Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:20
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2020-06-03 19:20:27
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:27
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1218.44 | 582.90 | 582.90 |
Net Site Energy | 1218.44 | 582.90 | 582.90 |
Total Source Energy | 3131.65 | 1498.17 | 1498.17 |
Net Source Energy | 3131.65 | 1498.17 | 1498.17 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 349.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 450.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 59.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 151.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 64.98 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 869.35 | 349.09 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 349.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 14.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 450.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 59.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 151.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 64.98 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 244.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 110.34 | 167.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 415.89 | 167.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 244.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 110.34 | 167.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 415.89 | 167.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 869.353 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 869.353 | 100.00 |
Total On-Site and Utility Electric Sources | 869.353 | 100.00 |
Total Electricity End Uses | 869.353 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1088.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Meter |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:27
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.75 | 20.75 | 16.9114 | 11.61 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.37 | 10.37 | 19.7854 | 11.61 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 18.1708 | 11.61 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 18.1708 | 11.61 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 18.1708 | 11.61 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.70 | 20.70 | 11.2173 | 11.61 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 11.2173 | 11.61 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 11.2173 | 11.61 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 11.2173 | 11.61 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.35 | 10.35 | 11.2173 | 11.61 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 14.6187 | 11.61 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 14.6187 | 11.61 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:27
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-16:49 | 11-JAN-17:00 | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 126660.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 19034.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 29013.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9061.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 6302.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 71471.06 | 126660.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 126660.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 19034.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 29013.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 9061.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 6302.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:27
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 378.41 | 0.00 | 0.00 | 0.00 |
Cooling | 44.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1427.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 188.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 479.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 205.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2753.24 | 378.41 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 181.03 | 0.00 | 0.00 | 0.00 |
Cooling | 21.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 683.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 90.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 229.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 98.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1317.14 | 181.03 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 181.03 | 0.00 | 0.00 | 0.00 |
Cooling | 21.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 683.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 90.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 229.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 98.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1317.14 | 181.03 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:27
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.45 |
SMSTORE1 DIRECT AIR | 0.867098 |
SMSTORE2 DIRECT AIR | 0.986117 |
SMSTORE3 DIRECT AIR | 0.981659 |
SMSTORE4 DIRECT AIR | 0.975277 |
LGSTORE2 DIRECT AIR | 1.43 |
SMSTORE5 DIRECT AIR | 0.766020 |
SMSTORE6 DIRECT AIR | 0.755253 |
SMSTORE7 DIRECT AIR | 0.736656 |
SMSTORE8 DIRECT AIR | 0.719591 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.45 | 1.45 | 1.45 | 1.45 | 1.50 | 1.50 | 1.00 | 0.966748 | 1.50 |
PSZ-AC_2:2 | 0.867098 | 0.867098 | 0.867098 | 0.867098 | 0.874164 | 0.874164 | 1.00 | 0.991917 | 0.874164 |
PSZ-AC_3:3 | 0.986117 | 0.986117 | 0.986117 | 0.986117 | 0.986117 | 0.986117 | 1.00 | 1.000000 | 0.986117 |
PSZ-AC_4:4 | 0.981659 | 0.981659 | 0.981659 | 0.981659 | 0.981659 | 0.981659 | 1.00 | 1.00 | 0.981659 |
PSZ-AC_5:5 | 0.975277 | 0.975277 | 0.975277 | 0.975277 | 0.975277 | 0.975277 | 1.00 | 1.00 | 0.975277 |
PSZ-AC_6:6 | 1.43 | 1.43 | 1.43 | 1.43 | 1.47 | 1.47 | 1.00 | 0.970592 | 1.47 |
PSZ-AC_7:7 | 0.766020 | 0.766020 | 0.766020 | 0.766020 | 0.776072 | 0.776072 | 1.00 | 0.987047 | 0.776072 |
PSZ-AC_8:8 | 0.755253 | 0.755253 | 0.755253 | 0.755253 | 0.766591 | 0.766591 | 1.00 | 0.985211 | 0.766591 |
PSZ-AC_9:9 | 0.736656 | 0.736656 | 0.736656 | 0.736656 | 0.750725 | 0.750725 | 1.00 | 0.981260 | 0.750725 |
PSZ-AC_10:10 | 0.719591 | 0.719591 | 0.719591 | 0.719591 | 0.743752 | 0.743752 | 1.00 | 0.967515 | 0.743752 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.50 | 0.411453 |
PSZ-AC_2:2_OA_CONTROLLER | 0.874164 | 0.205727 |
PSZ-AC_3:3_OA_CONTROLLER | 0.986117 | 0.205727 |
PSZ-AC_4:4_OA_CONTROLLER | 0.981659 | 0.205727 |
PSZ-AC_5:5_OA_CONTROLLER | 0.975277 | 0.205727 |
PSZ-AC_6:6_OA_CONTROLLER | 1.47 | 0.411453 |
PSZ-AC_7:7_OA_CONTROLLER | 0.776072 | 0.205727 |
PSZ-AC_8:8_OA_CONTROLLER | 0.766591 | 0.205727 |
PSZ-AC_9:9_OA_CONTROLLER | 0.750725 | 0.205727 |
PSZ-AC_10:10_OA_CONTROLLER | 0.743752 | 0.205727 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.50 | 1.50 | 1.50 | 0.991122 | 24858.46 | 45349.67 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 0.874164 | 0.874164 | 0.874164 | 0.874164 | 14470.51 | 25868.79 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 0.986117 | 0.986117 | 0.986117 | 0.986117 | 16323.74 | 28560.67 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 0.981659 | 0.981659 | 0.981659 | 0.981659 | 16249.93 | 28459.82 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 0.975277 | 0.975277 | 0.975277 | 0.975277 | 16144.29 | 28315.48 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.47 | 1.47 | 1.47 | 0.970159 | 24332.68 | 44782.95 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.776072 | 0.776072 | 0.776072 | 0.776072 | 12846.75 | 23582.71 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.766591 | 0.766591 | 0.766591 | 0.766591 | 12689.79 | 23339.21 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.750725 | 0.750725 | 0.750725 | 0.750725 | 12427.17 | 22918.59 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 0.743752 | 0.743752 | 0.743752 | 0.743752 | 12311.74 | 22532.68 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 1.50 | 0.750850 | 1.00 | 24858.47 | 24858.46 | 12429.23 | 12429.23 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 0.874160 | 0.437080 | 0.582773 | 14470.45 | 14470.51 | 7235.26 | 7235.26 | 0.798654 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 0.986120 | 0.493060 | 0.657413 | 16323.79 | 16323.74 | 8161.87 | 8161.87 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 0.981660 | 0.490830 | 0.654440 | 16249.96 | 16249.93 | 8124.97 | 8124.97 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 0.975280 | 0.487640 | 0.650187 | 16144.35 | 16144.29 | 8072.15 | 8072.15 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 1.47 | 0.734970 | 0.979960 | 24332.73 | 24332.68 | 12166.34 | 12166.34 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 0.776070 | 0.388035 | 0.517380 | 12846.71 | 12846.75 | 6423.38 | 6423.38 | 0.798654 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 0.766590 | 0.383295 | 0.511060 | 12689.79 | 12689.79 | 6344.90 | 6344.90 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 0.750730 | 0.375365 | 0.500487 | 12427.25 | 12427.17 | 6213.59 | 6213.59 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 0.743750 | 0.371875 | 0.495833 | 12311.70 | 12311.74 | 6155.87 | 6155.87 | 0.798654 | 0.798660 | 0.798660 | 0.798660 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.50 | 1606.89 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 0.874164 | 967.84 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 0.986117 | 1091.79 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 0.981659 | 1086.85 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 0.975277 | 1079.79 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.47 | 1572.90 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.776072 | 859.23 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.766591 | 848.74 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.750725 | 831.17 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 0.743752 | 823.45 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | 45349.67 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | 25868.79 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | 28560.67 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | 28459.82 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | 28315.48 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | 44782.95 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | 23582.71 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | 23339.21 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | 22918.59 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | 22532.68 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:27
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:27
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:27
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.76 | 20.75 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.67 | 10.37 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.43 | 20.70 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.13 | 10.35 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 16.911 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.211 | No |
2 | SMSTORE1 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 19.785 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.085 | No |
3 | SMSTORE2 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.171 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.471 | No |
4 | SMSTORE3 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.171 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.471 | No |
5 | SMSTORE4 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.171 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.471 | No |
6 | LGSTORE2 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 11.217 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.517 | No |
7 | SMSTORE5 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 11.217 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.517 | No |
8 | SMSTORE6 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 11.217 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.517 | No |
9 | SMSTORE7 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 11.217 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.517 | No |
10 | SMSTORE8 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 11.217 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.517 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 3907.969 | 11.217 | 130.283 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3907.969 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 1983.747 | 5.694 | 66.133 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1983.747 |
3 | SMSTORE1_LIGHTS | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1953.984 | 11.217 | 130.283 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1953.984 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1492.505 | 8.568 | 99.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.505 |
5 | SMSTORE2_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 1953.984 | 11.217 | 130.283 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1953.984 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 1211.252 | 6.954 | 80.761 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.252 |
7 | SMSTORE3_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 1953.984 | 11.217 | 130.283 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1953.984 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 1211.252 | 6.954 | 80.761 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.252 |
9 | SMSTORE4_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 1953.984 | 11.217 | 130.283 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1953.984 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 1211.252 | 6.954 | 80.761 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.252 |
11 | LGSTORE2_LIGHTS | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 3907.969 | 11.217 | 130.283 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3907.969 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 1953.984 | 11.217 | 130.283 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1953.984 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 1953.984 | 11.217 | 130.283 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1953.984 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 1953.984 | 11.217 | 130.283 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1953.984 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 1953.984 | 11.217 | 130.283 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1953.984 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL | 20 | 4 | 7 | 0.167 | 0.3276 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 30 | 2 | 7 | 0.167 | 0.1408 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 31 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2031 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.818 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.024 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.847 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1010000 | 2.1010000 | 2.1010000 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.37425166E-12 | 0.57871043E-15 | -0.13228690E-12 | 0.66334224E-16 |
23 | 6 | 0.33908220E-07 | 0.96335992E-10 | 0.77239784E-08 | -0.16395395E-12 |
24 | 5 | -0.21635695E-03 | 0.79974903E-06 | -0.11088099E-03 | 0.76168116E-08 |
25 | 4 | 0.32236193 | 0.37876375E-03 | 0.11057381 | -0.37885999E-04 |
26 | 3 | -7.8635639 | 0.11452881E-01 | -2.5162181 | 0.31939119E-01 |
27 | 2 | 42.839535 | 0.39843306E-01 | 15.989526 | -0.35527037 |
28 | 1 | -82.052783 | 0.17638980E-01 | -29.790376 | 1.1107362 |
29 | 0 | 46.824329 | 0.34823312E-03 | 16.276268 | |
30 | 7 | -0.30155247E-08 | -0.19705740E-14 | 0.18469307E-14 | -0.46079768E-16 |
31 | 6 | 0.40551627E-05 | 0.26926011E-08 | 0.31944497E-02 | -0.26797721E-04 |
32 | 5 | -0.28496186E-03 | 0.15923452E-05 | -0.22398486 | 0.19584477E-02 |
33 | 4 | 0.65115693E-02 | 0.72427529E-04 | 4.8338806 | -0.45306652E-01 |
34 | 3 | -0.57046066E-01 | 0.57554694E-03 | -38.045903 | 0.39892442 |
35 | 2 | 0.20237164 | 0.95689144E-03 | 116.53161 | -1.4185768 |
36 | 1 | -0.29197338 | 0.29127682E-03 | -143.93536 | 2.0495010 |
37 | 0 | 0.14232195 | 0.70641069E-05 | 60.838472 | |
38 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
39 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
40 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
41 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
42 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
43 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
44 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
45 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
46 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
47 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
48 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
49 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
50 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
51 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
52 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
53 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
54 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521549E-14 | -0.37274185E-16 |
55 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
56 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
57 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
58 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
59 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
60 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
61 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
62 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521548E-14 | -0.37274183E-16 |
63 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
64 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
65 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
66 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
67 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
68 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
69 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
70 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
71 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
72 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
73 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
74 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
75 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
76 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
77 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
78 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274181E-16 |
79 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
80 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
81 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
82 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
83 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
84 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
85 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
86 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
87 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
88 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
89 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
90 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
91 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
92 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
93 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
94 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
95 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
96 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
97 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
98 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
99 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
100 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
101 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
102 | 7 | -0.20778300E-08 | -0.65167512E-15 | 0.79548166E-14 | -0.12010680E-15 |
103 | 6 | 0.57088823E-05 | 0.38884884E-08 | 0.31895855E-02 | -0.26756916E-04 |
104 | 5 | -0.40892418E-03 | 0.23023551E-05 | -0.22370841 | 0.19560076E-02 |
105 | 4 | 0.93961169E-02 | 0.10478953E-03 | 4.8292766 | -0.45262394E-01 |
106 | 3 | -0.82481111E-01 | 0.83319714E-03 | -38.019897 | 0.39863696 |
107 | 2 | 0.29283299 | 0.13859693E-02 | 116.48099 | -1.4178998 |
108 | 1 | -0.42263540 | 0.42218679E-03 | -143.90557 | 2.0490113 |
109 | 0 | 0.20604930 | 0.10232106E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.38_SHGC_0.38 | 29 | 1 | VerySmooth | 2.159 | 0.374 | 0.294 | 0.419 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 30.0 | 0.159 | 4.569E-004 | 2.517E-004 | 0.317 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 30.0 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 15.0 | 4.561E-002 | 2.619E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 30.0 | 9.122E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 30.0 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 15.0 | 0.113 | 6.514E-004 | 3.022E-004 | 0.453 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 16961.38190 | 20353.65828 | 1.20980 | 1.45177 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.38408E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
2 | LGSTORE1 | Heating | 16420.24932 | 19704.29919 | 0.71544 | 0.85853 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
3 | SMSTORE1 | Cooling | 10075.69644 | 12090.83573 | 0.72258 | 0.86710 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.38408E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
4 | SMSTORE1 | Heating | 8106.75097 | 9728.10116 | 0.35322 | 0.42386 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
5 | SMSTORE2 | Cooling | 11402.96472 | 13683.55767 | 0.82176 | 0.98612 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.39500 | 8.38408E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
6 | SMSTORE2 | Heating | 8207.69535 | 9849.23442 | 0.35761 | 0.42914 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
7 | SMSTORE3 | Cooling | 11353.28275 | 13623.93930 | 0.81805 | 0.98166 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.39500 | 8.38408E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
8 | SMSTORE3 | Heating | 8292.48875 | 9950.98650 | 0.36131 | 0.43357 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
9 | SMSTORE4 | Cooling | 11279.96589 | 13535.95907 | 0.81273 | 0.97528 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.39500 | 8.38408E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
10 | SMSTORE4 | Heating | 8454.48350 | 10145.38020 | 0.36837 | 0.44204 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
11 | LGSTORE2 | Cooling | 16676.76378 | 20012.11654 | 1.18892 | 1.42671 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.38408E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
12 | LGSTORE2 | Heating | 16280.82271 | 19536.98725 | 0.70937 | 0.85124 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
13 | SMSTORE5 | Cooling | 8933.54937 | 10720.25924 | 0.63835 | 0.76602 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.38408E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
14 | SMSTORE5 | Heating | 8713.43868 | 10456.12642 | 0.37965 | 0.45558 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
15 | SMSTORE6 | Cooling | 8811.57971 | 10573.89565 | 0.62938 | 0.75525 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.38408E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
16 | SMSTORE6 | Heating | 8715.72797 | 10458.87357 | 0.37975 | 0.45570 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
17 | SMSTORE7 | Cooling | 8601.08531 | 10321.30237 | 0.61388 | 0.73666 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.38408E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
18 | SMSTORE7 | Heating | 8973.25347 | 10767.90416 | 0.39097 | 0.46916 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
19 | SMSTORE8 | Cooling | 8407.94543 | 10089.53452 | 0.59966 | 0.71959 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.38408E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
20 | SMSTORE8 | Heating | 10366.74816 | 12440.09779 | 0.45168 | 0.54202 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 21159.93 | 1.50170 | 1.50170 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 31932.62 | 0.85853 | 0.85853 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 11831.34 | 0.87416 | 0.87416 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 15844.03 | 0.42386 | 0.42386 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 12502.18 | 0.98612 | 0.98612 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 15963.40 | 0.42914 | 0.42914 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 12443.29 | 0.98166 | 0.98166 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 16063.67 | 0.43357 | 0.43357 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 12356.91 | 0.97528 | 0.97528 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 16255.23 | 0.44204 | 0.44204 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 20336.95 | 1.46994 | 1.46994 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 31767.76 | 0.85124 | 0.85124 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 10378.24 | 0.77607 | 0.77607 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 16561.45 | 0.45558 | 0.45558 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 10263.74 | 0.76659 | 0.76659 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 16564.16 | 0.45570 | 0.45570 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 10116.07 | 0.75073 | 0.75073 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 16868.69 | 0.46916 | 0.46916 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 10025.11 | 0.74375 | 0.74375 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 18516.51 | 0.54202 | 0.54202 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.45177 |
2 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.86710 |
3 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98612 |
4 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98166 |
5 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.97528 |
6 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.42671 |
7 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.76602 |
8 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.75525 |
9 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.73666 |
10 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.71959 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.45177 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.45177 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.45177 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.45177 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.50170 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.50170 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 0.96675 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.86710 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.86710 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.86710 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.86710 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.87416 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.87416 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 0.99192 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98612 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98612 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98612 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98612 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.98612 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 0.98612 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98166 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98166 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98166 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98166 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.98166 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.98166 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.97528 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.97528 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.97528 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.97528 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97528 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 0.97528 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.42671 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.42671 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.42671 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.42671 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.46994 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.46994 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 0.97059 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.76602 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.76602 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.76602 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.76602 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.77607 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.77607 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.98705 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.75525 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.75525 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.75525 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.75525 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.76659 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.76659 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.98521 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.73666 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.73666 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.73666 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.73666 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.75073 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.75073 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.98126 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.71959 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.71959 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.71959 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.71959 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.74375 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 0.74375 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 0.96751 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.50170 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 0.87416 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 0.98612 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 0.98166 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 0.97528 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.46994 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.77607 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.76659 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.75073 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 0.74375 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.50170 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.50170 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.50170 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.50170 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.99112 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.50170 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.75085 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.00113 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 24858.46714 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 24858.46000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12429.23000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 12429.23000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24858.46000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 45349.66976 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
122 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.50170 |
123 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1606.88932 |
124 | Coil:Heating:Fuel | PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 45349.66976 |
125 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.87416 |
126 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.87416 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.87416 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.87416 |
130 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.87416 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.87416 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.43708 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.58277 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 14470.45191 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 14470.51000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 7235.25500 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 7235.25500 |
138 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79865 |
139 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
140 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
141 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 14470.51000 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25868.78869 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
146 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.87416 |
147 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 967.83801 |
148 | Coil:Heating:Fuel | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 25868.78869 |
149 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.98612 |
150 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
151 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.98612 |
152 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.98612 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.98612 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.98612 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.98612 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49306 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65741 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 16323.78745 |
159 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 16323.74000 |
160 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8161.87000 |
161 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8161.87000 |
162 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
163 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
164 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16323.74000 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28560.66949 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
170 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.98612 |
171 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1091.78852 |
172 | Coil:Heating:Fuel | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 28560.66949 |
173 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.98166 |
174 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.98166 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.98166 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.98166 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.98166 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.98166 |
180 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49083 |
181 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65444 |
182 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 16249.95862 |
183 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 16249.93000 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8124.96500 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8124.96500 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16249.93000 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28459.82354 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
194 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.98166 |
195 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1086.85186 |
196 | Coil:Heating:Fuel | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 28459.82354 |
197 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97528 |
198 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97528 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97528 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97528 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97528 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.97528 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48764 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65019 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 16144.34696 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 16144.29000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8072.14500 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8072.14500 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
214 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16144.29000 |
215 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28315.47954 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
218 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.97528 |
219 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1079.78618 |
220 | Coil:Heating:Fuel | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 28315.47954 |
221 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.46994 |
222 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.46994 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.46994 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.46994 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97016 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.46994 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.73497 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.97996 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 24332.72637 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 24332.68000 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12166.34000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 12166.34000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24332.68000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 44782.95217 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
241 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
242 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.46994 |
243 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1572.90232 |
244 | Coil:Heating:Fuel | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 44782.95217 |
245 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.77607 |
246 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.77607 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.77607 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.77607 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77607 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.77607 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.38804 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.51738 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 12846.71412 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 12846.75000 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 6423.37500 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 6423.37500 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79865 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
262 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 12846.75000 |
263 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 23582.71074 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
266 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.77607 |
267 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 859.23485 |
268 | Coil:Heating:Fuel | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 23582.71074 |
269 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.76659 |
270 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
271 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.76659 |
272 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.76659 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.76659 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.76659 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.76659 |
276 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.38330 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.51106 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 12689.78646 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 12689.79000 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 6344.89500 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 6344.89500 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 12689.79000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 23339.20632 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.76659 |
291 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 848.73737 |
292 | Coil:Heating:Fuel | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 23339.20632 |
293 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.75073 |
294 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.75073 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.75073 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.75073 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75073 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.75073 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.37537 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.50049 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 12427.24714 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 12427.17000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 6213.58500 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 6213.58500 |
306 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
307 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
308 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
309 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
310 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 12427.17000 |
311 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 22918.59455 |
312 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
313 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
314 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.75073 |
315 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 831.17204 |
316 | Coil:Heating:Fuel | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 22918.59455 |
317 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.74375 |
318 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
319 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.74375 |
320 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.74375 |
321 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.74375 |
322 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.74375 |
323 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.74375 |
324 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.37188 |
325 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.49583 |
326 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 12311.70336 |
327 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 12311.74000 |
328 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 6155.87000 |
329 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 6155.87000 |
330 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79865 |
331 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
332 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
333 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
334 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 12311.74000 |
335 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 22532.67698 |
336 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
337 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
338 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.74375 |
339 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 823.45153 |
340 | Coil:Heating:Fuel | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 22532.67698 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 23681.6 | 11.11 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 13785.4 | 32.16 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 15550.9 | 40.34 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 15480.6 | 52.36 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 15380.0 | 64.53 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 23180.7 | 51.29 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 12238.5 | 115.34 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 12089.0 | 128.60 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 11838.8 | 143.15 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 11728.9 | 156.32 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.328 | 0.312 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.328 | 0.312 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.328 | 0.312 | 58.20 | 78.94 | 58.20 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.141 | 0.136 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.328 | 0.312 | 29.10 | 39.47 | 29.10 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.328 | 0.312 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.328 | 0.312 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.328 | 0.312 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.328 | 0.312 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.328 | 0.312 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.328 | 0.312 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.328 | 0.312 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.328 | 0.312 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.328 | 0.312 | 58.24 | 78.94 | 58.24 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.328 | 0.312 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.328 | 0.312 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.328 | 0.312 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.328 | 0.312 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.328 | 0.312 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.328 | 0.312 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.328 | 0.312 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.328 | 0.312 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.328 | 0.312 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.203 | 0.194 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 14 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 1.7780552394E-002 | 0.1036881509 | Pass | Pass | 0.1700404415 | 0.6169961481 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 4.3948554353E-002 | 8.5399872100E-002 | Pass | Pass | 0.2439778108 | 1.6013318508 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 2.3623316010E-002 | 0.1091080951 | Pass | Pass | 0.2950392047 | 2.2210161413 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 2.9670195019E-002 | 0.1565247443 | Pass | Pass | 7.5123761068E-002 | 0.2441826322 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.4218468427E-002 | 0.1866767515 | Pass | Pass | 7.8706966487E-002 | 0.2559491600 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 3.6970271526E-002 | 0.1797248721 | Pass | Pass | 1.0033746308 | 11.1761936392 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 3.7670464622E-002 | 0.1855031067 | Pass | Pass | 0.1266661758 | 0.5259263900 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 3.9131753146E-002 | 0.1947179445 | Pass | Pass | 6.9533989600E-002 | 0.2211517376 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 4.3689059702E-002 | 0.2269226388 | Pass | Pass | 4.3730101359E-002 | 0.1300020089 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 6.1798550783E-002 | 0.2947201862 | Pass | Pass | 2.9980390711E-002 | 9.6015293648E-002 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:27
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:27
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL | 0.30 | 0.312 | 0.328 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.312 | 0.328 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.312 | 0.328 | 78.94 | 58.20 | 180.00 | 90.00 | S |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.312 | 0.328 | 39.47 | 29.10 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.312 | 0.328 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.312 | 0.328 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.312 | 0.328 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.312 | 0.328 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.312 | 0.328 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.312 | 0.328 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.312 | 0.328 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.312 | 0.328 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.312 | 0.328 | 78.94 | 58.24 | 180.00 | 90.00 | S |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.312 | 0.328 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.312 | 0.328 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.312 | 0.328 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.312 | 0.328 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.312 | 0.328 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.312 | 0.328 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.312 | 0.328 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.312 | 0.328 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL | 0.30 | 0.312 | 0.328 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.141 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | ||
