Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:20
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2020-06-03 19:20:35
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:35
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1452.44 | 694.84 | 694.84 |
Net Site Energy | 1452.44 | 694.84 | 694.84 |
Total Source Energy | 3775.66 | 1806.26 | 1806.26 |
Net Source Energy | 3775.66 | 1806.26 | 1806.26 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 395.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 128.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 550.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 92.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 93.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 63.63 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1056.75 | 395.70 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 395.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 128.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 550.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 92.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 93.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 63.63 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 307.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 136.68 | 189.30 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 505.54 | 189.30 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 307.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 136.68 | 189.30 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 505.54 | 189.30 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1056.749 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1056.749 | 100.00 |
Total On-Site and Utility Electric Sources | 1056.749 | 100.00 |
Total Electricity End Uses | 1056.749 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.33 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1702.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Meter |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:35
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.75 | 20.75 | 20.0855 | 11.61 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.37 | 10.37 | 22.9594 | 11.61 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 20.8066 | 11.61 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 20.8066 | 11.61 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 20.8066 | 11.61 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.70 | 20.70 | 13.4441 | 11.61 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 13.4441 | 11.61 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 13.4441 | 11.61 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 13.4441 | 11.61 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.35 | 10.35 | 13.4441 | 11.61 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 17.1846 | 11.61 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 17.1846 | 11.61 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:35
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-AUG-12:39 | 02-JAN-08:09 | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 205499.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 48571.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 34106.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8609.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 6664.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 106010.89 | 205499.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 205499.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 48571.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 34106.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 8609.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 6664.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:35
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 428.93 | 0.00 | 0.00 | 0.00 |
Cooling | 407.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1744.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 291.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 296.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 201.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3346.72 | 428.93 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 205.20 | 0.00 | 0.00 | 0.00 |
Cooling | 194.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 834.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 139.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 141.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 96.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1601.06 | 205.20 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 205.20 | 0.00 | 0.00 | 0.00 |
Cooling | 194.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 834.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 139.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 141.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 96.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1601.06 | 205.20 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:35
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.78 |
SMSTORE1 DIRECT AIR | 1.01 |
SMSTORE2 DIRECT AIR | 1.04 |
SMSTORE3 DIRECT AIR | 1.03 |
SMSTORE4 DIRECT AIR | 1.03 |
LGSTORE2 DIRECT AIR | 1.70 |
SMSTORE5 DIRECT AIR | 0.918038 |
SMSTORE6 DIRECT AIR | 0.911479 |
SMSTORE7 DIRECT AIR | 0.904326 |
SMSTORE8 DIRECT AIR | 0.939964 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.78 | 1.78 | 1.78 | 1.78 | 1.81 | 1.81 | 1.00 | 0.986987 | 1.81 |
PSZ-AC_2:2 | 1.01 | 1.01 | 1.01 | 1.01 | 1.01 | 1.01 | 1.00 | 1.00 | 1.01 |
PSZ-AC_3:3 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.00 | 1.00 | 1.04 |
PSZ-AC_4:4 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.00 | 1.00 | 1.03 |
PSZ-AC_5:5 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.00 | 1.00 | 1.03 |
PSZ-AC_6:6 | 1.70 | 1.70 | 1.70 | 1.70 | 1.71 | 1.71 | 1.00 | 0.995118 | 1.71 |
PSZ-AC_7:7 | 0.918038 | 0.918038 | 0.918038 | 0.918038 | 0.918038 | 0.918038 | 1.00 | 1.00 | 0.918038 |
PSZ-AC_8:8 | 0.911479 | 0.911479 | 0.911479 | 0.911479 | 0.911479 | 0.911479 | 1.00 | 1.00 | 0.911479 |
PSZ-AC_9:9 | 0.904326 | 0.904326 | 0.904326 | 0.904326 | 0.904326 | 0.904326 | 1.00 | 1.000000 | 0.904326 |
PSZ-AC_10:10 | 0.939964 | 0.939964 | 0.939964 | 0.939964 | 0.939964 | 0.939964 | 1.00 | 1.00 | 0.939964 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.81 | 0.411453 |
PSZ-AC_2:2_OA_CONTROLLER | 1.01 | 0.205727 |
PSZ-AC_3:3_OA_CONTROLLER | 1.04 | 0.205727 |
PSZ-AC_4:4_OA_CONTROLLER | 1.03 | 0.205727 |
PSZ-AC_5:5_OA_CONTROLLER | 1.03 | 0.205727 |
PSZ-AC_6:6_OA_CONTROLLER | 1.71 | 0.411453 |
PSZ-AC_7:7_OA_CONTROLLER | 0.918038 | 0.205727 |
PSZ-AC_8:8_OA_CONTROLLER | 0.911479 | 0.205727 |
PSZ-AC_9:9_OA_CONTROLLER | 0.904326 | 0.205727 |
PSZ-AC_10:10_OA_CONTROLLER | 0.939964 | 0.205727 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.81 | 1.81 | 1.81 | 1.19 | 40990.24 | 56567.15 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.01 | 1.01 | 1.01 | 0.667276 | 22448.30 | 31016.26 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 0.687094 | 23092.38 | 31702.38 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.03 | 1.03 | 1.03 | 0.681909 | 22900.57 | 31522.86 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.03 | 1.03 | 1.03 | 0.681666 | 22950.44 | 31514.44 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.71 | 1.71 | 1.71 | 1.13 | 39234.95 | 54748.74 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.918038 | 0.918038 | 0.918038 | 0.605905 | 20933.46 | 28891.45 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.911479 | 0.911479 | 0.911479 | 0.601576 | 20823.77 | 28741.59 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.904326 | 0.904326 | 0.904326 | 0.596855 | 20688.23 | 28578.12 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 0.939964 | 0.939964 | 0.939964 | 0.620376 | 21266.15 | 29392.87 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 1.81 | 0.903185 | 1.20 | 38781.05 | 40990.24 | 20495.12 | 20495.12 | 0.699200 | 0.699200 | 0.699200 | 0.699200 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 1.01 | 0.505510 | 0.674013 | 21205.03 | 22448.30 | 11224.15 | 11224.15 | 0.705099 | 0.705100 | 0.705100 | 0.705100 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 1.04 | 0.520525 | 0.694033 | 21812.24 | 23092.38 | 11546.19 | 11546.19 | 0.705369 | 0.705370 | 0.705370 | 0.705370 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 1.03 | 0.516600 | 0.688800 | 21629.94 | 22900.57 | 11450.28 | 11450.28 | 0.705581 | 0.705580 | 0.705580 | 0.705580 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 1.03 | 0.516415 | 0.688553 | 21681.13 | 22950.44 | 11475.22 | 11475.22 | 0.704886 | 0.704890 | 0.704890 | 0.704890 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 1.71 | 0.855830 | 1.14 | 37149.99 | 39234.95 | 19617.47 | 19617.47 | 0.696507 | 0.696510 | 0.696510 | 0.696510 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 0.918040 | 0.459020 | 0.612027 | 19813.85 | 20933.46 | 10466.73 | 10466.73 | 0.697902 | 0.697900 | 0.697900 | 0.697900 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 0.911480 | 0.455740 | 0.607653 | 19712.74 | 20823.77 | 10411.89 | 10411.89 | 0.697391 | 0.697390 | 0.697390 | 0.697390 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 0.904330 | 0.452165 | 0.602887 | 19586.44 | 20688.23 | 10344.11 | 10344.11 | 0.697033 | 0.697030 | 0.697030 | 0.697030 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 0.939960 | 0.469980 | 0.626640 | 20117.37 | 21266.15 | 10633.08 | 10633.08 | 0.700000 | 0.700000 | 0.700000 | 0.700000 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.81 | 1932.91 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.01 | 1119.36 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1152.61 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.03 | 1143.91 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.03 | 1143.50 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.71 | 1831.56 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.918038 | 1016.41 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.911479 | 1009.15 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.904326 | 1001.23 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 0.939964 | 1040.69 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | 56567.15 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | 31016.26 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | 31702.38 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | 31522.86 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | 31514.44 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | 54748.74 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | 28891.45 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | 28741.59 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | 28578.12 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | 29392.87 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:35
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:35
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:35
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.76 | 20.75 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.67 | 10.37 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.43 | 20.70 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.13 | 10.35 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 20.085 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.385 | No |
2 | SMSTORE1 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 22.959 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 27.259 | No |
3 | SMSTORE2 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 20.807 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.107 | No |
4 | SMSTORE3 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 20.807 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.107 | No |
5 | SMSTORE4 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 20.807 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.107 | No |
6 | LGSTORE2 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
7 | SMSTORE5 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
8 | SMSTORE6 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
9 | SMSTORE7 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
10 | SMSTORE8 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 4683.750 | 13.444 | 156.145 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4683.750 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 2313.749 | 6.641 | 77.135 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2313.749 |
3 | SMSTORE1_LIGHTS | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1657.501 | 9.515 | 110.515 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1657.501 |
5 | SMSTORE2_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 1282.497 | 7.363 | 85.511 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1282.497 |
7 | SMSTORE3_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 1282.497 | 7.363 | 85.511 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1282.497 |
9 | SMSTORE4_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 1282.497 | 7.363 | 85.511 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1282.497 |
11 | LGSTORE2_LIGHTS | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 4683.750 | 13.444 | 156.145 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4683.750 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 2341.875 | 13.444 | 156.146 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2341.875 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL | 20 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 30 | 2 | 7 | 0.167 | 0.1408 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 31 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2031 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.024 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.847 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8390000 | 2.8390000 | 2.8390000 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
23 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
24 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
25 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
26 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
27 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
28 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
29 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
30 | 7 | -0.30155247E-08 | -0.19705740E-14 | 0.18469307E-14 | -0.46079768E-16 |
31 | 6 | 0.40551627E-05 | 0.26926011E-08 | 0.31944497E-02 | -0.26797721E-04 |
32 | 5 | -0.28496186E-03 | 0.15923452E-05 | -0.22398486 | 0.19584477E-02 |
33 | 4 | 0.65115693E-02 | 0.72427529E-04 | 4.8338806 | -0.45306652E-01 |
34 | 3 | -0.57046066E-01 | 0.57554694E-03 | -38.045903 | 0.39892442 |
35 | 2 | 0.20237164 | 0.95689144E-03 | 116.53161 | -1.4185768 |
36 | 1 | -0.29197338 | 0.29127682E-03 | -143.93536 | 2.0495010 |
37 | 0 | 0.14232195 | 0.70641069E-05 | 60.838472 | |
38 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
39 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
40 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
41 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
42 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
43 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
44 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
45 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
46 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
47 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
48 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
49 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
50 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
51 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
52 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
53 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
54 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521549E-14 | -0.37274185E-16 |
55 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
56 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
57 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
58 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
59 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
60 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
61 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
62 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521548E-14 | -0.37274183E-16 |
63 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
64 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
65 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
66 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
67 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
68 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
69 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
70 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
71 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
72 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
73 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
74 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
75 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
76 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
77 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
78 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274181E-16 |
79 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
80 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
81 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
82 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
83 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
84 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
85 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
86 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
87 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
88 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
89 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
90 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
91 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
92 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
93 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
94 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
95 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
96 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
97 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
98 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
99 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
100 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
101 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
102 | 7 | -0.20778300E-08 | -0.65167512E-15 | 0.79548166E-14 | -0.12010680E-15 |
103 | 6 | 0.57088823E-05 | 0.38884884E-08 | 0.31895855E-02 | -0.26756916E-04 |
104 | 5 | -0.40892418E-03 | 0.23023551E-05 | -0.22370841 | 0.19560076E-02 |
105 | 4 | 0.93961169E-02 | 0.10478953E-03 | 4.8292766 | -0.45262394E-01 |
106 | 3 | -0.82481111E-01 | 0.83319714E-03 | -38.019897 | 0.39863696 |
107 | 2 | 0.29283299 | 0.13859693E-02 | 116.48099 | -1.4178998 |
108 | 1 | -0.42263540 | 0.42218679E-03 | -143.90557 | 2.0490113 |
109 | 0 | 0.20604930 | 0.10232106E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 29 | 1 | VerySmooth | 2.387 | 0.394 | 0.315 | 0.441 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.02786E-002 | 0.31435 | 0.47495 | 0.47495 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12239 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 30.0 | 0.159 | 4.569E-004 | 2.517E-004 | 0.317 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 30.0 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 15.0 | 4.561E-002 | 2.619E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 30.0 | 9.122E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 30.0 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 15.0 | 0.113 | 6.514E-004 | 3.022E-004 | 0.453 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 20910.66717 | 25092.80060 | 1.48572 | 1.78287 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.28800 | 1.40969E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
2 | LGSTORE1 | Heating | 21881.95012 | 26258.34014 | 0.94367 | 1.13240 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
3 | SMSTORE1 | Cooling | 11816.72252 | 14180.06703 | 0.84252 | 1.01102 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.28800 | 1.40969E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
4 | SMSTORE1 | Heating | 10729.13714 | 12874.96457 | 0.46270 | 0.55524 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
5 | SMSTORE2 | Cooling | 12160.18691 | 14592.22429 | 0.86754 | 1.04105 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 28.03000 | 1.40969E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
6 | SMSTORE2 | Heating | 10912.40608 | 13094.88730 | 0.47060 | 0.56472 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
7 | SMSTORE3 | Cooling | 12071.02402 | 14485.22882 | 0.86100 | 1.03320 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 28.03000 | 1.40969E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
8 | SMSTORE3 | Heating | 11013.86860 | 13216.64231 | 0.47498 | 0.56997 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
9 | SMSTORE4 | Cooling | 12066.39264 | 14479.67117 | 0.86069 | 1.03283 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 28.03000 | 1.40969E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
10 | SMSTORE4 | Heating | 11168.96059 | 13402.75271 | 0.48167 | 0.57800 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
11 | LGSTORE2 | Cooling | 20006.64078 | 24007.96894 | 1.41942 | 1.70331 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.28800 | 1.40969E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
12 | LGSTORE2 | Heating | 21420.44626 | 25704.53551 | 0.92378 | 1.10854 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
13 | SMSTORE5 | Cooling | 10757.10796 | 12908.52955 | 0.76503 | 0.91804 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.28800 | 1.40969E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
14 | SMSTORE5 | Heating | 11487.23865 | 13784.68638 | 0.49539 | 0.59447 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
15 | SMSTORE6 | Cooling | 10682.45050 | 12818.94060 | 0.75957 | 0.91148 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.28800 | 1.40969E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
16 | SMSTORE6 | Heating | 11474.42625 | 13769.31150 | 0.49484 | 0.59381 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
17 | SMSTORE7 | Cooling | 10600.96065 | 12721.15278 | 0.75360 | 0.90433 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.28800 | 1.40969E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
18 | SMSTORE7 | Heating | 11651.30142 | 13981.56171 | 0.50247 | 0.60296 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
19 | SMSTORE8 | Cooling | 11005.56366 | 13206.67639 | 0.78330 | 0.93996 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.28800 | 1.40969E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
20 | SMSTORE8 | Heating | 13359.22783 | 16031.07340 | 0.57611 | 0.69133 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 28295.15 | 1.80637 | 1.80637 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 41703.81 | 1.13240 | 1.13240 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 15211.72 | 1.01102 | 1.01102 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 20601.40 | 0.55524 | 0.55524 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 15186.09 | 1.04105 | 1.04105 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 20818.13 | 0.56472 | 0.56472 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 15225.99 | 1.03320 | 1.03320 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 20938.11 | 0.56997 | 0.56997 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 15094.77 | 1.03283 | 1.03283 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 21121.51 | 0.57800 | 0.57800 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 26749.87 | 1.71166 | 1.71166 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 41158.20 | 1.10854 | 1.10854 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 13769.08 | 0.91804 | 0.91804 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 21497.88 | 0.59447 | 0.59447 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 13683.26 | 0.91148 | 0.91148 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 21482.73 | 0.59381 | 0.59381 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 13623.33 | 0.90433 | 0.90433 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 21691.89 | 0.60296 | 0.60296 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 14141.10 | 0.93996 | 0.93996 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 23711.44 | 0.69133 | 0.69133 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.78287 |
2 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.01102 |
3 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.04105 |
4 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.03320 |
5 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.03283 |
6 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.70331 |
7 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.91804 |
8 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.91148 |
9 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.90433 |
10 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.93996 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.78287 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.78287 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.78287 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.78287 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.80637 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.80637 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 0.98699 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.01102 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.01102 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.01102 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.01102 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.01102 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.01102 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.04105 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.04105 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.04105 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.04105 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04105 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04105 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.03320 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.03320 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.03320 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.03320 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.03320 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.03320 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.03283 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.03283 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.03283 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.03283 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.03283 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.03283 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.70331 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.70331 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.70331 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.70331 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.71166 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.71166 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 0.99512 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.91804 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.91804 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.91804 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.91804 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.91804 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.91804 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.91148 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.91148 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.91148 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.91148 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.91148 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.91148 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.90433 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.90433 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.90433 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.90433 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.90433 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.90433 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.93996 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.93996 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.93996 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.93996 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.93996 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 0.93996 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.80637 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.01102 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.04105 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.03320 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.03283 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.71166 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.91804 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.91148 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.90433 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 0.93996 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.80637 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.80637 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.80637 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.80637 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.19221 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.80637 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.90319 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.20425 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 38781.04733 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 40990.24000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 20495.12000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 20495.12000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69920 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69920 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69920 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69920 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 40990.24000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 56567.14751 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
122 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.80637 |
123 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1932.90630 |
124 | Coil:Heating:Fuel | PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 56567.14751 |
125 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.01102 |
126 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.01102 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.01102 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.01102 |
130 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.66728 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.01102 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50551 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.67401 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21205.03034 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22448.30000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11224.15000 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 11224.15000 |
138 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70510 |
139 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70510 |
140 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70510 |
141 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70510 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22448.30000 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31016.26425 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
146 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.01102 |
147 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1119.36378 |
148 | Coil:Heating:Fuel | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31016.26425 |
149 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04105 |
150 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
151 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04105 |
152 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04105 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04105 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68709 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04105 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52053 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69403 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21812.24114 |
159 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 23092.38000 |
160 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11546.19000 |
161 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 11546.19000 |
162 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70537 |
163 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70537 |
164 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70537 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70537 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23092.38000 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31702.37593 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
170 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04105 |
171 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1152.60904 |
172 | Coil:Heating:Fuel | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31702.37593 |
173 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.03320 |
174 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.03320 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.03320 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.03320 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68191 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.03320 |
180 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51660 |
181 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.68880 |
182 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21629.94289 |
183 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22900.57000 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11450.28500 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 11450.28500 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70558 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70558 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70558 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70558 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22900.57000 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31522.85815 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
194 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.03320 |
195 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1143.91111 |
196 | Coil:Heating:Fuel | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31522.85815 |
197 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.03283 |
198 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.03283 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.03283 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.03283 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68167 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.03283 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51642 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.68855 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21681.13427 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22950.44000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11475.22000 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 11475.22000 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70489 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70489 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70489 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70489 |
214 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22950.44000 |
215 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31514.44032 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
218 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.03283 |
219 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1143.50377 |
220 | Coil:Heating:Fuel | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31514.44032 |
221 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.71166 |
222 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.71166 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.71166 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.71166 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.12970 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.71166 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.85583 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.14111 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 37149.99190 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 39234.95000 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 19617.47500 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 19617.47500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69651 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69651 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69651 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69651 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 39234.95000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 54748.74411 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
241 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
242 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.71166 |
243 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1831.55989 |
244 | Coil:Heating:Fuel | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 54748.74411 |
245 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.91804 |
246 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.91804 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.91804 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.91804 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.60590 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.91804 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.45902 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.61203 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 19813.85392 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 20933.46000 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10466.73000 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 10466.73000 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69790 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69790 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69790 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69790 |
262 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20933.46000 |
263 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28891.45124 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
266 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.91804 |
267 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1016.41340 |
268 | Coil:Heating:Fuel | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 28891.45124 |
269 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.91148 |
270 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
271 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.91148 |
272 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.91148 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.91148 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.60158 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.91148 |
276 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.45574 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.60765 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 19712.74334 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 20823.77000 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10411.88500 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 10411.88500 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69739 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69739 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69739 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69739 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20823.77000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28741.59105 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.91148 |
291 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1009.15230 |
292 | Coil:Heating:Fuel | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 28741.59105 |
293 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.90433 |
294 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.90433 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.90433 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.90433 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.59685 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.90433 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.45217 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.60289 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 19586.43667 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 20688.23000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10344.11500 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 10344.11500 |
306 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69703 |
307 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69703 |
308 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69703 |
309 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69703 |
310 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20688.23000 |
311 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28578.12281 |
312 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
313 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
314 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.90433 |
315 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1001.23211 |
316 | Coil:Heating:Fuel | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 28578.12281 |
317 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.93996 |
318 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
319 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.93996 |
320 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.93996 |
321 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.93996 |
322 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.62038 |
323 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.93996 |
324 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.46998 |
325 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.62664 |
326 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 20117.37069 |
327 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 21266.15000 |
328 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10633.07500 |
329 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 10633.07500 |
330 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70000 |
331 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70000 |
332 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70000 |
333 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70000 |
334 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21266.15000 |
335 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29392.86785 |
336 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
337 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
338 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.93996 |
339 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1040.68908 |
340 | Coil:Heating:Fuel | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 29392.86785 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 39567.6 | 11.61 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 21652.4 | 33.20 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 22272.8 | 44.00 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 22087.2 | 56.10 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 22137.3 | 67.74 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 37886.7 | 51.58 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 20210.4 | 108.41 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 20105.8 | 120.80 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 19975.9 | 133.41 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 20525.9 | 141.38 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 58.20 | 78.94 | 58.20 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.141 | 0.136 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.10 | 39.47 | 29.10 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 58.24 | 78.94 | 58.24 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.203 | 0.194 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 10 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 5.1762133153E-002 | 0.2889975923 | Pass | Pass | 0.3661402493 | 2.4315503205 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 5.0165166084E-002 | 0.2085469262 | Pass | Pass | 7.2827836558E-002 | 0.2028773069 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 5.6689983945E-002 | 0.2911326071 | Pass | Pass | 4.9830789124E-002 | 0.1384803364 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 6.4634443496E-002 | 0.3226402712 | Pass | Pass | 3.9790474059E-002 | 0.1170866587 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 6.9660127835E-002 | 0.3483320526 | Pass | Pass | 3.5984860794E-002 | 0.1089426419 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 8.0929897636E-002 | 0.3882417959 | Pass | Pass | 3.1233950359E-002 | 0.1154937783 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 8.0167173012E-002 | 0.3899295218 | Pass | Pass | 2.9505952980E-002 | 0.1043790714 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 8.0556915399E-002 | 0.3927297177 | Pass | Pass | 2.8574096548E-002 | 9.8499200319E-002 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 8.3817367618E-002 | 0.4077763987 | Pass | Pass | 2.5693999647E-002 | 8.5183902458E-002 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 0.2042648765 | 0.4343629986 | Pass | Pass | 0.6634177870 | 3.7886336914 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:35
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:35
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 58.20 | 180.00 | 90.00 | S |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.10 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 58.24 | 180.00 | 90.00 | S |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.141 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | ||
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.080 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.203 | 174.19 | 174.19 | 270.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.387 | 0.394 | 0.441 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.387 | 0.394 | 0.441 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.387 | 0.394 | 0.441 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.387 | 0.394 | 0.441 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.387 | 0.394 | 0.441 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.387 | 0.394 | 0.441 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.387 | 0.394 | 0.441 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.387 | 0.394 | 0.441 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.387 | 0.394 | 0.441 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.387 | 0.394 | 0.441 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.387 | 0.394 | 0.441 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.387 | 0.394 | 0.441 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.42_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.387 | 0.394 | 0.441 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
Total or Average | 124.29 | 2.387 | 0.394 | 0.441 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 124.29 | 2.387 | 0.394 | 0.441 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.992 | 2.839 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.992 | 2.839 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE8_WALL_3 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:35
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:35
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | 13.4441 | 348.39 | 4683.75 | LightsWired | TYPE1_LIGHT_SCH | 98.22 | 168.00 | 98.21 | 0.0000 | Y | 86.34 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | 6.6413 | 348.39 | 2313.75 | LightsWired | TYPE1_LIGHT_SCH | 98.22 | 168.00 | 98.21 | 0.0000 | Y | 42.65 |
SMSTORE1_LIGHTS | SMSTORE1 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE1_LIGHT_SCH | 98.22 | 168.00 | 98.21 | 0.0000 | Y | 43.17 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | 9.5153 | 174.19 | 1657.50 | LightsWired | TYPE1_LIGHT_SCH | 98.22 | 168.00 | 98.21 | 0.0000 | Y | 30.56 |
SMSTORE2_LIGHTS | SMSTORE2 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 34.27 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | 7.3625 | 174.19 | 1282.50 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.77 |
SMSTORE3_LIGHTS | SMSTORE3 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 34.27 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | 7.3625 | 174.19 | 1282.50 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.77 |
SMSTORE4_LIGHTS | SMSTORE4 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 34.27 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | 7.3625 | 174.19 | 1282.50 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.77 |
LGSTORE2_LIGHTS | LGSTORE2 | 13.4441 | 348.39 | 4683.75 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 63.00 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | 0.0000 | 348.39 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 31.50 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 31.50 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 31.50 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | 13.4441 | 174.19 | 2341.87 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 31.50 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 8.5923 | 4180.64 | 35921.24 | 550.85 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 418.40 | AstronomicalClock | - | 42.43 | 42.43 | 3.33 | |
EXTERIOR_LIGHTS_B | 6630.02 | AstronomicalClock | - | 83.64 | 71.28 | 88.71 | |
Exterior Lighting Total | 7048.42 | 92.04 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:35
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 40990.24 | 28660.38 | 12329.86 | 0.70 | 3.73 | |||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 22448.30 | 15828.30 | 6620.00 | 0.71 | 3.80 | |||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 23092.38 | 16288.67 | 6803.71 | 0.71 | 3.80 | |||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 22900.57 | 16158.18 | 6742.39 | 0.71 | 3.80 | |||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 22950.44 | 16177.54 | 6772.90 | 0.70 | 3.80 | |||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 39234.95 | 27327.54 | 11907.41 | 0.70 | 3.80 | |||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 20933.46 | 14609.46 | 6324.00 | 0.70 | 3.80 | |||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 20823.77 | 14522.29 | 6301.48 | 0.70 | 3.80 | |||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 20688.23 | 14420.32 | 6267.91 | 0.70 | 3.80 | |||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 21266.15 | 14886.31 | 6379.85 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 39567.6 | 11.61 | ||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 21652.4 | 33.20 | ||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 22272.8 | 44.00 | ||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 22087.2 | 56.10 | ||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 22137.3 | 67.74 | ||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 37886.7 | 51.58 | ||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 20210.4 | 108.41 | ||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 20105.8 | 120.80 | ||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 19975.9 | 133.41 | ||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 20525.9 | 141.38 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 56567.15 | 0.80 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31016.26 | 0.80 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31702.38 | 0.80 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31522.86 | 0.80 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31514.44 | 0.80 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 54748.74 | 0.80 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 28891.45 | 0.80 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 28741.59 | 0.80 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 28578.12 | 0.80 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 29392.87 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.81 | 1932.91 | 1070.05 | 1.00 | 1.33 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.01 | 1119.36 | 1107.16 | 1.00 | 1.40 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1152.61 | 1107.16 | 1.00 | 1.39 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.03 | 1143.91 | 1107.16 | 1.00 | 1.39 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.03 | 1143.50 | 1107.16 | 1.00 | 1.39 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.71 | 1831.56 | 1070.05 | 1.00 | 1.34 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.92 | 1016.41 | 1107.16 | 1.00 | 1.42 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.91 | 1009.15 | 1107.16 | 1.00 | 1.43 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.90 | 1001.23 | 1107.16 | 1.00 | 1.43 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.94 | 1040.69 | 1107.16 | 1.00 | 1.42 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:35
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 20910.67 | 25092.80 | 72.03 | 1.486 | 1.783 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00916 | 29.29 | 0.01410 | 0.411 | 0.00 |
SMSTORE1 | 11816.72 | 14180.07 | 81.40 | 0.843 | 1.011 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00901 | 29.29 | 0.01410 | 0.206 | 0.00 |
SMSTORE2 | 12160.19 | 14592.22 | 83.77 | 0.868 | 1.041 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00914 | 28.03 | 0.01410 | 0.206 | 0.00 |
SMSTORE3 | 12071.02 | 14485.23 | 83.16 | 0.861 | 1.033 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00913 | 28.03 | 0.01410 | 0.206 | 0.00 |
SMSTORE4 | 12066.39 | 14479.67 | 83.12 | 0.861 | 1.033 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00915 | 28.03 | 0.01410 | 0.206 | 0.00 |
LGSTORE2 | 20006.64 | 24007.97 | 68.91 | 1.419 | 1.703 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00922 | 29.29 | 0.01410 | 0.411 | 0.00 |
SMSTORE5 | 10757.11 | 12908.53 | 74.10 | 0.765 | 0.918 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00917 | 29.29 | 0.01410 | 0.206 | 0.00 |
SMSTORE6 | 10682.45 | 12818.94 | 73.59 | 0.760 | 0.911 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00918 | 29.29 | 0.01410 | 0.206 | 0.00 |
SMSTORE7 | 10600.96 | 12721.15 | 73.03 | 0.754 | 0.904 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00921 | 29.29 | 0.01410 | 0.206 | 0.00 |
SMSTORE8 | 11005.56 | 13206.68 | 75.82 | 0.783 | 0.940 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00921 | 29.29 | 0.01410 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 21881.95 | 26258.34 | 75.37 | 0.944 | 1.132 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00661 | -10.70 | 0.00150 | 0.411 | 0.00 |
SMSTORE1 | 10729.14 | 12874.96 | 73.91 | 0.463 | 0.555 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00651 | -10.70 | 0.00150 | 0.206 | 0.00 |
SMSTORE2 | 10912.41 | 13094.89 | 75.17 | 0.471 | 0.565 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00653 | -10.70 | 0.00150 | 0.206 | 0.00 |
SMSTORE3 | 11013.87 | 13216.64 | 75.87 | 0.475 | 0.570 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00653 | -10.70 | 0.00150 | 0.206 | 0.00 |
SMSTORE4 | 11168.96 | 13402.75 | 76.94 | 0.482 | 0.578 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00655 | -10.70 | 0.00150 | 0.206 | 0.00 |
LGSTORE2 | 21420.45 | 25704.54 | 73.78 | 0.924 | 1.109 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00663 | -10.70 | 0.00150 | 0.411 | 0.00 |
SMSTORE5 | 11487.24 | 13784.69 | 79.13 | 0.495 | 0.594 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00657 | -10.70 | 0.00150 | 0.206 | 0.00 |
SMSTORE6 | 11474.43 | 13769.31 | 79.05 | 0.495 | 0.594 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00657 | -10.70 | 0.00150 | 0.206 | 0.00 |
