23.99 | 228.00 | 563.00 |
September | 33.30 | 02-SEP-12:00 | 23.47 | 19.40 | 5.70 | 23.32 | 185.00 | 789.00 |
October | 33.30 | 01-OCT-12:00 | 23.04 | 18.90 | 6.20 | 23.15 | 143.50 | 854.50 |
November | 30.60 | 03-NOV-12:00 | 22.49 | 18.90 | 7.70 | 20.57 | 148.00 | 798.50 |
December | 30.60 | 13-DEC-13:00 | 22.11 | 18.30 | 5.70 | 18.64 | 59.00 | 832.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 20.05 | 15.00 | 3.10 | 17.39 | 59.00 | 543.50 | |
Maximum of Months | 33.30 | 23.47 | 20.00 | 7.87 | 23.99 | 350.50 | 854.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.20 | 07-JAN-06:00 | 15.82 | 15.00 | 1.50 | 3.89 | 0.00 | 0.00 |
February | 13.30 | 12-FEB-06:00 | 12.64 | 12.20 | 3.10 | 0.73 | 0.00 | 0.00 |
March | 15.00 | 08-MAR-03:00 | 13.29 | 12.20 | 0.00 | 1.16 | 0.00 | 0.00 |
April | 17.80 | 22-APR-02:00 | 16.39 | 15.60 | 0.00 | 6.75 | 0.00 | 0.00 |
May | 18.90 | 23-MAY-05:00 | 17.45 | 16.70 | 2.10 | 9.33 | 110.00 | 159.50 |
June | 21.10 | 06-JUN-04:00 | 19.20 | 18.30 | 2.60 | 9.52 | 0.00 | 0.00 |
July | 22.20 | 09-JUL-03:00 | 20.00 | 18.90 | 1.50 | 11.84 | 0.00 | 0.00 |
August | 21.10 | 18-AUG-05:00 | 19.93 | 19.40 | 2.10 | 8.54 | 0.00 | 0.00 |
September | 22.20 | 19-SEP-04:00 | 20.25 | 19.40 | 2.60 | 11.84 | 0.00 | 0.00 |
October | 19.40 | 19-OCT-05:00 | 17.58 | 16.70 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 16.10 | 27-NOV-06:00 | 15.39 | 15.00 | 2.60 | 5.74 | 50.00 | 566.00 |
December | 16.70 | 26-DEC-01:00 | 15.01 | 13.90 | 2.60 | 4.31 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 12.64 | 12.20 | 0.00 | 0.73 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 20.25 | 19.40 | 3.10 | 11.84 | 110.00 | 566.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.03 | 01-JAN-15:00 | 27.80 | 21.10 | 4.10 | 20.92 | 91.00 | 199.00 |
February | 24.57 | 18-FEB-13:00 | 27.80 | 23.30 | 4.10 | 21.44 | 268.00 | 307.00 |
March | 23.81 | 13-MAR-12:00 | 27.80 | 22.20 | 5.70 | 22.47 | 468.50 | 259.00 |
April | 22.82 | 24-APR-11:00 | 28.30 | 20.60 | 4.60 | 19.87 | 357.00 | 446.00 |
May | 23.35 | 08-MAY-15:00 | 28.90 | 21.10 | 6.20 | 22.13 | 182.00 | 323.50 |
June | 23.02 | 20-JUN-13:00 | 28.90 | 20.60 | 7.70 | 21.96 | 370.50 | 346.50 |
July | 24.68 | 20-JUL-13:00 | 26.70 | 23.90 | 8.20 | 25.33 | 309.00 | 14.00 |
August | 25.47 | 19-AUG-14:00 | 31.70 | 23.30 | 5.20 | 25.33 | 229.00 | 409.00 |
September | 25.16 | 23-SEP-14:00 | 27.20 | 24.40 | 4.10 | 23.82 | 288.00 | 450.00 |
October | 24.72 | 15-OCT-13:00 | 31.70 | 22.20 | 5.20 | 22.98 | 151.50 | 527.00 |
November | 23.46 | 02-NOV-09:00 | 29.40 | 21.10 | 6.20 | 20.57 | 236.50 | 546.50 |
December | 23.69 | 03-DEC-10:00 | 26.10 | 22.80 | 6.70 | 24.50 | 251.50 | 3.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.82 | 26.10 | 20.60 | 4.10 | 19.87 | 91.00 | 3.00 | |
Maximum of Months | 25.47 | 31.70 | 24.40 | 8.20 | 25.33 | 468.50 | 546.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 01-JAN-15:00 | 27.80 | 23.03 | 4.10 | 20.92 | 91.00 | 199.00 |
February | 23.30 | 16-FEB-17:00 | 24.40 | 23.65 | 3.10 | 22.98 | 29.50 | 4.00 |
March | 22.20 | 13-MAR-10:00 | 27.20 | 23.57 | 4.60 | 21.78 | 336.00 | 148.00 |
April | 21.10 | 24-APR-23:00 | 22.80 | 21.58 | 1.50 | 18.82 | 0.00 | 0.00 |
May | 22.20 | 09-MAY-23:00 | 24.40 | 22.88 | 1.50 | 22.64 | 0.00 | 0.00 |
June | 20.80 | 09-JUN-00:10 | 22.15 | 21.03 | 3.78 | 18.14 | 0.00 | 0.00 |
July | 23.90 | 20-JUL-13:00 | 26.70 | 24.68 | 8.20 | 25.33 | 309.00 | 14.00 |
August | 23.30 | 19-AUG-14:00 | 31.70 | 25.47 | 5.20 | 25.33 | 229.00 | 409.00 |
September | 24.40 | 23-SEP-14:00 | 27.20 | 25.16 | 4.10 | 23.82 | 288.00 | 450.00 |
October | 22.80 | 24-OCT-12:00 | 26.10 | 23.69 | 4.10 | 19.70 | 259.00 | 474.50 |
November | 21.70 | 29-NOV-17:00 | 26.10 | 22.98 | 3.10 | 22.13 | 0.00 | 0.00 |
December | 22.80 | 03-DEC-10:00 | 26.10 | 23.69 | 6.70 | 24.50 | 251.50 | 3.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.80 | 22.15 | 21.03 | 1.50 | 18.14 | 0.00 | 0.00 | |
Maximum of Months | 24.40 | 31.70 | 25.47 | 8.20 | 25.33 | 336.00 | 474.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 26.59 | 31.34 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 26.78 | 37.09 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 27.35 | 43.34 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 28.17 | 47.38 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.01 | 50.82 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.64 | 52.70 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.90 | 53.08 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.71 | 53.00 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.13 | 48.47 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.31 | 39.62 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.47 | 33.78 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 26.84 | 30.10 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.25 | 43.42 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 26.59 | 30.10 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.90 | 53.08 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.271151E+09 | -159028057.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112123403.5 | 59.00 | 0.00 | 0.00 |
February | 0.244807E+09 | -143583120.6 | 0.00 | 0.00 | 672.00 | 0.00 | -101223763.9 | 58.99 | 0.00 | 0.00 |
March | 0.270698E+09 | -158630290.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112067628.1 | 58.99 | 0.00 | 0.00 |
April | 0.256238E+09 | -147841132.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108396970.7 | 58.99 | 0.00 | 0.00 |
May | 0.260470E+09 | -148720844.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111749393.6 | 58.99 | 0.00 | 0.00 |
June | 0.250198E+09 | -142212208.1 | 0.00 | 0.00 | 720.00 | 0.00 | -107986230.7 | 58.99 | 0.00 | 0.00 |
July | 0.254289E+09 | -142905545.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111383936.9 | 58.99 | 0.00 | 0.00 |
August | 0.258038E+09 | -146668832.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111368951.3 | 58.99 | 0.00 | 0.00 |
September | 0.251013E+09 | -143351681.1 | 0.00 | 0.00 | 720.00 | 0.00 | -107661783.8 | 58.99 | 0.00 | 0.00 |
October | 0.262181E+09 | -150654388.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111526480.6 | 58.99 | 0.00 | 0.00 |
November | 0.257409E+09 | -149344158.4 | 0.00 | 0.00 | 720.00 | 0.00 | -108064942.3 | 59.00 | 0.00 | 0.00 |
December | 0.269901E+09 | -158052137.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111848748.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.310639E+10 | -.179099E+10 | 8760.00 | -.131540E+10 | 58.99 | |||||
Minimum of Months | 0.244807E+09 | -159028057.7 | 0.00 | 0.00 | 672.00 | 0.00 | -112123403.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.271151E+09 | -142212208.1 | 0.00 | 0.00 | 744.00 | 0.00 | -101223763.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.270925E+09 | -159033713.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111891566.6 | 58.99 | 0.00 | 0.00 |
February | 0.244623E+09 | -143583670.0 | 0.00 | 0.00 | 672.00 | 0.00 | -101039142.7 | 58.99 | 0.00 | 0.00 |
March | 0.270507E+09 | -158620503.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111886696.3 | 58.99 | 0.00 | 0.00 |
April | 0.256050E+09 | -147835175.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108214489.6 | 58.99 | 0.00 | 0.00 |
May | 0.260330E+09 | -148734821.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111595307.2 | 58.99 | 0.00 | 0.00 |
June | 0.250086E+09 | -142210122.3 | 0.00 | 0.00 | 720.00 | 0.00 | -107876355.2 | 58.99 | 0.00 | 0.00 |
July | 0.254199E+09 | -142904938.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111293757.5 | 58.99 | 0.00 | 0.00 |
August | 0.257970E+09 | -146668684.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111301101.7 | 58.99 | 0.00 | 0.00 |
September | 0.250970E+09 | -143348206.4 | 0.00 | 0.00 | 720.00 | 0.00 | -107621549.7 | 58.99 | 0.00 | 0.00 |
October | 0.262073E+09 | -150655010.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111417633.9 | 58.99 | 0.00 | 0.00 |
November | 0.257278E+09 | -149370804.5 | 0.00 | 0.00 | 720.00 | 0.00 | -107907499.9 | 58.99 | 0.00 | 0.00 |
December | 0.269728E+09 | -158055533.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111672212.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.310474E+10 | -.179102E+10 | 8760.00 | -.131372E+10 | 58.99 | |||||
Minimum of Months | 0.244623E+09 | -159033713.9 | 0.00 | 0.00 | 672.00 | 0.00 | -111891566.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.270925E+09 | -142210122.3 | 0.00 | 0.00 | 744.00 | 0.00 | -101039142.7 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.250522E+09 | -139858742.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110663446.0 | 58.99 | 0.00 | 0.00 |
February | 0.226220E+09 | -126357154.6 | 0.00 | 0.00 | 672.00 | 0.00 | -99862669.0 | 58.99 | 0.00 | 0.00 |
March | 0.252232E+09 | -141670660.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110561344.1 | 58.99 | 0.00 | 0.00 |
April | 0.236826E+09 | -129920816.5 | 0.00 | 0.00 | 720.00 | 0.00 | -106904967.6 | 58.99 | 0.00 | 0.00 |
May | 0.241875E+09 | -131895302.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109980038.5 | 58.99 | 0.00 | 0.00 |
June | 0.233004E+09 | -126738931.0 | 0.00 | 0.00 | 720.00 | 0.00 | -106264836.1 | 59.00 | 0.00 | 0.00 |
July | 0.234123E+09 | -124843188.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109279520.5 | 58.99 | 0.00 | 0.00 |
August | 0.240528E+09 | -131104841.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109423335.9 | 58.99 | 0.00 | 0.00 |
September | 0.231485E+09 | -125894164.1 | 0.00 | 0.00 | 720.00 | 0.00 | -105591230.2 | 58.99 | 0.00 | 0.00 |
October | 0.241953E+09 | -132490073.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109462886.4 | 58.99 | 0.00 | 0.00 |
November | 0.238286E+09 | -131884529.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106401135.5 | 58.99 | 0.00 | 0.00 |
December | 0.248199E+09 | -137993012.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110205532.2 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.287525E+10 | -.158065E+10 | 8760.00 | -.129460E+10 | 58.99 | |||||
Minimum of Months | 0.226220E+09 | -141670660.6 | 0.00 | 0.00 | 672.00 | 0.00 | -110663446.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.252232E+09 | -124843188.6 | 0.00 | 0.00 | 744.00 | 0.00 | -99862669.0 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.250542E+09 | -139858809.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110683336.2 | 58.99 | 0.00 | 0.00 |
February | 0.226231E+09 | -126359755.2 | 0.00 | 0.00 | 672.00 | 0.00 | -99871318.9 | 58.99 | 0.00 | 0.00 |
March | 0.252237E+09 | -141671383.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110565190.0 | 58.99 | 0.00 | 0.00 |
April | 0.236834E+09 | -129919524.8 | 0.00 | 0.00 | 720.00 | 0.00 | -106914050.9 | 58.99 | 0.00 | 0.00 |
May | 0.241848E+09 | -131896120.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109951439.2 | 58.99 | 0.00 | 0.00 |
June | 0.232966E+09 | -126739013.3 | 0.00 | 0.00 | 720.00 | 0.00 | -106227064.8 | 59.00 | 0.00 | 0.00 |
July | 0.234052E+09 | -124851304.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109200978.6 | 58.99 | 0.00 | 0.00 |
August | 0.240460E+09 | -131084968.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109375330.3 | 58.99 | 0.00 | 0.00 |
September | 0.231413E+09 | -125886025.0 | 0.00 | 0.00 | 720.00 | 0.00 | -105526756.4 | 58.99 | 0.00 | 0.00 |
October | 0.241889E+09 | -132497771.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109391390.3 | 58.99 | 0.00 | 0.00 |
November | 0.238259E+09 | -131861247.4 | 0.00 | 0.00 | 720.00 | 0.00 | -106398232.4 | 58.99 | 0.00 | 0.00 |
December | 0.248199E+09 | -137970589.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110227928.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.287493E+10 | -.158060E+10 | 8760.00 | -.129433E+10 | 58.99 | |||||
Minimum of Months | 0.226231E+09 | -141671383.1 | 0.00 | 0.00 | 672.00 | 0.00 | -110683336.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.252237E+09 | -124851304.0 | 0.00 | 0.00 | 744.00 | 0.00 | -99871318.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.243508E+09 | -132176490.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111331333.1 | 59.00 | 0.00 | 0.00 |
