Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:20
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2020-06-03 19:20:39
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1619.50 | 774.76 | 774.76 |
Net Site Energy | 1619.50 | 774.76 | 774.76 |
Total Source Energy | 4002.24 | 1914.66 | 1914.66 |
Net Source Energy | 4002.24 | 1914.66 | 1914.66 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 540.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 52.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 550.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 189.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 65.74 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1078.59 | 540.92 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 540.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 52.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 550.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 91.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 189.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 65.74 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 307.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 147.23 | 258.77 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 515.99 | 258.77 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 307.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 147.23 | 258.77 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 515.99 | 258.77 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1078.587 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1078.587 | 100.00 |
Total On-Site and Utility Electric Sources | 1078.587 | 100.00 |
Total Electricity End Uses | 1078.587 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1.67 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2104.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Meter |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.75 | 20.75 | 20.0855 | 11.61 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.37 | 10.37 | 22.9594 | 11.61 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 20.8066 | 11.61 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 20.8066 | 11.61 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 20.8066 | 11.61 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.70 | 20.70 | 13.4441 | 11.61 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 13.4441 | 11.61 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 13.4441 | 11.61 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 13.4441 | 11.61 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.35 | 10.35 | 13.4441 | 11.61 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 17.1846 | 11.61 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 17.1846 | 11.61 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-JUL-13:39 | 08-JAN-17:00 | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 299239.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 36937.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 34106.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 12077.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 8970.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 100151.97 | 299239.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 299239.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 36937.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 34106.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 12077.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 8970.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 586.35 | 0.00 | 0.00 | 0.00 |
Cooling | 166.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1744.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 290.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 599.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 208.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3415.88 | 586.35 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 280.51 | 0.00 | 0.00 | 0.00 |
Cooling | 79.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 834.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 139.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 286.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 99.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1634.15 | 280.51 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 280.51 | 0.00 | 0.00 | 0.00 |
Cooling | 79.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 834.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 139.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 286.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 99.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1634.15 | 280.51 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.01 |
SMSTORE1 DIRECT AIR | 1.09 |
SMSTORE2 DIRECT AIR | 1.11 |
SMSTORE3 DIRECT AIR | 1.10 |
SMSTORE4 DIRECT AIR | 1.10 |
LGSTORE2 DIRECT AIR | 1.91 |
SMSTORE5 DIRECT AIR | 0.970657 |
SMSTORE6 DIRECT AIR | 0.959938 |
SMSTORE7 DIRECT AIR | 0.941655 |
SMSTORE8 DIRECT AIR | 1.02 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.01 | 2.01 | 2.01 | 2.01 | 2.01 | 2.01 | 1.00 | 1.00 | 2.01 |
PSZ-AC_2:2 | 1.09 | 1.09 | 1.09 | 1.09 | 1.12 | 1.12 | 1.00 | 0.974286 | 1.12 |
PSZ-AC_3:3 | 1.11 | 1.11 | 1.11 | 1.11 | 1.12 | 1.12 | 1.00 | 0.992633 | 1.12 |
PSZ-AC_4:4 | 1.10 | 1.10 | 1.10 | 1.10 | 1.12 | 1.12 | 1.00 | 0.982563 | 1.12 |
PSZ-AC_5:5 | 1.10 | 1.10 | 1.10 | 1.10 | 1.11 | 1.11 | 1.00 | 0.990285 | 1.11 |
PSZ-AC_6:6 | 1.91 | 1.91 | 1.91 | 1.91 | 1.91 | 1.91 | 1.00 | 1.000000 | 1.91 |
PSZ-AC_7:7 | 0.970657 | 0.970657 | 0.970657 | 0.970657 | 0.985500 | 0.985500 | 1.00 | 0.984939 | 0.985500 |
PSZ-AC_8:8 | 0.959938 | 0.959938 | 0.959938 | 0.959938 | 0.976201 | 0.976201 | 1.00 | 0.983341 | 0.976201 |
PSZ-AC_9:9 | 0.941655 | 0.941655 | 0.941655 | 0.941655 | 0.964988 | 0.964988 | 1.00 | 0.975820 | 0.964988 |
PSZ-AC_10:10 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.00 | 1.00 | 1.02 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.01 | 0.411453 |
PSZ-AC_2:2_OA_CONTROLLER | 1.12 | 0.205727 |
PSZ-AC_3:3_OA_CONTROLLER | 1.12 | 0.205727 |
PSZ-AC_4:4_OA_CONTROLLER | 1.12 | 0.205727 |
PSZ-AC_5:5_OA_CONTROLLER | 1.11 | 0.205727 |
PSZ-AC_6:6_OA_CONTROLLER | 1.91 | 0.411453 |
PSZ-AC_7:7_OA_CONTROLLER | 0.985500 | 0.205727 |
PSZ-AC_8:8_OA_CONTROLLER | 0.976201 | 0.205727 |
PSZ-AC_9:9_OA_CONTROLLER | 0.964988 | 0.205727 |
PSZ-AC_10:10_OA_CONTROLLER | 1.02 | 0.205727 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.01 | 2.01 | 2.01 | 1.33 | 33562.14 | 61453.37 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.12 | 1.12 | 1.12 | 1.12 | 18465.67 | 32334.82 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.12 | 1.12 | 1.12 | 1.12 | 18472.47 | 32752.20 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.12 | 1.12 | 1.12 | 1.12 | 18532.13 | 32598.32 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.11 | 1.11 | 1.11 | 1.11 | 18328.10 | 32527.11 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.91 | 1.91 | 1.91 | 1.26 | 32057.33 | 59420.49 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.985500 | 0.985500 | 0.985500 | 0.985500 | 16475.72 | 30012.00 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.976201 | 0.976201 | 0.976201 | 0.976201 | 16337.89 | 29797.67 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.964988 | 0.964988 | 0.964988 | 0.964988 | 16171.70 | 29432.09 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.02 | 1.02 | 1.02 | 1.02 | 17028.60 | 30917.69 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 2.01 | 1.01 | 1.34 | 33319.32 | 33562.14 | 16781.07 | 16781.07 | 0.795995 | 0.795990 | 0.795990 | 0.795990 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 1.12 | 0.557755 | 0.743673 | 18465.65 | 18465.67 | 9232.83 | 9232.83 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 1.12 | 0.557960 | 0.743947 | 18472.44 | 18472.47 | 9236.24 | 9236.24 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 1.12 | 0.559765 | 0.746353 | 18532.20 | 18532.13 | 9266.07 | 9266.07 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 1.11 | 0.553600 | 0.738133 | 18328.09 | 18328.10 | 9164.05 | 9164.05 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 1.91 | 0.955580 | 1.27 | 31636.48 | 32057.33 | 16028.67 | 16028.67 | 0.793829 | 0.793830 | 0.793830 | 0.793830 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 0.985500 | 0.492750 | 0.657000 | 16313.52 | 16475.72 | 8237.86 | 8237.86 | 0.795036 | 0.795040 | 0.795040 | 0.795040 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 0.976200 | 0.488100 | 0.650800 | 16159.58 | 16337.89 | 8168.94 | 8168.94 | 0.794643 | 0.794640 | 0.794640 | 0.794640 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 0.964990 | 0.482495 | 0.643327 | 15974.01 | 16171.70 | 8085.85 | 8085.85 | 0.794161 | 0.794160 | 0.794160 | 0.794160 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 1.02 | 0.507975 | 0.677300 | 16817.58 | 17028.60 | 8514.30 | 8514.30 | 0.794099 | 0.794100 | 0.794100 | 0.794100 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.01 | 2153.81 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.12 | 1235.05 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.12 | 1235.50 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.12 | 1239.49 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.11 | 1225.85 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.91 | 2045.03 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.985500 | 1091.11 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.976201 | 1080.81 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.964988 | 1068.39 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.02 | 1124.81 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | 61453.37 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | 32334.82 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | 32752.20 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | 32598.32 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | 32527.11 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | 59420.49 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | 30012.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | 29797.67 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | 29432.09 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | 30917.69 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.76 | 20.75 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.67 | 10.37 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.43 | 20.70 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.13 | 10.35 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 20.085 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.385 | No |
2 | SMSTORE1 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 22.959 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 27.259 | No |
3 | SMSTORE2 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 20.807 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.107 | No |
4 | SMSTORE3 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 20.807 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.107 | No |
5 | SMSTORE4 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 20.807 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.107 | No |
6 | LGSTORE2 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
7 | SMSTORE5 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
8 | SMSTORE6 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
9 | SMSTORE7 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
10 | SMSTORE8 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 4683.750 | 13.444 | 156.145 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4683.750 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 2313.749 | 6.641 | 77.135 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2313.749 |
3 | SMSTORE1_LIGHTS | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1657.501 | 9.515 | 110.515 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1657.501 |
5 | SMSTORE2_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 1282.497 | 7.363 | 85.511 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1282.497 |
7 | SMSTORE3_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 1282.497 | 7.363 | 85.511 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1282.497 |
9 | SMSTORE4_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 1282.497 | 7.363 | 85.511 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1282.497 |
11 | LGSTORE2_LIGHTS | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 4683.750 | 13.444 | 156.145 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4683.750 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL | 20 | 4 | 7 | 0.167 | 0.2903 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 30 | 2 | 7 | 0.167 | 0.1381 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 31 | 2 | 7 | 0.167 | 0.7817E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.7817E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.7817E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.7817E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.7817E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.7817E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.7817E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.7817E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1990 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.210 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.167 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.72 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.72 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.72 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.72 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.72 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.72 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.72 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.72 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.947 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8390000 | 2.8390000 | 2.8390000 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.37770232E-12 | 0.51790214E-15 | -0.12781252E-12 | 0.55998589E-16 |
23 | 6 | 0.34333646E-07 | 0.85611267E-10 | 0.78179037E-08 | -0.16618826E-12 |
24 | 5 | -0.21846269E-03 | 0.70914283E-06 | -0.11192726E-03 | 0.77079120E-08 |
25 | 4 | 0.32474569 | 0.33518246E-03 | 0.11143489 | -0.38230638E-04 |
26 | 3 | -7.9105893 | 0.10117084E-01 | -2.5301860 | 0.32170091E-01 |
27 | 2 | 42.994418 | 0.35140113E-01 | 16.046370 | -0.35699651 |
28 | 1 | -82.171251 | 0.15534856E-01 | -29.841212 | 1.1132611 |
29 | 0 | 46.824329 | 0.30626733E-03 | 16.275140 | |
30 | 7 | -0.30768122E-08 | -0.20915384E-14 | 0.14239733E-14 | -0.43231278E-16 |
31 | 6 | 0.39835568E-05 | 0.26399824E-08 | 0.31946650E-02 | -0.26799527E-04 |
32 | 5 | -0.27951707E-03 | 0.15609240E-05 | -0.22399710 | 0.19585557E-02 |
33 | 4 | 0.63843515E-02 | 0.70996553E-04 | 4.8340844 | -0.45308610E-01 |
34 | 3 | -0.55922562E-01 | 0.56414668E-03 | -38.047054 | 0.39893714 |
35 | 2 | 0.19837327 | 0.93792475E-03 | 116.53385 | -1.4186067 |
36 | 1 | -0.28619643 | 0.28546699E-03 | -143.93668 | 2.0495227 |
37 | 0 | 0.13950394 | 0.69324754E-05 | 60.838472 | |
38 | 7 | -0.54670353E-08 | -0.11613337E-13 | 0.14223840E-14 | -0.37368711E-16 |
39 | 6 | 0.25207632E-05 | 0.15026623E-08 | 0.31993138E-02 | -0.26838525E-04 |
40 | 5 | -0.16410687E-03 | 0.88486983E-06 | -0.22426121 | 0.19608870E-02 |
41 | 4 | 0.36607299E-02 | 0.40162528E-04 | 4.8384812 | -0.45350877E-01 |
42 | 3 | -0.31781560E-01 | 0.31856588E-03 | -38.071881 | 0.39921157 |
43 | 2 | 0.11233251 | 0.52874598E-03 | 116.58215 | -1.4192529 |
44 | 1 | -0.16179893 | 0.16057723E-03 | -143.96511 | 2.0499900 |
45 | 0 | 0.78801674E-01 | 0.38948424E-05 | 60.838472 | |
46 | 7 | -0.54670353E-08 | -0.11613337E-13 | 0.14223844E-14 | -0.37368717E-16 |
47 | 6 | 0.25207632E-05 | 0.15026623E-08 | 0.31993138E-02 | -0.26838525E-04 |
48 | 5 | -0.16410687E-03 | 0.88486983E-06 | -0.22426121 | 0.19608870E-02 |
49 | 4 | 0.36607299E-02 | 0.40162528E-04 | 4.8384812 | -0.45350877E-01 |
50 | 3 | -0.31781560E-01 | 0.31856588E-03 | -38.071881 | 0.39921157 |
51 | 2 | 0.11233251 | 0.52874598E-03 | 116.58215 | -1.4192529 |
52 | 1 | -0.16179893 | 0.16057723E-03 | -143.96511 | 2.0499900 |
53 | 0 | 0.78801674E-01 | 0.38948424E-05 | 60.838472 | |
54 | 7 | -0.54670353E-08 | -0.11613337E-13 | 0.14223843E-14 | -0.37368715E-16 |
55 | 6 | 0.25207632E-05 | 0.15026623E-08 | 0.31993138E-02 | -0.26838525E-04 |
56 | 5 | -0.16410687E-03 | 0.88486983E-06 | -0.22426121 | 0.19608870E-02 |
57 | 4 | 0.36607299E-02 | 0.40162528E-04 | 4.8384812 | -0.45350877E-01 |
58 | 3 | -0.31781560E-01 | 0.31856588E-03 | -38.071881 | 0.39921157 |
59 | 2 | 0.11233251 | 0.52874598E-03 | 116.58215 | -1.4192529 |
60 | 1 | -0.16179893 | 0.16057723E-03 | -143.96511 | 2.0499900 |
61 | 0 | 0.78801674E-01 | 0.38948424E-05 | 60.838472 | |
62 | 7 | -0.54670353E-08 | -0.11613337E-13 | 0.14223847E-14 | -0.37368722E-16 |
63 | 6 | 0.25207632E-05 | 0.15026623E-08 | 0.31993138E-02 | -0.26838525E-04 |
64 | 5 | -0.16410687E-03 | 0.88486983E-06 | -0.22426121 | 0.19608870E-02 |
65 | 4 | 0.36607299E-02 | 0.40162528E-04 | 4.8384812 | -0.45350877E-01 |
66 | 3 | -0.31781560E-01 | 0.31856588E-03 | -38.071881 | 0.39921157 |
67 | 2 | 0.11233251 | 0.52874598E-03 | 116.58215 | -1.4192529 |
68 | 1 | -0.16179893 | 0.16057723E-03 | -143.96511 | 2.0499900 |
69 | 0 | 0.78801674E-01 | 0.38948424E-05 | 60.838472 | |
70 | 7 | -0.54670353E-08 | -0.11613337E-13 | 0.14223844E-14 | -0.37368717E-16 |
71 | 6 | 0.25207632E-05 | 0.15026623E-08 | 0.31993138E-02 | -0.26838525E-04 |
72 | 5 | -0.16410687E-03 | 0.88486983E-06 | -0.22426121 | 0.19608870E-02 |
73 | 4 | 0.36607299E-02 | 0.40162528E-04 | 4.8384812 | -0.45350877E-01 |
74 | 3 | -0.31781560E-01 | 0.31856588E-03 | -38.071881 | 0.39921157 |
75 | 2 | 0.11233251 | 0.52874598E-03 | 116.58215 | -1.4192529 |
76 | 1 | -0.16179893 | 0.16057723E-03 | -143.96511 | 2.0499900 |
77 | 0 | 0.78801674E-01 | 0.38948424E-05 | 60.838472 | |
78 | 7 | -0.54670353E-08 | -0.11613337E-13 | 0.14223845E-14 | -0.37368719E-16 |
79 | 6 | 0.25207632E-05 | 0.15026623E-08 | 0.31993138E-02 | -0.26838525E-04 |
80 | 5 | -0.16410687E-03 | 0.88486983E-06 | -0.22426121 | 0.19608870E-02 |
81 | 4 | 0.36607299E-02 | 0.40162528E-04 | 4.8384812 | -0.45350877E-01 |
82 | 3 | -0.31781560E-01 | 0.31856588E-03 | -38.071881 | 0.39921157 |
83 | 2 | 0.11233251 | 0.52874598E-03 | 116.58215 | -1.4192529 |
84 | 1 | -0.16179893 | 0.16057723E-03 | -143.96511 | 2.0499900 |
85 | 0 | 0.78801674E-01 | 0.38948424E-05 | 60.838472 | |
86 | 7 | -0.54670353E-08 | -0.11613337E-13 | 0.14223840E-14 | -0.37368711E-16 |
87 | 6 | 0.25207632E-05 | 0.15026623E-08 | 0.31993138E-02 | -0.26838525E-04 |
88 | 5 | -0.16410687E-03 | 0.88486983E-06 | -0.22426121 | 0.19608870E-02 |
89 | 4 | 0.36607299E-02 | 0.40162528E-04 | 4.8384812 | -0.45350877E-01 |
90 | 3 | -0.31781560E-01 | 0.31856588E-03 | -38.071881 | 0.39921157 |
91 | 2 | 0.11233251 | 0.52874598E-03 | 116.58215 | -1.4192529 |
92 | 1 | -0.16179893 | 0.16057723E-03 | -143.96511 | 2.0499900 |
93 | 0 | 0.78801674E-01 | 0.38948424E-05 | 60.838472 | |
94 | 7 | -0.54670353E-08 | -0.11613337E-13 | 0.14223844E-14 | -0.37368717E-16 |
95 | 6 | 0.25207632E-05 | 0.15026623E-08 | 0.31993138E-02 | -0.26838525E-04 |
96 | 5 | -0.16410687E-03 | 0.88486983E-06 | -0.22426121 | 0.19608870E-02 |
97 | 4 | 0.36607299E-02 | 0.40162528E-04 | 4.8384812 | -0.45350877E-01 |
98 | 3 | -0.31781560E-01 | 0.31856588E-03 | -38.071881 | 0.39921157 |
99 | 2 | 0.11233251 | 0.52874598E-03 | 116.58215 | -1.4192529 |
100 | 1 | -0.16179893 | 0.16057723E-03 | -143.96511 | 2.0499900 |
101 | 0 | 0.78801674E-01 | 0.38948424E-05 | 60.838472 | |
102 | 7 | -0.21207308E-08 | -0.69128065E-15 | 0.45866753E-14 | -0.60902147E-16 |
103 | 6 | 0.56000727E-05 | 0.38109606E-08 | 0.31899011E-02 | -0.26759564E-04 |
104 | 5 | -0.40083884E-03 | 0.22562489E-05 | -0.22372635 | 0.19561660E-02 |
105 | 4 | 0.92084614E-02 | 0.10268861E-03 | 4.8295754 | -0.45265267E-01 |
106 | 3 | -0.80828076E-01 | 0.81646647E-03 | -38.021585 | 0.39865561 |
107 | 2 | 0.28695633 | 0.13581156E-02 | 116.48428 | -1.4179437 |
108 | 1 | -0.41414885 | 0.41367783E-03 | -143.90750 | 2.0490431 |
109 | 0 | 0.20191061 | 0.10030641E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 29 | 1 | VerySmooth | 2.387 | 0.394 | 0.315 | 0.441 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.02786E-002 | 0.31435 | 0.47495 | 0.47495 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12239 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 30.0 | 0.159 | 4.569E-004 | 2.517E-004 | 0.317 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 30.0 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 15.0 | 4.561E-002 | 2.619E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 30.0 | 9.122E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 30.0 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 15.0 | 0.113 | 6.514E-004 | 3.022E-004 | 0.453 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 19938.65574 | 23926.38689 | 1.67735 | 2.01282 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 33.40000 | 6.26594E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
2 | LGSTORE1 | Heating | 28808.05295 | 34569.66353 | 1.41980 | 1.70376 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
3 | SMSTORE1 | Cooling | 11065.49635 | 13278.59562 | 0.90569 | 1.08683 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.32000 | 6.26593E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
4 | SMSTORE1 | Heating | 14508.81051 | 17410.57261 | 0.71506 | 0.85807 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
5 | SMSTORE2 | Cooling | 11275.54089 | 13530.64907 | 0.92308 | 1.10770 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.60000 | 6.26593E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
6 | SMSTORE2 | Heating | 14681.31752 | 17617.58103 | 0.72356 | 0.86827 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
7 | SMSTORE3 | Cooling | 11199.37332 | 13439.24798 | 0.91667 | 1.10001 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.60000 | 6.26593E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
8 | SMSTORE3 | Heating | 14756.22382 | 17707.46858 | 0.72725 | 0.87270 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
9 | SMSTORE4 | Cooling | 11163.37761 | 13396.05313 | 0.91370 | 1.09644 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.60000 | 6.26593E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
10 | SMSTORE4 | Heating | 14897.52194 | 17877.02633 | 0.73421 | 0.88106 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
11 | LGSTORE2 | Cooling | 18931.53487 | 22717.84185 | 1.59263 | 1.91116 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.13333 | 6.26594E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
12 | LGSTORE2 | Heating | 28320.93996 | 33985.12795 | 1.39580 | 1.67496 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
13 | SMSTORE5 | Cooling | 9908.82878 | 11890.59453 | 0.80888 | 0.97066 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.32000 | 6.26593E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
14 | SMSTORE5 | Heating | 15231.91586 | 18278.29903 | 0.75070 | 0.90083 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
15 | SMSTORE6 | Cooling | 9802.31038 | 11762.77245 | 0.79995 | 0.95994 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.32000 | 6.26593E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
16 | SMSTORE6 | Heating | 15214.03603 | 18256.84323 | 0.74981 | 0.89978 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
17 | SMSTORE7 | Cooling | 9620.70690 | 11544.84828 | 0.78471 | 0.94165 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.32000 | 6.26593E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
18 | SMSTORE7 | Heating | 15385.01157 | 18462.01388 | 0.75824 | 0.90989 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
19 | SMSTORE8 | Cooling | 9583.11311 | 11499.73574 | 0.80618 | 0.96742 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.00000 | 6.26594E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
20 | SMSTORE8 | Heating | 17178.46335 | 20614.15602 | 0.84662 | 1.01595 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 27762.15 | 2.01282 | 2.01282 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 55273.88 | 1.70376 | 1.70376 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 15158.04 | 1.11551 | 1.11551 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 27760.80 | 0.85807 | 0.85807 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 15158.61 | 1.11592 | 1.11592 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 27964.79 | 0.86827 | 0.86827 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 15199.42 | 1.11953 | 1.11953 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 28053.37 | 0.87270 | 0.87270 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 15055.54 | 1.10720 | 1.10720 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 28220.46 | 0.88106 | 0.88106 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 26554.51 | 1.91116 | 1.91116 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 54697.92 | 1.67496 | 1.67496 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 13628.72 | 0.98550 | 0.98550 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 28615.90 | 0.90083 | 0.90083 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 13520.23 | 0.97620 | 0.97620 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 28594.75 | 0.89978 | 0.89978 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 13389.35 | 0.96499 | 0.96499 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 28796.94 | 0.90989 | 0.90989 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 13381.55 | 0.96742 | 0.96742 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 30917.69 | 1.01595 | 1.01595 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.01282 |
2 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.08683 |
3 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.10770 |
4 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.10001 |
5 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.09644 |
6 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.91116 |
7 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.97066 |
8 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.95994 |
9 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.94165 |
10 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.01595 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.01282 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.01282 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.01282 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.01282 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.01282 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.01282 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.08683 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.08683 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.08683 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.08683 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.11551 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.11551 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 0.97429 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.10770 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.10770 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.10770 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.10770 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.11592 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.11592 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 0.99263 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.10001 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.10001 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.10001 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.10001 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.11953 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.11953 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 0.98256 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.09644 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.09644 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.09644 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.09644 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.10720 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.10720 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 0.99029 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.91116 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.91116 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.91116 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.91116 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.91116 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.91116 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.97066 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.97066 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.97066 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.97066 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.98550 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.98550 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.98494 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.95994 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.95994 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.95994 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.95994 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97620 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.97620 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.98334 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.94165 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.94165 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.94165 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.94165 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.96499 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.96499 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.97582 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.01595 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.01595 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.01595 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.01595 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.01595 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.01595 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.01282 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.11551 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.11592 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.11953 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.10720 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.91116 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.98550 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.97620 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.96499 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.01595 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.01282 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.01282 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.01282 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.01282 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.32846 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.01282 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.00641 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.34188 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 33319.31799 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 33562.14000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 16781.07000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 16781.07000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79600 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79599 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79599 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79599 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33562.14000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 61453.37218 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
122 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.01282 |
123 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2153.81089 |
124 | Coil:Heating:Fuel | PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 61453.37218 |
125 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.11551 |
126 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.11551 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.11551 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.11551 |
130 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.11551 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.11551 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55776 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.74367 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18465.65138 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 18465.67000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9232.83500 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 9232.83500 |
138 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79865 |
139 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
140 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
141 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18465.67000 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32334.82214 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
146 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.11551 |
147 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1235.04764 |
148 | Coil:Heating:Fuel | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 32334.82214 |
149 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.11592 |
150 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
151 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.11592 |
152 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.11592 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.11592 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.11592 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.11592 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55796 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.74395 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18472.43834 |
159 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 18472.47000 |
160 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9236.23500 |
161 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 9236.23500 |
162 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79865 |
163 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
164 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18472.47000 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32752.19712 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
170 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.11592 |
171 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1235.50279 |
172 | Coil:Heating:Fuel | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 32752.19712 |
173 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.11953 |
174 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.11953 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.11953 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.11953 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.11953 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.11953 |
180 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55977 |
181 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.74635 |
182 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18532.19666 |
183 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 18532.13000 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9266.06500 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 9266.06500 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18532.13000 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32598.31966 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
194 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.11953 |
195 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1239.49294 |
196 | Coil:Heating:Fuel | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 32598.31966 |
197 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.10720 |
198 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.10720 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.10720 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.10720 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.10720 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.10720 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55360 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.73813 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18328.09138 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 18328.10000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9164.05000 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 9164.05000 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
214 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18328.10000 |
215 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32527.10907 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
218 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.10720 |
219 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1225.84655 |
220 | Coil:Heating:Fuel | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 32527.10907 |
221 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.91116 |
222 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.91116 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.91116 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.91116 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.26136 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.91116 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.95558 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.27411 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 31636.48403 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 32057.33000 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 16028.66500 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 16028.66500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79383 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79383 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79383 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79383 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32057.33000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 59420.48923 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
241 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
242 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.91116 |
243 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2045.02844 |
244 | Coil:Heating:Fuel | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 59420.48923 |
245 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.98550 |
246 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.98550 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.98550 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.98550 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.98550 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.98550 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49275 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65700 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 16313.52425 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 16475.72000 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8237.86000 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8237.86000 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79504 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79504 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79504 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79504 |
262 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16475.72000 |
263 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30012.00094 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
266 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.98550 |
267 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1091.10526 |
268 | Coil:Heating:Fuel | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 30012.00094 |
269 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97620 |
270 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
271 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97620 |
272 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97620 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97620 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97620 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.97620 |
276 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48810 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65080 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 16159.57623 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 16337.89000 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8168.94500 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8168.94500 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79464 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79464 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79464 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79464 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16337.89000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29797.66925 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.97620 |
291 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1080.80927 |
292 | Coil:Heating:Fuel | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 29797.66925 |
293 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.96499 |
294 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.96499 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.96499 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.96499 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96499 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.96499 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48250 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.64333 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 15974.01093 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 16171.70000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8085.85000 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8085.85000 |
306 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79416 |
307 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79416 |
308 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79416 |
309 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79416 |
310 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16171.70000 |
311 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29432.08939 |
312 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
313 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
314 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.96499 |
315 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1068.39456 |
316 | Coil:Heating:Fuel | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 29432.08939 |
317 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.01595 |
318 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
319 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.01595 |
320 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.01595 |
321 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.01595 |
322 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.01595 |
323 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.01595 |
324 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50798 |
325 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.67730 |
326 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 16817.57987 |
327 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 17028.60000 |
328 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8514.30000 |
329 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8514.30000 |
330 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79410 |
331 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79410 |
332 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79410 |
333 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79410 |
334 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17028.60000 |
335 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30917.68904 |
336 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
337 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
338 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.01595 |
339 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1124.81260 |
340 | Coil:Heating:Fuel | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 30917.68904 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 31984.5 | 11.12 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 17591.4 | 33.35 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 17597.9 | 45.17 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 17654.7 | 56.85 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 17460.4 | 69.32 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 30559.3 | 48.41 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 15703.3 | 112.19 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 15572.7 | 125.02 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 15415.3 | 138.20 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 16232.3 | 143.11 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.290 | 0.278 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.290 | 0.278 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.290 | 0.278 | 58.20 | 78.94 | 58.20 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.138 | 0.134 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.290 | 0.278 | 29.10 | 39.47 | 29.10 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.290 | 0.278 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 7.817E-002 | 7.671E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.290 | 0.278 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.290 | 0.278 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 7.817E-002 | 7.671E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.290 | 0.278 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.290 | 0.278 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 7.817E-002 | 7.671E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.290 | 0.278 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.290 | 0.278 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 7.817E-002 | 7.671E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.290 | 0.278 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.290 | 0.278 | 58.24 | 78.94 | 58.24 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 7.817E-002 | 7.671E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.290 | 0.278 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.290 | 0.278 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 7.817E-002 | 7.671E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.290 | 0.278 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.290 | 0.278 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 7.817E-002 | 7.671E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.290 | 0.278 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.290 | 0.278 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 7.817E-002 | 7.671E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.290 | 0.278 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.290 | 0.278 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.290 | 0.278 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.199 | 0.190 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 13 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 2.9041306831E-002 | 0.1650446791 | Pass | Pass | 0.1977678427 | 0.5612038687 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 6.8807444083E-002 | 0.1224329590 | Pass | Pass | 6.9266362090E-002 | 0.2556652629 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 3.3505552225E-002 | 0.1276055093 | Pass | Pass | 0.2015037840 | 0.7838598662 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.2571216710E-002 | 0.1703948010 | Pass | Pass | 0.2031500022 | 0.9133534619 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.5739750585E-002 | 0.2035702873 | Pass | Pass | 0.2152915003 | 0.8659103555 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 4.2157592930E-002 | 0.2217751247 | Pass | Pass | 0.3492039814 | 1.3766013089 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.2750964131E-002 | 0.2253385689 | Pass | Pass | 0.1790756525 | 0.5024028069 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.2262194061E-002 | 0.2280095999 | Pass | Pass | 0.1667742446 | 0.7364608609 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 4.7674819020E-002 | 0.2478695276 | Pass | Pass | 0.2145281377 | 1.2161509622 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 6.7838387138E-002 | 0.3526457446 | Pass | Pass | 8.0036917972E-002 | 0.4207202790 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL | 0.30 | 0.278 | 0.290 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.278 | 0.290 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.278 | 0.290 | 78.94 | 58.20 | 180.00 | 90.00 | S |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.278 | 0.290 | 39.47 | 29.10 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.278 | 0.290 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.278 | 0.290 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.278 | 0.290 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.278 | 0.290 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.278 | 0.290 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.278 | 0.290 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.278 | 0.290 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.278 | 0.290 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.278 | 0.290 | 78.94 | 58.24 | 180.00 | 90.00 | S |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.278 | 0.290 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.278 | 0.290 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.278 | 0.290 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.278 | 0.290 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.278 | 0.290 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.278 | 0.290 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.278 | 0.290 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.278 | 0.290 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL | 0.30 | 0.278 | 0.290 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.138 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.078 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.078 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.078 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.078 | 174.19 | 174.19 | 270.00 | 180.00 | ||
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.078 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.078 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.078 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.078 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.199 | 174.19 | 174.19 | 270.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.387 | 0.394 | 0.441 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.387 | 0.394 | 0.441 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.387 | 0.394 | 0.441 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.387 | 0.394 | 0.441 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.387 | 0.394 | 0.441 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.387 | 0.394 | 0.441 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.387 | 0.394 | 0.441 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.387 | 0.394 | 0.441 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.387 | 0.394 | 0.441 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.387 | 0.394 | 0.441 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.387 | 0.394 | 0.441 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.387 | 0.394 | 0.441 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
Total or Average | 124.29 | 2.387 | 0.394 | 0.441 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 124.29 | 2.387 | 0.394 | 0.441 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.992 | 2.839 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.992 | 2.839 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE8_WALL_3 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | 13.4441 | 348.39 | 4683.75 | LightsWired | TYPE1_LIGHT_SCH | 98.22 | 168.00 | 98.21 | 0.0000 | Y | 86.34 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | 6.6413 | 348.39 | 2313.75 | LightsWired | TYPE1_LIGHT_SCH | 98.22 | 168.00 | 98.21 | 0.0000 | Y | 42.65 |
SMSTORE1_LIGHTS | SMSTORE1 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE1_LIGHT_SCH | 98.22 | 168.00 | 98.21 | 0.0000 | Y | 43.17 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | 9.5153 | 174.19 | 1657.50 | LightsWired | TYPE1_LIGHT_SCH | 98.22 | 168.00 | 98.21 | 0.0000 | Y | 30.56 |
SMSTORE2_LIGHTS | SMSTORE2 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 34.27 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | 7.3625 | 174.19 | 1282.50 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.77 |
SMSTORE3_LIGHTS | SMSTORE3 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 34.27 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | 7.3625 | 174.19 | 1282.50 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.77 |
SMSTORE4_LIGHTS | SMSTORE4 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 34.27 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | 7.3625 | 174.19 | 1282.50 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.77 |
LGSTORE2_LIGHTS | LGSTORE2 | 13.4441 | 348.39 | 4683.75 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 63.00 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | 0.0000 | 348.39 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 31.50 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 31.50 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 31.50 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 31.50 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 8.5923 | 4180.64 | 35921.24 | 550.85 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 418.40 | AstronomicalClock | - | 42.11 | 42.11 | 3.31 | |
EXTERIOR_LIGHTS_B | 6630.02 | AstronomicalClock | - | 83.57 | 71.13 | 88.52 | |
Exterior Lighting Total | 7048.42 | 91.83 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 33562.14 | 26715.13 | 6847.01 | 0.80 | 3.80 | |||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 18465.67 | 14747.79 | 3717.88 | 0.80 | 4.12 | |||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 18472.47 | 14753.22 | 3719.25 | 0.80 | 4.12 | |||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 18532.13 | 14800.87 | 3731.26 | 0.80 | 4.12 | |||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 18328.10 | 14637.92 | 3690.18 | 0.80 | 4.12 | |||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 32057.33 | 25448.07 | 6609.26 | 0.79 | 3.80 | |||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 16475.72 | 13098.86 | 3376.86 | 0.80 | 4.12 | |||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 16337.89 | 12982.74 | 3355.15 | 0.79 | 4.12 | |||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 16171.70 | 12842.92 | 3328.78 | 0.79 | 4.12 | |||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 17028.60 | 13522.41 | 3506.19 | 0.79 | 4.12 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 31984.5 | 11.12 | ||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 17591.4 | 33.35 | ||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 17597.9 | 45.17 | ||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 17654.7 | 56.85 | ||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 17460.4 | 69.32 | ||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 30559.3 | 48.41 | ||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 15703.3 | 112.19 | ||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 15572.7 | 125.02 | ||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 15415.3 | 138.20 | ||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 16232.3 | 143.11 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 61453.37 | 0.80 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 32334.82 | 0.80 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 32752.20 | 0.80 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 32598.32 | 0.80 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 32527.11 | 0.80 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 59420.49 | 0.80 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 30012.00 | 0.80 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 29797.67 | 0.80 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 29432.09 | 0.80 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 30917.69 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.01 | 2153.81 | 1070.05 | 1.00 | 1.31 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.12 | 1235.05 | 1107.16 | 1.00 | 1.38 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.12 | 1235.50 | 1107.16 | 1.00 | 1.38 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.12 | 1239.49 | 1107.16 | 1.00 | 1.38 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.11 | 1225.85 | 1107.16 | 1.00 | 1.38 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.91 | 2045.03 | 1070.05 | 1.00 | 1.32 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.99 | 1091.11 | 1107.16 | 1.00 | 1.41 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.98 | 1080.81 | 1107.16 | 1.00 | 1.41 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.96 | 1068.39 | 1107.16 | 1.00 | 1.41 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.02 | 1124.81 | 1107.16 | 1.00 | 1.40 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 19938.66 | 23926.39 | 68.68 | 1.677 | 2.013 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 23.89 | 23.89 | 0.00720 | 33.40 | 0.00627 | 0.411 | 0.00 |