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.080 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.203 | 174.19 | 174.19 | 270.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.374 | 0.419 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.374 | 0.419 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.374 | 0.419 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.374 | 0.419 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.159 | 0.374 | 0.419 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.159 | 0.374 | 0.419 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.374 | 0.419 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.374 | 0.419 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.159 | 0.374 | 0.419 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.374 | 0.419 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.374 | 0.419 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.374 | 0.419 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.374 | 0.419 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.374 | 0.419 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.374 | 0.419 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.374 | 0.419 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.374 | 0.419 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.374 | 0.419 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.374 | 0.419 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.374 | 0.419 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.374 | 0.419 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.374 | 0.419 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.374 | 0.419 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.374 | 0.419 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.374 | 0.419 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.374 | 0.419 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.374 | 0.419 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.374 | 0.419 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.374 | 0.419 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.374 | 0.419 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.374 | 0.419 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.374 | 0.419 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.374 | 0.419 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.374 | 0.419 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.374 | 0.419 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.38_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.374 | 0.419 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
Total or Average | 124.29 | 2.159 | 0.374 | 0.419 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 124.29 | 2.159 | 0.374 | 0.419 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:27
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:27
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | 11.2173 | 348.39 | 3907.97 | LightsWired | TYPE1_LIGHT_SCH | 98.22 | 168.00 | 96.33 | 0.0000 | Y | 70.67 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | 5.6941 | 348.39 | 1983.75 | LightsWired | TYPE1_LIGHT_SCH | 98.22 | 112.00 | 95.26 | 0.0000 | Y | 35.47 |
SMSTORE1_LIGHTS | SMSTORE1 | 11.2173 | 174.19 | 1953.98 | LightsWired | TYPE1_LIGHT_SCH | 98.22 | 168.00 | 96.33 | 0.0000 | Y | 35.33 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | 8.5681 | 174.19 | 1492.50 | LightsWired | TYPE1_LIGHT_SCH | 98.22 | 112.00 | 95.26 | 0.0000 | Y | 26.69 |
SMSTORE2_LIGHTS | SMSTORE2 | 11.2173 | 174.19 | 1953.98 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 74.85 | 0.0000 | Y | 27.46 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | 6.9535 | 174.19 | 1211.25 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.65 |
SMSTORE3_LIGHTS | SMSTORE3 | 11.2173 | 174.19 | 1953.98 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 74.85 | 0.0000 | Y | 27.46 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | 6.9535 | 174.19 | 1211.25 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.65 |
SMSTORE4_LIGHTS | SMSTORE4 | 11.2173 | 174.19 | 1953.98 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 74.85 | 0.0000 | Y | 27.46 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | 6.9535 | 174.19 | 1211.25 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.65 |
LGSTORE2_LIGHTS | LGSTORE2 | 11.2173 | 348.39 | 3907.97 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 68.34 | 0.0000 | Y | 50.13 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | 0.0000 | 348.39 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | 11.2173 | 174.19 | 1953.98 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 68.34 | 0.0000 | Y | 25.07 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | 11.2173 | 174.19 | 1953.98 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 68.34 | 0.0000 | Y | 25.07 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | 11.2173 | 174.19 | 1953.98 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 68.34 | 0.0000 | Y | 25.07 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | 11.2173 | 174.19 | 1953.98 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 68.34 | 0.0000 | Y | 25.07 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 7.3094 | 4180.64 | 30557.82 | 450.89 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 418.40 | AstronomicalClock | - | 42.50 | 42.50 | 3.34 | |
EXTERIOR_LIGHTS_B | 2520.30 | AstronomicalClock | - | 83.54 | 63.02 | 29.81 | |
EXTERIOR_LIGHTS_C | 2520.30 | AstronomicalClock | - | 83.54 | 56.02 | 26.50 | |
Exterior Lighting Total | 5459.01 | 59.65 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:27
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 24858.46 | 19853.46 | 5005.00 | 0.80 | 3.80 | |||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 14470.51 | 11557.02 | 2913.49 | 0.80 | 4.12 | |||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 16323.74 | 13037.12 | 3286.62 | 0.80 | 4.12 | |||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 16249.93 | 12978.17 | 3271.76 | 0.80 | 4.12 | |||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 16144.29 | 12893.80 | 3250.49 | 0.80 | 4.12 | |||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 24332.68 | 19433.54 | 4899.14 | 0.80 | 3.80 | |||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 12846.75 | 10260.19 | 2586.56 | 0.80 | 4.12 | |||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 12689.79 | 10134.83 | 2554.96 | 0.80 | 4.12 | |||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 12427.17 | 9925.08 | 2502.09 | 0.80 | 4.12 | |||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 12311.74 | 9832.89 | 2478.85 | 0.80 | 4.12 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 23681.6 | 11.11 | ||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 13785.4 | 32.16 | ||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 15550.9 | 40.34 | ||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 15480.6 | 52.36 | ||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 15380.0 | 64.53 | ||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 23180.7 | 51.29 | ||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 12238.5 | 115.34 | ||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 12089.0 | 128.60 | ||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 11838.8 | 143.15 | ||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 11728.9 | 156.32 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 45349.67 | 0.80 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 25868.79 | 0.80 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 28560.67 | 0.80 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 28459.82 | 0.80 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 28315.48 | 0.80 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 44782.95 | 0.80 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 23582.71 | 0.80 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 23339.21 | 0.80 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 22918.59 | 0.80 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 22532.68 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.50 | 1606.89 | 1070.05 | 1.00 | 1.36 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.87 | 967.84 | 1107.16 | 1.00 | 1.44 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.99 | 1091.79 | 1107.16 | 1.00 | 1.41 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.98 | 1086.85 | 1107.16 | 1.00 | 1.41 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.98 | 1079.79 | 1107.16 | 1.00 | 1.41 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.47 | 1572.90 | 1070.05 | 1.00 | 1.37 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.78 | 859.23 | 1107.16 | 1.00 | 1.47 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.77 | 848.74 | 1107.16 | 1.00 | 1.48 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.75 | 831.17 | 1107.16 | 1.00 | 1.48 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.74 | 823.45 | 1107.16 | 1.00 | 1.49 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:27
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 16961.38 | 20353.66 | 58.42 | 1.210 | 1.452 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00935 | 22.94 | 0.00838 | 0.411 | 0.00 |
SMSTORE1 | 10075.70 | 12090.84 | 69.41 | 0.723 | 0.867 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00906 | 22.94 | 0.00838 | 0.206 | 0.00 |
SMSTORE2 | 11402.96 | 13683.56 | 78.55 | 0.822 | 0.986 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00927 | 21.39 | 0.00838 | 0.206 | 0.00 |
SMSTORE3 | 11353.28 | 13623.94 | 78.21 | 0.818 | 0.982 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00924 | 21.39 | 0.00838 | 0.206 | 0.00 |
SMSTORE4 | 11279.97 | 13535.96 | 77.71 | 0.813 | 0.975 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00930 | 21.39 | 0.00838 | 0.206 | 0.00 |
LGSTORE2 | 16676.76 | 20012.12 | 57.44 | 1.189 | 1.427 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00955 | 22.94 | 0.00838 | 0.411 | 0.00 |
SMSTORE5 | 8933.55 | 10720.26 | 61.54 | 0.638 | 0.766 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00942 | 22.94 | 0.00838 | 0.206 | 0.00 |
SMSTORE6 | 8811.58 | 10573.90 | 60.70 | 0.629 | 0.755 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00946 | 22.94 | 0.00838 | 0.206 | 0.00 |
SMSTORE7 | 8601.09 | 10321.30 | 59.25 | 0.614 | 0.737 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00952 | 22.94 | 0.00838 | 0.206 | 0.00 |
SMSTORE8 | 8407.95 | 10089.53 | 57.92 | 0.600 | 0.720 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00947 | 22.94 | 0.00838 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 16420.25 | 19704.30 | 56.56 | 0.715 | 0.859 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00678 | -4.30 | 0.00266 | 0.411 | 0.00 |
SMSTORE1 | 8106.75 | 9728.10 | 55.85 | 0.353 | 0.424 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00666 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE2 | 8207.70 | 9849.23 | 56.54 | 0.358 | 0.429 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00666 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE3 | 8292.49 | 9950.99 | 57.13 | 0.361 | 0.434 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00667 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE4 | 8454.48 | 10145.38 | 58.24 | 0.368 | 0.442 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00669 | -4.30 | 0.00266 | 0.206 | 0.00 |
LGSTORE2 | 16280.82 | 19536.99 | 56.08 | 0.709 | 0.851 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00678 | -4.30 | 0.00266 | 0.411 | 0.00 |
SMSTORE5 | 8713.44 | 10456.13 | 60.03 | 0.380 | 0.456 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00671 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE6 | 8715.73 | 10458.87 | 60.04 | 0.380 | 0.456 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00671 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE7 | 8973.25 | 10767.90 | 61.82 | 0.391 | 0.469 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00673 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE8 | 10366.75 | 12440.10 | 71.42 | 0.452 | 0.542 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00682 | -4.30 | 0.00266 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.50 | 1.50 | 0.86 | 0.86 | 1.5017 | 1.4518 | 1.5017 | 0.9667 | 1.0000 |
PSZ-AC_2:2 | 0.87 | 0.87 | 0.42 | 0.42 | 0.8742 | 0.8671 | 0.8742 | 0.9919 | 1.0000 |
PSZ-AC_3:3 | 0.99 | 0.99 | 0.43 | 0.43 | 0.9861 | 0.9861 | 0.9861 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 0.98 | 0.98 | 0.43 | 0.43 | 0.9817 | 0.9817 | 0.9817 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 0.98 | 0.98 | 0.44 | 0.44 | 0.9753 | 0.9753 | 0.9753 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.47 | 1.47 | 0.85 | 0.85 | 1.4699 | 1.4267 | 1.4699 | 0.9706 | 1.0000 |
PSZ-AC_7:7 | 0.78 | 0.78 | 0.46 | 0.46 | 0.7761 | 0.7660 | 0.7761 | 0.9870 | 1.0000 |
PSZ-AC_8:8 | 0.77 | 0.77 | 0.46 | 0.46 | 0.7666 | 0.7553 | 0.7666 | 0.9852 | 1.0000 |
PSZ-AC_9:9 | 0.75 | 0.75 | 0.47 | 0.47 | 0.7507 | 0.7367 | 0.7507 | 0.9813 | 1.0000 |
PSZ-AC_10:10 | 0.74 | 0.74 | 0.54 | 0.54 | 0.7438 | 0.7196 | 0.7438 | 0.9675 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 12429.230 | 0.000 | 1.501700 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 12429.23 | 11983.43 | 1.501700 | 24.58 | 16.63 | 0.00869592 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00838408 | 17.00 | 27.3992 | 23.89 | 0.00935498 | 50.0965 | 16863.34 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 45349.670 | 45349.670 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 45349.67 | 45349.67 | 1.501699 | 8.93 | 6.16 | 0.00480172 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 27.3992 | 21.11 | 0.00677500 | 43.1336 | 16420.25 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 7235.255 | 0.000 | 0.874160 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 7235.26 | 6992.19 | 0.874160 | 24.48 | 16.59 | 0.00868175 | 12.80 | 12.00 | 0.00850000 | 26.32 | 0.00838408 | 16.97 | 23.5342 | 23.89 | 0.00906330 | 48.5543 | 10075.70 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 25868.789 | 25868.789 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 25868.79 | 25868.79 | 0.874164 | 8.78 | 5.98 | 0.00471552 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 23.5341 | 21.11 | 0.00665643 | 42.3872 | 8106.75 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 8161.870 | 0.000 | 0.986120 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 8161.87 | 7268.97 | 0.986120 | 23.39 | 16.55 | 0.00908898 | 12.80 | 12.00 | 0.00850000 | 21.39 | 0.00838408 | 15.22 | 20.8622 | 23.89 | 0.00927480 | 49.6749 | 11402.96 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 28560.669 | 28560.669 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28560.67 | 28560.67 | 0.986117 | 8.93 | 6.09 | 0.00474348 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 20.8623 | 21.11 | 0.00666427 | 42.4367 | 8207.70 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 8124.965 | 0.000 | 0.981660 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 8124.97 | 7277.40 | 0.981660 | 23.39 | 16.53 | 0.00905833 | 12.80 | 12.00 | 0.00850000 | 21.39 | 0.00838408 | 15.22 | 20.9570 | 23.89 | 0.00923709 | 49.4751 | 11353.28 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 28459.824 | 28459.824 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28459.82 | 28459.82 | 0.981659 | 9.05 | 6.18 | 0.00476727 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 20.9571 | 21.11 | 0.00667218 | 42.4866 | 8292.49 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 8072.145 | 0.000 | 0.975280 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 8072.15 | 7160.78 | 0.975280 | 23.38 | 16.57 | 0.00910990 | 12.80 | 12.00 | 0.00850000 | 21.39 | 0.00838408 | 15.22 | 21.0941 | 23.89 | 0.00930393 | 49.8289 | 11279.97 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 28315.480 | 28315.480 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28315.48 | 28315.48 | 0.975277 | 9.28 | 6.35 | 0.00481217 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 21.0942 | 21.11 | 0.00668788 | 42.5855 | 8454.48 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 12166.340 | 0.000 | 1.469940 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 12166.34 | 11722.64 | 1.469940 | 24.58 | 16.64 | 0.00869943 | 12.80 | 12.00 | 0.00850000 | 26.32 | 0.00838408 | 16.97 | 27.9912 | 23.89 | 0.00955469 | 51.1524 | 16676.76 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 44782.952 | 44782.952 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 44782.95 | 44782.95 | 1.469937 | 8.83 | 6.09 | 0.00478550 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 27.9912 | 21.11 | 0.00677630 | 43.1417 | 16280.82 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 6423.375 | 0.000 | 0.776070 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6423.38 | 6197.05 | 0.776070 | 24.57 | 16.63 | 0.00869221 | 12.80 | 12.00 | 0.00850000 | 26.32 | 0.00838408 | 16.97 | 26.5088 | 23.89 | 0.00942382 | 50.4610 | 8933.55 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 23582.711 | 23582.711 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 23582.71 | 23582.71 | 0.776072 | 9.63 | 6.60 | 0.00488028 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 26.5087 | 21.11 | 0.00671044 | 42.7276 | 8713.44 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 6344.895 | 0.000 | 0.766590 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6344.90 | 6120.58 | 0.766590 | 24.58 | 16.63 | 0.00869301 | 12.80 | 12.00 | 0.00850000 | 26.32 | 0.00838408 | 16.97 | 26.8366 | 23.89 | 0.00945628 | 50.6325 | 8811.58 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 23339.206 | 23339.206 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 23339.21 | 23339.21 | 0.766591 | 9.64 | 6.61 | 0.00488093 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 26.8366 | 21.11 | 0.00671075 | 42.7296 | 8715.73 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 6213.585 | 0.000 | 0.750730 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6213.59 | 5992.97 | 0.750730 | 24.59 | 16.63 | 0.00869403 | 12.80 | 12.00 | 0.00850000 | 26.32 | 0.00838408 | 16.97 | 27.4036 | 23.89 | 0.00951600 | 50.9479 | 8601.09 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 22918.595 | 22918.595 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 22918.59 | 22918.59 | 0.750725 | 9.97 | 6.85 | 0.00494592 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 27.4037 | 21.11 | 0.00673296 | 42.8696 | 8973.25 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 6155.870 | 0.000 | 0.743750 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6155.87 | 5935.26 | 0.743750 | 24.52 | 16.61 | 0.00869498 | 12.80 | 12.00 | 0.00850000 | 26.10 | 0.00838408 | 16.90 | 27.6607 | 23.89 | 0.00947477 | 50.7297 | 8407.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 22532.677 | 22532.677 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 22532.68 | 22532.68 | 0.743752 | 11.46 | 7.91 | 0.00524211 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 27.6607 | 21.11 | 0.00682319 | 43.4384 | 10366.75 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:20:27
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12429.230 | 0.000 | 1.501700 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0053 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 12429.23 | 11983.43 | 1.0000 | 1.78908335 | 1.501700 | 24.58 | 16.63 | 0.00869592 | 46841.7 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12429.23 | 26.40 | 0.00838408 | 17.00 | 0.41145340 | 27.3992 | 23.89 | 0.00881370 | 23.89 | 0.00935498 | 50.0965 | 16863.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 45349.670 | 45349.670 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.501699 | 1.78908261 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 45349.67 | 45349.67 | 1.0000 | 1.78908261 | 1.501699 | 8.93 | 6.16 | 0.00480172 | 21062.9 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 45349.67 | -4.30 | 0.00265759 | -4.30 | 0.41145340 | 27.3992 | 21.11 | 0.00677500 | 21.11 | 0.00677500 | 43.1336 | 16420.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 7235.255 | 0.000 | 0.874160 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9789 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 7235.26 | 6992.19 | 1.0000 | 1.04144976 | 0.874160 | 24.48 | 16.59 | 0.00868175 | 46707.3 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7235.26 | 26.32 | 0.00838408 | 16.97 | 0.20572670 | 23.5342 | 23.89 | 0.00877738 | 23.89 | 0.00906330 | 48.5543 | 10075.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25868.789 | 25868.789 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.874164 | 1.04145420 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 25868.79 | 25868.79 | 1.0000 | 1.04145420 | 0.874164 | 8.78 | 5.98 | 0.00471552 | 20688.3 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25868.79 | -4.30 | 0.00265759 | -4.30 | 0.20572670 | 23.5341 | 21.11 | 0.00665643 | 21.11 | 0.00665643 | 42.3872 | 8106.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8161.870 | 0.000 | 0.986120 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.7360 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 8161.87 | 7268.97 | 1.0000 | 1.17483577 | 0.986120 | 23.39 | 16.55 | 0.00908898 | 46629.6 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8161.87 | 21.39 | 0.00838408 | 15.22 | 0.20572670 | 20.8622 | 23.92 | 0.00927480 | 23.89 | 0.00927480 | 49.6749 | 11402.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28560.669 | 28560.669 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.986117 | 1.17483270 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28560.67 | 28560.67 | 1.0000 | 1.17483270 | 0.986117 | 8.93 | 6.09 | 0.00474348 | 20912.4 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28560.67 | -4.30 | 0.00265759 | -4.30 | 0.20572670 | 20.8623 | 21.11 | 0.00666427 | 21.11 | 0.00666427 | 42.4367 | 8207.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8124.965 | 0.000 | 0.981660 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6790 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 8124.97 | 7277.40 | 1.0000 | 1.16952225 | 0.981660 | 23.39 | 16.53 | 0.00905833 | 46549.6 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8124.97 | 21.39 | 0.00838408 | 15.22 | 0.20572670 | 20.9570 | 23.92 | 0.00923709 | 23.89 | 0.00923709 | 49.4751 | 11353.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28459.824 | 28459.824 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.981659 | 1.16952054 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28459.82 | 28459.82 | 1.0000 | 1.16952054 | 0.981659 | 9.05 | 6.18 | 0.00476727 | 21098.6 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28459.82 | -4.30 | 0.00265759 | -4.30 | 0.20572670 | 20.9571 | 21.11 | 0.00667218 | 21.11 | 0.00667218 | 42.4866 | 8292.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8072.145 | 0.000 | 0.975280 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.7748 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 8072.15 | 7160.78 | 1.0000 | 1.16192130 | 0.975280 | 23.38 | 16.57 | 0.00910990 | 46676.0 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8072.15 | 21.39 | 0.00838408 | 15.22 | 0.20572670 | 21.0941 | 23.92 | 0.00930393 | 23.89 | 0.00930393 | 49.8289 | 11279.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28315.480 | 28315.480 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.975277 | 1.16191743 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28315.48 | 28315.48 | 1.0000 | 1.16191743 | 0.975277 | 9.28 | 6.35 | 0.00481217 | 21445.8 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28315.48 | -4.30 | 0.00265759 | -4.30 | 0.20572670 | 21.0942 | 21.11 | 0.00668788 | 21.11 | 0.00668788 | 42.5855 | 8454.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12166.340 | 0.000 | 1.469940 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0118 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 12166.34 | 11722.64 | 1.0000 | 1.75124537 | 1.469940 | 24.58 | 16.64 | 0.00869943 | 46857.4 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12166.34 | 26.32 | 0.00838408 | 16.97 | 0.41145340 | 27.9912 | 23.89 | 0.00882539 | 23.89 | 0.00955469 | 51.1524 | 16676.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 44782.952 | 44782.952 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.469937 | 1.75124207 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 44782.95 | 44782.95 | 1.0000 | 1.75124207 | 1.469937 | 8.83 | 6.09 | 0.00478550 | 20916.4 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 44782.95 | -4.30 | 0.00265759 | -4.30 | 0.41145340 | 27.9912 | 21.11 | 0.00677630 | 21.11 | 0.00677630 | 43.1417 | 16280.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 6423.375 | 0.000 | 0.776070 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9984 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6423.38 | 6197.05 | 1.0000 | 0.92458808 | 0.776070 | 24.57 | 16.63 | 0.00869221 | 46823.8 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6423.38 | 26.32 | 0.00838408 | 16.97 | 0.20572670 | 26.5088 | 23.89 | 0.00881162 | 23.89 | 0.00942382 | 50.4610 | 8933.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23582.711 | 23582.711 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.776072 | 0.92459041 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 23582.71 | 23582.71 | 1.0000 | 0.92459041 | 0.776072 | 9.63 | 6.60 | 0.00488028 | 21973.7 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23582.71 | -4.30 | 0.00265759 | -4.30 | 0.20572670 | 26.5087 | 21.11 | 0.00671044 | 21.11 | 0.00671044 | 42.7276 | 8713.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 6344.895 | 0.000 | 0.766590 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9999 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6344.90 | 6120.58 | 1.0000 | 0.91329387 | 0.766590 | 24.58 | 16.63 | 0.00869301 | 46834.1 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6344.90 | 26.32 | 0.00838408 | 16.97 | 0.20572670 | 26.8366 | 23.89 | 0.00881471 | 23.89 | 0.00945628 | 50.6325 | 8811.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23339.206 | 23339.206 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.766591 | 0.91329447 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 23339.21 | 23339.21 | 1.0000 | 0.91329447 | 0.766591 | 9.64 | 6.61 | 0.00488093 | 21978.4 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23339.21 | -4.30 | 0.00265759 | -4.30 | 0.20572670 | 26.8366 | 21.11 | 0.00671075 | 21.11 | 0.00671075 | 42.7296 | 8715.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 6213.585 | 0.000 | 0.750730 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0018 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6213.59 | 5992.97 | 1.0000 | 0.89439871 | 0.750730 | 24.59 | 16.63 | 0.00869403 | 46847.6 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6213.59 | 26.32 | 0.00838408 | 16.97 | 0.20572670 | 27.4036 | 23.89 | 0.00881878 | 23.89 | 0.00951600 | 50.9479 | 8601.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 22918.595 | 22918.595 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.750725 | 0.89439307 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 22918.59 | 22918.59 | 1.0000 | 0.89439307 | 0.750725 | 9.97 | 6.85 | 0.00494592 | 22475.9 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22918.59 | -4.30 | 0.00265759 | -4.30 | 0.20572670 | 27.4037 | 21.11 | 0.00673296 | 21.11 | 0.00673296 | 42.8696 | 8973.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 6155.870 | 0.000 | 0.743750 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0035 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6155.87 | 5935.26 | 1.0000 | 0.88608293 | 0.743750 | 24.52 | 16.61 | 0.00869498 | 46785.7 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6155.87 | 26.10 | 0.00838408 | 16.90 | 0.20572670 | 27.6607 | 23.89 | 0.00882076 | 23.89 | 0.00947477 | 50.7297 | 8407.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 22532.677 | 22532.677 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.743752 | 0.88608532 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 22532.68 | 22532.68 | 1.0000 | 0.88608532 | 0.743752 | 11.46 | 7.91 | 0.00524211 | 24741.5 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22532.68 | -4.30 | 0.00265759 | -4.30 | 0.20572670 | 27.6607 | 21.11 | 0.00682319 | 21.11 | 0.00682319 | 43.4384 | 10366.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:27
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.50 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.99 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.98 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.98 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.47 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 1008.00 | 4412.67 | 237.50 |
SMSTORE1 | 1057.00 | 3726.33 | 19.17 |
SMSTORE2 | 898.17 | 2879.50 | 61.00 |
SMSTORE3 | 880.50 | 2927.50 | 91.67 |
SMSTORE4 | 830.00 | 3051.33 | 138.33 |
LGSTORE2 | 700.67 | 3199.00 | 274.67 |
SMSTORE5 | 662.50 | 3136.17 | 299.67 |
SMSTORE6 | 672.00 | 3167.17 | 334.00 |
SMSTORE7 | 707.00 | 3262.67 | 424.67 |
SMSTORE8 | 1079.83 | 3399.50 | 924.67 |
Facility | 2170.83 | 4944.17 | 1088.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 4.67 | 0.00 | 0.00 | 0.00 |
Facility | 5.17 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:27
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.872 | 0.223 | 0.000 | 0.000 |
SMSTORE1 | 4.52 | 15.00 | 902.60 | 0.616 | 0.242 | 0.000 | 0.000 |
SMSTORE2 | 3.77 | 15.00 | 902.60 | 1.134 | 0.317 | 0.000 | 0.000 |
SMSTORE3 | 3.77 | 15.00 | 902.60 | 1.124 | 0.317 | 0.000 | 0.000 |
SMSTORE4 | 3.77 | 15.00 | 902.60 | 1.093 | 0.317 | 0.000 | 0.000 |
LGSTORE2 | 13.19 | 30.00 | 1805.20 | 0.897 | 0.304 | 0.000 | 0.000 |
SMSTORE5 | 6.60 | 15.00 | 902.60 | 0.831 | 0.339 | 0.000 | 0.000 |
SMSTORE6 | 6.60 | 15.00 | 902.60 | 0.831 | 0.339 | 0.000 | 0.000 |
SMSTORE7 | 6.60 | 15.00 | 902.60 | 0.831 | 0.339 | 0.000 | 0.000 |
SMSTORE8 | 6.60 | 15.00 | 902.60 | 0.830 | 0.350 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 4.52 | 15.00 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 3.77 | 15.00 | 902.60 | 0.808 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 3.77 | 15.00 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 3.77 | 15.00 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 13.19 | 30.00 | 1805.20 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 6.60 | 15.00 | 902.60 | 0.808 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 6.60 | 15.00 | 902.60 | 0.808 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 6.60 | 15.00 | 902.60 | 0.808 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 6.60 | 15.00 | 902.60 | 0.808 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:27
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:20:27
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 869.35 | 2102.83 | 29-JAN-08:00 | 71471.06 | 22-JUL-16:50 |
Electricity:Building | 579.04 | 891.83 | 01-JAN-00:20 | 37073.46 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 132.39 | 148.64 | 01-JAN-00:20 | 6930.31 | 01-JAN-10:10 |
InteriorLights:Electricity | 450.89 | 450.00 | 01-JAN-00:20 | 29013.96 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 106.14 | 75.00 | 01-JAN-00:20 | 5587.06 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 450.89 | 450.00 | 01-JAN-00:20 | 29013.96 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 75.15 | 74.32 | 01-JAN-00:20 | 3939.90 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 62.02 | 37.50 | 01-JAN-00:20 | 3268.27 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 54.53 | 74.32 | 01-JAN-00:10 | 3678.60 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 44.11 | 37.50 | 01-JAN-00:10 | 3006.97 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 54.53 | 74.32 | 01-JAN-00:10 | 3678.60 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 44.11 | 37.50 | 01-JAN-00:10 | 3006.97 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 54.53 | 74.32 | 01-JAN-00:10 | 3678.60 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 44.11 | 37.50 | 01-JAN-00:10 | 3006.97 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 69.31 | 148.64 | 01-JAN-00:10 | 5055.82 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 50.13 | 75.00 | 01-JAN-00:10 | 3712.57 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 34.65 | 74.32 | 01-JAN-00:10 | 2527.91 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 25.07 | 37.50 | 01-JAN-00:10 | 1856.29 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 34.65 | 74.32 | 01-JAN-00:10 | 2527.91 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 25.07 | 37.50 | 01-JAN-00:10 | 1856.29 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 34.65 | 74.32 | 01-JAN-00:10 | 2527.91 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 25.07 | 37.50 | 01-JAN-00:10 | 1856.29 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 34.65 | 74.32 | 01-JAN-00:10 | 2527.91 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 25.07 | 37.50 | 01-JAN-00:10 | 1856.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
Electricity:Plant | 64.98 | 1211.00 | 06-JAN-08:10 | 11859.72 | 12-JAN-13:50 |
WaterSystems:Electricity | 64.98 | 1211.00 | 06-JAN-08:10 | 11859.72 | 12-JAN-13:50 |
Water Heater:WaterSystems:Electricity | 64.98 | 1211.00 | 06-JAN-08:10 | 11859.72 | 12-JAN-13:50 |
ElectricityPurchased:Facility | 869.35 | 2102.83 | 29-JAN-08:00 | 71471.06 | 22-JUL-16:50 |
ElectricityPurchased:Plant | 869.35 | 2102.83 | 29-JAN-08:00 | 71471.06 | 22-JUL-16:50 |
Cogeneration:ElectricityPurchased | 869.35 | 2102.83 | 29-JAN-08:00 | 71471.06 | 22-JUL-16:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 869.35 | 2102.83 | 29-JAN-08:00 | 71471.06 | 22-JUL-16:50 |
ElectricityNet:Plant | 869.35 | 2102.83 | 29-JAN-08:00 | 71471.06 | 22-JUL-16:50 |
Cogeneration:ElectricityNet | 869.35 | 2102.83 | 29-JAN-08:00 | 71471.06 | 22-JUL-16:50 |
Electricity:HVAC | 165.68 | 0.00 | 01-JAN-00:10 | 28458.27 | 22-JUL-15:00 |
Fans:Electricity | 151.54 | 0.00 | 01-JAN-00:10 | 9580.65 | 11-JAN-18:00 |
General:Fans:Electricity | 151.54 | 0.00 | 01-JAN-00:10 | 9580.65 | 11-JAN-18:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 14.14 | 0.00 | 01-JAN-00:10 | 19389.65 | 22-JUL-15:00 |
ExteriorLights:Electricity | 59.65 | 0.00 | 01-JAN-08:20 | 5459.01 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 59.65 | 0.00 | 01-JAN-08:20 | 5459.01 | 01-JAN-06:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 349.09 | 0.00 | 01-JAN-00:10 | 126660.40 | 11-JAN-18:00 |
Gas:HVAC | 349.09 | 0.00 | 01-JAN-00:10 | 126660.40 | 11-JAN-18:00 |
Heating:Gas | 349.09 | 0.00 | 01-JAN-00:10 | 126660.40 | 11-JAN-18:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 651.49 | 0.00 | 01-JAN-00:10 | 167075.95 | 10-JAN-08:10 |
EnergyTransfer:Building | 310.74 | 0.00 | 01-JAN-00:10 | 77281.31 | 10-JAN-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 71.66 | 0.00 | 01-JAN-00:10 | 12537.03 | 10-JAN-08:10 |
Heating:EnergyTransfer | 65.50 | 0.00 | 01-JAN-00:10 | 77281.31 | 10-JAN-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 6.41 | 0.00 | 01-JAN-00:10 | 12537.03 | 10-JAN-08:10 |
Cooling:EnergyTransfer | 245.24 | 0.00 | 01-JAN-00:10 | 62528.97 | 22-JUL-15:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 65.25 | 0.00 | 01-JAN-00:10 | 10959.99 | 22-JUL-16:20 |
EnergyTransfer:Zone:SMSTORE1 | 36.41 | 0.00 | 01-JAN-00:10 | 5984.87 | 22-JUL-16:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 1.65 | 0.00 | 01-JAN-00:10 | 3871.68 | 10-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 34.76 | 0.00 | 01-JAN-00:10 | 5984.87 | 22-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE2 | 27.73 | 0.00 | 01-JAN-00:10 | 5764.04 | 22-JUL-15:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 2.70 | 0.00 | 01-JAN-00:10 | 5496.94 | 31-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 25.02 | 0.00 | 01-JAN-00:10 | 5764.04 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE3 | 26.79 | 0.00 | 01-JAN-00:10 | 6111.56 | 11-JAN-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 3.27 | 0.00 | 01-JAN-00:10 | 6111.56 | 11-JAN-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 23.53 | 0.00 | 01-JAN-00:10 | 5729.84 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE4 | 24.86 | 0.00 | 01-JAN-00:10 | 6247.40 | 17-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 4.19 | 0.00 | 01-JAN-00:10 | 6247.40 | 17-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 20.67 | 0.00 | 01-JAN-00:10 | 5573.03 | 22-JUL-15:00 |
EnergyTransfer:Zone:LGSTORE2 | 40.82 | 0.00 | 01-JAN-00:10 | 15563.46 | 10-JAN-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 10.57 | 0.00 | 01-JAN-00:10 | 15563.46 | 10-JAN-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 30.25 | 0.00 | 01-JAN-00:10 | 9672.54 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE5 | 19.91 | 0.00 | 01-JAN-00:10 | 8051.29 | 31-DEC-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 6.69 | 0.00 | 01-JAN-00:10 | 8051.29 | 31-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 13.22 | 0.00 | 01-JAN-00:10 | 5007.77 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE6 | 19.80 | 0.00 | 01-JAN-00:10 | 8274.25 | 31-DEC-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 7.08 | 0.00 | 01-JAN-00:10 | 8274.25 | 31-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 12.72 | 0.00 | 01-JAN-00:10 | 4944.09 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE7 | 19.79 | 0.00 | 01-JAN-00:10 | 9274.58 | 10-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 8.58 | 0.00 | 01-JAN-00:10 | 9274.58 | 10-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 11.21 | 0.00 | 01-JAN-00:10 | 4817.38 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE8 | 22.96 | 0.00 | 01-JAN-00:10 | 12701.09 | 10-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 14.36 | 0.00 | 01-JAN-00:10 | 12701.09 | 10-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 8.60 | 0.00 | 01-JAN-00:10 | 4737.49 | 22-JUL-15:00 |
EnergyTransfer:HVAC | 340.75 | 0.00 | 01-JAN-00:10 | 101328.32 | 11-JAN-18:00 |
HeatingCoils:EnergyTransfer | 279.27 | 0.00 | 01-JAN-00:10 | 101328.32 | 11-JAN-18:00 |
CoolingCoils:EnergyTransfer | 61.48 | 0.00 | 01-JAN-00:10 | 86890.58 | 22-JUL-15:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:27
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 6.410 | -65.250 | 0.000 | 0.000 | 13.763 | 106.140 | 26.249 | 15.615 | 0.000 | 0.065 | 0.001 | 0.000 | -10.920 | 0.000 | -33.185 | -58.886 |
SMSTORE1 | 0.000 | 0.000 | 1.653 | -34.760 | 0.000 | 0.000 | 6.673 | 62.022 | 13.125 | 7.697 | 0.000 | 0.035 | 0.000 | 0.000 | -5.786 | 0.000 | -17.587 | -33.070 |
SMSTORE2 | 0.000 | 0.000 | 2.704 | -25.024 | 0.000 | 0.000 | 4.083 | 44.110 | 10.421 | 7.698 | 0.000 | 0.035 | 0.001 | 0.000 | -5.685 | 0.000 | -17.878 | -20.464 |
SMSTORE3 | 0.000 | 0.000 | 3.265 | -23.526 | 0.000 | 0.000 | 4.091 | 44.110 | 10.421 | 7.716 | 0.000 | 0.035 | 0.001 | 0.000 | -5.614 | 0.000 | -17.804 | -22.694 |
SMSTORE4 | 0.000 | 0.000 | 4.188 | -20.674 | 0.000 | 0.000 | 4.105 | 44.110 | 10.421 | 7.748 | 0.000 | 0.035 | 0.000 | 0.000 | -5.533 | 0.000 | -17.678 | -26.723 |
LGSTORE2 | 0.000 | 0.000 | 10.573 | -30.247 | 0.000 | 0.000 | 14.285 | 50.132 | 19.173 | 15.654 | 0.000 | 0.063 | 0.001 | 0.000 | -10.663 | 0.000 | -31.426 | -37.544 |
SMSTORE5 | 0.000 | 0.000 | 6.694 | -13.220 | 0.000 | 0.000 | 7.114 | 25.066 | 9.586 | 7.812 | 0.000 | 0.035 | 0.000 | 0.000 | -5.335 | 0.000 | -17.405 | -20.347 |
SMSTORE6 | 0.000 | 0.000 | 7.078 | -12.721 | 0.000 | 0.000 | 7.120 | 25.066 | 9.586 | 7.823 | 0.000 | 0.035 | 0.000 | 0.000 | -5.311 | 0.000 | -17.372 | -21.304 |
SMSTORE7 | 0.000 | 0.000 | 8.578 | -11.214 | 0.000 | 0.000 | 7.141 | 25.066 | 9.586 | 7.854 | 0.000 | 0.035 | 0.002 | 0.000 | -5.230 | 0.000 | -17.261 | -24.555 |
SMSTORE8 | 0.000 | 0.000 | 14.356 | -8.602 | 0.000 | 0.000 | 7.175 | 25.066 | 9.586 | 7.933 | 0.000 | 0.036 | 0.001 | 0.000 | -4.963 | 0.000 | -19.667 | -30.921 |
Total Facility | 0.000 | 0.000 | 65.498 | -245.238 | 0.000 | 0.000 | 75.549 | 450.890 | 128.154 | 93.552 | 0.000 | 0.410 | 0.007 | 0.000 | -65.042 | 0.000 | -207.264 | -296.509 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 23-JUL-07:03 | 0.00 | 0.00 | 0.00 | -19904.85 | 0.00 | 0.00 | 99.61 | 75.00 | 74.62 | 140.28 | 0.00 | 0.00 | 19774.57 | 0.00 | -0.00 | 0.00 | -259.23 | 0.00 |
SMSTORE1 | 06-AUG-07:02 | 0.00 | 0.00 | 0.00 | -12231.14 | 0.00 | 0.00 | 49.90 | 37.50 | 37.31 | 12.97 | 0.00 | 0.00 | 12332.54 | 0.00 | -0.00 | 0.00 | -239.08 | 0.00 |
SMSTORE2 | 24-JUL-06:02 | 0.00 | 0.00 | 0.00 | -16259.12 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 16305.98 | 0.00 | -90.92 | 0.00 | -30.26 | 0.00 |
SMSTORE3 | 24-JUL-06:02 | 0.00 | 0.00 | 0.00 | -16092.36 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 16139.04 | 0.00 | -90.75 | 0.00 | -30.25 | 0.00 |
SMSTORE4 | 23-JUL-07:03 | 0.00 | 0.00 | 0.00 | -13898.90 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 64.15 | 0.00 | 0.00 | 13895.06 | 0.00 | -0.00 | 0.00 | -135.12 | 0.00 |
LGSTORE2 | 23-JUL-08:63 | 0.00 | 0.00 | 0.00 | -17853.67 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 463.12 | 0.00 | 0.00 | 17446.93 | 0.00 | -0.00 | 0.00 | -205.03 | 0.00 |
SMSTORE5 | 23-JUL-08:63 | 0.00 | 0.00 | 0.00 | -8194.10 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 233.05 | 0.00 | 0.00 | 7999.94 | 0.00 | -0.00 | 0.00 | -113.20 | 0.00 |
SMSTORE6 | 23-JUL-08:63 | 0.00 | 0.00 | 0.00 | -7677.63 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 234.05 | 0.00 | 0.00 | 7482.34 | 0.00 | -0.00 | 0.00 | -113.08 | 0.00 |
SMSTORE7 | 23-JUL-08:63 | 0.00 | 0.00 | 0.00 | -6024.31 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 236.71 | 0.00 | 0.00 | 5826.01 | 0.00 | -0.00 | 0.00 | -112.73 | 0.00 |
SMSTORE8 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | -4737.54 | 0.00 | 0.00 | 840.50 | 1856.29 | 671.63 | 711.47 | 0.00 | 831.95 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -174.28 |
Total Facility | 23-JUL-07:03 | 0.00 | 0.00 | 0.00 | -76988.65 | 0.00 | 0.00 | 148.11 | 450.00 | 444.79 | 824.61 | 0.00 | 0.00 | 77076.58 | 0.00 | 0.00 | 0.00 | -1955.44 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 20-NOV-08:61 | 0.00 | 0.00 | 45783.63 | 0.00 | 0.00 | 0.00 | 130.07 | 75.00 | 74.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -630.33 | 0.00 | -818.57 | -44614.43 |
SMSTORE1 | 17-FEB-08:61 | 0.00 | 0.00 | 26053.38 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 99.10 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -535.12 | -25691.69 |
SMSTORE2 | 31-DEC-08:62 | 0.00 | 0.00 | 28066.02 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -373.57 | 0.00 | -500.93 | -27266.34 |
SMSTORE3 | 26-FEB-08:62 | 0.00 | 0.00 | 27973.21 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 240.76 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -493.18 | -27795.61 |
SMSTORE4 | 26-FEB-08:62 | 0.00 | 0.00 | 27840.94 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 245.04 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -486.85 | -27673.95 |
LGSTORE2 | 20-NOV-08:61 | 0.00 | 0.00 | 45222.33 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -598.85 | 0.00 | -774.96 | -43997.16 |
SMSTORE5 | 20-NOV-08:61 | 0.00 | 0.00 | 23812.99 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -298.79 | 0.00 | -431.44 | -23157.08 |
SMSTORE6 | 20-NOV-08:61 | 0.00 | 0.00 | 23573.31 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -297.08 | 0.00 | -429.22 | -22921.32 |
SMSTORE7 | 20-NOV-08:61 | 0.00 | 0.00 | 23160.51 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -290.81 | 0.00 | -420.66 | -22523.37 |
SMSTORE8 | 20-NOV-08:61 | 0.00 | 0.00 | 22785.50 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -270.64 | 0.00 | -402.73 | -22186.45 |
Total Facility | 10-JAN-08:61 | 0.00 | 0.00 | 217438.69 | 0.00 | 0.00 | 0.00 | 385.23 | 450.00 | 1452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2313.62 | 0.00 | -6924.30 | -210488.23 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:27
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.4518 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.5017 | 0.2740 | 1.0000 | 0.4115 | 0.2740 | ||
PSZ-AC_2:2 | 0.8671 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.8742 | 0.2353 | 1.0000 | 0.2057 | 0.2353 | ||
PSZ-AC_3:3 | 0.9861 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9861 | 0.2086 | 1.0000 | 0.2057 | 0.2086 | ||
PSZ-AC_4:4 | 0.9817 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9817 | 0.2096 | 1.0000 | 0.2057 | 0.2096 | ||
PSZ-AC_5:5 | 0.9753 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9753 | 0.2109 | 1.0000 | 0.2057 | 0.2109 | ||
PSZ-AC_6:6 | 1.4267 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.4699 | 0.2799 | 1.0000 | 0.4115 | 0.2799 | ||
PSZ-AC_7:7 | 0.7660 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.7761 | 0.2651 | 1.0000 | 0.2057 | 0.2651 | ||
PSZ-AC_8:8 | 0.7553 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.7666 | 0.2684 | 1.0000 | 0.2057 | 0.2684 | ||
PSZ-AC_9:9 | 0.7367 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.7507 | 0.2740 | 1.0000 | 0.2057 | 0.2740 | ||
PSZ-AC_10:10 | 0.7196 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.7438 | 0.2766 | 1.0000 | 0.2057 | 0.2766 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.4518 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.4518 | 1.0000 | 1.0000 | 0.4115 | 0.2834 | ||
PSZ-AC_2:2 | 0.8671 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.8671 | 1.0000 | 1.0000 | 0.2057 | 0.2373 | ||
PSZ-AC_3:3 | 0.9861 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9861 | 1.0000 | 1.0000 | 0.2057 | 0.2086 | ||
PSZ-AC_4:4 | 0.9817 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9817 | 1.0000 | 1.0000 | 0.2057 | 0.2096 | ||
PSZ-AC_5:5 | 0.9753 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9753 | 1.0000 | 1.0000 | 0.2057 | 0.2109 | ||
PSZ-AC_6:6 | 1.4267 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.4267 | 1.0000 | 1.0000 | 0.4115 | 0.2884 | ||
PSZ-AC_7:7 | 0.7660 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.7660 | 1.0000 | 1.0000 | 0.2057 | 0.2686 | ||
PSZ-AC_8:8 | 0.7553 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.7553 | 1.0000 | 1.0000 | 0.2057 | 0.2724 | ||
PSZ-AC_9:9 | 0.7367 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.7367 | 1.0000 | 1.0000 | 0.2057 | 0.2793 | ||
PSZ-AC_10:10 | 0.7196 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.7196 | 1.0000 | 1.0000 | 0.2057 | 0.2859 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 1.4518 | 1.4518 | 1.4518 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 0.8671 | 0.8671 | 0.8671 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 0.9861 | 0.9861 | 0.9861 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 0.9817 | 0.9817 | 0.9817 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 0.9753 | 0.9753 | 0.9753 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 1.4267 | 1.4267 | 1.4267 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 0.7660 | 0.7660 | 0.7660 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 0.7553 | 0.7553 | 0.7553 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 0.7367 | 0.7367 | 0.7367 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 0.7196 | 0.7196 | 0.7196 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.4518 | 1.5017 | 1.4518 | 1.4518 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.8671 | 0.8742 | 0.8671 | 0.8671 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 0.9861 | 0.9861 | 0.9861 | 0.9861 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 0.9817 | 0.9817 | 0.9817 | 0.9817 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 0.9753 | 0.9753 | 0.9753 | 0.9753 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.4267 | 1.4699 | 1.4267 | 1.4267 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.7660 | 0.7761 | 0.7660 | 0.7660 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.7553 | 0.7666 | 0.7553 | 0.7553 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.7367 | 0.7507 | 0.7367 | 0.7367 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.7196 | 0.7438 | 0.7196 | 0.7196 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 1.4518 | 1.4518 | 1.4518 | 0.4115 | 0.4793 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 0.8671 | 0.8671 | 0.8671 | 0.2057 | 0.4854 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 0.9861 | 0.9861 | 0.9861 | 0.2057 | 0.4794 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 0.9817 | 0.9817 | 0.9817 | 0.2057 | 0.4745 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 0.9753 | 0.9753 | 0.9753 | 0.2057 | 0.4654 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 1.4267 | 1.4267 | 1.4267 | 0.4115 | 0.4834 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 0.7660 | 0.7660 | 0.7660 | 0.2057 | 0.4516 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 0.7553 | 0.7553 | 0.7553 | 0.2057 | 0.4515 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 0.7367 | 0.7367 | 0.7367 | 0.2057 | 0.4385 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 0.7196 | 0.7196 | 0.7196 | 0.2057 | 0.3796 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.4518 | 1.4518 | 1.4518 | 1.4518 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.8671 | 0.8671 | 0.8671 | 0.8671 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 0.9861 | 0.9861 | 0.9861 | 0.9861 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 0.9817 | 0.9817 | 0.9817 | 0.9817 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 0.9753 | 0.9753 | 0.9753 | 0.9753 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.4267 | 1.4267 | 1.4267 | 1.4267 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.7660 | 0.7660 | 0.7660 | 0.7660 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.7553 | 0.7553 | 0.7553 | 0.7553 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.7367 | 0.7367 | 0.7367 | 0.7367 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.7196 | 0.7196 | 0.7196 | 0.7196 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:27
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 349.09 | 126660.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 14.14 | 19389.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 450.89 | 29013.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 59.65 | 5459.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 151.54 | 9580.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 64.98 | 11859.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 869.35 |