SMSTORE7 | 11651.30 | 13981.56 | 80.26 | 0.502 | 0.603 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00659 | -10.70 | 0.00150 | 0.206 | 0.00 |
SMSTORE8 | 13359.23 | 16031.07 | 92.03 | 0.576 | 0.691 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00663 | -10.70 | 0.00150 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.81 | 1.81 | 1.13 | 1.13 | 1.8064 | 1.7829 | 1.8064 | 0.9870 | 1.0000 |
PSZ-AC_2:2 | 1.01 | 1.01 | 0.56 | 0.56 | 1.0110 | 1.0110 | 1.0110 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.04 | 1.04 | 0.56 | 0.56 | 1.0411 | 1.0411 | 1.0411 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.03 | 1.03 | 0.57 | 0.57 | 1.0332 | 1.0332 | 1.0332 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.03 | 1.03 | 0.58 | 0.58 | 1.0328 | 1.0328 | 1.0328 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.71 | 1.71 | 1.11 | 1.11 | 1.7117 | 1.7033 | 1.7117 | 0.9951 | 1.0000 |
PSZ-AC_7:7 | 0.92 | 0.92 | 0.59 | 0.59 | 0.9180 | 0.9180 | 0.9180 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 0.91 | 0.91 | 0.59 | 0.59 | 0.9115 | 0.9115 | 0.9115 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 0.90 | 0.90 | 0.60 | 0.60 | 0.9043 | 0.9043 | 0.9043 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 0.94 | 0.94 | 0.69 | 0.69 | 0.9400 | 0.9400 | 0.9400 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 20495.120 | 0.000 | 1.806370 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 20495.12 | 14986.07 | 1.806370 | 25.76 | 18.68 | 0.01058544 | 12.80 | 12.09 | 0.00850000 | 32.10 | 0.01409687 | 23.10 | 22.7779 | 23.89 | 0.00915927 | 49.5654 | 20489.99 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 56567.148 | 56567.148 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 56567.15 | 56567.15 | 1.806375 | 9.55 | 6.48 | 0.00475203 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 22.7779 | 21.10 | 0.00660577 | 42.5036 | 21881.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 11224.150 | 0.000 | 1.011020 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 11224.15 | 8297.40 | 1.011020 | 25.56 | 18.53 | 0.01047367 | 12.80 | 12.09 | 0.00850000 | 31.92 | 0.01409688 | 23.05 | 20.3484 | 23.89 | 0.00900854 | 48.7596 | 11170.66 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 31016.264 | 31016.264 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31016.26 | 31016.26 | 1.011024 | 9.32 | 6.25 | 0.00465369 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 20.3484 | 21.10 | 0.00650769 | 41.8793 | 10729.14 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 11546.190 | 0.000 | 1.041050 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 11546.19 | 8534.60 | 1.041050 | 25.55 | 18.53 | 0.01047285 | 12.80 | 12.09 | 0.00850000 | 31.85 | 0.01409688 | 23.04 | 19.7615 | 23.89 | 0.00914279 | 49.4776 | 11161.64 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 31702.376 | 31702.376 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31702.38 | 31702.38 | 1.041051 | 9.52 | 6.40 | 0.00469608 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 19.7614 | 21.10 | 0.00652538 | 41.9920 | 10912.41 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 11450.285 | 0.000 | 1.033200 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 11450.28 | 8468.43 | 1.033200 | 25.55 | 18.52 | 0.01046793 | 12.80 | 12.09 | 0.00850000 | 31.85 | 0.01409688 | 23.04 | 19.9116 | 23.89 | 0.00913160 | 49.4176 | 11194.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 31522.858 | 31522.858 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31522.86 | 31522.86 | 1.033195 | 9.63 | 6.48 | 0.00471856 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 19.9117 | 21.10 | 0.00653419 | 42.0481 | 11013.87 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 11475.220 | 0.000 | 1.032830 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 11475.22 | 8471.25 | 1.032830 | 25.56 | 18.54 | 0.01048420 | 12.80 | 12.09 | 0.00850000 | 31.85 | 0.01409688 | 23.04 | 19.9187 | 23.89 | 0.00915428 | 49.5390 | 11083.93 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 31514.440 | 31514.440 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31514.44 | 31514.44 | 1.032827 | 9.79 | 6.60 | 0.00475255 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 19.9188 | 21.10 | 0.00654782 | 42.1349 | 11168.96 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 19617.475 | 0.000 | 1.711660 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 19617.47 | 14202.32 | 1.711660 | 25.82 | 18.77 | 0.01067173 | 12.80 | 12.09 | 0.00850000 | 31.85 | 0.01409688 | 23.04 | 24.0383 | 23.89 | 0.00922488 | 49.9160 | 19227.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 54748.744 | 54748.744 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 54748.74 | 54748.74 | 1.711663 | 9.30 | 6.33 | 0.00472971 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 24.0382 | 21.11 | 0.00663374 | 42.6810 | 21420.45 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 10466.730 | 0.000 | 0.918040 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 10466.73 | 7579.51 | 0.918040 | 25.73 | 18.73 | 0.01065742 | 12.80 | 12.09 | 0.00850000 | 31.79 | 0.01409687 | 23.02 | 22.4093 | 23.89 | 0.00916857 | 49.6153 | 9959.37 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 28891.451 | 28891.451 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28891.45 | 28891.45 | 0.918038 | 10.10 | 6.83 | 0.00481915 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 22.4094 | 21.10 | 0.00657360 | 42.2991 | 11487.24 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 10411.885 | 0.000 | 0.911480 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 10411.89 | 7529.62 | 0.911480 | 25.75 | 18.75 | 0.01067004 | 12.80 | 12.09 | 0.00850000 | 31.79 | 0.01409687 | 23.02 | 22.5706 | 23.89 | 0.00918377 | 49.6965 | 9886.90 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 28741.591 | 28741.591 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28741.59 | 28741.59 | 0.911479 | 10.09 | 6.83 | 0.00481654 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 22.5706 | 21.10 | 0.00657261 | 42.2928 | 11474.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 10344.115 | 0.000 | 0.904330 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 10344.11 | 7473.51 | 0.904330 | 25.76 | 18.76 | 0.01067894 | 12.80 | 12.09 | 0.00850000 | 31.79 | 0.01409687 | 23.02 | 22.7491 | 23.89 | 0.00920673 | 49.8193 | 9835.90 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 28578.123 | 28578.123 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28578.12 | 28578.12 | 0.904326 | 10.25 | 6.95 | 0.00485261 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 22.7492 | 21.10 | 0.00658690 | 42.3838 | 11651.30 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 10633.075 | 0.000 | 0.939960 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 10633.08 | 7729.87 | 0.939960 | 25.66 | 18.68 | 0.01061638 | 12.80 | 12.09 | 0.00850000 | 31.73 | 0.01409688 | 23.00 | 21.8868 | 23.89 | 0.00920932 | 49.8336 | 10317.67 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 29392.868 | 29392.868 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29392.87 | 29392.87 | 0.939964 | 11.64 | 7.92 | 0.00510805 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 21.8867 | 21.10 | 0.00663495 | 42.6911 | 13359.23 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:20:35
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20495.120 | 0.000 | 1.806370 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5178 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 20495.12 | 14986.07 | 1.0000 | 2.17413787 | 1.806370 | 25.76 | 18.68 | 0.01058544 | 52863.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20495.12 | 32.10 | 0.01409687 | 23.10 | 0.41145340 | 22.7779 | 23.89 | 0.00954899 | 23.89 | 0.00915927 | 49.5654 | 20489.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 56567.148 | 56567.148 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.806375 | 2.17414350 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 56567.15 | 56567.15 | 1.0000 | 2.17414350 | 1.806375 | 9.55 | 6.48 | 0.00475203 | 21565.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 56567.15 | -10.70 | 0.00150390 | -10.70 | 0.41145340 | 22.7779 | 21.11 | 0.00660577 | 21.10 | 0.00660577 | 42.5036 | 21881.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 11224.150 | 0.000 | 1.011020 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3100 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 11224.15 | 8297.40 | 1.0000 | 1.21685860 | 1.011020 | 25.56 | 18.53 | 0.01047367 | 52377.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11224.15 | 31.92 | 0.01409688 | 23.05 | 0.20572670 | 20.3484 | 23.89 | 0.00951776 | 23.89 | 0.00900854 | 48.7596 | 11170.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31016.264 | 31016.264 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.011024 | 1.21686311 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31016.26 | 31016.26 | 1.0000 | 1.21686311 | 1.011024 | 9.32 | 6.25 | 0.00465369 | 21086.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31016.26 | -10.70 | 0.00150390 | -10.70 | 0.20572670 | 20.3484 | 21.11 | 0.00650769 | 21.10 | 0.00650769 | 41.8793 | 10729.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 11546.190 | 0.000 | 1.041050 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3085 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 11546.19 | 8534.60 | 1.0000 | 1.25300256 | 1.041050 | 25.55 | 18.53 | 0.01047285 | 52364.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11546.19 | 31.85 | 0.01409688 | 23.04 | 0.20572670 | 19.7615 | 23.89 | 0.00951576 | 23.89 | 0.00914279 | 49.4776 | 11161.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31702.376 | 31702.376 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.041051 | 1.25300412 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31702.38 | 31702.38 | 1.0000 | 1.25300412 | 1.041051 | 9.52 | 6.40 | 0.00469608 | 21393.4 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31702.38 | -10.70 | 0.00150390 | -10.70 | 0.20572670 | 19.7614 | 21.11 | 0.00652538 | 21.10 | 0.00652538 | 41.9920 | 10912.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 11450.285 | 0.000 | 1.033200 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2994 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 11450.28 | 8468.43 | 1.0000 | 1.24355433 | 1.033200 | 25.55 | 18.52 | 0.01046793 | 52346.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11450.28 | 31.85 | 0.01409688 | 23.04 | 0.20572670 | 19.9116 | 23.89 | 0.00951319 | 23.89 | 0.00913160 | 49.4176 | 11194.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31522.858 | 31522.858 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.033195 | 1.24354858 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31522.86 | 31522.86 | 1.0000 | 1.24354858 | 1.033195 | 9.63 | 6.48 | 0.00471856 | 21558.3 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31522.86 | -10.70 | 0.00150390 | -10.70 | 0.20572670 | 19.9117 | 21.11 | 0.00653419 | 21.10 | 0.00653419 | 42.0481 | 11013.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 11475.220 | 0.000 | 1.032830 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3296 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 11475.22 | 8471.25 | 1.0000 | 1.24310900 | 1.032830 | 25.56 | 18.54 | 0.01048420 | 52405.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11475.22 | 31.85 | 0.01409688 | 23.04 | 0.20572670 | 19.9187 | 23.89 | 0.00952170 | 23.89 | 0.00915428 | 49.5390 | 11083.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31514.440 | 31514.440 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.032827 | 1.24310575 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31514.44 | 31514.44 | 1.0000 | 1.24310575 | 1.032827 | 9.79 | 6.60 | 0.00475255 | 21805.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31514.44 | -10.70 | 0.00150390 | -10.70 | 0.20572670 | 19.9188 | 21.11 | 0.00654782 | 21.10 | 0.00654782 | 42.1349 | 11168.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19617.475 | 0.000 | 1.711660 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.6782 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 19617.47 | 14202.32 | 1.0000 | 2.06014539 | 1.711660 | 25.82 | 18.77 | 0.01067173 | 53142.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19617.47 | 31.85 | 0.01409688 | 23.04 | 0.41145340 | 24.0383 | 23.89 | 0.00957741 | 23.89 | 0.00922488 | 49.9160 | 19227.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 54748.744 | 54748.744 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.711663 | 2.06014851 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 54748.74 | 54748.74 | 1.0000 | 2.06014851 | 1.711663 | 9.30 | 6.33 | 0.00472971 | 21256.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54748.74 | -10.70 | 0.00150390 | -10.70 | 0.41145340 | 24.0382 | 21.11 | 0.00663374 | 21.11 | 0.00663374 | 42.6810 | 21420.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 10466.730 | 0.000 | 0.918040 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.6516 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 10466.73 | 7579.51 | 1.0000 | 1.10494834 | 0.918040 | 25.73 | 18.73 | 0.01065742 | 53022.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10466.73 | 31.79 | 0.01409687 | 23.02 | 0.20572670 | 22.4093 | 23.89 | 0.00960827 | 23.89 | 0.00916857 | 49.6153 | 9959.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28891.451 | 28891.451 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.918038 | 1.10494550 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28891.45 | 28891.45 | 1.0000 | 1.10494550 | 0.918038 | 10.10 | 6.83 | 0.00481915 | 22291.3 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28891.45 | -10.70 | 0.00150390 | -10.70 | 0.20572670 | 22.4094 | 21.11 | 0.00657360 | 21.10 | 0.00657360 | 42.2991 | 11487.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 10411.885 | 0.000 | 0.911480 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.6751 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 10411.89 | 7529.62 | 1.0000 | 1.09705275 | 0.911480 | 25.75 | 18.75 | 0.01067004 | 53068.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10411.89 | 31.79 | 0.01409687 | 23.02 | 0.20572670 | 22.5706 | 23.89 | 0.00961472 | 23.89 | 0.00918377 | 49.6965 | 9886.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28741.591 | 28741.591 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.911479 | 1.09705194 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28741.59 | 28741.59 | 1.0000 | 1.09705194 | 0.911479 | 10.09 | 6.83 | 0.00481654 | 22272.2 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28741.59 | -10.70 | 0.00150390 | -10.70 | 0.20572670 | 22.5706 | 21.11 | 0.00657261 | 21.10 | 0.00657261 | 42.2928 | 11474.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 10344.115 | 0.000 | 0.904330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.6916 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 10344.11 | 7473.51 | 1.0000 | 1.08844705 | 0.904330 | 25.76 | 18.76 | 0.01067894 | 53101.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10344.11 | 31.79 | 0.01409687 | 23.02 | 0.20572670 | 22.7491 | 23.89 | 0.00961927 | 23.89 | 0.00920673 | 49.8193 | 9835.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28578.123 | 28578.123 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.904326 | 1.08844188 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28578.12 | 28578.12 | 1.0000 | 1.08844188 | 0.904326 | 10.25 | 6.95 | 0.00485261 | 22532.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28578.12 | -10.70 | 0.00150390 | -10.70 | 0.20572670 | 22.7492 | 21.11 | 0.00658690 | 21.10 | 0.00658690 | 42.3838 | 11651.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 10633.075 | 0.000 | 0.939960 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5753 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 10633.08 | 7729.87 | 1.0000 | 1.13133114 | 0.939960 | 25.66 | 18.68 | 0.01061638 | 52843.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10633.08 | 31.73 | 0.01409688 | 23.00 | 0.20572670 | 21.8868 | 23.89 | 0.00959829 | 23.89 | 0.00920932 | 49.8336 | 10317.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29392.868 | 29392.868 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.939964 | 1.13133565 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29392.87 | 29392.87 | 1.0000 | 1.13133565 | 0.939964 | 11.64 | 7.92 | 0.00510805 | 24583.2 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29392.87 | -10.70 | 0.00150390 | -10.70 | 0.20572670 | 21.8867 | 21.11 | 0.00663495 | 21.10 | 0.00663495 | 42.6911 | 13359.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:35
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialEnthalpy | 0.41 | 1.81 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.01 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.04 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.03 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.03 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialEnthalpy | 0.41 | 1.71 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 0.92 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 0.91 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 0.90 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 0.94 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 2732.67 | 3127.00 | 600.33 |
SMSTORE1 | 2399.83 | 2857.33 | 192.67 |
SMSTORE2 | 1972.00 | 2278.33 | 326.00 |
SMSTORE3 | 2002.67 | 2337.67 | 373.17 |
SMSTORE4 | 2018.83 | 2407.50 | 438.67 |
LGSTORE2 | 1962.67 | 2355.00 | 649.83 |
SMSTORE5 | 1940.83 | 2417.83 | 711.33 |
SMSTORE6 | 1964.33 | 2452.83 | 759.83 |
SMSTORE7 | 2073.67 | 2518.33 | 911.33 |
SMSTORE8 | 2462.33 | 2688.67 | 1399.33 |
Facility | 3764.00 | 3796.00 | 1702.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 2.67 | 0.00 | 0.33 | 0.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.33 | 0.17 | 0.00 | 0.00 |
SMSTORE4 | 0.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 1.17 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.83 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 1.17 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 2.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 13.33 | 0.00 | 0.00 | 0.00 |
Facility | 16.17 | 0.17 | 0.33 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:35
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.914 | 0.236 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.806 | 0.248 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 0.983 | 0.323 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 0.977 | 0.323 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 0.969 | 0.323 | 0.000 | 0.000 |
LGSTORE2 | 13.22 | 30.00 | 1805.20 | 0.923 | 0.310 | 0.000 | 0.000 |
SMSTORE5 | 6.61 | 15.00 | 902.60 | 0.933 | 0.344 | 0.000 | 0.000 |
SMSTORE6 | 6.61 | 15.00 | 902.60 | 0.930 | 0.344 | 0.000 | 0.000 |
SMSTORE7 | 6.61 | 15.00 | 902.60 | 0.924 | 0.344 | 0.000 | 0.000 |
SMSTORE8 | 6.61 | 15.00 | 902.60 | 0.923 | 0.369 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 13.22 | 30.00 | 1805.20 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 6.61 | 15.00 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 6.61 | 15.00 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 6.61 | 15.00 | 902.60 | 0.797 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 6.61 | 15.00 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:35
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:20:35
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1056.75 | 3448.90 | 01-JAN-07:50 | 106010.89 | 16-AUG-12:40 |
Electricity:Building | 679.00 | 2237.90 | 01-JAN-00:10 | 42165.88 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 155.25 | 423.51 | 01-JAN-00:10 | 7978.91 | 01-JAN-10:10 |
InteriorLights:Electricity | 550.85 | 1795.07 | 01-JAN-08:10 | 34106.38 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 129.00 | 349.25 | 01-JAN-08:10 | 6635.66 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 550.85 | 1795.07 | 01-JAN-08:10 | 34106.38 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 86.85 | 236.79 | 01-JAN-00:10 | 4464.19 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 73.73 | 199.61 | 01-JAN-08:10 | 3792.57 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 63.46 | 218.04 | 01-JAN-00:10 | 4114.78 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 53.04 | 181.22 | 01-JAN-00:10 | 3443.15 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 63.46 | 218.04 | 01-JAN-00:10 | 4114.78 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 53.04 | 181.22 | 01-JAN-00:10 | 3443.15 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 63.46 | 218.04 | 01-JAN-00:10 | 4114.78 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 53.04 | 181.22 | 01-JAN-00:10 | 3443.15 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 82.18 | 307.83 | 01-JAN-00:10 | 5792.81 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 63.00 | 234.19 | 01-JAN-00:10 | 4449.56 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 41.09 | 153.91 | 01-JAN-00:10 | 2896.41 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 31.50 | 117.09 | 01-JAN-00:10 | 2224.78 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 41.09 | 153.91 | 01-JAN-00:10 | 2896.41 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 31.50 | 117.09 | 01-JAN-00:10 | 2224.78 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 41.09 | 153.91 | 01-JAN-00:10 | 2896.41 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 31.50 | 117.09 | 01-JAN-00:10 | 2224.78 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 41.09 | 153.91 | 01-JAN-00:10 | 2896.41 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 31.50 | 117.09 | 01-JAN-00:10 | 2224.78 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
Electricity:Plant | 63.63 | 1211.00 | 05-JAN-07:10 | 11862.96 | 24-JAN-14:00 |
WaterSystems:Electricity | 63.63 | 1211.00 | 05-JAN-07:10 | 11862.96 | 24-JAN-14:00 |
Water Heater:WaterSystems:Electricity | 63.63 | 1211.00 | 05-JAN-07:10 | 11862.96 | 24-JAN-14:00 |
ElectricityPurchased:Facility | 1056.75 | 3448.90 | 01-JAN-07:50 | 106010.89 | 16-AUG-12:40 |
ElectricityPurchased:Plant | 1056.75 | 3448.90 | 01-JAN-07:50 | 106010.89 | 16-AUG-12:40 |
Cogeneration:ElectricityPurchased | 1056.75 | 3448.90 | 01-JAN-07:50 | 106010.89 | 16-AUG-12:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1056.75 | 3448.90 | 01-JAN-07:50 | 106010.89 | 16-AUG-12:40 |
ElectricityNet:Plant | 1056.75 | 3448.90 | 01-JAN-07:50 | 106010.89 | 16-AUG-12:40 |
Cogeneration:ElectricityNet | 1056.75 | 3448.90 | 01-JAN-07:50 | 106010.89 | 16-AUG-12:40 |
Electricity:HVAC | 222.07 | 0.00 | 01-JAN-00:10 | 58008.90 | 08-JUL-12:10 |
Fans:Electricity | 93.53 | 0.00 | 01-JAN-00:10 | 8722.97 | 08-JUL-12:20 |
General:Fans:Electricity | 93.53 | 0.00 | 01-JAN-00:10 | 8722.97 | 08-JUL-12:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 128.54 | 0.00 | 01-JAN-00:10 | 49288.03 | 08-JUL-12:10 |
ExteriorLights:Electricity | 92.04 | 0.00 | 01-JAN-07:30 | 7048.42 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 92.04 | 0.00 | 01-JAN-07:30 | 7048.42 | 01-JAN-06:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 395.70 | 0.00 | 01-JAN-00:10 | 205499.62 | 02-JAN-08:10 |
Gas:HVAC | 395.70 | 0.00 | 01-JAN-00:10 | 205499.62 | 02-JAN-08:10 |
Heating:Gas | 395.70 | 0.00 | 01-JAN-00:10 | 205499.62 | 02-JAN-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1383.64 | 0.00 | 01-JAN-00:10 | 308547.57 | 02-JAN-08:10 |
EnergyTransfer:Building | 533.46 | 0.00 | 01-JAN-00:10 | 144147.87 | 02-JAN-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 113.88 | 0.00 | 01-JAN-00:10 | 24839.79 | 06-FEB-08:10 |
Heating:EnergyTransfer | 77.73 | 0.00 | 01-JAN-00:10 | 144145.05 | 02-JAN-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 9.09 | 0.00 | 01-JAN-00:10 | 24839.79 | 06-FEB-08:10 |
Cooling:EnergyTransfer | 455.73 | 0.00 | 01-JAN-00:10 | 89850.46 | 18-AUG-13:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 104.79 | 0.00 | 01-JAN-00:10 | 15298.50 | 18-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE1 | 61.04 | 0.00 | 01-JAN-00:10 | 9087.64 | 25-OCT-20:20 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 2.27 | 0.00 | 01-JAN-00:10 | 8784.47 | 06-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 58.77 | 0.00 | 01-JAN-00:10 | 9087.64 | 25-OCT-20:20 |
EnergyTransfer:Zone:SMSTORE2 | 46.73 | 0.00 | 01-JAN-00:10 | 11372.90 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 3.62 | 0.00 | 01-JAN-00:10 | 11372.90 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 43.11 | 0.00 | 01-JAN-00:10 | 8052.00 | 18-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE3 | 46.13 | 0.00 | 01-JAN-00:10 | 12865.49 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 4.21 | 0.00 | 01-JAN-00:10 | 12865.49 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 41.91 | 0.00 | 01-JAN-00:10 | 8058.97 | 18-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 44.42 | 0.00 | 01-JAN-00:10 | 13975.27 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 5.10 | 0.00 | 01-JAN-00:10 | 13975.27 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 39.32 | 0.00 | 01-JAN-00:10 | 7905.97 | 18-AUG-13:00 |
EnergyTransfer:Zone:LGSTORE2 | 71.07 | 0.00 | 01-JAN-00:10 | 31438.51 | 02-JAN-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 12.59 | 0.00 | 01-JAN-00:10 | 31438.51 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 58.48 | 0.00 | 01-JAN-00:10 | 13750.60 | 10-JUL-14:30 |
EnergyTransfer:Zone:SMSTORE5 | 36.74 | 0.00 | 01-JAN-00:10 | 16238.91 | 02-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 7.56 | 0.00 | 01-JAN-00:10 | 16238.91 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 29.18 | 0.00 | 01-JAN-00:10 | 7151.01 | 10-JUL-14:30 |
EnergyTransfer:Zone:SMSTORE6 | 36.36 | 0.00 | 01-JAN-00:10 | 16372.30 | 02-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 7.93 | 0.00 | 01-JAN-00:10 | 16372.30 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 28.43 | 0.00 | 01-JAN-00:10 | 7086.68 | 10-JUL-14:30 |
EnergyTransfer:Zone:SMSTORE7 | 36.20 | 0.00 | 01-JAN-00:10 | 17102.11 | 02-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 9.36 | 0.00 | 01-JAN-00:10 | 17102.11 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 26.84 | 0.00 | 01-JAN-00:10 | 7018.47 | 10-JUL-14:30 |
EnergyTransfer:Zone:SMSTORE8 | 40.89 | 0.00 | 01-JAN-00:10 | 18197.44 | 02-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 16.00 | 0.00 | 01-JAN-00:10 | 18197.44 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 24.89 | 0.00 | 01-JAN-00:10 | 7534.59 | 18-AUG-13:00 |
EnergyTransfer:HVAC | 850.18 | 0.00 | 01-JAN-00:10 | 206664.79 | 08-JUL-12:20 |
HeatingCoils:EnergyTransfer | 316.56 | 0.00 | 01-JAN-00:10 | 164399.70 | 02-JAN-08:10 |
CoolingCoils:EnergyTransfer | 533.63 | 0.00 | 01-JAN-00:10 | 206664.79 | 08-JUL-12:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:35
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 9.092 | -104.788 | 0.000 | 0.000 | 13.348 | 128.996 | 26.249 | 19.727 | 0.000 | 2.349 | 0.005 | 0.000 | -10.218 | 0.000 | -34.966 | -49.789 |
SMSTORE1 | 0.000 | 0.000 | 2.270 | -58.771 | 0.000 | 0.000 | 6.572 | 73.727 | 13.125 | 9.793 | 0.000 | 1.259 | 0.000 | 0.000 | -5.363 | 0.000 | -16.779 | -25.832 |
SMSTORE2 | 0.000 | 0.000 | 3.621 | -43.109 | 0.000 | 0.000 | 4.004 | 53.039 | 10.421 | 9.787 | 0.000 | 1.241 | 0.000 | 0.000 | -5.294 | 0.000 | -17.379 | -16.331 |
SMSTORE3 | 0.000 | 0.000 | 4.212 | -41.914 | 0.000 | 0.000 | 4.008 | 53.039 | 10.421 | 9.801 | 0.000 | 1.241 | 0.003 | 0.000 | -5.234 | 0.000 | -17.304 | -18.270 |
SMSTORE4 | 0.000 | 0.000 | 5.099 | -39.321 | 0.000 | 0.000 | 4.016 | 53.039 | 10.421 | 9.825 | 0.000 | 1.241 | 0.002 | 0.000 | -5.165 | 0.000 | -17.203 | -21.951 |
LGSTORE2 | 0.000 | 0.000 | 12.590 | -58.483 | 0.000 | 0.000 | 13.839 | 63.003 | 19.173 | 19.756 | 0.000 | 2.243 | 0.007 | 0.000 | -9.953 | 0.000 | -31.558 | -30.609 |
SMSTORE5 | 0.000 | 0.000 | 7.557 | -29.183 | 0.000 | 0.000 | 6.925 | 31.501 | 9.586 | 9.882 | 0.000 | 1.245 | 0.002 | 0.000 | -4.963 | 0.000 | -17.103 | -15.449 |
SMSTORE6 | 0.000 | 0.000 | 7.927 | -28.428 | 0.000 | 0.000 | 6.931 | 31.501 | 9.586 | 9.895 | 0.000 | 1.246 | 0.002 | 0.000 | -4.934 | 0.000 | -17.059 | -16.666 |
SMSTORE7 | 0.000 | 0.000 | 9.360 | -26.835 | 0.000 | 0.000 | 6.943 | 31.501 | 9.586 | 9.923 | 0.000 | 1.246 | 0.006 | 0.000 | -4.857 | 0.000 | -16.949 | -19.919 |
SMSTORE8 | 0.000 | 0.000 | 15.999 | -24.893 | 0.000 | 0.000 | 6.964 | 31.501 | 9.586 | 9.995 | 0.000 | 1.329 | 0.002 | 0.000 | -4.581 | 0.000 | -22.015 | -23.884 |
Total Facility | 0.000 | 0.000 | 77.727 | -455.726 | 0.000 | 0.000 | 73.548 | 550.849 | 128.154 | 118.384 | 0.000 | 14.639 | 0.028 | 0.000 | -60.562 | 0.000 | -208.314 | -238.700 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 25-AUG-07:02 | 0.00 | 0.00 | 0.00 | -39174.89 | 0.00 | 0.00 | 0.00 | 349.87 | 73.64 | 84.61 | 0.00 | 0.00 | 38961.46 | 0.00 | -0.00 | 0.00 | -294.69 | 0.00 |
SMSTORE1 | 25-AUG-07:02 | 0.00 | 0.00 | 0.00 | -21807.24 | 0.00 | 0.00 | 0.00 | 199.97 | 36.82 | 38.28 | 0.00 | 0.00 | 21679.17 | 0.00 | -0.00 | 0.00 | -147.00 | 0.00 |
SMSTORE2 | 15-SEP-06:02 | 0.00 | 0.00 | 0.00 | -22276.33 | 0.00 | 0.00 | 0.00 | 181.22 | 36.82 | 0.00 | 0.00 | 0.00 | 22261.71 | 0.00 | -177.71 | 0.00 | -25.71 | 0.00 |
SMSTORE3 | 15-SEP-06:02 | 0.00 | 0.00 | 0.00 | -22123.15 | 0.00 | 0.00 | 0.00 | 181.22 | 36.82 | 0.00 | 0.00 | 0.00 | 22108.85 | 0.00 | -177.96 | 0.00 | -25.77 | 0.00 |
SMSTORE4 | 15-SEP-06:02 | 0.00 | 0.00 | 0.00 | -21998.72 | 0.00 | 0.00 | 0.00 | 181.22 | 36.82 | 0.00 | 0.00 | 0.00 | 21981.58 | 0.00 | -175.51 | 0.00 | -25.38 | 0.00 |
LGSTORE2 | 25-AUG-07:02 | 0.00 | 0.00 | 0.00 | -37250.10 | 0.00 | 0.00 | 0.00 | 234.19 | 73.64 | 86.08 | 0.00 | 0.00 | 37119.42 | 0.00 | -0.00 | 0.00 | -263.23 | 0.00 |
SMSTORE5 | 25-AUG-07:02 | 0.00 | 0.00 | 0.00 | -19529.26 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 45.04 | 0.00 | 0.00 | 19470.97 | 0.00 | -0.00 | 0.00 | -140.66 | 0.00 |
SMSTORE6 | 25-AUG-07:02 | 0.00 | 0.00 | 0.00 | -18828.28 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 45.93 | 0.00 | 0.00 | 18768.99 | 0.00 | -0.00 | 0.00 | -140.55 | 0.00 |
SMSTORE7 | 23-AUG-07:02 | 0.00 | 0.00 | 0.00 | -17463.85 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 117.22 | 0.00 | 0.00 | 17271.39 | 0.00 | -0.00 | 0.00 | -78.68 | 0.00 |
SMSTORE8 | 02-SEP-07:01 | 0.00 | 0.00 | 0.00 | -16836.46 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 152.24 | 0.00 | 0.00 | 16626.65 | 0.00 | -0.00 | 0.00 | -96.34 | 0.00 |
Total Facility | 25-AUG-07:02 | 0.00 | 0.00 | 0.00 | -171698.07 | 0.00 | 0.00 | 157.59 | 6688.96 | 1450.75 | 574.92 | 0.00 | 0.00 | 164541.14 | 0.00 | 0.00 | 0.00 | -1715.30 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 02-JAN-08:61 | 0.00 | 0.00 | 56764.40 | 0.00 | 0.00 | 0.00 | 142.98 | 349.25 | 74.62 | 384.35 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1617.22 | -56098.38 |
SMSTORE1 | 02-JAN-08:61 | 0.00 | 0.00 | 31076.08 | 0.00 | 0.00 | 0.00 | 68.87 | 199.61 | 37.31 | 171.21 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -842.21 | -30710.87 |
SMSTORE2 | 02-JAN-07:01 | 0.00 | 0.00 | 31729.63 | 0.00 | 0.00 | 0.00 | 0.00 | 181.22 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -601.44 | 0.00 | -68.70 | -31277.52 |
SMSTORE3 | 02-JAN-07:01 | 0.00 | 0.00 | 31558.18 | 0.00 | 0.00 | 0.00 | 0.00 | 181.22 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -588.83 | 0.00 | -67.31 | -31120.08 |
SMSTORE4 | 02-JAN-07:01 | 0.00 | 0.00 | 31551.35 | 0.00 | 0.00 | 0.00 | 0.00 | 181.22 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -580.63 | 0.00 | -66.37 | -31122.38 |
LGSTORE2 | 02-JAN-08:12 | 0.00 | 0.00 | 55185.85 | 0.00 | 0.00 | 0.00 | 0.00 | 234.19 | 73.64 | 710.63 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1591.17 | -54613.14 |
SMSTORE5 | 02-JAN-08:12 | 0.00 | 0.00 | 29153.74 | 0.00 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 354.02 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -876.48 | -28785.20 |
SMSTORE6 | 02-JAN-08:12 | 0.00 | 0.00 | 29018.92 | 0.00 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 354.87 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -875.36 | -28652.35 |
SMSTORE7 | 02-JAN-08:12 | 0.00 | 0.00 | 28898.87 | 0.00 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 358.25 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -871.11 | -28539.92 |
SMSTORE8 | 02-JAN-08:12 | 0.00 | 0.00 | 29780.75 | 0.00 | 0.00 | 0.00 | 0.00 | 117.09 | 36.82 | 367.21 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1027.31 | -29274.57 |
Total Facility | 02-JAN-08:61 | 0.00 | 0.00 | 274322.18 | 0.00 | 0.00 | 0.00 | 396.81 | 6687.98 | 1452.23 | 2481.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9650.40 | -275690.20 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:35
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.7829 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.8064 | 0.2278 | 1.0000 | 0.4115 | 0.2278 | ||
PSZ-AC_2:2 | 1.0110 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0110 | 0.2035 | 1.0000 | 0.2057 | 0.2035 | ||
PSZ-AC_3:3 | 1.0411 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0411 | 0.1976 | 1.0000 | 0.2057 | 0.1976 | ||
PSZ-AC_4:4 | 1.0332 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0332 | 0.1991 | 1.0000 | 0.2057 | 0.1991 | ||
PSZ-AC_5:5 | 1.0328 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0328 | 0.1992 | 1.0000 | 0.2057 | 0.1992 | ||
PSZ-AC_6:6 | 1.7033 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.7117 | 0.2404 | 1.0000 | 0.4115 | 0.2404 | ||
PSZ-AC_7:7 | 0.9180 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9180 | 0.2241 | 1.0000 | 0.2057 | 0.2241 | ||
PSZ-AC_8:8 | 0.9115 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9115 | 0.2257 | 1.0000 | 0.2057 | 0.2257 | ||
PSZ-AC_9:9 | 0.9043 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9043 | 0.2275 | 1.0000 | 0.2057 | 0.2275 | ||
PSZ-AC_10:10 | 0.9400 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9400 | 0.2189 | 1.0000 | 0.2057 | 0.2189 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.7829 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.7829 | 1.0000 | 1.0000 | 0.4115 | 0.2308 | ||
PSZ-AC_2:2 | 1.0110 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0110 | 1.0000 | 1.0000 | 0.2057 | 0.2035 | ||
PSZ-AC_3:3 | 1.0411 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0411 | 1.0000 | 1.0000 | 0.2057 | 0.1976 | ||
PSZ-AC_4:4 | 1.0332 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0332 | 1.0000 | 1.0000 | 0.2057 | 0.1991 | ||
PSZ-AC_5:5 | 1.0328 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0328 | 1.0000 | 1.0000 | 0.2057 | 0.1992 | ||
PSZ-AC_6:6 | 1.7033 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.7033 | 1.0000 | 1.0000 | 0.4115 | 0.2416 | ||
PSZ-AC_7:7 | 0.9180 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9180 | 1.0000 | 1.0000 | 0.2057 | 0.2241 | ||
PSZ-AC_8:8 | 0.9115 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9115 | 1.0000 | 1.0000 | 0.2057 | 0.2257 | ||
PSZ-AC_9:9 | 0.9043 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9043 | 1.0000 | 1.0000 | 0.2057 | 0.2275 | ||
PSZ-AC_10:10 | 0.9400 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9400 | 1.0000 | 1.0000 | 0.2057 | 0.2189 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 1.7829 | 1.7829 | 1.7829 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.0110 | 1.0110 | 1.0110 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.0411 | 1.0411 | 1.0411 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.0332 | 1.0332 | 1.0332 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.0328 | 1.0328 | 1.0328 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 1.7033 | 1.7033 | 1.7033 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 0.9180 | 0.9180 | 0.9180 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 0.9115 | 0.9115 | 0.9115 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 0.9043 | 0.9043 | 0.9043 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 0.9400 | 0.9400 | 0.9400 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.7829 | 1.8064 | 1.7829 | 1.7829 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0110 | 1.0110 | 1.0110 | 1.0110 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0411 | 1.0411 | 1.0411 | 1.0411 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0332 | 1.0332 | 1.0332 | 1.0332 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0328 | 1.0328 | 1.0328 | 1.0328 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.7033 | 1.7117 | 1.7033 | 1.7033 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9180 | 0.9180 | 0.9180 | 0.9180 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9115 | 0.9115 | 0.9115 | 0.9115 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9043 | 0.9043 | 0.9043 | 0.9043 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.9400 | 0.9400 | 0.9400 | 0.9400 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 1.7829 | 1.7829 | 1.7829 | 0.4115 | 0.3633 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.0110 | 1.0110 | 1.0110 | 0.2057 | 0.3705 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.0411 | 1.0411 | 1.0411 | 0.2057 | 0.3643 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.0332 | 1.0332 | 1.0332 | 0.2057 | 0.3609 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.0328 | 1.0328 | 1.0328 | 0.2057 | 0.3559 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 1.7033 | 1.7033 | 1.7033 | 0.4115 | 0.3712 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 0.9180 | 0.9180 | 0.9180 | 0.2057 | 0.3461 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 0.9115 | 0.9115 | 0.9115 | 0.2057 | 0.3465 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 0.9043 | 0.9043 | 0.9043 | 0.2057 | 0.3412 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 0.9400 | 0.9400 | 0.9400 | 0.2057 | 0.2976 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.7829 | 1.7829 | 1.7829 | 1.7829 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0110 | 1.0110 | 1.0110 | 1.0110 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0411 | 1.0411 | 1.0411 | 1.0411 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0332 | 1.0332 | 1.0332 | 1.0332 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0328 | 1.0328 | 1.0328 | 1.0328 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.7033 | 1.7033 | 1.7033 | 1.7033 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9180 | 0.9180 | 0.9180 | 0.9180 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9115 | 0.9115 | 0.9115 | 0.9115 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9043 | 0.9043 | 0.9043 | 0.9043 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.9400 | 0.9400 | 0.9400 | 0.9400 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:35
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.33 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 395.70 | 205499.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 128.54 | 49288.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 550.85 | 34106.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 92.04 | 7048.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 93.53 | 8722.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 63.63 | 11862.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 1056.75 |
Natural Gas | 0.00 | 395.70 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1452.44 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 263.52 |
Space Heating | 0.00 |
Space Cooling | 61.49 |
Fans (All) | 44.75 |
Service Water Heating | 30.44 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 505.54 |
Subtotal | 505.54 |
Natural Gas [MJ/m2] | |
Space Heating | 189.30 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 189.30 |
Subtotal | 189.30 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 37.93 |
Space Heating | 27.24 |
Space Cooling | 8.85 |
Fans (All) | 6.44 |
Service Water Heating | 4.38 |
Receptacle Equipment | 8.82 |
Miscellaneous | 6.34 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
TYPE1_LIGHT_SCH | 5122. | 8760. |
TYPE2_LIGHT_SCH | 4096. | 8760. |
TYPE3_LIGHT_SCH | 3767. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUALSPSCHED | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.106631E+12 |
February | 0.000 | 0.100984E+12 |
March | 0.000 | 0.562084E+11 |
April | 0.000 | 0.183643E+11 |
May | 0.000 | 0.381174E+09 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.258219E+09 |
November | 0.000 | 0.351313E+11 |
December | 0.000 | 0.777369E+11 |
Annual Sum or Average | 0.395695E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.106631E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.106631E+12 |
February | 0.000 | 0.100984E+12 |
March | 0.000 | 0.562084E+11 |
April | 0.000 | 0.183643E+11 |
May | 0.000 | 0.381174E+09 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.258219E+09 |
November | 0.000 | 0.351313E+11 |
December | 0.000 | 0.777369E+11 |
Annual Sum or Average | 0.395695E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.106631E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Meter
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.106631E+12 |
February | 0.000 | 0.100984E+12 |
March | 0.000 | 0.562084E+11 |
April | 0.000 | 0.183643E+11 |
May | 0.000 | 0.381174E+09 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.258219E+09 |
November | 0.000 | 0.351313E+11 |
December | 0.000 | 0.777369E+11 |
Annual Sum or Average | 0.395695E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.106631E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.106631E+12 |
February | 0.000 | 0.100984E+12 |
March | 0.000 | 0.562084E+11 |
April | 0.000 | 0.183643E+11 |
May | 0.000 | 0.381174E+09 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.258219E+09 |
November | 0.000 | 0.351313E+11 |
December | 0.000 | 0.777369E+11 |
Annual Sum or Average | 0.395695E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.106631E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Meter
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.106631E+12 |
February | 0.000 | 0.100984E+12 |
March | 0.000 | 0.562084E+11 |
April | 0.000 | 0.183643E+11 |
May | 0.000 | 0.381174E+09 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.258219E+09 |
November | 0.000 | 0.351313E+11 |
December | 0.000 | 0.777369E+11 |
Annual Sum or Average | 0.395695E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.106631E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.106631E+12 |
February | 0.000 | 0.100984E+12 |
March | 0.000 | 0.562084E+11 |
April | 0.000 | 0.183643E+11 |
May | 0.000 | 0.381174E+09 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.258219E+09 |
November | 0.000 | 0.351313E+11 |
December | 0.000 | 0.777369E+11 |
Annual Sum or Average | 0.395695E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.106631E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.106631E+12 |
February | 0.000 | 0.100984E+12 |
March | 0.000 | 0.562084E+11 |
April | 0.000 | 0.183643E+11 |
May | 0.000 | 0.381174E+09 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.258219E+09 |
November | 0.000 | 0.351313E+11 |
December | 0.000 | 0.777369E+11 |
Annual Sum or Average | 0.395695E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.106631E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Meter
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.106631E+12 |
February | 0.000 | 0.100984E+12 |
March | 0.000 | 0.562084E+11 |
April | 0.000 | 0.183643E+11 |
May | 0.000 | 0.381174E+09 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.258219E+09 |
November | 0.000 | 0.351313E+11 |
December | 0.000 | 0.777369E+11 |
Annual Sum or Average | 0.395695E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.106631E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Meter
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.106631E+12 |
February | 0.000 | 0.100984E+12 |
March | 0.000 | 0.562084E+11 |
April | 0.000 | 0.183643E+11 |
May | 0.000 | 0.381174E+09 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.258219E+09 |
November | 0.000 | 0.351313E+11 |
December | 0.000 | 0.777369E+11 |
Annual Sum or Average | 0.395695E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.106631E+12 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.208391E+10 | 11758.94 | 02-JAN-18:52 | -5.0 | -8.0 | 0.568205E+09 | 680.13 | 16-JAN-13:09 | 2.67 | 0.71 |
February | 0.190201E+10 | 14849.66 | 05-FEB-22:02 | -11.3 | -12.9 | 0.512887E+09 | 680.12 | 10-FEB-13:20 | 2.80 | -0.5 |
March | 0.426075E+10 | 10186.61 | 17-MAR-23:03 | -1.7 | -1.9 | 0.576963E+09 | 800.83 | 03-MAR-13:00 | 15.00 | 8.61 |
April | 0.599062E+10 | 8206.83 | 08-APR-12:30 | 23.60 | 16.17 | 0.622888E+09 | 899.04 | 07-APR-12:00 | 26.70 | 16.37 |
May | 0.891936E+10 | 26585.92 | 31-MAY-07:03 | 21.38 | 17.98 | 0.735153E+09 | 899.05 | 28-MAY-16:10 | 23.43 | 15.48 |
June | 0.133141E+11 | 31365.21 | 23-JUN-07:02 | 23.45 | 17.62 | 0.722028E+09 | 899.06 | 04-JUN-16:10 | 22.02 | 14.52 |
July | 0.167837E+11 | 32784.81 | 11-JUL-07:02 | 22.30 | 16.04 | 0.753628E+09 | 899.04 | 04-JUL-17:49 | 24.08 | 18.48 |
August | 0.175802E+11 | 39179.43 | 25-AUG-07:02 | 18.48 | 12.47 | 0.743125E+09 | 899.07 | 20-AUG-17:30 | 24.15 | 18.27 |
September | 0.136808E+11 | 37624.27 | 15-SEP-07:02 | 17.38 | 13.03 | 0.728149E+09 | 899.06 | 29-SEP-12:09 | 20.10 | 13.47 |
October | 0.111745E+11 | 35722.03 | 14-OCT-07:02 | 14.50 | 13.57 | 0.732466E+09 | 899.06 | 22-OCT-16:10 | 18.90 | 16.82 |
November | 0.574605E+10 | 10895.96 | 24-NOV-00:03 | -3.3 | -5.7 | 0.596342E+09 | 899.03 | 04-NOV-12:20 | 17.80 | 12.56 |
December | 0.335303E+10 | 10934.47 | 22-DEC-00:03 | -3.3 | -5.8 | 0.571561E+09 | 724.98 | 17-DEC-13:00 | 12.20 | 5.27 |
Annual Sum or Average | 0.104789E+12 | 0.786340E+10 | ||||||||
Minimum of Months | 0.190201E+10 | 8206.83 | -11.3 | -12.9 | 0.512887E+09 | 680.12 | 2.67 | -0.5 | ||
Maximum of Months | 0.175802E+11 | 39179.43 | 23.60 | 17.98 | 0.753628E+09 | 899.07 | 26.70 | 18.48 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113550E+10 | 4986.17 | 01-JAN-10:13 | -1.8 | -5.0 | 0.296348E+09 | 412.70 | 22-JAN-18:00 | 6.10 | 5.30 |
February | 0.105532E+10 | 3697.05 | 19-FEB-09:01 | 4.37 | 2.78 | 0.267858E+09 | 416.53 | 20-FEB-18:00 | 3.90 | 2.68 |
March | 0.227496E+10 | 4441.25 | 19-MAR-08:23 | 0.60 | 0.49 | 0.307721E+09 | 449.41 | 26-MAR-17:00 | 10.00 | 9.07 |
April | 0.336962E+10 | 17881.60 | 10-APR-20:09 | 15.22 | 7.89 | 0.327960E+09 | 449.52 | 08-APR-12:30 | 23.60 | 16.17 |
May | 0.550907E+10 | 17622.19 | 30-MAY-07:03 | 23.17 | 16.05 | 0.371431E+09 | 449.53 | 28-MAY-16:49 | 21.57 | 15.20 |
June | 0.771265E+10 | 17843.57 | 23-JUN-07:02 | 23.45 | 17.62 | 0.360532E+09 | 449.53 | 04-JUN-16:10 | 22.02 | 14.52 |
July | 0.936082E+10 | 18452.25 | 11-JUL-07:02 | 22.30 | 16.04 | 0.376821E+09 | 449.50 | 04-JUL-17:10 | 24.82 | 18.28 |
August | 0.966386E+10 | 21809.74 | 25-AUG-07:02 | 18.48 | 12.47 | 0.371496E+09 | 449.53 | 20-AUG-16:00 | 25.00 | 17.88 |
September | 0.774711E+10 | 21038.86 | 15-SEP-07:02 | 17.38 | 13.03 | 0.363608E+09 | 449.53 | 29-SEP-12:09 | 20.10 | 13.47 |
October | 0.625417E+10 | 19809.96 | 14-OCT-07:02 | 14.50 | 13.57 | 0.371749E+09 | 449.53 | 22-OCT-16:10 | 18.90 | 16.82 |
November | 0.297870E+10 | 10978.62 | 03-NOV-20:15 | 12.80 | 10.66 | 0.316590E+09 | 449.52 | 04-NOV-12:20 | 17.80 | 12.56 |
December | 0.170981E+10 | 4169.21 | 06-DEC-09:23 | 1.40 | -1.1 | 0.302001E+09 | 444.60 | 17-DEC-18:00 | 7.80 | 3.51 |
Annual Sum or Average | 0.587716E+11 | 0.403411E+10 | ||||||||
Minimum of Months | 0.105532E+10 | 3697.05 | -1.8 | -5.0 | 0.267858E+09 | 412.70 | 3.90 | 2.68 | ||
Maximum of Months | 0.966386E+10 | 21809.74 | 23.45 | 17.62 | 0.376821E+09 | 449.53 | 25.00 | 18.28 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.721316E+09 | 5286.93 | 08-JAN-11:02 | -3.1 | -4.6 | 0.169144E+09 | 340.06 | 07-JAN-13:00 | 0.60 | -4.0 |
February | 0.690154E+09 | 5076.48 | 14-FEB-09:43 | -2.3 | -5.4 | 0.153637E+09 | 340.06 | 18-FEB-13:09 | 6.78 | 3.76 |
March | 0.176807E+10 | 4437.93 | 08-MAR-08:61 | 1.28 | 1.28 | 0.179448E+09 | 374.58 | 27-MAR-17:19 | 20.37 | 15.14 |
April | 0.250178E+10 | 4728.27 | 08-APR-12:20 | 23.87 | 16.20 | 0.188809E+09 | 449.48 | 08-APR-12:00 | 22.80 | 16.06 |
May | 0.379949E+10 | 16520.97 | 30-MAY-06:03 | 20.47 | 15.44 | 0.224610E+09 | 449.51 | 27-MAY-12:09 | 19.60 | 12.78 |
June | 0.569429E+10 | 18096.33 | 23-JUN-06:02 | 21.38 | 16.99 | 0.222178E+09 | 449.52 | 03-JUN-12:00 | 22.80 | 14.35 |
July | 0.694034E+10 | 19159.30 | 11-JUL-06:02 | 20.87 | 15.61 | 0.223996E+09 | 449.48 | 01-JUL-12:50 | 25.68 | 20.26 |
August | 0.740698E+10 | 21942.23 | 25-AUG-06:02 | 17.88 | 13.10 | 0.230229E+09 | 449.50 | 26-AUG-12:30 | 25.30 | 18.30 |
September | 0.561069E+10 | 22282.82 | 15-SEP-06:02 | 15.37 | 12.31 | 0.218866E+09 | 449.50 | 02-SEP-12:20 | 24.60 | 17.27 |
October | 0.454000E+10 | 19271.50 | 13-OCT-06:02 | 14.18 | 14.18 | 0.219730E+09 | 449.50 | 21-OCT-12:09 | 18.98 | 15.59 |
November | 0.224062E+10 | 7580.21 | 04-NOV-06:02 | 9.90 | 8.71 | 0.179734E+09 | 449.51 | 04-NOV-12:20 | 17.80 | 12.56 |
December | 0.119564E+10 | 4506.10 | 09-DEC-08:32 | 0.20 | -1.2 | 0.169198E+09 | 340.06 | 09-DEC-13:09 | 3.98 | 1.61 |
Annual Sum or Average | 0.431094E+11 | 0.237958E+10 | ||||||||
Minimum of Months | 0.690154E+09 | 4437.93 | -3.1 | -5.4 | 0.153637E+09 | 340.06 | 0.60 | -4.0 | ||
Maximum of Months | 0.740698E+10 | 22282.82 | 23.87 | 16.99 | 0.230229E+09 | 449.52 | 25.68 | 20.26 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.597206E+09 | 5323.71 | 10-JAN-10:02 | -3.3 | -4.8 | 0.169143E+09 | 340.06 | 07-JAN-13:00 | 0.60 | -4.0 |
February | 0.585472E+09 | 6504.40 | 06-FEB-18:42 | -8.0 | -9.0 | 0.153636E+09 | 340.06 | 18-FEB-13:09 | 6.78 | 3.76 |
March | 0.157934E+10 | 4381.74 | 19-MAR-09:13 | 0.77 | 0.61 | 0.178678E+09 | 374.58 | 27-MAR-17:19 | 20.37 | 15.14 |
April | 0.232596E+10 | 4577.68 | 08-APR-12:20 | 23.87 | 16.20 | 0.187764E+09 | 449.48 | 08-APR-12:00 | 22.80 | 16.06 |
May | 0.368246E+10 | 16142.89 | 30-MAY-06:03 | 20.47 | 15.44 | 0.223888E+09 | 449.51 | 27-MAY-12:09 | 19.60 | 12.78 |
June | 0.566434E+10 | 17960.58 | 23-JUN-06:02 | 21.38 | 16.99 | 0.222173E+09 | 449.52 | 03-JUN-12:00 | 22.80 | 14.35 |
July | 0.693942E+10 | 19056.55 | 11-JUL-06:02 | 20.87 | 15.61 | 0.223993E+09 | 449.48 | 01-JUL-12:50 | 25.68 | 20.26 |
August | 0.741624E+10 | 21802.20 | 25-AUG-06:02 | 17.88 | 13.10 | 0.230227E+09 | 449.50 | 26-AUG-12:30 | 25.30 | 18.30 |
September | 0.558246E+10 | 22129.55 | 15-SEP-06:02 | 15.37 | 12.31 | 0.218855E+09 | 449.50 | 02-SEP-12:20 | 24.60 | 17.27 |
October | 0.445105E+10 | 19064.93 | 13-OCT-06:02 | 14.18 | 14.18 | 0.219153E+09 | 449.50 | 21-OCT-12:09 | 18.98 | 15.59 |
November | 0.206360E+10 | 4093.51 | 04-NOV-06:02 | 9.90 | 8.71 | 0.178305E+09 | 449.51 | 04-NOV-12:20 | 17.80 | 12.56 |
December | 0.102725E+10 | 4029.05 | 20-DEC-08:61 | 2.85 | 1.75 | 0.169120E+09 | 340.06 | 09-DEC-13:09 | 3.98 | 1.61 |
Annual Sum or Average | 0.419148E+11 | 0.237493E+10 | ||||||||
Minimum of Months | 0.585472E+09 | 4029.05 | -8.0 | -9.0 | 0.153636E+09 | 340.06 | 0.60 | -4.0 | ||
Maximum of Months | 0.741624E+10 | 22129.55 | 23.87 | 16.99 | 0.230227E+09 | 449.52 | 25.68 | 20.26 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.442339E+09 | 4351.69 | 07-JAN-09:23 | 0.85 | -1.7 | 0.169143E+09 | 340.06 | 28-JAN-13:00 | 5.60 | 4.52 |
February | 0.439773E+09 | 4410.67 | 04-FEB-18:42 | 0.60 | -1.2 | 0.153637E+09 | 340.06 | 18-FEB-13:20 | 6.87 | 3.74 |
March | 0.133644E+10 | 4840.61 | 22-MAR-08:43 | -1.3 | -4.9 | 0.177784E+09 | 374.58 | 27-MAR-16:40 | 21.47 | 15.71 |
April | 0.206916E+10 | 4258.52 | 08-APR-12:20 | 23.87 | 16.20 | 0.186350E+09 | 449.48 | 08-APR-12:00 | 22.80 | 16.06 |
May | 0.339879E+10 | 14177.23 | 30-MAY-06:03 | 20.47 | 15.44 | 0.222273E+09 | 449.51 | 27-MAY-12:09 | 19.60 | 12.78 |
June | 0.544506E+10 | 17876.10 | 23-JUN-06:02 | 21.38 | 16.99 | 0.222152E+09 | 449.52 | 03-JUN-12:00 | 22.80 | 14.35 |
July | 0.673921E+10 | 18940.15 | 11-JUL-06:02 | 20.87 | 15.61 | 0.223975E+09 | 449.47 | 29-JUL-12:00 | 26.10 | 20.42 |
August | 0.720799E+10 | 21679.01 | 25-AUG-06:02 | 17.88 | 13.10 | 0.230209E+09 | 449.50 | 26-AUG-12:39 | 25.40 | 18.33 |
September | 0.536883E+10 | 22005.14 | 15-SEP-06:02 | 15.37 | 12.31 | 0.218820E+09 | 449.50 | 02-SEP-12:30 | 24.70 | 17.22 |
October | 0.422328E+10 | 16457.39 | 13-OCT-06:02 | 14.18 | 14.18 | 0.218009E+09 | 449.50 | 21-OCT-12:09 | 18.98 | 15.59 |
November | 0.182021E+10 | 3875.73 | 18-NOV-08:61 | 3.48 | 2.23 | 0.176076E+09 | 449.50 | 04-NOV-12:30 | 17.80 | 12.60 |
December | 0.830516E+09 | 4037.43 | 30-DEC-09:43 | 2.20 | 1.69 | 0.169046E+09 | 340.06 | 09-DEC-13:00 | 4.40 | 1.80 |
Annual Sum or Average | 0.393216E+11 | 0.236747E+10 | ||||||||
Minimum of Months | 0.439773E+09 | 3875.73 | -1.3 | -4.9 | 0.153637E+09 | 340.06 | 4.40 | 1.80 | ||
Maximum of Months | 0.720799E+10 | 22005.14 | 23.87 | 16.99 | 0.230209E+09 | 449.52 | 26.10 | 20.42 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.264454E+09 | 8193.90 | 25-JAN-20:23 | 2.50 | 1.36 | 0.578271E+09 | 906.82 | 21-JAN-15:00 | 7.80 | 6.70 |
February | 0.245856E+09 | 2985.78 | 02-FEB-12:00 | 6.10 | 1.17 | 0.526487E+09 | 906.82 | 25-FEB-15:50 | 3.80 | -0.7 |
March | 0.144466E+10 | 7416.28 | 09-MAR-09:43 | 3.90 | 2.45 | 0.603424E+09 | 1063.80 | 27-MAR-16:00 | 21.10 | 15.40 |
April | 0.268708E+10 | 6987.04 | 12-APR-08:63 | 5.78 | 0.37 | 0.627278E+09 | 1198.64 | 08-APR-14:09 | 20.78 | 15.21 |
May | 0.494725E+10 | 25723.85 | 30-MAY-07:03 | 23.17 | 16.05 | 0.743081E+09 | 1198.70 | 20-MAY-14:09 | 22.88 | 13.44 |
June | 0.848329E+10 | 30388.28 | 23-JUN-07:02 | 23.45 | 17.62 | 0.761938E+09 | 1198.66 | 10-JUN-14:09 | 23.22 | 14.42 |
July | 0.108740E+11 | 31406.16 | 11-JUL-07:02 | 22.30 | 16.04 | 0.766631E+09 | 1198.61 | 01-JUL-14:39 | 25.97 | 19.88 |
August | 0.117452E+11 | 37255.43 | 25-AUG-07:02 | 18.48 | 12.47 | 0.789030E+09 | 1198.62 | 19-AUG-14:00 | 28.90 | 16.54 |
September | 0.833637E+10 | 35715.94 | 15-SEP-07:02 | 17.38 | 13.03 | 0.750979E+09 | 1198.72 | 30-SEP-14:09 | 19.40 | 13.84 |
October | 0.648032E+10 | 27660.46 | 14-OCT-07:02 | 14.50 | 13.57 | 0.733102E+09 | 1198.68 | 21-OCT-14:09 | 19.40 | 17.53 |
November | 0.232361E+10 | 5943.81 | 06-NOV-09:03 | 7.98 | 4.27 | 0.584063E+09 | 1198.65 | 04-NOV-14:20 | 16.87 | 12.93 |
December | 0.651886E+09 | 9355.66 | 06-DEC-20:33 | 0.00 | -2.4 | 0.579249E+09 | 906.82 | 09-DEC-15:00 | 5.60 | 2.32 |
Annual Sum or Average | 0.584839E+11 | 0.804353E+10 | ||||||||
Minimum of Months | 0.245856E+09 | 2985.78 | 0.00 | -2.4 | 0.526487E+09 | 906.82 | 3.80 | -0.7 | ||
Maximum of Months | 0.117452E+11 | 37255.43 | 23.45 | 17.62 | 0.789030E+09 | 1198.72 | 28.90 | 19.88 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115940E+09 | 5425.19 | 05-JAN-11:43 | -3.4 | -6.2 | 0.289134E+09 | 453.40 | 21-JAN-15:09 | 8.22 | 6.90 |
February | 0.106275E+09 | 5028.52 | 03-FEB-20:53 | -1.7 | -3.9 | 0.263242E+09 | 453.41 | 18-FEB-15:50 | 6.70 | 3.00 |
March | 0.659590E+09 | 4591.67 | 16-MAR-19:33 | 0.20 | -0.1 | 0.301428E+09 | 531.90 | 27-MAR-16:00 | 21.10 | 15.40 |
April | 0.124640E+10 | 3410.34 | 12-APR-08:63 | 5.78 | 0.37 | 0.312516E+09 | 599.32 | 08-APR-14:09 | 20.78 | 15.21 |
May | 0.239005E+10 | 11924.95 | 30-MAY-07:03 | 23.17 | 16.05 | 0.369478E+09 | 599.35 | 20-MAY-14:09 | 22.88 | 13.44 |
June | 0.429767E+10 | 16112.73 | 23-JUN-07:02 | 23.45 | 17.62 | 0.380962E+09 | 599.33 | 10-JUN-14:09 | 23.22 | 14.42 |
July | 0.556920E+10 | 16633.19 | 11-JUL-07:02 | 22.30 | 16.04 | 0.383303E+09 | 599.29 | 29-JUL-14:00 | 25.60 | 20.61 |
August | 0.601339E+10 | 19532.16 | 25-AUG-07:02 | 18.48 | 12.47 | 0.394504E+09 | 599.31 | 19-AUG-14:00 | 28.90 | 16.54 |
September | 0.421914E+10 | 17435.46 | 15-SEP-07:02 | 17.38 | 13.03 | 0.375472E+09 | 599.36 | 30-SEP-14:09 | 19.40 | 13.84 |
October | 0.319753E+10 | 13380.91 | 06-OCT-07:02 | 20.00 | 18.15 | 0.365702E+09 | 599.34 | 21-OCT-14:09 | 19.40 | 17.53 |
November | 0.108282E+10 | 2937.07 | 18-NOV-14:55 | 6.70 | 3.36 | 0.290757E+09 | 599.33 | 04-NOV-14:20 | 16.87 | 12.93 |
December | 0.285633E+09 | 4476.02 | 27-DEC-20:42 | 0.68 | 0.45 | 0.289622E+09 | 453.41 | 02-DEC-15:00 | 6.10 | 1.03 |
Annual Sum or Average | 0.291836E+11 | 0.401612E+10 | ||||||||
Minimum of Months | 0.106275E+09 | 2937.07 | -3.4 | -6.2 | 0.263242E+09 | 453.40 | 6.10 | 1.03 | ||
Maximum of Months | 0.601339E+10 | 19532.16 | 23.45 | 18.15 | 0.394504E+09 | 599.36 | 28.90 | 20.61 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 99950910.56 | 5407.23 | 05-JAN-11:53 | -3.3 | -6.1 | 0.289134E+09 | 453.40 | 21-JAN-15:09 | 8.22 | 6.90 |
February | 89064227.38 | 4294.26 | 22-FEB-10:23 | 1.40 | -2.4 | 0.263241E+09 | 453.41 | 18-FEB-15:50 | 6.70 | 3.00 |
March | 0.612571E+09 | 5017.77 | 17-MAR-19:42 | -1.6 | -2.3 | 0.301135E+09 | 531.90 | 27-MAR-16:49 | 21.28 | 15.55 |
April | 0.118098E+10 | 3378.63 | 12-APR-08:63 | 5.78 | 0.37 | 0.311318E+09 | 599.32 | 08-APR-14:09 | 20.78 | 15.21 |
May | 0.228011E+10 | 10891.31 | 30-MAY-07:03 | 23.17 | 16.05 | 0.367308E+09 | 599.35 | 20-MAY-14:09 | 22.88 | 13.44 |
June | 0.420945E+10 | 15993.14 | 23-JUN-07:02 | 23.45 | 17.62 | 0.380956E+09 | 599.33 | 10-JUN-14:09 | 23.22 | 14.42 |
July | 0.548763E+10 | 16495.44 | 11-JUL-07:02 | 22.30 | 16.04 | 0.383298E+09 | 599.29 | 29-JUL-14:00 | 25.60 | 20.61 |
August | 0.593285E+10 | 18831.01 | 25-AUG-07:02 | 18.48 | 12.47 | 0.394500E+09 | 599.31 | 19-AUG-14:00 | 28.90 | 16.54 |