February | 0.219960E+09 | -119517534.4 | 0.00 | 0.00 | 672.00 | 0.00 | -100442719.9 | 58.99 | 0.00 | 0.00 |
March | 0.245320E+09 | -134060247.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111259947.6 | 58.99 | 0.00 | 0.00 |
April | 0.230519E+09 | -122944993.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107573622.4 | 58.99 | 0.00 | 0.00 |
May | 0.235343E+09 | -124731664.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110611311.7 | 58.99 | 0.00 | 0.00 |
June | 0.226790E+09 | -119925993.6 | 0.00 | 0.00 | 720.00 | 0.00 | -106863857.1 | 59.00 | 0.00 | 0.00 |
July | 0.227923E+09 | -118076367.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109847128.8 | 58.99 | 0.00 | 0.00 |
August | 0.234142E+09 | -124035770.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110106685.0 | 58.99 | 0.00 | 0.00 |
September | 0.225272E+09 | -119124076.1 | 0.00 | 0.00 | 720.00 | 0.00 | -106148416.4 | 58.99 | 0.00 | 0.00 |
October | 0.235295E+09 | -125231938.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110062747.8 | 58.99 | 0.00 | 0.00 |
November | 0.231526E+09 | -124549458.7 | 0.00 | 0.00 | 720.00 | 0.00 | -106976187.3 | 58.99 | 0.00 | 0.00 |
December | 0.241305E+09 | -130483024.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110822382.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.279690E+10 | -.149486E+10 | 8760.00 | -.130205E+10 | 58.99 | |||||
Minimum of Months | 0.219960E+09 | -134060247.8 | 0.00 | 0.00 | 672.00 | 0.00 | -111331333.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.245320E+09 | -118076367.3 | 0.00 | 0.00 | 744.00 | 0.00 | -100442719.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.243632E+09 | -132175140.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111456627.4 | 59.00 | 0.00 | 0.00 |
February | 0.220069E+09 | -119514498.9 | 0.00 | 0.00 | 672.00 | 0.00 | -100554179.5 | 58.98 | 0.00 | 0.00 |
March | 0.245450E+09 | -134061999.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111388163.2 | 58.99 | 0.00 | 0.00 |
April | 0.230638E+09 | -122938655.0 | 0.00 | 0.00 | 720.00 | 0.00 | -107699416.4 | 58.99 | 0.00 | 0.00 |
May | 0.235488E+09 | -124736988.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110750735.8 | 58.99 | 0.00 | 0.00 |
June | 0.226927E+09 | -119954047.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106972658.8 | 58.99 | 0.00 | 0.00 |
July | 0.228071E+09 | -118058411.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110012551.2 | 58.99 | 0.00 | 0.00 |
August | 0.234299E+09 | -124039449.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110259875.6 | 58.99 | 0.00 | 0.00 |
September | 0.225429E+09 | -119128207.7 | 0.00 | 0.00 | 720.00 | 0.00 | -106301028.3 | 58.99 | 0.00 | 0.00 |
October | 0.235443E+09 | -125206297.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110237074.9 | 59.00 | 0.00 | 0.00 |
November | 0.231666E+09 | -124555359.8 | 0.00 | 0.00 | 720.00 | 0.00 | -107110373.8 | 58.99 | 0.00 | 0.00 |
December | 0.241455E+09 | -130478945.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110975907.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.279857E+10 | -.149485E+10 | 8760.00 | -.130372E+10 | 58.99 | |||||
Minimum of Months | 0.220069E+09 | -134061999.3 | 0.00 | 0.00 | 672.00 | 0.00 | -111456627.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.245450E+09 | -118058411.9 | 0.00 | 0.00 | 744.00 | 0.00 | -100554179.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.243684E+09 | -132173448.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111510099.5 | 59.00 | 0.00 | 0.00 |
February | 0.220114E+09 | -119507174.2 | 0.00 | 0.00 | 672.00 | 0.00 | -100606383.3 | 58.99 | 0.00 | 0.00 |
March | 0.245499E+09 | -134054179.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111444879.7 | 58.99 | 0.00 | 0.00 |
April | 0.230682E+09 | -122924142.0 | 0.00 | 0.00 | 720.00 | 0.00 | -107758255.3 | 58.99 | 0.00 | 0.00 |
May | 0.235531E+09 | -124740081.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110790469.1 | 58.99 | 0.00 | 0.00 |
June | 0.226970E+09 | -119932102.8 | 0.00 | 0.00 | 720.00 | 0.00 | -107037681.8 | 58.99 | 0.00 | 0.00 |
July | 0.228122E+09 | -118072773.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110049480.3 | 58.99 | 0.00 | 0.00 |
August | 0.234338E+09 | -124042254.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110295928.4 | 58.99 | 0.00 | 0.00 |
September | 0.225470E+09 | -119129947.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106340111.4 | 58.99 | 0.00 | 0.00 |
October | 0.235483E+09 | -125218507.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110264175.9 | 58.99 | 0.00 | 0.00 |
November | 0.231704E+09 | -124565617.3 | 0.00 | 0.00 | 720.00 | 0.00 | -107138820.1 | 58.99 | 0.00 | 0.00 |
December | 0.241508E+09 | -130513961.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110993737.3 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.279910E+10 | -.149487E+10 | 8760.00 | -.130423E+10 | 58.99 | |||||
Minimum of Months | 0.220114E+09 | -134054179.7 | 0.00 | 0.00 | 672.00 | 0.00 | -111510099.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.245499E+09 | -118072773.4 | 0.00 | 0.00 | 744.00 | 0.00 | -100606383.3 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 326.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 285.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 336.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 360.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 384.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 392.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 398.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 382.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 346.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 316.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 318.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4207.17 | ||||||||||
Minimum of Months | 285.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 398.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.253538E+11 | 0.175468E+11 | 49730.85 | 31-JAN-08:62 | 29285.87 | 0.00 |
February | 0.00 | 0.00 | 0.269437E+11 | 0.168324E+11 | 51465.37 | 17-FEB-08:62 | 25425.73 | 0.00 |
March | 0.00 | 0.00 | 0.282279E+11 | 0.191509E+11 | 50209.19 | 03-MAR-08:62 | 27054.43 | 0.00 |
April | 0.00 | 0.00 | 0.269309E+11 | 0.187873E+11 | 49154.11 | 25-APR-07:02 | 31716.61 | 0.00 |
May | 0.00 | 0.00 | 0.341366E+11 | 0.229686E+11 | 50493.79 | 10-MAY-07:02 | 28595.73 | 0.00 |
June | 0.00 | 0.00 | 0.347307E+11 | 0.232292E+11 | 50075.29 | 14-JUN-07:02 | 30026.31 | 0.00 |
July | 0.00 | 0.00 | 0.405988E+11 | 0.267674E+11 | 51453.62 | 20-JUL-07:01 | 27128.51 | 0.00 |
August | 0.00 | 0.00 | 0.412058E+11 | 0.273660E+11 | 50704.30 | 08-AUG-07:01 | 28997.72 | 0.00 |
September | 0.00 | 0.00 | 0.414529E+11 | 0.264502E+11 | 51084.98 | 30-SEP-07:02 | 27224.99 | 0.00 |
October | 0.00 | 0.00 | 0.402688E+11 | 0.262957E+11 | 50388.48 | 13-OCT-07:01 | 29585.28 | 0.00 |
November | 0.00 | 0.00 | 0.336379E+11 | 0.220178E+11 | 50514.69 | 01-NOV-07:01 | 28962.05 | 0.00 |
December | 0.00 | 0.00 | 0.306341E+11 | 0.201556E+11 | 50830.03 | 03-DEC-08:61 | 28935.16 | 0.00 |
Annual Sum or Average | 0.404122E+12 | 0.267568E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.253538E+11 | 0.168324E+11 | 49154.11 | 25425.73 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.414529E+11 | 0.273660E+11 | 51465.37 | 31716.61 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.135970E+11 | 0.974433E+10 | 25629.05 | 31-JAN-08:62 | 17323.85 | 0.00 |
February | 0.00 | 0.00 | 0.140749E+11 | 0.915271E+10 | 26354.18 | 17-FEB-08:62 | 15623.07 | 0.00 |
March | 0.00 | 0.00 | 0.147404E+11 | 0.103248E+11 | 25764.38 | 03-MAR-08:62 | 16511.60 | 0.00 |
April | 0.00 | 0.00 | 0.139862E+11 | 0.100619E+11 | 25335.89 | 14-APR-07:02 | 18041.18 | 0.00 |
May | 0.00 | 0.00 | 0.173809E+11 | 0.120431E+11 | 25956.92 | 10-MAY-07:02 | 16998.40 | 0.00 |
June | 0.00 | 0.00 | 0.174993E+11 | 0.120266E+11 | 25846.19 | 14-JUN-07:02 | 17362.06 | 0.00 |
July | 0.00 | 0.00 | 0.202437E+11 | 0.137188E+11 | 26448.74 | 20-JUL-07:01 | 16027.59 | 0.00 |
August | 0.00 | 0.00 | 0.205420E+11 | 0.139953E+11 | 26107.84 | 08-AUG-07:01 | 16896.17 | 0.00 |
September | 0.00 | 0.00 | 0.204440E+11 | 0.134035E+11 | 26246.43 | 30-SEP-07:02 | 16269.86 | 0.00 |
October | 0.00 | 0.00 | 0.203298E+11 | 0.136709E+11 | 25934.81 | 13-OCT-07:01 | 17251.07 | 0.00 |
November | 0.00 | 0.00 | 0.172087E+11 | 0.116276E+11 | 26032.21 | 01-NOV-07:01 | 16931.62 | 0.00 |
December | 0.00 | 0.00 | 0.159566E+11 | 0.108850E+11 | 26251.43 | 03-DEC-08:61 | 16665.77 | 0.00 |
Annual Sum or Average | 0.206003E+12 | 0.140655E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.135970E+11 | 0.915271E+10 | 25335.89 | 15623.07 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.205420E+11 | 0.139953E+11 | 26448.74 | 18041.18 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.105871E+11 | 0.739336E+10 | 26516.91 | 02-JAN-07:02 | 14965.13 | 0.00 |
February | 0.00 | 0.00 | 0.110483E+11 | 0.695612E+10 | 27267.53 | 18-FEB-07:02 | 12908.48 | 0.00 |
March | 0.00 | 0.00 | 0.116268E+11 | 0.793897E+10 | 26903.15 | 13-MAR-06:02 | 13771.51 | 0.00 |
April | 0.00 | 0.00 | 0.108936E+11 | 0.764237E+10 | 26426.97 | 24-APR-06:02 | 14553.18 | 0.00 |
May | 0.00 | 0.00 | 0.139667E+11 | 0.946721E+10 | 26936.59 | 15-MAY-06:02 | 13394.64 | 0.00 |
June | 0.00 | 0.00 | 0.142163E+11 | 0.951972E+10 | 26467.26 | 18-JUN-07:01 | 15850.58 | 0.00 |
July | 0.00 | 0.00 | 0.163066E+11 | 0.107963E+11 | 27297.59 | 23-JUL-07:01 | 13777.85 | 0.00 |
August | 0.00 | 0.00 | 0.169179E+11 | 0.113079E+11 | 27099.17 | 20-AUG-07:01 | 14129.35 | 0.00 |
September | 0.00 | 0.00 | 0.164142E+11 | 0.104987E+11 | 27452.31 | 25-SEP-06:01 | 12737.49 | 0.00 |
October | 0.00 | 0.00 | 0.164230E+11 | 0.108186E+11 | 26916.64 | 10-OCT-06:01 | 13616.77 | 0.00 |
November | 0.00 | 0.00 | 0.139083E+11 | 0.916063E+10 | 26736.63 | 24-NOV-07:02 | 14323.79 | 0.00 |
December | 0.00 | 0.00 | 0.125832E+11 | 0.833793E+10 | 26906.67 | 03-DEC-08:61 | 14750.19 | 0.00 |
Annual Sum or Average | 0.164892E+12 | 0.109838E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.105871E+11 | 0.695612E+10 | 26426.97 | 12737.49 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.169179E+11 | 0.113079E+11 | 27452.31 | 15850.58 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.105501E+11 | 0.736677E+10 | 26570.51 | 02-JAN-07:02 | 15014.42 | 0.00 |
February | 0.00 | 0.00 | 0.110182E+11 | 0.693593E+10 | 27320.08 | 18-FEB-07:02 | 12926.99 | 0.00 |
March | 0.00 | 0.00 | 0.116022E+11 | 0.792185E+10 | 26957.30 | 13-MAR-06:02 | 13813.73 | 0.00 |
April | 0.00 | 0.00 | 0.108661E+11 | 0.762265E+10 | 26477.50 | 24-APR-06:02 | 14581.19 | 0.00 |
May | 0.00 | 0.00 | 0.139659E+11 | 0.946803E+10 | 26991.33 | 15-MAY-06:02 | 13445.03 | 0.00 |
June | 0.00 | 0.00 | 0.142223E+11 | 0.952607E+10 | 26521.74 | 18-JUN-07:01 | 15904.84 | 0.00 |
July | 0.00 | 0.00 | 0.163376E+11 | 0.108219E+11 | 27353.86 | 23-JUL-07:01 | 13832.11 | 0.00 |
August | 0.00 | 0.00 | 0.169443E+11 | 0.113300E+11 | 27156.68 | 20-AUG-07:01 | 14191.69 | 0.00 |
September | 0.00 | 0.00 | 0.164567E+11 | 0.105326E+11 | 27512.67 | 25-SEP-06:01 | 12814.45 | 0.00 |
October | 0.00 | 0.00 | 0.164574E+11 | 0.108464E+11 | 26975.48 | 10-OCT-06:01 | 13694.33 | 0.00 |
November | 0.00 | 0.00 | 0.139040E+11 | 0.915951E+10 | 26792.44 | 24-NOV-07:02 | 14382.71 | 0.00 |
December | 0.00 | 0.00 | 0.125632E+11 | 0.832458E+10 | 26959.44 | 03-DEC-08:61 | 14790.33 | 0.00 |
Annual Sum or Average | 0.164888E+12 | 0.109856E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.105501E+11 | 0.693593E+10 | 26477.50 | 12814.45 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.169443E+11 | 0.113300E+11 | 27512.67 | 15904.84 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.102813E+11 | 0.715349E+10 | 26371.94 | 02-JAN-07:02 | 14823.68 | 0.00 |
February | 0.00 | 0.00 | 0.107563E+11 | 0.673911E+10 | 27119.04 | 18-FEB-07:02 | 12698.45 | 0.00 |
March | 0.00 | 0.00 | 0.113162E+11 | 0.769813E+10 | 26754.75 | 13-MAR-06:02 | 13615.04 | 0.00 |
April | 0.00 | 0.00 | 0.106001E+11 | 0.741165E+10 | 26278.10 | 24-APR-06:02 | 14372.73 | 0.00 |