Natural Gas | 0.00 | 349.09 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1218.44 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 215.70 |
Space Heating | 0.00 |
Space Cooling | 6.77 |
Fans (All) | 72.49 |
Service Water Heating | 31.09 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 415.89 |
Subtotal | 415.89 |
Natural Gas [MJ/m2] | |
Space Heating | 167.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 167.00 |
Subtotal | 167.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 37.01 |
Space Heating | 28.65 |
Space Cooling | 1.16 |
Fans (All) | 12.44 |
Service Water Heating | 5.33 |
Receptacle Equipment | 10.52 |
Miscellaneous | 4.90 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
TYPE1_LIGHT_SCH | 5122. | 8760. |
TYPE2_LIGHT_SCH | 4096. | 8760. |
TYPE3_LIGHT_SCH | 3767. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUALSPSCHED | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.723562E+11 |
February | 0.000 | 0.591868E+11 |
March | 0.000 | 0.541567E+11 |
April | 0.000 | 0.139650E+11 |
May | 0.000 | 0.951943E+10 |
June | 0.000 | 0.527618E+09 |
July | 0.000 | 0.349844E+08 |
August | 0.000 | 0.000 |
September | 0.000 | 0.294652E+08 |
October | 0.000 | 0.148888E+11 |
November | 0.000 | 0.463347E+11 |
December | 0.000 | 0.780913E+11 |
Annual Sum or Average | 0.349091E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.780913E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.723562E+11 |
February | 0.000 | 0.591868E+11 |
March | 0.000 | 0.541567E+11 |
April | 0.000 | 0.139650E+11 |
May | 0.000 | 0.951943E+10 |
June | 0.000 | 0.527618E+09 |
July | 0.000 | 0.349844E+08 |
August | 0.000 | 0.000 |
September | 0.000 | 0.294652E+08 |
October | 0.000 | 0.148888E+11 |
November | 0.000 | 0.463347E+11 |
December | 0.000 | 0.780913E+11 |
Annual Sum or Average | 0.349091E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.780913E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Meter
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.723562E+11 |
February | 0.000 | 0.591868E+11 |
March | 0.000 | 0.541567E+11 |
April | 0.000 | 0.139650E+11 |
May | 0.000 | 0.951943E+10 |
June | 0.000 | 0.527618E+09 |
July | 0.000 | 0.349844E+08 |
August | 0.000 | 0.000 |
September | 0.000 | 0.294652E+08 |
October | 0.000 | 0.148888E+11 |
November | 0.000 | 0.463347E+11 |
December | 0.000 | 0.780913E+11 |
Annual Sum or Average | 0.349091E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.780913E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.723562E+11 |
February | 0.000 | 0.591868E+11 |
March | 0.000 | 0.541567E+11 |
April | 0.000 | 0.139650E+11 |
May | 0.000 | 0.951943E+10 |
June | 0.000 | 0.527618E+09 |
July | 0.000 | 0.349844E+08 |
August | 0.000 | 0.000 |
September | 0.000 | 0.294652E+08 |
October | 0.000 | 0.148888E+11 |
November | 0.000 | 0.463347E+11 |
December | 0.000 | 0.780913E+11 |
Annual Sum or Average | 0.349091E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.780913E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Meter
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.723562E+11 |
February | 0.000 | 0.591868E+11 |
March | 0.000 | 0.541567E+11 |
April | 0.000 | 0.139650E+11 |
May | 0.000 | 0.951943E+10 |
June | 0.000 | 0.527618E+09 |
July | 0.000 | 0.349844E+08 |
August | 0.000 | 0.000 |
September | 0.000 | 0.294652E+08 |
October | 0.000 | 0.148888E+11 |
November | 0.000 | 0.463347E+11 |
December | 0.000 | 0.780913E+11 |
Annual Sum or Average | 0.349091E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.780913E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.723562E+11 |
February | 0.000 | 0.591868E+11 |
March | 0.000 | 0.541567E+11 |
April | 0.000 | 0.139650E+11 |
May | 0.000 | 0.951943E+10 |
June | 0.000 | 0.527618E+09 |
July | 0.000 | 0.349844E+08 |
August | 0.000 | 0.000 |
September | 0.000 | 0.294652E+08 |
October | 0.000 | 0.148888E+11 |
November | 0.000 | 0.463347E+11 |
December | 0.000 | 0.780913E+11 |
Annual Sum or Average | 0.349091E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.780913E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.723562E+11 |
February | 0.000 | 0.591868E+11 |
March | 0.000 | 0.541567E+11 |
April | 0.000 | 0.139650E+11 |
May | 0.000 | 0.951943E+10 |
June | 0.000 | 0.527618E+09 |
July | 0.000 | 0.349844E+08 |
August | 0.000 | 0.000 |
September | 0.000 | 0.294652E+08 |
October | 0.000 | 0.148888E+11 |
November | 0.000 | 0.463347E+11 |
December | 0.000 | 0.780913E+11 |
Annual Sum or Average | 0.349091E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.780913E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Meter
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.723562E+11 |
February | 0.000 | 0.591868E+11 |
March | 0.000 | 0.541567E+11 |
April | 0.000 | 0.139650E+11 |
May | 0.000 | 0.951943E+10 |
June | 0.000 | 0.527618E+09 |
July | 0.000 | 0.349844E+08 |
August | 0.000 | 0.000 |
September | 0.000 | 0.294652E+08 |
October | 0.000 | 0.148888E+11 |
November | 0.000 | 0.463347E+11 |
December | 0.000 | 0.780913E+11 |
Annual Sum or Average | 0.349091E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.780913E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Meter
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.723562E+11 |
February | 0.000 | 0.591868E+11 |
March | 0.000 | 0.541567E+11 |
April | 0.000 | 0.139650E+11 |
May | 0.000 | 0.951943E+10 |
June | 0.000 | 0.527618E+09 |
July | 0.000 | 0.349844E+08 |
August | 0.000 | 0.000 |
September | 0.000 | 0.294652E+08 |
October | 0.000 | 0.148888E+11 |
November | 0.000 | 0.463347E+11 |
December | 0.000 | 0.780913E+11 |
Annual Sum or Average | 0.349091E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.780913E+11 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.248666E+10 | 9817.02 | 12-JAN-11:32 | -0.9 | -1.7 | 0.568310E+09 | 680.12 | 13-JAN-13:20 | 7.67 | 6.06 |
February | 0.227097E+10 | 10023.11 | 18-FEB-00:03 | -1.2 | -1.5 | 0.512985E+09 | 680.12 | 20-FEB-17:30 | 7.50 | 4.72 |
March | 0.279925E+10 | 8642.95 | 03-MAR-00:03 | 1.55 | 0.95 | 0.563266E+09 | 683.82 | 19-MAR-17:30 | 11.50 | 10.70 |
April | 0.620173E+10 | 8286.79 | 30-APR-16:25 | 24.00 | 12.83 | 0.588620E+09 | 899.05 | 30-APR-12:09 | 22.00 | 13.84 |
May | 0.669409E+10 | 7057.02 | 06-MAY-24:00 | 4.00 | 4.00 | 0.619194E+09 | 899.02 | 21-MAY-17:19 | 20.00 | 12.91 |
June | 0.763209E+10 | 9590.05 | 13-JUN-17:00 | 27.00 | 17.51 | 0.680003E+09 | 899.24 | 25-JUN-17:00 | 22.00 | 19.93 |
July | 0.877304E+10 | 19907.06 | 23-JUL-07:03 | 18.17 | 14.52 | 0.739817E+09 | 899.02 | 16-JUL-16:49 | 18.33 | 15.09 |
August | 0.896347E+10 | 12850.45 | 06-AUG-07:02 | 13.17 | 12.51 | 0.741936E+09 | 899.04 | 20-AUG-17:00 | 17.00 | 13.48 |
September | 0.806275E+10 | 8563.50 | 13-SEP-14:00 | 23.00 | 16.21 | 0.710090E+09 | 899.03 | 10-SEP-17:10 | 19.00 | 15.89 |
October | 0.609650E+10 | 7630.27 | 05-OCT-20:00 | 5.00 | 4.08 | 0.603511E+09 | 878.18 | 07-OCT-12:00 | 17.00 | 9.19 |
November | 0.328305E+10 | 7482.92 | 03-NOV-23:13 | 4.00 | 2.72 | 0.549780E+09 | 686.57 | 10-NOV-13:00 | 12.00 | 8.90 |
December | 0.198690E+10 | 10757.12 | 30-DEC-00:03 | -2.8 | -4.2 | 0.571075E+09 | 680.13 | 15-DEC-13:09 | 6.00 | 5.05 |
Annual Sum or Average | 0.652505E+11 | 0.744859E+10 | ||||||||
Minimum of Months | 0.198690E+10 | 7057.02 | -2.8 | -4.2 | 0.512985E+09 | 680.12 | 6.00 | 4.72 | ||
Maximum of Months | 0.896347E+10 | 19907.06 | 27.00 | 17.51 | 0.741936E+09 | 899.24 | 22.00 | 19.93 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128615E+10 | 3925.87 | 22-JAN-09:01 | 1.17 | 0.40 | 0.298773E+09 | 419.18 | 29-JAN-18:00 | 9.00 | 8.43 |
February | 0.124719E+10 | 3638.94 | 12-FEB-09:01 | 2.33 | 1.83 | 0.269109E+09 | 416.92 | 05-FEB-18:00 | 6.00 | 5.04 |
March | 0.155027E+10 | 3423.41 | 12-MAR-08:61 | 3.33 | 1.48 | 0.297218E+09 | 435.24 | 19-MAR-17:00 | 11.00 | 10.48 |
April | 0.284920E+10 | 4886.95 | 30-APR-15:00 | 24.00 | 13.10 | 0.327227E+09 | 449.51 | 16-APR-17:40 | 10.33 | 7.18 |
May | 0.308600E+10 | 4068.18 | 28-MAY-17:10 | 12.00 | 7.58 | 0.342887E+09 | 449.51 | 21-MAY-17:30 | 20.00 | 12.99 |
June | 0.411180E+10 | 9319.00 | 25-JUN-07:02 | 14.50 | 11.95 | 0.357921E+09 | 449.55 | 25-JUN-17:00 | 22.00 | 19.93 |
July | 0.515174E+10 | 12007.75 | 23-JUL-07:03 | 18.17 | 14.52 | 0.376192E+09 | 449.51 | 23-JUL-17:00 | 21.00 | 16.53 |
August | 0.548369E+10 | 12231.48 | 06-AUG-07:02 | 13.17 | 12.51 | 0.371511E+09 | 449.53 | 20-AUG-17:19 | 20.33 | 14.50 |
September | 0.464466E+10 | 6924.82 | 13-SEP-07:03 | 12.67 | 11.93 | 0.363392E+09 | 449.51 | 10-SEP-17:10 | 19.00 | 15.89 |
October | 0.270875E+10 | 4174.47 | 05-OCT-20:10 | 5.17 | 4.17 | 0.337250E+09 | 449.50 | 01-OCT-17:00 | 11.00 | 8.38 |
November | 0.171279E+10 | 3419.17 | 05-NOV-08:61 | 3.50 | 2.51 | 0.292864E+09 | 420.15 | 05-NOV-17:00 | 6.00 | 5.05 |
December | 0.928227E+09 | 3644.93 | 17-DEC-09:01 | 2.17 | 1.81 | 0.298753E+09 | 406.13 | 17-DEC-18:00 | 2.00 | 1.57 |
Annual Sum or Average | 0.347605E+11 | 0.393310E+10 | ||||||||
Minimum of Months | 0.928227E+09 | 3419.17 | 1.17 | 0.40 | 0.269109E+09 | 406.13 | 2.00 | 1.57 | ||
Maximum of Months | 0.548369E+10 | 12231.48 | 24.00 | 14.52 | 0.376192E+09 | 449.55 | 22.00 | 19.93 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.873070E+09 | 3975.80 | 09-JAN-09:43 | -1.2 | -2.3 | 0.169277E+09 | 340.06 | 28-JAN-13:00 | 11.00 | 9.40 |
February | 0.821075E+09 | 3721.47 | 25-FEB-08:61 | 1.17 | 1.17 | 0.153663E+09 | 340.67 | 04-FEB-13:00 | 9.00 | 6.12 |
March | 0.111330E+10 | 3710.74 | 21-MAR-07:01 | 1.33 | 0.85 | 0.174240E+09 | 370.92 | 25-MAR-12:00 | 14.00 | 11.21 |
April | 0.223763E+10 | 4530.05 | 30-APR-14:00 | 23.00 | 12.75 | 0.188367E+09 | 449.50 | 29-APR-12:00 | 19.00 | 12.78 |
May | 0.246125E+10 | 3665.60 | 23-MAY-17:10 | 18.00 | 13.64 | 0.199784E+09 | 449.49 | 27-MAY-12:00 | 15.00 | 10.67 |
June | 0.287971E+10 | 11191.71 | 27-JUN-06:02 | 15.00 | 15.00 | 0.218963E+09 | 449.49 | 24-JUN-12:09 | 16.83 | 12.75 |
July | 0.350927E+10 | 16263.07 | 24-JUL-06:02 | 13.17 | 13.07 | 0.222983E+09 | 449.49 | 29-JUL-12:09 | 17.00 | 13.95 |
August | 0.386605E+10 | 12268.28 | 06-AUG-07:02 | 13.17 | 12.51 | 0.229712E+09 | 449.50 | 05-AUG-12:30 | 19.50 | 14.42 |
September | 0.322616E+10 | 12379.40 | 02-SEP-06:02 | 13.17 | 12.51 | 0.217745E+09 | 449.50 | 23-SEP-12:00 | 19.00 | 14.77 |
October | 0.217492E+10 | 3492.76 | 12-OCT-07:03 | 3.67 | 3.67 | 0.192340E+09 | 449.49 | 07-OCT-12:09 | 16.17 | 10.37 |
November | 0.126496E+10 | 3728.03 | 04-NOV-07:01 | 1.33 | 0.86 | 0.164434E+09 | 348.05 | 25-NOV-13:39 | 10.00 | 5.63 |
December | 0.596632E+09 | 3513.82 | 09-DEC-08:61 | 2.00 | 1.57 | 0.168944E+09 | 340.06 | 23-DEC-13:09 | 9.33 | 6.65 |
Annual Sum or Average | 0.250240E+11 | 0.230045E+10 | ||||||||
Minimum of Months | 0.596632E+09 | 3492.76 | -1.2 | -2.3 | 0.153663E+09 | 340.06 | 9.00 | 5.63 | ||
Maximum of Months | 0.386605E+10 | 16263.07 | 23.00 | 15.00 | 0.229712E+09 | 449.50 | 19.50 | 14.77 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.730241E+09 | 3500.59 | 20-JAN-08:61 | 2.00 | 1.57 | 0.169181E+09 | 340.06 | 28-JAN-13:00 | 11.00 | 9.40 |
February | 0.686498E+09 | 3277.40 | 23-FEB-08:61 | 2.50 | 1.93 | 0.153651E+09 | 340.06 | 04-FEB-13:09 | 9.00 | 6.12 |
March | 0.953338E+09 | 3663.42 | 21-MAR-07:01 | 1.33 | 0.85 | 0.174048E+09 | 366.97 | 25-MAR-12:00 | 14.00 | 11.21 |
April | 0.209480E+10 | 4419.59 | 30-APR-14:00 | 23.00 | 12.75 | 0.186300E+09 | 449.50 | 29-APR-12:00 | 19.00 | 12.78 |
May | 0.234490E+10 | 3519.67 | 23-MAY-17:10 | 18.00 | 13.64 | 0.197589E+09 | 449.49 | 27-MAY-12:00 | 15.00 | 10.67 |
June | 0.277384E+10 | 10421.02 | 27-JUN-06:02 | 15.00 | 15.00 | 0.218245E+09 | 449.49 | 24-JUN-12:09 | 16.83 | 12.75 |
July | 0.342075E+10 | 16096.20 | 24-JUL-06:02 | 13.17 | 13.07 | 0.222786E+09 | 449.49 | 29-JUL-12:09 | 17.00 | 13.95 |
August | 0.379459E+10 | 10937.87 | 06-AUG-07:02 | 13.17 | 12.51 | 0.229690E+09 | 449.50 | 05-AUG-12:30 | 19.50 | 14.42 |
September | 0.312872E+10 | 11250.60 | 02-SEP-06:02 | 13.17 | 12.51 | 0.217597E+09 | 449.50 | 23-SEP-12:00 | 19.00 | 14.77 |
October | 0.201263E+10 | 3441.05 | 12-OCT-07:03 | 3.67 | 3.67 | 0.190502E+09 | 449.49 | 07-OCT-12:09 | 16.17 | 10.37 |
November | 0.108514E+10 | 3693.89 | 04-NOV-07:01 | 1.33 | 0.86 | 0.164109E+09 | 342.18 | 25-NOV-13:39 | 10.00 | 5.63 |
December | 0.500497E+09 | 3734.68 | 30-DEC-18:33 | 0.00 | -0.8 | 0.168942E+09 | 340.06 | 23-DEC-13:09 | 9.33 | 6.65 |
Annual Sum or Average | 0.235259E+11 | 0.229264E+10 | ||||||||
Minimum of Months | 0.500497E+09 | 3277.40 | 0.00 | -0.8 | 0.153651E+09 | 340.06 | 9.00 | 5.63 | ||
Maximum of Months | 0.379459E+10 | 16096.20 | 23.00 | 15.00 | 0.229690E+09 | 449.50 | 19.50 | 14.77 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.548667E+09 | 3300.64 | 04-JAN-10:33 | 2.00 | 1.44 | 0.169142E+09 | 340.06 | 28-JAN-13:00 | 11.00 | 9.40 |
February | 0.521153E+09 | 2955.72 | 10-FEB-08:61 | 4.33 | 4.19 | 0.153640E+09 | 340.06 | 04-FEB-13:09 | 9.00 | 6.12 |
March | 0.746400E+09 | 2993.68 | 29-MAR-07:01 | 4.17 | 3.69 | 0.173852E+09 | 360.75 | 25-MAR-12:00 | 14.00 | 11.21 |
April | 0.185216E+10 | 4134.32 | 30-APR-15:00 | 24.00 | 13.10 | 0.183014E+09 | 449.49 | 29-APR-12:09 | 18.17 | 12.10 |
May | 0.209595E+10 | 3214.61 | 23-MAY-17:10 | 18.00 | 13.64 | 0.194025E+09 | 449.49 | 27-MAY-12:50 | 15.17 | 10.66 |
June | 0.246353E+10 | 7818.36 | 27-JUN-06:02 | 15.00 | 15.00 | 0.215595E+09 | 449.49 | 24-JUN-12:09 | 16.83 | 12.75 |
July | 0.312465E+10 | 13898.16 | 23-JUL-07:03 | 18.17 | 14.52 | 0.222006E+09 | 449.49 | 29-JUL-12:09 | 17.00 | 13.95 |
August | 0.353191E+10 | 8025.53 | 19-AUG-06:02 | 12.00 | 11.46 | 0.229620E+09 | 449.50 | 05-AUG-12:30 | 19.50 | 14.42 |
September | 0.282633E+10 | 8108.54 | 02-SEP-06:02 | 13.17 | 12.51 | 0.216948E+09 | 449.50 | 23-SEP-12:00 | 19.00 | 14.77 |
October | 0.173316E+10 | 3330.92 | 12-OCT-07:03 | 3.67 | 3.67 | 0.187168E+09 | 449.49 | 07-OCT-12:20 | 16.33 | 10.15 |
November | 0.863731E+09 | 3265.45 | 04-NOV-07:01 | 1.33 | 0.86 | 0.163827E+09 | 340.06 | 18-NOV-13:09 | 10.00 | 7.78 |
December | 0.366495E+09 | 1773.37 | 08-DEC-12:00 | 7.00 | 4.67 | 0.168935E+09 | 340.06 | 23-DEC-13:09 | 9.33 | 6.65 |
Annual Sum or Average | 0.206741E+11 | 0.227777E+10 | ||||||||
Minimum of Months | 0.366495E+09 | 1773.37 | 1.33 | 0.86 | 0.153640E+09 | 340.06 | 9.00 | 6.12 | ||
Maximum of Months | 0.353191E+10 | 13898.16 | 24.00 | 15.00 | 0.229620E+09 | 449.50 | 19.50 | 14.77 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.365617E+09 | 8813.66 | 02-JAN-20:12 | 1.33 | 0.79 | 0.578270E+09 | 906.82 | 28-JAN-15:00 | 10.00 | 8.89 |
February | 0.372594E+09 | 6991.91 | 11-FEB-18:57 | 5.00 | 4.51 | 0.526485E+09 | 906.82 | 25-FEB-15:00 | 5.00 | 5.00 |
March | 0.597198E+09 | 5008.35 | 21-MAR-16:15 | 9.00 | 5.99 | 0.596385E+09 | 906.83 | 04-MAR-15:09 | 6.00 | 4.33 |
April | 0.278547E+10 | 6562.88 | 30-APR-15:00 | 24.00 | 13.10 | 0.597364E+09 | 1198.64 | 29-APR-14:00 | 20.00 | 12.74 |
May | 0.335280E+10 | 6610.38 | 01-MAY-08:63 | 8.00 | 6.01 | 0.626664E+09 | 1101.98 | 27-MAY-14:09 | 15.67 | 10.93 |
June | 0.444760E+10 | 7501.21 | 13-JUN-17:00 | 27.00 | 17.51 | 0.688068E+09 | 1198.65 | 24-JUN-14:09 | 18.83 | 13.60 |
July | 0.489235E+10 | 17853.10 | 23-JUL-08:63 | 19.17 | 15.33 | 0.740622E+09 | 1198.63 | 22-JUL-14:00 | 29.00 | 16.98 |
August | 0.522953E+10 | 7875.61 | 14-AUG-17:00 | 27.00 | 14.36 | 0.786130E+09 | 1198.68 | 19-AUG-14:09 | 19.17 | 14.83 |
September | 0.463823E+10 | 7474.68 | 13-SEP-14:10 | 23.00 | 16.21 | 0.717414E+09 | 1198.66 | 23-SEP-14:00 | 19.00 | 14.77 |
October | 0.263928E+10 | 6904.42 | 03-OCT-19:00 | 6.00 | 5.05 | 0.603620E+09 | 1198.59 | 07-OCT-14:00 | 19.00 | 10.08 |
November | 0.728091E+09 | 5587.57 | 21-NOV-10:23 | 8.00 | 6.29 | 0.557008E+09 | 906.82 | 25-NOV-15:00 | 8.00 | 4.80 |
December | 0.198009E+09 | 9993.53 | 26-DEC-19:03 | -1.2 | -1.6 | 0.579249E+09 | 906.82 | 23-DEC-15:09 | 9.00 | 6.98 |
Annual Sum or Average | 0.302468E+11 | 0.759728E+10 | ||||||||
Minimum of Months | 0.198009E+09 | 5008.35 | -1.2 | -1.6 | 0.526485E+09 | 906.82 | 5.00 | 4.33 | ||
Maximum of Months | 0.522953E+10 | 17853.10 | 27.00 | 17.51 | 0.786130E+09 | 1198.68 | 29.00 | 16.98 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152332E+09 | 4523.96 | 10-JAN-11:02 | -1.8 | -1.8 | 0.289135E+09 | 453.41 | 28-JAN-15:30 | 10.50 | 8.88 |
February | 0.165418E+09 | 3573.09 | 15-FEB-20:53 | 2.00 | 2.00 | 0.263241E+09 | 453.41 | 25-FEB-15:00 | 5.00 | 5.00 |
March | 0.264668E+09 | 2347.74 | 08-MAR-10:15 | 7.00 | 3.57 | 0.298190E+09 | 453.41 | 04-MAR-15:09 | 6.00 | 4.33 |
April | 0.116883E+10 | 3371.07 | 30-APR-15:00 | 24.00 | 13.10 | 0.301413E+09 | 599.32 | 29-APR-14:00 | 20.00 | 12.74 |
May | 0.138792E+10 | 2747.61 | 01-MAY-08:63 | 8.00 | 6.01 | 0.317285E+09 | 569.10 | 27-MAY-14:09 | 15.67 | 10.93 |
June | 0.182435E+10 | 3844.44 | 13-JUN-17:00 | 27.00 | 17.51 | 0.351195E+09 | 599.33 | 24-JUN-14:09 | 18.83 | 13.60 |
July | 0.222750E+10 | 8194.12 | 23-JUL-08:63 | 19.17 | 15.33 | 0.374019E+09 | 599.33 | 29-JUL-14:00 | 17.00 | 13.95 |
August | 0.252516E+10 | 4080.07 | 14-AUG-17:00 | 27.00 | 14.36 | 0.393878E+09 | 599.34 | 26-AUG-14:09 | 17.83 | 14.80 |
September | 0.201259E+10 | 3822.13 | 13-SEP-14:10 | 23.00 | 16.21 | 0.365058E+09 | 599.33 | 23-SEP-14:00 | 19.00 | 14.77 |
October | 0.108523E+10 | 3073.93 | 05-OCT-20:00 | 5.00 | 4.08 | 0.305384E+09 | 599.32 | 07-OCT-14:30 | 18.00 | 10.00 |
November | 0.323769E+09 | 3795.60 | 27-NOV-20:53 | 1.00 | 0.17 | 0.278509E+09 | 453.41 | 18-NOV-15:30 | 8.50 | 6.12 |
December | 82483101.16 | 4328.93 | 26-DEC-18:53 | -1.0 | -1.4 | 0.289622E+09 | 453.41 | 23-DEC-15:09 | 9.00 | 6.98 |
Annual Sum or Average | 0.132202E+11 | 0.382693E+10 | ||||||||
Minimum of Months | 82483101.16 | 2347.74 | -1.8 | -1.8 | 0.263241E+09 | 453.41 | 5.00 | 4.33 | ||
Maximum of Months | 0.252516E+10 | 8194.12 | 27.00 | 17.51 | 0.393878E+09 | 599.34 | 20.00 | 14.80 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136753E+09 | 3358.75 | 13-JAN-20:33 | 3.00 | 2.55 | 0.289117E+09 | 453.41 | 21-JAN-15:00 | 6.10 | 5.14 |
February | 0.143802E+09 | 3662.52 | 15-FEB-20:33 | 1.67 | 1.67 | 0.263243E+09 | 453.41 | 25-FEB-15:00 | 5.00 | 5.00 |
March | 0.239778E+09 | 3356.36 | 11-MAR-18:43 | 3.00 | 2.55 | 0.298188E+09 | 453.41 | 04-MAR-15:09 | 6.00 | 4.33 |
April | 0.111166E+10 | 3275.46 | 30-APR-15:00 | 24.00 | 13.10 | 0.300726E+09 | 599.32 | 29-APR-14:00 | 20.00 | 12.74 |
May | 0.132214E+10 | 2738.57 | 01-MAY-08:63 | 8.00 | 6.01 | 0.316302E+09 | 564.80 | 27-MAY-14:09 | 15.67 | 10.93 |
June | 0.177727E+10 | 3750.21 | 13-JUN-17:00 | 27.00 | 17.51 | 0.349389E+09 | 599.33 | 24-JUN-14:09 | 18.83 | 13.60 |
July | 0.216373E+10 | 7677.64 | 23-JUL-08:63 | 19.17 | 15.33 | 0.373195E+09 | 599.33 | 29-JUL-14:00 | 17.00 | 13.95 |
August | 0.245038E+10 | 4010.48 | 14-AUG-17:00 | 27.00 | 14.36 | 0.393805E+09 | 599.34 | 26-AUG-14:09 | 17.83 | 14.80 |
September | 0.196831E+10 | 3748.55 | 13-SEP-14:20 | 23.00 | 16.21 | 0.364105E+09 | 599.33 | 23-SEP-14:00 | 19.00 | 14.77 |
October | 0.104013E+10 | 3007.26 | 05-OCT-19:50 | 5.33 | 4.33 | 0.304415E+09 | 599.32 | 07-OCT-14:50 | 18.67 | 10.06 |
November | 0.295177E+09 | 3809.52 | 27-NOV-20:33 | 1.00 | 0.25 | 0.278510E+09 | 453.41 | 18-NOV-15:09 | 8.83 | 6.42 |
December | 72024965.83 | 3999.99 | 18-DEC-19:03 | 0.17 | -0.2 | 0.289618E+09 | 453.41 | 23-DEC-15:09 | 9.00 | 6.98 |
Annual Sum or Average | 0.127212E+11 | 0.382061E+10 | ||||||||
Minimum of Months | 72024965.83 | 2738.57 | 0.17 | -0.2 | 0.263243E+09 | 453.41 | 5.00 | 4.33 | ||
Maximum of Months | 0.245038E+10 | 7677.64 | 27.00 | 17.51 | 0.393805E+09 | 599.34 | 20.00 | 14.80 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 88227407.78 | 3404.97 | 05-JAN-18:53 | 2.90 | 2.45 | 0.289134E+09 | 453.41 | 21-JAN-15:00 | 6.10 | 5.14 |
February | 84238210.53 | 3607.70 | 15-FEB-19:33 | 2.00 | 1.86 | 0.263241E+09 | 453.41 | 25-FEB-15:00 | 5.00 | 5.00 |
March | 0.160955E+09 | 3831.51 | 02-MAR-20:53 | 1.00 | 0.59 | 0.298194E+09 | 453.41 | 04-MAR-15:09 | 6.00 | 4.33 |
April | 0.939991E+09 | 3029.28 | 30-APR-15:00 | 24.00 | 13.10 | 0.299034E+09 | 599.32 | 29-APR-14:00 | 20.00 | 12.74 |
May | 0.113285E+10 | 2680.77 | 01-MAY-08:63 | 8.00 | 6.01 | 0.313417E+09 | 549.59 | 27-MAY-14:09 | 15.67 | 10.93 |
June | 0.163536E+10 | 3535.27 | 13-JUN-17:00 | 27.00 | 17.51 | 0.343555E+09 | 599.33 | 24-JUN-14:09 | 18.83 | 13.60 |
July | 0.197677E+10 | 6024.32 | 23-JUL-08:63 | 19.17 | 15.33 | 0.370398E+09 | 599.32 | 15-JUL-14:00 | 18.00 | 12.88 |
August | 0.222970E+10 | 3824.71 | 14-AUG-17:00 | 27.00 | 14.36 | 0.393453E+09 | 599.34 | 26-AUG-14:09 | 17.83 | 14.80 |
September | 0.182245E+10 | 3575.51 | 13-SEP-14:20 | 23.00 | 16.21 | 0.360077E+09 | 599.33 | 23-SEP-14:00 | 19.00 | 14.77 |
October | 0.897700E+09 | 2917.44 | 03-OCT-19:00 | 6.00 | 5.05 | 0.301688E+09 | 599.30 | 07-OCT-14:00 | 19.00 | 10.08 |
November | 0.206542E+09 | 2383.39 | 25-NOV-18:55 | 7.00 | 4.34 | 0.278498E+09 | 453.41 | 18-NOV-15:00 | 8.00 | 5.66 |
December | 38839646.15 | 3148.73 | 12-DEC-19:53 | 4.00 | 3.12 | 0.289623E+09 | 453.41 | 23-DEC-15:09 | 9.00 | 6.98 |
Annual Sum or Average | 0.112136E+11 | 0.380031E+10 | ||||||||
Minimum of Months | 38839646.15 | 2383.39 | 1.00 | 0.59 | 0.263241E+09 | 453.41 | 5.00 | 4.33 | ||
Maximum of Months | 0.222970E+10 | 6024.32 | 27.00 | 17.51 | 0.393453E+09 | 599.34 | 20.00 | 14.80 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14559191.07 | 2774.06 | 06-JAN-11:15 | 5.33 | 4.70 | 0.289133E+09 | 453.41 | 28-JAN-15:00 | 10.00 | 8.89 |
February | 10720875.32 | 3278.02 | 09-FEB-18:23 | 3.50 | 3.27 | 0.263242E+09 | 453.41 | 25-FEB-15:00 | 5.00 | 5.00 |
March | 27337269.86 | 2394.97 | 16-MAR-17:05 | 7.00 | 5.21 | 0.298192E+09 | 453.41 | 04-MAR-15:09 | 6.00 | 4.33 |
April | 0.624778E+09 | 2693.17 | 30-APR-15:00 | 24.00 | 13.10 | 0.297104E+09 | 599.32 | 29-APR-14:00 | 20.00 | 12.74 |
May | 0.743291E+09 | 2431.72 | 01-MAY-08:63 | 8.00 | 6.01 | 0.309295E+09 | 531.91 | 23-MAY-12:20 | 19.33 | 14.89 |
June | 0.138064E+10 | 3290.90 | 13-JUN-17:00 | 27.00 | 17.51 | 0.333393E+09 | 599.33 | 24-JUN-14:30 | 18.50 | 13.32 |
July | 0.168586E+10 | 4737.49 | 22-JUL-15:00 | 29.00 | 16.98 | 0.365065E+09 | 599.32 | 15-JUL-14:00 | 18.00 | 12.88 |
August | 0.185843E+10 | 3519.97 | 14-AUG-17:00 | 27.00 | 14.36 | 0.391710E+09 | 599.34 | 26-AUG-14:09 | 17.83 | 14.80 |
September | 0.158771E+10 | 3333.70 | 13-SEP-14:10 | 23.00 | 16.21 | 0.352628E+09 | 599.34 | 23-SEP-14:00 | 19.00 | 14.77 |
October | 0.605825E+09 | 2528.24 | 03-OCT-18:40 | 7.33 | 6.04 | 0.297961E+09 | 594.10 | 07-OCT-14:00 | 19.00 | 10.08 |
November | 61038822.87 | 2717.02 | 28-NOV-11:35 | 5.57 | 3.43 | 0.278502E+09 | 453.41 | 25-NOV-15:09 | 8.83 | 5.23 |
December | 1400829.77 | 367.61 | 06-DEC-12:00 | 8.00 | 5.64 | 0.289625E+09 | 453.41 | 23-DEC-15:09 | 9.00 | 6.98 |
Annual Sum or Average | 0.860159E+10 | 0.376585E+10 | ||||||||
Minimum of Months | 1400829.77 | 367.61 | 3.50 | 3.27 | 0.263242E+09 | 453.41 | 5.00 | 4.33 | ||
Maximum of Months | 0.185843E+10 | 4737.49 | 29.00 | 17.51 | 0.391710E+09 | 599.34 | 20.00 | 14.89 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151954E+10 | 45777.79 | 31-JAN-08:61 | 1.17 |
February | 0.976123E+09 | 45778.75 | 17-FEB-08:61 | -2.3 |
March | 0.865017E+09 | 45765.54 | 27-MAR-07:01 | 2.50 |
April | 0.164093E+09 | 45477.75 | 01-APR-07:01 | 4.17 |
May | 0.101692E+09 | 45449.75 | 05-MAY-07:01 | 7.17 |
June | 51736470.95 | 788.44 | 13-JUN-07:07 | 19.33 |
July | 34125111.57 | 1074.27 | 23-JUL-07:05 | 18.17 |
August | 20684379.47 | 848.97 | 06-AUG-07:03 | 13.17 |
September | 51383157.19 | 801.52 | 16-SEP-07:07 | 14.33 |
October | 0.125759E+09 | 39234.54 | 23-OCT-07:01 | 4.50 |
November | 0.584435E+09 | 45783.59 | 20-NOV-08:61 | 1.33 |
December | 0.191517E+10 | 45765.96 | 15-DEC-08:61 | 1.33 |
Annual Sum or Average | 0.640975E+10 | |||
Minimum of Months | 20684379.47 | 788.44 | -2.3 | |
Maximum of Months | 0.191517E+10 | 45783.59 | 19.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.373753E+09 | 26047.79 | 10-JAN-08:61 | -5.7 |
February | 0.174921E+09 | 26053.43 | 17-FEB-08:61 | -2.3 |
March | 0.170000E+09 | 19806.46 | 16-MAR-07:01 | 2.33 |
April | 88019960.07 | 1045.52 | 30-APR-07:05 | 16.23 |
May | 78074031.45 | 942.22 | 03-MAY-07:13 | 7.33 |
June | 28054533.08 | 1252.68 | 13-JUN-07:07 | 19.33 |
July | 21433180.86 | 1382.01 | 23-JUL-07:05 | 18.17 |
August | 18550874.54 | 1281.94 | 06-AUG-07:03 | 13.17 |
September | 25066357.18 | 1208.53 | 16-SEP-07:07 | 14.33 |
October | 92135205.55 | 967.07 | 13-OCT-07:25 | 10.50 |
November | 0.148863E+09 | 25699.27 | 29-NOV-08:61 | -0.7 |
December | 0.433725E+09 | 26046.30 | 30-DEC-08:61 | 0.00 |
Annual Sum or Average | 0.165260E+10 | |||
Minimum of Months | 18550874.54 | 942.22 | -5.7 | |
Maximum of Months | 0.433725E+09 | 26053.43 | 19.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.634134E+09 | 28055.06 | 10-JAN-07:02 | -4.3 |
February | 0.350920E+09 | 26984.39 | 20-FEB-08:62 | 1.33 |
March | 0.301103E+09 | 16120.54 | 06-MAR-07:02 | 4.33 |
April | 0.105936E+09 | 5205.35 | 08-APR-07:10 | 2.50 |
May | 83198257.72 | 1042.25 | 28-MAY-07:02 | 11.50 |
June | 26408207.31 | 1422.05 | 27-JUN-06:04 | 15.00 |
July | 27236754.39 | 2048.92 | 22-JUL-17:12 | 29.33 |
August | 16678302.65 | 1444.05 | 06-AUG-07:03 | 13.17 |
September | 23529593.21 | 1427.95 | 02-SEP-06:03 | 13.17 |
October | 99844572.14 | 1953.95 | 23-OCT-07:05 | 4.50 |
November | 0.262039E+09 | 18128.64 | 20-NOV-07:02 | 1.00 |
December | 0.773080E+09 | 28066.01 | 31-DEC-08:62 | 0.00 |
Annual Sum or Average | 0.270411E+10 | |||
Minimum of Months | 16678302.65 | 1042.25 | -4.3 | |
Maximum of Months | 0.773080E+09 | 28066.01 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.763228E+09 | 27962.58 | 10-JAN-07:02 | -4.3 |
February | 0.440530E+09 | 27973.23 | 26-FEB-08:62 | 1.50 |
March | 0.378145E+09 | 21801.41 | 06-MAR-07:02 | 4.33 |
April | 0.114881E+09 | 6069.63 | 01-APR-06:03 | 3.17 |
May | 87611511.38 | 2073.41 | 06-MAY-06:05 | 3.50 |
June | 34000167.80 | 1388.43 | 27-JUN-06:04 | 15.00 |
July | 30162145.82 | 2046.52 | 22-JUL-17:12 | 29.33 |
August | 14793711.27 | 1394.31 | 06-AUG-07:03 | 13.17 |
September | 29478451.66 | 1384.93 | 02-SEP-06:03 | 13.17 |
October | 0.109502E+09 | 5299.70 | 23-OCT-06:03 | 4.00 |
November | 0.332404E+09 | 23656.18 | 20-NOV-07:02 | 1.00 |
December | 0.930559E+09 | 27972.98 | 31-DEC-08:62 | 0.00 |
Annual Sum or Average | 0.326530E+10 | |||
Minimum of Months | 14793711.27 | 1384.93 | -4.3 | |
Maximum of Months | 0.930559E+09 | 27973.23 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.949884E+09 | 27830.25 | 10-JAN-07:02 | -4.3 |
February | 0.599130E+09 | 27840.96 | 26-FEB-08:62 | 1.50 |
March | 0.522665E+09 | 26736.21 | 06-MAR-07:02 | 4.33 |
April | 0.135223E+09 | 8211.44 | 01-APR-06:03 | 3.17 |
May | 98618258.43 | 3897.71 | 06-MAY-06:05 | 3.50 |
June | 52775539.35 | 1285.02 | 27-JUN-06:04 | 15.00 |
July | 36954481.72 | 2047.91 | 22-JUL-17:12 | 29.33 |
August | 10957006.77 | 1283.61 | 17-AUG-06:04 | 14.17 |
September | 47238786.83 | 1275.07 | 02-SEP-06:03 | 13.17 |
October | 0.123933E+09 | 8217.32 | 23-OCT-06:03 | 4.00 |
November | 0.443617E+09 | 27579.95 | 20-NOV-07:02 | 1.00 |
December | 0.116697E+10 | 27840.29 | 31-DEC-08:62 | 0.00 |
Annual Sum or Average | 0.418796E+10 | |||
Minimum of Months | 10957006.77 | 1275.07 | -4.3 | |
Maximum of Months | 0.116697E+10 | 27840.96 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237271E+10 | 45215.79 | 31-JAN-08:61 | 1.17 |
February | 0.166894E+10 | 45215.50 | 17-FEB-08:61 | -2.3 |
March | 0.149957E+10 | 45204.79 | 27-MAR-07:01 | 2.50 |
April | 0.259065E+09 | 44922.32 | 01-APR-07:01 | 4.17 |
May | 0.131911E+09 | 44904.95 | 05-MAY-07:01 | 7.17 |
June | 56023654.68 | 6881.59 | 08-JUN-07:02 | 10.17 |
July | 48404920.22 | 2888.12 | 22-JUL-17:03 | 29.17 |
August | 33379941.78 | 740.76 | 17-AUG-07:07 | 15.17 |
September | 54104119.30 | 661.45 | 02-SEP-07:07 | 13.83 |
October | 0.303136E+09 | 44922.45 | 23-OCT-07:01 | 4.50 |
November | 0.124820E+10 | 45222.33 | 20-NOV-08:61 | 1.33 |
December | 0.289759E+10 | 45206.86 | 18-DEC-08:61 | 1.00 |
Annual Sum or Average | 0.105730E+11 | |||
Minimum of Months | 33379941.78 | 661.45 | -2.3 | |
Maximum of Months | 0.289759E+10 | 45222.33 | 29.17 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142963E+10 | 23809.54 | 31-JAN-08:61 | 1.17 |
February | 0.104235E+10 | 23809.99 | 17-FEB-08:61 | -2.3 |
March | 0.952461E+09 | 23803.35 | 27-MAR-07:01 | 2.50 |
April | 0.191764E+09 | 23646.91 | 01-APR-07:01 | 4.17 |
May | 0.125749E+09 | 23638.91 | 05-MAY-07:01 | 7.17 |
June | 68545477.22 | 5474.81 | 08-JUN-07:02 | 10.17 |
July | 49154249.69 | 1898.49 | 22-JUL-17:12 | 29.33 |
August | 27082674.92 | 875.34 | 17-AUG-07:07 | 15.17 |
September | 64536226.29 | 840.61 | 21-SEP-07:13 | 9.00 |
October | 0.226663E+09 | 23648.14 | 23-OCT-07:01 | 4.50 |
November | 0.789843E+09 | 23812.98 | 20-NOV-08:61 | 1.33 |
December | 0.172615E+10 | 23805.07 | 27-DEC-08:61 | -1.0 |
Annual Sum or Average | 0.669394E+10 | |||
Minimum of Months | 27082674.92 | 840.61 | -2.3 | |
Maximum of Months | 0.172615E+10 | 23812.98 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150393E+10 | 23569.41 | 31-JAN-08:61 | 1.17 |
February | 0.110535E+10 | 23569.82 | 17-FEB-08:61 | -2.3 |
March | 0.101646E+10 | 23563.80 | 27-MAR-07:01 | 2.50 |
April | 0.208373E+09 | 23410.93 | 01-APR-07:01 | 4.17 |
May | 0.132205E+09 | 23402.62 | 05-MAY-07:01 | 7.17 |
June | 70779302.16 | 7747.50 | 08-JUN-07:02 | 10.17 |
July | 51754571.93 | 1889.46 | 22-JUL-17:12 | 29.33 |
August | 30980177.90 | 809.87 | 30-AUG-07:03 | 12.33 |
September | 66738820.37 | 830.93 | 21-SEP-07:13 | 9.00 |
October | 0.248812E+09 | 23411.52 | 23-OCT-07:01 | 4.50 |
November | 0.844644E+09 | 23573.31 | 20-NOV-08:61 | 1.33 |
December | 0.179755E+10 | 23565.21 | 27-DEC-08:61 | -1.0 |
Annual Sum or Average | 0.707758E+10 | |||
Minimum of Months | 30980177.90 | 809.87 | -2.3 | |
Maximum of Months | 0.179755E+10 | 23573.31 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.178282E+10 | 23156.85 | 31-JAN-08:61 | 1.17 |
February | 0.135506E+10 | 23157.04 | 17-FEB-08:61 | -2.3 |
March | 0.126659E+10 | 23151.44 | 27-MAR-07:01 | 2.50 |
April | 0.278624E+09 | 23005.16 | 01-APR-07:01 | 4.17 |
May | 0.182321E+09 | 22995.22 | 05-MAY-07:01 | 7.17 |
June | 77798810.89 | 14578.65 | 08-JUN-07:02 | 10.17 |
July | 62051620.64 | 1879.73 | 22-JUL-17:12 | 29.33 |
August | 54422240.07 | 794.22 | 30-AUG-07:15 | 12.67 |
September | 74075532.73 | 815.46 | 21-SEP-07:13 | 9.00 |
October | 0.327795E+09 | 23004.35 | 23-OCT-07:01 | 4.50 |
November | 0.103191E+10 | 23160.51 | 20-NOV-08:61 | 1.33 |
December | 0.208425E+10 | 23152.27 | 18-DEC-08:61 | 1.00 |
Annual Sum or Average | 0.857773E+10 | |||
Minimum of Months | 54422240.07 | 794.22 | -2.3 | |
Maximum of Months | 0.208425E+10 | 23160.51 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.283705E+10 | 22781.48 | 31-JAN-08:61 | 1.17 |
February | 0.231761E+10 | 22781.75 | 17-FEB-08:61 | -2.3 |
March | 0.221554E+10 | 22776.19 | 27-MAR-07:01 | 2.50 |
April | 0.577698E+09 | 22633.74 | 01-APR-07:01 | 4.17 |
May | 0.437616E+09 | 22616.57 | 05-MAY-07:01 | 7.17 |
June | 0.107803E+09 | 22395.41 | 08-JUN-07:02 | 10.17 |
July | 86956848.42 | 10236.98 | 05-JUL-07:03 | 12.17 |
August | 78651069.57 | 786.74 | 30-AUG-07:15 | 12.67 |
September | 81019860.60 | 6071.51 | 07-SEP-07:03 | 10.33 |
October | 0.664148E+09 | 22629.58 | 23-OCT-07:01 | 4.50 |
November | 0.174230E+10 | 22785.50 | 20-NOV-08:61 | 1.33 |
December | 0.320943E+10 | 22775.13 | 18-DEC-08:61 | 1.00 |
Annual Sum or Average | 0.143558E+11 | |||
Minimum of Months | 78651069.57 | 786.74 | -2.3 | |
Maximum of Months | 0.320943E+10 | 22785.50 | 12.67 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.900155E+10 | 5587.06 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.814396E+10 | 5587.06 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.901902E+10 | 5587.06 | 01-MAR-10:09 | 0.223053E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.873329E+10 | 5587.06 | 01-APR-09:09 | 0.215990E+10 | 1343.25 | 01-APR-09:09 |
May | 0.900155E+10 | 5587.06 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.873302E+10 | 5587.06 | 01-JUN-09:09 | 0.215990E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.901915E+10 | 5587.06 | 01-JUL-09:09 | 0.223053E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.900155E+10 | 5587.06 | 01-AUG-09:09 | 0.222596E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.875049E+10 | 5587.06 | 01-SEP-09:09 | 0.216447E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.900168E+10 | 5587.06 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.869809E+10 | 5587.06 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.903649E+10 | 5587.06 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.106140E+12 | 0.262491E+11 | ||||
Minimum of Months | 0.814396E+10 | 5587.06 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.903649E+10 | 5587.06 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.525997E+10 | 3268.27 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.475885E+10 | 3268.27 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.527019E+10 | 3268.27 | 01-MAR-10:09 | 0.111526E+10 | 671.63 | 01-MAR-10:09 |
April | 0.510323E+10 | 3268.27 | 01-APR-09:09 | 0.107995E+10 | 671.63 | 01-APR-09:09 |
May | 0.525997E+10 | 3268.27 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.510306E+10 | 3268.27 | 01-JUN-09:09 | 0.107995E+10 | 671.63 | 01-JUN-09:09 |
July | 0.527027E+10 | 3268.27 | 01-JUL-09:09 | 0.111526E+10 | 671.63 | 01-JUL-09:09 |
August | 0.525997E+10 | 3268.27 | 01-AUG-09:09 | 0.111298E+10 | 671.63 | 01-AUG-09:09 |
September | 0.511328E+10 | 3268.27 | 01-SEP-09:09 | 0.108223E+10 | 671.63 | 01-SEP-09:09 |
October | 0.526005E+10 | 3268.27 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.508263E+10 | 3268.27 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.528040E+10 | 3268.27 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.620219E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.475885E+10 | 3268.27 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.528040E+10 | 3268.27 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.372206E+10 | 3006.97 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.337152E+10 | 3006.97 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.380758E+10 | 3006.97 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.361234E+10 | 3006.97 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.376482E+10 | 3006.97 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.367648E+10 | 3006.97 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.370068E+10 | 3006.97 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.380758E+10 | 3006.97 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.361234E+10 | 3006.97 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.372206E+10 | 3006.97 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.361234E+10 | 3006.97 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.370068E+10 | 3006.97 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.441105E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.337152E+10 | 3006.97 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.380758E+10 | 3006.97 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.372206E+10 | 3006.97 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.337152E+10 | 3006.97 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.380758E+10 | 3006.97 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.361234E+10 | 3006.97 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.376482E+10 | 3006.97 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.367648E+10 | 3006.97 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.370068E+10 | 3006.97 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.380758E+10 | 3006.97 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.361234E+10 | 3006.97 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.372206E+10 | 3006.97 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.361234E+10 | 3006.97 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.370068E+10 | 3006.97 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.441105E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.337152E+10 | 3006.97 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.380758E+10 | 3006.97 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.372206E+10 | 3006.97 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.337152E+10 | 3006.97 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.380758E+10 | 3006.97 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.361234E+10 | 3006.97 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.376482E+10 | 3006.97 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.367648E+10 | 3006.97 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.370068E+10 | 3006.97 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.380758E+10 | 3006.97 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.361234E+10 | 3006.97 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.372206E+10 | 3006.97 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.361234E+10 | 3006.97 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.370068E+10 | 3006.97 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.441105E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.337152E+10 | 3006.97 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.380758E+10 | 3006.97 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.422804E+10 | 3712.57 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.383070E+10 | 3712.57 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.433280E+10 | 3712.57 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.410432E+10 | 3712.57 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.428042E+10 | 3712.57 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.418290E+10 | 3712.57 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.420185E+10 | 3712.57 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.433280E+10 | 3712.57 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.410432E+10 | 3712.57 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.422804E+10 | 3712.57 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.410432E+10 | 3712.57 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.420185E+10 | 3712.57 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.501324E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.383070E+10 | 3712.57 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.433280E+10 | 3712.57 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.211402E+10 | 1856.29 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.191535E+10 | 1856.29 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.216640E+10 | 1856.29 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.205216E+10 | 1856.29 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.214021E+10 | 1856.29 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.209145E+10 | 1856.29 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.210092E+10 | 1856.29 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.216640E+10 | 1856.29 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.205216E+10 | 1856.29 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.211402E+10 | 1856.29 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.205216E+10 | 1856.29 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.210092E+10 | 1856.29 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.250662E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.191535E+10 | 1856.29 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.216640E+10 | 1856.29 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.211402E+10 | 1856.29 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.191535E+10 | 1856.29 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.216640E+10 | 1856.29 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.205216E+10 | 1856.29 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.214021E+10 | 1856.29 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.209145E+10 | 1856.29 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.210092E+10 | 1856.29 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.216640E+10 | 1856.29 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.205216E+10 | 1856.29 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.211402E+10 | 1856.29 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.205216E+10 | 1856.29 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.210092E+10 | 1856.29 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.250662E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.191535E+10 | 1856.29 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.216640E+10 | 1856.29 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.211402E+10 | 1856.29 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.191535E+10 | 1856.29 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.216640E+10 | 1856.29 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.205216E+10 | 1856.29 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.214021E+10 | 1856.29 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.209145E+10 | 1856.29 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.210092E+10 | 1856.29 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.216640E+10 | 1856.29 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.205216E+10 | 1856.29 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.211402E+10 | 1856.29 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.205216E+10 | 1856.29 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.210092E+10 | 1856.29 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.250662E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.191535E+10 | 1856.29 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.216640E+10 | 1856.29 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.211402E+10 | 1856.29 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.191535E+10 | 1856.29 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.216640E+10 | 1856.29 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.205216E+10 | 1856.29 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.214021E+10 | 1856.29 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.209145E+10 | 1856.29 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.210092E+10 | 1856.29 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.216640E+10 | 1856.29 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.205216E+10 | 1856.29 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.211402E+10 | 1856.29 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.205216E+10 | 1856.29 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.210092E+10 | 1856.29 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.250662E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.191535E+10 | 1856.29 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.216640E+10 | 1856.29 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.180574E+10 | 0.900155E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379757E+10 |
February | 0.163016E+10 | 0.814396E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342837E+10 |
March | 0.178954E+10 | 0.901902E+10 | 0.223053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324174E+10 |
April | 0.174484E+10 | 0.873329E+10 | 0.215990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 263028.56 | 0.231954E+10 |
May | 0.179537E+10 | 0.900155E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18121.60 | 0.281243E+10 |
June | 0.173447E+10 | 0.873302E+10 | 0.215990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10790000.42 | 0.209104E+10 |
July | 0.181028E+10 | 0.901915E+10 | 0.223053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47490527.77 | 0.182030E+10 |
August | 0.178501E+10 | 0.900155E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6341800.85 | 0.149371E+10 |
September | 0.174937E+10 | 0.875049E+10 | 0.216447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187070E+10 |
October | 0.180574E+10 | 0.900168E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261148E+10 |
November | 0.174613E+10 | 0.869809E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342643E+10 |
December | 0.181481E+10 | 0.903649E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427197E+10 |
Annual Sum or Average | 0.212115E+11 | 0.106140E+12 | 0.262491E+11 | 64903479.20 | 0.331853E+11 | ||||
Minimum of Months | 0.163016E+10 | 0.814396E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149371E+10 |
Maximum of Months | 0.181481E+10 | 0.903649E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47490527.77 | 0.427197E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.902868E+09 | 0.525997E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205452E+10 |
February | 0.815075E+09 | 0.475885E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181253E+10 |
March | 0.894769E+09 | 0.527019E+10 | 0.111526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175601E+10 |
April | 0.872416E+09 | 0.510323E+10 | 0.107995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 145166.07 | 0.132052E+10 |
May | 0.897684E+09 | 0.525997E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9981.02 | 0.149627E+10 |
June | 0.867232E+09 | 0.510306E+10 | 0.107995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5887676.00 | 0.110411E+10 |
July | 0.905135E+09 | 0.527027E+10 | 0.111526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26000865.19 | 0.908628E+09 |
August | 0.892501E+09 | 0.525997E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3454841.80 | 0.730284E+09 |
September | 0.874683E+09 | 0.511328E+10 | 0.108223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.960674E+09 |
October | 0.902868E+09 | 0.526005E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144812E+10 |
November | 0.873064E+09 | 0.508263E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179163E+10 |
December | 0.907403E+09 | 0.528040E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220401E+10 |
Annual Sum or Average | 0.106057E+11 | 0.620219E+11 | 0.131245E+11 | 35498530.10 | 0.175873E+11 | ||||
Minimum of Months | 0.815075E+09 | 0.475885E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.730284E+09 |
Maximum of Months | 0.907403E+09 | 0.528040E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26000865.19 | 0.220401E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.372206E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206178E+10 |
February | 0.487879E+09 | 0.337152E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182987E+10 |
March | 0.551374E+09 | 0.380758E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175979E+10 |
April | 0.524810E+09 | 0.361234E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69138.81 | 0.132098E+10 |
May | 0.544247E+09 | 0.376482E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9977.33 | 0.152251E+10 |
June | 0.532585E+09 | 0.367648E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5846558.91 | 0.115090E+10 |
July | 0.536472E+09 | 0.370068E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25574472.61 | 0.957669E+09 |
August | 0.551374E+09 | 0.380758E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3454571.30 | 0.769072E+09 |
September | 0.524810E+09 | 0.361234E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.993581E+09 |
October | 0.537120E+09 | 0.372206E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145956E+10 |
November | 0.518979E+09 | 0.361234E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180935E+10 |
December | 0.536472E+09 | 0.370068E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224264E+10 |
Annual Sum or Average | 0.638324E+10 | 0.441105E+11 | 0.104207E+11 | 34954718.96 | 0.178777E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.337152E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769072E+09 |
Maximum of Months | 0.551374E+09 | 0.380758E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25574472.61 | 0.224264E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.372206E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206002E+10 |
February | 0.487879E+09 | 0.337152E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182821E+10 |
March | 0.551374E+09 | 0.380758E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175809E+10 |
April | 0.524810E+09 | 0.361234E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69138.50 | 0.130607E+10 |
May | 0.544247E+09 | 0.376482E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9976.39 | 0.150387E+10 |
June | 0.532585E+09 | 0.367648E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5846714.64 | 0.114408E+10 |
July | 0.536472E+09 | 0.370068E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25572128.27 | 0.954730E+09 |
August | 0.551374E+09 | 0.380758E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3454559.67 | 0.768172E+09 |
September | 0.524810E+09 | 0.361234E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.991380E+09 |
October | 0.537120E+09 | 0.372206E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144555E+10 |
November | 0.518979E+09 | 0.361234E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180464E+10 |
December | 0.536472E+09 | 0.370068E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223927E+10 |
Annual Sum or Average | 0.638324E+10 | 0.441105E+11 | 0.104207E+11 | 34952517.48 | 0.178041E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.337152E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.768172E+09 |
Maximum of Months | 0.551374E+09 | 0.380758E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25572128.27 | 0.223927E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.372206E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205885E+10 |
February | 0.487879E+09 | 0.337152E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182677E+10 |
March | 0.551374E+09 | 0.380758E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175657E+10 |
April | 0.524810E+09 | 0.361234E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69137.40 | 0.128332E+10 |
May | 0.544247E+09 | 0.376482E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9975.07 | 0.147472E+10 |
June | 0.532585E+09 | 0.367648E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5847082.47 | 0.112229E+10 |