September | 0.414294E+10 | 16872.08 | 02-SEP-07:01 | 21.70 | 16.22 | 0.375433E+09 | 599.36 | 30-SEP-14:09 | 19.40 | 13.84 |
October | 0.311482E+10 | 13259.81 | 06-OCT-07:02 | 20.00 | 18.15 | 0.364578E+09 | 599.34 | 21-OCT-14:09 | 19.40 | 17.53 |
November | 0.102735E+10 | 4566.29 | 24-NOV-20:42 | 0.28 | -1.9 | 0.289559E+09 | 599.32 | 04-NOV-14:50 | 17.12 | 13.03 |
December | 0.250544E+09 | 2378.47 | 20-DEC-14:25 | 9.15 | 5.46 | 0.289623E+09 | 453.41 | 02-DEC-15:00 | 6.10 | 1.03 |
Annual Sum or Average | 0.284283E+11 | 0.401008E+10 | ||||||||
Minimum of Months | 89064227.38 | 2378.47 | -3.3 | -6.1 | 0.263241E+09 | 453.40 | 6.10 | 1.03 | ||
Maximum of Months | 0.593285E+10 | 18831.01 | 23.45 | 18.15 | 0.394500E+09 | 599.36 | 28.90 | 20.61 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58918631.49 | 5621.87 | 31-JAN-11:43 | -4.2 | -7.4 | 0.289134E+09 | 453.40 | 21-JAN-15:09 | 8.22 | 6.90 |
February | 48959625.20 | 5297.37 | 03-FEB-18:12 | -2.8 | -5.0 | 0.263243E+09 | 453.41 | 18-FEB-15:00 | 6.70 | 2.97 |
March | 0.470249E+09 | 3964.65 | 13-MAR-10:13 | 2.57 | -1.5 | 0.300457E+09 | 524.74 | 27-MAR-16:40 | 21.47 | 15.71 |
April | 0.996952E+09 | 2848.94 | 11-APR-08:63 | 8.58 | 2.69 | 0.308872E+09 | 599.32 | 08-APR-14:09 | 20.78 | 15.21 |
May | 0.204137E+10 | 7711.77 | 31-MAY-07:03 | 21.38 | 17.98 | 0.362974E+09 | 599.35 | 20-MAY-14:09 | 22.88 | 13.44 |
June | 0.401231E+10 | 15797.35 | 23-JUN-07:02 | 23.45 | 17.62 | 0.380935E+09 | 599.33 | 10-JUN-14:09 | 23.22 | 14.42 |
July | 0.535241E+10 | 16276.21 | 11-JUL-07:02 | 22.30 | 16.04 | 0.383288E+09 | 599.30 | 29-JUL-14:00 | 25.60 | 20.61 |
August | 0.582026E+10 | 17465.18 | 23-AUG-07:02 | 20.87 | 14.95 | 0.394495E+09 | 599.31 | 19-AUG-14:00 | 28.90 | 16.54 |
September | 0.400303E+10 | 16668.66 | 02-SEP-07:01 | 21.70 | 16.22 | 0.375302E+09 | 599.36 | 30-SEP-14:09 | 19.40 | 13.84 |
October | 0.295094E+10 | 13027.18 | 06-OCT-07:02 | 20.00 | 18.15 | 0.362161E+09 | 599.34 | 21-OCT-14:09 | 19.40 | 17.53 |
November | 0.908012E+09 | 4731.56 | 22-NOV-19:33 | -0.4 | -2.9 | 0.287659E+09 | 593.43 | 04-NOV-14:09 | 16.78 | 12.90 |
December | 0.171918E+09 | 4404.08 | 21-DEC-10:13 | 0.97 | -2.2 | 0.289622E+09 | 453.41 | 02-DEC-15:00 | 6.10 | 1.03 |
Annual Sum or Average | 0.268353E+11 | 0.399814E+10 | ||||||||
Minimum of Months | 48959625.20 | 2848.94 | -4.2 | -7.4 | 0.263243E+09 | 453.40 | 6.10 | 1.03 | ||
Maximum of Months | 0.582026E+10 | 17465.18 | 23.45 | 18.15 | 0.394495E+09 | 599.36 | 28.90 | 20.61 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3520899.28 | 546.00 | 19-JAN-12:00 | 7.20 | 3.78 | 0.289135E+09 | 453.41 | 14-JAN-15:09 | -6.6 | -7.1 |
February | 1825915.59 | 439.98 | 17-FEB-12:00 | 7.20 | 2.02 | 0.263243E+09 | 453.41 | 11-FEB-15:00 | 5.00 | 2.16 |
March | 0.180501E+09 | 3649.52 | 29-MAR-19:43 | 3.90 | 3.00 | 0.299556E+09 | 502.72 | 27-MAR-16:40 | 21.47 | 15.71 |
April | 0.615330E+09 | 3008.37 | 03-APR-18:03 | 6.60 | 3.50 | 0.305259E+09 | 599.32 | 08-APR-14:09 | 20.78 | 15.21 |
May | 0.165089E+10 | 5247.18 | 30-MAY-13:00 | 30.00 | 17.98 | 0.354185E+09 | 599.34 | 20-MAY-14:09 | 22.88 | 13.44 |
June | 0.368071E+10 | 13667.25 | 26-JUN-07:02 | 23.40 | 18.25 | 0.380831E+09 | 599.34 | 10-JUN-14:09 | 23.22 | 14.42 |
July | 0.538066E+10 | 16428.15 | 11-JUL-07:02 | 22.30 | 16.04 | 0.383285E+09 | 599.30 | 29-JUL-14:30 | 26.15 | 20.63 |
August | 0.603674E+10 | 15842.82 | 19-AUG-07:02 | 21.28 | 16.53 | 0.394499E+09 | 599.31 | 19-AUG-14:00 | 28.90 | 16.54 |
September | 0.394745E+10 | 16838.71 | 02-SEP-07:01 | 21.70 | 16.22 | 0.374747E+09 | 599.36 | 30-SEP-14:09 | 19.40 | 13.84 |
October | 0.271183E+10 | 5788.86 | 06-OCT-07:02 | 20.00 | 18.15 | 0.357680E+09 | 599.35 | 14-OCT-14:09 | 18.30 | 16.20 |
November | 0.652331E+09 | 3378.58 | 30-NOV-19:13 | 5.00 | 1.30 | 0.285374E+09 | 583.93 | 04-NOV-14:09 | 16.78 | 12.90 |
December | 32176533.74 | 4479.60 | 21-DEC-18:23 | 0.55 | -2.9 | 0.289624E+09 | 453.41 | 16-DEC-15:39 | 9.47 | 4.10 |
Annual Sum or Average | 0.248940E+11 | 0.397742E+10 | ||||||||
Minimum of Months | 1825915.59 | 439.98 | 0.55 | -2.9 | 0.263243E+09 | 453.41 | -6.6 | -7.1 | ||
Maximum of Months | 0.603674E+10 | 16838.71 | 30.00 | 18.25 | 0.394499E+09 | 599.36 | 28.90 | 20.63 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.296073E+10 | 56764.38 | 02-JAN-08:61 | -11.0 |
February | 0.290102E+10 | 56738.37 | 15-FEB-08:61 | -4.0 |
March | 0.949739E+09 | 56748.67 | 20-MAR-07:01 | -0.1 |
April | 0.271771E+09 | 56726.19 | 03-APR-07:01 | 3.68 |
May | 44015261.31 | 1475.11 | 31-MAY-07:05 | 21.38 |
June | 22346476.46 | 1446.68 | 08-JUN-07:04 | 21.88 |
July | 17816484.23 | 1425.13 | 12-JUL-07:05 | 25.18 |
August | 19931935.77 | 1630.24 | 25-AUG-07:04 | 18.48 |
September | 23718165.69 | 1581.20 | 15-SEP-07:04 | 17.38 |
October | 41387373.80 | 1581.97 | 14-OCT-07:04 | 14.50 |
November | 0.437149E+09 | 56753.66 | 24-NOV-08:61 | -3.5 |
December | 0.140196E+10 | 56745.25 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.909158E+10 | |||
Minimum of Months | 17816484.23 | 1425.13 | -11.0 | |
Maximum of Months | 0.296073E+10 | 56764.38 | 25.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.846396E+09 | 31076.09 | 02-JAN-08:61 | -11.0 |
February | 0.793114E+09 | 31059.57 | 13-FEB-08:61 | -8.7 |
March | 0.156176E+09 | 31032.76 | 17-MAR-07:01 | -1.1 |
April | 43110375.94 | 11968.21 | 21-APR-07:01 | 6.10 |
May | 16215417.16 | 979.15 | 30-MAY-07:05 | 23.17 |
June | 13580310.65 | 910.61 | 11-JUN-07:05 | 18.58 |
July | 10670401.69 | 865.83 | 31-JUL-07:05 | 24.18 |
August | 11488426.28 | 996.54 | 25-AUG-07:04 | 18.48 |
September | 15602407.42 | 959.29 | 15-SEP-07:04 | 17.38 |
October | 19168732.25 | 948.36 | 14-OCT-07:04 | 14.50 |
November | 77937116.11 | 29561.01 | 22-NOV-08:61 | -1.6 |
December | 0.266931E+09 | 31021.10 | 07-DEC-08:61 | 0.28 |
Annual Sum or Average | 0.227039E+10 | |||
Minimum of Months | 10670401.69 | 865.83 | -11.0 | |
Maximum of Months | 0.846396E+09 | 31076.09 | 24.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127546E+10 | 31729.63 | 02-JAN-07:01 | -11.6 |
February | 0.113436E+10 | 31712.64 | 12-FEB-08:61 | -10.5 |
March | 0.286707E+09 | 31237.93 | 13-MAR-06:01 | -0.5 |
April | 67626075.99 | 21183.42 | 02-APR-07:02 | 4.18 |
May | 17516639.39 | 958.53 | 30-MAY-06:05 | 20.47 |
June | 24052458.86 | 2007.98 | 19-JUN-19:03 | 31.42 |
July | 30627899.57 | 1656.61 | 16-JUL-16:02 | 29.90 |
August | 45357568.11 | 2480.61 | 04-AUG-19:02 | 33.12 |
September | 18691461.52 | 1000.36 | 15-SEP-06:04 | 15.37 |
October | 22127297.31 | 965.62 | 14-OCT-06:05 | 14.40 |
November | 0.174087E+09 | 31273.69 | 23-NOV-08:61 | -2.6 |
December | 0.524212E+09 | 31567.76 | 31-DEC-08:61 | -1.7 |
Annual Sum or Average | 0.362082E+10 | |||
Minimum of Months | 17516639.39 | 958.53 | -11.6 | |
Maximum of Months | 0.127546E+10 | 31729.63 | 33.12 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146756E+10 | 31558.18 | 02-JAN-07:01 | -11.6 |
February | 0.128181E+10 | 31540.03 | 12-FEB-08:61 | -10.5 |
March | 0.354678E+09 | 31072.11 | 13-MAR-06:01 | -0.5 |
April | 85145315.87 | 26769.04 | 02-APR-07:02 | 4.18 |
May | 20352685.23 | 941.40 | 30-MAY-06:05 | 20.47 |
June | 23993594.14 | 2008.61 | 19-JUN-19:03 | 31.42 |
July | 30272300.68 | 1656.34 | 16-JUL-16:02 | 29.90 |
August | 45121136.72 | 2480.37 | 04-AUG-19:02 | 33.12 |
September | 18207016.69 | 989.32 | 15-SEP-06:04 | 15.37 |
October | 22913588.35 | 944.03 | 14-OCT-06:05 | 14.40 |
November | 0.225505E+09 | 31106.36 | 23-NOV-08:61 | -2.6 |
December | 0.636667E+09 | 31397.20 | 31-DEC-08:61 | -1.7 |
Annual Sum or Average | 0.421223E+10 | |||
Minimum of Months | 18207016.69 | 941.40 | -11.6 | |
Maximum of Months | 0.146756E+10 | 31558.18 | 33.12 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.173745E+10 | 31551.35 | 02-JAN-07:01 | -11.6 |
February | 0.150130E+10 | 31532.79 | 12-FEB-08:61 | -10.5 |
March | 0.468915E+09 | 31065.74 | 13-MAR-06:01 | -0.5 |
April | 0.121681E+09 | 30837.57 | 02-APR-07:02 | 4.18 |
May | 23734243.44 | 879.93 | 30-MAY-06:05 | 20.47 |
June | 24289911.73 | 2015.25 | 19-JUN-19:03 | 31.42 |
July | 32240409.80 | 1661.97 | 16-JUL-16:02 | 29.90 |
August | 46445021.43 | 2486.00 | 04-AUG-19:02 | 33.12 |
September | 18568127.10 | 984.87 | 15-SEP-06:04 | 15.37 |
October | 24286662.12 | 880.89 | 05-OCT-06:05 | 15.68 |
November | 0.289722E+09 | 31099.38 | 23-NOV-08:61 | -2.6 |
December | 0.809982E+09 | 31390.03 | 31-DEC-08:61 | -1.7 |
Annual Sum or Average | 0.509861E+10 | |||
Minimum of Months | 18568127.10 | 879.93 | -11.6 | |
Maximum of Months | 0.173745E+10 | 31551.35 | 33.12 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.416236E+10 | 55185.85 | 02-JAN-08:12 | -10.9 |
February | 0.352228E+10 | 54977.53 | 13-FEB-08:61 | -8.7 |
March | 0.135485E+10 | 54977.17 | 14-MAR-07:01 | -1.4 |
April | 0.363631E+09 | 54960.97 | 03-APR-07:01 | 3.68 |
May | 50463647.35 | 1398.75 | 30-MAY-07:05 | 23.17 |
June | 25830517.72 | 1391.00 | 25-JUN-16:03 | 26.02 |
July | 38532001.87 | 3317.72 | 16-JUL-16:02 | 29.90 |
August | 36736606.75 | 3255.25 | 13-AUG-16:02 | 29.90 |
September | 24793815.40 | 1475.95 | 15-SEP-07:04 | 17.38 |
October | 45604925.59 | 1339.48 | 14-OCT-07:04 | 14.50 |
November | 0.812712E+09 | 54977.00 | 24-NOV-08:61 | -3.5 |
December | 0.215217E+10 | 54972.43 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.125900E+11 | |||
Minimum of Months | 24793815.40 | 1339.48 | -10.9 | |
Maximum of Months | 0.416236E+10 | 55185.85 | 29.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242741E+10 | 29153.74 | 02-JAN-08:12 | -10.9 |
February | 0.208772E+10 | 29005.29 | 13-FEB-08:61 | -8.7 |
March | 0.861639E+09 | 29004.02 | 23-MAR-07:01 | -2.9 |
April | 0.230114E+09 | 28994.53 | 03-APR-07:01 | 3.68 |
May | 29008229.54 | 2698.43 | 01-MAY-07:02 | 10.37 |
June | 14444453.48 | 782.53 | 23-JUN-07:04 | 23.45 |
July | 21410972.92 | 1675.67 | 16-JUL-16:02 | 29.90 |
August | 19569315.94 | 1642.10 | 13-AUG-16:02 | 29.90 |
September | 13636697.62 | 787.68 | 15-SEP-07:04 | 17.38 |
October | 25759724.24 | 704.09 | 06-OCT-07:04 | 20.00 |
November | 0.521335E+09 | 29003.28 | 24-NOV-08:61 | -3.5 |
December | 0.130498E+10 | 29001.54 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.755702E+10 | |||
Minimum of Months | 13636697.62 | 704.09 | -10.9 | |
Maximum of Months | 0.242741E+10 | 29153.74 | 29.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.251019E+10 | 29018.92 | 02-JAN-08:12 | -10.9 |
February | 0.217374E+10 | 28859.24 | 13-FEB-08:61 | -8.7 |
March | 0.930807E+09 | 28857.72 | 23-MAR-07:01 | -2.9 |
April | 0.262127E+09 | 28848.23 | 03-APR-07:01 | 3.68 |
May | 31371043.71 | 6864.99 | 01-MAY-07:02 | 10.37 |
June | 14344966.97 | 774.25 | 23-JUN-07:04 | 23.45 |
July | 21500260.81 | 1676.82 | 16-JUL-16:02 | 29.90 |
August | 19865572.73 | 1643.44 | 13-AUG-16:02 | 29.90 |
September | 13605033.62 | 766.85 | 15-SEP-07:04 | 17.38 |
October | 26179059.76 | 696.96 | 06-OCT-07:04 | 20.00 |
November | 0.554646E+09 | 28857.12 | 24-NOV-08:61 | -3.5 |
December | 0.136890E+10 | 28855.42 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.792728E+10 | |||
Minimum of Months | 13605033.62 | 696.96 | -10.9 | |
Maximum of Months | 0.251019E+10 | 29018.92 | 29.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.285392E+10 | 28898.87 | 02-JAN-08:12 | -10.9 |
February | 0.251701E+10 | 28743.67 | 07-FEB-08:12 | -8.5 |
March | 0.116905E+10 | 28700.77 | 23-MAR-07:01 | -2.9 |
April | 0.359897E+09 | 28691.72 | 03-APR-07:01 | 3.68 |
May | 41458204.75 | 16107.07 | 01-MAY-07:02 | 10.37 |
June | 13664994.40 | 754.56 | 23-JUN-07:04 | 23.45 |
July | 21334361.46 | 1679.02 | 16-JUL-16:02 | 29.90 |
August | 19830407.22 | 1644.63 | 13-AUG-16:02 | 29.90 |
September | 14166349.11 | 745.38 | 09-SEP-07:04 | 17.88 |
October | 29077184.40 | 1875.21 | 29-OCT-08:63 | 6.88 |
November | 0.683282E+09 | 28700.71 | 24-NOV-08:61 | -3.5 |
December | 0.163715E+10 | 28697.38 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.935983E+10 | |||
Minimum of Months | 13664994.40 | 745.38 | -10.9 | |
Maximum of Months | 0.285392E+10 | 28898.87 | 29.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.449917E+10 | 29780.75 | 02-JAN-08:12 | -10.9 |
February | 0.418365E+10 | 29716.45 | 07-FEB-08:12 | -8.5 |
March | 0.225035E+10 | 29499.07 | 20-MAR-07:01 | -0.1 |
April | 0.869462E+09 | 29483.19 | 03-APR-07:01 | 3.68 |
May | 0.101499E+09 | 28870.97 | 02-MAY-07:02 | 12.15 |
June | 18577686.46 | 735.11 | 25-JUN-16:03 | 26.02 |
July | 20616635.96 | 1681.51 | 16-JUL-16:02 | 29.90 |
August | 19053183.33 | 1637.78 | 13-AUG-16:02 | 29.90 |
September | 19738342.21 | 729.60 | 03-SEP-08:04 | 21.38 |
October | 45563746.21 | 18028.65 | 31-OCT-07:01 | 6.28 |
November | 0.120971E+10 | 29499.98 | 24-NOV-08:61 | -3.5 |
December | 0.276119E+10 | 29492.10 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.159986E+11 | |||
Minimum of Months | 18577686.46 | 729.60 | -10.9 | |
Maximum of Months | 0.449917E+10 | 29780.75 | 29.90 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.109389E+11 | 6635.66 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.989784E+10 | 6635.66 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.109616E+11 | 6635.66 | 01-MAR-10:09 | 0.223053E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.106145E+11 | 6635.66 | 01-APR-09:09 | 0.215990E+10 | 1343.25 | 01-APR-09:09 |
May | 0.109389E+11 | 6635.66 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.106145E+11 | 6635.66 | 01-JUN-09:09 | 0.215990E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.109616E+11 | 6635.66 | 01-JUL-09:09 | 0.223053E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.109389E+11 | 6635.66 | 01-AUG-09:09 | 0.222596E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.106372E+11 | 6635.66 | 01-SEP-09:09 | 0.216447E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.109389E+11 | 6635.66 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.105693E+11 | 6635.66 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.109842E+11 | 6635.66 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.128996E+12 | 0.262491E+11 | ||||
Minimum of Months | 0.989784E+10 | 6635.66 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.109842E+11 | 6635.66 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.625207E+10 | 3792.57 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.565704E+10 | 3792.57 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.626500E+10 | 3792.57 | 01-MAR-10:09 | 0.111526E+10 | 671.63 | 01-MAR-10:09 |
April | 0.606666E+10 | 3792.57 | 01-APR-09:09 | 0.107995E+10 | 671.63 | 01-APR-09:09 |
May | 0.625207E+10 | 3792.57 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.606666E+10 | 3792.57 | 01-JUN-09:09 | 0.107995E+10 | 671.63 | 01-JUN-09:09 |
July | 0.626500E+10 | 3792.57 | 01-JUL-09:09 | 0.111526E+10 | 671.63 | 01-JUL-09:09 |
August | 0.625207E+10 | 3792.57 | 01-AUG-09:09 | 0.111298E+10 | 671.63 | 01-AUG-09:09 |
September | 0.607960E+10 | 3792.57 | 01-SEP-09:09 | 0.108223E+10 | 671.63 | 01-SEP-09:09 |
October | 0.625207E+10 | 3792.57 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.604079E+10 | 3792.57 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.627794E+10 | 3792.57 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.737270E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.565704E+10 | 3792.57 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.627794E+10 | 3792.57 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.447798E+10 | 3443.15 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.405524E+10 | 3443.15 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.457193E+10 | 3443.15 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.434490E+10 | 3443.15 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.452496E+10 | 3443.15 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.441536E+10 | 3443.15 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.445450E+10 | 3443.15 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.457193E+10 | 3443.15 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.434490E+10 | 3443.15 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.447798E+10 | 3443.15 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.434490E+10 | 3443.15 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.445450E+10 | 3443.15 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.530391E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.405524E+10 | 3443.15 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.457193E+10 | 3443.15 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.447798E+10 | 3443.15 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.405524E+10 | 3443.15 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.457193E+10 | 3443.15 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.434490E+10 | 3443.15 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.452496E+10 | 3443.15 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.441536E+10 | 3443.15 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.445450E+10 | 3443.15 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.457193E+10 | 3443.15 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.434490E+10 | 3443.15 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.447798E+10 | 3443.15 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.434490E+10 | 3443.15 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.445450E+10 | 3443.15 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.530391E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.405524E+10 | 3443.15 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.457193E+10 | 3443.15 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.447798E+10 | 3443.15 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.405524E+10 | 3443.15 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.457193E+10 | 3443.15 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.434490E+10 | 3443.15 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.452496E+10 | 3443.15 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.441536E+10 | 3443.15 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.445450E+10 | 3443.15 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.457193E+10 | 3443.15 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.434490E+10 | 3443.15 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.447798E+10 | 3443.15 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.434490E+10 | 3443.15 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.445450E+10 | 3443.15 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.530391E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.405524E+10 | 3443.15 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.457193E+10 | 3443.15 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.531643E+10 | 4449.56 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.481564E+10 | 4449.56 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.543783E+10 | 4449.56 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.515962E+10 | 4449.56 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.537713E+10 | 4449.56 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.525067E+10 | 4449.56 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.528608E+10 | 4449.56 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.543783E+10 | 4449.56 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.515962E+10 | 4449.56 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.531643E+10 | 4449.56 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.515962E+10 | 4449.56 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.528608E+10 | 4449.56 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.630030E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.481564E+10 | 4449.56 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.543783E+10 | 4449.56 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.265822E+10 | 2224.78 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.240782E+10 | 2224.78 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.271892E+10 | 2224.78 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.257981E+10 | 2224.78 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.268857E+10 | 2224.78 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.262534E+10 | 2224.78 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.264304E+10 | 2224.78 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.271892E+10 | 2224.78 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.257981E+10 | 2224.78 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.265822E+10 | 2224.78 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.257981E+10 | 2224.78 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.264304E+10 | 2224.78 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.315015E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.240782E+10 | 2224.78 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.271892E+10 | 2224.78 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.265822E+10 | 2224.78 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.240782E+10 | 2224.78 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.271892E+10 | 2224.78 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.257981E+10 | 2224.78 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.268857E+10 | 2224.78 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.262534E+10 | 2224.78 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.264304E+10 | 2224.78 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.271892E+10 | 2224.78 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.257981E+10 | 2224.78 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.265822E+10 | 2224.78 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.257981E+10 | 2224.78 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.264304E+10 | 2224.78 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.315015E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.240782E+10 | 2224.78 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.271892E+10 | 2224.78 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.265822E+10 | 2224.78 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.240782E+10 | 2224.78 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.271892E+10 | 2224.78 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.257981E+10 | 2224.78 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.268857E+10 | 2224.78 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.262534E+10 | 2224.78 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.264304E+10 | 2224.78 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.271892E+10 | 2224.78 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.257981E+10 | 2224.78 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.265822E+10 | 2224.78 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.257981E+10 | 2224.78 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.264304E+10 | 2224.78 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.315015E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.240782E+10 | 2224.78 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.271892E+10 | 2224.78 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.265822E+10 | 2224.78 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.240782E+10 | 2224.78 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.271892E+10 | 2224.78 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.257981E+10 | 2224.78 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.268857E+10 | 2224.78 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.262534E+10 | 2224.78 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.264304E+10 | 2224.78 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.271892E+10 | 2224.78 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.257981E+10 | 2224.78 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.265822E+10 | 2224.78 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.257981E+10 | 2224.78 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.264304E+10 | 2224.78 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.315015E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.240782E+10 | 2224.78 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.271892E+10 | 2224.78 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.180574E+10 | 0.109389E+11 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629792E+10 |
February | 0.163016E+10 | 0.989784E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585012E+10 |
March | 0.178954E+10 | 0.109616E+11 | 0.223053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462561E+10 |
April | 0.174484E+10 | 0.106145E+11 | 0.215990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12850151.66 | 0.291392E+10 |
May | 0.179537E+10 | 0.109389E+11 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69920110.82 | 0.173713E+10 |
June | 0.173447E+10 | 0.106145E+11 | 0.215990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350388E+09 | 0.539257E+09 |
July | 0.181028E+10 | 0.109616E+11 | 0.223053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.831925E+09 | 96608468.44 |
August | 0.178501E+10 | 0.109389E+11 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.917366E+09 | 0.157741E+09 |
September | 0.174937E+10 | 0.106372E+11 | 0.216447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163522E+09 | 0.809757E+09 |
October | 0.180574E+10 | 0.109389E+11 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2999141.62 | 0.229934E+10 |
November | 0.174613E+10 | 0.105693E+11 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416405E+10 |
December | 0.181481E+10 | 0.109842E+11 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547437E+10 |
Annual Sum or Average | 0.212115E+11 | 0.128996E+12 | 0.262491E+11 | 0.234897E+10 | 0.349658E+11 | ||||
Minimum of Months | 0.163016E+10 | 0.989784E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96608468.44 |
Maximum of Months | 0.181481E+10 | 0.109842E+11 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.917366E+09 | 0.629792E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.902868E+09 | 0.625207E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301175E+10 |
February | 0.815075E+09 | 0.565704E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282443E+10 |
March | 0.894769E+09 | 0.626500E+10 | 0.111526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225097E+10 |
April | 0.872416E+09 | 0.606666E+10 | 0.107995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6917522.44 | 0.142323E+10 |
May | 0.897684E+09 | 0.625207E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37836374.48 | 0.839314E+09 |
June | 0.867232E+09 | 0.606666E+10 | 0.107995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187256E+09 | 0.227555E+09 |
July | 0.905135E+09 | 0.626500E+10 | 0.111526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446341E+09 | 32491582.82 |
August | 0.892501E+09 | 0.625207E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490945E+09 | 53590966.15 |
September | 0.874683E+09 | 0.607960E+10 | 0.108223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88156765.52 | 0.367953E+09 |
October | 0.902868E+09 | 0.625207E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1617381.25 | 0.110087E+10 |
November | 0.873064E+09 | 0.604079E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200957E+10 |
December | 0.907403E+09 | 0.627794E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263727E+10 |
Annual Sum or Average | 0.106057E+11 | 0.737270E+11 | 0.131245E+11 | 0.125907E+10 | 0.167790E+11 | ||||
Minimum of Months | 0.815075E+09 | 0.565704E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32491582.82 |
Maximum of Months | 0.907403E+09 | 0.627794E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490945E+09 | 0.301175E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.447798E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311535E+10 |
February | 0.487879E+09 | 0.405524E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290957E+10 |
March | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230543E+10 |
April | 0.524810E+09 | 0.434490E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6917259.20 | 0.145027E+10 |
May | 0.544247E+09 | 0.452496E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37653870.26 | 0.867438E+09 |
June | 0.532585E+09 | 0.441536E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184911E+09 | 0.258621E+09 |
July | 0.536472E+09 | 0.445450E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437184E+09 | 52260940.29 |
August | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485388E+09 | 69940204.72 |
September | 0.524810E+09 | 0.434490E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 86991806.61 | 0.398484E+09 |
October | 0.537120E+09 | 0.447798E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1617058.55 | 0.114764E+10 |
November | 0.518979E+09 | 0.434490E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207142E+10 |
December | 0.536472E+09 | 0.445450E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273237E+10 |
Annual Sum or Average | 0.638324E+10 | 0.530391E+11 | 0.104207E+11 | 0.124066E+10 | 0.173788E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.405524E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52260940.29 |
Maximum of Months | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485388E+09 | 0.311535E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.447798E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310663E+10 |
February | 0.487879E+09 | 0.405524E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290363E+10 |
March | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229405E+10 |
April | 0.524810E+09 | 0.434490E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6917198.73 | 0.143830E+10 |
May | 0.544247E+09 | 0.452496E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37653940.86 | 0.860289E+09 |
June | 0.532585E+09 | 0.441536E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184901E+09 | 0.258283E+09 |
July | 0.536472E+09 | 0.445450E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437126E+09 | 52520525.86 |
August | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485304E+09 | 70294997.65 |
September | 0.524810E+09 | 0.434490E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 86992694.01 | 0.398197E+09 |
October | 0.537120E+09 | 0.447798E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1617053.93 | 0.114141E+10 |
November | 0.518979E+09 | 0.434490E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205486E+10 |
December | 0.536472E+09 | 0.445450E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272505E+10 |
Annual Sum or Average | 0.638324E+10 | 0.530391E+11 | 0.104207E+11 | 0.124051E+10 | 0.173035E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.405524E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52520525.86 |
Maximum of Months | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485304E+09 | 0.310663E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.447798E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309984E+10 |
February | 0.487879E+09 | 0.405524E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289887E+10 |
March | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228295E+10 |
April | 0.524810E+09 | 0.434490E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6917865.00 | 0.142404E+10 |
May | 0.544247E+09 | 0.452496E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37654658.14 | 0.845550E+09 |
June | 0.532585E+09 | 0.441536E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184973E+09 | 0.255640E+09 |
July | 0.536472E+09 | 0.445450E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437373E+09 | 50271334.54 |
August | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485592E+09 | 68266385.37 |
September | 0.524810E+09 | 0.434490E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 86995303.70 | 0.395865E+09 |
October | 0.537120E+09 | 0.447798E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1617140.28 | 0.112977E+10 |
November | 0.518979E+09 | 0.434490E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203290E+10 |
December | 0.536472E+09 | 0.445450E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271930E+10 |
Annual Sum or Average | 0.638324E+10 | 0.530391E+11 | 0.104207E+11 | 0.124112E+10 | 0.172033E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.405524E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50271334.54 |
Maximum of Months | 0.551374E+09 | 0.457193E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485592E+09 | 0.309984E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.183632E+10 | 0.531643E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572069E+10 |
February | 0.167188E+10 | 0.481564E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535284E+10 |
March | 0.189386E+10 | 0.543783E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419432E+10 |
April | 0.180380E+10 | 0.515962E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12461220.86 | 0.258670E+10 |
May | 0.186509E+10 | 0.537713E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67792859.38 | 0.149779E+10 |
June | 0.182945E+10 | 0.525067E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334502E+09 | 0.479278E+09 |
July | 0.183943E+10 | 0.528608E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789803E+09 | 92771517.47 |
August | 0.189386E+10 | 0.543783E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.878199E+09 | 0.130597E+09 |
September | 0.180380E+10 | 0.515962E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156899E+09 | 0.736608E+09 |
October | 0.183632E+10 | 0.531643E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2912985.56 | 0.204532E+10 |
November | 0.176881E+10 | 0.515962E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370067E+10 |
December | 0.183943E+10 | 0.528608E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502062E+10 |
Annual Sum or Average | 0.218821E+11 | 0.630030E+11 | 0.191729E+11 | 0.224257E+10 | 0.315582E+11 | ||||
Minimum of Months | 0.167188E+10 | 0.481564E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92771517.47 |
Maximum of Months | 0.189386E+10 | 0.543783E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.878199E+09 | 0.572069E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311159E+10 |
February | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291572E+10 |
March | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228013E+10 |
April | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6919460.80 | 0.139894E+10 |
May | 0.932542E+09 | 0.268857E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37666318.21 | 0.801923E+09 |
June | 0.914724E+09 | 0.262534E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185612E+09 | 0.253125E+09 |
July | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438760E+09 | 45794007.26 |
August | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487582E+09 | 65525979.05 |
September | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87156249.62 | 0.395725E+09 |
October | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1618729.29 | 0.110283E+10 |
November | 0.884402E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200075E+10 |
December | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273059E+10 |
Annual Sum or Average | 0.109410E+11 | 0.315015E+11 | 0.958644E+10 | 0.124532E+10 | 0.171026E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45794007.26 |
Maximum of Months | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487582E+09 | 0.311159E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310957E+10 |
February | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291381E+10 |
March | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227692E+10 |
April | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6919434.18 | 0.139202E+10 |
May | 0.932542E+09 | 0.268857E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37666017.21 | 0.790961E+09 |
June | 0.914724E+09 | 0.262534E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185644E+09 | 0.252138E+09 |
July | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438893E+09 | 45100106.43 |
August | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487699E+09 | 64917328.46 |
September | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87161587.53 | 0.394840E+09 |
October | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1618794.15 | 0.109660E+10 |
November | 0.884402E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199343E+10 |
December | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272867E+10 |
Annual Sum or Average | 0.109410E+11 | 0.315015E+11 | 0.958644E+10 | 0.124560E+10 | 0.170590E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45100106.43 |
Maximum of Months | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487699E+09 | 0.310957E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310075E+10 |
February | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290616E+10 |
March | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226689E+10 |
April | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6919417.69 | 0.137572E+10 |
May | 0.932542E+09 | 0.268857E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37663923.01 | 0.768407E+09 |
June | 0.914724E+09 | 0.262534E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185731E+09 | 0.249116E+09 |
July | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439205E+09 | 43226118.13 |
August | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487925E+09 | 63431563.49 |
September | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87171039.52 | 0.392427E+09 |
October | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1618714.48 | 0.108251E+10 |
November | 0.884402E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197918E+10 |
December | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272092E+10 |
Annual Sum or Average | 0.109410E+11 | 0.315015E+11 | 0.958644E+10 | 0.124623E+10 | 0.169487E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43226118.13 |
Maximum of Months | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487925E+09 | 0.310075E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400945E+10 |
February | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370714E+10 |
March | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290079E+10 |
April | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7312403.15 | 0.176434E+10 |
May | 0.932542E+09 | 0.268857E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39480404.41 | 0.962217E+09 |
June | 0.914724E+09 | 0.262534E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199403E+09 | 0.377287E+09 |
July | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467261E+09 | 83497426.55 |
August | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522311E+09 | 0.125233E+09 |
September | 0.901896E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91912930.50 | 0.545596E+09 |
October | 0.918158E+09 | 0.265822E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1705429.97 | 0.142906E+10 |
November | 0.884402E+09 | 0.257981E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260133E+10 |
December | 0.919713E+09 | 0.264304E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350954E+10 |
Annual Sum or Average | 0.109410E+11 | 0.315015E+11 | 0.958644E+10 | 0.132939E+10 | 0.220155E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.240782E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83497426.55 |
Maximum of Months | 0.946926E+09 | 0.271892E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522311E+09 | 0.400945E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2159.72 | 01-JAN-13:09 | 6635.66 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 10105.67 | 14-JAN-12:10 |
February | 2159.72 | 03-FEB-13:09 | 6635.66 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 10612.62 | 06-FEB-12:10 |
March | 2159.72 | 03-MAR-13:09 | 6635.66 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7452.17 | 17-MAR-11:10 |
April | 2159.72 | 01-APR-12:09 | 6635.66 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 852.69 | 07-APR-13:00 | 5353.82 | 01-APR-12:00 |
May | 2159.72 | 05-MAY-12:09 | 6635.66 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1834.84 | 30-MAY-13:00 | 3315.36 | 14-MAY-16:30 |
June | 2159.72 | 02-JUN-12:09 | 6635.66 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3742.13 | 19-JUN-12:00 | 1781.92 | 03-JUN-17:00 |
July | 2159.72 | 01-JUL-12:09 | 6635.66 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2908.49 | 07-JUL-12:00 | 517.44 | 23-JUL-17:00 |
August | 2159.72 | 04-AUG-12:09 | 6635.66 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3042.02 | 24-AUG-15:00 | 859.56 | 06-AUG-12:00 |
September | 2159.72 | 01-SEP-12:09 | 6635.66 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2114.95 | 01-SEP-14:00 | 2730.14 | 23-SEP-11:10 |
October | 2159.72 | 01-OCT-12:09 | 6635.66 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 335.64 | 04-OCT-13:00 | 4342.94 | 08-OCT-11:10 |
November | 2159.72 | 03-NOV-12:09 | 6635.66 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7255.11 | 22-NOV-18:00 |
December | 2159.72 | 01-DEC-13:09 | 6635.66 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 9111.64 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2159.72 | 6635.66 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.44 | |||||
Maximum of Months | 2159.72 | 6635.66 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3742.13 | 10612.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 01-JAN-13:09 | 3792.57 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5368.21 | 14-JAN-12:10 |
February | 1079.86 | 03-FEB-13:09 | 3792.57 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5688.61 | 06-FEB-12:10 |
March | 1079.86 | 03-MAR-13:09 | 3792.57 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4034.70 | 17-MAR-11:10 |
April | 1079.86 | 01-APR-12:09 | 3792.57 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 461.32 | 07-APR-13:00 | 2939.75 | 01-APR-12:00 |
May | 1079.86 | 05-MAY-12:09 | 3792.57 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 997.33 | 30-MAY-13:00 | 1829.32 | 14-MAY-16:00 |
June | 1079.86 | 02-JUN-12:09 | 3792.57 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2034.04 | 19-JUN-12:00 | 957.33 | 03-JUN-17:00 |
July | 1079.86 | 01-JUL-12:09 | 3792.57 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1593.14 | 07-JUL-12:00 | 282.03 | 23-JUL-17:00 |
August | 1079.86 | 04-AUG-12:09 | 3792.57 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1626.16 | 24-AUG-15:00 | 467.20 | 06-AUG-12:00 |
September | 1079.86 | 01-SEP-12:09 | 3792.57 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.93 | 01-SEP-14:00 | 1500.70 | 23-SEP-11:10 |
October | 1079.86 | 01-OCT-12:09 | 3792.57 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.42 | 04-OCT-13:00 | 2483.60 | 28-OCT-11:10 |
November | 1079.86 | 03-NOV-12:09 | 3792.57 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3878.37 | 22-NOV-18:00 |
December | 1079.86 | 01-DEC-13:09 | 3792.57 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 4884.06 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3792.57 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.03 | |||||
Maximum of Months | 1079.86 | 3792.57 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2034.04 | 5688.61 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3443.15 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5368.18 | 14-JAN-12:10 |
February | 1079.86 | 04-FEB-13:09 | 3443.15 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5688.60 | 06-FEB-12:10 |
March | 1079.86 | 04-MAR-13:09 | 3443.15 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4034.70 | 17-MAR-11:10 |
April | 1079.86 | 01-APR-12:09 | 3443.15 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 461.29 | 07-APR-13:00 | 2939.74 | 01-APR-12:00 |
May | 1079.86 | 06-MAY-12:09 | 3443.15 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 997.31 | 30-MAY-13:00 | 1806.80 | 14-MAY-16:00 |
June | 1079.86 | 03-JUN-12:09 | 3443.15 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2034.02 | 19-JUN-12:00 | 957.31 | 03-JUN-17:00 |
July | 1079.86 | 01-JUL-12:09 | 3443.15 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1593.13 | 07-JUL-12:00 | 568.16 | 23-JUL-17:00 |
August | 1079.86 | 05-AUG-12:09 | 3443.15 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1625.95 | 24-AUG-15:00 | 734.96 | 06-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 3443.15 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.89 | 01-SEP-14:00 | 1500.70 | 23-SEP-11:10 |
October | 1079.86 | 07-OCT-12:09 | 3443.15 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.38 | 04-OCT-13:00 | 2462.76 | 28-OCT-11:10 |
November | 1079.86 | 04-NOV-12:09 | 3443.15 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3878.36 | 22-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3443.15 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 4884.06 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 568.16 | |||||
Maximum of Months | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2034.02 | 5688.60 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3443.15 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5368.18 | 14-JAN-12:10 |
February | 1079.86 | 04-FEB-13:09 | 3443.15 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5688.60 | 06-FEB-12:10 |
March | 1079.86 | 04-MAR-13:09 | 3443.15 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4034.70 | 17-MAR-11:10 |
April | 1079.86 | 01-APR-12:09 | 3443.15 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 461.29 | 07-APR-13:00 | 2939.74 | 01-APR-12:00 |
May | 1079.86 | 06-MAY-12:09 | 3443.15 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 997.31 | 30-MAY-13:00 | 1795.20 | 14-MAY-16:00 |
June | 1079.86 | 03-JUN-12:09 | 3443.15 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2034.02 | 19-JUN-12:00 | 957.31 | 03-JUN-17:00 |
July | 1079.86 | 01-JUL-12:09 | 3443.15 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1593.13 | 07-JUL-12:00 | 568.05 | 23-JUL-17:00 |
August | 1079.86 | 05-AUG-12:09 | 3443.15 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1625.94 | 24-AUG-15:00 | 735.35 | 06-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 3443.15 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.90 | 01-SEP-14:00 | 1500.70 | 23-SEP-11:10 |
October | 1079.86 | 07-OCT-12:09 | 3443.15 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.38 | 04-OCT-13:00 | 2440.82 | 28-OCT-11:10 |
November | 1079.86 | 04-NOV-12:09 | 3443.15 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3878.36 | 22-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3443.15 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 4884.06 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 568.05 | |||||
Maximum of Months | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2034.02 | 5688.60 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3443.15 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5368.18 | 14-JAN-12:10 |
February | 1079.86 | 04-FEB-13:09 | 3443.15 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5688.60 | 06-FEB-12:10 |
March | 1079.86 | 04-MAR-13:09 | 3443.15 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4034.70 | 17-MAR-11:10 |
April | 1079.86 | 01-APR-12:09 | 3443.15 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 461.28 | 07-APR-13:00 | 2939.74 | 01-APR-12:00 |
May | 1079.86 | 06-MAY-12:09 | 3443.15 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 997.31 | 30-MAY-13:00 | 1767.40 | 14-MAY-16:00 |
June | 1079.86 | 03-JUN-12:09 | 3443.15 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2034.02 | 19-JUN-12:00 | 957.30 | 03-JUN-17:00 |
July | 1079.86 | 01-JUL-12:09 | 3443.15 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1593.13 | 07-JUL-12:00 | 557.90 | 23-JUL-17:00 |
August | 1079.86 | 05-AUG-12:09 | 3443.15 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1625.96 | 24-AUG-15:00 | 725.39 | 06-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 3443.15 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.89 | 01-SEP-14:00 | 1500.70 | 23-SEP-11:10 |
October | 1079.86 | 07-OCT-12:09 | 3443.15 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.36 | 04-OCT-13:00 | 2397.79 | 28-OCT-11:10 |
November | 1079.86 | 04-NOV-12:09 | 3443.15 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3878.36 | 22-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3443.15 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 4884.06 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.90 | |||||
Maximum of Months | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2034.02 | 5688.60 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2879.63 | 07-JAN-15:09 | 4449.56 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9683.67 | 14-JAN-12:10 |
February | 2879.63 | 04-FEB-15:09 | 4449.56 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 10249.93 | 06-FEB-12:10 |
March | 2879.63 | 04-MAR-15:09 | 4449.56 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7260.72 | 17-MAR-11:10 |
April | 2879.63 | 01-APR-14:09 | 4449.56 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 830.41 | 07-APR-13:00 | 5280.99 | 01-APR-12:00 |
May | 2879.63 | 06-MAY-14:09 | 4449.56 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1793.91 | 30-MAY-13:00 | 2983.97 | 14-MAY-16:00 |
June | 2879.63 | 03-JUN-14:09 | 4449.56 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3658.62 | 19-JUN-12:00 | 1724.36 | 03-JUN-17:00 |
July | 2879.63 | 01-JUL-14:09 | 4449.56 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2862.84 | 07-JUL-12:00 | 924.16 | 23-JUL-17:00 |
August | 2879.63 | 05-AUG-14:09 | 4449.56 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2931.16 | 24-AUG-15:00 | 1224.81 | 06-AUG-17:00 |
September | 2879.63 | 02-SEP-14:09 | 4449.56 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2073.03 | 01-SEP-14:00 | 2668.79 | 23-SEP-11:10 |
October | 2879.63 | 07-OCT-14:09 | 4449.56 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 328.09 | 04-OCT-13:00 | 4117.10 | 28-OCT-11:10 |
November | 2879.63 | 04-NOV-14:09 | 4449.56 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6990.57 | 22-NOV-18:00 |
December | 2879.63 | 02-DEC-15:09 | 4449.56 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 8800.28 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2879.63 | 4449.56 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 924.16 | |||||
Maximum of Months | 2879.63 | 4449.56 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3658.62 | 10249.93 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2224.78 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5368.17 | 14-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 2224.78 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5688.59 | 06-FEB-12:10 |
March | 1439.81 | 04-MAR-15:09 | 2224.78 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4034.69 | 17-MAR-11:10 |
April | 1439.81 | 01-APR-14:09 | 2224.78 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 461.40 | 07-APR-13:00 | 2939.73 | 01-APR-12:00 |
May | 1439.81 | 06-MAY-14:09 | 2224.78 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 997.33 | 30-MAY-13:00 | 1641.48 | 14-MAY-16:00 |
June | 1439.81 | 03-JUN-14:09 | 2224.78 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2034.06 | 19-JUN-12:00 | 957.25 | 03-JUN-17:00 |
July | 1439.81 | 01-JUL-14:09 | 2224.78 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1593.16 | 07-JUL-12:00 | 505.50 | 23-JUL-17:00 |
August | 1439.81 | 05-AUG-14:09 | 2224.78 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1626.20 | 24-AUG-15:00 | 671.58 | 06-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 2224.78 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.92 | 01-SEP-14:00 | 1481.91 | 23-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 2224.78 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.39 | 04-OCT-13:00 | 2273.12 | 28-OCT-11:10 |
November | 1439.81 | 04-NOV-14:09 | 2224.78 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3878.35 | 22-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2224.78 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 4884.05 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.50 | |||||
Maximum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2034.06 | 5688.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2224.78 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5368.17 | 14-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 2224.78 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5688.59 | 06-FEB-12:10 |
March | 1439.81 | 04-MAR-15:09 | 2224.78 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4034.69 | 17-MAR-11:10 |
April | 1439.81 | 01-APR-14:09 | 2224.78 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 461.40 | 07-APR-13:00 | 2939.73 | 01-APR-12:00 |
May | 1439.81 | 06-MAY-14:09 | 2224.78 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 997.33 | 30-MAY-13:00 | 1616.55 | 14-MAY-16:00 |
June | 1439.81 | 03-JUN-14:09 | 2224.78 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2034.06 | 19-JUN-12:00 | 957.25 | 03-JUN-17:00 |
July | 1439.81 | 01-JUL-14:09 | 2224.78 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1593.16 | 07-JUL-12:00 | 501.23 | 23-JUL-17:00 |
August | 1439.81 | 05-AUG-14:09 | 2224.78 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1626.20 | 24-AUG-15:00 | 667.36 | 06-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 2224.78 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.92 | 01-SEP-14:00 | 1479.45 | 23-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 2224.78 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.54 | 04-OCT-13:00 | 2257.29 | 28-OCT-11:10 |
November | 1439.81 | 04-NOV-14:09 | 2224.78 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3878.35 | 22-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2224.78 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 4884.05 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.23 | |||||
Maximum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2034.06 | 5688.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2224.78 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5368.17 | 14-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 2224.78 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5688.59 | 06-FEB-12:10 |
March | 1439.81 | 04-MAR-15:09 | 2224.78 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4034.69 | 17-MAR-11:10 |
April | 1439.81 | 01-APR-14:09 | 2224.78 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 461.40 | 07-APR-13:00 | 2939.73 | 01-APR-12:00 |
May | 1439.81 | 06-MAY-14:09 | 2224.78 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 997.32 | 30-MAY-13:00 | 1564.91 | 14-MAY-16:00 |
June | 1439.81 | 03-JUN-14:09 | 2224.78 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2034.05 | 19-JUN-12:00 | 957.25 | 03-JUN-17:00 |
July | 1439.81 | 01-JUL-14:09 | 2224.78 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1593.16 | 07-JUL-12:00 | 492.01 | 23-JUL-17:00 |
August | 1439.81 | 05-AUG-14:09 | 2224.78 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1626.20 | 24-AUG-15:00 | 660.60 | 06-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 2224.78 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.92 | 01-SEP-14:00 | 1472.44 | 23-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 2224.78 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.53 | 04-OCT-13:00 | 2221.59 | 28-OCT-11:10 |
November | 1439.81 | 04-NOV-14:09 | 2224.78 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3878.35 | 22-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2224.78 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 4884.05 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492.01 | |||||
Maximum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2034.05 | 5688.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2224.78 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5789.59 | 14-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 2224.78 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6050.78 | 06-FEB-12:10 |
March | 1439.81 | 04-MAR-15:09 | 2224.78 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4225.86 | 17-MAR-11:10 |
April | 1439.81 | 01-APR-14:09 | 2224.78 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 483.84 | 07-APR-13:00 | 3012.43 | 01-APR-12:00 |
May | 1439.81 | 06-MAY-14:09 | 2224.78 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1038.22 | 30-MAY-13:00 | 1566.82 | 03-MAY-11:10 |
June | 1439.81 | 03-JUN-14:09 | 2224.78 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2117.50 | 19-JUN-12:00 | 1014.65 | 03-JUN-17:00 |
July | 1439.81 | 01-JUL-14:09 | 2224.78 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.80 | 07-JUL-12:00 | 483.21 | 23-JUL-17:00 |
August | 1439.81 | 05-AUG-14:09 | 2224.78 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1736.97 | 24-AUG-15:00 | 675.82 | 06-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 2224.78 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1194.89 | 01-SEP-14:00 | 1468.15 | 23-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 2224.78 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 190.02 | 04-OCT-13:00 | 2300.84 | 28-OCT-11:10 |