SMSTORE1 | 11065.50 | 13278.60 | 76.23 | 0.906 | 1.087 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00737 | 27.32 | 0.00627 | 0.206 | 0.00 |
SMSTORE2 | 11275.54 | 13530.65 | 77.68 | 0.923 | 1.108 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00750 | 24.60 | 0.00627 | 0.206 | 0.00 |
SMSTORE3 | 11199.37 | 13439.25 | 77.15 | 0.917 | 1.100 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00749 | 24.60 | 0.00627 | 0.206 | 0.00 |
SMSTORE4 | 11163.38 | 13396.05 | 76.90 | 0.914 | 1.096 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00751 | 24.60 | 0.00627 | 0.206 | 0.00 |
LGSTORE2 | 18931.53 | 22717.84 | 65.21 | 1.593 | 1.911 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00721 | 33.13 | 0.00627 | 0.411 | 0.00 |
SMSTORE5 | 9908.83 | 11890.59 | 68.26 | 0.809 | 0.971 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00754 | 27.32 | 0.00627 | 0.206 | 0.00 |
SMSTORE6 | 9802.31 | 11762.77 | 67.53 | 0.800 | 0.960 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00756 | 27.32 | 0.00627 | 0.206 | 0.00 |
SMSTORE7 | 9620.71 | 11544.85 | 66.28 | 0.785 | 0.942 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00760 | 27.32 | 0.00627 | 0.206 | 0.00 |
SMSTORE8 | 9583.11 | 11499.74 | 66.02 | 0.806 | 0.967 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 23.89 | 23.89 | 0.00719 | 33.00 | 0.00627 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 28808.05 | 34569.66 | 99.23 | 1.420 | 1.704 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00673 | -27.60 | 0.00034 | 0.411 | 0.00 |
SMSTORE1 | 14508.81 | 17410.57 | 99.95 | 0.715 | 0.858 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00663 | -27.60 | 0.00034 | 0.206 | 0.00 |
SMSTORE2 | 14681.32 | 17617.58 | 101.14 | 0.724 | 0.868 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00664 | -27.60 | 0.00034 | 0.206 | 0.00 |
SMSTORE3 | 14756.22 | 17707.47 | 101.65 | 0.727 | 0.873 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00665 | -27.60 | 0.00034 | 0.206 | 0.00 |
SMSTORE4 | 14897.52 | 17877.03 | 102.63 | 0.734 | 0.881 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00666 | -27.60 | 0.00034 | 0.206 | 0.00 |
LGSTORE2 | 28320.94 | 33985.13 | 97.55 | 1.396 | 1.675 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00673 | -27.60 | 0.00034 | 0.411 | 0.00 |
SMSTORE5 | 15231.92 | 18278.30 | 104.93 | 0.751 | 0.901 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00668 | -27.60 | 0.00034 | 0.206 | 0.00 |
SMSTORE6 | 15214.04 | 18256.84 | 104.81 | 0.750 | 0.900 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00668 | -27.60 | 0.00034 | 0.206 | 0.00 |
SMSTORE7 | 15385.01 | 18462.01 | 105.99 | 0.758 | 0.910 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00669 | -27.60 | 0.00034 | 0.206 | 0.00 |
SMSTORE8 | 17178.46 | 20614.16 | 118.34 | 0.847 | 1.016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00677 | -27.60 | 0.00034 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.01 | 2.01 | 1.70 | 1.70 | 2.0128 | 2.0128 | 2.0128 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.12 | 1.12 | 0.86 | 0.86 | 1.1155 | 1.0868 | 1.1155 | 0.9743 | 1.0000 |
PSZ-AC_3:3 | 1.12 | 1.12 | 0.87 | 0.87 | 1.1159 | 1.1077 | 1.1159 | 0.9926 | 1.0000 |
PSZ-AC_4:4 | 1.12 | 1.12 | 0.87 | 0.87 | 1.1195 | 1.1000 | 1.1195 | 0.9826 | 1.0000 |
PSZ-AC_5:5 | 1.11 | 1.11 | 0.88 | 0.88 | 1.1072 | 1.0964 | 1.1072 | 0.9903 | 1.0000 |
PSZ-AC_6:6 | 1.91 | 1.91 | 1.67 | 1.67 | 1.9112 | 1.9112 | 1.9112 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 0.99 | 0.99 | 0.90 | 0.90 | 0.9855 | 0.9707 | 0.9855 | 0.9849 | 1.0000 |
PSZ-AC_8:8 | 0.98 | 0.98 | 0.90 | 0.90 | 0.9762 | 0.9599 | 0.9762 | 0.9833 | 1.0000 |
PSZ-AC_9:9 | 0.96 | 0.96 | 0.91 | 0.91 | 0.9650 | 0.9417 | 0.9650 | 0.9758 | 1.0000 |
PSZ-AC_10:10 | 0.97 | 0.97 | 1.02 | 1.02 | 1.0159 | 1.0159 | 1.0159 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 16781.070 | 0.000 | 2.012820 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 16781.07 | 16781.07 | 2.012820 | 25.83 | 14.37 | 0.00700867 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 20.4416 | 23.89 | 0.00719951 | 34.1917 | 19938.66 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 61453.372 | 61453.372 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 61453.37 | 61453.37 | 2.012818 | 9.34 | 5.90 | 0.00518881 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 20.4417 | 21.10 | 0.00673200 | 37.8969 | 28808.05 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 9232.835 | 0.000 | 1.115510 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 9232.83 | 9232.83 | 1.115510 | 25.64 | 14.30 | 0.00700572 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 18.4424 | 23.89 | 0.00736581 | 34.9745 | 11047.24 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 32334.822 | 32334.822 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32334.82 | 32334.82 | 1.115511 | 9.43 | 5.86 | 0.00512364 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 18.4424 | 21.10 | 0.00663165 | 37.3389 | 14508.81 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 9236.235 | 0.000 | 1.115920 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 9236.24 | 9236.24 | 1.115920 | 25.64 | 14.30 | 0.00700573 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 18.4356 | 23.89 | 0.00750042 | 35.6074 | 11047.72 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 32752.197 | 32752.197 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32752.20 | 32752.20 | 1.115922 | 9.57 | 5.96 | 0.00515022 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 18.4356 | 21.10 | 0.00664326 | 37.4035 | 14681.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 9266.065 | 0.000 | 1.119530 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 9266.07 | 9266.07 | 1.119530 | 25.64 | 14.30 | 0.00700586 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 18.3762 | 23.89 | 0.00748770 | 35.5475 | 11082.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 32598.320 | 32598.320 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32598.32 | 32598.32 | 1.119526 | 9.62 | 6.00 | 0.00516158 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 18.3762 | 21.10 | 0.00664821 | 37.4311 | 14756.22 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 9164.050 | 0.000 | 1.107200 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 9164.05 | 9164.05 | 1.107200 | 25.66 | 14.31 | 0.00700538 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 18.5808 | 23.89 | 0.00751335 | 35.6681 | 10960.71 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 32527.109 | 32527.109 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32527.11 | 32527.11 | 1.107200 | 9.73 | 6.07 | 0.00518281 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 18.5808 | 21.10 | 0.00665750 | 37.4829 | 14897.52 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 16028.665 | 0.000 | 1.911160 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 16028.67 | 16028.67 | 1.911160 | 25.94 | 14.41 | 0.00700789 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 21.5290 | 23.89 | 0.00721210 | 34.2509 | 18919.27 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 59420.489 | 59420.489 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 59420.49 | 59420.49 | 1.911157 | 9.14 | 5.77 | 0.00516154 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 21.5290 | 21.10 | 0.00673102 | 37.8912 | 28320.94 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 8237.860 | 0.000 | 0.985500 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 8237.86 | 8237.86 | 0.985500 | 25.88 | 14.38 | 0.00699929 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 20.8754 | 23.89 | 0.00754452 | 35.8149 | 9756.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 30012.001 | 30012.001 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30012.00 | 30012.00 | 0.985500 | 9.98 | 6.24 | 0.00523172 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 20.8754 | 21.10 | 0.00667893 | 37.6023 | 15231.92 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 8168.945 | 0.000 | 0.976200 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 8168.94 | 8168.94 | 0.976200 | 25.89 | 14.39 | 0.00699871 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 21.0742 | 23.89 | 0.00756378 | 35.9054 | 9664.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 29797.669 | 29797.669 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29797.67 | 29797.67 | 0.976201 | 9.97 | 6.24 | 0.00522915 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 21.0742 | 21.10 | 0.00667780 | 37.5960 | 15214.04 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 8085.850 | 0.000 | 0.964990 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 8085.85 | 8085.85 | 0.964990 | 25.92 | 14.39 | 0.00699798 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 21.3190 | 23.89 | 0.00759962 | 36.0738 | 9554.27 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 29432.089 | 29432.089 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29432.09 | 29432.09 | 0.964988 | 10.09 | 6.32 | 0.00525353 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 21.3191 | 21.10 | 0.00668850 | 37.6556 | 15385.01 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 8514.300 | 0.000 | 1.015950 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 8514.30 | 8514.30 | 1.015950 | 25.92 | 14.39 | 0.00699397 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 20.2497 | 23.89 | 0.00719204 | 34.1565 | 9547.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 30917.689 | 30917.689 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30917.69 | 30917.69 | 1.015945 | 11.24 | 7.09 | 0.00546647 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 20.2498 | 21.10 | 0.00676768 | 38.0971 | 17178.46 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16781.070 | 0.000 | 2.012820 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8688 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 16781.07 | 16781.07 | 1.0000 | 2.11978101 | 2.012820 | 25.83 | 14.37 | 0.00700867 | 43823.3 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16781.07 | 33.40 | 0.00626594 | 16.30 | 0.41145340 | 20.4416 | 23.89 | 0.00719951 | 23.89 | 0.00719951 | 34.1917 | 19938.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 61453.372 | 61453.372 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.012818 | 2.11977938 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 61453.37 | 61453.37 | 1.0000 | 2.11977938 | 2.012818 | 9.34 | 5.90 | 0.00518881 | 22455.9 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 61453.37 | -27.60 | 0.00034190 | -27.60 | 0.41145340 | 20.4417 | 21.11 | 0.00673200 | 21.10 | 0.00673200 | 37.8969 | 28808.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 9232.835 | 0.000 | 1.115510 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8633 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 9232.83 | 9232.83 | 1.0000 | 1.17478807 | 1.115510 | 25.64 | 14.30 | 0.00700572 | 43622.7 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9232.83 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 18.4424 | 23.89 | 0.00717306 | 23.89 | 0.00736581 | 34.9745 | 11047.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32334.822 | 32334.822 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.115511 | 1.17478901 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32334.82 | 32334.82 | 1.0000 | 1.17478901 | 1.115511 | 9.43 | 5.86 | 0.00512364 | 22377.7 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32334.82 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 18.4424 | 21.11 | 0.00663165 | 21.10 | 0.00663165 | 37.3389 | 14508.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 9236.235 | 0.000 | 1.115920 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8633 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 9236.24 | 9236.24 | 1.0000 | 1.17521985 | 1.115920 | 25.64 | 14.30 | 0.00700573 | 43622.7 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9236.24 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 18.4356 | 23.89 | 0.00717306 | 23.89 | 0.00750042 | 35.6074 | 11047.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32752.197 | 32752.197 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.115922 | 1.17522196 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32752.20 | 32752.20 | 1.0000 | 1.17522196 | 1.115922 | 9.57 | 5.96 | 0.00515022 | 22583.8 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32752.20 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 18.4356 | 21.11 | 0.00664326 | 21.10 | 0.00664326 | 37.4035 | 14681.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 9266.065 | 0.000 | 1.119530 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8635 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 9266.07 | 9266.07 | 1.0000 | 1.17902169 | 1.119530 | 25.64 | 14.30 | 0.00700586 | 43617.5 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9266.07 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 18.3762 | 23.89 | 0.00717258 | 23.89 | 0.00748770 | 35.5475 | 11082.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32598.320 | 32598.320 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.119526 | 1.17901743 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32598.32 | 32598.32 | 1.0000 | 1.17901743 | 1.119526 | 9.62 | 6.00 | 0.00516158 | 22671.8 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32598.32 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 18.3762 | 21.11 | 0.00664821 | 21.10 | 0.00664821 | 37.4311 | 14756.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 9164.050 | 0.000 | 1.107200 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8627 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 9164.05 | 9164.05 | 1.0000 | 1.16603648 | 1.107200 | 25.66 | 14.31 | 0.00700538 | 43636.0 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9164.05 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 18.5808 | 23.89 | 0.00717426 | 23.89 | 0.00751335 | 35.6681 | 10960.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32527.109 | 32527.109 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.107200 | 1.16603685 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32527.11 | 32527.11 | 1.0000 | 1.16603685 | 1.107200 | 9.73 | 6.07 | 0.00518281 | 22835.8 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32527.11 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 18.5808 | 21.11 | 0.00665750 | 21.10 | 0.00665750 | 37.4829 | 14897.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16028.665 | 0.000 | 1.911160 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8673 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 16028.67 | 16028.67 | 1.0000 | 2.01271881 | 1.911160 | 25.94 | 14.41 | 0.00700789 | 43927.9 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16028.67 | 33.40 | 0.00626594 | 16.30 | 0.41145340 | 21.5290 | 23.89 | 0.00721161 | 23.89 | 0.00721210 | 34.2509 | 18919.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 59420.489 | 59420.489 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.911157 | 2.01271576 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 59420.49 | 59420.49 | 1.0000 | 2.01271576 | 1.911157 | 9.14 | 5.77 | 0.00516154 | 22182.2 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 59420.49 | -27.60 | 0.00034190 | -27.60 | 0.41145340 | 21.5290 | 21.11 | 0.00673102 | 21.10 | 0.00673102 | 37.8912 | 28320.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8237.860 | 0.000 | 0.985500 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8513 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 8237.86 | 8237.86 | 1.0000 | 1.03786935 | 0.985500 | 25.88 | 14.38 | 0.00699929 | 43842.6 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8237.86 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 20.8754 | 23.89 | 0.00719292 | 23.89 | 0.00754452 | 35.8149 | 9756.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30012.001 | 30012.001 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.985500 | 1.03786966 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30012.00 | 30012.00 | 1.0000 | 1.03786966 | 0.985500 | 9.98 | 6.24 | 0.00523172 | 23212.3 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30012.00 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 20.8754 | 21.11 | 0.00667893 | 21.10 | 0.00667893 | 37.6023 | 15231.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8168.945 | 0.000 | 0.976200 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8503 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 8168.94 | 8168.94 | 1.0000 | 1.02807515 | 0.976200 | 25.89 | 14.39 | 0.00699871 | 43860.3 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8168.94 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 21.0742 | 23.89 | 0.00719451 | 23.89 | 0.00756378 | 35.9054 | 9664.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29797.669 | 29797.669 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.976201 | 1.02807602 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29797.67 | 29797.67 | 1.0000 | 1.02807602 | 0.976201 | 9.97 | 6.24 | 0.00522915 | 23192.6 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29797.67 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 21.0742 | 21.11 | 0.00667780 | 21.10 | 0.00667780 | 37.5960 | 15214.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8085.850 | 0.000 | 0.964990 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8489 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 8085.85 | 8085.85 | 1.0000 | 1.01626945 | 0.964990 | 25.92 | 14.39 | 0.00699798 | 43882.1 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8085.85 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 21.3190 | 23.89 | 0.00719646 | 23.89 | 0.00759962 | 36.0738 | 9554.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29432.089 | 29432.089 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.964988 | 1.01626703 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29432.09 | 29432.09 | 1.0000 | 1.01626703 | 0.964988 | 10.09 | 6.32 | 0.00525353 | 23379.6 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29432.09 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 21.3191 | 21.11 | 0.00668850 | 21.10 | 0.00668850 | 37.6556 | 15385.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8514.300 | 0.000 | 1.015950 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8414 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 8514.30 | 8514.30 | 1.0000 | 1.06993746 | 1.015950 | 25.92 | 14.39 | 0.00699397 | 43873.3 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8514.30 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 20.2497 | 23.89 | 0.00719154 | 23.89 | 0.00719204 | 34.1565 | 9547.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30917.689 | 30917.689 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.015945 | 1.06993240 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30917.69 | 30917.69 | 1.0000 | 1.06993240 | 1.015945 | 11.24 | 7.09 | 0.00546647 | 25082.8 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30917.69 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 20.2498 | 21.11 | 0.00676768 | 21.10 | 0.00676768 | 38.0971 | 17178.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.01 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.12 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.12 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.12 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.11 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.91 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.99 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.98 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.96 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.02 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 1852.67 | 3916.67 | 1054.33 |
SMSTORE1 | 1354.33 | 3633.50 | 550.50 |
SMSTORE2 | 1328.00 | 2739.17 | 605.17 |
SMSTORE3 | 1396.50 | 2776.33 | 675.67 |
SMSTORE4 | 1452.50 | 2860.17 | 771.50 |
LGSTORE2 | 1492.17 | 2850.17 | 1030.00 |
SMSTORE5 | 1447.00 | 2871.83 | 1069.83 |
SMSTORE6 | 1472.33 | 2897.00 | 1111.83 |
SMSTORE7 | 1569.17 | 2957.17 | 1242.67 |
SMSTORE8 | 1938.17 | 3086.83 | 1658.17 |
Facility | 3037.17 | 4485.83 | 2104.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 7.00 | 0.00 | 1.67 | 0.00 |
SMSTORE1 | 1.17 | 0.00 | 0.17 | 0.00 |
SMSTORE2 | 0.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 1.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 1.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 3.83 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 3.83 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 4.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 5.33 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 31.33 | 0.00 | 0.00 | 0.00 |
Facility | 37.50 | 0.00 | 1.67 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.982 | 0.241 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 1.067 | 0.253 | 0.000 | 0.000 |
SMSTORE2 | 3.77 | 15.00 | 902.60 | 1.228 | 0.329 | 0.000 | 0.000 |
SMSTORE3 | 3.77 | 15.00 | 902.60 | 1.222 | 0.329 | 0.000 | 0.000 |
SMSTORE4 | 3.77 | 15.00 | 902.60 | 1.194 | 0.329 | 0.000 | 0.000 |
LGSTORE2 | 13.20 | 30.00 | 1805.20 | 0.966 | 0.316 | 0.000 | 0.000 |
SMSTORE5 | 6.60 | 15.00 | 902.60 | 1.109 | 0.351 | 0.000 | 0.000 |
SMSTORE6 | 6.60 | 15.00 | 902.60 | 1.100 | 0.351 | 0.000 | 0.000 |
SMSTORE7 | 6.60 | 15.00 | 902.60 | 1.080 | 0.351 | 0.000 | 0.000 |
SMSTORE8 | 6.60 | 15.00 | 902.60 | 1.064 | 0.377 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 3.77 | 15.00 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 3.77 | 15.00 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 3.77 | 15.00 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 13.20 | 30.00 | 1805.20 | 0.806 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 6.60 | 15.00 | 902.60 | 0.806 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 6.60 | 15.00 | 902.60 | 0.806 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 6.60 | 15.00 | 902.60 | 0.806 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 6.60 | 15.00 | 902.60 | 0.806 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1078.59 | 3448.90 | 12-FEB-08:00 | 100151.97 | 17-JUL-13:40 |
Electricity:Building | 679.00 | 2237.90 | 01-JAN-00:10 | 42165.88 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 155.25 | 423.51 | 01-JAN-00:10 | 7978.91 | 01-JAN-10:10 |
InteriorLights:Electricity | 550.85 | 1795.07 | 01-JAN-08:10 | 34106.38 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 129.00 | 349.25 | 01-JAN-08:10 | 6635.66 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 550.85 | 1795.07 | 01-JAN-08:10 | 34106.38 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 86.85 | 236.79 | 01-JAN-00:10 | 4464.19 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 73.73 | 199.61 | 01-JAN-08:10 | 3792.57 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 63.46 | 218.04 | 01-JAN-00:10 | 4114.78 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 53.04 | 181.22 | 01-JAN-00:10 | 3443.15 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 63.46 | 218.04 | 01-JAN-00:10 | 4114.78 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 53.04 | 181.22 | 01-JAN-00:10 | 3443.15 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 63.46 | 218.04 | 01-JAN-00:10 | 4114.78 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 53.04 | 181.22 | 01-JAN-00:10 | 3443.15 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 82.18 | 307.83 | 01-JAN-00:10 | 5792.81 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 63.00 | 234.19 | 01-JAN-00:10 | 4449.56 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 41.09 | 153.91 | 01-JAN-00:10 | 2896.41 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 31.50 | 117.09 | 01-JAN-00:10 | 2224.78 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 41.09 | 153.91 | 01-JAN-00:10 | 2896.41 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 31.50 | 117.09 | 01-JAN-00:10 | 2224.78 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 41.09 | 153.91 | 01-JAN-00:10 | 2896.41 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 31.50 | 117.09 | 01-JAN-00:10 | 2224.78 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 41.09 | 153.91 | 01-JAN-00:10 | 2896.41 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 31.50 | 117.09 | 01-JAN-00:10 | 2224.78 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
Electricity:Plant | 65.74 | 1211.00 | 06-JAN-00:20 | 11881.78 | 07-JAN-14:30 |
WaterSystems:Electricity | 65.74 | 1211.00 | 06-JAN-00:20 | 11881.78 | 07-JAN-14:30 |
Water Heater:WaterSystems:Electricity | 65.74 | 1211.00 | 06-JAN-00:20 | 11881.78 | 07-JAN-14:30 |
ElectricityPurchased:Facility | 1078.59 | 3448.90 | 12-FEB-08:00 | 100151.97 | 17-JUL-13:40 |
ElectricityPurchased:Plant | 1078.59 | 3448.90 | 12-FEB-08:00 | 100151.97 | 17-JUL-13:40 |
Cogeneration:ElectricityPurchased | 1078.59 | 3448.90 | 12-FEB-08:00 | 100151.97 | 17-JUL-13:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1078.59 | 3448.90 | 12-FEB-08:00 | 100151.97 | 17-JUL-13:40 |
ElectricityNet:Plant | 1078.59 | 3448.90 | 12-FEB-08:00 | 100151.97 | 17-JUL-13:40 |
Cogeneration:ElectricityNet | 1078.59 | 3448.90 | 12-FEB-08:00 | 100151.97 | 17-JUL-13:40 |
Electricity:HVAC | 242.01 | 0.00 | 01-JAN-00:10 | 51021.13 | 17-JUL-16:10 |
Fans:Electricity | 189.31 | 0.00 | 01-JAN-00:10 | 12585.67 | 08-JAN-18:00 |
General:Fans:Electricity | 189.31 | 0.00 | 01-JAN-00:10 | 12585.67 | 08-JAN-18:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 52.70 | 0.00 | 01-JAN-00:10 | 38755.30 | 17-JUL-16:10 |
ExteriorLights:Electricity | 91.83 | 0.00 | 01-JAN-08:20 | 7048.42 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 91.83 | 0.00 | 01-JAN-08:20 | 7048.42 | 01-JAN-06:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 540.92 | 0.00 | 01-JAN-00:10 | 299239.86 | 08-JAN-18:00 |
Gas:HVAC | 540.92 | 0.00 | 01-JAN-00:10 | 299239.86 | 08-JAN-18:00 |
Heating:Gas | 540.92 | 0.00 | 01-JAN-00:10 | 299239.86 | 08-JAN-18:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1147.88 | 0.00 | 01-JAN-00:10 | 366582.65 | 09-JAN-08:10 |
EnergyTransfer:Building | 491.01 | 0.00 | 01-JAN-00:10 | 171135.27 | 09-JAN-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 102.72 | 0.00 | 01-JAN-00:10 | 32652.13 | 27-JAN-08:10 |
Heating:EnergyTransfer | 150.79 | 0.00 | 01-JAN-00:10 | 171135.27 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 20.02 | 0.00 | 01-JAN-00:10 | 32652.13 | 27-JAN-08:10 |
Cooling:EnergyTransfer | 340.22 | 0.00 | 01-JAN-00:10 | 92496.84 | 17-JUL-16:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 82.70 | 0.00 | 01-JAN-00:10 | 19258.71 | 28-JAN-00:10 |
EnergyTransfer:Zone:SMSTORE1 | 53.05 | 0.00 | 01-JAN-00:10 | 13512.91 | 11-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 6.83 | 0.00 | 01-JAN-00:10 | 13512.91 | 11-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 46.22 | 0.00 | 01-JAN-00:10 | 11148.89 | 27-JUL-20:20 |
EnergyTransfer:Zone:SMSTORE2 | 41.56 | 0.00 | 01-JAN-00:10 | 14838.37 | 09-JAN-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 8.61 | 0.00 | 01-JAN-00:10 | 14838.37 | 09-JAN-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 32.95 | 0.00 | 01-JAN-00:10 | 8326.71 | 17-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE3 | 41.30 | 0.00 | 01-JAN-00:10 | 16022.80 | 09-JAN-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 9.44 | 0.00 | 01-JAN-00:10 | 16022.80 | 09-JAN-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 31.85 | 0.00 | 01-JAN-00:10 | 8374.22 | 17-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE4 | 39.95 | 0.00 | 01-JAN-00:10 | 15930.29 | 29-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 10.77 | 0.00 | 01-JAN-00:10 | 15930.29 | 29-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 29.19 | 0.00 | 01-JAN-00:10 | 8252.00 | 17-JUL-16:10 |
EnergyTransfer:Zone:LGSTORE2 | 67.72 | 0.00 | 01-JAN-00:10 | 32795.17 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 24.02 | 0.00 | 01-JAN-00:10 | 32795.17 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 43.70 | 0.00 | 01-JAN-00:10 | 14299.53 | 17-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE5 | 34.55 | 0.00 | 01-JAN-00:10 | 17336.73 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 14.05 | 0.00 | 01-JAN-00:10 | 17336.73 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 20.49 | 0.00 | 01-JAN-00:10 | 7482.90 | 17-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE6 | 34.41 | 0.00 | 01-JAN-00:10 | 17379.78 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 14.51 | 0.00 | 01-JAN-00:10 | 17379.78 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 19.90 | 0.00 | 01-JAN-00:10 | 7420.37 | 17-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE7 | 34.57 | 0.00 | 01-JAN-00:10 | 17340.95 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 16.38 | 0.00 | 01-JAN-00:10 | 17340.95 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 18.19 | 0.00 | 01-JAN-00:10 | 7324.39 | 17-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE8 | 41.19 | 0.00 | 01-JAN-00:10 | 19704.38 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 26.15 | 0.00 | 01-JAN-00:10 | 19704.38 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 15.03 | 0.00 | 01-JAN-00:10 | 7422.72 | 17-JUL-16:10 |
EnergyTransfer:HVAC | 656.87 | 0.00 | 01-JAN-00:10 | 239391.89 | 08-JAN-18:00 |
HeatingCoils:EnergyTransfer | 432.73 | 0.00 | 01-JAN-00:10 | 239391.89 | 08-JAN-18:00 |
CoolingCoils:EnergyTransfer | 224.13 | 0.00 | 01-JAN-00:10 | 139408.92 | 17-JUL-16:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 20.022 | -82.695 | 0.000 | 0.000 | 13.546 | 128.996 | 26.249 | 22.561 | 0.000 | 1.726 | 0.004 | 0.000 | -14.680 | 0.000 | -43.879 | -71.847 |
SMSTORE1 | 0.000 | 0.000 | 6.831 | -46.215 | 0.000 | 0.000 | 6.608 | 73.727 | 13.125 | 11.156 | 0.000 | 0.931 | 0.001 | 0.000 | -7.700 | 0.000 | -21.265 | -37.198 |
SMSTORE2 | 0.000 | 0.000 | 8.611 | -32.949 | 0.000 | 0.000 | 4.027 | 53.039 | 10.421 | 11.142 | 0.000 | 0.912 | 0.001 | 0.000 | -7.600 | 0.000 | -21.912 | -25.691 |
SMSTORE3 | 0.000 | 0.000 | 9.442 | -31.853 | 0.000 | 0.000 | 4.035 | 53.039 | 10.421 | 11.160 | 0.000 | 0.912 | 0.001 | 0.000 | -7.526 | 0.000 | -21.816 | -27.814 |
SMSTORE4 | 0.000 | 0.000 | 10.766 | -29.186 | 0.000 | 0.000 | 4.049 | 53.039 | 10.421 | 11.193 | 0.000 | 0.912 | 0.000 | 0.000 | -7.433 | 0.000 | -21.674 | -32.087 |
LGSTORE2 | 0.000 | 0.000 | 24.019 | -43.704 | 0.000 | 0.000 | 14.058 | 63.003 | 19.173 | 22.581 | 0.000 | 1.648 | 0.001 | 0.000 | -14.335 | 0.000 | -39.516 | -46.928 |
SMSTORE5 | 0.000 | 0.000 | 14.054 | -20.491 | 0.000 | 0.000 | 7.000 | 31.501 | 9.586 | 11.269 | 0.000 | 0.915 | 0.002 | 0.000 | -7.187 | 0.000 | -21.571 | -25.077 |
SMSTORE6 | 0.000 | 0.000 | 14.509 | -19.905 | 0.000 | 0.000 | 7.005 | 31.501 | 9.586 | 11.279 | 0.000 | 0.915 | 0.001 | 0.000 | -7.160 | 0.000 | -21.537 | -26.193 |
SMSTORE7 | 0.000 | 0.000 | 16.378 | -18.190 | 0.000 | 0.000 | 7.020 | 31.501 | 9.586 | 11.311 | 0.000 | 0.915 | 0.000 | 0.000 | -7.067 | 0.000 | -21.415 | -30.039 |
SMSTORE8 | 0.000 | 0.000 | 26.155 | -15.033 | 0.000 | 0.000 | 7.050 | 31.501 | 9.586 | 11.403 | 0.000 | 0.967 | 0.001 | 0.000 | -6.721 | 0.000 | -27.786 | -37.122 |
Total Facility | 0.000 | 0.000 | 150.788 | -340.220 | 0.000 | 0.000 | 74.397 | 550.849 | 128.154 | 135.055 | 0.000 | 10.752 | 0.013 | 0.000 | -87.409 | 0.000 | -262.370 | -359.996 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 04-SEP-07:02 | 0.00 | 0.00 | 0.00 | -34700.79 | 0.00 | 0.00 | 94.03 | 349.25 | 74.62 | 97.49 | 0.00 | 0.00 | 34272.49 | 0.00 | -0.00 | 0.00 | -187.09 | 0.00 |
SMSTORE1 | 18-OCT-21:37 | 0.00 | 0.00 | 0.00 | -22784.66 | 0.00 | 0.00 | 315.18 | 3792.57 | 671.63 | 0.00 | 0.00 | 0.00 | 18281.51 | 0.00 | -242.79 | 0.00 | -33.43 | 0.00 |
SMSTORE2 | 12-AUG-06:02 | 0.00 | 0.00 | 0.00 | -23448.37 | 0.00 | 0.00 | 0.00 | 181.22 | 36.82 | 0.00 | 0.00 | 0.00 | 23424.37 | 0.00 | -173.69 | 0.00 | -20.34 | 0.00 |
SMSTORE3 | 12-AUG-06:02 | 0.00 | 0.00 | 0.00 | -23556.14 | 0.00 | 0.00 | 0.00 | 181.22 | 36.82 | 0.00 | 0.00 | 0.00 | 23533.20 | 0.00 | -174.66 | 0.00 | -20.43 | 0.00 |
SMSTORE4 | 12-AUG-06:02 | 0.00 | 0.00 | 0.00 | -23194.78 | 0.00 | 0.00 | 0.00 | 181.22 | 36.82 | 0.00 | 0.00 | 0.00 | 23168.83 | 0.00 | -171.94 | 0.00 | -20.14 | 0.00 |
LGSTORE2 | 27-JUL-07:02 | 0.00 | 0.00 | 0.00 | -34065.40 | 0.00 | 0.00 | 0.00 | 234.19 | 73.64 | 0.00 | 0.00 | 0.00 | 34142.36 | 0.00 | -2.03 | 0.00 | -382.76 | 0.00 |
SMSTORE5 | 05-SEP-07:02 | 0.00 | 0.00 | 0.00 | -17165.42 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 0.00 | 0.00 | 0.00 | 17171.76 | 0.00 | -30.12 | 0.00 | -130.12 | 0.00 |
SMSTORE6 | 05-SEP-07:02 | 0.00 | 0.00 | 0.00 | -16981.90 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 0.00 | 0.00 | 0.00 | 16986.50 | 0.00 | -29.16 | 0.00 | -129.35 | 0.00 |
SMSTORE7 | 05-SEP-07:02 | 0.00 | 0.00 | 0.00 | -16697.41 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 0.00 | 0.00 | 0.00 | 16697.29 | 0.00 | -26.96 | 0.00 | -126.82 | 0.00 |
SMSTORE8 | 05-SEP-07:02 | 0.00 | 0.00 | 0.00 | -17120.82 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 0.00 | 0.00 | 0.00 | 17128.32 | 0.00 | -19.70 | 0.00 | -141.71 | 0.00 |
Total Facility | 05-SEP-07:02 | 0.00 | 0.00 | 0.00 | -164100.90 | 0.00 | 0.00 | 297.58 | 6687.98 | 1452.23 | 0.00 | 0.00 | 0.00 | 157376.25 | 0.00 | -257.19 | 0.00 | -1455.95 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 11-JAN-08:61 | 0.00 | 0.00 | 61593.51 | 0.00 | 0.00 | 0.00 | 151.84 | 349.25 | 74.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1376.05 | 0.00 | -1995.39 | -58797.78 |
SMSTORE1 | 08-JAN-08:61 | 0.00 | 0.00 | 32372.48 | 0.00 | 0.00 | 0.00 | 72.09 | 199.61 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -858.64 | 0.00 | -1021.20 | -30801.65 |
SMSTORE2 | 05-FEB-08:61 | 0.00 | 0.00 | 32781.35 | 0.00 | 0.00 | 0.00 | 0.00 | 181.22 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -407.57 | 0.00 | -917.64 | -31674.67 |
SMSTORE3 | 05-FEB-08:61 | 0.00 | 0.00 | 32633.88 | 0.00 | 0.00 | 0.00 | 0.00 | 181.22 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -400.62 | 0.00 | -909.88 | -31541.91 |
SMSTORE4 | 05-FEB-08:61 | 0.00 | 0.00 | 32565.67 | 0.00 | 0.00 | 0.00 | 0.00 | 181.22 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -394.15 | 0.00 | -902.26 | -31487.80 |
LGSTORE2 | 08-JAN-09:12 | 0.00 | 0.00 | 59760.21 | 0.00 | 0.00 | 0.00 | 0.00 | 234.19 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1124.49 | 0.00 | -2017.66 | -56925.89 |
SMSTORE5 | 08-JAN-09:12 | 0.00 | 0.00 | 30294.66 | 0.00 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -563.11 | 0.00 | -1117.95 | -28767.51 |
SMSTORE6 | 08-JAN-09:12 | 0.00 | 0.00 | 30089.79 | 0.00 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -563.70 | 0.00 | -1121.87 | -28558.13 |
SMSTORE7 | 08-JAN-09:12 | 0.00 | 0.00 | 29761.79 | 0.00 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -561.37 | 0.00 | -1119.93 | -28234.40 |
SMSTORE8 | 08-JAN-09:12 | 0.00 | 0.00 | 31340.70 | 0.00 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -547.86 | 0.00 | -1180.43 | -29766.32 |
Total Facility | 09-JAN-08:61 | 0.00 | 0.00 | 297424.46 | 0.00 | 0.00 | 0.00 | 410.21 | 6687.98 | 1452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -10318.90 | 0.00 | -12231.33 | -283424.65 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0128 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.0128 | 0.2044 | 1.0000 | 0.4115 | 0.2044 | ||
PSZ-AC_2:2 | 1.0868 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1155 | 0.1844 | 1.0000 | 0.2057 | 0.1844 | ||
PSZ-AC_3:3 | 1.1077 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1159 | 0.1844 | 1.0000 | 0.2057 | 0.1844 | ||
PSZ-AC_4:4 | 1.1000 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1195 | 0.1838 | 1.0000 | 0.2057 | 0.1838 | ||
PSZ-AC_5:5 | 1.0964 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1072 | 0.1858 | 1.0000 | 0.2057 | 0.1858 | ||
PSZ-AC_6:6 | 1.9112 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.9112 | 0.2153 | 1.0000 | 0.4115 | 0.2153 | ||
PSZ-AC_7:7 | 0.9707 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9855 | 0.2088 | 1.0000 | 0.2057 | 0.2088 | ||
PSZ-AC_8:8 | 0.9599 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9762 | 0.2107 | 1.0000 | 0.2057 | 0.2107 | ||
PSZ-AC_9:9 | 0.9417 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9650 | 0.2132 | 1.0000 | 0.2057 | 0.2132 | ||
PSZ-AC_10:10 | 1.0159 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0159 | 0.2127 | 1.0000 | 0.2057 | 0.2025 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0128 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.0128 | 1.0000 | 1.0000 | 0.4115 | 0.2044 | ||
PSZ-AC_2:2 | 1.0868 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0868 | 1.0000 | 1.0000 | 0.2057 | 0.1893 | ||
PSZ-AC_3:3 | 1.1077 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1077 | 1.0000 | 1.0000 | 0.2057 | 0.1857 | ||
PSZ-AC_4:4 | 1.1000 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1000 | 1.0000 | 1.0000 | 0.2057 | 0.1870 | ||
PSZ-AC_5:5 | 1.0964 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0964 | 1.0000 | 1.0000 | 0.2057 | 0.1876 | ||
PSZ-AC_6:6 | 1.9112 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.9112 | 1.0000 | 1.0000 | 0.4115 | 0.2153 | ||
PSZ-AC_7:7 | 0.9707 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9707 | 1.0000 | 1.0000 | 0.2057 | 0.2119 | ||
PSZ-AC_8:8 | 0.9599 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9599 | 1.0000 | 1.0000 | 0.2057 | 0.2143 | ||
PSZ-AC_9:9 | 0.9417 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9417 | 1.0000 | 1.0000 | 0.2057 | 0.2185 | ||
PSZ-AC_10:10 | 1.0159 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0159 | 1.0000 | 1.0000 | 0.2057 | 0.2025 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 2.0128 | 2.0128 | 2.0128 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.0868 | 1.0868 | 1.0868 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.1077 | 1.1077 | 1.1077 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.1000 | 1.1000 | 1.1000 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.0964 | 1.0964 | 1.0964 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 1.9112 | 1.9112 | 1.9112 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 0.9707 | 0.9707 | 0.9707 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 0.9599 | 0.9599 | 0.9599 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 0.9417 | 0.9417 | 0.9417 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.0159 | 1.0159 | 1.0159 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0128 | 2.0128 | 2.0128 | 2.0128 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0868 | 1.1155 | 1.0868 | 1.0868 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1077 | 1.1159 | 1.1077 | 1.1077 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1000 | 1.1195 | 1.1000 | 1.1000 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0964 | 1.1072 | 1.0964 | 1.0964 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.9112 | 1.9112 | 1.9112 | 1.9112 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9707 | 0.9855 | 0.9707 | 0.9707 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9599 | 0.9762 | 0.9599 | 0.9599 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9417 | 0.9650 | 0.9417 | 0.9417 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0159 | 1.0159 | 1.0159 | 1.0159 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 2.0128 | 2.0128 | 2.0128 | 0.4115 | 0.2415 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.0868 | 1.0868 | 1.0868 | 0.2057 | 0.2398 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.1077 | 1.1077 | 1.1077 | 0.2057 | 0.2369 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.1000 | 1.1000 | 1.1000 | 0.2057 | 0.2357 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.0964 | 1.0964 | 1.0964 | 0.2057 | 0.2335 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 1.9112 | 1.9112 | 1.9112 | 0.4115 | 0.2456 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 0.9707 | 0.9707 | 0.9707 | 0.2057 | 0.2284 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 0.9599 | 0.9599 | 0.9599 | 0.2057 | 0.2286 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 0.9417 | 0.9417 | 0.9417 | 0.2057 | 0.2261 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.0159 | 1.0159 | 1.0159 | 0.2057 | 0.2025 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0128 | 2.0128 | 2.0128 | 2.0128 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0868 | 1.0868 | 1.0868 | 1.0868 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1077 | 1.1077 | 1.1077 | 1.1077 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1000 | 1.1000 | 1.1000 | 1.1000 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0964 | 1.0964 | 1.0964 | 1.0964 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.9112 | 1.9112 | 1.9112 | 1.9112 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9707 | 0.9707 | 0.9707 | 0.9707 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9599 | 0.9599 | 0.9599 | 0.9599 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9417 | 0.9417 | 0.9417 | 0.9417 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0159 | 1.0159 | 1.0159 | 1.0159 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 1.67 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 1.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 540.92 | 299239.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 52.70 | 38755.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 550.85 | 34106.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 91.83 | 7048.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 189.31 | 12585.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 65.74 | 11881.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 1078.59 |
Natural Gas | 0.00 | 540.92 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1619.50 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 263.52 |
Space Heating | 0.00 |
Space Cooling | 25.21 |
Fans (All) | 90.57 |
Service Water Heating | 31.45 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 515.99 |
Subtotal | 515.99 |
Natural Gas [MJ/m2] | |
Space Heating | 258.77 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 258.77 |
Subtotal | 258.77 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 34.01 |
Space Heating | 33.40 |
Space Cooling | 3.25 |
Fans (All) | 11.69 |
Service Water Heating | 4.06 |
Receptacle Equipment | 7.91 |
Miscellaneous | 5.67 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
TYPE1_LIGHT_SCH | 5122. | 8760. |
TYPE2_LIGHT_SCH | 4096. | 8760. |
TYPE3_LIGHT_SCH | 3767. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUALSPSCHED | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.165194E+12 |
February | 0.000 | 0.908550E+11 |
March | 0.000 | 0.697554E+11 |
April | 0.000 | 0.248116E+11 |
May | 0.000 | 0.156679E+11 |
June | 0.000 | 0.301501E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 1976959.617 |
September | 0.000 | 0.174792E+10 |
October | 0.000 | 0.879564E+10 |
November | 0.000 | 0.473985E+11 |
December | 0.000 | 0.116388E+12 |
Annual Sum or Average | 0.540917E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.165194E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.165194E+12 |
February | 0.000 | 0.908550E+11 |
March | 0.000 | 0.697554E+11 |
April | 0.000 | 0.248116E+11 |
May | 0.000 | 0.156679E+11 |
June | 0.000 | 0.301501E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 1976959.617 |
September | 0.000 | 0.174792E+10 |
October | 0.000 | 0.879564E+10 |
November | 0.000 | 0.473985E+11 |
December | 0.000 | 0.116388E+12 |
Annual Sum or Average | 0.540917E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.165194E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.165194E+12 |
February | 0.000 | 0.908550E+11 |
March | 0.000 | 0.697554E+11 |
April | 0.000 | 0.248116E+11 |
May | 0.000 | 0.156679E+11 |
June | 0.000 | 0.301501E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 1976959.617 |
September | 0.000 | 0.174792E+10 |
October | 0.000 | 0.879564E+10 |
November | 0.000 | 0.473985E+11 |
December | 0.000 | 0.116388E+12 |
Annual Sum or Average | 0.540917E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.165194E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.165194E+12 |
February | 0.000 | 0.908550E+11 |
March | 0.000 | 0.697554E+11 |
April | 0.000 | 0.248116E+11 |
May | 0.000 | 0.156679E+11 |
June | 0.000 | 0.301501E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 1976959.617 |
September | 0.000 | 0.174792E+10 |
October | 0.000 | 0.879564E+10 |
November | 0.000 | 0.473985E+11 |
December | 0.000 | 0.116388E+12 |
Annual Sum or Average | 0.540917E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.165194E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.165194E+12 |
February | 0.000 | 0.908550E+11 |
March | 0.000 | 0.697554E+11 |
April | 0.000 | 0.248116E+11 |
May | 0.000 | 0.156679E+11 |
June | 0.000 | 0.301501E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 1976959.617 |
September | 0.000 | 0.174792E+10 |
October | 0.000 | 0.879564E+10 |
November | 0.000 | 0.473985E+11 |
December | 0.000 | 0.116388E+12 |
Annual Sum or Average | 0.540917E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.165194E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.165194E+12 |
February | 0.000 | 0.908550E+11 |
March | 0.000 | 0.697554E+11 |
April | 0.000 | 0.248116E+11 |
May | 0.000 | 0.156679E+11 |
June | 0.000 | 0.301501E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 1976959.617 |
September | 0.000 | 0.174792E+10 |
October | 0.000 | 0.879564E+10 |
November | 0.000 | 0.473985E+11 |
December | 0.000 | 0.116388E+12 |
Annual Sum or Average | 0.540917E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.165194E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.165194E+12 |
February | 0.000 | 0.908550E+11 |
March | 0.000 | 0.697554E+11 |
April | 0.000 | 0.248116E+11 |
May | 0.000 | 0.156679E+11 |
June | 0.000 | 0.301501E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 1976959.617 |
September | 0.000 | 0.174792E+10 |
October | 0.000 | 0.879564E+10 |
November | 0.000 | 0.473985E+11 |
December | 0.000 | 0.116388E+12 |
Annual Sum or Average | 0.540917E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.165194E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.165194E+12 |
February | 0.000 | 0.908550E+11 |
March | 0.000 | 0.697554E+11 |
April | 0.000 | 0.248116E+11 |
May | 0.000 | 0.156679E+11 |
June | 0.000 | 0.301501E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 1976959.617 |
September | 0.000 | 0.174792E+10 |
October | 0.000 | 0.879564E+10 |
November | 0.000 | 0.473985E+11 |
December | 0.000 | 0.116388E+12 |
Annual Sum or Average | 0.540917E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.165194E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.165194E+12 |
February | 0.000 | 0.908550E+11 |
March | 0.000 | 0.697554E+11 |
April | 0.000 | 0.248116E+11 |
May | 0.000 | 0.156679E+11 |
June | 0.000 | 0.301501E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 1976959.617 |
September | 0.000 | 0.174792E+10 |
October | 0.000 | 0.879564E+10 |
November | 0.000 | 0.473985E+11 |
December | 0.000 | 0.116388E+12 |
Annual Sum or Average | 0.540917E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.165194E+12 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136406E+10 | 20429.05 | 28-JAN-00:01 | -29.2 | -29.5 | 0.567908E+09 | 680.12 | 13-JAN-13:39 | 6.50 | 2.60 |
February | 0.249284E+10 | 16945.42 | 04-FEB-00:01 | -21.0 | -21.3 | 0.522509E+09 | 856.47 | 26-FEB-17:10 | 14.85 | 5.61 |
March | 0.337131E+10 | 15297.06 | 04-MAR-00:01 | -17.2 | -17.7 | 0.565895E+09 | 697.28 | 26-MAR-17:30 | 9.15 | 1.37 |
April | 0.473490E+10 | 9879.28 | 28-APR-23:03 | -4.6 | -6.1 | 0.603146E+09 | 898.99 | 16-APR-17:19 | 19.80 | 8.87 |
May | 0.661891E+10 | 10138.70 | 20-MAY-16:10 | 29.82 | 15.08 | 0.668629E+09 | 899.01 | 13-MAY-12:09 | 23.40 | 10.96 |
June | 0.104414E+11 | 22219.47 | 22-JUN-07:03 | 19.37 | 14.44 | 0.714242E+09 | 899.03 | 25-JUN-17:00 | 23.30 | 14.11 |
July | 0.141846E+11 | 31304.33 | 27-JUL-07:02 | 13.98 | 10.40 | 0.753393E+09 | 899.02 | 16-JUL-16:00 | 33.30 | 17.40 |
August | 0.135787E+11 | 34058.35 | 08-AUG-07:02 | 19.60 | 12.39 | 0.739498E+09 | 899.07 | 06-AUG-16:10 | 35.50 | 16.21 |
September | 0.109932E+11 | 34700.65 | 04-SEP-07:02 | 20.02 | 12.32 | 0.702315E+09 | 899.08 | 10-SEP-12:00 | 18.30 | 13.27 |
October | 0.815785E+10 | 10206.86 | 18-OCT-14:00 | 25.00 | 11.37 | 0.677525E+09 | 898.99 | 29-OCT-17:19 | 10.20 | 4.47 |
November | 0.462827E+10 | 9102.17 | 02-NOV-08:05 | -2.8 | -4.0 | 0.579118E+09 | 890.54 | 04-NOV-12:00 | 16.70 | 8.09 |
December | 0.212914E+10 | 17999.72 | 29-DEC-00:01 | -23.6 | -23.9 | 0.571065E+09 | 680.12 | 09-DEC-13:09 | 3.95 | 0.92 |
Annual Sum or Average | 0.826951E+11 | 0.766524E+10 | ||||||||
Minimum of Months | 0.136406E+10 | 9102.17 | -29.2 | -29.5 | 0.522509E+09 | 680.12 | 3.95 | 0.92 | ||
Maximum of Months | 0.141846E+11 | 34700.65 | 29.82 | 15.08 | 0.753393E+09 | 899.08 | 35.50 | 17.40 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.661577E+09 | 7344.01 | 05-JAN-18:02 | -20.8 | -21.3 | 0.293651E+09 | 422.58 | 01-JAN-18:00 | 2.80 | -0.1 |
February | 0.112161E+10 | 3776.85 | 21-FEB-21:00 | -1.7 | -2.7 | 0.279227E+09 | 449.50 | 26-FEB-17:49 | 11.85 | 4.36 |
March | 0.164856E+10 | 3701.88 | 01-MAR-09:03 | -2.3 | -3.4 | 0.306981E+09 | 447.76 | 26-MAR-17:00 | 8.90 | 1.04 |
April | 0.238644E+10 | 19766.74 | 25-APR-20:02 | 12.12 | 5.44 | 0.331190E+09 | 449.50 | 08-APR-12:09 | 12.80 | 6.16 |
May | 0.385045E+10 | 20739.05 | 31-MAY-21:38 | 16.80 | 8.64 | 0.351371E+09 | 449.51 | 13-MAY-12:09 | 23.40 | 10.96 |
June | 0.642371E+10 | 21443.56 | 24-JUN-21:15 | 16.70 | 8.47 | 0.357463E+09 | 449.52 | 18-JUN-17:00 | 25.00 | 14.44 |
July | 0.835996E+10 | 21140.69 | 27-JUL-07:02 | 13.98 | 10.40 | 0.374941E+09 | 449.53 | 09-JUL-17:49 | 27.88 | 13.09 |
August | 0.802427E+10 | 20992.15 | 14-AUG-20:07 | 17.43 | 9.80 | 0.369018E+09 | 449.51 | 20-AUG-12:09 | 18.98 | 12.62 |
September | 0.628965E+10 | 20810.02 | 23-SEP-19:08 | 15.50 | 9.35 | 0.357481E+09 | 449.53 | 10-SEP-12:50 | 18.77 | 13.26 |
October | 0.426779E+10 | 22784.72 | 18-OCT-21:37 | 15.20 | 7.17 | 0.359509E+09 | 449.50 | 29-OCT-17:19 | 10.20 | 4.47 |
November | 0.216764E+10 | 19590.06 | 04-NOV-22:31 | 12.87 | 6.04 | 0.317626E+09 | 449.50 | 05-NOV-17:19 | 12.73 | 5.65 |
December | 0.101352E+10 | 3994.86 | 03-DEC-09:01 | -3.4 | -5.7 | 0.299182E+09 | 414.49 | 10-DEC-18:00 | 0.00 | -3.2 |
Annual Sum or Average | 0.462152E+11 | 0.399764E+10 | ||||||||
Minimum of Months | 0.661577E+09 | 3701.88 | -20.8 | -21.3 | 0.279227E+09 | 414.49 | 0.00 | -3.2 | ||
Maximum of Months | 0.835996E+10 | 22784.72 | 17.43 | 10.40 | 0.374941E+09 | 449.53 | 27.88 | 14.44 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.367243E+09 | 3705.38 | 02-JAN-08:61 | -2.0 | -4.1 | 0.169359E+09 | 358.56 | 14-JAN-13:20 | 10.20 | 4.86 |
February | 0.755509E+09 | 6052.64 | 02-FEB-19:52 | -14.4 | -14.9 | 0.160253E+09 | 436.72 | 25-FEB-13:00 | 15.00 | 5.03 |
March | 0.133116E+10 | 5430.77 | 01-MAR-08:61 | -9.3 | -10.0 | 0.179954E+09 | 379.23 | 18-MAR-12:00 | 11.70 | 3.92 |
April | 0.178955E+10 | 4014.12 | 28-APR-07:01 | -3.2 | -4.6 | 0.190907E+09 | 449.49 | 08-APR-12:09 | 12.80 | 6.16 |
May | 0.259205E+10 | 9710.70 | 20-MAY-06:02 | 14.13 | 10.25 | 0.208148E+09 | 449.50 | 13-MAY-12:09 | 23.40 | 10.96 |
June | 0.449939E+10 | 20135.28 | 30-JUN-06:01 | 12.67 | 9.41 | 0.220840E+09 | 449.50 | 03-JUN-12:00 | 23.90 | 14.38 |
July | 0.595325E+10 | 22189.83 | 28-JUL-06:01 | 12.48 | 9.43 | 0.224138E+09 | 449.50 | 01-JUL-12:00 | 26.70 | 16.71 |
August | 0.583832E+10 | 23448.04 | 12-AUG-06:02 | 14.87 | 7.98 | 0.229700E+09 | 449.49 | 12-AUG-12:00 | 30.00 | 14.95 |
September | 0.444772E+10 | 21555.13 | 26-SEP-06:01 | 9.03 | 7.14 | 0.213556E+09 | 449.50 | 23-SEP-12:09 | 21.28 | 11.86 |
October | 0.306123E+10 | 13571.77 | 19-OCT-06:01 | 12.02 | 5.44 | 0.209117E+09 | 449.49 | 28-OCT-12:09 | 18.12 | 9.55 |
November | 0.162717E+10 | 5017.21 | 11-NOV-09:01 | -7.9 | -8.8 | 0.180742E+09 | 449.49 | 04-NOV-12:09 | 16.20 | 7.85 |
December | 0.686878E+09 | 3911.45 | 21-DEC-08:61 | -5.7 | -7.0 | 0.169711E+09 | 355.26 | 02-DEC-13:00 | 9.40 | 4.25 |
Annual Sum or Average | 0.329495E+11 | 0.235643E+10 | ||||||||
Minimum of Months | 0.367243E+09 | 3705.38 | -14.4 | -14.9 | 0.160253E+09 | 355.26 | 9.40 | 3.92 | ||
Maximum of Months | 0.595325E+10 | 23448.04 | 14.87 | 10.25 | 0.229700E+09 | 449.50 | 30.00 | 16.71 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.288626E+09 | 5933.01 | 06-JAN-18:32 | -13.9 | -14.9 | 0.169269E+09 | 353.23 | 14-JAN-13:20 | 10.20 | 4.86 |
February | 0.654887E+09 | 5127.22 | 01-FEB-20:23 | -10.3 | -12.0 | 0.159538E+09 | 430.88 | 25-FEB-13:00 | 15.00 | 5.03 |
March | 0.119260E+10 | 5364.23 | 01-MAR-08:61 | -9.3 | -10.0 | 0.178801E+09 | 374.45 | 18-MAR-12:00 | 11.70 | 3.92 |
April | 0.162375E+10 | 3976.37 | 28-APR-07:01 | -3.2 | -4.6 | 0.189293E+09 | 449.44 | 08-APR-12:39 | 12.80 | 6.10 |
May | 0.245299E+10 | 8921.46 | 20-MAY-06:02 | 14.13 | 10.25 | 0.207171E+09 | 449.50 | 13-MAY-12:09 | 23.40 | 10.96 |
June | 0.445903E+10 | 20429.98 | 30-JUN-06:01 | 12.67 | 9.41 | 0.220779E+09 | 449.50 | 03-JUN-12:00 | 23.90 | 14.38 |
July | 0.596658E+10 | 22270.98 | 28-JUL-06:01 | 12.48 | 9.43 | 0.224136E+09 | 449.50 | 01-JUL-12:00 | 26.70 | 16.71 |
August | 0.584287E+10 | 23555.81 | 12-AUG-06:02 | 14.87 | 7.98 | 0.229681E+09 | 449.49 | 12-AUG-12:00 | 30.00 | 14.95 |
September | 0.439585E+10 | 21247.09 | 26-SEP-06:01 | 9.03 | 7.14 | 0.213188E+09 | 449.50 | 23-SEP-12:09 | 21.28 | 11.86 |
October | 0.291581E+10 | 12359.64 | 19-OCT-06:01 | 12.02 | 5.44 | 0.208117E+09 | 449.49 | 28-OCT-12:09 | 18.12 | 9.55 |
November | 0.148353E+10 | 4970.18 | 11-NOV-09:01 | -7.9 | -8.8 | 0.179090E+09 | 449.49 | 04-NOV-12:09 | 16.20 | 7.85 |
December | 0.576665E+09 | 3670.07 | 07-DEC-08:61 | -1.8 | -2.9 | 0.169448E+09 | 350.54 | 02-DEC-13:00 | 9.40 | 4.25 |
Annual Sum or Average | 0.318532E+11 | 0.234851E+10 | ||||||||
Minimum of Months | 0.288626E+09 | 3670.07 | -13.9 | -14.9 | 0.159538E+09 | 350.54 | 9.40 | 3.92 | ||
Maximum of Months | 0.596658E+10 | 23555.81 | 14.87 | 10.25 | 0.229681E+09 | 449.50 | 30.00 | 16.71 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202911E+09 | 5164.66 | 19-JAN-11:13 | -10.4 | -11.1 | 0.169181E+09 | 345.58 | 14-JAN-13:20 | 10.20 | 4.86 |
February | 0.528213E+09 | 4368.11 | 28-FEB-08:61 | -4.5 | -4.7 | 0.158550E+09 | 420.78 | 25-FEB-13:00 | 15.00 | 5.03 |
March | 0.988452E+09 | 5277.60 | 01-MAR-08:61 | -9.3 | -10.0 | 0.177343E+09 | 367.51 | 18-MAR-12:00 | 11.70 | 3.92 |
April | 0.134582E+10 | 3935.92 | 28-APR-07:01 | -3.2 | -4.6 | 0.186407E+09 | 437.12 | 08-APR-12:30 | 12.80 | 6.12 |
May | 0.215008E+10 | 5455.85 | 20-MAY-06:02 | 14.13 | 10.25 | 0.205302E+09 | 449.50 | 13-MAY-12:09 | 23.40 | 10.96 |
June | 0.418924E+10 | 17681.78 | 24-JUN-06:02 | 14.37 | 12.04 | 0.220543E+09 | 449.50 | 03-JUN-12:00 | 23.90 | 14.38 |
July | 0.572913E+10 | 21486.64 | 27-JUL-06:02 | 13.40 | 10.16 | 0.224105E+09 | 449.50 | 01-JUL-12:00 | 26.70 | 16.71 |
August | 0.559346E+10 | 23194.46 | 12-AUG-06:02 | 14.87 | 7.98 | 0.229510E+09 | 449.49 | 12-AUG-12:00 | 30.00 | 14.95 |
September | 0.413796E+10 | 20519.32 | 03-SEP-07:02 | 18.27 | 10.73 | 0.212340E+09 | 449.50 | 23-SEP-12:09 | 21.28 | 11.86 |