July | 0.536472E+09 | 0.370068E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25589310.16 | 0.945907E+09 |
August | 0.551374E+09 | 0.380758E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3454517.29 | 0.765922E+09 |
September | 0.524810E+09 | 0.361234E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.984606E+09 |
October | 0.537120E+09 | 0.372206E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142167E+10 |
November | 0.518979E+09 | 0.361234E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180090E+10 |
December | 0.536472E+09 | 0.370068E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223634E+10 |
Annual Sum or Average | 0.638324E+10 | 0.441105E+11 | 0.104207E+11 | 34970022.39 | 0.176779E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.337152E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765922E+09 |
Maximum of Months | 0.551374E+09 | 0.380758E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25589310.16 | 0.223634E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.183632E+10 | 0.422804E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371358E+10 |
February | 0.167188E+10 | 0.383070E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330849E+10 |
March | 0.189386E+10 | 0.433280E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316770E+10 |
April | 0.180380E+10 | 0.410432E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 124240.47 | 0.222083E+10 |
May | 0.186509E+10 | 0.428042E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17912.09 | 0.256875E+10 |
June | 0.182945E+10 | 0.418290E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10520404.84 | 0.187834E+10 |
July | 0.183943E+10 | 0.420185E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46126791.53 | 0.166065E+10 |
August | 0.189386E+10 | 0.433280E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6213461.93 | 0.139892E+10 |
September | 0.180380E+10 | 0.410432E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170725E+10 |
October | 0.183632E+10 | 0.422804E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245972E+10 |
November | 0.176881E+10 | 0.410432E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327243E+10 |
December | 0.183943E+10 | 0.420185E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406939E+10 |
Annual Sum or Average | 0.218821E+11 | 0.501324E+11 | 0.191729E+11 | 63002810.87 | 0.314261E+11 | ||||
Minimum of Months | 0.167188E+10 | 0.383070E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139892E+10 |
Maximum of Months | 0.189386E+10 | 0.433280E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46126791.53 | 0.406939E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.211402E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206037E+10 |
February | 0.835938E+09 | 0.191535E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182895E+10 |
March | 0.946926E+09 | 0.216640E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175736E+10 |
April | 0.901896E+09 | 0.205216E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69247.25 | 0.123753E+10 |
May | 0.932542E+09 | 0.214021E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9979.39 | 0.141853E+10 |
June | 0.914724E+09 | 0.209145E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5849885.96 | 0.105081E+10 |
July | 0.919713E+09 | 0.210092E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25659902.62 | 0.917679E+09 |
August | 0.946926E+09 | 0.216640E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3454879.08 | 0.765586E+09 |
September | 0.901896E+09 | 0.205216E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.957184E+09 |
October | 0.918158E+09 | 0.211402E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136780E+10 |
November | 0.884402E+09 | 0.205216E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180322E+10 |
December | 0.919713E+09 | 0.210092E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224027E+10 |
Annual Sum or Average | 0.109410E+11 | 0.250662E+11 | 0.958644E+10 | 35043894.30 | 0.174053E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.191535E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765586E+09 |
Maximum of Months | 0.946926E+09 | 0.216640E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25659902.62 | 0.224027E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.211402E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205987E+10 |
February | 0.835938E+09 | 0.191535E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182842E+10 |
March | 0.946926E+09 | 0.216640E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175703E+10 |
April | 0.901896E+09 | 0.205216E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69245.41 | 0.123467E+10 |
May | 0.932542E+09 | 0.214021E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9979.24 | 0.141335E+10 |
June | 0.914724E+09 | 0.209145E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5850062.83 | 0.104266E+10 |
July | 0.919713E+09 | 0.210092E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25665693.72 | 0.913243E+09 |
August | 0.946926E+09 | 0.216640E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3454871.42 | 0.764648E+09 |
September | 0.901896E+09 | 0.205216E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952928E+09 |
October | 0.918158E+09 | 0.211402E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136340E+10 |
November | 0.884402E+09 | 0.205216E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180249E+10 |
December | 0.919713E+09 | 0.210092E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223937E+10 |
Annual Sum or Average | 0.109410E+11 | 0.250662E+11 | 0.958644E+10 | 35049852.62 | 0.173721E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.191535E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.764648E+09 |
Maximum of Months | 0.946926E+09 | 0.216640E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25665693.72 | 0.223937E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.211402E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205848E+10 |
February | 0.835938E+09 | 0.191535E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182625E+10 |
March | 0.946926E+09 | 0.216640E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175592E+10 |
April | 0.901896E+09 | 0.205216E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69239.56 | 0.122733E+10 |
May | 0.932542E+09 | 0.214021E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9978.71 | 0.139765E+10 |
June | 0.914724E+09 | 0.209145E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5850577.80 | 0.101621E+10 |
July | 0.919713E+09 | 0.210092E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25680798.79 | 0.898258E+09 |
August | 0.946926E+09 | 0.216640E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3454828.67 | 0.760767E+09 |
September | 0.901896E+09 | 0.205216E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.934983E+09 |
October | 0.918158E+09 | 0.211402E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135024E+10 |
November | 0.884402E+09 | 0.205216E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179964E+10 |
December | 0.919713E+09 | 0.210092E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223573E+10 |
Annual Sum or Average | 0.109410E+11 | 0.250662E+11 | 0.958644E+10 | 35065423.52 | 0.172615E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.191535E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760767E+09 |
Maximum of Months | 0.946926E+09 | 0.216640E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25680798.79 | 0.223573E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.211402E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218366E+10 |
February | 0.835938E+09 | 0.191535E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201279E+10 |
March | 0.946926E+09 | 0.216640E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186454E+10 |
April | 0.901896E+09 | 0.205216E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69649.72 | 0.133852E+10 |
May | 0.932542E+09 | 0.214021E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10185.33 | 0.170259E+10 |
June | 0.914724E+09 | 0.209145E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6054354.35 | 0.122630E+10 |
July | 0.919713E+09 | 0.210092E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26517987.96 | 0.112402E+10 |
August | 0.946926E+09 | 0.216640E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582880.92 | 0.952165E+09 |
September | 0.901896E+09 | 0.205216E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110963E+10 |
October | 0.918158E+09 | 0.211402E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153076E+10 |
November | 0.884402E+09 | 0.205216E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204910E+10 |
December | 0.919713E+09 | 0.210092E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257298E+10 |
Annual Sum or Average | 0.109410E+11 | 0.250662E+11 | 0.958644E+10 | 36235058.29 | 0.196671E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.191535E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952165E+09 |
Maximum of Months | 0.946926E+09 | 0.216640E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26517987.96 | 0.257298E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2159.72 | 01-JAN-13:09 | 5587.06 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8008.27 | 11-JAN-18:00 |
February | 2159.72 | 03-FEB-13:09 | 5587.06 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6021.79 | 24-FEB-18:00 |
March | 2159.72 | 03-MAR-13:09 | 5587.06 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6220.34 | 15-MAR-12:00 |
April | 2159.72 | 01-APR-12:09 | 5587.06 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.04 | 30-APR-17:00 | 4389.64 | 10-APR-11:10 |
May | 2159.72 | 05-MAY-12:09 | 5587.06 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.20 | 22-MAY-15:00 | 4455.98 | 01-MAY-15:00 |
June | 2159.72 | 02-JUN-12:09 | 5587.06 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 906.33 | 13-JUN-17:00 | 3679.46 | 07-JUN-11:10 |
July | 2159.72 | 01-JUL-12:09 | 5587.06 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1478.40 | 22-JUL-15:00 | 3176.55 | 30-JUL-17:00 |
August | 2159.72 | 04-AUG-12:09 | 5587.06 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 903.90 | 14-AUG-17:00 | 2485.14 | 30-AUG-17:00 |
September | 2159.72 | 01-SEP-12:09 | 5587.06 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 3424.90 | 30-SEP-11:10 |
October | 2159.72 | 01-OCT-12:09 | 5587.06 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 3956.18 | 27-OCT-17:00 |
November | 2159.72 | 03-NOV-12:09 | 5587.06 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6540.14 | 28-NOV-18:00 |
December | 2159.72 | 01-DEC-13:09 | 5587.06 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7439.34 | 29-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2159.72 | 5587.06 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2485.14 | |||||
Maximum of Months | 2159.72 | 5587.06 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1478.40 | 8008.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 01-JAN-13:09 | 3268.27 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4432.44 | 11-JAN-18:00 |
February | 1079.86 | 03-FEB-13:09 | 3268.27 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.94 | 24-FEB-18:00 |
March | 1079.86 | 03-MAR-13:09 | 3268.27 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.27 | 15-MAR-12:00 |
April | 1079.86 | 01-APR-12:09 | 3268.27 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.60 | 30-APR-17:00 | 2416.47 | 10-APR-11:10 |
May | 1079.86 | 05-MAY-12:09 | 3268.27 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.64 | 22-MAY-15:00 | 2575.05 | 01-MAY-15:00 |
June | 1079.86 | 02-JUN-12:09 | 3268.27 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.66 | 13-JUN-17:00 | 2206.04 | 07-JUN-11:10 |
July | 1079.86 | 01-JUL-12:09 | 3268.27 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.85 | 22-JUL-15:00 | 1942.89 | 04-JUL-14:00 |
August | 1079.86 | 04-AUG-12:09 | 3268.27 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 14-AUG-17:00 | 1344.49 | 30-AUG-17:00 |
September | 1079.86 | 01-SEP-12:09 | 3268.27 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1977.70 | 30-SEP-11:10 |
October | 1079.86 | 01-OCT-12:09 | 3268.27 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 2189.68 | 27-OCT-17:00 |
November | 1079.86 | 03-NOV-12:09 | 3268.27 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3591.16 | 28-NOV-18:00 |
December | 1079.86 | 01-DEC-13:09 | 3268.27 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.99 | 29-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3268.27 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.49 | |||||
Maximum of Months | 1079.86 | 3268.27 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 811.85 | 4432.44 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3006.97 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4432.44 | 11-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 3006.97 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.92 | 24-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3006.97 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.28 | 15-MAR-12:00 |
April | 1079.86 | 01-APR-12:09 | 3006.97 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.52 | 30-APR-15:00 | 2416.48 | 10-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 3006.97 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 | 22-MAY-15:00 | 2586.02 | 01-MAY-15:00 |
June | 1079.86 | 03-JUN-12:09 | 3006.97 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.64 | 13-JUN-17:00 | 2220.92 | 07-JUN-11:10 |
July | 1079.86 | 01-JUL-12:09 | 3006.97 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.85 | 22-JUL-15:00 | 1936.13 | 04-JUL-14:00 |
August | 1079.86 | 05-AUG-12:09 | 3006.97 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.45 | 14-AUG-17:00 | 1344.43 | 30-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 3006.97 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1983.51 | 30-SEP-11:10 |
October | 1079.86 | 07-OCT-12:09 | 3006.97 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 2189.67 | 27-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 3006.97 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3591.16 | 28-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3006.97 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.99 | 29-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3006.97 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.43 | |||||
Maximum of Months | 1079.86 | 3006.97 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 811.85 | 4432.44 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3006.97 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4432.44 | 11-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 3006.97 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.91 | 24-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3006.97 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.28 | 15-MAR-12:00 |
April | 1079.86 | 01-APR-12:09 | 3006.97 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.52 | 30-APR-15:00 | 2416.48 | 10-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 3006.97 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 | 22-MAY-15:00 | 2575.83 | 01-MAY-15:00 |
June | 1079.86 | 03-JUN-12:09 | 3006.97 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.64 | 13-JUN-17:00 | 2191.28 | 07-JUN-11:10 |
July | 1079.86 | 01-JUL-12:09 | 3006.97 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.85 | 22-JUL-15:00 | 1912.89 | 04-JUL-14:00 |
August | 1079.86 | 05-AUG-12:09 | 3006.97 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.45 | 14-AUG-17:00 | 1344.43 | 30-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 3006.97 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1980.90 | 30-SEP-11:10 |
October | 1079.86 | 07-OCT-12:09 | 3006.97 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 2189.67 | 27-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 3006.97 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3591.16 | 28-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3006.97 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.99 | 29-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3006.97 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.43 | |||||
Maximum of Months | 1079.86 | 3006.97 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 811.85 | 4432.44 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3006.97 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4432.44 | 11-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 3006.97 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.92 | 24-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3006.97 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.28 | 15-MAR-12:00 |
April | 1079.86 | 01-APR-12:09 | 3006.97 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.52 | 30-APR-15:00 | 2416.48 | 10-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 3006.97 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 | 22-MAY-15:00 | 2535.73 | 01-MAY-15:00 |
June | 1079.86 | 03-JUN-12:09 | 3006.97 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.63 | 13-JUN-17:00 | 2111.04 | 07-JUN-11:10 |
July | 1079.86 | 01-JUL-12:09 | 3006.97 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.85 | 22-JUL-15:00 | 1846.48 | 04-JUL-14:00 |
August | 1079.86 | 05-AUG-12:09 | 3006.97 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.45 | 14-AUG-17:00 | 1344.43 | 30-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 3006.97 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1971.11 | 30-SEP-11:10 |
October | 1079.86 | 07-OCT-12:09 | 3006.97 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 2189.67 | 27-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 3006.97 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3591.16 | 28-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3006.97 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.99 | 29-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3006.97 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.43 | |||||
Maximum of Months | 1079.86 | 3006.97 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 811.85 | 4432.44 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2879.63 | 07-JAN-15:09 | 3712.57 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 7954.69 | 11-JAN-18:00 |
February | 2879.63 | 04-FEB-15:09 | 3712.57 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5965.67 | 24-FEB-18:00 |
March | 2879.63 | 04-MAR-15:09 | 3712.57 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6220.31 | 15-MAR-12:00 |
April | 2879.63 | 01-APR-14:09 | 3712.57 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.72 | 30-APR-15:00 | 4339.63 | 10-APR-11:10 |
May | 2879.63 | 06-MAY-14:09 | 3712.57 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.85 | 22-MAY-15:00 | 4269.82 | 01-MAY-15:00 |
June | 2879.63 | 03-JUN-14:09 | 3712.57 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 894.05 | 13-JUN-17:00 | 3608.61 | 07-JUN-11:10 |
July | 2879.63 | 01-JUL-14:09 | 3712.57 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1458.45 | 22-JUL-15:00 | 2886.97 | 04-JUL-14:00 |
August | 2879.63 | 05-AUG-14:09 | 3712.57 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 893.52 | 14-AUG-17:00 | 2419.63 | 30-AUG-17:00 |
September | 2879.63 | 02-SEP-14:09 | 3712.57 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 3318.21 | 30-SEP-11:10 |
October | 2879.63 | 07-OCT-14:09 | 3712.57 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 3929.71 | 27-OCT-17:00 |
November | 2879.63 | 04-NOV-14:09 | 3712.57 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6451.20 | 28-NOV-18:00 |
December | 2879.63 | 02-DEC-15:09 | 3712.57 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7354.05 | 29-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2879.63 | 3712.57 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2419.63 | |||||
Maximum of Months | 2879.63 | 3712.57 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1458.45 | 7954.69 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 1856.29 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4432.43 | 11-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 1856.29 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.90 | 24-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 1856.29 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.27 | 15-MAR-12:00 |
April | 1439.81 | 01-APR-14:09 | 1856.29 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 | 30-APR-15:00 | 2416.48 | 10-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 1856.29 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 | 22-MAY-15:00 | 2420.68 | 01-MAY-15:00 |
June | 1439.81 | 03-JUN-14:09 | 1856.29 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.65 | 13-JUN-17:00 | 2007.14 | 07-JUN-11:10 |
July | 1439.81 | 01-JUL-14:09 | 1856.29 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.87 | 22-JUL-15:00 | 1653.00 | 04-JUL-14:00 |
August | 1439.81 | 05-AUG-14:09 | 1856.29 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 14-AUG-17:00 | 1344.46 | 30-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 1856.29 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1909.51 | 30-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 1856.29 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 2189.67 | 27-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 1856.29 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3591.15 | 28-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 1856.29 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.97 | 29-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.46 | |||||
Maximum of Months | 1439.81 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 811.87 | 4432.43 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 1856.29 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4432.43 | 11-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 1856.29 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.90 | 24-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 1856.29 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.26 | 15-MAR-12:00 |
April | 1439.81 | 01-APR-14:09 | 1856.29 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 | 30-APR-15:00 | 2416.48 | 10-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 1856.29 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 | 22-MAY-15:00 | 2408.11 | 01-MAY-15:00 |
June | 1439.81 | 03-JUN-14:09 | 1856.29 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.65 | 13-JUN-17:00 | 2007.14 | 07-JUN-11:10 |
July | 1439.81 | 01-JUL-14:09 | 1856.29 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.87 | 22-JUL-15:00 | 1635.14 | 04-JUL-14:00 |
August | 1439.81 | 05-AUG-14:09 | 1856.29 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 14-AUG-17:00 | 1344.46 | 30-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 1856.29 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1900.06 | 30-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 1856.29 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 2189.67 | 27-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 1856.29 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3591.15 | 28-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 1856.29 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.97 | 29-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.46 | |||||
Maximum of Months | 1439.81 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 811.87 | 4432.43 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 1856.29 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4432.42 | 11-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 1856.29 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.90 | 24-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 1856.29 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.27 | 15-MAR-12:00 |
April | 1439.81 | 01-APR-14:09 | 1856.29 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.55 | 30-APR-15:00 | 2416.48 | 10-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 1856.29 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 | 22-MAY-15:00 | 2368.46 | 01-MAY-15:00 |
June | 1439.81 | 03-JUN-14:09 | 1856.29 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.64 | 13-JUN-17:00 | 2007.14 | 07-JUN-11:10 |
July | 1439.81 | 01-JUL-14:09 | 1856.29 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.87 | 22-JUL-15:00 | 1603.70 | 27-JUL-11:10 |
August | 1439.81 | 05-AUG-14:09 | 1856.29 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 14-AUG-17:00 | 1344.46 | 30-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 1856.29 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1857.02 | 30-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 1856.29 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 2189.67 | 27-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 1856.29 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3591.15 | 28-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 1856.29 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.97 | 29-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.46 | |||||
Maximum of Months | 1439.81 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 811.87 | 4432.42 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 1856.29 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4485.93 | 11-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 1856.29 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3378.86 | 24-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 1856.29 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.27 | 15-MAR-12:00 |
April | 1439.81 | 01-APR-14:09 | 1856.29 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.75 | 30-APR-15:00 | 2466.41 | 10-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 1856.29 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.98 | 22-MAY-15:00 | 2486.03 | 01-MAY-13:00 |
June | 1439.81 | 03-JUN-14:09 | 1856.29 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 509.95 | 13-JUN-17:00 | 2077.88 | 07-JUN-11:10 |
July | 1439.81 | 01-JUL-14:09 | 1856.29 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 831.95 | 22-JUL-15:00 | 1581.27 | 27-JUL-11:10 |
August | 1439.81 | 05-AUG-14:09 | 1856.29 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 507.81 | 14-AUG-17:00 | 1407.44 | 30-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 1856.29 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1825.80 | 30-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 1856.29 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 2216.10 | 27-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 1856.29 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3679.95 | 28-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 1856.29 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4180.13 | 29-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1407.44 | |||||
Maximum of Months | 1439.81 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 831.95 | 4485.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9817.02 | 12-JAN-11:32 | 1439.81 | 22348.22 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 992.06 |
February | 10023.11 | 18-FEB-00:03 | 719.91 | 11762.22 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.83 |
March | 8642.95 | 03-MAR-00:03 | 539.93 | 8821.67 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8286.79 | 30-APR-16:25 | 4319.44 | 11174.11 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 29.71 | 0.00 |
May | 7057.02 | 06-MAY-24:00 | 179.98 | 2940.56 | 746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9590.05 | 13-JUN-17:00 | 1799.77 | 5587.06 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 906.33 | 0.00 |
July | 19907.06 | 23-JUL-07:03 | 719.91 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.23 |
August | 12850.45 | 06-AUG-07:02 | 1079.86 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.72 |
September | 8563.50 | 13-SEP-14:00 | 1439.81 | 5587.06 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.12 |
October | 7630.27 | 05-OCT-20:00 | 1079.86 | 5587.06 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.01 |
November | 7482.92 | 03-NOV-23:13 | 539.93 | 8821.67 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.92 |
December | 10757.12 | 30-DEC-00:03 | 719.91 | 11762.22 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.77 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7057.02 | 179.98 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19907.06 | 4319.44 | 22348.22 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 906.33 | 992.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3925.87 | 22-JAN-09:01 | 899.88 | 17201.43 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 458.76 |
February | 3638.94 | 12-FEB-09:01 | 899.88 | 17201.43 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.61 |
March | 3423.41 | 12-MAR-08:61 | 899.88 | 17201.43 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.15 |
April | 4886.95 | 30-APR-15:00 | 719.90 | 3268.27 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 | 0.00 |
May | 4068.18 | 28-MAY-17:10 | 2159.71 | 6536.54 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.53 |
June | 9319.00 | 25-JUN-07:02 | 449.94 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.40 |
July | 12007.75 | 23-JUL-07:03 | 359.95 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.59 |
August | 12231.48 | 06-AUG-07:02 | 539.93 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.08 |
September | 6924.82 | 13-SEP-07:03 | 359.95 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.99 |
October | 4174.47 | 05-OCT-20:10 | 1619.78 | 9804.81 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.21 |
November | 3419.17 | 05-NOV-08:61 | 809.89 | 15481.28 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468.60 |
December | 3644.93 | 17-DEC-09:01 | 899.88 | 17201.43 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.88 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3419.17 | 359.95 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12231.48 | 2159.71 | 17201.43 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 | 468.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3975.80 | 09-JAN-09:43 | 539.93 | 9020.92 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 529.28 |
February | 3721.47 | 25-FEB-08:61 | 809.89 | 337.50 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.97 |
March | 3710.74 | 21-MAR-07:01 | 719.90 | 300.00 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.28 |
April | 4530.05 | 30-APR-14:00 | 539.93 | 3006.97 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.05 |
May | 3665.60 | 23-MAY-17:10 | 899.88 | 3006.97 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.86 |
June | 11191.71 | 27-JUN-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 |
July | 16263.07 | 24-JUL-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.26 |
August | 12268.28 | 06-AUG-07:02 | 0.00 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.04 |
September | 12379.40 | 02-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.43 |
October | 3492.76 | 12-OCT-07:03 | 359.95 | 150.00 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479.43 |
November | 3728.03 | 04-NOV-07:01 | 719.90 | 300.00 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495.59 |
December | 3513.82 | 09-DEC-08:61 | 809.89 | 337.50 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.74 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3492.76 | 0.00 | 150.00 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.43 | |
Maximum of Months | 16263.07 | 899.88 | 9020.92 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 529.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3500.59 | 20-JAN-08:61 | 719.90 | 300.00 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.41 |
February | 3277.40 | 23-FEB-08:61 | 809.89 | 337.50 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.06 |
March | 3663.42 | 21-MAR-07:01 | 719.90 | 300.00 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.23 |
April | 4419.59 | 30-APR-14:00 | 539.93 | 3006.97 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.05 |
May | 3519.67 | 23-MAY-17:10 | 899.88 | 3006.97 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.86 |
June | 10421.02 | 27-JUN-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.82 |
July | 16096.20 | 24-JUL-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.25 |
August | 10937.87 | 06-AUG-07:02 | 0.00 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.95 |
September | 11250.60 | 02-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.43 |
October | 3441.05 | 12-OCT-07:03 | 359.95 | 150.00 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.19 |
November | 3693.89 | 04-NOV-07:01 | 719.90 | 300.00 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.48 |
December | 3734.68 | 30-DEC-18:33 | 269.96 | 4747.86 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.28 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3277.40 | 0.00 | 150.00 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.43 | |
Maximum of Months | 16096.20 | 899.88 | 4747.86 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3300.64 | 04-JAN-10:33 | 539.93 | 9020.92 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.10 |
February | 2955.72 | 10-FEB-08:61 | 719.90 | 300.00 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.29 |
March | 2993.68 | 29-MAR-07:01 | 719.90 | 300.00 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.05 |
April | 4134.32 | 30-APR-15:00 | 359.95 | 3006.97 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 16.52 | 0.00 |
May | 3214.61 | 23-MAY-17:10 | 899.88 | 3006.97 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.86 |
June | 7818.36 | 27-JUN-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.80 |
July | 13898.16 | 23-JUL-07:03 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.12 |
August | 8025.53 | 19-AUG-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.68 |
September | 8108.54 | 02-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.43 |
October | 3330.92 | 12-OCT-07:03 | 359.95 | 150.00 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.56 |
November | 3265.45 | 04-NOV-07:01 | 719.90 | 300.00 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.44 |
December | 1773.37 | 08-DEC-12:00 | 179.98 | 3006.97 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.60 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1773.37 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13898.16 | 899.88 | 9020.92 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.52 | 487.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8813.66 | 02-JAN-20:12 | 1583.79 | 7815.94 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.45 |
February | 6991.91 | 11-FEB-18:57 | 1187.85 | 5861.95 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 626.61 |
March | 5008.35 | 21-MAR-16:15 | 5111.34 | 7425.14 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3611.52 |
April | 6562.88 | 30-APR-15:00 | 2483.68 | 3712.57 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 29.72 | 0.00 |
May | 6610.38 | 01-MAY-08:63 | 1187.85 | 225.00 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 709.87 |
June | 7501.21 | 13-JUN-17:00 | 2555.67 | 3712.57 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 894.05 | 0.00 |
July | 17853.10 | 23-JUL-08:63 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.03 |
August | 7875.61 | 14-AUG-17:00 | 2555.67 | 3712.57 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 893.52 | 0.00 |
September | 7474.68 | 13-SEP-14:10 | 2483.68 | 3712.57 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.94 |
October | 6904.42 | 03-OCT-19:00 | 935.88 | 3712.57 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.68 |
November | 5587.57 | 21-NOV-10:23 | 1187.85 | 11137.71 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 533.11 |
December | 9993.53 | 26-DEC-19:03 | 3743.51 | 14850.28 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 899.41 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5008.35 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17853.10 | 5111.34 | 14850.28 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.05 | 3611.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4523.96 | 10-JAN-11:02 | 3095.59 | 7425.14 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 572.36 |
February | 3573.09 | 15-FEB-20:53 | 593.92 | 2930.98 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2347.74 | 08-MAR-10:15 | 395.95 | 3712.57 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307.13 |
April | 3371.07 | 30-APR-15:00 | 1241.83 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 | 0.00 |
May | 2747.61 | 01-MAY-08:63 | 593.92 | 112.50 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.99 |
June | 3844.44 | 13-JUN-17:00 | 1277.83 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 497.65 | 0.00 |
July | 8194.12 | 23-JUL-08:63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.20 |
August | 4080.07 | 14-AUG-17:00 | 1277.83 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 0.00 |
September | 3822.13 | 13-SEP-14:10 | 1241.83 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.33 |
October | 3073.93 | 05-OCT-20:00 | 197.97 | 976.99 | 373.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.61 |
November | 3795.60 | 27-NOV-20:53 | 593.92 | 2930.98 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.17 |
December | 4328.93 | 26-DEC-18:53 | 2447.67 | 7425.14 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.67 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2347.74 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8194.12 | 3095.59 | 7425.14 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 497.65 | 572.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3358.75 | 13-JAN-20:33 | 593.92 | 2930.98 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3662.52 | 15-FEB-20:33 | 593.92 | 2930.98 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3356.36 | 11-MAR-18:43 | 593.92 | 2930.98 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.30 |
April | 3275.46 | 30-APR-15:00 | 1241.83 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 | 0.00 |
May | 2738.57 | 01-MAY-08:63 | 593.92 | 112.50 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.45 |
June | 3750.21 | 13-JUN-17:00 | 1277.83 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 497.65 | 0.00 |
July | 7677.64 | 23-JUL-08:63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.08 |
August | 4010.48 | 14-AUG-17:00 | 1277.83 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 0.00 |
September | 3748.55 | 13-SEP-14:20 | 1241.83 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.33 |
October | 3007.26 | 05-OCT-19:50 | 197.97 | 976.99 | 373.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.47 |
November | 3809.52 | 27-NOV-20:33 | 593.92 | 2930.98 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.91 |
December | 3999.99 | 18-DEC-19:03 | 1403.81 | 5568.86 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2738.57 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7677.64 | 1403.81 | 5568.86 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 497.65 | 473.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3404.97 | 05-JAN-18:53 | 1835.76 | 5568.86 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.71 |
February | 3607.70 | 15-FEB-19:33 | 1403.81 | 5568.86 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.98 |
March | 3831.51 | 02-MAR-20:53 | 593.92 | 2930.98 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3029.28 | 30-APR-15:00 | 1241.83 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 16.55 | 0.00 |
May | 2680.77 | 01-MAY-08:63 | 593.92 | 112.50 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.54 |
June | 3535.27 | 13-JUN-17:00 | 1277.83 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 497.64 | 0.00 |
July | 6024.32 | 23-JUL-08:63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.73 |
August | 3824.71 | 14-AUG-17:00 | 1277.83 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 0.00 |
September | 3575.51 | 13-SEP-14:20 | 1241.83 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.33 |
October | 2917.44 | 03-OCT-19:00 | 467.94 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.16 |
November | 2383.39 | 25-NOV-18:55 | 395.95 | 1953.98 | 746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.33 |
December | 3148.73 | 12-DEC-19:53 | 1403.81 | 5568.86 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.37 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2383.39 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6024.32 | 1835.76 | 5568.86 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 497.64 | 426.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2774.06 | 06-JAN-11:15 | 1547.79 | 3712.57 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.11 |
February | 3278.02 | 09-FEB-18:23 | 1835.76 | 5568.86 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 441.59 |
March | 2394.97 | 16-MAR-17:05 | 1223.84 | 3712.57 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.74 |
April | 2693.17 | 30-APR-15:00 | 1241.83 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 16.75 | 0.00 |
May | 2431.72 | 01-MAY-08:63 | 593.92 | 112.50 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.02 |
June | 3290.90 | 13-JUN-17:00 | 1277.83 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 509.95 | 0.00 |
July | 4737.49 | 22-JUL-15:00 | 1439.81 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 831.95 | 0.00 |
August | 3519.97 | 14-AUG-17:00 | 1277.83 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 507.81 | 0.00 |
September | 3333.70 | 13-SEP-14:10 | 1241.83 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.53 |
October | 2528.24 | 03-OCT-18:40 | 467.94 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.93 |
November | 2717.02 | 28-NOV-11:35 | 1547.79 | 3712.57 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.53 |
December | 367.61 | 06-DEC-12:00 | 773.90 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.43 |
Annual Sum or Average | |||||||||||
Minimum of Months | 367.61 | 467.94 | 112.50 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4737.49 | 1835.76 | 5568.86 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 831.95 | 441.59 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.746433E+11 | 61582.29 | 03-JAN-17:10 | 0.723562E+11 | 126660.40 | 11-JAN-17:00 |
February | 0.667939E+11 | 61299.84 | 01-FEB-18:19 | 0.591868E+11 | 97585.98 | 17-FEB-08:09 |
March | 0.737276E+11 | 59120.38 | 21-MAR-18:49 | 0.541567E+11 | 100041.20 | 15-MAR-11:00 |
April | 0.696909E+11 | 62534.42 | 30-APR-14:20 | 0.139650E+11 | 57430.43 | 10-APR-11:09 |
May | 0.713934E+11 | 60279.67 | 22-MAY-14:39 | 0.951943E+10 | 38814.45 | 06-MAY-07:10 |
June | 0.708641E+11 | 67896.38 | 13-JUN-16:00 | 0.527618E+09 | 20828.10 | 07-JUN-11:09 |
July | 0.739042E+11 | 71471.06 | 22-JUL-16:49 | 34984416.65 | 4687.31 | 05-JUL-08:30 |
August | 0.764107E+11 | 67533.37 | 14-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.722800E+11 | 64346.89 | 13-SEP-13:00 | 29465167.26 | 3800.43 | 08-SEP-08:00 |
October | 0.730733E+11 | 61059.32 | 04-OCT-18:30 | 0.148888E+11 | 50085.22 | 23-OCT-07:10 |
November | 0.718401E+11 | 63349.29 | 10-NOV-18:40 | 0.463347E+11 | 94585.91 | 19-NOV-17:00 |
December | 0.747312E+11 | 61377.88 | 08-DEC-18:00 | 0.780913E+11 | 117544.04 | 29-DEC-16:00 |
Annual Sum or Average | 0.869353E+12 | 0.349091E+12 | ||||
Minimum of Months | 0.667939E+11 | 59120.38 | 0.00 | 0.00 | ||
Maximum of Months | 0.764107E+11 | 71471.06 | 0.780913E+11 | 126660.40 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.381118E+11 | 0.710881E+10 | 0.108325E+11 | 0.00 | 0.129918E+11 | 0.00 | 0.00 | 2827.64 | 0.00 | 0.00 | 0.00 | 0.559844E+10 | 0.00 |
February | 0.345095E+11 | 0.566910E+10 | 0.980803E+10 | 0.00 | 0.117301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507714E+10 | 0.00 |
March | 0.387104E+11 | 0.524511E+10 | 0.110038E+11 | 0.00 | 0.131207E+11 | 0.00 | 0.00 | 1738229.08 | 0.00 | 0.00 | 0.00 | 0.564588E+10 | 0.00 |
April | 0.369865E+11 | 0.403370E+10 | 0.105115E+11 | 0.00 | 0.123184E+11 | 0.00 | 0.00 | 0.456337E+09 | 0.00 | 0.00 | 0.00 | 0.538446E+10 | 0.00 |
May | 0.383972E+11 | 0.338237E+10 | 0.109147E+11 | 0.00 | 0.127896E+11 | 0.00 | 0.00 | 0.380593E+09 | 0.00 | 0.00 | 0.00 | 0.552892E+10 | 0.00 |
June | 0.374142E+11 | 0.289405E+10 | 0.106349E+11 | 0.00 | 0.124878E+11 | 0.00 | 0.00 | 0.213374E+10 | 0.00 | 0.00 | 0.00 | 0.529932E+10 | 0.00 |
July | 0.379970E+11 | 0.312235E+10 | 0.107982E+11 | 0.00 | 0.126826E+11 | 0.00 | 0.00 | 0.391120E+10 | 0.00 | 0.00 | 0.00 | 0.539282E+10 | 0.00 |
August | 0.386827E+11 | 0.377016E+10 | 0.109970E+11 | 0.00 | 0.129569E+11 | 0.00 | 0.00 | 0.458061E+10 | 0.00 | 0.00 | 0.00 | 0.542341E+10 | 0.00 |
September | 0.370138E+11 | 0.462327E+10 | 0.105184E+11 | 0.00 | 0.123319E+11 | 0.00 | 0.00 | 0.255610E+10 | 0.00 | 0.00 | 0.00 | 0.523656E+10 | 0.00 |
October | 0.381120E+11 | 0.584778E+10 | 0.108325E+11 | 0.00 | 0.126911E+11 | 0.00 | 0.00 | 0.119080E+09 | 0.00 | 0.00 | 0.00 | 0.547083E+10 | 0.00 |
November | 0.369307E+11 | 0.659506E+10 | 0.104978E+11 | 0.00 | 0.124627E+11 | 0.00 | 0.00 | 2029451.30 | 0.00 | 0.00 | 0.00 | 0.535178E+10 | 0.00 |
December | 0.380245E+11 | 0.736102E+10 | 0.108050E+11 | 0.00 | 0.129720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556867E+10 | 0.00 |
Annual Sum or Average | 0.450890E+12 | 0.596528E+11 | 0.128154E+12 | 0.151536E+12 | 0.00 | 0.141414E+11 | 0.649782E+11 | ||||||
Minimum of Months | 0.345095E+11 | 0.289405E+10 | 0.980803E+10 | 0.00 | 0.117301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507714E+10 | 0.00 |
Maximum of Months | 0.387104E+11 | 0.736102E+10 | 0.110038E+11 | 0.00 | 0.131207E+11 | 0.00 | 0.00 | 0.458061E+10 | 0.00 | 0.00 | 0.00 | 0.564588E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.723562E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.591868E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.541567E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.139650E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.951943E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.527618E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 34984416.65 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 29465167.26 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.148888E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.463347E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.780913E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.349091E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.780913E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 29013.96 | 01-JAN-11:09 | 5459.01 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 9580.65 | 11-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 29013.96 | 01-FEB-10:09 | 5459.01 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 9375.83 | 17-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 29013.96 | 01-MAR-10:09 | 5459.01 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 9436.86 | 15-MAR-11:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 29013.96 | 01-APR-09:09 | 5459.01 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 9219.78 | 01-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 29013.96 | 01-MAY-09:09 | 5459.01 | 01-MAY-19:19 | 8059.50 | 01-MAY-09:09 | 0.00 | 9122.00 | 05-MAY-08:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 29013.96 | 01-JUN-09:09 | 5459.01 | 01-JUN-19:00 | 8059.50 | 01-JUN-09:09 | 0.00 | 9014.69 | 07-JUN-11:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 29013.96 | 01-JUL-09:09 | 5459.01 | 01-JUL-20:19 | 8059.50 | 01-JUL-09:09 | 0.00 | 9077.92 | 22-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 29013.96 | 01-AUG-09:09 | 5459.01 | 01-AUG-19:49 | 8059.50 | 01-AUG-09:09 | 0.00 | 8860.78 | 01-AUG-11:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 29013.96 | 01-SEP-09:09 | 5459.01 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 8882.66 | 08-SEP-08:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 29013.96 | 01-OCT-10:09 | 5459.01 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 9155.61 | 23-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 29013.96 | 01-NOV-09:09 | 5459.01 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 9397.35 | 28-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 29013.96 | 01-DEC-10:09 | 5459.01 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 9533.43 | 29-DEC-16:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 29013.96 | 5459.01 | 8059.50 | 0.00 | 8860.78 | 0.00 | 0.00 | |||||
Maximum of Months | 29013.96 | 5459.01 | 8059.50 | 0.00 | 9580.65 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 4.71 | 29-JAN-21:00 | 0.00 | 0.00 | 0.00 | 11859.72 | 12-JAN-13:50 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 10962.66 | 01-FEB-12:39 | 0.00 |
March | 89.81 | 19-MAR-19:19 | 0.00 | 0.00 | 0.00 | 9730.43 | 16-MAR-12:39 | 0.00 |
April | 12061.07 | 30-APR-14:00 | 0.00 | 0.00 | 0.00 | 10200.23 | 01-APR-17:00 | 0.00 |
May | 9434.28 | 22-MAY-14:00 | 0.00 | 0.00 | 0.00 | 10156.72 | 19-MAY-13:20 | 0.00 |
June | 16490.55 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | 9945.07 | 12-JUN-12:00 | 0.00 |
July | 19389.65 | 22-JUL-14:00 | 0.00 | 0.00 | 0.00 | 9708.24 | 01-JUL-13:30 | 0.00 |
August | 15898.24 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 | 9674.60 | 09-AUG-16:40 | 0.00 |
September | 13016.54 | 13-SEP-14:09 | 0.00 | 0.00 | 0.00 | 9707.12 | 23-SEP-13:50 | 0.00 |
October | 1384.34 | 07-OCT-14:00 | 0.00 | 0.00 | 0.00 | 9713.88 | 02-OCT-12:00 | 0.00 |
November | 98.92 | 08-NOV-22:00 | 0.00 | 0.00 | 0.00 | 11796.92 | 10-NOV-18:40 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 10179.88 | 14-DEC-09:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9674.60 | 0.00 | ||