May | 0.00 | 0.00 | 0.137079E+11 | 0.926204E+10 | 26790.46 | 15-MAY-06:02 | 13260.78 | 0.00 |
June | 0.00 | 0.00 | 0.139754E+11 | 0.932956E+10 | 26319.34 | 18-JUN-07:01 | 15684.68 | 0.00 |
July | 0.00 | 0.00 | 0.160993E+11 | 0.106305E+11 | 27148.70 | 23-JUL-07:01 | 13625.59 | 0.00 |
August | 0.00 | 0.00 | 0.166909E+11 | 0.111262E+11 | 26952.57 | 20-AUG-07:01 | 13984.07 | 0.00 |
September | 0.00 | 0.00 | 0.162199E+11 | 0.103454E+11 | 27308.55 | 25-SEP-06:01 | 12641.29 | 0.00 |
October | 0.00 | 0.00 | 0.162096E+11 | 0.106488E+11 | 26775.83 | 10-OCT-06:01 | 13521.36 | 0.00 |
November | 0.00 | 0.00 | 0.136593E+11 | 0.896694E+10 | 26592.18 | 24-NOV-07:02 | 14191.18 | 0.00 |
December | 0.00 | 0.00 | 0.123045E+11 | 0.812127E+10 | 26755.39 | 03-DEC-08:61 | 14578.06 | 0.00 |
Annual Sum or Average | 0.161821E+12 | 0.107433E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.102813E+11 | 0.673911E+10 | 26278.10 | 12641.29 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.166909E+11 | 0.111262E+11 | 27308.55 | 15684.68 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.173056E+11 | 0.117286E+11 | 47069.30 | 01-JAN-09:02 | 26199.72 | 0.00 |
February | 0.00 | 0.00 | 0.183219E+11 | 0.111154E+11 | 47976.64 | 18-FEB-08:62 | 23313.03 | 0.00 |
March | 0.00 | 0.00 | 0.193335E+11 | 0.128140E+11 | 47670.94 | 13-MAR-07:02 | 23703.65 | 0.00 |
April | 0.00 | 0.00 | 0.179868E+11 | 0.122776E+11 | 46920.39 | 24-APR-07:02 | 25175.71 | 0.00 |
May | 0.00 | 0.00 | 0.237589E+11 | 0.156914E+11 | 47801.21 | 15-MAY-07:02 | 23464.56 | 0.00 |
June | 0.00 | 0.00 | 0.242565E+11 | 0.158159E+11 | 46948.93 | 18-JUN-08:61 | 27898.72 | 0.00 |
July | 0.00 | 0.00 | 0.281321E+11 | 0.181734E+11 | 48484.88 | 23-JUL-08:61 | 24308.54 | 0.00 |
August | 0.00 | 0.00 | 0.293005E+11 | 0.191403E+11 | 48105.25 | 20-AUG-08:61 | 25130.38 | 0.00 |
September | 0.00 | 0.00 | 0.283754E+11 | 0.176973E+11 | 48687.52 | 25-SEP-07:02 | 22177.77 | 0.00 |
October | 0.00 | 0.00 | 0.285052E+11 | 0.183282E+11 | 47746.63 | 10-OCT-07:02 | 23759.45 | 0.00 |
November | 0.00 | 0.00 | 0.236158E+11 | 0.151184E+11 | 47522.63 | 24-NOV-08:62 | 25381.46 | 0.00 |
December | 0.00 | 0.00 | 0.210129E+11 | 0.134906E+11 | 47940.26 | 03-DEC-09:01 | 25172.35 | 0.00 |
Annual Sum or Average | 0.279905E+12 | 0.181391E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.173056E+11 | 0.111154E+11 | 46920.39 | 22177.77 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.293005E+11 | 0.191403E+11 | 48687.52 | 27898.72 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.889326E+10 | 0.603437E+10 | 24536.09 | 01-JAN-09:02 | 13636.01 | 0.00 |
February | 0.00 | 0.00 | 0.941646E+10 | 0.571740E+10 | 24988.21 | 18-FEB-08:62 | 12173.61 | 0.00 |
March | 0.00 | 0.00 | 0.994140E+10 | 0.659424E+10 | 24864.26 | 13-MAR-07:02 | 12316.52 | 0.00 |
April | 0.00 | 0.00 | 0.925194E+10 | 0.632129E+10 | 24461.72 | 24-APR-07:02 | 13106.47 | 0.00 |
May | 0.00 | 0.00 | 0.122515E+11 | 0.809673E+10 | 24931.80 | 15-MAY-07:02 | 12178.95 | 0.00 |
June | 0.00 | 0.00 | 0.124970E+11 | 0.815515E+10 | 24467.08 | 18-JUN-08:61 | 14509.99 | 0.00 |
July | 0.00 | 0.00 | 0.145260E+11 | 0.939076E+10 | 25270.96 | 23-JUL-08:61 | 12610.34 | 0.00 |
August | 0.00 | 0.00 | 0.151347E+11 | 0.989407E+10 | 25073.46 | 20-AUG-08:61 | 13053.00 | 0.00 |
September | 0.00 | 0.00 | 0.146456E+11 | 0.914091E+10 | 25405.84 | 25-SEP-07:02 | 11470.24 | 0.00 |
October | 0.00 | 0.00 | 0.147335E+11 | 0.948046E+10 | 24908.63 | 10-OCT-07:02 | 12338.67 | 0.00 |
November | 0.00 | 0.00 | 0.121708E+11 | 0.779991E+10 | 24776.23 | 24-NOV-08:62 | 13193.50 | 0.00 |
December | 0.00 | 0.00 | 0.108172E+11 | 0.695280E+10 | 24981.11 | 03-DEC-09:01 | 13094.30 | 0.00 |
Annual Sum or Average | 0.144279E+12 | 0.935781E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.889326E+10 | 0.571740E+10 | 24461.72 | 11470.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.151347E+11 | 0.989407E+10 | 25405.84 | 14509.99 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.880684E+10 | 0.596600E+10 | 24430.19 | 01-JAN-09:02 | 13546.44 | 0.00 |
February | 0.00 | 0.00 | 0.933007E+10 | 0.565316E+10 | 24884.89 | 18-FEB-08:62 | 12079.05 | 0.00 |
March | 0.00 | 0.00 | 0.985261E+10 | 0.652486E+10 | 24756.58 | 13-MAR-07:02 | 12233.55 | 0.00 |
April | 0.00 | 0.00 | 0.917379E+10 | 0.625892E+10 | 24356.19 | 24-APR-07:02 | 13019.65 | 0.00 |
May | 0.00 | 0.00 | 0.121735E+11 | 0.803368E+10 | 24824.35 | 15-MAY-07:02 | 12098.82 | 0.00 |
June | 0.00 | 0.00 | 0.124202E+11 | 0.809321E+10 | 24361.73 | 18-JUN-08:61 | 14420.06 | 0.00 |
July | 0.00 | 0.00 | 0.144513E+11 | 0.932944E+10 | 25162.63 | 23-JUL-08:61 | 12528.13 | 0.00 |
August | 0.00 | 0.00 | 0.150608E+11 | 0.983280E+10 | 24966.59 | 20-AUG-08:61 | 12973.45 | 0.00 |
September | 0.00 | 0.00 | 0.145695E+11 | 0.907983E+10 | 25296.82 | 25-SEP-07:02 | 11399.43 | 0.00 |
October | 0.00 | 0.00 | 0.146569E+11 | 0.941781E+10 | 24801.34 | 10-OCT-07:02 | 12260.65 | 0.00 |
November | 0.00 | 0.00 | 0.120876E+11 | 0.773420E+10 | 24669.46 | 24-NOV-08:62 | 13107.23 | 0.00 |
December | 0.00 | 0.00 | 0.107313E+11 | 0.688528E+10 | 24873.72 | 03-DEC-09:01 | 13008.04 | 0.00 |
Annual Sum or Average | 0.143314E+12 | 0.928092E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.880684E+10 | 0.565316E+10 | 24356.19 | 11399.43 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.150608E+11 | 0.983280E+10 | 25296.82 | 14420.06 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.870363E+10 | 0.589098E+10 | 24449.43 | 01-JAN-09:02 | 13509.49 | 0.00 |
February | 0.00 | 0.00 | 0.921351E+10 | 0.557329E+10 | 24909.77 | 18-FEB-08:62 | 12019.48 | 0.00 |
March | 0.00 | 0.00 | 0.974368E+10 | 0.644759E+10 | 24778.93 | 13-MAR-07:02 | 12202.80 | 0.00 |
April | 0.00 | 0.00 | 0.910725E+10 | 0.621109E+10 | 24376.60 | 24-APR-07:02 | 12987.24 | 0.00 |
May | 0.00 | 0.00 | 0.121540E+11 | 0.802059E+10 | 24846.72 | 15-MAY-07:02 | 12073.66 | 0.00 |
June | 0.00 | 0.00 | 0.124069E+11 | 0.808488E+10 | 24384.26 | 18-JUN-08:61 | 14405.68 | 0.00 |
July | 0.00 | 0.00 | 0.144616E+11 | 0.933944E+10 | 25188.35 | 23-JUL-08:61 | 12519.86 | 0.00 |
August | 0.00 | 0.00 | 0.150889E+11 | 0.985608E+10 | 24991.83 | 20-AUG-08:61 | 12969.72 | 0.00 |
September | 0.00 | 0.00 | 0.145740E+11 | 0.908470E+10 | 25323.14 | 25-SEP-07:02 | 11391.60 | 0.00 |
October | 0.00 | 0.00 | 0.146607E+11 | 0.942240E+10 | 24826.50 | 10-OCT-07:02 | 12252.21 | 0.00 |
November | 0.00 | 0.00 | 0.120345E+11 | 0.769703E+10 | 24691.25 | 24-NOV-08:62 | 13082.05 | 0.00 |
December | 0.00 | 0.00 | 0.106506E+11 | 0.682753E+10 | 24897.07 | 03-DEC-09:01 | 12989.07 | 0.00 |
Annual Sum or Average | 0.142799E+12 | 0.924556E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.870363E+10 | 0.557329E+10 | 24376.60 | 11391.60 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.150889E+11 | 0.985608E+10 | 25323.14 | 14405.68 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.957608E+10 | 0.663157E+10 | 26894.49 | 02-JAN-08:62 | 14955.48 | 0.00 |
February | 0.00 | 0.00 | 0.988330E+10 | 0.612069E+10 | 27846.95 | 18-FEB-08:62 | 12027.23 | 0.00 |
March | 0.00 | 0.00 | 0.105992E+11 | 0.717355E+10 | 27335.53 | 13-MAR-07:02 | 13343.35 | 0.00 |
April | 0.00 | 0.00 | 0.102610E+11 | 0.716125E+10 | 26815.61 | 24-APR-07:02 | 14406.28 | 0.00 |
May | 0.00 | 0.00 | 0.138123E+11 | 0.935410E+10 | 27343.12 | 15-MAY-07:02 | 13445.37 | 0.00 |
June | 0.00 | 0.00 | 0.140929E+11 | 0.941509E+10 | 26976.03 | 25-JUN-08:61 | 15959.61 | 0.00 |
July | 0.00 | 0.00 | 0.163950E+11 | 0.108629E+11 | 27902.03 | 23-JUL-08:61 | 14106.66 | 0.00 |
August | 0.00 | 0.00 | 0.172036E+11 | 0.115347E+11 | 27646.25 | 20-AUG-08:61 | 14511.48 | 0.00 |
September | 0.00 | 0.00 | 0.162088E+11 | 0.103571E+11 | 27913.39 | 25-SEP-07:02 | 12587.22 | 0.00 |
October | 0.00 | 0.00 | 0.164616E+11 | 0.108672E+11 | 27395.94 | 10-OCT-07:02 | 13450.41 | 0.00 |
November | 0.00 | 0.00 | 0.132492E+11 | 0.866623E+10 | 27244.35 | 24-NOV-08:62 | 14353.06 | 0.00 |
December | 0.00 | 0.00 | 0.116644E+11 | 0.765276E+10 | 27530.51 | 03-DEC-09:01 | 14332.65 | 0.00 |
Annual Sum or Average | 0.159407E+12 | 0.105797E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.957608E+10 | 0.612069E+10 | 26815.61 | 12027.23 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.172036E+11 | 0.115347E+11 | 27913.39 | 15959.61 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156927E+10 | 0.36 | 2136.88 | 01-JAN-08:62 | 0.87 |
February | 0.144290E+10 | 0.36 | 2136.88 | 03-FEB-08:62 | 0.87 |
March | 0.157854E+10 | 0.36 | 2136.88 | 01-MAR-08:62 | 0.87 |
April | 0.151476E+10 | 0.36 | 2136.88 | 05-APR-07:02 | 0.87 |
May | 0.161057E+10 | 0.36 | 2136.88 | 01-MAY-07:02 | 0.87 |
June | 0.157290E+10 | 0.37 | 2136.88 | 01-JUN-07:02 | 0.87 |
July | 0.174550E+10 | 0.38 | 2136.88 | 01-JUL-07:02 | 0.87 |
August | 0.177868E+10 | 0.39 | 2136.88 | 01-AUG-07:02 | 0.86 |
September | 0.174795E+10 | 0.39 | 2136.88 | 01-SEP-07:01 | 0.86 |
October | 0.176816E+10 | 0.38 | 2136.88 | 01-OCT-07:01 | 0.86 |
November | 0.159092E+10 | 0.37 | 2136.88 | 01-NOV-07:01 | 0.86 |
December | 0.160241E+10 | 0.36 | 2136.88 | 01-DEC-08:61 | 0.86 |
Annual Sum or Average | 0.195226E+11 | 0.37 | |||
Minimum of Months | 0.144290E+10 | 0.36 | 2136.88 | 0.86 | |
Maximum of Months | 0.177868E+10 | 0.39 | 2136.88 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.763815E+09 | 0.38 | 1170.88 | 01-JAN-08:62 | 0.90 |
February | 0.710789E+09 | 0.39 | 1170.88 | 01-FEB-08:62 | 0.90 |
March | 0.776701E+09 | 0.38 | 1170.88 | 01-MAR-08:62 | 0.90 |
April | 0.740431E+09 | 0.38 | 1170.88 | 05-APR-07:02 | 0.90 |
May | 0.803005E+09 | 0.39 | 1170.88 | 01-MAY-07:02 | 0.90 |
June | 0.787035E+09 | 0.39 | 1170.88 | 01-JUN-07:02 | 0.90 |
July | 0.881382E+09 | 0.40 | 1170.88 | 01-JUL-07:02 | 0.90 |
August | 0.901049E+09 | 0.40 | 1170.88 | 01-AUG-07:02 | 0.90 |
September | 0.883590E+09 | 0.41 | 1170.88 | 01-SEP-07:01 | 0.90 |
October | 0.896817E+09 | 0.40 | 1170.88 | 01-OCT-07:01 | 0.90 |
November | 0.793316E+09 | 0.39 | 1170.88 | 01-NOV-07:01 | 0.90 |
December | 0.789146E+09 | 0.39 | 1170.88 | 01-DEC-08:61 | 0.90 |
Annual Sum or Average | 0.972708E+10 | 0.39 | |||
Minimum of Months | 0.710789E+09 | 0.38 | 1170.88 | 0.90 | |
Maximum of Months | 0.901049E+09 | 0.41 | 1170.88 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.684987E+09 | 0.30 | 1166.81 | 01-JAN-08:62 | 0.89 |
February | 0.630083E+09 | 0.30 | 1166.81 | 01-FEB-07:03 | 0.90 |
March | 0.699407E+09 | 0.30 | 1166.81 | 01-MAR-07:02 | 0.89 |
April | 0.659776E+09 | 0.30 | 1166.81 | 01-APR-06:02 | 0.90 |
May | 0.707878E+09 | 0.30 | 1166.81 | 01-MAY-06:02 | 0.90 |
June | 0.693903E+09 | 0.31 | 1166.81 | 01-JUN-06:02 | 0.90 |
July | 0.761662E+09 | 0.31 | 1166.81 | 01-JUL-06:02 | 0.90 |
August | 0.795667E+09 | 0.33 | 1166.81 | 01-AUG-06:02 | 0.89 |
September | 0.761772E+09 | 0.32 | 1166.81 | 01-SEP-06:01 | 0.89 |
October | 0.781880E+09 | 0.32 | 1166.81 | 01-OCT-07:01 | 0.89 |
November | 0.698183E+09 | 0.31 | 1166.81 | 01-NOV-06:01 | 0.89 |
December | 0.693996E+09 | 0.30 | 1166.81 | 01-DEC-07:02 | 0.89 |
Annual Sum or Average | 0.856919E+10 | 0.31 | |||
Minimum of Months | 0.630083E+09 | 0.30 | 1166.81 | 0.89 | |
Maximum of Months | 0.795667E+09 | 0.33 | 1166.81 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.686460E+09 | 0.30 | 1169.76 | 01-JAN-08:62 | 0.89 |
February | 0.631107E+09 | 0.30 | 1169.76 | 01-FEB-07:03 | 0.90 |
March | 0.700732E+09 | 0.30 | 1169.76 | 01-MAR-07:02 | 0.89 |
April | 0.661244E+09 | 0.30 | 1169.76 | 01-APR-06:02 | 0.90 |
May | 0.708941E+09 | 0.30 | 1169.76 | 01-MAY-06:02 | 0.90 |
June | 0.695039E+09 | 0.31 | 1169.76 | 01-JUN-06:02 | 0.90 |
July | 0.763137E+09 | 0.31 | 1169.76 | 01-JUL-06:02 | 0.90 |
August | 0.797043E+09 | 0.33 | 1169.76 | 01-AUG-06:02 | 0.89 |
September | 0.763579E+09 | 0.32 | 1169.76 | 01-SEP-06:01 | 0.89 |
October | 0.783492E+09 | 0.32 | 1169.76 | 01-OCT-07:01 | 0.89 |
November | 0.699413E+09 | 0.31 | 1169.76 | 01-NOV-06:01 | 0.89 |
December | 0.695244E+09 | 0.30 | 1169.76 | 01-DEC-07:02 | 0.89 |
Annual Sum or Average | 0.858543E+10 | 0.31 | |||
Minimum of Months | 0.631107E+09 | 0.30 | 1169.76 | 0.89 | |