October | 0.262423E+10 | 8548.07 | 19-OCT-06:01 | 12.02 | 5.44 | 0.205930E+09 | 449.49 | 28-OCT-12:09 | 18.12 | 9.55 |
November | 0.125830E+10 | 4671.05 | 11-NOV-09:01 | -7.9 | -8.8 | 0.176007E+09 | 449.49 | 04-NOV-12:30 | 16.40 | 7.95 |
December | 0.437954E+09 | 4758.33 | 14-DEC-10:23 | -8.3 | -8.6 | 0.169198E+09 | 344.25 | 02-DEC-13:00 | 9.40 | 4.25 |
Annual Sum or Average | 0.291858E+11 | 0.233442E+10 | ||||||||
Minimum of Months | 0.202911E+09 | 3935.92 | -10.4 | -11.1 | 0.158550E+09 | 344.25 | 9.40 | 3.92 | ||
Maximum of Months | 0.572913E+10 | 23194.46 | 18.27 | 12.04 | 0.229510E+09 | 449.50 | 30.00 | 16.71 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 79065496.54 | 4953.29 | 01-JAN-15:05 | 6.83 | 2.30 | 0.578267E+09 | 906.82 | 21-JAN-15:20 | 2.93 | -1.5 |
February | 0.642478E+09 | 5536.35 | 27-FEB-19:20 | 6.47 | 2.39 | 0.533543E+09 | 1037.38 | 25-FEB-15:50 | 15.00 | 5.15 |
March | 0.110976E+10 | 4531.08 | 01-MAR-12:00 | 3.90 | 0.93 | 0.597362E+09 | 930.49 | 18-MAR-14:00 | 12.20 | 4.15 |
April | 0.195474E+10 | 5838.08 | 29-APR-15:13 | 4.97 | -1.1 | 0.605859E+09 | 1063.81 | 07-APR-16:00 | 21.10 | 9.06 |
May | 0.311515E+10 | 8721.41 | 20-MAY-16:00 | 30.00 | 15.19 | 0.675396E+09 | 1198.63 | 27-MAY-14:00 | 23.30 | 12.28 |
June | 0.635905E+10 | 21605.95 | 22-JUN-07:03 | 19.37 | 14.44 | 0.750106E+09 | 1198.64 | 03-JUN-14:09 | 24.18 | 14.31 |
July | 0.900952E+10 | 34064.63 | 27-JUL-07:02 | 13.98 | 10.40 | 0.766261E+09 | 1198.63 | 08-JUL-14:09 | 19.08 | 9.43 |
August | 0.881667E+10 | 32952.22 | 08-AUG-07:02 | 19.60 | 12.39 | 0.783566E+09 | 1198.72 | 05-AUG-14:20 | 34.40 | 17.09 |
September | 0.642623E+10 | 33490.66 | 05-SEP-07:02 | 18.98 | 12.61 | 0.714866E+09 | 1198.73 | 02-SEP-14:20 | 34.07 | 16.06 |
October | 0.413323E+10 | 8817.63 | 21-OCT-08:62 | -0.5 | -1.4 | 0.669808E+09 | 1198.63 | 21-OCT-14:00 | 16.10 | 8.09 |
November | 0.179073E+10 | 6099.73 | 06-NOV-11:40 | 5.27 | 1.51 | 0.569894E+09 | 1185.93 | 04-NOV-14:50 | 16.78 | 7.98 |
December | 0.267460E+09 | 11957.43 | 12-DEC-20:02 | -9.3 | -9.7 | 0.579244E+09 | 906.82 | 02-DEC-15:00 | 3.90 | 1.29 |
Annual Sum or Average | 0.437041E+11 | 0.782417E+10 | ||||||||
Minimum of Months | 79065496.54 | 4531.08 | -9.3 | -9.7 | 0.533543E+09 | 906.82 | 2.93 | -1.5 | ||
Maximum of Months | 0.900952E+10 | 34064.63 | 30.00 | 15.19 | 0.783566E+09 | 1198.73 | 34.40 | 17.09 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 32589824.99 | 3032.23 | 04-JAN-11:43 | 0.73 | -3.1 | 0.289133E+09 | 453.41 | 14-JAN-15:09 | 10.50 | 5.05 |
February | 0.244149E+09 | 3562.73 | 16-FEB-20:23 | -2.0 | -4.2 | 0.268289E+09 | 540.65 | 25-FEB-15:00 | 15.00 | 5.18 |
March | 0.461487E+09 | 2226.79 | 01-MAR-12:00 | 3.90 | 0.93 | 0.299722E+09 | 482.90 | 18-MAR-14:00 | 12.20 | 4.15 |
April | 0.696644E+09 | 2963.66 | 14-APR-09:03 | 1.12 | 0.57 | 0.308381E+09 | 548.89 | 01-APR-14:00 | 18.30 | 6.98 |
May | 0.129864E+10 | 4514.42 | 20-MAY-16:00 | 30.00 | 15.19 | 0.342282E+09 | 599.32 | 27-MAY-14:00 | 23.30 | 12.28 |
June | 0.310431E+10 | 9605.05 | 23-JUN-07:03 | 20.47 | 13.17 | 0.376804E+09 | 599.32 | 17-JUN-14:09 | 18.98 | 10.18 |
July | 0.457328E+10 | 15291.14 | 27-JUL-07:02 | 13.98 | 10.40 | 0.383369E+09 | 599.32 | 01-JUL-14:00 | 24.40 | 16.22 |
August | 0.443425E+10 | 16843.54 | 08-AUG-07:02 | 19.60 | 12.39 | 0.392468E+09 | 599.32 | 19-AUG-14:09 | 21.28 | 11.33 |
September | 0.309056E+10 | 17165.91 | 05-SEP-07:02 | 18.98 | 12.61 | 0.360454E+09 | 599.33 | 09-SEP-14:09 | 27.70 | 13.65 |
October | 0.174590E+10 | 4505.25 | 18-OCT-14:40 | 25.00 | 11.51 | 0.341677E+09 | 599.32 | 21-OCT-14:00 | 16.10 | 8.09 |
November | 0.693415E+09 | 3279.44 | 06-NOV-09:03 | -0.0 | -1.7 | 0.288690E+09 | 599.32 | 04-NOV-14:00 | 16.70 | 7.95 |
December | 0.116044E+09 | 5034.66 | 12-DEC-18:23 | -8.9 | -9.3 | 0.289633E+09 | 453.41 | 09-DEC-15:20 | 8.73 | 3.32 |
Annual Sum or Average | 0.204913E+11 | 0.394090E+10 | ||||||||
Minimum of Months | 32589824.99 | 2226.79 | -8.9 | -9.3 | 0.268289E+09 | 453.41 | 8.73 | 3.32 | ||
Maximum of Months | 0.457328E+10 | 17165.91 | 30.00 | 15.19 | 0.392468E+09 | 599.33 | 27.70 | 16.22 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 27717011.19 | 4187.21 | 03-JAN-19:33 | -4.6 | -6.8 | 0.289134E+09 | 453.41 | 14-JAN-15:09 | 10.50 | 5.05 |
February | 0.228002E+09 | 4739.62 | 23-FEB-20:03 | -7.3 | -7.8 | 0.267965E+09 | 537.11 | 25-FEB-15:00 | 15.00 | 5.18 |
March | 0.424762E+09 | 3306.89 | 31-MAR-19:43 | -0.6 | -1.8 | 0.299479E+09 | 479.75 | 18-MAR-14:00 | 12.20 | 4.15 |
April | 0.654774E+09 | 2955.35 | 14-APR-09:13 | 1.23 | 0.59 | 0.307255E+09 | 545.52 | 01-APR-14:00 | 18.30 | 6.98 |
May | 0.123619E+10 | 4421.22 | 20-MAY-16:00 | 30.00 | 15.19 | 0.341478E+09 | 599.32 | 27-MAY-14:00 | 23.30 | 12.28 |
June | 0.301451E+10 | 8918.70 | 23-JUN-07:03 | 20.47 | 13.17 | 0.376613E+09 | 599.32 | 17-JUN-14:09 | 18.98 | 10.18 |
July | 0.448576E+10 | 14681.25 | 17-JUL-07:02 | 23.17 | 14.92 | 0.383347E+09 | 599.32 | 01-JUL-14:00 | 24.40 | 16.22 |
August | 0.434943E+10 | 16661.23 | 08-AUG-07:02 | 19.60 | 12.39 | 0.392402E+09 | 599.32 | 19-AUG-14:09 | 21.28 | 11.33 |
September | 0.302520E+10 | 16982.40 | 05-SEP-07:02 | 18.98 | 12.61 | 0.360120E+09 | 599.33 | 09-SEP-14:09 | 27.70 | 13.65 |
October | 0.170017E+10 | 4427.42 | 18-OCT-14:40 | 25.00 | 11.51 | 0.340903E+09 | 599.32 | 21-OCT-14:00 | 16.10 | 8.09 |
November | 0.661436E+09 | 3403.22 | 25-NOV-10:53 | -1.1 | -2.3 | 0.288061E+09 | 599.32 | 04-NOV-14:00 | 16.70 | 7.95 |
December | 96994722.33 | 4974.38 | 12-DEC-18:03 | -8.5 | -9.0 | 0.289628E+09 | 453.41 | 09-DEC-15:39 | 9.67 | 3.60 |
Annual Sum or Average | 0.199050E+11 | 0.393638E+10 | ||||||||
Minimum of Months | 27717011.19 | 2955.35 | -8.5 | -9.0 | 0.267965E+09 | 453.41 | 9.67 | 3.60 | ||
Maximum of Months | 0.448576E+10 | 16982.40 | 30.00 | 15.19 | 0.392402E+09 | 599.33 | 27.70 | 16.22 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12358758.57 | 1924.28 | 17-JAN-11:45 | 6.10 | 1.55 | 0.289133E+09 | 453.41 | 14-JAN-15:09 | 10.50 | 5.05 |
February | 0.165616E+09 | 3206.23 | 15-FEB-19:13 | 0.00 | -1.8 | 0.267023E+09 | 525.06 | 25-FEB-15:00 | 15.00 | 5.18 |
March | 0.303163E+09 | 3326.57 | 31-MAR-18:03 | -0.6 | -1.8 | 0.298876E+09 | 469.88 | 18-MAR-14:00 | 12.20 | 4.15 |
April | 0.512214E+09 | 2880.42 | 29-APR-10:23 | 1.65 | -2.7 | 0.303780E+09 | 533.78 | 01-APR-14:00 | 18.30 | 6.98 |
May | 0.103323E+10 | 4180.46 | 20-MAY-16:00 | 30.00 | 15.19 | 0.338737E+09 | 599.32 | 27-MAY-14:00 | 23.30 | 12.28 |
June | 0.275628E+10 | 6811.63 | 23-JUN-07:03 | 20.47 | 13.17 | 0.375682E+09 | 599.32 | 17-JUN-14:09 | 18.98 | 10.18 |
July | 0.428805E+10 | 14395.76 | 17-JUL-07:02 | 23.17 | 14.92 | 0.383255E+09 | 599.32 | 01-JUL-14:00 | 24.40 | 16.22 |
August | 0.415402E+10 | 16379.24 | 08-AUG-07:02 | 19.60 | 12.39 | 0.392110E+09 | 599.32 | 19-AUG-14:09 | 21.28 | 11.33 |
September | 0.283925E+10 | 16697.91 | 05-SEP-07:02 | 18.98 | 12.61 | 0.358841E+09 | 599.33 | 09-SEP-14:09 | 27.70 | 13.65 |
October | 0.152740E+10 | 4195.95 | 18-OCT-14:40 | 25.00 | 11.51 | 0.337679E+09 | 599.32 | 21-OCT-14:00 | 16.10 | 8.09 |
November | 0.543471E+09 | 2454.60 | 06-NOV-11:30 | 5.05 | 1.38 | 0.286227E+09 | 599.32 | 04-NOV-14:00 | 16.70 | 7.95 |
December | 55176940.17 | 4060.07 | 21-DEC-19:42 | -3.9 | -6.3 | 0.289626E+09 | 453.41 | 09-DEC-15:00 | 10.60 | 3.83 |
Annual Sum or Average | 0.181902E+11 | 0.392097E+10 | ||||||||
Minimum of Months | 12358758.57 | 1924.28 | -3.9 | -6.3 | 0.267023E+09 | 453.41 | 10.50 | 3.83 | ||
Maximum of Months | 0.428805E+10 | 16697.91 | 30.00 | 15.19 | 0.392110E+09 | 599.33 | 27.70 | 16.22 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 873971.75 | 488.42 | 14-JAN-12:00 | 10.00 | 4.77 | 0.289134E+09 | 453.41 | 14-JAN-15:00 | 10.00 | 4.55 |
February | 59052014.92 | 1594.22 | 27-FEB-18:20 | 8.67 | 3.70 | 0.265480E+09 | 498.08 | 25-FEB-15:00 | 15.00 | 5.18 |
March | 62411302.90 | 2955.48 | 01-MAR-20:13 | 0.97 | -0.7 | 0.298271E+09 | 453.41 | 18-MAR-14:00 | 12.20 | 4.15 |
April | 0.179060E+09 | 1509.86 | 10-APR-10:35 | 7.97 | 2.15 | 0.297977E+09 | 531.91 | 06-APR-16:10 | 22.02 | 10.90 |
May | 0.618260E+09 | 3772.23 | 20-MAY-16:00 | 30.00 | 15.19 | 0.333285E+09 | 599.32 | 27-MAY-14:00 | 23.30 | 12.28 |
June | 0.227893E+10 | 5303.91 | 23-JUN-14:10 | 31.13 | 15.20 | 0.372481E+09 | 599.33 | 17-JUN-14:50 | 19.32 | 10.21 |
July | 0.404145E+10 | 14767.39 | 17-JUL-07:02 | 23.17 | 14.92 | 0.382872E+09 | 599.33 | 01-JUL-14:00 | 24.40 | 16.22 |
August | 0.388968E+10 | 15772.78 | 07-AUG-07:02 | 22.77 | 12.36 | 0.391169E+09 | 599.32 | 19-AUG-14:09 | 21.28 | 11.33 |
September | 0.248810E+10 | 17121.67 | 05-SEP-07:02 | 18.98 | 12.61 | 0.356037E+09 | 599.33 | 09-SEP-14:09 | 27.70 | 13.65 |
October | 0.113307E+10 | 3862.76 | 18-OCT-14:40 | 25.00 | 11.51 | 0.331519E+09 | 599.32 | 28-OCT-14:09 | 19.08 | 9.41 |
November | 0.278516E+09 | 2311.32 | 14-NOV-19:25 | 3.65 | -1.9 | 0.283349E+09 | 583.70 | 04-NOV-14:00 | 16.70 | 7.95 |
December | 3913868.93 | 2483.90 | 07-DEC-18:05 | 2.80 | 0.11 | 0.289623E+09 | 453.41 | 09-DEC-15:30 | 9.20 | 3.46 |
Annual Sum or Average | 0.150333E+11 | 0.389120E+10 | ||||||||
Minimum of Months | 873971.75 | 488.42 | 0.97 | -1.9 | 0.265480E+09 | 453.41 | 9.20 | 3.46 | ||
Maximum of Months | 0.404145E+10 | 17121.67 | 31.13 | 15.20 | 0.391169E+09 | 599.33 | 27.70 | 16.22 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.759076E+10 | 61593.47 | 11-JAN-08:61 | -17.3 |
February | 0.345566E+10 | 61548.74 | 05-FEB-08:61 | -20.1 |
March | 0.231048E+10 | 61535.00 | 04-MAR-08:61 | -19.9 |
April | 0.621529E+09 | 61477.36 | 22-APR-07:01 | 2.85 |
May | 0.371652E+09 | 61455.74 | 01-MAY-07:01 | 0.78 |
June | 38117672.33 | 1476.45 | 22-JUN-07:05 | 19.37 |
July | 26639845.15 | 1667.16 | 25-JUL-07:05 | 23.58 |
August | 27014145.45 | 1673.47 | 08-AUG-07:04 | 19.60 |
September | 55195404.81 | 28190.16 | 20-SEP-07:01 | 4.78 |
October | 0.125964E+09 | 61466.53 | 10-OCT-07:01 | -5.7 |
November | 0.117755E+10 | 61502.53 | 21-NOV-08:61 | -8.0 |
December | 0.422148E+10 | 61546.69 | 29-DEC-08:61 | -27.9 |
Annual Sum or Average | 0.200220E+11 | |||
Minimum of Months | 26639845.15 | 1476.45 | -27.9 | |
Maximum of Months | 0.759076E+10 | 61593.47 | 23.58 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.280637E+10 | 32372.51 | 08-JAN-08:61 | -27.2 |
February | 0.113730E+10 | 32369.65 | 05-FEB-08:61 | -20.1 |
March | 0.610544E+09 | 32358.44 | 04-MAR-08:61 | -19.9 |
April | 0.150244E+09 | 32323.06 | 29-APR-07:01 | -4.5 |
May | 0.103719E+09 | 26495.55 | 09-MAY-07:01 | 0.78 |
June | 22190248.59 | 1859.17 | 22-JUN-07:05 | 19.37 |
July | 24117646.12 | 1959.71 | 25-JUL-07:05 | 23.58 |
August | 23797288.48 | 1968.45 | 11-AUG-07:05 | 21.05 |
September | 41248354.79 | 1949.81 | 03-SEP-07:04 | 18.27 |
October | 72746674.85 | 1973.15 | 10-OCT-07:01 | -5.7 |
November | 0.394392E+09 | 32339.28 | 27-NOV-08:61 | -12.7 |
December | 0.144469E+10 | 32366.08 | 29-DEC-08:61 | -27.9 |
Annual Sum or Average | 0.683136E+10 | |||
Minimum of Months | 22190248.59 | 1859.17 | -27.9 | |
Maximum of Months | 0.280637E+10 | 32372.51 | 23.58 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.328940E+10 | 32781.00 | 08-JAN-08:61 | -27.2 |
February | 0.140226E+10 | 32781.36 | 05-FEB-08:61 | -20.1 |
March | 0.804917E+09 | 32751.15 | 05-MAR-08:61 | -18.1 |
April | 0.193687E+09 | 26671.04 | 29-APR-06:02 | -6.8 |
May | 0.160506E+09 | 32131.68 | 08-MAY-06:01 | -2.7 |
June | 51079469.63 | 1855.17 | 21-JUN-06:05 | 17.38 |
July | 0.100832E+09 | 2779.58 | 17-JUL-19:02 | 33.48 |
August | 81677583.78 | 3170.75 | 06-AUG-16:11 | 35.40 |
September | 68134478.50 | 2949.09 | 02-SEP-17:02 | 34.03 |
October | 74175035.82 | 8142.44 | 10-OCT-06:03 | -6.1 |
November | 0.536942E+09 | 32726.07 | 27-NOV-07:01 | -13.5 |
December | 0.184762E+10 | 32757.38 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.861123E+10 | |||
Minimum of Months | 51079469.63 | 1855.17 | -27.6 | |
Maximum of Months | 0.328940E+10 | 32781.36 | 35.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.351899E+10 | 32633.40 | 08-JAN-08:61 | -27.2 |
February | 0.153854E+10 | 32633.88 | 05-FEB-08:61 | -20.1 |
March | 0.925662E+09 | 32603.68 | 05-MAR-08:61 | -18.1 |
April | 0.222907E+09 | 30297.37 | 29-APR-06:02 | -6.8 |
May | 0.191005E+09 | 32060.80 | 08-MAY-06:01 | -2.7 |
June | 52524878.77 | 1860.11 | 23-JUN-06:05 | 18.58 |
July | 0.100436E+09 | 2779.81 | 17-JUL-19:02 | 33.48 |
August | 81119699.52 | 3173.41 | 06-AUG-16:11 | 35.40 |
September | 70718717.26 | 2951.46 | 02-SEP-17:02 | 34.03 |
October | 90361708.64 | 13112.35 | 10-OCT-06:03 | -6.1 |
November | 0.627347E+09 | 32579.31 | 27-NOV-07:01 | -13.5 |
December | 0.202261E+10 | 32610.03 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.944223E+10 | |||
Minimum of Months | 52524878.77 | 1860.11 | -27.6 | |
Maximum of Months | 0.351899E+10 | 32633.88 | 35.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.388085E+10 | 32564.52 | 08-JAN-08:61 | -27.2 |
February | 0.177117E+10 | 32565.68 | 05-FEB-08:61 | -20.1 |
March | 0.111661E+10 | 32535.73 | 05-MAR-08:61 | -18.1 |
April | 0.286430E+09 | 31789.72 | 30-APR-07:02 | -3.2 |
May | 0.240208E+09 | 32000.89 | 08-MAY-06:01 | -2.7 |
June | 55967226.96 | 1805.37 | 22-JUN-06:04 | 16.57 |
July | 99992624.58 | 2780.88 | 17-JUL-19:02 | 33.48 |
August | 81668843.81 | 3167.81 | 06-AUG-16:11 | 35.40 |
September | 77897492.76 | 2952.06 | 02-SEP-17:02 | 34.03 |
October | 0.120591E+09 | 17631.20 | 10-OCT-06:03 | -6.1 |
November | 0.738908E+09 | 32512.34 | 27-NOV-07:01 | -13.5 |
December | 0.229591E+10 | 32542.29 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.107662E+11 | |||
Minimum of Months | 55967226.96 | 1805.37 | -27.6 | |
Maximum of Months | 0.388085E+10 | 32565.68 | 35.40 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.838344E+10 | 59760.23 | 08-JAN-09:12 | -27.0 |
February | 0.405868E+10 | 59572.18 | 04-FEB-08:61 | -20.0 |
March | 0.271845E+10 | 59555.76 | 04-MAR-08:61 | -19.9 |
April | 0.790276E+09 | 59503.40 | 22-APR-07:01 | 2.85 |
May | 0.539042E+09 | 59494.34 | 08-MAY-07:01 | -2.1 |
June | 47747120.28 | 1950.30 | 24-JUN-17:03 | 27.52 |
July | 67691238.98 | 4270.80 | 16-JUL-16:02 | 32.88 |
August | 63631271.63 | 5326.74 | 06-AUG-16:02 | 35.50 |
September | 94815248.12 | 33863.67 | 20-SEP-07:01 | 4.78 |
October | 0.246924E+09 | 59513.73 | 10-OCT-07:01 | -5.7 |
November | 0.178988E+10 | 59538.63 | 27-NOV-08:61 | -12.7 |
December | 0.521867E+10 | 59612.71 | 31-DEC-09:01 | -26.2 |
Annual Sum or Average | 0.240193E+11 | |||
Minimum of Months | 47747120.28 | 1950.30 | -27.0 | |
Maximum of Months | 0.838344E+10 | 59760.23 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.470261E+10 | 30294.68 | 08-JAN-09:12 | -27.0 |
February | 0.233948E+10 | 30121.82 | 04-FEB-08:61 | -20.0 |
March | 0.161667E+10 | 30112.29 | 04-MAR-08:61 | -19.9 |
April | 0.515070E+09 | 30083.94 | 29-APR-07:01 | -4.5 |
May | 0.368926E+09 | 30080.21 | 08-MAY-07:01 | -2.1 |
June | 52870837.91 | 1515.56 | 24-JUN-17:12 | 27.23 |
July | 56717665.37 | 2631.82 | 16-JUL-16:02 | 32.88 |
August | 50352430.88 | 3140.10 | 06-AUG-16:02 | 35.50 |
September | 88962488.80 | 17591.56 | 20-SEP-07:01 | 4.78 |
October | 0.197987E+09 | 30090.43 | 10-OCT-07:01 | -5.7 |
November | 0.107541E+10 | 30103.76 | 27-NOV-08:61 | -12.7 |
December | 0.298910E+10 | 30120.75 | 31-DEC-09:01 | -26.2 |
Annual Sum or Average | 0.140541E+11 | |||
Minimum of Months | 50352430.88 | 1515.56 | -27.0 | |
Maximum of Months | 0.470261E+10 | 30294.68 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.479340E+10 | 30089.80 | 08-JAN-09:12 | -27.0 |
February | 0.241045E+10 | 29913.32 | 04-FEB-08:61 | -20.0 |
March | 0.169201E+10 | 29903.26 | 04-MAR-08:61 | -19.9 |
April | 0.563652E+09 | 29875.94 | 29-APR-07:01 | -4.5 |
May | 0.396951E+09 | 29872.26 | 08-MAY-07:01 | -2.1 |
June | 56429285.09 | 1509.52 | 24-JUN-17:12 | 27.23 |
July | 56988006.75 | 2629.16 | 16-JUL-16:02 | 32.88 |
August | 51355518.98 | 3137.95 | 06-AUG-16:02 | 35.50 |
September | 90136568.37 | 19234.35 | 20-SEP-07:01 | 4.78 |
October | 0.206411E+09 | 29882.41 | 10-OCT-07:01 | -5.7 |
November | 0.112286E+10 | 29895.49 | 27-NOV-08:61 | -12.7 |
December | 0.306809E+10 | 29913.10 | 31-DEC-09:01 | -26.2 |
Annual Sum or Average | 0.145087E+11 | |||
Minimum of Months | 51355518.98 | 1509.52 | -27.0 | |
Maximum of Months | 0.479340E+10 | 30089.80 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.519019E+10 | 29761.80 | 08-JAN-09:12 | -27.0 |
February | 0.270677E+10 | 29578.30 | 05-FEB-09:01 | -20.4 |
March | 0.198894E+10 | 29552.24 | 04-MAR-08:61 | -19.9 |
April | 0.753498E+09 | 29524.51 | 22-APR-07:01 | 2.85 |
May | 0.505943E+09 | 29520.16 | 08-MAY-07:01 | -2.1 |
June | 70471399.16 | 2311.55 | 17-JUN-07:03 | 8.77 |
July | 58431946.39 | 2627.32 | 16-JUL-16:02 | 32.88 |
August | 56348616.44 | 3136.55 | 06-AUG-16:02 | 35.50 |
September | 99524363.05 | 25377.35 | 20-SEP-07:01 | 4.78 |
October | 0.241441E+09 | 29527.73 | 10-OCT-07:01 | -5.7 |
November | 0.129291E+10 | 29541.15 | 27-NOV-08:61 | -12.7 |
December | 0.341321E+10 | 29589.76 | 31-DEC-09:13 | -25.8 |
Annual Sum or Average | 0.163777E+11 | |||
Minimum of Months | 56348616.44 | 2311.55 | -27.0 | |
Maximum of Months | 0.519019E+10 | 29761.80 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.765881E+10 | 31340.71 | 08-JAN-09:12 | -27.0 |
February | 0.428448E+10 | 31122.44 | 05-FEB-09:01 | -20.4 |
March | 0.354738E+10 | 31122.96 | 06-MAR-08:13 | -15.5 |
April | 0.163193E+10 | 30969.41 | 22-APR-07:01 | 2.85 |
May | 0.100728E+10 | 30962.53 | 01-MAY-07:01 | 0.78 |
June | 0.106608E+09 | 17841.86 | 17-JUN-07:03 | 8.77 |
July | 73637623.99 | 2661.89 | 16-JUL-16:02 | 32.88 |
August | 84749057.52 | 3491.42 | 18-AUG-07:05 | 10.37 |
September | 0.167069E+09 | 30510.21 | 20-SEP-07:01 | 4.78 |
October | 0.418048E+09 | 30965.51 | 10-OCT-07:01 | -5.7 |
November | 0.208406E+10 | 31014.79 | 27-NOV-08:61 | -12.7 |
December | 0.509054E+10 | 31149.45 | 31-DEC-09:13 | -25.8 |
Annual Sum or Average | 0.261546E+11 | |||
Minimum of Months | 73637623.99 | 2661.89 | -27.0 | |
Maximum of Months | 0.765881E+10 | 31340.71 | 32.88 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.109389E+11 | 6635.66 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.989784E+10 | 6635.66 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.109616E+11 | 6635.66 | 01-MAR-10:09 | 0.223053E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.106145E+11 | 6635.66 | 01-APR-09:09 | 0.215990E+10 | 1343.25 | 01-APR-09:09 |
May | 0.109389E+11 | 6635.66 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.106145E+11 | 6635.66 | 01-JUN-09:09 | 0.215990E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.109616E+11 | 6635.66 | 01-JUL-09:09 | 0.223053E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.109389E+11 | 6635.66 | 01-AUG-09:09 | 0.222596E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.106372E+11 | 6635.66 | 01-SEP-09:09 | 0.216447E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.109389E+11 | 6635.66 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.105693E+11 | 6635.66 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.109842E+11 | 6635.66 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.128996E+12 | 0.262491E+11 | ||||
Minimum of Months | 0.989784E+10 | 6635.66 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.109842E+11 | 6635.66 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.625207E+10 | 3792.57 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.565704E+10 | 3792.57 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.626500E+10 | 3792.57 | 01-MAR-10:09 | 0.111526E+10 | 671.63 | 01-MAR-10:09 |
April | 0.606666E+10 | 3792.57 | 01-APR-09:09 | 0.107995E+10 | 671.63 | 01-APR-09:09 |
May | 0.625207E+10 | 3792.57 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.606666E+10 | 3792.57 | 01-JUN-09:09 | 0.107995E+10 | 671.63 | 01-JUN-09:09 |
July | 0.626500E+10 | 3792.57 | 01-JUL-09:09 | 0.111526E+10 | 671.63 | 01-JUL-09:09 |
August | 0.625207E+10 | 3792.57 | 01-AUG-09:09 | 0.111298E+10 | 671.63 | 01-AUG-09:09 |
September | 0.607960E+10 | 3792.57 | 01-SEP-09:09 | 0.108223E+10 | 671.63 | 01-SEP-09:09 |
October | 0.625207E+10 | 3792.57 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.604079E+10 | 3792.57 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.627794E+10 | 3792.57 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.737270E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.565704E+10 | 3792.57 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.627794E+10 | 3792.57 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.447798E+10 | 3443.15 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.405524E+10 | 3443.15 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.457193E+10 | 3443.15 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.434490E+10 | 3443.15 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.452496E+10 | 3443.15 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.441536E+10 | 3443.15 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.445450E+10 | 3443.15 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.457193E+10 | 3443.15 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.434490E+10 | 3443.15 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.447798E+10 | 3443.15 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.434490E+10 | 3443.15 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.445450E+10 | 3443.15 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.530391E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.405524E+10 | 3443.15 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.457193E+10 | 3443.15 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.447798E+10 | 3443.15 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.405524E+10 | 3443.15 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.457193E+10 | 3443.15 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.434490E+10 | 3443.15 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.452496E+10 | 3443.15 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.441536E+10 | 3443.15 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.445450E+10 | 3443.15 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.457193E+10 | 3443.15 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.434490E+10 | 3443.15 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.447798E+10 | 3443.15 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.434490E+10 | 3443.15 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.445450E+10 | 3443.15 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.530391E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.405524E+10 | 3443.15 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.457193E+10 | 3443.15 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.447798E+10 | 3443.15 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.405524E+10 | 3443.15 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.457193E+10 | 3443.15 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.434490E+10 | 3443.15 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.452496E+10 | 3443.15 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.441536E+10 | 3443.15 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.445450E+10 | 3443.15 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.457193E+10 | 3443.15 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.434490E+10 | 3443.15 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.447798E+10 | 3443.15 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.434490E+10 | 3443.15 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.445450E+10 | 3443.15 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.530391E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.405524E+10 | 3443.15 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.457193E+10 | 3443.15 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.531643E+10 | 4449.56 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.481564E+10 | 4449.56 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.543783E+10 | 4449.56 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.515962E+10 | 4449.56 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.537713E+10 | 4449.56 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.525067E+10 | 4449.56 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.528608E+10 | 4449.56 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.543783E+10 | 4449.56 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.515962E+10 | 4449.56 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.531643E+10 | 4449.56 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.515962E+10 | 4449.56 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.528608E+10 | 4449.56 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.630030E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.481564E+10 | 4449.56 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.543783E+10 | 4449.56 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.265822E+10 | 2224.78 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.240782E+10 | 2224.78 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.271892E+10 | 2224.78 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.257981E+10 | 2224.78 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.268857E+10 | 2224.78 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.262534E+10 | 2224.78 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.264304E+10 | 2224.78 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.271892E+10 | 2224.78 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.257981E+10 | 2224.78 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.265822E+10 | 2224.78 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.257981E+10 | 2224.78 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.264304E+10 | 2224.78 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.315015E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.240782E+10 | 2224.78 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.271892E+10 | 2224.78 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.265822E+10 | 2224.78 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.240782E+10 | 2224.78 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.271892E+10 | 2224.78 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.257981E+10 | 2224.78 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.268857E+10 | 2224.78 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.262534E+10 | 2224.78 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.264304E+10 | 2224.78 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.271892E+10 | 2224.78 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.257981E+10 | 2224.78 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.265822E+10 | 2224.78 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.257981E+10 | 2224.78 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.264304E+10 | 2224.78 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.315015E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.240782E+10 | 2224.78 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.271892E+10 | 2224.78 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.265822E+10 | 2224.78 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.240782E+10 | 2224.78 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.271892E+10 | 2224.78 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.257981E+10 | 2224.78 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.268857E+10 | 2224.78 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.262534E+10 | 2224.78 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.264304E+10 | 2224.78 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.271892E+10 | 2224.78 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.257981E+10 | 2224.78 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.265822E+10 | 2224.78 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.257981E+10 | 2224.78 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.264304E+10 | 2224.78 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.315015E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.240782E+10 | 2224.78 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.271892E+10 | 2224.78 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.265822E+10 | 2224.78 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.240782E+10 | 2224.78 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.271892E+10 | 2224.78 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.257981E+10 | 2224.78 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.268857E+10 | 2224.78 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.262534E+10 | 2224.78 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.264304E+10 | 2224.78 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.271892E+10 | 2224.78 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.257981E+10 | 2224.78 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.265822E+10 | 2224.78 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.257981E+10 | 2224.78 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.264304E+10 | 2224.78 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.315015E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.240782E+10 | 2224.78 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.271892E+10 | 2224.78 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.180574E+10 | 0.109389E+11 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822907E+10 |
February | 0.163016E+10 | 0.989784E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550751E+10 |
March | 0.178954E+10 | 0.109616E+11 | 0.223053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505519E+10 |
April | 0.174484E+10 | 0.106145E+11 | 0.215990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322222E+10 |
May | 0.179537E+10 | 0.109389E+11 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40073783.78 | 0.281450E+10 |
June | 0.173447E+10 | 0.106145E+11 | 0.215990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249750E+09 | 0.128281E+10 |
July | 0.181028E+10 | 0.109616E+11 | 0.223053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677602E+09 | 0.614750E+09 |
August | 0.178501E+10 | 0.109389E+11 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518198E+09 | 0.890144E+09 |
September | 0.174937E+10 | 0.106372E+11 | 0.216447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237866E+09 | 0.186516E+10 |
October | 0.180574E+10 | 0.109389E+11 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2821184.76 | 0.312953E+10 |
November | 0.174613E+10 | 0.105693E+11 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467677E+10 |
December | 0.181481E+10 | 0.109842E+11 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659134E+10 |
Annual Sum or Average | 0.212115E+11 | 0.128996E+12 | 0.262491E+11 | 0.172631E+10 | 0.438790E+11 | ||||
Minimum of Months | 0.163016E+10 | 0.989784E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614750E+09 |
Maximum of Months | 0.181481E+10 | 0.109842E+11 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677602E+09 | 0.822907E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.902868E+09 | 0.625207E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402497E+10 |
February | 0.815075E+09 | 0.565704E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268549E+10 |
March | 0.894769E+09 | 0.626500E+10 | 0.111526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248732E+10 |
April | 0.872416E+09 | 0.606666E+10 | 0.107995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162016E+10 |
May | 0.897684E+09 | 0.625207E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21469884.26 | 0.135218E+10 |
June | 0.867232E+09 | 0.606666E+10 | 0.107995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134783E+09 | 0.565441E+09 |
July | 0.905135E+09 | 0.626500E+10 | 0.111526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366026E+09 | 0.242499E+09 |
August | 0.892501E+09 | 0.625207E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279253E+09 | 0.381049E+09 |
September | 0.874683E+09 | 0.607960E+10 | 0.108223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128207E+09 | 0.853828E+09 |
October | 0.902868E+09 | 0.625207E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1515570.23 | 0.151950E+10 |
November | 0.873064E+09 | 0.604079E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229975E+10 |
December | 0.907403E+09 | 0.627794E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323285E+10 |
Annual Sum or Average | 0.106057E+11 | 0.737270E+11 | 0.131245E+11 | 0.931254E+09 | 0.212650E+11 | ||||
Minimum of Months | 0.815075E+09 | 0.565704E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242499E+09 |
Maximum of Months | 0.907403E+09 | 0.627794E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366026E+09 | 0.402497E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.447798E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412497E+10 |
February | 0.487879E+09 | 0.405524E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276114E+10 |
March | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254625E+10 |
April | 0.524810E+09 | 0.434490E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166224E+10 |
May | 0.544247E+09 | 0.452496E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21312444.66 | 0.139382E+10 |
June | 0.532585E+09 | 0.441536E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133353E+09 | 0.602381E+09 |
July | 0.536472E+09 | 0.445450E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357434E+09 | 0.274497E+09 |
August | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275845E+09 | 0.410377E+09 |
September | 0.524810E+09 | 0.434490E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122323E+09 | 0.894192E+09 |
October | 0.537120E+09 | 0.447798E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1515539.63 | 0.156441E+10 |
November | 0.518979E+09 | 0.434490E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235618E+10 |
December | 0.536472E+09 | 0.445450E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332119E+10 |
Annual Sum or Average | 0.638324E+10 | 0.530391E+11 | 0.104207E+11 | 0.911784E+09 | 0.219117E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.405524E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274497E+09 |
Maximum of Months | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357434E+09 | 0.412497E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.447798E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411712E+10 |
February | 0.487879E+09 | 0.405524E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274969E+10 |
March | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253384E+10 |
April | 0.524810E+09 | 0.434490E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164780E+10 |
May | 0.544247E+09 | 0.452496E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21312888.47 | 0.138436E+10 |
June | 0.532585E+09 | 0.441536E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133355E+09 | 0.601532E+09 |
July | 0.536472E+09 | 0.445450E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357363E+09 | 0.274815E+09 |
August | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275787E+09 | 0.410321E+09 |
September | 0.524810E+09 | 0.434490E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122252E+09 | 0.890543E+09 |
October | 0.537120E+09 | 0.447798E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1515539.47 | 0.155427E+10 |
November | 0.518979E+09 | 0.434490E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233892E+10 |
December | 0.536472E+09 | 0.445450E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331244E+10 |
Annual Sum or Average | 0.638324E+10 | 0.530391E+11 | 0.104207E+11 | 0.911585E+09 | 0.218157E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.405524E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274815E+09 |
Maximum of Months | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357363E+09 | 0.411712E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.447798E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411070E+10 |
February | 0.487879E+09 | 0.405524E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273763E+10 |
March | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252049E+10 |
April | 0.524810E+09 | 0.434490E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162522E+10 |
May | 0.544247E+09 | 0.452496E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21315228.15 | 0.136813E+10 |
June | 0.532585E+09 | 0.441536E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133361E+09 | 0.597533E+09 |
July | 0.536472E+09 | 0.445450E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357587E+09 | 0.272437E+09 |
August | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275871E+09 | 0.407112E+09 |
September | 0.524810E+09 | 0.434490E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122352E+09 | 0.881736E+09 |
October | 0.537120E+09 | 0.447798E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1515540.38 | 0.153543E+10 |
November | 0.518979E+09 | 0.434490E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231237E+10 |
December | 0.536472E+09 | 0.445450E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330515E+10 |
Annual Sum or Average | 0.638324E+10 | 0.530391E+11 | 0.104207E+11 | 0.912002E+09 | 0.216739E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.405524E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272437E+09 |
Maximum of Months | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357587E+09 | 0.411070E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.183632E+10 | 0.531643E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.756094E+10 |
February | 0.167188E+10 | 0.481564E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501134E+10 |
March | 0.189386E+10 | 0.543783E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461377E+10 |
April | 0.180380E+10 | 0.515962E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288461E+10 |
May | 0.186509E+10 | 0.537713E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38450261.65 | 0.246187E+10 |
June | 0.182945E+10 | 0.525067E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240418E+09 | 0.110449E+10 |
July | 0.183943E+10 | 0.528608E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646660E+09 | 0.516302E+09 |
August | 0.189386E+10 | 0.543783E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498107E+09 | 0.759343E+09 |
September | 0.180380E+10 | 0.515962E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221493E+09 | 0.160933E+10 |
October | 0.183632E+10 | 0.531643E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2730552.52 | 0.274093E+10 |
November | 0.176881E+10 | 0.515962E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417443E+10 |
December | 0.183943E+10 | 0.528608E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.607823E+10 |
Annual Sum or Average | 0.218821E+11 | 0.630030E+11 | 0.191729E+11 | 0.164786E+10 | 0.395156E+11 | ||||
Minimum of Months | 0.167188E+10 | 0.481564E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516302E+09 |
Maximum of Months | 0.189386E+10 | 0.543783E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646660E+09 | 0.756094E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412977E+10 |
February | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273411E+10 |
March | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251635E+10 |
April | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158640E+10 |
May | 0.932542E+09 | 0.268857E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21326326.93 | 0.134688E+10 |
June | 0.914724E+09 | 0.262534E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133490E+09 | 0.596392E+09 |
July | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358908E+09 | 0.271836E+09 |
August | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276520E+09 | 0.406637E+09 |
September | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122810E+09 | 0.874829E+09 |
October | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1515708.11 | 0.150800E+10 |
November | 0.884402E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228155E+10 |
December | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331779E+10 |
Annual Sum or Average | 0.109410E+11 | 0.315015E+11 | 0.958644E+10 | 0.914571E+09 | 0.215705E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271836E+09 |
Maximum of Months | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358908E+09 | 0.412977E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412823E+10 |
February | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273100E+10 |
March | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251380E+10 |
April | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158065E+10 |
May | 0.932542E+09 | 0.268857E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21327300.31 | 0.134219E+10 |
June | 0.914724E+09 | 0.262534E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133499E+09 | 0.594711E+09 |
July | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358992E+09 | 0.270940E+09 |
August | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276557E+09 | 0.405644E+09 |
September | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122854E+09 | 0.872680E+09 |
October | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1515708.36 | 0.150397E+10 |
November | 0.884402E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227746E+10 |
December | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331603E+10 |
Annual Sum or Average | 0.109410E+11 | 0.315015E+11 | 0.958644E+10 | 0.914745E+09 | 0.215373E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270940E+09 |
Maximum of Months | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358992E+09 | 0.412823E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412133E+10 |
February | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271968E+10 |
March | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250522E+10 |
April | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156151E+10 |
May | 0.932542E+09 | 0.268857E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21330387.76 | 0.132543E+10 |
June | 0.914724E+09 | 0.262534E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133555E+09 | 0.587773E+09 |
July | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359199E+09 | 0.268104E+09 |
August | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276625E+09 | 0.402150E+09 |
September | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122930E+09 | 0.864277E+09 |
October | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1515704.96 | 0.148709E+10 |
November | 0.884402E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226399E+10 |
December | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330888E+10 |
Annual Sum or Average | 0.109410E+11 | 0.315015E+11 | 0.958644E+10 | 0.915155E+09 | 0.214154E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268104E+09 |
Maximum of Months | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359199E+09 | 0.412133E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516683E+10 |
February | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347586E+10 |
March | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319623E+10 |
April | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199402E+10 |
May | 0.932542E+09 | 0.268857E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22714374.21 | 0.176144E+10 |
June | 0.914724E+09 | 0.262534E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140825E+09 | 0.846333E+09 |
July | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379039E+09 | 0.445347E+09 |
August | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292746E+09 | 0.608806E+09 |
September | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129832E+09 | 0.123034E+10 |
October | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1606602.96 | 0.197090E+10 |
November | 0.884402E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294044E+10 |
December | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414968E+10 |
Annual Sum or Average | 0.109410E+11 | 0.315015E+11 | 0.958644E+10 | 0.966764E+09 | 0.277862E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445347E+09 |
Maximum of Months | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379039E+09 | 0.516683E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2159.72 | 01-JAN-13:09 | 6635.66 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 15364.07 | 10-JAN-18:00 |
February | 2159.72 | 03-FEB-13:09 | 6635.66 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 12414.04 | 09-FEB-18:00 |
March | 2159.72 | 03-MAR-13:09 | 6635.66 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 11849.64 | 04-MAR-18:00 |
April | 2159.72 | 01-APR-12:09 | 6635.66 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 7152.78 | 27-APR-11:10 |
May | 2159.72 | 05-MAY-12:09 | 6635.66 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1606.61 | 20-MAY-16:00 | 6558.07 | 22-MAY-16:00 |
June | 2159.72 | 02-JUN-12:09 | 6635.66 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2254.08 | 29-JUN-15:00 | 4389.35 | 16-JUN-11:05 |
July | 2159.72 | 01-JUL-12:09 | 6635.66 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3402.02 | 17-JUL-16:00 | 2673.25 | 05-JUL-11:10 |
August | 2159.72 | 04-AUG-12:09 | 6635.66 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3013.90 | 05-AUG-16:00 | 4252.50 | 17-AUG-11:05 |
September | 2159.72 | 01-SEP-12:09 | 6635.66 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2770.44 | 02-SEP-15:00 | 5059.85 | 12-SEP-11:10 |
October | 2159.72 | 01-OCT-12:09 | 6635.66 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 300.32 | 18-OCT-14:00 | 6168.47 | 10-OCT-11:10 |
November | 2159.72 | 03-NOV-12:09 | 6635.66 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 10834.03 | 26-NOV-18:00 |
December | 2159.72 | 01-DEC-13:09 | 6635.66 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13286.17 | 28-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2159.72 | 6635.66 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2673.25 | |||||
Maximum of Months | 2159.72 | 6635.66 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3402.02 | 15364.07 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 01-JAN-13:09 | 3792.57 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8415.71 | 10-JAN-18:00 |
February | 1079.86 | 03-FEB-13:09 | 3792.57 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6783.34 | 09-FEB-18:00 |
March | 1079.86 | 03-MAR-13:09 | 3792.57 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6558.56 | 04-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 3792.57 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3838.45 | 27-APR-11:10 |
May | 1079.86 | 05-MAY-12:09 | 3792.57 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 867.12 | 20-MAY-16:00 | 3450.85 | 22-MAY-16:00 |
June | 1079.86 | 02-JUN-12:09 | 3792.57 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.97 | 29-JUN-15:00 | 2580.36 | 16-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 3792.57 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.59 | 17-JUL-16:00 | 1485.06 | 05-JUL-11:10 |
August | 1079.86 | 04-AUG-12:09 | 3792.57 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.32 | 05-AUG-16:00 | 2420.81 | 17-AUG-11:05 |
September | 1079.86 | 01-SEP-12:09 | 3792.57 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.52 | 02-SEP-15:00 | 2869.99 | 12-SEP-11:05 |
October | 1079.86 | 01-OCT-12:09 | 3792.57 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.34 | 18-OCT-14:00 | 3337.96 | 10-OCT-11:10 |
November | 1079.86 | 03-NOV-12:09 | 3792.57 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5891.64 | 26-NOV-18:00 |
December | 1079.86 | 01-DEC-13:09 | 3792.57 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7350.57 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3792.57 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1485.06 | |||||
Maximum of Months | 1079.86 | 3792.57 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.59 | 8415.71 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3443.15 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8415.69 | 10-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 3443.15 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6783.33 | 09-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3443.15 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6558.56 | 04-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 3443.15 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3838.44 | 27-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 3443.15 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 867.12 | 20-MAY-16:00 | 3450.83 | 22-MAY-16:00 |
June | 1079.86 | 03-JUN-12:09 | 3443.15 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.97 | 29-JUN-15:00 | 2572.19 | 16-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 3443.15 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.58 | 17-JUL-16:00 | 1485.06 | 05-JUL-11:10 |
August | 1079.86 | 05-AUG-12:09 | 3443.15 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.32 | 05-AUG-16:00 | 2425.80 | 17-AUG-11:05 |
September | 1079.86 | 02-SEP-12:09 | 3443.15 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.52 | 02-SEP-15:00 | 2865.87 | 12-SEP-11:05 |
October | 1079.86 | 07-OCT-12:09 | 3443.15 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.34 | 18-OCT-14:00 | 3337.08 | 10-OCT-11:10 |
November | 1079.86 | 04-NOV-12:09 | 3443.15 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5891.64 | 26-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3443.15 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7350.58 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1485.06 | |||||
Maximum of Months | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.58 | 8415.69 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3443.15 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8415.69 | 10-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 3443.15 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6783.33 | 09-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3443.15 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6558.56 | 04-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 3443.15 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3838.42 | 27-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 3443.15 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 867.12 | 20-MAY-16:00 | 3450.83 | 22-MAY-16:00 |
June | 1079.86 | 03-JUN-12:09 | 3443.15 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.97 | 29-JUN-15:00 | 2563.49 | 16-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 3443.15 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.58 | 17-JUL-16:00 | 1485.06 | 05-JUL-11:10 |
August | 1079.86 | 05-AUG-12:09 | 3443.15 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.32 | 05-AUG-16:00 | 2423.21 | 17-AUG-11:05 |
September | 1079.86 | 02-SEP-12:09 | 3443.15 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.52 | 02-SEP-15:00 | 2856.16 | 12-SEP-11:05 |
October | 1079.86 | 07-OCT-12:09 | 3443.15 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.34 | 18-OCT-14:00 | 3337.08 | 10-OCT-11:10 |
November | 1079.86 | 04-NOV-12:09 | 3443.15 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5891.64 | 26-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3443.15 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7350.58 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1485.06 | |||||
Maximum of Months | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.58 | 8415.69 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3443.15 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8415.69 | 10-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 3443.15 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6783.33 | 09-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3443.15 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6558.56 | 04-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 3443.15 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3838.42 | 27-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 3443.15 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 867.12 | 20-MAY-16:00 | 3450.84 | 22-MAY-16:00 |
June | 1079.86 | 03-JUN-12:09 | 3443.15 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.97 | 29-JUN-15:00 | 2530.81 | 16-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 3443.15 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.58 | 17-JUL-16:00 | 1485.07 | 05-JUL-11:10 |
August | 1079.86 | 05-AUG-12:09 | 3443.15 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.32 | 05-AUG-16:00 | 2393.34 | 17-AUG-11:05 |
September | 1079.86 | 02-SEP-12:09 | 3443.15 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.52 | 02-SEP-15:00 | 2815.10 | 12-SEP-11:05 |
October | 1079.86 | 07-OCT-12:09 | 3443.15 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.34 | 18-OCT-14:00 | 3337.08 | 10-OCT-11:10 |
November | 1079.86 | 04-NOV-12:09 | 3443.15 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5891.64 | 26-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3443.15 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7350.58 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1485.07 | |||||
Maximum of Months | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.58 | 8415.69 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2879.63 | 07-JAN-15:09 | 4449.56 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 15122.72 | 10-JAN-18:00 |
February | 2879.63 | 04-FEB-15:09 | 4449.56 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 12193.06 | 09-FEB-18:00 |
March | 2879.63 | 04-MAR-15:09 | 4449.56 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 11770.36 | 04-MAR-18:00 |
April | 2879.63 | 01-APR-14:09 | 4449.56 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 6915.20 | 27-APR-11:10 |
May | 2879.63 | 06-MAY-14:09 | 4449.56 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1561.15 | 20-MAY-16:00 | 6232.53 | 22-MAY-16:00 |
June | 2879.63 | 03-JUN-14:09 | 4449.56 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2159.34 | 29-JUN-15:00 | 4348.49 | 16-JUN-11:05 |
July | 2879.63 | 01-JUL-14:09 | 4449.56 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3334.48 | 17-JUL-16:00 | 2603.09 | 05-JUL-11:10 |
August | 2879.63 | 05-AUG-14:09 | 4449.56 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2946.71 | 05-AUG-16:00 | 4010.76 | 17-AUG-11:05 |
September | 2879.63 | 02-SEP-14:09 | 4449.56 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2681.19 | 02-SEP-15:00 | 4867.39 | 12-SEP-11:10 |
October | 2879.63 | 07-OCT-14:09 | 4449.56 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 290.66 | 18-OCT-14:00 | 6005.89 | 10-OCT-11:10 |
November | 2879.63 | 04-NOV-14:09 | 4449.56 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 10596.59 | 26-NOV-18:00 |
December | 2879.63 | 02-DEC-15:09 | 4449.56 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13191.80 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2879.63 | 4449.56 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2603.09 | |||||
Maximum of Months | 2879.63 | 4449.56 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3334.48 | 15122.72 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2224.78 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8415.69 | 10-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2224.78 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6783.32 | 09-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2224.78 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6558.55 | 04-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 2224.78 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3838.41 | 27-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 2224.78 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 867.14 | 20-MAY-16:00 | 3450.82 | 22-MAY-16:00 |
June | 1439.81 | 03-JUN-14:09 | 2224.78 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.98 | 29-JUN-15:00 | 2431.14 | 16-JUN-11:05 |
July | 1439.81 | 01-JUL-14:09 | 2224.78 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.61 | 17-JUL-16:00 | 1475.28 | 05-JUL-11:10 |
August | 1439.81 | 05-AUG-14:09 | 2224.78 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.34 | 05-AUG-16:00 | 2288.81 | 17-AUG-11:05 |
September | 1439.81 | 02-SEP-14:09 | 2224.78 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.54 | 02-SEP-15:00 | 2703.53 | 12-SEP-11:05 |
October | 1439.81 | 07-OCT-14:09 | 2224.78 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.35 | 18-OCT-14:00 | 3337.07 | 10-OCT-11:10 |
November | 1439.81 | 04-NOV-14:09 | 2224.78 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5891.63 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2224.78 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7350.58 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1475.28 | |||||