November | 1439.81 | 04-NOV-14:09 | 2224.78 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4142.53 | 22-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2224.78 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 5195.02 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.21 | |||||
Maximum of Months | 1439.81 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2117.50 | 6050.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11758.94 | 02-JAN-18:52 | 8998.83 | 33178.29 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1373.59 |
February | 14849.66 | 05-FEB-22:02 | 4319.44 | 39813.95 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 886.40 |
March | 10186.61 | 17-MAR-23:03 | 719.91 | 13969.81 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.65 |
April | 8206.83 | 08-APR-12:30 | 2159.72 | 6635.66 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.60 |
May | 26585.92 | 31-MAY-07:03 | 719.91 | 1396.98 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.26 |
June | 31365.21 | 23-JUN-07:02 | 0.00 | 1749.37 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.01 |
July | 32784.81 | 11-JUL-07:02 | 1079.86 | 2095.47 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.40 |
August | 39179.43 | 25-AUG-07:02 | 0.00 | 1749.37 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.69 |
September | 37624.27 | 15-SEP-07:02 | 0.00 | 1749.37 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.72 |
October | 35722.03 | 14-OCT-07:02 | 0.00 | 1749.37 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389.95 |
November | 10895.96 | 24-NOV-00:03 | 719.91 | 13969.81 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.48 |
December | 10934.47 | 22-DEC-00:03 | 719.91 | 13969.81 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.27 |
Annual Sum or Average | |||||||||||
Minimum of Months | 8206.83 | 0.00 | 1396.98 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.01 | |
Maximum of Months | 39179.43 | 8998.83 | 39813.95 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1373.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4986.17 | 01-JAN-10:13 | 719.90 | 15170.27 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 746.00 |
February | 3697.05 | 19-FEB-09:01 | 899.88 | 19960.88 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.89 |
March | 4441.25 | 19-MAR-08:23 | 359.95 | 7984.35 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 595.47 |
April | 17881.60 | 10-APR-20:09 | 3779.50 | 26547.97 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.75 |
May | 17622.19 | 30-MAY-07:03 | 359.95 | 798.44 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.01 |
June | 17843.57 | 23-JUN-07:02 | 0.00 | 999.84 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.44 |
July | 18452.25 | 11-JUL-07:02 | 539.93 | 1197.65 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.49 |
August | 21809.74 | 25-AUG-07:02 | 0.00 | 999.84 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.00 |
September | 21038.86 | 15-SEP-07:02 | 0.00 | 999.84 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.23 |
October | 19809.96 | 14-OCT-07:02 | 0.00 | 999.84 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.35 |
November | 10978.62 | 03-NOV-20:15 | 1079.86 | 7585.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.60 |
December | 4169.21 | 06-DEC-09:23 | 269.96 | 5988.27 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.58 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3697.05 | 0.00 | 798.44 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.01 | |
Maximum of Months | 21809.74 | 3779.50 | 26547.97 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 746.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5286.93 | 08-JAN-11:02 | 1439.81 | 13772.62 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 648.14 |
February | 5076.48 | 14-FEB-09:43 | 719.90 | 13772.62 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.87 |
March | 4437.93 | 08-MAR-08:61 | 899.88 | 18121.86 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 546.79 |
April | 4728.27 | 08-APR-12:20 | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.96 |
May | 16520.97 | 30-MAY-06:03 | 0.00 | 724.87 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.15 |
June | 18096.33 | 23-JUN-06:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.32 |
July | 19159.30 | 11-JUL-06:02 | 0.00 | 1087.31 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.81 |
August | 21942.23 | 25-AUG-06:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.48 |
September | 22282.82 | 15-SEP-06:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.71 |
October | 19271.50 | 13-OCT-06:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7580.21 | 04-NOV-06:02 | 0.00 | 1087.31 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 |
December | 4506.10 | 09-DEC-08:32 | 359.95 | 7248.74 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 524.77 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4437.93 | 0.00 | 724.87 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22282.82 | 1439.81 | 18121.86 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5323.71 | 10-JAN-10:02 | 719.90 | 13772.62 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 678.55 |
February | 6504.40 | 06-FEB-18:42 | 4499.40 | 17215.77 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 909.82 |
March | 4381.74 | 19-MAR-09:13 | 719.90 | 13772.62 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 593.84 |
April | 4577.68 | 08-APR-12:20 | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.96 |
May | 16142.89 | 30-MAY-06:03 | 0.00 | 724.87 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.15 |
June | 17960.58 | 23-JUN-06:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.36 |
July | 19056.55 | 11-JUL-06:02 | 0.00 | 1087.31 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.96 |
August | 21802.20 | 25-AUG-06:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.60 |
September | 22129.55 | 15-SEP-06:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.77 |
October | 19064.93 | 13-OCT-06:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4093.51 | 04-NOV-06:02 | 0.00 | 1087.31 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 |
December | 4029.05 | 20-DEC-08:61 | 629.92 | 12685.30 | 2611.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.34 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4029.05 | 0.00 | 724.87 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22129.55 | 4499.40 | 17215.77 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 909.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4351.69 | 07-JAN-09:23 | 719.90 | 13772.62 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 606.28 |
February | 4410.67 | 04-FEB-18:42 | 359.95 | 7248.74 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.24 |
March | 4840.61 | 22-MAR-08:43 | 719.90 | 13772.62 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 695.76 |
April | 4258.52 | 08-APR-12:20 | 1079.86 | 3443.15 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 |
May | 14177.23 | 30-MAY-06:03 | 0.00 | 724.87 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.11 |
June | 17876.10 | 23-JUN-06:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.78 |
July | 18940.15 | 11-JUL-06:02 | 0.00 | 1087.31 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.54 |
August | 21679.01 | 25-AUG-06:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.08 |
September | 22005.14 | 15-SEP-06:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.38 |
October | 16457.39 | 13-OCT-06:02 | 0.00 | 906.09 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3875.73 | 18-NOV-08:61 | 719.90 | 14497.49 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.35 |
December | 4037.43 | 30-DEC-09:43 | 719.90 | 13772.62 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 650.71 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3875.73 | 0.00 | 724.87 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22005.14 | 1079.86 | 14497.49 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 695.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8193.90 | 25-JAN-20:23 | 1583.79 | 9367.50 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.21 |
February | 2985.78 | 02-FEB-12:00 | 1547.80 | 4449.56 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 811.94 |
March | 7416.28 | 09-MAR-09:43 | 1187.85 | 7025.62 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 741.94 |
April | 6987.04 | 12-APR-08:63 | 1187.85 | 7025.62 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 865.56 |
May | 25723.85 | 30-MAY-07:03 | 0.00 | 936.75 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.99 |
June | 30388.28 | 23-JUN-07:02 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.92 |
July | 31406.16 | 11-JUL-07:02 | 0.00 | 1405.12 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.31 |
August | 37255.43 | 25-AUG-07:02 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.23 |
September | 35715.94 | 15-SEP-07:02 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.02 |
October | 27660.46 | 14-OCT-07:02 | 0.00 | 1170.94 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.75 |
November | 5943.81 | 06-NOV-09:03 | 1187.85 | 7025.62 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 729.44 |
December | 9355.66 | 06-DEC-20:33 | 1583.79 | 9367.50 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.67 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2985.78 | 0.00 | 936.75 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.99 | |
Maximum of Months | 37255.43 | 1583.79 | 9367.50 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 865.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5425.19 | 05-JAN-11:43 | 3095.59 | 8899.12 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 710.15 |
February | 5028.52 | 03-FEB-20:53 | 791.89 | 4683.75 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.83 |
March | 4591.67 | 16-MAR-19:33 | 791.89 | 4683.75 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.38 |
April | 3410.34 | 12-APR-08:63 | 593.92 | 3512.81 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 467.14 |
May | 11924.95 | 30-MAY-07:03 | 0.00 | 468.37 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.11 |
June | 16112.73 | 23-JUN-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.70 |
July | 16633.19 | 11-JUL-07:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.82 |
August | 19532.16 | 25-AUG-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.66 |
September | 17435.46 | 15-SEP-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.07 |
October | 13380.91 | 06-OCT-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.56 |
November | 2937.07 | 18-NOV-14:55 | 2771.63 | 4449.56 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2511.42 |
December | 4476.02 | 27-DEC-20:42 | 791.89 | 4683.75 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.80 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2937.07 | 0.00 | 468.37 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.11 | |
Maximum of Months | 19532.16 | 3095.59 | 8899.12 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2511.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5407.23 | 05-JAN-11:53 | 3095.59 | 8899.12 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 708.87 |
February | 4294.26 | 22-FEB-10:23 | 791.89 | 8899.12 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 558.32 |
March | 5017.77 | 17-MAR-19:42 | 791.89 | 4683.75 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.26 |
April | 3378.63 | 12-APR-08:63 | 593.92 | 3512.81 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.76 |
May | 10891.31 | 30-MAY-07:03 | 0.00 | 468.37 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.90 |
June | 15993.14 | 23-JUN-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.63 |
July | 16495.44 | 11-JUL-07:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.80 |
August | 18831.01 | 25-AUG-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.55 |
September | 16872.08 | 02-SEP-07:01 | 0.00 | 819.66 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.16 |
October | 13259.81 | 06-OCT-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.37 |
November | 4566.29 | 24-NOV-20:42 | 791.89 | 4683.75 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.27 |
December | 2378.47 | 20-DEC-14:25 | 1799.76 | 4449.56 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2024.09 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2378.47 | 0.00 | 468.37 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.63 | |
Maximum of Months | 18831.01 | 3095.59 | 8899.12 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2024.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5621.87 | 31-JAN-11:43 | 3095.59 | 8899.12 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 744.75 |
February | 5297.37 | 03-FEB-18:12 | 2447.67 | 8899.12 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 625.36 |
March | 3964.65 | 13-MAR-10:13 | 2321.69 | 6674.34 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 574.98 |
April | 2848.94 | 11-APR-08:63 | 593.92 | 3512.81 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.06 |
May | 7711.77 | 31-MAY-07:03 | 0.00 | 468.37 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.46 |
June | 15797.35 | 23-JUN-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.25 |
July | 16276.21 | 11-JUL-07:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.04 |
August | 17465.18 | 23-AUG-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.68 |
September | 16668.66 | 02-SEP-07:01 | 0.00 | 819.66 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.87 |
October | 13027.18 | 06-OCT-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.91 |
November | 4731.56 | 22-NOV-19:33 | 1871.75 | 8899.12 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 669.55 |
December | 4404.08 | 21-DEC-10:13 | 791.89 | 8899.12 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 570.03 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2848.94 | 0.00 | 468.37 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.25 | |
Maximum of Months | 17465.18 | 3095.59 | 8899.12 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 744.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 546.00 | 19-JAN-12:00 | 773.90 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 574.13 |
February | 439.98 | 17-FEB-12:00 | 773.90 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.86 |
March | 3649.52 | 29-MAR-19:43 | 593.92 | 3512.81 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.23 |
April | 3008.37 | 03-APR-18:03 | 1403.81 | 6674.34 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 510.13 |
May | 5247.18 | 30-MAY-13:00 | 1277.83 | 2224.78 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1038.22 | 0.00 |
June | 13667.25 | 26-JUN-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.62 |
July | 16428.15 | 11-JUL-07:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.83 |
August | 15842.82 | 19-AUG-07:02 | 0.00 | 702.56 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.52 |
September | 16838.71 | 02-SEP-07:01 | 0.00 | 819.66 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.34 |
October | 5788.86 | 06-OCT-07:02 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.24 |
November | 3378.58 | 30-NOV-19:13 | 1403.81 | 6674.34 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 667.31 |
December | 4479.60 | 21-DEC-18:23 | 2447.67 | 8899.12 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.91 |
Annual Sum or Average | |||||||||||
Minimum of Months | 439.98 | 0.00 | 585.47 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16838.71 | 2447.67 | 8899.12 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1038.22 | 667.31 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.818127E+11 | 68166.15 | 04-JAN-16:49 | 0.106631E+12 | 205499.62 | 02-JAN-08:09 |
February | 0.733966E+11 | 66228.01 | 22-FEB-17:40 | 0.100984E+12 | 202636.97 | 06-FEB-08:09 |
March | 0.801371E+11 | 64462.34 | 10-MAR-18:30 | 0.562084E+11 | 120512.94 | 22-MAR-07:10 |
April | 0.760503E+11 | 72763.79 | 08-APR-12:20 | 0.183643E+11 | 80907.04 | 02-APR-08:09 |
May | 0.816275E+11 | 81392.46 | 30-MAY-12:00 | 0.381174E+09 | 12254.62 | 01-MAY-07:10 |
June | 0.977131E+11 | 103413.86 | 19-JUN-12:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.114077E+12 | 103401.53 | 08-JUL-12:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.114910E+12 | 106010.89 | 16-AUG-12:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.932788E+11 | 92433.54 | 07-SEP-14:20 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.846910E+11 | 77287.80 | 04-OCT-12:09 | 0.258219E+09 | 16415.87 | 28-OCT-08:30 |
November | 0.777242E+11 | 63839.09 | 01-NOV-17:49 | 0.351313E+11 | 113791.36 | 23-NOV-17:00 |
December | 0.813310E+11 | 63293.90 | 31-DEC-16:40 | 0.777369E+11 | 154864.66 | 31-DEC-17:00 |
Annual Sum or Average | 0.105675E+13 | 0.395695E+12 | ||||
Minimum of Months | 0.733966E+11 | 63293.90 | 0.00 | 0.00 | ||
Maximum of Months | 0.114910E+12 | 106010.89 | 0.106631E+12 | 205499.62 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.465742E+11 | 0.984028E+10 | 0.108325E+11 | 0.00 | 0.894944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561634E+10 | 0.00 |
February | 0.421675E+11 | 0.814818E+10 | 0.980803E+10 | 0.00 | 0.817783E+10 | 0.00 | 0.00 | 2140.49 | 0.00 | 0.00 | 0.00 | 0.509503E+10 | 0.00 |
March | 0.472558E+11 | 0.800487E+10 | 0.110038E+11 | 0.00 | 0.822867E+10 | 0.00 | 0.00 | 10791010.61 | 0.00 | 0.00 | 0.00 | 0.563308E+10 | 0.00 |
April | 0.451947E+11 | 0.672895E+10 | 0.105115E+11 | 0.00 | 0.732718E+10 | 0.00 | 0.00 | 0.964344E+09 | 0.00 | 0.00 | 0.00 | 0.532358E+10 | 0.00 |
May | 0.468973E+11 | 0.614493E+10 | 0.109147E+11 | 0.00 | 0.738228E+10 | 0.00 | 0.00 | 0.491388E+10 | 0.00 | 0.00 | 0.00 | 0.537438E+10 | 0.00 |
June | 0.456793E+11 | 0.553732E+10 | 0.106349E+11 | 0.00 | 0.724473E+10 | 0.00 | 0.00 | 0.235129E+11 | 0.00 | 0.00 | 0.00 | 0.510387E+10 | 0.00 |
July | 0.464483E+11 | 0.587160E+10 | 0.107982E+11 | 0.00 | 0.775270E+10 | 0.00 | 0.00 | 0.380394E+11 | 0.00 | 0.00 | 0.00 | 0.516648E+10 | 0.00 |
August | 0.472203E+11 | 0.654884E+10 | 0.109970E+11 | 0.00 | 0.800781E+10 | 0.00 | 0.00 | 0.369452E+11 | 0.00 | 0.00 | 0.00 | 0.519063E+10 | 0.00 |
September | 0.452303E+11 | 0.729987E+10 | 0.105184E+11 | 0.00 | 0.713017E+10 | 0.00 | 0.00 | 0.180643E+11 | 0.00 | 0.00 | 0.00 | 0.503585E+10 | 0.00 |
October | 0.465742E+11 | 0.860117E+10 | 0.108325E+11 | 0.00 | 0.731965E+10 | 0.00 | 0.00 | 0.607513E+10 | 0.00 | 0.00 | 0.00 | 0.528833E+10 | 0.00 |
November | 0.451236E+11 | 0.925369E+10 | 0.104978E+11 | 0.00 | 0.757775E+10 | 0.00 | 0.00 | 12216371.81 | 0.00 | 0.00 | 0.00 | 0.525913E+10 | 0.00 |
December | 0.464839E+11 | 0.100644E+11 | 0.108050E+11 | 0.00 | 0.843626E+10 | 0.00 | 0.00 | 9493.58 | 0.00 | 0.00 | 0.00 | 0.554145E+10 | 0.00 |
Annual Sum or Average | 0.550849E+12 | 0.920441E+11 | 0.128154E+12 | 0.935345E+11 | 0.00 | 0.128538E+12 | 0.636282E+11 | ||||||
Minimum of Months | 0.421675E+11 | 0.553732E+10 | 0.980803E+10 | 0.00 | 0.713017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503585E+10 | 0.00 |
Maximum of Months | 0.472558E+11 | 0.100644E+11 | 0.110038E+11 | 0.00 | 0.894944E+10 | 0.00 | 0.00 | 0.380394E+11 | 0.00 | 0.00 | 0.00 | 0.563308E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.106631E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.100984E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.562084E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.183643E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.381174E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.258219E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.351313E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.777369E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.395695E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.106631E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 34106.38 | 01-JAN-11:09 | 7048.42 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 8411.36 | 02-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 34106.38 | 01-FEB-10:09 | 7048.42 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 8363.65 | 06-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 34106.38 | 01-MAR-10:09 | 7048.42 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 6983.48 | 22-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 34106.38 | 01-APR-09:09 | 7048.42 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 6316.41 | 02-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 34106.38 | 01-MAY-09:09 | 7048.42 | 01-MAY-18:49 | 8059.50 | 01-MAY-09:09 | 0.00 | 5715.35 | 31-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 34106.38 | 01-JUN-09:09 | 7048.42 | 01-JUN-19:19 | 8059.50 | 01-JUN-09:09 | 0.00 | 8004.68 | 19-JUN-12:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 34106.38 | 01-JUL-09:09 | 7048.42 | 01-JUL-19:30 | 8059.50 | 01-JUL-09:09 | 0.00 | 8722.97 | 08-JUL-12:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 34106.38 | 01-AUG-09:09 | 7048.42 | 01-AUG-19:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 8690.96 | 16-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 34106.38 | 01-SEP-09:09 | 7048.42 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 6702.39 | 08-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 34106.38 | 01-OCT-10:09 | 7048.42 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 5905.81 | 06-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 34106.38 | 01-NOV-09:09 | 7048.42 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 6872.36 | 23-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 34106.38 | 01-DEC-10:09 | 7048.42 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 7564.36 | 31-DEC-17:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 34106.38 | 7048.42 | 8059.50 | 0.00 | 5715.35 | 0.00 | 0.00 | |||||
Maximum of Months | 34106.38 | 7048.42 | 8059.50 | 0.00 | 8722.97 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 11862.96 | 24-JAN-13:00 | 0.00 |
February | 3.57 | 20-FEB-20:19 | 0.00 | 0.00 | 0.00 | 11762.46 | 22-FEB-20:00 | 0.00 |
March | 2295.69 | 27-MAR-16:10 | 0.00 | 0.00 | 0.00 | 11853.83 | 27-MAR-12:50 | 0.00 |
April | 15845.58 | 07-APR-12:00 | 0.00 | 0.00 | 0.00 | 11567.74 | 08-APR-13:39 | 0.00 |
May | 26991.05 | 31-MAY-13:00 | 0.00 | 0.00 | 0.00 | 8877.82 | 10-MAY-17:10 | 0.00 |
June | 48692.27 | 19-JUN-12:09 | 0.00 | 0.00 | 0.00 | 7575.95 | 07-JUN-12:20 | 0.00 |
July | 49288.03 | 08-JUL-12:09 | 0.00 | 0.00 | 0.00 | 9393.78 | 26-JUL-13:20 | 0.00 |
August | 49260.22 | 16-AUG-12:00 | 0.00 | 0.00 | 0.00 | 9682.49 | 18-AUG-13:39 | 0.00 |
September | 37223.94 | 14-SEP-12:00 | 0.00 | 0.00 | 0.00 | 9654.95 | 07-SEP-16:19 | 0.00 |
October | 25043.73 | 04-OCT-12:00 | 0.00 | 0.00 | 0.00 | 10262.05 | 07-OCT-11:30 | 0.00 |
November | 1686.14 | 04-NOV-12:00 | 0.00 | 0.00 | 0.00 | 11035.21 | 07-NOV-16:40 | 0.00 |
December | 6.94 | 17-DEC-23:10 | 0.00 | 0.00 | 0.00 | 8140.56 | 07-DEC-14:50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7575.95 | 0.00 | ||
Maximum of Months | 49288.03 | 0.00 | 0.00 | 0.00 | 11862.96 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 68166.15 | 04-JAN-16:49 | 34106.38 | 8059.50 | 7048.42 | 0.00 | 7152.97 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 66228.01 | 22-FEB-17:40 | 34106.38 | 8059.50 | 7048.42 | 0.00 | 6205.49 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 64462.34 | 10-MAR-18:30 | 34106.38 | 8059.50 | 7048.42 | 0.00 | 5503.08 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 72763.79 | 08-APR-12:20 | 34106.38 | 8059.50 | 0.00 | 0.00 | 4956.54 | 0.00 | 0.00 | 15407.19 | 0.00 |
May | 81392.46 | 30-MAY-12:00 | 34106.38 | 8059.50 | 0.00 | 0.00 | 4956.54 | 0.00 | 0.00 | 26692.04 | 0.00 |
June | 103413.86 | 19-JUN-12:09 | 34106.38 | 8059.50 | 0.00 | 0.00 | 8004.68 | 0.00 | 0.00 | 48692.27 | 0.00 |
July | 103401.53 | 08-JUL-12:20 | 34106.38 | 8059.50 | 0.00 | 0.00 | 8722.97 | 0.00 | 0.00 | 49182.32 | 0.00 |
August | 106010.89 | 16-AUG-12:39 | 34106.38 | 8059.50 | 0.00 | 0.00 | 8609.09 | 0.00 | 0.00 | 48571.90 | 0.00 |
September | 92433.54 | 07-SEP-14:20 | 34106.38 | 8059.50 | 0.00 | 0.00 | 6283.38 | 0.00 | 0.00 | 36185.09 | 0.00 |
October | 77287.80 | 04-OCT-12:09 | 34106.38 | 8059.50 | 0.00 | 0.00 | 4956.54 | 0.00 | 0.00 | 24100.03 | 0.00 |
November | 63839.09 | 01-NOV-17:49 | 34106.38 | 8059.50 | 7048.42 | 0.00 | 4956.54 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 63293.90 | 31-DEC-16:40 | 34106.38 | 8059.50 | 7048.42 | 0.00 | 7252.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 63293.90 | 34106.38 | 8059.50 | 0.00 | 0.00 | 4956.54 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 106010.89 | 34106.38 | 8059.50 | 7048.42 | 0.00 | 8722.97 | 0.00 | 0.00 | 49182.32 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 205499.62 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 202636.97 | 06-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 120512.94 | 22-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 80907.04 | 02-APR-08:09 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 12254.62 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 16415.87 | 28-OCT-08:30 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 113791.36 | 23-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 154864.66 | 31-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 205499.62 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.50 | 20.45 | 0.33 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.67 | 20.47 | 0.33 | 20.48 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 20.54 | 0.33 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 20.49 | 0.00 | 0.17 | 24.45 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.49 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 20.41 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.17 | 20.31 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 20.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 20.24 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.67 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.17 | 20.30 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.17 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.50 | 20.35 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.33 | 18.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5.67 | 18.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.50 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.33 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 20.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 13.33 | 18.98 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.67 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.08 | 188.17 | 21.03 | 188.17 | 21.03 |
February | 448.00 | 21.07 | 193.00 | 21.03 | 193.00 | 21.03 |
March | 489.17 | 21.23 | 42.17 | 20.96 | 42.17 | 20.96 |
April | 378.83 | 21.72 | 42.83 | 23.33 | 8.00 | 20.90 |
May | 148.83 | 23.19 | 152.67 | 23.87 | 23.17 | 23.89 |
June | 24.50 | 23.88 | 428.67 | 23.89 | 22.33 | 23.89 |
July | 18.00 | 23.92 | 496.00 | 23.89 | 18.00 | 23.92 |
August | 2.83 | 24.01 | 476.17 | 23.89 | 2.83 | 24.01 |
September | 16.00 | 23.81 | 386.67 | 23.89 | 10.17 | 23.90 |
October | 167.00 | 22.93 | 241.67 | 23.88 | 13.50 | 23.89 |
November | 441.83 | 21.64 | 22.83 | 21.59 | 17.17 | 20.85 |
December | 496.00 | 21.08 | 61.83 | 20.87 | 61.83 | 20.87 |
Annual Sum or Average | 3127.00 | 21.51 | 2732.67 | 23.35 | 600.33 | 21.43 |
Minimum of Months | 2.83 | 21.07 | 22.83 | 20.87 | 2.83 | 20.85 |
Maximum of Months | 496.00 | 24.01 | 496.00 | 23.89 | 193.00 | 24.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.55 | 68.83 | 21.12 | 68.83 | 21.12 |
February | 448.00 | 21.56 | 59.50 | 21.12 | 59.50 | 21.12 |
March | 486.50 | 21.93 | 11.67 | 21.84 | 8.67 | 21.13 |
April | 326.00 | 22.30 | 48.33 | 23.88 | 0.17 | 21.22 |
May | 79.17 | 23.60 | 194.17 | 23.87 | 19.83 | 23.89 |
June | 5.67 | 23.81 | 413.00 | 23.88 | 4.50 | 23.88 |
July | 3.83 | 23.89 | 494.67 | 23.89 | 3.83 | 23.89 |
August | 0.67 | 23.88 | 465.17 | 23.89 | 0.50 | 24.00 |
September | 14.00 | 23.78 | 374.67 | 23.88 | 7.83 | 23.89 |
October | 118.17 | 23.42 | 243.83 | 23.87 | 6.83 | 23.88 |
November | 383.33 | 22.16 | 17.33 | 23.33 | 3.50 | 21.16 |
December | 496.00 | 21.69 | 8.67 | 21.15 | 8.67 | 21.15 |
Annual Sum or Average | 2857.33 | 21.96 | 2399.83 | 23.71 | 192.67 | 21.75 |
Minimum of Months | 0.67 | 21.55 | 8.67 | 21.12 | 0.17 | 21.12 |
Maximum of Months | 496.00 | 23.89 | 494.67 | 23.89 | 68.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 103.33 | 21.11 | 103.33 | 21.11 |
February | 336.00 | 21.11 | 95.83 | 21.11 | 95.83 | 21.11 |
March | 372.83 | 21.32 | 17.00 | 21.11 | 17.00 | 21.11 |
April | 269.50 | 21.76 | 27.50 | 23.81 | 1.50 | 21.11 |
May | 88.83 | 23.44 | 130.83 | 23.98 | 22.00 | 23.91 |
June | 15.67 | 24.38 | 330.00 | 24.02 | 15.00 | 24.41 |
July | 16.50 | 25.14 | 369.00 | 24.06 | 16.50 | 25.14 |
August | 6.83 | 26.24 | 366.83 | 24.06 | 6.83 | 26.24 |
September | 13.33 | 23.92 | 301.17 | 24.02 | 9.50 | 24.05 |
October | 108.50 | 23.09 | 194.00 | 23.96 | 9.17 | 23.98 |
November | 310.33 | 21.66 | 13.67 | 22.56 | 6.50 | 21.11 |
December | 369.00 | 21.12 | 22.83 | 21.11 | 22.83 | 21.11 |
Annual Sum or Average | 2278.33 | 21.57 | 1972.00 | 23.66 | 326.00 | 21.93 |
Minimum of Months | 6.83 | 21.11 | 13.67 | 21.11 | 1.50 | 21.11 |
Maximum of Months | 372.83 | 26.24 | 369.00 | 24.06 | 103.33 | 26.24 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 119.83 | 21.11 | 119.83 | 21.11 |
February | 336.00 | 21.11 | 113.50 | 21.11 | 113.50 | 21.11 |
March | 373.17 | 21.28 | 19.83 | 21.11 | 19.83 | 21.11 |
April | 282.67 | 21.78 | 27.17 | 23.68 | 2.67 | 21.11 |
May | 107.83 | 23.30 | 119.67 | 23.99 | 22.00 | 23.91 |
June | 15.83 | 24.37 | 330.00 | 24.02 | 15.17 | 24.40 |
July | 16.50 | 25.14 | 369.00 | 24.06 | 16.50 | 25.14 |
August | 7.00 | 26.26 | 367.17 | 24.06 | 7.00 | 26.26 |
September | 14.83 | 23.89 | 300.67 | 24.02 | 9.67 | 24.04 |
October | 118.17 | 23.04 | 192.50 | 23.96 | 10.00 | 23.97 |
November | 325.67 | 21.66 | 14.33 | 22.33 | 8.00 | 21.11 |
December | 369.00 | 21.12 | 29.00 | 21.11 | 29.00 | 21.11 |
Annual Sum or Average | 2337.67 | 21.58 | 2002.67 | 23.60 | 373.17 | 21.84 |
Minimum of Months | 7.00 | 21.11 | 14.33 | 21.11 | 2.67 | 21.11 |
Maximum of Months | 373.17 | 26.26 | 369.00 | 24.06 | 119.83 | 26.26 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 136.50 | 21.11 | 136.50 | 21.11 |
February | 336.00 | 21.11 | 130.67 | 21.11 | 130.67 | 21.11 |
March | 373.83 | 21.25 | 25.50 | 21.11 | 25.50 | 21.11 |
April | 291.50 | 21.75 | 26.33 | 23.52 | 4.00 | 21.11 |
May | 130.50 | 23.13 | 102.67 | 23.98 | 22.33 | 23.91 |
June | 18.50 | 24.28 | 327.83 | 24.02 | 17.33 | 24.31 |
July | 21.50 | 24.90 | 369.00 | 24.05 | 21.50 | 24.90 |
August | 8.67 | 25.75 | 365.67 | 24.06 | 8.67 | 25.75 |
September | 17.83 | 23.88 | 296.50 | 24.01 | 11.33 | 24.07 |
October | 130.17 | 22.92 | 186.00 | 23.95 | 11.67 | 23.95 |
November | 339.00 | 21.61 | 14.50 | 21.69 | 11.50 | 21.11 |
December | 369.00 | 21.11 | 37.67 | 21.11 | 37.67 | 21.11 |
Annual Sum or Average | 2407.50 | 21.58 | 2018.83 | 23.52 | 438.67 | 21.81 |
Minimum of Months | 8.67 | 21.11 | 14.50 | 21.11 | 4.00 | 21.11 |
Maximum of Months | 373.83 | 25.75 | 369.00 | 24.06 | 136.50 | 25.75 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 175.83 | 21.11 | 175.83 | 21.11 |
February | 308.00 | 21.11 | 175.83 | 21.11 | 175.83 | 21.11 |
March | 348.00 | 21.20 | 41.83 | 21.11 | 41.83 | 21.11 |
April | 291.50 | 21.70 | 13.50 | 22.93 | 4.67 | 21.11 |
May | 165.50 | 22.79 | 68.00 | 23.87 | 23.50 | 23.84 |
June | 32.00 | 24.05 | 289.83 | 23.92 | 30.33 | 24.06 |
July | 33.33 | 24.23 | 337.17 | 23.95 | 33.33 | 24.23 |
August | 16.17 | 24.33 | 325.33 | 23.94 | 16.17 | 24.33 |
September | 20.50 | 23.77 | 256.17 | 23.93 | 13.83 | 23.91 |
October | 139.83 | 22.61 | 158.33 | 23.90 | 13.67 | 23.89 |
November | 322.17 | 21.42 | 25.83 | 21.11 | 25.83 | 21.11 |
December | 338.00 | 21.11 | 95.00 | 21.11 | 95.00 | 21.11 |
Annual Sum or Average | 2355.00 | 21.57 | 1962.67 | 23.18 | 649.83 | 21.70 |
Minimum of Months | 16.17 | 21.11 | 13.50 | 21.11 | 4.67 | 21.11 |
Maximum of Months | 348.00 | 24.33 | 337.17 | 23.95 | 175.83 | 24.33 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 180.17 | 21.11 | 180.17 | 21.11 |
February | 308.00 | 21.11 | 184.17 | 21.11 | 184.17 | 21.11 |
March | 348.00 | 21.19 | 52.00 | 21.11 | 52.00 | 21.11 |
April | 298.83 | 21.72 | 12.17 | 22.52 | 6.00 | 21.11 |
May | 186.17 | 22.78 | 62.33 | 23.87 | 23.33 | 23.83 |
June | 36.33 | 24.02 | 278.33 | 23.92 | 33.67 | 24.04 |
July | 46.50 | 24.13 | 336.83 | 23.95 | 46.50 | 24.13 |
August | 18.83 | 24.26 | 313.00 | 23.94 | 18.83 | 24.26 |
September | 25.33 | 23.77 | 237.17 | 23.93 | 14.50 | 23.91 |
October | 147.67 | 22.63 | 146.50 | 23.90 | 14.00 | 23.89 |
November | 324.17 | 21.40 | 29.67 | 21.11 | 29.67 | 21.11 |
December | 338.00 | 21.11 | 108.50 | 21.11 | 108.50 | 21.11 |
Annual Sum or Average | 2417.83 | 21.61 | 1940.83 | 23.11 | 711.33 | 21.73 |
Minimum of Months | 18.83 | 21.11 | 12.17 | 21.11 | 6.00 | 21.11 |
Maximum of Months | 348.00 | 24.26 | 336.83 | 23.95 | 184.17 | 24.26 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 187.83 | 21.11 | 187.83 | 21.11 |
February | 308.00 | 21.11 | 193.33 | 21.11 | 193.33 | 21.11 |
March | 348.00 | 21.18 | 57.83 | 21.11 | 57.83 | 21.11 |
April | 302.17 | 21.70 | 13.67 | 22.23 | 8.17 | 21.11 |
May | 200.50 | 22.74 | 60.00 | 23.86 | 23.17 | 23.80 |
June | 39.50 | 24.01 | 276.83 | 23.92 | 36.17 | 24.03 |
July | 52.00 | 24.09 | 336.50 | 23.95 | 52.00 | 24.09 |
August | 20.50 | 24.23 | 309.17 | 23.94 | 20.50 | 24.23 |
September | 26.83 | 23.75 | 233.67 | 23.93 | 14.83 | 23.91 |
October | 152.17 | 22.58 | 143.67 | 23.90 | 14.17 | 23.89 |
November | 325.17 | 21.37 | 33.67 | 21.11 | 33.67 | 21.11 |
December | 338.00 | 21.11 | 118.17 | 21.11 | 118.17 | 21.11 |
Annual Sum or Average | 2452.83 | 21.62 | 1964.33 | 23.07 | 759.83 | 21.73 |
Minimum of Months | 20.50 | 21.11 | 13.67 | 21.11 | 8.17 | 21.11 |
Maximum of Months | 348.00 | 24.23 | 336.50 | 23.95 | 193.33 | 24.23 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 215.67 | 21.11 | 215.67 | 21.11 |
February | 308.00 | 21.11 | 217.67 | 21.11 | 217.67 | 21.11 |
March | 348.00 | 21.17 | 79.50 | 21.11 | 79.50 | 21.11 |
April | 308.33 | 21.66 | 19.67 | 21.72 | 15.33 | 21.11 |
May | 223.00 | 22.65 | 53.00 | 23.82 | 23.00 | 23.68 |
June | 48.83 | 23.99 | 271.83 | 23.92 | 44.17 | 24.01 |
July | 58.33 | 24.07 | 336.50 | 23.95 | 58.33 | 24.07 |
August | 22.50 | 24.20 | 307.50 | 23.94 | 22.50 | 24.20 |
September | 34.33 | 23.71 | 230.17 | 23.93 | 17.50 | 23.90 |
October | 162.67 | 22.50 | 139.00 | 23.89 | 14.50 | 23.89 |
November | 326.33 | 21.32 | 45.17 | 21.11 | 45.17 | 21.11 |
December | 338.00 | 21.11 | 158.00 | 21.11 | 158.00 | 21.11 |
Annual Sum or Average | 2518.33 | 21.63 | 2073.67 | 22.93 | 911.33 | 21.68 |
Minimum of Months | 22.50 | 21.11 | 19.67 | 21.11 | 14.50 | 21.11 |
Maximum of Months | 348.00 | 24.20 | 336.50 | 23.95 | 217.67 | 24.20 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 279.50 | 21.11 | 279.50 | 21.11 |
February | 308.00 | 21.11 | 293.67 | 21.11 | 293.67 | 21.11 |
March | 348.00 | 21.14 | 175.83 | 21.11 | 175.83 | 21.11 |
April | 318.00 | 21.61 | 52.50 | 21.11 | 52.50 | 21.11 |
May | 271.50 | 22.50 | 45.83 | 23.51 | 23.33 | 23.08 |
June | 95.83 | 23.92 | 262.50 | 23.91 | 88.50 | 23.94 |
July | 84.17 | 24.02 | 336.67 | 23.95 | 84.17 | 24.02 |
August | 26.83 | 24.15 | 315.83 | 23.94 | 26.83 | 24.15 |
September | 47.17 | 23.59 | 227.17 | 23.93 | 20.67 | 23.90 |
October | 182.33 | 22.35 | 134.83 | 23.88 | 16.33 | 23.80 |
November | 328.83 | 21.27 | 77.50 | 21.11 | 77.50 | 21.11 |
December | 338.00 | 21.11 | 260.50 | 21.11 | 260.50 | 21.11 |
Annual Sum or Average | 2688.67 | 21.68 | 2462.33 | 22.62 | 1399.33 | 21.63 |
Minimum of Months | 26.83 | 21.11 | 45.83 | 21.11 | 16.33 | 21.11 |
Maximum of Months | 348.00 | 24.15 | 336.67 | 23.95 | 293.67 | 24.15 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.06922 | 21.93705 | -0.5050 | 10.67452 |
February | 448.00000 | 21.06251 | 16.60366 | -0.5362 | 11.28741 |
March | 496.00000 | 21.26040 | 28.17163 | -0.3665 | 8.41626 |
April | 480.00000 | 22.16901 | 35.22600 | -0.0845 | 7.34790 |
May | 496.00000 | 23.64810 | 41.68340 | -0.5597 | 12.34974 |
June | 480.00000 | 23.89644 | 51.74833 | -0.3268 | 7.40061 |
July | 496.00000 | 23.90296 | 56.74622 | -0.2460 | 6.35189 |
August | 496.00000 | 23.90280 | 50.50445 | -0.2749 | 6.75232 |
September | 480.00000 | 23.88991 | 46.05891 | -0.3556 | 7.85863 |
October | 496.00000 | 23.55935 | 39.33102 | 0.35495 | 8.78934 |
November | 480.00000 | 21.81336 | 30.24943 | -0.1923 | 7.51315 |
December | 496.00000 | 21.08153 | 21.65164 | -0.4627 | 9.62275 |
Annual Sum or Average | 5840.00000 | 22.61361 | 36.77855 | -0.2949 | 8.68854 |
Minimum of Months | 448.00000 | 21.06251 | 16.60366 | -0.5597 | 6.35189 |
Maximum of Months | 496.00000 | 23.90296 | 56.74622 | 0.35495 | 12.34974 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.52886 | 22.77362 | -0.3720 | 8.54979 |
February | 448.00000 | 21.53499 | 17.49586 | -0.3970 | 8.86302 |
March | 496.00000 | 21.94551 | 28.14942 | -0.2017 | 6.93272 |
April | 480.00000 | 22.78700 | 34.58345 | 0.06125 | 6.84456 |
May | 496.00000 | 23.80980 | 40.80986 | -0.4912 | 10.38724 |
June | 480.00000 | 23.88458 | 49.09897 | -0.3420 | 7.63456 |
July | 496.00000 | 23.90423 | 54.07297 | -0.2678 | 6.60891 |
August | 496.00000 | 23.89975 | 48.74259 | -0.2967 | 7.02002 |
September | 480.00000 | 23.87943 | 44.59687 | -0.3681 | 8.03804 |
October | 496.00000 | 23.76056 | 38.33104 | 0.39468 | 8.85138 |
November | 480.00000 | 22.47663 | 29.95735 | -0.0419 | 6.89982 |
December | 496.00000 | 21.67383 | 22.24178 | -0.3158 | 7.67898 |
Annual Sum or Average | 5840.00000 | 22.93153 | 36.01573 | -0.2189 | 7.85637 |
Minimum of Months | 448.00000 | 21.52886 | 17.49586 | -0.4912 | 6.60891 |
Maximum of Months | 496.00000 | 23.90423 | 54.07297 | 0.39468 | 10.38724 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10991 | 21.87457 | -0.4729 | 9.91931 |
February | 336.00000 | 21.10981 | 16.30515 | -0.4953 | 10.28107 |
March | 379.00000 | 21.36186 | 27.38338 | -0.3252 | 7.84684 |
April | 360.00000 | 22.30416 | 34.00094 | -0.0440 | 7.12848 |
May | 375.00000 | 23.78183 | 41.07663 | -0.5057 | 10.91056 |
June | 366.00000 | 23.98518 | 51.13699 | -0.3003 | 7.15939 |
July | 369.00000 | 24.02089 | 56.57046 | -0.2144 | 6.24716 |
August | 379.00000 | 24.02070 | 50.03655 | -0.2490 | 6.67060 |
September | 360.00000 | 23.97275 | 45.79562 | -0.3335 | 7.63057 |
October | 371.00000 | 23.68108 | 39.17554 | 0.38595 | 9.03700 |
November | 360.00000 | 21.95376 | 29.69512 | -0.1514 | 7.37320 |
December | 369.00000 | 21.12136 | 21.21196 | -0.4360 | 9.05375 |
Annual Sum or Average | 4395.00000 | 22.71391 | 36.33876 | -0.2608 | 8.26275 |
Minimum of Months | 336.00000 | 21.10981 | 16.30515 | -0.5057 | 6.24716 |
Maximum of Months | 379.00000 | 24.02089 | 56.57046 | 0.38595 | 10.91056 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10972 | 21.87528 | -0.4861 | 10.19436 |
February | 336.00000 | 21.10968 | 16.30576 | -0.5067 | 10.52593 |
March | 379.00000 | 21.32515 | 27.45728 | -0.3431 | 8.03955 |
April | 360.00000 | 22.24214 | 34.15991 | -0.0658 | 7.18733 |
May | 375.00000 | 23.73808 | 41.22404 | -0.5260 | 11.48983 |
June | 366.00000 | 23.98422 | 51.17124 | -0.3017 | 7.17639 |
July | 369.00000 | 24.02045 | 56.57159 | -0.2146 | 6.24754 |
August | 379.00000 | 24.02038 | 50.02492 | -0.2488 | 6.66824 |
September | 360.00000 | 23.97084 | 45.81636 | -0.3353 | 7.66016 |
October | 371.00000 | 23.64538 | 39.28225 | 0.37501 | 8.95874 |
November | 360.00000 | 21.87217 | 29.86751 | -0.1788 | 7.42838 |
December | 369.00000 | 21.11756 | 21.21646 | -0.4476 | 9.26628 |
Annual Sum or Average | 4395.00000 | 22.69159 | 36.39799 | -0.2723 | 8.39498 |
Minimum of Months | 336.00000 | 21.10968 | 16.30576 | -0.5260 | 6.24754 |
Maximum of Months | 379.00000 | 24.02045 | 56.57159 | 0.37501 | 11.48983 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10983 | 21.87492 | -0.5014 | 10.52431 |
February | 336.00000 | 21.10968 | 16.30552 | -0.5211 | 10.84659 |
March | 379.00000 | 21.28340 | 27.53931 | -0.3640 | 8.28880 |
April | 360.00000 | 22.15650 | 34.37660 | -0.0949 | 7.23502 |
May | 375.00000 | 23.63965 | 41.57166 | -0.5696 | 12.80414 |
June | 366.00000 | 23.98022 | 51.49489 | -0.3083 | 7.25740 |
July | 369.00000 | 24.01717 | 56.90393 | -0.2196 | 6.28002 |
August | 379.00000 | 24.01716 | 50.25350 | -0.2546 | 6.71856 |
September | 360.00000 | 23.96432 | 46.03539 | -0.3433 | 7.77990 |
October | 371.00000 | 23.57618 | 39.61046 | 0.35469 | 8.82339 |
November | 360.00000 | 21.74585 | 30.14116 | -0.2178 | 7.48549 |
December | 369.00000 | 21.11399 | 21.22069 | -0.4608 | 9.51788 |
Annual Sum or Average | 4395.00000 | 22.65468 | 36.59541 | -0.2907 | 8.62288 |
Minimum of Months | 336.00000 | 21.10968 | 16.30552 | -0.5696 | 6.28002 |
Maximum of Months | 379.00000 | 24.01717 | 56.90393 | 0.35469 | 12.80414 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10985 | 22.69804 | -0.5498 | 11.59294 |
February | 308.00000 | 21.10994 | 17.09313 | -0.5673 | 11.90021 |
March | 348.00000 | 21.19793 | 28.51453 | -0.4159 | 9.01256 |
April | 330.00000 | 21.95320 | 35.63419 | -0.1649 | 7.38796 |
May | 344.00000 | 23.34448 | 43.18607 | -0.6901 | 16.73788 |
June | 336.00000 | 23.91163 | 53.00271 | -0.3441 | 7.67548 |
July | 338.00000 | 23.93693 | 58.39411 | -0.2523 | 6.48539 |
August | 348.00000 | 23.92356 | 51.35192 | -0.2915 | 7.00372 |
September | 330.00000 | 23.90024 | 47.23326 | -0.3781 | 8.24870 |
October | 340.00000 | 23.36114 | 41.07636 | 0.29966 | 8.45979 |
November | 330.00000 | 21.48092 | 31.42907 | -0.3045 | 7.92454 |
December | 338.00000 | 21.10972 | 21.90793 | -0.5035 | 10.37478 |
Annual Sum or Average | 4030.00000 | 22.53975 | 37.78322 | -0.3459 | 9.39642 |
Minimum of Months | 308.00000 | 21.10972 | 17.09313 | -0.6901 | 6.48539 |
Maximum of Months | 348.00000 | 23.93693 | 58.39411 | 0.29966 | 16.73788 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10979 | 22.64447 | -0.5535 | 11.66758 |
February | 308.00000 | 21.10967 | 17.03966 | -0.5729 | 12.02658 |
March | 348.00000 | 21.19162 | 28.48157 | -0.4277 | 9.20543 |
April | 330.00000 | 21.92239 | 35.66630 | -0.1841 | 7.46016 |
May | 344.00000 | 23.28443 | 43.33308 | -0.7314 | 18.16124 |
June | 336.00000 | 23.91108 | 53.19107 | -0.3673 | 8.01766 |
July | 338.00000 | 23.93603 | 58.61654 | -0.2782 | 6.76742 |
August | 348.00000 | 23.92286 | 51.49641 | -0.3189 | 7.34774 |
September | 330.00000 | 23.89968 | 47.35781 | -0.4014 | 8.62083 |
October | 340.00000 | 23.33913 | 41.22667 | 0.27928 | 8.27543 |
November | 330.00000 | 21.44294 | 31.46146 | -0.3247 | 8.08473 |
December | 338.00000 | 21.10960 | 21.85631 | -0.5104 | 10.52023 |
Annual Sum or Average | 4030.00000 | 22.52633 | 37.85498 | -0.3651 | 9.67857 |
Minimum of Months | 308.00000 | 21.10960 | 17.03966 | -0.7314 | 6.76742 |
Maximum of Months | 348.00000 | 23.93603 | 58.61654 | 0.27928 | 18.16124 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10985 | 22.64456 | -0.5585 | 11.78242 |
February | 308.00000 | 21.10960 | 17.04011 | -0.5785 | 12.16387 |
March | 348.00000 | 21.18380 | 28.49807 | -0.4352 | 9.32886 |
April | 330.00000 | 21.88465 | 35.75844 | -0.1977 | 7.51855 |
May | 344.00000 | 23.21518 | 43.54391 | -0.7614 | 19.29359 |
June | 336.00000 | 23.91040 | 53.33588 | -0.3711 | 8.07857 |
July | 338.00000 | 23.93554 | 58.75626 | -0.2815 | 6.80300 |
August | 348.00000 | 23.92252 | 51.57976 | -0.3223 | 7.39248 |
September | 330.00000 | 23.89725 | 47.43540 | -0.4058 | 8.70129 |
October | 340.00000 | 23.30184 | 41.36300 | 0.26782 | 8.23272 |
November | 330.00000 | 21.40547 | 31.54223 | -0.3379 | 8.19618 |
December | 338.00000 | 21.10986 | 21.85611 | -0.5155 | 10.63174 |
Annual Sum or Average | 4030.00000 | 22.51013 | 37.93743 | -0.3740 | 9.84423 |
Minimum of Months | 308.00000 | 21.10960 | 17.04011 | -0.7614 | 6.80300 |
Maximum of Months | 348.00000 | 23.93554 | 58.75626 | 0.26782 | 19.29359 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10985 | 22.64462 | -0.5739 | 12.15208 |
February | 308.00000 | 21.10983 | 17.03995 | -0.5959 | 12.59769 |
March | 348.00000 | 21.16675 | 28.53217 | -0.4547 | 9.67139 |
April | 330.00000 | 21.80563 | 35.94654 | -0.2275 | 7.70470 |
May | 344.00000 | 23.07428 | 43.98135 | -0.8203 | 21.50661 |
June | 336.00000 | 23.90826 | 53.70968 | -0.3766 | 8.17148 |
July | 338.00000 | 23.93467 | 59.04544 | -0.2832 | 6.82139 |
August | 348.00000 | 23.92203 | 51.73073 | -0.3237 | 7.41264 |
September | 330.00000 | 23.88981 | 47.61441 | -0.4115 | 8.82747 |
October | 340.00000 | 23.21896 | 41.64906 | 0.24518 | 8.18737 |
November | 330.00000 | 21.34682 | 31.66619 | -0.3610 | 8.44680 |
December | 338.00000 | 21.10935 | 21.85678 | -0.5302 | 10.95792 |
Annual Sum or Average | 4030.00000 | 22.47744 | 38.11057 | -0.3920 | 10.20772 |
Minimum of Months | 308.00000 | 21.10935 | 17.03995 | -0.8203 | 6.82139 |
Maximum of Months | 348.00000 | 23.93467 | 59.04544 | 0.24518 | 21.50661 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10995 | 22.55281 | -0.6331 | 13.68313 |
February | 308.00000 | 21.10994 | 16.95503 | -0.6620 | 14.37961 |
March | 348.00000 | 21.14437 | 28.43426 | -0.5188 | 10.97322 |
April | 330.00000 | 21.68532 | 36.11738 | -0.2987 | 8.48625 |
May | 344.00000 | 22.79147 | 44.76200 | -0.9478 | 26.50806 |
June | 336.00000 | 23.89893 | 55.07985 | -0.3898 | 8.41977 |
July | 338.00000 | 23.93441 | 59.87809 | -0.2762 | 6.73642 |
August | 348.00000 | 23.92254 | 52.01734 | -0.3107 | 7.25701 |
September | 330.00000 | 23.86427 | 48.03218 | -0.4197 | 9.10949 |
October | 340.00000 | 23.05738 | 41.97935 | 0.20106 | 8.21833 |
November | 330.00000 | 21.27543 | 31.66430 | -0.4104 | 9.22200 |
December | 338.00000 | 21.10976 | 21.76553 | -0.5835 | 12.22697 |
Annual Sum or Average | 4030.00000 | 22.41924 | 38.43159 | -0.4366 | 11.27217 |
Minimum of Months | 308.00000 | 21.10976 | 16.95503 | -0.9478 | 6.73642 |
Maximum of Months | 348.00000 | 23.93441 | 59.87809 | 0.20106 | 26.50806 |
Report: DXReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 11060635.30 | 3126658.03 | 5.17 | 7885372.53 | 3175262.77 | 0.00 | 0.16 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 2588.32 | 27-MAR-16:10 | 1839.33 | 27-MAR-16:10 | 748.99 | 27-MAR-16:10 | 726.56 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.765029E+09 | 0.204991E+09 | 63.53 | 0.645178E+09 | 0.119851E+09 | 0.00 | 0.61 | 07-APR-13:00 | 0.00 | 01-APR-00:05 | 11012.15 | 08-APR-12:10 | 9763.30 | 07-APR-13:00 | 2738.63 | 09-APR-11:00 | 2906.08 | 07-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.405897E+10 | 0.105457E+10 | 239.92 | 0.338535E+10 | 0.673622E+09 | 0.00 | 0.93 | 31-MAY-14:00 | 0.00 | 01-MAY-00:10 | 39373.85 | 31-MAY-07:03 | 30554.05 | 31-MAY-07:03 | 8819.80 | 31-MAY-07:03 | 8520.05 | 31-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.197729E+11 | 0.483690E+10 | 459.88 | 0.130356E+11 | 0.673727E+10 | 0.00 | 1.00 | 08-JUN-07:02 | 0.00 | 01-JUN-00:10 | 45045.13 | 25-JUN-07:02 | 35454.09 | 23-JUN-07:02 | 24218.67 | 16-JUN-07:02 | 10092.66 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.335728E+11 | 0.794781E+10 | 499.75 | 0.206331E+11 | 0.129397E+11 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 46172.10 | 22-JUL-07:01 | 32474.94 | 12-JUL-07:02 | 23046.06 | 22-JUL-07:04 | 9995.22 | 10-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.313175E+11 | 0.757897E+10 | 496.78 | 0.213184E+11 | 0.999914E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 45668.46 | 17-AUG-07:01 | 33605.53 | 31-AUG-07:02 | 21182.80 | 17-AUG-07:04 | 10023.04 | 04-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.155976E+11 | 0.381483E+10 | 416.66 | 0.110173E+11 | 0.458035E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 45038.43 | 14-SEP-07:02 | 33712.25 | 04-SEP-07:02 | 19066.48 | 14-SEP-07:03 | 9772.08 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.529318E+10 | 0.131465E+10 | 252.83 | 0.351088E+10 | 0.178230E+10 | 0.00 | 1.00 | 06-OCT-07:02 | 0.00 | 01-OCT-00:05 | 43383.67 | 06-OCT-07:02 | 23746.02 | 14-OCT-07:02 | 20665.87 | 06-OCT-07:02 | 9293.28 | 06-OCT-07:02 | 0.00 | 01-OCT-00:05 |
November | 11728542.79 | 3293525.53 | 12.69 | 9291877.48 | 2436665.31 | 0.00 | 0.14 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 | 2191.77 | 04-NOV-13:00 | 1698.17 | 04-NOV-13:00 | 493.60 | 04-NOV-13:00 | 609.94 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.110401E+12 | 0.267591E+11 | 2447.21 | 0.735629E+11 | 0.368378E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.335728E+11 | 0.794781E+10 | 499.75 | 0.213184E+11 | 0.129397E+11 | 0.00 | 1.00 | 0.00 | 46172.10 | 35454.09 | 24218.67 | 10092.66 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 7024.65 | 2140.49 | 0.17 | 7024.65 | 0.00 | 0.00 | 0.00 | 20-FEB-20:20 | 0.00 | 01-FEB-00:10 | 11.71 | 20-FEB-20:20 | 11.71 | 20-FEB-20:20 | 0.00 | 01-FEB-00:10 | 3.57 | 20-FEB-20:20 | 0.00 | 01-FEB-00:10 |
March | 17195048.15 | 4739585.21 | 8.42 | 12568489.02 | 4626559.13 | 0.00 | 0.25 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 2318.70 | 27-MAR-16:10 | 1668.59 | 27-MAR-16:10 | 650.10 | 27-MAR-16:10 | 623.70 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.602690E+09 | 0.152465E+09 | 76.61 | 0.508590E+09 | 94099464.46 | 0.00 | 1.00 | 07-APR-20:02 | 0.00 | 01-APR-00:05 | 22070.70 | 07-APR-20:02 | 20833.64 | 10-APR-20:09 | 8210.13 | 09-APR-17:10 | 4714.00 | 07-APR-20:02 | 0.00 | 01-APR-00:05 |
May | 0.289998E+10 | 0.716650E+09 | 248.24 | 0.246358E+10 | 0.436397E+09 | 0.00 | 1.00 | 09-MAY-20:02 | 0.00 | 01-MAY-00:10 | 22580.11 | 30-MAY-07:03 | 21125.73 | 20-MAY-18:52 | 7076.29 | 30-MAY-22:23 | 4944.34 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.114175E+11 | 0.275900E+10 | 448.82 | 0.792406E+10 | 0.349345E+10 | 0.00 | 1.00 | 01-JUN-20:52 | 0.00 | 01-JUN-00:10 | 23956.92 | 27-JUN-07:02 | 20312.62 | 23-JUN-07:02 | 12300.50 | 06-JUN-20:20 | 5386.90 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.173806E+11 | 0.411925E+10 | 499.43 | 0.112869E+11 | 0.609378E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 24513.47 | 22-JUL-07:01 | 19811.39 | 02-JUL-07:02 | 9484.43 | 22-JUL-07:03 | 5351.11 | 10-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.163604E+11 | 0.395140E+10 | 492.71 | 0.116394E+11 | 0.472099E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24244.91 | 17-AUG-07:01 | 20903.38 | 24-AUG-22:00 | 9043.89 | 07-AUG-07:02 | 5371.81 | 17-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.889458E+10 | 0.214748E+10 | 402.70 | 0.657667E+10 | 0.231791E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 24015.68 | 14-SEP-07:02 | 21128.85 | 10-SEP-17:02 | 10050.89 | 22-SEP-20:52 | 5208.05 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.347548E+10 | 0.832669E+09 | 242.39 | 0.234947E+10 | 0.112601E+10 | 0.00 | 1.00 | 02-OCT-20:10 | 0.00 | 01-OCT-00:05 | 23651.39 | 06-OCT-07:02 | 21125.73 | 25-OCT-20:07 | 12801.36 | 23-OCT-20:25 | 4985.64 | 06-OCT-07:02 | 0.00 | 01-OCT-00:05 |
November | 22464828.26 | 6036069.99 | 20.85 | 18389958.06 | 4074870.21 | 0.00 | 0.22 | 10-NOV-00:10 | 0.00 | 01-NOV-00:10 | 10669.49 | 03-NOV-20:15 | 8350.85 | 03-NOV-20:15 | 2318.64 | 03-NOV-20:15 | 2267.39 | 03-NOV-20:15 | 0.00 | 01-NOV-00:10 |
December | 31236.97 | 9493.58 | 0.50 | 31236.97 | 0.00 | 0.00 | 0.00 | 17-DEC-23:10 | 0.00 | 01-DEC-00:05 | 22.83 | 17-DEC-23:10 | 22.83 | 17-DEC-23:10 | 0.00 | 02-DEC-23:10 | 6.94 | 17-DEC-23:10 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.610710E+11 | 0.146897E+11 | 2440.83 | 0.427797E+11 | 0.182913E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.173806E+11 | 0.411925E+10 | 499.43 | 0.116394E+11 | 0.609378E+10 | 0.00 | 1.00 | 0.00 | 24513.47 | 21128.85 | 12801.36 | 5386.90 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 5629136.24 | 1565399.24 | 5.33 | 4047831.00 | 1581305.24 | 0.00 | 0.16 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 1444.87 | 27-MAR-16:10 | 1036.80 | 27-MAR-16:10 | 408.07 | 27-MAR-16:10 | 398.64 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.408378E+09 | 0.107255E+09 | 58.67 | 0.346642E+09 | 61735568.15 | 0.00 | 0.62 | 08-APR-12:10 | 0.00 | 01-APR-00:05 | 6300.84 | 08-APR-12:10 | 5477.13 | 07-APR-13:00 | 1548.23 | 09-APR-11:00 | 1584.80 | 07-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.185455E+10 | 0.476667E+09 | 204.49 | 0.158206E+10 | 0.272494E+09 | 0.00 | 0.95 | 23-MAY-06:03 | 0.00 | 01-MAY-00:10 | 20941.68 | 31-MAY-06:03 | 15114.32 | 30-MAY-06:03 | 7951.30 | 31-MAY-06:03 | 4451.49 | 31-MAY-06:03 | 0.00 | 01-MAY-00:10 |
June | 0.860330E+10 | 0.208099E+10 | 343.01 | 0.582900E+10 | 0.277431E+10 | 0.00 | 1.00 | 08-JUN-06:03 | 0.00 | 01-JUN-00:10 | 26045.27 | 25-JUN-07:02 | 20654.04 | 23-JUN-06:02 | 14019.68 | 16-JUN-06:02 | 5464.89 | 19-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.137701E+11 | 0.323069E+10 | 364.32 | 0.867644E+10 | 0.509362E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:05 | 26112.15 | 22-JUL-06:01 | 19319.61 | 12-JUL-06:02 | 14527.58 | 24-JUL-06:03 | 5545.21 | 09-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.129999E+11 | 0.311996E+10 | 373.31 | 0.907147E+10 | 0.392845E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 26311.39 | 06-AUG-07:01 | 21582.23 | 31-AUG-06:02 | 13536.03 | 06-AUG-07:04 | 5537.82 | 05-AUG-06:01 | 0.00 | 01-AUG-00:10 |
September | 0.650808E+10 | 0.157245E+10 | 309.48 | 0.468794E+10 | 0.182014E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 25645.74 | 14-SEP-06:02 | 19937.38 | 04-SEP-07:02 | 11633.75 | 06-SEP-06:03 | 5422.84 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.239162E+10 | 0.584946E+09 | 201.52 | 0.162310E+10 | 0.768520E+09 | 0.00 | 1.00 | 06-OCT-06:02 | 0.00 | 01-OCT-00:05 | 24408.91 | 06-OCT-06:02 | 12688.20 | 06-OCT-06:02 | 11892.08 | 25-OCT-06:03 | 5139.47 | 06-OCT-06:02 | 0.00 | 01-OCT-00:05 |
November | 5545257.86 | 1534022.89 | 13.03 | 4391232.89 | 1154024.98 | 0.00 | 0.13 | 04-NOV-12:50 | 0.00 | 01-NOV-00:10 | 1074.52 | 04-NOV-12:50 | 841.72 | 04-NOV-12:50 | 235.43 | 04-NOV-13:00 | 295.13 | 04-NOV-12:50 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.465471E+11 | 0.111761E+11 | 1873.17 | 0.318251E+11 | 0.147220E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.137701E+11 | 0.323069E+10 | 373.31 | 0.907147E+10 | 0.509362E+10 | 0.00 | 1.00 | 0.00 | 26311.39 | 21582.23 | 14527.58 | 5545.21 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 3390313.26 | 950317.12 | 4.33 | 2436627.77 | 953685.49 | 0.00 | 0.12 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 1085.96 | 27-MAR-16:10 | 778.22 | 27-MAR-16:10 | 307.74 | 27-MAR-16:10 | 302.50 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.379774E+09 | 0.100092E+09 | 52.42 | 0.322172E+09 | 57601792.19 | 0.00 | 0.61 | 08-APR-12:10 | 0.00 | 01-APR-00:05 | 6123.36 | 08-APR-12:10 | 5239.62 | 07-APR-13:00 | 1518.79 | 09-APR-11:00 | 1543.76 | 08-APR-12:10 | 0.00 | 01-APR-00:05 |
May | 0.180492E+10 | 0.463971E+09 | 197.25 | 0.154054E+10 | 0.264384E+09 | 0.00 | 0.90 | 31-MAY-14:00 | 0.00 | 01-MAY-00:10 | 20676.71 | 31-MAY-06:03 | 14746.33 | 30-MAY-06:03 | 7854.79 | 31-MAY-06:03 | 4395.21 | 31-MAY-06:03 | 0.00 | 01-MAY-00:10 |
June | 0.856676E+10 | 0.207047E+10 | 342.94 | 0.580152E+10 | 0.276524E+10 | 0.00 | 1.00 | 08-JUN-06:03 | 0.00 | 01-JUN-00:10 | 25829.19 | 25-JUN-07:02 | 20489.02 | 23-JUN-06:02 | 13907.23 | 16-JUN-06:02 | 5419.51 | 19-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.137654E+11 | 0.322578E+10 | 364.48 | 0.867284E+10 | 0.509260E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:05 | 25898.49 | 22-JUL-06:01 | 19176.72 | 12-JUL-06:02 | 14405.13 | 24-JUL-06:03 | 5499.12 | 09-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.130092E+11 | 0.311870E+10 | 373.28 | 0.907942E+10 | 0.392975E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 26098.15 | 06-AUG-07:01 | 21414.13 | 31-AUG-06:02 | 13397.86 | 06-AUG-07:04 | 5491.97 | 05-AUG-06:01 | 0.00 | 01-AUG-00:10 |
September | 0.648754E+10 | 0.156580E+10 | 309.46 | 0.467275E+10 | 0.181479E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 25434.36 | 14-SEP-06:02 | 19796.43 | 04-SEP-07:02 | 11530.41 | 06-SEP-06:03 | 5377.94 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.233823E+10 | 0.572011E+09 | 198.07 | 0.158565E+10 | 0.752583E+09 | 0.00 | 1.00 | 06-OCT-06:02 | 0.00 | 01-OCT-00:05 | 24205.79 | 06-OCT-06:02 | 12579.75 | 06-OCT-06:02 | 11801.88 | 25-OCT-06:03 | 5096.73 | 06-OCT-06:02 | 0.00 | 01-OCT-00:05 |
November | 3802627.88 | 1055356.71 | 11.39 | 2995252.13 | 807375.75 | 0.00 | 0.10 | 04-NOV-12:50 | 0.00 | 01-NOV-00:10 | 877.41 | 04-NOV-12:50 | 687.04 | 04-NOV-12:50 | 192.72 | 04-NOV-13:00 | 242.34 | 04-NOV-12:50 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.463590E+11 | 0.111188E+11 | 1853.63 | 0.316803E+11 | 0.146787E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.137654E+11 | 0.322578E+10 | 373.28 | 0.907942E+10 | 0.509260E+10 | 0.00 | 1.00 | 0.00 | 26098.15 | 21414.13 | 14405.13 | 5499.12 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 1329026.60 | 375894.30 | 3.17 | 952494.27 | 376532.33 | 0.00 | 0.08 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 673.68 | 27-MAR-16:10 | 481.75 | 27-MAR-16:10 | 191.94 | 27-MAR-16:10 | 189.84 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.330584E+09 | 87892461.45 | 46.50 | 0.280718E+09 | 49866711.17 | 0.00 | 0.58 | 08-APR-12:10 | 0.00 | 01-APR-00:05 | 5758.39 | 08-APR-12:10 | 4868.73 | 07-APR-13:00 | 1410.42 | 09-APR-11:00 | 1465.45 | 08-APR-12:10 | 0.00 | 01-APR-00:05 |