Maximum of Months | 19389.65 | 0.00 | 0.00 | 0.00 | 11859.72 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 61582.29 | 03-JAN-17:10 | 29013.96 | 8059.50 | 5459.01 | 0.00 | 9363.08 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 61299.84 | 01-FEB-18:19 | 29013.96 | 8059.50 | 5459.01 | 0.00 | 9079.80 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 59120.38 | 21-MAR-18:49 | 29013.96 | 8059.50 | 5459.01 | 0.00 | 9026.70 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 62534.42 | 30-APR-14:20 | 29013.96 | 8059.50 | 0.00 | 0.00 | 8860.78 | 0.00 | 0.00 | 11170.53 | 0.00 |
May | 60279.67 | 22-MAY-14:39 | 29013.96 | 8059.50 | 0.00 | 0.00 | 8860.78 | 0.00 | 0.00 | 8896.65 | 0.00 |
June | 67896.38 | 13-JUN-16:00 | 29013.96 | 8059.50 | 0.00 | 0.00 | 8890.20 | 0.00 | 0.00 | 16490.55 | 0.00 |
July | 71471.06 | 22-JUL-16:49 | 29013.96 | 8059.50 | 0.00 | 0.00 | 9061.00 | 0.00 | 0.00 | 19034.43 | 0.00 |
August | 67533.37 | 14-AUG-14:00 | 29013.96 | 8059.50 | 0.00 | 0.00 | 8860.78 | 0.00 | 0.00 | 14220.93 | 0.00 |
September | 64346.89 | 13-SEP-13:00 | 29013.96 | 8059.50 | 0.00 | 0.00 | 8860.78 | 0.00 | 0.00 | 12953.34 | 0.00 |
October | 61059.32 | 04-OCT-18:30 | 29013.96 | 8059.50 | 5459.01 | 0.00 | 8860.78 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 63349.29 | 10-NOV-18:40 | 29013.96 | 8059.50 | 5459.01 | 0.00 | 9019.90 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 61377.88 | 08-DEC-18:00 | 29013.96 | 8059.50 | 5459.01 | 0.00 | 9161.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 59120.38 | 29013.96 | 8059.50 | 0.00 | 0.00 | 8860.78 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 71471.06 | 29013.96 | 8059.50 | 5459.01 | 0.00 | 9363.08 | 0.00 | 0.00 | 19034.43 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 126660.40 | 11-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 97585.98 | 17-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 100041.20 | 15-MAR-11:00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 57430.43 | 10-APR-11:09 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 38814.45 | 06-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 20828.10 | 07-JUN-11:09 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 4687.31 | 05-JUL-08:30 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 3800.43 | 08-SEP-08:00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 50085.22 | 23-OCT-07:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 94585.91 | 19-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 117544.04 | 29-DEC-16:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 126660.40 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 20.51 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.00 | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.00 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4.67 | 20.43 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.08 | 68.67 | 20.94 | 68.67 | 20.94 |
February | 448.00 | 21.08 | 36.17 | 20.72 | 36.17 | 20.72 |
March | 496.00 | 21.09 | 37.33 | 20.90 | 37.33 | 20.90 |
April | 444.50 | 21.44 | 6.17 | 20.62 | 6.17 | 20.62 |
May | 442.50 | 21.60 | 14.33 | 23.45 | 1.67 | 20.15 |
June | 269.83 | 22.61 | 86.00 | 23.89 | 0.00 | 0.00 |
July | 120.00 | 22.89 | 243.67 | 23.89 | 0.00 | 0.00 |
August | 55.17 | 23.49 | 295.50 | 23.89 | 0.00 | 0.00 |
September | 171.17 | 22.97 | 132.67 | 23.88 | 0.00 | 0.00 |
October | 493.50 | 21.56 | 0.67 | 20.53 | 0.67 | 20.53 |
November | 480.00 | 21.10 | 18.50 | 20.93 | 18.50 | 20.93 |
December | 496.00 | 21.07 | 68.33 | 20.88 | 68.33 | 20.88 |
Annual Sum or Average | 4412.67 | 21.47 | 1008.00 | 23.18 | 237.50 | 20.87 |
Minimum of Months | 55.17 | 21.07 | 0.67 | 20.53 | 0.00 | 0.00 |
Maximum of Months | 496.00 | 23.49 | 295.50 | 23.89 | 68.67 | 20.94 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.64 | 8.83 | 21.15 | 8.83 | 21.15 |
February | 448.00 | 21.62 | 1.00 | 21.41 | 1.00 | 21.41 |
March | 496.00 | 21.67 | 0.50 | 21.38 | 0.50 | 21.38 |
April | 399.00 | 22.54 | 4.00 | 23.89 | 0.00 | 0.00 |
May | 384.17 | 22.71 | 35.83 | 23.89 | 0.00 | 0.00 |
June | 74.67 | 23.30 | 177.33 | 23.88 | 0.00 | 0.00 |
July | 19.17 | 23.61 | 289.00 | 23.89 | 0.00 | 0.00 |
August | 6.33 | 23.87 | 331.50 | 23.89 | 0.00 | 0.00 |
September | 43.00 | 23.55 | 200.17 | 23.89 | 0.00 | 0.00 |
October | 384.00 | 22.45 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 480.00 | 21.78 | 1.33 | 21.20 | 1.33 | 21.20 |
December | 496.00 | 21.59 | 7.50 | 21.19 | 7.50 | 21.19 |
Annual Sum or Average | 3726.33 | 22.01 | 1057.00 | 23.84 | 19.17 | 21.19 |
Minimum of Months | 6.33 | 21.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.00 | 23.87 | 331.50 | 23.89 | 8.83 | 21.41 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.12 | 22.33 | 21.11 | 22.33 | 21.11 |
February | 336.00 | 21.11 | 7.17 | 21.11 | 7.17 | 21.11 |
March | 379.00 | 21.13 | 6.33 | 21.11 | 6.33 | 21.11 |
April | 305.83 | 21.95 | 3.33 | 24.82 | 0.00 | 0.00 |
May | 302.17 | 22.19 | 32.83 | 23.91 | 0.00 | 0.00 |
June | 73.33 | 23.16 | 147.00 | 23.95 | 0.00 | 0.00 |
July | 25.17 | 23.43 | 234.00 | 23.98 | 0.00 | 0.00 |
August | 13.67 | 23.59 | 266.83 | 23.98 | 0.00 | 0.00 |
September | 43.83 | 23.29 | 153.17 | 23.94 | 0.00 | 0.00 |
October | 300.50 | 21.85 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 360.00 | 21.16 | 3.83 | 21.11 | 3.83 | 21.11 |
December | 369.00 | 21.11 | 21.33 | 21.11 | 21.33 | 21.11 |
Annual Sum or Average | 2879.50 | 21.52 | 898.17 | 23.78 | 61.00 | 21.11 |
Minimum of Months | 13.67 | 21.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 379.00 | 23.59 | 266.83 | 24.82 | 22.33 | 21.11 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 30.00 | 21.11 | 30.00 | 21.11 |
February | 336.00 | 21.11 | 12.67 | 21.11 | 12.67 | 21.11 |
March | 379.00 | 21.12 | 11.17 | 21.11 | 11.17 | 21.11 |
April | 311.67 | 21.85 | 2.83 | 24.80 | 0.17 | 21.11 |
May | 304.17 | 22.06 | 22.50 | 23.92 | 0.00 | 0.00 |
June | 87.17 | 23.12 | 129.50 | 23.95 | 0.00 | 0.00 |
July | 34.83 | 23.39 | 225.00 | 23.98 | 0.00 | 0.00 |
August | 16.00 | 23.57 | 262.83 | 23.98 | 0.00 | 0.00 |
September | 48.67 | 23.27 | 146.33 | 23.94 | 0.00 | 0.00 |
October | 310.00 | 21.78 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 360.00 | 21.15 | 5.33 | 21.11 | 5.33 | 21.11 |
December | 369.00 | 21.11 | 32.33 | 21.11 | 32.33 | 21.11 |
Annual Sum or Average | 2927.50 | 21.50 | 880.50 | 23.67 | 91.67 | 21.11 |
Minimum of Months | 16.00 | 21.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 379.00 | 23.57 | 262.83 | 24.80 | 32.33 | 21.11 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 43.50 | 21.11 | 43.50 | 21.11 |
February | 336.00 | 21.11 | 20.67 | 21.11 | 20.67 | 21.11 |
March | 379.00 | 21.12 | 18.00 | 21.11 | 18.00 | 21.11 |
April | 322.33 | 21.72 | 2.17 | 24.26 | 0.67 | 21.11 |
May | 312.17 | 21.87 | 11.00 | 23.93 | 0.00 | 0.00 |
June | 124.00 | 22.96 | 92.50 | 23.96 | 0.00 | 0.00 |
July | 53.50 | 23.26 | 207.67 | 23.98 | 0.00 | 0.00 |
August | 21.33 | 23.53 | 249.83 | 23.97 | 0.00 | 0.00 |
September | 67.17 | 23.22 | 129.17 | 23.94 | 0.00 | 0.00 |
October | 335.83 | 21.75 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 360.00 | 21.13 | 10.33 | 21.11 | 10.33 | 21.11 |
December | 369.00 | 21.11 | 45.17 | 21.11 | 45.17 | 21.11 |
Annual Sum or Average | 3051.33 | 21.50 | 830.00 | 23.49 | 138.33 | 21.11 |
Minimum of Months | 21.33 | 21.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 379.00 | 23.53 | 249.83 | 24.26 | 45.17 | 21.11 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 90.00 | 21.11 | 90.00 | 21.11 |
February | 308.00 | 21.11 | 32.83 | 21.11 | 32.83 | 21.11 |
March | 348.00 | 21.11 | 37.00 | 21.11 | 37.00 | 21.11 |
April | 311.33 | 21.35 | 3.17 | 21.99 | 2.50 | 21.11 |
May | 324.33 | 21.51 | 3.83 | 23.89 | 0.00 | 0.00 |
June | 239.50 | 22.31 | 34.17 | 23.92 | 0.00 | 0.00 |
July | 106.00 | 22.63 | 131.50 | 23.92 | 0.00 | 0.00 |
August | 43.00 | 23.28 | 187.33 | 23.90 | 0.00 | 0.00 |
September | 170.83 | 22.80 | 68.50 | 23.90 | 0.00 | 0.00 |
October | 340.00 | 21.42 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 330.00 | 21.11 | 17.33 | 21.11 | 17.33 | 21.11 |
December | 338.00 | 21.11 | 95.00 | 21.11 | 95.00 | 21.11 |
Annual Sum or Average | 3199.00 | 21.47 | 700.67 | 22.81 | 274.67 | 21.11 |
Minimum of Months | 43.00 | 21.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.28 | 187.33 | 23.92 | 95.00 | 21.11 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 94.67 | 21.11 | 94.67 | 21.11 |
February | 308.00 | 21.11 | 36.50 | 21.11 | 36.50 | 21.11 |
March | 348.00 | 21.11 | 42.17 | 21.11 | 42.17 | 21.11 |
April | 311.67 | 21.44 | 4.50 | 21.77 | 3.83 | 21.11 |
May | 319.17 | 21.61 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 228.83 | 22.58 | 26.00 | 23.95 | 0.00 | 0.00 |
July | 96.33 | 22.88 | 114.83 | 23.93 | 0.00 | 0.00 |
August | 35.67 | 23.54 | 161.50 | 23.92 | 0.00 | 0.00 |
September | 140.50 | 23.06 | 59.83 | 23.92 | 0.00 | 0.00 |
October | 340.00 | 21.53 | 0.17 | 21.11 | 0.17 | 21.11 |
November | 330.00 | 21.11 | 20.00 | 21.11 | 20.00 | 21.11 |
December | 338.00 | 21.11 | 102.33 | 21.11 | 102.33 | 21.11 |
Annual Sum or Average | 3136.17 | 21.52 | 662.50 | 22.65 | 299.67 | 21.11 |
Minimum of Months | 35.67 | 21.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.54 | 161.50 | 23.95 | 102.33 | 21.11 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 106.83 | 21.11 | 106.83 | 21.11 |
February | 308.00 | 21.11 | 40.67 | 21.11 | 40.67 | 21.11 |
March | 348.00 | 21.11 | 47.33 | 21.11 | 47.33 | 21.11 |
April | 312.83 | 21.43 | 5.00 | 21.70 | 4.33 | 21.11 |
May | 322.67 | 21.60 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 234.50 | 22.53 | 21.33 | 23.95 | 0.00 | 0.00 |
July | 101.83 | 22.84 | 109.83 | 23.93 | 0.00 | 0.00 |
August | 40.00 | 23.53 | 150.83 | 23.92 | 0.00 | 0.00 |
September | 151.33 | 23.05 | 55.33 | 23.92 | 0.00 | 0.00 |
October | 340.00 | 21.50 | 0.17 | 21.11 | 0.17 | 21.11 |
November | 330.00 | 21.11 | 22.83 | 21.11 | 22.83 | 21.11 |
December | 338.00 | 21.11 | 111.83 | 21.11 | 111.83 | 21.11 |
Annual Sum or Average | 3167.17 | 21.52 | 672.00 | 22.53 | 334.00 | 21.11 |
Minimum of Months | 40.00 | 21.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.53 | 150.83 | 23.95 | 111.83 | 21.11 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 123.83 | 21.11 | 123.83 | 21.11 |
February | 308.00 | 21.11 | 53.83 | 21.11 | 53.83 | 21.11 |
March | 348.00 | 21.11 | 64.50 | 21.11 | 64.50 | 21.11 |
April | 316.17 | 21.40 | 8.67 | 21.36 | 8.17 | 21.11 |
May | 329.83 | 21.56 | 0.17 | 21.11 | 0.17 | 21.11 |
June | 254.33 | 22.37 | 15.67 | 23.96 | 0.00 | 0.00 |
July | 120.83 | 22.75 | 94.00 | 23.93 | 0.00 | 0.00 |
August | 52.50 | 23.46 | 126.83 | 23.92 | 0.00 | 0.00 |
September | 185.00 | 22.93 | 45.33 | 23.91 | 0.00 | 0.00 |
October | 340.00 | 21.42 | 0.50 | 21.11 | 0.50 | 21.11 |
November | 330.00 | 21.11 | 33.00 | 21.11 | 33.00 | 21.11 |
December | 338.00 | 21.11 | 140.67 | 21.11 | 140.67 | 21.11 |
Annual Sum or Average | 3262.67 | 21.52 | 707.00 | 22.23 | 424.67 | 21.11 |
Minimum of Months | 52.50 | 21.11 | 0.17 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.46 | 140.67 | 23.96 | 140.67 | 21.11 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 194.67 | 21.11 | 194.67 | 21.11 |
February | 308.00 | 21.11 | 157.33 | 21.11 | 157.33 | 21.11 |
March | 348.00 | 21.11 | 172.33 | 21.11 | 172.33 | 21.11 |
April | 320.50 | 21.38 | 29.00 | 21.11 | 29.00 | 21.11 |
May | 336.67 | 21.48 | 8.33 | 21.11 | 8.33 | 21.11 |
June | 278.00 | 22.10 | 14.17 | 23.88 | 0.33 | 21.11 |
July | 162.00 | 22.63 | 58.83 | 23.95 | 0.00 | 0.00 |
August | 83.83 | 23.26 | 56.50 | 23.93 | 0.00 | 0.00 |
September | 214.50 | 22.65 | 26.00 | 23.91 | 0.00 | 0.00 |
October | 340.00 | 21.31 | 10.67 | 21.11 | 10.67 | 21.11 |
November | 330.00 | 21.11 | 92.33 | 21.11 | 92.33 | 21.11 |
December | 338.00 | 21.11 | 259.67 | 21.11 | 259.67 | 21.11 |
Annual Sum or Average | 3399.50 | 21.50 | 1079.83 | 21.52 | 924.67 | 21.11 |
Minimum of Months | 83.83 | 21.11 | 8.33 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.26 | 259.67 | 23.95 | 259.67 | 21.11 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.08035 | 31.19617 | -0.4397 | 9.22402 |
February | 448.00000 | 21.07417 | 32.21125 | -0.4284 | 8.96649 |
March | 496.00000 | 21.08462 | 32.33625 | -0.4220 | 8.83711 |
April | 480.00000 | 21.62645 | 32.52871 | -0.2258 | 7.20031 |
May | 496.00000 | 21.83607 | 38.57090 | -1.2226 | 38.11924 |
June | 480.00000 | 23.12078 | 44.79780 | -0.7288 | 17.62260 |
July | 496.00000 | 23.61926 | 45.13342 | -0.5425 | 12.00042 |
August | 496.00000 | 23.82893 | 45.06532 | -0.4711 | 9.88078 |
September | 480.00000 | 23.50263 | 42.77164 | -0.6069 | 13.59401 |
October | 496.00000 | 21.57822 | 41.26075 | -0.1921 | 6.45623 |
November | 480.00000 | 21.09470 | 36.49982 | -0.3784 | 8.10621 |
December | 496.00000 | 21.07228 | 30.34250 | -0.4623 | 9.58956 |
Annual Sum or Average | 5840.00000 | 22.04796 | 37.75594 | -0.5110 | 12.50434 |
Minimum of Months | 448.00000 | 21.07228 | 30.34250 | -1.2226 | 6.45623 |
Maximum of Months | 496.00000 | 23.82893 | 45.13342 | -0.1921 | 38.11924 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.61943 | 32.35606 | -0.2928 | 7.35440 |
February | 448.00000 | 21.59856 | 33.23761 | -0.2860 | 7.13717 |
March | 496.00000 | 21.65544 | 33.15615 | -0.2715 | 7.11223 |
April | 480.00000 | 22.75114 | 32.06893 | 0.02334 | 6.13328 |
May | 496.00000 | 22.96111 | 37.18693 | -0.8792 | 22.98011 |
June | 480.00000 | 23.76973 | 43.13669 | -0.5225 | 11.09440 |
July | 496.00000 | 23.86881 | 44.03379 | -0.4564 | 9.51700 |
August | 496.00000 | 23.89048 | 44.22216 | -0.4398 | 9.15038 |
September | 480.00000 | 23.85329 | 41.93967 | -0.4876 | 10.18958 |
October | 496.00000 | 22.74989 | 40.09462 | 0.06484 | 6.12767 |
November | 480.00000 | 21.76477 | 36.83596 | -0.2172 | 6.60482 |
December | 496.00000 | 21.56813 | 31.37711 | -0.3232 | 7.61923 |
Annual Sum or Average | 5840.00000 | 22.67572 | 37.49403 | -0.3415 | 9.27725 |
Minimum of Months | 448.00000 | 21.56813 | 31.37711 | -0.8792 | 6.12767 |
Maximum of Months | 496.00000 | 23.89048 | 44.22216 | 0.06484 | 22.98011 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11957 | 31.18206 | -0.4066 | 8.58805 |
February | 336.00000 | 21.11388 | 32.40852 | -0.3915 | 8.26662 |
March | 379.00000 | 21.13507 | 31.73519 | -0.3880 | 8.22392 |
April | 360.00000 | 22.25479 | 30.74472 | -0.0816 | 6.51981 |
May | 375.00000 | 22.53375 | 36.78373 | -0.9954 | 27.98637 |
June | 366.00000 | 23.73909 | 42.98077 | -0.5304 | 11.44769 |
July | 369.00000 | 23.89333 | 44.59879 | -0.4458 | 9.44693 |
August | 379.00000 | 23.93099 | 45.02150 | -0.4237 | 8.93948 |
September | 360.00000 | 23.83172 | 41.95683 | -0.4916 | 10.44016 |
October | 371.00000 | 22.23683 | 39.64761 | -0.0392 | 6.29479 |
November | 360.00000 | 21.17160 | 36.25035 | -0.3436 | 7.59268 |
December | 369.00000 | 21.11151 | 30.18689 | -0.4301 | 8.93268 |
Annual Sum or Average | 4395.00000 | 22.34764 | 36.99689 | -0.4153 | 10.26390 |
Minimum of Months | 336.00000 | 21.11151 | 30.18689 | -0.9954 | 6.29479 |
Maximum of Months | 379.00000 | 23.93099 | 45.02150 | -0.0392 | 27.98637 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11340 | 31.19597 | -0.4194 | 8.80962 |
February | 336.00000 | 21.11204 | 32.41233 | -0.4024 | 8.45127 |
March | 379.00000 | 21.12575 | 31.75382 | -0.3999 | 8.42002 |
April | 360.00000 | 22.14013 | 30.95578 | -0.1143 | 6.65323 |
May | 375.00000 | 22.41254 | 37.04753 | -1.0418 | 30.06040 |
June | 366.00000 | 23.69754 | 43.09796 | -0.5500 | 11.99566 |
July | 369.00000 | 23.87922 | 44.64793 | -0.4550 | 9.66231 |
August | 379.00000 | 23.92722 | 45.04163 | -0.4282 | 9.02283 |
September | 360.00000 | 23.81825 | 42.01234 | -0.5012 | 10.66927 |
October | 371.00000 | 22.13584 | 39.90708 | -0.0690 | 6.38020 |
November | 360.00000 | 21.15139 | 36.29878 | -0.3585 | 7.80240 |
December | 369.00000 | 21.11051 | 30.18908 | -0.4415 | 9.14514 |
Annual Sum or Average | 4395.00000 | 22.31011 | 37.08598 | -0.4331 | 10.63342 |
Minimum of Months | 336.00000 | 21.11051 | 30.18908 | -1.0418 | 6.38020 |
Maximum of Months | 379.00000 | 23.92722 | 45.04163 | -0.0690 | 30.06040 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11065 | 31.20203 | -0.4335 | 9.06742 |
February | 336.00000 | 21.11037 | 32.41600 | -0.4154 | 8.67900 |
March | 379.00000 | 21.11724 | 31.77082 | -0.4142 | 8.66344 |
April | 360.00000 | 21.95670 | 31.30869 | -0.1652 | 6.84606 |
May | 375.00000 | 22.21434 | 37.49008 | -1.1178 | 33.42929 |
June | 366.00000 | 23.55127 | 43.50898 | -0.6130 | 13.85773 |
July | 369.00000 | 23.82853 | 44.81577 | -0.4843 | 10.39128 |
August | 379.00000 | 23.91545 | 45.10947 | -0.4415 | 9.28197 |
September | 360.00000 | 23.76879 | 42.19509 | -0.5312 | 11.42686 |
October | 371.00000 | 21.95537 | 40.36157 | -0.1202 | 6.43647 |
November | 360.00000 | 21.13372 | 36.34277 | -0.3742 | 8.03444 |
December | 369.00000 | 21.10993 | 30.19055 | -0.4560 | 9.42244 |
Annual Sum or Average | 4395.00000 | 22.23884 | 37.26613 | -0.4654 | 11.34453 |
Minimum of Months | 336.00000 | 21.10993 | 30.19055 | -1.1178 | 6.43647 |
Maximum of Months | 379.00000 | 23.91545 | 45.10947 | -0.1202 | 33.42929 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10951 | 32.15386 | -0.4753 | 9.86176 |
February | 308.00000 | 21.10975 | 33.29122 | -0.4545 | 9.37989 |
March | 348.00000 | 21.10964 | 32.62372 | -0.4545 | 9.38553 |
April | 330.00000 | 21.49843 | 33.04030 | -0.2794 | 7.57601 |
May | 344.00000 | 21.64910 | 39.63610 | -1.3084 | 42.03217 |
June | 336.00000 | 22.74997 | 46.44326 | -0.8661 | 22.65500 |
July | 338.00000 | 23.46605 | 46.46332 | -0.6128 | 14.21140 |
August | 348.00000 | 23.80544 | 45.98471 | -0.4980 | 10.44714 |
September | 330.00000 | 23.29548 | 44.27775 | -0.6871 | 16.06267 |
October | 340.00000 | 21.42588 | 42.47720 | -0.2525 | 6.82628 |
November | 330.00000 | 21.10956 | 37.32658 | -0.4156 | 8.69751 |
December | 338.00000 | 21.10966 | 31.10635 | -0.5026 | 10.35164 |
Annual Sum or Average | 4030.00000 | 21.96037 | 38.77792 | -0.5690 | 14.02211 |
Minimum of Months | 308.00000 | 21.10951 | 31.10635 | -1.3084 | 6.82628 |
Maximum of Months | 348.00000 | 23.80544 | 46.46332 | -0.2525 | 42.03217 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10978 | 32.09578 | -0.4800 | 9.95063 |
February | 308.00000 | 21.10962 | 33.23493 | -0.4604 | 9.49098 |
March | 348.00000 | 21.10958 | 32.57089 | -0.4608 | 9.50633 |
April | 330.00000 | 21.58396 | 32.84431 | -0.2781 | 7.64648 |
May | 344.00000 | 21.77792 | 39.27308 | -1.2967 | 41.61376 |
June | 336.00000 | 22.98832 | 45.70179 | -0.8289 | 21.16316 |
July | 338.00000 | 23.60159 | 45.78118 | -0.6008 | 13.63194 |
August | 348.00000 | 23.86203 | 45.49487 | -0.5041 | 10.49507 |
September | 330.00000 | 23.51978 | 43.58650 | -0.6492 | 14.68315 |
October | 340.00000 | 21.53470 | 42.17894 | -0.2449 | 6.87224 |
November | 330.00000 | 21.11012 | 37.26031 | -0.4221 | 8.80903 |
December | 338.00000 | 21.10959 | 31.04307 | -0.5058 | 10.41916 |
Annual Sum or Average | 4030.00000 | 22.04209 | 38.46329 | -0.5628 | 13.75545 |
Minimum of Months | 308.00000 | 21.10958 | 31.04307 | -1.2967 | 6.87224 |
Maximum of Months | 348.00000 | 23.86203 | 45.78118 | -0.2449 | 41.61376 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10930 | 32.09706 | -0.4850 | 10.05260 |
February | 308.00000 | 21.10980 | 33.23466 | -0.4655 | 9.58994 |
March | 348.00000 | 21.10935 | 32.57114 | -0.4658 | 9.60323 |
April | 330.00000 | 21.56343 | 32.88348 | -0.2865 | 7.72841 |
May | 344.00000 | 21.74721 | 39.34517 | -1.3117 | 42.31388 |
June | 336.00000 | 22.93065 | 45.87339 | -0.8512 | 22.01664 |
July | 338.00000 | 23.57301 | 45.89678 | -0.6141 | 14.07327 |
August | 348.00000 | 23.85588 | 45.56060 | -0.5102 | 10.63748 |
September | 330.00000 | 23.48680 | 43.69358 | -0.6629 | 15.12053 |
October | 340.00000 | 21.50587 | 42.24206 | -0.2550 | 6.93783 |
November | 330.00000 | 21.10979 | 37.26157 | -0.4267 | 8.89224 |
December | 338.00000 | 21.10949 | 31.04362 | -0.5104 | 10.51661 |
Annual Sum or Average | 4030.00000 | 22.02484 | 38.51668 | -0.5722 | 14.02326 |
Minimum of Months | 308.00000 | 21.10930 | 31.04362 | -1.3117 | 6.93783 |
Maximum of Months | 348.00000 | 23.85588 | 45.89678 | -0.2550 | 42.31388 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10967 | 32.09590 | -0.4989 | 10.34345 |
February | 308.00000 | 21.10962 | 33.23520 | -0.4803 | 9.88612 |
March | 348.00000 | 21.10960 | 32.57026 | -0.4798 | 9.88480 |
April | 330.00000 | 21.51219 | 32.98238 | -0.3075 | 7.93879 |
May | 344.00000 | 21.65676 | 39.55837 | -1.3535 | 44.26843 |
June | 336.00000 | 22.74351 | 46.42227 | -0.9195 | 24.71924 |
July | 338.00000 | 23.47608 | 46.27048 | -0.6543 | 15.45636 |
August | 348.00000 | 23.83016 | 45.77979 | -0.5285 | 11.08801 |
September | 330.00000 | 23.34799 | 44.10657 | -0.7151 | 16.88492 |
October | 340.00000 | 21.42460 | 42.41601 | -0.2822 | 7.12691 |
November | 330.00000 | 21.10956 | 37.26314 | -0.4392 | 9.12279 |
December | 338.00000 | 21.10943 | 31.04443 | -0.5238 | 10.80971 |
Annual Sum or Average | 4030.00000 | 21.96876 | 38.68757 | -0.6004 | 14.86295 |
Minimum of Months | 308.00000 | 21.10943 | 31.04443 | -1.3535 | 7.12691 |
Maximum of Months | 348.00000 | 23.83016 | 46.42227 | -0.2822 | 44.26843 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10966 | 32.06504 | -0.5509 | 11.51409 |
February | 308.00000 | 21.10955 | 33.15538 | -0.5353 | 11.07364 |
March | 348.00000 | 21.10964 | 32.50270 | -0.5331 | 11.03284 |
April | 330.00000 | 21.45117 | 33.00532 | -0.3537 | 8.55398 |
May | 344.00000 | 21.52550 | 39.75367 | -1.4403 | 48.55413 |
June | 336.00000 | 22.41403 | 47.22711 | -1.0494 | 30.27900 |
July | 338.00000 | 23.28435 | 46.85988 | -0.7384 | 18.41092 |
August | 348.00000 | 23.73094 | 46.18301 | -0.5858 | 12.67206 |
September | 330.00000 | 23.07673 | 44.67541 | -0.8216 | 20.82183 |
October | 340.00000 | 21.31545 | 42.49933 | -0.3394 | 7.76926 |
November | 330.00000 | 21.10940 | 37.12768 | -0.4845 | 10.01996 |
December | 338.00000 | 21.10995 | 30.91282 | -0.5742 | 11.98945 |
Annual Sum or Average | 4030.00000 | 21.86905 | 38.87441 | -0.6691 | 16.96492 |
Minimum of Months | 308.00000 | 21.10940 | 30.91282 | -1.4403 | 7.76926 |
Maximum of Months | 348.00000 | 23.73094 | 47.22711 | -0.3394 | 48.55413 |
Report: DXReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.323868E+09 | 80635973.83 | 28.50 | 0.321540E+09 | 2327646.71 | 0.00 | 0.80 | 30-APR-16:25 | 0.00 | 01-APR-00:05 | 8980.78 | 30-APR-16:25 | 8980.78 | 30-APR-16:25 | 264.48 | 30-APR-19:50 | 2141.10 | 30-APR-16:25 | 0.00 | 01-APR-00:05 |
May | 0.170007E+09 | 44534782.18 | 27.50 | 0.145163E+09 | 24844279.40 | 0.00 | 0.63 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 6905.14 | 22-MAY-15:00 | 6305.43 | 22-MAY-15:00 | 664.17 | 23-MAY-17:10 | 1726.39 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.141391E+10 | 0.342654E+09 | 95.53 | 0.116856E+10 | 0.245349E+09 | 0.00 | 0.98 | 13-JUN-16:00 | 0.00 | 01-JUN-00:10 | 12838.60 | 13-JUN-17:00 | 11846.00 | 13-JUN-17:00 | 5313.76 | 25-JUN-18:00 | 2983.70 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.273904E+10 | 0.681027E+09 | 233.64 | 0.230698E+10 | 0.432062E+09 | 0.00 | 1.00 | 22-JUL-12:10 | 0.00 | 01-JUL-00:10 | 20155.59 | 23-JUL-07:03 | 15157.34 | 23-JUL-07:03 | 4998.25 | 23-JUL-07:03 | 4293.42 | 23-JUL-07:03 | 0.00 | 01-JUL-00:10 |
August | 0.290729E+10 | 0.733201E+09 | 309.38 | 0.236556E+10 | 0.541728E+09 | 0.00 | 0.99 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 11808.93 | 14-AUG-17:00 | 11808.93 | 14-AUG-17:00 | 2773.17 | 06-AUG-07:02 | 2802.28 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.151299E+10 | 0.375629E+09 | 148.06 | 0.126035E+10 | 0.252635E+09 | 0.00 | 0.84 | 13-SEP-14:00 | 0.00 | 01-SEP-00:10 | 10017.48 | 13-SEP-14:00 | 8502.08 | 13-SEP-14:00 | 2347.33 | 12-SEP-14:00 | 2304.79 | 13-SEP-14:00 | 0.00 | 01-SEP-00:10 |
October | 64536.19 | 18190.04 | 2.00 | 64536.19 | 0.00 | 0.00 | 0.01 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 | 103.89 | 07-OCT-15:00 | 103.89 | 07-OCT-15:00 | 0.00 | 07-OCT-15:10 | 29.28 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.906718E+10 | 0.225770E+10 | 844.61 | 0.756823E+10 | 0.149895E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.290729E+10 | 0.733201E+09 | 309.38 | 0.236556E+10 | 0.541728E+09 | 0.00 | 1.00 | 0.00 | 20155.59 | 15157.34 | 5313.76 | 4293.42 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 10028.10 | 2827.64 | 0.17 | 9454.39 | 573.70 | 0.00 | 0.00 | 29-JAN-22:00 | 0.00 | 01-JAN-00:10 | 16.71 | 29-JAN-22:00 | 15.76 | 29-JAN-22:00 | 0.96 | 29-JAN-22:00 | 4.71 | 29-JAN-22:00 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 6229936.63 | 1738229.08 | 9.33 | 5705396.59 | 524540.04 | 0.00 | 0.07 | 19-MAR-19:20 | 0.00 | 01-MAR-00:10 | 323.59 | 19-MAR-19:20 | 285.05 | 19-MAR-19:20 | 38.54 | 19-MAR-19:20 | 89.81 | 19-MAR-19:20 | 0.00 | 01-MAR-00:10 |
April | 0.791552E+09 | 0.185245E+09 | 148.40 | 0.791543E+09 | 9074.66 | 0.00 | 0.82 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 5880.87 | 30-APR-15:00 | 5880.87 | 30-APR-15:00 | 4.92 | 26-APR-18:00 | 1218.29 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.913815E+09 | 0.219890E+09 | 187.63 | 0.876711E+09 | 37104327.73 | 0.00 | 0.70 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5004.16 | 22-MAY-15:00 | 4797.66 | 22-MAY-15:00 | 465.76 | 23-MAY-14:00 | 1067.49 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.282918E+10 | 0.645857E+09 | 367.64 | 0.260978E+10 | 0.219396E+09 | 0.00 | 0.96 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 11070.59 | 25-JUN-07:02 | 10880.48 | 25-JUN-07:02 | 1393.42 | 26-JUN-17:10 | 2128.97 | 25-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.464004E+10 | 0.103700E+10 | 459.30 | 0.424387E+10 | 0.396166E+09 | 0.00 | 1.00 | 23-JUL-07:03 | 0.00 | 01-JUL-00:10 | 14794.62 | 23-JUL-07:03 | 13930.99 | 23-JUL-07:03 | 1238.52 | 18-JUL-07:03 | 2899.40 | 23-JUL-07:03 | 0.00 | 01-JUL-00:10 |
August | 0.529344E+10 | 0.117333E+10 | 491.60 | 0.482015E+10 | 0.473291E+09 | 0.00 | 1.00 | 06-AUG-07:02 | 0.00 | 01-AUG-00:10 | 14699.49 | 06-AUG-07:02 | 13865.45 | 06-AUG-07:02 | 982.94 | 17-AUG-13:40 | 2883.52 | 06-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.360060E+10 | 0.816498E+09 | 441.38 | 0.334259E+10 | 0.258004E+09 | 0.00 | 0.99 | 15-SEP-07:03 | 0.00 | 01-SEP-00:10 | 9158.17 | 13-SEP-07:03 | 8457.14 | 13-SEP-07:03 | 981.27 | 12-SEP-14:00 | 1723.87 | 13-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 0.459124E+09 | 0.116015E+09 | 148.53 | 0.450529E+09 | 8595653.63 | 0.00 | 0.55 | 08-OCT-17:10 | 0.00 | 01-OCT-00:05 | 3283.99 | 08-OCT-17:10 | 2997.85 | 01-OCT-17:10 | 443.92 | 08-OCT-17:10 | 770.95 | 08-OCT-17:10 | 0.00 | 01-OCT-00:05 |
November | 7285458.76 | 2029451.30 | 15.33 | 6998988.68 | 286470.09 | 0.00 | 0.07 | 05-NOV-19:20 | 0.00 | 01-NOV-00:10 | 357.03 | 08-NOV-23:00 | 351.61 | 05-NOV-19:20 | 38.34 | 08-NOV-23:00 | 98.92 | 08-NOV-23:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.185413E+11 | 0.419761E+10 | 2269.31 | 0.171479E+11 | 0.139338E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.529344E+10 | 0.117333E+10 | 491.60 | 0.482015E+10 | 0.473291E+09 | 0.00 | 1.00 | 0.00 | 14794.62 | 13930.99 | 1393.42 | 2899.40 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.108511E+09 | 24165611.52 | 33.54 | 0.108353E+09 | 158419.39 | 0.00 | 0.72 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 5638.02 | 30-APR-15:00 | 5638.02 | 30-APR-15:00 | 53.78 | 28-APR-15:00 | 1204.20 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 67274550.24 | 15288028.69 | 44.11 | 62460937.15 | 4813613.09 | 0.00 | 0.60 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4687.93 | 22-MAY-15:00 | 4473.49 | 22-MAY-15:00 | 262.28 | 22-MAY-14:00 | 1030.41 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.656428E+09 | 0.142302E+09 | 149.36 | 0.577852E+09 | 78575490.75 | 0.00 | 0.87 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 9221.63 | 27-JUN-06:02 | 7018.37 | 13-JUN-17:00 | 4127.07 | 27-JUN-06:02 | 1718.50 | 27-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.934689E+09 | 0.206180E+09 | 202.00 | 0.853742E+09 | 80946599.80 | 0.00 | 0.98 | 18-JUL-06:03 | 0.00 | 01-JUL-00:10 | 15361.40 | 23-JUL-07:03 | 12252.37 | 23-JUL-07:03 | 6163.65 | 24-JUL-06:02 | 3008.77 | 23-JUL-07:03 | 0.00 | 01-JUL-00:10 |
August | 0.927191E+09 | 0.206706E+09 | 231.31 | 0.812392E+09 | 0.114798E+09 | 0.00 | 0.86 | 06-AUG-07:02 | 0.00 | 01-AUG-00:10 | 7051.74 | 06-AUG-07:02 | 6943.06 | 14-AUG-17:00 | 2650.88 | 17-AUG-06:02 | 1502.34 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.617812E+09 | 0.136924E+09 | 164.35 | 0.549589E+09 | 68223894.39 | 0.00 | 0.87 | 02-SEP-06:02 | 0.00 | 01-SEP-00:10 | 7207.58 | 02-SEP-06:02 | 5146.24 | 13-SEP-14:00 | 2488.11 | 02-SEP-06:02 | 1394.72 | 02-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 116435.40 | 28571.10 | 28.83 | 116430.06 | 5.34 | 0.00 | 0.02 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 | 150.97 | 07-OCT-15:00 | 150.97 | 07-OCT-15:00 | 0.00 | 02-OCT-15:00 | 36.99 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.331202E+10 | 0.731595E+09 | 853.51 | 0.296451E+10 | 0.347516E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.934689E+09 | 0.206706E+09 | 231.31 | 0.853742E+09 | 0.114798E+09 | 0.00 | 0.98 | 0.00 | 15361.40 | 12252.37 | 6163.65 | 3008.77 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.102434E+09 | 22836847.45 | 30.58 | 0.102301E+09 | 133154.65 | 0.00 | 0.71 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 5528.65 | 30-APR-15:00 | 5528.65 | 30-APR-15:00 | 46.80 | 28-APR-15:00 | 1184.01 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 57308304.78 | 13068287.02 | 41.00 | 53510943.61 | 3797361.18 | 0.00 | 0.57 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4408.54 | 22-MAY-15:00 | 4205.10 | 22-MAY-15:00 | 242.52 | 22-MAY-14:00 | 977.05 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.637164E+09 | 0.138393E+09 | 140.37 | 0.560936E+09 | 76227925.21 | 0.00 | 0.90 | 27-JUN-06:02 | 0.00 | 01-JUN-00:10 | 7834.16 | 27-JUN-06:02 | 6937.51 | 13-JUN-17:00 | 3507.89 | 27-JUN-06:02 | 1561.51 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.913436E+09 | 0.201553E+09 | 200.10 | 0.835147E+09 | 78289098.33 | 0.00 | 0.95 | 22-JUL-15:00 | 0.00 | 01-JUL-00:10 | 15487.34 | 23-JUL-07:03 | 12349.46 | 23-JUL-07:03 | 6067.24 | 24-JUL-06:02 | 3036.03 | 23-JUL-07:03 | 0.00 | 01-JUL-00:10 |
August | 0.904373E+09 | 0.201789E+09 | 229.81 | 0.792894E+09 | 0.111479E+09 | 0.00 | 0.84 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 6877.15 | 14-AUG-17:00 | 6877.15 | 14-AUG-17:00 | 2276.75 | 17-AUG-06:02 | 1489.66 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.594436E+09 | 0.131935E+09 | 159.99 | 0.529384E+09 | 65051361.12 | 0.00 | 0.71 | 02-SEP-06:02 | 0.00 | 01-SEP-00:10 | 5743.71 | 13-SEP-14:00 | 5089.57 | 13-SEP-14:00 | 1901.79 | 02-SEP-06:02 | 1202.24 | 13-SEP-14:00 | 0.00 | 01-SEP-00:10 |
October | 36817.76 | 9078.48 | 27.00 | 36816.01 | 1.75 | 0.00 | 0.00 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 | 22.79 | 07-OCT-15:00 | 22.79 | 07-OCT-15:00 | 0.00 | 02-OCT-15:10 | 5.61 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.320919E+10 | 0.709584E+09 | 828.86 | 0.287421E+10 | 0.334978E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.913436E+09 | 0.201789E+09 | 229.81 | 0.835147E+09 | 0.111479E+09 | 0.00 | 0.95 | 0.00 | 15487.34 | 12349.46 | 6067.24 | 3036.03 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 86014309.09 | 19215843.60 | 27.00 | 85947861.18 | 66447.92 | 0.00 | 0.68 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 5241.18 | 30-APR-15:00 | 5241.18 | 30-APR-15:00 | 27.27 | 28-APR-15:00 | 1131.62 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 44216637.18 | 10139974.18 | 34.83 | 41656498.01 | 2560139.18 | 0.00 | 0.52 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 3976.82 | 22-MAY-15:00 | 3790.81 | 22-MAY-15:00 | 213.57 | 22-MAY-14:20 | 893.03 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.580933E+09 | 0.126984E+09 | 111.73 | 0.511912E+09 | 69020818.65 | 0.00 | 0.85 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 7114.51 | 13-JUN-16:50 | 6687.95 | 13-JUN-17:00 | 1361.41 | 27-JUN-06:02 | 1515.91 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.837072E+09 | 0.185307E+09 | 188.09 | 0.769149E+09 | 67923034.91 | 0.00 | 0.94 | 22-JUL-15:00 | 0.00 | 01-JUL-00:10 | 13253.59 | 23-JUL-07:03 | 10597.96 | 23-JUL-07:03 | 4220.06 | 24-JUL-06:02 | 2570.19 | 23-JUL-07:03 | 0.00 | 01-JUL-00:10 |
August | 0.818477E+09 | 0.183126E+09 | 223.77 | 0.720627E+09 | 97849808.87 | 0.00 | 0.83 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 6696.77 | 14-AUG-17:00 | 6696.77 | 14-AUG-17:00 | 1061.67 | 17-AUG-14:00 | 1456.66 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.525271E+09 | 0.117135E+09 | 148.14 | 0.469125E+09 | 56146138.36 | 0.00 | 0.69 | 13-SEP-14:00 | 0.00 | 01-SEP-00:10 | 5518.33 | 13-SEP-14:00 | 4888.50 | 13-SEP-14:00 | 959.52 | 12-SEP-14:00 | 1161.81 | 13-SEP-14:00 | 0.00 | 01-SEP-00:10 |
October | 9282.89 | 2288.62 | 10.33 | 9282.89 | 0.00 | 0.00 | 0.00 | 07-OCT-13:00 | 0.00 | 01-OCT-00:05 | 1.55 | 07-OCT-13:00 | 1.55 | 07-OCT-13:00 | 0.00 | 07-OCT-12:40 | 0.38 | 07-OCT-13:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.289199E+10 | 0.641911E+09 | 743.90 | 0.259843E+10 | 0.293566E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.837072E+09 | 0.185307E+09 | 223.77 | 0.769149E+09 | 97849808.87 | 0.00 | 0.94 | 0.00 | 13253.59 | 10597.96 | 4220.06 | 2570.19 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.120725E+09 | 31030577.46 | 13.50 | 0.119995E+09 | 729843.43 | 0.00 | 0.69 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 7244.31 | 30-APR-15:00 | 7244.31 | 30-APR-15:00 | 93.08 | 28-APR-15:00 | 1791.15 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 50335831.03 | 13417475.79 | 10.83 | 45020796.22 | 5315034.82 | 0.00 | 0.48 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4998.72 | 22-MAY-15:00 | 4507.46 | 22-MAY-15:00 | 491.26 | 22-MAY-15:00 | 1302.55 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.845844E+09 | 0.211592E+09 | 62.61 | 0.709210E+09 | 0.136634E+09 | 0.00 | 0.90 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 10651.52 | 13-JUN-16:30 | 9713.22 | 13-JUN-17:00 | 2350.23 | 26-JUN-16:40 | 2551.62 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.148704E+10 | 0.374508E+09 | 145.21 | 0.128488E+10 | 0.202166E+09 | 0.00 | 1.00 | 21-JUL-16:40 | 0.00 | 01-JUL-00:10 | 18595.84 | 23-JUL-08:63 | 14451.26 | 23-JUL-08:63 | 4144.58 | 23-JUL-08:63 | 3961.13 | 23-JUL-08:63 | 0.00 | 01-JUL-00:10 |
August | 0.171808E+10 | 0.437408E+09 | 211.92 | 0.141890E+10 | 0.299180E+09 | 0.00 | 0.88 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 10039.31 | 14-AUG-17:00 | 10039.31 | 14-AUG-17:00 | 2069.92 | 17-AUG-14:10 | 2461.64 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.904344E+09 | 0.228852E+09 | 88.53 | 0.768871E+09 | 0.135473E+09 | 0.00 | 0.77 | 13-SEP-14:10 | 0.00 | 01-SEP-00:10 | 8765.45 | 13-SEP-14:10 | 7410.87 | 13-SEP-14:10 | 1843.44 | 12-SEP-14:10 | 2062.89 | 13-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 1621.56 | 458.35 | 1.00 | 1621.56 | 0.00 | 0.00 | 0.00 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 | 0.98 | 07-OCT-15:00 | 0.98 | 07-OCT-15:00 | 0.00 | 07-OCT-15:30 | 0.28 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.512638E+10 | 0.129681E+10 | 533.60 | 0.434688E+10 | 0.779499E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.171808E+10 | 0.437408E+09 | 211.92 | 0.141890E+10 | 0.299180E+09 | 0.00 | 1.00 | 0.00 | 18595.84 | 14451.26 | 4144.58 | 3961.13 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.123930E+09 | 27857215.37 | 22.17 | 0.123930E+09 | 0.00 | 0.00 | 0.69 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 4256.53 | 30-APR-15:00 | 4256.53 | 30-APR-15:00 | 0.00 | 29-APR-15:00 | 916.33 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 89370292.61 | 20831624.14 | 21.67 | 80796242.39 | 8574050.22 | 0.00 | 0.49 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 2962.30 | 22-MAY-15:00 | 2790.35 | 22-MAY-15:00 | 233.58 | 23-MAY-14:10 | 670.58 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.701989E+09 | 0.154861E+09 | 96.97 | 0.626577E+09 | 75412107.89 | 0.00 | 0.87 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 5884.03 | 13-JUN-17:00 | 5494.58 | 13-JUN-17:00 | 1053.40 | 26-JUN-17:10 | 1242.33 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.162099E+10 | 0.359895E+09 | 229.22 | 0.144577E+10 | 0.175222E+09 | 0.00 | 1.00 | 22-JUL-16:30 | 0.00 | 01-JUL-00:10 | 9777.68 | 23-JUL-08:63 | 9777.68 | 23-JUL-08:63 | 1030.47 | 24-JUL-07:03 | 1880.92 | 23-JUL-08:63 | 0.00 | 01-JUL-00:10 |
August | 0.217415E+10 | 0.484099E+09 | 318.64 | 0.192743E+10 | 0.246718E+09 | 0.00 | 0.87 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 5708.50 | 14-AUG-17:00 | 5708.50 | 14-AUG-17:00 | 859.29 | 17-AUG-13:00 | 1223.94 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.100463E+10 | 0.222415E+09 | 155.36 | 0.904767E+09 | 99861429.00 | 0.00 | 0.76 | 13-SEP-14:20 | 0.00 | 01-SEP-00:10 | 4971.51 | 13-SEP-14:20 | 4475.48 | 13-SEP-14:10 | 795.63 | 12-SEP-14:10 | 1023.39 | 13-SEP-14:20 | 0.00 | 01-SEP-00:10 |
October | 5696037.51 | 1351745.65 | 2.67 | 5696037.51 | 0.00 | 0.00 | 0.21 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 | 1108.35 | 07-OCT-15:00 | 1108.35 | 07-OCT-15:00 | 0.00 | 07-OCT-15:40 | 258.95 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.572075E+10 | 0.127131E+10 | 846.69 | 0.511497E+10 | 0.605787E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.217415E+10 | 0.484099E+09 | 318.64 | 0.192743E+10 | 0.246718E+09 | 0.00 | 1.00 | 0.00 | 9777.68 | 9777.68 | 1053.40 | 1880.92 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.115634E+09 | 26018236.23 | 20.33 | 0.115634E+09 | 0.00 | 0.00 | 0.68 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 4150.44 | 30-APR-15:00 | 4150.44 | 30-APR-15:00 | 0.00 | 30-APR-15:00 | 895.48 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 80839987.43 | 18889181.70 | 19.83 | 73096516.49 | 7743470.95 | 0.00 | 0.48 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 2853.54 | 22-MAY-15:00 | 2687.10 | 22-MAY-15:00 | 219.02 | 23-MAY-14:10 | 647.94 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.658923E+09 | 0.145462E+09 | 89.92 | 0.587291E+09 | 71632006.06 | 0.00 | 0.86 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 5771.90 | 13-JUN-17:00 | 5389.63 | 13-JUN-17:00 | 1032.58 | 26-JUN-17:10 | 1220.45 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.154016E+10 | 0.342198E+09 | 222.04 | 0.137332E+10 | 0.166846E+09 | 0.00 | 1.00 | 22-JUL-16:40 | 0.00 | 01-JUL-00:10 | 9196.68 | 23-JUL-08:63 | 9196.68 | 23-JUL-08:63 | 945.02 | 24-JUL-07:03 | 1761.52 | 23-JUL-08:63 | 0.00 | 01-JUL-00:10 |
August | 0.207223E+10 | 0.461956E+09 | 314.15 | 0.183559E+10 | 0.236638E+09 | 0.00 | 0.87 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 5628.44 | 14-AUG-17:00 | 5628.44 | 14-AUG-17:00 | 846.78 | 17-AUG-13:00 | 1207.29 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.948779E+09 | 0.210210E+09 | 143.83 | 0.853844E+09 | 94935371.51 | 0.00 | 0.75 | 13-SEP-14:20 | 0.00 | 01-SEP-00:10 | 4881.55 | 13-SEP-14:20 | 4391.26 | 13-SEP-14:20 | 780.88 | 12-SEP-14:10 | 1006.00 | 13-SEP-14:20 | 0.00 | 01-SEP-00:10 |
October | 4581224.02 | 1090407.49 | 2.17 | 4581224.02 | 0.00 | 0.00 | 0.19 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 | 991.53 | 07-OCT-15:00 | 991.53 | 07-OCT-15:00 | 0.00 | 07-OCT-15:40 | 232.80 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.542115E+10 | 0.120582E+10 | 812.28 | 0.484335E+10 | 0.577794E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.207223E+10 | 0.461956E+09 | 314.15 | 0.183559E+10 | 0.236638E+09 | 0.00 | 1.00 | 0.00 | 9196.68 | 9196.68 | 1032.58 | 1761.52 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 96017409.44 | 21683616.09 | 17.00 | 96017409.44 | 0.00 | 0.00 | 0.66 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 3886.76 | 30-APR-15:00 | 3886.76 | 30-APR-15:00 | 0.00 | 30-APR-12:00 | 844.89 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 61853812.40 | 14556828.14 | 17.33 | 56007479.30 | 5846333.10 | 0.00 | 0.45 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 2585.93 | 22-MAY-15:00 | 2433.32 | 22-MAY-15:00 | 180.47 | 23-MAY-17:10 | 592.48 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.557769E+09 | 0.123503E+09 | 76.33 | 0.495192E+09 | 62576651.93 | 0.00 | 0.85 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 5524.06 | 13-JUN-17:00 | 5156.71 | 13-JUN-17:00 | 974.92 | 26-JUN-17:10 | 1173.71 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.132421E+10 | 0.294787E+09 | 196.92 | 0.118143E+10 | 0.142786E+09 | 0.00 | 1.00 | 22-JUL-16:40 | 0.00 | 01-JUL-00:10 | 7367.37 | 23-JUL-08:63 | 7367.37 | 23-JUL-08:63 | 765.32 | 24-JUL-17:10 | 1473.97 | 22-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.177783E+10 | 0.397561E+09 | 292.39 | 0.157188E+10 | 0.205953E+09 | 0.00 | 0.86 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 5425.22 | 14-AUG-17:00 | 5425.22 | 14-AUG-17:00 | 820.20 | 17-AUG-14:10 | 1167.74 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.799009E+09 | 0.177579E+09 | 124.33 | 0.717628E+09 | 81380779.57 | 0.00 | 0.74 | 13-SEP-14:20 | 0.00 | 01-SEP-00:10 | 4675.51 | 13-SEP-14:20 | 4200.19 | 13-SEP-14:20 | 745.82 | 12-SEP-14:10 | 967.54 | 13-SEP-14:20 | 0.00 | 01-SEP-00:10 |
October | 2192506.20 | 528092.26 | 1.67 | 2192506.20 | 0.00 | 0.00 | 0.13 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 | 652.94 | 07-OCT-15:00 | 652.94 | 07-OCT-15:00 | 0.00 | 07-OCT-15:00 | 155.72 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.461889E+10 | 0.103020E+10 | 725.97 | 0.412034E+10 | 0.498542E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.177783E+10 | 0.397561E+09 | 292.39 | 0.157188E+10 | 0.205953E+09 | 0.00 | 1.00 | 0.00 | 7367.37 | 7367.37 | 974.92 | 1473.97 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 77581809.45 | 17648774.33 | 14.17 | 77581809.45 | 0.00 | 0.00 | 0.61 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 3543.05 | 30-APR-15:00 | 3543.05 | 30-APR-15:00 | 0.00 | 30-APR-14:40 | 780.43 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 42033508.84 | 9976842.32 | 15.33 | 38334227.39 | 3699281.45 | 0.00 | 0.40 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 2267.80 | 22-MAY-15:00 | 2132.32 | 22-MAY-15:00 | 135.48 | 22-MAY-15:00 | 526.37 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.459364E+09 | 0.102134E+09 | 60.67 | 0.407108E+09 | 52256469.75 | 0.00 | 0.82 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 5256.64 | 13-JUN-17:00 | 4904.26 | 13-JUN-17:00 | 853.74 | 26-JUN-17:10 | 1126.26 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.102781E+10 | 0.228746E+09 | 159.06 | 0.925267E+09 | 0.102539E+09 | 0.00 | 1.00 | 22-JUL-16:10 | 0.00 | 01-JUL-00:10 | 6835.22 | 22-JUL-15:00 | 6835.22 | 22-JUL-15:00 | 671.25 | 24-JUL-17:10 | 1454.74 | 22-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.134118E+10 | 0.301431E+09 | 237.33 | 0.118522E+10 | 0.155961E+09 | 0.00 | 0.82 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 5113.05 | 14-AUG-17:00 | 5113.05 | 14-AUG-17:00 | 787.82 | 17-AUG-13:00 | 1112.21 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.621963E+09 | 0.138919E+09 | 100.33 | 0.558278E+09 | 63684298.78 | 0.00 | 0.71 | 13-SEP-14:10 | 0.00 | 01-SEP-00:10 | 4400.83 | 13-SEP-14:10 | 3949.99 | 13-SEP-14:10 | 700.22 | 12-SEP-14:10 | 919.18 | 13-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 147363.85 | 36076.93 | 0.50 | 147363.85 | 0.00 | 0.00 | 0.03 | 07-OCT-15:10 | 0.00 | 01-OCT-00:05 | 157.40 | 07-OCT-15:10 | 157.40 | 07-OCT-15:10 | 0.00 | 01-OCT-00:05 | 38.48 | 07-OCT-15:10 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.357008E+10 | 0.798891E+09 | 587.39 | 0.319194E+10 | 0.378140E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.134118E+10 | 0.301431E+09 | 237.33 | 0.118522E+10 | 0.155961E+09 | 0.00 | 1.00 | 0.00 | 6835.22 | 6835.22 | 853.74 | 1454.74 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.50 | 46.92 | 25.57 | 69.53 | 72.35 | 0.00 | 0.00 | 744.00 |
February | 88.57 | 54.05 | 34.52 | 83.65 | 70.15 | 0.00 | 0.00 | 672.00 |
March | 54.77 | 15.95 | 38.81 | 37.65 | 59.14 | 0.00 | 0.00 | 744.00 |
April | 113.72 | 51.41 | 62.31 | 102.73 | 49.14 | 0.00 | 0.00 | 720.00 |
May | 94.03 | 30.60 | 63.43 | 68.35 | 43.27 | 0.00 | 0.00 | 744.00 |
June | 86.62 | 20.96 | 65.67 | 62.95 | 35.30 | 0.00 | 0.00 | 720.00 |
July | 93.86 | 29.38 | 64.47 | 73.76 | 33.57 | 0.00 | 0.00 | 744.00 |
August | 109.99 | 49.48 | 60.51 | 101.02 | 36.88 | 0.00 | 0.00 | 744.00 |
September | 130.03 | 76.19 | 53.84 | 132.47 | 46.39 | 0.00 | 0.00 | 720.00 |
October | 89.33 | 52.22 | 37.11 | 89.56 | 56.35 | 0.00 | 0.00 | 744.00 |
November | 63.30 | 38.50 | 24.80 | 60.70 | 66.67 | 0.00 | 0.00 | 720.00 |
December | 50.17 | 32.14 | 18.03 | 46.98 | 81.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 87.11 | 41.32 | 45.78 | 77.26 | 54.18 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 50.17 | 15.95 | 18.03 | 37.65 | 33.57 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.03 | 76.19 | 65.67 | 132.47 | 81.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.50 | 46.92 | 25.57 | 69.53 | 72.35 | 0.00 | 0.00 | 744.00 |
February | 88.57 | 54.05 | 34.52 | 83.65 | 70.15 | 0.00 | 0.00 | 672.00 |
March | 54.77 | 15.95 | 38.81 | 37.65 | 59.14 | 0.00 | 0.00 | 744.00 |
April | 113.72 | 51.41 | 62.31 | 102.73 | 49.14 | 0.00 | 0.00 | 720.00 |
May | 94.03 | 30.60 | 63.43 | 68.35 | 43.27 | 0.00 | 0.00 | 744.00 |
June | 86.62 | 20.96 | 65.67 | 62.95 | 35.30 | 0.00 | 0.00 | 720.00 |
July | 93.86 | 29.38 | 64.47 | 73.76 | 33.57 | 0.00 | 0.00 | 744.00 |
August | 109.99 | 49.48 | 60.51 | 101.02 | 36.88 | 0.00 | 0.00 | 744.00 |
September | 130.03 | 76.19 | 53.84 | 132.47 | 46.39 | 0.00 | 0.00 | 720.00 |
October | 89.33 | 52.22 | 37.11 | 89.56 | 56.35 | 0.00 | 0.00 | 744.00 |
November | 63.30 | 38.50 | 24.80 | 60.70 | 66.67 | 0.00 | 0.00 | 720.00 |
December | 50.17 | 32.14 | 18.03 | 46.98 | 81.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 87.11 | 41.32 | 45.78 | 77.26 | 54.18 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 50.17 | 15.95 | 18.03 | 37.65 | 33.57 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.03 | 76.19 | 65.67 | 132.47 | 81.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.50 | 46.92 | 25.57 | 69.53 | 72.35 | 0.00 | 0.00 | 744.00 |
February | 88.57 | 54.05 | 34.52 | 83.65 | 70.15 | 0.00 | 0.00 | 672.00 |
March | 54.77 | 15.95 | 38.81 | 37.65 | 59.14 | 0.00 | 0.00 | 744.00 |
April | 113.72 | 51.41 | 62.31 | 102.73 | 49.14 | 0.00 | 0.00 | 720.00 |
May | 94.03 | 30.60 | 63.43 | 68.35 | 43.27 | 0.00 | 0.00 | 744.00 |
June | 86.62 | 20.96 | 65.67 | 62.95 | 35.30 | 0.00 | 0.00 | 720.00 |
July | 93.86 | 29.38 | 64.47 | 73.76 | 33.57 | 0.00 | 0.00 | 744.00 |
August | 109.99 | 49.48 | 60.51 | 101.02 | 36.88 | 0.00 | 0.00 | 744.00 |
September | 130.03 | 76.19 | 53.84 | 132.47 | 46.39 | 0.00 | 0.00 | 720.00 |
October | 89.33 | 52.22 | 37.11 | 89.56 | 56.35 | 0.00 | 0.00 | 744.00 |
November | 63.30 | 38.50 | 24.80 | 60.70 | 66.67 | 0.00 | 0.00 | 720.00 |
December | 50.17 | 32.14 | 18.03 | 46.98 | 81.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 87.11 | 41.32 | 45.78 | 77.26 | 54.18 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 50.17 | 15.95 | 18.03 | 37.65 | 33.57 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.03 | 76.19 | 65.67 | 132.47 | 81.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.50 | 46.92 | 25.57 | 69.53 | 72.35 | 0.00 | 0.00 | 744.00 |
February | 88.57 | 54.05 | 34.52 | 83.65 | 70.15 | 0.00 | 0.00 | 672.00 |
March | 54.77 | 15.95 | 38.81 | 37.65 | 59.14 | 0.00 | 0.00 | 744.00 |
April | 113.72 | 51.41 | 62.31 | 102.73 | 49.14 | 0.00 | 0.00 | 720.00 |
May | 94.03 | 30.60 | 63.43 | 68.35 | 43.27 | 0.00 | 0.00 | 744.00 |
June | 86.62 | 20.96 | 65.67 | 62.95 | 35.30 | 0.00 | 0.00 | 720.00 |
July | 93.86 | 29.38 | 64.47 | 73.76 | 33.57 | 0.00 | 0.00 | 744.00 |
August | 109.99 | 49.48 | 60.51 | 101.02 | 36.88 | 0.00 | 0.00 | 744.00 |
September | 130.03 | 76.19 | 53.84 | 132.47 | 46.39 | 0.00 | 0.00 | 720.00 |
October | 89.33 | 52.22 | 37.11 | 89.56 | 56.35 | 0.00 | 0.00 | 744.00 |
November | 63.30 | 38.50 | 24.80 | 60.70 | 66.67 | 0.00 | 0.00 | 720.00 |
December | 50.17 | 32.14 | 18.03 | 46.98 | 81.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 87.11 | 41.32 | 45.78 | 77.26 | 54.18 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 50.17 | 15.95 | 18.03 | 37.65 | 33.57 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.03 | 76.19 | 65.67 | 132.47 | 81.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.28 | 56.49 | 30.79 | 83.75 | 86.50 | 0.00 | 0.00 | 744.00 |
February | 106.63 | 65.07 | 41.56 | 100.78 | 83.82 | 0.00 | 0.00 | 672.00 |
March | 65.94 | 19.21 | 46.73 | 45.43 | 70.71 | 0.00 | 0.00 | 744.00 |
April | 136.91 | 61.89 | 75.02 | 123.73 | 58.79 | 0.00 | 0.00 | 720.00 |
May | 113.21 | 36.85 | 76.36 | 82.41 | 51.70 | 0.00 | 0.00 | 744.00 |
June | 104.29 | 25.23 | 79.06 | 75.87 | 42.21 | 0.00 | 0.00 | 720.00 |
July | 113.00 | 35.37 | 77.62 | 88.85 | 40.15 | 0.00 | 0.00 | 744.00 |
August | 132.42 | 59.57 | 72.86 | 121.61 | 44.14 | 0.00 | 0.00 | 744.00 |
September | 156.55 | 91.73 | 64.82 | 159.45 | 55.51 | 0.00 | 0.00 | 720.00 |
October | 107.54 | 62.86 | 44.68 | 107.82 | 67.40 | 0.00 | 0.00 | 744.00 |
November | 76.21 | 46.35 | 29.86 | 73.10 | 79.70 | 0.00 | 0.00 | 720.00 |
December | 60.40 | 38.69 | 21.71 | 56.60 | 97.81 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 104.87 | 49.75 | 55.12 | 93.06 | 64.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.40 | 19.21 | 21.71 | 45.43 | 40.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 156.55 | 91.73 | 79.06 | 159.45 | 97.81 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.28 | 56.49 | 30.79 | 83.75 | 86.50 | 0.00 | 0.00 | 744.00 |
February | 106.63 | 65.07 | 41.56 | 100.78 | 83.82 | 0.00 | 0.00 | 672.00 |
March | 65.94 | 19.21 | 46.73 | 45.43 | 70.71 | 0.00 | 0.00 | 744.00 |
April | 136.91 | 61.89 | 75.02 | 123.73 | 58.79 | 0.00 | 0.00 | 720.00 |
May | 113.21 | 36.85 | 76.36 | 82.41 | 51.70 | 0.00 | 0.00 | 744.00 |
June | 104.29 | 25.23 | 79.06 | 75.87 | 42.21 | 0.00 | 0.00 | 720.00 |
July | 113.00 | 35.37 | 77.62 | 88.85 | 40.15 | 0.00 | 0.00 | 744.00 |