Maximum of Months | 0.797043E+09 | 0.33 | 1169.76 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.679241E+09 | 0.30 | 1158.70 | 01-JAN-08:62 | 0.89 |
February | 0.623787E+09 | 0.30 | 1158.70 | 02-FEB-07:03 | 0.90 |
March | 0.692941E+09 | 0.30 | 1158.70 | 01-MAR-07:02 | 0.89 |
April | 0.654468E+09 | 0.30 | 1158.70 | 01-APR-06:02 | 0.90 |
May | 0.700004E+09 | 0.30 | 1158.70 | 01-MAY-06:02 | 0.90 |
June | 0.686181E+09 | 0.31 | 1158.70 | 01-JUN-06:02 | 0.90 |
July | 0.752717E+09 | 0.31 | 1158.70 | 01-JUL-06:02 | 0.90 |
August | 0.786162E+09 | 0.33 | 1158.70 | 01-AUG-06:02 | 0.89 |
September | 0.753161E+09 | 0.32 | 1158.70 | 01-SEP-06:01 | 0.89 |
October | 0.772965E+09 | 0.32 | 1158.70 | 01-OCT-07:01 | 0.89 |
November | 0.690878E+09 | 0.30 | 1158.70 | 01-NOV-06:01 | 0.89 |
December | 0.687308E+09 | 0.30 | 1158.70 | 01-DEC-07:02 | 0.89 |
Annual Sum or Average | 0.847981E+10 | 0.31 | |||
Minimum of Months | 0.623787E+09 | 0.30 | 1158.70 | 0.89 | |
Maximum of Months | 0.786162E+09 | 0.33 | 1158.70 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.105315E+10 | 0.26 | 1943.43 | 01-JAN-09:02 | 0.86 |
February | 0.968320E+09 | 0.27 | 1943.43 | 04-FEB-08:62 | 0.87 |
March | 0.107471E+10 | 0.27 | 1943.43 | 01-MAR-08:62 | 0.87 |
April | 0.101372E+10 | 0.26 | 1943.43 | 05-APR-07:02 | 0.87 |
May | 0.108927E+10 | 0.27 | 1943.43 | 01-MAY-07:02 | 0.87 |
June | 0.107028E+10 | 0.27 | 1943.43 | 01-JUN-07:02 | 0.87 |
July | 0.118532E+10 | 0.28 | 1943.43 | 01-JUL-07:02 | 0.87 |
August | 0.124047E+10 | 0.29 | 1943.43 | 01-AUG-07:02 | 0.86 |
September | 0.118868E+10 | 0.29 | 1943.43 | 01-SEP-07:01 | 0.86 |
October | 0.121961E+10 | 0.29 | 1943.43 | 01-OCT-08:62 | 0.86 |
November | 0.108020E+10 | 0.27 | 1943.43 | 01-NOV-07:01 | 0.86 |
December | 0.106813E+10 | 0.27 | 1943.43 | 01-DEC-08:61 | 0.86 |
Annual Sum or Average | 0.132519E+11 | 0.28 | |||
Minimum of Months | 0.968320E+09 | 0.26 | 1943.43 | 0.86 | |
Maximum of Months | 0.124047E+10 | 0.29 | 1943.43 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.568495E+09 | 0.27 | 1049.87 | 01-JAN-09:02 | 0.89 |
February | 0.522454E+09 | 0.28 | 1049.87 | 04-FEB-08:62 | 0.90 |
March | 0.580050E+09 | 0.28 | 1049.87 | 01-MAR-08:62 | 0.90 |
April | 0.547364E+09 | 0.27 | 1049.87 | 05-APR-07:02 | 0.90 |
May | 0.587555E+09 | 0.28 | 1049.87 | 01-MAY-07:02 | 0.90 |
June | 0.576990E+09 | 0.28 | 1049.87 | 01-JUN-07:02 | 0.90 |
July | 0.639300E+09 | 0.29 | 1049.87 | 01-JUL-07:02 | 0.90 |
August | 0.669788E+09 | 0.30 | 1049.87 | 01-AUG-07:02 | 0.89 |
September | 0.640458E+09 | 0.30 | 1049.87 | 01-SEP-07:01 | 0.89 |
October | 0.658272E+09 | 0.30 | 1049.87 | 01-OCT-08:62 | 0.89 |
November | 0.582448E+09 | 0.28 | 1049.87 | 01-NOV-07:01 | 0.89 |
December | 0.576243E+09 | 0.27 | 1049.87 | 01-DEC-08:61 | 0.89 |
Annual Sum or Average | 0.714942E+10 | 0.28 | |||
Minimum of Months | 0.522454E+09 | 0.27 | 1049.87 | 0.89 | |
Maximum of Months | 0.669788E+09 | 0.30 | 1049.87 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.565087E+09 | 0.27 | 1043.87 | 01-JAN-09:02 | 0.89 |
February | 0.519231E+09 | 0.28 | 1043.87 | 04-FEB-08:62 | 0.90 |
March | 0.576558E+09 | 0.28 | 1043.87 | 01-MAR-08:62 | 0.90 |
April | 0.544144E+09 | 0.27 | 1043.87 | 05-APR-07:02 | 0.90 |
May | 0.583970E+09 | 0.28 | 1043.87 | 01-MAY-07:02 | 0.90 |
June | 0.573444E+09 | 0.28 | 1043.87 | 01-JUN-07:02 | 0.90 |
July | 0.635474E+09 | 0.29 | 1043.87 | 01-JUL-07:02 | 0.90 |
August | 0.665966E+09 | 0.30 | 1043.87 | 01-AUG-07:02 | 0.89 |
September | 0.636638E+09 | 0.30 | 1043.87 | 01-SEP-07:01 | 0.89 |
October | 0.654424E+09 | 0.30 | 1043.87 | 01-OCT-08:62 | 0.89 |
November | 0.578849E+09 | 0.28 | 1043.87 | 01-NOV-07:01 | 0.89 |
December | 0.572721E+09 | 0.27 | 1043.87 | 01-DEC-08:61 | 0.89 |
Annual Sum or Average | 0.710651E+10 | 0.28 | |||
Minimum of Months | 0.519231E+09 | 0.27 | 1043.87 | 0.89 | |
Maximum of Months | 0.665966E+09 | 0.30 | 1043.87 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.565478E+09 | 0.27 | 1045.50 | 01-JAN-09:02 | 0.89 |
February | 0.519275E+09 | 0.28 | 1045.50 | 04-FEB-08:62 | 0.90 |
March | 0.576968E+09 | 0.28 | 1045.50 | 01-MAR-08:62 | 0.90 |
April | 0.544765E+09 | 0.27 | 1045.50 | 06-APR-07:02 | 0.90 |
May | 0.584668E+09 | 0.28 | 1045.50 | 01-MAY-07:02 | 0.90 |
June | 0.574214E+09 | 0.28 | 1045.50 | 01-JUN-07:02 | 0.90 |
July | 0.636697E+09 | 0.29 | 1045.50 | 01-JUL-07:02 | 0.90 |
August | 0.667842E+09 | 0.30 | 1045.50 | 01-AUG-07:02 | 0.89 |
September | 0.637719E+09 | 0.30 | 1045.50 | 01-SEP-07:01 | 0.89 |
October | 0.655706E+09 | 0.30 | 1045.50 | 01-OCT-08:62 | 0.89 |
November | 0.579046E+09 | 0.28 | 1045.50 | 01-NOV-07:01 | 0.89 |
December | 0.572958E+09 | 0.27 | 1045.50 | 01-DEC-08:61 | 0.89 |
Annual Sum or Average | 0.711534E+10 | 0.28 | |||
Minimum of Months | 0.519275E+09 | 0.27 | 1045.50 | 0.89 | |
Maximum of Months | 0.667842E+09 | 0.30 | 1045.50 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.646101E+09 | 0.27 | 1196.08 | 01-JAN-09:02 | 0.89 |
February | 0.591736E+09 | 0.28 | 1196.08 | 17-FEB-08:62 | 0.89 |
March | 0.659088E+09 | 0.28 | 1196.08 | 02-MAR-08:62 | 0.89 |
April | 0.623459E+09 | 0.27 | 1196.08 | 07-APR-07:02 | 0.90 |
May | 0.675296E+09 | 0.28 | 1196.08 | 04-MAY-07:02 | 0.89 |
June | 0.664266E+09 | 0.29 | 1196.08 | 01-JUN-07:02 | 0.89 |
July | 0.740221E+09 | 0.29 | 1196.08 | 01-JUL-07:02 | 0.89 |
August | 0.780586E+09 | 0.31 | 1196.08 | 01-AUG-07:02 | 0.89 |
September | 0.735755E+09 | 0.30 | 1196.08 | 01-SEP-07:01 | 0.89 |
October | 0.761506E+09 | 0.30 | 1196.08 | 01-OCT-08:62 | 0.89 |
November | 0.661670E+09 | 0.28 | 1196.08 | 01-NOV-07:01 | 0.89 |
December | 0.653851E+09 | 0.27 | 1196.08 | 01-DEC-08:61 | 0.89 |
Annual Sum or Average | 0.819353E+10 | 0.29 | |||
Minimum of Months | 0.591736E+09 | 0.27 | 1196.08 | 0.89 | |
Maximum of Months | 0.780586E+09 | 0.31 | 1196.08 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.31 | 0.41 |
February | 0.14 | 0.90 |
March | 0.69 | 0.36 |
April | 0.00 | 0.00 |
May | 0.75 | 0.00 |
June | 0.94 | 0.00 |
July | 0.56 | 0.00 |
August | 0.19 | 0.00 |
September | 0.00 | 0.00 |
October | 0.72 | 0.00 |
November | 0.58 | 0.00 |
December | 0.53 | 0.00 |
Annual Sum or Average | 5.42 | 0.09 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.94 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.64 | 0.10 |
February | 0.14 | 0.00 |
March | 0.69 | 0.00 |
April | 0.00 | 0.00 |
May | 1.25 | 0.00 |
June | 1.53 | 0.00 |
July | 0.56 | 0.00 |
August | 0.28 | 0.00 |
September | 0.00 | 0.00 |
October | 0.97 | 0.00 |
November | 0.75 | 0.00 |
December | 1.03 | 0.00 |
Annual Sum or Average | 7.83 | 0.01 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.53 | 0.10 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.21 | 0.75 |
February | 0.31 | 0.75 |
March | 1.36 | 0.66 |
April | 0.50 | 0.75 |
May | 2.07 | 0.75 |
June | 2.05 | 0.75 |
July | 1.65 | 0.75 |
August | 1.32 | 0.75 |
September | 1.96 | 0.75 |
October | 2.28 | 0.75 |
November | 1.30 | 0.75 |
December | 1.47 | 0.75 |
Annual Sum or Average | 16.48 | 0.74 |
Minimum of Months | 0.21 | 0.66 |
Maximum of Months | 2.28 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.21 | 0.75 |
February | 0.31 | 0.75 |
March | 1.52 | 0.59 |
April | 0.50 | 0.75 |
May | 2.07 | 0.75 |
June | 2.05 | 0.75 |
July | 1.65 | 0.75 |
August | 1.32 | 0.75 |
September | 1.96 | 0.75 |
October | 2.28 | 0.75 |
November | 1.30 | 0.75 |
December | 1.39 | 0.75 |
Annual Sum or Average | 16.56 | 0.73 |
Minimum of Months | 0.21 | 0.59 |
Maximum of Months | 2.28 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.21 | 0.75 |
February | 0.22 | 0.47 |
March | 1.03 | 0.75 |
April | 0.42 | 0.75 |
May | 1.93 | 0.75 |
June | 2.00 | 0.75 |
July | 1.65 | 0.75 |
August | 1.43 | 0.66 |
September | 1.79 | 0.75 |
October | 2.31 | 0.70 |
November | 1.21 | 0.75 |
December | 1.22 | 0.75 |
Annual Sum or Average | 15.42 | 0.73 |
Minimum of Months | 0.21 | 0.47 |
Maximum of Months | 2.31 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.12 | 3.30 |
February | 0.00 | 0.00 |
March | 0.34 | 3.30 |
April | 0.25 | 3.30 |
May | 0.62 | 3.00 |
June | 0.90 | 2.28 |
July | 2.68 | 1.66 |
August | 1.79 | 1.77 |
September | 1.89 | 1.94 |
October | 1.73 | 1.87 |
November | 0.74 | 2.06 |
December | 0.33 | 3.30 |
Annual Sum or Average | 11.40 | 2.05 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.68 | 3.30 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.12 | 1.65 |
February | 0.00 | 0.00 |
March | 0.34 | 1.65 |
April | 0.25 | 1.65 |
May | 0.51 | 1.47 |
June | 0.73 | 1.40 |
July | 2.01 | 1.10 |
August | 1.59 | 0.96 |
September | 1.28 | 1.29 |
October | 1.27 | 1.11 |
November | 0.74 | 1.03 |
December | 0.25 | 1.65 |
Annual Sum or Average | 9.10 | 1.20 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.01 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.12 | 1.65 |
February | 0.00 | 0.00 |
March | 0.34 | 1.65 |
April | 0.25 | 1.65 |
May | 0.51 | 1.47 |
June | 0.73 | 1.40 |
July | 1.93 | 1.08 |
August | 1.59 | 0.96 |
September | 1.28 | 1.29 |
October | 1.13 | 1.16 |
November | 0.66 | 1.16 |
December | 0.25 | 1.65 |
Annual Sum or Average | 8.79 | 1.22 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.93 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.12 | 1.65 |
February | 0.00 | 0.00 |
March | 0.34 | 1.65 |
April | 0.25 | 1.65 |
May | 0.51 | 1.47 |
June | 0.68 | 1.38 |
July | 2.01 | 1.10 |
August | 1.59 | 0.96 |
September | 1.22 | 1.27 |
October | 1.13 | 1.16 |
November | 0.66 | 1.16 |
December | 0.25 | 1.65 |
Annual Sum or Average | 8.77 | 1.22 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.01 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.12 | 1.65 |
February | 0.00 | 0.00 |
March | 0.51 | 1.11 |
April | 0.25 | 1.65 |
May | 0.71 | 1.33 |
June | 0.90 | 1.14 |
July | 3.07 | 0.75 |
August | 2.63 | 0.60 |
September | 1.80 | 1.01 |
October | 1.81 | 0.89 |
November | 0.74 | 1.03 |
December | 0.25 | 1.65 |
Annual Sum or Average | 12.79 | 0.91 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.07 | 1.65 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.779694E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.788206E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.845990E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.814394E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.991665E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.998067E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.116005E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.118529E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.117022E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.115454E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.969436E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.899281E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.117568E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.779694E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.118529E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.407659E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.405791E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.435222E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.416787E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.501658E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.501202E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.579000E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.591392E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.578949E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.581732E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.491986E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.461694E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.595307E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.405791E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.591392E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.322924E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.321760E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.348380E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.329537E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.404723E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.407173E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