May | 0.166233E+10 | 0.429081E+09 | 181.45 | 0.141865E+10 | 0.243680E+09 | 0.00 | 0.88 | 31-MAY-14:00 | 0.00 | 01-MAY-00:10 | 18152.98 | 31-MAY-06:03 | 12795.43 | 30-MAY-06:03 | 6979.04 | 31-MAY-06:03 | 3859.81 | 31-MAY-06:03 | 0.00 | 01-MAY-00:10 |
June | 0.828614E+10 | 0.201085E+10 | 343.24 | 0.559127E+10 | 0.269487E+10 | 0.00 | 1.00 | 15-JUN-06:02 | 0.00 | 01-JUN-00:10 | 25870.42 | 25-JUN-07:02 | 20401.21 | 23-JUN-06:02 | 13982.30 | 16-JUN-06:02 | 5431.07 | 19-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.134930E+11 | 0.317059E+10 | 364.15 | 0.846588E+10 | 0.502709E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:05 | 25936.38 | 22-JUL-06:01 | 19086.80 | 12-JUL-06:02 | 14469.27 | 24-JUL-06:03 | 5511.16 | 09-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.127497E+11 | 0.306340E+10 | 372.85 | 0.886650E+10 | 0.388316E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 26141.69 | 06-AUG-07:01 | 21339.89 | 31-AUG-06:02 | 13543.44 | 06-AUG-07:04 | 5503.60 | 05-AUG-06:01 | 0.00 | 01-AUG-00:10 |
September | 0.626492E+10 | 0.151760E+10 | 306.22 | 0.450004E+10 | 0.176488E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 25480.00 | 14-SEP-06:02 | 19726.31 | 04-SEP-07:02 | 11592.50 | 06-SEP-06:03 | 5388.94 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.215395E+10 | 0.529214E+09 | 187.85 | 0.145710E+10 | 0.696843E+09 | 0.00 | 1.00 | 06-OCT-06:02 | 0.00 | 01-OCT-00:05 | 24254.06 | 06-OCT-06:02 | 12567.03 | 06-OCT-06:02 | 11687.03 | 06-OCT-06:02 | 5107.23 | 06-OCT-06:02 | 0.00 | 01-OCT-00:05 |
November | 1044638.62 | 293443.17 | 5.17 | 821014.33 | 223624.29 | 0.00 | 0.04 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 | 362.00 | 04-NOV-13:00 | 281.79 | 04-NOV-13:00 | 80.21 | 04-NOV-13:00 | 101.56 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.449429E+11 | 0.108093E+11 | 1810.60 | 0.305819E+11 | 0.143610E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.134930E+11 | 0.317059E+10 | 372.85 | 0.886650E+10 | 0.502709E+10 | 0.00 | 1.00 | 0.00 | 26141.69 | 21339.89 | 14469.27 | 5511.16 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 115019.97 | 32922.59 | 1.33 | 80616.57 | 34403.40 | 0.00 | 0.01 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 189.77 | 27-MAR-16:10 | 133.00 | 27-MAR-16:10 | 56.77 | 27-MAR-16:10 | 54.32 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.443704E+09 | 0.119586E+09 | 35.67 | 0.372539E+09 | 71165404.75 | 0.00 | 0.52 | 08-APR-12:00 | 0.00 | 01-APR-00:05 | 8766.56 | 08-APR-12:00 | 7597.34 | 07-APR-13:00 | 1752.22 | 08-APR-13:10 | 2310.70 | 07-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.248643E+10 | 0.641818E+09 | 141.19 | 0.207568E+10 | 0.410749E+09 | 0.00 | 0.90 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 | 35048.55 | 31-MAY-07:03 | 28440.69 | 31-MAY-07:03 | 7752.14 | 30-MAY-07:03 | 7570.52 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.136563E+11 | 0.330942E+10 | 335.43 | 0.895260E+10 | 0.470374E+10 | 0.00 | 1.00 | 08-JUN-07:02 | 0.00 | 01-JUN-00:10 | 44304.32 | 25-JUN-08:62 | 34200.22 | 23-JUN-07:02 | 23001.42 | 25-JUN-08:04 | 9502.26 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.230832E+11 | 0.539139E+10 | 352.03 | 0.140249E+11 | 0.905822E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 44281.37 | 09-JUL-08:62 | 32463.12 | 12-JUL-07:02 | 25298.55 | 24-JUL-07:04 | 9483.01 | 09-JUL-08:05 | 0.00 | 01-JUL-00:05 |
August | 0.221171E+11 | 0.529301E+10 | 363.46 | 0.149866E+11 | 0.713048E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 43866.17 | 06-AUG-08:62 | 36670.98 | 26-AUG-07:02 | 25790.52 | 06-AUG-08:62 | 9428.95 | 04-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.103037E+11 | 0.249289E+10 | 295.70 | 0.718951E+10 | 0.311417E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 43077.01 | 14-SEP-07:02 | 32627.68 | 04-SEP-08:62 | 18526.04 | 14-SEP-07:03 | 9202.61 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.323589E+10 | 0.797195E+09 | 158.19 | 0.212486E+10 | 0.111103E+10 | 0.00 | 1.00 | 06-OCT-07:02 | 0.00 | 01-OCT-00:05 | 41499.39 | 06-OCT-07:02 | 21731.63 | 06-OCT-07:02 | 19767.76 | 06-OCT-07:02 | 8735.87 | 06-OCT-07:02 | 0.00 | 01-OCT-00:05 |
November | 9722.77 | 2759.89 | 2.17 | 7987.79 | 1734.98 | 0.00 | 0.00 | 04-NOV-16:00 | 0.00 | 01-NOV-00:10 | 2.29 | 04-NOV-16:00 | 1.91 | 04-NOV-16:00 | 0.41 | 04-NOV-15:50 | 0.65 | 04-NOV-16:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.753264E+11 | 0.180453E+11 | 1685.17 | 0.497268E+11 | 0.255996E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.230832E+11 | 0.539139E+10 | 363.46 | 0.149866E+11 | 0.905822E+10 | 0.00 | 1.00 | 0.00 | 44304.32 | 36670.98 | 25790.52 | 9502.26 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 523.26 | 149.73 | 0.83 | 369.12 | 154.14 | 0.00 | 0.00 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 0.48 | 27-MAR-16:10 | 0.34 | 27-MAR-16:10 | 0.14 | 27-MAR-16:10 | 0.14 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.209254E+09 | 56766024.52 | 33.83 | 0.176388E+09 | 32865944.17 | 0.00 | 0.49 | 08-APR-12:00 | 0.00 | 01-APR-00:05 | 4392.66 | 08-APR-12:00 | 3784.64 | 07-APR-13:00 | 858.95 | 08-APR-13:00 | 1159.65 | 07-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.121942E+10 | 0.316407E+09 | 136.18 | 0.101957E+10 | 0.199850E+09 | 0.00 | 0.87 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 | 16047.53 | 30-MAY-07:03 | 12874.64 | 31-MAY-07:03 | 3614.47 | 30-MAY-07:03 | 3510.18 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.692037E+10 | 0.168877E+10 | 333.24 | 0.455420E+10 | 0.236617E+10 | 0.00 | 1.00 | 15-JUN-07:02 | 0.00 | 01-JUN-00:10 | 23641.91 | 25-JUN-08:62 | 18250.61 | 23-JUN-07:02 | 12334.32 | 25-JUN-08:62 | 5069.84 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.117933E+11 | 0.277267E+10 | 351.95 | 0.719372E+10 | 0.459956E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 23637.85 | 09-JUL-08:62 | 17316.06 | 12-JUL-07:02 | 13493.51 | 24-JUL-07:02 | 5059.59 | 09-JUL-08:05 | 0.00 | 01-JUL-00:05 |
August | 0.113010E+11 | 0.271989E+10 | 363.84 | 0.768101E+10 | 0.362001E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 23408.54 | 06-AUG-08:62 | 19047.13 | 31-AUG-07:02 | 13765.05 | 06-AUG-08:62 | 5030.77 | 04-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.521072E+10 | 0.126862E+10 | 293.16 | 0.364867E+10 | 0.156205E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 22978.67 | 14-SEP-07:02 | 17381.65 | 04-SEP-08:62 | 9904.95 | 14-SEP-07:03 | 4909.66 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.157483E+10 | 0.389994E+09 | 151.50 | 0.103839E+10 | 0.536433E+09 | 0.00 | 1.00 | 06-OCT-07:02 | 0.00 | 01-OCT-00:05 | 22142.03 | 06-OCT-07:02 | 11609.76 | 06-OCT-07:02 | 10532.27 | 06-OCT-07:02 | 4661.00 | 06-OCT-07:02 | 0.00 | 01-OCT-00:05 |
November | 3199.66 | 909.04 | 1.33 | 2591.85 | 607.81 | 0.00 | 0.00 | 04-NOV-16:00 | 0.00 | 01-NOV-00:10 | 1.00 | 04-NOV-16:00 | 0.83 | 04-NOV-16:00 | 0.17 | 04-NOV-15:50 | 0.28 | 04-NOV-16:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.382289E+11 | 0.921312E+10 | 1665.88 | 0.253120E+11 | 0.129169E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.117933E+11 | 0.277267E+10 | 363.84 | 0.768101E+10 | 0.459956E+10 | 0.00 | 1.00 | 0.00 | 23641.91 | 19047.13 | 13765.05 | 5069.84 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 295.20 | 84.40 | 0.33 | 208.09 | 87.11 | 0.00 | 0.00 | 27-MAR-16:20 | 0.00 | 01-MAR-00:10 | 0.38 | 27-MAR-16:20 | 0.27 | 27-MAR-16:20 | 0.11 | 27-MAR-16:20 | 0.11 | 27-MAR-16:20 | 0.00 | 01-MAR-00:10 |
April | 0.195339E+09 | 53146738.69 | 31.50 | 0.164569E+09 | 30770002.29 | 0.00 | 0.48 | 08-APR-12:00 | 0.00 | 01-APR-00:05 | 4267.89 | 08-APR-12:00 | 3661.18 | 07-APR-13:00 | 836.24 | 08-APR-13:00 | 1126.98 | 07-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.116608E+10 | 0.302907E+09 | 130.49 | 0.972447E+09 | 0.193633E+09 | 0.00 | 0.92 | 29-MAY-08:63 | 0.00 | 01-MAY-00:10 | 14851.00 | 31-MAY-07:03 | 11908.69 | 31-MAY-07:03 | 3343.97 | 30-MAY-07:03 | 3208.09 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.680417E+10 | 0.166174E+10 | 332.07 | 0.446730E+10 | 0.233687E+10 | 0.00 | 1.00 | 15-JUN-07:02 | 0.00 | 01-JUN-00:10 | 23513.62 | 25-JUN-08:62 | 18108.19 | 23-JUN-07:02 | 12315.85 | 25-JUN-08:62 | 5043.28 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.116797E+11 | 0.274684E+10 | 351.72 | 0.710666E+10 | 0.457307E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 23511.09 | 09-JUL-08:62 | 17177.99 | 12-JUL-07:02 | 13436.91 | 24-JUL-07:02 | 5033.08 | 09-JUL-08:05 | 0.00 | 01-JUL-00:05 |
August | 0.111991E+11 | 0.269585E+10 | 363.60 | 0.759570E+10 | 0.360340E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 23285.02 | 06-AUG-08:62 | 18904.42 | 31-AUG-07:02 | 13705.45 | 06-AUG-08:62 | 5004.42 | 04-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.513489E+10 | 0.125093E+10 | 291.64 | 0.358824E+10 | 0.154665E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 22858.93 | 14-SEP-07:02 | 17246.28 | 04-SEP-08:62 | 9904.74 | 14-SEP-07:03 | 4883.86 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.151576E+10 | 0.375822E+09 | 146.20 | 0.997571E+09 | 0.518191E+09 | 0.00 | 1.00 | 06-OCT-07:02 | 0.00 | 01-OCT-00:05 | 22025.31 | 06-OCT-07:02 | 11532.34 | 06-OCT-07:02 | 10492.97 | 06-OCT-07:02 | 4636.48 | 06-OCT-07:02 | 0.00 | 01-OCT-00:05 |
November | 1001.71 | 284.59 | 0.33 | 823.44 | 178.26 | 0.00 | 0.00 | 04-NOV-16:00 | 0.00 | 01-NOV-00:10 | 0.87 | 04-NOV-16:00 | 0.72 | 04-NOV-16:00 | 0.15 | 04-NOV-15:50 | 0.25 | 04-NOV-16:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.376951E+11 | 0.908723E+10 | 1647.90 | 0.248925E+11 | 0.128026E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.116797E+11 | 0.274684E+10 | 363.60 | 0.759570E+10 | 0.457307E+10 | 0.00 | 1.00 | 0.00 | 23513.62 | 18904.42 | 13705.45 | 5043.28 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.166475E+09 | 45577890.28 | 29.00 | 0.140088E+09 | 26386376.47 | 0.00 | 0.46 | 08-APR-12:00 | 0.00 | 01-APR-00:05 | 3994.59 | 08-APR-12:00 | 3410.76 | 07-APR-13:00 | 786.59 | 08-APR-13:00 | 1059.03 | 07-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.105261E+10 | 0.274348E+09 | 117.14 | 0.873284E+09 | 0.179329E+09 | 0.00 | 0.97 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 | 10921.93 | 31-MAY-07:03 | 8602.88 | 31-MAY-07:03 | 2847.13 | 31-MAY-13:00 | 2331.50 | 31-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.653952E+10 | 0.160103E+10 | 329.76 | 0.427955E+10 | 0.225997E+10 | 0.00 | 1.00 | 15-JUN-07:02 | 0.00 | 01-JUN-00:10 | 23342.47 | 25-JUN-08:62 | 17876.41 | 23-JUN-07:02 | 12361.94 | 25-JUN-08:62 | 5010.45 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.114841E+11 | 0.270344E+10 | 352.39 | 0.696459E+10 | 0.451949E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 23343.62 | 09-JUL-08:62 | 16948.03 | 12-JUL-07:02 | 13387.28 | 24-JUL-07:02 | 5000.33 | 09-JUL-08:05 | 0.00 | 01-JUL-00:05 |
August | 0.110517E+11 | 0.266142E+10 | 363.54 | 0.747800E+10 | 0.357370E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 23130.05 | 06-AUG-08:62 | 18689.64 | 31-AUG-07:02 | 13639.81 | 06-AUG-08:62 | 4971.70 | 04-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.499870E+10 | 0.121905E+10 | 287.10 | 0.348458E+10 | 0.151412E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 22706.11 | 14-SEP-07:02 | 17046.77 | 04-SEP-08:62 | 9879.90 | 14-SEP-07:02 | 4851.40 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.140471E+10 | 0.349140E+09 | 138.96 | 0.922123E+09 | 0.482590E+09 | 0.00 | 1.00 | 06-OCT-07:02 | 0.00 | 01-OCT-00:05 | 21884.77 | 06-OCT-07:02 | 11404.85 | 06-OCT-07:02 | 10479.92 | 06-OCT-07:02 | 4606.68 | 06-OCT-07:02 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.366978E+11 | 0.885401E+10 | 1617.88 | 0.241422E+11 | 0.125556E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.114841E+11 | 0.270344E+10 | 363.54 | 0.747800E+10 | 0.451949E+10 | 0.00 | 1.00 | 0.00 | 23343.62 | 18689.64 | 13639.81 | 5010.45 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.132516E+09 | 36572306.30 | 25.33 | 0.111666E+09 | 20850010.63 | 0.00 | 0.43 | 08-APR-12:00 | 0.00 | 01-APR-00:05 | 3831.08 | 08-APR-12:00 | 3266.31 | 07-APR-13:00 | 739.34 | 08-APR-12:10 | 1019.72 | 08-APR-12:00 | 0.00 | 01-APR-00:05 |
May | 0.905929E+09 | 0.237461E+09 | 98.19 | 0.748377E+09 | 0.157552E+09 | 0.00 | 0.82 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 | 8580.05 | 31-MAY-14:10 | 7229.67 | 30-MAY-13:00 | 2793.36 | 31-MAY-13:00 | 2100.00 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.605531E+10 | 0.149377E+10 | 314.05 | 0.396224E+10 | 0.209307E+10 | 0.00 | 1.00 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 | 24113.01 | 25-JUN-08:62 | 14589.83 | 26-JUN-07:02 | 13528.61 | 25-JUN-08:62 | 5149.71 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.115684E+11 | 0.273089E+10 | 354.14 | 0.700630E+10 | 0.456210E+10 | 0.00 | 1.00 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 | 24394.19 | 22-JUL-07:01 | 16252.92 | 11-JUL-07:02 | 14197.54 | 22-JUL-07:01 | 5135.83 | 09-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.113885E+11 | 0.274255E+10 | 363.85 | 0.771847E+10 | 0.367007E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24099.30 | 17-AUG-07:01 | 16252.41 | 22-AUG-07:01 | 14231.02 | 06-AUG-08:62 | 5112.20 | 05-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.498258E+10 | 0.121460E+10 | 272.65 | 0.348676E+10 | 0.149582E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 23733.45 | 14-SEP-07:02 | 16824.31 | 04-SEP-08:62 | 12625.18 | 22-SEP-07:02 | 5007.49 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.132657E+10 | 0.329495E+09 | 128.61 | 0.877514E+09 | 0.449055E+09 | 0.00 | 0.82 | 04-OCT-13:00 | 0.00 | 01-OCT-00:05 | 8580.05 | 06-OCT-07:02 | 6105.94 | 04-OCT-13:00 | 4279.16 | 06-OCT-07:02 | 1996.32 | 04-OCT-13:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.363598E+11 | 0.878534E+10 | 1556.83 | 0.239113E+11 | 0.124485E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.115684E+11 | 0.274255E+10 | 363.85 | 0.771847E+10 | 0.456210E+10 | 0.00 | 1.00 | 0.00 | 24394.19 | 16824.31 | 14231.02 | 5149.71 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.61 | 63.26 | 33.35 | 87.68 | 94.15 | 0.00 | 0.00 | 744.00 |
February | 127.47 | 84.39 | 43.08 | 114.74 | 93.59 | 0.00 | 0.00 | 672.00 |
March | 114.99 | 63.84 | 51.15 | 100.17 | 67.75 | 0.00 | 0.00 | 744.00 |
April | 89.19 | 35.26 | 53.93 | 67.36 | 50.47 | 0.00 | 0.00 | 720.00 |
May | 78.16 | 16.29 | 61.87 | 59.53 | 33.69 | 0.00 | 0.00 | 744.00 |
June | 73.34 | 11.20 | 62.15 | 68.83 | 17.81 | 0.00 | 0.00 | 720.00 |
July | 76.88 | 13.34 | 63.54 | 82.86 | 9.02 | 0.00 | 0.00 | 744.00 |
August | 102.67 | 38.07 | 64.60 | 107.78 | 13.19 | 0.00 | 0.00 | 744.00 |
September | 111.43 | 57.65 | 53.79 | 116.21 | 27.34 | 0.00 | 0.00 | 720.00 |
October | 152.71 | 95.78 | 56.92 | 162.84 | 49.45 | 0.00 | 0.00 | 744.00 |
November | 105.85 | 63.57 | 42.28 | 102.30 | 69.47 | 0.00 | 0.00 | 720.00 |
December | 104.69 | 74.32 | 30.37 | 101.57 | 85.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.72 | 51.25 | 51.47 | 97.61 | 50.72 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.34 | 11.20 | 30.37 | 59.53 | 9.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.71 | 95.78 | 64.60 | 162.84 | 94.15 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.61 | 63.26 | 33.35 | 87.68 | 94.15 | 0.00 | 0.00 | 744.00 |
February | 127.47 | 84.39 | 43.08 | 114.74 | 93.59 | 0.00 | 0.00 | 672.00 |
March | 114.99 | 63.84 | 51.15 | 100.17 | 67.75 | 0.00 | 0.00 | 744.00 |
April | 89.19 | 35.26 | 53.93 | 67.36 | 50.47 | 0.00 | 0.00 | 720.00 |
May | 78.16 | 16.29 | 61.87 | 59.53 | 33.69 | 0.00 | 0.00 | 744.00 |
June | 73.34 | 11.20 | 62.15 | 68.83 | 17.81 | 0.00 | 0.00 | 720.00 |
July | 76.88 | 13.34 | 63.54 | 82.86 | 9.02 | 0.00 | 0.00 | 744.00 |
August | 102.67 | 38.07 | 64.60 | 107.78 | 13.19 | 0.00 | 0.00 | 744.00 |
September | 111.43 | 57.65 | 53.79 | 116.21 | 27.34 | 0.00 | 0.00 | 720.00 |
October | 152.71 | 95.78 | 56.92 | 162.84 | 49.45 | 0.00 | 0.00 | 744.00 |
November | 105.85 | 63.57 | 42.28 | 102.30 | 69.47 | 0.00 | 0.00 | 720.00 |
December | 104.69 | 74.32 | 30.37 | 101.57 | 85.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.72 | 51.25 | 51.47 | 97.61 | 50.72 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.34 | 11.20 | 30.37 | 59.53 | 9.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.71 | 95.78 | 64.60 | 162.84 | 94.15 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.61 | 63.26 | 33.35 | 87.68 | 94.15 | 0.00 | 0.00 | 744.00 |
February | 127.47 | 84.39 | 43.08 | 114.74 | 93.59 | 0.00 | 0.00 | 672.00 |
March | 114.99 | 63.84 | 51.15 | 100.17 | 67.75 | 0.00 | 0.00 | 744.00 |
April | 89.19 | 35.26 | 53.93 | 67.36 | 50.47 | 0.00 | 0.00 | 720.00 |
May | 78.16 | 16.29 | 61.87 | 59.53 | 33.69 | 0.00 | 0.00 | 744.00 |
June | 73.34 | 11.20 | 62.15 | 68.83 | 17.81 | 0.00 | 0.00 | 720.00 |
July | 76.88 | 13.34 | 63.54 | 82.86 | 9.02 | 0.00 | 0.00 | 744.00 |
August | 102.67 | 38.07 | 64.60 | 107.78 | 13.19 | 0.00 | 0.00 | 744.00 |
September | 111.43 | 57.65 | 53.79 | 116.21 | 27.34 | 0.00 | 0.00 | 720.00 |
October | 152.71 | 95.78 | 56.92 | 162.84 | 49.45 | 0.00 | 0.00 | 744.00 |
November | 105.85 | 63.57 | 42.28 | 102.30 | 69.47 | 0.00 | 0.00 | 720.00 |
December | 104.69 | 74.32 | 30.37 | 101.57 | 85.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.72 | 51.25 | 51.47 | 97.61 | 50.72 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.34 | 11.20 | 30.37 | 59.53 | 9.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.71 | 95.78 | 64.60 | 162.84 | 94.15 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.61 | 63.26 | 33.35 | 87.68 | 94.15 | 0.00 | 0.00 | 744.00 |
February | 127.47 | 84.39 | 43.08 | 114.74 | 93.59 | 0.00 | 0.00 | 672.00 |
March | 114.99 | 63.84 | 51.15 | 100.17 | 67.75 | 0.00 | 0.00 | 744.00 |
April | 89.19 | 35.26 | 53.93 | 67.36 | 50.47 | 0.00 | 0.00 | 720.00 |
May | 78.16 | 16.29 | 61.87 | 59.53 | 33.69 | 0.00 | 0.00 | 744.00 |
June | 73.34 | 11.20 | 62.15 | 68.83 | 17.81 | 0.00 | 0.00 | 720.00 |
July | 76.88 | 13.34 | 63.54 | 82.86 | 9.02 | 0.00 | 0.00 | 744.00 |
August | 102.67 | 38.07 | 64.60 | 107.78 | 13.19 | 0.00 | 0.00 | 744.00 |
September | 111.43 | 57.65 | 53.79 | 116.21 | 27.34 | 0.00 | 0.00 | 720.00 |
October | 152.71 | 95.78 | 56.92 | 162.84 | 49.45 | 0.00 | 0.00 | 744.00 |
November | 105.85 | 63.57 | 42.28 | 102.30 | 69.47 | 0.00 | 0.00 | 720.00 |
December | 104.69 | 74.32 | 30.37 | 101.57 | 85.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.72 | 51.25 | 51.47 | 97.61 | 50.72 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.34 | 11.20 | 30.37 | 59.53 | 9.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.71 | 95.78 | 64.60 | 162.84 | 94.15 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.31 | 76.16 | 40.15 | 105.75 | 112.28 | 0.00 | 0.00 | 744.00 |
February | 153.47 | 101.61 | 51.86 | 138.36 | 111.60 | 0.00 | 0.00 | 672.00 |
March | 138.45 | 76.86 | 61.58 | 120.76 | 80.81 | 0.00 | 0.00 | 744.00 |
April | 107.38 | 42.45 | 64.93 | 81.23 | 60.25 | 0.00 | 0.00 | 720.00 |
May | 94.10 | 19.62 | 74.48 | 71.74 | 40.27 | 0.00 | 0.00 | 744.00 |
June | 88.30 | 13.48 | 74.82 | 82.77 | 21.35 | 0.00 | 0.00 | 720.00 |
July | 92.56 | 16.07 | 76.50 | 99.54 | 10.85 | 0.00 | 0.00 | 744.00 |
August | 123.61 | 45.84 | 77.77 | 129.51 | 15.85 | 0.00 | 0.00 | 744.00 |
September | 134.16 | 69.40 | 64.76 | 139.81 | 32.76 | 0.00 | 0.00 | 720.00 |
October | 183.85 | 115.32 | 68.53 | 196.02 | 59.15 | 0.00 | 0.00 | 744.00 |
November | 127.44 | 76.54 | 50.90 | 123.27 | 82.96 | 0.00 | 0.00 | 720.00 |
December | 126.04 | 89.48 | 36.57 | 122.41 | 102.17 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.67 | 61.70 | 61.97 | 117.55 | 60.57 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 88.30 | 13.48 | 36.57 | 71.74 | 10.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 183.85 | 115.32 | 77.77 | 196.02 | 112.28 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.31 | 76.16 | 40.15 | 105.75 | 112.28 | 0.00 | 0.00 | 744.00 |
February | 153.47 | 101.61 | 51.86 | 138.36 | 111.60 | 0.00 | 0.00 | 672.00 |
March | 138.45 | 76.86 | 61.58 | 120.76 | 80.81 | 0.00 | 0.00 | 744.00 |
April | 107.38 | 42.45 | 64.93 | 81.23 | 60.25 | 0.00 | 0.00 | 720.00 |
May | 94.10 | 19.62 | 74.48 | 71.74 | 40.27 | 0.00 | 0.00 | 744.00 |
June | 88.30 | 13.48 | 74.82 | 82.77 | 21.35 | 0.00 | 0.00 | 720.00 |
July | 92.56 | 16.07 | 76.50 | 99.54 | 10.85 | 0.00 | 0.00 | 744.00 |
August | 123.61 | 45.84 | 77.77 | 129.51 | 15.85 | 0.00 | 0.00 | 744.00 |
September | 134.16 | 69.40 | 64.76 | 139.81 | 32.76 | 0.00 | 0.00 | 720.00 |
October | 183.85 | 115.32 | 68.53 | 196.02 | 59.15 | 0.00 | 0.00 | 744.00 |
November | 127.44 | 76.54 | 50.90 | 123.27 | 82.96 | 0.00 | 0.00 | 720.00 |
December | 126.04 | 89.48 | 36.57 | 122.41 | 102.17 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.67 | 61.70 | 61.97 | 117.55 | 60.57 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 88.30 | 13.48 | 36.57 | 71.74 | 10.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 183.85 | 115.32 | 77.77 | 196.02 | 112.28 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.61 | 63.26 | 33.35 | 86.81 | 98.73 | 0.00 | 0.00 | 744.00 |
February | 127.47 | 84.39 | 43.08 | 113.62 | 98.33 | 0.00 | 0.00 | 672.00 |
March | 114.99 | 63.84 | 51.15 | 99.02 | 72.53 | 0.00 | 0.00 | 744.00 |
April | 89.19 | 35.26 | 53.93 | 66.12 | 54.36 | 0.00 | 0.00 | 720.00 |
May | 78.16 | 16.29 | 61.87 | 58.58 | 35.21 | 0.00 | 0.00 | 744.00 |
June | 73.34 | 11.20 | 62.15 | 68.59 | 18.27 | 0.00 | 0.00 | 720.00 |
July | 76.88 | 13.34 | 63.54 | 82.86 | 9.26 | 0.00 | 0.00 | 744.00 |
August | 102.67 | 38.07 | 64.60 | 107.90 | 13.34 | 0.00 | 0.00 | 744.00 |
September | 111.43 | 57.65 | 53.79 | 116.07 | 27.70 | 0.00 | 0.00 | 720.00 |
October | 152.71 | 95.78 | 56.92 | 162.11 | 50.76 | 0.00 | 0.00 | 744.00 |
November | 105.85 | 63.57 | 42.28 | 101.09 | 73.44 | 0.00 | 0.00 | 720.00 |
December | 104.69 | 74.32 | 30.37 | 100.64 | 90.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.72 | 51.25 | 51.47 | 96.91 | 53.25 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.34 | 11.20 | 30.37 | 58.58 | 9.26 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.71 | 95.78 | 64.60 | 162.11 | 98.73 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.61 | 63.26 | 33.35 | 86.81 | 98.73 | 0.00 | 0.00 | 744.00 |
February | 127.47 | 84.39 | 43.08 | 113.62 | 98.33 | 0.00 | 0.00 | 672.00 |
March | 114.99 | 63.84 | 51.15 | 99.02 | 72.53 | 0.00 | 0.00 | 744.00 |
April | 89.19 | 35.26 | 53.93 | 66.12 | 54.36 | 0.00 | 0.00 | 720.00 |
May | 78.16 | 16.29 | 61.87 | 58.58 | 35.21 | 0.00 | 0.00 | 744.00 |
June | 73.34 | 11.20 | 62.15 | 68.59 | 18.27 | 0.00 | 0.00 | 720.00 |
July | 76.88 | 13.34 | 63.54 | 82.86 | 9.26 | 0.00 | 0.00 | 744.00 |
August | 102.67 | 38.07 | 64.60 | 107.90 | 13.34 | 0.00 | 0.00 | 744.00 |
September | 111.43 | 57.65 | 53.79 | 116.07 | 27.70 | 0.00 | 0.00 | 720.00 |
October | 152.71 | 95.78 | 56.92 | 162.11 | 50.76 | 0.00 | 0.00 | 744.00 |
November | 105.85 | 63.57 | 42.28 | 101.09 | 73.44 | 0.00 | 0.00 | 720.00 |
December | 104.69 | 74.32 | 30.37 | 100.64 | 90.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.72 | 51.25 | 51.47 | 96.91 | 53.25 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.34 | 11.20 | 30.37 | 58.58 | 9.26 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.71 | 95.78 | 64.60 | 162.11 | 98.73 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.31 | 76.16 | 40.15 | 104.70 | 117.70 | 0.00 | 0.00 | 744.00 |
February | 153.47 | 101.61 | 51.86 | 137.02 | 117.21 | 0.00 | 0.00 | 672.00 |
March | 138.45 | 76.86 | 61.58 | 119.37 | 86.46 | 0.00 | 0.00 | 744.00 |
April | 107.38 | 42.45 | 64.93 | 79.74 | 64.85 | 0.00 | 0.00 | 720.00 |
May | 94.10 | 19.62 | 74.48 | 70.60 | 42.08 | 0.00 | 0.00 | 744.00 |
June | 88.30 | 13.48 | 74.82 | 82.48 | 21.89 | 0.00 | 0.00 | 720.00 |
July | 92.56 | 16.07 | 76.50 | 99.53 | 11.14 | 0.00 | 0.00 | 744.00 |
August | 123.61 | 45.84 | 77.77 | 129.66 | 16.04 | 0.00 | 0.00 | 744.00 |
September | 134.16 | 69.40 | 64.76 | 139.64 | 33.19 | 0.00 | 0.00 | 720.00 |
October | 183.85 | 115.32 | 68.53 | 195.16 | 60.70 | 0.00 | 0.00 | 744.00 |
November | 127.44 | 76.54 | 50.90 | 121.83 | 87.65 | 0.00 | 0.00 | 720.00 |
December | 126.04 | 89.48 | 36.57 | 121.30 | 107.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.67 | 61.70 | 61.97 | 116.70 | 63.57 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 88.30 | 13.48 | 36.57 | 70.60 | 11.14 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 183.85 | 115.32 | 77.77 | 195.16 | 117.70 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.61 | 63.26 | 33.35 | 87.10 | 95.70 | 0.00 | 0.00 | 744.00 |
February | 127.47 | 84.39 | 43.08 | 113.89 | 95.69 | 0.00 | 0.00 | 672.00 |
March | 114.99 | 63.84 | 51.15 | 99.39 | 70.08 | 0.00 | 0.00 | 744.00 |
April | 89.19 | 35.26 | 53.93 | 66.57 | 52.76 | 0.00 | 0.00 | 720.00 |
May | 78.16 | 16.29 | 61.87 | 58.74 | 35.64 | 0.00 | 0.00 | 744.00 |
June | 73.34 | 11.20 | 62.15 | 68.47 | 19.65 | 0.00 | 0.00 | 720.00 |
July | 76.88 | 13.34 | 63.54 | 82.51 | 11.00 | 0.00 | 0.00 | 744.00 |
August | 102.67 | 38.07 | 64.60 | 107.58 | 15.15 | 0.00 | 0.00 | 744.00 |
September | 111.43 | 57.65 | 53.79 | 116.03 | 29.24 | 0.00 | 0.00 | 720.00 |
October | 152.71 | 95.78 | 56.92 | 162.33 | 51.27 | 0.00 | 0.00 | 744.00 |
November | 105.85 | 63.57 | 42.28 | 101.56 | 71.43 | 0.00 | 0.00 | 720.00 |
December | 104.69 | 74.32 | 30.37 | 100.97 | 87.43 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.72 | 51.25 | 51.47 | 97.05 | 52.67 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.34 | 11.20 | 30.37 | 58.74 | 11.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.71 | 95.78 | 64.60 | 162.33 | 95.70 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.61 | 63.26 | 33.35 | 87.10 | 95.70 | 0.00 | 0.00 | 744.00 |
February | 127.47 | 84.39 | 43.08 | 113.89 | 95.69 | 0.00 | 0.00 | 672.00 |
March | 114.99 | 63.84 | 51.15 | 99.39 | 70.08 | 0.00 | 0.00 | 744.00 |
April | 89.19 | 35.26 | 53.93 | 66.57 | 52.76 | 0.00 | 0.00 | 720.00 |
May | 78.16 | 16.29 | 61.87 | 58.74 | 35.64 | 0.00 | 0.00 | 744.00 |
June | 73.34 | 11.20 | 62.15 | 68.47 | 19.65 | 0.00 | 0.00 | 720.00 |
July | 76.88 | 13.34 | 63.54 | 82.51 | 11.00 | 0.00 | 0.00 | 744.00 |
August | 102.67 | 38.07 | 64.60 | 107.58 | 15.15 | 0.00 | 0.00 | 744.00 |
September | 111.43 | 57.65 | 53.79 | 116.03 | 29.24 | 0.00 | 0.00 | 720.00 |
October | 152.71 | 95.78 | 56.92 | 162.33 | 51.27 | 0.00 | 0.00 | 744.00 |
November | 105.85 | 63.57 | 42.28 | 101.56 | 71.43 | 0.00 | 0.00 | 720.00 |
December | 104.69 | 74.32 | 30.37 | 100.97 | 87.43 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.72 | 51.25 | 51.47 | 97.05 | 52.67 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.34 | 11.20 | 30.37 | 58.74 | 11.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.71 | 95.78 | 64.60 | 162.33 | 95.70 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.67 | 75.74 | 39.93 | 104.48 | 113.47 | 0.00 | 0.00 | 744.00 |
February | 152.63 | 101.05 | 51.58 | 136.59 | 113.44 | 0.00 | 0.00 | 672.00 |
March | 137.69 | 76.44 | 61.25 | 119.17 | 83.09 | 0.00 | 0.00 | 744.00 |
April | 106.79 | 42.22 | 64.57 | 79.84 | 62.60 | 0.00 | 0.00 | 720.00 |
May | 93.58 | 19.51 | 74.08 | 70.41 | 42.34 | 0.00 | 0.00 | 744.00 |
June | 87.82 | 13.41 | 74.41 | 81.89 | 23.38 | 0.00 | 0.00 | 720.00 |
July | 92.06 | 15.98 | 76.08 | 98.58 | 13.12 | 0.00 | 0.00 | 744.00 |
August | 122.94 | 45.59 | 77.35 | 128.58 | 18.07 | 0.00 | 0.00 | 744.00 |
September | 133.43 | 69.02 | 64.40 | 138.83 | 34.79 | 0.00 | 0.00 | 720.00 |
October | 182.85 | 114.69 | 68.16 | 194.36 | 60.95 | 0.00 | 0.00 | 744.00 |
November | 126.74 | 76.12 | 50.62 | 121.74 | 84.79 | 0.00 | 0.00 | 720.00 |
December | 125.35 | 88.99 | 36.37 | 121.03 | 103.72 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 122.99 | 61.36 | 61.63 | 116.24 | 62.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 87.82 | 13.41 | 36.37 | 70.41 | 13.12 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 182.85 | 114.69 | 77.35 | 194.36 | 113.47 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.61 | 63.26 | 33.35 | 87.25 | 94.51 | 0.00 | 0.00 | 744.00 |
February | 127.47 | 84.39 | 43.08 | 114.04 | 94.66 | 0.00 | 0.00 | 672.00 |
March | 114.99 | 63.84 | 51.15 | 99.60 | 69.05 | 0.00 | 0.00 | 744.00 |
April | 89.19 | 35.26 | 53.93 | 66.86 | 51.83 | 0.00 | 0.00 | 720.00 |
May | 78.16 | 16.29 | 61.87 | 58.96 | 35.16 | 0.00 | 0.00 | 744.00 |
June | 73.34 | 11.20 | 62.15 | 68.50 | 19.60 | 0.00 | 0.00 | 720.00 |
July | 76.88 | 13.34 | 63.54 | 82.51 | 11.05 | 0.00 | 0.00 | 744.00 |
August | 102.67 | 38.07 | 64.60 | 107.57 | 15.22 | 0.00 | 0.00 | 744.00 |
September | 111.43 | 57.65 | 53.79 | 116.05 | 29.18 | 0.00 | 0.00 | 720.00 |
October | 152.71 | 95.78 | 56.92 | 162.48 | 50.86 | 0.00 | 0.00 | 744.00 |
November | 105.85 | 63.57 | 42.28 | 101.87 | 70.30 | 0.00 | 0.00 | 720.00 |
December | 104.69 | 74.32 | 30.37 | 101.11 | 86.42 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.72 | 51.25 | 51.47 | 97.19 | 52.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.34 | 11.20 | 30.37 | 58.96 | 11.05 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.71 | 95.78 | 64.60 | 162.48 | 94.66 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.61 | 63.26 | 33.35 | 87.25 | 94.51 | 0.00 | 0.00 | 744.00 |
February | 127.47 | 84.39 | 43.08 | 114.04 | 94.66 | 0.00 | 0.00 | 672.00 |
March | 114.99 | 63.84 | 51.15 | 99.60 | 69.05 | 0.00 | 0.00 | 744.00 |
April | 89.19 | 35.26 | 53.93 | 66.86 | 51.83 | 0.00 | 0.00 | 720.00 |
May | 78.16 | 16.29 | 61.87 | 58.96 | 35.16 | 0.00 | 0.00 | 744.00 |
June | 73.34 | 11.20 | 62.15 | 68.50 | 19.60 | 0.00 | 0.00 | 720.00 |
July | 76.88 | 13.34 | 63.54 | 82.51 | 11.05 | 0.00 | 0.00 | 744.00 |
August | 102.67 | 38.07 | 64.60 | 107.57 | 15.22 | 0.00 | 0.00 | 744.00 |
September | 111.43 | 57.65 | 53.79 | 116.05 | 29.18 | 0.00 | 0.00 | 720.00 |
October | 152.71 | 95.78 | 56.92 | 162.48 | 50.86 | 0.00 | 0.00 | 744.00 |
November | 105.85 | 63.57 | 42.28 | 101.87 | 70.30 | 0.00 | 0.00 | 720.00 |
December | 104.69 | 74.32 | 30.37 | 101.11 | 86.42 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.72 | 51.25 | 51.47 | 97.19 | 52.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.34 | 11.20 | 30.37 | 58.96 | 11.05 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.71 | 95.78 | 64.60 | 162.48 | 94.66 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.67 | 75.74 | 39.93 | 104.67 | 112.05 | 0.00 | 0.00 | 744.00 |
February | 152.63 | 101.05 | 51.58 | 136.78 | 112.21 | 0.00 | 0.00 | 672.00 |
March | 137.69 | 76.44 | 61.25 | 119.42 | 81.87 | 0.00 | 0.00 | 744.00 |
April | 106.79 | 42.22 | 64.57 | 80.18 | 61.49 | 0.00 | 0.00 | 720.00 |
May | 93.58 | 19.51 | 74.08 | 70.67 | 41.77 | 0.00 | 0.00 | 744.00 |
June | 87.82 | 13.41 | 74.41 | 81.92 | 23.32 | 0.00 | 0.00 | 720.00 |
July | 92.06 | 15.98 | 76.08 | 98.57 | 13.17 | 0.00 | 0.00 | 744.00 |
August | 122.94 | 45.59 | 77.35 | 128.56 | 18.15 | 0.00 | 0.00 | 744.00 |
September | 133.43 | 69.02 | 64.40 | 138.85 | 34.72 | 0.00 | 0.00 | 720.00 |
October | 182.85 | 114.69 | 68.16 | 194.54 | 60.46 | 0.00 | 0.00 | 744.00 |
November | 126.74 | 76.12 | 50.62 | 122.10 | 83.45 | 0.00 | 0.00 | 720.00 |
December | 125.35 | 88.99 | 36.37 | 121.21 | 102.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 122.99 | 61.36 | 61.63 | 116.41 | 61.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 87.82 | 13.41 | 36.37 | 70.67 | 13.17 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 182.85 | 114.69 | 77.35 | 194.54 | 112.21 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.61 | 63.26 | 33.35 | 87.43 | 93.57 | 0.00 | 0.00 | 744.00 |
February | 127.47 | 84.39 | 43.08 | 114.24 | 93.81 | 0.00 | 0.00 | 672.00 |
March | 114.99 | 63.84 | 51.15 | 99.84 | 68.19 | 0.00 | 0.00 | 744.00 |
April | 89.19 | 35.26 | 53.93 | 67.23 | 50.92 | 0.00 | 0.00 | 720.00 |
May | 78.16 | 16.29 | 61.87 | 59.41 | 34.34 | 0.00 | 0.00 | 744.00 |
June | 73.34 | 11.20 | 62.15 | 68.65 | 19.28 | 0.00 | 0.00 | 720.00 |
July | 76.88 | 13.34 | 63.54 | 82.65 | 10.76 | 0.00 | 0.00 | 744.00 |
August | 102.67 | 38.07 | 64.60 | 107.70 | 14.92 | 0.00 | 0.00 | 744.00 |
September | 111.43 | 57.65 | 53.79 | 116.16 | 28.82 | 0.00 | 0.00 | 720.00 |
October | 152.71 | 95.78 | 56.92 | 162.75 | 50.21 | 0.00 | 0.00 | 744.00 |
November | 105.85 | 63.57 | 42.28 | 102.30 | 69.15 | 0.00 | 0.00 | 720.00 |
December | 104.69 | 74.32 | 30.37 | 101.28 | 85.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.72 | 51.25 | 51.47 | 97.43 | 51.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.34 | 11.20 | 30.37 | 59.41 | 10.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.71 | 95.78 | 64.60 | 162.75 | 93.81 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.61 | 63.26 | 33.35 | 87.43 | 93.57 | 0.00 | 0.00 | 744.00 |
February | 127.47 | 84.39 | 43.08 | 114.24 | 93.81 | 0.00 | 0.00 | 672.00 |
March | 114.99 | 63.84 | 51.15 | 99.84 | 68.19 | 0.00 | 0.00 | 744.00 |
April | 89.19 | 35.26 | 53.93 | 67.23 | 50.92 | 0.00 | 0.00 | 720.00 |
May | 78.16 | 16.29 | 61.87 | 59.41 | 34.34 | 0.00 | 0.00 | 744.00 |
June | 73.34 | 11.20 | 62.15 | 68.65 | 19.28 | 0.00 | 0.00 | 720.00 |
July | 76.88 | 13.34 | 63.54 | 82.65 | 10.76 | 0.00 | 0.00 | 744.00 |
August | 102.67 | 38.07 | 64.60 | 107.70 | 14.92 | 0.00 | 0.00 | 744.00 |
September | 111.43 | 57.65 | 53.79 | 116.16 | 28.82 | 0.00 | 0.00 | 720.00 |
October | 152.71 | 95.78 | 56.92 | 162.75 | 50.21 | 0.00 | 0.00 | 744.00 |
November | 105.85 | 63.57 | 42.28 | 102.30 | 69.15 | 0.00 | 0.00 | 720.00 |
December | 104.69 | 74.32 | 30.37 | 101.28 | 85.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.72 | 51.25 | 51.47 | 97.43 | 51.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.34 | 11.20 | 30.37 | 59.41 | 10.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.71 | 95.78 | 64.60 | 162.75 | 93.81 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.67 | 75.74 | 39.93 | 104.89 | 110.93 | 0.00 | 0.00 | 744.00 |
February | 152.63 | 101.05 | 51.58 | 137.02 | 111.21 | 0.00 | 0.00 | 672.00 |
March | 137.69 | 76.44 | 61.25 | 119.71 | 80.84 | 0.00 | 0.00 | 744.00 |
April | 106.79 | 42.22 | 64.57 | 80.63 | 60.42 | 0.00 | 0.00 | 720.00 |
May | 93.58 | 19.51 | 74.08 | 71.22 | 40.80 | 0.00 | 0.00 | 744.00 |
June | 87.82 | 13.41 | 74.41 | 82.11 | 22.93 | 0.00 | 0.00 | 720.00 |
July | 92.06 | 15.98 | 76.08 | 98.75 | 12.83 | 0.00 | 0.00 | 744.00 |
August | 122.94 | 45.59 | 77.35 | 128.72 | 17.80 | 0.00 | 0.00 | 744.00 |
September | 133.43 | 69.02 | 64.40 | 138.99 | 34.30 | 0.00 | 0.00 | 720.00 |
October | 182.85 | 114.69 | 68.16 | 194.86 | 59.69 | 0.00 | 0.00 | 744.00 |
November | 126.74 | 76.12 | 50.62 | 122.62 | 82.08 | 0.00 | 0.00 | 720.00 |
December | 125.35 | 88.99 | 36.37 | 121.40 | 101.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 122.99 | 61.36 | 61.63 | 116.69 | 61.00 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 87.82 | 13.41 | 36.37 | 71.22 | 12.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 182.85 | 114.69 | 77.35 | 194.86 | 111.21 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.61 | 63.26 | 33.35 | 88.20 | 90.66 | 0.00 | 0.00 | 744.00 |
February | 127.47 | 84.39 | 43.08 | 115.10 | 91.11 | 0.00 | 0.00 | 672.00 |
March | 114.99 | 63.84 | 51.15 | 100.56 | 65.88 | 0.00 | 0.00 | 744.00 |
April | 89.19 | 35.26 | 53.93 | 68.07 | 48.74 | 0.00 | 0.00 | 720.00 |
May | 78.16 | 16.29 | 61.87 | 60.41 | 32.36 | 0.00 | 0.00 | 744.00 |
June | 73.34 | 11.20 | 62.15 | 68.74 | 18.24 | 0.00 | 0.00 | 720.00 |
July | 76.88 | 13.34 | 63.54 | 82.50 | 9.85 | 0.00 | 0.00 | 744.00 |
August | 102.67 | 38.07 | 64.60 | 107.54 | 13.94 | 0.00 | 0.00 | 744.00 |
September | 111.43 | 57.65 | 53.79 | 116.24 | 27.77 | 0.00 | 0.00 | 720.00 |
October | 152.71 | 95.78 | 56.92 | 163.36 | 48.56 | 0.00 | 0.00 | 744.00 |
November | 105.85 | 63.57 | 42.28 | 103.30 | 66.55 | 0.00 | 0.00 | 720.00 |
December | 104.69 | 74.32 | 30.37 | 101.94 | 83.38 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.72 | 51.25 | 51.47 | 97.96 | 49.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.34 | 11.20 | 30.37 | 60.41 | 9.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.71 | 95.78 | 64.60 | 163.36 | 91.11 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.61 | 63.26 | 33.35 | 88.20 | 90.66 | 0.00 | 0.00 | 744.00 |
February | 127.47 | 84.39 | 43.08 | 115.10 | 91.11 | 0.00 | 0.00 | 672.00 |
March | 114.99 | 63.84 | 51.15 | 100.56 | 65.88 | 0.00 | 0.00 | 744.00 |
April | 89.19 | 35.26 | 53.93 | 68.07 | 48.74 | 0.00 | 0.00 | 720.00 |
May | 78.16 | 16.29 | 61.87 | 60.41 | 32.36 | 0.00 | 0.00 | 744.00 |
June | 73.34 | 11.20 | 62.15 | 68.74 | 18.24 | 0.00 | 0.00 | 720.00 |
July | 76.88 | 13.34 | 63.54 | 82.50 | 9.85 | 0.00 | 0.00 | 744.00 |
August | 102.67 | 38.07 | 64.60 | 107.54 | 13.94 | 0.00 | 0.00 | 744.00 |
September | 111.43 | 57.65 | 53.79 | 116.24 | 27.77 | 0.00 | 0.00 | 720.00 |
October | 152.71 | 95.78 | 56.92 | 163.36 | 48.56 | 0.00 | 0.00 | 744.00 |
November | 105.85 | 63.57 | 42.28 | 103.30 | 66.55 | 0.00 | 0.00 | 720.00 |
December | 104.69 | 74.32 | 30.37 | 101.94 | 83.38 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.72 | 51.25 | 51.47 | 97.96 | 49.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.34 | 11.20 | 30.37 | 60.41 | 9.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.71 | 95.78 | 64.60 | 163.36 | 91.11 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.61 | 63.26 | 33.35 | 88.20 | 90.66 | 0.00 | 0.00 | 744.00 |
February | 127.47 | 84.39 | 43.08 | 115.10 | 91.11 | 0.00 | 0.00 | 672.00 |
March | 114.99 | 63.84 | 51.15 | 100.56 | 65.88 | 0.00 | 0.00 | 744.00 |
April | 89.19 | 35.26 | 53.93 | 68.07 | 48.74 | 0.00 | 0.00 | 720.00 |
May | 78.16 | 16.29 | 61.87 | 60.41 | 32.36 | 0.00 | 0.00 | 744.00 |
June | 73.34 | 11.20 | 62.15 | 68.74 | 18.24 | 0.00 | 0.00 | 720.00 |
July | 76.88 | 13.34 | 63.54 | 82.50 | 9.85 | 0.00 | 0.00 | 744.00 |
August | 102.67 | 38.07 | 64.60 | 107.54 | 13.94 | 0.00 | 0.00 | 744.00 |
September | 111.43 | 57.65 | 53.79 | 116.24 | 27.77 | 0.00 | 0.00 | 720.00 |
October | 152.71 | 95.78 | 56.92 | 163.36 | 48.56 | 0.00 | 0.00 | 744.00 |
November | 105.85 | 63.57 | 42.28 | 103.30 | 66.55 | 0.00 | 0.00 | 720.00 |
December | 104.69 | 74.32 | 30.37 | 101.94 | 83.38 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.72 | 51.25 | 51.47 | 97.96 | 49.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.34 | 11.20 | 30.37 | 60.41 | 9.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.71 | 95.78 | 64.60 | 163.36 | 91.11 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.61 | 63.26 | 33.35 | 88.20 | 90.66 | 0.00 | 0.00 | 744.00 |
February | 127.47 | 84.39 | 43.08 | 115.10 | 91.11 | 0.00 | 0.00 | 672.00 |
March | 114.99 | 63.84 | 51.15 | 100.56 | 65.88 | 0.00 | 0.00 | 744.00 |
April | 89.19 | 35.26 | 53.93 | 68.07 | 48.74 | 0.00 | 0.00 | 720.00 |
May | 78.16 | 16.29 | 61.87 | 60.41 | 32.36 | 0.00 | 0.00 | 744.00 |
June | 73.34 | 11.20 | 62.15 | 68.74 | 18.24 | 0.00 | 0.00 | 720.00 |
July | 76.88 | 13.34 | 63.54 | 82.50 | 9.85 | 0.00 | 0.00 | 744.00 |
August | 102.67 | 38.07 | 64.60 | 107.54 | 13.94 | 0.00 | 0.00 | 744.00 |
September | 111.43 | 57.65 | 53.79 | 116.24 | 27.77 | 0.00 | 0.00 | 720.00 |
October | 152.71 | 95.78 | 56.92 | 163.36 | 48.56 | 0.00 | 0.00 | 744.00 |
November | 105.85 | 63.57 | 42.28 | 103.30 | 66.55 | 0.00 | 0.00 | 720.00 |
December | 104.69 | 74.32 | 30.37 | 101.94 | 83.38 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.72 | 51.25 | 51.47 | 97.96 | 49.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.34 | 11.20 | 30.37 | 60.41 | 9.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.71 | 95.78 | 64.60 | 163.36 | 91.11 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.67 | 75.74 | 39.93 | 105.80 | 107.48 | 0.00 | 0.00 | 744.00 |
February | 152.63 | 101.05 | 51.58 | 138.05 | 108.01 | 0.00 | 0.00 | 672.00 |
March | 137.69 | 76.44 | 61.25 | 120.58 | 78.11 | 0.00 | 0.00 | 744.00 |
April | 106.79 | 42.22 | 64.57 | 81.65 | 57.84 | 0.00 | 0.00 | 720.00 |
May | 93.58 | 19.51 | 74.08 | 72.41 | 38.45 | 0.00 | 0.00 | 744.00 |
June | 87.82 | 13.41 | 74.41 | 82.23 | 21.71 | 0.00 | 0.00 | 720.00 |
July | 92.06 | 15.98 | 76.08 | 98.59 | 11.75 | 0.00 | 0.00 | 744.00 |
August | 122.94 | 45.59 | 77.35 | 128.55 | 16.64 | 0.00 | 0.00 | 744.00 |
September | 133.43 | 69.02 | 64.40 | 139.10 | 33.05 | 0.00 | 0.00 | 720.00 |
October | 182.85 | 114.69 | 68.16 | 195.59 | 57.73 | 0.00 | 0.00 | 744.00 |
November | 126.74 | 76.12 | 50.62 | 123.81 | 78.99 | 0.00 | 0.00 | 720.00 |
December | 125.35 | 88.99 | 36.37 | 122.20 | 98.91 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 122.99 | 61.36 | 61.63 | 117.33 | 58.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 87.82 | 13.41 | 36.37 | 72.41 | 11.75 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 182.85 | 114.69 | 77.35 | 195.59 | 108.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.67 | 75.74 | 39.93 | 105.80 | 107.48 | 0.00 | 0.00 | 744.00 |
February | 152.63 | 101.05 | 51.58 | 138.05 | 108.01 | 0.00 | 0.00 | 672.00 |
March | 137.69 | 76.44 | 61.25 | 120.58 | 78.11 | 0.00 | 0.00 | 744.00 |
April | 106.79 | 42.22 | 64.57 | 81.65 | 57.84 | 0.00 | 0.00 | 720.00 |
May | 93.58 | 19.51 | 74.08 | 72.41 | 38.45 | 0.00 | 0.00 | 744.00 |
June | 87.82 | 13.41 | 74.41 | 82.23 | 21.71 | 0.00 | 0.00 | 720.00 |
July | 92.06 | 15.98 | 76.08 | 98.59 | 11.75 | 0.00 | 0.00 | 744.00 |
August | 122.94 | 45.59 | 77.35 | 128.55 | 16.64 | 0.00 | 0.00 | 744.00 |
September | 133.43 | 69.02 | 64.40 | 139.10 | 33.05 | 0.00 | 0.00 | 720.00 |
October | 182.85 | 114.69 | 68.16 | 195.59 | 57.73 | 0.00 | 0.00 | 744.00 |
November | 126.74 | 76.12 | 50.62 | 123.81 | 78.99 | 0.00 | 0.00 | 720.00 |
December | 125.35 | 88.99 | 36.37 | 122.20 | 98.91 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 122.99 | 61.36 | 61.63 | 117.33 | 58.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 87.82 | 13.41 | 36.37 | 72.41 | 11.75 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 182.85 | 114.69 | 77.35 | 195.59 | 108.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.61 | 63.26 | 33.35 | 87.96 | 91.01 | 0.00 | 0.00 | 744.00 |
February | 127.47 | 84.39 | 43.08 | 114.84 | 91.40 | 0.00 | 0.00 | 672.00 |
March | 114.99 | 63.84 | 51.15 | 100.42 | 65.90 | 0.00 | 0.00 | 744.00 |
April | 89.19 | 35.26 | 53.93 | 68.14 | 48.54 | 0.00 | 0.00 | 720.00 |
May | 78.16 | 16.29 | 61.87 | 60.70 | 31.92 | 0.00 | 0.00 | 744.00 |
June | 73.34 | 11.20 | 62.15 | 68.96 | 17.96 | 0.00 | 0.00 | 720.00 |
July | 76.88 | 13.34 | 63.54 | 82.82 | 9.50 | 0.00 | 0.00 | 744.00 |
August | 102.67 | 38.07 | 64.60 | 107.88 | 13.56 | 0.00 | 0.00 | 744.00 |
September | 111.43 | 57.65 | 53.79 | 116.32 | 27.45 | 0.00 | 0.00 | 720.00 |
October | 152.71 | 95.78 | 56.92 | 163.33 | 48.23 | 0.00 | 0.00 | 744.00 |
November | 105.85 | 63.57 | 42.28 | 103.26 | 66.37 | 0.00 | 0.00 | 720.00 |
December | 104.69 | 74.32 | 30.37 | 101.74 | 83.57 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.72 | 51.25 | 51.47 | 97.99 | 49.38 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.34 | 11.20 | 30.37 | 60.70 | 9.50 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.71 | 95.78 | 64.60 | 163.33 | 91.40 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.61 | 63.26 | 33.35 | 87.96 | 91.01 | 0.00 | 0.00 | 744.00 |
February | 127.47 | 84.39 | 43.08 | 114.84 | 91.40 | 0.00 | 0.00 | 672.00 |
March | 114.99 | 63.84 | 51.15 | 100.42 | 65.90 | 0.00 | 0.00 | 744.00 |
April | 89.19 | 35.26 | 53.93 | 68.14 | 48.54 | 0.00 | 0.00 | 720.00 |
May | 78.16 | 16.29 | 61.87 | 60.70 | 31.92 | 0.00 | 0.00 | 744.00 |
June | 73.34 | 11.20 | 62.15 | 68.96 | 17.96 | 0.00 | 0.00 | 720.00 |
July | 76.88 | 13.34 | 63.54 | 82.82 | 9.50 | 0.00 | 0.00 | 744.00 |
August | 102.67 | 38.07 | 64.60 | 107.88 | 13.56 | 0.00 | 0.00 | 744.00 |
September | 111.43 | 57.65 | 53.79 | 116.32 | 27.45 | 0.00 | 0.00 | 720.00 |
October | 152.71 | 95.78 | 56.92 | 163.33 | 48.23 | 0.00 | 0.00 | 744.00 |
November | 105.85 | 63.57 | 42.28 | 103.26 | 66.37 | 0.00 | 0.00 | 720.00 |
December | 104.69 | 74.32 | 30.37 | 101.74 | 83.57 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.72 | 51.25 | 51.47 | 97.99 | 49.38 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.34 | 11.20 | 30.37 | 60.70 | 9.50 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.71 | 95.78 | 64.60 | 163.33 | 91.40 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.67 | 75.74 | 39.93 | 105.53 | 107.88 | 0.00 | 0.00 | 744.00 |
February | 152.63 | 101.05 | 51.58 | 137.76 | 108.32 | 0.00 | 0.00 | 672.00 |
March | 137.69 | 76.44 | 61.25 | 120.42 | 78.12 | 0.00 | 0.00 | 744.00 |
April | 106.79 | 42.22 | 64.57 | 81.73 | 57.59 | 0.00 | 0.00 | 720.00 |
May | 93.58 | 19.51 | 74.08 | 72.77 | 37.92 | 0.00 | 0.00 | 744.00 |
June | 87.82 | 13.41 | 74.41 | 82.50 | 21.37 | 0.00 | 0.00 | 720.00 |
July | 92.06 | 15.98 | 76.08 | 98.97 | 11.34 | 0.00 | 0.00 | 744.00 |
August | 122.94 | 45.59 | 77.35 | 128.95 | 16.19 | 0.00 | 0.00 | 744.00 |
September | 133.43 | 69.02 | 64.40 | 139.20 | 32.67 | 0.00 | 0.00 | 720.00 |
October | 182.85 | 114.69 | 68.16 | 195.56 | 57.33 | 0.00 | 0.00 | 744.00 |
November | 126.74 | 76.12 | 50.62 | 123.77 | 78.77 | 0.00 | 0.00 | 720.00 |
December | 125.35 | 88.99 | 36.37 | 121.97 | 99.12 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 122.99 | 61.36 | 61.63 | 117.38 | 58.60 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 87.82 | 13.41 | 36.37 | 72.77 | 11.34 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 182.85 | 114.69 | 77.35 | 195.56 | 108.32 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.61 | 63.26 | 33.35 | 88.02 | 90.71 | 0.00 | 0.00 | 744.00 |
February | 127.47 | 84.39 | 43.08 | 114.93 | 91.06 | 0.00 | 0.00 | 672.00 |
March | 114.99 | 63.84 | 51.15 | 100.52 | 65.55 | 0.00 | 0.00 | 744.00 |
April | 89.19 | 35.26 | 53.93 | 68.33 | 48.13 | 0.00 | 0.00 | 720.00 |
May | 78.16 | 16.29 | 61.87 | 61.04 | 31.44 | 0.00 | 0.00 | 744.00 |
June | 73.34 | 11.20 | 62.15 | 69.06 | 17.82 | 0.00 | 0.00 | 720.00 |
July | 76.88 | 13.34 | 63.54 | 82.91 | 9.39 | 0.00 | 0.00 | 744.00 |
August | 102.67 | 38.07 | 64.60 | 107.96 | 13.45 | 0.00 | 0.00 | 744.00 |
September | 111.43 | 57.65 | 53.79 | 116.39 | 27.30 | 0.00 | 0.00 | 720.00 |
October | 152.71 | 95.78 | 56.92 | 163.49 | 47.91 | 0.00 | 0.00 | 744.00 |
November | 105.85 | 63.57 | 42.28 | 103.43 | 65.97 | 0.00 | 0.00 | 720.00 |
December | 104.69 | 74.32 | 30.37 | 101.81 | 83.28 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.72 | 51.25 | 51.47 | 98.12 | 49.10 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.34 | 11.20 | 30.37 | 61.04 | 9.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.71 | 95.78 | 64.60 | 163.49 | 91.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.61 | 63.26 | 33.35 | 88.02 | 90.71 | 0.00 | 0.00 | 744.00 |
February | 127.47 | 84.39 | 43.08 | 114.93 | 91.06 | 0.00 | 0.00 | 672.00 |
March | 114.99 | 63.84 | 51.15 | 100.52 | 65.55 | 0.00 | 0.00 | 744.00 |
April | 89.19 | 35.26 | 53.93 | 68.33 | 48.13 | 0.00 | 0.00 | 720.00 |
May | 78.16 | 16.29 | 61.87 | 61.04 | 31.44 | 0.00 | 0.00 | 744.00 |
June | 73.34 | 11.20 | 62.15 | 69.06 | 17.82 | 0.00 | 0.00 | 720.00 |
July | 76.88 | 13.34 | 63.54 | 82.91 | 9.39 | 0.00 | 0.00 | 744.00 |
August | 102.67 | 38.07 | 64.60 | 107.96 | 13.45 | 0.00 | 0.00 | 744.00 |
September | 111.43 | 57.65 | 53.79 | 116.39 | 27.30 | 0.00 | 0.00 | 720.00 |
October | 152.71 | 95.78 | 56.92 | 163.49 | 47.91 | 0.00 | 0.00 | 744.00 |
November | 105.85 | 63.57 | 42.28 | 103.43 | 65.97 | 0.00 | 0.00 | 720.00 |
December | 104.69 | 74.32 | 30.37 | 101.81 | 83.28 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.72 | 51.25 | 51.47 | 98.12 | 49.10 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.34 | 11.20 | 30.37 | 61.04 | 9.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.71 | 95.78 | 64.60 | 163.49 | 91.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.67 | 75.74 | 39.93 | 105.60 | 107.52 | 0.00 | 0.00 | 744.00 |
February | 152.63 | 101.05 | 51.58 | 137.87 | 107.93 | 0.00 | 0.00 | 672.00 |
March | 137.69 | 76.44 | 61.25 | 120.54 | 77.70 | 0.00 | 0.00 | 744.00 |
April | 106.79 | 42.22 | 64.57 | 81.96 | 57.10 | 0.00 | 0.00 | 720.00 |
May | 93.58 | 19.51 | 74.08 | 73.18 | 37.35 | 0.00 | 0.00 | 744.00 |
June | 87.82 | 13.41 | 74.41 | 82.62 | 21.21 | 0.00 | 0.00 | 720.00 |
July | 92.06 | 15.98 | 76.08 | 99.09 | 11.21 | 0.00 | 0.00 | 744.00 |
August | 122.94 | 45.59 | 77.35 | 129.05 | 16.06 | 0.00 | 0.00 | 744.00 |
September | 133.43 | 69.02 | 64.40 | 139.29 | 32.49 | 0.00 | 0.00 | 720.00 |
October | 182.85 | 114.69 | 68.16 | 195.76 | 56.95 | 0.00 | 0.00 | 744.00 |
November | 126.74 | 76.12 | 50.62 | 123.97 | 78.29 | 0.00 | 0.00 | 720.00 |
December | 125.35 | 88.99 | 36.37 | 122.05 | 98.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 122.99 | 61.36 | 61.63 | 117.53 | 58.27 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 87.82 | 13.41 | 36.37 | 73.18 | 11.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 182.85 | 114.69 | 77.35 | 195.76 | 107.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.61 | 63.26 | 33.35 | 88.23 | 89.57 | 0.00 | 0.00 | 744.00 |
February | 127.47 | 84.39 | 43.08 | 115.21 | 89.84 | 0.00 | 0.00 | 672.00 |
March | 114.99 | 63.84 | 51.15 | 100.80 | 64.41 | 0.00 | 0.00 | 744.00 |
April | 89.19 | 35.26 | 53.93 | 68.76 | 47.03 | 0.00 | 0.00 | 720.00 |
May | 78.16 | 16.29 | 61.87 | 61.75 | 30.40 | 0.00 | 0.00 | 744.00 |
June | 73.34 | 11.20 | 62.15 | 69.27 | 17.50 | 0.00 | 0.00 | 720.00 |
July | 76.88 | 13.34 | 63.54 | 83.04 | 9.19 | 0.00 | 0.00 | 744.00 |
August | 102.67 | 38.07 | 64.60 | 108.03 | 13.29 | 0.00 | 0.00 | 744.00 |
September | 111.43 | 57.65 | 53.79 | 116.50 | 27.01 | 0.00 | 0.00 | 720.00 |
October | 152.71 | 95.78 | 56.92 | 163.81 | 47.22 | 0.00 | 0.00 | 744.00 |
November | 105.85 | 63.57 | 42.28 | 103.75 | 65.05 | 0.00 | 0.00 | 720.00 |
December | 104.69 | 74.32 | 30.37 | 102.04 | 82.26 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.72 | 51.25 | 51.47 | 98.39 | 48.33 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.34 | 11.20 | 30.37 | 61.75 | 9.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.71 | 95.78 | 64.60 | 163.81 | 89.84 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.61 | 63.26 | 33.35 | 88.23 | 89.57 | 0.00 | 0.00 | 744.00 |
February | 127.47 | 84.39 | 43.08 | 115.21 | 89.84 | 0.00 | 0.00 | 672.00 |
March | 114.99 | 63.84 | 51.15 | 100.80 | 64.41 | 0.00 | 0.00 | 744.00 |
April | 89.19 | 35.26 | 53.93 | 68.76 | 47.03 | 0.00 | 0.00 | 720.00 |
May | 78.16 | 16.29 | 61.87 | 61.75 | 30.40 | 0.00 | 0.00 | 744.00 |
June | 73.34 | 11.20 | 62.15 | 69.27 | 17.50 | 0.00 | 0.00 | 720.00 |
July | 76.88 | 13.34 | 63.54 | 83.04 | 9.19 | 0.00 | 0.00 | 744.00 |
August | 102.67 | 38.07 | 64.60 | 108.03 | 13.29 | 0.00 | 0.00 | 744.00 |
September | 111.43 | 57.65 | 53.79 | 116.50 | 27.01 | 0.00 | 0.00 | 720.00 |
October | 152.71 | 95.78 | 56.92 | 163.81 | 47.22 | 0.00 | 0.00 | 744.00 |
November | 105.85 | 63.57 | 42.28 | 103.75 | 65.05 | 0.00 | 0.00 | 720.00 |
December | 104.69 | 74.32 | 30.37 | 102.04 | 82.26 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.72 | 51.25 | 51.47 | 98.39 | 48.33 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.34 | 11.20 | 30.37 | 61.75 | 9.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.71 | 95.78 | 64.60 | 163.81 | 89.84 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.67 | 75.74 | 39.93 | 105.85 | 106.16 | 0.00 | 0.00 | 744.00 |
February | 152.63 | 101.05 | 51.58 | 138.21 | 106.47 | 0.00 | 0.00 | 672.00 |
March | 137.69 | 76.44 | 61.25 | 120.88 | 76.34 | 0.00 | 0.00 | 744.00 |
April | 106.79 | 42.22 | 64.57 | 82.48 | 55.79 | 0.00 | 0.00 | 720.00 |
May | 93.58 | 19.51 | 74.08 | 74.03 | 36.12 | 0.00 | 0.00 | 744.00 |
June | 87.82 | 13.41 | 74.41 | 82.87 | 20.83 | 0.00 | 0.00 | 720.00 |
July | 92.06 | 15.98 | 76.08 | 99.24 | 10.98 | 0.00 | 0.00 | 744.00 |
August | 122.94 | 45.59 | 77.35 | 129.14 | 15.86 | 0.00 | 0.00 | 744.00 |
September | 133.43 | 69.02 | 64.40 | 139.41 | 32.15 | 0.00 | 0.00 | 720.00 |
October | 182.85 | 114.69 | 68.16 | 196.15 | 56.14 | 0.00 | 0.00 | 744.00 |
November | 126.74 | 76.12 | 50.62 | 124.37 | 77.20 | 0.00 | 0.00 | 720.00 |
December | 125.35 | 88.99 | 36.37 | 122.33 | 97.55 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 122.99 | 61.36 | 61.63 | 117.86 | 57.35 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 87.82 | 13.41 | 36.37 | 74.03 | 10.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 182.85 | 114.69 | 77.35 | 196.15 | 106.47 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.61 | 63.26 | 33.35 | 88.97 | 84.97 | 0.00 | 0.00 | 744.00 |
February | 127.47 | 84.39 | 43.08 | 116.21 | 84.86 | 0.00 | 0.00 | 672.00 |
March | 114.99 | 63.84 | 51.15 | 101.70 | 59.95 | 0.00 | 0.00 | 744.00 |
April | 89.19 | 35.26 | 53.93 | 69.85 | 43.22 | 0.00 | 0.00 | 720.00 |
May | 78.16 | 16.29 | 61.87 | 63.41 | 27.49 | 0.00 | 0.00 | 744.00 |
June | 73.34 | 11.20 | 62.15 | 69.90 | 16.22 | 0.00 | 0.00 | 720.00 |
July | 76.88 | 13.34 | 63.54 | 83.23 | 8.59 | 0.00 | 0.00 | 744.00 |
August | 102.67 | 38.07 | 64.60 | 107.98 | 12.82 | 0.00 | 0.00 | 744.00 |
September | 111.43 | 57.65 | 53.79 | 116.67 | 26.05 | 0.00 | 0.00 | 720.00 |
October | 152.71 | 95.78 | 56.92 | 164.47 | 45.22 | 0.00 | 0.00 | 744.00 |
November | 105.85 | 63.57 | 42.28 | 104.55 | 62.08 | 0.00 | 0.00 | 720.00 |
December | 104.69 | 74.32 | 30.37 | 102.82 | 78.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.72 | 51.25 | 51.47 | 99.10 | 45.59 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.34 | 11.20 | 30.37 | 63.41 | 8.59 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.71 | 95.78 | 64.60 | 164.47 | 84.97 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.61 | 63.26 | 33.35 | 88.97 | 84.97 | 0.00 | 0.00 | 744.00 |
February | 127.47 | 84.39 | 43.08 | 116.21 | 84.86 | 0.00 | 0.00 | 672.00 |
March | 114.99 | 63.84 | 51.15 | 101.70 | 59.95 | 0.00 | 0.00 | 744.00 |
April | 89.19 | 35.26 | 53.93 | 69.85 | 43.22 | 0.00 | 0.00 | 720.00 |
May | 78.16 | 16.29 | 61.87 | 63.41 | 27.49 | 0.00 | 0.00 | 744.00 |
June | 73.34 | 11.20 | 62.15 | 69.90 | 16.22 | 0.00 | 0.00 | 720.00 |
July | 76.88 | 13.34 | 63.54 | 83.23 | 8.59 | 0.00 | 0.00 | 744.00 |
August | 102.67 | 38.07 | 64.60 | 107.98 | 12.82 | 0.00 | 0.00 | 744.00 |
September | 111.43 | 57.65 | 53.79 | 116.67 | 26.05 | 0.00 | 0.00 | 720.00 |
October | 152.71 | 95.78 | 56.92 | 164.47 | 45.22 | 0.00 | 0.00 | 744.00 |
November | 105.85 | 63.57 | 42.28 | 104.55 | 62.08 | 0.00 | 0.00 | 720.00 |
December | 104.69 | 74.32 | 30.37 | 102.82 | 78.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.72 | 51.25 | 51.47 | 99.10 | 45.59 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.34 | 11.20 | 30.37 | 63.41 | 8.59 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.71 | 95.78 | 64.60 | 164.47 | 84.97 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.67 | 75.74 | 39.93 | 106.76 | 100.70 | 0.00 | 0.00 | 744.00 |
February | 152.63 | 101.05 | 51.58 | 139.42 | 100.55 | 0.00 | 0.00 | 672.00 |
March | 137.69 | 76.44 | 61.25 | 121.97 | 71.05 | 0.00 | 0.00 | 744.00 |
April | 106.79 | 42.22 | 64.57 | 83.80 | 51.29 | 0.00 | 0.00 | 720.00 |
May | 93.58 | 19.51 | 74.08 | 76.02 | 32.67 | 0.00 | 0.00 | 744.00 |
June | 87.82 | 13.41 | 74.41 | 83.63 | 19.32 | 0.00 | 0.00 | 720.00 |
July | 92.06 | 15.98 | 76.08 | 99.46 | 10.26 | 0.00 | 0.00 | 744.00 |
August | 122.94 | 45.59 | 77.35 | 129.08 | 15.31 | 0.00 | 0.00 | 744.00 |
September | 133.43 | 69.02 | 64.40 | 139.62 | 31.01 | 0.00 | 0.00 | 720.00 |
October | 182.85 | 114.69 | 68.16 | 196.93 | 53.77 | 0.00 | 0.00 | 744.00 |
November | 126.74 | 76.12 | 50.62 | 125.32 | 73.69 | 0.00 | 0.00 | 720.00 |
December | 125.35 | 88.99 | 36.37 | 123.27 | 92.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 122.99 | 61.36 | 61.63 | 118.72 | 54.10 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 87.82 | 13.41 | 36.37 | 76.02 | 10.26 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 182.85 | 114.69 | 77.35 | 196.93 | 100.70 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258749E+09 | 0.169433E+09 | 89316326.44 | 0.234852E+09 | 0.252177E+09 |
February | 0.308379E+09 | 0.204166E+09 | 0.104212E+09 | 0.277580E+09 | 0.226421E+09 |
March | 0.307997E+09 | 0.170990E+09 | 0.137007E+09 | 0.268296E+09 | 0.181461E+09 |
April | 0.231174E+09 | 91392890.91 | 0.139781E+09 | 0.174606E+09 | 0.130823E+09 |
May | 0.209341E+09 | 43639964.46 | 0.165701E+09 | 0.159439E+09 | 90226334.47 |
June | 0.190110E+09 | 29024665.61 | 0.161085E+09 | 0.178403E+09 | 46173358.61 |
July | 0.205925E+09 | 35739716.11 | 0.170185E+09 | 0.221940E+09 | 24147105.62 |
August | 0.274997E+09 | 0.101975E+09 | 0.173022E+09 | 0.288669E+09 | 35315179.82 |
September | 0.288835E+09 | 0.149416E+09 | 0.139418E+09 | 0.301222E+09 | 70860696.86 |
October | 0.409007E+09 | 0.256550E+09 | 0.152458E+09 | 0.436145E+09 | 0.132436E+09 |
November | 0.274367E+09 | 0.164785E+09 | 0.109583E+09 | 0.265160E+09 | 0.180059E+09 |
December | 0.280402E+09 | 0.199057E+09 | 81345888.24 | 0.272050E+09 | 0.229326E+09 |
Annual Sum or Average | 0.323928E+10 | 0.161617E+10 | 0.162311E+10 | 0.307836E+10 | 0.159943E+10 |