Maximum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.61 | 8415.69 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2224.78 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8415.69 | 10-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2224.78 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6783.32 | 09-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2224.78 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6558.55 | 04-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 2224.78 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3838.41 | 27-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 2224.78 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 867.14 | 20-MAY-16:00 | 3450.82 | 22-MAY-16:00 |
June | 1439.81 | 03-JUN-14:09 | 2224.78 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.98 | 29-JUN-15:00 | 2426.39 | 16-JUN-11:05 |
July | 1439.81 | 01-JUL-14:09 | 2224.78 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.61 | 17-JUL-16:00 | 1472.41 | 05-JUL-11:10 |
August | 1439.81 | 05-AUG-14:09 | 2224.78 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.34 | 05-AUG-16:00 | 2281.80 | 17-AUG-11:05 |
September | 1439.81 | 02-SEP-14:09 | 2224.78 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.54 | 02-SEP-15:00 | 2702.38 | 12-SEP-11:05 |
October | 1439.81 | 07-OCT-14:09 | 2224.78 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.35 | 18-OCT-14:00 | 3337.07 | 10-OCT-11:10 |
November | 1439.81 | 04-NOV-14:09 | 2224.78 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5891.63 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2224.78 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7350.58 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1472.41 | |||||
Maximum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.61 | 8415.69 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2224.78 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8415.69 | 10-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2224.78 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6783.32 | 09-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2224.78 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6558.55 | 04-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 2224.78 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3838.42 | 27-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 2224.78 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 867.14 | 20-MAY-16:00 | 3450.82 | 22-MAY-16:00 |
June | 1439.81 | 03-JUN-14:09 | 2224.78 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.98 | 29-JUN-15:00 | 2422.29 | 16-JUN-11:05 |
July | 1439.81 | 01-JUL-14:09 | 2224.78 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.61 | 17-JUL-16:00 | 1461.60 | 05-JUL-11:10 |
August | 1439.81 | 05-AUG-14:09 | 2224.78 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.34 | 05-AUG-16:00 | 2251.07 | 17-AUG-11:05 |
September | 1439.81 | 02-SEP-14:09 | 2224.78 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.54 | 02-SEP-15:00 | 2699.79 | 12-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 2224.78 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.35 | 18-OCT-14:00 | 3337.07 | 10-OCT-11:10 |
November | 1439.81 | 04-NOV-14:09 | 2224.78 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5891.64 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2224.78 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7350.58 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1461.60 | |||||
Maximum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.61 | 8415.69 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2224.78 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8656.72 | 10-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2224.78 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 7003.99 | 09-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2224.78 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6689.31 | 04-MAR-14:00 |
April | 1439.81 | 01-APR-14:09 | 2224.78 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4075.67 | 27-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 2224.78 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 912.60 | 20-MAY-16:00 | 3775.94 | 22-MAY-16:00 |
June | 1439.81 | 03-JUN-14:09 | 2224.78 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1291.67 | 29-JUN-15:00 | 2462.91 | 16-JUN-11:05 |
July | 1439.81 | 01-JUL-14:09 | 2224.78 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1922.12 | 17-JUL-16:00 | 1414.16 | 05-JUL-11:10 |
August | 1439.81 | 05-AUG-14:09 | 2224.78 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1705.54 | 05-AUG-16:00 | 2347.00 | 17-AUG-11:05 |
September | 1439.81 | 02-SEP-14:09 | 2224.78 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1577.77 | 02-SEP-15:00 | 2891.97 | 12-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 2224.78 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 171.02 | 18-OCT-14:00 | 3499.42 | 10-OCT-11:10 |
November | 1439.81 | 04-NOV-14:09 | 2224.78 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6128.78 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2224.78 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7465.44 | 28-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1414.16 | |||||
Maximum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1922.12 | 8656.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20429.05 | 28-JAN-00:01 | 1619.79 | 31432.07 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.07 |
February | 16945.42 | 04-FEB-00:01 | 1439.81 | 27939.61 | 5970.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.12 |
March | 15297.06 | 04-MAR-00:01 | 1259.84 | 24447.16 | 5223.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.48 |
April | 9879.28 | 28-APR-23:03 | 719.91 | 13969.81 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.44 |
May | 10138.70 | 20-MAY-16:10 | 1799.77 | 6635.66 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1553.57 | 0.00 |
June | 22219.47 | 22-JUN-07:03 | 719.91 | 1396.98 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.44 |
July | 31304.33 | 27-JUL-07:02 | 1079.86 | 2095.47 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.31 |
August | 34058.35 | 08-AUG-07:02 | 899.88 | 1746.23 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.63 |
September | 34700.65 | 04-SEP-07:02 | 1079.86 | 2095.47 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.09 |
October | 10206.86 | 18-OCT-14:00 | 1439.81 | 6635.66 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 300.32 | 0.00 |
November | 9102.17 | 02-NOV-08:05 | 719.91 | 13969.81 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1017.02 |
December | 17999.72 | 29-DEC-00:01 | 1439.81 | 27939.61 | 5970.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.32 |
Annual Sum or Average | |||||||||||
Minimum of Months | 9102.17 | 719.91 | 1396.98 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34700.65 | 1799.77 | 31432.07 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1553.57 | 1017.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7344.01 | 05-JAN-18:02 | 4499.40 | 18962.84 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1223.81 |
February | 3776.85 | 21-FEB-21:00 | 539.93 | 3792.57 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.48 |
March | 3701.88 | 01-MAR-09:03 | 269.96 | 5988.27 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 578.23 |
April | 19766.74 | 25-APR-20:02 | 5399.28 | 37925.68 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20739.05 | 31-MAY-21:38 | 2159.71 | 15170.27 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.59 |
June | 21443.56 | 24-JUN-21:15 | 4319.42 | 30340.54 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.49 |
July | 21140.69 | 27-JUL-07:02 | 539.93 | 1197.65 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.58 |
August | 20992.15 | 14-AUG-20:07 | 5399.28 | 37925.68 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.51 |
September | 20810.02 | 23-SEP-19:08 | 2159.71 | 15170.27 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.03 |
October | 22784.72 | 18-OCT-21:37 | 5399.28 | 37925.68 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.43 |
November | 19590.06 | 04-NOV-22:31 | 3599.52 | 37925.68 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.88 |
December | 3994.86 | 03-DEC-09:01 | 899.88 | 19960.88 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 661.37 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3701.88 | 269.96 | 1197.65 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22784.72 | 5399.28 | 37925.68 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1223.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3705.38 | 02-JAN-08:61 | 899.88 | 18121.86 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 524.09 |
February | 6052.64 | 02-FEB-19:52 | 1799.76 | 17215.77 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 841.86 |
March | 5430.77 | 01-MAR-08:61 | 809.89 | 16309.68 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.59 |
April | 4014.12 | 28-APR-07:01 | 899.88 | 18121.86 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.20 |
May | 9710.70 | 20-MAY-06:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.01 |
June | 20135.28 | 30-JUN-06:01 | 0.00 | 1268.53 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.26 |
July | 22189.83 | 28-JUL-06:01 | 0.00 | 1268.53 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23448.04 | 12-AUG-06:02 | 0.00 | 1087.31 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.34 |
September | 21555.13 | 26-SEP-06:01 | 0.00 | 1449.75 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.34 |
October | 13571.77 | 19-OCT-06:01 | 0.00 | 1268.53 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.42 |
November | 5017.21 | 11-NOV-09:01 | 809.89 | 16309.68 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 665.66 |
December | 3911.45 | 21-DEC-08:61 | 899.88 | 18121.86 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.50 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3705.38 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23448.04 | 1799.76 | 18121.86 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 841.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5933.01 | 06-JAN-18:32 | 4499.40 | 17215.77 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 840.16 |
February | 5127.22 | 01-FEB-20:23 | 359.95 | 7248.74 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.54 |
March | 5364.23 | 01-MAR-08:61 | 809.89 | 16309.68 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 670.25 |
April | 3976.37 | 28-APR-07:01 | 899.88 | 18121.86 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.96 |
May | 8921.46 | 20-MAY-06:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.00 |
June | 20429.98 | 30-JUN-06:01 | 0.00 | 1268.53 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.26 |
July | 22270.98 | 28-JUL-06:01 | 0.00 | 1268.53 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23555.81 | 12-AUG-06:02 | 0.00 | 1087.31 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.43 |
September | 21247.09 | 26-SEP-06:01 | 0.00 | 1449.75 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.34 |
October | 12359.64 | 19-OCT-06:01 | 0.00 | 1268.53 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.41 |
November | 4970.18 | 11-NOV-09:01 | 809.89 | 16309.68 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 661.14 |
December | 3670.07 | 07-DEC-08:61 | 899.88 | 18121.86 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.54 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3670.07 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23555.81 | 4499.40 | 18121.86 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 840.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5164.66 | 19-JAN-11:13 | 719.90 | 13772.62 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 753.18 |
February | 4368.11 | 28-FEB-08:61 | 719.90 | 14497.49 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 608.09 |
March | 5277.60 | 01-MAR-08:61 | 809.89 | 16309.68 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 659.73 |
April | 3935.92 | 28-APR-07:01 | 899.88 | 18121.86 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.57 |
May | 5455.85 | 20-MAY-06:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.95 |
June | 17681.78 | 24-JUN-06:02 | 0.00 | 1087.31 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.09 |
July | 21486.64 | 27-JUL-06:02 | 0.00 | 1087.31 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.39 |
August | 23194.46 | 12-AUG-06:02 | 0.00 | 1087.31 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.14 |
September | 20519.32 | 03-SEP-07:02 | 0.00 | 906.09 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.90 |
October | 8548.07 | 19-OCT-06:01 | 0.00 | 1268.53 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.36 |
November | 4671.05 | 11-NOV-09:01 | 809.89 | 16309.68 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.31 |
December | 4758.33 | 14-DEC-10:23 | 719.90 | 13772.62 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 657.72 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3935.92 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.14 | |
Maximum of Months | 23194.46 | 899.88 | 18121.86 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 753.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4953.29 | 01-JAN-15:05 | 4967.35 | 8899.12 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3870.87 |
February | 5536.35 | 27-FEB-19:20 | 935.88 | 4449.56 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 692.17 |
March | 4531.08 | 01-MAR-12:00 | 1547.80 | 4449.56 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 761.81 |
April | 5838.08 | 29-APR-15:13 | 7990.96 | 13348.69 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4404.88 |
May | 8721.41 | 20-MAY-16:00 | 2663.65 | 4449.56 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1561.15 | 0.00 |
June | 21605.95 | 22-JUN-07:03 | 0.00 | 936.75 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.18 |
July | 34064.63 | 27-JUL-07:02 | 0.00 | 1405.12 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.76 |
August | 32952.22 | 08-AUG-07:02 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.51 |
September | 33490.66 | 05-SEP-07:02 | 0.00 | 1405.12 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.62 |
October | 8817.63 | 21-OCT-08:62 | 1583.79 | 9367.50 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 920.20 |
November | 6099.73 | 06-NOV-11:40 | 1547.80 | 4449.56 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 632.21 |
December | 11957.43 | 12-DEC-20:02 | 1979.74 | 11709.37 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.75 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4531.08 | 0.00 | 936.75 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34064.63 | 7990.96 | 13348.69 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 1561.15 | 4404.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3032.23 | 04-JAN-11:43 | 2321.69 | 6674.34 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 499.52 |
February | 3562.73 | 16-FEB-20:23 | 593.92 | 3512.81 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.40 |
March | 2226.79 | 01-MAR-12:00 | 773.90 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.33 |
April | 2963.66 | 14-APR-09:03 | 593.92 | 6674.34 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 496.52 |
May | 4514.42 | 20-MAY-16:00 | 1331.82 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 867.14 | 0.00 |
June | 9605.05 | 23-JUN-07:03 | 0.00 | 468.37 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.42 |
July | 15291.14 | 27-JUL-07:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.14 |
August | 16843.54 | 08-AUG-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.25 |
September | 17165.91 | 05-SEP-07:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.12 |
October | 4505.25 | 18-OCT-14:40 | 1241.83 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 161.24 | 0.00 |
November | 3279.44 | 06-NOV-09:03 | 593.92 | 3512.81 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.99 |
December | 5034.66 | 12-DEC-18:23 | 2447.67 | 8899.12 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 712.57 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2226.79 | 0.00 | 468.37 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17165.91 | 2447.67 | 8899.12 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 867.14 | 712.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4187.21 | 03-JAN-19:33 | 1871.75 | 8899.12 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 617.19 |
February | 4739.62 | 23-FEB-20:03 | 791.89 | 4683.75 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.48 |
March | 3306.89 | 31-MAR-19:43 | 593.92 | 3512.81 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.54 |
April | 2955.35 | 14-APR-09:13 | 593.92 | 6674.34 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.51 |
May | 4421.22 | 20-MAY-16:00 | 1331.82 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 867.14 | 0.00 |
June | 8918.70 | 23-JUN-07:03 | 0.00 | 468.37 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.30 |
July | 14681.25 | 17-JUL-07:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.61 |
August | 16661.23 | 08-AUG-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.42 |
September | 16982.40 | 05-SEP-07:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.35 |
October | 4427.42 | 18-OCT-14:40 | 1241.83 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 161.24 | 0.00 |
November | 3403.22 | 25-NOV-10:53 | 593.92 | 6674.34 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 549.63 |
December | 4974.38 | 12-DEC-18:03 | 2447.67 | 8899.12 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 706.82 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2955.35 | 0.00 | 468.37 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16982.40 | 2447.67 | 8899.12 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 867.14 | 706.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1924.28 | 17-JAN-11:45 | 1547.79 | 4449.56 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 410.86 |
February | 3206.23 | 15-FEB-19:13 | 1403.81 | 6674.34 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.35 |
March | 3326.57 | 31-MAR-18:03 | 1403.81 | 6674.34 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.23 |
April | 2880.42 | 29-APR-10:23 | 3131.58 | 6674.34 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 463.74 |
May | 4180.46 | 20-MAY-16:00 | 1331.82 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 867.14 | 0.00 |
June | 6811.63 | 23-JUN-07:03 | 0.00 | 468.37 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.92 |
July | 14395.76 | 17-JUL-07:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.59 |
August | 16379.24 | 08-AUG-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.87 |
September | 16697.91 | 05-SEP-07:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.82 |
October | 4195.95 | 18-OCT-14:40 | 1241.83 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 161.24 | 0.00 |
November | 2454.60 | 06-NOV-11:30 | 773.90 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.01 |
December | 4060.07 | 21-DEC-19:42 | 1871.75 | 8899.12 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 555.10 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1924.28 | 0.00 | 468.37 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16697.91 | 3131.58 | 8899.12 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 867.14 | 555.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 488.42 | 14-JAN-12:00 | 1043.86 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.17 |
February | 1594.22 | 27-FEB-18:20 | 611.92 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.73 |
March | 2955.48 | 01-MAR-20:13 | 593.92 | 3512.81 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.56 |
April | 1509.86 | 10-APR-10:35 | 1547.79 | 4449.56 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.50 |
May | 3772.23 | 20-MAY-16:00 | 1331.82 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 912.60 | 0.00 |
June | 5303.91 | 23-JUN-14:10 | 1241.83 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1034.37 | 0.00 |
July | 14767.39 | 17-JUL-07:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.95 |
August | 15772.78 | 07-AUG-07:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.84 |
September | 17121.67 | 05-SEP-07:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.71 |
October | 3862.76 | 18-OCT-14:40 | 1241.83 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 170.90 | 0.00 |
November | 2311.32 | 14-NOV-19:25 | 935.88 | 4449.56 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.65 |
December | 2483.90 | 07-DEC-18:05 | 1223.84 | 4449.56 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 679.38 |
Annual Sum or Average | |||||||||||
Minimum of Months | 488.42 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17121.67 | 1547.79 | 4449.56 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1034.37 | 679.38 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.901040E+11 | 72788.89 | 25-JAN-19:00 | 0.165194E+12 | 299239.86 | 08-JAN-17:00 |
February | 0.802955E+11 | 70726.58 | 01-FEB-17:49 | 0.908550E+11 | 229715.51 | 05-FEB-17:00 |
March | 0.884095E+11 | 68740.71 | 02-MAR-18:30 | 0.697554E+11 | 208442.40 | 04-MAR-17:00 |
April | 0.831747E+11 | 65644.72 | 06-APR-18:00 | 0.248116E+11 | 102744.58 | 29-APR-07:10 |
May | 0.871297E+11 | 79345.08 | 20-MAY-15:20 | 0.156679E+11 | 101846.99 | 08-MAY-07:10 |
June | 0.911752E+11 | 83972.61 | 28-JUN-14:00 | 0.301501E+09 | 18311.81 | 16-JUN-11:20 |
July | 0.101802E+12 | 100151.97 | 17-JUL-13:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.100864E+12 | 93356.88 | 05-AUG-15:30 | 1976959.62 | 1846.72 | 18-AUG-07:10 |
September | 0.911913E+11 | 91921.27 | 02-SEP-14:50 | 0.174792E+10 | 30006.82 | 20-SEP-07:10 |
October | 0.883936E+11 | 75947.22 | 18-OCT-12:30 | 0.879564E+10 | 83891.67 | 10-OCT-08:09 |
November | 0.861831E+11 | 69387.57 | 18-NOV-16:00 | 0.473985E+11 | 184806.89 | 26-NOV-17:00 |
December | 0.898643E+11 | 71204.28 | 29-DEC-17:30 | 0.116388E+12 | 261255.86 | 31-DEC-17:00 |
Annual Sum or Average | 0.107859E+13 | 0.540917E+12 | ||||
Minimum of Months | 0.802955E+11 | 65644.72 | 0.00 | 0.00 | ||
Maximum of Months | 0.101802E+12 | 100151.97 | 0.165194E+12 | 299239.86 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.465742E+11 | 0.103816E+11 | 0.108325E+11 | 0.00 | 0.165505E+11 | 0.00 | 0.00 | 13619.61 | 0.00 | 0.00 | 0.00 | 0.576525E+10 | 0.00 |
February | 0.421675E+11 | 0.845267E+10 | 0.980803E+10 | 0.00 | 0.146291E+11 | 0.00 | 0.00 | 1755741.97 | 0.00 | 0.00 | 0.00 | 0.523643E+10 | 0.00 |
March | 0.472558E+11 | 0.806408E+10 | 0.110038E+11 | 0.00 | 0.162645E+11 | 0.00 | 0.00 | 446876.46 | 0.00 | 0.00 | 0.00 | 0.582082E+10 | 0.00 |
April | 0.451947E+11 | 0.649635E+10 | 0.105115E+11 | 0.00 | 0.153455E+11 | 0.00 | 0.00 | 0.112546E+09 | 0.00 | 0.00 | 0.00 | 0.551398E+10 | 0.00 |
May | 0.468973E+11 | 0.559968E+10 | 0.109147E+11 | 0.00 | 0.159836E+11 | 0.00 | 0.00 | 0.213179E+10 | 0.00 | 0.00 | 0.00 | 0.560256E+10 | 0.00 |
June | 0.456793E+11 | 0.489666E+10 | 0.106349E+11 | 0.00 | 0.155903E+11 | 0.00 | 0.00 | 0.906020E+10 | 0.00 | 0.00 | 0.00 | 0.531382E+10 | 0.00 |
July | 0.464483E+11 | 0.527024E+10 | 0.107982E+11 | 0.00 | 0.158642E+11 | 0.00 | 0.00 | 0.180589E+11 | 0.00 | 0.00 | 0.00 | 0.536222E+10 | 0.00 |
August | 0.472203E+11 | 0.619060E+10 | 0.109970E+11 | 0.00 | 0.161916E+11 | 0.00 | 0.00 | 0.148834E+11 | 0.00 | 0.00 | 0.00 | 0.538101E+10 | 0.00 |
September | 0.452303E+11 | 0.723220E+10 | 0.105184E+11 | 0.00 | 0.154566E+11 | 0.00 | 0.00 | 0.754303E+10 | 0.00 | 0.00 | 0.00 | 0.521076E+10 | 0.00 |
October | 0.465742E+11 | 0.881685E+10 | 0.108325E+11 | 0.00 | 0.158135E+11 | 0.00 | 0.00 | 0.902205E+09 | 0.00 | 0.00 | 0.00 | 0.545440E+10 | 0.00 |
November | 0.451236E+11 | 0.971466E+10 | 0.104978E+11 | 0.00 | 0.154450E+11 | 0.00 | 0.00 | 4889601.42 | 0.00 | 0.00 | 0.00 | 0.539707E+10 | 0.00 |
December | 0.464839E+11 | 0.107157E+11 | 0.108050E+11 | 0.00 | 0.161761E+11 | 0.00 | 0.00 | 59817.87 | 0.00 | 0.00 | 0.00 | 0.568362E+10 | 0.00 |
Annual Sum or Average | 0.550849E+12 | 0.918313E+11 | 0.128154E+12 | 0.189310E+12 | 0.00 | 0.526992E+11 | 0.657419E+11 | ||||||
Minimum of Months | 0.421675E+11 | 0.489666E+10 | 0.980803E+10 | 0.00 | 0.146291E+11 | 0.00 | 0.00 | 13619.61 | 0.00 | 0.00 | 0.00 | 0.521076E+10 | 0.00 |
Maximum of Months | 0.472558E+11 | 0.107157E+11 | 0.110038E+11 | 0.00 | 0.165505E+11 | 0.00 | 0.00 | 0.180589E+11 | 0.00 | 0.00 | 0.00 | 0.582082E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.165194E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.908550E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.697554E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.248116E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.156679E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.301501E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 1976959.62 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.174792E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.879564E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.473985E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.116388E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.540917E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.165194E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 34106.38 | 01-JAN-11:09 | 7048.42 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 12585.67 | 08-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 34106.38 | 01-FEB-10:09 | 7048.42 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 12211.52 | 05-FEB-17:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 34106.38 | 01-MAR-10:09 | 7048.42 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 12149.19 | 06-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 34106.38 | 01-APR-09:09 | 7048.42 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 11553.49 | 29-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 34106.38 | 01-MAY-09:09 | 7048.42 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 11520.57 | 08-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 34106.38 | 01-JUN-09:09 | 7048.42 | 01-JUN-20:10 | 8059.50 | 01-JUN-09:09 | 0.00 | 11303.40 | 22-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 34106.38 | 01-JUL-09:09 | 7048.42 | 01-JUL-20:30 | 8059.50 | 01-JUL-09:09 | 0.00 | 12265.83 | 17-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 34106.38 | 01-AUG-09:09 | 7048.42 | 01-AUG-19:00 | 8059.50 | 01-AUG-09:09 | 0.00 | 11910.38 | 06-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 34106.38 | 01-SEP-09:09 | 7048.42 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 11856.53 | 02-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 34106.38 | 01-OCT-10:09 | 7048.42 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 11486.47 | 10-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 34106.38 | 01-NOV-09:09 | 7048.42 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 11973.51 | 26-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 34106.38 | 01-DEC-10:09 | 7048.42 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 12395.47 | 31-DEC-12:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 34106.38 | 7048.42 | 8059.50 | 0.00 | 11303.40 | 0.00 | 0.00 | |||||
Maximum of Months | 34106.38 | 7048.42 | 8059.50 | 0.00 | 12585.67 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 6.70 | 15-JAN-21:00 | 0.00 | 0.00 | 0.00 | 11881.78 | 07-JAN-14:30 | 0.00 |
February | 377.88 | 26-FEB-18:10 | 0.00 | 0.00 | 0.00 | 11881.17 | 10-FEB-14:09 | 0.00 |
March | 57.62 | 29-MAR-22:10 | 0.00 | 0.00 | 0.00 | 11218.02 | 24-MAR-12:39 | 0.00 |
April | 7032.84 | 07-APR-13:00 | 0.00 | 0.00 | 0.00 | 9737.22 | 18-APR-13:39 | 0.00 |
May | 20363.58 | 20-MAY-15:00 | 0.00 | 0.00 | 0.00 | 9737.40 | 01-MAY-12:50 | 0.00 |
June | 25212.98 | 29-JUN-14:00 | 0.00 | 0.00 | 0.00 | 9714.20 | 28-JUN-12:09 | 0.00 |
July | 38755.30 | 17-JUL-16:10 | 0.00 | 0.00 | 0.00 | 9709.71 | 17-JUL-12:20 | 0.00 |
August | 34178.14 | 06-AUG-15:00 | 0.00 | 0.00 | 0.00 | 9706.03 | 21-AUG-12:30 | 0.00 |
September | 33155.82 | 02-SEP-14:00 | 0.00 | 0.00 | 0.00 | 9707.03 | 26-SEP-13:50 | 0.00 |
October | 16087.73 | 18-OCT-14:30 | 0.00 | 0.00 | 0.00 | 9718.58 | 24-OCT-12:09 | 0.00 |
November | 521.13 | 05-NOV-20:00 | 0.00 | 0.00 | 0.00 | 9649.41 | 12-NOV-12:20 | 0.00 |
December | 23.09 | 10-DEC-20:40 | 0.00 | 0.00 | 0.00 | 9746.38 | 29-DEC-13:30 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 0.00 | 0.00 | 0.00 | 9649.41 | 0.00 | ||
Maximum of Months | 38755.30 | 0.00 | 0.00 | 0.00 | 11881.78 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 72788.89 | 25-JAN-19:00 | 34106.38 | 8059.50 | 7048.42 | 0.00 | 11765.01 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 70726.58 | 01-FEB-17:49 | 34106.38 | 8059.50 | 7048.42 | 0.00 | 11812.41 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 68740.71 | 02-MAR-18:30 | 34106.38 | 8059.50 | 7048.42 | 0.00 | 11101.59 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 65644.72 | 06-APR-18:00 | 34106.38 | 8059.50 | 7048.42 | 0.00 | 10980.55 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 79345.08 | 20-MAY-15:20 | 34106.38 | 8059.50 | 0.00 | 0.00 | 10980.55 | 0.00 | 0.00 | 19134.16 | 0.00 |
June | 83972.61 | 28-JUN-14:00 | 34106.38 | 8059.50 | 0.00 | 0.00 | 10980.55 | 0.00 | 0.00 | 22779.46 | 0.00 |
July | 100151.97 | 17-JUL-13:39 | 34106.38 | 8059.50 | 0.00 | 0.00 | 12077.98 | 0.00 | 0.00 | 36937.89 | 0.00 |
August | 93356.88 | 05-AUG-15:30 | 34106.38 | 8059.50 | 0.00 | 0.00 | 11687.09 | 0.00 | 0.00 | 31949.18 | 0.00 |
September | 91921.27 | 02-SEP-14:50 | 34106.38 | 8059.50 | 0.00 | 0.00 | 11852.82 | 0.00 | 0.00 | 33087.69 | 0.00 |
October | 75947.22 | 18-OCT-12:30 | 34106.38 | 8059.50 | 0.00 | 0.00 | 10980.55 | 0.00 | 0.00 | 14012.38 | 0.00 |
November | 69387.57 | 18-NOV-16:00 | 34106.38 | 8059.50 | 7048.42 | 0.00 | 11056.75 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71204.28 | 29-DEC-17:30 | 34106.38 | 8059.50 | 7048.42 | 0.00 | 12291.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 65644.72 | 34106.38 | 8059.50 | 0.00 | 0.00 | 10980.55 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 100151.97 | 34106.38 | 8059.50 | 7048.42 | 0.00 | 12291.99 | 0.00 | 0.00 | 36937.89 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 299239.86 | 08-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 229715.51 | 05-FEB-17:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 208442.40 | 04-MAR-17:00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 102744.58 | 29-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 101846.99 | 08-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 18311.81 | 16-JUN-11:20 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 1846.72 | 18-AUG-07:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 30006.82 | 20-SEP-07:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 83891.67 | 10-OCT-08:09 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 184806.89 | 26-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 261255.86 | 31-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 299239.86 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 20.31 | 1.17 | 20.31 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.17 | 20.47 | 0.17 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.50 | 20.43 | 0.17 | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.67 | 20.48 | 0.17 | 20.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7.00 | 20.39 | 1.67 | 20.32 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 20.48 | 1.17 | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 20.42 | 0.17 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.17 | 20.43 | 0.17 | 20.54 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 20.50 | 0.17 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 20.44 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.17 | 20.37 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 20.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 20.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.83 | 20.35 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 20.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.83 | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 20.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 20.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.83 | 20.27 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 20.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.83 | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 20.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.83 | 20.25 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 20.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.83 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 20.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 20.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4.00 | 20.25 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 19.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.17 | 20.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 20.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.17 | 20.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5.33 | 19.93 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.67 | 16.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4.67 | 18.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3.83 | 17.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.50 | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.67 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 20.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5.17 | 18.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.33 | 17.41 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 15.67 | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.05 | 330.67 | 21.02 | 330.67 | 21.02 |
February | 448.00 | 21.18 | 181.33 | 20.98 | 181.33 | 20.98 |
March | 496.00 | 21.11 | 142.33 | 20.99 | 142.33 | 20.99 |
April | 475.33 | 21.76 | 38.83 | 20.91 | 38.83 | 20.91 |
May | 354.83 | 22.00 | 38.67 | 22.45 | 19.50 | 21.03 |
June | 91.67 | 22.99 | 148.67 | 23.89 | 0.00 | 0.00 |
July | 14.83 | 23.64 | 292.33 | 23.89 | 0.50 | 23.89 |
August | 42.33 | 23.16 | 190.83 | 23.89 | 0.00 | 0.00 |
September | 163.67 | 22.42 | 153.17 | 23.89 | 5.33 | 23.81 |
October | 360.33 | 22.18 | 4.50 | 21.14 | 4.50 | 21.14 |
November | 477.67 | 21.50 | 79.50 | 21.11 | 79.50 | 21.11 |
December | 496.00 | 21.06 | 251.83 | 21.00 | 251.83 | 21.00 |
Annual Sum or Average | 3916.67 | 21.54 | 1852.67 | 22.26 | 1054.33 | 21.02 |
Minimum of Months | 14.83 | 21.05 | 4.50 | 20.91 | 0.00 | 0.00 |
Maximum of Months | 496.00 | 23.64 | 330.67 | 23.89 | 330.67 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.42 | 236.83 | 21.12 | 236.83 | 21.12 |
February | 445.83 | 21.85 | 114.67 | 21.15 | 114.67 | 21.15 |
March | 496.00 | 21.91 | 51.33 | 21.18 | 51.33 | 21.18 |
April | 441.33 | 22.74 | 2.50 | 21.18 | 2.50 | 21.18 |
May | 310.00 | 22.77 | 20.67 | 23.74 | 1.17 | 21.36 |
June | 61.17 | 23.38 | 154.17 | 23.87 | 0.00 | 0.00 |
July | 14.00 | 23.40 | 285.33 | 23.87 | 0.00 | 0.00 |
August | 34.33 | 23.40 | 191.00 | 23.88 | 0.00 | 0.00 |
September | 113.33 | 23.08 | 159.33 | 23.87 | 5.50 | 23.89 |
October | 272.67 | 22.96 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 452.83 | 22.38 | 23.00 | 21.15 | 23.00 | 21.15 |
December | 496.00 | 21.58 | 115.50 | 21.13 | 115.50 | 21.13 |
Annual Sum or Average | 3633.50 | 22.18 | 1354.33 | 22.77 | 550.50 | 21.17 |
Minimum of Months | 14.00 | 21.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.00 | 23.40 | 285.33 | 23.88 | 236.83 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.12 | 217.67 | 21.11 | 217.67 | 21.11 |
February | 336.00 | 21.43 | 114.50 | 21.11 | 114.50 | 21.11 |
March | 379.00 | 21.36 | 69.00 | 21.11 | 69.00 | 21.11 |
April | 334.33 | 22.21 | 7.50 | 21.11 | 7.50 | 21.11 |
May | 241.17 | 22.31 | 28.33 | 23.91 | 5.00 | 21.11 |
June | 38.83 | 23.10 | 141.17 | 24.17 | 0.00 | 0.00 |
July | 5.50 | 24.60 | 251.83 | 24.16 | 1.00 | 28.49 |
August | 19.17 | 23.64 | 181.50 | 24.21 | 0.83 | 28.98 |
September | 91.50 | 22.78 | 132.67 | 24.13 | 7.00 | 24.78 |
October | 207.83 | 22.40 | 1.83 | 23.95 | 0.67 | 21.11 |
November | 345.83 | 21.87 | 38.67 | 21.11 | 38.67 | 21.11 |
December | 369.00 | 21.15 | 143.33 | 21.11 | 143.33 | 21.11 |
Annual Sum or Average | 2739.17 | 21.73 | 1328.00 | 22.80 | 605.17 | 21.18 |
Minimum of Months | 5.50 | 21.12 | 1.83 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 379.00 | 24.60 | 251.83 | 24.21 | 217.67 | 28.98 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 233.33 | 21.11 | 233.33 | 21.11 |
February | 336.00 | 21.40 | 122.17 | 21.11 | 122.17 | 21.11 |
March | 379.00 | 21.31 | 80.33 | 21.11 | 80.33 | 21.11 |
April | 345.83 | 22.18 | 9.83 | 21.11 | 9.83 | 21.11 |
May | 248.00 | 22.27 | 29.83 | 23.60 | 7.83 | 21.11 |
June | 40.50 | 23.10 | 140.50 | 24.17 | 0.00 | 0.00 |
July | 5.67 | 24.71 | 252.33 | 24.16 | 1.17 | 28.52 |
August | 20.00 | 23.63 | 182.33 | 24.21 | 0.83 | 29.00 |
September | 95.50 | 22.75 | 131.33 | 24.13 | 6.83 | 24.81 |
October | 216.50 | 22.37 | 3.00 | 22.83 | 1.83 | 21.11 |
November | 349.33 | 21.80 | 48.67 | 21.11 | 48.67 | 21.11 |
December | 369.00 | 21.13 | 162.83 | 21.11 | 162.83 | 21.11 |
Annual Sum or Average | 2776.33 | 21.71 | 1396.50 | 22.71 | 675.67 | 21.17 |
Minimum of Months | 5.67 | 21.11 | 3.00 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 379.00 | 24.71 | 252.33 | 24.21 | 233.33 | 29.00 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 251.17 | 21.11 | 251.17 | 21.11 |
February | 336.00 | 21.35 | 134.83 | 21.11 | 134.83 | 21.11 |
March | 379.00 | 21.25 | 99.50 | 21.11 | 99.50 | 21.11 |
April | 356.83 | 22.08 | 16.00 | 21.11 | 16.00 | 21.11 |
May | 261.83 | 22.21 | 31.50 | 23.21 | 11.50 | 21.11 |
June | 48.33 | 23.10 | 133.33 | 24.16 | 0.00 | 0.00 |
July | 6.67 | 24.32 | 241.33 | 24.16 | 0.83 | 28.60 |
August | 26.50 | 23.56 | 170.67 | 24.21 | 0.83 | 28.94 |
September | 106.17 | 22.66 | 123.50 | 24.13 | 6.83 | 24.69 |
October | 242.17 | 22.35 | 3.17 | 22.03 | 2.50 | 21.11 |
November | 356.67 | 21.69 | 61.67 | 21.11 | 61.67 | 21.11 |
December | 369.00 | 21.12 | 185.83 | 21.11 | 185.83 | 21.11 |
Annual Sum or Average | 2860.17 | 21.68 | 1452.50 | 22.57 | 771.50 | 21.16 |
Minimum of Months | 6.67 | 21.11 | 3.17 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 379.00 | 24.32 | 251.17 | 24.21 | 251.17 | 28.94 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 296.17 | 21.11 | 296.17 | 21.11 |
February | 308.00 | 21.20 | 184.00 | 21.11 | 184.00 | 21.11 |
March | 348.00 | 21.12 | 139.17 | 21.11 | 139.17 | 21.11 |
April | 330.00 | 21.62 | 37.33 | 21.11 | 37.33 | 21.11 |
May | 278.67 | 21.96 | 29.50 | 21.70 | 23.83 | 21.11 |
June | 91.67 | 23.12 | 84.00 | 23.97 | 0.00 | 0.00 |
July | 9.83 | 23.66 | 175.00 | 24.00 | 0.33 | 28.61 |
August | 32.33 | 23.01 | 111.17 | 24.00 | 0.50 | 28.68 |
September | 147.50 | 22.48 | 93.50 | 24.03 | 6.33 | 24.24 |
October | 296.17 | 22.14 | 4.33 | 21.11 | 4.33 | 21.11 |
November | 330.00 | 21.27 | 98.33 | 21.11 | 98.33 | 21.11 |
December | 338.00 | 21.11 | 239.67 | 21.11 | 239.67 | 21.11 |
Annual Sum or Average | 2850.17 | 21.55 | 1492.17 | 22.02 | 1030.00 | 21.14 |
Minimum of Months | 9.83 | 21.11 | 4.33 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.66 | 296.17 | 24.03 | 296.17 | 28.68 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 298.67 | 21.11 | 298.67 | 21.11 |
February | 308.00 | 21.24 | 190.50 | 21.11 | 190.50 | 21.11 |
March | 348.00 | 21.14 | 147.17 | 21.11 | 147.17 | 21.11 |
April | 330.00 | 21.78 | 42.83 | 21.11 | 42.83 | 21.11 |
May | 283.50 | 22.17 | 31.00 | 21.51 | 27.50 | 21.11 |
June | 94.33 | 23.36 | 68.33 | 24.02 | 0.00 | 0.00 |
July | 13.00 | 23.97 | 145.17 | 24.04 | 0.67 | 28.39 |
August | 36.17 | 23.37 | 86.67 | 24.05 | 0.50 | 28.79 |
September | 146.83 | 22.73 | 81.83 | 24.07 | 7.17 | 24.21 |
October | 304.00 | 22.44 | 5.33 | 21.11 | 5.33 | 21.11 |
November | 330.00 | 21.38 | 104.67 | 21.11 | 104.67 | 21.11 |
December | 338.00 | 21.11 | 244.83 | 21.11 | 244.83 | 21.11 |
Annual Sum or Average | 2871.83 | 21.68 | 1447.00 | 21.89 | 1069.83 | 21.14 |
Minimum of Months | 13.00 | 21.11 | 5.33 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.97 | 298.67 | 24.07 | 298.67 | 28.79 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 302.17 | 21.11 | 302.17 | 21.11 |
February | 308.00 | 21.23 | 202.50 | 21.11 | 202.50 | 21.11 |
March | 348.00 | 21.14 | 155.33 | 21.11 | 155.33 | 21.11 |
April | 330.00 | 21.75 | 47.33 | 21.11 | 47.33 | 21.11 |
May | 292.00 | 22.19 | 33.67 | 21.37 | 31.33 | 21.11 |
June | 101.67 | 23.37 | 64.17 | 24.03 | 0.00 | 0.00 |
July | 14.00 | 23.90 | 139.50 | 24.05 | 0.50 | 28.50 |
August | 38.50 | 23.38 | 82.83 | 24.06 | 0.50 | 28.76 |
September | 149.17 | 22.72 | 79.83 | 24.07 | 7.17 | 24.21 |
October | 307.67 | 22.43 | 6.17 | 21.11 | 6.17 | 21.11 |
November | 330.00 | 21.36 | 109.67 | 21.11 | 109.67 | 21.11 |
December | 338.00 | 21.11 | 249.17 | 21.11 | 249.17 | 21.11 |
Annual Sum or Average | 2897.00 | 21.68 | 1472.33 | 21.85 | 1111.83 | 21.14 |
Minimum of Months | 14.00 | 21.11 | 6.17 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.90 | 302.17 | 24.07 | 302.17 | 28.76 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 312.33 | 21.11 | 312.33 | 21.11 |
February | 308.00 | 21.20 | 228.67 | 21.11 | 228.67 | 21.11 |
March | 348.00 | 21.12 | 184.50 | 21.11 | 184.50 | 21.11 |
April | 330.00 | 21.65 | 66.50 | 21.11 | 66.50 | 21.11 |
May | 306.17 | 22.17 | 43.83 | 21.20 | 43.00 | 21.11 |
June | 118.17 | 23.35 | 54.83 | 24.03 | 0.00 | 0.00 |
July | 18.50 | 23.80 | 128.00 | 24.05 | 0.33 | 28.66 |
August | 44.50 | 23.36 | 73.83 | 24.07 | 0.50 | 28.72 |
September | 155.50 | 22.66 | 77.00 | 24.07 | 7.17 | 24.04 |
October | 320.33 | 22.38 | 7.67 | 21.11 | 7.67 | 21.11 |
November | 330.00 | 21.31 | 124.67 | 21.11 | 124.67 | 21.11 |
December | 338.00 | 21.11 | 267.33 | 21.11 | 267.33 | 21.11 |
Annual Sum or Average | 2957.17 | 21.67 | 1569.17 | 21.74 | 1242.67 | 21.13 |
Minimum of Months | 18.50 | 21.11 | 7.67 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.80 | 312.33 | 24.07 | 312.33 | 28.72 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 332.50 | 21.11 | 332.50 | 21.11 |
February | 308.00 | 21.16 | 275.83 | 21.11 | 275.83 | 21.11 |
March | 348.00 | 21.11 | 285.33 | 21.11 | 285.33 | 21.11 |
April | 330.00 | 21.49 | 161.50 | 21.11 | 161.50 | 21.11 |
May | 327.33 | 22.10 | 85.67 | 21.15 | 85.00 | 21.11 |
June | 158.17 | 23.23 | 45.17 | 24.02 | 0.00 | 0.00 |
July | 35.50 | 23.68 | 105.17 | 24.08 | 0.33 | 28.66 |
August | 66.17 | 23.32 | 65.00 | 24.08 | 0.50 | 28.76 |
September | 172.67 | 22.59 | 74.00 | 24.00 | 9.17 | 23.53 |
October | 333.00 | 22.23 | 21.17 | 21.11 | 21.17 | 21.11 |
November | 330.00 | 21.23 | 173.00 | 21.11 | 173.00 | 21.11 |
December | 338.00 | 21.11 | 313.83 | 21.11 | 313.83 | 21.11 |
Annual Sum or Average | 3086.83 | 21.66 | 1938.17 | 21.55 | 1658.17 | 21.13 |
Minimum of Months | 35.50 | 21.11 | 21.17 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.68 | 332.50 | 24.08 | 332.50 | 28.76 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.03680 | 10.62836 | -0.6433 | 14.25331 |
February | 448.00000 | 21.17892 | 13.83231 | -0.5333 | 11.73795 |
March | 496.00000 | 21.09808 | 15.58325 | -0.5164 | 10.93719 |
April | 480.00000 | 21.77975 | 20.56916 | -0.2945 | 8.07713 |
May | 496.00000 | 22.53421 | 24.09329 | -1.0967 | 33.61281 |
June | 480.00000 | 23.71522 | 31.02625 | -0.5821 | 13.05730 |
July | 496.00000 | 23.88405 | 33.71438 | -0.4535 | 9.49070 |
August | 496.00000 | 23.82937 | 30.31658 | -0.5012 | 10.68730 |
September | 480.00000 | 23.38916 | 31.26375 | -0.6720 | 16.99790 |
October | 496.00000 | 22.64560 | 22.71307 | -0.0169 | 6.56732 |
November | 480.00000 | 21.50463 | 16.96159 | -0.3735 | 8.89256 |
December | 496.00000 | 21.05144 | 12.91902 | -0.5775 | 12.39063 |
Annual Sum or Average | 5840.00000 | 22.30997 | 22.00256 | -0.5221 | 13.08363 |
Minimum of Months | 448.00000 | 21.03680 | 10.62836 | -1.0967 | 6.56732 |
Maximum of Months | 496.00000 | 23.88405 | 33.71438 | -0.0169 | 33.61281 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.39831 | 11.68141 | -0.5147 | 11.40072 |
February | 448.00000 | 21.84179 | 14.33814 | -0.3575 | 9.08294 |
March | 496.00000 | 21.89102 | 16.24228 | -0.3149 | 7.97728 |
April | 480.00000 | 22.81817 | 20.03547 | -0.0537 | 6.34702 |
May | 496.00000 | 23.15990 | 23.62834 | -0.8850 | 24.06005 |
June | 480.00000 | 23.79107 | 30.88177 | -0.5387 | 11.50835 |
July | 496.00000 | 23.83496 | 33.85549 | -0.4578 | 9.58117 |
August | 496.00000 | 23.82227 | 30.31596 | -0.4935 | 10.33666 |
September | 480.00000 | 23.67177 | 30.85364 | -0.5787 | 13.14159 |
October | 496.00000 | 23.36798 | 22.02059 | 0.14016 | 6.31494 |
November | 480.00000 | 22.44521 | 16.92254 | -0.1595 | 7.12750 |
December | 496.00000 | 21.55889 | 13.87969 | -0.4337 | 9.64343 |
Annual Sum or Average | 5840.00000 | 22.80381 | 22.08933 | -0.3881 | 10.56657 |
Minimum of Months | 448.00000 | 21.39831 | 11.68141 | -0.8850 | 6.31494 |
Maximum of Months | 496.00000 | 23.83496 | 33.85549 | 0.14016 | 24.06005 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11774 | 10.29789 | -0.5954 | 12.75520 |
February | 336.00000 | 21.43585 | 13.09059 | -0.4546 | 10.33508 |
March | 379.00000 | 21.36569 | 15.22745 | -0.4252 | 9.28579 |
April | 360.00000 | 22.33391 | 19.50840 | -0.1540 | 7.01093 |
May | 375.00000 | 22.90896 | 22.99854 | -0.9682 | 28.17062 |
June | 366.00000 | 23.90724 | 30.52324 | -0.5114 | 11.23060 |
July | 369.00000 | 24.03940 | 33.39797 | -0.4036 | 8.85592 |
August | 379.00000 | 23.99233 | 29.91005 | -0.4477 | 9.66501 |
September | 360.00000 | 23.66194 | 30.79959 | -0.5840 | 14.07871 |
October | 371.00000 | 23.08061 | 21.84541 | 0.08175 | 6.51730 |
November | 360.00000 | 21.96058 | 16.33509 | -0.2613 | 7.99205 |
December | 369.00000 | 21.14754 | 12.74779 | -0.5313 | 11.19420 |
Annual Sum or Average | 4395.00000 | 22.58702 | 21.44391 | -0.4389 | 11.45559 |
Minimum of Months | 336.00000 | 21.11774 | 10.29789 | -0.9682 | 6.51730 |
Maximum of Months | 379.00000 | 24.03940 | 33.39797 | 0.08175 | 28.17062 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11406 | 10.30182 | -0.6089 | 13.08718 |
February | 336.00000 | 21.39765 | 13.12191 | -0.4744 | 10.63005 |
March | 379.00000 | 21.31458 | 15.27280 | -0.4472 | 9.62719 |
April | 360.00000 | 22.24436 | 19.61652 | -0.1829 | 7.18216 |
May | 375.00000 | 22.85607 | 23.06163 | -0.9951 | 29.34032 |
June | 366.00000 | 23.90221 | 30.53304 | -0.5152 | 11.33966 |
July | 369.00000 | 24.03904 | 33.39785 | -0.4031 | 8.85264 |
August | 379.00000 | 23.99110 | 29.91323 | -0.4480 | 9.67854 |
September | 360.00000 | 23.63815 | 30.84067 | -0.5948 | 14.51475 |
October | 371.00000 | 23.02413 | 21.92163 | 0.06296 | 6.54672 |
November | 360.00000 | 21.87235 | 16.43273 | -0.2911 | 8.23659 |
December | 369.00000 | 21.13455 | 12.76257 | -0.5462 | 11.51616 |
Annual Sum or Average | 4395.00000 | 22.55194 | 21.48490 | -0.4546 | 11.74467 |
Minimum of Months | 336.00000 | 21.11406 | 10.30182 | -0.9951 | 6.54672 |
Maximum of Months | 379.00000 | 24.03904 | 33.39785 | 0.06296 | 29.34032 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11097 | 10.30651 | -0.6256 | 13.52041 |
February | 336.00000 | 21.34733 | 13.16610 | -0.5005 | 11.04588 |
March | 379.00000 | 21.25223 | 15.33173 | -0.4751 | 10.09286 |
April | 360.00000 | 22.09145 | 19.80370 | -0.2307 | 7.48402 |
May | 375.00000 | 22.74906 | 23.20157 | -1.0468 | 31.50055 |
June | 366.00000 | 23.88108 | 30.57901 | -0.5329 | 11.81332 |
July | 369.00000 | 24.03390 | 33.41454 | -0.4130 | 9.01411 |
August | 379.00000 | 23.97853 | 29.93929 | -0.4608 | 9.95194 |
September | 360.00000 | 23.57886 | 30.96592 | -0.6248 | 15.58102 |
October | 371.00000 | 22.90141 | 22.09337 | 0.02484 | 6.56740 |
November | 360.00000 | 21.71143 | 16.62160 | -0.3403 | 8.62152 |
December | 369.00000 | 21.12206 | 12.77810 | -0.5638 | 11.91759 |
Annual Sum or Average | 4395.00000 | 22.48808 | 21.57004 | -0.4833 | 12.29313 |
Minimum of Months | 336.00000 | 21.11097 | 10.30651 | -1.0468 | 6.56740 |
Maximum of Months | 379.00000 | 24.03390 | 33.41454 | 0.02484 | 31.50055 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10981 | 11.07603 | -0.6786 | 14.96568 |
February | 308.00000 | 21.19682 | 14.04822 | -0.5754 | 12.41684 |
March | 348.00000 | 21.12016 | 16.29603 | -0.5417 | 11.34938 |
April | 330.00000 | 21.61659 | 21.14896 | -0.3589 | 8.60897 |
May | 344.00000 | 22.33058 | 24.48684 | -1.2094 | 38.51855 |
June | 336.00000 | 23.69307 | 31.36090 | -0.6151 | 14.02357 |
July | 338.00000 | 23.92235 | 33.85331 | -0.4657 | 9.82922 |
August | 348.00000 | 23.83180 | 30.79405 | -0.5220 | 11.30663 |
September | 330.00000 | 23.28826 | 32.16528 | -0.7327 | 19.35743 |
October | 340.00000 | 22.37262 | 23.61184 | -0.1027 | 6.76776 |
November | 330.00000 | 21.27231 | 17.96380 | -0.4645 | 10.04538 |
December | 338.00000 | 21.10958 | 13.59330 | -0.6146 | 13.15995 |
Annual Sum or Average | 4030.00000 | 22.24759 | 22.58747 | -0.5743 | 14.23687 |
Minimum of Months | 308.00000 | 21.10958 | 11.07603 | -1.2094 | 6.76776 |
Maximum of Months | 348.00000 | 23.92235 | 33.85331 | -0.1027 | 38.51855 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10974 | 11.01619 | -0.6773 | 14.90361 |
February | 308.00000 | 21.23842 | 13.94928 | -0.5728 | 12.41212 |
March | 348.00000 | 21.14348 | 16.20699 | -0.5459 | 11.45846 |
April | 330.00000 | 21.77483 | 20.86663 | -0.3440 | 8.53824 |
May | 344.00000 | 22.48545 | 24.12451 | -1.1900 | 37.59159 |
June | 336.00000 | 23.76604 | 31.22979 | -0.6183 | 13.93342 |
July | 338.00000 | 23.93774 | 33.93481 | -0.4862 | 10.23760 |
August | 348.00000 | 23.86478 | 30.64591 | -0.5386 | 11.55715 |
September | 330.00000 | 23.40696 | 31.95633 | -0.7244 | 18.81491 |
October | 340.00000 | 22.59582 | 23.17714 | -0.0757 | 6.73011 |
November | 330.00000 | 21.38183 | 17.76206 | -0.4549 | 9.99942 |
December | 338.00000 | 21.10973 | 13.52943 | -0.6170 | 13.20451 |
Annual Sum or Average | 4030.00000 | 22.32670 | 22.42058 | -0.5714 | 14.15651 |
Minimum of Months | 308.00000 | 21.10973 | 11.01619 | -1.1900 | 6.73011 |
Maximum of Months | 348.00000 | 23.93774 | 33.93481 | -0.0757 | 37.59159 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10973 | 11.01647 | -0.6813 | 15.01455 |
February | 308.00000 | 21.22911 | 13.95816 | -0.5796 | 12.55344 |
March | 348.00000 | 21.13792 | 16.21258 | -0.5526 | 11.60537 |
April | 330.00000 | 21.74302 | 20.90846 | -0.3561 | 8.69086 |
May | 344.00000 | 22.45913 | 24.16908 | -1.2049 | 38.25082 |
June | 336.00000 | 23.75782 | 31.25184 | -0.6265 | 14.17103 |
July | 338.00000 | 23.93623 | 33.94156 | -0.4913 | 10.34414 |
August | 348.00000 | 23.86176 | 30.65380 | -0.5440 | 11.69148 |
September | 330.00000 | 23.39395 | 31.98719 | -0.7325 | 19.09918 |
October | 340.00000 | 22.57086 | 23.21538 | -0.0840 | 6.76092 |
November | 330.00000 | 21.36304 | 17.78604 | -0.4631 | 10.13447 |
December | 338.00000 | 21.10993 | 13.52961 | -0.6219 | 13.32738 |
Annual Sum or Average | 4030.00000 | 22.31490 | 22.43981 | -0.5791 | 14.34571 |
Minimum of Months | 308.00000 | 21.10973 | 11.01647 | -1.2049 | 6.76092 |
Maximum of Months | 348.00000 | 23.93623 | 33.94156 | -0.0840 | 38.25082 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10984 | 11.01668 | -0.6950 | 15.40625 |
February | 308.00000 | 21.20335 | 13.98181 | -0.6009 | 13.01975 |
March | 348.00000 | 21.12457 | 16.22586 | -0.5720 | 12.05467 |
April | 330.00000 | 21.64506 | 21.03487 | -0.3933 | 9.18726 |
May | 344.00000 | 22.36956 | 24.31923 | -1.2521 | 40.38014 |
June | 336.00000 | 23.72015 | 31.33193 | -0.6520 | 14.99162 |
July | 338.00000 | 23.93101 | 33.95680 | -0.5005 | 10.55269 |
August | 348.00000 | 23.84894 | 30.67954 | -0.5557 | 12.03435 |
September | 330.00000 | 23.34476 | 32.08987 | -0.7570 | 20.03862 |
October | 340.00000 | 22.46668 | 23.36984 | -0.1150 | 6.87717 |
November | 330.00000 | 21.30977 | 17.85422 | -0.4863 | 10.52794 |
December | 338.00000 | 21.10991 | 13.53017 | -0.6367 | 13.72255 |
Annual Sum or Average | 4030.00000 | 22.27425 | 22.50320 | -0.6023 | 14.94322 |
Minimum of Months | 308.00000 | 21.10984 | 11.01668 | -1.2521 | 6.87717 |
Maximum of Months | 348.00000 | 23.93101 | 33.95680 | -0.1150 | 40.38014 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10994 | 10.90859 | -0.7564 | 17.31381 |
February | 308.00000 | 21.16432 | 13.92402 | -0.6728 | 14.90222 |
March | 348.00000 | 21.11133 | 16.09239 | -0.6413 | 13.84945 |
April | 330.00000 | 21.48419 | 21.10641 | -0.4882 | 10.82006 |
May | 344.00000 | 22.18615 | 24.60376 | -1.3729 | 45.98465 |
June | 336.00000 | 23.59292 | 31.56468 | -0.7309 | 17.75413 |
July | 338.00000 | 23.91149 | 34.00052 | -0.5225 | 11.13442 |
August | 348.00000 | 23.80714 | 30.70393 | -0.5855 | 13.05785 |
September | 330.00000 | 23.23568 | 32.19783 | -0.8158 | 22.44890 |
October | 340.00000 | 22.26260 | 23.54433 | -0.1851 | 7.34724 |
November | 330.00000 | 21.23049 | 17.86592 | -0.5465 | 11.77518 |
December | 338.00000 | 21.10983 | 13.44420 | -0.6958 | 15.41404 |
Annual Sum or Average | 4030.00000 | 22.19280 | 22.55077 | -0.6686 | 16.86363 |
Minimum of Months | 308.00000 | 21.10983 | 10.90859 | -1.3729 | 7.34724 |
Maximum of Months | 348.00000 | 23.91149 | 34.00052 | -0.1851 | 45.98465 |
Report: DXReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 1038.41 | 293.52 | 2.33 | 1038.41 | 0.00 | 0.00 | 0.00 | 27-FEB-15:30 | 0.00 | 01-FEB-00:05 | 0.23 | 27-FEB-15:30 | 0.23 | 27-FEB-15:30 | 0.00 | 01-FEB-00:05 | 0.06 | 27-FEB-15:30 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 78136340.39 | 21250830.97 | 24.39 | 78136340.39 | 0.00 | 0.00 | 0.36 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 4645.54 | 07-APR-14:00 | 4645.54 | 07-APR-14:00 | 0.00 | 07-APR-16:50 | 1243.58 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.184004E+10 | 0.474821E+09 | 135.95 | 0.182484E+10 | 15201745.63 | 0.00 | 0.90 | 20-MAY-16:10 | 0.00 | 01-MAY-00:10 | 13607.91 | 20-MAY-16:10 | 13607.91 | 20-MAY-16:10 | 352.57 | 20-MAY-11:00 | 3540.97 | 20-MAY-16:10 | 0.00 | 01-MAY-00:10 |
June | 0.732350E+10 | 0.185879E+10 | 324.62 | 0.694958E+10 | 0.373928E+09 | 0.00 | 1.00 | 29-JUN-12:40 | 0.00 | 01-JUN-00:10 | 24970.70 | 22-JUN-07:03 | 18555.37 | 22-JUN-07:03 | 6415.32 | 22-JUN-07:03 | 5319.96 | 22-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.144701E+11 | 0.371925E+10 | 438.67 | 0.140201E+11 | 0.450014E+09 | 0.00 | 1.00 | 16-JUL-07:02 | 0.00 | 01-JUL-00:03 | 34614.82 | 19-JUL-07:02 | 32512.89 | 18-JUL-07:02 | 11194.76 | 19-JUL-07:02 | 7363.24 | 19-JUL-07:02 | 0.00 | 01-JUL-00:03 |
August | 0.118450E+11 | 0.304777E+10 | 411.97 | 0.117409E+11 | 0.104039E+09 | 0.00 | 1.00 | 06-AUG-07:02 | 0.00 | 01-AUG-00:10 | 31894.10 | 10-AUG-07:02 | 31894.10 | 10-AUG-07:02 | 4910.99 | 01-AUG-07:02 | 6942.66 | 07-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.658170E+10 | 0.166068E+10 | 264.93 | 0.618798E+10 | 0.393724E+09 | 0.00 | 1.00 | 04-SEP-07:02 | 0.00 | 01-SEP-00:10 | 32822.04 | 07-SEP-07:02 | 30815.06 | 04-SEP-07:02 | 12011.95 | 07-SEP-07:02 | 6987.13 | 07-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.796668E+09 | 0.203457E+09 | 94.69 | 0.796668E+09 | 41.22 | 0.00 | 0.80 | 18-OCT-14:00 | 0.00 | 01-OCT-00:05 | 11555.49 | 18-OCT-14:00 | 11555.49 | 18-OCT-14:00 | 0.02 | 13-OCT-17:10 | 2816.01 | 18-OCT-14:00 | 0.00 | 01-OCT-00:05 |
November | 1743.16 | 492.73 | 4.67 | 1743.16 | 0.00 | 0.00 | 0.00 | 04-NOV-17:10 | 0.00 | 01-NOV-00:10 | 0.27 | 04-NOV-17:10 | 0.27 | 04-NOV-17:10 | 0.00 | 04-NOV-17:10 | 0.08 | 04-NOV-17:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.429351E+11 | 0.109860E+11 | 1702.22 | 0.415982E+11 | 0.133691E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.144701E+11 | 0.371925E+10 | 438.67 | 0.140201E+11 | 0.450014E+09 | 0.00 | 1.00 | 0.00 | 34614.82 | 32512.89 | 12011.95 | 7363.24 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 48576.06 | 13619.61 | 0.83 | 48576.06 | 0.00 | 0.00 | 0.00 | 15-JAN-22:00 | 0.00 | 01-JAN-00:10 | 23.90 | 15-JAN-22:00 | 23.90 | 15-JAN-22:00 | 0.00 | 15-JAN-21:40 | 6.70 | 15-JAN-22:00 | 0.00 | 01-JAN-00:10 |
February | 6450077.04 | 1749757.47 | 14.08 | 6450077.04 | 0.00 | 0.00 | 0.23 | 26-FEB-18:10 | 0.00 | 01-FEB-00:05 | 1429.37 | 26-FEB-18:10 | 1429.37 | 26-FEB-18:10 | 0.00 | 28-FEB-22:50 | 377.88 | 26-FEB-18:10 | 0.00 | 01-FEB-00:05 |
March | 1601843.59 | 446876.46 | 5.00 | 1601843.59 | 0.00 | 0.00 | 0.04 | 29-MAR-22:10 | 0.00 | 01-MAR-00:10 | 207.18 | 29-MAR-22:10 | 207.18 | 29-MAR-22:10 | 0.00 | 12-MAR-21:40 | 57.62 | 29-MAR-22:10 | 0.00 | 01-MAR-00:10 |