August | 132.42 | 59.57 | 72.86 | 121.61 | 44.14 | 0.00 | 0.00 | 744.00 |
September | 156.55 | 91.73 | 64.82 | 159.45 | 55.51 | 0.00 | 0.00 | 720.00 |
October | 107.54 | 62.86 | 44.68 | 107.82 | 67.40 | 0.00 | 0.00 | 744.00 |
November | 76.21 | 46.35 | 29.86 | 73.10 | 79.70 | 0.00 | 0.00 | 720.00 |
December | 60.40 | 38.69 | 21.71 | 56.60 | 97.81 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 104.87 | 49.75 | 55.12 | 93.06 | 64.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.40 | 19.21 | 21.71 | 45.43 | 40.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 156.55 | 91.73 | 79.06 | 159.45 | 97.81 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.50 | 46.92 | 25.57 | 68.88 | 76.00 | 0.00 | 0.00 | 744.00 |
February | 88.57 | 54.05 | 34.52 | 82.91 | 73.90 | 0.00 | 0.00 | 672.00 |
March | 54.77 | 15.95 | 38.81 | 36.88 | 62.73 | 0.00 | 0.00 | 744.00 |
April | 113.72 | 51.41 | 62.31 | 100.68 | 53.44 | 0.00 | 0.00 | 720.00 |
May | 94.03 | 30.60 | 63.43 | 66.16 | 47.51 | 0.00 | 0.00 | 744.00 |
June | 86.62 | 20.96 | 65.67 | 61.15 | 37.69 | 0.00 | 0.00 | 720.00 |
July | 93.86 | 29.38 | 64.47 | 72.84 | 34.95 | 0.00 | 0.00 | 744.00 |
August | 109.99 | 49.48 | 60.51 | 100.56 | 37.80 | 0.00 | 0.00 | 744.00 |
September | 130.03 | 76.19 | 53.84 | 131.54 | 48.22 | 0.00 | 0.00 | 720.00 |
October | 89.33 | 52.22 | 37.11 | 88.00 | 61.30 | 0.00 | 0.00 | 744.00 |
November | 63.30 | 38.50 | 24.80 | 60.07 | 70.64 | 0.00 | 0.00 | 720.00 |
December | 50.17 | 32.14 | 18.03 | 46.54 | 85.91 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 87.11 | 41.32 | 45.78 | 76.17 | 57.43 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 50.17 | 15.95 | 18.03 | 36.88 | 34.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.03 | 76.19 | 65.67 | 131.54 | 85.91 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.50 | 46.92 | 25.57 | 68.88 | 76.00 | 0.00 | 0.00 | 744.00 |
February | 88.57 | 54.05 | 34.52 | 82.91 | 73.90 | 0.00 | 0.00 | 672.00 |
March | 54.77 | 15.95 | 38.81 | 36.88 | 62.73 | 0.00 | 0.00 | 744.00 |
April | 113.72 | 51.41 | 62.31 | 100.68 | 53.44 | 0.00 | 0.00 | 720.00 |
May | 94.03 | 30.60 | 63.43 | 66.16 | 47.51 | 0.00 | 0.00 | 744.00 |
June | 86.62 | 20.96 | 65.67 | 61.15 | 37.69 | 0.00 | 0.00 | 720.00 |
July | 93.86 | 29.38 | 64.47 | 72.84 | 34.95 | 0.00 | 0.00 | 744.00 |
August | 109.99 | 49.48 | 60.51 | 100.56 | 37.80 | 0.00 | 0.00 | 744.00 |
September | 130.03 | 76.19 | 53.84 | 131.54 | 48.22 | 0.00 | 0.00 | 720.00 |
October | 89.33 | 52.22 | 37.11 | 88.00 | 61.30 | 0.00 | 0.00 | 744.00 |
November | 63.30 | 38.50 | 24.80 | 60.07 | 70.64 | 0.00 | 0.00 | 720.00 |
December | 50.17 | 32.14 | 18.03 | 46.54 | 85.91 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 87.11 | 41.32 | 45.78 | 76.17 | 57.43 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 50.17 | 15.95 | 18.03 | 36.88 | 34.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.03 | 76.19 | 65.67 | 131.54 | 85.91 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.28 | 56.49 | 30.79 | 82.97 | 90.85 | 0.00 | 0.00 | 744.00 |
February | 106.63 | 65.07 | 41.56 | 99.88 | 88.27 | 0.00 | 0.00 | 672.00 |
March | 65.94 | 19.21 | 46.73 | 44.50 | 74.98 | 0.00 | 0.00 | 744.00 |
April | 136.91 | 61.89 | 75.02 | 121.29 | 63.90 | 0.00 | 0.00 | 720.00 |
May | 113.21 | 36.85 | 76.36 | 79.79 | 56.72 | 0.00 | 0.00 | 744.00 |
June | 104.29 | 25.23 | 79.06 | 73.73 | 45.04 | 0.00 | 0.00 | 720.00 |
July | 113.00 | 35.37 | 77.62 | 87.75 | 41.79 | 0.00 | 0.00 | 744.00 |
August | 132.42 | 59.57 | 72.86 | 121.06 | 45.24 | 0.00 | 0.00 | 744.00 |
September | 156.55 | 91.73 | 64.82 | 158.34 | 57.69 | 0.00 | 0.00 | 720.00 |
October | 107.54 | 62.86 | 44.68 | 105.96 | 73.27 | 0.00 | 0.00 | 744.00 |
November | 76.21 | 46.35 | 29.86 | 72.35 | 84.40 | 0.00 | 0.00 | 720.00 |
December | 60.40 | 38.69 | 21.71 | 56.07 | 102.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 104.87 | 49.75 | 55.12 | 91.75 | 68.63 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.40 | 19.21 | 21.71 | 44.50 | 41.79 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 156.55 | 91.73 | 79.06 | 158.34 | 102.59 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.50 | 46.92 | 25.57 | 69.14 | 73.93 | 0.00 | 0.00 | 744.00 |
February | 88.57 | 54.05 | 34.52 | 83.17 | 71.93 | 0.00 | 0.00 | 672.00 |
March | 54.77 | 15.95 | 38.81 | 37.12 | 60.91 | 0.00 | 0.00 | 744.00 |
April | 113.72 | 51.41 | 62.31 | 101.01 | 52.45 | 0.00 | 0.00 | 720.00 |
May | 94.03 | 30.60 | 63.43 | 66.47 | 46.72 | 0.00 | 0.00 | 744.00 |
June | 86.62 | 20.96 | 65.67 | 61.12 | 38.18 | 0.00 | 0.00 | 720.00 |
July | 93.86 | 29.38 | 64.47 | 72.77 | 35.65 | 0.00 | 0.00 | 744.00 |
August | 109.99 | 49.48 | 60.51 | 100.54 | 38.60 | 0.00 | 0.00 | 744.00 |
September | 130.03 | 76.19 | 53.84 | 131.58 | 48.79 | 0.00 | 0.00 | 720.00 |
October | 89.33 | 52.22 | 37.11 | 88.24 | 60.06 | 0.00 | 0.00 | 744.00 |
November | 63.30 | 38.50 | 24.80 | 60.32 | 68.43 | 0.00 | 0.00 | 720.00 |
December | 50.17 | 32.14 | 18.03 | 46.72 | 83.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 87.11 | 41.32 | 45.78 | 76.33 | 56.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 50.17 | 15.95 | 18.03 | 37.12 | 35.65 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.03 | 76.19 | 65.67 | 131.58 | 83.71 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.50 | 46.92 | 25.57 | 69.14 | 73.93 | 0.00 | 0.00 | 744.00 |
February | 88.57 | 54.05 | 34.52 | 83.17 | 71.93 | 0.00 | 0.00 | 672.00 |
March | 54.77 | 15.95 | 38.81 | 37.12 | 60.91 | 0.00 | 0.00 | 744.00 |
April | 113.72 | 51.41 | 62.31 | 101.01 | 52.45 | 0.00 | 0.00 | 720.00 |
May | 94.03 | 30.60 | 63.43 | 66.47 | 46.72 | 0.00 | 0.00 | 744.00 |
June | 86.62 | 20.96 | 65.67 | 61.12 | 38.18 | 0.00 | 0.00 | 720.00 |
July | 93.86 | 29.38 | 64.47 | 72.77 | 35.65 | 0.00 | 0.00 | 744.00 |
August | 109.99 | 49.48 | 60.51 | 100.54 | 38.60 | 0.00 | 0.00 | 744.00 |
September | 130.03 | 76.19 | 53.84 | 131.58 | 48.79 | 0.00 | 0.00 | 720.00 |
October | 89.33 | 52.22 | 37.11 | 88.24 | 60.06 | 0.00 | 0.00 | 744.00 |
November | 63.30 | 38.50 | 24.80 | 60.32 | 68.43 | 0.00 | 0.00 | 720.00 |
December | 50.17 | 32.14 | 18.03 | 46.72 | 83.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 87.11 | 41.32 | 45.78 | 76.33 | 56.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 50.17 | 15.95 | 18.03 | 37.12 | 35.65 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.03 | 76.19 | 65.67 | 131.58 | 83.71 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.81 | 56.18 | 30.62 | 82.84 | 87.90 | 0.00 | 0.00 | 744.00 |
February | 106.05 | 64.72 | 41.34 | 99.64 | 85.46 | 0.00 | 0.00 | 672.00 |
March | 65.58 | 19.10 | 46.47 | 44.55 | 72.41 | 0.00 | 0.00 | 744.00 |
April | 136.16 | 61.55 | 74.61 | 121.02 | 62.36 | 0.00 | 0.00 | 720.00 |
May | 112.59 | 36.64 | 75.95 | 79.72 | 55.48 | 0.00 | 0.00 | 744.00 |
June | 103.72 | 25.10 | 78.63 | 73.29 | 45.36 | 0.00 | 0.00 | 720.00 |
July | 112.38 | 35.18 | 77.20 | 87.19 | 42.37 | 0.00 | 0.00 | 744.00 |
August | 131.70 | 59.24 | 72.46 | 120.38 | 45.92 | 0.00 | 0.00 | 744.00 |
September | 155.70 | 91.23 | 64.46 | 157.52 | 58.02 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.52 | 44.43 | 105.67 | 71.41 | 0.00 | 0.00 | 744.00 |
November | 75.80 | 46.10 | 29.69 | 72.26 | 81.32 | 0.00 | 0.00 | 720.00 |
December | 60.07 | 38.48 | 21.59 | 55.99 | 99.43 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 104.30 | 49.48 | 54.82 | 91.45 | 67.20 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.07 | 19.10 | 21.59 | 44.55 | 42.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 155.70 | 91.23 | 78.63 | 157.52 | 99.43 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.50 | 46.92 | 25.57 | 69.28 | 73.02 | 0.00 | 0.00 | 744.00 |
February | 88.57 | 54.05 | 34.52 | 83.30 | 71.10 | 0.00 | 0.00 | 672.00 |
March | 54.77 | 15.95 | 38.81 | 37.27 | 60.12 | 0.00 | 0.00 | 744.00 |
April | 113.72 | 51.41 | 62.31 | 101.39 | 51.53 | 0.00 | 0.00 | 720.00 |
May | 94.03 | 30.60 | 63.43 | 66.87 | 45.86 | 0.00 | 0.00 | 744.00 |
June | 86.62 | 20.96 | 65.67 | 61.33 | 37.75 | 0.00 | 0.00 | 720.00 |
July | 93.86 | 29.38 | 64.47 | 72.89 | 35.37 | 0.00 | 0.00 | 744.00 |
August | 109.99 | 49.48 | 60.51 | 100.60 | 38.42 | 0.00 | 0.00 | 744.00 |
September | 130.03 | 76.19 | 53.84 | 131.67 | 48.45 | 0.00 | 0.00 | 720.00 |
October | 89.33 | 52.22 | 37.11 | 88.49 | 59.05 | 0.00 | 0.00 | 744.00 |
November | 63.30 | 38.50 | 24.80 | 60.45 | 67.49 | 0.00 | 0.00 | 720.00 |
December | 50.17 | 32.14 | 18.03 | 46.81 | 82.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 87.11 | 41.32 | 45.78 | 76.51 | 55.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 50.17 | 15.95 | 18.03 | 37.27 | 35.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.03 | 76.19 | 65.67 | 131.67 | 82.76 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.50 | 46.92 | 25.57 | 69.28 | 73.02 | 0.00 | 0.00 | 744.00 |
February | 88.57 | 54.05 | 34.52 | 83.30 | 71.10 | 0.00 | 0.00 | 672.00 |
March | 54.77 | 15.95 | 38.81 | 37.27 | 60.12 | 0.00 | 0.00 | 744.00 |
April | 113.72 | 51.41 | 62.31 | 101.39 | 51.53 | 0.00 | 0.00 | 720.00 |
May | 94.03 | 30.60 | 63.43 | 66.87 | 45.86 | 0.00 | 0.00 | 744.00 |
June | 86.62 | 20.96 | 65.67 | 61.33 | 37.75 | 0.00 | 0.00 | 720.00 |
July | 93.86 | 29.38 | 64.47 | 72.89 | 35.37 | 0.00 | 0.00 | 744.00 |
August | 109.99 | 49.48 | 60.51 | 100.60 | 38.42 | 0.00 | 0.00 | 744.00 |
September | 130.03 | 76.19 | 53.84 | 131.67 | 48.45 | 0.00 | 0.00 | 720.00 |
October | 89.33 | 52.22 | 37.11 | 88.49 | 59.05 | 0.00 | 0.00 | 744.00 |
November | 63.30 | 38.50 | 24.80 | 60.45 | 67.49 | 0.00 | 0.00 | 720.00 |
December | 50.17 | 32.14 | 18.03 | 46.81 | 82.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 87.11 | 41.32 | 45.78 | 76.51 | 55.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 50.17 | 15.95 | 18.03 | 37.27 | 35.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.03 | 76.19 | 65.67 | 131.67 | 82.76 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.81 | 56.18 | 30.62 | 83.00 | 86.81 | 0.00 | 0.00 | 744.00 |
February | 106.05 | 64.72 | 41.34 | 99.81 | 84.46 | 0.00 | 0.00 | 672.00 |
March | 65.58 | 19.10 | 46.47 | 44.72 | 71.47 | 0.00 | 0.00 | 744.00 |
April | 136.16 | 61.55 | 74.61 | 121.47 | 61.27 | 0.00 | 0.00 | 720.00 |
May | 112.59 | 36.64 | 75.95 | 80.20 | 54.45 | 0.00 | 0.00 | 744.00 |
June | 103.72 | 25.10 | 78.63 | 73.54 | 44.85 | 0.00 | 0.00 | 720.00 |
July | 112.38 | 35.18 | 77.20 | 87.33 | 42.04 | 0.00 | 0.00 | 744.00 |
August | 131.70 | 59.24 | 72.46 | 120.45 | 45.70 | 0.00 | 0.00 | 744.00 |
September | 155.70 | 91.23 | 64.46 | 157.64 | 57.63 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.52 | 44.43 | 105.96 | 70.20 | 0.00 | 0.00 | 744.00 |
November | 75.80 | 46.10 | 29.69 | 72.42 | 80.20 | 0.00 | 0.00 | 720.00 |
December | 60.07 | 38.48 | 21.59 | 56.10 | 98.30 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 104.30 | 49.48 | 54.82 | 91.66 | 66.36 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.07 | 19.10 | 21.59 | 44.72 | 42.04 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 155.70 | 91.23 | 78.63 | 157.64 | 98.30 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.50 | 46.92 | 25.57 | 69.43 | 72.29 | 0.00 | 0.00 | 744.00 |
February | 88.57 | 54.05 | 34.52 | 83.46 | 70.42 | 0.00 | 0.00 | 672.00 |
March | 54.77 | 15.95 | 38.81 | 37.44 | 59.47 | 0.00 | 0.00 | 744.00 |
April | 113.72 | 51.41 | 62.31 | 101.97 | 50.46 | 0.00 | 0.00 | 720.00 |
May | 94.03 | 30.60 | 63.43 | 67.52 | 44.75 | 0.00 | 0.00 | 744.00 |
June | 86.62 | 20.96 | 65.67 | 61.96 | 36.82 | 0.00 | 0.00 | 720.00 |
July | 93.86 | 29.38 | 64.47 | 73.24 | 34.77 | 0.00 | 0.00 | 744.00 |
August | 109.99 | 49.48 | 60.51 | 100.76 | 38.03 | 0.00 | 0.00 | 744.00 |
September | 130.03 | 76.19 | 53.84 | 131.96 | 47.77 | 0.00 | 0.00 | 720.00 |
October | 89.33 | 52.22 | 37.11 | 88.92 | 57.76 | 0.00 | 0.00 | 744.00 |
November | 63.30 | 38.50 | 24.80 | 60.58 | 66.75 | 0.00 | 0.00 | 720.00 |
December | 50.17 | 32.14 | 18.03 | 46.92 | 81.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 87.11 | 41.32 | 45.78 | 76.83 | 55.03 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 50.17 | 15.95 | 18.03 | 37.44 | 34.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.03 | 76.19 | 65.67 | 131.96 | 81.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.50 | 46.92 | 25.57 | 69.43 | 72.29 | 0.00 | 0.00 | 744.00 |
February | 88.57 | 54.05 | 34.52 | 83.46 | 70.42 | 0.00 | 0.00 | 672.00 |
March | 54.77 | 15.95 | 38.81 | 37.44 | 59.47 | 0.00 | 0.00 | 744.00 |
April | 113.72 | 51.41 | 62.31 | 101.97 | 50.46 | 0.00 | 0.00 | 720.00 |
May | 94.03 | 30.60 | 63.43 | 67.52 | 44.75 | 0.00 | 0.00 | 744.00 |
June | 86.62 | 20.96 | 65.67 | 61.96 | 36.82 | 0.00 | 0.00 | 720.00 |
July | 93.86 | 29.38 | 64.47 | 73.24 | 34.77 | 0.00 | 0.00 | 744.00 |
August | 109.99 | 49.48 | 60.51 | 100.76 | 38.03 | 0.00 | 0.00 | 744.00 |
September | 130.03 | 76.19 | 53.84 | 131.96 | 47.77 | 0.00 | 0.00 | 720.00 |
October | 89.33 | 52.22 | 37.11 | 88.92 | 57.76 | 0.00 | 0.00 | 744.00 |
November | 63.30 | 38.50 | 24.80 | 60.58 | 66.75 | 0.00 | 0.00 | 720.00 |
December | 50.17 | 32.14 | 18.03 | 46.92 | 81.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 87.11 | 41.32 | 45.78 | 76.83 | 55.03 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 50.17 | 15.95 | 18.03 | 37.44 | 34.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.03 | 76.19 | 65.67 | 131.96 | 81.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.81 | 56.18 | 30.62 | 83.18 | 85.93 | 0.00 | 0.00 | 744.00 |
February | 106.05 | 64.72 | 41.34 | 99.99 | 83.65 | 0.00 | 0.00 | 672.00 |
March | 65.58 | 19.10 | 46.47 | 44.93 | 70.69 | 0.00 | 0.00 | 744.00 |
April | 136.16 | 61.55 | 74.61 | 122.16 | 60.00 | 0.00 | 0.00 | 720.00 |
May | 112.59 | 36.64 | 75.95 | 80.98 | 53.14 | 0.00 | 0.00 | 744.00 |
June | 103.72 | 25.10 | 78.63 | 74.30 | 43.74 | 0.00 | 0.00 | 720.00 |
July | 112.38 | 35.18 | 77.20 | 87.75 | 41.33 | 0.00 | 0.00 | 744.00 |
August | 131.70 | 59.24 | 72.46 | 120.65 | 45.24 | 0.00 | 0.00 | 744.00 |
September | 155.70 | 91.23 | 64.46 | 157.98 | 56.82 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.52 | 44.43 | 106.48 | 68.67 | 0.00 | 0.00 | 744.00 |
November | 75.80 | 46.10 | 29.69 | 72.58 | 79.33 | 0.00 | 0.00 | 720.00 |
December | 60.07 | 38.48 | 21.59 | 56.23 | 97.30 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 104.30 | 49.48 | 54.82 | 92.05 | 65.40 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.07 | 19.10 | 21.59 | 44.93 | 41.33 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 155.70 | 91.23 | 78.63 | 157.98 | 97.30 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.50 | 46.92 | 25.57 | 69.83 | 70.40 | 0.00 | 0.00 | 744.00 |
February | 88.57 | 54.05 | 34.52 | 83.92 | 68.57 | 0.00 | 0.00 | 672.00 |
March | 54.77 | 15.95 | 38.81 | 37.88 | 57.80 | 0.00 | 0.00 | 744.00 |
April | 113.72 | 51.41 | 62.31 | 103.08 | 48.28 | 0.00 | 0.00 | 720.00 |
May | 94.03 | 30.60 | 63.43 | 68.84 | 42.41 | 0.00 | 0.00 | 744.00 |
June | 86.62 | 20.96 | 65.67 | 63.76 | 34.34 | 0.00 | 0.00 | 720.00 |
July | 93.86 | 29.38 | 64.47 | 74.16 | 33.15 | 0.00 | 0.00 | 744.00 |
August | 109.99 | 49.48 | 60.51 | 101.05 | 36.91 | 0.00 | 0.00 | 744.00 |
September | 130.03 | 76.19 | 53.84 | 132.88 | 45.74 | 0.00 | 0.00 | 720.00 |
October | 89.33 | 52.22 | 37.11 | 89.95 | 55.05 | 0.00 | 0.00 | 744.00 |
November | 63.30 | 38.50 | 24.80 | 60.91 | 64.97 | 0.00 | 0.00 | 720.00 |
December | 50.17 | 32.14 | 18.03 | 47.23 | 79.51 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 87.11 | 41.32 | 45.78 | 77.60 | 53.02 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 50.17 | 15.95 | 18.03 | 37.88 | 33.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.03 | 76.19 | 65.67 | 132.88 | 79.51 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.50 | 46.92 | 25.57 | 69.83 | 70.40 | 0.00 | 0.00 | 744.00 |
February | 88.57 | 54.05 | 34.52 | 83.92 | 68.57 | 0.00 | 0.00 | 672.00 |
March | 54.77 | 15.95 | 38.81 | 37.88 | 57.80 | 0.00 | 0.00 | 744.00 |
April | 113.72 | 51.41 | 62.31 | 103.08 | 48.28 | 0.00 | 0.00 | 720.00 |
May | 94.03 | 30.60 | 63.43 | 68.84 | 42.41 | 0.00 | 0.00 | 744.00 |
June | 86.62 | 20.96 | 65.67 | 63.76 | 34.34 | 0.00 | 0.00 | 720.00 |
July | 93.86 | 29.38 | 64.47 | 74.16 | 33.15 | 0.00 | 0.00 | 744.00 |
August | 109.99 | 49.48 | 60.51 | 101.05 | 36.91 | 0.00 | 0.00 | 744.00 |
September | 130.03 | 76.19 | 53.84 | 132.88 | 45.74 | 0.00 | 0.00 | 720.00 |
October | 89.33 | 52.22 | 37.11 | 89.95 | 55.05 | 0.00 | 0.00 | 744.00 |
November | 63.30 | 38.50 | 24.80 | 60.91 | 64.97 | 0.00 | 0.00 | 720.00 |
December | 50.17 | 32.14 | 18.03 | 47.23 | 79.51 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 87.11 | 41.32 | 45.78 | 77.60 | 53.02 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 50.17 | 15.95 | 18.03 | 37.88 | 33.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.03 | 76.19 | 65.67 | 132.88 | 79.51 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.50 | 46.92 | 25.57 | 69.83 | 70.40 | 0.00 | 0.00 | 744.00 |
February | 88.57 | 54.05 | 34.52 | 83.92 | 68.57 | 0.00 | 0.00 | 672.00 |
March | 54.77 | 15.95 | 38.81 | 37.88 | 57.80 | 0.00 | 0.00 | 744.00 |
April | 113.72 | 51.41 | 62.31 | 103.08 | 48.28 | 0.00 | 0.00 | 720.00 |
May | 94.03 | 30.60 | 63.43 | 68.84 | 42.41 | 0.00 | 0.00 | 744.00 |
June | 86.62 | 20.96 | 65.67 | 63.76 | 34.34 | 0.00 | 0.00 | 720.00 |
July | 93.86 | 29.38 | 64.47 | 74.16 | 33.15 | 0.00 | 0.00 | 744.00 |
August | 109.99 | 49.48 | 60.51 | 101.05 | 36.91 | 0.00 | 0.00 | 744.00 |
September | 130.03 | 76.19 | 53.84 | 132.88 | 45.74 | 0.00 | 0.00 | 720.00 |
October | 89.33 | 52.22 | 37.11 | 89.95 | 55.05 | 0.00 | 0.00 | 744.00 |
November | 63.30 | 38.50 | 24.80 | 60.91 | 64.97 | 0.00 | 0.00 | 720.00 |
December | 50.17 | 32.14 | 18.03 | 47.23 | 79.51 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 87.11 | 41.32 | 45.78 | 77.60 | 53.02 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 50.17 | 15.95 | 18.03 | 37.88 | 33.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.03 | 76.19 | 65.67 | 132.88 | 79.51 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.50 | 46.92 | 25.57 | 69.83 | 70.40 | 0.00 | 0.00 | 744.00 |
February | 88.57 | 54.05 | 34.52 | 83.92 | 68.57 | 0.00 | 0.00 | 672.00 |
March | 54.77 | 15.95 | 38.81 | 37.88 | 57.80 | 0.00 | 0.00 | 744.00 |
April | 113.72 | 51.41 | 62.31 | 103.08 | 48.28 | 0.00 | 0.00 | 720.00 |
May | 94.03 | 30.60 | 63.43 | 68.84 | 42.41 | 0.00 | 0.00 | 744.00 |
June | 86.62 | 20.96 | 65.67 | 63.76 | 34.34 | 0.00 | 0.00 | 720.00 |
July | 93.86 | 29.38 | 64.47 | 74.16 | 33.15 | 0.00 | 0.00 | 744.00 |
August | 109.99 | 49.48 | 60.51 | 101.05 | 36.91 | 0.00 | 0.00 | 744.00 |
September | 130.03 | 76.19 | 53.84 | 132.88 | 45.74 | 0.00 | 0.00 | 720.00 |
October | 89.33 | 52.22 | 37.11 | 89.95 | 55.05 | 0.00 | 0.00 | 744.00 |
November | 63.30 | 38.50 | 24.80 | 60.91 | 64.97 | 0.00 | 0.00 | 720.00 |
December | 50.17 | 32.14 | 18.03 | 47.23 | 79.51 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 87.11 | 41.32 | 45.78 | 77.60 | 53.02 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 50.17 | 15.95 | 18.03 | 37.88 | 33.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.03 | 76.19 | 65.67 | 132.88 | 79.51 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.81 | 56.18 | 30.62 | 83.67 | 83.68 | 0.00 | 0.00 | 744.00 |
February | 106.05 | 64.72 | 41.34 | 100.55 | 81.45 | 0.00 | 0.00 | 672.00 |
March | 65.58 | 19.10 | 46.47 | 45.47 | 68.70 | 0.00 | 0.00 | 744.00 |
April | 136.16 | 61.55 | 74.61 | 123.49 | 57.41 | 0.00 | 0.00 | 720.00 |
May | 112.59 | 36.64 | 75.95 | 82.56 | 50.37 | 0.00 | 0.00 | 744.00 |
June | 103.72 | 25.10 | 78.63 | 76.44 | 40.82 | 0.00 | 0.00 | 720.00 |
July | 112.38 | 35.18 | 77.20 | 88.86 | 39.41 | 0.00 | 0.00 | 744.00 |
August | 131.70 | 59.24 | 72.46 | 121.00 | 43.91 | 0.00 | 0.00 | 744.00 |
September | 155.70 | 91.23 | 64.46 | 159.09 | 54.42 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.52 | 44.43 | 107.70 | 65.45 | 0.00 | 0.00 | 744.00 |
November | 75.80 | 46.10 | 29.69 | 72.97 | 77.21 | 0.00 | 0.00 | 720.00 |
December | 60.07 | 38.48 | 21.59 | 56.60 | 94.43 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 104.30 | 49.48 | 54.82 | 92.98 | 63.02 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.07 | 19.10 | 21.59 | 45.47 | 39.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 155.70 | 91.23 | 78.63 | 159.09 | 94.43 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.81 | 56.18 | 30.62 | 83.67 | 83.68 | 0.00 | 0.00 | 744.00 |
February | 106.05 | 64.72 | 41.34 | 100.55 | 81.45 | 0.00 | 0.00 | 672.00 |
March | 65.58 | 19.10 | 46.47 | 45.47 | 68.70 | 0.00 | 0.00 | 744.00 |
April | 136.16 | 61.55 | 74.61 | 123.49 | 57.41 | 0.00 | 0.00 | 720.00 |
May | 112.59 | 36.64 | 75.95 | 82.56 | 50.37 | 0.00 | 0.00 | 744.00 |
June | 103.72 | 25.10 | 78.63 | 76.44 | 40.82 | 0.00 | 0.00 | 720.00 |
July | 112.38 | 35.18 | 77.20 | 88.86 | 39.41 | 0.00 | 0.00 | 744.00 |
August | 131.70 | 59.24 | 72.46 | 121.00 | 43.91 | 0.00 | 0.00 | 744.00 |
September | 155.70 | 91.23 | 64.46 | 159.09 | 54.42 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.52 | 44.43 | 107.70 | 65.45 | 0.00 | 0.00 | 744.00 |
November | 75.80 | 46.10 | 29.69 | 72.97 | 77.21 | 0.00 | 0.00 | 720.00 |
December | 60.07 | 38.48 | 21.59 | 56.60 | 94.43 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 104.30 | 49.48 | 54.82 | 92.98 | 63.02 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.07 | 19.10 | 21.59 | 45.47 | 39.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 155.70 | 91.23 | 78.63 | 159.09 | 94.43 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.50 | 46.92 | 25.57 | 69.71 | 70.44 | 0.00 | 0.00 | 744.00 |
February | 88.57 | 54.05 | 34.52 | 83.79 | 68.65 | 0.00 | 0.00 | 672.00 |
March | 54.77 | 15.95 | 38.81 | 37.78 | 57.78 | 0.00 | 0.00 | 744.00 |
April | 113.72 | 51.41 | 62.31 | 102.96 | 48.20 | 0.00 | 0.00 | 720.00 |
May | 94.03 | 30.60 | 63.43 | 68.70 | 42.42 | 0.00 | 0.00 | 744.00 |
June | 86.62 | 20.96 | 65.67 | 63.50 | 34.42 | 0.00 | 0.00 | 720.00 |
July | 93.86 | 29.38 | 64.47 | 74.03 | 33.14 | 0.00 | 0.00 | 744.00 |
August | 109.99 | 49.48 | 60.51 | 100.98 | 36.84 | 0.00 | 0.00 | 744.00 |
September | 130.03 | 76.19 | 53.84 | 132.55 | 45.94 | 0.00 | 0.00 | 720.00 |
October | 89.33 | 52.22 | 37.11 | 89.76 | 55.06 | 0.00 | 0.00 | 744.00 |
November | 63.30 | 38.50 | 24.80 | 60.82 | 65.02 | 0.00 | 0.00 | 720.00 |
December | 50.17 | 32.14 | 18.03 | 47.14 | 79.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 87.11 | 41.32 | 45.78 | 77.46 | 53.06 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 50.17 | 15.95 | 18.03 | 37.78 | 33.14 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.03 | 76.19 | 65.67 | 132.55 | 79.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.50 | 46.92 | 25.57 | 69.71 | 70.44 | 0.00 | 0.00 | 744.00 |
February | 88.57 | 54.05 | 34.52 | 83.79 | 68.65 | 0.00 | 0.00 | 672.00 |
March | 54.77 | 15.95 | 38.81 | 37.78 | 57.78 | 0.00 | 0.00 | 744.00 |
April | 113.72 | 51.41 | 62.31 | 102.96 | 48.20 | 0.00 | 0.00 | 720.00 |
May | 94.03 | 30.60 | 63.43 | 68.70 | 42.42 | 0.00 | 0.00 | 744.00 |
June | 86.62 | 20.96 | 65.67 | 63.50 | 34.42 | 0.00 | 0.00 | 720.00 |
July | 93.86 | 29.38 | 64.47 | 74.03 | 33.14 | 0.00 | 0.00 | 744.00 |
August | 109.99 | 49.48 | 60.51 | 100.98 | 36.84 | 0.00 | 0.00 | 744.00 |
September | 130.03 | 76.19 | 53.84 | 132.55 | 45.94 | 0.00 | 0.00 | 720.00 |
October | 89.33 | 52.22 | 37.11 | 89.76 | 55.06 | 0.00 | 0.00 | 744.00 |
November | 63.30 | 38.50 | 24.80 | 60.82 | 65.02 | 0.00 | 0.00 | 720.00 |
December | 50.17 | 32.14 | 18.03 | 47.14 | 79.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 87.11 | 41.32 | 45.78 | 77.46 | 53.06 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 50.17 | 15.95 | 18.03 | 37.78 | 33.14 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.03 | 76.19 | 65.67 | 132.55 | 79.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.81 | 56.18 | 30.62 | 83.54 | 83.72 | 0.00 | 0.00 | 744.00 |
February | 106.05 | 64.72 | 41.34 | 100.41 | 81.53 | 0.00 | 0.00 | 672.00 |
March | 65.58 | 19.10 | 46.47 | 45.36 | 68.67 | 0.00 | 0.00 | 744.00 |
April | 136.16 | 61.55 | 74.61 | 123.36 | 57.30 | 0.00 | 0.00 | 720.00 |
May | 112.59 | 36.64 | 75.95 | 82.40 | 50.37 | 0.00 | 0.00 | 744.00 |
June | 103.72 | 25.10 | 78.63 | 76.14 | 40.90 | 0.00 | 0.00 | 720.00 |
July | 112.38 | 35.18 | 77.20 | 88.71 | 39.39 | 0.00 | 0.00 | 744.00 |
August | 131.70 | 59.24 | 72.46 | 120.93 | 43.83 | 0.00 | 0.00 | 744.00 |
September | 155.70 | 91.23 | 64.46 | 158.71 | 54.64 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.52 | 44.43 | 107.49 | 65.45 | 0.00 | 0.00 | 744.00 |
November | 75.80 | 46.10 | 29.69 | 72.87 | 77.25 | 0.00 | 0.00 | 720.00 |
December | 60.07 | 38.48 | 21.59 | 56.50 | 94.68 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 104.30 | 49.48 | 54.82 | 92.81 | 63.06 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.07 | 19.10 | 21.59 | 45.36 | 39.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 155.70 | 91.23 | 78.63 | 158.71 | 94.68 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.50 | 46.92 | 25.57 | 69.77 | 70.18 | 0.00 | 0.00 | 744.00 |
February | 88.57 | 54.05 | 34.52 | 83.85 | 68.39 | 0.00 | 0.00 | 672.00 |
March | 54.77 | 15.95 | 38.81 | 37.85 | 57.54 | 0.00 | 0.00 | 744.00 |
April | 113.72 | 51.41 | 62.31 | 103.08 | 47.96 | 0.00 | 0.00 | 720.00 |
May | 94.03 | 30.60 | 63.43 | 68.86 | 42.16 | 0.00 | 0.00 | 744.00 |
June | 86.62 | 20.96 | 65.67 | 63.73 | 34.14 | 0.00 | 0.00 | 720.00 |
July | 93.86 | 29.38 | 64.47 | 74.19 | 32.93 | 0.00 | 0.00 | 744.00 |
August | 109.99 | 49.48 | 60.51 | 101.07 | 36.69 | 0.00 | 0.00 | 744.00 |
September | 130.03 | 76.19 | 53.84 | 132.67 | 45.72 | 0.00 | 0.00 | 720.00 |
October | 89.33 | 52.22 | 37.11 | 89.86 | 54.77 | 0.00 | 0.00 | 744.00 |
November | 63.30 | 38.50 | 24.80 | 60.86 | 64.78 | 0.00 | 0.00 | 720.00 |
December | 50.17 | 32.14 | 18.03 | 47.17 | 79.48 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 87.11 | 41.32 | 45.78 | 77.56 | 52.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 50.17 | 15.95 | 18.03 | 37.85 | 32.93 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.03 | 76.19 | 65.67 | 132.67 | 79.48 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.50 | 46.92 | 25.57 | 69.77 | 70.18 | 0.00 | 0.00 | 744.00 |
February | 88.57 | 54.05 | 34.52 | 83.85 | 68.39 | 0.00 | 0.00 | 672.00 |
March | 54.77 | 15.95 | 38.81 | 37.85 | 57.54 | 0.00 | 0.00 | 744.00 |
April | 113.72 | 51.41 | 62.31 | 103.08 | 47.96 | 0.00 | 0.00 | 720.00 |
May | 94.03 | 30.60 | 63.43 | 68.86 | 42.16 | 0.00 | 0.00 | 744.00 |
June | 86.62 | 20.96 | 65.67 | 63.73 | 34.14 | 0.00 | 0.00 | 720.00 |
July | 93.86 | 29.38 | 64.47 | 74.19 | 32.93 | 0.00 | 0.00 | 744.00 |
August | 109.99 | 49.48 | 60.51 | 101.07 | 36.69 | 0.00 | 0.00 | 744.00 |
September | 130.03 | 76.19 | 53.84 | 132.67 | 45.72 | 0.00 | 0.00 | 720.00 |
October | 89.33 | 52.22 | 37.11 | 89.86 | 54.77 | 0.00 | 0.00 | 744.00 |
November | 63.30 | 38.50 | 24.80 | 60.86 | 64.78 | 0.00 | 0.00 | 720.00 |
December | 50.17 | 32.14 | 18.03 | 47.17 | 79.48 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 87.11 | 41.32 | 45.78 | 77.56 | 52.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 50.17 | 15.95 | 18.03 | 37.85 | 32.93 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.03 | 76.19 | 65.67 | 132.67 | 79.48 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.81 | 56.18 | 30.62 | 83.60 | 83.41 | 0.00 | 0.00 | 744.00 |
February | 106.05 | 64.72 | 41.34 | 100.48 | 81.22 | 0.00 | 0.00 | 672.00 |
March | 65.58 | 19.10 | 46.47 | 45.44 | 68.38 | 0.00 | 0.00 | 744.00 |
April | 136.16 | 61.55 | 74.61 | 123.51 | 57.02 | 0.00 | 0.00 | 720.00 |
May | 112.59 | 36.64 | 75.95 | 82.59 | 50.06 | 0.00 | 0.00 | 744.00 |
June | 103.72 | 25.10 | 78.63 | 76.42 | 40.57 | 0.00 | 0.00 | 720.00 |
July | 112.38 | 35.18 | 77.20 | 88.91 | 39.14 | 0.00 | 0.00 | 744.00 |
August | 131.70 | 59.24 | 72.46 | 121.03 | 43.65 | 0.00 | 0.00 | 744.00 |
September | 155.70 | 91.23 | 64.46 | 158.85 | 54.38 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.52 | 44.43 | 107.62 | 65.10 | 0.00 | 0.00 | 744.00 |
November | 75.80 | 46.10 | 29.69 | 72.92 | 76.96 | 0.00 | 0.00 | 720.00 |
December | 60.07 | 38.48 | 21.59 | 56.54 | 94.37 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 104.30 | 49.48 | 54.82 | 92.94 | 62.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.07 | 19.10 | 21.59 | 45.44 | 39.14 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 155.70 | 91.23 | 78.63 | 158.85 | 94.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.50 | 46.92 | 25.57 | 69.93 | 69.31 | 0.00 | 0.00 | 744.00 |
February | 88.57 | 54.05 | 34.52 | 84.05 | 67.48 | 0.00 | 0.00 | 672.00 |
March | 54.77 | 15.95 | 38.81 | 38.04 | 56.72 | 0.00 | 0.00 | 744.00 |
April | 113.72 | 51.41 | 62.31 | 103.39 | 47.23 | 0.00 | 0.00 | 720.00 |
May | 94.03 | 30.60 | 63.43 | 69.30 | 41.33 | 0.00 | 0.00 | 744.00 |
June | 86.62 | 20.96 | 65.67 | 64.42 | 33.25 | 0.00 | 0.00 | 720.00 |
July | 93.86 | 29.38 | 64.47 | 74.67 | 32.26 | 0.00 | 0.00 | 744.00 |
August | 109.99 | 49.48 | 60.51 | 101.32 | 36.18 | 0.00 | 0.00 | 744.00 |
September | 130.03 | 76.19 | 53.84 | 133.12 | 44.88 | 0.00 | 0.00 | 720.00 |
October | 89.33 | 52.22 | 37.11 | 90.16 | 53.90 | 0.00 | 0.00 | 744.00 |
November | 63.30 | 38.50 | 24.80 | 60.99 | 63.98 | 0.00 | 0.00 | 720.00 |
December | 50.17 | 32.14 | 18.03 | 47.28 | 78.57 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 87.11 | 41.32 | 45.78 | 77.87 | 52.02 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 50.17 | 15.95 | 18.03 | 38.04 | 32.26 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.03 | 76.19 | 65.67 | 133.12 | 78.57 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.50 | 46.92 | 25.57 | 69.93 | 69.31 | 0.00 | 0.00 | 744.00 |
February | 88.57 | 54.05 | 34.52 | 84.05 | 67.48 | 0.00 | 0.00 | 672.00 |
March | 54.77 | 15.95 | 38.81 | 38.04 | 56.72 | 0.00 | 0.00 | 744.00 |
April | 113.72 | 51.41 | 62.31 | 103.39 | 47.23 | 0.00 | 0.00 | 720.00 |
May | 94.03 | 30.60 | 63.43 | 69.30 | 41.33 | 0.00 | 0.00 | 744.00 |
June | 86.62 | 20.96 | 65.67 | 64.42 | 33.25 | 0.00 | 0.00 | 720.00 |
July | 93.86 | 29.38 | 64.47 | 74.67 | 32.26 | 0.00 | 0.00 | 744.00 |
August | 109.99 | 49.48 | 60.51 | 101.32 | 36.18 | 0.00 | 0.00 | 744.00 |
September | 130.03 | 76.19 | 53.84 | 133.12 | 44.88 | 0.00 | 0.00 | 720.00 |
October | 89.33 | 52.22 | 37.11 | 90.16 | 53.90 | 0.00 | 0.00 | 744.00 |
November | 63.30 | 38.50 | 24.80 | 60.99 | 63.98 | 0.00 | 0.00 | 720.00 |
December | 50.17 | 32.14 | 18.03 | 47.28 | 78.57 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 87.11 | 41.32 | 45.78 | 77.87 | 52.02 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 50.17 | 15.95 | 18.03 | 38.04 | 32.26 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.03 | 76.19 | 65.67 | 133.12 | 78.57 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.81 | 56.18 | 30.62 | 83.80 | 82.37 | 0.00 | 0.00 | 744.00 |
February | 106.05 | 64.72 | 41.34 | 100.72 | 80.13 | 0.00 | 0.00 | 672.00 |
March | 65.58 | 19.10 | 46.47 | 45.67 | 67.40 | 0.00 | 0.00 | 744.00 |
April | 136.16 | 61.55 | 74.61 | 123.88 | 56.16 | 0.00 | 0.00 | 720.00 |
May | 112.59 | 36.64 | 75.95 | 83.13 | 49.08 | 0.00 | 0.00 | 744.00 |
June | 103.72 | 25.10 | 78.63 | 77.25 | 39.51 | 0.00 | 0.00 | 720.00 |
July | 112.38 | 35.18 | 77.20 | 89.48 | 38.34 | 0.00 | 0.00 | 744.00 |
August | 131.70 | 59.24 | 72.46 | 121.34 | 43.04 | 0.00 | 0.00 | 744.00 |
September | 155.70 | 91.23 | 64.46 | 159.38 | 53.39 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.52 | 44.43 | 107.97 | 64.07 | 0.00 | 0.00 | 744.00 |
November | 75.80 | 46.10 | 29.69 | 73.08 | 76.01 | 0.00 | 0.00 | 720.00 |
December | 60.07 | 38.48 | 21.59 | 56.67 | 93.28 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 104.30 | 49.48 | 54.82 | 93.31 | 61.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.07 | 19.10 | 21.59 | 45.67 | 38.34 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 155.70 | 91.23 | 78.63 | 159.38 | 93.28 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.50 | 46.92 | 25.57 | 70.49 | 66.25 | 0.00 | 0.00 | 744.00 |
February | 88.57 | 54.05 | 34.52 | 84.75 | 64.16 | 0.00 | 0.00 | 672.00 |
March | 54.77 | 15.95 | 38.81 | 38.72 | 53.76 | 0.00 | 0.00 | 744.00 |
April | 113.72 | 51.41 | 62.31 | 104.15 | 44.82 | 0.00 | 0.00 | 720.00 |
May | 94.03 | 30.60 | 63.43 | 70.36 | 38.65 | 0.00 | 0.00 | 744.00 |
June | 86.62 | 20.96 | 65.67 | 65.86 | 30.83 | 0.00 | 0.00 | 720.00 |
July | 93.86 | 29.38 | 64.47 | 75.74 | 30.24 | 0.00 | 0.00 | 744.00 |
August | 109.99 | 49.48 | 60.51 | 102.07 | 34.30 | 0.00 | 0.00 | 744.00 |
September | 130.03 | 76.19 | 53.84 | 134.06 | 42.51 | 0.00 | 0.00 | 720.00 |
October | 89.33 | 52.22 | 37.11 | 90.80 | 51.35 | 0.00 | 0.00 | 744.00 |
November | 63.30 | 38.50 | 24.80 | 61.44 | 61.17 | 0.00 | 0.00 | 720.00 |
December | 50.17 | 32.14 | 18.03 | 47.66 | 75.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 87.11 | 41.32 | 45.78 | 78.66 | 49.36 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 50.17 | 15.95 | 18.03 | 38.72 | 30.24 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.03 | 76.19 | 65.67 | 134.06 | 75.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.50 | 46.92 | 25.57 | 70.49 | 66.25 | 0.00 | 0.00 | 744.00 |
February | 88.57 | 54.05 | 34.52 | 84.75 | 64.16 | 0.00 | 0.00 | 672.00 |
March | 54.77 | 15.95 | 38.81 | 38.72 | 53.76 | 0.00 | 0.00 | 744.00 |
April | 113.72 | 51.41 | 62.31 | 104.15 | 44.82 | 0.00 | 0.00 | 720.00 |
May | 94.03 | 30.60 | 63.43 | 70.36 | 38.65 | 0.00 | 0.00 | 744.00 |
June | 86.62 | 20.96 | 65.67 | 65.86 | 30.83 | 0.00 | 0.00 | 720.00 |
July | 93.86 | 29.38 | 64.47 | 75.74 | 30.24 | 0.00 | 0.00 | 744.00 |
August | 109.99 | 49.48 | 60.51 | 102.07 | 34.30 | 0.00 | 0.00 | 744.00 |
September | 130.03 | 76.19 | 53.84 | 134.06 | 42.51 | 0.00 | 0.00 | 720.00 |
October | 89.33 | 52.22 | 37.11 | 90.80 | 51.35 | 0.00 | 0.00 | 744.00 |
November | 63.30 | 38.50 | 24.80 | 61.44 | 61.17 | 0.00 | 0.00 | 720.00 |
December | 50.17 | 32.14 | 18.03 | 47.66 | 75.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 87.11 | 41.32 | 45.78 | 78.66 | 49.36 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 50.17 | 15.95 | 18.03 | 38.72 | 30.24 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.03 | 76.19 | 65.67 | 134.06 | 75.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.81 | 56.18 | 30.62 | 84.48 | 78.71 | 0.00 | 0.00 | 744.00 |
February | 106.05 | 64.72 | 41.34 | 101.58 | 76.18 | 0.00 | 0.00 | 672.00 |
March | 65.58 | 19.10 | 46.47 | 46.51 | 63.87 | 0.00 | 0.00 | 744.00 |
April | 136.16 | 61.55 | 74.61 | 124.80 | 53.29 | 0.00 | 0.00 | 720.00 |
May | 112.59 | 36.64 | 75.95 | 84.40 | 45.90 | 0.00 | 0.00 | 744.00 |
June | 103.72 | 25.10 | 78.63 | 78.97 | 36.64 | 0.00 | 0.00 | 720.00 |
July | 112.38 | 35.18 | 77.20 | 90.77 | 35.96 | 0.00 | 0.00 | 744.00 |
August | 131.70 | 59.24 | 72.46 | 122.24 | 40.82 | 0.00 | 0.00 | 744.00 |
September | 155.70 | 91.23 | 64.46 | 160.50 | 50.57 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.52 | 44.43 | 108.74 | 61.04 | 0.00 | 0.00 | 744.00 |
November | 75.80 | 46.10 | 29.69 | 73.63 | 72.65 | 0.00 | 0.00 | 720.00 |
December | 60.07 | 38.48 | 21.59 | 57.14 | 89.27 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 104.30 | 49.48 | 54.82 | 94.26 | 58.66 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.07 | 19.10 | 21.59 | 46.51 | 35.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 155.70 | 91.23 | 78.63 | 160.50 | 89.27 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194175E+09 | 0.125679E+09 | 68496261.89 | 0.186229E+09 | 0.193776E+09 |
February | 0.214268E+09 | 0.130753E+09 | 83514726.52 | 0.202377E+09 | 0.169717E+09 |
March | 0.146691E+09 | 42731373.88 | 0.103960E+09 | 0.100845E+09 | 0.158412E+09 |
April | 0.294759E+09 | 0.133243E+09 | 0.161515E+09 | 0.266271E+09 | 0.127380E+09 |
May | 0.251857E+09 | 81970893.54 | 0.169886E+09 | 0.183076E+09 | 0.115896E+09 |
June | 0.224531E+09 | 54325019.07 | 0.170206E+09 | 0.163156E+09 | 91499912.68 |
July | 0.251382E+09 | 78696662.53 | 0.172685E+09 | 0.197556E+09 | 89917598.19 |
August | 0.294602E+09 | 0.132519E+09 | 0.162083E+09 | 0.270560E+09 | 98774554.02 |
September | 0.337041E+09 | 0.197494E+09 | 0.139547E+09 | 0.343365E+09 | 0.120239E+09 |
October | 0.239249E+09 | 0.139853E+09 | 99396061.01 | 0.239873E+09 | 0.150939E+09 |
November | 0.164079E+09 | 99797898.63 | 64280894.52 | 0.157324E+09 | 0.172820E+09 |
December | 0.134365E+09 | 86070827.38 | 48294549.36 | 0.125827E+09 | 0.219305E+09 |
Annual Sum or Average | 0.274700E+10 | 0.130313E+10 | 0.144386E+10 | 0.243646E+10 | 0.170868E+10 |
Minimum of Months | 0.134365E+09 | 42731373.88 | 48294549.36 | 0.100845E+09 | 89917598.19 |
Maximum of Months | 0.337041E+09 | 0.197494E+09 | 0.172685E+09 | 0.343365E+09 | 0.219305E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194175E+09 | 0.125679E+09 | 68496261.89 | 0.186229E+09 | 0.193776E+09 |
February | 0.214268E+09 | 0.130753E+09 | 83514726.52 | 0.202377E+09 | 0.169717E+09 |
March | 0.146691E+09 | 42731373.88 | 0.103960E+09 | 0.100845E+09 | 0.158412E+09 |
April | 0.294759E+09 | 0.133243E+09 | 0.161515E+09 | 0.266271E+09 | 0.127380E+09 |
May | 0.251857E+09 | 81970893.54 | 0.169886E+09 | 0.183076E+09 | 0.115896E+09 |
June | 0.224531E+09 | 54325019.07 | 0.170206E+09 | 0.163156E+09 | 91499912.68 |
July | 0.251382E+09 | 78696662.53 | 0.172685E+09 | 0.197556E+09 | 89917598.19 |
August | 0.294602E+09 | 0.132519E+09 | 0.162083E+09 | 0.270560E+09 | 98774554.02 |
September | 0.337041E+09 | 0.197494E+09 | 0.139547E+09 | 0.343365E+09 | 0.120239E+09 |
October | 0.239249E+09 | 0.139853E+09 | 99396061.01 | 0.239873E+09 | 0.150939E+09 |
November | 0.164079E+09 | 99797898.63 | 64280894.52 | 0.157324E+09 | 0.172820E+09 |
December | 0.134365E+09 | 86070827.38 | 48294549.36 | 0.125827E+09 | 0.219305E+09 |
Annual Sum or Average | 0.274700E+10 | 0.130313E+10 | 0.144386E+10 | 0.243646E+10 | 0.170868E+10 |
Minimum of Months | 0.134365E+09 | 42731373.88 | 48294549.36 | 0.100845E+09 | 89917598.19 |
Maximum of Months | 0.337041E+09 | 0.197494E+09 | 0.172685E+09 | 0.343365E+09 | 0.219305E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194175E+09 | 0.125679E+09 | 68496261.89 | 0.186229E+09 | 0.193776E+09 |
February | 0.214268E+09 | 0.130753E+09 | 83514726.52 | 0.202377E+09 | 0.169717E+09 |
March | 0.146691E+09 | 42731373.88 | 0.103960E+09 | 0.100845E+09 | 0.158412E+09 |
April | 0.294759E+09 | 0.133243E+09 | 0.161515E+09 | 0.266271E+09 | 0.127380E+09 |
May | 0.251857E+09 | 81970893.54 | 0.169886E+09 | 0.183076E+09 | 0.115896E+09 |
June | 0.224531E+09 | 54325019.07 | 0.170206E+09 | 0.163156E+09 | 91499912.68 |
July | 0.251382E+09 | 78696662.53 | 0.172685E+09 | 0.197556E+09 | 89917598.19 |
August | 0.294602E+09 | 0.132519E+09 | 0.162083E+09 | 0.270560E+09 | 98774554.02 |
September | 0.337041E+09 | 0.197494E+09 | 0.139547E+09 | 0.343365E+09 | 0.120239E+09 |
October | 0.239249E+09 | 0.139853E+09 | 99396061.01 | 0.239873E+09 | 0.150939E+09 |
November | 0.164079E+09 | 99797898.63 | 64280894.52 | 0.157324E+09 | 0.172820E+09 |
December | 0.134365E+09 | 86070827.38 | 48294549.36 | 0.125827E+09 | 0.219305E+09 |
Annual Sum or Average | 0.274700E+10 | 0.130313E+10 | 0.144386E+10 | 0.243646E+10 | 0.170868E+10 |
Minimum of Months | 0.134365E+09 | 42731373.88 | 48294549.36 | 0.100845E+09 | 89917598.19 |
Maximum of Months | 0.337041E+09 | 0.197494E+09 | 0.172685E+09 | 0.343365E+09 | 0.219305E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194175E+09 | 0.125679E+09 | 68496261.89 | 0.186229E+09 | 0.193776E+09 |
February | 0.214268E+09 | 0.130753E+09 | 83514726.52 | 0.202377E+09 | 0.169717E+09 |
March | 0.146691E+09 | 42731373.88 | 0.103960E+09 | 0.100845E+09 | 0.158412E+09 |
April | 0.294759E+09 | 0.133243E+09 | 0.161515E+09 | 0.266271E+09 | 0.127380E+09 |
May | 0.251857E+09 | 81970893.54 | 0.169886E+09 | 0.183076E+09 | 0.115896E+09 |
June | 0.224531E+09 | 54325019.07 | 0.170206E+09 | 0.163156E+09 | 91499912.68 |
July | 0.251382E+09 | 78696662.53 | 0.172685E+09 | 0.197556E+09 | 89917598.19 |
August | 0.294602E+09 | 0.132519E+09 | 0.162083E+09 | 0.270560E+09 | 98774554.02 |
September | 0.337041E+09 | 0.197494E+09 | 0.139547E+09 | 0.343365E+09 | 0.120239E+09 |
October | 0.239249E+09 | 0.139853E+09 | 99396061.01 | 0.239873E+09 | 0.150939E+09 |
November | 0.164079E+09 | 99797898.63 | 64280894.52 | 0.157324E+09 | 0.172820E+09 |
December | 0.134365E+09 | 86070827.38 | 48294549.36 | 0.125827E+09 | 0.219305E+09 |
Annual Sum or Average | 0.274700E+10 | 0.130313E+10 | 0.144386E+10 | 0.243646E+10 | 0.170868E+10 |
Minimum of Months | 0.134365E+09 | 42731373.88 | 48294549.36 | 0.100845E+09 | 89917598.19 |
Maximum of Months | 0.337041E+09 | 0.197494E+09 | 0.172685E+09 | 0.343365E+09 | 0.219305E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233776E+09 | 0.151311E+09 | 82465894.25 | 0.224325E+09 | 0.231684E+09 |
February | 0.257967E+09 | 0.157420E+09 | 0.100547E+09 | 0.243800E+09 | 0.202787E+09 |
March | 0.176609E+09 | 51446325.14 | 0.125162E+09 | 0.121688E+09 | 0.189400E+09 |
April | 0.354874E+09 | 0.160418E+09 | 0.194456E+09 | 0.320721E+09 | 0.152379E+09 |
May | 0.303222E+09 | 98688641.56 | 0.204534E+09 | 0.220732E+09 | 0.138486E+09 |
June | 0.270323E+09 | 65404463.74 | 0.204919E+09 | 0.196667E+09 | 0.109400E+09 |
July | 0.302651E+09 | 94746639.76 | 0.207904E+09 | 0.237983E+09 | 0.107550E+09 |
August | 0.354685E+09 | 0.159546E+09 | 0.195140E+09 | 0.325732E+09 | 0.118237E+09 |
September | 0.405780E+09 | 0.237773E+09 | 0.168007E+09 | 0.413306E+09 | 0.143894E+09 |
October | 0.288043E+09 | 0.168375E+09 | 0.119668E+09 | 0.288781E+09 | 0.180529E+09 |
November | 0.197542E+09 | 0.120151E+09 | 77390813.79 | 0.189487E+09 | 0.206588E+09 |
December | 0.161769E+09 | 0.103625E+09 | 58144095.62 | 0.151607E+09 | 0.261962E+09 |
Annual Sum or Average | 0.330724E+10 | 0.156890E+10 | 0.173834E+10 | 0.293483E+10 | 0.204290E+10 |
Minimum of Months | 0.161769E+09 | 51446325.14 | 58144095.62 | 0.121688E+09 | 0.107550E+09 |
Maximum of Months | 0.405780E+09 | 0.237773E+09 | 0.207904E+09 | 0.413306E+09 | 0.261962E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233776E+09 | 0.151311E+09 | 82465894.25 | 0.224325E+09 | 0.231684E+09 |
February | 0.257967E+09 | 0.157420E+09 | 0.100547E+09 | 0.243800E+09 | 0.202787E+09 |
March | 0.176609E+09 | 51446325.14 | 0.125162E+09 | 0.121688E+09 | 0.189400E+09 |
April | 0.354874E+09 | 0.160418E+09 | 0.194456E+09 | 0.320721E+09 | 0.152379E+09 |
May | 0.303222E+09 | 98688641.56 | 0.204534E+09 | 0.220732E+09 | 0.138486E+09 |
June | 0.270323E+09 | 65404463.74 | 0.204919E+09 | 0.196667E+09 | 0.109400E+09 |
July | 0.302651E+09 | 94746639.76 | 0.207904E+09 | 0.237983E+09 | 0.107550E+09 |
August | 0.354685E+09 | 0.159546E+09 | 0.195140E+09 | 0.325732E+09 | 0.118237E+09 |
September | 0.405780E+09 | 0.237773E+09 | 0.168007E+09 | 0.413306E+09 | 0.143894E+09 |
October | 0.288043E+09 | 0.168375E+09 | 0.119668E+09 | 0.288781E+09 | 0.180529E+09 |
November | 0.197542E+09 | 0.120151E+09 | 77390813.79 | 0.189487E+09 | 0.206588E+09 |
December | 0.161769E+09 | 0.103625E+09 | 58144095.62 | 0.151607E+09 | 0.261962E+09 |
Annual Sum or Average | 0.330724E+10 | 0.156890E+10 | 0.173834E+10 | 0.293483E+10 | 0.204290E+10 |
Minimum of Months | 0.161769E+09 | 51446325.14 | 58144095.62 | 0.121688E+09 | 0.107550E+09 |
Maximum of Months | 0.405780E+09 | 0.237773E+09 | 0.207904E+09 | 0.413306E+09 | 0.261962E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194175E+09 | 0.125679E+09 | 68496261.89 | 0.184490E+09 | 0.203553E+09 |
February | 0.214268E+09 | 0.130753E+09 | 83514726.52 | 0.200575E+09 | 0.178782E+09 |
March | 0.146691E+09 | 42731373.88 | 0.103960E+09 | 98788008.47 | 0.168012E+09 |
April | 0.294759E+09 | 0.133243E+09 | 0.161515E+09 | 0.260975E+09 | 0.138527E+09 |
May | 0.251857E+09 | 81970893.54 | 0.169886E+09 | 0.177201E+09 | 0.127244E+09 |
June | 0.224531E+09 | 54325019.07 | 0.170206E+09 | 0.158505E+09 | 97691625.46 |
July | 0.251382E+09 | 78696662.53 | 0.172685E+09 | 0.195094E+09 | 93607094.14 |
August | 0.294602E+09 | 0.132519E+09 | 0.162083E+09 | 0.269329E+09 | 0.101250E+09 |
September | 0.337041E+09 | 0.197494E+09 | 0.139547E+09 | 0.340950E+09 | 0.124991E+09 |
October | 0.239249E+09 | 0.139853E+09 | 99396061.01 | 0.235707E+09 | 0.164180E+09 |
November | 0.164079E+09 | 99797898.63 | 64280894.52 | 0.155697E+09 | 0.183092E+09 |
December | 0.134365E+09 | 86070827.38 | 48294549.36 | 0.124643E+09 | 0.230092E+09 |
Annual Sum or Average | 0.274700E+10 | 0.130313E+10 | 0.144386E+10 | 0.240195E+10 | 0.181102E+10 |
Minimum of Months | 0.134365E+09 | 42731373.88 | 48294549.36 | 98788008.47 | 93607094.14 |
Maximum of Months | 0.337041E+09 | 0.197494E+09 | 0.172685E+09 | 0.340950E+09 | 0.230092E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194175E+09 | 0.125679E+09 | 68496261.89 | 0.184490E+09 | 0.203553E+09 |
February | 0.214268E+09 | 0.130753E+09 | 83514726.52 | 0.200575E+09 | 0.178782E+09 |
March | 0.146691E+09 | 42731373.88 | 0.103960E+09 | 98788008.47 | 0.168012E+09 |
April | 0.294759E+09 | 0.133243E+09 | 0.161515E+09 | 0.260975E+09 | 0.138527E+09 |
May | 0.251857E+09 | 81970893.54 | 0.169886E+09 | 0.177201E+09 | 0.127244E+09 |
June | 0.224531E+09 | 54325019.07 | 0.170206E+09 | 0.158505E+09 | 97691625.46 |
July | 0.251382E+09 | 78696662.53 | 0.172685E+09 | 0.195094E+09 | 93607094.14 |
August | 0.294602E+09 | 0.132519E+09 | 0.162083E+09 | 0.269329E+09 | 0.101250E+09 |
September | 0.337041E+09 | 0.197494E+09 | 0.139547E+09 | 0.340950E+09 | 0.124991E+09 |
October | 0.239249E+09 | 0.139853E+09 | 99396061.01 | 0.235707E+09 | 0.164180E+09 |
November | 0.164079E+09 | 99797898.63 | 64280894.52 | 0.155697E+09 | 0.183092E+09 |
December | 0.134365E+09 | 86070827.38 | 48294549.36 | 0.124643E+09 | 0.230092E+09 |
Annual Sum or Average | 0.274700E+10 | 0.130313E+10 | 0.144386E+10 | 0.240195E+10 | 0.181102E+10 |
Minimum of Months | 0.134365E+09 | 42731373.88 | 48294549.36 | 98788008.47 | 93607094.14 |
Maximum of Months | 0.337041E+09 | 0.197494E+09 | 0.172685E+09 | 0.340950E+09 | 0.230092E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233776E+09 | 0.151311E+09 | 82465894.25 | 0.222225E+09 | 0.243320E+09 |
February | 0.257967E+09 | 0.157420E+09 | 0.100547E+09 | 0.241621E+09 | 0.213546E+09 |
March | 0.176609E+09 | 51446325.14 | 0.125162E+09 | 0.119192E+09 | 0.200815E+09 |
April | 0.354874E+09 | 0.160418E+09 | 0.194456E+09 | 0.314382E+09 | 0.165620E+09 |
May | 0.303222E+09 | 98688641.56 | 0.204534E+09 | 0.213698E+09 | 0.151923E+09 |
June | 0.270323E+09 | 65404463.74 | 0.204919E+09 | 0.191102E+09 | 0.116746E+09 |
July | 0.302651E+09 | 94746639.76 | 0.207904E+09 | 0.235031E+09 | 0.111923E+09 |
August | 0.354685E+09 | 0.159546E+09 | 0.195140E+09 | 0.324249E+09 | 0.121177E+09 |
September | 0.405780E+09 | 0.237773E+09 | 0.168007E+09 | 0.410417E+09 | 0.149536E+09 |
October | 0.288043E+09 | 0.168375E+09 | 0.119668E+09 | 0.283808E+09 | 0.196254E+09 |
November | 0.197542E+09 | 0.120151E+09 | 77390813.79 | 0.187532E+09 | 0.218774E+09 |
December | 0.161769E+09 | 0.103625E+09 | 58144095.62 | 0.150177E+09 | 0.274781E+09 |
Annual Sum or Average | 0.330724E+10 | 0.156890E+10 | 0.173834E+10 | 0.289344E+10 | 0.216442E+10 |
Minimum of Months | 0.161769E+09 | 51446325.14 | 58144095.62 | 0.119192E+09 | 0.111923E+09 |
Maximum of Months | 0.405780E+09 | 0.237773E+09 | 0.207904E+09 | 0.410417E+09 | 0.274781E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194175E+09 | 0.125679E+09 | 68496261.89 | 0.185196E+09 | 0.198018E+09 |
February | 0.214268E+09 | 0.130753E+09 | 83514726.52 | 0.201197E+09 | 0.174025E+09 |
March | 0.146691E+09 | 42731373.88 | 0.103960E+09 | 99432822.63 | 0.163152E+09 |
April | 0.294759E+09 | 0.133243E+09 | 0.161515E+09 | 0.261819E+09 | 0.135938E+09 |
May | 0.251857E+09 | 81970893.54 | 0.169886E+09 | 0.178028E+09 | 0.125144E+09 |
June | 0.224531E+09 | 54325019.07 | 0.170206E+09 | 0.158424E+09 | 98965200.96 |
July | 0.251382E+09 | 78696662.53 | 0.172685E+09 | 0.194911E+09 | 95480650.25 |
August | 0.294602E+09 | 0.132519E+09 | 0.162083E+09 | 0.269287E+09 | 0.103387E+09 |
September | 0.337041E+09 | 0.197494E+09 | 0.139547E+09 | 0.341047E+09 | 0.126456E+09 |
October | 0.239249E+09 | 0.139853E+09 | 99396061.01 | 0.236350E+09 | 0.160877E+09 |
November | 0.164079E+09 | 99797898.63 | 64280894.52 | 0.156360E+09 | 0.177360E+09 |
December | 0.134365E+09 | 86070827.38 | 48294549.36 | 0.125143E+09 | 0.224208E+09 |
Annual Sum or Average | 0.274700E+10 | 0.130313E+10 | 0.144386E+10 | 0.240719E+10 | 0.178301E+10 |
Minimum of Months | 0.134365E+09 | 42731373.88 | 48294549.36 | 99432822.63 | 95480650.25 |
Maximum of Months | 0.337041E+09 | 0.197494E+09 | 0.172685E+09 | 0.341047E+09 | 0.224208E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194175E+09 | 0.125679E+09 | 68496261.89 | 0.185196E+09 | 0.198018E+09 |
February | 0.214268E+09 | 0.130753E+09 | 83514726.52 | 0.201197E+09 | 0.174025E+09 |
March | 0.146691E+09 | 42731373.88 | 0.103960E+09 | 99432822.63 | 0.163152E+09 |
April | 0.294759E+09 | 0.133243E+09 | 0.161515E+09 | 0.261819E+09 | 0.135938E+09 |
May | 0.251857E+09 | 81970893.54 | 0.169886E+09 | 0.178028E+09 | 0.125144E+09 |
June | 0.224531E+09 | 54325019.07 | 0.170206E+09 | 0.158424E+09 | 98965200.96 |
July | 0.251382E+09 | 78696662.53 | 0.172685E+09 | 0.194911E+09 | 95480650.25 |
August | 0.294602E+09 | 0.132519E+09 | 0.162083E+09 | 0.269287E+09 | 0.103387E+09 |
September | 0.337041E+09 | 0.197494E+09 | 0.139547E+09 | 0.341047E+09 | 0.126456E+09 |
October | 0.239249E+09 | 0.139853E+09 | 99396061.01 | 0.236350E+09 | 0.160877E+09 |
November | 0.164079E+09 | 99797898.63 | 64280894.52 | 0.156360E+09 | 0.177360E+09 |
December | 0.134365E+09 | 86070827.38 | 48294549.36 | 0.125143E+09 | 0.224208E+09 |
Annual Sum or Average | 0.274700E+10 | 0.130313E+10 | 0.144386E+10 | 0.240719E+10 | 0.178301E+10 |
Minimum of Months | 0.134365E+09 | 42731373.88 | 48294549.36 | 99432822.63 | 95480650.25 |
Maximum of Months | 0.337041E+09 | 0.197494E+09 | 0.172685E+09 | 0.341047E+09 | 0.224208E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.232499E+09 | 0.150484E+09 | 82015260.95 | 0.221866E+09 | 0.235419E+09 |
February | 0.256557E+09 | 0.156559E+09 | 99997896.23 | 0.241056E+09 | 0.206742E+09 |