Minimum of Months | 0.190110E+09 | 29024665.61 | 81345888.24 | 0.159439E+09 | 24147105.62 |
Maximum of Months | 0.409007E+09 | 0.256550E+09 | 0.173022E+09 | 0.436145E+09 | 0.252177E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258749E+09 | 0.169433E+09 | 89316326.44 | 0.234852E+09 | 0.252177E+09 |
February | 0.308379E+09 | 0.204166E+09 | 0.104212E+09 | 0.277580E+09 | 0.226421E+09 |
March | 0.307997E+09 | 0.170990E+09 | 0.137007E+09 | 0.268296E+09 | 0.181461E+09 |
April | 0.231174E+09 | 91392890.91 | 0.139781E+09 | 0.174606E+09 | 0.130823E+09 |
May | 0.209341E+09 | 43639964.46 | 0.165701E+09 | 0.159439E+09 | 90226334.47 |
June | 0.190110E+09 | 29024665.61 | 0.161085E+09 | 0.178403E+09 | 46173358.61 |
July | 0.205925E+09 | 35739716.11 | 0.170185E+09 | 0.221940E+09 | 24147105.62 |
August | 0.274997E+09 | 0.101975E+09 | 0.173022E+09 | 0.288669E+09 | 35315179.82 |
September | 0.288835E+09 | 0.149416E+09 | 0.139418E+09 | 0.301222E+09 | 70860696.86 |
October | 0.409007E+09 | 0.256550E+09 | 0.152458E+09 | 0.436145E+09 | 0.132436E+09 |
November | 0.274367E+09 | 0.164785E+09 | 0.109583E+09 | 0.265160E+09 | 0.180059E+09 |
December | 0.280402E+09 | 0.199057E+09 | 81345888.24 | 0.272050E+09 | 0.229326E+09 |
Annual Sum or Average | 0.323928E+10 | 0.161617E+10 | 0.162311E+10 | 0.307836E+10 | 0.159943E+10 |
Minimum of Months | 0.190110E+09 | 29024665.61 | 81345888.24 | 0.159439E+09 | 24147105.62 |
Maximum of Months | 0.409007E+09 | 0.256550E+09 | 0.173022E+09 | 0.436145E+09 | 0.252177E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258749E+09 | 0.169433E+09 | 89316326.44 | 0.234852E+09 | 0.252177E+09 |
February | 0.308379E+09 | 0.204166E+09 | 0.104212E+09 | 0.277580E+09 | 0.226421E+09 |
March | 0.307997E+09 | 0.170990E+09 | 0.137007E+09 | 0.268296E+09 | 0.181461E+09 |
April | 0.231174E+09 | 91392890.91 | 0.139781E+09 | 0.174606E+09 | 0.130823E+09 |
May | 0.209341E+09 | 43639964.46 | 0.165701E+09 | 0.159439E+09 | 90226334.47 |
June | 0.190110E+09 | 29024665.61 | 0.161085E+09 | 0.178403E+09 | 46173358.61 |
July | 0.205925E+09 | 35739716.11 | 0.170185E+09 | 0.221940E+09 | 24147105.62 |
August | 0.274997E+09 | 0.101975E+09 | 0.173022E+09 | 0.288669E+09 | 35315179.82 |
September | 0.288835E+09 | 0.149416E+09 | 0.139418E+09 | 0.301222E+09 | 70860696.86 |
October | 0.409007E+09 | 0.256550E+09 | 0.152458E+09 | 0.436145E+09 | 0.132436E+09 |
November | 0.274367E+09 | 0.164785E+09 | 0.109583E+09 | 0.265160E+09 | 0.180059E+09 |
December | 0.280402E+09 | 0.199057E+09 | 81345888.24 | 0.272050E+09 | 0.229326E+09 |
Annual Sum or Average | 0.323928E+10 | 0.161617E+10 | 0.162311E+10 | 0.307836E+10 | 0.159943E+10 |
Minimum of Months | 0.190110E+09 | 29024665.61 | 81345888.24 | 0.159439E+09 | 24147105.62 |
Maximum of Months | 0.409007E+09 | 0.256550E+09 | 0.173022E+09 | 0.436145E+09 | 0.252177E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258749E+09 | 0.169433E+09 | 89316326.44 | 0.234852E+09 | 0.252177E+09 |
February | 0.308379E+09 | 0.204166E+09 | 0.104212E+09 | 0.277580E+09 | 0.226421E+09 |
March | 0.307997E+09 | 0.170990E+09 | 0.137007E+09 | 0.268296E+09 | 0.181461E+09 |
April | 0.231174E+09 | 91392890.91 | 0.139781E+09 | 0.174606E+09 | 0.130823E+09 |
May | 0.209341E+09 | 43639964.46 | 0.165701E+09 | 0.159439E+09 | 90226334.47 |
June | 0.190110E+09 | 29024665.61 | 0.161085E+09 | 0.178403E+09 | 46173358.61 |
July | 0.205925E+09 | 35739716.11 | 0.170185E+09 | 0.221940E+09 | 24147105.62 |
August | 0.274997E+09 | 0.101975E+09 | 0.173022E+09 | 0.288669E+09 | 35315179.82 |
September | 0.288835E+09 | 0.149416E+09 | 0.139418E+09 | 0.301222E+09 | 70860696.86 |
October | 0.409007E+09 | 0.256550E+09 | 0.152458E+09 | 0.436145E+09 | 0.132436E+09 |
November | 0.274367E+09 | 0.164785E+09 | 0.109583E+09 | 0.265160E+09 | 0.180059E+09 |
December | 0.280402E+09 | 0.199057E+09 | 81345888.24 | 0.272050E+09 | 0.229326E+09 |
Annual Sum or Average | 0.323928E+10 | 0.161617E+10 | 0.162311E+10 | 0.307836E+10 | 0.159943E+10 |
Minimum of Months | 0.190110E+09 | 29024665.61 | 81345888.24 | 0.159439E+09 | 24147105.62 |
Maximum of Months | 0.409007E+09 | 0.256550E+09 | 0.173022E+09 | 0.436145E+09 | 0.252177E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.311521E+09 | 0.203989E+09 | 0.107532E+09 | 0.283232E+09 | 0.300728E+09 |
February | 0.371271E+09 | 0.245805E+09 | 0.125466E+09 | 0.334725E+09 | 0.269978E+09 |
March | 0.370812E+09 | 0.205863E+09 | 0.164949E+09 | 0.323433E+09 | 0.216433E+09 |
April | 0.278321E+09 | 0.110032E+09 | 0.168289E+09 | 0.210552E+09 | 0.156179E+09 |
May | 0.252035E+09 | 52540220.37 | 0.199495E+09 | 0.192153E+09 | 0.107872E+09 |
June | 0.228882E+09 | 34944169.78 | 0.193938E+09 | 0.214546E+09 | 55339065.18 |
July | 0.247923E+09 | 43028737.16 | 0.204894E+09 | 0.266601E+09 | 29064299.66 |
August | 0.331082E+09 | 0.122773E+09 | 0.208309E+09 | 0.346887E+09 | 42463589.73 |
September | 0.347742E+09 | 0.179890E+09 | 0.167852E+09 | 0.362381E+09 | 84913876.56 |
October | 0.492423E+09 | 0.308872E+09 | 0.183551E+09 | 0.525029E+09 | 0.158424E+09 |
November | 0.330324E+09 | 0.198392E+09 | 0.131932E+09 | 0.319527E+09 | 0.215024E+09 |
December | 0.337590E+09 | 0.239654E+09 | 97936168.08 | 0.327862E+09 | 0.273663E+09 |
Annual Sum or Average | 0.389993E+10 | 0.194578E+10 | 0.195414E+10 | 0.370693E+10 | 0.191008E+10 |
Minimum of Months | 0.228882E+09 | 34944169.78 | 97936168.08 | 0.192153E+09 | 29064299.66 |
Maximum of Months | 0.492423E+09 | 0.308872E+09 | 0.208309E+09 | 0.525029E+09 | 0.300728E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.311521E+09 | 0.203989E+09 | 0.107532E+09 | 0.283232E+09 | 0.300728E+09 |
February | 0.371271E+09 | 0.245805E+09 | 0.125466E+09 | 0.334725E+09 | 0.269978E+09 |
March | 0.370812E+09 | 0.205863E+09 | 0.164949E+09 | 0.323433E+09 | 0.216433E+09 |
April | 0.278321E+09 | 0.110032E+09 | 0.168289E+09 | 0.210552E+09 | 0.156179E+09 |
May | 0.252035E+09 | 52540220.37 | 0.199495E+09 | 0.192153E+09 | 0.107872E+09 |
June | 0.228882E+09 | 34944169.78 | 0.193938E+09 | 0.214546E+09 | 55339065.18 |
July | 0.247923E+09 | 43028737.16 | 0.204894E+09 | 0.266601E+09 | 29064299.66 |
August | 0.331082E+09 | 0.122773E+09 | 0.208309E+09 | 0.346887E+09 | 42463589.73 |
September | 0.347742E+09 | 0.179890E+09 | 0.167852E+09 | 0.362381E+09 | 84913876.56 |
October | 0.492423E+09 | 0.308872E+09 | 0.183551E+09 | 0.525029E+09 | 0.158424E+09 |
November | 0.330324E+09 | 0.198392E+09 | 0.131932E+09 | 0.319527E+09 | 0.215024E+09 |
December | 0.337590E+09 | 0.239654E+09 | 97936168.08 | 0.327862E+09 | 0.273663E+09 |
Annual Sum or Average | 0.389993E+10 | 0.194578E+10 | 0.195414E+10 | 0.370693E+10 | 0.191008E+10 |
Minimum of Months | 0.228882E+09 | 34944169.78 | 97936168.08 | 0.192153E+09 | 29064299.66 |
Maximum of Months | 0.492423E+09 | 0.308872E+09 | 0.208309E+09 | 0.525029E+09 | 0.300728E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258749E+09 | 0.169433E+09 | 89316326.44 | 0.232506E+09 | 0.264444E+09 |
February | 0.308379E+09 | 0.204166E+09 | 0.104212E+09 | 0.274868E+09 | 0.237891E+09 |
March | 0.307997E+09 | 0.170990E+09 | 0.137007E+09 | 0.265209E+09 | 0.194254E+09 |
April | 0.231174E+09 | 91392890.91 | 0.139781E+09 | 0.171385E+09 | 0.140899E+09 |
May | 0.209341E+09 | 43639964.46 | 0.165701E+09 | 0.156893E+09 | 94302325.98 |
June | 0.190110E+09 | 29024665.61 | 0.161085E+09 | 0.177776E+09 | 47360500.43 |
July | 0.205925E+09 | 35739716.11 | 0.170185E+09 | 0.221926E+09 | 24789064.58 |
August | 0.274997E+09 | 0.101975E+09 | 0.173022E+09 | 0.289011E+09 | 35730092.97 |
September | 0.288835E+09 | 0.149416E+09 | 0.139418E+09 | 0.300862E+09 | 71798344.11 |
October | 0.409007E+09 | 0.256550E+09 | 0.152458E+09 | 0.434195E+09 | 0.135962E+09 |
November | 0.274367E+09 | 0.164785E+09 | 0.109583E+09 | 0.262027E+09 | 0.190345E+09 |
December | 0.280402E+09 | 0.199057E+09 | 81345888.24 | 0.269563E+09 | 0.241573E+09 |
Annual Sum or Average | 0.323928E+10 | 0.161617E+10 | 0.162311E+10 | 0.305622E+10 | 0.167935E+10 |
Minimum of Months | 0.190110E+09 | 29024665.61 | 81345888.24 | 0.156893E+09 | 24789064.58 |
Maximum of Months | 0.409007E+09 | 0.256550E+09 | 0.173022E+09 | 0.434195E+09 | 0.264444E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258749E+09 | 0.169433E+09 | 89316326.44 | 0.232506E+09 | 0.264444E+09 |
February | 0.308379E+09 | 0.204166E+09 | 0.104212E+09 | 0.274868E+09 | 0.237891E+09 |
March | 0.307997E+09 | 0.170990E+09 | 0.137007E+09 | 0.265209E+09 | 0.194254E+09 |
April | 0.231174E+09 | 91392890.91 | 0.139781E+09 | 0.171385E+09 | 0.140899E+09 |
May | 0.209341E+09 | 43639964.46 | 0.165701E+09 | 0.156893E+09 | 94302325.98 |
June | 0.190110E+09 | 29024665.61 | 0.161085E+09 | 0.177776E+09 | 47360500.43 |
July | 0.205925E+09 | 35739716.11 | 0.170185E+09 | 0.221926E+09 | 24789064.58 |
August | 0.274997E+09 | 0.101975E+09 | 0.173022E+09 | 0.289011E+09 | 35730092.97 |
September | 0.288835E+09 | 0.149416E+09 | 0.139418E+09 | 0.300862E+09 | 71798344.11 |
October | 0.409007E+09 | 0.256550E+09 | 0.152458E+09 | 0.434195E+09 | 0.135962E+09 |
November | 0.274367E+09 | 0.164785E+09 | 0.109583E+09 | 0.262027E+09 | 0.190345E+09 |
December | 0.280402E+09 | 0.199057E+09 | 81345888.24 | 0.269563E+09 | 0.241573E+09 |
Annual Sum or Average | 0.323928E+10 | 0.161617E+10 | 0.162311E+10 | 0.305622E+10 | 0.167935E+10 |
Minimum of Months | 0.190110E+09 | 29024665.61 | 81345888.24 | 0.156893E+09 | 24789064.58 |
Maximum of Months | 0.409007E+09 | 0.256550E+09 | 0.173022E+09 | 0.434195E+09 | 0.264444E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.311521E+09 | 0.203989E+09 | 0.107532E+09 | 0.280416E+09 | 0.315255E+09 |
February | 0.371271E+09 | 0.245805E+09 | 0.125466E+09 | 0.331467E+09 | 0.283562E+09 |
March | 0.370812E+09 | 0.205863E+09 | 0.164949E+09 | 0.319725E+09 | 0.231561E+09 |
April | 0.278321E+09 | 0.110032E+09 | 0.168289E+09 | 0.206676E+09 | 0.168097E+09 |
May | 0.252035E+09 | 52540220.37 | 0.199495E+09 | 0.189096E+09 | 0.112708E+09 |
June | 0.228882E+09 | 34944169.78 | 0.193938E+09 | 0.213786E+09 | 56748558.77 |
July | 0.247923E+09 | 43028737.16 | 0.204894E+09 | 0.266572E+09 | 29829484.54 |
August | 0.331082E+09 | 0.122773E+09 | 0.208309E+09 | 0.347286E+09 | 42957559.99 |
September | 0.347742E+09 | 0.179890E+09 | 0.167852E+09 | 0.361958E+09 | 86021681.93 |
October | 0.492423E+09 | 0.308872E+09 | 0.183551E+09 | 0.522727E+09 | 0.162590E+09 |
November | 0.330324E+09 | 0.198392E+09 | 0.131932E+09 | 0.315795E+09 | 0.227180E+09 |
December | 0.337590E+09 | 0.239654E+09 | 97936168.08 | 0.324886E+09 | 0.288140E+09 |
Annual Sum or Average | 0.389993E+10 | 0.194578E+10 | 0.195414E+10 | 0.368039E+10 | 0.200465E+10 |
Minimum of Months | 0.228882E+09 | 34944169.78 | 97936168.08 | 0.189096E+09 | 29829484.54 |
Maximum of Months | 0.492423E+09 | 0.308872E+09 | 0.208309E+09 | 0.522727E+09 | 0.315255E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258749E+09 | 0.169433E+09 | 89316326.44 | 0.233280E+09 | 0.256315E+09 |
February | 0.308379E+09 | 0.204166E+09 | 0.104212E+09 | 0.275514E+09 | 0.231487E+09 |
March | 0.307997E+09 | 0.170990E+09 | 0.137007E+09 | 0.266201E+09 | 0.187699E+09 |
April | 0.231174E+09 | 91392890.91 | 0.139781E+09 | 0.172558E+09 | 0.136747E+09 |
May | 0.209341E+09 | 43639964.46 | 0.165701E+09 | 0.157330E+09 | 95463549.24 |
June | 0.190110E+09 | 29024665.61 | 0.161085E+09 | 0.177473E+09 | 50932891.43 |
July | 0.205925E+09 | 35739716.11 | 0.170185E+09 | 0.221001E+09 | 29465844.49 |
August | 0.274997E+09 | 0.101975E+09 | 0.173022E+09 | 0.288140E+09 | 40568859.96 |
September | 0.288835E+09 | 0.149416E+09 | 0.139418E+09 | 0.300746E+09 | 75780883.21 |
October | 0.409007E+09 | 0.256550E+09 | 0.152458E+09 | 0.434797E+09 | 0.137323E+09 |
November | 0.274367E+09 | 0.164785E+09 | 0.109583E+09 | 0.263256E+09 | 0.185141E+09 |
December | 0.280402E+09 | 0.199057E+09 | 81345888.24 | 0.270429E+09 | 0.234166E+09 |
Annual Sum or Average | 0.323928E+10 | 0.161617E+10 | 0.162311E+10 | 0.306073E+10 | 0.166109E+10 |
Minimum of Months | 0.190110E+09 | 29024665.61 | 81345888.24 | 0.157330E+09 | 29465844.49 |
Maximum of Months | 0.409007E+09 | 0.256550E+09 | 0.173022E+09 | 0.434797E+09 | 0.256315E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258749E+09 | 0.169433E+09 | 89316326.44 | 0.233280E+09 | 0.256315E+09 |
February | 0.308379E+09 | 0.204166E+09 | 0.104212E+09 | 0.275514E+09 | 0.231487E+09 |
March | 0.307997E+09 | 0.170990E+09 | 0.137007E+09 | 0.266201E+09 | 0.187699E+09 |
April | 0.231174E+09 | 91392890.91 | 0.139781E+09 | 0.172558E+09 | 0.136747E+09 |
May | 0.209341E+09 | 43639964.46 | 0.165701E+09 | 0.157330E+09 | 95463549.24 |
June | 0.190110E+09 | 29024665.61 | 0.161085E+09 | 0.177473E+09 | 50932891.43 |
July | 0.205925E+09 | 35739716.11 | 0.170185E+09 | 0.221001E+09 | 29465844.49 |
August | 0.274997E+09 | 0.101975E+09 | 0.173022E+09 | 0.288140E+09 | 40568859.96 |
September | 0.288835E+09 | 0.149416E+09 | 0.139418E+09 | 0.300746E+09 | 75780883.21 |
October | 0.409007E+09 | 0.256550E+09 | 0.152458E+09 | 0.434797E+09 | 0.137323E+09 |
November | 0.274367E+09 | 0.164785E+09 | 0.109583E+09 | 0.263256E+09 | 0.185141E+09 |
December | 0.280402E+09 | 0.199057E+09 | 81345888.24 | 0.270429E+09 | 0.234166E+09 |
Annual Sum or Average | 0.323928E+10 | 0.161617E+10 | 0.162311E+10 | 0.306073E+10 | 0.166109E+10 |
Minimum of Months | 0.190110E+09 | 29024665.61 | 81345888.24 | 0.157330E+09 | 29465844.49 |
Maximum of Months | 0.409007E+09 | 0.256550E+09 | 0.173022E+09 | 0.434797E+09 | 0.256315E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.309818E+09 | 0.202874E+09 | 0.106945E+09 | 0.279828E+09 | 0.303905E+09 |
February | 0.369243E+09 | 0.244462E+09 | 0.124781E+09 | 0.330445E+09 | 0.274431E+09 |
March | 0.368786E+09 | 0.204738E+09 | 0.164048E+09 | 0.319176E+09 | 0.222548E+09 |
April | 0.276800E+09 | 0.109431E+09 | 0.167369E+09 | 0.206955E+09 | 0.162251E+09 |
May | 0.250658E+09 | 52253115.34 | 0.198405E+09 | 0.188586E+09 | 0.113394E+09 |
June | 0.227631E+09 | 34753218.03 | 0.192878E+09 | 0.212262E+09 | 60592816.01 |
July | 0.246568E+09 | 42793607.45 | 0.203775E+09 | 0.264036E+09 | 35129583.41 |
August | 0.329273E+09 | 0.122102E+09 | 0.207171E+09 | 0.344375E+09 | 48385739.23 |
September | 0.345842E+09 | 0.178907E+09 | 0.166935E+09 | 0.359845E+09 | 90186002.95 |
October | 0.489732E+09 | 0.307184E+09 | 0.182548E+09 | 0.520586E+09 | 0.163237E+09 |
November | 0.328519E+09 | 0.197308E+09 | 0.131211E+09 | 0.315541E+09 | 0.219764E+09 |
December | 0.335745E+09 | 0.238344E+09 | 97400997.77 | 0.324158E+09 | 0.277804E+09 |
Annual Sum or Average | 0.387862E+10 | 0.193515E+10 | 0.194347E+10 | 0.366579E+10 | 0.197163E+10 |
Minimum of Months | 0.227631E+09 | 34753218.03 | 97400997.77 | 0.188586E+09 | 35129583.41 |
Maximum of Months | 0.489732E+09 | 0.307184E+09 | 0.207171E+09 | 0.520586E+09 | 0.303905E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258749E+09 | 0.169433E+09 | 89316326.44 | 0.233700E+09 | 0.253144E+09 |
February | 0.308379E+09 | 0.204166E+09 | 0.104212E+09 | 0.275892E+09 | 0.228997E+09 |
March | 0.307997E+09 | 0.170990E+09 | 0.137007E+09 | 0.266766E+09 | 0.184947E+09 |
April | 0.231174E+09 | 91392890.91 | 0.139781E+09 | 0.173294E+09 | 0.134334E+09 |
May | 0.209341E+09 | 43639964.46 | 0.165701E+09 | 0.157906E+09 | 94181244.46 |
June | 0.190110E+09 | 29024665.61 | 0.161085E+09 | 0.177541E+09 | 50805744.36 |
July | 0.205925E+09 | 35739716.11 | 0.170185E+09 | 0.220984E+09 | 29595192.19 |
August | 0.274997E+09 | 0.101975E+09 | 0.173022E+09 | 0.288102E+09 | 40760289.23 |
September | 0.288835E+09 | 0.149416E+09 | 0.139418E+09 | 0.300792E+09 | 75630255.15 |
October | 0.409007E+09 | 0.256550E+09 | 0.152458E+09 | 0.435182E+09 | 0.136228E+09 |
November | 0.274367E+09 | 0.164785E+09 | 0.109583E+09 | 0.264052E+09 | 0.182227E+09 |
December | 0.280402E+09 | 0.199057E+09 | 81345888.24 | 0.270826E+09 | 0.231463E+09 |
Annual Sum or Average | 0.323928E+10 | 0.161617E+10 | 0.162311E+10 | 0.306504E+10 | 0.164231E+10 |
Minimum of Months | 0.190110E+09 | 29024665.61 | 81345888.24 | 0.157906E+09 | 29595192.19 |
Maximum of Months | 0.409007E+09 | 0.256550E+09 | 0.173022E+09 | 0.435182E+09 | 0.253144E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258749E+09 | 0.169433E+09 | 89316326.44 | 0.233700E+09 | 0.253144E+09 |
February | 0.308379E+09 | 0.204166E+09 | 0.104212E+09 | 0.275892E+09 | 0.228997E+09 |
March | 0.307997E+09 | 0.170990E+09 | 0.137007E+09 | 0.266766E+09 | 0.184947E+09 |
April | 0.231174E+09 | 91392890.91 | 0.139781E+09 | 0.173294E+09 | 0.134334E+09 |
May | 0.209341E+09 | 43639964.46 | 0.165701E+09 | 0.157906E+09 | 94181244.46 |
June | 0.190110E+09 | 29024665.61 | 0.161085E+09 | 0.177541E+09 | 50805744.36 |
July | 0.205925E+09 | 35739716.11 | 0.170185E+09 | 0.220984E+09 | 29595192.19 |
August | 0.274997E+09 | 0.101975E+09 | 0.173022E+09 | 0.288102E+09 | 40760289.23 |
September | 0.288835E+09 | 0.149416E+09 | 0.139418E+09 | 0.300792E+09 | 75630255.15 |
October | 0.409007E+09 | 0.256550E+09 | 0.152458E+09 | 0.435182E+09 | 0.136228E+09 |
November | 0.274367E+09 | 0.164785E+09 | 0.109583E+09 | 0.264052E+09 | 0.182227E+09 |
December | 0.280402E+09 | 0.199057E+09 | 81345888.24 | 0.270826E+09 | 0.231463E+09 |
Annual Sum or Average | 0.323928E+10 | 0.161617E+10 | 0.162311E+10 | 0.306504E+10 | 0.164231E+10 |
Minimum of Months | 0.190110E+09 | 29024665.61 | 81345888.24 | 0.157906E+09 | 29595192.19 |
Maximum of Months | 0.409007E+09 | 0.256550E+09 | 0.173022E+09 | 0.435182E+09 | 0.253144E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.309818E+09 | 0.202874E+09 | 0.106945E+09 | 0.280339E+09 | 0.300126E+09 |
February | 0.369243E+09 | 0.244462E+09 | 0.124781E+09 | 0.330904E+09 | 0.271465E+09 |
March | 0.368786E+09 | 0.204738E+09 | 0.164048E+09 | 0.319860E+09 | 0.219275E+09 |
April | 0.276800E+09 | 0.109431E+09 | 0.167369E+09 | 0.207838E+09 | 0.159384E+09 |
May | 0.250658E+09 | 52253115.34 | 0.198405E+09 | 0.189278E+09 | 0.111871E+09 |
June | 0.227631E+09 | 34753218.03 | 0.192878E+09 | 0.212344E+09 | 60442126.25 |
July | 0.246568E+09 | 42793607.45 | 0.203775E+09 | 0.264015E+09 | 35282701.38 |
August | 0.329273E+09 | 0.122102E+09 | 0.207171E+09 | 0.344330E+09 | 48612668.39 |
September | 0.345842E+09 | 0.178907E+09 | 0.166935E+09 | 0.359902E+09 | 90006058.07 |
October | 0.489732E+09 | 0.307184E+09 | 0.182548E+09 | 0.521048E+09 | 0.161936E+09 |
November | 0.328519E+09 | 0.197308E+09 | 0.131211E+09 | 0.316495E+09 | 0.216300E+09 |
December | 0.335745E+09 | 0.238344E+09 | 97400997.77 | 0.324638E+09 | 0.274585E+09 |
Annual Sum or Average | 0.387862E+10 | 0.193515E+10 | 0.194347E+10 | 0.367099E+10 | 0.194928E+10 |
Minimum of Months | 0.227631E+09 | 34753218.03 | 97400997.77 | 0.189278E+09 | 35282701.38 |
Maximum of Months | 0.489732E+09 | 0.307184E+09 | 0.207171E+09 | 0.521048E+09 | 0.300126E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258749E+09 | 0.169433E+09 | 89316326.44 | 0.234183E+09 | 0.250612E+09 |
February | 0.308379E+09 | 0.204166E+09 | 0.104212E+09 | 0.276371E+09 | 0.226957E+09 |
March | 0.307997E+09 | 0.170990E+09 | 0.137007E+09 | 0.267415E+09 | 0.182641E+09 |
April | 0.231174E+09 | 91392890.91 | 0.139781E+09 | 0.174253E+09 | 0.131993E+09 |
May | 0.209341E+09 | 43639964.46 | 0.165701E+09 | 0.159127E+09 | 91984926.25 |
June | 0.190110E+09 | 29024665.61 | 0.161085E+09 | 0.177951E+09 | 49961242.75 |
July | 0.205925E+09 | 35739716.11 | 0.170185E+09 | 0.221370E+09 | 28827211.55 |
August | 0.274997E+09 | 0.101975E+09 | 0.173022E+09 | 0.288451E+09 | 39955820.44 |
September | 0.288835E+09 | 0.149416E+09 | 0.139418E+09 | 0.301100E+09 | 74694125.16 |
October | 0.409007E+09 | 0.256550E+09 | 0.152458E+09 | 0.435911E+09 | 0.134484E+09 |
November | 0.274367E+09 | 0.164785E+09 | 0.109583E+09 | 0.265171E+09 | 0.179249E+09 |
December | 0.280402E+09 | 0.199057E+09 | 81345888.24 | 0.271256E+09 | 0.229417E+09 |
Annual Sum or Average | 0.323928E+10 | 0.161617E+10 | 0.162311E+10 | 0.307256E+10 | 0.162078E+10 |
Minimum of Months | 0.190110E+09 | 29024665.61 | 81345888.24 | 0.159127E+09 | 28827211.55 |
Maximum of Months | 0.409007E+09 | 0.256550E+09 | 0.173022E+09 | 0.435911E+09 | 0.250612E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258749E+09 | 0.169433E+09 | 89316326.44 | 0.234183E+09 | 0.250612E+09 |
February | 0.308379E+09 | 0.204166E+09 | 0.104212E+09 | 0.276371E+09 | 0.226957E+09 |
March | 0.307997E+09 | 0.170990E+09 | 0.137007E+09 | 0.267415E+09 | 0.182641E+09 |
April | 0.231174E+09 | 91392890.91 | 0.139781E+09 | 0.174253E+09 | 0.131993E+09 |
May | 0.209341E+09 | 43639964.46 | 0.165701E+09 | 0.159127E+09 | 91984926.25 |
June | 0.190110E+09 | 29024665.61 | 0.161085E+09 | 0.177951E+09 | 49961242.75 |
July | 0.205925E+09 | 35739716.11 | 0.170185E+09 | 0.221370E+09 | 28827211.55 |
August | 0.274997E+09 | 0.101975E+09 | 0.173022E+09 | 0.288451E+09 | 39955820.44 |
September | 0.288835E+09 | 0.149416E+09 | 0.139418E+09 | 0.301100E+09 | 74694125.16 |
October | 0.409007E+09 | 0.256550E+09 | 0.152458E+09 | 0.435911E+09 | 0.134484E+09 |
November | 0.274367E+09 | 0.164785E+09 | 0.109583E+09 | 0.265171E+09 | 0.179249E+09 |
December | 0.280402E+09 | 0.199057E+09 | 81345888.24 | 0.271256E+09 | 0.229417E+09 |
Annual Sum or Average | 0.323928E+10 | 0.161617E+10 | 0.162311E+10 | 0.307256E+10 | 0.162078E+10 |
Minimum of Months | 0.190110E+09 | 29024665.61 | 81345888.24 | 0.159127E+09 | 28827211.55 |
Maximum of Months | 0.409007E+09 | 0.256550E+09 | 0.173022E+09 | 0.435911E+09 | 0.250612E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.309818E+09 | 0.202874E+09 | 0.106945E+09 | 0.280928E+09 | 0.297109E+09 |
February | 0.369243E+09 | 0.244462E+09 | 0.124781E+09 | 0.331488E+09 | 0.269036E+09 |
March | 0.368786E+09 | 0.204738E+09 | 0.164048E+09 | 0.320644E+09 | 0.216535E+09 |
April | 0.276800E+09 | 0.109431E+09 | 0.167369E+09 | 0.208990E+09 | 0.156609E+09 |
May | 0.250658E+09 | 52253115.34 | 0.198405E+09 | 0.190742E+09 | 0.109270E+09 |
June | 0.227631E+09 | 34753218.03 | 0.192878E+09 | 0.212839E+09 | 59445681.78 |
July | 0.246568E+09 | 42793607.45 | 0.203775E+09 | 0.264481E+09 | 34377071.52 |
August | 0.329273E+09 | 0.122102E+09 | 0.207171E+09 | 0.344751E+09 | 47662614.75 |
September | 0.345842E+09 | 0.178907E+09 | 0.166935E+09 | 0.360273E+09 | 88898767.70 |
October | 0.489732E+09 | 0.307184E+09 | 0.182548E+09 | 0.521922E+09 | 0.159870E+09 |
November | 0.328519E+09 | 0.197308E+09 | 0.131211E+09 | 0.317835E+09 | 0.212763E+09 |
December | 0.335745E+09 | 0.238344E+09 | 97400997.77 | 0.325161E+09 | 0.272148E+09 |
Annual Sum or Average | 0.387862E+10 | 0.193515E+10 | 0.194347E+10 | 0.368005E+10 | 0.192372E+10 |
Minimum of Months | 0.227631E+09 | 34753218.03 | 97400997.77 | 0.190742E+09 | 34377071.52 |
Maximum of Months | 0.489732E+09 | 0.307184E+09 | 0.207171E+09 | 0.521922E+09 | 0.297109E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258749E+09 | 0.169433E+09 | 89316326.44 | 0.236229E+09 | 0.242817E+09 |
February | 0.308379E+09 | 0.204166E+09 | 0.104212E+09 | 0.278462E+09 | 0.220419E+09 |
March | 0.307997E+09 | 0.170990E+09 | 0.137007E+09 | 0.269350E+09 | 0.176455E+09 |
April | 0.231174E+09 | 91392890.91 | 0.139781E+09 | 0.176445E+09 | 0.126342E+09 |
May | 0.209341E+09 | 43639964.46 | 0.165701E+09 | 0.161795E+09 | 86674170.79 |
June | 0.190110E+09 | 29024665.61 | 0.161085E+09 | 0.178176E+09 | 47285286.07 |
July | 0.205925E+09 | 35739716.11 | 0.170185E+09 | 0.220968E+09 | 26384949.00 |
August | 0.274997E+09 | 0.101975E+09 | 0.173022E+09 | 0.288030E+09 | 37347951.04 |
September | 0.288835E+09 | 0.149416E+09 | 0.139418E+09 | 0.301299E+09 | 71968946.39 |
October | 0.409007E+09 | 0.256550E+09 | 0.152458E+09 | 0.437551E+09 | 0.130051E+09 |
November | 0.274367E+09 | 0.164785E+09 | 0.109583E+09 | 0.267766E+09 | 0.172486E+09 |
December | 0.280402E+09 | 0.199057E+09 | 81345888.24 | 0.273049E+09 | 0.223318E+09 |
Annual Sum or Average | 0.323928E+10 | 0.161617E+10 | 0.162311E+10 | 0.308912E+10 | 0.156155E+10 |
Minimum of Months | 0.190110E+09 | 29024665.61 | 81345888.24 | 0.161795E+09 | 26384949.00 |
Maximum of Months | 0.409007E+09 | 0.256550E+09 | 0.173022E+09 | 0.437551E+09 | 0.242817E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258749E+09 | 0.169433E+09 | 89316326.44 | 0.236229E+09 | 0.242817E+09 |
February | 0.308379E+09 | 0.204166E+09 | 0.104212E+09 | 0.278462E+09 | 0.220419E+09 |
March | 0.307997E+09 | 0.170990E+09 | 0.137007E+09 | 0.269350E+09 | 0.176455E+09 |
April | 0.231174E+09 | 91392890.91 | 0.139781E+09 | 0.176445E+09 | 0.126342E+09 |
May | 0.209341E+09 | 43639964.46 | 0.165701E+09 | 0.161795E+09 | 86674170.79 |
June | 0.190110E+09 | 29024665.61 | 0.161085E+09 | 0.178176E+09 | 47285286.07 |
July | 0.205925E+09 | 35739716.11 | 0.170185E+09 | 0.220968E+09 | 26384949.00 |
August | 0.274997E+09 | 0.101975E+09 | 0.173022E+09 | 0.288030E+09 | 37347951.04 |
September | 0.288835E+09 | 0.149416E+09 | 0.139418E+09 | 0.301299E+09 | 71968946.39 |
October | 0.409007E+09 | 0.256550E+09 | 0.152458E+09 | 0.437551E+09 | 0.130051E+09 |
November | 0.274367E+09 | 0.164785E+09 | 0.109583E+09 | 0.267766E+09 | 0.172486E+09 |
December | 0.280402E+09 | 0.199057E+09 | 81345888.24 | 0.273049E+09 | 0.223318E+09 |
Annual Sum or Average | 0.323928E+10 | 0.161617E+10 | 0.162311E+10 | 0.308912E+10 | 0.156155E+10 |
Minimum of Months | 0.190110E+09 | 29024665.61 | 81345888.24 | 0.161795E+09 | 26384949.00 |
Maximum of Months | 0.409007E+09 | 0.256550E+09 | 0.173022E+09 | 0.437551E+09 | 0.242817E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258749E+09 | 0.169433E+09 | 89316326.44 | 0.236229E+09 | 0.242817E+09 |
February | 0.308379E+09 | 0.204166E+09 | 0.104212E+09 | 0.278462E+09 | 0.220419E+09 |
March | 0.307997E+09 | 0.170990E+09 | 0.137007E+09 | 0.269350E+09 | 0.176455E+09 |
April | 0.231174E+09 | 91392890.91 | 0.139781E+09 | 0.176445E+09 | 0.126342E+09 |
May | 0.209341E+09 | 43639964.46 | 0.165701E+09 | 0.161795E+09 | 86674170.79 |
June | 0.190110E+09 | 29024665.61 | 0.161085E+09 | 0.178176E+09 | 47285286.07 |
July | 0.205925E+09 | 35739716.11 | 0.170185E+09 | 0.220968E+09 | 26384949.00 |
August | 0.274997E+09 | 0.101975E+09 | 0.173022E+09 | 0.288030E+09 | 37347951.04 |
September | 0.288835E+09 | 0.149416E+09 | 0.139418E+09 | 0.301299E+09 | 71968946.39 |
October | 0.409007E+09 | 0.256550E+09 | 0.152458E+09 | 0.437551E+09 | 0.130051E+09 |
November | 0.274367E+09 | 0.164785E+09 | 0.109583E+09 | 0.267766E+09 | 0.172486E+09 |
December | 0.280402E+09 | 0.199057E+09 | 81345888.24 | 0.273049E+09 | 0.223318E+09 |
Annual Sum or Average | 0.323928E+10 | 0.161617E+10 | 0.162311E+10 | 0.308912E+10 | 0.156155E+10 |
Minimum of Months | 0.190110E+09 | 29024665.61 | 81345888.24 | 0.161795E+09 | 26384949.00 |
Maximum of Months | 0.409007E+09 | 0.256550E+09 | 0.173022E+09 | 0.437551E+09 | 0.242817E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258749E+09 | 0.169433E+09 | 89316326.44 | 0.236229E+09 | 0.242817E+09 |
February | 0.308379E+09 | 0.204166E+09 | 0.104212E+09 | 0.278462E+09 | 0.220419E+09 |
March | 0.307997E+09 | 0.170990E+09 | 0.137007E+09 | 0.269350E+09 | 0.176455E+09 |
April | 0.231174E+09 | 91392890.91 | 0.139781E+09 | 0.176445E+09 | 0.126342E+09 |
May | 0.209341E+09 | 43639964.46 | 0.165701E+09 | 0.161795E+09 | 86674170.79 |
June | 0.190110E+09 | 29024665.61 | 0.161085E+09 | 0.178176E+09 | 47285286.07 |
July | 0.205925E+09 | 35739716.11 | 0.170185E+09 | 0.220968E+09 | 26384949.00 |
August | 0.274997E+09 | 0.101975E+09 | 0.173022E+09 | 0.288030E+09 | 37347951.04 |
September | 0.288835E+09 | 0.149416E+09 | 0.139418E+09 | 0.301299E+09 | 71968946.39 |
October | 0.409007E+09 | 0.256550E+09 | 0.152458E+09 | 0.437551E+09 | 0.130051E+09 |
November | 0.274367E+09 | 0.164785E+09 | 0.109583E+09 | 0.267766E+09 | 0.172486E+09 |
December | 0.280402E+09 | 0.199057E+09 | 81345888.24 | 0.273049E+09 | 0.223318E+09 |
Annual Sum or Average | 0.323928E+10 | 0.161617E+10 | 0.162311E+10 | 0.308912E+10 | 0.156155E+10 |
Minimum of Months | 0.190110E+09 | 29024665.61 | 81345888.24 | 0.161795E+09 | 26384949.00 |
Maximum of Months | 0.409007E+09 | 0.256550E+09 | 0.173022E+09 | 0.437551E+09 | 0.242817E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.309818E+09 | 0.202874E+09 | 0.106945E+09 | 0.283370E+09 | 0.287881E+09 |
February | 0.369243E+09 | 0.244462E+09 | 0.124781E+09 | 0.333980E+09 | 0.261305E+09 |
March | 0.368786E+09 | 0.204738E+09 | 0.164048E+09 | 0.322958E+09 | 0.209217E+09 |
April | 0.276800E+09 | 0.109431E+09 | 0.167369E+09 | 0.211626E+09 | 0.149929E+09 |
May | 0.250658E+09 | 52253115.34 | 0.198405E+09 | 0.193947E+09 | 0.102990E+09 |
June | 0.227631E+09 | 34753218.03 | 0.192878E+09 | 0.213152E+09 | 56279278.43 |
July | 0.246568E+09 | 42793607.45 | 0.203775E+09 | 0.264061E+09 | 31482210.53 |
August | 0.329273E+09 | 0.122102E+09 | 0.207171E+09 | 0.344303E+09 | 44565629.58 |
September | 0.345842E+09 | 0.178907E+09 | 0.166935E+09 | 0.360535E+09 | 85662598.97 |
October | 0.489732E+09 | 0.307184E+09 | 0.182548E+09 | 0.523871E+09 | 0.154622E+09 |
November | 0.328519E+09 | 0.197308E+09 | 0.131211E+09 | 0.320918E+09 | 0.204755E+09 |
December | 0.335745E+09 | 0.238344E+09 | 97400997.77 | 0.327293E+09 | 0.264923E+09 |
Annual Sum or Average | 0.387862E+10 | 0.193515E+10 | 0.194347E+10 | 0.370001E+10 | 0.185361E+10 |
Minimum of Months | 0.227631E+09 | 34753218.03 | 97400997.77 | 0.193947E+09 | 31482210.53 |
Maximum of Months | 0.489732E+09 | 0.307184E+09 | 0.207171E+09 | 0.523871E+09 | 0.287881E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.309818E+09 | 0.202874E+09 | 0.106945E+09 | 0.283370E+09 | 0.287881E+09 |
February | 0.369243E+09 | 0.244462E+09 | 0.124781E+09 | 0.333980E+09 | 0.261305E+09 |
March | 0.368786E+09 | 0.204738E+09 | 0.164048E+09 | 0.322958E+09 | 0.209217E+09 |
April | 0.276800E+09 | 0.109431E+09 | 0.167369E+09 | 0.211626E+09 | 0.149929E+09 |
May | 0.250658E+09 | 52253115.34 | 0.198405E+09 | 0.193947E+09 | 0.102990E+09 |
June | 0.227631E+09 | 34753218.03 | 0.192878E+09 | 0.213152E+09 | 56279278.43 |
July | 0.246568E+09 | 42793607.45 | 0.203775E+09 | 0.264061E+09 | 31482210.53 |
August | 0.329273E+09 | 0.122102E+09 | 0.207171E+09 | 0.344303E+09 | 44565629.58 |
September | 0.345842E+09 | 0.178907E+09 | 0.166935E+09 | 0.360535E+09 | 85662598.97 |
October | 0.489732E+09 | 0.307184E+09 | 0.182548E+09 | 0.523871E+09 | 0.154622E+09 |
November | 0.328519E+09 | 0.197308E+09 | 0.131211E+09 | 0.320918E+09 | 0.204755E+09 |
December | 0.335745E+09 | 0.238344E+09 | 97400997.77 | 0.327293E+09 | 0.264923E+09 |
Annual Sum or Average | 0.387862E+10 | 0.193515E+10 | 0.194347E+10 | 0.370001E+10 | 0.185361E+10 |
Minimum of Months | 0.227631E+09 | 34753218.03 | 97400997.77 | 0.193947E+09 | 31482210.53 |
Maximum of Months | 0.489732E+09 | 0.307184E+09 | 0.207171E+09 | 0.523871E+09 | 0.287881E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258749E+09 | 0.169433E+09 | 89316326.44 | 0.235580E+09 | 0.243770E+09 |
February | 0.308379E+09 | 0.204166E+09 | 0.104212E+09 | 0.277832E+09 | 0.221104E+09 |
March | 0.307997E+09 | 0.170990E+09 | 0.137007E+09 | 0.268957E+09 | 0.176517E+09 |
April | 0.231174E+09 | 91392890.91 | 0.139781E+09 | 0.176616E+09 | 0.125814E+09 |
May | 0.209341E+09 | 43639964.46 | 0.165701E+09 | 0.162572E+09 | 85493117.52 |
June | 0.190110E+09 | 29024665.61 | 0.161085E+09 | 0.178740E+09 | 46547787.75 |
July | 0.205925E+09 | 35739716.11 | 0.170185E+09 | 0.221822E+09 | 25455162.34 |
August | 0.274997E+09 | 0.101975E+09 | 0.173022E+09 | 0.288933E+09 | 36326563.11 |
September | 0.288835E+09 | 0.149416E+09 | 0.139418E+09 | 0.301505E+09 | 71144071.50 |
October | 0.409007E+09 | 0.256550E+09 | 0.152458E+09 | 0.437450E+09 | 0.129168E+09 |
November | 0.274367E+09 | 0.164785E+09 | 0.109583E+09 | 0.267649E+09 | 0.172043E+09 |
December | 0.280402E+09 | 0.199057E+09 | 81345888.24 | 0.272494E+09 | 0.223842E+09 |
Annual Sum or Average | 0.323928E+10 | 0.161617E+10 | 0.162311E+10 | 0.309015E+10 | 0.155722E+10 |
Minimum of Months | 0.190110E+09 | 29024665.61 | 81345888.24 | 0.162572E+09 | 25455162.34 |
Maximum of Months | 0.409007E+09 | 0.256550E+09 | 0.173022E+09 | 0.437450E+09 | 0.243770E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258749E+09 | 0.169433E+09 | 89316326.44 | 0.235580E+09 | 0.243770E+09 |
February | 0.308379E+09 | 0.204166E+09 | 0.104212E+09 | 0.277832E+09 | 0.221104E+09 |
March | 0.307997E+09 | 0.170990E+09 | 0.137007E+09 | 0.268957E+09 | 0.176517E+09 |
April | 0.231174E+09 | 91392890.91 | 0.139781E+09 | 0.176616E+09 | 0.125814E+09 |
May | 0.209341E+09 | 43639964.46 | 0.165701E+09 | 0.162572E+09 | 85493117.52 |
June | 0.190110E+09 | 29024665.61 | 0.161085E+09 | 0.178740E+09 | 46547787.75 |
July | 0.205925E+09 | 35739716.11 | 0.170185E+09 | 0.221822E+09 | 25455162.34 |
August | 0.274997E+09 | 0.101975E+09 | 0.173022E+09 | 0.288933E+09 | 36326563.11 |
September | 0.288835E+09 | 0.149416E+09 | 0.139418E+09 | 0.301505E+09 | 71144071.50 |
October | 0.409007E+09 | 0.256550E+09 | 0.152458E+09 | 0.437450E+09 | 0.129168E+09 |
November | 0.274367E+09 | 0.164785E+09 | 0.109583E+09 | 0.267649E+09 | 0.172043E+09 |
December | 0.280402E+09 | 0.199057E+09 | 81345888.24 | 0.272494E+09 | 0.223842E+09 |
Annual Sum or Average | 0.323928E+10 | 0.161617E+10 | 0.162311E+10 | 0.309015E+10 | 0.155722E+10 |
Minimum of Months | 0.190110E+09 | 29024665.61 | 81345888.24 | 0.162572E+09 | 25455162.34 |
Maximum of Months | 0.409007E+09 | 0.256550E+09 | 0.173022E+09 | 0.437450E+09 | 0.243770E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.309818E+09 | 0.202874E+09 | 0.106945E+09 | 0.282638E+09 | 0.288939E+09 |
February | 0.369243E+09 | 0.244462E+09 | 0.124781E+09 | 0.333276E+09 | 0.262051E+09 |
March | 0.368786E+09 | 0.204738E+09 | 0.164048E+09 | 0.322531E+09 | 0.209230E+09 |
April | 0.276800E+09 | 0.109431E+09 | 0.167369E+09 | 0.211854E+09 | 0.149265E+09 |
May | 0.250658E+09 | 52253115.34 | 0.198405E+09 | 0.194897E+09 | 0.101567E+09 |
June | 0.227631E+09 | 34753218.03 | 0.192878E+09 | 0.213837E+09 | 55397728.28 |
July | 0.246568E+09 | 42793607.45 | 0.203775E+09 | 0.265086E+09 | 30377840.73 |
August | 0.329273E+09 | 0.122102E+09 | 0.207171E+09 | 0.345384E+09 | 43351257.48 |
September | 0.345842E+09 | 0.178907E+09 | 0.166935E+09 | 0.360807E+09 | 84671868.90 |
October | 0.489732E+09 | 0.307184E+09 | 0.182548E+09 | 0.523799E+09 | 0.153548E+09 |
November | 0.328519E+09 | 0.197308E+09 | 0.131211E+09 | 0.320821E+09 | 0.204179E+09 |
December | 0.335745E+09 | 0.238344E+09 | 97400997.77 | 0.326674E+09 | 0.265480E+09 |
Annual Sum or Average | 0.387862E+10 | 0.193515E+10 | 0.194347E+10 | 0.370160E+10 | 0.184806E+10 |
Minimum of Months | 0.227631E+09 | 34753218.03 | 97400997.77 | 0.194897E+09 | 30377840.73 |
Maximum of Months | 0.489732E+09 | 0.307184E+09 | 0.207171E+09 | 0.523799E+09 | 0.288939E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258749E+09 | 0.169433E+09 | 89316326.44 | 0.235746E+09 | 0.242966E+09 |
February | 0.308379E+09 | 0.204166E+09 | 0.104212E+09 | 0.278039E+09 | 0.220304E+09 |
March | 0.307997E+09 | 0.170990E+09 | 0.137007E+09 | 0.269222E+09 | 0.175576E+09 |
April | 0.231174E+09 | 91392890.91 | 0.139781E+09 | 0.177100E+09 | 0.124762E+09 |
May | 0.209341E+09 | 43639964.46 | 0.165701E+09 | 0.163491E+09 | 84204463.19 |
June | 0.190110E+09 | 29024665.61 | 0.161085E+09 | 0.179010E+09 | 46197938.83 |
July | 0.205925E+09 | 35739716.11 | 0.170185E+09 | 0.222077E+09 | 25156897.73 |
August | 0.274997E+09 | 0.101975E+09 | 0.173022E+09 | 0.289152E+09 | 36034143.38 |
September | 0.288835E+09 | 0.149416E+09 | 0.139418E+09 | 0.301687E+09 | 70768774.77 |
October | 0.409007E+09 | 0.256550E+09 | 0.152458E+09 | 0.437880E+09 | 0.128321E+09 |
November | 0.274367E+09 | 0.164785E+09 | 0.109583E+09 | 0.268079E+09 | 0.170996E+09 |
December | 0.280402E+09 | 0.199057E+09 | 81345888.24 | 0.272687E+09 | 0.223051E+09 |
Annual Sum or Average | 0.323928E+10 | 0.161617E+10 | 0.162311E+10 | 0.309417E+10 | 0.154834E+10 |
Minimum of Months | 0.190110E+09 | 29024665.61 | 81345888.24 | 0.163491E+09 | 25156897.73 |
Maximum of Months | 0.409007E+09 | 0.256550E+09 | 0.173022E+09 | 0.437880E+09 | 0.242966E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258749E+09 | 0.169433E+09 | 89316326.44 | 0.235746E+09 | 0.242966E+09 |
February | 0.308379E+09 | 0.204166E+09 | 0.104212E+09 | 0.278039E+09 | 0.220304E+09 |
March | 0.307997E+09 | 0.170990E+09 | 0.137007E+09 | 0.269222E+09 | 0.175576E+09 |
April | 0.231174E+09 | 91392890.91 | 0.139781E+09 | 0.177100E+09 | 0.124762E+09 |
May | 0.209341E+09 | 43639964.46 | 0.165701E+09 | 0.163491E+09 | 84204463.19 |
June | 0.190110E+09 | 29024665.61 | 0.161085E+09 | 0.179010E+09 | 46197938.83 |
July | 0.205925E+09 | 35739716.11 | 0.170185E+09 | 0.222077E+09 | 25156897.73 |
August | 0.274997E+09 | 0.101975E+09 | 0.173022E+09 | 0.289152E+09 | 36034143.38 |
September | 0.288835E+09 | 0.149416E+09 | 0.139418E+09 | 0.301687E+09 | 70768774.77 |
October | 0.409007E+09 | 0.256550E+09 | 0.152458E+09 | 0.437880E+09 | 0.128321E+09 |
November | 0.274367E+09 | 0.164785E+09 | 0.109583E+09 | 0.268079E+09 | 0.170996E+09 |
December | 0.280402E+09 | 0.199057E+09 | 81345888.24 | 0.272687E+09 | 0.223051E+09 |
Annual Sum or Average | 0.323928E+10 | 0.161617E+10 | 0.162311E+10 | 0.309417E+10 | 0.154834E+10 |
Minimum of Months | 0.190110E+09 | 29024665.61 | 81345888.24 | 0.163491E+09 | 25156897.73 |
Maximum of Months | 0.409007E+09 | 0.256550E+09 | 0.173022E+09 | 0.437880E+09 | 0.242966E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.309818E+09 | 0.202874E+09 | 0.106945E+09 | 0.282840E+09 | 0.287979E+09 |
February | 0.369243E+09 | 0.244462E+09 | 0.124781E+09 | 0.333526E+09 | 0.261096E+09 |
March | 0.368786E+09 | 0.204738E+09 | 0.164048E+09 | 0.322853E+09 | 0.208109E+09 |
April | 0.276800E+09 | 0.109431E+09 | 0.167369E+09 | 0.212436E+09 | 0.148016E+09 |
May | 0.250658E+09 | 52253115.34 | 0.198405E+09 | 0.195997E+09 | 0.100038E+09 |
June | 0.227631E+09 | 34753218.03 | 0.192878E+09 | 0.214163E+09 | 54981334.48 |
July | 0.246568E+09 | 42793607.45 | 0.203775E+09 | 0.265394E+09 | 30023036.37 |
August | 0.329273E+09 | 0.122102E+09 | 0.207171E+09 | 0.345648E+09 | 43003799.61 |
September | 0.345842E+09 | 0.178907E+09 | 0.166935E+09 | 0.361028E+09 | 84225368.98 |
October | 0.489732E+09 | 0.307184E+09 | 0.182548E+09 | 0.524315E+09 | 0.152542E+09 |
November | 0.328519E+09 | 0.197308E+09 | 0.131211E+09 | 0.321336E+09 | 0.202933E+09 |
December | 0.335745E+09 | 0.238344E+09 | 97400997.77 | 0.326908E+09 | 0.264536E+09 |
Annual Sum or Average | 0.387862E+10 | 0.193515E+10 | 0.194347E+10 | 0.370644E+10 | 0.183748E+10 |
Minimum of Months | 0.227631E+09 | 34753218.03 | 97400997.77 | 0.195997E+09 | 30023036.37 |
Maximum of Months | 0.489732E+09 | 0.307184E+09 | 0.207171E+09 | 0.524315E+09 | 0.287979E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258749E+09 | 0.169433E+09 | 89316326.44 | 0.236307E+09 | 0.239911E+09 |
February | 0.308379E+09 | 0.204166E+09 | 0.104212E+09 | 0.278720E+09 | 0.217335E+09 |
March | 0.307997E+09 | 0.170990E+09 | 0.137007E+09 | 0.269972E+09 | 0.172521E+09 |
April | 0.231174E+09 | 91392890.91 | 0.139781E+09 | 0.178224E+09 | 0.121893E+09 |
May | 0.209341E+09 | 43639964.46 | 0.165701E+09 | 0.165391E+09 | 81428905.63 |
June | 0.190110E+09 | 29024665.61 | 0.161085E+09 | 0.179546E+09 | 45351698.48 |
July | 0.205925E+09 | 35739716.11 | 0.170185E+09 | 0.222414E+09 | 24625769.86 |
August | 0.274997E+09 | 0.101975E+09 | 0.173022E+09 | 0.289360E+09 | 35594756.31 |
September | 0.288835E+09 | 0.149416E+09 | 0.139418E+09 | 0.301960E+09 | 70015229.31 |
October | 0.409007E+09 | 0.256550E+09 | 0.152458E+09 | 0.438755E+09 | 0.126486E+09 |
November | 0.274367E+09 | 0.164785E+09 | 0.109583E+09 | 0.268928E+09 | 0.168611E+09 |
December | 0.280402E+09 | 0.199057E+09 | 81345888.24 | 0.273293E+09 | 0.220325E+09 |
Annual Sum or Average | 0.323928E+10 | 0.161617E+10 | 0.162311E+10 | 0.310287E+10 | 0.152410E+10 |
Minimum of Months | 0.190110E+09 | 29024665.61 | 81345888.24 | 0.165391E+09 | 24625769.86 |
Maximum of Months | 0.409007E+09 | 0.256550E+09 | 0.173022E+09 | 0.438755E+09 | 0.239911E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258749E+09 | 0.169433E+09 | 89316326.44 | 0.236307E+09 | 0.239911E+09 |
February | 0.308379E+09 | 0.204166E+09 | 0.104212E+09 | 0.278720E+09 | 0.217335E+09 |
March | 0.307997E+09 | 0.170990E+09 | 0.137007E+09 | 0.269972E+09 | 0.172521E+09 |
April | 0.231174E+09 | 91392890.91 | 0.139781E+09 | 0.178224E+09 | 0.121893E+09 |
May | 0.209341E+09 | 43639964.46 | 0.165701E+09 | 0.165391E+09 | 81428905.63 |
June | 0.190110E+09 | 29024665.61 | 0.161085E+09 | 0.179546E+09 | 45351698.48 |
July | 0.205925E+09 | 35739716.11 | 0.170185E+09 | 0.222414E+09 | 24625769.86 |
August | 0.274997E+09 | 0.101975E+09 | 0.173022E+09 | 0.289360E+09 | 35594756.31 |
September | 0.288835E+09 | 0.149416E+09 | 0.139418E+09 | 0.301960E+09 | 70015229.31 |
October | 0.409007E+09 | 0.256550E+09 | 0.152458E+09 | 0.438755E+09 | 0.126486E+09 |
November | 0.274367E+09 | 0.164785E+09 | 0.109583E+09 | 0.268928E+09 | 0.168611E+09 |
December | 0.280402E+09 | 0.199057E+09 | 81345888.24 | 0.273293E+09 | 0.220325E+09 |
Annual Sum or Average | 0.323928E+10 | 0.161617E+10 | 0.162311E+10 | 0.310287E+10 | 0.152410E+10 |
Minimum of Months | 0.190110E+09 | 29024665.61 | 81345888.24 | 0.165391E+09 | 24625769.86 |
Maximum of Months | 0.409007E+09 | 0.256550E+09 | 0.173022E+09 | 0.438755E+09 | 0.239911E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.309818E+09 | 0.202874E+09 | 0.106945E+09 | 0.283521E+09 | 0.284342E+09 |
February | 0.369243E+09 | 0.244462E+09 | 0.124781E+09 | 0.334353E+09 | 0.257562E+09 |
March | 0.368786E+09 | 0.204738E+09 | 0.164048E+09 | 0.323764E+09 | 0.204477E+09 |
April | 0.276800E+09 | 0.109431E+09 | 0.167369E+09 | 0.213787E+09 | 0.144614E+09 |
May | 0.250658E+09 | 52253115.34 | 0.198405E+09 | 0.198271E+09 | 96750773.79 |
June | 0.227631E+09 | 34753218.03 | 0.192878E+09 | 0.214806E+09 | 53982074.85 |
July | 0.246568E+09 | 42793607.45 | 0.203775E+09 | 0.265796E+09 | 29398434.04 |
August | 0.329273E+09 | 0.122102E+09 | 0.207171E+09 | 0.345896E+09 | 42487120.40 |
September | 0.345842E+09 | 0.178907E+09 | 0.166935E+09 | 0.361356E+09 | 83334420.04 |
October | 0.489732E+09 | 0.307184E+09 | 0.182548E+09 | 0.525361E+09 | 0.150369E+09 |
November | 0.328519E+09 | 0.197308E+09 | 0.131211E+09 | 0.322356E+09 | 0.200102E+09 |
December | 0.335745E+09 | 0.238344E+09 | 97400997.77 | 0.327641E+09 | 0.261291E+09 |
Annual Sum or Average | 0.387862E+10 | 0.193515E+10 | 0.194347E+10 | 0.371691E+10 | 0.180871E+10 |
Minimum of Months | 0.227631E+09 | 34753218.03 | 97400997.77 | 0.198271E+09 | 29398434.04 |
Maximum of Months | 0.489732E+09 | 0.307184E+09 | 0.207171E+09 | 0.525361E+09 | 0.284342E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258749E+09 | 0.169433E+09 | 89316326.44 | 0.238304E+09 | 0.227585E+09 |
February | 0.308379E+09 | 0.204166E+09 | 0.104212E+09 | 0.281143E+09 | 0.205291E+09 |
March | 0.307997E+09 | 0.170990E+09 | 0.137007E+09 | 0.272382E+09 | 0.160577E+09 |
April | 0.231174E+09 | 91392890.91 | 0.139781E+09 | 0.181057E+09 | 0.112037E+09 |
May | 0.209341E+09 | 43639964.46 | 0.165701E+09 | 0.169847E+09 | 73619685.05 |
June | 0.190110E+09 | 29024665.61 | 0.161085E+09 | 0.181190E+09 | 42045216.69 |
July | 0.205925E+09 | 35739716.11 | 0.170185E+09 | 0.222918E+09 | 23016036.95 |
August | 0.274997E+09 | 0.101975E+09 | 0.173022E+09 | 0.289226E+09 | 34338188.61 |
September | 0.288835E+09 | 0.149416E+09 | 0.139418E+09 | 0.302417E+09 | 67524447.80 |
October | 0.409007E+09 | 0.256550E+09 | 0.152458E+09 | 0.440510E+09 | 0.121119E+09 |
November | 0.274367E+09 | 0.164785E+09 | 0.109583E+09 | 0.270988E+09 | 0.160919E+09 |
December | 0.280402E+09 | 0.199057E+09 | 81345888.24 | 0.275391E+09 | 0.209530E+09 |
Annual Sum or Average | 0.323928E+10 | 0.161617E+10 | 0.162311E+10 | 0.312537E+10 | 0.143760E+10 |
Minimum of Months | 0.190110E+09 | 29024665.61 | 81345888.24 | 0.169847E+09 | 23016036.95 |
Maximum of Months | 0.409007E+09 | 0.256550E+09 | 0.173022E+09 | 0.440510E+09 | 0.227585E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258749E+09 | 0.169433E+09 | 89316326.44 | 0.238304E+09 | 0.227585E+09 |
February | 0.308379E+09 | 0.204166E+09 | 0.104212E+09 | 0.281143E+09 | 0.205291E+09 |
March | 0.307997E+09 | 0.170990E+09 | 0.137007E+09 | 0.272382E+09 | 0.160577E+09 |
April | 0.231174E+09 | 91392890.91 | 0.139781E+09 | 0.181057E+09 | 0.112037E+09 |
May | 0.209341E+09 | 43639964.46 | 0.165701E+09 | 0.169847E+09 | 73619685.05 |
June | 0.190110E+09 | 29024665.61 | 0.161085E+09 | 0.181190E+09 | 42045216.69 |
July | 0.205925E+09 | 35739716.11 | 0.170185E+09 | 0.222918E+09 | 23016036.95 |
August | 0.274997E+09 | 0.101975E+09 | 0.173022E+09 | 0.289226E+09 | 34338188.61 |
September | 0.288835E+09 | 0.149416E+09 | 0.139418E+09 | 0.302417E+09 | 67524447.80 |
October | 0.409007E+09 | 0.256550E+09 | 0.152458E+09 | 0.440510E+09 | 0.121119E+09 |
November | 0.274367E+09 | 0.164785E+09 | 0.109583E+09 | 0.270988E+09 | 0.160919E+09 |
December | 0.280402E+09 | 0.199057E+09 | 81345888.24 | 0.275391E+09 | 0.209530E+09 |
Annual Sum or Average | 0.323928E+10 | 0.161617E+10 | 0.162311E+10 | 0.312537E+10 | 0.143760E+10 |
Minimum of Months | 0.190110E+09 | 29024665.61 | 81345888.24 | 0.169847E+09 | 23016036.95 |
Maximum of Months | 0.409007E+09 | 0.256550E+09 | 0.173022E+09 | 0.440510E+09 | 0.227585E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.309818E+09 | 0.202874E+09 | 0.106945E+09 | 0.285947E+09 | 0.269705E+09 |
February | 0.369243E+09 | 0.244462E+09 | 0.124781E+09 | 0.337296E+09 | 0.243261E+09 |
March | 0.368786E+09 | 0.204738E+09 | 0.164048E+09 | 0.326696E+09 | 0.190305E+09 |
April | 0.276800E+09 | 0.109431E+09 | 0.167369E+09 | 0.217212E+09 | 0.132939E+09 |
May | 0.250658E+09 | 52253115.34 | 0.198405E+09 | 0.203603E+09 | 87502831.33 |
June | 0.227631E+09 | 34753218.03 | 0.192878E+09 | 0.216779E+09 | 50068361.21 |
July | 0.246568E+09 | 42793607.45 | 0.203775E+09 | 0.266397E+09 | 27490651.91 |
August | 0.329273E+09 | 0.122102E+09 | 0.207171E+09 | 0.345729E+09 | 40999576.39 |
September | 0.345842E+09 | 0.178907E+09 | 0.166935E+09 | 0.361902E+09 | 80388258.40 |
October | 0.489732E+09 | 0.307184E+09 | 0.182548E+09 | 0.527456E+09 | 0.144022E+09 |
November | 0.328519E+09 | 0.197308E+09 | 0.131211E+09 | 0.324833E+09 | 0.190992E+09 |
December | 0.335745E+09 | 0.238344E+09 | 97400997.77 | 0.330178E+09 | 0.248478E+09 |
Annual Sum or Average | 0.387862E+10 | 0.193515E+10 | 0.194347E+10 | 0.374403E+10 | 0.170615E+10 |
Minimum of Months | 0.227631E+09 | 34753218.03 | 97400997.77 | 0.203603E+09 | 27490651.91 |
Maximum of Months | 0.489732E+09 | 0.307184E+09 | 0.207171E+09 | 0.527456E+09 | 0.269705E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 562.23 | 601.17 | 619.04 | 405.36 | 213.68 | 0.00 | 0.00 |
February | 735.68 | 597.57 | 816.82 | 540.79 | 276.03 | 0.00 | 0.00 |
March | 642.19 | 432.61 | 736.86 | 409.08 | 327.78 | 0.00 | 0.00 |
April | 431.92 | 322.40 | 571.50 | 225.94 | 345.56 | 0.00 | 0.00 |
May | 381.59 | 215.30 | 500.83 | 104.41 | 396.43 | 0.00 | 0.00 |
June | 440.86 | 113.96 | 469.99 | 71.75 | 398.23 | 0.00 | 0.00 |
July | 530.53 | 57.76 | 492.66 | 85.50 | 407.16 | 0.00 | 0.00 |
August | 690.13 | 84.45 | 657.91 | 243.97 | 413.94 | 0.00 | 0.00 |
September | 744.46 | 174.87 | 714.05 | 369.38 | 344.67 | 0.00 | 0.00 |
October | 1043.40 | 316.08 | 978.52 | 613.78 | 364.74 | 0.00 | 0.00 |
November | 655.75 | 443.78 | 678.29 | 407.38 | 270.91 | 0.00 | 0.00 |
December | 651.11 | 546.83 | 670.84 | 476.23 | 194.61 | 0.00 | 0.00 |
Annual Sum or Average | 625.55 | 324.01 | 658.20 | 328.39 | 329.81 | 0.00 | 0.00 |
Minimum of Months | 381.59 | 57.76 | 469.99 | 71.75 | 194.61 | 0.00 | 0.00 |
Maximum of Months | 1043.40 | 601.17 | 978.52 | 613.78 | 413.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 278.31 | 315.17 | 309.52 | 202.68 | 106.84 | 0.00 | 0.00 |
February | 364.25 | 313.88 | 408.41 | 270.39 | 138.02 | 0.00 | 0.00 |
March | 317.41 | 231.51 | 368.43 | 204.54 | 163.89 | 0.00 | 0.00 |
April | 211.98 | 173.57 | 285.75 | 112.97 | 172.78 | 0.00 | 0.00 |
May | 187.75 | 112.50 | 250.42 | 52.20 | 198.21 | 0.00 | 0.00 |
June | 219.65 | 58.44 | 234.99 | 35.88 | 199.12 | 0.00 | 0.00 |
July | 265.24 | 29.65 | 246.33 | 42.75 | 203.58 | 0.00 | 0.00 |
August | 345.47 | 42.72 | 328.96 | 121.98 | 206.97 | 0.00 | 0.00 |
September | 371.79 | 88.59 | 357.03 | 184.69 | 172.33 | 0.00 | 0.00 |
October | 519.38 | 162.23 | 489.26 | 306.89 | 182.37 | 0.00 | 0.00 |
November | 324.02 | 234.52 | 339.14 | 203.69 | 135.45 | 0.00 | 0.00 |
December | 322.58 | 287.97 | 335.42 | 238.11 | 97.31 | 0.00 | 0.00 |
Annual Sum or Average | 310.53 | 170.07 | 329.10 | 164.20 | 164.90 | 0.00 | 0.00 |
Minimum of Months | 187.75 | 29.65 | 234.99 | 35.88 | 97.31 | 0.00 | 0.00 |
Maximum of Months | 519.38 | 315.17 | 489.26 | 306.89 | 206.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 278.67 | 304.86 | 308.88 | 202.26 | 106.62 | 0.00 | 0.00 |
February | 364.37 | 304.81 | 407.57 | 269.84 | 137.73 | 0.00 | 0.00 |
March | 317.94 | 223.25 | 367.67 | 204.12 | 163.55 | 0.00 | 0.00 |
April | 212.99 | 168.11 | 285.16 | 112.74 | 172.43 | 0.00 | 0.00 |
May | 187.89 | 113.62 | 249.90 | 52.10 | 197.81 | 0.00 | 0.00 |
June | 218.83 | 62.68 | 234.51 | 35.80 | 198.71 | 0.00 | 0.00 |
July | 263.60 | 35.12 | 245.83 | 42.66 | 203.16 | 0.00 | 0.00 |
August | 343.73 | 48.36 | 328.28 | 121.73 | 206.55 | 0.00 | 0.00 |
September | 370.89 | 93.27 | 356.29 | 184.31 | 171.98 | 0.00 | 0.00 |
October | 519.03 | 163.49 | 488.26 | 306.26 | 182.00 | 0.00 | 0.00 |
November | 324.87 | 227.64 | 338.45 | 203.27 | 135.18 | 0.00 | 0.00 |
December | 322.96 | 278.58 | 334.73 | 237.63 | 97.11 | 0.00 | 0.00 |
Annual Sum or Average | 310.35 | 167.87 | 328.42 | 163.86 | 164.56 | 0.00 | 0.00 |
Minimum of Months | 187.89 | 35.12 | 234.51 | 35.80 | 97.11 | 0.00 | 0.00 |
Maximum of Months | 519.03 | 304.86 | 488.26 | 306.26 | 206.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 279.17 | 301.08 | 308.88 | 202.26 | 106.62 | 0.00 | 0.00 |
February | 364.87 | 301.53 | 407.57 | 269.84 | 137.73 | 0.00 | 0.00 |
March | 318.62 | 219.97 | 367.67 | 204.12 | 163.55 | 0.00 | 0.00 |
April | 213.90 | 165.14 | 285.16 | 112.74 | 172.43 | 0.00 | 0.00 |
May | 188.58 | 112.09 | 249.90 | 52.10 | 197.81 | 0.00 | 0.00 |
June | 218.91 | 62.52 | 234.51 | 35.80 | 198.71 | 0.00 | 0.00 |
July | 263.58 | 35.27 | 245.83 | 42.66 | 203.16 | 0.00 | 0.00 |
August | 343.69 | 48.59 | 328.28 | 121.73 | 206.55 | 0.00 | 0.00 |
September | 370.94 | 93.08 | 356.29 | 184.31 | 171.98 | 0.00 | 0.00 |
October | 519.49 | 162.18 | 488.26 | 306.26 | 182.00 | 0.00 | 0.00 |
November | 325.85 | 224.06 | 338.45 | 203.27 | 135.18 | 0.00 | 0.00 |
December | 323.44 | 275.36 | 334.73 | 237.63 | 97.11 | 0.00 | 0.00 |
Annual Sum or Average | 310.79 | 165.97 | 328.42 | 163.86 | 164.56 | 0.00 | 0.00 |
Minimum of Months | 188.58 | 35.27 | 234.51 | 35.80 | 97.11 | 0.00 | 0.00 |
Maximum of Months | 519.49 | 301.53 | 488.26 | 306.26 | 206.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 279.75 | 298.06 | 308.88 | 202.26 | 106.62 | 0.00 | 0.00 |
February | 365.50 | 298.84 | 407.57 | 269.84 | 137.73 | 0.00 | 0.00 |
March | 319.40 | 217.23 | 367.67 | 204.12 | 163.55 | 0.00 | 0.00 |
April | 215.08 | 162.27 | 285.16 | 112.74 | 172.43 | 0.00 | 0.00 |
May | 190.04 | 109.48 | 249.90 | 52.10 | 197.81 | 0.00 | 0.00 |
June | 219.42 | 61.48 | 234.51 | 35.80 | 198.71 | 0.00 | 0.00 |
July | 264.05 | 34.36 | 245.83 | 42.66 | 203.16 | 0.00 | 0.00 |
August | 344.11 | 47.63 | 328.28 | 121.73 | 206.55 | 0.00 | 0.00 |
September | 371.32 | 91.93 | 356.29 | 184.31 | 171.98 | 0.00 | 0.00 |
October | 520.36 | 160.11 | 488.26 | 306.26 | 182.00 | 0.00 | 0.00 |
November | 327.23 | 220.39 | 338.45 | 203.27 | 135.18 | 0.00 | 0.00 |
December | 323.95 | 272.92 | 334.73 | 237.63 | 97.11 | 0.00 | 0.00 |
Annual Sum or Average | 311.55 | 163.79 | 328.42 | 163.86 | 164.56 | 0.00 | 0.00 |
Minimum of Months | 190.04 | 34.36 | 234.51 | 35.80 | 97.11 | 0.00 | 0.00 |
Maximum of Months | 520.36 | 298.84 | 488.26 | 306.26 | 206.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 564.39 | 577.59 | 617.77 | 404.53 | 213.24 | 0.00 | 0.00 |
February | 736.53 | 580.47 | 815.15 | 539.68 | 275.47 | 0.00 | 0.00 |
March | 643.41 | 419.75 | 735.35 | 408.24 | 327.11 | 0.00 | 0.00 |
April | 435.58 | 310.66 | 570.33 | 225.48 | 344.85 | 0.00 | 0.00 |
May | 386.45 | 206.35 | 499.81 | 104.19 | 395.61 | 0.00 | 0.00 |
June | 439.43 | 116.40 | 469.02 | 71.61 | 397.41 | 0.00 | 0.00 |
July | 527.18 | 62.91 | 491.65 | 85.33 | 406.32 | 0.00 | 0.00 |
August | 687.25 | 89.05 | 656.56 | 243.47 | 413.09 | 0.00 | 0.00 |
September | 743.16 | 177.16 | 712.59 | 368.63 | 343.96 | 0.00 | 0.00 |
October | 1044.63 | 309.68 | 976.51 | 612.52 | 364.00 | 0.00 | 0.00 |
November | 660.84 | 424.17 | 676.89 | 406.54 | 270.35 | 0.00 | 0.00 |
December | 652.17 | 531.33 | 669.47 | 475.25 | 194.22 | 0.00 | 0.00 |
Annual Sum or Average | 626.47 | 315.62 | 656.85 | 327.72 | 329.13 | 0.00 | 0.00 |
Minimum of Months | 386.45 | 62.91 | 469.02 | 71.61 | 194.22 | 0.00 | 0.00 |
Maximum of Months | 1044.63 | 580.47 | 976.51 | 612.52 | 413.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 281.44 | 289.90 | 308.88 | 202.26 | 106.62 | 0.00 | 0.00 |
February | 367.45 | 291.11 | 407.57 | 269.84 | 137.73 | 0.00 | 0.00 |
March | 321.25 | 209.92 | 367.67 | 204.12 | 163.55 | 0.00 | 0.00 |
April | 218.01 | 154.67 | 285.16 | 112.74 | 172.43 | 0.00 | 0.00 |
May | 194.16 | 101.76 | 249.90 | 52.10 | 197.81 | 0.00 | 0.00 |
June | 220.42 | 57.29 | 234.51 | 35.80 | 198.71 | 0.00 | 0.00 |
July | 264.61 | 30.35 | 245.83 | 42.66 | 203.16 | 0.00 | 0.00 |
August | 344.70 | 43.31 | 328.28 | 121.73 | 206.55 | 0.00 | 0.00 |
September | 371.84 | 87.56 | 356.29 | 184.31 | 171.98 | 0.00 | 0.00 |
October | 522.21 | 153.78 | 488.26 | 306.26 | 182.00 | 0.00 | 0.00 |
November | 330.29 | 211.52 | 338.45 | 203.27 | 135.18 | 0.00 | 0.00 |
December | 325.44 | 266.26 | 334.73 | 237.63 | 97.11 | 0.00 | 0.00 |
Annual Sum or Average | 313.35 | 157.36 | 328.42 | 163.86 | 164.56 | 0.00 | 0.00 |
Minimum of Months | 194.16 | 30.35 | 234.51 | 35.80 | 97.11 | 0.00 | 0.00 |
Maximum of Months | 522.21 | 291.11 | 488.26 | 306.26 | 206.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 281.64 | 288.94 | 308.88 | 202.26 | 106.62 | 0.00 | 0.00 |
February | 367.73 | 290.06 | 407.57 | 269.84 | 137.73 | 0.00 | 0.00 |
March | 321.57 | 208.80 | 367.67 | 204.12 | 163.55 | 0.00 | 0.00 |
April | 218.61 | 153.37 | 285.16 | 112.74 | 172.43 | 0.00 | 0.00 |
May | 195.26 | 100.23 | 249.90 | 52.10 | 197.81 | 0.00 | 0.00 |
June | 220.75 | 56.86 | 234.51 | 35.80 | 198.71 | 0.00 | 0.00 |
July | 264.92 | 29.99 | 245.83 | 42.66 | 203.16 | 0.00 | 0.00 |
August | 344.96 | 42.96 | 328.28 | 121.73 | 206.55 | 0.00 | 0.00 |
September | 372.07 | 87.10 | 356.29 | 184.31 | 171.98 | 0.00 | 0.00 |
October | 522.73 | 152.77 | 488.26 | 306.26 | 182.00 | 0.00 | 0.00 |
November | 330.82 | 210.23 | 338.45 | 203.27 | 135.18 | 0.00 | 0.00 |
December | 325.67 | 265.32 | 334.73 | 237.63 | 97.11 | 0.00 | 0.00 |
Annual Sum or Average | 313.76 | 156.46 | 328.42 | 163.86 | 164.56 | 0.00 | 0.00 |
Minimum of Months | 195.26 | 29.99 | 234.51 | 35.80 | 97.11 | 0.00 | 0.00 |
Maximum of Months | 522.73 | 290.06 | 488.26 | 306.26 | 206.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 282.31 | 285.31 | 308.88 | 202.26 | 106.62 | 0.00 | 0.00 |
February | 368.63 | 286.14 | 407.57 | 269.84 | 137.73 | 0.00 | 0.00 |
March | 322.47 | 205.17 | 367.67 | 204.12 | 163.55 | 0.00 | 0.00 |
April | 220.00 | 149.85 | 285.16 | 112.74 | 172.43 | 0.00 | 0.00 |
May | 197.53 | 96.93 | 249.90 | 52.10 | 197.81 | 0.00 | 0.00 |
June | 221.41 | 55.82 | 234.51 | 35.80 | 198.71 | 0.00 | 0.00 |
July | 265.32 | 29.36 | 245.83 | 42.66 | 203.16 | 0.00 | 0.00 |
August | 345.21 | 42.44 | 328.28 | 121.73 | 206.55 | 0.00 | 0.00 |
September | 372.41 | 86.17 | 356.29 | 184.31 | 171.98 | 0.00 | 0.00 |
October | 523.77 | 150.59 | 488.26 | 306.26 | 182.00 | 0.00 | 0.00 |
November | 331.87 | 207.30 | 338.45 | 203.27 | 135.18 | 0.00 | 0.00 |
December | 326.40 | 262.07 | 334.73 | 237.63 | 97.11 | 0.00 | 0.00 |
Annual Sum or Average | 314.65 | 154.01 | 328.42 | 163.86 | 164.56 | 0.00 | 0.00 |
Minimum of Months | 197.53 | 29.36 | 234.51 | 35.80 | 97.11 | 0.00 | 0.00 |
Maximum of Months | 523.77 | 286.14 | 488.26 | 306.26 | 206.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 284.71 | 270.64 | 308.88 | 202.26 | 106.62 | 0.00 | 0.00 |
February | 371.85 | 270.27 | 407.57 | 269.84 | 137.73 | 0.00 | 0.00 |
March | 325.36 | 190.96 | 367.67 | 204.12 | 163.55 | 0.00 | 0.00 |
April | 223.50 | 137.74 | 285.16 | 112.74 | 172.43 | 0.00 | 0.00 |
May | 202.84 | 87.64 | 249.90 | 52.10 | 197.81 | 0.00 | 0.00 |
June | 223.44 | 51.76 | 234.51 | 35.80 | 198.71 | 0.00 | 0.00 |
July | 265.92 | 27.45 | 245.83 | 42.66 | 203.16 | 0.00 | 0.00 |
August | 345.05 | 40.95 | 328.28 | 121.73 | 206.55 | 0.00 | 0.00 |
September | 372.97 | 83.12 | 356.29 | 184.31 | 171.98 | 0.00 | 0.00 |
October | 525.86 | 144.21 | 488.26 | 306.26 | 182.00 | 0.00 | 0.00 |
November | 334.42 | 197.85 | 338.45 | 203.27 | 135.18 | 0.00 | 0.00 |
December | 328.91 | 249.23 | 334.73 | 237.63 | 97.11 | 0.00 | 0.00 |
Annual Sum or Average | 316.93 | 145.27 | 328.42 | 163.86 | 164.56 | 0.00 | 0.00 |
Minimum of Months | 202.84 | 27.45 | 234.51 | 35.80 | 97.11 | 0.00 | 0.00 |
Maximum of Months | 525.86 | 270.64 | 488.26 | 306.26 | 206.55 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.150587E+10 | 0.161016E+10 | 0.165804E+10 | 0.108571E+10 | 0.572330E+09 | 0.00 | 0.00 |
February | 0.177977E+10 | 0.144564E+10 | 0.197606E+10 | 0.130828E+10 | 0.667782E+09 | 0.00 | 0.00 |