April | 0.126946E+09 | 28508756.07 | 61.73 | 0.126946E+09 | 0.00 | 0.00 | 1.00 | 06-APR-20:02 | 0.00 | 01-APR-00:05 | 17377.73 | 16-APR-17:07 | 17377.73 | 16-APR-17:07 | 0.00 | 07-APR-14:00 | 3394.68 | 06-APR-20:02 | 0.00 | 01-APR-00:05 |
May | 0.148118E+10 | 0.318763E+09 | 147.92 | 0.147253E+10 | 8646729.01 | 0.00 | 1.00 | 12-MAY-20:11 | 0.00 | 01-MAY-00:10 | 17713.85 | 20-MAY-18:17 | 17713.85 | 20-MAY-18:17 | 3307.81 | 20-MAY-21:40 | 3642.96 | 20-MAY-18:17 | 0.00 | 01-MAY-00:10 |
June | 0.498648E+10 | 0.107891E+10 | 300.69 | 0.479691E+10 | 0.189570E+09 | 0.00 | 1.00 | 03-JUN-18:01 | 0.00 | 01-JUN-00:10 | 18542.91 | 21-JUN-20:02 | 17679.07 | 25-JUN-17:40 | 5959.00 | 21-JUN-23:00 | 3743.22 | 18-JUN-19:11 | 0.00 | 01-JUN-00:10 |
July | 0.918186E+10 | 0.203500E+10 | 381.07 | 0.895444E+10 | 0.227417E+09 | 0.00 | 1.00 | 01-JUL-18:02 | 0.00 | 01-JUL-00:03 | 19096.60 | 18-JUL-21:58 | 17919.25 | 18-JUL-07:02 | 8161.28 | 18-JUL-21:58 | 3735.55 | 18-JUL-20:02 | 0.00 | 01-JUL-00:03 |
August | 0.753637E+10 | 0.166999E+10 | 357.07 | 0.749499E+10 | 41380515.05 | 0.00 | 1.00 | 02-AUG-21:22 | 0.00 | 01-AUG-00:10 | 17951.98 | 08-AUG-22:54 | 17621.85 | 07-AUG-22:01 | 3280.85 | 01-AUG-07:02 | 3665.50 | 08-AUG-22:01 | 0.00 | 01-AUG-00:10 |
September | 0.407223E+10 | 0.887977E+09 | 242.02 | 0.388314E+10 | 0.189096E+09 | 0.00 | 1.00 | 01-SEP-20:01 | 0.00 | 01-SEP-00:10 | 18840.07 | 06-SEP-20:02 | 17704.41 | 04-SEP-19:51 | 6715.30 | 06-SEP-23:00 | 3707.44 | 06-SEP-20:02 | 0.00 | 01-SEP-00:10 |
October | 0.557142E+09 | 0.121659E+09 | 123.81 | 0.557142E+09 | 13.28 | 0.00 | 1.00 | 02-OCT-20:02 | 0.00 | 01-OCT-00:05 | 17377.73 | 21-OCT-18:02 | 17377.73 | 21-OCT-18:02 | 0.13 | 25-OCT-07:02 | 3394.68 | 02-OCT-20:02 | 0.00 | 01-OCT-00:05 |
November | 18977613.30 | 4864883.07 | 31.57 | 18977613.30 | 0.00 | 0.00 | 1.00 | 03-NOV-20:02 | 0.00 | 01-NOV-00:10 | 17377.73 | 04-NOV-22:31 | 17377.73 | 04-NOV-22:31 | 0.00 | 19-NOV-20:10 | 3394.68 | 03-NOV-20:02 | 0.00 | 01-NOV-00:10 |
December | 213578.94 | 59817.87 | 1.83 | 213578.94 | 0.00 | 0.00 | 0.01 | 10-DEC-20:40 | 0.00 | 01-DEC-00:03 | 82.56 | 10-DEC-20:40 | 82.56 | 10-DEC-20:40 | 0.00 | 10-DEC-21:00 | 23.09 | 10-DEC-20:40 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.279695E+11 | 0.614794E+10 | 1667.61 | 0.273134E+11 | 0.656110E+09 | 0.00 | ||||||||||||||
Minimum of Months | 48576.06 | 13619.61 | 0.83 | 48576.06 | 0.00 | 0.00 | 0.00 | 0.00 | 23.90 | 23.90 | 0.00 | 6.70 | 0.00 | |||||||
Maximum of Months | 0.918186E+10 | 0.203500E+10 | 381.07 | 0.895444E+10 | 0.227417E+09 | 0.00 | 1.00 | 0.00 | 19096.60 | 17919.25 | 8161.28 | 3743.22 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 9506.18 | 2342.07 | 7.33 | 9506.18 | 0.00 | 0.00 | 0.00 | 27-FEB-16:50 | 0.00 | 01-FEB-00:05 | 12.86 | 27-FEB-16:50 | 12.86 | 27-FEB-16:50 | 0.00 | 26-FEB-16:50 | 3.17 | 27-FEB-16:50 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 72999945.51 | 16902635.93 | 45.67 | 72999945.51 | 0.00 | 0.00 | 0.49 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 3887.15 | 07-APR-14:00 | 3887.15 | 07-APR-14:00 | 0.00 | 07-APR-13:40 | 876.37 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.907847E+09 | 0.202127E+09 | 123.77 | 0.906496E+09 | 1350986.63 | 0.00 | 0.90 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 | 8215.53 | 20-MAY-16:00 | 8215.53 | 20-MAY-16:00 | 578.98 | 20-MAY-06:02 | 1870.27 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.358325E+10 | 0.792017E+09 | 261.43 | 0.347691E+10 | 0.106342E+09 | 0.00 | 1.00 | 22-JUN-06:02 | 0.00 | 01-JUN-00:10 | 18183.60 | 22-JUN-06:02 | 12821.70 | 24-JUN-06:02 | 5802.70 | 22-JUN-06:02 | 3572.63 | 22-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.678002E+10 | 0.152588E+10 | 317.58 | 0.666053E+10 | 0.119496E+09 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:03 | 18874.71 | 19-JUL-06:02 | 17574.38 | 25-JUL-06:03 | 6004.89 | 19-JUL-06:02 | 3699.38 | 19-JUL-06:02 | 0.00 | 01-JUL-00:03 |
August | 0.563376E+10 | 0.126729E+10 | 301.13 | 0.561191E+10 | 21855663.33 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 17577.56 | 06-AUG-07:02 | 17577.56 | 06-AUG-07:02 | 3297.78 | 14-AUG-06:01 | 3460.68 | 06-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.290428E+10 | 0.640517E+09 | 213.69 | 0.277194E+10 | 0.132339E+09 | 0.00 | 1.00 | 03-SEP-07:02 | 0.00 | 01-SEP-00:10 | 18089.14 | 07-SEP-06:02 | 17384.13 | 03-SEP-07:02 | 6534.68 | 07-SEP-06:02 | 3553.35 | 07-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.430084E+09 | 95297896.15 | 109.54 | 0.430084E+09 | 0.00 | 0.00 | 0.81 | 18-OCT-14:00 | 0.00 | 01-OCT-00:05 | 7138.32 | 18-OCT-14:00 | 7138.32 | 18-OCT-14:00 | 0.00 | 15-OCT-14:00 | 1510.94 | 18-OCT-14:00 | 0.00 | 01-OCT-00:05 |
November | 8333.07 | 2053.69 | 17.33 | 8333.07 | 0.00 | 0.00 | 0.00 | 05-NOV-13:40 | 0.00 | 01-NOV-00:10 | 3.23 | 05-NOV-13:40 | 3.23 | 05-NOV-13:40 | 0.00 | 05-NOV-14:30 | 0.80 | 05-NOV-13:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.203123E+11 | 0.454004E+10 | 1397.48 | 0.199309E+11 | 0.381383E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.678002E+10 | 0.152588E+10 | 317.58 | 0.666053E+10 | 0.132339E+09 | 0.00 | 1.00 | 0.00 | 18874.71 | 17577.56 | 6534.68 | 3699.38 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 2003.66 | 493.82 | 6.67 | 2003.66 | 0.00 | 0.00 | 0.00 | 27-FEB-12:20 | 0.00 | 01-FEB-00:05 | 0.16 | 27-FEB-12:20 | 0.16 | 27-FEB-12:20 | 0.00 | 27-FEB-15:20 | 0.04 | 27-FEB-12:20 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 64290749.50 | 14968437.19 | 38.17 | 64290749.50 | 0.00 | 0.00 | 0.46 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 3691.87 | 07-APR-14:00 | 3691.87 | 07-APR-14:00 | 0.00 | 07-APR-14:20 | 837.76 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.880140E+09 | 0.196422E+09 | 120.90 | 0.878922E+09 | 1218085.11 | 0.00 | 0.89 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 | 8168.27 | 20-MAY-16:00 | 8168.27 | 20-MAY-16:00 | 419.06 | 20-MAY-06:02 | 1863.26 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.356316E+10 | 0.788397E+09 | 261.13 | 0.345756E+10 | 0.105595E+09 | 0.00 | 1.00 | 22-JUN-06:02 | 0.00 | 01-JUN-00:10 | 18242.95 | 22-JUN-06:02 | 12865.80 | 24-JUN-06:02 | 5820.19 | 22-JUN-06:02 | 3584.30 | 22-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.679714E+10 | 0.152996E+10 | 317.88 | 0.667679E+10 | 0.120352E+09 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:03 | 18937.00 | 19-JUL-06:02 | 17633.18 | 25-JUL-06:03 | 6017.28 | 19-JUL-06:02 | 3711.55 | 19-JUL-06:02 | 0.00 | 01-JUL-00:03 |
August | 0.564078E+10 | 0.126922E+10 | 301.19 | 0.561896E+10 | 21811926.56 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 17637.92 | 06-AUG-07:02 | 17637.92 | 06-AUG-07:02 | 3473.57 | 14-AUG-06:01 | 3472.65 | 06-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.289414E+10 | 0.638604E+09 | 211.48 | 0.276138E+10 | 0.132760E+09 | 0.00 | 1.00 | 03-SEP-07:02 | 0.00 | 01-SEP-00:10 | 18148.73 | 07-SEP-06:02 | 17440.26 | 03-SEP-07:02 | 6551.30 | 07-SEP-06:02 | 3565.07 | 07-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.405919E+09 | 90146311.94 | 106.12 | 0.405919E+09 | 0.00 | 0.00 | 0.80 | 18-OCT-14:00 | 0.00 | 01-OCT-00:05 | 7052.57 | 18-OCT-14:00 | 7052.57 | 18-OCT-14:00 | 0.00 | 18-OCT-15:30 | 1497.39 | 18-OCT-14:00 | 0.00 | 01-OCT-00:05 |
November | 50415.24 | 12413.99 | 12.83 | 50415.24 | 0.00 | 0.00 | 0.00 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 | 33.68 | 05-NOV-15:00 | 33.68 | 05-NOV-15:00 | 0.00 | 04-NOV-14:30 | 8.29 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.202456E+11 | 0.452772E+10 | 1376.35 | 0.198639E+11 | 0.381738E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.679714E+10 | 0.152996E+10 | 317.88 | 0.667679E+10 | 0.132760E+09 | 0.00 | 1.00 | 0.00 | 18937.00 | 17637.92 | 6551.30 | 3711.55 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 1318.69 | 325.00 | 5.67 | 1318.69 | 0.00 | 0.00 | 0.00 | 27-FEB-15:30 | 0.00 | 01-FEB-00:05 | 0.14 | 27-FEB-15:30 | 0.14 | 27-FEB-15:30 | 0.00 | 01-FEB-00:05 | 0.04 | 27-FEB-15:30 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 48615235.35 | 11436385.44 | 32.00 | 48615235.35 | 0.00 | 0.00 | 0.42 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 3260.38 | 07-APR-14:00 | 3260.38 | 07-APR-14:00 | 0.00 | 07-APR-14:00 | 749.12 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.804208E+09 | 0.180466E+09 | 111.69 | 0.803310E+09 | 897617.07 | 0.00 | 0.88 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 | 7925.14 | 20-MAY-16:00 | 7925.14 | 20-MAY-16:00 | 73.26 | 28-MAY-10:30 | 1815.51 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.341073E+10 | 0.757165E+09 | 256.10 | 0.331070E+10 | 0.100026E+09 | 0.00 | 1.00 | 22-JUN-06:02 | 0.00 | 01-JUN-00:10 | 18036.29 | 22-JUN-06:02 | 12251.31 | 22-JUN-06:02 | 5784.97 | 22-JUN-06:02 | 3543.66 | 22-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.660025E+10 | 0.148919E+10 | 316.58 | 0.648553E+10 | 0.114720E+09 | 0.00 | 1.00 | 15-JUL-06:02 | 0.00 | 01-JUL-00:03 | 18724.03 | 19-JUL-06:02 | 17248.27 | 26-JUL-06:02 | 5976.08 | 19-JUL-06:02 | 3669.95 | 19-JUL-06:02 | 0.00 | 01-JUL-00:03 |
August | 0.546186E+10 | 0.123169E+10 | 298.70 | 0.544204E+10 | 19813217.04 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 17436.41 | 06-AUG-07:02 | 17436.41 | 06-AUG-07:02 | 2957.94 | 01-AUG-06:02 | 3432.80 | 06-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.278062E+10 | 0.614831E+09 | 202.31 | 0.265228E+10 | 0.128335E+09 | 0.00 | 1.00 | 03-SEP-07:02 | 0.00 | 01-SEP-00:10 | 17944.71 | 07-SEP-06:02 | 17248.27 | 03-SEP-07:02 | 6503.29 | 07-SEP-06:02 | 3524.95 | 07-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.356282E+09 | 79408804.59 | 91.22 | 0.356282E+09 | 0.00 | 0.00 | 0.78 | 18-OCT-14:00 | 0.00 | 01-OCT-00:05 | 6790.26 | 18-OCT-14:00 | 6790.26 | 18-OCT-14:00 | 0.00 | 18-OCT-12:00 | 1449.39 | 18-OCT-14:00 | 0.00 | 01-OCT-00:05 |
November | 35205.35 | 8671.22 | 8.50 | 35205.35 | 0.00 | 0.00 | 0.00 | 03-NOV-18:10 | 0.00 | 01-NOV-00:10 | 22.95 | 03-NOV-18:10 | 22.95 | 03-NOV-18:10 | 0.00 | 04-NOV-14:30 | 5.65 | 03-NOV-18:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.194626E+11 | 0.436419E+10 | 1322.78 | 0.190988E+11 | 0.363791E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.660025E+10 | 0.148919E+10 | 316.58 | 0.648553E+10 | 0.128335E+09 | 0.00 | 1.00 | 0.00 | 18724.03 | 17436.41 | 6503.29 | 3669.95 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 115.62 | 32.68 | 0.67 | 115.62 | 0.00 | 0.00 | 0.00 | 27-FEB-15:30 | 0.00 | 01-FEB-00:05 | 0.08 | 27-FEB-15:30 | 0.08 | 27-FEB-15:30 | 0.00 | 01-FEB-00:05 | 0.02 | 27-FEB-15:30 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 31025337.40 | 8599728.82 | 11.17 | 31025337.40 | 0.00 | 0.00 | 0.26 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 3070.86 | 07-APR-14:10 | 3070.86 | 07-APR-14:10 | 0.00 | 07-APR-13:20 | 844.92 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.104699E+10 | 0.275519E+09 | 78.58 | 0.104038E+10 | 6606043.32 | 0.00 | 0.85 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 | 12226.55 | 20-MAY-16:00 | 12226.55 | 20-MAY-16:00 | 342.68 | 20-MAY-11:00 | 3232.04 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.518578E+10 | 0.133573E+10 | 230.88 | 0.493249E+10 | 0.253286E+09 | 0.00 | 1.00 | 29-JUN-13:20 | 0.00 | 01-JUN-00:10 | 24156.23 | 22-JUN-07:03 | 19378.28 | 23-JUN-07:03 | 6043.67 | 22-JUN-07:03 | 5146.34 | 22-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.103051E+11 | 0.268262E+10 | 311.83 | 0.100230E+11 | 0.282081E+09 | 0.00 | 1.00 | 16-JUL-08:62 | 0.00 | 01-JUL-00:03 | 32909.06 | 19-JUL-07:02 | 31031.67 | 18-JUL-07:02 | 10016.92 | 19-JUL-07:02 | 7007.55 | 19-JUL-07:02 | 0.00 | 01-JUL-00:03 |
August | 0.857078E+10 | 0.222840E+10 | 301.44 | 0.850193E+10 | 68845678.67 | 0.00 | 1.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 30998.51 | 09-AUG-07:03 | 30887.83 | 06-AUG-08:62 | 5038.16 | 01-AUG-07:02 | 6893.80 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.437926E+10 | 0.111099E+10 | 169.97 | 0.408139E+10 | 0.297868E+09 | 0.00 | 1.00 | 03-SEP-08:62 | 0.00 | 01-SEP-00:10 | 31310.81 | 07-SEP-07:02 | 31022.69 | 04-SEP-08:62 | 11349.64 | 07-SEP-07:02 | 7158.79 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.466329E+09 | 0.120989E+09 | 53.42 | 0.466329E+09 | 0.00 | 0.00 | 0.73 | 18-OCT-14:30 | 0.00 | 01-OCT-00:05 | 9912.02 | 18-OCT-14:30 | 9912.02 | 18-OCT-14:30 | 0.00 | 18-OCT-13:00 | 2466.72 | 18-OCT-14:30 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.299852E+11 | 0.776285E+10 | 1157.96 | 0.290765E+11 | 0.908687E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.103051E+11 | 0.268262E+10 | 311.83 | 0.100230E+11 | 0.297868E+09 | 0.00 | 1.00 | 0.00 | 32909.06 | 31031.67 | 11349.64 | 7158.79 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 465.35 | 114.69 | 2.17 | 465.35 | 0.00 | 0.00 | 0.00 | 27-FEB-15:10 | 0.00 | 01-FEB-00:05 | 0.12 | 27-FEB-15:10 | 0.12 | 27-FEB-15:10 | 0.00 | 27-FEB-14:50 | 0.03 | 27-FEB-15:10 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 17484889.60 | 4204471.49 | 17.08 | 17484889.60 | 0.00 | 0.00 | 0.30 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 2043.20 | 07-APR-14:00 | 2043.20 | 07-APR-14:00 | 0.00 | 07-APR-14:50 | 484.80 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.589708E+09 | 0.134431E+09 | 87.03 | 0.589196E+09 | 511883.29 | 0.00 | 0.86 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 | 6949.86 | 20-MAY-16:00 | 6949.86 | 20-MAY-16:00 | 59.34 | 20-MAY-11:00 | 1598.96 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.287147E+10 | 0.644193E+09 | 239.51 | 0.277531E+10 | 96160243.82 | 0.00 | 1.00 | 29-JUN-12:50 | 0.00 | 01-JUN-00:10 | 9831.77 | 22-JUN-07:03 | 8486.43 | 29-JUN-15:00 | 2289.15 | 22-JUN-07:03 | 1992.22 | 29-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.572170E+10 | 0.130329E+10 | 309.13 | 0.561987E+10 | 0.101839E+09 | 0.00 | 1.00 | 16-JUL-08:62 | 0.00 | 01-JUL-00:03 | 16942.37 | 19-JUL-07:02 | 15952.41 | 18-JUL-07:02 | 5252.92 | 19-JUL-07:02 | 3327.54 | 19-JUL-07:02 | 0.00 | 01-JUL-00:03 |
August | 0.470919E+10 | 0.107178E+10 | 298.28 | 0.469382E+10 | 15372627.52 | 0.00 | 1.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 15878.85 | 06-AUG-08:62 | 15878.85 | 06-AUG-08:62 | 1937.94 | 01-AUG-07:02 | 3269.96 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.231867E+10 | 0.515592E+09 | 174.10 | 0.219915E+10 | 0.119520E+09 | 0.00 | 1.00 | 03-SEP-08:62 | 0.00 | 01-SEP-00:10 | 16115.32 | 07-SEP-07:02 | 15949.98 | 04-SEP-08:62 | 5915.46 | 07-SEP-07:02 | 3395.96 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.240413E+09 | 54083346.57 | 64.11 | 0.240413E+09 | 0.00 | 0.00 | 0.75 | 18-OCT-14:30 | 0.00 | 01-OCT-00:05 | 5839.68 | 18-OCT-14:40 | 5839.68 | 18-OCT-14:40 | 0.00 | 15-OCT-14:30 | 1257.92 | 18-OCT-14:40 | 0.00 | 01-OCT-00:05 |
November | 491.67 | 121.18 | 2.67 | 491.67 | 0.00 | 0.00 | 0.00 | 04-NOV-13:30 | 0.00 | 01-NOV-00:10 | 0.12 | 04-NOV-13:30 | 0.12 | 04-NOV-13:30 | 0.00 | 01-NOV-00:10 | 0.03 | 04-NOV-13:30 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.164686E+11 | 0.372758E+10 | 1194.08 | 0.161352E+11 | 0.333404E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.572170E+10 | 0.130329E+10 | 309.13 | 0.561987E+10 | 0.119520E+09 | 0.00 | 1.00 | 0.00 | 16942.37 | 15952.41 | 5915.46 | 3395.96 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 9572.31 | 2358.35 | 2.17 | 9572.31 | 0.00 | 0.00 | 0.00 | 27-FEB-14:10 | 0.00 | 01-FEB-00:05 | 11.42 | 27-FEB-14:10 | 11.42 | 27-FEB-14:10 | 0.00 | 27-FEB-14:30 | 2.81 | 27-FEB-14:10 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 15315195.97 | 3691746.80 | 16.42 | 15315195.97 | 0.00 | 0.00 | 0.29 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 1930.24 | 07-APR-14:00 | 1930.24 | 07-APR-14:00 | 0.00 | 06-APR-15:40 | 459.63 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.569308E+09 | 0.130041E+09 | 83.78 | 0.568828E+09 | 479594.24 | 0.00 | 0.86 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 | 6846.38 | 20-MAY-16:00 | 6846.38 | 20-MAY-16:00 | 57.64 | 20-MAY-11:00 | 1577.39 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.281426E+10 | 0.632112E+09 | 236.93 | 0.271983E+10 | 94434075.77 | 0.00 | 1.00 | 29-JUN-12:50 | 0.00 | 01-JUN-00:10 | 8877.25 | 22-JUN-07:03 | 8404.47 | 29-JUN-15:00 | 2045.27 | 22-JUN-07:03 | 1972.55 | 29-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.564119E+10 | 0.128595E+10 | 307.82 | 0.554114E+10 | 0.100054E+09 | 0.00 | 1.00 | 16-JUL-08:62 | 0.00 | 01-JUL-00:03 | 16798.95 | 19-JUL-07:02 | 15816.06 | 18-JUL-07:02 | 5220.50 | 19-JUL-07:02 | 3299.44 | 19-JUL-07:02 | 0.00 | 01-JUL-00:03 |
August | 0.464213E+10 | 0.105727E+10 | 296.92 | 0.462712E+10 | 15007308.13 | 0.00 | 1.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 15742.74 | 06-AUG-08:62 | 15742.74 | 06-AUG-08:62 | 1721.06 | 01-AUG-07:02 | 3241.96 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.228321E+10 | 0.508009E+09 | 170.36 | 0.216516E+10 | 0.118044E+09 | 0.00 | 1.00 | 03-SEP-08:62 | 0.00 | 01-SEP-00:10 | 15979.21 | 07-SEP-07:02 | 15813.28 | 04-SEP-08:62 | 5876.50 | 07-SEP-07:02 | 3366.92 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.232017E+09 | 52250915.25 | 62.61 | 0.232017E+09 | 0.00 | 0.00 | 0.75 | 18-OCT-14:30 | 0.00 | 01-OCT-00:05 | 5751.55 | 18-OCT-14:40 | 5751.55 | 18-OCT-14:40 | 0.00 | 18-OCT-12:40 | 1240.52 | 18-OCT-14:40 | 0.00 | 01-OCT-00:05 |
November | 355.09 | 87.52 | 2.33 | 355.09 | 0.00 | 0.00 | 0.00 | 04-NOV-15:50 | 0.00 | 01-NOV-00:10 | 0.09 | 04-NOV-15:50 | 0.09 | 04-NOV-15:50 | 0.00 | 01-NOV-00:10 | 0.02 | 04-NOV-15:50 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.161974E+11 | 0.366932E+10 | 1179.33 | 0.158694E+11 | 0.328019E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.564119E+10 | 0.128595E+10 | 307.82 | 0.554114E+10 | 0.118044E+09 | 0.00 | 1.00 | 0.00 | 16798.95 | 15816.06 | 5876.50 | 3366.92 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 98.80 | 24.35 | 0.83 | 98.80 | 0.00 | 0.00 | 0.00 | 27-FEB-15:20 | 0.00 | 01-FEB-00:05 | 0.06 | 27-FEB-15:20 | 0.06 | 27-FEB-15:20 | 0.00 | 27-FEB-15:20 | 0.02 | 27-FEB-15:20 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 9795962.37 | 2380398.22 | 10.83 | 9795962.37 | 0.00 | 0.00 | 0.24 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 1602.39 | 07-APR-14:00 | 1602.39 | 07-APR-14:00 | 0.00 | 07-APR-13:50 | 386.04 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.513047E+09 | 0.118012E+09 | 73.92 | 0.512658E+09 | 389354.92 | 0.00 | 0.84 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 | 6593.27 | 20-MAY-16:00 | 6593.27 | 20-MAY-16:00 | 52.78 | 20-MAY-11:00 | 1527.91 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.267380E+10 | 0.603098E+09 | 228.61 | 0.258333E+10 | 90469174.32 | 0.00 | 1.00 | 23-JUN-14:00 | 0.00 | 01-JUN-00:10 | 8238.09 | 29-JUN-15:00 | 8238.09 | 29-JUN-15:00 | 1370.25 | 22-JUN-07:03 | 1931.10 | 29-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.547828E+10 | 0.125174E+10 | 305.62 | 0.538193E+10 | 96342970.33 | 0.00 | 1.00 | 16-JUL-08:62 | 0.00 | 01-JUL-00:03 | 16623.53 | 19-JUL-07:02 | 15647.64 | 18-JUL-07:02 | 5195.01 | 19-JUL-07:02 | 3265.18 | 19-JUL-07:02 | 0.00 | 01-JUL-00:03 |
August | 0.450441E+10 | 0.102816E+10 | 292.82 | 0.449021E+10 | 14198529.38 | 0.00 | 1.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 15573.97 | 06-AUG-08:62 | 15573.97 | 06-AUG-08:62 | 1095.09 | 01-AUG-07:02 | 3207.28 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.220413E+10 | 0.491332E+09 | 163.11 | 0.208912E+10 | 0.115006E+09 | 0.00 | 1.00 | 03-SEP-08:62 | 0.00 | 01-SEP-00:10 | 15596.05 | 06-SEP-07:02 | 15567.25 | 04-SEP-08:62 | 5656.92 | 07-SEP-07:02 | 3319.10 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.205995E+09 | 46610856.02 | 54.42 | 0.205995E+09 | 0.00 | 0.00 | 0.73 | 18-OCT-14:30 | 0.00 | 01-OCT-00:05 | 5507.67 | 18-OCT-14:40 | 5507.67 | 18-OCT-14:40 | 0.00 | 18-OCT-12:20 | 1195.20 | 18-OCT-14:40 | 0.00 | 01-OCT-00:05 |
November | 3563.22 | 878.02 | 1.17 | 3563.22 | 0.00 | 0.00 | 0.00 | 04-NOV-15:10 | 0.00 | 01-NOV-00:10 | 5.42 | 04-NOV-15:10 | 5.42 | 04-NOV-15:10 | 0.00 | 01-NOV-00:10 | 1.34 | 04-NOV-15:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.155894E+11 | 0.354133E+10 | 1131.33 | 0.152730E+11 | 0.316406E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.547828E+10 | 0.125174E+10 | 305.62 | 0.538193E+10 | 0.115006E+09 | 0.00 | 1.00 | 0.00 | 16623.53 | 15647.64 | 5656.92 | 3319.10 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 2422677.87 | 602657.89 | 1.67 | 2422677.87 | 0.00 | 0.00 | 0.13 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 866.41 | 07-APR-14:00 | 866.41 | 07-APR-14:00 | 0.00 | 07-APR-14:40 | 215.12 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.431294E+09 | 0.101185E+09 | 60.08 | 0.431043E+09 | 251420.60 | 0.00 | 0.77 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 | 6241.68 | 20-MAY-16:00 | 6241.68 | 20-MAY-16:00 | 38.32 | 20-MAY-11:00 | 1477.66 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.248821E+10 | 0.569791E+09 | 202.89 | 0.240338E+10 | 84835283.87 | 0.00 | 0.97 | 29-JUN-15:00 | 0.00 | 01-JUN-00:10 | 8135.39 | 29-JUN-15:00 | 8135.39 | 29-JUN-15:00 | 1168.00 | 20-JUN-15:20 | 1919.11 | 29-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.536604E+10 | 0.123603E+10 | 295.61 | 0.527562E+10 | 90422139.13 | 0.00 | 1.00 | 17-JUL-07:02 | 0.00 | 01-JUL-00:03 | 16766.21 | 17-JUL-07:02 | 15339.22 | 17-JUL-07:02 | 3567.77 | 16-JUL-08:62 | 3399.60 | 17-JUL-07:02 | 0.00 | 01-JUL-00:03 |
August | 0.439879E+10 | 0.101183E+10 | 279.06 | 0.438626E+10 | 12526357.17 | 0.00 | 1.00 | 07-AUG-07:02 | 0.00 | 01-AUG-00:10 | 16133.23 | 07-AUG-07:02 | 16133.23 | 07-AUG-07:02 | 434.59 | 22-AUG-14:20 | 3248.30 | 07-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.211152E+10 | 0.474497E+09 | 148.33 | 0.200536E+10 | 0.106161E+09 | 0.00 | 1.00 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 | 16369.02 | 04-SEP-08:62 | 16369.02 | 04-SEP-08:62 | 3758.13 | 07-SEP-14:50 | 3489.47 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.167433E+09 | 38302531.44 | 44.42 | 0.167433E+09 | 0.00 | 0.00 | 0.67 | 18-OCT-14:30 | 0.00 | 01-OCT-00:05 | 5230.94 | 18-OCT-14:40 | 5230.94 | 18-OCT-14:40 | 0.00 | 18-OCT-15:50 | 1155.77 | 18-OCT-14:40 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.149657E+11 | 0.343224E+10 | 1032.06 | 0.146715E+11 | 0.294196E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.536604E+10 | 0.123603E+10 | 295.61 | 0.527562E+10 | 0.106161E+09 | 0.00 | 1.00 | 0.00 | 16766.21 | 16369.02 | 3758.13 | 3489.47 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 104.60 | 137.69 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 143.60 | 102.68 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 120.17 | 90.66 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 88.62 | 67.00 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 70.94 | 53.85 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 77.56 | 37.93 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.42 | 29.51 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.14 | 33.69 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.85 | 48.41 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 145.43 | 69.36 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 126.85 | 87.17 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 102.92 | 118.01 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 111.61 | 72.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 70.94 | 29.51 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 145.43 | 137.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 104.60 | 137.69 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 143.60 | 102.68 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 120.17 | 90.66 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 88.62 | 67.00 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 70.94 | 53.85 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 77.56 | 37.93 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.42 | 29.51 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.14 | 33.69 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.85 | 48.41 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 145.43 | 69.36 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 126.85 | 87.17 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 102.92 | 118.01 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 111.61 | 72.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 70.94 | 29.51 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 145.43 | 137.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 104.60 | 137.69 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 143.60 | 102.68 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 120.17 | 90.66 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 88.62 | 67.00 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 70.94 | 53.85 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 77.56 | 37.93 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.42 | 29.51 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.14 | 33.69 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.85 | 48.41 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 145.43 | 69.36 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 126.85 | 87.17 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 102.92 | 118.01 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 111.61 | 72.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 70.94 | 29.51 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 145.43 | 137.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 104.60 | 137.69 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 143.60 | 102.68 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 120.17 | 90.66 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 88.62 | 67.00 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 70.94 | 53.85 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 77.56 | 37.93 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.42 | 29.51 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.14 | 33.69 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.85 | 48.41 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 145.43 | 69.36 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 126.85 | 87.17 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 102.92 | 118.01 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 111.61 | 72.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 70.94 | 29.51 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 145.43 | 137.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.04 | 101.44 | 40.61 | 126.22 | 164.03 | 0.00 | 0.00 | 744.00 |
February | 180.96 | 130.15 | 50.80 | 173.15 | 122.40 | 0.00 | 0.00 | 672.00 |
March | 161.82 | 90.90 | 70.92 | 144.91 | 108.09 | 0.00 | 0.00 | 744.00 |
April | 130.03 | 62.20 | 67.83 | 106.82 | 79.95 | 0.00 | 0.00 | 720.00 |
May | 115.50 | 38.35 | 77.15 | 85.52 | 64.27 | 0.00 | 0.00 | 744.00 |
June | 114.76 | 33.45 | 81.30 | 93.38 | 45.32 | 0.00 | 0.00 | 720.00 |
July | 123.72 | 45.68 | 78.03 | 115.94 | 35.33 | 0.00 | 0.00 | 744.00 |
August | 147.05 | 74.14 | 72.92 | 148.11 | 40.32 | 0.00 | 0.00 | 744.00 |
September | 163.17 | 100.00 | 63.17 | 170.73 | 57.86 | 0.00 | 0.00 | 720.00 |
October | 170.57 | 117.96 | 52.61 | 175.16 | 82.84 | 0.00 | 0.00 | 744.00 |
November | 155.43 | 112.58 | 42.85 | 152.88 | 104.00 | 0.00 | 0.00 | 720.00 |
December | 135.07 | 97.52 | 37.55 | 124.16 | 140.68 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 144.76 | 83.39 | 61.37 | 134.48 | 86.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.76 | 33.45 | 37.55 | 85.52 | 35.33 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 180.96 | 130.15 | 81.30 | 175.16 | 164.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.04 | 101.44 | 40.61 | 126.22 | 164.03 | 0.00 | 0.00 | 744.00 |
February | 180.96 | 130.15 | 50.80 | 173.15 | 122.40 | 0.00 | 0.00 | 672.00 |
March | 161.82 | 90.90 | 70.92 | 144.91 | 108.09 | 0.00 | 0.00 | 744.00 |
April | 130.03 | 62.20 | 67.83 | 106.82 | 79.95 | 0.00 | 0.00 | 720.00 |
May | 115.50 | 38.35 | 77.15 | 85.52 | 64.27 | 0.00 | 0.00 | 744.00 |
June | 114.76 | 33.45 | 81.30 | 93.38 | 45.32 | 0.00 | 0.00 | 720.00 |
July | 123.72 | 45.68 | 78.03 | 115.94 | 35.33 | 0.00 | 0.00 | 744.00 |
August | 147.05 | 74.14 | 72.92 | 148.11 | 40.32 | 0.00 | 0.00 | 744.00 |
September | 163.17 | 100.00 | 63.17 | 170.73 | 57.86 | 0.00 | 0.00 | 720.00 |
October | 170.57 | 117.96 | 52.61 | 175.16 | 82.84 | 0.00 | 0.00 | 744.00 |
November | 155.43 | 112.58 | 42.85 | 152.88 | 104.00 | 0.00 | 0.00 | 720.00 |
December | 135.07 | 97.52 | 37.55 | 124.16 | 140.68 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 144.76 | 83.39 | 61.37 | 134.48 | 86.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.76 | 33.45 | 37.55 | 85.52 | 35.33 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 180.96 | 130.15 | 81.30 | 175.16 | 164.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 103.47 | 142.68 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 141.83 | 107.81 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 118.47 | 96.37 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 86.53 | 72.73 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 69.32 | 57.62 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 76.87 | 39.18 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.28 | 29.95 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.89 | 34.32 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.01 | 50.32 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 143.85 | 73.02 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 124.88 | 92.32 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 101.75 | 122.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 110.38 | 76.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 69.32 | 29.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 143.85 | 142.68 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 103.47 | 142.68 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 141.83 | 107.81 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 118.47 | 96.37 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 86.53 | 72.73 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 69.32 | 57.62 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 76.87 | 39.18 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.28 | 29.95 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.89 | 34.32 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.01 | 50.32 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 143.85 | 73.02 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 124.88 | 92.32 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 101.75 | 122.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 110.38 | 76.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 69.32 | 29.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 143.85 | 142.68 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.04 | 101.44 | 40.61 | 124.87 | 169.95 | 0.00 | 0.00 | 744.00 |
February | 180.96 | 130.15 | 50.80 | 171.04 | 128.48 | 0.00 | 0.00 | 672.00 |
March | 161.82 | 90.90 | 70.92 | 142.88 | 114.85 | 0.00 | 0.00 | 744.00 |
April | 130.03 | 62.20 | 67.83 | 104.32 | 86.75 | 0.00 | 0.00 | 720.00 |
May | 115.50 | 38.35 | 77.15 | 83.59 | 68.72 | 0.00 | 0.00 | 744.00 |
June | 114.76 | 33.45 | 81.30 | 92.54 | 46.80 | 0.00 | 0.00 | 720.00 |
July | 123.72 | 45.68 | 78.03 | 115.76 | 35.84 | 0.00 | 0.00 | 744.00 |
August | 147.05 | 74.14 | 72.92 | 147.81 | 41.06 | 0.00 | 0.00 | 744.00 |
September | 163.17 | 100.00 | 63.17 | 169.73 | 60.11 | 0.00 | 0.00 | 720.00 |
October | 170.57 | 117.96 | 52.61 | 173.28 | 87.17 | 0.00 | 0.00 | 744.00 |
November | 155.43 | 112.58 | 42.85 | 150.54 | 110.08 | 0.00 | 0.00 | 720.00 |
December | 135.07 | 97.52 | 37.55 | 122.76 | 146.37 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 144.76 | 83.39 | 61.37 | 132.99 | 91.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.76 | 33.45 | 37.55 | 83.59 | 35.84 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 180.96 | 130.15 | 81.30 | 173.28 | 169.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 103.76 | 139.61 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 142.28 | 105.23 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 118.85 | 93.81 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 86.84 | 71.05 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 69.42 | 57.03 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 76.60 | 40.39 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.73 | 31.83 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.50 | 36.09 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 140.81 | 51.31 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 144.07 | 72.42 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 125.32 | 90.28 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 102.11 | 119.92 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 110.47 | 75.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 69.42 | 31.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 144.07 | 139.61 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 103.76 | 139.61 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 142.28 | 105.23 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 118.85 | 93.81 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 86.84 | 71.05 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 69.42 | 57.03 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 76.60 | 40.39 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.73 | 31.83 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.50 | 36.09 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 140.81 | 51.31 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 144.07 | 72.42 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 125.32 | 90.28 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 102.11 | 119.92 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 110.47 | 75.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 69.42 | 31.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 144.07 | 139.61 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 124.54 | 165.38 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 170.65 | 124.73 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 142.55 | 111.20 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 104.13 | 84.29 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 83.25 | 67.63 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 91.72 | 47.95 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 114.48 | 37.85 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 146.54 | 42.89 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 168.56 | 60.92 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 172.59 | 85.97 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 150.24 | 107.06 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 122.52 | 142.14 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 132.38 | 89.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 83.25 | 37.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 172.59 | 165.38 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 103.92 | 138.40 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 142.57 | 104.08 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 119.12 | 92.65 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 87.18 | 69.93 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 69.67 | 56.27 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 76.65 | 40.27 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.71 | 31.90 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.49 | 36.12 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 140.88 | 51.05 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 144.29 | 71.64 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 125.67 | 89.06 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 102.30 | 118.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 110.65 | 74.91 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 69.67 | 31.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 144.29 | 138.40 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 103.92 | 138.40 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 142.57 | 104.08 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 119.12 | 92.65 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 87.18 | 69.93 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 69.67 | 56.27 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 76.65 | 40.27 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.71 | 31.90 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.49 | 36.12 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 140.88 | 51.05 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 144.29 | 71.64 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 125.67 | 89.06 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 102.30 | 118.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 110.65 | 74.91 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 69.67 | 31.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 144.29 | 138.40 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 124.74 | 163.93 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 170.99 | 123.36 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 142.87 | 109.82 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 104.53 | 82.95 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 83.55 | 66.73 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 91.78 | 47.80 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 114.46 | 37.93 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 146.53 | 42.93 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 168.66 | 60.62 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 172.86 | 85.04 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 150.66 | 105.61 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 122.76 | 140.78 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 132.60 | 88.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 83.55 | 37.93 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 172.86 | 163.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 104.12 | 137.39 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 142.92 | 103.04 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 119.45 | 91.57 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 87.72 | 68.55 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 70.16 | 55.19 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 76.90 | 39.75 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.87 | 31.52 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.65 | 35.68 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.14 | 50.34 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 144.73 | 70.52 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 126.21 | 87.63 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 102.52 | 117.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 110.97 | 73.98 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 70.16 | 31.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 144.73 | 137.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 104.12 | 137.39 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 142.92 | 103.04 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 119.45 | 91.57 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 87.72 | 68.55 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 70.16 | 55.19 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 76.90 | 39.75 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.87 | 31.52 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.65 | 35.68 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.14 | 50.34 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 144.73 | 70.52 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 126.21 | 87.63 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 102.52 | 117.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 110.97 | 73.98 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 70.16 | 31.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 144.73 | 137.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 124.98 | 162.73 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 171.42 | 122.12 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 143.27 | 108.54 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 105.18 | 81.31 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 84.14 | 65.45 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 92.07 | 47.19 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 114.66 | 37.48 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 146.72 | 42.41 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 168.97 | 59.78 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 173.39 | 83.71 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 151.30 | 103.92 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 123.03 | 139.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 132.99 | 87.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 84.14 | 37.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 173.39 | 162.73 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 105.00 | 133.82 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 144.24 | 99.84 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 120.49 | 88.60 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 89.17 | 65.26 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 71.50 | 52.37 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 77.50 | 38.07 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.01 | 30.22 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.91 | 34.21 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.90 | 48.33 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 146.19 | 67.56 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 127.68 | 84.15 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 103.43 | 114.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 111.94 | 71.33 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 71.50 | 30.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 146.19 | 133.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 105.00 | 133.82 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 144.24 | 99.84 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 120.49 | 88.60 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 89.17 | 65.26 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 71.50 | 52.37 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 77.50 | 38.07 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.01 | 30.22 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.91 | 34.21 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.90 | 48.33 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 146.19 | 67.56 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 127.68 | 84.15 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 103.43 | 114.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 111.94 | 71.33 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 71.50 | 30.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 146.19 | 133.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 105.00 | 133.82 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 144.24 | 99.84 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 120.49 | 88.60 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 89.17 | 65.26 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 71.50 | 52.37 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 77.50 | 38.07 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.01 | 30.22 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.91 | 34.21 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.90 | 48.33 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 146.19 | 67.56 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 127.68 | 84.15 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 103.43 | 114.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 111.94 | 71.33 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 71.50 | 30.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 146.19 | 133.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 105.00 | 133.82 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 144.24 | 99.84 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 120.49 | 88.60 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 89.17 | 65.26 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 71.50 | 52.37 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 77.50 | 38.07 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.01 | 30.22 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.91 | 34.21 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.90 | 48.33 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 146.19 | 67.56 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 127.68 | 84.15 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 103.43 | 114.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 111.94 | 71.33 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 71.50 | 30.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 146.19 | 133.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 126.03 | 158.53 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 172.98 | 118.35 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 144.52 | 105.03 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 106.91 | 77.42 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 85.74 | 62.13 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 92.80 | 45.21 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 114.84 | 35.95 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 147.04 | 40.67 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 169.88 | 57.41 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 175.12 | 80.21 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 153.05 | 99.81 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 124.11 | 136.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 134.14 | 84.61 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 85.74 | 35.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 175.12 | 158.53 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 126.03 | 158.53 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 172.98 | 118.35 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 144.52 | 105.03 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 106.91 | 77.42 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 85.74 | 62.13 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 92.80 | 45.21 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 114.84 | 35.95 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 147.04 | 40.67 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 169.88 | 57.41 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 175.12 | 80.21 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 153.05 | 99.81 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 124.11 | 136.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 134.14 | 84.61 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 85.74 | 35.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 175.12 | 158.53 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 104.61 | 134.55 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 143.79 | 100.26 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 120.18 | 88.84 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 88.91 | 65.44 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 71.30 | 52.52 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 77.53 | 38.01 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.26 | 29.96 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.02 | 34.00 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.70 | 48.40 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 145.67 | 67.92 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 127.30 | 84.46 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 103.07 | 115.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 111.72 | 71.53 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 71.30 | 29.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 145.67 | 134.55 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 104.61 | 134.55 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 143.79 | 100.26 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 120.18 | 88.84 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 88.91 | 65.44 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 71.30 | 52.52 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 77.53 | 38.01 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.26 | 29.96 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.02 | 34.00 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.70 | 48.40 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 145.67 | 67.92 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 127.30 | 84.46 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 103.07 | 115.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 111.72 | 71.53 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 71.30 | 29.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 145.67 | 134.55 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 125.58 | 159.34 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 172.47 | 118.81 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 144.17 | 105.29 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 106.61 | 77.61 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 85.52 | 62.28 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 92.85 | 45.12 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 115.13 | 35.64 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 147.18 | 40.42 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 169.65 | 57.47 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 174.53 | 80.63 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 152.62 | 100.15 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 123.70 | 136.54 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 133.89 | 84.83 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 85.52 | 35.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 174.53 | 159.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 104.66 | 134.29 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 143.89 | 99.95 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 120.27 | 88.51 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 89.06 | 65.03 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 71.47 | 52.19 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 77.66 | 37.80 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.35 | 29.81 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.10 | 33.84 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.78 | 48.20 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 145.78 | 67.68 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 127.41 | 84.16 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 103.14 | 114.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 111.82 | 71.27 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 71.47 | 29.81 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 145.78 | 134.29 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 104.66 | 134.29 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 143.89 | 99.95 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 120.27 | 88.51 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 89.06 | 65.03 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 71.47 | 52.19 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 77.66 | 37.80 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.35 | 29.81 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.10 | 33.84 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.78 | 48.20 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 145.78 | 67.68 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 127.41 | 84.16 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 103.14 | 114.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 111.82 | 71.27 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 71.47 | 29.81 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 145.78 | 134.29 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 125.64 | 159.04 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 172.60 | 118.45 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 144.28 | 104.89 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 106.80 | 77.13 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 85.72 | 61.89 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 93.00 | 44.88 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 115.25 | 35.45 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 147.28 | 40.23 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 169.75 | 57.24 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 174.65 | 80.34 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 152.75 | 99.80 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 123.79 | 136.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 134.02 | 84.51 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 85.72 | 35.45 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 174.65 | 159.04 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 104.84 | 133.23 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 144.23 | 98.76 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 120.56 | 87.31 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 89.54 | 63.63 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 71.99 | 51.03 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.05 | 37.10 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.54 | 29.43 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.27 | 33.41 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.03 | 47.56 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 146.17 | 66.73 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 127.73 | 83.15 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 103.37 | 113.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 112.13 | 70.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 71.99 | 29.43 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 146.17 | 133.23 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 104.84 | 133.23 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 144.23 | 98.76 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 120.56 | 87.31 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 89.54 | 63.63 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 71.99 | 51.03 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.05 | 37.10 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.54 | 29.43 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.27 | 33.41 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.03 | 47.56 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 146.17 | 66.73 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 127.73 | 83.15 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 103.37 | 113.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 112.13 | 70.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 71.99 | 29.43 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 146.17 | 133.23 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 125.86 | 157.78 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 173.00 | 117.03 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 144.64 | 103.47 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 107.38 | 75.47 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 86.35 | 60.52 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 93.48 | 44.05 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 115.47 | 35.00 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 147.49 | 39.72 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 170.04 | 56.48 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 175.12 | 79.21 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 153.15 | 98.60 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 124.06 | 134.89 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 134.39 | 83.41 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 86.35 | 35.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 175.12 | 157.78 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 105.57 | 128.77 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 145.38 | 94.01 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 121.59 | 82.52 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 90.85 | 58.84 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 73.40 | 47.15 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 79.25 | 34.52 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 97.03 | 27.96 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.70 | 31.83 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.61 | 45.37 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 147.08 | 63.77 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 128.66 | 79.61 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 104.17 | 109.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 113.04 | 66.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 73.40 | 27.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 147.08 | 128.77 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 105.57 | 128.77 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 145.38 | 94.01 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 121.59 | 82.52 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 90.85 | 58.84 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 73.40 | 47.15 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 79.25 | 34.52 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 97.03 | 27.96 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.70 | 31.83 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.61 | 45.37 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 147.08 | 63.77 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 128.66 | 79.61 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 104.17 | 109.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 113.04 | 66.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 73.40 | 27.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 147.08 | 128.77 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 126.75 | 152.47 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 174.40 | 111.40 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 145.88 | 97.78 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 108.96 | 69.78 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 88.04 | 55.92 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 94.92 | 40.99 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 116.06 | 33.27 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 148.01 | 37.85 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 170.75 | 53.89 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 176.21 | 75.71 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 154.26 | 94.40 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 125.04 | 129.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 135.49 | 79.32 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 88.04 | 33.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 176.21 | 152.47 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.280155E+09 | 0.368793E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.347392E+09 | 0.248395E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.321869E+09 | 0.242832E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.229693E+09 | 0.173658E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.189994E+09 | 0.144241E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.201043E+09 | 98326364.86 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258256E+09 | 79044544.26 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329816E+09 | 90248668.19 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.367687E+09 | 0.125480E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.389521E+09 | 0.185763E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.328789E+09 | 0.225949E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.275666E+09 | 0.316068E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.351988E+10 | 0.229880E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.189994E+09 | 79044544.26 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.389521E+09 | 0.368793E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.280155E+09 | 0.368793E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.347392E+09 | 0.248395E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.321869E+09 | 0.242832E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.229693E+09 | 0.173658E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.189994E+09 | 0.144241E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.201043E+09 | 98326364.86 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258256E+09 | 79044544.26 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329816E+09 | 90248668.19 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.367687E+09 | 0.125480E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.389521E+09 | 0.185763E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.328789E+09 | 0.225949E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.275666E+09 | 0.316068E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.351988E+10 | 0.229880E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.189994E+09 | 79044544.26 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.389521E+09 | 0.368793E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.280155E+09 | 0.368793E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.347392E+09 | 0.248395E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.321869E+09 | 0.242832E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.229693E+09 | 0.173658E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.189994E+09 | 0.144241E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.201043E+09 | 98326364.86 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258256E+09 | 79044544.26 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329816E+09 | 90248668.19 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.367687E+09 | 0.125480E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.389521E+09 | 0.185763E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.328789E+09 | 0.225949E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.275666E+09 | 0.316068E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.351988E+10 | 0.229880E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.189994E+09 | 79044544.26 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.389521E+09 | 0.368793E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.280155E+09 | 0.368793E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.347392E+09 | 0.248395E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.321869E+09 | 0.242832E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.229693E+09 | 0.173658E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.189994E+09 | 0.144241E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.201043E+09 | 98326364.86 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258256E+09 | 79044544.26 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329816E+09 | 90248668.19 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.367687E+09 | 0.125480E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.389521E+09 | 0.185763E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.328789E+09 | 0.225949E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.275666E+09 | 0.316068E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.351988E+10 | 0.229880E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.189994E+09 | 79044544.26 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.389521E+09 | 0.368793E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.380453E+09 | 0.271690E+09 | 0.108762E+09 | 0.338077E+09 | 0.439350E+09 |