March | 0.175644E+09 | 51165197.68 | 0.124479E+09 | 0.119324E+09 | 0.193953E+09 |
April | 0.352935E+09 | 0.159541E+09 | 0.193393E+09 | 0.313673E+09 | 0.161628E+09 |
May | 0.301565E+09 | 98149359.37 | 0.203416E+09 | 0.213516E+09 | 0.148597E+09 |
June | 0.268846E+09 | 65047062.30 | 0.203799E+09 | 0.189959E+09 | 0.117568E+09 |
July | 0.300997E+09 | 94228898.56 | 0.206768E+09 | 0.233533E+09 | 0.113471E+09 |
August | 0.352747E+09 | 0.158674E+09 | 0.194073E+09 | 0.322430E+09 | 0.122986E+09 |
September | 0.403563E+09 | 0.236474E+09 | 0.167089E+09 | 0.408293E+09 | 0.150398E+09 |
October | 0.286469E+09 | 0.167455E+09 | 0.119014E+09 | 0.283024E+09 | 0.191259E+09 |
November | 0.196463E+09 | 0.119495E+09 | 76967913.17 | 0.187306E+09 | 0.210790E+09 |
December | 0.160885E+09 | 0.103058E+09 | 57826368.32 | 0.149962E+09 | 0.266303E+09 |
Annual Sum or Average | 0.328917E+10 | 0.156033E+10 | 0.172884E+10 | 0.288394E+10 | 0.211911E+10 |
Minimum of Months | 0.160885E+09 | 51165197.68 | 57826368.32 | 0.119324E+09 | 0.113471E+09 |
Maximum of Months | 0.403563E+09 | 0.236474E+09 | 0.206768E+09 | 0.408293E+09 | 0.266303E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194175E+09 | 0.125679E+09 | 68496261.89 | 0.185561E+09 | 0.195583E+09 |
February | 0.214268E+09 | 0.130753E+09 | 83514726.52 | 0.201521E+09 | 0.172003E+09 |
March | 0.146691E+09 | 42731373.88 | 0.103960E+09 | 99813467.14 | 0.161035E+09 |
April | 0.294759E+09 | 0.133243E+09 | 0.161515E+09 | 0.262797E+09 | 0.133576E+09 |
May | 0.251857E+09 | 81970893.54 | 0.169886E+09 | 0.179103E+09 | 0.122833E+09 |
June | 0.224531E+09 | 54325019.07 | 0.170206E+09 | 0.158967E+09 | 97853699.72 |
July | 0.251382E+09 | 78696662.53 | 0.172685E+09 | 0.195219E+09 | 94740240.67 |
August | 0.294602E+09 | 0.132519E+09 | 0.162083E+09 | 0.269434E+09 | 0.102891E+09 |
September | 0.337041E+09 | 0.197494E+09 | 0.139547E+09 | 0.341296E+09 | 0.125589E+09 |
October | 0.239249E+09 | 0.139853E+09 | 99396061.01 | 0.237009E+09 | 0.158157E+09 |
November | 0.164079E+09 | 99797898.63 | 64280894.52 | 0.156689E+09 | 0.174926E+09 |
December | 0.134365E+09 | 86070827.38 | 48294549.36 | 0.125385E+09 | 0.221673E+09 |
Annual Sum or Average | 0.274700E+10 | 0.130313E+10 | 0.144386E+10 | 0.241279E+10 | 0.176086E+10 |
Minimum of Months | 0.134365E+09 | 42731373.88 | 48294549.36 | 99813467.14 | 94740240.67 |
Maximum of Months | 0.337041E+09 | 0.197494E+09 | 0.172685E+09 | 0.341296E+09 | 0.221673E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194175E+09 | 0.125679E+09 | 68496261.89 | 0.185561E+09 | 0.195583E+09 |
February | 0.214268E+09 | 0.130753E+09 | 83514726.52 | 0.201521E+09 | 0.172003E+09 |
March | 0.146691E+09 | 42731373.88 | 0.103960E+09 | 99813467.14 | 0.161035E+09 |
April | 0.294759E+09 | 0.133243E+09 | 0.161515E+09 | 0.262797E+09 | 0.133576E+09 |
May | 0.251857E+09 | 81970893.54 | 0.169886E+09 | 0.179103E+09 | 0.122833E+09 |
June | 0.224531E+09 | 54325019.07 | 0.170206E+09 | 0.158967E+09 | 97853699.72 |
July | 0.251382E+09 | 78696662.53 | 0.172685E+09 | 0.195219E+09 | 94740240.67 |
August | 0.294602E+09 | 0.132519E+09 | 0.162083E+09 | 0.269434E+09 | 0.102891E+09 |
September | 0.337041E+09 | 0.197494E+09 | 0.139547E+09 | 0.341296E+09 | 0.125589E+09 |
October | 0.239249E+09 | 0.139853E+09 | 99396061.01 | 0.237009E+09 | 0.158157E+09 |
November | 0.164079E+09 | 99797898.63 | 64280894.52 | 0.156689E+09 | 0.174926E+09 |
December | 0.134365E+09 | 86070827.38 | 48294549.36 | 0.125385E+09 | 0.221673E+09 |
Annual Sum or Average | 0.274700E+10 | 0.130313E+10 | 0.144386E+10 | 0.241279E+10 | 0.176086E+10 |
Minimum of Months | 0.134365E+09 | 42731373.88 | 48294549.36 | 99813467.14 | 94740240.67 |
Maximum of Months | 0.337041E+09 | 0.197494E+09 | 0.172685E+09 | 0.341296E+09 | 0.221673E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.232499E+09 | 0.150484E+09 | 82015260.95 | 0.222309E+09 | 0.232511E+09 |
February | 0.256557E+09 | 0.156559E+09 | 99997896.23 | 0.241451E+09 | 0.204332E+09 |
March | 0.175644E+09 | 51165197.68 | 0.124479E+09 | 0.119787E+09 | 0.191427E+09 |
April | 0.352935E+09 | 0.159541E+09 | 0.193393E+09 | 0.314845E+09 | 0.158818E+09 |
May | 0.301565E+09 | 98149359.37 | 0.203416E+09 | 0.214804E+09 | 0.145852E+09 |
June | 0.268846E+09 | 65047062.30 | 0.203799E+09 | 0.190612E+09 | 0.116248E+09 |
July | 0.300997E+09 | 94228898.56 | 0.206768E+09 | 0.233904E+09 | 0.112591E+09 |
August | 0.352747E+09 | 0.158674E+09 | 0.194073E+09 | 0.322608E+09 | 0.122397E+09 |
September | 0.403563E+09 | 0.236474E+09 | 0.167089E+09 | 0.408593E+09 | 0.149366E+09 |
October | 0.286469E+09 | 0.167455E+09 | 0.119014E+09 | 0.283813E+09 | 0.188021E+09 |
November | 0.196463E+09 | 0.119495E+09 | 76967913.17 | 0.187705E+09 | 0.207886E+09 |
December | 0.160885E+09 | 0.103058E+09 | 57826368.32 | 0.150257E+09 | 0.263278E+09 |
Annual Sum or Average | 0.328917E+10 | 0.156033E+10 | 0.172884E+10 | 0.289069E+10 | 0.209273E+10 |
Minimum of Months | 0.160885E+09 | 51165197.68 | 57826368.32 | 0.119787E+09 | 0.112591E+09 |
Maximum of Months | 0.403563E+09 | 0.236474E+09 | 0.206768E+09 | 0.408593E+09 | 0.263278E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194175E+09 | 0.125679E+09 | 68496261.89 | 0.185950E+09 | 0.193616E+09 |
February | 0.214268E+09 | 0.130753E+09 | 83514726.52 | 0.201894E+09 | 0.170364E+09 |
March | 0.146691E+09 | 42731373.88 | 0.103960E+09 | 0.100270E+09 | 0.159280E+09 |
April | 0.294759E+09 | 0.133243E+09 | 0.161515E+09 | 0.264305E+09 | 0.130797E+09 |
May | 0.251857E+09 | 81970893.54 | 0.169886E+09 | 0.180851E+09 | 0.119858E+09 |
June | 0.224531E+09 | 54325019.07 | 0.170206E+09 | 0.160608E+09 | 95425382.21 |
July | 0.251382E+09 | 78696662.53 | 0.172685E+09 | 0.196158E+09 | 93132957.46 |
August | 0.294602E+09 | 0.132519E+09 | 0.162083E+09 | 0.269874E+09 | 0.101852E+09 |
September | 0.337041E+09 | 0.197494E+09 | 0.139547E+09 | 0.342027E+09 | 0.123831E+09 |
October | 0.239249E+09 | 0.139853E+09 | 99396061.01 | 0.238168E+09 | 0.154702E+09 |
November | 0.164079E+09 | 99797898.63 | 64280894.52 | 0.157030E+09 | 0.173019E+09 |
December | 0.134365E+09 | 86070827.38 | 48294549.36 | 0.125673E+09 | 0.219437E+09 |
Annual Sum or Average | 0.274700E+10 | 0.130313E+10 | 0.144386E+10 | 0.242281E+10 | 0.173532E+10 |
Minimum of Months | 0.134365E+09 | 42731373.88 | 48294549.36 | 0.100270E+09 | 93132957.46 |
Maximum of Months | 0.337041E+09 | 0.197494E+09 | 0.172685E+09 | 0.342027E+09 | 0.219437E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194175E+09 | 0.125679E+09 | 68496261.89 | 0.185950E+09 | 0.193616E+09 |
February | 0.214268E+09 | 0.130753E+09 | 83514726.52 | 0.201894E+09 | 0.170364E+09 |
March | 0.146691E+09 | 42731373.88 | 0.103960E+09 | 0.100270E+09 | 0.159280E+09 |
April | 0.294759E+09 | 0.133243E+09 | 0.161515E+09 | 0.264305E+09 | 0.130797E+09 |
May | 0.251857E+09 | 81970893.54 | 0.169886E+09 | 0.180851E+09 | 0.119858E+09 |
June | 0.224531E+09 | 54325019.07 | 0.170206E+09 | 0.160608E+09 | 95425382.21 |
July | 0.251382E+09 | 78696662.53 | 0.172685E+09 | 0.196158E+09 | 93132957.46 |
August | 0.294602E+09 | 0.132519E+09 | 0.162083E+09 | 0.269874E+09 | 0.101852E+09 |
September | 0.337041E+09 | 0.197494E+09 | 0.139547E+09 | 0.342027E+09 | 0.123831E+09 |
October | 0.239249E+09 | 0.139853E+09 | 99396061.01 | 0.238168E+09 | 0.154702E+09 |
November | 0.164079E+09 | 99797898.63 | 64280894.52 | 0.157030E+09 | 0.173019E+09 |
December | 0.134365E+09 | 86070827.38 | 48294549.36 | 0.125673E+09 | 0.219437E+09 |
Annual Sum or Average | 0.274700E+10 | 0.130313E+10 | 0.144386E+10 | 0.242281E+10 | 0.173532E+10 |
Minimum of Months | 0.134365E+09 | 42731373.88 | 48294549.36 | 0.100270E+09 | 93132957.46 |
Maximum of Months | 0.337041E+09 | 0.197494E+09 | 0.172685E+09 | 0.342027E+09 | 0.219437E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.232499E+09 | 0.150484E+09 | 82015260.95 | 0.222782E+09 | 0.230161E+09 |
February | 0.256557E+09 | 0.156559E+09 | 99997896.23 | 0.241905E+09 | 0.202378E+09 |
March | 0.175644E+09 | 51165197.68 | 0.124479E+09 | 0.120343E+09 | 0.189335E+09 |
April | 0.352935E+09 | 0.159541E+09 | 0.193393E+09 | 0.316650E+09 | 0.155517E+09 |
May | 0.301565E+09 | 98149359.37 | 0.203416E+09 | 0.216898E+09 | 0.142327E+09 |
June | 0.268846E+09 | 65047062.30 | 0.203799E+09 | 0.192580E+09 | 0.113369E+09 |
July | 0.300997E+09 | 94228898.56 | 0.206768E+09 | 0.235034E+09 | 0.110687E+09 |
August | 0.352747E+09 | 0.158674E+09 | 0.194073E+09 | 0.323142E+09 | 0.121166E+09 |
September | 0.403563E+09 | 0.236474E+09 | 0.167089E+09 | 0.409476E+09 | 0.147279E+09 |
October | 0.286469E+09 | 0.167455E+09 | 0.119014E+09 | 0.285200E+09 | 0.183914E+09 |
November | 0.196463E+09 | 0.119495E+09 | 76967913.17 | 0.188118E+09 | 0.205612E+09 |
December | 0.160885E+09 | 0.103058E+09 | 57826368.32 | 0.150607E+09 | 0.260607E+09 |
Annual Sum or Average | 0.328917E+10 | 0.156033E+10 | 0.172884E+10 | 0.290273E+10 | 0.206235E+10 |
Minimum of Months | 0.160885E+09 | 51165197.68 | 57826368.32 | 0.120343E+09 | 0.110687E+09 |
Maximum of Months | 0.403563E+09 | 0.236474E+09 | 0.206768E+09 | 0.409476E+09 | 0.260607E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194175E+09 | 0.125679E+09 | 68496261.89 | 0.187029E+09 | 0.188548E+09 |
February | 0.214268E+09 | 0.130753E+09 | 83514726.52 | 0.203007E+09 | 0.165889E+09 |
March | 0.146691E+09 | 42731373.88 | 0.103960E+09 | 0.101461E+09 | 0.154819E+09 |
April | 0.294759E+09 | 0.133243E+09 | 0.161515E+09 | 0.267180E+09 | 0.125139E+09 |
May | 0.251857E+09 | 81970893.54 | 0.169886E+09 | 0.184388E+09 | 0.113594E+09 |
June | 0.224531E+09 | 54325019.07 | 0.170206E+09 | 0.165258E+09 | 89019375.51 |
July | 0.251382E+09 | 78696662.53 | 0.172685E+09 | 0.198634E+09 | 88784721.71 |
August | 0.294602E+09 | 0.132519E+09 | 0.162083E+09 | 0.270645E+09 | 98853587.79 |
September | 0.337041E+09 | 0.197494E+09 | 0.139547E+09 | 0.344437E+09 | 0.118566E+09 |
October | 0.239249E+09 | 0.139853E+09 | 99396061.01 | 0.240920E+09 | 0.147456E+09 |
November | 0.164079E+09 | 99797898.63 | 64280894.52 | 0.157879E+09 | 0.168410E+09 |
December | 0.134365E+09 | 86070827.38 | 48294549.36 | 0.126488E+09 | 0.212970E+09 |
Annual Sum or Average | 0.274700E+10 | 0.130313E+10 | 0.144386E+10 | 0.244733E+10 | 0.167205E+10 |
Minimum of Months | 0.134365E+09 | 42731373.88 | 48294549.36 | 0.101461E+09 | 88784721.71 |
Maximum of Months | 0.337041E+09 | 0.197494E+09 | 0.172685E+09 | 0.344437E+09 | 0.212970E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194175E+09 | 0.125679E+09 | 68496261.89 | 0.187029E+09 | 0.188548E+09 |
February | 0.214268E+09 | 0.130753E+09 | 83514726.52 | 0.203007E+09 | 0.165889E+09 |
March | 0.146691E+09 | 42731373.88 | 0.103960E+09 | 0.101461E+09 | 0.154819E+09 |
April | 0.294759E+09 | 0.133243E+09 | 0.161515E+09 | 0.267180E+09 | 0.125139E+09 |
May | 0.251857E+09 | 81970893.54 | 0.169886E+09 | 0.184388E+09 | 0.113594E+09 |
June | 0.224531E+09 | 54325019.07 | 0.170206E+09 | 0.165258E+09 | 89019375.51 |
July | 0.251382E+09 | 78696662.53 | 0.172685E+09 | 0.198634E+09 | 88784721.71 |
August | 0.294602E+09 | 0.132519E+09 | 0.162083E+09 | 0.270645E+09 | 98853587.79 |
September | 0.337041E+09 | 0.197494E+09 | 0.139547E+09 | 0.344437E+09 | 0.118566E+09 |
October | 0.239249E+09 | 0.139853E+09 | 99396061.01 | 0.240920E+09 | 0.147456E+09 |
November | 0.164079E+09 | 99797898.63 | 64280894.52 | 0.157879E+09 | 0.168410E+09 |
December | 0.134365E+09 | 86070827.38 | 48294549.36 | 0.126488E+09 | 0.212970E+09 |
Annual Sum or Average | 0.274700E+10 | 0.130313E+10 | 0.144386E+10 | 0.244733E+10 | 0.167205E+10 |
Minimum of Months | 0.134365E+09 | 42731373.88 | 48294549.36 | 0.101461E+09 | 88784721.71 |
Maximum of Months | 0.337041E+09 | 0.197494E+09 | 0.172685E+09 | 0.344437E+09 | 0.212970E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194175E+09 | 0.125679E+09 | 68496261.89 | 0.187029E+09 | 0.188548E+09 |
February | 0.214268E+09 | 0.130753E+09 | 83514726.52 | 0.203007E+09 | 0.165889E+09 |
March | 0.146691E+09 | 42731373.88 | 0.103960E+09 | 0.101461E+09 | 0.154819E+09 |
April | 0.294759E+09 | 0.133243E+09 | 0.161515E+09 | 0.267180E+09 | 0.125139E+09 |
May | 0.251857E+09 | 81970893.54 | 0.169886E+09 | 0.184388E+09 | 0.113594E+09 |
June | 0.224531E+09 | 54325019.07 | 0.170206E+09 | 0.165258E+09 | 89019375.51 |
July | 0.251382E+09 | 78696662.53 | 0.172685E+09 | 0.198634E+09 | 88784721.71 |
August | 0.294602E+09 | 0.132519E+09 | 0.162083E+09 | 0.270645E+09 | 98853587.79 |
September | 0.337041E+09 | 0.197494E+09 | 0.139547E+09 | 0.344437E+09 | 0.118566E+09 |
October | 0.239249E+09 | 0.139853E+09 | 99396061.01 | 0.240920E+09 | 0.147456E+09 |
November | 0.164079E+09 | 99797898.63 | 64280894.52 | 0.157879E+09 | 0.168410E+09 |
December | 0.134365E+09 | 86070827.38 | 48294549.36 | 0.126488E+09 | 0.212970E+09 |
Annual Sum or Average | 0.274700E+10 | 0.130313E+10 | 0.144386E+10 | 0.244733E+10 | 0.167205E+10 |
Minimum of Months | 0.134365E+09 | 42731373.88 | 48294549.36 | 0.101461E+09 | 88784721.71 |
Maximum of Months | 0.337041E+09 | 0.197494E+09 | 0.172685E+09 | 0.344437E+09 | 0.212970E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194175E+09 | 0.125679E+09 | 68496261.89 | 0.187029E+09 | 0.188548E+09 |
February | 0.214268E+09 | 0.130753E+09 | 83514726.52 | 0.203007E+09 | 0.165889E+09 |
March | 0.146691E+09 | 42731373.88 | 0.103960E+09 | 0.101461E+09 | 0.154819E+09 |
April | 0.294759E+09 | 0.133243E+09 | 0.161515E+09 | 0.267180E+09 | 0.125139E+09 |
May | 0.251857E+09 | 81970893.54 | 0.169886E+09 | 0.184388E+09 | 0.113594E+09 |
June | 0.224531E+09 | 54325019.07 | 0.170206E+09 | 0.165258E+09 | 89019375.51 |
July | 0.251382E+09 | 78696662.53 | 0.172685E+09 | 0.198634E+09 | 88784721.71 |
August | 0.294602E+09 | 0.132519E+09 | 0.162083E+09 | 0.270645E+09 | 98853587.79 |
September | 0.337041E+09 | 0.197494E+09 | 0.139547E+09 | 0.344437E+09 | 0.118566E+09 |
October | 0.239249E+09 | 0.139853E+09 | 99396061.01 | 0.240920E+09 | 0.147456E+09 |
November | 0.164079E+09 | 99797898.63 | 64280894.52 | 0.157879E+09 | 0.168410E+09 |
December | 0.134365E+09 | 86070827.38 | 48294549.36 | 0.126488E+09 | 0.212970E+09 |
Annual Sum or Average | 0.274700E+10 | 0.130313E+10 | 0.144386E+10 | 0.244733E+10 | 0.167205E+10 |
Minimum of Months | 0.134365E+09 | 42731373.88 | 48294549.36 | 0.101461E+09 | 88784721.71 |
Maximum of Months | 0.337041E+09 | 0.197494E+09 | 0.172685E+09 | 0.344437E+09 | 0.212970E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.232499E+09 | 0.150484E+09 | 82015260.95 | 0.224089E+09 | 0.224115E+09 |
February | 0.256557E+09 | 0.156559E+09 | 99997896.23 | 0.243248E+09 | 0.197054E+09 |
March | 0.175644E+09 | 51165197.68 | 0.124479E+09 | 0.121796E+09 | 0.184015E+09 |
April | 0.352935E+09 | 0.159541E+09 | 0.193393E+09 | 0.320089E+09 | 0.148804E+09 |
May | 0.301565E+09 | 98149359.37 | 0.203416E+09 | 0.221124E+09 | 0.134923E+09 |
June | 0.268846E+09 | 65047062.30 | 0.203799E+09 | 0.198125E+09 | 0.105796E+09 |
July | 0.300997E+09 | 94228898.56 | 0.206768E+09 | 0.238003E+09 | 0.105545E+09 |
August | 0.352747E+09 | 0.158674E+09 | 0.194073E+09 | 0.324087E+09 | 0.117614E+09 |
September | 0.403563E+09 | 0.236474E+09 | 0.167089E+09 | 0.412350E+09 | 0.141044E+09 |
October | 0.286469E+09 | 0.167455E+09 | 0.119014E+09 | 0.288476E+09 | 0.175307E+09 |
November | 0.196463E+09 | 0.119495E+09 | 76967913.17 | 0.189142E+09 | 0.200120E+09 |
December | 0.160885E+09 | 0.103058E+09 | 57826368.32 | 0.151595E+09 | 0.252912E+09 |
Annual Sum or Average | 0.328917E+10 | 0.156033E+10 | 0.172884E+10 | 0.293212E+10 | 0.198725E+10 |
Minimum of Months | 0.160885E+09 | 51165197.68 | 57826368.32 | 0.121796E+09 | 0.105545E+09 |
Maximum of Months | 0.403563E+09 | 0.236474E+09 | 0.206768E+09 | 0.412350E+09 | 0.252912E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.232499E+09 | 0.150484E+09 | 82015260.95 | 0.224089E+09 | 0.224115E+09 |
February | 0.256557E+09 | 0.156559E+09 | 99997896.23 | 0.243248E+09 | 0.197054E+09 |
March | 0.175644E+09 | 51165197.68 | 0.124479E+09 | 0.121796E+09 | 0.184015E+09 |
April | 0.352935E+09 | 0.159541E+09 | 0.193393E+09 | 0.320089E+09 | 0.148804E+09 |
May | 0.301565E+09 | 98149359.37 | 0.203416E+09 | 0.221124E+09 | 0.134923E+09 |
June | 0.268846E+09 | 65047062.30 | 0.203799E+09 | 0.198125E+09 | 0.105796E+09 |
July | 0.300997E+09 | 94228898.56 | 0.206768E+09 | 0.238003E+09 | 0.105545E+09 |
August | 0.352747E+09 | 0.158674E+09 | 0.194073E+09 | 0.324087E+09 | 0.117614E+09 |
September | 0.403563E+09 | 0.236474E+09 | 0.167089E+09 | 0.412350E+09 | 0.141044E+09 |
October | 0.286469E+09 | 0.167455E+09 | 0.119014E+09 | 0.288476E+09 | 0.175307E+09 |
November | 0.196463E+09 | 0.119495E+09 | 76967913.17 | 0.189142E+09 | 0.200120E+09 |
December | 0.160885E+09 | 0.103058E+09 | 57826368.32 | 0.151595E+09 | 0.252912E+09 |
Annual Sum or Average | 0.328917E+10 | 0.156033E+10 | 0.172884E+10 | 0.293212E+10 | 0.198725E+10 |
Minimum of Months | 0.160885E+09 | 51165197.68 | 57826368.32 | 0.121796E+09 | 0.105545E+09 |
Maximum of Months | 0.403563E+09 | 0.236474E+09 | 0.206768E+09 | 0.412350E+09 | 0.252912E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194175E+09 | 0.125679E+09 | 68496261.89 | 0.186721E+09 | 0.188674E+09 |
February | 0.214268E+09 | 0.130753E+09 | 83514726.52 | 0.202697E+09 | 0.166076E+09 |
March | 0.146691E+09 | 42731373.88 | 0.103960E+09 | 0.101194E+09 | 0.154767E+09 |
April | 0.294759E+09 | 0.133243E+09 | 0.161515E+09 | 0.266873E+09 | 0.124930E+09 |
May | 0.251857E+09 | 81970893.54 | 0.169886E+09 | 0.184005E+09 | 0.113618E+09 |
June | 0.224531E+09 | 54325019.07 | 0.170206E+09 | 0.164581E+09 | 89227728.19 |
July | 0.251382E+09 | 78696662.53 | 0.172685E+09 | 0.198283E+09 | 88763929.43 |
August | 0.294602E+09 | 0.132519E+09 | 0.162083E+09 | 0.270469E+09 | 98673308.85 |
September | 0.337041E+09 | 0.197494E+09 | 0.139547E+09 | 0.343575E+09 | 0.119089E+09 |
October | 0.239249E+09 | 0.139853E+09 | 99396061.01 | 0.240411E+09 | 0.147479E+09 |
November | 0.164079E+09 | 99797898.63 | 64280894.52 | 0.157642E+09 | 0.168536E+09 |
December | 0.134365E+09 | 86070827.38 | 48294549.36 | 0.126247E+09 | 0.213589E+09 |
Annual Sum or Average | 0.274700E+10 | 0.130313E+10 | 0.144386E+10 | 0.244270E+10 | 0.167342E+10 |
Minimum of Months | 0.134365E+09 | 42731373.88 | 48294549.36 | 0.101194E+09 | 88763929.43 |
Maximum of Months | 0.337041E+09 | 0.197494E+09 | 0.172685E+09 | 0.343575E+09 | 0.213589E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194175E+09 | 0.125679E+09 | 68496261.89 | 0.186721E+09 | 0.188674E+09 |
February | 0.214268E+09 | 0.130753E+09 | 83514726.52 | 0.202697E+09 | 0.166076E+09 |
March | 0.146691E+09 | 42731373.88 | 0.103960E+09 | 0.101194E+09 | 0.154767E+09 |
April | 0.294759E+09 | 0.133243E+09 | 0.161515E+09 | 0.266873E+09 | 0.124930E+09 |
May | 0.251857E+09 | 81970893.54 | 0.169886E+09 | 0.184005E+09 | 0.113618E+09 |
June | 0.224531E+09 | 54325019.07 | 0.170206E+09 | 0.164581E+09 | 89227728.19 |
July | 0.251382E+09 | 78696662.53 | 0.172685E+09 | 0.198283E+09 | 88763929.43 |
August | 0.294602E+09 | 0.132519E+09 | 0.162083E+09 | 0.270469E+09 | 98673308.85 |
September | 0.337041E+09 | 0.197494E+09 | 0.139547E+09 | 0.343575E+09 | 0.119089E+09 |
October | 0.239249E+09 | 0.139853E+09 | 99396061.01 | 0.240411E+09 | 0.147479E+09 |
November | 0.164079E+09 | 99797898.63 | 64280894.52 | 0.157642E+09 | 0.168536E+09 |
December | 0.134365E+09 | 86070827.38 | 48294549.36 | 0.126247E+09 | 0.213589E+09 |
Annual Sum or Average | 0.274700E+10 | 0.130313E+10 | 0.144386E+10 | 0.244270E+10 | 0.167342E+10 |
Minimum of Months | 0.134365E+09 | 42731373.88 | 48294549.36 | 0.101194E+09 | 88763929.43 |
Maximum of Months | 0.337041E+09 | 0.197494E+09 | 0.172685E+09 | 0.343575E+09 | 0.213589E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.232499E+09 | 0.150484E+09 | 82015260.95 | 0.223743E+09 | 0.224235E+09 |
February | 0.256557E+09 | 0.156559E+09 | 99997896.23 | 0.242901E+09 | 0.197243E+09 |
March | 0.175644E+09 | 51165197.68 | 0.124479E+09 | 0.121497E+09 | 0.183931E+09 |
April | 0.352935E+09 | 0.159541E+09 | 0.193393E+09 | 0.319758E+09 | 0.148534E+09 |
May | 0.301565E+09 | 98149359.37 | 0.203416E+09 | 0.220703E+09 | 0.134919E+09 |
June | 0.268846E+09 | 65047062.30 | 0.203799E+09 | 0.197358E+09 | 0.106017E+09 |
July | 0.300997E+09 | 94228898.56 | 0.206768E+09 | 0.237613E+09 | 0.105500E+09 |
August | 0.352747E+09 | 0.158674E+09 | 0.194073E+09 | 0.323902E+09 | 0.117383E+09 |
September | 0.403563E+09 | 0.236474E+09 | 0.167089E+09 | 0.411363E+09 | 0.141638E+09 |
October | 0.286469E+09 | 0.167455E+09 | 0.119014E+09 | 0.287903E+09 | 0.175304E+09 |
November | 0.196463E+09 | 0.119495E+09 | 76967913.17 | 0.188878E+09 | 0.200235E+09 |
December | 0.160885E+09 | 0.103058E+09 | 57826368.32 | 0.151322E+09 | 0.253597E+09 |
Annual Sum or Average | 0.328917E+10 | 0.156033E+10 | 0.172884E+10 | 0.292694E+10 | 0.198854E+10 |
Minimum of Months | 0.160885E+09 | 51165197.68 | 57826368.32 | 0.121497E+09 | 0.105500E+09 |
Maximum of Months | 0.403563E+09 | 0.236474E+09 | 0.206768E+09 | 0.411363E+09 | 0.253597E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194175E+09 | 0.125679E+09 | 68496261.89 | 0.186869E+09 | 0.187975E+09 |
February | 0.214268E+09 | 0.130753E+09 | 83514726.52 | 0.202854E+09 | 0.165439E+09 |
March | 0.146691E+09 | 42731373.88 | 0.103960E+09 | 0.101369E+09 | 0.154120E+09 |
April | 0.294759E+09 | 0.133243E+09 | 0.161515E+09 | 0.267186E+09 | 0.124318E+09 |
May | 0.251857E+09 | 81970893.54 | 0.169886E+09 | 0.184430E+09 | 0.112916E+09 |
June | 0.224531E+09 | 54325019.07 | 0.170206E+09 | 0.165183E+09 | 88497063.90 |
July | 0.251382E+09 | 78696662.53 | 0.172685E+09 | 0.198715E+09 | 88200347.14 |
August | 0.294602E+09 | 0.132519E+09 | 0.162083E+09 | 0.270697E+09 | 98267661.07 |
September | 0.337041E+09 | 0.197494E+09 | 0.139547E+09 | 0.343893E+09 | 0.118518E+09 |
October | 0.239249E+09 | 0.139853E+09 | 99396061.01 | 0.240694E+09 | 0.146699E+09 |
November | 0.164079E+09 | 99797898.63 | 64280894.52 | 0.157758E+09 | 0.167900E+09 |
December | 0.134365E+09 | 86070827.38 | 48294549.36 | 0.126340E+09 | 0.212888E+09 |
Annual Sum or Average | 0.274700E+10 | 0.130313E+10 | 0.144386E+10 | 0.244599E+10 | 0.166574E+10 |
Minimum of Months | 0.134365E+09 | 42731373.88 | 48294549.36 | 0.101369E+09 | 88200347.14 |
Maximum of Months | 0.337041E+09 | 0.197494E+09 | 0.172685E+09 | 0.343893E+09 | 0.212888E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194175E+09 | 0.125679E+09 | 68496261.89 | 0.186869E+09 | 0.187975E+09 |
February | 0.214268E+09 | 0.130753E+09 | 83514726.52 | 0.202854E+09 | 0.165439E+09 |
March | 0.146691E+09 | 42731373.88 | 0.103960E+09 | 0.101369E+09 | 0.154120E+09 |
April | 0.294759E+09 | 0.133243E+09 | 0.161515E+09 | 0.267186E+09 | 0.124318E+09 |
May | 0.251857E+09 | 81970893.54 | 0.169886E+09 | 0.184430E+09 | 0.112916E+09 |
June | 0.224531E+09 | 54325019.07 | 0.170206E+09 | 0.165183E+09 | 88497063.90 |
July | 0.251382E+09 | 78696662.53 | 0.172685E+09 | 0.198715E+09 | 88200347.14 |
August | 0.294602E+09 | 0.132519E+09 | 0.162083E+09 | 0.270697E+09 | 98267661.07 |
September | 0.337041E+09 | 0.197494E+09 | 0.139547E+09 | 0.343893E+09 | 0.118518E+09 |
October | 0.239249E+09 | 0.139853E+09 | 99396061.01 | 0.240694E+09 | 0.146699E+09 |
November | 0.164079E+09 | 99797898.63 | 64280894.52 | 0.157758E+09 | 0.167900E+09 |
December | 0.134365E+09 | 86070827.38 | 48294549.36 | 0.126340E+09 | 0.212888E+09 |
Annual Sum or Average | 0.274700E+10 | 0.130313E+10 | 0.144386E+10 | 0.244599E+10 | 0.166574E+10 |
Minimum of Months | 0.134365E+09 | 42731373.88 | 48294549.36 | 0.101369E+09 | 88200347.14 |
Maximum of Months | 0.337041E+09 | 0.197494E+09 | 0.172685E+09 | 0.343893E+09 | 0.212888E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.232499E+09 | 0.150484E+09 | 82015260.95 | 0.223923E+09 | 0.223400E+09 |
February | 0.256557E+09 | 0.156559E+09 | 99997896.23 | 0.243091E+09 | 0.196481E+09 |
March | 0.175644E+09 | 51165197.68 | 0.124479E+09 | 0.121710E+09 | 0.183159E+09 |
April | 0.352935E+09 | 0.159541E+09 | 0.193393E+09 | 0.320135E+09 | 0.147807E+09 |
May | 0.301565E+09 | 98149359.37 | 0.203416E+09 | 0.221214E+09 | 0.134085E+09 |
June | 0.268846E+09 | 65047062.30 | 0.203799E+09 | 0.198079E+09 | 0.105150E+09 |
July | 0.300997E+09 | 94228898.56 | 0.206768E+09 | 0.238131E+09 | 0.104830E+09 |
August | 0.352747E+09 | 0.158674E+09 | 0.194073E+09 | 0.324177E+09 | 0.116900E+09 |
September | 0.403563E+09 | 0.236474E+09 | 0.167089E+09 | 0.411744E+09 | 0.140959E+09 |
October | 0.286469E+09 | 0.167455E+09 | 0.119014E+09 | 0.288242E+09 | 0.174374E+09 |
November | 0.196463E+09 | 0.119495E+09 | 76967913.17 | 0.189019E+09 | 0.199474E+09 |
December | 0.160885E+09 | 0.103058E+09 | 57826368.32 | 0.151436E+09 | 0.252759E+09 |
Annual Sum or Average | 0.328917E+10 | 0.156033E+10 | 0.172884E+10 | 0.293090E+10 | 0.197938E+10 |
Minimum of Months | 0.160885E+09 | 51165197.68 | 57826368.32 | 0.121710E+09 | 0.104830E+09 |
Maximum of Months | 0.403563E+09 | 0.236474E+09 | 0.206768E+09 | 0.411744E+09 | 0.252759E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194175E+09 | 0.125679E+09 | 68496261.89 | 0.187298E+09 | 0.185650E+09 |
February | 0.214268E+09 | 0.130753E+09 | 83514726.52 | 0.203333E+09 | 0.163242E+09 |
March | 0.146691E+09 | 42731373.88 | 0.103960E+09 | 0.101876E+09 | 0.151913E+09 |
April | 0.294759E+09 | 0.133243E+09 | 0.161515E+09 | 0.267988E+09 | 0.122432E+09 |
May | 0.251857E+09 | 81970893.54 | 0.169886E+09 | 0.185624E+09 | 0.110695E+09 |
June | 0.224531E+09 | 54325019.07 | 0.170206E+09 | 0.166983E+09 | 86175359.21 |
July | 0.251382E+09 | 78696662.53 | 0.172685E+09 | 0.199991E+09 | 86399643.13 |
August | 0.294602E+09 | 0.132519E+09 | 0.162083E+09 | 0.271374E+09 | 96893882.65 |
September | 0.337041E+09 | 0.197494E+09 | 0.139547E+09 | 0.345040E+09 | 0.116336E+09 |
October | 0.239249E+09 | 0.139853E+09 | 99396061.01 | 0.241480E+09 | 0.144362E+09 |
November | 0.164079E+09 | 99797898.63 | 64280894.52 | 0.158098E+09 | 0.165833E+09 |
December | 0.134365E+09 | 86070827.38 | 48294549.36 | 0.126636E+09 | 0.210432E+09 |
Annual Sum or Average | 0.274700E+10 | 0.130313E+10 | 0.144386E+10 | 0.245572E+10 | 0.164036E+10 |
Minimum of Months | 0.134365E+09 | 42731373.88 | 48294549.36 | 0.101876E+09 | 86175359.21 |
Maximum of Months | 0.337041E+09 | 0.197494E+09 | 0.172685E+09 | 0.345040E+09 | 0.210432E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194175E+09 | 0.125679E+09 | 68496261.89 | 0.187298E+09 | 0.185650E+09 |
February | 0.214268E+09 | 0.130753E+09 | 83514726.52 | 0.203333E+09 | 0.163242E+09 |
March | 0.146691E+09 | 42731373.88 | 0.103960E+09 | 0.101876E+09 | 0.151913E+09 |
April | 0.294759E+09 | 0.133243E+09 | 0.161515E+09 | 0.267988E+09 | 0.122432E+09 |
May | 0.251857E+09 | 81970893.54 | 0.169886E+09 | 0.185624E+09 | 0.110695E+09 |
June | 0.224531E+09 | 54325019.07 | 0.170206E+09 | 0.166983E+09 | 86175359.21 |
July | 0.251382E+09 | 78696662.53 | 0.172685E+09 | 0.199991E+09 | 86399643.13 |
August | 0.294602E+09 | 0.132519E+09 | 0.162083E+09 | 0.271374E+09 | 96893882.65 |
September | 0.337041E+09 | 0.197494E+09 | 0.139547E+09 | 0.345040E+09 | 0.116336E+09 |
October | 0.239249E+09 | 0.139853E+09 | 99396061.01 | 0.241480E+09 | 0.144362E+09 |
November | 0.164079E+09 | 99797898.63 | 64280894.52 | 0.158098E+09 | 0.165833E+09 |
December | 0.134365E+09 | 86070827.38 | 48294549.36 | 0.126636E+09 | 0.210432E+09 |
Annual Sum or Average | 0.274700E+10 | 0.130313E+10 | 0.144386E+10 | 0.245572E+10 | 0.164036E+10 |
Minimum of Months | 0.134365E+09 | 42731373.88 | 48294549.36 | 0.101876E+09 | 86175359.21 |
Maximum of Months | 0.337041E+09 | 0.197494E+09 | 0.172685E+09 | 0.345040E+09 | 0.210432E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.232499E+09 | 0.150484E+09 | 82015260.95 | 0.224445E+09 | 0.220626E+09 |
February | 0.256557E+09 | 0.156559E+09 | 99997896.23 | 0.243674E+09 | 0.193863E+09 |
March | 0.175644E+09 | 51165197.68 | 0.124479E+09 | 0.122328E+09 | 0.180527E+09 |
April | 0.352935E+09 | 0.159541E+09 | 0.193393E+09 | 0.321102E+09 | 0.145565E+09 |
May | 0.301565E+09 | 98149359.37 | 0.203416E+09 | 0.222650E+09 | 0.131455E+09 |
June | 0.268846E+09 | 65047062.30 | 0.203799E+09 | 0.200229E+09 | 0.102399E+09 |
July | 0.300997E+09 | 94228898.56 | 0.206768E+09 | 0.239658E+09 | 0.102698E+09 |
August | 0.352747E+09 | 0.158674E+09 | 0.194073E+09 | 0.324993E+09 | 0.115273E+09 |
September | 0.403563E+09 | 0.236474E+09 | 0.167089E+09 | 0.413116E+09 | 0.138375E+09 |
October | 0.286469E+09 | 0.167455E+09 | 0.119014E+09 | 0.289185E+09 | 0.171595E+09 |
November | 0.196463E+09 | 0.119495E+09 | 76967913.17 | 0.189432E+09 | 0.197011E+09 |
December | 0.160885E+09 | 0.103058E+09 | 57826368.32 | 0.151795E+09 | 0.249832E+09 |
Annual Sum or Average | 0.328917E+10 | 0.156033E+10 | 0.172884E+10 | 0.294261E+10 | 0.194922E+10 |
Minimum of Months | 0.160885E+09 | 51165197.68 | 57826368.32 | 0.122328E+09 | 0.102399E+09 |
Maximum of Months | 0.403563E+09 | 0.236474E+09 | 0.206768E+09 | 0.413116E+09 | 0.249832E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194175E+09 | 0.125679E+09 | 68496261.89 | 0.188807E+09 | 0.177444E+09 |
February | 0.214268E+09 | 0.130753E+09 | 83514726.52 | 0.205025E+09 | 0.155212E+09 |
March | 0.146691E+09 | 42731373.88 | 0.103960E+09 | 0.103708E+09 | 0.143987E+09 |
April | 0.294759E+09 | 0.133243E+09 | 0.161515E+09 | 0.269956E+09 | 0.116184E+09 |
May | 0.251857E+09 | 81970893.54 | 0.169886E+09 | 0.188449E+09 | 0.103507E+09 |
June | 0.224531E+09 | 54325019.07 | 0.170206E+09 | 0.170712E+09 | 79902795.60 |
July | 0.251382E+09 | 78696662.53 | 0.172685E+09 | 0.202873E+09 | 80994215.08 |
August | 0.294602E+09 | 0.132519E+09 | 0.162083E+09 | 0.273384E+09 | 91867651.95 |
September | 0.337041E+09 | 0.197494E+09 | 0.139547E+09 | 0.347472E+09 | 0.110176E+09 |
October | 0.239249E+09 | 0.139853E+09 | 99396061.01 | 0.243194E+09 | 0.137542E+09 |
November | 0.164079E+09 | 99797898.63 | 64280894.52 | 0.159257E+09 | 0.158541E+09 |
December | 0.134365E+09 | 86070827.38 | 48294549.36 | 0.127663E+09 | 0.201416E+09 |
Annual Sum or Average | 0.274700E+10 | 0.130313E+10 | 0.144386E+10 | 0.248050E+10 | 0.155677E+10 |
Minimum of Months | 0.134365E+09 | 42731373.88 | 48294549.36 | 0.103708E+09 | 79902795.60 |
Maximum of Months | 0.337041E+09 | 0.197494E+09 | 0.172685E+09 | 0.347472E+09 | 0.201416E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194175E+09 | 0.125679E+09 | 68496261.89 | 0.188807E+09 | 0.177444E+09 |
February | 0.214268E+09 | 0.130753E+09 | 83514726.52 | 0.205025E+09 | 0.155212E+09 |
March | 0.146691E+09 | 42731373.88 | 0.103960E+09 | 0.103708E+09 | 0.143987E+09 |
April | 0.294759E+09 | 0.133243E+09 | 0.161515E+09 | 0.269956E+09 | 0.116184E+09 |
May | 0.251857E+09 | 81970893.54 | 0.169886E+09 | 0.188449E+09 | 0.103507E+09 |
June | 0.224531E+09 | 54325019.07 | 0.170206E+09 | 0.170712E+09 | 79902795.60 |
July | 0.251382E+09 | 78696662.53 | 0.172685E+09 | 0.202873E+09 | 80994215.08 |
August | 0.294602E+09 | 0.132519E+09 | 0.162083E+09 | 0.273384E+09 | 91867651.95 |
September | 0.337041E+09 | 0.197494E+09 | 0.139547E+09 | 0.347472E+09 | 0.110176E+09 |
October | 0.239249E+09 | 0.139853E+09 | 99396061.01 | 0.243194E+09 | 0.137542E+09 |
November | 0.164079E+09 | 99797898.63 | 64280894.52 | 0.159257E+09 | 0.158541E+09 |
December | 0.134365E+09 | 86070827.38 | 48294549.36 | 0.127663E+09 | 0.201416E+09 |
Annual Sum or Average | 0.274700E+10 | 0.130313E+10 | 0.144386E+10 | 0.248050E+10 | 0.155677E+10 |
Minimum of Months | 0.134365E+09 | 42731373.88 | 48294549.36 | 0.103708E+09 | 79902795.60 |
Maximum of Months | 0.337041E+09 | 0.197494E+09 | 0.172685E+09 | 0.347472E+09 | 0.201416E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.232499E+09 | 0.150484E+09 | 82015260.95 | 0.226285E+09 | 0.210830E+09 |
February | 0.256557E+09 | 0.156559E+09 | 99997896.23 | 0.245736E+09 | 0.184296E+09 |
March | 0.175644E+09 | 51165197.68 | 0.124479E+09 | 0.124562E+09 | 0.171069E+09 |
April | 0.352935E+09 | 0.159541E+09 | 0.193393E+09 | 0.323486E+09 | 0.138133E+09 |
May | 0.301565E+09 | 98149359.37 | 0.203416E+09 | 0.226059E+09 | 0.122946E+09 |
June | 0.268846E+09 | 65047062.30 | 0.203799E+09 | 0.204688E+09 | 94973601.68 |
July | 0.300997E+09 | 94228898.56 | 0.206768E+09 | 0.243111E+09 | 96303961.58 |
August | 0.352747E+09 | 0.158674E+09 | 0.194073E+09 | 0.327410E+09 | 0.109319E+09 |
September | 0.403563E+09 | 0.236474E+09 | 0.167089E+09 | 0.416024E+09 | 0.131073E+09 |
October | 0.286469E+09 | 0.167455E+09 | 0.119014E+09 | 0.291250E+09 | 0.163481E+09 |
November | 0.196463E+09 | 0.119495E+09 | 76967913.17 | 0.190842E+09 | 0.188321E+09 |
December | 0.160885E+09 | 0.103058E+09 | 57826368.32 | 0.153046E+09 | 0.239088E+09 |
Annual Sum or Average | 0.328917E+10 | 0.156033E+10 | 0.172884E+10 | 0.297250E+10 | 0.184983E+10 |
Minimum of Months | 0.160885E+09 | 51165197.68 | 57826368.32 | 0.124562E+09 | 94973601.68 |
Maximum of Months | 0.403563E+09 | 0.236474E+09 | 0.206768E+09 | 0.416024E+09 | 0.239088E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 445.63 | 462.39 | 464.55 | 300.68 | 163.87 | 0.00 | 0.00 |
February | 536.17 | 448.26 | 567.55 | 346.33 | 221.21 | 0.00 | 0.00 |
March | 241.47 | 378.00 | 350.95 | 102.23 | 248.72 | 0.00 | 0.00 |
April | 658.38 | 314.15 | 728.70 | 329.40 | 399.30 | 0.00 | 0.00 |
May | 438.23 | 276.49 | 602.55 | 196.11 | 406.44 | 0.00 | 0.00 |
June | 403.53 | 225.62 | 555.08 | 134.30 | 420.78 | 0.00 | 0.00 |
July | 472.74 | 214.59 | 601.41 | 188.28 | 413.14 | 0.00 | 0.00 |
August | 647.29 | 235.80 | 704.82 | 317.04 | 387.77 | 0.00 | 0.00 |
September | 848.79 | 296.58 | 833.23 | 488.24 | 344.99 | 0.00 | 0.00 |
October | 573.87 | 360.22 | 572.39 | 334.59 | 237.80 | 0.00 | 0.00 |
November | 388.99 | 426.10 | 405.63 | 246.72 | 158.91 | 0.00 | 0.00 |
December | 301.12 | 523.13 | 321.46 | 205.92 | 115.54 | 0.00 | 0.00 |
Annual Sum or Average | 495.16 | 346.29 | 558.17 | 264.79 | 293.38 | 0.00 | 0.00 |
Minimum of Months | 241.47 | 214.59 | 321.46 | 102.23 | 115.54 | 0.00 | 0.00 |
Maximum of Months | 848.79 | 523.13 | 833.23 | 488.24 | 420.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 220.73 | 242.84 | 232.28 | 150.34 | 81.94 | 0.00 | 0.00 |
February | 265.70 | 236.07 | 283.77 | 173.17 | 110.61 | 0.00 | 0.00 |
March | 118.27 | 200.43 | 175.47 | 51.12 | 124.36 | 0.00 | 0.00 |
April | 322.66 | 170.79 | 364.35 | 164.70 | 199.65 | 0.00 | 0.00 |
May | 212.10 | 151.74 | 301.28 | 98.05 | 203.22 | 0.00 | 0.00 |
June | 196.03 | 120.42 | 277.54 | 67.15 | 210.39 | 0.00 | 0.00 |
July | 233.43 | 111.69 | 300.71 | 94.14 | 206.57 | 0.00 | 0.00 |
August | 322.17 | 120.85 | 352.41 | 158.52 | 193.89 | 0.00 | 0.00 |
September | 421.42 | 154.14 | 416.61 | 244.12 | 172.49 | 0.00 | 0.00 |
October | 281.97 | 195.87 | 286.19 | 167.29 | 118.90 | 0.00 | 0.00 |
November | 192.49 | 225.68 | 202.82 | 123.36 | 79.46 | 0.00 | 0.00 |
December | 149.14 | 274.40 | 160.73 | 102.96 | 57.77 | 0.00 | 0.00 |
Annual Sum or Average | 244.08 | 183.49 | 279.09 | 132.39 | 146.69 | 0.00 | 0.00 |
Minimum of Months | 118.27 | 111.69 | 160.73 | 51.12 | 57.77 | 0.00 | 0.00 |
Maximum of Months | 421.42 | 274.40 | 416.61 | 244.12 | 210.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 221.12 | 235.76 | 231.80 | 150.03 | 81.77 | 0.00 | 0.00 |
February | 265.98 | 229.33 | 283.19 | 172.81 | 110.38 | 0.00 | 0.00 |
March | 118.80 | 194.24 | 175.11 | 51.01 | 124.10 | 0.00 | 0.00 |
April | 323.04 | 167.25 | 363.60 | 164.36 | 199.24 | 0.00 | 0.00 |
May | 212.65 | 148.93 | 300.66 | 97.85 | 202.80 | 0.00 | 0.00 |
June | 195.53 | 121.72 | 276.97 | 67.01 | 209.96 | 0.00 | 0.00 |
July | 232.73 | 113.66 | 300.09 | 93.94 | 206.14 | 0.00 | 0.00 |
August | 321.46 | 123.12 | 351.68 | 158.20 | 193.49 | 0.00 | 0.00 |
September | 420.67 | 155.60 | 415.76 | 243.62 | 172.14 | 0.00 | 0.00 |
October | 282.15 | 191.54 | 285.61 | 166.95 | 118.66 | 0.00 | 0.00 |
November | 192.91 | 218.18 | 202.40 | 123.11 | 79.29 | 0.00 | 0.00 |
December | 149.44 | 266.85 | 160.40 | 102.75 | 57.65 | 0.00 | 0.00 |
Annual Sum or Average | 244.11 | 180.27 | 278.51 | 132.12 | 146.39 | 0.00 | 0.00 |
Minimum of Months | 118.80 | 113.66 | 160.40 | 51.01 | 57.65 | 0.00 | 0.00 |
Maximum of Months | 420.67 | 266.85 | 415.76 | 243.62 | 209.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 221.56 | 232.85 | 231.80 | 150.03 | 81.77 | 0.00 | 0.00 |
February | 266.41 | 226.66 | 283.19 | 172.81 | 110.38 | 0.00 | 0.00 |
March | 119.26 | 191.72 | 175.11 | 51.01 | 124.10 | 0.00 | 0.00 |
April | 324.24 | 164.34 | 363.60 | 164.36 | 199.24 | 0.00 | 0.00 |
May | 213.94 | 146.18 | 300.66 | 97.85 | 202.80 | 0.00 | 0.00 |
June | 196.20 | 120.35 | 276.97 | 67.01 | 209.96 | 0.00 | 0.00 |
July | 233.10 | 112.78 | 300.09 | 93.94 | 206.14 | 0.00 | 0.00 |
August | 321.64 | 122.53 | 351.68 | 158.20 | 193.49 | 0.00 | 0.00 |
September | 420.98 | 154.53 | 415.76 | 243.62 | 172.14 | 0.00 | 0.00 |
October | 282.94 | 188.30 | 285.61 | 166.95 | 118.66 | 0.00 | 0.00 |
November | 193.32 | 215.18 | 202.40 | 123.11 | 79.29 | 0.00 | 0.00 |
December | 149.73 | 263.82 | 160.40 | 102.75 | 57.65 | 0.00 | 0.00 |
Annual Sum or Average | 244.68 | 178.03 | 278.51 | 132.12 | 146.39 | 0.00 | 0.00 |
Minimum of Months | 119.26 | 112.78 | 160.40 | 51.01 | 57.65 | 0.00 | 0.00 |
Maximum of Months | 420.98 | 263.82 | 415.76 | 243.62 | 209.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 222.03 | 230.51 | 231.80 | 150.03 | 81.77 | 0.00 | 0.00 |
February | 266.90 | 224.50 | 283.19 | 172.81 | 110.38 | 0.00 | 0.00 |
March | 119.80 | 189.63 | 175.11 | 51.01 | 124.10 | 0.00 | 0.00 |
April | 326.10 | 160.92 | 363.60 | 164.36 | 199.24 | 0.00 | 0.00 |
May | 216.02 | 142.64 | 300.66 | 97.85 | 202.80 | 0.00 | 0.00 |
June | 198.22 | 117.37 | 276.97 | 67.01 | 209.96 | 0.00 | 0.00 |
July | 234.23 | 110.87 | 300.09 | 93.94 | 206.14 | 0.00 | 0.00 |
August | 322.17 | 121.29 | 351.68 | 158.20 | 193.49 | 0.00 | 0.00 |
September | 421.89 | 152.37 | 415.76 | 243.62 | 172.14 | 0.00 | 0.00 |
October | 284.32 | 184.18 | 285.61 | 166.95 | 118.66 | 0.00 | 0.00 |
November | 193.74 | 212.83 | 202.40 | 123.11 | 79.29 | 0.00 | 0.00 |
December | 150.07 | 261.16 | 160.40 | 102.75 | 57.65 | 0.00 | 0.00 |
Annual Sum or Average | 245.70 | 175.45 | 278.51 | 132.12 | 146.39 | 0.00 | 0.00 |
Minimum of Months | 119.80 | 110.87 | 160.40 | 51.01 | 57.65 | 0.00 | 0.00 |
Maximum of Months | 421.89 | 261.16 | 415.76 | 243.62 | 209.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 446.64 | 448.93 | 463.60 | 300.06 | 163.54 | 0.00 | 0.00 |
February | 536.76 | 437.20 | 566.38 | 345.62 | 220.76 | 0.00 | 0.00 |
March | 242.47 | 368.62 | 350.23 | 102.02 | 248.21 | 0.00 | 0.00 |
April | 659.30 | 307.93 | 727.20 | 328.73 | 398.48 | 0.00 | 0.00 |
May | 440.49 | 270.39 | 601.31 | 195.71 | 405.61 | 0.00 | 0.00 |
June | 407.90 | 219.01 | 553.94 | 134.03 | 419.92 | 0.00 | 0.00 |
July | 474.37 | 211.41 | 600.18 | 187.89 | 412.29 | 0.00 | 0.00 |
August | 646.19 | 235.45 | 703.37 | 316.39 | 386.98 | 0.00 | 0.00 |
September | 849.71 | 291.80 | 831.52 | 487.24 | 344.28 | 0.00 | 0.00 |
October | 575.21 | 351.12 | 571.21 | 333.90 | 237.31 | 0.00 | 0.00 |
November | 389.58 | 414.30 | 404.80 | 246.21 | 158.59 | 0.00 | 0.00 |
December | 302.10 | 506.91 | 320.80 | 205.50 | 115.30 | 0.00 | 0.00 |
Annual Sum or Average | 496.37 | 338.11 | 557.02 | 264.24 | 292.78 | 0.00 | 0.00 |
Minimum of Months | 242.47 | 211.41 | 320.80 | 102.02 | 115.30 | 0.00 | 0.00 |
Maximum of Months | 849.71 | 506.91 | 831.52 | 487.24 | 419.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 222.96 | 224.61 | 231.80 | 150.03 | 81.77 | 0.00 | 0.00 |
February | 267.98 | 218.83 | 283.19 | 172.81 | 110.38 | 0.00 | 0.00 |
March | 120.92 | 184.24 | 175.11 | 51.01 | 124.10 | 0.00 | 0.00 |
April | 329.28 | 153.70 | 363.60 | 164.36 | 199.24 | 0.00 | 0.00 |
May | 219.80 | 135.21 | 300.66 | 97.85 | 202.80 | 0.00 | 0.00 |
June | 203.13 | 109.75 | 276.97 | 67.01 | 209.96 | 0.00 | 0.00 |
July | 236.78 | 105.67 | 300.09 | 93.94 | 206.14 | 0.00 | 0.00 |
August | 322.89 | 117.51 | 351.68 | 158.20 | 193.49 | 0.00 | 0.00 |
September | 423.81 | 146.53 | 415.76 | 243.62 | 172.14 | 0.00 | 0.00 |
October | 287.01 | 175.58 | 285.61 | 166.95 | 118.66 | 0.00 | 0.00 |
November | 194.51 | 207.29 | 202.40 | 123.11 | 79.29 | 0.00 | 0.00 |
December | 150.77 | 254.17 | 160.40 | 102.75 | 57.65 | 0.00 | 0.00 |
Annual Sum or Average | 247.73 | 169.18 | 278.51 | 132.12 | 146.39 | 0.00 | 0.00 |
Minimum of Months | 120.92 | 105.67 | 160.40 | 51.01 | 57.65 | 0.00 | 0.00 |
Maximum of Months | 423.81 | 254.17 | 415.76 | 243.62 | 209.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 223.14 | 223.77 | 231.80 | 150.03 | 81.77 | 0.00 | 0.00 |
February | 268.19 | 217.99 | 283.19 | 172.81 | 110.38 | 0.00 | 0.00 |
March | 121.13 | 183.47 | 175.11 | 51.01 | 124.10 | 0.00 | 0.00 |
April | 329.67 | 152.95 | 363.60 | 164.36 | 199.24 | 0.00 | 0.00 |
May | 220.31 | 134.38 | 300.66 | 97.85 | 202.80 | 0.00 | 0.00 |
June | 203.88 | 108.85 | 276.97 | 67.01 | 209.96 | 0.00 | 0.00 |
July | 237.29 | 105.00 | 300.09 | 93.94 | 206.14 | 0.00 | 0.00 |
August | 323.17 | 117.02 | 351.68 | 158.20 | 193.49 | 0.00 | 0.00 |
September | 424.20 | 145.83 | 415.76 | 243.62 | 172.14 | 0.00 | 0.00 |
October | 287.35 | 174.65 | 285.61 | 166.95 | 118.66 | 0.00 | 0.00 |
November | 194.65 | 206.51 | 202.40 | 123.11 | 79.29 | 0.00 | 0.00 |
December | 150.88 | 253.34 | 160.40 | 102.75 | 57.65 | 0.00 | 0.00 |
Annual Sum or Average | 248.06 | 168.41 | 278.51 | 132.12 | 146.39 | 0.00 | 0.00 |
Minimum of Months | 121.13 | 105.00 | 160.40 | 51.01 | 57.65 | 0.00 | 0.00 |
Maximum of Months | 424.20 | 253.34 | 415.76 | 243.62 | 209.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 223.66 | 221.00 | 231.80 | 150.03 | 81.77 | 0.00 | 0.00 |
February | 268.82 | 215.09 | 283.19 | 172.81 | 110.38 | 0.00 | 0.00 |
March | 121.74 | 180.84 | 175.11 | 51.01 | 124.10 | 0.00 | 0.00 |
April | 330.66 | 150.63 | 363.60 | 164.36 | 199.24 | 0.00 | 0.00 |
May | 221.74 | 131.74 | 300.66 | 97.85 | 202.80 | 0.00 | 0.00 |
June | 206.09 | 106.00 | 276.97 | 67.01 | 209.96 | 0.00 | 0.00 |
July | 238.81 | 102.86 | 300.09 | 93.94 | 206.14 | 0.00 | 0.00 |
August | 323.98 | 115.39 | 351.68 | 158.20 | 193.49 | 0.00 | 0.00 |
September | 425.62 | 143.15 | 415.76 | 243.62 | 172.14 | 0.00 | 0.00 |
October | 288.29 | 171.86 | 285.61 | 166.95 | 118.66 | 0.00 | 0.00 |
November | 195.07 | 203.96 | 202.40 | 123.11 | 79.29 | 0.00 | 0.00 |
December | 151.23 | 250.41 | 160.40 | 102.75 | 57.65 | 0.00 | 0.00 |
Annual Sum or Average | 249.05 | 165.84 | 278.51 | 132.12 | 146.39 | 0.00 | 0.00 |
Minimum of Months | 121.74 | 102.86 | 160.40 | 51.01 | 57.65 | 0.00 | 0.00 |
Maximum of Months | 425.62 | 250.41 | 415.76 | 243.62 | 209.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 225.47 | 211.21 | 231.80 | 150.03 | 81.77 | 0.00 | 0.00 |
February | 271.08 | 204.50 | 283.19 | 172.81 | 110.38 | 0.00 | 0.00 |
March | 123.95 | 171.39 | 175.11 | 51.01 | 124.10 | 0.00 | 0.00 |
April | 333.10 | 142.94 | 363.60 | 164.36 | 199.24 | 0.00 | 0.00 |
May | 225.12 | 123.19 | 300.66 | 97.85 | 202.80 | 0.00 | 0.00 |
June | 210.69 | 98.29 | 276.97 | 67.01 | 209.96 | 0.00 | 0.00 |
July | 242.26 | 96.44 | 300.09 | 93.94 | 206.14 | 0.00 | 0.00 |
August | 326.38 | 109.41 | 351.68 | 158.20 | 193.49 | 0.00 | 0.00 |
September | 428.61 | 135.58 | 415.76 | 243.62 | 172.14 | 0.00 | 0.00 |
October | 290.34 | 163.74 | 285.61 | 166.95 | 118.66 | 0.00 | 0.00 |
November | 196.51 | 194.99 | 202.40 | 123.11 | 79.29 | 0.00 | 0.00 |
December | 152.47 | 239.67 | 160.40 | 102.75 | 57.65 | 0.00 | 0.00 |
Annual Sum or Average | 251.57 | 157.39 | 278.51 | 132.12 | 146.39 | 0.00 | 0.00 |
Minimum of Months | 123.95 | 96.44 | 160.40 | 51.01 | 57.65 | 0.00 | 0.00 |
Maximum of Months | 428.61 | 239.67 | 415.76 | 243.62 | 209.96 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.119357E+10 | 0.123847E+10 | 0.124425E+10 | 0.805336E+09 | 0.438917E+09 | 0.00 | 0.00 |
February | 0.129711E+10 | 0.108444E+10 | 0.137300E+10 | 0.837851E+09 | 0.535154E+09 | 0.00 | 0.00 |
March | 0.646757E+09 | 0.101245E+10 | 0.939983E+09 | 0.273818E+09 | 0.666165E+09 | 0.00 | 0.00 |
April | 0.170652E+10 | 0.814279E+09 | 0.188878E+10 | 0.853809E+09 | 0.103497E+10 | 0.00 | 0.00 |
May | 0.117377E+10 | 0.740554E+09 | 0.161387E+10 | 0.525261E+09 | 0.108861E+10 | 0.00 | 0.00 |
June | 0.104596E+10 | 0.584800E+09 | 0.143877E+10 | 0.348109E+09 | 0.109066E+10 | 0.00 | 0.00 |
July | 0.126619E+10 | 0.574770E+09 | 0.161083E+10 | 0.504280E+09 | 0.110655E+10 | 0.00 | 0.00 |
August | 0.173370E+10 | 0.631572E+09 | 0.188778E+10 | 0.849167E+09 | 0.103861E+10 | 0.00 | 0.00 |
September | 0.220007E+10 | 0.768745E+09 | 0.215973E+10 | 0.126552E+10 | 0.894202E+09 | 0.00 | 0.00 |
October | 0.153706E+10 | 0.964814E+09 | 0.153308E+10 | 0.896161E+09 | 0.636919E+09 | 0.00 | 0.00 |
November | 0.100827E+10 | 0.110446E+10 | 0.105140E+10 | 0.639494E+09 | 0.411905E+09 | 0.00 | 0.00 |
December | 0.806522E+09 | 0.140115E+10 | 0.860999E+09 | 0.551533E+09 | 0.309466E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.156155E+11 | 0.109205E+11 | 0.176025E+11 | 0.835034E+10 | 0.925213E+10 | 0.00 | 0.00 |
Minimum of Months | 0.646757E+09 | 0.574770E+09 | 0.860999E+09 | 0.273818E+09 | 0.309466E+09 | 0.00 | 0.00 |
Maximum of Months | 0.220007E+10 | 0.140115E+10 | 0.215973E+10 | 0.126552E+10 | 0.110655E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.591205E+09 | 0.650426E+09 | 0.622126E+09 | 0.402668E+09 | 0.219458E+09 | 0.00 | 0.00 |
February | 0.642771E+09 | 0.571110E+09 | 0.686502E+09 | 0.418926E+09 | 0.267577E+09 | 0.00 | 0.00 |
March | 0.316768E+09 | 0.536838E+09 | 0.469992E+09 | 0.136909E+09 | 0.333083E+09 | 0.00 | 0.00 |
April | 0.836332E+09 | 0.442675E+09 | 0.944391E+09 | 0.426905E+09 | 0.517487E+09 | 0.00 | 0.00 |
May | 0.568099E+09 | 0.406410E+09 | 0.806936E+09 | 0.262630E+09 | 0.544305E+09 | 0.00 | 0.00 |
June | 0.508112E+09 | 0.312129E+09 | 0.719385E+09 | 0.174055E+09 | 0.545330E+09 | 0.00 | 0.00 |
July | 0.625220E+09 | 0.299137E+09 | 0.805414E+09 | 0.252140E+09 | 0.553274E+09 | 0.00 | 0.00 |
August | 0.862908E+09 | 0.323677E+09 | 0.943889E+09 | 0.424583E+09 | 0.519306E+09 | 0.00 | 0.00 |
September | 0.109232E+10 | 0.399518E+09 | 0.107986E+10 | 0.632762E+09 | 0.447101E+09 | 0.00 | 0.00 |
October | 0.755222E+09 | 0.524613E+09 | 0.766540E+09 | 0.448081E+09 | 0.318460E+09 | 0.00 | 0.00 |
November | 0.498925E+09 | 0.584957E+09 | 0.525700E+09 | 0.319747E+09 | 0.205953E+09 | 0.00 | 0.00 |
December | 0.399463E+09 | 0.734964E+09 | 0.430500E+09 | 0.275766E+09 | 0.154733E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.769734E+10 | 0.578645E+10 | 0.880124E+10 | 0.417517E+10 | 0.462607E+10 | 0.00 | 0.00 |
Minimum of Months | 0.316768E+09 | 0.299137E+09 | 0.430500E+09 | 0.136909E+09 | 0.154733E+09 | 0.00 | 0.00 |
Maximum of Months | 0.109232E+10 | 0.734964E+09 | 0.107986E+10 | 0.632762E+09 | 0.553274E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.592259E+09 | 0.631456E+09 | 0.620849E+09 | 0.401841E+09 | 0.219008E+09 | 0.00 | 0.00 |
February | 0.643449E+09 | 0.554790E+09 | 0.685093E+09 | 0.418065E+09 | 0.267027E+09 | 0.00 | 0.00 |
March | 0.318189E+09 | 0.520257E+09 | 0.469027E+09 | 0.136628E+09 | 0.332399E+09 | 0.00 | 0.00 |
April | 0.837310E+09 | 0.433504E+09 | 0.942452E+09 | 0.426028E+09 | 0.516424E+09 | 0.00 | 0.00 |
May | 0.569571E+09 | 0.398885E+09 | 0.805279E+09 | 0.262091E+09 | 0.543188E+09 | 0.00 | 0.00 |
June | 0.506807E+09 | 0.315499E+09 | 0.717908E+09 | 0.173697E+09 | 0.544211E+09 | 0.00 | 0.00 |
July | 0.623355E+09 | 0.304432E+09 | 0.803761E+09 | 0.251622E+09 | 0.552138E+09 | 0.00 | 0.00 |
August | 0.861004E+09 | 0.329759E+09 | 0.941951E+09 | 0.423712E+09 | 0.518240E+09 | 0.00 | 0.00 |
September | 0.109039E+10 | 0.403310E+09 | 0.107765E+10 | 0.631462E+09 | 0.446183E+09 | 0.00 | 0.00 |
October | 0.755723E+09 | 0.513013E+09 | 0.764966E+09 | 0.447161E+09 | 0.317806E+09 | 0.00 | 0.00 |
November | 0.500025E+09 | 0.565511E+09 | 0.524620E+09 | 0.319091E+09 | 0.205530E+09 | 0.00 | 0.00 |
December | 0.400248E+09 | 0.714719E+09 | 0.429616E+09 | 0.275200E+09 | 0.154415E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.769833E+10 | 0.568513E+10 | 0.878317E+10 | 0.416660E+10 | 0.461657E+10 | 0.00 | 0.00 |
Minimum of Months | 0.318189E+09 | 0.304432E+09 | 0.429616E+09 | 0.136628E+09 | 0.154415E+09 | 0.00 | 0.00 |
Maximum of Months | 0.109039E+10 | 0.714719E+09 | 0.107765E+10 | 0.631462E+09 | 0.552138E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.593431E+09 | 0.623676E+09 | 0.620849E+09 | 0.401841E+09 | 0.219008E+09 | 0.00 | 0.00 |
February | 0.644492E+09 | 0.548338E+09 | 0.685093E+09 | 0.418065E+09 | 0.267027E+09 | 0.00 | 0.00 |
March | 0.319413E+09 | 0.513495E+09 | 0.469027E+09 | 0.136628E+09 | 0.332399E+09 | 0.00 | 0.00 |
April | 0.840438E+09 | 0.425969E+09 | 0.942452E+09 | 0.426028E+09 | 0.516424E+09 | 0.00 | 0.00 |
May | 0.573011E+09 | 0.391518E+09 | 0.805279E+09 | 0.262091E+09 | 0.543188E+09 | 0.00 | 0.00 |
June | 0.508546E+09 | 0.311955E+09 | 0.717908E+09 | 0.173697E+09 | 0.544211E+09 | 0.00 | 0.00 |
July | 0.624342E+09 | 0.302072E+09 | 0.803761E+09 | 0.251622E+09 | 0.552138E+09 | 0.00 | 0.00 |
August | 0.861475E+09 | 0.328179E+09 | 0.941951E+09 | 0.423712E+09 | 0.518240E+09 | 0.00 | 0.00 |
September | 0.109119E+10 | 0.400543E+09 | 0.107765E+10 | 0.631462E+09 | 0.446183E+09 | 0.00 | 0.00 |
October | 0.757831E+09 | 0.504334E+09 | 0.764966E+09 | 0.447161E+09 | 0.317806E+09 | 0.00 | 0.00 |
November | 0.501083E+09 | 0.557736E+09 | 0.524620E+09 | 0.319091E+09 | 0.205530E+09 | 0.00 | 0.00 |
December | 0.401028E+09 | 0.706625E+09 | 0.429616E+09 | 0.275200E+09 | 0.154415E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.771628E+10 | 0.561444E+10 | 0.878317E+10 | 0.416660E+10 | 0.461657E+10 | 0.00 | 0.00 |
Minimum of Months | 0.319413E+09 | 0.302072E+09 | 0.429616E+09 | 0.136628E+09 | 0.154415E+09 | 0.00 | 0.00 |
Maximum of Months | 0.109119E+10 | 0.706625E+09 | 0.107765E+10 | 0.631462E+09 | 0.552138E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.594682E+09 | 0.617393E+09 | 0.620849E+09 | 0.401841E+09 | 0.219008E+09 | 0.00 | 0.00 |
February | 0.645693E+09 | 0.543107E+09 | 0.685093E+09 | 0.418065E+09 | 0.267027E+09 | 0.00 | 0.00 |
March | 0.320882E+09 | 0.507895E+09 | 0.469027E+09 | 0.136628E+09 | 0.332399E+09 | 0.00 | 0.00 |
April | 0.845259E+09 | 0.417110E+09 | 0.942452E+09 | 0.426028E+09 | 0.516424E+09 | 0.00 | 0.00 |