.465862E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.487412E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.464282E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.470510E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.398285E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.366258E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.478711E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.321760E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.487412E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.322360E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.321304E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.348077E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.329201E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.404888E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.407490E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.466726E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.488169E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.465431E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.471465E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.398398E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.366045E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.478955E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.321304E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.488169E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.315697E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.314871E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.340964E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.322650E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.398220E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.401088E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.460174E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.481191E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.458957E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.464688E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.392156E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.359614E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.471027E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.314871E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.481191E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.531309E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.535115E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.581069E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.546719E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.687929E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.693988E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.801716E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.842548E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.800753E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.814505E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.676617E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.613007E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.812527E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.531309E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.842548E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.272364E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.273999E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.297731E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.280247E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.352636E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.355424E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.411199E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.432371E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.410491E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.418169E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.346729E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.314184E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.416554E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.272364E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.432371E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.270034E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.271719E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.295332E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.278108E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.350445E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.353278E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.409027E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.430186E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.408295E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.415939E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.344459E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.311878E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.413870E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.270034E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.430186E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.267840E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.269244E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.293020E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.276738E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.350149E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.353125E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.409472E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.431093E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.408598E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.416234E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.343431E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.310222E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.412917E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.267840E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.431093E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.297233E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.293271E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.322406E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.312265E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.398593E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.401922E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.466149E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.493447E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.457971E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.470556E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.381189E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.343047E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.463805E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.293271E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.493447E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.156927E+10 | 0.253538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144290E+10 | 0.269437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157854E+10 | 0.282279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151476E+10 | 0.269309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161057E+10 | 0.341366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.157290E+10 | 0.347307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.174550E+10 | 0.405988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.177868E+10 | 0.412058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174795E+10 | 0.414529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176816E+10 | 0.402688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159092E+10 | 0.336379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160241E+10 | 0.306341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195226E+11 | 0.404122E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.144290E+10 | 0.253538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.177868E+10 | 0.414529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.763815E+09 | 0.135970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.710789E+09 | 0.140749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.776701E+09 | 0.147404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.740431E+09 | 0.139862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.803005E+09 | 0.173809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.787035E+09 | 0.174993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.881382E+09 | 0.202437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.901049E+09 | 0.205420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.883590E+09 | 0.204440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.896817E+09 | 0.203298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.793316E+09 | 0.172087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.789146E+09 | 0.159566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.972708E+10 | 0.206003E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.710789E+09 | 0.135970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.901049E+09 | 0.205420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.684987E+09 | 0.105871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.630083E+09 | 0.110483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.699407E+09 | 0.116268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.659776E+09 | 0.108936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.707878E+09 | 0.139667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.693903E+09 | 0.142163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.761662E+09 | 0.163066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.795667E+09 | 0.169179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.761772E+09 | 0.164142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.781880E+09 | 0.164230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.698183E+09 | 0.139083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.693996E+09 | 0.125832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.856919E+10 | 0.164892E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.630083E+09 | 0.105871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.795667E+09 | 0.169179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.686460E+09 | 0.105501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.631107E+09 | 0.110182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.700732E+09 | 0.116022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.661244E+09 | 0.108661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.708941E+09 | 0.139659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.695039E+09 | 0.142223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.763137E+09 | 0.163376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.797043E+09 | 0.169443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.763579E+09 | 0.164567E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.783492E+09 | 0.164574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.699413E+09 | 0.139040E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.695244E+09 | 0.125632E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.858543E+10 | 0.164888E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.631107E+09 | 0.105501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.797043E+09 | 0.169443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.679241E+09 | 0.102813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.623787E+09 | 0.107563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.692941E+09 | 0.113162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.654468E+09 | 0.106001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.700004E+09 | 0.137079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.686181E+09 | 0.139754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.752717E+09 | 0.160993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.786162E+09 | 0.166909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.753161E+09 | 0.162199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.772965E+09 | 