March | 0.172005E+10 | 0.115871E+10 | 0.197361E+10 | 0.109569E+10 | 0.877926E+09 | 0.00 | 0.00 |
April | 0.111953E+10 | 0.835652E+09 | 0.148134E+10 | 0.585636E+09 | 0.895700E+09 | 0.00 | 0.00 |
May | 0.102206E+10 | 0.576649E+09 | 0.134143E+10 | 0.279640E+09 | 0.106179E+10 | 0.00 | 0.00 |
June | 0.114270E+10 | 0.295372E+09 | 0.121820E+10 | 0.185987E+09 | 0.103221E+10 | 0.00 | 0.00 |
July | 0.142096E+10 | 0.154716E+09 | 0.131955E+10 | 0.229016E+09 | 0.109053E+10 | 0.00 | 0.00 |
August | 0.184845E+10 | 0.226187E+09 | 0.176215E+10 | 0.653447E+09 | 0.110871E+10 | 0.00 | 0.00 |
September | 0.192965E+10 | 0.453270E+09 | 0.185082E+10 | 0.957445E+09 | 0.893379E+09 | 0.00 | 0.00 |
October | 0.279464E+10 | 0.846590E+09 | 0.262088E+10 | 0.164394E+10 | 0.976932E+09 | 0.00 | 0.00 |
November | 0.169969E+10 | 0.115028E+10 | 0.175812E+10 | 0.105592E+10 | 0.702193E+09 | 0.00 | 0.00 |
December | 0.174392E+10 | 0.146463E+10 | 0.179679E+10 | 0.127553E+10 | 0.521256E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.197273E+11 | 0.102179E+11 | 0.207570E+11 | 0.103562E+11 | 0.104007E+11 | 0.00 | 0.00 |
Minimum of Months | 0.102206E+10 | 0.154716E+09 | 0.121820E+10 | 0.185987E+09 | 0.521256E+09 | 0.00 | 0.00 |
Maximum of Months | 0.279464E+10 | 0.161016E+10 | 0.262088E+10 | 0.164394E+10 | 0.110871E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.745428E+09 | 0.844143E+09 | 0.829020E+09 | 0.542855E+09 | 0.286165E+09 | 0.00 | 0.00 |
February | 0.881203E+09 | 0.759343E+09 | 0.988028E+09 | 0.654138E+09 | 0.333891E+09 | 0.00 | 0.00 |
March | 0.850141E+09 | 0.620067E+09 | 0.986807E+09 | 0.547844E+09 | 0.438963E+09 | 0.00 | 0.00 |
April | 0.549445E+09 | 0.449895E+09 | 0.740668E+09 | 0.292818E+09 | 0.447850E+09 | 0.00 | 0.00 |
May | 0.502881E+09 | 0.301312E+09 | 0.670717E+09 | 0.139820E+09 | 0.530896E+09 | 0.00 | 0.00 |
June | 0.569338E+09 | 0.151469E+09 | 0.609101E+09 | 92993500.99 | 0.516107E+09 | 0.00 | 0.00 |
July | 0.710424E+09 | 79407443.22 | 0.659773E+09 | 0.114508E+09 | 0.545265E+09 | 0.00 | 0.00 |
August | 0.925307E+09 | 0.114417E+09 | 0.881076E+09 | 0.326724E+09 | 0.554353E+09 | 0.00 | 0.00 |
September | 0.963682E+09 | 0.229618E+09 | 0.925412E+09 | 0.478722E+09 | 0.446689E+09 | 0.00 | 0.00 |
October | 0.139112E+10 | 0.434513E+09 | 0.131044E+10 | 0.821972E+09 | 0.488466E+09 | 0.00 | 0.00 |
November | 0.839848E+09 | 0.607870E+09 | 0.879059E+09 | 0.527962E+09 | 0.351097E+09 | 0.00 | 0.00 |
December | 0.864011E+09 | 0.771286E+09 | 0.898395E+09 | 0.637767E+09 | 0.260628E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.979283E+10 | 0.536334E+10 | 0.103785E+11 | 0.517812E+10 | 0.520037E+10 | 0.00 | 0.00 |
Minimum of Months | 0.502881E+09 | 79407443.22 | 0.609101E+09 | 92993500.99 | 0.260628E+09 | 0.00 | 0.00 |
Maximum of Months | 0.139112E+10 | 0.844143E+09 | 0.131044E+10 | 0.821972E+09 | 0.554353E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.746388E+09 | 0.816534E+09 | 0.827317E+09 | 0.541740E+09 | 0.285577E+09 | 0.00 | 0.00 |
February | 0.881473E+09 | 0.737405E+09 | 0.986000E+09 | 0.652794E+09 | 0.333205E+09 | 0.00 | 0.00 |
March | 0.851576E+09 | 0.597944E+09 | 0.984780E+09 | 0.546719E+09 | 0.438062E+09 | 0.00 | 0.00 |
April | 0.552071E+09 | 0.435744E+09 | 0.739147E+09 | 0.292217E+09 | 0.446931E+09 | 0.00 | 0.00 |
May | 0.503247E+09 | 0.304321E+09 | 0.669339E+09 | 0.139533E+09 | 0.529806E+09 | 0.00 | 0.00 |
June | 0.567207E+09 | 0.162459E+09 | 0.607850E+09 | 92802549.24 | 0.515048E+09 | 0.00 | 0.00 |
July | 0.706038E+09 | 94061126.81 | 0.658419E+09 | 0.114273E+09 | 0.544146E+09 | 0.00 | 0.00 |
August | 0.920656E+09 | 0.129523E+09 | 0.879267E+09 | 0.326053E+09 | 0.553214E+09 | 0.00 | 0.00 |
September | 0.961336E+09 | 0.241748E+09 | 0.923512E+09 | 0.477739E+09 | 0.445772E+09 | 0.00 | 0.00 |
October | 0.139018E+10 | 0.437882E+09 | 0.130775E+10 | 0.820284E+09 | 0.487463E+09 | 0.00 | 0.00 |
November | 0.842053E+09 | 0.590046E+09 | 0.877253E+09 | 0.526878E+09 | 0.350376E+09 | 0.00 | 0.00 |
December | 0.865016E+09 | 0.746135E+09 | 0.896550E+09 | 0.636457E+09 | 0.260093E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.978724E+10 | 0.529380E+10 | 0.103572E+11 | 0.516749E+10 | 0.518969E+10 | 0.00 | 0.00 |
Minimum of Months | 0.503247E+09 | 94061126.81 | 0.607850E+09 | 92802549.24 | 0.260093E+09 | 0.00 | 0.00 |
Maximum of Months | 0.139018E+10 | 0.816534E+09 | 0.130775E+10 | 0.820284E+09 | 0.553214E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.747739E+09 | 0.806413E+09 | 0.827317E+09 | 0.541740E+09 | 0.285577E+09 | 0.00 | 0.00 |
February | 0.882686E+09 | 0.729458E+09 | 0.986000E+09 | 0.652794E+09 | 0.333205E+09 | 0.00 | 0.00 |
March | 0.853391E+09 | 0.589168E+09 | 0.984780E+09 | 0.546719E+09 | 0.438062E+09 | 0.00 | 0.00 |
April | 0.554425E+09 | 0.428051E+09 | 0.739147E+09 | 0.292217E+09 | 0.446931E+09 | 0.00 | 0.00 |
May | 0.505090E+09 | 0.300233E+09 | 0.669339E+09 | 0.139533E+09 | 0.529806E+09 | 0.00 | 0.00 |
June | 0.567427E+09 | 0.162054E+09 | 0.607850E+09 | 92802549.24 | 0.515048E+09 | 0.00 | 0.00 |
July | 0.705983E+09 | 94473050.53 | 0.658419E+09 | 0.114273E+09 | 0.544146E+09 | 0.00 | 0.00 |
August | 0.920534E+09 | 0.130133E+09 | 0.879267E+09 | 0.326053E+09 | 0.553214E+09 | 0.00 | 0.00 |
September | 0.961486E+09 | 0.241267E+09 | 0.923512E+09 | 0.477739E+09 | 0.445772E+09 | 0.00 | 0.00 |
October | 0.139141E+10 | 0.434391E+09 | 0.130775E+10 | 0.820284E+09 | 0.487463E+09 | 0.00 | 0.00 |
November | 0.844597E+09 | 0.580753E+09 | 0.877253E+09 | 0.526878E+09 | 0.350376E+09 | 0.00 | 0.00 |
December | 0.866291E+09 | 0.737512E+09 | 0.896550E+09 | 0.636457E+09 | 0.260093E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.980106E+10 | 0.523391E+10 | 0.103572E+11 | 0.516749E+10 | 0.518969E+10 | 0.00 | 0.00 |
Minimum of Months | 0.505090E+09 | 94473050.53 | 0.607850E+09 | 92802549.24 | 0.260093E+09 | 0.00 | 0.00 |
Maximum of Months | 0.139141E+10 | 0.806413E+09 | 0.130775E+10 | 0.820284E+09 | 0.553214E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.749292E+09 | 0.798332E+09 | 0.827317E+09 | 0.541740E+09 | 0.285577E+09 | 0.00 | 0.00 |
February | 0.884228E+09 | 0.722949E+09 | 0.986000E+09 | 0.652794E+09 | 0.333205E+09 | 0.00 | 0.00 |
March | 0.855473E+09 | 0.581816E+09 | 0.984780E+09 | 0.546719E+09 | 0.438062E+09 | 0.00 | 0.00 |
April | 0.557494E+09 | 0.420594E+09 | 0.739147E+09 | 0.292217E+09 | 0.446931E+09 | 0.00 | 0.00 |
May | 0.508996E+09 | 0.293239E+09 | 0.669339E+09 | 0.139533E+09 | 0.529806E+09 | 0.00 | 0.00 |
June | 0.568741E+09 | 0.159368E+09 | 0.607850E+09 | 92802549.24 | 0.515048E+09 | 0.00 | 0.00 |
July | 0.707221E+09 | 92031485.19 | 0.658419E+09 | 0.114273E+09 | 0.544146E+09 | 0.00 | 0.00 |
August | 0.921652E+09 | 0.127574E+09 | 0.879267E+09 | 0.326053E+09 | 0.553214E+09 | 0.00 | 0.00 |
September | 0.962472E+09 | 0.238287E+09 | 0.923512E+09 | 0.477739E+09 | 0.445772E+09 | 0.00 | 0.00 |
October | 0.139374E+10 | 0.428838E+09 | 0.130775E+10 | 0.820284E+09 | 0.487463E+09 | 0.00 | 0.00 |
November | 0.848178E+09 | 0.571261E+09 | 0.877253E+09 | 0.526878E+09 | 0.350376E+09 | 0.00 | 0.00 |
December | 0.867673E+09 | 0.730982E+09 | 0.896550E+09 | 0.636457E+09 | 0.260093E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.982516E+10 | 0.516527E+10 | 0.103572E+11 | 0.516749E+10 | 0.518969E+10 | 0.00 | 0.00 |
Minimum of Months | 0.508996E+09 | 92031485.19 | 0.607850E+09 | 92802549.24 | 0.260093E+09 | 0.00 | 0.00 |
Maximum of Months | 0.139374E+10 | 0.798332E+09 | 0.130775E+10 | 0.820284E+09 | 0.553214E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.151166E+10 | 0.154703E+10 | 0.165463E+10 | 0.108348E+10 | 0.571154E+09 | 0.00 | 0.00 |
February | 0.178180E+10 | 0.140428E+10 | 0.197200E+10 | 0.130559E+10 | 0.666411E+09 | 0.00 | 0.00 |
March | 0.172331E+10 | 0.112425E+10 | 0.196956E+10 | 0.109344E+10 | 0.876123E+09 | 0.00 | 0.00 |
April | 0.112903E+10 | 0.805225E+09 | 0.147829E+10 | 0.584433E+09 | 0.893861E+09 | 0.00 | 0.00 |
May | 0.103507E+10 | 0.552675E+09 | 0.133868E+10 | 0.279066E+09 | 0.105961E+10 | 0.00 | 0.00 |
June | 0.113901E+10 | 0.301699E+09 | 0.121570E+10 | 0.185605E+09 | 0.103010E+10 | 0.00 | 0.00 |
July | 0.141199E+10 | 0.168504E+09 | 0.131684E+10 | 0.228546E+09 | 0.108829E+10 | 0.00 | 0.00 |
August | 0.184073E+10 | 0.238523E+09 | 0.175853E+10 | 0.652106E+09 | 0.110643E+10 | 0.00 | 0.00 |
September | 0.192626E+10 | 0.459201E+09 | 0.184702E+10 | 0.955479E+09 | 0.891544E+09 | 0.00 | 0.00 |
October | 0.279794E+10 | 0.829446E+09 | 0.261549E+10 | 0.164057E+10 | 0.974926E+09 | 0.00 | 0.00 |
November | 0.171290E+10 | 0.109945E+10 | 0.175451E+10 | 0.105376E+10 | 0.700751E+09 | 0.00 | 0.00 |
December | 0.174678E+10 | 0.142312E+10 | 0.179310E+10 | 0.127291E+10 | 0.520186E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.197565E+11 | 0.995341E+10 | 0.207144E+11 | 0.103350E+11 | 0.103794E+11 | 0.00 | 0.00 |
Minimum of Months | 0.103507E+10 | 0.168504E+09 | 0.121570E+10 | 0.185605E+09 | 0.520186E+09 | 0.00 | 0.00 |
Maximum of Months | 0.279794E+10 | 0.154703E+10 | 0.261549E+10 | 0.164057E+10 | 0.110643E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.753797E+09 | 0.776478E+09 | 0.827317E+09 | 0.541740E+09 | 0.285577E+09 | 0.00 | 0.00 |
February | 0.888939E+09 | 0.704259E+09 | 0.986000E+09 | 0.652794E+09 | 0.333205E+09 | 0.00 | 0.00 |
March | 0.860444E+09 | 0.562262E+09 | 0.984780E+09 | 0.546719E+09 | 0.438062E+09 | 0.00 | 0.00 |
April | 0.565086E+09 | 0.400894E+09 | 0.739147E+09 | 0.292217E+09 | 0.446931E+09 | 0.00 | 0.00 |
May | 0.520040E+09 | 0.272552E+09 | 0.669339E+09 | 0.139533E+09 | 0.529806E+09 | 0.00 | 0.00 |
June | 0.571318E+09 | 0.148493E+09 | 0.607850E+09 | 92802549.24 | 0.515048E+09 | 0.00 | 0.00 |
July | 0.708730E+09 | 81288100.62 | 0.658419E+09 | 0.114273E+09 | 0.544146E+09 | 0.00 | 0.00 |
August | 0.923250E+09 | 0.116004E+09 | 0.879267E+09 | 0.326053E+09 | 0.553214E+09 | 0.00 | 0.00 |
September | 0.963817E+09 | 0.226960E+09 | 0.923512E+09 | 0.477739E+09 | 0.445772E+09 | 0.00 | 0.00 |
October | 0.139870E+10 | 0.411884E+09 | 0.130775E+10 | 0.820284E+09 | 0.487463E+09 | 0.00 | 0.00 |
November | 0.856120E+09 | 0.548265E+09 | 0.877253E+09 | 0.526878E+09 | 0.350376E+09 | 0.00 | 0.00 |
December | 0.871661E+09 | 0.713163E+09 | 0.896550E+09 | 0.636457E+09 | 0.260093E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.988190E+10 | 0.496250E+10 | 0.103572E+11 | 0.516749E+10 | 0.518969E+10 | 0.00 | 0.00 |
Minimum of Months | 0.520040E+09 | 81288100.62 | 0.607850E+09 | 92802549.24 | 0.260093E+09 | 0.00 | 0.00 |
Maximum of Months | 0.139870E+10 | 0.776478E+09 | 0.130775E+10 | 0.820284E+09 | 0.553214E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.754333E+09 | 0.773910E+09 | 0.827317E+09 | 0.541740E+09 | 0.285577E+09 | 0.00 | 0.00 |
February | 0.889604E+09 | 0.701704E+09 | 0.986000E+09 | 0.652794E+09 | 0.333205E+09 | 0.00 | 0.00 |
March | 0.861297E+09 | 0.559260E+09 | 0.984780E+09 | 0.546719E+09 | 0.438062E+09 | 0.00 | 0.00 |
April | 0.566636E+09 | 0.397539E+09 | 0.739147E+09 | 0.292217E+09 | 0.446931E+09 | 0.00 | 0.00 |
May | 0.522978E+09 | 0.268446E+09 | 0.669339E+09 | 0.139533E+09 | 0.529806E+09 | 0.00 | 0.00 |
June | 0.572183E+09 | 0.147377E+09 | 0.607850E+09 | 92802549.24 | 0.515048E+09 | 0.00 | 0.00 |
July | 0.709548E+09 | 80336786.60 | 0.658419E+09 | 0.114273E+09 | 0.544146E+09 | 0.00 | 0.00 |
August | 0.923953E+09 | 0.115072E+09 | 0.879267E+09 | 0.326053E+09 | 0.553214E+09 | 0.00 | 0.00 |
September | 0.964402E+09 | 0.225763E+09 | 0.923512E+09 | 0.477739E+09 | 0.445772E+09 | 0.00 | 0.00 |
October | 0.140008E+10 | 0.409183E+09 | 0.130775E+10 | 0.820284E+09 | 0.487463E+09 | 0.00 | 0.00 |
November | 0.857494E+09 | 0.544925E+09 | 0.877253E+09 | 0.526878E+09 | 0.350376E+09 | 0.00 | 0.00 |
December | 0.872280E+09 | 0.710637E+09 | 0.896550E+09 | 0.636457E+09 | 0.260093E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.989478E+10 | 0.493415E+10 | 0.103572E+11 | 0.516749E+10 | 0.518969E+10 | 0.00 | 0.00 |
Minimum of Months | 0.522978E+09 | 80336786.60 | 0.607850E+09 | 92802549.24 | 0.260093E+09 | 0.00 | 0.00 |
Maximum of Months | 0.140008E+10 | 0.773910E+09 | 0.130775E+10 | 0.820284E+09 | 0.553214E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.756134E+09 | 0.764163E+09 | 0.827317E+09 | 0.541740E+09 | 0.285577E+09 | 0.00 | 0.00 |
February | 0.891791E+09 | 0.692231E+09 | 0.986000E+09 | 0.652794E+09 | 0.333205E+09 | 0.00 | 0.00 |
March | 0.863708E+09 | 0.549518E+09 | 0.984780E+09 | 0.546719E+09 | 0.438062E+09 | 0.00 | 0.00 |
April | 0.570233E+09 | 0.388399E+09 | 0.739147E+09 | 0.292217E+09 | 0.446931E+09 | 0.00 | 0.00 |
May | 0.529054E+09 | 0.259608E+09 | 0.669339E+09 | 0.139533E+09 | 0.529806E+09 | 0.00 | 0.00 |
June | 0.573899E+09 | 0.144685E+09 | 0.607850E+09 | 92802549.24 | 0.515048E+09 | 0.00 | 0.00 |
July | 0.710624E+09 | 78649947.01 | 0.658419E+09 | 0.114273E+09 | 0.544146E+09 | 0.00 | 0.00 |
August | 0.924616E+09 | 0.113677E+09 | 0.879267E+09 | 0.326053E+09 | 0.553214E+09 | 0.00 | 0.00 |
September | 0.965276E+09 | 0.223365E+09 | 0.923512E+09 | 0.477739E+09 | 0.445772E+09 | 0.00 | 0.00 |
October | 0.140287E+10 | 0.403341E+09 | 0.130775E+10 | 0.820284E+09 | 0.487463E+09 | 0.00 | 0.00 |
November | 0.860212E+09 | 0.537323E+09 | 0.877253E+09 | 0.526878E+09 | 0.350376E+09 | 0.00 | 0.00 |
December | 0.874227E+09 | 0.701941E+09 | 0.896550E+09 | 0.636457E+09 | 0.260093E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.992265E+10 | 0.485690E+10 | 0.103572E+11 | 0.516749E+10 | 0.518969E+10 | 0.00 | 0.00 |
Minimum of Months | 0.529054E+09 | 78649947.01 | 0.607850E+09 | 92802549.24 | 0.260093E+09 | 0.00 | 0.00 |
Maximum of Months | 0.140287E+10 | 0.764163E+09 | 0.130775E+10 | 0.820284E+09 | 0.553214E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.762555E+09 | 0.724875E+09 | 0.827317E+09 | 0.541740E+09 | 0.285577E+09 | 0.00 | 0.00 |
February | 0.899581E+09 | 0.653843E+09 | 0.986000E+09 | 0.652794E+09 | 0.333205E+09 | 0.00 | 0.00 |
March | 0.871457E+09 | 0.511458E+09 | 0.984780E+09 | 0.546719E+09 | 0.438062E+09 | 0.00 | 0.00 |
April | 0.579325E+09 | 0.357011E+09 | 0.739147E+09 | 0.292217E+09 | 0.446931E+09 | 0.00 | 0.00 |
May | 0.543297E+09 | 0.234742E+09 | 0.669339E+09 | 0.139533E+09 | 0.529806E+09 | 0.00 | 0.00 |
June | 0.579159E+09 | 0.134159E+09 | 0.607850E+09 | 92802549.24 | 0.515048E+09 | 0.00 | 0.00 |
July | 0.712233E+09 | 73522694.03 | 0.658419E+09 | 0.114273E+09 | 0.544146E+09 | 0.00 | 0.00 |
August | 0.924181E+09 | 0.109676E+09 | 0.879267E+09 | 0.326053E+09 | 0.553214E+09 | 0.00 | 0.00 |
September | 0.966736E+09 | 0.215437E+09 | 0.923512E+09 | 0.477739E+09 | 0.445772E+09 | 0.00 | 0.00 |
October | 0.140848E+10 | 0.386260E+09 | 0.130775E+10 | 0.820284E+09 | 0.487463E+09 | 0.00 | 0.00 |
November | 0.866808E+09 | 0.512830E+09 | 0.877253E+09 | 0.526878E+09 | 0.350376E+09 | 0.00 | 0.00 |
December | 0.880960E+09 | 0.667538E+09 | 0.896550E+09 | 0.636457E+09 | 0.260093E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.999477E+10 | 0.458135E+10 | 0.103572E+11 | 0.516749E+10 | 0.518969E+10 | 0.00 | 0.00 |
Minimum of Months | 0.543297E+09 | 73522694.03 | 0.607850E+09 | 92802549.24 | 0.260093E+09 | 0.00 | 0.00 |
Maximum of Months | 0.140848E+10 | 0.724875E+09 | 0.130775E+10 | 0.820284E+09 | 0.553214E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.6 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.5 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.46 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 7.99 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.30 | 9.14 | 4.42 | 7.76 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.07 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.75 | 20.26 | 4.06 | 17.38 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.83 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.95 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.02 | 7.95 | 4.86 | 2.63 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 5.00 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.97 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.51 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.5 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.75 | 20.26 | 5.65 | 17.38 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.34 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.33 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.37 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 17.98 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.26 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.29 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.20 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.31 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.52 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.56 | 8.50 | 3.60 | 6.14 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.63 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.34 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.26 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.4 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.2 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.4 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.56 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.34 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.46 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.1 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.4 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.2 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.98 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.69 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.42 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.95 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.09 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.83 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.56 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.75 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.09 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.69 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.95 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.16 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.56 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.364435E+09 | -240405068.2 | 0.00 | 0.00 | 744.00 | 0.00 | -124029854.6 | 58.99 | 0.00 | 0.00 |
February | 0.332606E+09 | -220487404.3 | 0.00 | 0.00 | 672.00 | 0.00 | -112118126.3 | 58.99 | 0.00 | 0.00 |
March | 0.365001E+09 | -242340562.2 | 0.00 | 0.00 | 744.00 | 0.00 | -122660182.0 | 58.99 | 0.00 | 0.00 |
April | 0.335442E+09 | -219905295.8 | 0.00 | 0.00 | 720.00 | 0.00 | -115537025.6 | 58.99 | 0.00 | 0.00 |
May | 0.325598E+09 | -211550072.7 | 0.00 | 0.00 | 744.00 | 0.00 | -114047855.7 | 58.99 | 0.00 | 0.00 |
June | 0.300417E+09 | -191756581.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108660172.3 | 58.99 | 0.00 | 0.00 |
July | 0.295865E+09 | -184152704.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111712354.3 | 58.99 | 0.00 | 0.00 |
August | 0.296751E+09 | -185069817.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111680909.0 | 58.99 | 0.00 | 0.00 |
September | 0.291466E+09 | -182922800.5 | 0.00 | 0.00 | 720.00 | 0.00 | -108543493.7 | 58.99 | 0.00 | 0.00 |
October | 0.313360E+09 | -199541243.1 | 0.00 | 0.00 | 744.00 | 0.00 | -113818967.1 | 58.99 | 0.00 | 0.00 |
November | 0.324246E+09 | -207784847.4 | 0.00 | 0.00 | 720.00 | 0.00 | -116461124.0 | 58.99 | 0.00 | 0.00 |
December | 0.353845E+09 | -230504926.2 | 0.00 | 0.00 | 744.00 | 0.00 | -123340104.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.389903E+10 | -.251642E+10 | 8760.00 | -.138261E+10 | 58.99 | |||||
Minimum of Months | 0.291466E+09 | -242340562.2 | 0.00 | 0.00 | 672.00 | 0.00 | -124029854.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.365001E+09 | -182922800.5 | 0.00 | 0.00 | 744.00 | 0.00 | -108543493.7 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.362250E+09 | -240403778.5 | 0.00 | 0.00 | 744.00 | 0.00 | -121845801.4 | 58.99 | 0.00 | 0.00 |
February | 0.330532E+09 | -220483344.5 | 0.00 | 0.00 | 672.00 | 0.00 | -110048398.6 | 58.99 | 0.00 | 0.00 |
March | 0.362225E+09 | -242344787.0 | 0.00 | 0.00 | 744.00 | 0.00 | -119880204.5 | 58.99 | 0.00 | 0.00 |
April | 0.333047E+09 | -219905808.1 | 0.00 | 0.00 | 720.00 | 0.00 | -113141107.9 | 58.99 | 0.00 | 0.00 |
May | 0.324610E+09 | -211549982.7 | 0.00 | 0.00 | 744.00 | 0.00 | -113060494.8 | 58.99 | 0.00 | 0.00 |
June | 0.300151E+09 | -191757249.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108394085.8 | 58.99 | 0.00 | 0.00 |
July | 0.295646E+09 | -184149133.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111497293.3 | 58.99 | 0.00 | 0.00 |
August | 0.296590E+09 | -185069652.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111520337.4 | 58.99 | 0.00 | 0.00 |
September | 0.291280E+09 | -182925117.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108354660.4 | 58.99 | 0.00 | 0.00 |
October | 0.312431E+09 | -199536763.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112894593.3 | 58.99 | 0.00 | 0.00 |
November | 0.321792E+09 | -207782326.6 | 0.00 | 0.00 | 720.00 | 0.00 | -114009613.0 | 58.99 | 0.00 | 0.00 |
December | 0.351345E+09 | -230504599.5 | 0.00 | 0.00 | 744.00 | 0.00 | -120840404.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.388190E+10 | -.251641E+10 | 8760.00 | -.136549E+10 | 58.99 | |||||
Minimum of Months | 0.291280E+09 | -242344787.0 | 0.00 | 0.00 | 672.00 | 0.00 | -121845801.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.362250E+09 | -182925117.6 | 0.00 | 0.00 | 744.00 | 0.00 | -108354660.4 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.335225E+09 | -211403378.1 | 0.00 | 0.00 | 744.00 | 0.00 | -123821654.5 | 58.99 | 0.00 | 0.00 |
February | 0.305718E+09 | -194055002.1 | 0.00 | 0.00 | 672.00 | 0.00 | -111663308.8 | 58.98 | 0.00 | 0.00 |
March | 0.338149E+09 | -216450116.3 | 0.00 | 0.00 | 744.00 | 0.00 | -121698401.3 | 58.99 | 0.00 | 0.00 |
April | 0.307634E+09 | -193267066.0 | 0.00 | 0.00 | 720.00 | 0.00 | -114366972.4 | 58.99 | 0.00 | 0.00 |
May | 0.300386E+09 | -187647352.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112739021.8 | 59.00 | 0.00 | 0.00 |
June | 0.278148E+09 | -170876326.6 | 0.00 | 0.00 | 720.00 | 0.00 | -107271538.5 | 59.00 | 0.00 | 0.00 |
July | 0.270671E+09 | -160843192.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109828012.6 | 59.00 | 0.00 | 0.00 |
August | 0.275277E+09 | -165430720.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109846489.8 | 58.99 | 0.00 | 0.00 |
September | 0.267819E+09 | -160650901.5 | 0.00 | 0.00 | 720.00 | 0.00 | -107167722.6 | 59.00 | 0.00 | 0.00 |
October | 0.288120E+09 | -175498721.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112621054.5 | 58.99 | 0.00 | 0.00 |
November | 0.298953E+09 | -183456189.9 | 0.00 | 0.00 | 720.00 | 0.00 | -115496823.0 | 58.99 | 0.00 | 0.00 |
December | 0.323991E+09 | -201200864.6 | 0.00 | 0.00 | 744.00 | 0.00 | -122790419.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.359009E+10 | -.222078E+10 | 8760.00 | -.136931E+10 | 58.99 | |||||
Minimum of Months | 0.267819E+09 | -216450116.3 | 0.00 | 0.00 | 672.00 | 0.00 | -123821654.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.338149E+09 | -160650901.5 | 0.00 | 0.00 | 744.00 | 0.00 | -107167722.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.335677E+09 | -211410811.4 | 0.00 | 0.00 | 744.00 | 0.00 | -124265826.3 | 58.99 | 0.00 | 0.00 |
February | 0.306108E+09 | -194038625.2 | 0.00 | 0.00 | 672.00 | 0.00 | -112069394.6 | 59.00 | 0.00 | 0.00 |
March | 0.338610E+09 | -216449471.1 | 0.00 | 0.00 | 744.00 | 0.00 | -122160927.0 | 58.99 | 0.00 | 0.00 |
April | 0.308115E+09 | -193276313.4 | 0.00 | 0.00 | 720.00 | 0.00 | -114838645.4 | 58.99 | 0.00 | 0.00 |
May | 0.300656E+09 | -187664479.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112991730.9 | 58.99 | 0.00 | 0.00 |
June | 0.278168E+09 | -170902260.5 | 0.00 | 0.00 | 720.00 | 0.00 | -107265797.5 | 58.99 | 0.00 | 0.00 |
July | 0.270629E+09 | -160851964.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109777357.6 | 58.99 | 0.00 | 0.00 |
August | 0.275234E+09 | -165446338.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109787634.6 | 58.98 | 0.00 | 0.00 |
September | 0.267841E+09 | -160679618.5 | 0.00 | 0.00 | 720.00 | 0.00 | -107161632.5 | 58.99 | 0.00 | 0.00 |
October | 0.288350E+09 | -175532911.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112816677.5 | 58.98 | 0.00 | 0.00 |
November | 0.299513E+09 | -183452369.2 | 0.00 | 0.00 | 720.00 | 0.00 | -116060721.1 | 58.99 | 0.00 | 0.00 |
December | 0.324400E+09 | -201183614.7 | 0.00 | 0.00 | 744.00 | 0.00 | -123216850.2 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.359330E+10 | -.222089E+10 | 8760.00 | -.137241E+10 | 58.99 | |||||
Minimum of Months | 0.267841E+09 | -216449471.1 | 0.00 | 0.00 | 672.00 | 0.00 | -124265826.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.338610E+09 | -160679618.5 | 0.00 | 0.00 | 744.00 | 0.00 | -107161632.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.325632E+09 | -199835791.7 | 0.00 | 0.00 | 744.00 | 0.00 | -125795788.6 | 58.98 | 0.00 | 0.00 |
February | 0.296903E+09 | -183490579.6 | 0.00 | 0.00 | 672.00 | 0.00 | -113412279.3 | 59.00 | 0.00 | 0.00 |
March | 0.328462E+09 | -204797008.1 | 0.00 | 0.00 | 744.00 | 0.00 | -123664988.8 | 58.99 | 0.00 | 0.00 |
April | 0.299483E+09 | -182875242.4 | 0.00 | 0.00 | 720.00 | 0.00 | -116607711.6 | 58.99 | 0.00 | 0.00 |
May | 0.292392E+09 | -177476734.1 | 0.00 | 0.00 | 744.00 | 0.00 | -114915458.9 | 58.99 | 0.00 | 0.00 |
June | 0.269705E+09 | -161711666.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107993786.4 | 58.99 | 0.00 | 0.00 |
July | 0.262571E+09 | -152132603.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110438854.4 | 58.99 | 0.00 | 0.00 |
August | 0.267073E+09 | -156536230.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110536348.2 | 58.99 | 0.00 | 0.00 |
September | 0.259902E+09 | -152045338.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107856285.8 | 58.99 | 0.00 | 0.00 |
October | 0.280145E+09 | -165863328.3 | 0.00 | 0.00 | 744.00 | 0.00 | -114282010.3 | 59.00 | 0.00 | 0.00 |
November | 0.291370E+09 | -173265200.2 | 0.00 | 0.00 | 720.00 | 0.00 | -118104393.1 | 58.99 | 0.00 | 0.00 |
December | 0.314726E+09 | -190277166.3 | 0.00 | 0.00 | 744.00 | 0.00 | -124448686.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.348836E+10 | -.210031E+10 | 8760.00 | -.138806E+10 | 58.99 | |||||
Minimum of Months | 0.259902E+09 | -204797008.1 | 0.00 | 0.00 | 672.00 | 0.00 | -125795788.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.328462E+09 | -152045338.2 | 0.00 | 0.00 | 744.00 | 0.00 | -107856285.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.325622E+09 | -199836440.2 | 0.00 | 0.00 | 744.00 | 0.00 | -125785992.6 | 58.98 | 0.00 | 0.00 |
February | 0.296914E+09 | -183491053.9 | 0.00 | 0.00 | 672.00 | 0.00 | -113422597.0 | 59.00 | 0.00 | 0.00 |
March | 0.328538E+09 | -204795580.1 | 0.00 | 0.00 | 744.00 | 0.00 | -123742339.9 | 58.99 | 0.00 | 0.00 |
April | 0.299653E+09 | -182863633.3 | 0.00 | 0.00 | 720.00 | 0.00 | -116789465.6 | 59.00 | 0.00 | 0.00 |
May | 0.292714E+09 | -177481694.6 | 0.00 | 0.00 | 744.00 | 0.00 | -115232079.2 | 58.99 | 0.00 | 0.00 |
June | 0.269825E+09 | -161707871.4 | 0.00 | 0.00 | 720.00 | 0.00 | -108116798.8 | 58.99 | 0.00 | 0.00 |
July | 0.262727E+09 | -152128503.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110598846.5 | 58.99 | 0.00 | 0.00 |
August | 0.267253E+09 | -156528268.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110724412.3 | 58.99 | 0.00 | 0.00 |
September | 0.260029E+09 | -152040615.8 | 0.00 | 0.00 | 720.00 | 0.00 | -107988123.5 | 58.99 | 0.00 | 0.00 |
October | 0.280339E+09 | -165855441.5 | 0.00 | 0.00 | 744.00 | 0.00 | -114483505.6 | 59.00 | 0.00 | 0.00 |
November | 0.291570E+09 | -173278453.1 | 0.00 | 0.00 | 720.00 | 0.00 | -118291084.3 | 58.99 | 0.00 | 0.00 |
December | 0.314749E+09 | -190277660.0 | 0.00 | 0.00 | 744.00 | 0.00 | -124471274.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.348993E+10 | -.210029E+10 | 8760.00 | -.138965E+10 | 58.99 | |||||
Minimum of Months | 0.260029E+09 | -204795580.1 | 0.00 | 0.00 | 672.00 | 0.00 | -125785992.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.328538E+09 | -152040615.8 | 0.00 | 0.00 | 744.00 | 0.00 | -107988123.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.325735E+09 | -199831827.6 | 0.00 | 0.00 | 744.00 | 0.00 | -125902922.2 | 58.99 | 0.00 | 0.00 |
February | 0.297026E+09 | -183494823.6 | 0.00 | 0.00 | 672.00 | 0.00 | -113531317.4 | 58.99 | 0.00 | 0.00 |
March | 0.328689E+09 | -204793123.6 | 0.00 | 0.00 | 744.00 | 0.00 | -123895670.3 | 58.99 | 0.00 | 0.00 |
April | 0.299864E+09 | -182892015.6 | 0.00 | 0.00 | 720.00 | 0.00 | -116972334.1 | 58.99 | 0.00 | 0.00 |
May | 0.293052E+09 | -177467652.0 | 0.00 | 0.00 | 744.00 | 0.00 | -115583854.8 | 58.99 | 0.00 | 0.00 |
June | 0.269907E+09 | -161700813.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108205896.9 | 59.00 | 0.00 | 0.00 |
July | 0.262794E+09 | -152126920.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110667204.2 | 58.99 | 0.00 | 0.00 |
August | 0.267314E+09 | -156530606.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110783520.8 | 58.99 | 0.00 | 0.00 |
September | 0.260096E+09 | -152041022.8 | 0.00 | 0.00 | 720.00 | 0.00 | -108055430.1 | 58.99 | 0.00 | 0.00 |
October | 0.280530E+09 | -165866566.5 | 0.00 | 0.00 | 744.00 | 0.00 | -114663737.6 | 58.99 | 0.00 | 0.00 |
November | 0.291790E+09 | -173272988.1 | 0.00 | 0.00 | 720.00 | 0.00 | -118516618.6 | 58.99 | 0.00 | 0.00 |
December | 0.314859E+09 | -190278745.6 | 0.00 | 0.00 | 744.00 | 0.00 | -124580183.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.349166E+10 | -.210030E+10 | 8760.00 | -.139136E+10 | 58.99 | |||||
Minimum of Months | 0.260096E+09 | -204793123.6 | 0.00 | 0.00 | 672.00 | 0.00 | -125902922.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.328689E+09 | -152041022.8 | 0.00 | 0.00 | 744.00 | 0.00 | -108055430.1 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 199.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 216.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 261.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 372.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 365.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 389.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 285.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 305.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 240.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 211.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3472.67 | ||||||||||
Minimum of Months | 199.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 389.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.154306E+11 | 56567.15 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149692E+11 | 56567.15 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.770449E+10 | 56567.15 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.223907E+10 | 56567.15 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5877197.00 | 3188.63 | 29-OCT-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.456747E+10 | 56567.15 | 20-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110861E+11 | 56567.15 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.560028E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.154306E+11 | 56567.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.480317E+10 | 31016.26 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.465887E+10 | 31016.26 | 03-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196438E+10 | 31016.26 | 17-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.383279E+09 | 11615.34 | 21-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112476E+10 | 29506.34 | 22-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.309539E+10 | 31016.26 | 07-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160299E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.480317E+10 | 31016.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.601854E+10 | 31702.38 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.574574E+10 | 31702.38 | 03-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.277919E+10 | 31702.38 | 13-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.679744E+09 | 21377.16 | 02-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168418E+10 | 31702.38 | 23-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.418075E+10 | 31702.38 | 31-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210881E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.601854E+10 | 31702.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.633431E+10 | 31522.86 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.599821E+10 | 31522.86 | 03-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.301865E+10 | 31522.86 | 13-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.794178E+09 | 27226.29 | 02-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3980.07 | 6.63 | 29-OCT-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.186036E+10 | 31522.86 | 22-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.446029E+10 | 31522.86 | 07-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224660E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.633431E+10 | 31522.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.675150E+10 | 31514.44 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.635697E+10 | 31514.44 | 03-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.335029E+10 | 31514.44 | 13-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.961720E+09 | 31514.44 | 02-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1259113.30 | 1229.94 | 29-OCT-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.208468E+10 | 31514.44 | 22-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.482252E+10 | 31514.44 | 07-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.243289E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.675150E+10 | 31514.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.140226E+11 | 54748.74 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130634E+11 | 54748.74 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.767057E+10 | 54748.74 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262688E+10 | 54748.74 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9492686.29 | 2743.79 | 01-MAY-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18301515.99 | 3362.38 | 28-OCT-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.496087E+10 | 54748.74 | 15-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105015E+11 | 54748.74 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.528737E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.140226E+11 | 54748.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.730701E+10 | 28891.45 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.681388E+10 | 28891.45 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.401724E+10 | 28891.45 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138817E+10 | 28891.45 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8709218.53 | 2339.57 | 01-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11441380.33 | 2505.06 | 31-OCT-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.260174E+10 | 28891.45 | 15-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.545701E+10 | 28891.45 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.276052E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.730701E+10 | 28891.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.740806E+10 | 28741.59 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.691894E+10 | 28741.59 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.413254E+10 | 28741.59 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146127E+10 | 28741.59 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16990860.36 | 6589.07 | 01-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17188873.84 | 2613.29 | 28-OCT-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.267865E+10 | 28741.59 | 15-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.555827E+10 | 28741.59 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.281919E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.740806E+10 | 28741.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.779057E+10 | 28578.12 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.729970E+10 | 28578.12 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.450526E+10 | 28578.12 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168817E+10 | 28578.12 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 52806412.20 | 16084.22 | 01-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 34535765.79 | 3558.63 | 28-OCT-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.290739E+10 | 28578.12 | 15-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.590344E+10 | 28578.12 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.301819E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.779057E+10 | 28578.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.943836E+10 | 29392.87 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.896232E+10 | 29392.87 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.582408E+10 | 29392.87 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.246895E+10 | 29392.87 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.216940E+09 | 29392.87 | 01-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117967E+09 | 17948.23 | 31-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.363490E+10 | 29392.87 | 13-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.712423E+10 | 29392.87 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.377878E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.943836E+10 | 29392.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 11060635.30 | 7885372.53 | 2588.32 | 27-MAR-16:10 | 1839.33 | 0.00 |
April | 0.00 | 0.00 | 0.765029E+09 | 0.645178E+09 | 11012.15 | 08-APR-12:10 | 9128.67 | 0.00 |
May | 0.00 | 0.00 | 0.405897E+10 | 0.338535E+10 | 39373.85 | 31-MAY-07:03 | 30554.05 | 0.00 |
June | 0.00 | 0.00 | 0.197729E+11 | 0.130356E+11 | 45045.13 | 25-JUN-07:02 | 25545.81 | 0.00 |
July | 0.00 | 0.00 | 0.335728E+11 | 0.206331E+11 | 46172.10 | 22-JUL-07:01 | 23211.87 | 0.00 |
August | 0.00 | 0.00 | 0.313175E+11 | 0.213184E+11 | 45668.46 | 17-AUG-07:01 | 24725.14 | 0.00 |
September | 0.00 | 0.00 | 0.155976E+11 | 0.110173E+11 | 45038.43 | 14-SEP-07:02 | 26142.40 | 0.00 |
October | 0.00 | 0.00 | 0.529318E+10 | 0.351088E+10 | 43383.67 | 06-OCT-07:02 | 22717.79 | 0.00 |
November | 0.00 | 0.00 | 11728542.79 | 9291877.48 | 2191.77 | 04-NOV-13:00 | 1698.17 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.110401E+12 | 0.735629E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.335728E+11 | 0.213184E+11 | 46172.10 | 30554.05 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 7024.65 | 7024.65 | 11.71 | 20-FEB-20:20 | 11.71 | 0.00 |
March | 0.00 | 0.00 | 17195048.15 | 12568489.02 | 2318.70 | 27-MAR-16:10 | 1668.59 | 0.00 |
April | 0.00 | 0.00 | 0.602690E+09 | 0.508590E+09 | 22070.70 | 07-APR-20:02 | 17966.46 | 0.00 |
May | 0.00 | 0.00 | 0.289998E+10 | 0.246358E+10 | 22580.11 | 30-MAY-07:03 | 18553.89 | 0.00 |
June | 0.00 | 0.00 | 0.114175E+11 | 0.792406E+10 | 23956.92 | 27-JUN-07:02 | 16595.08 | 0.00 |
July | 0.00 | 0.00 | 0.173806E+11 | 0.112869E+11 | 24513.47 | 22-JUL-07:01 | 15159.82 | 0.00 |
August | 0.00 | 0.00 | 0.163604E+11 | 0.116394E+11 | 24244.91 | 17-AUG-07:01 | 15863.19 | 0.00 |
September | 0.00 | 0.00 | 0.889458E+10 | 0.657667E+10 | 24015.68 | 14-SEP-07:02 | 16610.62 | 0.00 |
October | 0.00 | 0.00 | 0.347548E+10 | 0.234947E+10 | 23651.39 | 06-OCT-07:02 | 12964.91 | 0.00 |
November | 0.00 | 0.00 | 22464828.26 | 18389958.06 | 10669.49 | 03-NOV-20:15 | 8350.85 | 0.00 |
December | 0.00 | 0.00 | 31236.97 | 31236.97 | 22.83 | 17-DEC-23:10 | 22.83 | 0.00 |
Annual Sum or Average | 0.610710E+11 | 0.427797E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.173806E+11 | 0.116394E+11 | 24513.47 | 18553.89 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 5629136.24 | 4047831.00 | 1444.87 | 27-MAR-16:10 | 1036.80 | 0.00 |
April | 0.00 | 0.00 | 0.408378E+09 | 0.346642E+09 | 6300.84 | 08-APR-12:10 | 5281.79 | 0.00 |
May | 0.00 | 0.00 | 0.185455E+10 | 0.158206E+10 | 20941.68 | 31-MAY-06:03 | 12990.38 | 0.00 |
June | 0.00 | 0.00 | 0.860330E+10 | 0.582900E+10 | 26045.27 | 25-JUN-07:02 | 13000.08 | 0.00 |
July | 0.00 | 0.00 | 0.137701E+11 | 0.867644E+10 | 26112.15 | 22-JUL-06:01 | 13252.82 | 0.00 |
August | 0.00 | 0.00 | 0.129999E+11 | 0.907147E+10 | 26311.39 | 06-AUG-07:01 | 12828.74 | 0.00 |
September | 0.00 | 0.00 | 0.650808E+10 | 0.468794E+10 | 25645.74 | 14-SEP-06:02 | 14343.96 | 0.00 |
October | 0.00 | 0.00 | 0.239162E+10 | 0.162310E+10 | 24408.91 | 06-OCT-06:02 | 12688.20 | 0.00 |
November | 0.00 | 0.00 | 5545257.86 | 4391232.89 | 1074.52 | 04-NOV-12:50 | 841.72 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.465471E+11 | 0.318251E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.137701E+11 | 0.907147E+10 | 26311.39 | 14343.96 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 3390313.26 | 2436627.77 | 1085.96 | 27-MAR-16:10 | 778.22 | 0.00 |
April | 0.00 | 0.00 | 0.379774E+09 | 0.322172E+09 | 6123.36 | 08-APR-12:10 | 5126.45 | 0.00 |
May | 0.00 | 0.00 | 0.180492E+10 | 0.154054E+10 | 20676.71 | 31-MAY-06:03 | 12821.91 | 0.00 |
June | 0.00 | 0.00 | 0.856676E+10 | 0.580152E+10 | 25829.19 | 25-JUN-07:02 | 12887.35 | 0.00 |
July | 0.00 | 0.00 | 0.137654E+11 | 0.867284E+10 | 25898.49 | 22-JUL-06:01 | 13158.80 | 0.00 |
August | 0.00 | 0.00 | 0.130092E+11 | 0.907942E+10 | 26098.15 | 06-AUG-07:01 | 12757.95 | 0.00 |
September | 0.00 | 0.00 | 0.648754E+10 | 0.467275E+10 | 25434.36 | 14-SEP-06:02 | 14221.37 | 0.00 |
October | 0.00 | 0.00 | 0.233823E+10 | 0.158565E+10 | 24205.79 | 06-OCT-06:02 | 12579.75 | 0.00 |
November | 0.00 | 0.00 | 3802627.88 | 2995252.13 | 877.41 | 04-NOV-12:50 | 687.04 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.463590E+11 | 0.316803E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.137654E+11 | 0.907942E+10 | 26098.15 | 14221.37 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 1329026.60 | 952494.27 | 673.68 | 27-MAR-16:10 | 481.75 | 0.00 |
April | 0.00 | 0.00 | 0.330584E+09 | 0.280718E+09 | 5758.39 | 08-APR-12:10 | 4803.57 | 0.00 |
May | 0.00 | 0.00 | 0.166233E+10 | 0.141865E+10 | 18152.98 | 31-MAY-06:03 | 11173.93 | 0.00 |
June | 0.00 | 0.00 | 0.828614E+10 | 0.559127E+10 | 25870.42 | 25-JUN-07:02 | 12763.45 | 0.00 |
July | 0.00 | 0.00 | 0.134930E+11 | 0.846588E+10 | 25936.38 | 22-JUL-06:01 | 13020.82 | 0.00 |
August | 0.00 | 0.00 | 0.127497E+11 | 0.886650E+10 | 26141.69 | 06-AUG-07:01 | 12631.89 | 0.00 |
September | 0.00 | 0.00 | 0.626492E+10 | 0.450004E+10 | 25480.00 | 14-SEP-06:02 | 14093.99 | 0.00 |
October | 0.00 | 0.00 | 0.215395E+10 | 0.145710E+10 | 24254.06 | 06-OCT-06:02 | 12567.03 | 0.00 |
November | 0.00 | 0.00 | 1044638.62 | 821014.33 | 362.00 | 04-NOV-13:00 | 281.79 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.449429E+11 | 0.305819E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.134930E+11 | 0.886650E+10 | 26141.69 | 14093.99 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 115019.97 | 80616.57 | 189.77 | 27-MAR-16:10 | 133.00 | 0.00 |
April | 0.00 | 0.00 | 0.443704E+09 | 0.372539E+09 | 8766.56 | 08-APR-12:00 | 7114.75 | 0.00 |
May | 0.00 | 0.00 | 0.248643E+10 | 0.207568E+10 | 35048.55 | 31-MAY-07:03 | 28440.69 | 0.00 |
June | 0.00 | 0.00 | 0.136563E+11 | 0.895260E+10 | 44304.32 | 25-JUN-08:62 | 21304.48 | 0.00 |
July | 0.00 | 0.00 | 0.230832E+11 | 0.140249E+11 | 44281.37 | 09-JUL-08:62 | 21741.47 | 0.00 |
August | 0.00 | 0.00 | 0.221171E+11 | 0.149866E+11 | 43866.17 | 06-AUG-08:62 | 18075.65 | 0.00 |
September | 0.00 | 0.00 | 0.103037E+11 | 0.718951E+10 | 43077.01 | 14-SEP-07:02 | 24695.38 | 0.00 |
October | 0.00 | 0.00 | 0.323589E+10 | 0.212486E+10 | 41499.39 | 06-OCT-07:02 | 21731.63 | 0.00 |
November | 0.00 | 0.00 | 9722.77 | 7987.79 | 2.29 | 04-NOV-16:00 | 1.91 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.753264E+11 | 0.497268E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.230832E+11 | 0.149866E+11 | 44304.32 | 28440.69 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 523.26 | 369.12 | 0.48 | 27-MAR-16:10 | 0.34 | 0.00 |
April | 0.00 | 0.00 | 0.209254E+09 | 0.176388E+09 | 4392.66 | 08-APR-12:00 | 3567.66 | 0.00 |
May | 0.00 | 0.00 | 0.121942E+10 | 0.101957E+10 | 16047.53 | 30-MAY-07:03 | 12433.07 | 0.00 |
June | 0.00 | 0.00 | 0.692037E+10 | 0.455420E+10 | 23641.91 | 25-JUN-08:62 | 11307.59 | 0.00 |
July | 0.00 | 0.00 | 0.117933E+11 | 0.719372E+10 | 23637.85 | 09-JUL-08:62 | 11520.15 | 0.00 |
August | 0.00 | 0.00 | 0.113010E+11 | 0.768101E+10 | 23408.54 | 06-AUG-08:62 | 9643.49 | 0.00 |
September | 0.00 | 0.00 | 0.521072E+10 | 0.364867E+10 | 22978.67 | 14-SEP-07:02 | 13154.28 | 0.00 |
October | 0.00 | 0.00 | 0.157483E+10 | 0.103839E+10 | 22142.03 | 06-OCT-07:02 | 11609.76 | 0.00 |
November | 0.00 | 0.00 | 3199.66 | 2591.85 | 1.00 | 04-NOV-16:00 | 0.83 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.382289E+11 | 0.253120E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.117933E+11 | 0.768101E+10 | 23641.91 | 13154.28 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 295.20 | 208.09 | 0.38 | 27-MAR-16:20 | 0.27 | 0.00 |
April | 0.00 | 0.00 | 0.195339E+09 | 0.164569E+09 | 4267.89 | 08-APR-12:00 | 3456.93 | 0.00 |
May | 0.00 | 0.00 | 0.116608E+10 | 0.972447E+09 | 14851.00 | 31-MAY-07:03 | 11908.69 | 0.00 |
June | 0.00 | 0.00 | 0.680417E+10 | 0.446730E+10 | 23513.62 | 25-JUN-08:62 | 11197.78 | 0.00 |
July | 0.00 | 0.00 | 0.116797E+11 | 0.710666E+10 | 23511.09 | 09-JUL-08:62 | 11409.06 | 0.00 |
August | 0.00 | 0.00 | 0.111991E+11 | 0.759570E+10 | 23285.02 | 06-AUG-08:62 | 9579.57 | 0.00 |
September | 0.00 | 0.00 | 0.513489E+10 | 0.358824E+10 | 22858.93 | 14-SEP-07:02 | 13030.73 | 0.00 |
October | 0.00 | 0.00 | 0.151576E+10 | 0.997571E+09 | 22025.31 | 06-OCT-07:02 | 11532.34 | 0.00 |
November | 0.00 | 0.00 | 1001.71 | 823.44 | 0.87 | 04-NOV-16:00 | 0.72 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.376951E+11 | 0.248925E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.116797E+11 | 0.759570E+10 | 23513.62 | 13030.73 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.166475E+09 | 0.140088E+09 | 3994.59 | 08-APR-12:00 | 3225.40 | 0.00 |
May | 0.00 | 0.00 | 0.105261E+10 | 0.873284E+09 | 10921.93 | 31-MAY-07:03 | 8602.88 | 0.00 |
June | 0.00 | 0.00 | 0.653952E+10 | 0.427955E+10 | 23342.47 | 25-JUN-08:62 | 10980.53 | 0.00 |
July | 0.00 | 0.00 | 0.114841E+11 | 0.696459E+10 | 23343.62 | 09-JUL-08:62 | 11213.77 | 0.00 |
August | 0.00 | 0.00 | 0.110517E+11 | 0.747800E+10 | 23130.05 | 06-AUG-08:62 | 9490.24 | 0.00 |
September | 0.00 | 0.00 | 0.499870E+10 | 0.348458E+10 | 22706.11 | 14-SEP-07:02 | 12826.21 | 0.00 |
October | 0.00 | 0.00 | 0.140471E+10 | 0.922123E+09 | 21884.77 | 06-OCT-07:02 | 11404.85 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.366978E+11 | 0.241422E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.114841E+11 | 0.747800E+10 | 23343.62 | 12826.21 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.132516E+09 | 0.111666E+09 | 3831.08 | 08-APR-12:00 | 3098.00 | 0.00 |
May | 0.00 | 0.00 | 0.905929E+09 | 0.748377E+09 | 8580.05 | 31-MAY-14:10 | 5876.57 | 0.00 |
June | 0.00 | 0.00 | 0.605531E+10 | 0.396224E+10 | 24113.01 | 25-JUN-08:62 | 10584.41 | 0.00 |
July | 0.00 | 0.00 | 0.115684E+11 | 0.700630E+10 | 24394.19 | 22-JUL-07:01 | 10196.65 | 0.00 |
August | 0.00 | 0.00 | 0.113885E+11 | 0.771847E+10 | 24099.30 | 17-AUG-07:01 | 11171.87 | 0.00 |
September | 0.00 | 0.00 | 0.498258E+10 | 0.348676E+10 | 23733.45 | 14-SEP-07:02 | 11789.90 | 0.00 |
October | 0.00 | 0.00 | 0.132657E+10 | 0.877514E+09 | 8580.05 | 06-OCT-07:02 | 4300.89 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.363598E+11 | 0.239113E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.115684E+11 | 0.771847E+10 | 24394.19 | 11789.90 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.172072E+10 | 0.41 | 1932.91 | 01-JAN-08:61 | 0.88 |
February | 0.157768E+10 | 0.42 | 1932.91 | 01-FEB-08:61 | 0.88 |
March | 0.156390E+10 | 0.39 | 1932.91 | 01-MAR-08:61 | 0.88 |
April | 0.140698E+10 | 0.37 | 1932.91 | 01-APR-07:01 | 0.88 |
May | 0.140314E+10 | 0.36 | 1767.87 | 31-MAY-07:03 | 0.84 |
June | 0.138196E+10 | 0.36 | 1932.91 | 08-JUN-07:02 | 0.87 |
July | 0.150932E+10 | 0.37 | 1932.91 | 01-JUL-07:02 | 0.87 |
August | 0.153305E+10 | 0.37 | 1932.91 | 01-AUG-07:02 | 0.87 |
September | 0.137562E+10 | 0.36 | 1932.91 | 01-SEP-07:02 | 0.87 |
October | 0.140386E+10 | 0.36 | 1932.91 | 06-OCT-07:02 | 0.87 |
November | 0.144924E+10 | 0.38 | 1932.91 | 20-NOV-08:61 | 0.88 |
December | 0.163592E+10 | 0.40 | 1932.91 | 01-DEC-08:61 | 0.88 |
Annual Sum or Average | 0.179614E+11 | 0.38 | |||
Minimum of Months | 0.137562E+10 | 0.36 | 1767.87 | 0.84 | |
Maximum of Months | 0.172072E+10 | 0.42 | 1932.91 | 0.88 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.711926E+09 | 0.31 | 1119.36 | 01-JAN-08:61 | 0.91 |
February | 0.650939E+09 | 0.32 | 1119.36 | 03-FEB-08:61 | 0.91 |
March | 0.670769E+09 | 0.33 | 1119.36 | 17-MAR-07:01 | 0.91 |
April | 0.676413E+09 | 0.35 | 699.26 | 21-APR-07:01 | 0.72 |
May | 0.774999E+09 | 0.36 | 1119.36 | 30-MAY-07:03 | 0.90 |
June | 0.727262E+09 | 0.37 | 1119.36 | 08-JUN-07:02 | 0.90 |
July | 0.801324E+09 | 0.39 | 1119.36 | 01-JUL-07:02 | 0.90 |
August | 0.808889E+09 | 0.39 | 1119.36 | 01-AUG-07:02 | 0.90 |
September | 0.732237E+09 | 0.37 | 1119.36 | 01-SEP-07:02 | 0.90 |
October | 0.766252E+09 | 0.37 | 1119.36 | 06-OCT-07:02 | 0.90 |
November | 0.666635E+09 | 0.34 | 1086.67 | 22-NOV-08:61 | 0.90 |
December | 0.672550E+09 | 0.31 | 1119.36 | 07-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.866019E+10 | 0.35 | |||
Minimum of Months | 0.650939E+09 | 0.31 | 699.26 | 0.72 | |
Maximum of Months | 0.808889E+09 | 0.39 | 1119.36 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.798513E+09 | 0.33 | 1152.61 | 01-JAN-08:61 | 0.91 |
February | 0.729491E+09 | 0.34 | 1152.61 | 03-FEB-07:02 | 0.91 |
March | 0.741126E+09 | 0.32 | 1152.61 | 13-MAR-06:01 | 0.91 |
April | 0.662133E+09 | 0.30 | 927.37 | 02-APR-07:02 | 0.82 |
May | 0.674083E+09 | 0.30 | 1007.11 | 30-MAY-06:03 | 0.85 |
June | 0.665426E+09 | 0.30 | 1152.61 | 08-JUN-06:03 | 0.90 |
July | 0.702055E+09 | 0.30 | 1152.61 | 01-JUL-06:03 | 0.90 |
August | 0.728280E+09 | 0.31 | 1152.61 | 01-AUG-06:02 | 0.90 |
September | 0.651442E+09 | 0.30 | 1152.61 | 01-SEP-06:02 | 0.89 |
October | 0.667901E+09 | 0.30 | 1152.61 | 06-OCT-06:02 | 0.90 |
November | 0.684044E+09 | 0.31 | 1152.61 | 23-NOV-08:61 | 0.91 |
December | 0.755103E+09 | 0.32 | 1152.61 | 31-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.845960E+10 | 0.31 | |||
Minimum of Months | 0.651442E+09 | 0.30 | 927.37 | 0.82 | |
Maximum of Months | 0.798513E+09 | 0.34 | 1152.61 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.800104E+09 | 0.34 | 1143.91 | 01-JAN-08:61 | 0.91 |
February | 0.730191E+09 | 0.34 | 1143.91 | 03-FEB-07:02 | 0.91 |
March | 0.741090E+09 | 0.32 | 1143.91 | 13-MAR-06:01 | 0.91 |
April | 0.659712E+09 | 0.30 | 1050.36 | 02-APR-07:02 | 0.87 |
May | 0.668988E+09 | 0.30 | 988.74 | 31-MAY-06:03 | 0.84 |
June | 0.660702E+09 | 0.30 | 1143.91 | 08-JUN-06:03 | 0.90 |
July | 0.698867E+09 | 0.30 | 1143.91 | 01-JUL-06:03 | 0.90 |
August | 0.725486E+09 | 0.31 | 1143.91 | 01-AUG-06:02 | 0.90 |
September | 0.646704E+09 | 0.30 | 1143.91 | 01-SEP-06:02 | 0.89 |
October | 0.662803E+09 | 0.30 | 1143.91 | 06-OCT-06:02 | 0.90 |
November | 0.682926E+09 | 0.31 | 1143.91 | 22-NOV-07:02 | 0.91 |
December | 0.756007E+09 | 0.32 | 1143.91 | 07-DEC-07:02 | 0.91 |
Annual Sum or Average | 0.843358E+10 | 0.31 | |||
Minimum of Months | 0.646704E+09 | 0.30 | 988.74 | 0.84 | |
Maximum of Months | 0.800104E+09 | 0.34 | 1143.91 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.808939E+09 | 0.34 | 1143.50 | 01-JAN-08:61 | 0.91 |
February | 0.737777E+09 | 0.34 | 1143.50 | 03-FEB-07:02 | 0.91 |
March | 0.748064E+09 | 0.32 | 1143.50 | 13-MAR-06:01 | 0.91 |
April | 0.663129E+09 | 0.30 | 1143.50 | 02-APR-07:02 | 0.91 |
May | 0.668680E+09 | 0.30 | 838.32 | 31-MAY-06:03 | 0.78 |
June | 0.659412E+09 | 0.30 | 1143.50 | 15-JUN-06:02 | 0.89 |
July | 0.693921E+09 | 0.30 | 1143.50 | 01-JUL-06:03 | 0.90 |
August | 0.719913E+09 | 0.31 | 1143.50 | 01-AUG-06:02 | 0.90 |
September | 0.645776E+09 | 0.30 | 1143.50 | 01-SEP-06:02 | 0.89 |
October | 0.662387E+09 | 0.30 | 1143.50 | 06-OCT-06:02 | 0.90 |
November | 0.687577E+09 | 0.31 | 1143.50 | 22-NOV-07:02 | 0.91 |
December | 0.763650E+09 | 0.33 | 1143.50 | 07-DEC-07:02 | 0.91 |
Annual Sum or Average | 0.845922E+10 | 0.31 | |||
Minimum of Months | 0.645776E+09 | 0.30 | 838.32 | 0.78 | |
Maximum of Months | 0.808939E+09 | 0.34 | 1143.50 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.125996E+10 | 0.31 | 1831.56 | 01-JAN-09:01 | 0.88 |
February | 0.114840E+10 | 0.31 | 1831.56 | 01-FEB-08:61 | 0.88 |
March | 0.115356E+10 | 0.30 | 1831.56 | 01-MAR-08:61 | 0.88 |
April | 0.100221E+10 | 0.27 | 1831.56 | 01-APR-07:01 | 0.88 |
May | 0.989519E+09 | 0.27 | 1554.45 | 31-MAY-07:03 | 0.81 |
June | 0.981137E+09 | 0.27 | 1831.56 | 08-JUN-07:02 | 0.87 |
July | 0.105283E+10 | 0.27 | 1831.56 | 01-JUL-07:02 | 0.86 |
August | 0.109762E+10 | 0.28 | 1831.56 | 01-AUG-07:02 | 0.87 |
September | 0.957532E+09 | 0.26 | 1831.56 | 01-SEP-07:02 | 0.87 |
October | 0.979276E+09 | 0.26 | 1831.56 | 06-OCT-07:02 | 0.87 |
November | 0.104906E+10 | 0.28 | 1831.56 | 15-NOV-08:61 | 0.88 |
December | 0.118401E+10 | 0.30 | 1831.56 | 01-DEC-08:61 | 0.88 |
Annual Sum or Average | 0.128551E+11 | 0.28 | |||
Minimum of Months | 0.957532E+09 | 0.26 | 1554.45 | 0.81 | |
Maximum of Months | 0.125996E+10 | 0.31 | 1831.56 | 0.88 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.697247E+09 | 0.32 | 1016.41 | 01-JAN-09:01 | 0.91 |
February | 0.635611E+09 | 0.32 | 1016.41 | 01-FEB-08:61 | 0.91 |
March | 0.639515E+09 | 0.31 | 1016.41 | 01-MAR-08:61 | 0.91 |
April | 0.556211E+09 | 0.28 | 1016.41 | 01-APR-07:01 | 0.91 |
May | 0.549139E+09 | 0.28 | 720.93 | 30-MAY-07:03 | 0.77 |
June | 0.542579E+09 | 0.28 | 1016.41 | 15-JUN-07:02 | 0.90 |
July | 0.574436E+09 | 0.28 | 1016.41 | 01-JUL-07:02 | 0.89 |
August | 0.598141E+09 | 0.29 | 1016.41 | 01-AUG-07:02 | 0.90 |
September | 0.530163E+09 | 0.27 | 1016.41 | 01-SEP-07:02 | 0.90 |
October | 0.543388E+09 | 0.27 | 1016.41 | 06-OCT-07:02 | 0.90 |
November | 0.581827E+09 | 0.29 | 1016.41 | 15-NOV-08:61 | 0.91 |
December | 0.655269E+09 | 0.31 | 1016.41 | 01-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.710352E+10 | 0.29 | |||
Minimum of Months | 0.530163E+09 | 0.27 | 720.93 | 0.77 | |
Maximum of Months | 0.697247E+09 | 0.32 | 1016.41 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.695193E+09 | 0.32 | 1009.15 | 01-JAN-09:01 | 0.91 |
February | 0.634028E+09 | 0.32 | 1009.15 | 01-FEB-08:61 | 0.91 |
March | 0.637814E+09 | 0.31 | 1009.15 | 01-MAR-08:61 | 0.91 |
April | 0.553929E+09 | 0.28 | 1009.15 | 01-APR-07:01 | 0.91 |
May | 0.545372E+09 | 0.28 | 644.17 | 31-MAY-07:03 | 0.72 |
June | 0.538527E+09 | 0.28 | 1009.15 | 15-JUN-07:02 | 0.90 |
July | 0.569792E+09 | 0.28 | 1009.15 | 01-JUL-07:02 | 0.89 |
August | 0.593453E+09 | 0.29 | 1009.15 | 01-AUG-07:02 | 0.90 |
September | 0.526297E+09 | 0.27 | 1009.15 | 01-SEP-07:02 | 0.90 |
October | 0.539603E+09 | 0.27 | 1009.15 | 06-OCT-07:02 | 0.90 |
November | 0.579575E+09 | 0.29 | 1009.15 | 15-NOV-08:61 | 0.91 |
December | 0.653318E+09 | 0.31 | 1009.15 | 01-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.706690E+10 | 0.29 | |||
Minimum of Months | 0.526297E+09 | 0.27 | 644.17 | 0.72 | |
Maximum of Months | 0.695193E+09 | 0.32 | 1009.15 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.698663E+09 | 0.32 | 1001.23 | 01-JAN-09:01 | 0.91 |
February | 0.637883E+09 | 0.33 | 1001.23 | 01-FEB-08:61 | 0.91 |
March | 0.641137E+09 | 0.31 | 1001.23 | 01-MAR-08:61 | 0.91 |
April | 0.554526E+09 | 0.29 | 1001.23 | 01-APR-07:01 | 0.91 |
May | 0.541779E+09 | 0.28 | 738.60 | 01-MAY-07:02 | 0.78 |
June | 0.533871E+09 | 0.28 | 1001.23 | 15-JUN-07:02 | 0.90 |
July | 0.564217E+09 | 0.28 | 1001.23 | 01-JUL-07:02 | 0.89 |
August | 0.588411E+09 | 0.29 | 1001.23 | 01-AUG-07:02 | 0.90 |
September | 0.521995E+09 | 0.27 | 1001.23 | 01-SEP-07:02 | 0.90 |
October | 0.535696E+09 | 0.27 | 1001.23 | 06-OCT-07:02 | 0.90 |
November | 0.580155E+09 | 0.29 | 1001.23 | 15-NOV-08:61 | 0.91 |
December | 0.656111E+09 | 0.31 | 1001.23 | 01-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.705444E+10 | 0.29 | |||
Minimum of Months | 0.521995E+09 | 0.27 | 738.60 | 0.78 | |
Maximum of Months | 0.698663E+09 | 0.33 | 1001.23 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.758179E+09 | 0.35 | 1040.69 | 01-JAN-09:01 | 0.91 |
February | 0.695834E+09 | 0.35 | 1040.69 | 01-FEB-08:61 | 0.91 |
March | 0.691691E+09 | 0.32 | 1040.69 | 01-MAR-08:61 | 0.91 |
April | 0.591943E+09 | 0.29 | 1040.69 | 01-APR-07:01 | 0.91 |
May | 0.566581E+09 | 0.28 | 1040.69 | 01-MAY-07:02 | 0.90 |
June | 0.553856E+09 | 0.28 | 1040.69 | 19-JUN-07:02 | 0.89 |
July | 0.585937E+09 | 0.28 | 1040.69 | 02-JUL-08:62 | 0.89 |
August | 0.614572E+09 | 0.29 | 1040.69 | 01-AUG-07:02 | 0.89 |
September | 0.542405E+09 | 0.27 | 1040.69 | 01-SEP-07:02 | 0.89 |