February | 0.437770E+09 | 0.314863E+09 | 0.122907E+09 | 0.418887E+09 | 0.296111E+09 |
March | 0.433407E+09 | 0.243461E+09 | 0.189946E+09 | 0.388135E+09 | 0.289512E+09 |
April | 0.337031E+09 | 0.161216E+09 | 0.175815E+09 | 0.276878E+09 | 0.207237E+09 |
May | 0.309355E+09 | 0.102713E+09 | 0.206642E+09 | 0.229063E+09 | 0.172129E+09 |
June | 0.297452E+09 | 86712993.89 | 0.210739E+09 | 0.242033E+09 | 0.117475E+09 |
July | 0.331364E+09 | 0.122361E+09 | 0.209003E+09 | 0.310532E+09 | 94627051.48 |
August | 0.393866E+09 | 0.198570E+09 | 0.195296E+09 | 0.396708E+09 | 0.107982E+09 |
September | 0.422938E+09 | 0.259211E+09 | 0.163727E+09 | 0.442543E+09 | 0.149962E+09 |
October | 0.456854E+09 | 0.315950E+09 | 0.140904E+09 | 0.469147E+09 | 0.221873E+09 |
November | 0.402876E+09 | 0.291803E+09 | 0.111073E+09 | 0.396263E+09 | 0.269556E+09 |
December | 0.361772E+09 | 0.261197E+09 | 0.100575E+09 | 0.332554E+09 | 0.376784E+09 |
Annual Sum or Average | 0.456514E+10 | 0.262975E+10 | 0.193539E+10 | 0.424082E+10 | 0.274260E+10 |
Minimum of Months | 0.297452E+09 | 86712993.89 | 0.100575E+09 | 0.229063E+09 | 94627051.48 |
Maximum of Months | 0.456854E+09 | 0.315950E+09 | 0.210739E+09 | 0.469147E+09 | 0.439350E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.380453E+09 | 0.271690E+09 | 0.108762E+09 | 0.338077E+09 | 0.439350E+09 |
February | 0.437770E+09 | 0.314863E+09 | 0.122907E+09 | 0.418887E+09 | 0.296111E+09 |
March | 0.433407E+09 | 0.243461E+09 | 0.189946E+09 | 0.388135E+09 | 0.289512E+09 |
April | 0.337031E+09 | 0.161216E+09 | 0.175815E+09 | 0.276878E+09 | 0.207237E+09 |
May | 0.309355E+09 | 0.102713E+09 | 0.206642E+09 | 0.229063E+09 | 0.172129E+09 |
June | 0.297452E+09 | 86712993.89 | 0.210739E+09 | 0.242033E+09 | 0.117475E+09 |
July | 0.331364E+09 | 0.122361E+09 | 0.209003E+09 | 0.310532E+09 | 94627051.48 |
August | 0.393866E+09 | 0.198570E+09 | 0.195296E+09 | 0.396708E+09 | 0.107982E+09 |
September | 0.422938E+09 | 0.259211E+09 | 0.163727E+09 | 0.442543E+09 | 0.149962E+09 |
October | 0.456854E+09 | 0.315950E+09 | 0.140904E+09 | 0.469147E+09 | 0.221873E+09 |
November | 0.402876E+09 | 0.291803E+09 | 0.111073E+09 | 0.396263E+09 | 0.269556E+09 |
December | 0.361772E+09 | 0.261197E+09 | 0.100575E+09 | 0.332554E+09 | 0.376784E+09 |
Annual Sum or Average | 0.456514E+10 | 0.262975E+10 | 0.193539E+10 | 0.424082E+10 | 0.274260E+10 |
Minimum of Months | 0.297452E+09 | 86712993.89 | 0.100575E+09 | 0.229063E+09 | 94627051.48 |
Maximum of Months | 0.456854E+09 | 0.315950E+09 | 0.210739E+09 | 0.469147E+09 | 0.439350E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.277129E+09 | 0.382153E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.343122E+09 | 0.260817E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.317322E+09 | 0.258117E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.224293E+09 | 0.188518E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.185674E+09 | 0.154325E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.199256E+09 | 0.101563E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257873E+09 | 80205298.25 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329157E+09 | 91930452.53 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.365509E+09 | 0.130435E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.385288E+09 | 0.195580E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.323682E+09 | 0.239281E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.272537E+09 | 0.328970E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.348084E+10 | 0.241190E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.185674E+09 | 80205298.25 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.385288E+09 | 0.382153E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.277129E+09 | 0.382153E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.343122E+09 | 0.260817E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.317322E+09 | 0.258117E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.224293E+09 | 0.188518E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.185674E+09 | 0.154325E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.199256E+09 | 0.101563E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257873E+09 | 80205298.25 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329157E+09 | 91930452.53 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.365509E+09 | 0.130435E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.385288E+09 | 0.195580E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.323682E+09 | 0.239281E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.272537E+09 | 0.328970E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.348084E+10 | 0.241190E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.185674E+09 | 80205298.25 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.385288E+09 | 0.382153E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.380453E+09 | 0.271690E+09 | 0.108762E+09 | 0.334454E+09 | 0.455182E+09 |
February | 0.437770E+09 | 0.314863E+09 | 0.122907E+09 | 0.413791E+09 | 0.310812E+09 |
March | 0.433407E+09 | 0.243461E+09 | 0.189946E+09 | 0.382685E+09 | 0.307607E+09 |
April | 0.337031E+09 | 0.161216E+09 | 0.175815E+09 | 0.270409E+09 | 0.224848E+09 |
May | 0.309355E+09 | 0.102713E+09 | 0.206642E+09 | 0.223876E+09 | 0.184063E+09 |
June | 0.297452E+09 | 86712993.89 | 0.210739E+09 | 0.239872E+09 | 0.121304E+09 |
July | 0.331364E+09 | 0.122361E+09 | 0.209003E+09 | 0.310049E+09 | 96004018.56 |
August | 0.393866E+09 | 0.198570E+09 | 0.195296E+09 | 0.395907E+09 | 0.109972E+09 |
September | 0.422938E+09 | 0.259211E+09 | 0.163727E+09 | 0.439947E+09 | 0.155812E+09 |
October | 0.456854E+09 | 0.315950E+09 | 0.140904E+09 | 0.464120E+09 | 0.233475E+09 |
November | 0.402876E+09 | 0.291803E+09 | 0.111073E+09 | 0.390191E+09 | 0.285324E+09 |
December | 0.361772E+09 | 0.261197E+09 | 0.100575E+09 | 0.328811E+09 | 0.392043E+09 |
Annual Sum or Average | 0.456514E+10 | 0.262975E+10 | 0.193539E+10 | 0.419411E+10 | 0.287645E+10 |
Minimum of Months | 0.297452E+09 | 86712993.89 | 0.100575E+09 | 0.223876E+09 | 96004018.56 |
Maximum of Months | 0.456854E+09 | 0.315950E+09 | 0.210739E+09 | 0.464120E+09 | 0.455182E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.277910E+09 | 0.373938E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.344214E+09 | 0.254582E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.318331E+09 | 0.251271E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.225095E+09 | 0.184172E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.185935E+09 | 0.152745E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.198556E+09 | 0.104698E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.256401E+09 | 85259749.35 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328099E+09 | 96654683.10 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.364968E+09 | 0.132985E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.385868E+09 | 0.193970E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.324830E+09 | 0.234000E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.273488E+09 | 0.321190E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.348370E+10 | 0.238546E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.185935E+09 | 85259749.35 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.385868E+09 | 0.373938E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.277910E+09 | 0.373938E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.344214E+09 | 0.254582E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.318331E+09 | 0.251271E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.225095E+09 | 0.184172E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.185935E+09 | 0.152745E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.198556E+09 | 0.104698E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.256401E+09 | 85259749.35 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328099E+09 | 96654683.10 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.364968E+09 | 0.132985E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.385868E+09 | 0.193970E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.324830E+09 | 0.234000E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.273488E+09 | 0.321190E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.348370E+10 | 0.238546E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.185935E+09 | 85259749.35 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.385868E+09 | 0.373938E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.333571E+09 | 0.442960E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.412845E+09 | 0.301740E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.381806E+09 | 0.297837E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.269895E+09 | 0.218473E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.222977E+09 | 0.181149E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.237742E+09 | 0.124288E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.306630E+09 | 0.101384E+09 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.392499E+09 | 0.114889E+09 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.436914E+09 | 0.157917E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.462277E+09 | 0.230251E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.389429E+09 | 0.277505E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.328167E+09 | 0.380700E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.417475E+10 | 0.282909E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.222977E+09 | 0.101384E+09 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.462277E+09 | 0.442960E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.278350E+09 | 0.370679E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.344897E+09 | 0.251802E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.319038E+09 | 0.248163E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.225973E+09 | 0.181249E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.186601E+09 | 0.150711E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.198680E+09 | 0.104377E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.256355E+09 | 85438927.74 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328077E+09 | 96731376.64 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.365169E+09 | 0.132312E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.386458E+09 | 0.191887E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.325725E+09 | 0.230833E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.274001E+09 | 0.318125E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.348932E+10 | 0.236231E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.186601E+09 | 85438927.74 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.386458E+09 | 0.370679E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.278350E+09 | 0.370679E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.344897E+09 | 0.251802E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.319038E+09 | 0.248163E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.225973E+09 | 0.181249E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.186601E+09 | 0.150711E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.198680E+09 | 0.104377E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.256355E+09 | 85438927.74 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328077E+09 | 96731376.64 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.365169E+09 | 0.132312E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.386458E+09 | 0.191887E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.325725E+09 | 0.230833E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.274001E+09 | 0.318125E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.348932E+10 | 0.236231E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.186601E+09 | 85438927.74 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.386458E+09 | 0.370679E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.334106E+09 | 0.439077E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.413669E+09 | 0.298435E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.382659E+09 | 0.294144E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.270950E+09 | 0.215002E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.223776E+09 | 0.178733E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.237891E+09 | 0.123906E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.306575E+09 | 0.101597E+09 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.392472E+09 | 0.114979E+09 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.437154E+09 | 0.157118E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.462986E+09 | 0.227778E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.390501E+09 | 0.273743E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.328789E+09 | 0.377052E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.418153E+10 | 0.280156E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.223776E+09 | 0.101597E+09 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.462986E+09 | 0.439077E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.278876E+09 | 0.367976E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.345748E+09 | 0.249271E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.319924E+09 | 0.245274E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.227379E+09 | 0.177674E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.187924E+09 | 0.147822E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.199315E+09 | 0.103033E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.256786E+09 | 84425098.06 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328503E+09 | 95559962.00 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.365847E+09 | 0.130489E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.387634E+09 | 0.188871E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.327126E+09 | 0.227141E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.274597E+09 | 0.315593E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.349966E+10 | 0.233313E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.187924E+09 | 84425098.06 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.387634E+09 | 0.367976E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.278876E+09 | 0.367976E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.345748E+09 | 0.249271E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.319924E+09 | 0.245274E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.227379E+09 | 0.177674E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.187924E+09 | 0.147822E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.199315E+09 | 0.103033E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.256786E+09 | 84425098.06 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328503E+09 | 95559962.00 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.365847E+09 | 0.130489E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.387634E+09 | 0.188871E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.327126E+09 | 0.227141E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.274597E+09 | 0.315593E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.349966E+10 | 0.233313E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.187924E+09 | 84425098.06 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.387634E+09 | 0.367976E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.334745E+09 | 0.435855E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.414693E+09 | 0.295425E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.383728E+09 | 0.290709E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.272636E+09 | 0.210758E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.225367E+09 | 0.175310E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.238657E+09 | 0.122315E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.307095E+09 | 0.100398E+09 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.392988E+09 | 0.113594E+09 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.437971E+09 | 0.154958E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.464396E+09 | 0.224202E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.392177E+09 | 0.269359E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.329511E+09 | 0.374037E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.419396E+10 | 0.276692E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.225367E+09 | 0.100398E+09 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.464396E+09 | 0.435855E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.281243E+09 | 0.358435E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.348938E+09 | 0.241537E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.322733E+09 | 0.237308E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.231139E+09 | 0.169156E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.191494E+09 | 0.140270E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.200871E+09 | 98684346.77 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257166E+09 | 80952323.14 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329190E+09 | 91622117.49 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.367814E+09 | 0.125269E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.391558E+09 | 0.180941E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.330937E+09 | 0.218117E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.277031E+09 | 0.307307E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.353012E+10 | 0.224960E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.191494E+09 | 80952323.14 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.391558E+09 | 0.358435E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.281243E+09 | 0.358435E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.348938E+09 | 0.241537E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.322733E+09 | 0.237308E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.231139E+09 | 0.169156E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.191494E+09 | 0.140270E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.200871E+09 | 98684346.77 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257166E+09 | 80952323.14 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329190E+09 | 91622117.49 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.367814E+09 | 0.125269E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.391558E+09 | 0.180941E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.330937E+09 | 0.218117E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.277031E+09 | 0.307307E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.353012E+10 | 0.224960E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.191494E+09 | 80952323.14 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.391558E+09 | 0.358435E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.281243E+09 | 0.358435E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.348938E+09 | 0.241537E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.322733E+09 | 0.237308E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.231139E+09 | 0.169156E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.191494E+09 | 0.140270E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.200871E+09 | 98684346.77 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257166E+09 | 80952323.14 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329190E+09 | 91622117.49 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.367814E+09 | 0.125269E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.391558E+09 | 0.180941E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.330937E+09 | 0.218117E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.277031E+09 | 0.307307E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.353012E+10 | 0.224960E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.191494E+09 | 80952323.14 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.391558E+09 | 0.358435E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.281243E+09 | 0.358435E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.348938E+09 | 0.241537E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.322733E+09 | 0.237308E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.231139E+09 | 0.169156E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.191494E+09 | 0.140270E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.200871E+09 | 98684346.77 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257166E+09 | 80952323.14 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329190E+09 | 91622117.49 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.367814E+09 | 0.125269E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.391558E+09 | 0.180941E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.330937E+09 | 0.218117E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.277031E+09 | 0.307307E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.353012E+10 | 0.224960E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.191494E+09 | 80952323.14 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.391558E+09 | 0.358435E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.337567E+09 | 0.424610E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.418475E+09 | 0.286301E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.387094E+09 | 0.281323E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.277119E+09 | 0.200684E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.229642E+09 | 0.166396E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.240543E+09 | 0.117180E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.307594E+09 | 96289135.21 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.393844E+09 | 0.108937E+09 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.440319E+09 | 0.148795E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.469040E+09 | 0.214837E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.396702E+09 | 0.258715E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.332413E+09 | 0.364264E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.423035E+10 | 0.266833E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.229642E+09 | 96289135.21 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.469040E+09 | 0.424610E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.337567E+09 | 0.424610E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.418475E+09 | 0.286301E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.387094E+09 | 0.281323E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.277119E+09 | 0.200684E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.229642E+09 | 0.166396E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.240543E+09 | 0.117180E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.307594E+09 | 96289135.21 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.393844E+09 | 0.108937E+09 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.440319E+09 | 0.148795E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.469040E+09 | 0.214837E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.396702E+09 | 0.258715E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.332413E+09 | 0.364264E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.423035E+10 | 0.266833E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.229642E+09 | 96289135.21 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.469040E+09 | 0.424610E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.280181E+09 | 0.360368E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.347846E+09 | 0.242547E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.321883E+09 | 0.237948E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.230446E+09 | 0.169615E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.190975E+09 | 0.140667E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.200949E+09 | 98521107.24 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257816E+09 | 80250939.77 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329490E+09 | 91061046.33 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.367276E+09 | 0.125444E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.390169E+09 | 0.181924E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.329953E+09 | 0.218921E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.276073E+09 | 0.308601E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.352306E+10 | 0.225587E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.190975E+09 | 80250939.77 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.390169E+09 | 0.360368E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.280181E+09 | 0.360368E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.347846E+09 | 0.242547E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.321883E+09 | 0.237948E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.230446E+09 | 0.169615E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.190975E+09 | 0.140667E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.200949E+09 | 98521107.24 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257816E+09 | 80250939.77 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329490E+09 | 91061046.33 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.367276E+09 | 0.125444E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.390169E+09 | 0.181924E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.329953E+09 | 0.218921E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.276073E+09 | 0.308601E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.352306E+10 | 0.225587E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.190975E+09 | 80250939.77 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.390169E+09 | 0.360368E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.336350E+09 | 0.426789E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.417236E+09 | 0.287425E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.386133E+09 | 0.282001E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.276334E+09 | 0.201174E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.229058E+09 | 0.166818E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.240656E+09 | 0.116960E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.308376E+09 | 95445802.73 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.394219E+09 | 0.108252E+09 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.439720E+09 | 0.148964E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.467453E+09 | 0.215946E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.395591E+09 | 0.259597E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.331322E+09 | 0.365707E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.422245E+10 | 0.267508E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.229058E+09 | 95445802.73 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.467453E+09 | 0.426789E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.280317E+09 | 0.359685E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.348100E+09 | 0.241807E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.322140E+09 | 0.237055E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.230852E+09 | 0.168570E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.191421E+09 | 0.139779E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.201288E+09 | 97980458.20 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258069E+09 | 79844015.12 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329711E+09 | 90632384.45 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.367501E+09 | 0.124935E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.390454E+09 | 0.181273E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.330241E+09 | 0.218145E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.276262E+09 | 0.307829E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.352636E+10 | 0.224754E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.191421E+09 | 79844015.12 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.390454E+09 | 0.359685E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.280317E+09 | 0.359685E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.348100E+09 | 0.241807E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.322140E+09 | 0.237055E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.230852E+09 | 0.168570E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.191421E+09 | 0.139779E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.201288E+09 | 97980458.20 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258069E+09 | 79844015.12 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329711E+09 | 90632384.45 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.367501E+09 | 0.124935E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.390454E+09 | 0.181273E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.330241E+09 | 0.218145E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.276262E+09 | 0.307829E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.352636E+10 | 0.224754E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.191421E+09 | 79844015.12 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.390454E+09 | 0.359685E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.336515E+09 | 0.425975E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.417542E+09 | 0.286544E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.386446E+09 | 0.280939E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.276823E+09 | 0.199932E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.229595E+09 | 0.165764E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.241064E+09 | 0.116319E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.308681E+09 | 94962507.58 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.394486E+09 | 0.107743E+09 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.439992E+09 | 0.148360E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.467795E+09 | 0.215173E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.395938E+09 | 0.258675E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.331551E+09 | 0.364787E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.422643E+10 | 0.266517E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.229595E+09 | 94962507.58 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.467795E+09 | 0.425975E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.280793E+09 | 0.356845E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.348920E+09 | 0.238930E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.322919E+09 | 0.233847E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.232100E+09 | 0.164939E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.192816E+09 | 0.136683E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.202307E+09 | 96171920.74 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258568E+09 | 78812666.70 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.330167E+09 | 89492929.98 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.368135E+09 | 0.123267E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.391488E+09 | 0.178722E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.331085E+09 | 0.215531E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.276859E+09 | 0.304888E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.353616E+10 | 0.221813E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.192816E+09 | 78812666.70 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.391488E+09 | 0.356845E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.280793E+09 | 0.356845E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.348920E+09 | 0.238930E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.322919E+09 | 0.233847E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.232100E+09 | 0.164939E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.192816E+09 | 0.136683E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.202307E+09 | 96171920.74 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258568E+09 | 78812666.70 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.330167E+09 | 89492929.98 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.368135E+09 | 0.123267E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.391488E+09 | 0.178722E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.331085E+09 | 0.215531E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.276859E+09 | 0.304888E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.353616E+10 | 0.221813E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.192816E+09 | 78812666.70 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.391488E+09 | 0.356845E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.337095E+09 | 0.422593E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.418532E+09 | 0.283124E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.387393E+09 | 0.277128E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.278322E+09 | 0.195617E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.231270E+09 | 0.162092E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.242288E+09 | 0.114178E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.309283E+09 | 93743976.72 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.395036E+09 | 0.106396E+09 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.440753E+09 | 0.146384E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.469033E+09 | 0.212152E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.396953E+09 | 0.255573E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.332277E+09 | 0.361291E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.423824E+10 | 0.263027E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.231270E+09 | 93743976.72 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.469033E+09 | 0.422593E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.282751E+09 | 0.344901E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.351701E+09 | 0.227437E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.325665E+09 | 0.221016E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.235487E+09 | 0.152507E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.196593E+09 | 0.126285E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.205421E+09 | 89471703.28 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.259882E+09 | 74893484.06 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.331326E+09 | 85254747.62 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.369655E+09 | 0.117591E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.393928E+09 | 0.170797E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.333477E+09 | 0.206339E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.279020E+09 | 0.293038E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.356491E+10 | 0.210953E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.196593E+09 | 74893484.06 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.393928E+09 | 0.344901E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.282751E+09 | 0.344901E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.351701E+09 | 0.227437E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.325665E+09 | 0.221016E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.235487E+09 | 0.152507E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.196593E+09 | 0.126285E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.205421E+09 | 89471703.28 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.259882E+09 | 74893484.06 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.331326E+09 | 85254747.62 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.369655E+09 | 0.117591E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.393928E+09 | 0.170797E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.333477E+09 | 0.206339E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.279020E+09 | 0.293038E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.356491E+10 | 0.210953E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.196593E+09 | 74893484.06 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.393928E+09 | 0.344901E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.339480E+09 | 0.408376E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.421901E+09 | 0.269492E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.390735E+09 | 0.261895E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.282418E+09 | 0.180874E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.235819E+09 | 0.149783E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.246025E+09 | 0.106254E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.310864E+09 | 89111289.67 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.396435E+09 | 0.101390E+09 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.442580E+09 | 0.139678E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.471957E+09 | 0.202780E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.399839E+09 | 0.244690E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.334903E+09 | 0.347227E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.427296E+10 | 0.250155E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.235819E+09 | 89111289.67 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.471957E+09 | 0.408376E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 670.84 | 878.83 | 756.02 | 539.89 | 216.13 | 0.00 | 0.00 |
February | 920.69 | 655.51 | 963.12 | 692.72 | 270.40 | 0.00 | 0.00 |
March | 770.51 | 578.83 | 861.25 | 483.79 | 377.45 | 0.00 | 0.00 |
April | 568.10 | 427.90 | 692.06 | 331.04 | 361.02 | 0.00 | 0.00 |
May | 454.79 | 343.94 | 614.74 | 204.11 | 410.63 | 0.00 | 0.00 |
June | 497.01 | 242.38 | 610.79 | 178.06 | 432.73 | 0.00 | 0.00 |
July | 617.57 | 188.71 | 658.47 | 243.15 | 415.32 | 0.00 | 0.00 |
August | 788.78 | 215.41 | 782.67 | 394.59 | 388.08 | 0.00 | 0.00 |
September | 908.89 | 309.35 | 868.46 | 532.26 | 336.20 | 0.00 | 0.00 |
October | 932.04 | 443.10 | 907.84 | 627.84 | 280.00 | 0.00 | 0.00 |
November | 813.15 | 556.68 | 827.26 | 599.19 | 228.08 | 0.00 | 0.00 |
December | 660.01 | 753.38 | 718.90 | 519.04 | 199.86 | 0.00 | 0.00 |
Annual Sum or Average | 715.41 | 465.51 | 770.47 | 443.83 | 326.64 | 0.00 | 0.00 |
Minimum of Months | 454.79 | 188.71 | 610.79 | 178.06 | 199.86 | 0.00 | 0.00 |
Maximum of Months | 932.04 | 878.83 | 963.12 | 692.72 | 432.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 331.81 | 455.30 | 378.01 | 269.95 | 108.06 | 0.00 | 0.00 |
February | 454.71 | 344.10 | 481.56 | 346.36 | 135.20 | 0.00 | 0.00 |
March | 379.83 | 307.59 | 430.62 | 241.90 | 188.73 | 0.00 | 0.00 |
April | 277.39 | 232.21 | 346.03 | 165.52 | 180.51 | 0.00 | 0.00 |
May | 222.23 | 183.96 | 307.37 | 102.05 | 205.32 | 0.00 | 0.00 |
June | 246.29 | 125.17 | 305.39 | 89.03 | 216.37 | 0.00 | 0.00 |
July | 308.32 | 95.73 | 329.24 | 121.58 | 207.66 | 0.00 | 0.00 |
August | 393.60 | 109.70 | 391.34 | 197.29 | 194.04 | 0.00 | 0.00 |
September | 451.76 | 160.76 | 434.23 | 266.13 | 168.10 | 0.00 | 0.00 |
October | 460.98 | 233.21 | 453.92 | 313.92 | 140.00 | 0.00 | 0.00 |
November | 400.29 | 294.71 | 413.63 | 299.59 | 114.04 | 0.00 | 0.00 |
December | 326.27 | 392.02 | 359.45 | 259.52 | 99.93 | 0.00 | 0.00 |
Annual Sum or Average | 353.75 | 244.17 | 385.23 | 221.91 | 163.32 | 0.00 | 0.00 |
Minimum of Months | 222.23 | 95.73 | 305.39 | 89.03 | 99.93 | 0.00 | 0.00 |
Maximum of Months | 460.98 | 455.30 | 481.56 | 346.36 | 216.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 332.06 | 444.61 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 455.22 | 335.19 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 380.25 | 298.83 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 277.81 | 226.40 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 222.09 | 181.69 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 244.93 | 128.74 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 305.94 | 101.52 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 391.54 | 115.07 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 450.17 | 163.54 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 460.73 | 230.81 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 400.88 | 287.62 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 326.74 | 381.97 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 353.31 | 240.99 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 222.09 | 101.52 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 460.73 | 444.61 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 332.59 | 440.72 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 456.13 | 331.53 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 381.10 | 295.13 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 278.90 | 222.80 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 222.89 | 179.27 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 245.08 | 128.34 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 305.89 | 101.73 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 391.51 | 115.16 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 450.42 | 162.71 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 461.43 | 228.33 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 401.99 | 283.72 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 327.36 | 378.32 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 353.89 | 238.65 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 222.89 | 101.73 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 461.43 | 440.72 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 333.22 | 437.50 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 457.25 | 328.19 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 382.16 | 291.69 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 280.63 | 218.40 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 224.47 | 175.83 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 245.87 | 126.69 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 306.40 | 100.53 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 392.02 | 113.77 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 451.26 | 160.47 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 462.84 | 224.74 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 403.71 | 279.18 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 328.07 | 375.31 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 354.94 | 235.70 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 224.47 | 100.53 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 462.84 | 437.50 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 672.08 | 852.36 | 754.47 | 538.78 | 215.68 | 0.00 | 0.00 |
February | 922.91 | 636.06 | 961.15 | 691.30 | 269.85 | 0.00 | 0.00 |
March | 771.03 | 564.47 | 859.48 | 482.80 | 376.68 | 0.00 | 0.00 |
April | 570.52 | 415.89 | 690.64 | 330.36 | 360.28 | 0.00 | 0.00 |
May | 457.46 | 333.73 | 613.48 | 203.69 | 409.79 | 0.00 | 0.00 |
June | 495.59 | 242.71 | 609.53 | 177.69 | 431.84 | 0.00 | 0.00 |
July | 613.74 | 192.80 | 657.12 | 242.65 | 414.47 | 0.00 | 0.00 |
August | 785.71 | 218.18 | 781.07 | 393.78 | 387.29 | 0.00 | 0.00 |
September | 907.37 | 308.13 | 866.68 | 531.17 | 335.51 | 0.00 | 0.00 |
October | 935.00 | 430.64 | 905.98 | 626.55 | 279.42 | 0.00 | 0.00 |
November | 816.80 | 536.23 | 825.57 | 597.96 | 227.61 | 0.00 | 0.00 |
December | 661.94 | 730.94 | 717.42 | 517.97 | 199.45 | 0.00 | 0.00 |
Annual Sum or Average | 716.04 | 454.56 | 768.89 | 442.92 | 325.97 | 0.00 | 0.00 |
Minimum of Months | 457.46 | 192.80 | 609.53 | 177.69 | 199.45 | 0.00 | 0.00 |
Maximum of Months | 935.00 | 852.36 | 961.15 | 691.30 | 431.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 334.79 | 428.44 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 460.04 | 319.33 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 384.52 | 282.96 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 284.42 | 208.49 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 228.12 | 167.32 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 247.90 | 121.14 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 307.65 | 95.56 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 393.22 | 108.41 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 453.04 | 154.26 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 465.87 | 216.47 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 407.21 | 269.07 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 329.85 | 366.98 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 357.32 | 227.89 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 228.12 | 95.56 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 465.87 | 428.44 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 334.96 | 427.62 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 460.38 | 318.35 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 384.83 | 281.90 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 284.93 | 207.20 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 228.66 | 166.26 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 248.32 | 120.48 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 307.95 | 95.08 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 393.48 | 107.90 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 453.32 | 153.64 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 466.21 | 215.70 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 407.57 | 268.12 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 330.08 | 366.06 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 357.66 | 227.05 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 228.66 | 95.08 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 466.21 | 427.62 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 335.53 | 424.24 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 461.46 | 314.56 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 385.76 | 278.08 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 286.47 | 202.74 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 230.33 | 162.58 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 249.58 | 118.26 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 308.55 | 93.85 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 394.03 | 106.55 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 454.10 | 151.59 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 467.45 | 212.66 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 408.61 | 264.90 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 330.79 | 362.55 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 358.66 | 224.08 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 230.33 | 93.85 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 467.45 | 424.24 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 337.88 | 410.01 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 465.15 | 299.42 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 389.06 | 262.82 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 290.66 | 187.46 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 234.84 | 150.22 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 253.42 | 110.03 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 310.12 | 89.19 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 395.42 | 101.52 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 455.98 | 144.62 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 470.36 | 203.25 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 411.57 | 253.61 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 333.39 | 348.45 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 361.58 | 213.11 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 234.84 | 89.19 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 470.36 | 410.01 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.179677E+10 | 0.235387E+10 | 0.202492E+10 | 0.144605E+10 | 0.578876E+09 | 0.00 | 0.00 |
February | 0.222734E+10 | 0.158580E+10 | 0.232999E+10 | 0.167583E+10 | 0.654159E+09 | 0.00 | 0.00 |
March | 0.206374E+10 | 0.155034E+10 | 0.230677E+10 | 0.129580E+10 | 0.101097E+10 | 0.00 | 0.00 |
April | 0.147253E+10 | 0.110911E+10 | 0.179381E+10 | 0.858059E+09 | 0.935756E+09 | 0.00 | 0.00 |
May | 0.121810E+10 | 0.921219E+09 | 0.164651E+10 | 0.546682E+09 | 0.109983E+10 | 0.00 | 0.00 |
June | 0.128824E+10 | 0.628255E+09 | 0.158316E+10 | 0.461522E+09 | 0.112164E+10 | 0.00 | 0.00 |
July | 0.165409E+10 | 0.505431E+09 | 0.176365E+10 | 0.651256E+09 | 0.111240E+10 | 0.00 | 0.00 |
August | 0.211268E+10 | 0.576958E+09 | 0.209631E+10 | 0.105687E+10 | 0.103944E+10 | 0.00 | 0.00 |
September | 0.235583E+10 | 0.801843E+09 | 0.225105E+10 | 0.137963E+10 | 0.871421E+09 | 0.00 | 0.00 |
October | 0.249638E+10 | 0.118680E+10 | 0.243156E+10 | 0.168161E+10 | 0.749950E+09 | 0.00 | 0.00 |
November | 0.210768E+10 | 0.144291E+10 | 0.214427E+10 | 0.155309E+10 | 0.591174E+09 | 0.00 | 0.00 |
December | 0.176777E+10 | 0.201784E+10 | 0.192550E+10 | 0.139020E+10 | 0.535298E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.225611E+11 | 0.146804E+11 | 0.242975E+11 | 0.139966E+11 | 0.103009E+11 | 0.00 | 0.00 |
Minimum of Months | 0.121810E+10 | 0.505431E+09 | 0.158316E+10 | 0.461522E+09 | 0.535298E+09 | 0.00 | 0.00 |