0.162096E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.690878E+09 | 0.136593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.687308E+09 | 0.123045E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.847981E+10 | 0.161821E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.623787E+09 | 0.102813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.786162E+09 | 0.166909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.105315E+10 | 0.173056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.968320E+09 | 0.183219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107471E+10 | 0.193335E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101372E+10 | 0.179868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108927E+10 | 0.237589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107028E+10 | 0.242565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118532E+10 | 0.281321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124047E+10 | 0.293005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118868E+10 | 0.283754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121961E+10 | 0.285052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108020E+10 | 0.236158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106813E+10 | 0.210129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132519E+11 | 0.279905E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.968320E+09 | 0.173056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124047E+10 | 0.293005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.568495E+09 | 0.889326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.522454E+09 | 0.941646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.580050E+09 | 0.994140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.547364E+09 | 0.925194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587555E+09 | 0.122515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.576990E+09 | 0.124970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.639300E+09 | 0.145260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.669788E+09 | 0.151347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.640458E+09 | 0.146456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.658272E+09 | 0.147335E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.582448E+09 | 0.121708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.576243E+09 | 0.108172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.714942E+10 | 0.144279E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.522454E+09 | 0.889326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.669788E+09 | 0.151347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.565087E+09 | 0.880684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.519231E+09 | 0.933007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.576558E+09 | 0.985261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.544144E+09 | 0.917379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.583970E+09 | 0.121735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.573444E+09 | 0.124202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.635474E+09 | 0.144513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.665966E+09 | 0.150608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.636638E+09 | 0.145695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.654424E+09 | 0.146569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.578849E+09 | 0.120876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.572721E+09 | 0.107313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.710651E+10 | 0.143314E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.519231E+09 | 0.880684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.665966E+09 | 0.150608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.565478E+09 | 0.870363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.519275E+09 | 0.921351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.576968E+09 | 0.974368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.544765E+09 | 0.910725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.584668E+09 | 0.121540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.574214E+09 | 0.124069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.636697E+09 | 0.144616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.667842E+09 | 0.150889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.637719E+09 | 0.145740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.655706E+09 | 0.146607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.579046E+09 | 0.120345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.572958E+09 | 0.106506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.711534E+10 | 0.142799E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.519275E+09 | 0.870363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.667842E+09 | 0.150889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.646101E+09 | 0.957608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.591736E+09 | 0.988330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.659088E+09 | 0.105992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.623459E+09 | 0.102610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.675296E+09 | 0.138123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.664266E+09 | 0.140929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.740221E+09 | 0.163950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.780586E+09 | 0.172036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.735755E+09 | 0.162088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.761506E+09 | 0.164616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.661670E+09 | 0.132492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.653851E+09 | 0.116644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.819353E+10 | 0.159407E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.591736E+09 | 0.957608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.780586E+09 | 0.172036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.156927E+10 | 0.00 | 0.00 | 0.00 | 0.622767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144290E+10 | 0.00 | 0.00 | 0.00 | 0.643916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157854E+10 | 0.00 | 0.00 | 0.00 | 0.688136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151476E+10 | 0.00 | 0.00 | 0.00 | 0.662918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161057E+10 | 0.00 | 0.00 | 0.00 | 0.830608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.157290E+10 | 0.00 | 0.00 | 0.00 | 0.840776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.174550E+10 | 0.00 | 0.00 | 0.00 | 0.985500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.177868E+10 | 0.00 | 0.00 | 0.00 | 0.100742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174795E+10 | 0.00 | 0.00 | 0.00 | 0.995422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176816E+10 | 0.00 | 0.00 | 0.00 | 0.977721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159092E+10 | 0.00 | 0.00 | 0.00 | 0.810343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160241E+10 | 0.00 | 0.00 | 0.00 | 0.739040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195226E+11 | 0.00 | 0.00 | 0.00 | 0.980457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.144290E+10 | 0.00 | 0.00 | 0.00 | 0.622767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.177868E+10 | 0.00 | 0.00 | 0.00 | 0.100742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.763815E+09 | 0.00 | 0.00 | 0.00 | 0.331278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.710789E+09 | 0.00 | 0.00 | 0.00 | 0.334712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.776701E+09 | 0.00 | 0.00 | 0.00 | 0.357552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.740431E+09 | 0.00 | 0.00 | 0.00 | 0.342744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.803005E+09 | 0.00 | 0.00 | 0.00 | 0.421358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.787035E+09 | 0.00 | 0.00 | 0.00 | 0.422498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.881382E+09 | 0.00 | 0.00 | 0.00 | 0.490862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.901049E+09 | 0.00 | 0.00 | 0.00 | 0.501287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.883590E+09 | 0.00 | 0.00 | 0.00 | 0.490590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.896817E+09 | 0.00 | 0.00 | 0.00 | 0.492050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.793316E+09 | 0.00 | 0.00 | 0.00 | 0.412654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.789146E+09 | 0.00 | 0.00 | 0.00 | 0.382779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.972708E+10 | 0.00 | 0.00 | 0.00 | 0.498036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.710789E+09 | 0.00 | 0.00 | 0.00 | 0.331278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.901049E+09 | 0.00 | 0.00 | 0.00 | 0.501287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.684987E+09 | 0.00 | 0.00 | 0.00 | 0.254426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.630083E+09 | 0.00 | 0.00 | 0.00 | 0.258751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.699407E+09 | 0.00 | 0.00 | 0.00 | 0.278439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.659776E+09 | 0.00 | 0.00 | 0.00 | 0.263559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.707878E+09 | 0.00 | 0.00 | 0.00 | 0.333935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.693903E+09 | 0.00 | 0.00 | 0.00 | 0.337783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.761662E+09 | 0.00 | 0.00 | 0.00 | 0.389696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.795667E+09 | 0.00 | 0.00 | 0.00 | 0.407845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.761772E+09 | 0.00 | 0.00 | 0.00 | 0.388105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.781880E+09 | 0.00 | 0.00 | 0.00 | 0.392323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.698183E+09 | 0.00 | 0.00 | 0.00 | 0.328467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.693996E+09 | 0.00 | 0.00 | 0.00 | 0.296859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.856919E+10 | 0.00 | 0.00 | 0.00 | 0.393019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.630083E+09 | 0.00 | 0.00 | 0.00 | 0.254426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.795667E+09 | 0.00 | 0.00 | 0.00 | 0.407845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.686460E+09 | 0.00 | 0.00 | 0.00 | 0.253714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.631107E+09 | 0.00 | 0.00 | 0.00 | 0.258193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.700732E+09 | 0.00 | 0.00 | 0.00 | 0.278004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.661244E+09 | 0.00 | 0.00 | 0.00 | 0.263077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.708941E+09 | 0.00 | 0.00 | 0.00 | 0.333994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.695039E+09 | 0.00 | 0.00 | 0.00 | 0.337986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.763137E+09 | 0.00 | 0.00 | 0.00 | 0.390412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.797043E+09 | 0.00 | 0.00 | 0.00 | 0.408465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.763579E+09 | 0.00 | 0.00 | 0.00 | 0.389073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.783492E+09 | 0.00 | 0.00 | 0.00 | 0.393115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.699413E+09 | 0.00 | 0.00 | 0.00 | 0.328457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.695244E+09 | 0.00 | 0.00 | 0.00 | 0.296521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.858543E+10 | 0.00 | 0.00 | 0.00 | 0.393101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.631107E+09 | 0.00 | 0.00 | 0.00 | 0.253714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.797043E+09 | 0.00 | 0.00 | 0.00 | 0.408465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.679241E+09 | 0.00 | 0.00 | 0.00 | 0.247773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.623787E+09 | 0.00 | 0.00 | 0.00 | 0.252492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.692941E+09 | 0.00 | 0.00 | 0.00 | 0.271669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.654468E+09 | 0.00 | 0.00 | 0.00 | 0.257203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.700004E+09 | 0.00 | 0.00 | 0.00 | 0.328219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.686181E+09 | 0.00 | 0.00 | 0.00 | 0.332470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.752717E+09 | 0.00 | 0.00 | 0.00 | 0.384902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.786162E+09 | 0.00 | 0.00 | 0.00 | 0.402575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.753161E+09 | 0.00 | 0.00 | 0.00 | 0.383641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.772965E+09 | 0.00 | 0.00 | 0.00 | 0.387391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.690878E+09 | 0.00 | 0.00 | 0.00 | 0.323069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.687308E+09 | 0.00 | 0.00 | 0.00 | 0.290883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.847981E+10 | 0.00 | 0.00 | 0.00 | 0.386229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.623787E+09 | 0.00 | 0.00 | 0.00 | 0.247773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.786162E+09 | 0.00 | 0.00 | 0.00 | 0.402575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.105315E+10 | 0.00 | 0.00 | 0.00 | 0.425994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.968320E+09 | 0.00 | 0.00 | 0.00 | 0.438283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107471E+10 | 0.00 | 0.00 | 0.00 | 0.473598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101372E+10 | 0.00 | 0.00 | 0.00 | 0.445347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108927E+10 | 0.00 | 0.00 | 0.00 | 0.579002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107028E+10 | 0.00 | 0.00 | 0.00 | 0.586960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118532E+10 | 0.00 | 0.00 | 0.00 | 0.683184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124047E+10 | 0.00 | 0.00 | 0.00 | 0.718500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118868E+10 | 0.00 | 0.00 | 0.00 | 0.681885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121961E+10 | 0.00 | 0.00 | 0.00 | 0.692544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108020E+10 | 0.00 | 0.00 | 0.00 | 0.568597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106813E+10 | 0.00 | 0.00 | 0.00 | 0.506194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132519E+11 | 0.00 | 0.00 | 0.00 | 0.680009E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.968320E+09 | 0.00 | 0.00 | 0.00 | 0.425994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124047E+10 | 0.00 | 0.00 | 0.00 | 0.718500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.568495E+09 | 0.00 | 0.00 | 0.00 | 0.215515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.522454E+09 | 0.00 | 0.00 | 0.00 | 0.221754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.580050E+09 | 0.00 | 0.00 | 0.00 | 0.239726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.547364E+09 | 0.00 | 0.00 | 0.00 | 0.225510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587555E+09 | 0.00 | 0.00 | 0.00 | 0.293881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.576990E+09 | 0.00 | 0.00 | 0.00 | 0.297725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.639300E+09 | 0.00 | 0.00 | 0.00 | 0.347269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.669788E+09 | 0.00 | 0.00 | 0.00 | 0.365392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.640458E+09 | 0.00 | 0.00 | 0.00 | 0.346445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.658272E+09 | 0.00 | 0.00 | 0.00 | 0.352341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.582448E+09 | 0.00 | 0.00 | 0.00 | 0.288485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.576243E+09 | 0.00 | 0.00 | 0.00 | 0.256560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.714942E+10 | 0.00 | 0.00 | 0.00 | 0.345060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.522454E+09 | 0.00 | 0.00 | 0.00 | 0.215515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.669788E+09 | 0.00 | 0.00 | 0.00 | 0.365392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.565087E+09 | 0.00 | 0.00 | 0.00 | 0.213525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.519231E+09 | 0.00 | 0.00 | 0.00 | 0.219796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.576558E+09 | 0.00 | 0.00 | 0.00 | 0.237677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.544144E+09 | 0.00 | 0.00 | 0.00 | 0.223693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.583970E+09 | 0.00 | 0.00 | 0.00 | 0.292048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.573444E+09 | 0.00 | 0.00 | 0.00 | 0.295934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.635474E+09 | 0.00 | 0.00 | 0.00 | 0.345479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.665966E+09 | 0.00 | 0.00 | 0.00 | 0.363589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.636638E+09 | 0.00 | 0.00 | 0.00 | 0.344632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.654424E+09 | 0.00 | 0.00 | 0.00 | 0.350496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.578849E+09 | 0.00 | 0.00 | 0.00 | 0.286574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.572721E+09 | 0.00 | 0.00 | 0.00 | 0.254606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.710651E+10 | 0.00 | 0.00 | 0.00 | 0.342805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.519231E+09 | 0.00 | 0.00 | 0.00 | 0.213525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.665966E+09 | 0.00 | 0.00 | 0.00 | 0.363589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.565478E+09 | 0.00 | 0.00 | 0.00 | 0.211292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.519275E+09 | 0.00 | 0.00 | 0.00 | 0.217316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.576968E+09 | 0.00 | 0.00 | 0.00 | 0.235324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.544765E+09 | 0.00 | 0.00 | 0.00 | 0.222261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.584668E+09 | 0.00 | 0.00 | 0.00 | 0.291682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.574214E+09 | 0.00 | 0.00 | 0.00 | 0.295704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.636697E+09 | 0.00 | 0.00 | 0.00 | 0.345803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.667842E+09 | 0.00 | 0.00 | 0.00 | 0.364308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.637719E+09 | 0.00 | 0.00 | 0.00 | 0.344826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.655706E+09 | 0.00 | 0.00 | 0.00 | 0.350663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.579046E+09 | 0.00 | 0.00 | 0.00 | 0.285526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.572958E+09 | 0.00 | 0.00 | 0.00 | 0.252927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.711534E+10 | 0.00 | 0.00 | 0.00 | 0.341763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.519275E+09 | 0.00 | 0.00 | 0.00 | 0.211292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.667842E+09 | 0.00 | 0.00 | 0.00 | 0.364308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.646101E+09 | 0.00 | 0.00 | 0.00 | 0.232623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.591736E+09 | 0.00 | 0.00 | 0.00 | 0.234097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.659088E+09 | 0.00 | 0.00 | 0.00 | 0.256497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.623459E+09 | 0.00 | 0.00 | 0.00 | 0.249919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.675296E+09 | 0.00 | 0.00 | 0.00 | 0.331063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.664266E+09 | 0.00 | 0.00 | 0.00 | 0.335496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.740221E+09 | 0.00 | 0.00 | 0.00 | 0.392127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.780586E+09 | 0.00 | 0.00 | 0.00 | 0.415388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.735755E+09 | 0.00 | 0.00 | 0.00 | 0.384395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.761506E+09 | 0.00 | 0.00 | 0.00 | 0.394406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.661670E+09 | 0.00 | 0.00 | 0.00 | 0.315022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.653851E+09 | 0.00 | 0.00 | 0.00 | 0.277662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.819353E+10 | 0.00 | 0.00 | 0.00 | 0.381869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.591736E+09 | 0.00 | 0.00 | 0.00 | 0.232623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.780586E+09 | 0.00 | 0.00 | 0.00 | 0.415388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 11765438.15 | 0.488863E+10 | 0.00 | 2885532.97 | 36365598.62 | 0.00 | 0.124558E+09 | 0.00 | 0.57 |
February | 11018270.48 | 0.710408E+10 | 0.00 | 1642826.59 | 58792943.31 | 0.00 | 0.116165E+09 | 0.00 | 0.57 |
March | 10147121.22 | 0.662687E+10 | 0.00 | 1330098.46 | 42117566.71 | 0.00 | 69796402.49 | 0.00 | 0.57 |
April | 5397258.30 | 0.628527E+10 | 0.00 | 517039.82 | 47519906.41 | 0.00 | 10591355.67 | 0.00 | 0.57 |
May | 0.00 | 0.995325E+10 | 0.00 | 25909.44 | 87672224.19 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.00 | 0.102823E+11 | 0.00 | 0.00 | 80728029.21 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 12045.29 | 0.130784E+11 | 0.00 | 228257.09 | 74508880.28 | 0.00 | 326282.62 | 0.00 | 0.57 |
August | 0.00 | 0.135549E+11 | 0.00 | 0.00 | 81383886.93 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.138439E+11 | 0.00 | 0.00 | 80645674.42 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 0.00 | 0.131419E+11 | 0.00 | 62705.01 | 82535379.74 | 0.00 | 0.00 | 0.00 | 0.57 |
November | 2758.06 | 0.948854E+10 | 0.00 | 100595.59 | 76428122.79 | 0.00 | 334159.04 | 0.00 | 0.57 |
December | 1289604.42 | 0.773841E+10 | 0.00 | 690152.22 | 54792996.18 | 0.00 | 10891490.15 | 0.00 | 0.57 |
Annual Sum or Average | 39632495.90 | 0.115986E+12 | 0.00 | 7483117.20 | 0.803491E+09 | 0.00 | 0.332663E+09 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 0.488863E+10 | 0.00 | 0.00 | 36365598.62 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 11765438.15 | 0.138439E+11 | 0.00 | 2885532.97 | 87672224.19 | 0.00 | 0.124558E+09 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2423591.55 | 0.239176E+10 | 0.00 | 1026295.29 | 39739288.28 | 0.00 | 24008221.82 | 0.00 | 0.47 |
February | 925192.36 | 0.331245E+10 | 0.00 | 800735.91 | 50994727.24 | 0.00 | 15522406.58 | 0.00 | 0.48 |
March | 764047.30 | 0.312084E+10 | 0.00 | 334111.03 | 40737743.52 | 0.00 | 6615562.10 | 0.00 | 0.48 |
April | 1024994.37 | 0.292234E+10 | 0.00 | 111599.14 | 44372219.65 | 0.00 | 1744569.52 | 0.00 | 0.47 |
May | 0.00 | 0.451047E+10 | 0.00 | 0.00 | 69444919.71 | 0.00 | 0.00 | 0.00 | 0.48 |
June | 0.00 | 0.462367E+10 | 0.00 | 0.00 | 62552069.67 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.583536E+10 | 0.00 | 0.00 | 55298392.36 | 0.00 | 0.00 | 0.00 | 0.49 |
August | 0.00 | 0.607969E+10 | 0.00 | 0.00 | 67387521.06 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.611762E+10 | 0.00 | 0.00 | 59491216.69 | 0.00 | 0.00 | 0.00 | 0.49 |
October | 0.00 | 0.591920E+10 | 0.00 | 0.00 | 65598720.02 | 0.00 | 0.00 | 0.00 | 0.49 |
November | 0.00 | 0.435584E+10 | 0.00 | 0.00 | 57835320.80 | 0.00 | 0.00 | 0.00 | 0.48 |
December | 18981.36 | 0.358684E+10 | 0.00 | 121701.31 | 46638955.75 | 0.00 | 412017.97 | 0.00 | 0.48 |
Annual Sum or Average | 5156806.94 | 0.527761E+11 | 0.00 | 2394442.68 | 0.660091E+09 | 0.00 | 48302778.00 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.239176E+10 | 0.00 | 0.00 | 39739288.28 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 2423591.55 | 0.611762E+10 | 0.00 | 1026295.29 | 69444919.71 | 0.00 | 24008221.82 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 37254514.44 | 0.199181E+10 | 0.00 | 1355476.02 | 63224038.49 | 0.00 | 62765813.63 | 0.00 | 0.45 |
February | 21132972.11 | 0.270006E+10 | 0.00 | 908887.16 | 0.128352E+09 | 0.00 | 41816449.85 | 0.00 | 0.46 |
March | 20195927.26 | 0.258114E+10 | 0.00 | 931533.43 | 0.113422E+09 | 0.00 | 55929539.85 | 0.00 | 0.46 |
April | 9786063.56 | 0.240842E+10 | 0.00 | 679120.47 | 0.103093E+09 | 0.00 | 22630310.00 | 0.00 | 0.46 |
May | 1295275.63 | 0.375234E+10 | 0.00 | 602112.54 | 0.209192E+09 | 0.00 | 1439278.79 | 0.00 | 0.46 |
June | 0.00 | 0.390914E+10 | 0.00 | 69186.41 | 0.228217E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.480566E+10 | 0.00 | 118421.01 | 0.280657E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.507190E+10 | 0.00 | 245668.61 | 0.297999E+09 | 0.00 | 25855.39 | 0.00 | 0.46 |