October | 0.558484E+09 | 0.27 | 797.56 | 31-OCT-07:01 | 0.80 |
November | 0.616712E+09 | 0.30 | 1040.69 | 13-NOV-08:62 | 0.91 |
December | 0.704326E+09 | 0.32 | 1040.69 | 01-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.748052E+10 | 0.30 | |||
Minimum of Months | 0.542405E+09 | 0.27 | 797.56 | 0.80 | |
Maximum of Months | 0.758179E+09 | 0.35 | 1040.69 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.32 | 0.49 |
February | 1.38 | 0.59 |
March | 0.14 | 0.00 |
April | 0.08 | 1.50 |
May | 0.17 | 1.50 |
June | 0.06 | 0.00 |
July | 0.22 | 0.00 |
August | 0.58 | 0.43 |
September | 0.58 | 0.86 |
October | 0.53 | 0.24 |
November | 0.54 | 1.12 |
December | 0.14 | 1.50 |
Annual Sum or Average | 5.75 | 0.62 |
Minimum of Months | 0.06 | 0.00 |
Maximum of Months | 1.38 | 1.50 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.54 | 5.65 |
February | 1.46 | 5.74 |
March | 1.85 | 5.44 |
April | 2.15 | 5.47 |
May | 3.58 | 4.28 |
June | 4.89 | 4.19 |
July | 1.11 | 0.00 |
August | 1.63 | 0.89 |
September | 4.22 | 3.94 |
October | 7.97 | 5.04 |
November | 1.71 | 4.37 |
December | 2.60 | 5.57 |
Annual Sum or Average | 34.71 | 4.46 |
Minimum of Months | 1.11 | 0.00 |
Maximum of Months | 7.97 | 5.74 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.03 | 0.00 |
February | 0.00 | 0.00 |
March | 0.28 | 0.75 |
April | 0.89 | 0.75 |
May | 0.83 | 0.75 |
June | 0.56 | 0.75 |
July | 1.28 | 0.75 |
August | 1.82 | 0.68 |
September | 1.03 | 0.26 |
October | 1.65 | 0.40 |
November | 1.46 | 0.60 |
December | 0.00 | 0.00 |
Annual Sum or Average | 9.83 | 0.60 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.82 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 0.00 |
February | 0.00 | 0.00 |
March | 0.19 | 0.75 |
April | 0.89 | 0.75 |
May | 1.03 | 0.75 |
June | 0.56 | 0.75 |
July | 1.28 | 0.75 |
August | 1.65 | 0.75 |
September | 0.97 | 0.24 |
October | 1.74 | 0.41 |
November | 1.36 | 0.61 |
December | 0.00 | 0.00 |
Annual Sum or Average | 9.76 | 0.61 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.74 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.97 | 0.75 |
May | 1.03 | 0.75 |
June | 0.42 | 0.75 |
July | 1.12 | 0.75 |
August | 1.98 | 0.62 |
September | 0.89 | 0.19 |
October | 1.49 | 0.53 |
November | 1.33 | 0.66 |
December | 0.00 | 0.00 |
Annual Sum or Average | 9.31 | 0.61 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.98 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.50 | 0.00 |
February | 0.16 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.14 | 0.00 |
July | 0.70 | 2.64 |
August | 1.12 | 1.02 |
September | 0.22 | 0.00 |
October | 0.36 | 0.00 |
November | 0.00 | 0.00 |
December | 0.03 | 0.00 |
Annual Sum or Average | 3.24 | 0.93 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.12 | 2.64 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.37 | 0.00 |
February | 0.16 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.14 | 0.00 |
July | 0.62 | 1.28 |
August | 0.88 | 0.65 |
September | 0.14 | 0.00 |
October | 0.36 | 0.00 |
November | 0.00 | 0.00 |
December | 0.03 | 0.00 |
Annual Sum or Average | 2.69 | 0.51 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.88 | 1.28 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.54 | 0.00 |
February | 0.24 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.06 | 0.00 |
July | 0.62 | 1.28 |
August | 1.21 | 0.47 |
September | 0.14 | 0.00 |
October | 0.36 | 0.00 |
November | 0.00 | 0.00 |
December | 0.07 | 0.00 |
Annual Sum or Average | 3.24 | 0.42 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.21 | 1.28 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.72 | 0.00 |
February | 0.30 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.22 | 0.00 |
July | 0.62 | 1.28 |
August | 1.21 | 0.47 |
September | 0.31 | 0.00 |
October | 0.19 | 0.00 |
November | 0.00 | 0.00 |
December | 0.07 | 0.00 |
Annual Sum or Average | 3.64 | 0.37 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.21 | 1.28 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.34 | 0.00 |
February | 1.89 | 0.00 |
March | 0.81 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.14 | 0.00 |
July | 0.62 | 1.28 |
August | 0.88 | 0.65 |
September | 0.06 | 0.00 |
October | 0.00 | 0.00 |
November | 0.17 | 0.00 |
December | 0.94 | 0.00 |
Annual Sum or Average | 7.83 | 0.17 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.34 | 1.28 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.172072E+10 | 0.192883E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.157768E+10 | 0.187115E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.156703E+10 | 0.963061E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.161197E+10 | 0.279883E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.245771E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.621885E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.945713E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.911202E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.519045E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.271851E+10 | 7346496.25 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.145253E+10 | 0.570933E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.163592E+10 | 0.138577E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.447205E+11 | 0.700035E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.145253E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.945713E+10 | 0.192883E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.711926E+09 | 0.600397E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.650941E+09 | 0.582359E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.675508E+09 | 0.245547E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.828878E+09 | 0.479099E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.149165E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.348626E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.492058E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.476029E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.287971E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.159892E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.672671E+09 | 0.140595E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.672560E+09 | 0.386924E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.233499E+11 | 0.200373E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.650941E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.492058E+10 | 0.600397E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.798513E+09 | 0.752317E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.729491E+09 | 0.718217E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.742692E+09 | 0.347398E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.769389E+09 | 0.849680E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.115075E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.274642E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.393274E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.384824E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.222389E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.125285E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.685578E+09 | 0.210522E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.755103E+09 | 0.522594E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.196357E+11 | 0.263602E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.685578E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.393274E+10 | 0.752317E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.800104E+09 | 0.791788E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.730191E+09 | 0.749776E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.742040E+09 | 0.377331E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.759804E+09 | 0.992723E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.113296E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.273117E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.392465E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.384419E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.221251E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.123481E+10 | 4975.09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.683981E+09 | 0.232545E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.756007E+09 | 0.557536E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.195524E+11 | 0.280825E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.683981E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.392465E+10 | 0.791788E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.808939E+09 | 0.843937E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.737777E+09 | 0.794621E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.748440E+09 | 0.418787E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.751022E+09 | 0.120215E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.109776E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.267026E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.386451E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.378331E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.216338E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.119160E+10 | 1573891.62 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.687871E+09 | 0.260585E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.763650E+09 | 0.602815E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.192685E+11 | 0.304112E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.687871E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.386451E+10 | 0.843937E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.125996E+10 | 0.175283E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.114840E+10 | 0.163293E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.115359E+10 | 0.958821E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.112179E+10 | 0.328360E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.163134E+10 | 11865857.87 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.429055E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.644423E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.639063E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.345042E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.177647E+10 | 22876894.99 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.104906E+10 | 0.620109E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.118401E+10 | 0.131269E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.309004E+11 | 0.660921E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.104906E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.644423E+10 | 0.175283E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.697247E+09 | 0.913376E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.635611E+09 | 0.851735E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.639515E+09 | 0.502155E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.612977E+09 | 0.173521E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.865546E+09 | 10886523.16 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.223135E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.334710E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.331803E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.179879E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.933381E+09 | 14301725.42 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.581828E+09 | 0.325218E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.655269E+09 | 0.682127E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.163166E+11 | 0.345065E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.581828E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.334710E+10 | 0.913376E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.695193E+09 | 0.926008E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.634028E+09 | 0.864868E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.637814E+09 | 0.516568E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.607076E+09 | 0.182659E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.848279E+09 | 21238575.45 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.220027E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.331663E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.328930E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.177723E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.915425E+09 | 21486092.30 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.579575E+09 | 0.334832E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.653318E+09 | 0.694783E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.161541E+11 | 0.352399E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.579575E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.331663E+10 | 0.926008E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.698663E+09 | 0.973822E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.637883E+09 | 0.912463E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.641137E+09 | 0.563157E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.600104E+09 | 0.211022E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.816127E+09 | 66008015.25 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.213490E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.326766E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.324984E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.174104E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.884836E+09 | 43169707.24 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.580155E+09 | 0.363424E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.656111E+09 | 0.737930E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.159085E+11 | 0.377273E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.580155E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.326766E+10 | 0.973822E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.758179E+09 | 0.117980E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.695834E+09 | 0.112029E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.691691E+09 | 0.728010E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.628515E+09 | 0.308619E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.804041E+09 | 0.271175E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.204763E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.331683E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.335713E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.175700E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.887979E+09 | 0.147459E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.616712E+09 | 0.454363E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.704326E+09 | 0.890529E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.162659E+11 | 0.472347E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.616712E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.335713E+10 | 0.117980E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.172072E+10 | 0.00 | 0.154306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157768E+10 | 0.00 | 0.149692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156390E+10 | 11060635.30 | 0.770449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140698E+10 | 0.765029E+09 | 0.223907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140314E+10 | 0.405897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138196E+10 | 0.197729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150932E+10 | 0.335728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153305E+10 | 0.313175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137562E+10 | 0.155976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140386E+10 | 0.529318E+10 | 5877197.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144924E+10 | 11728542.79 | 0.456747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163592E+10 | 0.00 | 0.110861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179614E+11 | 0.110401E+12 | 0.560028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.172072E+10 | 0.335728E+11 | 0.154306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.711926E+09 | 0.00 | 0.480317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.650939E+09 | 7024.65 | 0.465887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.670769E+09 | 17195048.15 | 0.196438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.676413E+09 | 0.575433E+09 | 0.383279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.774999E+09 | 0.272540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.727262E+09 | 0.112674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.801324E+09 | 0.173806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.808889E+09 | 0.162940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.732237E+09 | 0.874807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.766252E+09 | 0.336480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.666635E+09 | 22464828.26 | 0.112476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.672550E+09 | 31236.97 | 0.309539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.866019E+10 | 0.603954E+11 | 0.160299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.650939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.808889E+09 | 0.173806E+11 | 0.480317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.798513E+09 | 0.00 | 0.601854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.729491E+09 | 0.00 | 0.574574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.741126E+09 | 5629136.24 | 0.277919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.662133E+09 | 0.408378E+09 | 0.679744E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.674083E+09 | 0.185455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.665426E+09 | 0.860330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.702055E+09 | 0.137701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.728280E+09 | 0.129999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.651442E+09 | 0.650808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.667901E+09 | 0.239162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.684044E+09 | 5545257.86 | 0.168418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.755103E+09 | 0.00 | 0.418075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.845960E+10 | 0.465471E+11 | 0.210881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.651442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.798513E+09 | 0.137701E+11 | 0.601854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.800104E+09 | 0.00 | 0.633431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.730191E+09 | 0.00 | 0.599821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.741090E+09 | 3390313.26 | 0.301865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.659712E+09 | 0.379774E+09 | 0.794178E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.668988E+09 | 0.180492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.660702E+09 | 0.856676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.698867E+09 | 0.137654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.725486E+09 | 0.130092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.646704E+09 | 0.648754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.662803E+09 | 0.233823E+10 | 3980.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.682926E+09 | 3802627.88 | 0.186036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.756007E+09 | 0.00 | 0.446029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.843358E+10 | 0.463590E+11 | 0.224660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.646704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.800104E+09 | 0.137654E+11 | 0.633431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.808939E+09 | 0.00 | 0.675150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.737777E+09 | 0.00 | 0.635697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.748064E+09 | 1329026.60 | 0.335029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.663129E+09 | 0.330584E+09 | 0.961720E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.668680E+09 | 0.166233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.659412E+09 | 0.828614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.693921E+09 | 0.134930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.719913E+09 | 0.127497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.645776E+09 | 0.626492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.662387E+09 | 0.215395E+10 | 1259113.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.687577E+09 | 1044638.62 | 0.208468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.763650E+09 | 0.00 | 0.482252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.845922E+10 | 0.449429E+11 | 0.243289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.645776E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.808939E+09 | 0.134930E+11 | 0.675150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.125996E+10 | 0.00 | 0.140226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114840E+10 | 0.00 | 0.130634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115356E+10 | 115019.97 | 0.767057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.100221E+10 | 0.443704E+09 | 0.262688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.989519E+09 | 0.248643E+10 | 9492686.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.981137E+09 | 0.136563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105283E+10 | 0.230832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109762E+10 | 0.221171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.957532E+09 | 0.103037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.979276E+09 | 0.323589E+10 | 18301515.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104906E+10 | 9722.77 | 0.496087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118401E+10 | 0.00 | 0.105015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128551E+11 | 0.753264E+11 | 0.528737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.957532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.125996E+10 | 0.230832E+11 | 0.140226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.697247E+09 | 0.00 | 0.730701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.635611E+09 | 0.00 | 0.681388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.639515E+09 | 523.26 | 0.401724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.556211E+09 | 0.209254E+09 | 0.138817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.549139E+09 | 0.121942E+10 | 8709218.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.542579E+09 | 0.692037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.574436E+09 | 0.117933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.598141E+09 | 0.113010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.530163E+09 | 0.521072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.543388E+09 | 0.157483E+10 | 11441380.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.581827E+09 | 3199.66 | 0.260174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.655269E+09 | 0.00 | 0.545701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.710352E+10 | 0.382289E+11 | 0.276052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.697247E+09 | 0.117933E+11 | 0.730701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.695193E+09 | 0.00 | 0.740806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.634028E+09 | 0.00 | 0.691894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.637814E+09 | 295.20 | 0.413254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.553929E+09 | 0.195339E+09 | 0.146127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.545372E+09 | 0.116608E+10 | 16990860.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.538527E+09 | 0.680417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.569792E+09 | 0.116797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.593453E+09 | 0.111991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.526297E+09 | 0.513489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.539603E+09 | 0.151576E+10 | 17188873.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.579575E+09 | 1001.71 | 0.267865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.653318E+09 | 0.00 | 0.555827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.706690E+10 | 0.376951E+11 | 0.281919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.526297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.695193E+09 | 0.116797E+11 | 0.740806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.698663E+09 | 0.00 | 0.779057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.637883E+09 | 0.00 | 0.729970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.641137E+09 | 0.00 | 0.450526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.554526E+09 | 0.166475E+09 | 0.168817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.541779E+09 | 0.105261E+10 | 52806412.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.533871E+09 | 0.653952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.564217E+09 | 0.114841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.588411E+09 | 0.110517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.521995E+09 | 0.499870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.535696E+09 | 0.140471E+10 | 34535765.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.580155E+09 | 0.00 | 0.290739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.656111E+09 | 0.00 | 0.590344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.705444E+10 | 0.366978E+11 | 0.301819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.521995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.698663E+09 | 0.114841E+11 | 0.779057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.758179E+09 | 0.00 | 0.943836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.695834E+09 | 0.00 | 0.896232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.691691E+09 | 0.00 | 0.582408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.591943E+09 | 0.132516E+09 | 0.246895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.566581E+09 | 0.905929E+09 | 0.216940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.553856E+09 | 0.605531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.585937E+09 | 0.115684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.614572E+09 | 0.113885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.542405E+09 | 0.498258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.558484E+09 | 0.132657E+10 | 0.117967E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.616712E+09 | 0.00 | 0.363490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.704326E+09 | 0.00 | 0.712423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.748052E+10 | 0.363598E+11 | 0.377878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.542405E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.758179E+09 | 0.115684E+11 | 0.943836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.172072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156390E+10 | 0.00 | 0.00 | 0.00 | 3126658.03 | 0.00 | 0.963061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140698E+10 | 0.00 | 0.00 | 0.00 | 0.204991E+09 | 0.00 | 0.279883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140314E+10 | 0.00 | 0.00 | 0.00 | 0.105457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138196E+10 | 0.00 | 0.00 | 0.00 | 0.483690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150932E+10 | 0.00 | 0.00 | 0.00 | 0.794781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153305E+10 | 0.00 | 0.00 | 0.00 | 0.757897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137562E+10 | 0.00 | 0.00 | 0.00 | 0.381483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140386E+10 | 0.00 | 0.00 | 0.00 | 0.131465E+10 | 0.00 | 7346496.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144924E+10 | 0.00 | 0.00 | 0.00 | 3293525.53 | 0.00 | 0.570933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179614E+11 | 0.00 | 0.00 | 0.00 | 0.267591E+11 | 0.00 | 0.700035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.137562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.172072E+10 | 0.00 | 0.00 | 0.00 | 0.794781E+10 | 0.00 | 0.192883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.711926E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.650939E+09 | 0.00 | 0.00 | 0.00 | 2140.49 | 0.00 | 0.582359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.670769E+09 | 0.00 | 0.00 | 0.00 | 4739585.21 | 0.00 | 0.245547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.676413E+09 | 0.00 | 0.00 | 0.00 | 0.152465E+09 | 0.00 | 0.479099E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.774999E+09 | 0.00 | 0.00 | 0.00 | 0.716650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.727262E+09 | 0.00 | 0.00 | 0.00 | 0.275900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.801324E+09 | 0.00 | 0.00 | 0.00 | 0.411925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.808889E+09 | 0.00 | 0.00 | 0.00 | 0.395140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.732237E+09 | 0.00 | 0.00 | 0.00 | 0.214748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.766252E+09 | 0.00 | 0.00 | 0.00 | 0.832669E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.666635E+09 | 0.00 | 0.00 | 0.00 | 6036069.99 | 0.00 | 0.140595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.672550E+09 | 0.00 | 0.00 | 0.00 | 9493.58 | 0.00 | 0.386924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.866019E+10 | 0.00 | 0.00 | 0.00 | 0.146897E+11 | 0.00 | 0.200373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.650939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.808889E+09 | 0.00 | 0.00 | 0.00 | 0.411925E+10 | 0.00 | 0.600397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.798513E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.752317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.729491E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.741126E+09 | 0.00 | 0.00 | 0.00 | 1565399.24 | 0.00 | 0.347398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.662133E+09 | 0.00 | 0.00 | 0.00 | 0.107255E+09 | 0.00 | 0.849680E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.674083E+09 | 0.00 | 0.00 | 0.00 | 0.476667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.665426E+09 | 0.00 | 0.00 | 0.00 | 0.208099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.702055E+09 | 0.00 | 0.00 | 0.00 | 0.323069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.728280E+09 | 0.00 | 0.00 | 0.00 | 0.311996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.651442E+09 | 0.00 | 0.00 | 0.00 | 0.157245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.667901E+09 | 0.00 | 0.00 | 0.00 | 0.584946E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.684044E+09 | 0.00 | 0.00 | 0.00 | 1534022.89 | 0.00 | 0.210522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.755103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.845960E+10 | 0.00 | 0.00 | 0.00 | 0.111761E+11 | 0.00 | 0.263602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.651442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.798513E+09 | 0.00 | 0.00 | 0.00 | 0.323069E+10 | 0.00 | 0.752317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.800104E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.730191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.749776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.741090E+09 | 0.00 | 0.00 | 0.00 | 950317.12 | 0.00 | 0.377331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.659712E+09 | 0.00 | 0.00 | 0.00 | 0.100092E+09 | 0.00 | 0.992723E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.668988E+09 | 0.00 | 0.00 | 0.00 | 0.463971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.660702E+09 | 0.00 | 0.00 | 0.00 | 0.207047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.698867E+09 | 0.00 | 0.00 | 0.00 | 0.322578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.725486E+09 | 0.00 | 0.00 | 0.00 | 0.311870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.646704E+09 | 0.00 | 0.00 | 0.00 | 0.156580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.662803E+09 | 0.00 | 0.00 | 0.00 | 0.572011E+09 | 0.00 | 4975.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.682926E+09 | 0.00 | 0.00 | 0.00 | 1055356.71 | 0.00 | 0.232545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.756007E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.843358E+10 | 0.00 | 0.00 | 0.00 | 0.111188E+11 | 0.00 | 0.280825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.646704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.800104E+09 | 0.00 | 0.00 | 0.00 | 0.322578E+10 | 0.00 | 0.791788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.808939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.843937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.737777E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.748064E+09 | 0.00 | 0.00 | 0.00 | 375894.30 | 0.00 | 0.418787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.663129E+09 | 0.00 | 0.00 | 0.00 | 87892461.45 | 0.00 | 0.120215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.668680E+09 | 0.00 | 0.00 | 0.00 | 0.429081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.659412E+09 | 0.00 | 0.00 | 0.00 | 0.201085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.693921E+09 | 0.00 | 0.00 | 0.00 | 0.317059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.719913E+09 | 0.00 | 0.00 | 0.00 | 0.306340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.645776E+09 | 0.00 | 0.00 | 0.00 | 0.151760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.662387E+09 | 0.00 | 0.00 | 0.00 | 0.529214E+09 | 0.00 | 1573891.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.687577E+09 | 0.00 | 0.00 | 0.00 | 293443.17 | 0.00 | 0.260585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.763650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.602815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.845922E+10 | 0.00 | 0.00 | 0.00 | 0.108093E+11 | 0.00 | 0.304112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.645776E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.808939E+09 | 0.00 | 0.00 | 0.00 | 0.317059E+10 | 0.00 | 0.843937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.125996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115356E+10 | 0.00 | 0.00 | 0.00 | 32922.59 | 0.00 | 0.958821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.100221E+10 | 0.00 | 0.00 | 0.00 | 0.119586E+09 | 0.00 | 0.328360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.989519E+09 | 0.00 | 0.00 | 0.00 | 0.641818E+09 | 0.00 | 11865857.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.981137E+09 | 0.00 | 0.00 | 0.00 | 0.330942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105283E+10 | 0.00 | 0.00 | 0.00 | 0.539139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109762E+10 | 0.00 | 0.00 | 0.00 | 0.529301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.957532E+09 | 0.00 | 0.00 | 0.00 | 0.249289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.979276E+09 | 0.00 | 0.00 | 0.00 | 0.797195E+09 | 0.00 | 22876894.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104906E+10 | 0.00 | 0.00 | 0.00 | 2759.89 | 0.00 | 0.620109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128551E+11 | 0.00 | 0.00 | 0.00 | 0.180453E+11 | 0.00 | 0.660921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.957532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.125996E+10 | 0.00 | 0.00 | 0.00 | 0.539139E+10 | 0.00 | 0.175283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.697247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.635611E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.851735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.639515E+09 | 0.00 | 0.00 | 0.00 | 149.73 | 0.00 | 0.502155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.556211E+09 | 0.00 | 0.00 | 0.00 | 56766024.52 | 0.00 | 0.173521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.549139E+09 | 0.00 | 0.00 | 0.00 | 0.316407E+09 | 0.00 | 10886523.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.542579E+09 | 0.00 | 0.00 | 0.00 | 0.168877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.574436E+09 | 0.00 | 0.00 | 0.00 | 0.277267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.598141E+09 | 0.00 | 0.00 | 0.00 | 0.271989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.530163E+09 | 0.00 | 0.00 | 0.00 | 0.126862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.543388E+09 | 0.00 | 0.00 | 0.00 | 0.389994E+09 | 0.00 | 14301725.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.581827E+09 | 0.00 | 0.00 | 0.00 | 909.04 | 0.00 | 0.325218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.655269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.710352E+10 | 0.00 | 0.00 | 0.00 | 0.921312E+10 | 0.00 | 0.345065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.530163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.697247E+09 | 0.00 | 0.00 | 0.00 | 0.277267E+10 | 0.00 | 0.913376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.695193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.926008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.634028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.864868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.637814E+09 | 0.00 | 0.00 | 0.00 | 84.40 | 0.00 | 0.516568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.553929E+09 | 0.00 | 0.00 | 0.00 | 53146738.69 | 0.00 | 0.182659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.545372E+09 | 0.00 | 0.00 | 0.00 | 0.302907E+09 | 0.00 | 21238575.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.538527E+09 | 0.00 | 0.00 | 0.00 | 0.166174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.569792E+09 | 0.00 | 0.00 | 0.00 | 0.274684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.593453E+09 | 0.00 | 0.00 | 0.00 | 0.269585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.526297E+09 | 0.00 | 0.00 | 0.00 | 0.125093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.539603E+09 | 0.00 | 0.00 | 0.00 | 0.375822E+09 | 0.00 | 21486092.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.579575E+09 | 0.00 | 0.00 | 0.00 | 284.59 | 0.00 | 0.334832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.653318E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.706690E+10 | 0.00 | 0.00 | 0.00 | 0.908723E+10 | 0.00 | 0.352399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.526297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.695193E+09 | 0.00 | 0.00 | 0.00 | 0.274684E+10 | 0.00 | 0.926008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.698663E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.973822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.637883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.641137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.554526E+09 | 0.00 | 0.00 | 0.00 | 45577890.28 | 0.00 | 0.211022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.541779E+09 | 0.00 | 0.00 | 0.00 | 0.274348E+09 | 0.00 | 66008015.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.533871E+09 | 0.00 | 0.00 | 0.00 | 0.160103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.564217E+09 | 0.00 | 0.00 | 0.00 | 0.270344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.588411E+09 | 0.00 | 0.00 | 0.00 | 0.266142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.521995E+09 | 0.00 | 0.00 | 0.00 | 0.121905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.535696E+09 | 0.00 | 0.00 | 0.00 | 0.349140E+09 | 0.00 | 43169707.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.580155E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.656111E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.737930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.705444E+10 | 0.00 | 0.00 | 0.00 | 0.885401E+10 | 0.00 | 0.377273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.521995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.698663E+09 | 0.00 | 0.00 | 0.00 | 0.270344E+10 | 0.00 | 0.973822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.758179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.695834E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.691691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.728010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.591943E+09 | 0.00 | 0.00 | 0.00 | 36572306.30 | 0.00 | 0.308619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.566581E+09 | 0.00 | 0.00 | 0.00 | 0.237461E+09 | 0.00 | 0.271175E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.553856E+09 | 0.00 | 0.00 | 0.00 | 0.149377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.585937E+09 | 0.00 | 0.00 | 0.00 | 0.273089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.614572E+09 | 0.00 | 0.00 | 0.00 | 0.274255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.542405E+09 | 0.00 | 0.00 | 0.00 | 0.121460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.558484E+09 | 0.00 | 0.00 | 0.00 | 0.329495E+09 | 0.00 | 0.147459E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.616712E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.704326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.890529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.748052E+10 | 0.00 | 0.00 | 0.00 | 0.878534E+10 | 0.00 | 0.472347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.542405E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.758179E+09 | 0.00 | 0.00 | 0.00 | 0.274255E+10 | 0.00 | 0.117980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.887873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.782942E+10 | 0.00 | 0.00 | 0.52 |
February | 0.833912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.756830E+10 | 0.00 | 0.00 | 0.53 |
March | 0.993818E+10 | 0.00 | 0.00 | 105930.68 | 0.00 | 0.294447E+10 | 0.112480E+09 | 0.00 | 0.53 |
April | 0.657091E+10 | 45494205.23 | 0.00 | 3186795.56 | 0.00 | 0.594811E+09 | 0.195601E+10 | 0.00 | 0.59 |
May | 0.175514E+10 | 0.400446E+09 | 0.00 | 13548935.43 | 0.00 | 0.00 | 0.555944E+10 | 0.00 | 0.75 |
June | 749408.12 | 0.473948E+10 | 0.00 | 8193717.49 | 0.00 | 0.00 | 0.178554E+10 | 0.00 | 0.70 |
July | 0.00 | 0.116654E+11 | 0.00 | 111840.64 | 0.00 | 0.00 | 2572072.27 | 0.00 | 0.54 |
August | 211571.42 | 0.953929E+10 | 0.00 | 2866806.04 | 0.00 | 0.00 | 0.218523E+09 | 0.00 | 0.57 |
September | 62160236.74 | 0.278257E+10 | 0.00 | 14064453.20 | 0.00 | 0.00 | 0.375471E+10 | 0.00 | 0.78 |
October | 0.255516E+10 | 0.358348E+09 | 0.00 | 13642866.32 | 0.00 | 0.00 | 0.598996E+10 | 0.00 | 0.75 |
November | 0.936184E+10 | 0.00 | 0.00 | 1204363.75 | 0.00 | 0.140666E+10 | 0.101021E+10 | 0.00 | 0.54 |
December | 0.103537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476093E+10 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.578159E+11 | 0.295310E+11 | 0.00 | 56925709.10 | 0.00 | 0.251046E+11 | 0.203895E+11 | 0.00 | 0.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.103537E+11 | 0.116654E+11 | 0.00 | 14064453.20 | 0.00 | 0.782942E+10 | 0.598996E+10 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.357022E+10 | 0.00 | 0.00 | 3232.56 | 0.00 | 0.241571E+10 | 2539852.85 | 0.00 | 0.38 |
February | 0.336987E+10 | 0.00 | 0.00 | 6299.91 | 0.00 | 0.235689E+10 | 4672513.63 | 0.00 | 0.38 |
March | 0.412345E+10 | 0.00 | 0.00 | 279261.44 | 0.00 | 0.620287E+09 | 0.197260E+09 | 0.00 | 0.41 |
April | 0.239990E+10 | 25647534.78 | 0.00 | 2665457.21 | 0.00 | 28773009.52 | 0.165606E+10 | 0.00 | 0.55 |
May | 0.306433E+09 | 0.197734E+09 | 0.00 | 8233519.82 | 0.00 | 0.00 | 0.381072E+10 | 0.00 | 0.82 |
June | 0.00 | 0.231853E+10 | 0.00 | 3355516.20 | 0.00 | 0.00 | 0.661221E+09 | 0.00 | 0.61 |
July | 0.00 | 0.531765E+10 | 0.00 | 49666.67 | 0.00 | 0.00 | 254722.57 | 0.00 | 0.45 |
August | 86407.58 | 0.436381E+10 | 0.00 | 812790.82 | 0.00 | 0.00 | 52978809.44 | 0.00 | 0.48 |
September | 1765543.35 | 0.132214E+10 | 0.00 | 6511604.05 | 0.00 | 0.00 | 0.188557E+10 | 0.00 | 0.75 |
October | 0.566202E+09 | 0.208713E+09 | 0.00 | 8222365.41 | 0.00 | 0.00 | 0.379170E+10 | 0.00 | 0.77 |
November | 0.310278E+10 | 0.00 | 0.00 | 1793864.90 | 0.00 | 0.350943E+09 | 0.144156E+10 | 0.00 | 0.47 |
December | 0.406438E+10 | 0.00 | 0.00 | 32977.93 | 0.00 | 0.132657E+10 | 24187322.91 | 0.00 | 0.38 |
Annual Sum or Average | 0.215051E+11 | 0.137542E+11 | 0.00 | 31966556.93 | 0.00 | 0.709917E+10 | 0.135287E+11 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3232.56 | 0.00 | 0.00 | 254722.57 | 0.00 | 0.38 |
Maximum of Months | 0.412345E+10 | 0.531765E+10 | 0.00 | 8233519.82 | 0.00 | 0.241571E+10 | 0.381072E+10 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.294625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341116E+10 | 0.00 | 0.00 | 0.41 |
February | 0.295472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315370E+10 | 0.00 | 0.00 | 0.41 |
March | 0.395223E+10 | 0.00 | 0.00 | 46845.66 | 0.00 | 0.110324E+10 | 43989851.20 | 0.00 | 0.43 |
April | 0.256515E+10 | 24315781.27 | 0.00 | 1129987.71 | 76992.01 | 0.199490E+09 | 0.759762E+09 | 0.00 | 0.49 |
May | 0.743714E+09 | 0.182468E+09 | 0.00 | 4326854.31 | 2436325.41 | 0.00 | 0.226669E+10 | 0.00 | 0.67 |
June | 45553173.29 | 0.190219E+10 | 0.00 | 2489638.35 | 85600529.94 | 0.00 | 0.580370E+09 | 0.00 | 0.57 |
July | 0.00 | 0.432919E+10 | 0.00 | 545076.53 | 0.238204E+09 | 0.00 | 6841165.24 | 0.00 | 0.42 |
August | 3165493.27 | 0.360714E+10 | 0.00 | 1318281.16 | 0.205380E+09 | 0.00 | 0.140581E+09 | 0.00 | 0.47 |
September | 98200221.37 | 0.108102E+10 | 0.00 | 4499619.16 | 52266596.24 | 0.00 | 0.142177E+10 | 0.00 | 0.65 |
October | 0.102255E+10 | 0.166381E+09 | 0.00 | 4519054.21 | 1432454.53 | 0.00 | 0.227045E+10 | 0.00 | 0.63 |
November | 0.336128E+10 | 0.00 | 0.00 | 577584.92 | 0.00 | 0.661469E+09 | 0.531016E+09 | 0.00 | 0.44 |
December | 0.369709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202660E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.213899E+11 | 0.112927E+11 | 0.00 | 19452942.00 | 0.585397E+09 | 0.105557E+11 | 0.802147E+10 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.395223E+10 | 0.432919E+10 | 0.00 | 4519054.21 | 0.238204E+09 | 0.341116E+10 | 0.227045E+10 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.271005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364739E+10 | 0.00 | 0.00 | 0.41 |
February | 0.276250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334595E+10 | 0.00 | 0.00 | 0.41 |
March | 0.375194E+10 | 0.00 | 0.00 | 36564.84 | 0.00 | 0.129136E+10 | 39888792.69 | 0.00 | 0.42 |
April | 0.254352E+10 | 23416561.13 | 0.00 | 1010399.60 | 66663.25 | 0.243874E+09 | 0.680681E+09 | 0.00 | 0.48 |
May | 0.790480E+09 | 0.181926E+09 | 0.00 | 4036829.82 | 2426830.22 | 0.00 | 0.214219E+10 | 0.00 | 0.66 |
June | 45411360.52 | 0.189811E+10 | 0.00 | 2464486.89 | 85377376.69 | 0.00 | 0.576224E+09 | 0.00 | 0.57 |
July | 0.00 | 0.432945E+10 | 0.00 | 558788.56 | 0.238060E+09 | 0.00 | 6763153.06 | 0.00 | 0.42 |
August | 3342650.40 | 0.360915E+10 | 0.00 | 1328638.88 | 0.205316E+09 | 0.00 | 0.139227E+09 | 0.00 | 0.47 |
September | 0.104877E+09 | 0.108008E+10 | 0.00 | 4446260.16 | 52183651.92 | 0.00 | 0.140150E+10 | 0.00 | 0.65 |
October | 0.107089E+10 | 0.163984E+09 | 0.00 | 4307812.14 | 1383938.71 | 0.00 | 0.217547E+10 | 0.00 | 0.62 |
November | 0.332991E+10 | 0.00 | 0.00 | 445032.81 | 0.00 | 0.774944E+09 | 0.395139E+09 | 0.00 | 0.43 |
December | 0.343613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228643E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.205490E+11 | 0.112861E+11 | 0.00 | 18634813.69 | 0.584815E+09 | 0.115900E+11 | 0.755708E+10 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.375194E+10 | 0.432945E+10 | 0.00 | 4446260.16 | 0.238060E+09 | 0.364739E+10 | 0.217547E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.230717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405029E+10 | 0.00 | 0.00 | 0.41 |
February | 0.238413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372430E+10 | 0.00 | 0.00 | 0.41 |
March | 0.343391E+10 | 0.00 | 0.00 | 25575.56 | 0.00 | 0.159934E+10 | 32072423.38 | 0.00 | 0.42 |
April | 0.251681E+10 | 22090444.45 | 0.00 | 799175.68 | 50185.95 | 0.305112E+09 | 0.567905E+09 | 0.00 | 0.47 |
May | 0.935799E+09 | 0.179466E+09 | 0.00 | 3417378.24 | 2397805.36 | 0.00 | 0.184508E+10 | 0.00 | 0.63 |
June | 45675672.21 | 0.185920E+10 | 0.00 | 2308724.40 | 84188445.68 | 0.00 | 0.582530E+09 | 0.00 | 0.57 |
July | 0.00 | 0.428196E+10 | 0.00 | 505963.52 | 0.236185E+09 | 0.00 | 6969816.42 | 0.00 | 0.42 |
August | 3583671.65 | 0.357713E+10 | 0.00 | 1242754.10 | 0.204322E+09 | 0.00 | 0.140826E+09 | 0.00 | 0.47 |
September | 0.129751E+09 | 0.106060E+10 | 0.00 | 4148231.04 | 51497076.03 | 0.00 | 0.135573E+10 | 0.00 | 0.64 |
October | 0.117000E+10 | 0.153594E+09 | 0.00 | 3914022.10 | 1213625.87 | 0.00 | 0.200952E+10 | 0.00 | 0.61 |
November | 0.325930E+10 | 0.00 | 0.00 | 284970.54 | 0.00 | 0.900882E+09 | 0.260768E+09 | 0.00 | 0.43 |
December | 0.314774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257367E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.193339E+11 | 0.111340E+11 | 0.00 | 16646795.19 | 0.579855E+09 | 0.131536E+11 | 0.680139E+10 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.343391E+10 | 0.428196E+10 | 0.00 | 4148231.04 | 0.236185E+09 | 0.405029E+10 | 0.200952E+10 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.224864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.947972E+10 | 0.00 | 0.00 | 0.38 |
February | 0.246857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.876254E+10 | 0.00 | 0.00 | 0.38 |
March | 0.491647E+10 | 0.00 | 0.00 | 10290.73 | 0.00 | 0.434358E+10 | 22129767.70 | 0.00 | 0.39 |
April | 0.451202E+10 | 33513088.41 | 0.00 | 637236.63 | 0.00 | 0.941180E+09 | 0.505596E+09 | 0.00 | 0.40 |
May | 0.210431E+10 | 0.317472E+09 | 0.00 | 3817359.18 | 3250700.77 | 0.00 | 0.226074E+10 | 0.00 | 0.50 |
June | 29714590.11 | 0.332007E+10 | 0.00 | 3352378.81 | 43487853.78 | 0.00 | 0.962438E+09 | 0.00 | 0.49 |
July | 26548.24 | 0.790208E+10 | 0.00 | 536653.10 | 0.131038E+09 | 0.00 | 5348266.93 | 0.00 | 0.39 |
August | 539375.29 | 0.679891E+10 | 0.00 | 1645601.17 | 91667546.75 | 0.00 | 0.147901E+09 | 0.00 | 0.42 |
September | 0.170687E+09 | 0.191997E+10 | 0.00 | 6474107.23 | 13732817.68 | 0.00 | 0.214065E+10 | 0.00 | 0.54 |
October | 0.237999E+10 | 0.225364E+09 | 0.00 | 5379315.40 | 0.00 | 0.00 | 0.282962E+10 | 0.00 | 0.51 |
November | 0.504617E+10 | 0.00 | 0.00 | 163231.60 | 0.00 | 0.271122E+10 | 0.153251E+09 | 0.00 | 0.38 |
December | 0.429927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627409E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.281764E+11 | 0.205174E+11 | 0.00 | 22016173.86 | 0.283177E+09 | 0.325123E+11 | 0.902768E+10 | 0.00 | 0.43 |
Minimum of Months | 26548.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.504617E+10 | 0.790208E+10 | 0.00 | 6474107.23 | 0.131038E+09 | 0.947972E+10 | 0.282962E+10 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483950E+10 | 0.00 | 0.00 | 0.38 |
February | 0.102535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458429E+10 | 0.00 | 0.00 | 0.38 |
March | 0.226297E+10 | 0.00 | 0.00 | 2999.22 | 0.00 | 0.236068E+10 | 8492850.13 | 0.00 | 0.39 |
April | 0.213475E+10 | 16291469.20 | 0.00 | 276912.90 | 0.00 | 0.629090E+09 | 0.204619E+09 | 0.00 | 0.41 |
May | 0.112425E+10 | 0.157547E+09 | 0.00 | 1770540.31 | 1594991.00 | 0.00 | 0.104601E+10 | 0.00 | 0.51 |
June | 14583530.23 | 0.164039E+10 | 0.00 | 1663622.58 | 21111873.14 | 0.00 | 0.519596E+09 | 0.00 | 0.51 |
July | 10474.87 | 0.392095E+10 | 0.00 | 246992.63 | 64201526.18 | 0.00 | 2990082.07 | 0.00 | 0.39 |
August | 906727.63 | 0.337945E+10 | 0.00 | 787288.78 | 45118011.05 | 0.00 | 79210665.80 | 0.00 | 0.42 |
September | 88539541.77 | 0.948773E+09 | 0.00 | 3217672.25 | 6609882.37 | 0.00 | 0.112316E+10 | 0.00 | 0.56 |
October | 0.121557E+10 | 0.106813E+09 | 0.00 | 2653917.28 | 0.00 | 0.00 | 0.143382E+10 | 0.00 | 0.52 |
November | 0.237387E+10 | 0.00 | 0.00 | 61394.91 | 0.00 | 0.149601E+10 | 62108855.52 | 0.00 | 0.38 |
December | 0.191546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336502E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.131745E+11 | 0.101702E+11 | 0.00 | 10681340.84 | 0.138636E+09 | 0.172746E+11 | 0.448001E+10 | 0.00 | 0.43 |
Minimum of Months | 10474.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.237387E+10 | 0.392095E+10 | 0.00 | 3217672.25 | 64201526.18 | 0.483950E+10 | 0.143382E+10 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.944963E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491287E+10 | 0.00 | 0.00 | 0.38 |
February | 0.921304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468837E+10 | 0.00 | 0.00 | 0.38 |
March | 0.218383E+10 | 0.00 | 0.00 | 1430.50 | 0.00 | 0.243826E+10 | 7020708.05 | 0.00 | 0.39 |
April | 0.206508E+10 | 15792387.02 | 0.00 | 254349.13 | 68966.68 | 0.706841E+09 | 0.181450E+09 | 0.00 | 0.40 |
May | 0.117651E+10 | 0.156357E+09 | 0.00 | 1589826.79 | 1599858.77 | 1518139.40 | 0.932371E+09 | 0.00 | 0.50 |
June | 14625487.25 | 0.162406E+10 | 0.00 | 1617678.87 | 20981085.57 | 0.00 | 0.520027E+09 | 0.00 | 0.50 |
July | 14429.52 | 0.390142E+10 | 0.00 | 241631.54 | 63972677.46 | 0.00 | 3025735.30 | 0.00 | 0.39 |
August | 816082.48 | 0.336777E+10 | 0.00 | 766910.11 | 45033231.79 | 0.00 | 79400024.90 | 0.00 | 0.42 |
September | 93936951.41 | 0.941670E+09 | 0.00 | 3126319.54 | 6575845.42 | 0.00 | 0.110252E+10 | 0.00 | 0.56 |
October | 0.125611E+10 | 0.103884E+09 | 0.00 | 2535530.38 | 0.00 | 0.00 | 0.136265E+10 | 0.00 | 0.52 |
November | 0.229333E+10 | 0.00 | 0.00 | 45506.65 | 0.00 | 0.156932E+10 | 54004108.28 | 0.00 | 0.38 |
December | 0.184226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343831E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.127928E+11 | 0.101110E+11 | 0.00 | 10179183.51 | 0.138232E+09 | 0.177555E+11 | 0.424247E+10 | 0.00 | 0.43 |
Minimum of Months | 14429.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.229333E+10 | 0.390142E+10 | 0.00 | 3126319.54 | 63972677.46 | 0.491287E+10 | 0.136265E+10 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.634552E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522328E+10 | 0.00 | 0.00 | 0.38 |
February | 0.610879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499889E+10 | 0.00 | 0.00 | 0.38 |
March | 0.190308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272001E+10 | 0.00 | 0.00 | 0.39 |
April | 0.187560E+10 | 14791641.31 | 0.00 | 209765.34 | 234560.18 | 0.889504E+09 | 0.157850E+09 | 0.00 | 0.40 |
May | 0.125176E+10 | 0.152968E+09 | 0.00 | 1205110.86 | 1628357.00 | 0.00 | 0.742538E+09 | 0.00 | 0.48 |
June | 17727057.05 | 0.158255E+10 | 0.00 | 1511211.73 | 20704402.26 | 0.00 | 0.519183E+09 | 0.00 | 0.50 |
July | 21775.29 | 0.386085E+10 | 0.00 | 210463.81 | 63573626.47 | 0.00 | 3204997.53 | 0.00 | 0.39 |
August | 727831.27 | 0.334677E+10 | 0.00 | 717652.47 | 44912024.46 | 0.00 | 80634096.58 | 0.00 | 0.42 |
September | 0.110799E+09 | 0.927432E+09 | 0.00 | 2948787.97 | 6517905.58 | 0.00 | 0.105489E+10 | 0.00 | 0.55 |
October | 0.132843E+10 | 98437419.21 | 0.00 | 2311310.05 | 0.00 | 1542797.76 | 0.122765E+10 | 0.00 | 0.51 |
November | 0.211465E+10 | 0.00 | 0.00 | 20240.58 | 0.00 | 0.174955E+10 | 31752891.18 | 0.00 | 0.38 |
December | 0.142274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385767E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.112710E+11 | 0.998380E+10 | 0.00 | 9134542.82 | 0.137571E+09 | 0.194405E+11 | 0.381771E+10 | 0.00 | 0.43 |
Minimum of Months | 21775.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.211465E+10 | 0.386085E+10 | 0.00 | 2948787.97 | 63573626.47 | 0.522328E+10 | 0.122765E+10 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 71975639.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577531E+10 | 0.00 | 0.00 | 0.38 |
February | 48354155.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555236E+10 | 0.00 | 0.00 | 0.38 |
March | 0.809668E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378759E+10 | 0.00 | 0.00 | 0.39 |
April | 0.123752E+10 | 13532608.71 | 0.00 | 151650.08 | 873495.61 | 0.148963E+10 | 0.133755E+09 | 0.00 | 0.40 |
May | 0.130301E+10 | 0.146413E+09 | 0.00 | 723317.81 | 1978447.71 | 80607994.33 | 0.458827E+09 | 0.00 | 0.47 |
June | 41583571.36 | 0.143044E+10 | 0.00 | 1364045.46 | 20654962.33 | 0.00 | 0.526420E+09 | 0.00 | 0.51 |
July | 199245.10 | 0.374785E+10 | 0.00 | 285825.99 | 61722882.03 | 0.00 | 17250842.66 | 0.00 | 0.39 |
August | 1098783.09 | 0.330604E+10 | 0.00 | 651273.63 | 44308759.62 | 0.00 | 83099029.90 | 0.00 | 0.43 |
September | 0.158729E+09 | 0.889780E+09 | 0.00 | 2715074.76 | 6306215.30 | 0.00 | 0.972845E+09 | 0.00 | 0.55 |
October | 0.139147E+10 | 95839361.00 | 0.00 | 1943358.86 | 0.00 | 6338380.03 | 0.105845E+10 | 0.00 | 0.50 |
November | 0.149852E+10 | 0.00 | 0.00 | 5321.00 | 0.00 | 0.234621E+10 | 10708921.85 | 0.00 | 0.38 |
December | 0.333376E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493644E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.689551E+10 | 0.962989E+10 | 0.00 | 7839867.59 | 0.135845E+09 | 0.239745E+11 | 0.326136E+10 | 0.00 | 0.43 |
Minimum of Months | 199245.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.149852E+10 | 0.374785E+10 | 0.00 | 2715074.76 | 61722882.03 | 0.577531E+10 | 0.105845E+10 | 0.00 | 0.55 |