Maximum of Months | 0.249638E+10 | 0.235387E+10 | 0.243156E+10 | 0.168161E+10 | 0.112164E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.888711E+09 | 0.121949E+10 | 0.101246E+10 | 0.723023E+09 | 0.289438E+09 | 0.00 | 0.00 |
February | 0.110003E+10 | 0.832445E+09 | 0.116499E+10 | 0.837915E+09 | 0.327080E+09 | 0.00 | 0.00 |
March | 0.101733E+10 | 0.823842E+09 | 0.115338E+10 | 0.647898E+09 | 0.505485E+09 | 0.00 | 0.00 |
April | 0.718994E+09 | 0.601882E+09 | 0.896907E+09 | 0.429029E+09 | 0.467878E+09 | 0.00 | 0.00 |
May | 0.595224E+09 | 0.492712E+09 | 0.823257E+09 | 0.273341E+09 | 0.549916E+09 | 0.00 | 0.00 |
June | 0.638384E+09 | 0.324430E+09 | 0.791580E+09 | 0.230761E+09 | 0.560820E+09 | 0.00 | 0.00 |
July | 0.825795E+09 | 0.256414E+09 | 0.881826E+09 | 0.325628E+09 | 0.556198E+09 | 0.00 | 0.00 |
August | 0.105422E+10 | 0.293833E+09 | 0.104816E+10 | 0.528435E+09 | 0.519722E+09 | 0.00 | 0.00 |
September | 0.117096E+10 | 0.416682E+09 | 0.112552E+10 | 0.689814E+09 | 0.435711E+09 | 0.00 | 0.00 |
October | 0.123470E+10 | 0.624636E+09 | 0.121578E+10 | 0.840807E+09 | 0.374975E+09 | 0.00 | 0.00 |
November | 0.103755E+10 | 0.763885E+09 | 0.107213E+10 | 0.776547E+09 | 0.295587E+09 | 0.00 | 0.00 |
December | 0.873885E+09 | 0.104998E+10 | 0.962748E+09 | 0.695099E+09 | 0.267649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111558E+11 | 0.770023E+10 | 0.121488E+11 | 0.699830E+10 | 0.515046E+10 | 0.00 | 0.00 |
Minimum of Months | 0.595224E+09 | 0.256414E+09 | 0.791580E+09 | 0.230761E+09 | 0.267649E+09 | 0.00 | 0.00 |
Maximum of Months | 0.123470E+10 | 0.121949E+10 | 0.121578E+10 | 0.840807E+09 | 0.560820E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.889389E+09 | 0.119084E+10 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.110127E+10 | 0.810903E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.101847E+10 | 0.800377E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.720084E+09 | 0.586817E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.594847E+09 | 0.486638E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.634853E+09 | 0.333684E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.819432E+09 | 0.271904E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.104870E+10 | 0.308198E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.116685E+10 | 0.423887E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.123401E+10 | 0.618191E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.103909E+10 | 0.745504E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.875141E+09 | 0.102308E+10 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111421E+11 | 0.760002E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.594847E+09 | 0.271904E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.123401E+10 | 0.119084E+10 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.890807E+09 | 0.118043E+10 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.110346E+10 | 0.802038E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.102073E+10 | 0.790469E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.722896E+09 | 0.577500E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.596977E+09 | 0.480153E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.635250E+09 | 0.332659E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.819286E+09 | 0.272475E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.104863E+10 | 0.308442E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.116749E+10 | 0.421743E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.123590E+10 | 0.611552E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.104195E+10 | 0.735407E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.876790E+09 | 0.101330E+10 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111602E+11 | 0.752617E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.596977E+09 | 0.272475E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.123590E+10 | 0.118043E+10 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.892497E+09 | 0.117181E+10 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.110619E+10 | 0.793966E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.102357E+10 | 0.781256E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.727393E+09 | 0.566104E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.601213E+09 | 0.470952E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.637286E+09 | 0.328381E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.820666E+09 | 0.269248E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.104999E+10 | 0.304714E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.116966E+10 | 0.415935E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.123966E+10 | 0.601943E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.104643E+10 | 0.723642E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.878705E+09 | 0.100522E+10 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111933E+11 | 0.743317E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.601213E+09 | 0.269248E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.123966E+10 | 0.117181E+10 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.180010E+10 | 0.228296E+10 | 0.202076E+10 | 0.144308E+10 | 0.577688E+09 | 0.00 | 0.00 |
February | 0.223270E+10 | 0.153875E+10 | 0.232520E+10 | 0.167239E+10 | 0.652816E+09 | 0.00 | 0.00 |
March | 0.206512E+10 | 0.151187E+10 | 0.230203E+10 | 0.129314E+10 | 0.100889E+10 | 0.00 | 0.00 |
April | 0.147879E+10 | 0.107799E+10 | 0.179013E+10 | 0.856297E+09 | 0.933834E+09 | 0.00 | 0.00 |
May | 0.122526E+10 | 0.893869E+09 | 0.164313E+10 | 0.545560E+09 | 0.109757E+10 | 0.00 | 0.00 |
June | 0.128457E+10 | 0.629097E+09 | 0.157991E+10 | 0.460574E+09 | 0.111934E+10 | 0.00 | 0.00 |
July | 0.164385E+10 | 0.516387E+09 | 0.176003E+10 | 0.649918E+09 | 0.111011E+10 | 0.00 | 0.00 |
August | 0.210445E+10 | 0.584361E+09 | 0.209201E+10 | 0.105470E+10 | 0.103731E+10 | 0.00 | 0.00 |
September | 0.235189E+10 | 0.798664E+09 | 0.224643E+10 | 0.137680E+10 | 0.869632E+09 | 0.00 | 0.00 |
October | 0.250431E+10 | 0.115344E+10 | 0.242657E+10 | 0.167816E+10 | 0.748410E+09 | 0.00 | 0.00 |
November | 0.211715E+10 | 0.138990E+10 | 0.213986E+10 | 0.154990E+10 | 0.589960E+09 | 0.00 | 0.00 |
December | 0.177295E+10 | 0.195776E+10 | 0.192154E+10 | 0.138734E+10 | 0.534199E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.225811E+11 | 0.143350E+11 | 0.242476E+11 | 0.139679E+11 | 0.102798E+11 | 0.00 | 0.00 |
Minimum of Months | 0.122526E+10 | 0.516387E+09 | 0.157991E+10 | 0.460574E+09 | 0.534199E+09 | 0.00 | 0.00 |
Maximum of Months | 0.250431E+10 | 0.228296E+10 | 0.242657E+10 | 0.167816E+10 | 0.111934E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.896712E+09 | 0.114752E+10 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.111293E+10 | 0.772518E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.102989E+10 | 0.757891E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.737224E+09 | 0.540403E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.611008E+09 | 0.448153E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.642554E+09 | 0.314003E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.824009E+09 | 0.255948E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.105320E+10 | 0.290374E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.117427E+10 | 0.399851E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.124779E+10 | 0.579794E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.105550E+10 | 0.697439E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.883466E+09 | 0.982908E+09 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.112686E+11 | 0.718681E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.611008E+09 | 0.255948E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.124779E+10 | 0.114752E+10 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.897147E+09 | 0.114534E+10 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.111374E+10 | 0.770159E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.103072E+10 | 0.755043E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.738526E+09 | 0.537071E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.612437E+09 | 0.445320E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.643640E+09 | 0.312280E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.824819E+09 | 0.254650E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.105391E+10 | 0.289007E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.117499E+10 | 0.398231E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.124870E+10 | 0.577718E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.105642E+10 | 0.694965E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.884073E+09 | 0.980444E+09 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.112791E+11 | 0.716023E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.612437E+09 | 0.254650E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.124870E+10 | 0.114534E+10 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.898678E+09 | 0.113628E+10 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.111637E+10 | 0.760984E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.103323E+10 | 0.744822E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.742522E+09 | 0.525494E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.616903E+09 | 0.435457E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.646901E+09 | 0.306522E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.826420E+09 | 0.251369E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.105537E+10 | 0.285382E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.117702E+10 | 0.392919E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.125201E+10 | 0.569594E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.105912E+10 | 0.686633E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.885993E+09 | 0.971066E+09 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.113105E+11 | 0.706652E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.616903E+09 | 0.251369E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.125201E+10 | 0.113628E+10 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.904981E+09 | 0.109818E+10 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.112530E+10 | 0.724364E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.104206E+10 | 0.703924E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.753391E+09 | 0.485888E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.629005E+09 | 0.402351E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.656866E+09 | 0.285197E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.830629E+09 | 0.238898E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.105909E+10 | 0.271900E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.118189E+10 | 0.374859E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.125981E+10 | 0.544374E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.106679E+10 | 0.657367E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.892942E+09 | 0.933301E+09 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.114028E+11 | 0.672060E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.629005E+09 | 0.238898E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.125981E+10 | 0.109818E+10 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.8 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -4.9 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.8 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.37 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.04 | 4.91 | 4.56 | 5.04 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.44 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.02 | 4.61 | 4.29 | 7.18 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.07 | 4.37 | 5.43 | 3.41 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.8 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.4 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.40 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.8 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.44 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.15 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.20 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.65 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.64 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.19 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.36 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.25 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.61 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.25 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.37 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.15 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.47 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.15 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.61 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.0 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.6 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.4 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.98 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.5 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.5 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.0 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.17 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.20 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.92 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.00 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.19 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.18 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.19 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.61 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.11 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.58 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.87 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.61 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.17 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.11 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.47 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.15 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.49 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.84 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.60 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.75 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.73 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.09 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.77 | 2.10 | 4.06 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.87 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.80 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.15 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.09 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.388214E+09 | -263098368.6 | 0.00 | 0.00 | 744.00 | 0.00 | -125115176.5 | 59.00 | 0.00 | 0.00 |
February | 0.355153E+09 | -243115406.8 | 0.00 | 0.00 | 672.00 | 0.00 | -112037720.0 | 58.99 | 0.00 | 0.00 |
March | 0.394365E+09 | -270552151.9 | 0.00 | 0.00 | 744.00 | 0.00 | -123812363.6 | 58.99 | 0.00 | 0.00 |
April | 0.366548E+09 | -249353329.8 | 0.00 | 0.00 | 720.00 | 0.00 | -117194978.5 | 58.99 | 0.00 | 0.00 |
May | 0.362028E+09 | -243584797.3 | 0.00 | 0.00 | 744.00 | 0.00 | -118443079.5 | 58.99 | 0.00 | 0.00 |
June | 0.333379E+09 | -223295542.7 | 0.00 | 0.00 | 720.00 | 0.00 | -110083474.5 | 58.99 | 0.00 | 0.00 |
July | 0.327509E+09 | -214925577.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112583417.2 | 58.99 | 0.00 | 0.00 |
August | 0.326869E+09 | -214077911.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112791413.6 | 58.99 | 0.00 | 0.00 |
September | 0.318856E+09 | -207993464.9 | 0.00 | 0.00 | 720.00 | 0.00 | -110862824.5 | 58.99 | 0.00 | 0.00 |
October | 0.340089E+09 | -222680923.1 | 0.00 | 0.00 | 744.00 | 0.00 | -117408425.4 | 59.00 | 0.00 | 0.00 |
November | 0.346495E+09 | -228636173.8 | 0.00 | 0.00 | 720.00 | 0.00 | -117858718.7 | 58.99 | 0.00 | 0.00 |
December | 0.376224E+09 | -251948163.3 | 0.00 | 0.00 | 744.00 | 0.00 | -124275653.1 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.423573E+10 | -.283326E+10 | 8760.00 | -.140247E+10 | 58.99 | |||||
Minimum of Months | 0.318856E+09 | -270552151.9 | 0.00 | 0.00 | 672.00 | 0.00 | -125115176.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.394365E+09 | -207993464.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110083474.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.386156E+09 | -263099181.1 | 0.00 | 0.00 | 744.00 | 0.00 | -123056653.7 | 59.00 | 0.00 | 0.00 |
February | 0.352616E+09 | -243119289.4 | 0.00 | 0.00 | 672.00 | 0.00 | -109496254.6 | 58.99 | 0.00 | 0.00 |
March | 0.391146E+09 | -270554977.3 | 0.00 | 0.00 | 744.00 | 0.00 | -120591092.6 | 58.99 | 0.00 | 0.00 |
April | 0.362876E+09 | -249340641.3 | 0.00 | 0.00 | 720.00 | 0.00 | -113535842.2 | 58.99 | 0.00 | 0.00 |
May | 0.359495E+09 | -243584165.0 | 0.00 | 0.00 | 744.00 | 0.00 | -115910488.1 | 58.99 | 0.00 | 0.00 |
June | 0.332682E+09 | -223287862.5 | 0.00 | 0.00 | 720.00 | 0.00 | -109394579.2 | 59.00 | 0.00 | 0.00 |
July | 0.327348E+09 | -214920798.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112427634.4 | 58.99 | 0.00 | 0.00 |
August | 0.326582E+09 | -214080520.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112501926.3 | 58.99 | 0.00 | 0.00 |
September | 0.317651E+09 | -207991193.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109659748.9 | 58.99 | 0.00 | 0.00 |
October | 0.337503E+09 | -222693669.6 | 0.00 | 0.00 | 744.00 | 0.00 | -114808956.0 | 58.99 | 0.00 | 0.00 |
November | 0.343230E+09 | -228638799.0 | 0.00 | 0.00 | 720.00 | 0.00 | -114590842.8 | 58.99 | 0.00 | 0.00 |
December | 0.373879E+09 | -251962710.2 | 0.00 | 0.00 | 744.00 | 0.00 | -121916201.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.421116E+10 | -.283327E+10 | 8760.00 | -.137789E+10 | 58.99 | |||||
Minimum of Months | 0.317651E+09 | -270554977.3 | 0.00 | 0.00 | 672.00 | 0.00 | -123056653.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.391146E+09 | -207991193.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109394579.2 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.356397E+09 | -231383588.3 | 0.00 | 0.00 | 744.00 | 0.00 | -125013351.2 | 58.99 | 0.00 | 0.00 |
February | 0.325150E+09 | -213949857.8 | 0.00 | 0.00 | 672.00 | 0.00 | -111199763.8 | 59.00 | 0.00 | 0.00 |
March | 0.364166E+09 | -241627797.1 | 0.00 | 0.00 | 744.00 | 0.00 | -122537788.8 | 59.00 | 0.00 | 0.00 |
April | 0.333982E+09 | -219125159.6 | 0.00 | 0.00 | 720.00 | 0.00 | -114856599.9 | 58.99 | 0.00 | 0.00 |
May | 0.332333E+09 | -216054688.9 | 0.00 | 0.00 | 744.00 | 0.00 | -116278012.6 | 59.00 | 0.00 | 0.00 |
June | 0.307302E+09 | -199018461.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108283152.8 | 58.99 | 0.00 | 0.00 |
July | 0.298308E+09 | -187735069.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110573071.0 | 58.99 | 0.00 | 0.00 |
August | 0.302255E+09 | -191359464.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110895874.9 | 58.99 | 0.00 | 0.00 |
September | 0.291492E+09 | -182666447.5 | 0.00 | 0.00 | 720.00 | 0.00 | -108825582.0 | 58.99 | 0.00 | 0.00 |
October | 0.311192E+09 | -195857642.6 | 0.00 | 0.00 | 744.00 | 0.00 | -115334481.1 | 58.99 | 0.00 | 0.00 |
November | 0.317991E+09 | -201864042.7 | 0.00 | 0.00 | 720.00 | 0.00 | -116127043.0 | 58.99 | 0.00 | 0.00 |
December | 0.343839E+09 | -219931453.1 | 0.00 | 0.00 | 744.00 | 0.00 | -123907487.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.388441E+10 | -.250057E+10 | 8760.00 | -.138383E+10 | 58.99 | |||||
Minimum of Months | 0.291492E+09 | -241627797.1 | 0.00 | 0.00 | 672.00 | 0.00 | -125013351.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.364166E+09 | -182666447.5 | 0.00 | 0.00 | 744.00 | 0.00 | -108283152.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.356895E+09 | -231366005.7 | 0.00 | 0.00 | 744.00 | 0.00 | -125528999.2 | 59.00 | 0.00 | 0.00 |
February | 0.325616E+09 | -213954861.3 | 0.00 | 0.00 | 672.00 | 0.00 | -111661235.7 | 58.99 | 0.00 | 0.00 |
March | 0.364706E+09 | -241639343.1 | 0.00 | 0.00 | 744.00 | 0.00 | -123066975.2 | 58.99 | 0.00 | 0.00 |
April | 0.334579E+09 | -219124797.5 | 0.00 | 0.00 | 720.00 | 0.00 | -115454420.3 | 58.99 | 0.00 | 0.00 |
May | 0.332713E+09 | -216084656.6 | 0.00 | 0.00 | 744.00 | 0.00 | -116628311.6 | 58.98 | 0.00 | 0.00 |
June | 0.307362E+09 | -199018598.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108343860.4 | 58.99 | 0.00 | 0.00 |
July | 0.298274E+09 | -187733228.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110540712.2 | 58.99 | 0.00 | 0.00 |
August | 0.302240E+09 | -191356148.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110883828.8 | 58.99 | 0.00 | 0.00 |
September | 0.291620E+09 | -182666255.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108953449.7 | 58.99 | 0.00 | 0.00 |
October | 0.311592E+09 | -195863400.4 | 0.00 | 0.00 | 744.00 | 0.00 | -115728285.6 | 58.99 | 0.00 | 0.00 |
November | 0.318602E+09 | -201859675.2 | 0.00 | 0.00 | 720.00 | 0.00 | -116742191.8 | 59.00 | 0.00 | 0.00 |
December | 0.344316E+09 | -219934748.5 | 0.00 | 0.00 | 744.00 | 0.00 | -124381034.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.388852E+10 | -.250060E+10 | 8760.00 | -.138791E+10 | 58.99 | |||||
Minimum of Months | 0.291620E+09 | -241639343.1 | 0.00 | 0.00 | 672.00 | 0.00 | -125528999.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.364706E+09 | -182666255.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108343860.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.345993E+09 | -218672154.8 | 0.00 | 0.00 | 744.00 | 0.00 | -127321321.4 | 59.00 | 0.00 | 0.00 |
February | 0.315891E+09 | -202328370.3 | 0.00 | 0.00 | 672.00 | 0.00 | -113562151.2 | 58.99 | 0.00 | 0.00 |
March | 0.353653E+09 | -228643128.3 | 0.00 | 0.00 | 744.00 | 0.00 | -125010187.6 | 58.99 | 0.00 | 0.00 |
April | 0.325677E+09 | -207370414.4 | 0.00 | 0.00 | 720.00 | 0.00 | -118306218.8 | 58.99 | 0.00 | 0.00 |
May | 0.323564E+09 | -204331326.4 | 0.00 | 0.00 | 744.00 | 0.00 | -119232755.7 | 58.99 | 0.00 | 0.00 |
June | 0.298032E+09 | -188310997.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109720902.4 | 58.99 | 0.00 | 0.00 |
July | 0.289096E+09 | -177559051.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111536452.7 | 58.99 | 0.00 | 0.00 |
August | 0.293077E+09 | -181120014.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111957290.5 | 58.97 | 0.00 | 0.00 |
September | 0.283425E+09 | -172862245.6 | 0.00 | 0.00 | 720.00 | 0.00 | -110562753.6 | 58.99 | 0.00 | 0.00 |
October | 0.303551E+09 | -185111317.1 | 0.00 | 0.00 | 744.00 | 0.00 | -118439775.4 | 58.99 | 0.00 | 0.00 |
November | 0.310152E+09 | -190667733.8 | 0.00 | 0.00 | 720.00 | 0.00 | -119483797.2 | 58.99 | 0.00 | 0.00 |
December | 0.334051E+09 | -207996133.9 | 0.00 | 0.00 | 744.00 | 0.00 | -126054691.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.377616E+10 | -.236497E+10 | 8760.00 | -.141119E+10 | 58.99 | |||||
Minimum of Months | 0.283425E+09 | -228643128.3 | 0.00 | 0.00 | 672.00 | 0.00 | -127321321.4 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.353653E+09 | -172862245.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109720902.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.345942E+09 | -218672082.9 | 0.00 | 0.00 | 744.00 | 0.00 | -127269460.2 | 59.00 | 0.00 | 0.00 |
February | 0.315821E+09 | -202328273.8 | 0.00 | 0.00 | 672.00 | 0.00 | -113492665.1 | 58.99 | 0.00 | 0.00 |
March | 0.353643E+09 | -228637172.5 | 0.00 | 0.00 | 744.00 | 0.00 | -125005895.8 | 58.99 | 0.00 | 0.00 |
April | 0.325445E+09 | -207346146.9 | 0.00 | 0.00 | 720.00 | 0.00 | -118098752.7 | 59.00 | 0.00 | 0.00 |
May | 0.323325E+09 | -204321060.3 | 0.00 | 0.00 | 744.00 | 0.00 | -119003529.5 | 59.00 | 0.00 | 0.00 |
June | 0.297946E+09 | -188308924.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109636681.3 | 58.99 | 0.00 | 0.00 |
July | 0.289199E+09 | -177533826.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111665007.0 | 59.00 | 0.00 | 0.00 |
August | 0.293153E+09 | -181000266.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112152686.5 | 59.02 | 0.00 | 0.00 |
September | 0.283265E+09 | -172856295.8 | 0.00 | 0.00 | 720.00 | 0.00 | -110408386.6 | 58.99 | 0.00 | 0.00 |
October | 0.303133E+09 | -185103909.6 | 0.00 | 0.00 | 744.00 | 0.00 | -118028702.5 | 58.99 | 0.00 | 0.00 |
November | 0.309998E+09 | -190664068.1 | 0.00 | 0.00 | 720.00 | 0.00 | -119333842.0 | 58.99 | 0.00 | 0.00 |
December | 0.334040E+09 | -207993037.1 | 0.00 | 0.00 | 744.00 | 0.00 | -126047090.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.377491E+10 | -.236477E+10 | 8760.00 | -.141014E+10 | 59.00 | |||||
Minimum of Months | 0.283265E+09 | -228637172.5 | 0.00 | 0.00 | 672.00 | 0.00 | -127269460.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.353643E+09 | -172856295.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109636681.3 | 59.02 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.346035E+09 | -218673412.8 | 0.00 | 0.00 | 744.00 | 0.00 | -127361317.7 | 58.99 | 0.00 | 0.00 |
February | 0.315944E+09 | -202326538.4 | 0.00 | 0.00 | 672.00 | 0.00 | -113617062.4 | 58.99 | 0.00 | 0.00 |
March | 0.353778E+09 | -228645689.8 | 0.00 | 0.00 | 744.00 | 0.00 | -125132176.6 | 58.99 | 0.00 | 0.00 |
April | 0.325640E+09 | -207376236.6 | 0.00 | 0.00 | 720.00 | 0.00 | -118264218.4 | 58.99 | 0.00 | 0.00 |
May | 0.323496E+09 | -204341081.9 | 0.00 | 0.00 | 744.00 | 0.00 | -119155018.1 | 58.99 | 0.00 | 0.00 |
June | 0.298069E+09 | -188306707.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109761914.7 | 58.99 | 0.00 | 0.00 |
July | 0.289264E+09 | -177567649.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111696305.9 | 58.98 | 0.00 | 0.00 |
August | 0.293220E+09 | -181038907.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112181499.4 | 59.00 | 0.00 | 0.00 |
September | 0.283367E+09 | -172854154.9 | 0.00 | 0.00 | 720.00 | 0.00 | -110512626.3 | 58.99 | 0.00 | 0.00 |
October | 0.303273E+09 | -185105566.4 | 0.00 | 0.00 | 744.00 | 0.00 | -118167217.4 | 58.99 | 0.00 | 0.00 |
November | 0.310145E+09 | -190658181.9 | 0.00 | 0.00 | 720.00 | 0.00 | -119486569.4 | 58.99 | 0.00 | 0.00 |
December | 0.334141E+09 | -207996151.0 | 0.00 | 0.00 | 744.00 | 0.00 | -126145107.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.377637E+10 | -.236489E+10 | 8760.00 | -.141148E+10 | 58.99 | |||||
Minimum of Months | 0.283367E+09 | -228645689.8 | 0.00 | 0.00 | 672.00 | 0.00 | -127361317.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.353778E+09 | -172854154.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109761914.7 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 304.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 385.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 417.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 421.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 352.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 317.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 269.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 236.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3965.83 | ||||||||||
Minimum of Months | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.257255E+11 | 61453.37 | 02-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141752E+11 | 61453.37 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113931E+11 | 61453.37 | 02-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.401525E+10 | 61453.37 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.242230E+10 | 61453.37 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 44539641.68 | 4671.48 | 16-JUN-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.243387E+09 | 27902.88 | 20-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125078E+10 | 61453.37 | 10-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.735610E+10 | 61453.37 | 13-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183170E+11 | 61453.37 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.849433E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.257255E+11 | 61453.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.823373E+10 | 32334.82 | 04-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.402028E+10 | 32334.82 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.241812E+10 | 32334.82 | 04-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.551274E+09 | 32334.82 | 29-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.352159E+09 | 26294.31 | 09-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.118057E+09 | 5453.34 | 10-OCT-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161544E+10 | 32334.82 | 27-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.519460E+10 | 32334.82 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.225037E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.823373E+10 | 32334.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.946972E+10 | 32752.20 | 06-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.487305E+10 | 32752.20 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.320768E+10 | 32752.20 | 04-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.796491E+09 | 27126.60 | 29-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.539339E+09 | 32673.43 | 08-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1720867.66 | 1014.76 | 19-SEP-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.242423E+09 | 7766.79 | 10-OCT-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.215358E+10 | 32752.20 | 26-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.632044E+10 | 32752.20 | 03-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.276044E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.946972E+10 | 32752.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.977200E+10 | 32598.32 | 06-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.508410E+10 | 32598.32 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.344543E+10 | 32598.32 | 04-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.904861E+09 | 30982.13 | 29-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.611624E+09 | 32598.32 | 08-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4400476.96 | 1180.43 | 19-SEP-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.292901E+09 | 13096.84 | 10-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.233289E+10 | 32598.32 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.659688E+10 | 32598.32 | 01-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.290451E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.977200E+10 | 32598.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.102396E+11 | 32527.11 | 04-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.543392E+10 | 32527.11 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.384187E+10 | 32527.11 | 04-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113239E+10 | 32527.11 | 29-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.736172E+09 | 32527.11 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18849175.69 | 3311.16 | 20-SEP-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.373968E+09 | 18023.08 | 10-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.261001E+10 | 32527.11 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.702601E+10 | 32527.11 | 01-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.314128E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.102396E+11 | 32527.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.219339E+11 | 59420.49 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125478E+11 | 59420.49 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101370E+11 | 59420.49 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.397315E+10 | 59420.49 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.254556E+10 | 59420.49 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 63689993.19 | 5294.15 | 16-JUN-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.397404E+09 | 33712.70 | 20-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164754E+10 | 59420.49 | 08-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.720663E+10 | 59420.49 | 11-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160746E+11 | 59420.49 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.765273E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.219339E+11 | 59420.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108005E+11 | 30012.00 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.597993E+10 | 30012.00 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.459971E+10 | 30012.00 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163898E+10 | 30012.00 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.104394E+10 | 30012.00 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10291493.05 | 1825.04 | 16-JUN-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.109971E+09 | 17351.34 | 20-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.609131E+09 | 30012.00 | 08-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.321016E+10 | 30012.00 | 11-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.769473E+10 | 30012.00 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.356973E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108005E+11 | 30012.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.109097E+11 | 29797.67 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.607645E+10 | 29797.67 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.472460E+10 | 29797.67 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172458E+10 | 29797.67 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109685E+10 | 29797.67 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13267850.42 | 1993.56 | 16-JUN-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.122308E+09 | 19075.21 | 20-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.641209E+09 | 29797.67 | 08-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.329727E+10 | 29797.67 | 11-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.780674E+10 | 29797.67 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.364130E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.109097E+11 | 29797.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113386E+11 | 29432.09 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.644295E+10 | 29432.09 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.515758E+10 | 29432.09 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202342E+10 | 29432.09 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.128004E+10 | 29432.09 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 27427192.22 | 2395.72 | 16-JUN-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.170689E+09 | 25511.13 | 20-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.753791E+09 | 29432.09 | 08-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.358588E+10 | 29432.09 | 10-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.821128E+10 | 29432.09 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.389916E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113386E+11 | 29432.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.137323E+11 | 30917.69 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.805036E+10 | 30917.69 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.687920E+10 | 30917.69 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.308890E+10 | 30917.69 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.190630E+10 | 30917.69 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 81984687.88 | 18244.34 | 17-JUN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1581567.69 | 2954.75 | 18-AUG-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.329609E+09 | 30917.69 | 19-SEP-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110670E+10 | 30917.69 | 04-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.455086E+10 | 30917.69 | 02-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.986771E+10 | 30917.69 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.495955E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.137323E+11 | 30917.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1038.41 | 1038.41 | 0.23 | 27-FEB-15:30 | 0.23 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 78136340.39 | 78136340.39 | 4645.54 | 07-APR-14:00 | 4645.54 | 0.00 |
May | 0.00 | 0.00 | 0.184004E+10 | 0.182484E+10 | 13607.91 | 20-MAY-16:10 | 13607.91 | 0.00 |
June | 0.00 | 0.00 | 0.732350E+10 | 0.694958E+10 | 24970.70 | 22-JUN-07:03 | 18555.37 | 0.00 |
July | 0.00 | 0.00 | 0.144701E+11 | 0.140201E+11 | 34614.82 | 19-JUL-07:02 | 23420.06 | 0.00 |
August | 0.00 | 0.00 | 0.118450E+11 | 0.117409E+11 | 31894.10 | 10-AUG-07:02 | 31894.10 | 0.00 |
September | 0.00 | 0.00 | 0.658170E+10 | 0.618798E+10 | 32822.04 | 07-SEP-07:02 | 20810.09 | 0.00 |
October | 0.00 | 0.00 | 0.796668E+09 | 0.796668E+09 | 11555.49 | 18-OCT-14:00 | 11555.49 | 0.00 |
November | 0.00 | 0.00 | 1743.16 | 1743.16 | 0.27 | 04-NOV-17:10 | 0.27 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.429351E+11 | 0.415982E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.144701E+11 | 0.140201E+11 | 34614.82 | 31894.10 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 48576.06 | 48576.06 | 23.90 | 15-JAN-22:00 | 23.90 | 0.00 |
February | 0.00 | 0.00 | 6450077.04 | 6450077.04 | 1429.37 | 26-FEB-18:10 | 1429.37 | 0.00 |
March | 0.00 | 0.00 | 1601843.59 | 1601843.59 | 207.18 | 29-MAR-22:10 | 207.18 | 0.00 |
April | 0.00 | 0.00 | 0.126946E+09 | 0.126946E+09 | 17377.73 | 16-APR-17:07 | 17377.73 | 0.00 |
May | 0.00 | 0.00 | 0.148118E+10 | 0.147253E+10 | 17713.85 | 20-MAY-18:17 | 17713.85 | 0.00 |
June | 0.00 | 0.00 | 0.498648E+10 | 0.479691E+10 | 18542.91 | 21-JUN-20:02 | 15000.65 | 0.00 |
July | 0.00 | 0.00 | 0.918186E+10 | 0.895444E+10 | 19096.60 | 18-JUL-21:58 | 10935.32 | 0.00 |
August | 0.00 | 0.00 | 0.753637E+10 | 0.749499E+10 | 17951.98 | 08-AUG-22:54 | 16598.75 | 0.00 |
September | 0.00 | 0.00 | 0.407223E+10 | 0.388314E+10 | 18840.07 | 06-SEP-20:02 | 13215.47 | 0.00 |
October | 0.00 | 0.00 | 0.557142E+09 | 0.557142E+09 | 17377.73 | 21-OCT-18:02 | 17377.73 | 0.00 |
November | 0.00 | 0.00 | 18977613.30 | 18977613.30 | 17377.73 | 04-NOV-22:31 | 17377.73 | 0.00 |
December | 0.00 | 0.00 | 213578.94 | 213578.94 | 82.56 | 10-DEC-20:40 | 82.56 | 0.00 |
Annual Sum or Average | 0.279695E+11 | 0.273134E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 48576.06 | 48576.06 | 23.90 | 23.90 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.918186E+10 | 0.895444E+10 | 19096.60 | 17713.85 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 9506.18 | 9506.18 | 12.86 | 27-FEB-16:50 | 12.86 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 72999945.51 | 72999945.51 | 3887.15 | 07-APR-14:00 | 3887.15 | 0.00 |
May | 0.00 | 0.00 | 0.907847E+09 | 0.906496E+09 | 8215.53 | 20-MAY-16:00 | 8215.53 | 0.00 |
June | 0.00 | 0.00 | 0.358325E+10 | 0.347691E+10 | 18183.60 | 22-JUN-06:02 | 12380.90 | 0.00 |
July | 0.00 | 0.00 | 0.678002E+10 | 0.666053E+10 | 18874.71 | 19-JUL-06:02 | 12869.82 | 0.00 |
August | 0.00 | 0.00 | 0.563376E+10 | 0.561191E+10 | 17577.56 | 06-AUG-07:02 | 17577.56 | 0.00 |
September | 0.00 | 0.00 | 0.290428E+10 | 0.277194E+10 | 18089.14 | 07-SEP-06:02 | 11554.46 | 0.00 |
October | 0.00 | 0.00 | 0.430084E+09 | 0.430084E+09 | 7138.32 | 18-OCT-14:00 | 7138.32 | 0.00 |
November | 0.00 | 0.00 | 8333.07 | 8333.07 | 3.23 | 05-NOV-13:40 | 3.23 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.203123E+11 | 0.199309E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.678002E+10 | 0.666053E+10 | 18874.71 | 17577.56 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 2003.66 | 2003.66 | 0.16 | 27-FEB-12:20 | 0.16 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 64290749.50 | 64290749.50 | 3691.87 | 07-APR-14:00 | 3691.87 | 0.00 |
May | 0.00 | 0.00 | 0.880140E+09 | 0.878922E+09 | 8168.27 | 20-MAY-16:00 | 8168.27 | 0.00 |
June | 0.00 | 0.00 | 0.356316E+10 | 0.345756E+10 | 18242.95 | 22-JUN-06:02 | 12422.76 | 0.00 |
July | 0.00 | 0.00 | 0.679714E+10 | 0.667679E+10 | 18937.00 | 19-JUL-06:02 | 12919.73 | 0.00 |
August | 0.00 | 0.00 | 0.564078E+10 | 0.561896E+10 | 17637.92 | 06-AUG-07:02 | 17637.92 | 0.00 |
September | 0.00 | 0.00 | 0.289414E+10 | 0.276138E+10 | 18148.73 | 07-SEP-06:02 | 11597.44 | 0.00 |
October | 0.00 | 0.00 | 0.405919E+09 | 0.405919E+09 | 7052.57 | 18-OCT-14:00 | 7052.57 | 0.00 |
November | 0.00 | 0.00 | 50415.24 | 50415.24 | 33.68 | 05-NOV-15:00 | 33.68 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.202456E+11 | 0.198639E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.679714E+10 | 0.667679E+10 | 18937.00 | 17637.92 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1318.69 | 1318.69 | 0.14 | 27-FEB-15:30 | 0.14 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 48615235.35 | 48615235.35 | 3260.38 | 07-APR-14:00 | 3260.38 | 0.00 |
May | 0.00 | 0.00 | 0.804208E+09 | 0.803310E+09 | 7925.14 | 20-MAY-16:00 | 7925.14 | 0.00 |
June | 0.00 | 0.00 | 0.341073E+10 | 0.331070E+10 | 18036.29 | 22-JUN-06:02 | 12251.31 | 0.00 |
July | 0.00 | 0.00 | 0.660025E+10 | 0.648553E+10 | 18724.03 | 19-JUL-06:02 | 12747.95 | 0.00 |
August | 0.00 | 0.00 | 0.546186E+10 | 0.544204E+10 | 17436.41 | 06-AUG-07:02 | 17436.41 | 0.00 |
September | 0.00 | 0.00 | 0.278062E+10 | 0.265228E+10 | 17944.71 | 07-SEP-06:02 | 11441.42 | 0.00 |
October | 0.00 | 0.00 | 0.356282E+09 | 0.356282E+09 | 6790.26 | 18-OCT-14:00 | 6790.26 | 0.00 |
November | 0.00 | 0.00 | 35205.35 | 35205.35 | 22.95 | 03-NOV-18:10 | 22.95 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.194626E+11 | 0.190988E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.660025E+10 | 0.648553E+10 | 18724.03 | 17436.41 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 115.62 | 115.62 | 0.08 | 27-FEB-15:30 | 0.08 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 31025337.40 | 31025337.40 | 3070.86 | 07-APR-14:10 | 3070.86 | 0.00 |
May | 0.00 | 0.00 | 0.104699E+10 | 0.104038E+10 | 12226.55 | 20-MAY-16:00 | 12226.55 | 0.00 |
June | 0.00 | 0.00 | 0.518578E+10 | 0.493249E+10 | 24156.23 | 22-JUN-07:03 | 18112.56 | 0.00 |
July | 0.00 | 0.00 | 0.103051E+11 | 0.100230E+11 | 32909.06 | 19-JUL-07:02 | 22892.15 | 0.00 |
August | 0.00 | 0.00 | 0.857078E+10 | 0.850193E+10 | 30998.51 | 09-AUG-07:03 | 28544.10 | 0.00 |
September | 0.00 | 0.00 | 0.437926E+10 | 0.408139E+10 | 31310.81 | 07-SEP-07:02 | 19961.17 | 0.00 |
October | 0.00 | 0.00 | 0.466329E+09 | 0.466329E+09 | 9912.02 | 18-OCT-14:30 | 9912.02 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.299852E+11 | 0.290765E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.103051E+11 | 0.100230E+11 | 32909.06 | 28544.10 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 465.35 | 465.35 | 0.12 | 27-FEB-15:10 | 0.12 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 17484889.60 | 17484889.60 | 2043.20 | 07-APR-14:00 | 2043.20 | 0.00 |
May | 0.00 | 0.00 | 0.589708E+09 | 0.589196E+09 | 6949.86 | 20-MAY-16:00 | 6949.86 | 0.00 |
June | 0.00 | 0.00 | 0.287147E+10 | 0.277531E+10 | 9831.77 | 22-JUN-07:03 | 7542.62 | 0.00 |
July | 0.00 | 0.00 | 0.572170E+10 | 0.561987E+10 | 16942.37 | 19-JUL-07:02 | 11689.46 | 0.00 |
August | 0.00 | 0.00 | 0.470919E+10 | 0.469382E+10 | 15878.85 | 06-AUG-08:62 | 15878.85 | 0.00 |
September | 0.00 | 0.00 | 0.231867E+10 | 0.219915E+10 | 16115.32 | 07-SEP-07:02 | 10199.86 | 0.00 |
October | 0.00 | 0.00 | 0.240413E+09 | 0.240413E+09 | 5839.68 | 18-OCT-14:40 | 5839.68 | 0.00 |
November | 0.00 | 0.00 | 491.67 | 491.67 | 0.12 | 04-NOV-13:30 | 0.12 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.164686E+11 | 0.161352E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.572170E+10 | 0.561987E+10 | 16942.37 | 15878.85 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 9572.31 | 9572.31 | 11.42 | 27-FEB-14:10 | 11.42 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 15315195.97 | 15315195.97 | 1930.24 | 07-APR-14:00 | 1930.24 | 0.00 |
May | 0.00 | 0.00 | 0.569308E+09 | 0.568828E+09 | 6846.38 | 20-MAY-16:00 | 6846.38 | 0.00 |
June | 0.00 | 0.00 | 0.281426E+10 | 0.271983E+10 | 8877.25 | 22-JUN-07:03 | 6831.98 | 0.00 |
July | 0.00 | 0.00 | 0.564119E+10 | 0.554114E+10 | 16798.95 | 19-JUL-07:02 | 11578.45 | 0.00 |
August | 0.00 | 0.00 | 0.464213E+10 | 0.462712E+10 | 15742.74 | 06-AUG-08:62 | 15742.74 | 0.00 |
September | 0.00 | 0.00 | 0.228321E+10 | 0.216516E+10 | 15979.21 | 07-SEP-07:02 | 10102.71 | 0.00 |
October | 0.00 | 0.00 | 0.232017E+09 | 0.232017E+09 | 5751.55 | 18-OCT-14:40 | 5751.55 | 0.00 |
November | 0.00 | 0.00 | 355.09 | 355.09 | 0.09 | 04-NOV-15:50 | 0.09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.161974E+11 | 0.158694E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.564119E+10 | 0.554114E+10 | 16798.95 | 15742.74 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 98.80 | 98.80 | 0.06 | 27-FEB-15:20 | 0.06 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 9795962.37 | 9795962.37 | 1602.39 | 07-APR-14:00 | 1602.39 | 0.00 |
May | 0.00 | 0.00 | 0.513047E+09 | 0.512658E+09 | 6593.27 | 20-MAY-16:00 | 6593.27 | 0.00 |
June | 0.00 | 0.00 | 0.267380E+10 | 0.258333E+10 | 8238.09 | 29-JUN-15:00 | 8238.09 | 0.00 |
July | 0.00 | 0.00 | 0.547828E+10 | 0.538193E+10 | 16623.53 | 19-JUL-07:02 | 11428.52 | 0.00 |
August | 0.00 | 0.00 | 0.450441E+10 | 0.449021E+10 | 15573.97 | 06-AUG-08:62 | 15573.97 | 0.00 |
September | 0.00 | 0.00 | 0.220413E+10 | 0.208912E+10 | 15596.05 | 06-SEP-07:02 | 10375.60 | 0.00 |
October | 0.00 | 0.00 | 0.205995E+09 | 0.205995E+09 | 5507.67 | 18-OCT-14:40 | 5507.67 | 0.00 |
November | 0.00 | 0.00 | 3563.22 | 3563.22 | 5.42 | 04-NOV-15:10 | 5.42 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.155894E+11 | 0.152730E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.547828E+10 | 0.538193E+10 | 16623.53 | 15573.97 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 2422677.87 | 2422677.87 | 866.41 | 07-APR-14:00 | 866.41 | 0.00 |
May | 0.00 | 0.00 | 0.431294E+09 | 0.431043E+09 | 6241.68 | 20-MAY-16:00 | 6241.68 | 0.00 |
June | 0.00 | 0.00 | 0.248821E+10 | 0.240338E+10 | 8135.39 | 29-JUN-15:00 | 8135.39 | 0.00 |
July | 0.00 | 0.00 | 0.536604E+10 | 0.527562E+10 | 16766.21 | 17-JUL-07:02 | 15339.22 | 0.00 |
August | 0.00 | 0.00 | 0.439879E+10 | 0.438626E+10 | 16133.23 | 07-AUG-07:02 | 16133.23 | 0.00 |
September | 0.00 | 0.00 | 0.211152E+10 | 0.200536E+10 | 16369.02 | 04-SEP-08:62 | 16369.02 | 0.00 |
October | 0.00 | 0.00 | 0.167433E+09 | 0.167433E+09 | 5230.94 | 18-OCT-14:40 | 5230.94 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.149657E+11 | 0.146715E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.536604E+10 | 0.527562E+10 | 16766.21 | 16369.02 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.210695E+10 | 0.50 | 2153.81 | 02-JAN-08:61 | 1.01 |
February | 0.171350E+10 | 0.47 | 2153.81 | 01-FEB-08:61 | 1.01 |
March | 0.180666E+10 | 0.45 | 2153.81 | 02-MAR-08:61 | 1.01 |
April | 0.160106E+10 | 0.43 | 2153.81 | 01-APR-07:01 | 1.01 |
May | 0.161414E+10 | 0.42 | 2153.81 | 01-MAY-07:01 | 1.01 |
June | 0.151880E+10 | 0.41 | 1509.98 | 22-JUN-07:03 | 0.84 |
July | 0.160700E+10 | 0.42 | 2153.81 | 16-JUL-07:02 | 0.99 |
August | 0.160260E+10 | 0.42 | 2153.81 | 06-AUG-07:02 | 1.00 |
September | 0.154522E+10 | 0.42 | 2153.81 | 04-SEP-07:02 | 1.00 |
October | 0.158945E+10 | 0.42 | 2153.81 | 10-OCT-07:01 | 1.00 |
November | 0.166566E+10 | 0.44 | 2153.81 | 13-NOV-08:61 | 1.01 |
December | 0.195527E+10 | 0.48 | 2153.81 | 01-DEC-08:61 | 1.01 |
Annual Sum or Average | 0.203263E+11 | 0.44 | |||
Minimum of Months | 0.151880E+10 | 0.41 | 1509.98 | 0.84 | |
Maximum of Months | 0.210695E+10 | 0.50 | 2153.81 | 1.01 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.168234E+10 | 0.58 | 1235.05 | 01-JAN-16:20 | 1.04 |
February | 0.153248E+10 | 0.58 | 1235.05 | 01-FEB-21:00 | 1.04 |
March | 0.170956E+10 | 0.58 | 1235.05 | 03-MAR-18:50 | 1.04 |
April | 0.174911E+10 | 0.65 | 1235.05 | 07-APR-10:30 | 1.04 |
May | 0.191055E+10 | 0.66 | 1235.05 | 01-MAY-11:50 | 1.04 |
June | 0.196452E+10 | 0.66 | 1235.05 | 07-JUN-10:40 | 1.04 |
July | 0.201140E+10 | 0.65 | 1235.05 | 05-JUL-07:30 | 1.03 |
August | 0.202598E+10 | 0.65 | 1235.05 | 02-AUG-14:40 | 1.04 |
September | 0.197504E+10 | 0.68 | 1235.05 | 01-SEP-08:70 | 1.03 |
October | 0.191158E+10 | 0.69 | 1235.05 | 04-OCT-16:10 | 1.04 |
November | 0.171639E+10 | 0.63 | 1235.05 | 04-NOV-10:20 | 1.04 |
December | 0.166926E+10 | 0.55 | 1235.05 | 02-DEC-17:40 | 1.04 |
Annual Sum or Average | 0.218582E+11 | 0.63 | |||
Minimum of Months | 0.153248E+10 | 0.55 | 1235.05 | 1.03 | |
Maximum of Months | 0.202598E+10 | 0.69 | 1235.05 | 1.04 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.178802E+10 | 0.56 | 1235.50 | 01-JAN-09:50 | 1.04 |
February | 0.161900E+10 | 0.56 | 1235.50 | 01-FEB-17:50 | 1.04 |
March | 0.182360E+10 | 0.57 | 1235.50 | 03-MAR-14:30 | 1.04 |
April | 0.173465E+10 | 0.56 | 1235.50 | 12-APR-07:40 | 1.04 |
May | 0.180581E+10 | 0.57 | 1235.50 | 01-MAY-07:01 | 1.04 |
June | 0.176133E+10 | 0.57 | 1235.50 | 01-JUN-15:00 | 1.03 |
July | 0.177912E+10 | 0.56 | 1235.50 | 02-JUL-08:63 | 1.03 |
August | 0.182360E+10 | 0.57 | 1235.50 | 01-AUG-14:20 | 1.03 |
September | 0.173465E+10 | 0.56 | 1235.50 | 02-SEP-08:30 | 1.03 |
October | 0.178802E+10 | 0.56 | 1235.50 | 05-OCT-07:20 | 1.04 |
November | 0.173465E+10 | 0.56 | 1235.50 | 10-NOV-09:20 | 1.04 |
December | 0.177912E+10 | 0.56 | 1235.50 | 01-DEC-11:30 | 1.04 |
Annual Sum or Average | 0.211716E+11 | 0.56 | |||
Minimum of Months | 0.161900E+10 | 0.56 | 1235.50 | 1.03 | |
Maximum of Months | 0.182360E+10 | 0.57 | 1235.50 | 1.04 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.179379E+10 | 0.56 | 1239.49 | 01-JAN-09:02 | 1.04 |
February | 0.162423E+10 | 0.56 | 1239.49 | 01-FEB-07:07 | 1.04 |
March | 0.182949E+10 | 0.57 | 1239.49 | 01-MAR-08:06 | 1.04 |
April | 0.174025E+10 | 0.56 | 1239.49 | 25-APR-11:50 | 1.04 |
May | 0.181164E+10 | 0.57 | 1239.49 | 01-MAY-06:30 | 1.04 |
June | 0.176702E+10 | 0.57 | 1239.49 | 01-JUN-13:20 | 1.03 |
July | 0.178487E+10 | 0.56 | 1239.49 | 01-JUL-08:40 | 1.03 |
August | 0.182949E+10 | 0.57 | 1239.49 | 20-AUG-12:20 | 1.03 |
September | 0.174025E+10 | 0.56 | 1239.49 | 01-SEP-06:03 | 1.03 |
October | 0.179379E+10 | 0.56 | 1239.49 | 02-OCT-12:00 | 1.04 |
November | 0.174025E+10 | 0.56 | 1239.49 | 02-NOV-07:17 | 1.04 |
December | 0.178487E+10 | 0.56 | 1239.49 | 01-DEC-08:03 | 1.04 |
Annual Sum or Average | 0.212400E+11 | 0.56 | |||
Minimum of Months | 0.162423E+10 | 0.56 | 1239.49 | 1.03 | |
Maximum of Months | 0.182949E+10 | 0.57 | 1239.49 | 1.04 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.177414E+10 | 0.56 | 1225.85 | 01-JAN-17:00 | 1.04 |
February | 0.160635E+10 | 0.56 | 1225.85 | 08-FEB-07:30 | 1.04 |
March | 0.180935E+10 | 0.57 | 1225.85 | 07-MAR-11:00 | 1.04 |
April | 0.172109E+10 | 0.56 | 1225.85 | 05-APR-08:17 | 1.04 |
May | 0.179170E+10 | 0.57 | 1225.85 | 02-MAY-13:20 | 1.03 |
June | 0.174757E+10 | 0.57 | 1225.85 | 04-JUN-09:20 | 1.03 |
July | 0.176522E+10 | 0.56 | 1225.85 | 04-JUL-07:08 | 1.03 |
August | 0.180935E+10 | 0.57 | 1225.85 | 12-AUG-11:50 | 1.04 |
September | 0.172109E+10 | 0.56 | 1225.85 | 12-SEP-14:20 | 1.03 |
October | 0.177405E+10 | 0.56 | 1225.85 | 02-OCT-13:10 | 1.04 |
November | 0.172109E+10 | 0.56 | 1225.85 | 04-NOV-15:20 | 1.04 |
December | 0.176522E+10 | 0.56 | 1225.85 | 01-DEC-08:30 | 1.04 |
Annual Sum or Average | 0.210062E+11 | 0.56 | |||
Minimum of Months | 0.160635E+10 | 0.56 | 1225.85 | 1.03 | |
Maximum of Months | 0.180935E+10 | 0.57 | 1225.85 | 1.04 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.154658E+10 | 0.38 | 2045.03 | 01-JAN-09:01 | 1.01 |
February | 0.124857E+10 | 0.35 | 2045.03 | 01-FEB-08:61 | 1.01 |
March | 0.132542E+10 | 0.35 | 2045.03 | 01-MAR-08:61 | 1.00 |
April | 0.114219E+10 | 0.32 | 2045.03 | 01-APR-07:01 | 1.01 |
May | 0.115688E+10 | 0.32 | 2045.03 | 01-MAY-07:01 | 1.01 |
June | 0.107958E+10 | 0.31 | 1460.95 | 22-JUN-07:03 | 0.85 |
July | 0.111794E+10 | 0.31 | 2045.03 | 16-JUL-08:62 | 0.99 |
August | 0.114479E+10 | 0.31 | 2045.03 | 06-AUG-08:62 | 1.00 |
September | 0.108315E+10 | 0.31 | 2045.03 | 03-SEP-08:62 | 1.00 |
October | 0.112656E+10 | 0.31 | 2045.03 | 08-OCT-08:61 | 1.00 |
November | 0.120896E+10 | 0.33 | 2045.03 | 11-NOV-09:01 | 1.01 |
December | 0.141874E+10 | 0.36 | 2045.03 | 01-DEC-08:61 | 1.01 |
Annual Sum or Average | 0.145994E+11 | 0.33 | |||
Minimum of Months | 0.107958E+10 | 0.31 | 1460.95 | 0.85 | |
Maximum of Months | 0.154658E+10 | 0.38 | 2045.03 | 1.01 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.145844E+10 | 0.53 | 1091.11 | 02-JAN-08:30 | 1.04 |
February | 0.131980E+10 | 0.52 | 1091.11 | 03-FEB-08:03 | 1.04 |
March | 0.148870E+10 | 0.53 | 1091.11 | 01-MAR-19:20 | 1.04 |
April | 0.141407E+10 | 0.52 | 1091.11 | 01-APR-07:40 | 1.04 |
May | 0.147299E+10 | 0.52 | 1091.11 | 01-MAY-16:50 | 1.04 |
June | 0.143764E+10 | 0.53 | 1091.11 | 01-JUN-14:50 | 1.03 |
July | 0.144942E+10 | 0.51 | 1091.11 | 01-JUL-07:40 | 1.03 |
August | 0.148870E+10 | 0.53 | 1091.11 | 01-AUG-17:50 | 1.03 |
September | 0.141407E+10 | 0.52 | 1091.11 | 08-SEP-10:00 | 1.04 |
October | 0.145728E+10 | 0.52 | 1091.11 | 03-OCT-08:20 | 1.04 |
November | 0.141407E+10 | 0.52 | 1091.11 | 02-NOV-07:30 | 1.04 |
December | 0.144961E+10 | 0.52 | 1091.11 | 01-DEC-17:40 | 1.04 |
Annual Sum or Average | 0.172648E+11 | 0.52 | |||
Minimum of Months | 0.131980E+10 | 0.51 | 1091.11 | 1.03 | |
Maximum of Months | 0.148870E+10 | 0.53 | 1091.11 | 1.04 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.144507E+10 | 0.53 | 1080.81 | 02-JAN-11:50 | 1.04 |
February | 0.130735E+10 | 0.52 | 1080.81 | 15-FEB-11:50 | 1.04 |
March | 0.147466E+10 | 0.53 | 1080.81 | 25-MAR-13:40 | 1.04 |
April | 0.140073E+10 | 0.52 | 1080.81 | 02-APR-08:50 | 1.04 |
May | 0.145909E+10 | 0.52 | 1080.81 | 02-MAY-07:50 | 1.04 |
June | 0.142407E+10 | 0.53 | 1080.81 | 08-JUN-18:10 | 1.04 |
July | 0.143575E+10 | 0.51 | 1080.81 | 31-JUL-15:40 | 1.04 |
August | 0.147466E+10 | 0.53 | 1080.81 | 05-AUG-12:10 | 1.03 |
September | 0.140073E+10 | 0.52 | 1080.81 | 07-SEP-08:20 | 1.03 |
October | 0.144353E+10 | 0.52 | 1080.81 | 07-OCT-12:20 | 1.03 |
November | 0.140073E+10 | 0.52 | 1080.81 | 02-NOV-15:40 | 1.04 |
December | 0.143595E+10 | 0.52 | 1080.81 | 02-DEC-12:00 | 1.04 |
Annual Sum or Average | 0.171023E+11 | 0.52 | |||
Minimum of Months | 0.130735E+10 | 0.51 | 1080.81 | 1.03 | |
Maximum of Months | 0.147466E+10 | 0.53 | 1080.81 | 1.04 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.142959E+10 | 0.53 | 1068.39 | 01-JAN-09:07 | 1.04 |
February | 0.129246E+10 | 0.52 | 1068.39 | 01-FEB-08:04 | 1.04 |
March | 0.145781E+10 | 0.53 | 1068.39 | 01-MAR-08:02 | 1.04 |
April | 0.138464E+10 | 0.52 | 1068.39 | 07-APR-12:10 | 1.04 |
May | 0.144233E+10 | 0.52 | 1068.39 | 23-MAY-16:20 | 1.04 |
June | 0.140772E+10 | 0.53 | 1068.39 | 07-JUN-14:50 | 1.04 |
July | 0.141926E+10 | 0.51 | 1068.39 | 01-JUL-09:00 | 1.03 |
August | 0.145772E+10 | 0.53 | 1068.39 | 15-AUG-19:15 | 1.03 |
September | 0.138464E+10 | 0.52 | 1068.39 | 12-SEP-10:10 | 1.03 |
October | 0.142695E+10 | 0.52 | 1068.39 | 23-OCT-11:20 | 1.04 |
November | 0.138464E+10 | 0.52 | 1068.39 | 01-NOV-07:02 | 1.04 |
December | 0.141958E+10 | 0.52 | 1068.39 | 06-DEC-11:30 | 1.04 |
Annual Sum or Average | 0.169073E+11 | 0.52 | |||
Minimum of Months | 0.129246E+10 | 0.51 | 1068.39 | 1.03 | |
Maximum of Months | 0.145781E+10 | 0.53 | 1068.39 | 1.04 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.152555E+10 | 0.60 | 1124.81 | 10-JAN-18:40 | 1.05 |
February | 0.136536E+10 | 0.55 | 1124.81 | 03-FEB-08:08 | 1.04 |
March | 0.153924E+10 | 0.55 | 1124.81 | 01-MAR-09:15 | 1.04 |
April | 0.145776E+10 | 0.52 | 1124.81 | 01-APR-12:10 | 1.04 |
May | 0.151850E+10 | 0.52 | 1124.81 | 03-MAY-14:40 | 1.04 |
June | 0.148205E+10 | 0.53 | 1124.81 | 05-JUN-10:10 | 1.04 |
July | 0.149420E+10 | 0.51 | 1124.81 | 15-JUL-14:50 | 1.03 |
August | 0.153469E+10 | 0.53 | 1124.81 | 02-AUG-18:40 | 1.04 |
September | 0.145776E+10 | 0.52 | 1124.81 | 02-SEP-13:20 | 1.03 |
October | 0.150230E+10 | 0.52 | 1124.81 | 03-OCT-18:20 | 1.04 |
November | 0.145858E+10 | 0.52 | 1124.81 | 01-NOV-08:10 | 1.04 |
December | 0.149844E+10 | 0.54 | 1124.81 | 04-DEC-16:50 | 1.04 |
Annual Sum or Average | 0.178344E+11 | 0.53 | |||
Minimum of Months | 0.136536E+10 | 0.51 | 1124.81 | 1.03 | |
Maximum of Months | 0.153924E+10 | 0.60 | 1124.81 | 1.05 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.36 | 0.24 |
February | 1.07 | 0.64 |
March | 0.85 | 0.61 |
April | 0.28 | 0.75 |
May | 0.00 | 0.00 |
June | 0.17 | 0.75 |
July | 0.17 | 0.00 |
August | 0.75 | 1.00 |
September | 0.42 | 1.20 |
October | 0.28 | 1.20 |
November | 0.33 | 0.75 |
December | 0.51 | 0.47 |
Annual Sum or Average | 6.17 | 0.64 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.36 | 1.20 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.42 | 4.00 |