September | 0.00 | 0.489819E+10 | 0.00 | 328856.33 | 0.306072E+09 | 0.00 | 179230.25 | 0.00 | 0.46 |
October | 402765.05 | 0.479118E+10 | 0.00 | 787635.64 | 0.279488E+09 | 0.00 | 2457150.56 | 0.00 | 0.46 |
November | 2544221.94 | 0.365928E+10 | 0.00 | 461975.59 | 0.180665E+09 | 0.00 | 4288135.15 | 0.00 | 0.46 |
December | 7246080.34 | 0.295280E+10 | 0.00 | 890173.34 | 0.141623E+09 | 0.00 | 10635725.33 | 0.00 | 0.45 |
Annual Sum or Average | 99857820.35 | 0.435219E+11 | 0.00 | 7379046.55 | 0.233200E+10 | 0.00 | 0.202167E+09 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.199181E+10 | 0.00 | 69186.41 | 63224038.49 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 37254514.44 | 0.507190E+10 | 0.00 | 1355476.02 | 0.306072E+09 | 0.00 | 62765813.63 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 37756736.03 | 0.198672E+10 | 0.00 | 1349508.72 | 62937472.99 | 0.00 | 63305720.12 | 0.00 | 0.45 |
February | 21410337.99 | 0.269468E+10 | 0.00 | 906623.84 | 0.127915E+09 | 0.00 | 42002391.12 | 0.00 | 0.46 |
March | 20403624.37 | 0.257746E+10 | 0.00 | 923189.68 | 0.113127E+09 | 0.00 | 56269397.39 | 0.00 | 0.46 |
April | 9832577.76 | 0.240388E+10 | 0.00 | 673982.19 | 0.103085E+09 | 0.00 | 22882904.77 | 0.00 | 0.46 |
May | 1290367.32 | 0.375201E+10 | 0.00 | 611189.89 | 0.208836E+09 | 0.00 | 1435583.26 | 0.00 | 0.46 |
June | 0.00 | 0.390955E+10 | 0.00 | 73882.36 | 0.228136E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.480997E+10 | 0.00 | 126165.92 | 0.280966E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.507608E+10 | 0.00 | 258142.22 | 0.297619E+09 | 0.00 | 25927.35 | 0.00 | 0.46 |
September | 0.00 | 0.490570E+10 | 0.00 | 344838.14 | 0.305578E+09 | 0.00 | 179663.82 | 0.00 | 0.46 |
October | 337810.00 | 0.479696E+10 | 0.00 | 813182.64 | 0.279369E+09 | 0.00 | 2503527.32 | 0.00 | 0.46 |
November | 2548049.75 | 0.365795E+10 | 0.00 | 466845.53 | 0.180417E+09 | 0.00 | 4340408.14 | 0.00 | 0.46 |
December | 7260437.74 | 0.294938E+10 | 0.00 | 889337.98 | 0.141235E+09 | 0.00 | 10849066.03 | 0.00 | 0.45 |
Annual Sum or Average | 0.100840E+09 | 0.435203E+11 | 0.00 | 7436889.14 | 0.232922E+10 | 0.00 | 0.203795E+09 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.198672E+10 | 0.00 | 73882.36 | 62937472.99 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 37756736.03 | 0.507608E+10 | 0.00 | 1349508.72 | 0.305578E+09 | 0.00 | 63305720.12 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 38541627.88 | 0.195441E+10 | 0.00 | 1288059.53 | 62207595.96 | 0.00 | 67038518.21 | 0.00 | 0.45 |
February | 24563025.56 | 0.265301E+10 | 0.00 | 831461.31 | 0.125376E+09 | 0.00 | 41273246.65 | 0.00 | 0.46 |
March | 22579203.52 | 0.253845E+10 | 0.00 | 828548.94 | 0.111646E+09 | 0.00 | 57469054.18 | 0.00 | 0.46 |
April | 10878639.83 | 0.236732E+10 | 0.00 | 606716.06 | 0.101840E+09 | 0.00 | 23320161.64 | 0.00 | 0.46 |
May | 1149317.34 | 0.371711E+10 | 0.00 | 554654.29 | 0.206638E+09 | 0.00 | 1676267.88 | 0.00 | 0.46 |
June | 0.00 | 0.387584E+10 | 0.00 | 59678.36 | 0.227080E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.477787E+10 | 0.00 | 113225.19 | 0.280799E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.504094E+10 | 0.00 | 233395.45 | 0.297586E+09 | 0.00 | 26137.71 | 0.00 | 0.46 |
September | 0.00 | 0.487184E+10 | 0.00 | 322358.90 | 0.304631E+09 | 0.00 | 183226.39 | 0.00 | 0.46 |
October | 423168.36 | 0.476273E+10 | 0.00 | 755086.97 | 0.277646E+09 | 0.00 | 2656901.12 | 0.00 | 0.46 |
November | 2585692.79 | 0.362439E+10 | 0.00 | 426914.36 | 0.178153E+09 | 0.00 | 4559116.97 | 0.00 | 0.46 |
December | 7160714.53 | 0.291281E+10 | 0.00 | 831601.15 | 0.140228E+09 | 0.00 | 12182932.60 | 0.00 | 0.45 |
Annual Sum or Average | 0.107881E+09 | 0.430967E+11 | 0.00 | 6851700.51 | 0.231383E+10 | 0.00 | 0.210386E+09 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.195441E+10 | 0.00 | 59678.36 | 62207595.96 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 38541627.88 | 0.504094E+10 | 0.00 | 1288059.53 | 0.304631E+09 | 0.00 | 67038518.21 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 30498256.01 | 0.356155E+10 | 0.00 | 1718532.33 | 60335297.44 | 0.00 | 0.101335E+09 | 0.00 | 0.42 |
February | 14876913.85 | 0.493078E+10 | 0.00 | 1014709.68 | 0.115164E+09 | 0.00 | 54469827.81 | 0.00 | 0.42 |
March | 16671106.76 | 0.474299E+10 | 0.00 | 830938.54 | 92691494.34 | 0.00 | 37566987.45 | 0.00 | 0.43 |
April | 9912109.23 | 0.440250E+10 | 0.00 | 495928.77 | 0.100507E+09 | 0.00 | 15761737.77 | 0.00 | 0.42 |
May | 37864.29 | 0.706599E+10 | 0.00 | 380969.17 | 0.181445E+09 | 0.00 | 475430.08 | 0.00 | 0.42 |
June | 0.00 | 0.731457E+10 | 0.00 | 20395.66 | 0.179494E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 61289.33 | 0.908230E+10 | 0.00 | 212310.25 | 0.248382E+09 | 0.00 | 392782.12 | 0.00 | 0.42 |
August | 0.00 | 0.971698E+10 | 0.00 | 123942.57 | 0.229888E+09 | 0.00 | 1726.01 | 0.00 | 0.43 |
September | 0.00 | 0.928285E+10 | 0.00 | 295296.78 | 0.256398E+09 | 0.00 | 157868.05 | 0.00 | 0.42 |
October | 222579.85 | 0.922077E+10 | 0.00 | 427310.96 | 0.242580E+09 | 0.00 | 684489.88 | 0.00 | 0.42 |
November | 4545043.57 | 0.680003E+10 | 0.00 | 69645.07 | 0.151350E+09 | 0.00 | 1301842.10 | 0.00 | 0.42 |
December | 7204287.91 | 0.543008E+10 | 0.00 | 1170853.89 | 0.113102E+09 | 0.00 | 8623519.80 | 0.00 | 0.42 |
Annual Sum or Average | 84029450.81 | 0.815514E+11 | 0.00 | 6760833.68 | 0.197134E+10 | 0.00 | 0.220771E+09 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.356155E+10 | 0.00 | 20395.66 | 60335297.44 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 30498256.01 | 0.971698E+10 | 0.00 | 1718532.33 | 0.256398E+09 | 0.00 | 0.101335E+09 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 15295146.99 | 0.175741E+10 | 0.00 | 859571.74 | 29920608.87 | 0.00 | 52138253.75 | 0.00 | 0.42 |
February | 7411323.69 | 0.243404E+10 | 0.00 | 503626.96 | 55236297.81 | 0.00 | 27648235.90 | 0.00 | 0.42 |
March | 8825081.52 | 0.234491E+10 | 0.00 | 400844.77 | 44160327.42 | 0.00 | 18677828.13 | 0.00 | 0.43 |
April | 5030333.91 | 0.217883E+10 | 0.00 | 234887.98 | 49502268.77 | 0.00 | 7915654.90 | 0.00 | 0.42 |
May | 20469.43 | 0.350667E+10 | 0.00 | 182154.91 | 88078068.23 | 0.00 | 259468.64 | 0.00 | 0.42 |
June | 0.00 | 0.363303E+10 | 0.00 | 11356.23 | 85736071.96 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 34848.20 | 0.451363E+10 | 0.00 | 98563.11 | 0.124248E+09 | 0.00 | 200262.27 | 0.00 | 0.42 |
August | 0.00 | 0.483355E+10 | 0.00 | 61654.93 | 0.113832E+09 | 0.00 | 3734.56 | 0.00 | 0.43 |
September | 0.00 | 0.461154E+10 | 0.00 | 147146.72 | 0.125413E+09 | 0.00 | 101618.29 | 0.00 | 0.42 |
October | 132742.98 | 0.458154E+10 | 0.00 | 211680.20 | 0.120214E+09 | 0.00 | 372682.51 | 0.00 | 0.42 |
November | 2408709.46 | 0.337259E+10 | 0.00 | 32609.02 | 72678147.76 | 0.00 | 691790.72 | 0.00 | 0.42 |
December | 3704755.92 | 0.268678E+10 | 0.00 | 559618.03 | 54635114.95 | 0.00 | 4431640.91 | 0.00 | 0.42 |
Annual Sum or Average | 42863412.10 | 0.404545E+11 | 0.00 | 3303714.57 | 0.963653E+09 | 0.00 | 0.112441E+09 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.175741E+10 | 0.00 | 11356.23 | 29920608.87 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 15295146.99 | 0.483355E+10 | 0.00 | 859571.74 | 0.125413E+09 | 0.00 | 52138253.75 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 15970762.52 | 0.174670E+10 | 0.00 | 848825.07 | 29983612.08 | 0.00 | 52872082.81 | 0.00 | 0.42 |
February | 7344117.77 | 0.241874E+10 | 0.00 | 495268.93 | 56267505.31 | 0.00 | 28330138.76 | 0.00 | 0.42 |
March | 8951918.76 | 0.233259E+10 | 0.00 | 385163.32 | 43875767.40 | 0.00 | 19104192.74 | 0.00 | 0.43 |
April | 5090875.50 | 0.216808E+10 | 0.00 | 224572.04 | 49816218.76 | 0.00 | 8119032.71 | 0.00 | 0.42 |
May | 20697.42 | 0.349668E+10 | 0.00 | 177808.64 | 87849713.61 | 0.00 | 258790.17 | 0.00 | 0.42 |
June | 0.00 | 0.362331E+10 | 0.00 | 9440.83 | 85492385.46 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 39900.73 | 0.450531E+10 | 0.00 | 96034.17 | 0.123762E+09 | 0.00 | 206075.40 | 0.00 | 0.42 |
August | 0.00 | 0.482524E+10 | 0.00 | 60817.03 | 0.113504E+09 | 0.00 | 3648.09 | 0.00 | 0.43 |
September | 0.00 | 0.460173E+10 | 0.00 | 144459.25 | 0.125331E+09 | 0.00 | 102001.26 | 0.00 | 0.42 |
October | 137135.42 | 0.457185E+10 | 0.00 | 207461.15 | 0.120305E+09 | 0.00 | 372585.16 | 0.00 | 0.42 |
November | 2420880.67 | 0.336050E+10 | 0.00 | 31290.96 | 73222309.37 | 0.00 | 721788.25 | 0.00 | 0.42 |
December | 3711362.20 | 0.267494E+10 | 0.00 | 543848.61 | 54191024.31 | 0.00 | 4590779.57 | 0.00 | 0.42 |
Annual Sum or Average | 43687651.00 | 0.403257E+11 | 0.00 | 3224990.00 | 0.963600E+09 | 0.00 | 0.114681E+09 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.174670E+10 | 0.00 | 9440.83 | 29983612.08 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 15970762.52 | 0.482524E+10 | 0.00 | 848825.07 | 0.125331E+09 | 0.00 | 52872082.81 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 16422878.64 | 0.172989E+10 | 0.00 | 810029.14 | 29517334.52 | 0.00 | 55419326.95 | 0.00 | 0.42 |
February | 8607041.61 | 0.239318E+10 | 0.00 | 463825.61 | 56858019.60 | 0.00 | 28393014.89 | 0.00 | 0.42 |
March | 11573917.01 | 0.231038E+10 | 0.00 | 348088.21 | 44380627.29 | 0.00 | 17679782.60 | 0.00 | 0.43 |
April | 5234323.27 | 0.215466E+10 | 0.00 | 196634.58 | 49627596.90 | 0.00 | 8555066.91 | 0.00 | 0.42 |
May | 22136.37 | 0.349016E+10 | 0.00 | 169223.71 | 88049629.18 | 0.00 | 253160.47 | 0.00 | 0.42 |
June | 0.00 | 0.361850E+10 | 0.00 | 4559.63 | 85106490.48 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 57695.78 | 0.450509E+10 | 0.00 | 87196.64 | 0.123333E+09 | 0.00 | 215121.40 | 0.00 | 0.42 |
August | 0.00 | 0.482555E+10 | 0.00 | 58745.26 | 0.115192E+09 | 0.00 | 3155.50 | 0.00 | 0.43 |
September | 0.00 | 0.459932E+10 | 0.00 | 138754.97 | 0.125411E+09 | 0.00 | 100380.81 | 0.00 | 0.42 |
October | 160954.98 | 0.456964E+10 | 0.00 | 195953.19 | 0.119894E+09 | 0.00 | 368915.80 | 0.00 | 0.42 |
November | 2438507.98 | 0.334945E+10 | 0.00 | 26542.70 | 72136377.28 | 0.00 | 804696.99 | 0.00 | 0.42 |
December | 3670656.95 | 0.265829E+10 | 0.00 | 504382.58 | 54283601.50 | 0.00 | 5101842.21 | 0.00 | 0.42 |
Annual Sum or Average | 48188112.60 | 0.402041E+11 | 0.00 | 3003936.21 | 0.963790E+09 | 0.00 | 0.116894E+09 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.172989E+10 | 0.00 | 4559.63 | 29517334.52 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 16422878.64 | 0.482555E+10 | 0.00 | 810029.14 | 0.125411E+09 | 0.00 | 55419326.95 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 18471453.84 | 0.176787E+10 | 0.00 | 897186.23 | 22394605.86 | 0.00 | 61387469.36 | 0.00 | 0.42 |
February | 14588576.79 | 0.240050E+10 | 0.00 | 439972.29 | 48032636.31 | 0.00 | 28713855.88 | 0.00 | 0.42 |
March | 19337062.46 | 0.231459E+10 | 0.00 | 346045.91 | 36589825.33 | 0.00 | 19366831.11 | 0.00 | 0.43 |
April | 6791776.69 | 0.221720E+10 | 0.00 | 267398.74 | 40809396.53 | 0.00 | 10125820.12 | 0.00 | 0.42 |
May | 36658.06 | 0.360516E+10 | 0.00 | 225476.41 | 72112145.76 | 0.00 | 221203.74 | 0.00 | 0.42 |
June | 0.00 | 0.372046E+10 | 0.00 | 68761.36 | 70258379.22 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 318893.43 | 0.461655E+10 | 0.00 | 220951.34 | 0.106221E+09 | 0.00 | 1422021.77 | 0.00 | 0.42 |
August | 0.00 | 0.495835E+10 | 0.00 | 70349.30 | 97349780.23 | 0.00 | 1426.91 | 0.00 | 0.43 |
September | 0.00 | 0.466013E+10 | 0.00 | 196126.86 | 0.114683E+09 | 0.00 | 111850.54 | 0.00 | 0.42 |
October | 96085.52 | 0.468009E+10 | 0.00 | 268970.86 | 0.108689E+09 | 0.00 | 488670.06 | 0.00 | 0.42 |
November | 2582047.21 | 0.340236E+10 | 0.00 | 96624.14 | 55052920.95 | 0.00 | 1295937.30 | 0.00 | 0.42 |
December | 4417653.38 | 0.270446E+10 | 0.00 | 598814.05 | 45829551.83 | 0.00 | 7032859.64 | 0.00 | 0.42 |
Annual Sum or Average | 66640207.37 | 0.410477E+11 | 0.00 | 3696677.51 | 0.818022E+09 | 0.00 | 0.130168E+09 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.176787E+10 | 0.00 | 68761.36 | 22394605.86 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 19337062.46 | 0.495835E+10 | 0.00 | 897186.23 | 0.114683E+09 | 0.00 | 61387469.36 | 0.00 | 0.43 |