February | 0.83 | 6.75 |
March | 2.04 | 4.59 |
April | 1.60 | 4.60 |
May | 3.18 | 4.29 |
June | 4.72 | 3.27 |
July | 3.90 | 2.60 |
August | 4.92 | 2.65 |
September | 3.69 | 3.91 |
October | 0.76 | 4.98 |
November | 1.03 | 3.64 |
December | 0.79 | 5.21 |
Annual Sum or Average | 27.90 | 3.67 |
Minimum of Months | 0.42 | 2.60 |
Maximum of Months | 4.92 | 6.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.26 | 0.00 |
February | 0.25 | 0.00 |
March | 0.00 | 0.00 |
April | 0.86 | 0.75 |
May | 1.28 | 0.75 |
June | 1.47 | 0.75 |
July | 2.49 | 0.72 |
August | 2.38 | 0.72 |
September | 1.85 | 0.75 |
October | 0.86 | 0.68 |
November | 1.17 | 0.59 |
December | 0.19 | 0.00 |
Annual Sum or Average | 13.07 | 0.68 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.49 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.37 | 0.00 |
February | 0.25 | 0.00 |
March | 0.07 | 0.00 |
April | 0.65 | 0.75 |
May | 1.53 | 0.63 |
June | 1.47 | 0.75 |
July | 2.40 | 0.72 |
August | 2.38 | 0.72 |
September | 1.85 | 0.75 |
October | 0.72 | 0.66 |
November | 1.33 | 0.47 |
December | 0.21 | 0.00 |
Annual Sum or Average | 13.25 | 0.64 |
Minimum of Months | 0.07 | 0.00 |
Maximum of Months | 2.40 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.49 | 0.00 |
February | 0.25 | 0.00 |
March | 0.07 | 0.00 |
April | 0.61 | 0.75 |
May | 0.95 | 0.75 |
June | 1.47 | 0.75 |
July | 2.35 | 0.72 |
August | 2.30 | 0.72 |
September | 1.73 | 0.75 |
October | 0.97 | 0.69 |
November | 0.44 | 0.47 |
December | 0.21 | 0.00 |
Annual Sum or Average | 11.84 | 0.66 |
Minimum of Months | 0.07 | 0.00 |
Maximum of Months | 2.35 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.49 | 0.00 |
February | 0.32 | 0.00 |
March | 0.34 | 0.00 |
April | 0.00 | 0.00 |
May | 0.17 | 3.30 |
June | 0.39 | 3.30 |
July | 1.02 | 2.85 |
August | 1.12 | 1.91 |
September | 0.70 | 3.30 |
October | 0.06 | 0.00 |
November | 0.12 | 0.00 |
December | 0.41 | 0.00 |
Annual Sum or Average | 6.14 | 1.51 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.49 | 3.30 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.98 | 0.00 |
February | 0.23 | 0.00 |
March | 0.25 | 0.00 |
April | 0.00 | 0.00 |
May | 0.17 | 1.65 |
June | 0.56 | 1.65 |
July | 0.99 | 1.42 |
August | 1.18 | 0.91 |
September | 0.79 | 1.65 |
October | 0.08 | 0.00 |
November | 0.12 | 0.00 |
December | 0.32 | 0.00 |
Annual Sum or Average | 5.69 | 0.88 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.18 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.01 | 0.00 |
February | 0.23 | 0.00 |
March | 0.34 | 0.00 |
April | 0.00 | 0.00 |
May | 0.17 | 1.65 |
June | 0.48 | 1.65 |
July | 0.85 | 1.54 |
August | 1.18 | 0.91 |
September | 0.79 | 1.65 |
October | 0.08 | 0.00 |
November | 0.12 | 0.00 |
December | 0.32 | 0.00 |
Annual Sum or Average | 5.57 | 0.85 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.18 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.68 | 0.00 |
February | 0.44 | 0.00 |
March | 0.42 | 0.00 |
April | 0.00 | 0.00 |
May | 0.17 | 1.65 |
June | 0.48 | 1.65 |
July | 0.85 | 1.54 |
August | 1.01 | 1.06 |
September | 0.79 | 1.65 |
October | 0.00 | 0.00 |
November | 0.23 | 0.00 |
December | 0.57 | 0.00 |
Annual Sum or Average | 6.64 | 0.72 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.68 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.37 | 0.00 |
February | 2.04 | 0.00 |
March | 0.81 | 0.00 |
April | 0.25 | 0.00 |
May | 0.34 | 0.84 |
June | 0.39 | 1.65 |
July | 0.85 | 1.54 |
August | 1.01 | 1.06 |
September | 0.79 | 1.65 |
October | 0.00 | 0.00 |
November | 0.92 | 0.00 |
December | 2.13 | 0.00 |
Annual Sum or Average | 12.91 | 0.36 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.37 | 1.65 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.210695E+10 | 0.321569E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.171350E+10 | 0.177190E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.180666E+10 | 0.142414E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.162231E+10 | 0.501906E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.208896E+10 | 0.302788E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.337758E+10 | 55674552.10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.532625E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.465037E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.320590E+10 | 0.304234E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.179291E+10 | 0.156348E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.166566E+10 | 0.919512E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.195527E+10 | 0.228963E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.313123E+11 | 0.106179E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.162231E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.532625E+10 | 0.321569E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.168235E+10 | 0.102922E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.153422E+10 | 0.502535E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.171001E+10 | 0.302265E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.177762E+10 | 0.689093E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.222932E+10 | 0.440199E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.304343E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.404640E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.369597E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.286302E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.203324E+10 | 0.147572E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.172125E+10 | 0.201930E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.166932E+10 | 0.649325E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.280061E+11 | 0.281296E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.153422E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.404640E+10 | 0.102922E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.178802E+10 | 0.118371E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.161901E+10 | 0.609131E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.182360E+10 | 0.400960E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.175155E+10 | 0.995613E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.200794E+10 | 0.674173E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.255335E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.330501E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.309089E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.237516E+10 | 2151084.57 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.188332E+10 | 0.303029E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.173465E+10 | 0.269198E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.177912E+10 | 0.790055E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.257116E+11 | 0.345055E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.161901E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.330501E+10 | 0.118371E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.179379E+10 | 0.122150E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.162423E+10 | 0.635513E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.182949E+10 | 0.430679E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.175522E+10 | 0.113108E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.200806E+10 | 0.764530E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.255542E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.331483E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.309871E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.237885E+10 | 5500596.20 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.188394E+10 | 0.366127E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.174026E+10 | 0.291611E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.178487E+10 | 0.824610E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.257677E+11 | 0.363064E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.162423E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.331483E+10 | 0.122150E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.177414E+10 | 0.127995E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.160635E+10 | 0.679240E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.180935E+10 | 0.480233E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.173252E+10 | 0.141549E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.197216E+10 | 0.920215E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.250473E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.325441E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.304103E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.233592E+10 | 23561469.61 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.185345E+10 | 0.467460E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.172110E+10 | 0.326251E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.176522E+10 | 0.878251E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.253704E+11 | 0.392660E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.160635E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.325441E+10 | 0.127995E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.154658E+10 | 0.274174E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.124857E+10 | 0.156847E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.132542E+10 | 0.126713E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.115079E+10 | 0.496644E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.143240E+10 | 0.318195E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.241530E+10 | 79612491.48 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.380056E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.337319E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.219414E+10 | 0.496755E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.124755E+10 | 0.205943E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.120896E+10 | 0.900828E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.141874E+10 | 0.200932E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.223622E+11 | 0.956591E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.115079E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.380056E+10 | 0.274174E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.145844E+10 | 0.135006E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.131980E+10 | 0.747491E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.148870E+10 | 0.574963E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.141828E+10 | 0.204873E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.160742E+10 | 0.130493E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.208183E+10 | 12864366.31 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.275272E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.256048E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.192966E+10 | 0.137464E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.151136E+10 | 0.761413E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.141407E+10 | 0.401270E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.144961E+10 | 0.961841E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.209924E+11 | 0.446216E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.131980E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.275272E+10 | 0.135006E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.144507E+10 | 0.136371E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.130735E+10 | 0.759556E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.147466E+10 | 0.590575E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.140442E+10 | 0.215572E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.158913E+10 | 0.137106E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.205619E+10 | 16584813.02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.272169E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.253193E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.190874E+10 | 0.152885E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.149578E+10 | 0.801511E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.140073E+10 | 0.412159E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.143595E+10 | 0.975842E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.207716E+11 | 0.455162E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.130735E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.272169E+10 | 0.136371E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.142959E+10 | 0.141732E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.129246E+10 | 0.805369E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.145781E+10 | 0.644698E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.138702E+10 | 0.252928E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.156035E+10 | 0.160005E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.201081E+10 | 34283990.28 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.267099E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.248587E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.187597E+10 | 0.213362E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.147356E+10 | 0.942239E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.138464E+10 | 0.448235E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.141958E+10 | 0.102641E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.204487E+11 | 0.487395E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.129246E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.267099E+10 | 0.141732E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.152555E+10 | 0.171654E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.136536E+10 | 0.100629E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.153924E+10 | 0.859900E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.145836E+10 | 0.386112E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.161968E+10 | 0.238287E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.205184E+10 | 0.102481E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.273023E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.254653E+10 | 1976959.62 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.193225E+10 | 0.412012E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.154060E+10 | 0.138338E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.145858E+10 | 0.568857E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.149844E+10 | 0.123346E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.212667E+11 | 0.619944E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.136536E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.273023E+10 | 0.171654E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.210695E+10 | 0.00 | 0.257255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.171350E+10 | 1038.41 | 0.141752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180666E+10 | 0.00 | 0.113931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160106E+10 | 78136340.39 | 0.401525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161414E+10 | 0.184004E+10 | 0.242230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151880E+10 | 0.732350E+10 | 44539641.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160700E+10 | 0.144701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160260E+10 | 0.118450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154522E+10 | 0.658170E+10 | 0.243387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158945E+10 | 0.796668E+09 | 0.125078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166566E+10 | 1743.16 | 0.735610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195527E+10 | 0.00 | 0.183170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203263E+11 | 0.429351E+11 | 0.849433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.210695E+10 | 0.144701E+11 | 0.257255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.168234E+10 | 48576.06 | 0.823373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153248E+10 | 6450077.04 | 0.402028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170956E+10 | 1601843.59 | 0.241812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174911E+10 | 0.126946E+09 | 0.551274E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.191055E+10 | 0.148118E+10 | 0.352159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.196452E+10 | 0.498648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.201140E+10 | 0.918186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.202598E+10 | 0.753637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.197504E+10 | 0.407223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.191158E+10 | 0.557142E+09 | 0.118057E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171639E+10 | 18977613.30 | 0.161544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166926E+10 | 213578.94 | 0.519460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218582E+11 | 0.279695E+11 | 0.225037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153248E+10 | 48576.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.202598E+10 | 0.918186E+10 | 0.823373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.178802E+10 | 0.00 | 0.946972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161900E+10 | 9506.18 | 0.487305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182360E+10 | 0.00 | 0.320768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173465E+10 | 72999945.51 | 0.796491E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.180581E+10 | 0.907847E+09 | 0.539339E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.176133E+10 | 0.358325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.177912E+10 | 0.678002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.182360E+10 | 0.563376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.173465E+10 | 0.290428E+10 | 1720867.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.178802E+10 | 0.430084E+09 | 0.242423E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173465E+10 | 8333.07 | 0.215358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177912E+10 | 0.00 | 0.632044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211716E+11 | 0.203123E+11 | 0.276044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.161900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182360E+10 | 0.678002E+10 | 0.946972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.179379E+10 | 0.00 | 0.977200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162423E+10 | 2003.66 | 0.508410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182949E+10 | 0.00 | 0.344543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174025E+10 | 64290749.50 | 0.904861E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181164E+10 | 0.880140E+09 | 0.611624E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.176702E+10 | 0.356316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.178487E+10 | 0.679714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.182949E+10 | 0.564078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174025E+10 | 0.289414E+10 | 4400476.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.179379E+10 | 0.405919E+09 | 0.292901E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174025E+10 | 50415.24 | 0.233289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178487E+10 | 0.00 | 0.659688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212400E+11 | 0.202456E+11 | 0.290451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.162423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182949E+10 | 0.679714E+10 | 0.977200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.177414E+10 | 0.00 | 0.102396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160635E+10 | 1318.69 | 0.543392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180935E+10 | 0.00 | 0.384187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172109E+10 | 48615235.35 | 0.113239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179170E+10 | 0.804208E+09 | 0.736172E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174757E+10 | 0.341073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176522E+10 | 0.660025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180935E+10 | 0.546186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172109E+10 | 0.278062E+10 | 18849175.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177405E+10 | 0.356282E+09 | 0.373968E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172109E+10 | 35205.35 | 0.261001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176522E+10 | 0.00 | 0.702601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210062E+11 | 0.194626E+11 | 0.314128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.160635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.180935E+10 | 0.660025E+10 | 0.102396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.154658E+10 | 0.00 | 0.219339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124857E+10 | 115.62 | 0.125478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132542E+10 | 0.00 | 0.101370E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.114219E+10 | 31025337.40 | 0.397315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115688E+10 | 0.104699E+10 | 0.254556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107958E+10 | 0.518578E+10 | 63689993.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111794E+10 | 0.103051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.114479E+10 | 0.857078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108315E+10 | 0.437926E+10 | 0.397404E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112656E+10 | 0.466329E+09 | 0.164754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120896E+10 | 0.00 | 0.720663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141874E+10 | 0.00 | 0.160746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145994E+11 | 0.299852E+11 | 0.765273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.107958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154658E+10 | 0.103051E+11 | 0.219339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.145844E+10 | 0.00 | 0.108005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131980E+10 | 465.35 | 0.597993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148870E+10 | 0.00 | 0.459971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141407E+10 | 17484889.60 | 0.163898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147299E+10 | 0.589708E+09 | 0.104394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143764E+10 | 0.287147E+10 | 10291493.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144942E+10 | 0.572170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.148870E+10 | 0.470919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141407E+10 | 0.231867E+10 | 0.109971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145728E+10 | 0.240413E+09 | 0.609131E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141407E+10 | 491.67 | 0.321016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144961E+10 | 0.00 | 0.769473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172648E+11 | 0.164686E+11 | 0.356973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.148870E+10 | 0.572170E+10 | 0.108005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.144507E+10 | 0.00 | 0.109097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130735E+10 | 9572.31 | 0.607645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147466E+10 | 0.00 | 0.472460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140073E+10 | 15315195.97 | 0.172458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145909E+10 | 0.569308E+09 | 0.109685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142407E+10 | 0.281426E+10 | 13267850.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143575E+10 | 0.564119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147466E+10 | 0.464213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140073E+10 | 0.228321E+10 | 0.122308E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144353E+10 | 0.232017E+09 | 0.641209E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140073E+10 | 355.09 | 0.329727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143595E+10 | 0.00 | 0.780674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171023E+11 | 0.161974E+11 | 0.364130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147466E+10 | 0.564119E+10 | 0.109097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.142959E+10 | 0.00 | 0.113386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129246E+10 | 98.80 | 0.644295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145781E+10 | 0.00 | 0.515758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138464E+10 | 9795962.37 | 0.202342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144233E+10 | 0.513047E+09 | 0.128004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140772E+10 | 0.267380E+10 | 27427192.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141926E+10 | 0.547828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145772E+10 | 0.450441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138464E+10 | 0.220413E+10 | 0.170689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142695E+10 | 0.205995E+09 | 0.753791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138464E+10 | 3563.22 | 0.358588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141958E+10 | 0.00 | 0.821128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169073E+11 | 0.155894E+11 | 0.389916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145781E+10 | 0.547828E+10 | 0.113386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.152555E+10 | 0.00 | 0.137323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136536E+10 | 0.00 | 0.805036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153924E+10 | 0.00 | 0.687920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145776E+10 | 2422677.87 | 0.308890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151850E+10 | 0.431294E+09 | 0.190630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148205E+10 | 0.248821E+10 | 81984687.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149420E+10 | 0.536604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153469E+10 | 0.439879E+10 | 1581567.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145776E+10 | 0.211152E+10 | 0.329609E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150230E+10 | 0.167433E+09 | 0.110670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145858E+10 | 0.00 | 0.455086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149844E+10 | 0.00 | 0.986771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178344E+11 | 0.149657E+11 | 0.495955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153924E+10 | 0.536604E+10 | 0.137323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.210695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.171350E+10 | 0.00 | 0.00 | 0.00 | 293.52 | 0.00 | 0.177190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160106E+10 | 0.00 | 0.00 | 0.00 | 21250830.97 | 0.00 | 0.501906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161414E+10 | 0.00 | 0.00 | 0.00 | 0.474821E+09 | 0.00 | 0.302788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151880E+10 | 0.00 | 0.00 | 0.00 | 0.185879E+10 | 0.00 | 55674552.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160700E+10 | 0.00 | 0.00 | 0.00 | 0.371925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160260E+10 | 0.00 | 0.00 | 0.00 | 0.304777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154522E+10 | 0.00 | 0.00 | 0.00 | 0.166068E+10 | 0.00 | 0.304234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158945E+10 | 0.00 | 0.00 | 0.00 | 0.203457E+09 | 0.00 | 0.156348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166566E+10 | 0.00 | 0.00 | 0.00 | 492.73 | 0.00 | 0.919512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203263E+11 | 0.00 | 0.00 | 0.00 | 0.109860E+11 | 0.00 | 0.106179E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.151880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.210695E+10 | 0.00 | 0.00 | 0.00 | 0.371925E+10 | 0.00 | 0.321569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.168234E+10 | 0.00 | 0.00 | 0.00 | 13619.61 | 0.00 | 0.102922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153248E+10 | 0.00 | 0.00 | 0.00 | 1749757.47 | 0.00 | 0.502535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170956E+10 | 0.00 | 0.00 | 0.00 | 446876.46 | 0.00 | 0.302265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174911E+10 | 0.00 | 0.00 | 0.00 | 28508756.07 | 0.00 | 0.689093E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.191055E+10 | 0.00 | 0.00 | 0.00 | 0.318763E+09 | 0.00 | 0.440199E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.196452E+10 | 0.00 | 0.00 | 0.00 | 0.107891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.201140E+10 | 0.00 | 0.00 | 0.00 | 0.203500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.202598E+10 | 0.00 | 0.00 | 0.00 | 0.166999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.197504E+10 | 0.00 | 0.00 | 0.00 | 0.887977E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.191158E+10 | 0.00 | 0.00 | 0.00 | 0.121659E+09 | 0.00 | 0.147572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171639E+10 | 0.00 | 0.00 | 0.00 | 4864883.07 | 0.00 | 0.201930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166926E+10 | 0.00 | 0.00 | 0.00 | 59817.87 | 0.00 | 0.649325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218582E+11 | 0.00 | 0.00 | 0.00 | 0.614794E+10 | 0.00 | 0.281296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.153248E+10 | 0.00 | 0.00 | 0.00 | 13619.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.202598E+10 | 0.00 | 0.00 | 0.00 | 0.203500E+10 | 0.00 | 0.102922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.178802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161900E+10 | 0.00 | 0.00 | 0.00 | 2342.07 | 0.00 | 0.609131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173465E+10 | 0.00 | 0.00 | 0.00 | 16902635.93 | 0.00 | 0.995613E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.180581E+10 | 0.00 | 0.00 | 0.00 | 0.202127E+09 | 0.00 | 0.674173E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.176133E+10 | 0.00 | 0.00 | 0.00 | 0.792017E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.177912E+10 | 0.00 | 0.00 | 0.00 | 0.152588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.182360E+10 | 0.00 | 0.00 | 0.00 | 0.126729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.173465E+10 | 0.00 | 0.00 | 0.00 | 0.640517E+09 | 0.00 | 2151084.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.178802E+10 | 0.00 | 0.00 | 0.00 | 95297896.15 | 0.00 | 0.303029E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173465E+10 | 0.00 | 0.00 | 0.00 | 2053.69 | 0.00 | 0.269198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.790055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211716E+11 | 0.00 | 0.00 | 0.00 | 0.454004E+10 | 0.00 | 0.345055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.161900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182360E+10 | 0.00 | 0.00 | 0.00 | 0.152588E+10 | 0.00 | 0.118371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.179379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162423E+10 | 0.00 | 0.00 | 0.00 | 493.82 | 0.00 | 0.635513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174025E+10 | 0.00 | 0.00 | 0.00 | 14968437.19 | 0.00 | 0.113108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181164E+10 | 0.00 | 0.00 | 0.00 | 0.196422E+09 | 0.00 | 0.764530E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.176702E+10 | 0.00 | 0.00 | 0.00 | 0.788397E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.178487E+10 | 0.00 | 0.00 | 0.00 | 0.152996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.182949E+10 | 0.00 | 0.00 | 0.00 | 0.126922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174025E+10 | 0.00 | 0.00 | 0.00 | 0.638604E+09 | 0.00 | 5500596.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.179379E+10 | 0.00 | 0.00 | 0.00 | 90146311.94 | 0.00 | 0.366127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174025E+10 | 0.00 | 0.00 | 0.00 | 12413.99 | 0.00 | 0.291611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212400E+11 | 0.00 | 0.00 | 0.00 | 0.452772E+10 | 0.00 | 0.363064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.162423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182949E+10 | 0.00 | 0.00 | 0.00 | 0.152996E+10 | 0.00 | 0.122150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.177414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160635E+10 | 0.00 | 0.00 | 0.00 | 325.00 | 0.00 | 0.679240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172109E+10 | 0.00 | 0.00 | 0.00 | 11436385.44 | 0.00 | 0.141549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179170E+10 | 0.00 | 0.00 | 0.00 | 0.180466E+09 | 0.00 | 0.920215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174757E+10 | 0.00 | 0.00 | 0.00 | 0.757165E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176522E+10 | 0.00 | 0.00 | 0.00 | 0.148919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180935E+10 | 0.00 | 0.00 | 0.00 | 0.123169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172109E+10 | 0.00 | 0.00 | 0.00 | 0.614831E+09 | 0.00 | 23561469.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177405E+10 | 0.00 | 0.00 | 0.00 | 79408804.59 | 0.00 | 0.467460E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172109E+10 | 0.00 | 0.00 | 0.00 | 8671.22 | 0.00 | 0.326251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.878251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210062E+11 | 0.00 | 0.00 | 0.00 | 0.436419E+10 | 0.00 | 0.392660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.160635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.180935E+10 | 0.00 | 0.00 | 0.00 | 0.148919E+10 | 0.00 | 0.127995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.154658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124857E+10 | 0.00 | 0.00 | 0.00 | 32.68 | 0.00 | 0.156847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.114219E+10 | 0.00 | 0.00 | 0.00 | 8599728.82 | 0.00 | 0.496644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115688E+10 | 0.00 | 0.00 | 0.00 | 0.275519E+09 | 0.00 | 0.318195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107958E+10 | 0.00 | 0.00 | 0.00 | 0.133573E+10 | 0.00 | 79612491.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111794E+10 | 0.00 | 0.00 | 0.00 | 0.268262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.114479E+10 | 0.00 | 0.00 | 0.00 | 0.222840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108315E+10 | 0.00 | 0.00 | 0.00 | 0.111099E+10 | 0.00 | 0.496755E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112656E+10 | 0.00 | 0.00 | 0.00 | 0.120989E+09 | 0.00 | 0.205943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.900828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145994E+11 | 0.00 | 0.00 | 0.00 | 0.776285E+10 | 0.00 | 0.956591E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.107958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154658E+10 | 0.00 | 0.00 | 0.00 | 0.268262E+10 | 0.00 | 0.274174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.145844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131980E+10 | 0.00 | 0.00 | 0.00 | 114.69 | 0.00 | 0.747491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141407E+10 | 0.00 | 0.00 | 0.00 | 4204471.49 | 0.00 | 0.204873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147299E+10 | 0.00 | 0.00 | 0.00 | 0.134431E+09 | 0.00 | 0.130493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143764E+10 | 0.00 | 0.00 | 0.00 | 0.644193E+09 | 0.00 | 12864366.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144942E+10 | 0.00 | 0.00 | 0.00 | 0.130329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.148870E+10 | 0.00 | 0.00 | 0.00 | 0.107178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141407E+10 | 0.00 | 0.00 | 0.00 | 0.515592E+09 | 0.00 | 0.137464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145728E+10 | 0.00 | 0.00 | 0.00 | 54083346.57 | 0.00 | 0.761413E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141407E+10 | 0.00 | 0.00 | 0.00 | 121.18 | 0.00 | 0.401270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172648E+11 | 0.00 | 0.00 | 0.00 | 0.372758E+10 | 0.00 | 0.446216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.131980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.148870E+10 | 0.00 | 0.00 | 0.00 | 0.130329E+10 | 0.00 | 0.135006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.144507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130735E+10 | 0.00 | 0.00 | 0.00 | 2358.35 | 0.00 | 0.759556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.590575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140073E+10 | 0.00 | 0.00 | 0.00 | 3691746.80 | 0.00 | 0.215572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145909E+10 | 0.00 | 0.00 | 0.00 | 0.130041E+09 | 0.00 | 0.137106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142407E+10 | 0.00 | 0.00 | 0.00 | 0.632112E+09 | 0.00 | 16584813.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143575E+10 | 0.00 | 0.00 | 0.00 | 0.128595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147466E+10 | 0.00 | 0.00 | 0.00 | 0.105727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140073E+10 | 0.00 | 0.00 | 0.00 | 0.508009E+09 | 0.00 | 0.152885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144353E+10 | 0.00 | 0.00 | 0.00 | 52250915.25 | 0.00 | 0.801511E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140073E+10 | 0.00 | 0.00 | 0.00 | 87.52 | 0.00 | 0.412159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.975842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171023E+11 | 0.00 | 0.00 | 0.00 | 0.366932E+10 | 0.00 | 0.455162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.130735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147466E+10 | 0.00 | 0.00 | 0.00 | 0.128595E+10 | 0.00 | 0.136371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.142959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129246E+10 | 0.00 | 0.00 | 0.00 | 24.35 | 0.00 | 0.805369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138464E+10 | 0.00 | 0.00 | 0.00 | 2380398.22 | 0.00 | 0.252928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144233E+10 | 0.00 | 0.00 | 0.00 | 0.118012E+09 | 0.00 | 0.160005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140772E+10 | 0.00 | 0.00 | 0.00 | 0.603098E+09 | 0.00 | 34283990.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141926E+10 | 0.00 | 0.00 | 0.00 | 0.125174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145772E+10 | 0.00 | 0.00 | 0.00 | 0.102816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138464E+10 | 0.00 | 0.00 | 0.00 | 0.491332E+09 | 0.00 | 0.213362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142695E+10 | 0.00 | 0.00 | 0.00 | 46610856.02 | 0.00 | 0.942239E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138464E+10 | 0.00 | 0.00 | 0.00 | 878.02 | 0.00 | 0.448235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169073E+11 | 0.00 | 0.00 | 0.00 | 0.354133E+10 | 0.00 | 0.487395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.129246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145781E+10 | 0.00 | 0.00 | 0.00 | 0.125174E+10 | 0.00 | 0.141732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.152555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.859900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145776E+10 | 0.00 | 0.00 | 0.00 | 602657.89 | 0.00 | 0.386112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151850E+10 | 0.00 | 0.00 | 0.00 | 0.101185E+09 | 0.00 | 0.238287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148205E+10 | 0.00 | 0.00 | 0.00 | 0.569791E+09 | 0.00 | 0.102481E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149420E+10 | 0.00 | 0.00 | 0.00 | 0.123603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153469E+10 | 0.00 | 0.00 | 0.00 | 0.101183E+10 | 0.00 | 1976959.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145776E+10 | 0.00 | 0.00 | 0.00 | 0.474497E+09 | 0.00 | 0.412012E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150230E+10 | 0.00 | 0.00 | 0.00 | 38302531.44 | 0.00 | 0.138338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.568857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178344E+11 | 0.00 | 0.00 | 0.00 | 0.343224E+10 | 0.00 | 0.619944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.136536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153924E+10 | 0.00 | 0.00 | 0.00 | 0.123603E+10 | 0.00 | 0.171654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.539113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166435E+11 | 0.00 | 0.00 | 0.52 |
February | 0.670039E+10 | 0.00 | 0.00 | 54616.74 | 0.00 | 0.854772E+10 | 60041186.65 | 0.00 | 0.53 |
March | 0.886549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581473E+10 | 0.00 | 0.00 | 0.53 |
April | 0.764361E+10 | 0.00 | 0.00 | 1109301.81 | 0.00 | 0.159973E+10 | 0.855266E+09 | 0.00 | 0.56 |
May | 0.535921E+10 | 45011099.82 | 0.00 | 9887915.87 | 3344713.77 | 0.961473E+09 | 0.264102E+10 | 0.00 | 0.68 |
June | 0.100567E+10 | 0.581975E+09 | 0.00 | 20755716.05 | 0.00 | 0.00 | 0.480500E+10 | 0.00 | 0.84 |
July | 96916116.86 | 0.148201E+10 | 0.00 | 26352342.56 | 282648.08 | 0.00 | 0.329399E+10 | 0.00 | 0.83 |
August | 0.415361E+09 | 0.103551E+10 | 0.00 | 27759499.18 | 124567.43 | 0.00 | 0.451270E+10 | 0.00 | 0.88 |
September | 0.262800E+10 | 0.545410E+09 | 0.00 | 17065694.48 | 0.00 | 2619868.55 | 0.465908E+10 | 0.00 | 0.80 |
October | 0.687342E+10 | 3890773.08 | 0.00 | 6007674.82 | 0.00 | 0.178219E+09 | 0.356055E+10 | 0.00 | 0.64 |
November | 0.969238E+10 | 0.00 | 0.00 | 227520.00 | 0.00 | 0.299922E+10 | 0.224183E+09 | 0.00 | 0.52 |
December | 0.859100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100254E+11 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.632626E+11 | 0.369381E+10 | 0.00 | 0.109220E+09 | 3751929.28 | 0.467726E+11 | 0.246118E+11 | 0.00 | 0.66 |
Minimum of Months | 96916116.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.969238E+10 | 0.148201E+10 | 0.00 | 27759499.18 | 3344713.77 | 0.166435E+11 | 0.480500E+10 | 0.00 | 0.88 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.240928E+10 | 0.00 | 0.00 | 13736.14 | 0.00 | 0.554571E+10 | 10741386.40 | 0.00 | 0.39 |
February | 0.294271E+10 | 0.00 | 0.00 | 362478.36 | 0.00 | 0.241948E+10 | 0.346262E+09 | 0.00 | 0.41 |
March | 0.381185E+10 | 0.00 | 0.00 | 79455.67 | 0.00 | 0.148614E+10 | 65445842.70 | 0.00 | 0.40 |
April | 0.256374E+10 | 0.00 | 0.00 | 1968130.33 | 0.00 | 0.290157E+09 | 0.177461E+10 | 0.00 | 0.58 |
May | 0.175877E+10 | 22729551.76 | 0.00 | 5290383.05 | 0.00 | 0.202830E+09 | 0.285298E+10 | 0.00 | 0.84 |
June | 0.210284E+09 | 0.274177E+09 | 0.00 | 9056118.25 | 0.00 | 0.00 | 0.377467E+10 | 0.00 | 1.13 |
July | 10211627.59 | 0.719824E+09 | 0.00 | 8961377.23 | 142738.09 | 0.00 | 0.221936E+10 | 0.00 | 1.00 |
August | 98739401.15 | 0.510171E+09 | 0.00 | 10716699.52 | 257204.57 | 0.00 | 0.323360E+10 | 0.00 | 1.14 |
September | 0.734451E+09 | 0.265950E+09 | 0.00 | 8454315.89 | 0.00 | 0.00 | 0.400310E+10 | 0.00 | 1.06 |
October | 0.181490E+10 | 2225540.83 | 0.00 | 5643507.28 | 0.00 | 8401831.80 | 0.411915E+10 | 0.00 | 0.80 |
November | 0.332869E+10 | 0.00 | 0.00 | 1136296.60 | 0.00 | 0.895424E+09 | 0.107627E+10 | 0.00 | 0.45 |
December | 0.323881E+10 | 0.00 | 0.00 | 11351.25 | 0.00 | 0.338243E+10 | 9120291.89 | 0.00 | 0.38 |
Annual Sum or Average | 0.229224E+11 | 0.179508E+10 | 0.00 | 51693849.58 | 399942.66 | 0.142306E+11 | 0.234853E+11 | 0.00 | 0.72 |
Minimum of Months | 10211627.59 | 0.00 | 0.00 | 11351.25 | 0.00 | 0.00 | 9120291.89 | 0.00 | 0.38 |
Maximum of Months | 0.381185E+10 | 0.719824E+09 | 0.00 | 10716699.52 | 257204.57 | 0.554571E+10 | 0.411915E+10 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.170605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673676E+10 | 0.00 | 0.00 | 0.41 |
February | 0.235829E+10 | 0.00 | 0.00 | 110741.74 | 0.00 | 0.344367E+10 | 0.143238E+09 | 0.00 | 0.42 |
March | 0.359339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206820E+10 | 0.00 | 0.00 | 0.42 |
April | 0.285720E+10 | 0.00 | 0.00 | 774743.25 | 0.00 | 0.463112E+09 | 0.835565E+09 | 0.00 | 0.51 |
May | 0.207672E+10 | 21447260.14 | 0.00 | 2285040.12 | 1007567.60 | 0.281528E+09 | 0.165015E+10 | 0.00 | 0.70 |
June | 0.418997E+09 | 0.253325E+09 | 0.00 | 4805023.61 | 5016138.37 | 0.00 | 0.261101E+10 | 0.00 | 0.93 |
July | 89806883.29 | 0.609881E+09 | 0.00 | 4543194.89 | 27766900.82 | 0.00 | 0.154252E+10 | 0.00 | 0.83 |
August | 0.236612E+09 | 0.454337E+09 | 0.00 | 5609317.00 | 17115076.02 | 0.00 | 0.230914E+10 | 0.00 | 0.95 |
September | 0.103948E+10 | 0.220599E+09 | 0.00 | 4479383.87 | 13709856.12 | 0.00 | 0.255684E+10 | 0.00 | 0.86 |
October | 0.234828E+10 | 2411376.54 | 0.00 | 2830843.87 | 0.00 | 46295877.86 | 0.233272E+10 | 0.00 | 0.67 |
November | 0.341290E+10 | 0.00 | 0.00 | 299554.75 | 0.00 | 0.128709E+10 | 0.388007E+09 | 0.00 | 0.43 |
December | 0.263596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441008E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.227737E+11 | 0.156200E+10 | 0.00 | 25737843.12 | 64615538.93 | 0.187367E+11 | 0.143692E+11 | 0.00 | 0.63 |
Minimum of Months | 89806883.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.359339E+10 | 0.609881E+09 | 0.00 | 5609317.00 | 27766900.82 | 0.673676E+10 | 0.261101E+10 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.147002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697170E+10 | 0.00 | 0.00 | 0.41 |
February | 0.214970E+10 | 0.00 | 0.00 | 76008.94 | 0.00 | 0.367155E+10 | 0.102453E+09 | 0.00 | 0.42 |
March | 0.335422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229166E+10 | 0.00 | 0.00 | 0.42 |
April | 0.284483E+10 | 0.00 | 0.00 | 632976.68 | 0.00 | 0.540252E+09 | 0.696438E+09 | 0.00 | 0.50 |
May | 0.208323E+10 | 21060597.11 | 0.00 | 2122195.67 | 1596465.39 | 0.322125E+09 | 0.153818E+10 | 0.00 | 0.69 |
June | 0.429313E+09 | 0.253201E+09 | 0.00 | 4730589.18 | 5017256.50 | 0.00 | 0.258400E+10 | 0.00 | 0.93 |
July | 89896952.82 | 0.610042E+09 | 0.00 | 4555908.51 | 27748964.54 | 0.00 | 0.154482E+10 | 0.00 | 0.83 |
August | 0.235171E+09 | 0.454330E+09 | 0.00 | 5604064.15 | 17099673.00 | 0.00 | 0.231436E+10 | 0.00 | 0.96 |
September | 0.105147E+10 | 0.220682E+09 | 0.00 | 4393450.13 | 13685254.58 | 0.00 | 0.250771E+10 | 0.00 | 0.86 |
October | 0.234888E+10 | 2413226.35 | 0.00 | 2611756.40 | 0.00 | 0.104333E+09 | 0.219088E+10 | 0.00 | 0.66 |
November | 0.329189E+10 | 0.00 | 0.00 | 216210.64 | 0.00 | 0.144572E+10 | 0.298947E+09 | 0.00 | 0.42 |
December | 0.244997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459230E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.217986E+11 | 0.156173E+10 | 0.00 | 24943160.32 | 65147614.01 | 0.199396E+11 | 0.137778E+11 | 0.00 | 0.63 |
Minimum of Months | 89896952.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.335422E+10 | 0.610042E+09 | 0.00 | 5604064.15 | 27748964.54 | 0.697170E+10 | 0.258400E+10 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.124031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.720059E+10 | 0.00 | 0.00 | 0.41 |
February | 0.184831E+10 | 0.00 | 0.00 | 43836.68 | 0.00 | 0.398160E+10 | 65241613.01 | 0.00 | 0.42 |
March | 0.302431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260255E+10 | 0.00 | 0.00 | 0.42 |
April | 0.283705E+10 | 0.00 | 0.00 | 413356.14 | 0.00 | 0.671147E+09 | 0.454706E+09 | 0.00 | 0.49 |
May | 0.207962E+10 | 20636773.74 | 0.00 | 1727036.30 | 2349573.75 | 0.404058E+09 | 0.128593E+10 | 0.00 | 0.66 |
June | 0.455800E+09 | 0.252024E+09 | 0.00 | 4283560.70 | 5047706.79 | 0.00 | 0.241566E+10 | 0.00 | 0.90 |
July | 92890099.35 | 0.609095E+09 | 0.00 | 4236948.26 | 28195477.97 | 0.00 | 0.148313E+10 | 0.00 | 0.81 |
August | 0.250049E+09 | 0.454354E+09 | 0.00 | 5173932.56 | 17297921.43 | 0.00 | 0.221021E+10 | 0.00 | 0.94 |
September | 0.111893E+10 | 0.219646E+09 | 0.00 | 3963473.68 | 13820223.14 | 312145.04 | 0.228134E+10 | 0.00 | 0.83 |
October | 0.246210E+10 | 2406889.57 | 0.00 | 2116456.26 | 0.00 | 0.190144E+09 | 0.177762E+10 | 0.00 | 0.63 |
November | 0.308008E+10 | 0.00 | 0.00 | 101480.75 | 0.00 | 0.172369E+10 | 0.151431E+09 | 0.00 | 0.42 |
December | 0.215695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488175E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.206464E+11 | 0.155816E+10 | 0.00 | 22060081.34 | 66710903.08 | 0.216558E+11 | 0.121253E+11 | 0.00 | 0.61 |
Minimum of Months | 92890099.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.308008E+10 | 0.609095E+09 | 0.00 | 5173932.56 | 28195477.97 | 0.720059E+10 | 0.241566E+10 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.807164E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147314E+11 | 0.00 | 0.00 | 0.38 |
February | 0.229438E+10 | 0.00 | 0.00 | 8793.25 | 0.00 | 0.841111E+10 | 13896133.46 | 0.00 | 0.38 |
March | 0.419927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.602718E+10 | 0.00 | 0.00 | 0.39 |
April | 0.430515E+10 | 0.00 | 0.00 | 226110.80 | 0.00 | 0.209887E+10 | 0.235215E+09 | 0.00 | 0.39 |
May | 0.350309E+10 | 28829529.65 | 0.00 | 1877100.14 | 5025062.37 | 0.130176E+10 | 0.903190E+09 | 0.00 | 0.45 |
June | 0.893625E+09 | 0.488727E+09 | 0.00 | 5395806.50 | 250120.46 | 0.00 | 0.243520E+10 | 0.00 | 0.56 |
July | 0.131909E+09 | 0.121462E+10 | 0.00 | 5895163.79 | 22178948.17 | 0.00 | 0.145283E+10 | 0.00 | 0.53 |
August | 0.395722E+09 | 0.852922E+09 | 0.00 | 7413180.03 | 25825211.87 | 0.00 | 0.237440E+10 | 0.00 | 0.59 |
September | 0.223858E+10 | 0.402284E+09 | 0.00 | 4880117.61 | 26421888.71 | 10642028.72 | 0.215839E+10 | 0.00 | 0.53 |
October | 0.488900E+10 | 1844227.27 | 0.00 | 1849705.90 | 0.00 | 0.507340E+09 | 0.125555E+10 | 0.00 | 0.44 |
November | 0.450701E+10 | 0.00 | 0.00 | 10168.83 | 0.00 | 0.425506E+10 | 27235891.50 | 0.00 | 0.38 |
December | 0.226395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106454E+11 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.304289E+11 | 0.298923E+10 | 0.00 | 27556146.85 | 79701231.58 | 0.479888E+11 | 0.108559E+11 | 0.00 | 0.45 |
Minimum of Months | 0.131909E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.488900E+10 | 0.121462E+10 | 0.00 | 7413180.03 | 26421888.71 | 0.147314E+11 | 0.243520E+10 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.344543E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741756E+10 | 0.00 | 0.00 | 0.38 |
February | 0.101404E+10 | 0.00 | 0.00 | 7289.72 | 0.00 | 0.433569E+10 | 18196995.39 | 0.00 | 0.38 |
March | 0.195202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316002E+10 | 0.00 | 0.00 | 0.39 |
April | 0.198268E+10 | 0.00 | 0.00 | 134927.01 | 0.00 | 0.121376E+10 | 0.207748E+09 | 0.00 | 0.41 |
May | 0.164660E+10 | 14225722.79 | 0.00 | 986067.71 | 2558909.44 | 0.702320E+09 | 0.740861E+09 | 0.00 | 0.54 |
June | 0.375375E+09 | 0.232849E+09 | 0.00 | 2891895.08 | 91829.34 | 0.00 | 0.175964E+10 | 0.00 | 0.74 |
July | 61209878.80 | 0.592293E+09 | 0.00 | 3030674.01 | 10406383.70 | 0.00 | 0.106495E+10 | 0.00 | 0.68 |
August | 0.193383E+09 | 0.424974E+09 | 0.00 | 3758548.63 | 13051008.36 | 0.00 | 0.168184E+10 | 0.00 | 0.79 |
September | 0.104539E+10 | 0.194996E+09 | 0.00 | 2649291.97 | 12662198.06 | 2627335.96 | 0.162726E+10 | 0.00 | 0.68 |
October | 0.223680E+10 | 1219355.20 | 0.00 | 1119993.19 | 0.00 | 0.303594E+09 | 0.105944E+10 | 0.00 | 0.51 |
November | 0.215232E+10 | 0.00 | 0.00 | 14236.05 | 0.00 | 0.224205E+10 | 27254692.22 | 0.00 | 0.38 |
December | 0.901603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554558E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.139060E+11 | 0.146056E+10 | 0.00 | 14592923.37 | 38770328.90 | 0.249232E+11 | 0.818719E+10 | 0.00 | 0.52 |
Minimum of Months | 61209878.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.223680E+10 | 0.592293E+09 | 0.00 | 3758548.63 | 13051008.36 | 0.741756E+10 | 0.175964E+10 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.303567E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.745857E+10 | 0.00 | 0.00 | 0.38 |
February | 0.939821E+09 | 0.00 | 0.00 | 5342.39 | 0.00 | 0.440845E+10 | 16066814.30 | 0.00 | 0.38 |
March | 0.185264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325777E+10 | 0.00 | 0.00 | 0.39 |
April | 0.193838E+10 | 0.00 | 0.00 | 117554.63 | 0.00 | 0.126677E+10 | 0.182102E+09 | 0.00 | 0.41 |
May | 0.165919E+10 | 14228085.83 | 0.00 | 915455.81 | 2656111.17 | 0.719613E+09 | 0.678454E+09 | 0.00 | 0.53 |
June | 0.391327E+09 | 0.232330E+09 | 0.00 | 2763646.45 | 93733.05 | 0.00 | 0.169515E+10 | 0.00 | 0.72 |
July | 65552367.21 | 0.591562E+09 | 0.00 | 2934499.54 | 10703153.92 | 0.00 | 0.103878E+10 | 0.00 | 0.67 |
August | 0.200454E+09 | 0.425074E+09 | 0.00 | 3641825.90 | 13100078.20 | 0.00 | 0.164168E+10 | 0.00 | 0.78 |
September | 0.105765E+10 | 0.194535E+09 | 0.00 | 2559308.30 | 12725933.67 | 7828336.58 | 0.157646E+10 | 0.00 | 0.67 |
October | 0.223103E+10 | 1212855.19 | 0.00 | 1059400.05 | 0.00 | 0.319593E+09 | 0.102042E+10 | 0.00 | 0.51 |
November | 0.209273E+10 | 0.00 | 0.00 | 12293.12 | 0.00 | 0.229883E+10 | 23905745.64 | 0.00 | 0.38 |
December | 0.823562E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562369E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.135559E+11 | 0.145894E+10 | 0.00 | 14009326.19 | 39279010.01 | 0.253611E+11 | 0.787302E+10 | 0.00 | 0.52 |
Minimum of Months | 65552367.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.223103E+10 | 0.591562E+09 | 0.00 | 3641825.90 | 13100078.20 | 0.745857E+10 | 0.169515E+10 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.149718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761249E+10 | 0.00 | 0.00 | 0.38 |
February | 0.711689E+09 | 0.00 | 0.00 | 1202.43 | 0.00 | 0.463859E+10 | 5035386.06 | 0.00 | 0.38 |
March | 0.149818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360828E+10 | 0.00 | 0.00 | 0.39 |
April | 0.172676E+10 | 0.00 | 0.00 | 69355.80 | 0.00 | 0.148052E+10 | 0.132950E+09 | 0.00 | 0.40 |
May | 0.154470E+10 | 14231150.07 | 0.00 | 731058.20 | 2990819.79 | 0.876863E+09 | 0.541138E+09 | 0.00 | 0.51 |
June | 0.475224E+09 | 0.231355E+09 | 0.00 | 2354626.64 | 96806.48 | 0.00 | 0.147111E+10 | 0.00 | 0.69 |
July | 87607525.87 | 0.590868E+09 | 0.00 | 2664188.45 | 11295839.26 | 0.00 | 0.961843E+09 | 0.00 | 0.66 |
August | 0.220915E+09 | 0.425324E+09 | 0.00 | 3324063.80 | 13121587.04 | 0.00 | 0.154016E+10 | 0.00 | 0.76 |
September | 0.109386E+10 | 0.193842E+09 | 0.00 | 2309410.80 | 12836879.17 | 18975376.60 | 0.144142E+10 | 0.00 | 0.66 |
October | 0.227277E+10 | 1204937.30 | 0.00 | 854182.85 | 0.00 | 0.385186E+09 | 0.822668E+09 | 0.00 | 0.49 |
November | 0.191802E+10 | 0.00 | 0.00 | 5890.05 | 0.00 | 0.246360E+10 | 16691702.39 | 0.00 | 0.38 |
December | 0.588794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585851E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.122882E+11 | 0.145683E+10 | 0.00 | 12313979.01 | 40341931.74 | 0.269430E+11 | 0.693302E+10 | 0.00 | 0.51 |
Minimum of Months | 87607525.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.227277E+10 | 0.590868E+09 | 0.00 | 3324063.80 | 13121587.04 | 0.761249E+10 | 0.154016E+10 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 8136066.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.774134E+10 | 0.00 | 0.00 | 0.38 |
February | 0.298942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503576E+10 | 0.00 | 0.00 | 0.38 |
March | 0.517680E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456682E+10 | 0.00 | 0.00 | 0.39 |
April | 0.101816E+10 | 0.00 | 0.00 | 3970.10 | 0.00 | 0.221267E+10 | 20061807.51 | 0.00 | 0.39 |
May | 0.107120E+10 | 14508000.67 | 0.00 | 434542.92 | 3547159.59 | 0.139571E+10 | 0.346952E+09 | 0.00 | 0.48 |
June | 0.626168E+09 | 0.231210E+09 | 0.00 | 1621605.31 | 105405.25 | 54026978.88 | 0.104749E+10 | 0.00 | 0.66 |
July | 0.123558E+09 | 0.589390E+09 | 0.00 | 2202761.43 | 11312425.81 | 0.00 | 0.853339E+09 | 0.00 | 0.65 |
August | 0.253369E+09 | 0.427432E+09 | 0.00 | 2766575.63 | 12985620.75 | 0.00 | 0.138837E+10 | 0.00 | 0.75 |
September | 0.972228E+09 | 0.192323E+09 | 0.00 | 1855242.15 | 12771693.83 | 0.239826E+09 | 0.121899E+10 | 0.00 | 0.64 |
October | 0.202246E+10 | 1253772.47 | 0.00 | 588250.88 | 0.00 | 0.724902E+09 | 0.600648E+09 | 0.00 | 0.48 |
November | 0.122696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313847E+10 | 0.00 | 0.00 | 0.38 |
December | 47509965.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638956E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.818637E+10 | 0.145612E+10 | 0.00 | 9472948.42 | 40722305.24 | 0.314991E+11 | 0.547586E+10 | 0.00 | 0.50 |
Minimum of Months | 8136066.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.202246E+10 | 0.589390E+09 | 0.00 | 2766575.63 | 12985620.75 | 0.774134E+10 | 0.138837E+10 | 0.00 | 0.75 |