May | 0.578599E+09 | 0.382043E+09 | 0.805279E+09 | 0.262091E+09 | 0.543188E+09 | 0.00 | 0.00 |
June | 0.513795E+09 | 0.304219E+09 | 0.717908E+09 | 0.173697E+09 | 0.544211E+09 | 0.00 | 0.00 |
July | 0.627349E+09 | 0.296953E+09 | 0.803761E+09 | 0.251622E+09 | 0.552138E+09 | 0.00 | 0.00 |
August | 0.862890E+09 | 0.324870E+09 | 0.941951E+09 | 0.423712E+09 | 0.518240E+09 | 0.00 | 0.00 |
September | 0.109353E+10 | 0.394942E+09 | 0.107765E+10 | 0.631462E+09 | 0.446183E+09 | 0.00 | 0.00 |
October | 0.761536E+09 | 0.493318E+09 | 0.764966E+09 | 0.447161E+09 | 0.317806E+09 | 0.00 | 0.00 |
November | 0.502179E+09 | 0.551649E+09 | 0.524620E+09 | 0.319091E+09 | 0.205530E+09 | 0.00 | 0.00 |
December | 0.401952E+09 | 0.699481E+09 | 0.429616E+09 | 0.275200E+09 | 0.154415E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.774835E+10 | 0.553298E+10 | 0.878317E+10 | 0.416660E+10 | 0.461657E+10 | 0.00 | 0.00 |
Minimum of Months | 0.320882E+09 | 0.296953E+09 | 0.429616E+09 | 0.136628E+09 | 0.154415E+09 | 0.00 | 0.00 |
Maximum of Months | 0.109353E+10 | 0.699481E+09 | 0.107765E+10 | 0.631462E+09 | 0.552138E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.119629E+10 | 0.120242E+10 | 0.124170E+10 | 0.803682E+09 | 0.438016E+09 | 0.00 | 0.00 |
February | 0.129852E+10 | 0.105766E+10 | 0.137019E+10 | 0.836131E+09 | 0.534055E+09 | 0.00 | 0.00 |
March | 0.649436E+09 | 0.987304E+09 | 0.938053E+09 | 0.273256E+09 | 0.664797E+09 | 0.00 | 0.00 |
April | 0.170890E+10 | 0.798164E+09 | 0.188490E+10 | 0.852056E+09 | 0.103285E+10 | 0.00 | 0.00 |
May | 0.117980E+10 | 0.724221E+09 | 0.161056E+10 | 0.524182E+09 | 0.108638E+10 | 0.00 | 0.00 |
June | 0.105728E+10 | 0.567668E+09 | 0.143582E+10 | 0.347394E+09 | 0.108842E+10 | 0.00 | 0.00 |
July | 0.127054E+10 | 0.566229E+09 | 0.160752E+10 | 0.503244E+09 | 0.110428E+10 | 0.00 | 0.00 |
August | 0.173076E+10 | 0.630641E+09 | 0.188390E+10 | 0.847423E+09 | 0.103648E+10 | 0.00 | 0.00 |
September | 0.220245E+10 | 0.756352E+09 | 0.215529E+10 | 0.126292E+10 | 0.892366E+09 | 0.00 | 0.00 |
October | 0.154063E+10 | 0.940436E+09 | 0.152993E+10 | 0.894321E+09 | 0.635612E+09 | 0.00 | 0.00 |
November | 0.100980E+10 | 0.107388E+10 | 0.104924E+10 | 0.638181E+09 | 0.411059E+09 | 0.00 | 0.00 |
December | 0.809141E+09 | 0.135770E+10 | 0.859231E+09 | 0.550400E+09 | 0.308831E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.156535E+11 | 0.106627E+11 | 0.175663E+11 | 0.833320E+10 | 0.923314E+10 | 0.00 | 0.00 |
Minimum of Months | 0.649436E+09 | 0.566229E+09 | 0.859231E+09 | 0.273256E+09 | 0.308831E+09 | 0.00 | 0.00 |
Maximum of Months | 0.220245E+10 | 0.135770E+10 | 0.215529E+10 | 0.126292E+10 | 0.110428E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.597184E+09 | 0.601582E+09 | 0.620849E+09 | 0.401841E+09 | 0.219008E+09 | 0.00 | 0.00 |
February | 0.648294E+09 | 0.529394E+09 | 0.685093E+09 | 0.418065E+09 | 0.267027E+09 | 0.00 | 0.00 |
March | 0.323884E+09 | 0.493465E+09 | 0.469027E+09 | 0.136628E+09 | 0.332399E+09 | 0.00 | 0.00 |
April | 0.853503E+09 | 0.398393E+09 | 0.942452E+09 | 0.426028E+09 | 0.516424E+09 | 0.00 | 0.00 |
May | 0.588712E+09 | 0.362154E+09 | 0.805279E+09 | 0.262091E+09 | 0.543188E+09 | 0.00 | 0.00 |
June | 0.526519E+09 | 0.284472E+09 | 0.717908E+09 | 0.173697E+09 | 0.544211E+09 | 0.00 | 0.00 |
July | 0.634179E+09 | 0.283027E+09 | 0.803761E+09 | 0.251622E+09 | 0.552138E+09 | 0.00 | 0.00 |
August | 0.864841E+09 | 0.314730E+09 | 0.941951E+09 | 0.423712E+09 | 0.518240E+09 | 0.00 | 0.00 |
September | 0.109851E+10 | 0.379815E+09 | 0.107765E+10 | 0.631462E+09 | 0.446183E+09 | 0.00 | 0.00 |
October | 0.768726E+09 | 0.470263E+09 | 0.764966E+09 | 0.447161E+09 | 0.317806E+09 | 0.00 | 0.00 |
November | 0.504160E+09 | 0.537305E+09 | 0.524620E+09 | 0.319091E+09 | 0.205530E+09 | 0.00 | 0.00 |
December | 0.403815E+09 | 0.680774E+09 | 0.429616E+09 | 0.275200E+09 | 0.154415E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.781233E+10 | 0.533537E+10 | 0.878317E+10 | 0.416660E+10 | 0.461657E+10 | 0.00 | 0.00 |
Minimum of Months | 0.323884E+09 | 0.283027E+09 | 0.429616E+09 | 0.136628E+09 | 0.154415E+09 | 0.00 | 0.00 |
Maximum of Months | 0.109851E+10 | 0.680774E+09 | 0.107765E+10 | 0.631462E+09 | 0.552138E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.597659E+09 | 0.599350E+09 | 0.620849E+09 | 0.401841E+09 | 0.219008E+09 | 0.00 | 0.00 |
February | 0.648798E+09 | 0.527359E+09 | 0.685093E+09 | 0.418065E+09 | 0.267027E+09 | 0.00 | 0.00 |
March | 0.324446E+09 | 0.491399E+09 | 0.469027E+09 | 0.136628E+09 | 0.332399E+09 | 0.00 | 0.00 |
April | 0.854508E+09 | 0.396443E+09 | 0.942452E+09 | 0.426028E+09 | 0.516424E+09 | 0.00 | 0.00 |
May | 0.590075E+09 | 0.359917E+09 | 0.805279E+09 | 0.262091E+09 | 0.543188E+09 | 0.00 | 0.00 |
June | 0.528445E+09 | 0.282143E+09 | 0.717908E+09 | 0.173697E+09 | 0.544211E+09 | 0.00 | 0.00 |
July | 0.635561E+09 | 0.281231E+09 | 0.803761E+09 | 0.251622E+09 | 0.552138E+09 | 0.00 | 0.00 |
August | 0.865572E+09 | 0.313435E+09 | 0.941951E+09 | 0.423712E+09 | 0.518240E+09 | 0.00 | 0.00 |
September | 0.109953E+10 | 0.377996E+09 | 0.107765E+10 | 0.631462E+09 | 0.446183E+09 | 0.00 | 0.00 |
October | 0.769630E+09 | 0.467772E+09 | 0.764966E+09 | 0.447161E+09 | 0.317806E+09 | 0.00 | 0.00 |
November | 0.504534E+09 | 0.535273E+09 | 0.524620E+09 | 0.319091E+09 | 0.205530E+09 | 0.00 | 0.00 |
December | 0.404116E+09 | 0.678534E+09 | 0.429616E+09 | 0.275200E+09 | 0.154415E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.782288E+10 | 0.531085E+10 | 0.878317E+10 | 0.416660E+10 | 0.461657E+10 | 0.00 | 0.00 |
Minimum of Months | 0.324446E+09 | 0.281231E+09 | 0.429616E+09 | 0.136628E+09 | 0.154415E+09 | 0.00 | 0.00 |
Maximum of Months | 0.109953E+10 | 0.678534E+09 | 0.107765E+10 | 0.631462E+09 | 0.552138E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.599041E+09 | 0.591926E+09 | 0.620849E+09 | 0.401841E+09 | 0.219008E+09 | 0.00 | 0.00 |
February | 0.650339E+09 | 0.520345E+09 | 0.685093E+09 | 0.418065E+09 | 0.267027E+09 | 0.00 | 0.00 |
March | 0.326079E+09 | 0.484351E+09 | 0.469027E+09 | 0.136628E+09 | 0.332399E+09 | 0.00 | 0.00 |
April | 0.857079E+09 | 0.390429E+09 | 0.942452E+09 | 0.426028E+09 | 0.516424E+09 | 0.00 | 0.00 |
May | 0.593899E+09 | 0.352846E+09 | 0.805279E+09 | 0.262091E+09 | 0.543188E+09 | 0.00 | 0.00 |
June | 0.534194E+09 | 0.274749E+09 | 0.717908E+09 | 0.173697E+09 | 0.544211E+09 | 0.00 | 0.00 |
July | 0.639639E+09 | 0.275497E+09 | 0.803761E+09 | 0.251622E+09 | 0.552138E+09 | 0.00 | 0.00 |
August | 0.867740E+09 | 0.309061E+09 | 0.941951E+09 | 0.423712E+09 | 0.518240E+09 | 0.00 | 0.00 |
September | 0.110320E+10 | 0.371047E+09 | 0.107765E+10 | 0.631462E+09 | 0.446183E+09 | 0.00 | 0.00 |
October | 0.772145E+09 | 0.460318E+09 | 0.764966E+09 | 0.447161E+09 | 0.317806E+09 | 0.00 | 0.00 |
November | 0.505628E+09 | 0.528676E+09 | 0.524620E+09 | 0.319091E+09 | 0.205530E+09 | 0.00 | 0.00 |
December | 0.405067E+09 | 0.670695E+09 | 0.429616E+09 | 0.275200E+09 | 0.154415E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.785405E+10 | 0.522994E+10 | 0.878317E+10 | 0.416660E+10 | 0.461657E+10 | 0.00 | 0.00 |
Minimum of Months | 0.326079E+09 | 0.274749E+09 | 0.429616E+09 | 0.136628E+09 | 0.154415E+09 | 0.00 | 0.00 |
Maximum of Months | 0.110320E+10 | 0.670695E+09 | 0.107765E+10 | 0.631462E+09 | 0.552138E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.603898E+09 | 0.565717E+09 | 0.620849E+09 | 0.401841E+09 | 0.219008E+09 | 0.00 | 0.00 |
February | 0.655787E+09 | 0.494719E+09 | 0.685093E+09 | 0.418065E+09 | 0.267027E+09 | 0.00 | 0.00 |
March | 0.331977E+09 | 0.459041E+09 | 0.469027E+09 | 0.136628E+09 | 0.332399E+09 | 0.00 | 0.00 |
April | 0.863399E+09 | 0.370500E+09 | 0.942452E+09 | 0.426028E+09 | 0.516424E+09 | 0.00 | 0.00 |
May | 0.602957E+09 | 0.329960E+09 | 0.805279E+09 | 0.262091E+09 | 0.543188E+09 | 0.00 | 0.00 |
June | 0.546113E+09 | 0.254779E+09 | 0.717908E+09 | 0.173697E+09 | 0.544211E+09 | 0.00 | 0.00 |
July | 0.648856E+09 | 0.258292E+09 | 0.803761E+09 | 0.251622E+09 | 0.552138E+09 | 0.00 | 0.00 |
August | 0.874178E+09 | 0.293054E+09 | 0.941951E+09 | 0.423712E+09 | 0.518240E+09 | 0.00 | 0.00 |
September | 0.111097E+10 | 0.351426E+09 | 0.107765E+10 | 0.631462E+09 | 0.446183E+09 | 0.00 | 0.00 |
October | 0.777638E+09 | 0.438565E+09 | 0.764966E+09 | 0.447161E+09 | 0.317806E+09 | 0.00 | 0.00 |
November | 0.509354E+09 | 0.505402E+09 | 0.524620E+09 | 0.319091E+09 | 0.205530E+09 | 0.00 | 0.00 |
December | 0.408373E+09 | 0.641920E+09 | 0.429616E+09 | 0.275200E+09 | 0.154415E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.793350E+10 | 0.496337E+10 | 0.878317E+10 | 0.416660E+10 | 0.461657E+10 | 0.00 | 0.00 |
Minimum of Months | 0.331977E+09 | 0.254779E+09 | 0.429616E+09 | 0.136628E+09 | 0.154415E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111097E+10 | 0.641920E+09 | 0.107765E+10 | 0.631462E+09 | 0.552138E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.24 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -2.0 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.23 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.06 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.26 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.48 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.74 | 10.65 | 2.92 | 3.94 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.42 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.65 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.74 | 10.65 | 3.35 | 4.48 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.36 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.21 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.10 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.06 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.51 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.77 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.15 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.21 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.08 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.62 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.62 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.51 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -6.9 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.8 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.04 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.4 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -6.9 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.06 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.29 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.04 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.53 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.00 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.94 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.44 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.53 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.362036E+09 | -238921489.5 | 0.00 | 0.00 | 744.00 | 0.00 | -123115000.4 | 58.99 | 0.00 | 0.00 |
February | 0.329785E+09 | -218406593.0 | 0.00 | 0.00 | 672.00 | 0.00 | -111378191.0 | 58.99 | 0.00 | 0.00 |
March | 0.366979E+09 | -243933949.9 | 0.00 | 0.00 | 744.00 | 0.00 | -123045315.3 | 58.99 | 0.00 | 0.00 |
April | 0.345993E+09 | -228945554.2 | 0.00 | 0.00 | 720.00 | 0.00 | -117047497.2 | 58.99 | 0.00 | 0.00 |
May | 0.350619E+09 | -230435641.3 | 0.00 | 0.00 | 744.00 | 0.00 | -120183381.1 | 58.99 | 0.00 | 0.00 |
June | 0.330983E+09 | -218885078.2 | 0.00 | 0.00 | 720.00 | 0.00 | -112097475.9 | 58.99 | 0.00 | 0.00 |
July | 0.331362E+09 | -217254353.2 | 0.00 | 0.00 | 744.00 | 0.00 | -114108003.4 | 58.99 | 0.00 | 0.00 |
August | 0.333122E+09 | -219770446.1 | 0.00 | 0.00 | 744.00 | 0.00 | -113351477.3 | 58.99 | 0.00 | 0.00 |
September | 0.323058E+09 | -212235801.6 | 0.00 | 0.00 | 720.00 | 0.00 | -110822343.0 | 58.99 | 0.00 | 0.00 |
October | 0.342501E+09 | -221704499.1 | 0.00 | 0.00 | 744.00 | 0.00 | -120796092.5 | 58.99 | 0.00 | 0.00 |
November | 0.338848E+09 | -220046350.0 | 0.00 | 0.00 | 720.00 | 0.00 | -118801163.3 | 58.99 | 0.00 | 0.00 |
December | 0.358032E+09 | -234600244.7 | 0.00 | 0.00 | 744.00 | 0.00 | -123432139.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.411332E+10 | -.270514E+10 | 8760.00 | -.140818E+10 | 58.99 | |||||
Minimum of Months | 0.323058E+09 | -243933949.9 | 0.00 | 0.00 | 672.00 | 0.00 | -123432139.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.366979E+09 | -212235801.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110822343.0 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.359850E+09 | -238921250.5 | 0.00 | 0.00 | 744.00 | 0.00 | -120928532.3 | 58.99 | 0.00 | 0.00 |
February | 0.327751E+09 | -218403326.3 | 0.00 | 0.00 | 672.00 | 0.00 | -109348038.3 | 58.99 | 0.00 | 0.00 |
March | 0.364693E+09 | -243938106.8 | 0.00 | 0.00 | 744.00 | 0.00 | -120754852.6 | 58.99 | 0.00 | 0.00 |
April | 0.342321E+09 | -228947633.2 | 0.00 | 0.00 | 720.00 | 0.00 | -113373088.7 | 58.99 | 0.00 | 0.00 |
May | 0.346811E+09 | -230441018.4 | 0.00 | 0.00 | 744.00 | 0.00 | -116370140.9 | 58.99 | 0.00 | 0.00 |
June | 0.328699E+09 | -218893359.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109805862.8 | 58.99 | 0.00 | 0.00 |
July | 0.330182E+09 | -217248454.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112933874.5 | 58.99 | 0.00 | 0.00 |
August | 0.332530E+09 | -219764143.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112765468.1 | 58.99 | 0.00 | 0.00 |
September | 0.321661E+09 | -212230578.6 | 0.00 | 0.00 | 720.00 | 0.00 | -109430061.7 | 58.99 | 0.00 | 0.00 |
October | 0.338641E+09 | -221710985.7 | 0.00 | 0.00 | 744.00 | 0.00 | -116930321.8 | 58.99 | 0.00 | 0.00 |
November | 0.336410E+09 | -220051604.7 | 0.00 | 0.00 | 720.00 | 0.00 | -116357992.4 | 58.99 | 0.00 | 0.00 |
December | 0.355894E+09 | -234600081.4 | 0.00 | 0.00 | 744.00 | 0.00 | -121294007.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.408544E+10 | -.270515E+10 | 8760.00 | -.138029E+10 | 58.99 | |||||
Minimum of Months | 0.321661E+09 | -243938106.8 | 0.00 | 0.00 | 672.00 | 0.00 | -121294007.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.364693E+09 | -212230578.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109348038.3 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.332793E+09 | -210100811.7 | 0.00 | 0.00 | 744.00 | 0.00 | -122692186.0 | 58.99 | 0.00 | 0.00 |
February | 0.303082E+09 | -192216691.5 | 0.00 | 0.00 | 672.00 | 0.00 | -110864927.6 | 58.99 | 0.00 | 0.00 |
March | 0.340277E+09 | -217866275.1 | 0.00 | 0.00 | 744.00 | 0.00 | -122410242.6 | 59.00 | 0.00 | 0.00 |
April | 0.315675E+09 | -201183689.9 | 0.00 | 0.00 | 720.00 | 0.00 | -114490913.1 | 59.00 | 0.00 | 0.00 |
May | 0.321692E+09 | -204356987.6 | 0.00 | 0.00 | 744.00 | 0.00 | -117335307.6 | 58.99 | 0.00 | 0.00 |
June | 0.304662E+09 | -195100778.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109561120.2 | 58.99 | 0.00 | 0.00 |
July | 0.302192E+09 | -189798063.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112394040.1 | 58.99 | 0.00 | 0.00 |
August | 0.308614E+09 | -196440295.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112173908.4 | 58.99 | 0.00 | 0.00 |
September | 0.295511E+09 | -186375236.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109135473.5 | 58.99 | 0.00 | 0.00 |
October | 0.313165E+09 | -194983011.7 | 0.00 | 0.00 | 744.00 | 0.00 | -118182288.8 | 58.99 | 0.00 | 0.00 |
November | 0.312433E+09 | -194313672.0 | 0.00 | 0.00 | 720.00 | 0.00 | -118118998.4 | 58.98 | 0.00 | 0.00 |
December | 0.327849E+09 | -204780253.7 | 0.00 | 0.00 | 744.00 | 0.00 | -123068303.7 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.377794E+10 | -.238752E+10 | 8760.00 | -.139043E+10 | 58.99 | |||||
Minimum of Months | 0.295511E+09 | -217866275.1 | 0.00 | 0.00 | 672.00 | 0.00 | -123068303.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.340277E+09 | -186375236.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109135473.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.333210E+09 | -210099297.4 | 0.00 | 0.00 | 744.00 | 0.00 | -123110989.8 | 58.99 | 0.00 | 0.00 |
February | 0.303438E+09 | -192204181.4 | 0.00 | 0.00 | 672.00 | 0.00 | -111233873.6 | 59.00 | 0.00 | 0.00 |
March | 0.340646E+09 | -217873030.9 | 0.00 | 0.00 | 744.00 | 0.00 | -122773079.1 | 58.99 | 0.00 | 0.00 |
April | 0.316281E+09 | -201204142.5 | 0.00 | 0.00 | 720.00 | 0.00 | -115076501.4 | 58.99 | 0.00 | 0.00 |
May | 0.322300E+09 | -204351603.1 | 0.00 | 0.00 | 744.00 | 0.00 | -117948004.7 | 58.99 | 0.00 | 0.00 |
June | 0.304931E+09 | -195109098.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109822019.7 | 58.99 | 0.00 | 0.00 |
July | 0.302357E+09 | -189794316.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112562548.8 | 58.99 | 0.00 | 0.00 |
August | 0.308713E+09 | -196437267.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112275864.5 | 58.99 | 0.00 | 0.00 |
September | 0.295677E+09 | -186377494.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109299576.7 | 58.99 | 0.00 | 0.00 |
October | 0.313765E+09 | -194990385.0 | 0.00 | 0.00 | 744.00 | 0.00 | -118775052.7 | 58.99 | 0.00 | 0.00 |
November | 0.312858E+09 | -194291997.2 | 0.00 | 0.00 | 720.00 | 0.00 | -118565904.7 | 58.99 | 0.00 | 0.00 |
December | 0.328243E+09 | -204801943.6 | 0.00 | 0.00 | 744.00 | 0.00 | -123440928.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.378242E+10 | -.238753E+10 | 8760.00 | -.139488E+10 | 58.99 | |||||
Minimum of Months | 0.295677E+09 | -217873030.9 | 0.00 | 0.00 | 672.00 | 0.00 | -123440928.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.340646E+09 | -186377494.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109299576.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.322906E+09 | -198569295.1 | 0.00 | 0.00 | 744.00 | 0.00 | -124336932.7 | 58.99 | 0.00 | 0.00 |
February | 0.294052E+09 | -181759385.5 | 0.00 | 0.00 | 672.00 | 0.00 | -112292942.4 | 59.00 | 0.00 | 0.00 |
March | 0.330069E+09 | -206170965.1 | 0.00 | 0.00 | 744.00 | 0.00 | -123898094.6 | 58.99 | 0.00 | 0.00 |
April | 0.308016E+09 | -190393729.8 | 0.00 | 0.00 | 720.00 | 0.00 | -117622272.0 | 58.99 | 0.00 | 0.00 |
May | 0.314112E+09 | -193265849.3 | 0.00 | 0.00 | 744.00 | 0.00 | -120846201.8 | 58.99 | 0.00 | 0.00 |
June | 0.297619E+09 | -184611867.4 | 0.00 | 0.00 | 720.00 | 0.00 | -113006680.8 | 58.99 | 0.00 | 0.00 |
July | 0.293923E+09 | -179499601.8 | 0.00 | 0.00 | 744.00 | 0.00 | -114423419.8 | 58.99 | 0.00 | 0.00 |
August | 0.299119E+09 | -185915917.0 | 0.00 | 0.00 | 744.00 | 0.00 | -113202799.8 | 58.98 | 0.00 | 0.00 |
September | 0.287741E+09 | -176366868.4 | 0.00 | 0.00 | 720.00 | 0.00 | -111374084.4 | 58.99 | 0.00 | 0.00 |
October | 0.305886E+09 | -184287527.5 | 0.00 | 0.00 | 744.00 | 0.00 | -121598459.1 | 58.99 | 0.00 | 0.00 |
November | 0.303166E+09 | -183506923.3 | 0.00 | 0.00 | 720.00 | 0.00 | -119659298.1 | 58.99 | 0.00 | 0.00 |
December | 0.318474E+09 | -193690093.1 | 0.00 | 0.00 | 744.00 | 0.00 | -124783545.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.367508E+10 | -.225804E+10 | 8760.00 | -.141704E+10 | 58.99 | |||||
Minimum of Months | 0.287741E+09 | -206170965.1 | 0.00 | 0.00 | 672.00 | 0.00 | -124783545.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.330069E+09 | -176366868.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111374084.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.322945E+09 | -198568537.1 | 0.00 | 0.00 | 744.00 | 0.00 | -124376870.2 | 59.00 | 0.00 | 0.00 |
February | 0.294084E+09 | -181760450.9 | 0.00 | 0.00 | 672.00 | 0.00 | -112323756.7 | 59.00 | 0.00 | 0.00 |
March | 0.330104E+09 | -206168106.5 | 0.00 | 0.00 | 744.00 | 0.00 | -123936390.8 | 58.99 | 0.00 | 0.00 |
April | 0.307944E+09 | -190397350.6 | 0.00 | 0.00 | 720.00 | 0.00 | -117546765.0 | 58.99 | 0.00 | 0.00 |
May | 0.313934E+09 | -193261791.5 | 0.00 | 0.00 | 744.00 | 0.00 | -120671908.3 | 58.99 | 0.00 | 0.00 |
June | 0.297234E+09 | -184610798.7 | 0.00 | 0.00 | 720.00 | 0.00 | -112622806.7 | 58.99 | 0.00 | 0.00 |
July | 0.293725E+09 | -179506769.1 | 0.00 | 0.00 | 744.00 | 0.00 | -114218660.6 | 58.99 | 0.00 | 0.00 |
August | 0.299074E+09 | -185816976.3 | 0.00 | 0.00 | 744.00 | 0.00 | -113257007.9 | 59.01 | 0.00 | 0.00 |
September | 0.287331E+09 | -176381661.4 | 0.00 | 0.00 | 720.00 | 0.00 | -110948937.4 | 58.99 | 0.00 | 0.00 |
October | 0.305758E+09 | -184290268.0 | 0.00 | 0.00 | 744.00 | 0.00 | -121467970.0 | 58.99 | 0.00 | 0.00 |
November | 0.303204E+09 | -183507669.2 | 0.00 | 0.00 | 720.00 | 0.00 | -119696076.2 | 58.99 | 0.00 | 0.00 |
December | 0.318483E+09 | -193690234.8 | 0.00 | 0.00 | 744.00 | 0.00 | -124793093.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.367382E+10 | -.225796E+10 | 8760.00 | -.141586E+10 | 58.99 | |||||
Minimum of Months | 0.287331E+09 | -206168106.5 | 0.00 | 0.00 | 672.00 | 0.00 | -124793093.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.330104E+09 | -176381661.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110948937.4 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.323057E+09 | -198567272.6 | 0.00 | 0.00 | 744.00 | 0.00 | -124489992.6 | 59.00 | 0.00 | 0.00 |
February | 0.294183E+09 | -181769802.7 | 0.00 | 0.00 | 672.00 | 0.00 | -112413101.2 | 58.99 | 0.00 | 0.00 |
March | 0.330208E+09 | -206153546.3 | 0.00 | 0.00 | 744.00 | 0.00 | -124054502.3 | 58.99 | 0.00 | 0.00 |
April | 0.308097E+09 | -190390685.5 | 0.00 | 0.00 | 720.00 | 0.00 | -117706436.6 | 58.99 | 0.00 | 0.00 |
May | 0.314115E+09 | -193260329.8 | 0.00 | 0.00 | 744.00 | 0.00 | -120854367.5 | 58.99 | 0.00 | 0.00 |
June | 0.297473E+09 | -184612569.8 | 0.00 | 0.00 | 720.00 | 0.00 | -112860496.2 | 58.99 | 0.00 | 0.00 |
July | 0.293873E+09 | -179518387.3 | 0.00 | 0.00 | 744.00 | 0.00 | -114354522.1 | 58.98 | 0.00 | 0.00 |
August | 0.299164E+09 | -185834150.6 | 0.00 | 0.00 | 744.00 | 0.00 | -113330161.9 | 59.01 | 0.00 | 0.00 |
September | 0.287483E+09 | -176379050.2 | 0.00 | 0.00 | 720.00 | 0.00 | -111104327.4 | 58.99 | 0.00 | 0.00 |
October | 0.305928E+09 | -184289724.9 | 0.00 | 0.00 | 744.00 | 0.00 | -121638224.0 | 58.99 | 0.00 | 0.00 |
November | 0.303302E+09 | -183506806.2 | 0.00 | 0.00 | 720.00 | 0.00 | -119795472.0 | 58.99 | 0.00 | 0.00 |
December | 0.318579E+09 | -193679483.5 | 0.00 | 0.00 | 744.00 | 0.00 | -124899180.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.367546E+10 | -.225796E+10 | 8760.00 | -.141750E+10 | 58.99 | |||||
Minimum of Months | 0.287483E+09 | -206153546.3 | 0.00 | 0.00 | 672.00 | 0.00 | -124899180.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.330208E+09 | -176379050.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111104327.4 | 59.01 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 195.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 217.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 215.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 417.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 410.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 396.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 337.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 234.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 171.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3515.67 | ||||||||||
Minimum of Months | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.114113E+11 | 45349.67 | 02-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.964819E+10 | 45349.67 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.870861E+10 | 45349.67 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.222614E+10 | 45349.67 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146873E+10 | 45349.67 | 05-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32884285.85 | 4076.69 | 08-JUN-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.220429E+10 | 38985.58 | 23-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.729345E+10 | 45349.67 | 03-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.124138E+11 | 45349.67 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.554074E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.124138E+11 | 45349.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.266997E+10 | 25868.79 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.199290E+10 | 25868.79 | 17-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159126E+10 | 19438.79 | 16-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.100418E+09 | 3689.65 | 01-APR-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15626781.37 | 1441.81 | 05-MAY-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 79618340.95 | 1744.48 | 31-OCT-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121297E+10 | 25507.65 | 29-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.306693E+10 | 25868.79 | 28-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107297E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.306693E+10 | 25868.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.348095E+10 | 28560.67 | 10-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.271484E+10 | 27418.46 | 20-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225407E+10 | 16128.44 | 06-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.242558E+09 | 8847.77 | 08-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 37935073.11 | 3231.43 | 06-MAY-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.222430E+09 | 4946.89 | 23-OCT-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182085E+10 | 18249.64 | 20-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.387504E+10 | 28560.67 | 26-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146487E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.387504E+10 | 28560.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.375844E+10 | 28459.82 | 09-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.294508E+10 | 28459.82 | 20-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.249517E+10 | 22195.73 | 06-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.330170E+09 | 5643.18 | 01-APR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 77672293.05 | 3883.90 | 06-MAY-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.329513E+09 | 6207.70 | 23-OCT-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.207212E+10 | 24139.95 | 20-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.413611E+10 | 28459.82 | 18-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161443E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.413611E+10 | 28459.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.413695E+10 | 28315.48 | 01-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.327840E+10 | 28315.48 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.285454E+10 | 27456.08 | 06-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.469305E+09 | 8017.12 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.180451E+09 | 6153.65 | 17-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.500957E+09 | 8025.97 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.240972E+10 | 28315.48 | 20-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.451760E+10 | 28315.48 | 03-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183479E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.451760E+10 | 28315.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105469E+11 | 44782.95 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.870691E+10 | 44782.95 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.832802E+10 | 44782.95 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.261242E+10 | 44782.95 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.191482E+10 | 44782.95 | 05-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 99343922.26 | 6325.46 | 08-JUN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2543417.80 | 1745.91 | 05-JUL-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2243971.88 | 1038.49 | 08-SEP-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.290436E+10 | 44782.95 | 21-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.739632E+10 | 44782.95 | 02-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111864E+11 | 44782.95 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.537003E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.111864E+11 | 44782.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.493038E+10 | 23582.71 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.401451E+10 | 23582.71 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.374444E+10 | 23582.71 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.979556E+09 | 23582.71 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.668268E+09 | 23582.71 | 05-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 25801880.11 | 4859.49 | 08-JUN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110211E+10 | 23582.71 | 15-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.327543E+10 | 23582.71 | 02-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.528092E+10 | 23582.71 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.240214E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.528092E+10 | 23582.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.503453E+10 | 23339.21 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.411210E+10 | 23339.21 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.384798E+10 | 23339.21 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105283E+10 | 23339.21 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.737603E+09 | 23339.21 | 05-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32969286.81 | 7241.07 | 08-JUN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 24232.32 | 40.39 | 05-JUL-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117393E+10 | 23339.21 | 15-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.337268E+10 | 23339.21 | 02-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.537688E+10 | 23339.21 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.247415E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.537688E+10 | 23339.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.538681E+10 | 22918.59 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.444354E+10 | 22918.59 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.420194E+10 | 22918.59 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128349E+10 | 22918.59 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.956538E+09 | 22918.59 | 05-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 58905995.91 | 14378.42 | 08-JUN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2434652.64 | 980.99 | 05-JUL-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 979206.72 | 484.39 | 08-SEP-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139329E+10 | 22918.59 | 15-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.367238E+10 | 22918.59 | 01-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.572112E+10 | 22918.59 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271214E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.572112E+10 | 22918.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.652867E+10 | 22532.68 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.549299E+10 | 22532.68 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.529930E+10 | 22532.68 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.187508E+10 | 22532.68 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155790E+10 | 22532.68 | 03-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172189E+09 | 22532.68 | 07-JUN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 22985230.55 | 10253.99 | 05-JUL-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20348955.20 | 5637.55 | 07-SEP-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.200057E+10 | 22532.68 | 14-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.454186E+10 | 22532.68 | 01-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.689827E+10 | 22532.68 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.344102E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.689827E+10 | 22532.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.323868E+09 | 0.321540E+09 | 8980.78 | 30-APR-16:25 | 8980.78 | 0.00 |
May | 0.00 | 0.00 | 0.170007E+09 | 0.145163E+09 | 6905.14 | 22-MAY-15:00 | 6305.43 | 0.00 |
June | 0.00 | 0.00 | 0.141391E+10 | 0.116856E+10 | 12838.60 | 13-JUN-17:00 | 11846.00 | 0.00 |
July | 0.00 | 0.00 | 0.273904E+10 | 0.230698E+10 | 20155.59 | 23-JUL-07:03 | 15157.34 | 0.00 |
August | 0.00 | 0.00 | 0.290729E+10 | 0.236556E+10 | 11808.93 | 14-AUG-17:00 | 11808.93 | 0.00 |
September | 0.00 | 0.00 | 0.151299E+10 | 0.126035E+10 | 10017.48 | 13-SEP-14:00 | 8502.08 | 0.00 |
October | 0.00 | 0.00 | 64536.19 | 64536.19 | 103.89 | 07-OCT-15:00 | 103.89 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.906718E+10 | 0.756823E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.290729E+10 | 0.236556E+10 | 20155.59 | 15157.34 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 10028.10 | 9454.39 | 16.71 | 29-JAN-22:00 | 15.76 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 6229936.63 | 5705396.59 | 323.59 | 19-MAR-19:20 | 285.05 | 0.00 |
April | 0.00 | 0.00 | 0.791552E+09 | 0.791543E+09 | 5880.87 | 30-APR-15:00 | 5880.87 | 0.00 |
May | 0.00 | 0.00 | 0.913815E+09 | 0.876711E+09 | 5004.16 | 22-MAY-15:00 | 4797.66 | 0.00 |
June | 0.00 | 0.00 | 0.282918E+10 | 0.260978E+10 | 11070.59 | 25-JUN-07:02 | 10880.48 | 0.00 |
July | 0.00 | 0.00 | 0.464004E+10 | 0.424387E+10 | 14794.62 | 23-JUL-07:03 | 13930.99 | 0.00 |
August | 0.00 | 0.00 | 0.529344E+10 | 0.482015E+10 | 14699.49 | 06-AUG-07:02 | 13865.45 | 0.00 |
September | 0.00 | 0.00 | 0.360060E+10 | 0.334259E+10 | 9158.17 | 13-SEP-07:03 | 8457.14 | 0.00 |
October | 0.00 | 0.00 | 0.459124E+09 | 0.450529E+09 | 3283.99 | 08-OCT-17:10 | 2840.08 | 0.00 |
November | 0.00 | 0.00 | 7285458.76 | 6998988.68 | 357.03 | 08-NOV-23:00 | 318.68 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.185413E+11 | 0.171479E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.529344E+10 | 0.482015E+10 | 14794.62 | 13930.99 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.108511E+09 | 0.108353E+09 | 5638.02 | 30-APR-15:00 | 5638.02 | 0.00 |
May | 0.00 | 0.00 | 67274550.24 | 62460937.15 | 4687.93 | 22-MAY-15:00 | 4473.49 | 0.00 |
June | 0.00 | 0.00 | 0.656428E+09 | 0.577852E+09 | 9221.63 | 27-JUN-06:02 | 5094.56 | 0.00 |
July | 0.00 | 0.00 | 0.934689E+09 | 0.853742E+09 | 15361.40 | 23-JUL-07:03 | 12252.37 | 0.00 |
August | 0.00 | 0.00 | 0.927191E+09 | 0.812392E+09 | 7051.74 | 06-AUG-07:02 | 4609.34 | 0.00 |
September | 0.00 | 0.00 | 0.617812E+09 | 0.549589E+09 | 7207.58 | 02-SEP-06:02 | 4719.47 | 0.00 |
October | 0.00 | 0.00 | 116435.40 | 116430.06 | 150.97 | 07-OCT-15:00 | 150.97 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.331202E+10 | 0.296451E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.934689E+09 | 0.853742E+09 | 15361.40 | 12252.37 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.102434E+09 | 0.102301E+09 | 5528.65 | 30-APR-15:00 | 5528.65 | 0.00 |
May | 0.00 | 0.00 | 57308304.78 | 53510943.61 | 4408.54 | 22-MAY-15:00 | 4205.10 | 0.00 |
June | 0.00 | 0.00 | 0.637164E+09 | 0.560936E+09 | 7834.16 | 27-JUN-06:02 | 4326.27 | 0.00 |
July | 0.00 | 0.00 | 0.913436E+09 | 0.835147E+09 | 15487.34 | 23-JUL-07:03 | 12349.46 | 0.00 |
August | 0.00 | 0.00 | 0.904373E+09 | 0.792894E+09 | 6877.15 | 14-AUG-17:00 | 6877.15 | 0.00 |
September | 0.00 | 0.00 | 0.594436E+09 | 0.529384E+09 | 5743.71 | 13-SEP-14:00 | 5089.57 | 0.00 |
October | 0.00 | 0.00 | 36817.76 | 36816.01 | 22.79 | 07-OCT-15:00 | 22.79 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.320919E+10 | 0.287421E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.913436E+09 | 0.835147E+09 | 15487.34 | 12349.46 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 86014309.09 | 85947861.18 | 5241.18 | 30-APR-15:00 | 5241.18 | 0.00 |
May | 0.00 | 0.00 | 44216637.18 | 41656498.01 | 3976.82 | 22-MAY-15:00 | 3790.81 | 0.00 |
June | 0.00 | 0.00 | 0.580933E+09 | 0.511912E+09 | 7114.51 | 13-JUN-16:50 | 6665.25 | 0.00 |
July | 0.00 | 0.00 | 0.837072E+09 | 0.769149E+09 | 13253.59 | 23-JUL-07:03 | 10597.96 | 0.00 |
August | 0.00 | 0.00 | 0.818477E+09 | 0.720627E+09 | 6696.77 | 14-AUG-17:00 | 6696.77 | 0.00 |
September | 0.00 | 0.00 | 0.525271E+09 | 0.469125E+09 | 5518.33 | 13-SEP-14:00 | 4888.50 | 0.00 |
October | 0.00 | 0.00 | 9282.89 | 9282.89 | 1.55 | 07-OCT-13:00 | 1.55 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.289199E+10 | 0.259843E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.837072E+09 | 0.769149E+09 | 13253.59 | 10597.96 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.120725E+09 | 0.119995E+09 | 7244.31 | 30-APR-15:00 | 7244.31 | 0.00 |
May | 0.00 | 0.00 | 50335831.03 | 45020796.22 | 4998.72 | 22-MAY-15:00 | 4507.46 | 0.00 |
June | 0.00 | 0.00 | 0.845844E+09 | 0.709210E+09 | 10651.52 | 13-JUN-16:30 | 9585.84 | 0.00 |
July | 0.00 | 0.00 | 0.148704E+10 | 0.128488E+10 | 18595.84 | 23-JUL-08:63 | 14451.26 | 0.00 |
August | 0.00 | 0.00 | 0.171808E+10 | 0.141890E+10 | 10039.31 | 14-AUG-17:00 | 10039.31 | 0.00 |
September | 0.00 | 0.00 | 0.904344E+09 | 0.768871E+09 | 8765.45 | 13-SEP-14:10 | 7410.87 | 0.00 |
October | 0.00 | 0.00 | 1621.56 | 1621.56 | 0.98 | 07-OCT-15:00 | 0.98 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.512638E+10 | 0.434688E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.171808E+10 | 0.141890E+10 | 18595.84 | 14451.26 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.123930E+09 | 0.123930E+09 | 4256.53 | 30-APR-15:00 | 4256.53 | 0.00 |
May | 0.00 | 0.00 | 89370292.61 | 80796242.39 | 2962.30 | 22-MAY-15:00 | 2790.35 | 0.00 |
June | 0.00 | 0.00 | 0.701989E+09 | 0.626577E+09 | 5884.03 | 13-JUN-17:00 | 5494.58 | 0.00 |
July | 0.00 | 0.00 | 0.162099E+10 | 0.144577E+10 | 9777.68 | 23-JUL-08:63 | 9777.68 | 0.00 |
August | 0.00 | 0.00 | 0.217415E+10 | 0.192743E+10 | 5708.50 | 14-AUG-17:00 | 5708.50 | 0.00 |
September | 0.00 | 0.00 | 0.100463E+10 | 0.904767E+09 | 4971.51 | 13-SEP-14:20 | 4474.88 | 0.00 |
October | 0.00 | 0.00 | 5696037.51 | 5696037.51 | 1108.35 | 07-OCT-15:00 | 1108.35 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.572075E+10 | 0.511497E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.217415E+10 | 0.192743E+10 | 9777.68 | 9777.68 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.115634E+09 | 0.115634E+09 | 4150.44 | 30-APR-15:00 | 4150.44 | 0.00 |
May | 0.00 | 0.00 | 80839987.43 | 73096516.49 | 2853.54 | 22-MAY-15:00 | 2687.10 | 0.00 |
June | 0.00 | 0.00 | 0.658923E+09 | 0.587291E+09 | 5771.90 | 13-JUN-17:00 | 5389.63 | 0.00 |
July | 0.00 | 0.00 | 0.154016E+10 | 0.137332E+10 | 9196.68 | 23-JUL-08:63 | 9196.68 | 0.00 |
August | 0.00 | 0.00 | 0.207223E+10 | 0.183559E+10 | 5628.44 | 14-AUG-17:00 | 5628.44 | 0.00 |
September | 0.00 | 0.00 | 0.948779E+09 | 0.853844E+09 | 4881.55 | 13-SEP-14:20 | 4391.26 | 0.00 |
October | 0.00 | 0.00 | 4581224.02 | 4581224.02 | 991.53 | 07-OCT-15:00 | 991.53 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.542115E+10 | 0.484335E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.207223E+10 | 0.183559E+10 | 9196.68 | 9196.68 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 96017409.44 | 96017409.44 | 3886.76 | 30-APR-15:00 | 3886.76 | 0.00 |
May | 0.00 | 0.00 | 61853812.40 | 56007479.30 | 2585.93 | 22-MAY-15:00 | 2433.32 | 0.00 |
June | 0.00 | 0.00 | 0.557769E+09 | 0.495192E+09 | 5524.06 | 13-JUN-17:00 | 5156.71 | 0.00 |
July | 0.00 | 0.00 | 0.132421E+10 | 0.118143E+10 | 7367.37 | 23-JUL-08:63 | 7367.37 | 0.00 |
August | 0.00 | 0.00 | 0.177783E+10 | 0.157188E+10 | 5425.22 | 14-AUG-17:00 | 5425.22 | 0.00 |
September | 0.00 | 0.00 | 0.799009E+09 | 0.717628E+09 | 4675.51 | 13-SEP-14:20 | 4200.19 | 0.00 |
October | 0.00 | 0.00 | 2192506.20 | 2192506.20 | 652.94 | 07-OCT-15:00 | 652.94 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.461889E+10 | 0.412034E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.177783E+10 | 0.157188E+10 | 7367.37 | 7367.37 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 77581809.45 | 77581809.45 | 3543.05 | 30-APR-15:00 | 3543.05 | 0.00 |
May | 0.00 | 0.00 | 42033508.84 | 38334227.39 | 2267.80 | 22-MAY-15:00 | 2132.32 | 0.00 |
June | 0.00 | 0.00 | 0.459364E+09 | 0.407108E+09 | 5256.64 | 13-JUN-17:00 | 4904.26 | 0.00 |
July | 0.00 | 0.00 | 0.102781E+10 | 0.925267E+09 | 6835.22 | 22-JUL-15:00 | 6835.22 | 0.00 |
August | 0.00 | 0.00 | 0.134118E+10 | 0.118522E+10 | 5113.05 | 14-AUG-17:00 | 5113.05 | 0.00 |
September | 0.00 | 0.00 | 0.621963E+09 | 0.558278E+09 | 4400.83 | 13-SEP-14:10 | 3949.99 | 0.00 |
October | 0.00 | 0.00 | 147363.85 | 147363.85 | 157.40 | 07-OCT-15:10 | 157.40 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.357008E+10 | 0.319194E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.134118E+10 | 0.118522E+10 | 6835.22 | 6835.22 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140901E+10 | 0.41 | 1606.89 | 02-JAN-08:61 | 0.89 |
February | 0.126027E+10 | 0.41 | 1606.89 | 01-FEB-08:61 | 0.89 |
March | 0.135367E+10 | 0.40 | 1606.89 | 01-MAR-08:61 | 0.89 |
April | 0.117883E+10 | 0.37 | 1606.89 | 01-APR-07:01 | 0.89 |
May | 0.119744E+10 | 0.37 | 1606.89 | 05-MAY-07:01 | 0.89 |
June | 0.113229E+10 | 0.36 | 729.43 | 08-JUN-08:15 | 0.58 |
July | 0.117137E+10 | 0.36 | 1253.84 | 23-JUL-07:03 | 0.78 |
August | 0.116622E+10 | 0.36 | 642.76 | 03-AUG-19:20 | 0.53 |
September | 0.113382E+10 | 0.36 | 642.76 | 10-SEP-21:50 | 0.53 |
October | 0.121308E+10 | 0.37 | 1471.59 | 23-OCT-07:01 | 0.85 |
November | 0.128197E+10 | 0.39 | 1606.89 | 03-NOV-07:01 | 0.89 |
December | 0.143490E+10 | 0.42 | 1606.89 | 01-DEC-08:61 | 0.89 |
Annual Sum or Average | 0.149329E+11 | 0.38 | |||
Minimum of Months | 0.113229E+10 | 0.36 | 642.76 | 0.53 | |
Maximum of Months | 0.143490E+10 | 0.42 | 1606.89 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.131355E+10 | 0.46 | 967.84 | 01-JAN-12:50 | 0.92 |
February | 0.118812E+10 | 0.46 | 967.84 | 28-FEB-19:00 | 0.92 |
March | 0.133570E+10 | 0.49 | 967.84 | 01-MAR-14:40 | 0.92 |
April | 0.133637E+10 | 0.62 | 967.84 | 01-APR-09:10 | 0.92 |
May | 0.140037E+10 | 0.63 | 967.84 | 11-MAY-15:00 | 0.92 |
June | 0.144870E+10 | 0.65 | 967.84 | 02-JUN-07:20 | 0.91 |
July | 0.151574E+10 | 0.65 | 967.84 | 02-JUL-12:10 | 0.91 |
August | 0.153487E+10 | 0.64 | 967.84 | 01-AUG-07:05 | 0.91 |
September | 0.144990E+10 | 0.65 | 967.84 | 01-SEP-11:10 | 0.91 |
October | 0.136988E+10 | 0.61 | 967.84 | 01-OCT-07:06 | 0.91 |
November | 0.127670E+10 | 0.49 | 967.84 | 02-NOV-11:40 | 0.92 |
December | 0.130658E+10 | 0.46 | 967.84 | 02-DEC-13:00 | 0.91 |
Annual Sum or Average | 0.164765E+11 | 0.57 | |||
Minimum of Months | 0.118812E+10 | 0.46 | 967.84 | 0.91 | |
Maximum of Months | 0.153487E+10 | 0.65 | 967.84 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.158004E+10 | 0.50 | 1091.79 | 01-JAN-12:20 | 0.92 |
February | 0.143068E+10 | 0.50 | 1091.79 | 01-FEB-20:50 | 0.92 |
March | 0.161148E+10 | 0.51 | 1091.79 | 02-MAR-14:20 | 0.92 |
April | 0.153287E+10 | 0.50 | 1091.79 | 03-APR-15:20 | 0.92 |
May | 0.159576E+10 | 0.50 | 1091.79 | 17-MAY-14:40 | 0.91 |
June | 0.155645E+10 | 0.50 | 1091.79 | 02-JUN-14:40 | 0.91 |
July | 0.157218E+10 | 0.49 | 1091.79 | 08-JUL-09:20 | 0.91 |
August | 0.161148E+10 | 0.50 | 1091.79 | 01-AUG-17:50 | 0.91 |
September | 0.153287E+10 | 0.49 | 1091.79 | 05-SEP-13:10 | 0.91 |
October | 0.158004E+10 | 0.49 | 1091.79 | 02-OCT-14:30 | 0.91 |
November | 0.153287E+10 | 0.50 | 1091.79 | 01-NOV-08:30 | 0.92 |
December | 0.157218E+10 | 0.49 | 1091.79 | 07-DEC-08:07 | 0.92 |
Annual Sum or Average | 0.187089E+11 | 0.50 | |||
Minimum of Months | 0.143068E+10 | 0.49 | 1091.79 | 0.91 | |
Maximum of Months | 0.161148E+10 | 0.51 | 1091.79 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157289E+10 | 0.50 | 1086.85 | 01-JAN-09:04 | 0.92 |
February | 0.142421E+10 | 0.50 | 1086.85 | 01-FEB-08:30 | 0.92 |
March | 0.160419E+10 | 0.51 | 1086.85 | 01-MAR-08:04 | 0.92 |
April | 0.152594E+10 | 0.50 | 1086.85 | 01-APR-07:06 | 0.92 |
May | 0.158854E+10 | 0.50 | 1086.85 | 01-MAY-06:10 | 0.92 |
June | 0.154942E+10 | 0.50 | 1086.85 | 01-JUN-12:10 | 0.91 |
July | 0.156507E+10 | 0.49 | 1086.85 | 01-JUL-11:00 | 0.91 |
August | 0.160419E+10 | 0.50 | 1086.85 | 01-AUG-06:08 | 0.91 |
September | 0.152594E+10 | 0.49 | 1086.85 | 01-SEP-06:10 | 0.91 |
October | 0.157289E+10 | 0.49 | 1086.85 | 01-OCT-14:30 | 0.91 |
November | 0.152594E+10 | 0.50 | 1086.85 | 01-NOV-08:10 | 0.92 |
December | 0.156507E+10 | 0.49 | 1086.85 | 01-DEC-14:20 | 0.92 |
Annual Sum or Average | 0.186243E+11 | 0.50 | |||
Minimum of Months | 0.142421E+10 | 0.49 | 1086.85 | 0.91 | |
Maximum of Months | 0.160419E+10 | 0.51 | 1086.85 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156267E+10 | 0.50 | 1079.79 | 02-JAN-07:50 | 0.92 |
February | 0.141495E+10 | 0.50 | 1079.79 | 01-FEB-09:30 | 0.92 |
March | 0.159376E+10 | 0.51 | 1079.79 | 01-MAR-08:15 | 0.92 |
April | 0.151602E+10 | 0.50 | 1079.79 | 01-APR-09:05 | 0.92 |
May | 0.157822E+10 | 0.50 | 1079.79 | 03-MAY-07:50 | 0.92 |
June | 0.153934E+10 | 0.50 | 1079.79 | 09-JUN-15:00 | 0.91 |
July | 0.155489E+10 | 0.49 | 1079.79 | 12-JUL-18:30 | 0.91 |
August | 0.159376E+10 | 0.50 | 1079.79 | 01-AUG-17:30 | 0.91 |
September | 0.151602E+10 | 0.49 | 1079.79 | 05-SEP-14:00 | 0.91 |
October | 0.156267E+10 | 0.49 | 1079.79 | 16-OCT-11:40 | 0.91 |
November | 0.151602E+10 | 0.50 | 1079.79 | 02-NOV-09:20 | 0.92 |
December | 0.155489E+10 | 0.49 | 1079.79 | 02-DEC-11:30 | 0.92 |
Annual Sum or Average | 0.185032E+11 | 0.50 | |||
Minimum of Months | 0.141495E+10 | 0.49 | 1079.79 | 0.91 | |
Maximum of Months | 0.159376E+10 | 0.51 | 1079.79 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.106257E+10 | 0.31 | 1572.90 | 01-JAN-09:01 | 0.89 |
February | 0.944520E+09 | 0.31 | 1572.90 | 01-FEB-08:61 | 0.89 |
March | 0.103393E+10 | 0.31 | 1572.90 | 01-MAR-08:61 | 0.89 |
April | 0.870446E+09 | 0.28 | 1572.90 | 01-APR-07:01 | 0.89 |
May | 0.889720E+09 | 0.28 | 1572.90 | 05-MAY-07:01 | 0.88 |
June | 0.831076E+09 | 0.27 | 762.46 | 08-JUN-07:02 | 0.61 |
July | 0.836522E+09 | 0.26 | 1132.37 | 23-JUL-08:63 | 0.75 |
August | 0.858427E+09 | 0.27 | 629.16 | 01-AUG-14:20 | 0.53 |
September | 0.815440E+09 | 0.27 | 651.05 | 08-SEP-09:00 | 0.55 |
October | 0.901513E+09 | 0.28 | 1572.90 | 21-OCT-07:01 | 0.89 |
November | 0.971260E+09 | 0.30 | 1572.90 | 02-NOV-07:01 | 0.88 |
December | 0.107152E+10 | 0.31 | 1572.90 | 01-DEC-08:61 | 0.89 |
Annual Sum or Average | 0.110869E+11 | 0.29 | |||
Minimum of Months | 0.815440E+09 | 0.26 | 629.16 | 0.53 | |
Maximum of Months | 0.107152E+10 | 0.31 | 1572.90 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.114759E+10 | 0.46 | 859.23 | 03-JAN-10:10 | 0.92 |
February | 0.103933E+10 | 0.46 | 859.23 | 04-FEB-15:20 | 0.92 |
March | 0.117234E+10 | 0.47 | 859.23 | 03-MAR-08:30 | 0.92 |
April | 0.111357E+10 | 0.46 | 859.23 | 02-APR-10:30 | 0.92 |
May | 0.115997E+10 | 0.46 | 859.23 | 04-MAY-09:40 | 0.91 |
June | 0.113213E+10 | 0.46 | 859.23 | 01-JUN-07:03 | 0.91 |
July | 0.114141E+10 | 0.45 | 859.23 | 14-JUL-18:00 | 0.91 |
August | 0.117234E+10 | 0.46 | 859.23 | 01-AUG-12:30 | 0.91 |
September | 0.111357E+10 | 0.46 | 859.23 | 12-SEP-07:50 | 0.91 |
October | 0.114759E+10 | 0.46 | 859.23 | 12-OCT-10:30 | 0.91 |
November | 0.111357E+10 | 0.46 | 859.23 | 01-NOV-10:10 | 0.92 |
December | 0.114141E+10 | 0.45 | 859.23 | 06-DEC-08:40 | 0.92 |
Annual Sum or Average | 0.135948E+11 | 0.46 | |||
Minimum of Months | 0.103933E+10 | 0.45 | 859.23 | 0.91 | |
Maximum of Months | 0.117234E+10 | 0.47 | 859.23 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.113357E+10 | 0.46 | 848.74 | 01-JAN-10:20 | 0.92 |
February | 0.102663E+10 | 0.46 | 848.74 | 01-FEB-09:20 | 0.92 |
March | 0.115802E+10 | 0.47 | 848.74 | 01-MAR-08:30 | 0.92 |
April | 0.109996E+10 | 0.46 | 848.74 | 01-APR-07:40 | 0.92 |
May | 0.114580E+10 | 0.46 | 848.74 | 03-MAY-09:40 | 0.92 |
June | 0.111830E+10 | 0.46 | 848.74 | 06-JUN-08:40 | 0.91 |
July | 0.112746E+10 | 0.45 | 848.74 | 05-JUL-18:20 | 0.92 |
August | 0.115802E+10 | 0.46 | 848.74 | 01-AUG-07:50 | 0.91 |
September | 0.109996E+10 | 0.46 | 848.74 | 01-SEP-11:50 | 0.91 |
October | 0.113357E+10 | 0.46 | 848.74 | 07-OCT-15:50 | 0.92 |
November | 0.109996E+10 | 0.46 | 848.74 | 01-NOV-10:20 | 0.92 |
December | 0.112746E+10 | 0.45 | 848.74 | 01-DEC-08:30 | 0.92 |
Annual Sum or Average | 0.134287E+11 | 0.46 | |||
Minimum of Months | 0.102663E+10 | 0.45 | 848.74 | 0.91 | |
Maximum of Months | 0.115802E+10 | 0.47 | 848.74 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.111011E+10 | 0.46 | 831.17 | 01-JAN-09:09 | 0.92 |
February | 0.100539E+10 | 0.46 | 831.17 | 01-FEB-10:10 | 0.91 |
March | 0.113405E+10 | 0.47 | 831.17 | 01-MAR-09:00 | 0.92 |
April | 0.107720E+10 | 0.46 | 831.17 | 17-APR-09:00 | 0.92 |
May | 0.112208E+10 | 0.46 | 831.17 | 01-MAY-16:30 | 0.91 |
June | 0.109515E+10 | 0.46 | 831.17 | 08-JUN-10:10 | 0.91 |
July | 0.110413E+10 | 0.45 | 831.17 | 04-JUL-16:50 | 0.91 |
August | 0.113405E+10 | 0.46 | 831.17 | 08-AUG-19:15 | 0.91 |
September | 0.107720E+10 | 0.46 | 831.17 | 12-SEP-09:40 | 0.91 |
October | 0.111011E+10 | 0.46 | 831.17 | 12-OCT-12:00 | 0.91 |
November | 0.107720E+10 | 0.46 | 831.17 | 01-NOV-07:30 | 0.92 |
December | 0.110413E+10 | 0.45 | 831.17 | 01-DEC-08:10 | 0.92 |
Annual Sum or Average | 0.131508E+11 | 0.46 | |||
Minimum of Months | 0.100539E+10 | 0.45 | 831.17 | 0.91 | |
Maximum of Months | 0.113405E+10 | 0.47 | 831.17 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.109980E+10 | 0.46 | 823.45 | 04-JAN-13:30 | 0.92 |
February | 0.996047E+09 | 0.46 | 823.45 | 15-FEB-10:00 | 0.92 |
March | 0.112352E+10 | 0.47 | 823.45 | 01-MAR-21:00 | 0.92 |
April | 0.106719E+10 | 0.46 | 823.45 | 01-APR-10:30 | 0.92 |
May | 0.111166E+10 | 0.46 | 823.45 | 13-MAY-12:20 | 0.91 |
June | 0.108498E+10 | 0.46 | 823.45 | 02-JUN-08:50 | 0.91 |
July | 0.109387E+10 | 0.45 | 823.45 | 04-JUL-10:20 | 0.91 |
August | 0.112352E+10 | 0.46 | 823.45 | 21-AUG-13:30 | 0.91 |
September | 0.106719E+10 | 0.46 | 823.45 | 01-SEP-12:20 | 0.91 |
October | 0.109980E+10 | 0.46 | 823.45 | 30-OCT-11:00 | 0.91 |
November | 0.106719E+10 | 0.46 | 823.45 | 21-NOV-08:15 | 0.92 |
December | 0.109387E+10 | 0.45 | 823.45 | 18-DEC-08:09 | 0.92 |
Annual Sum or Average | 0.130287E+11 | 0.46 | |||
Minimum of Months | 0.996047E+09 | 0.45 | 823.45 | 0.91 | |
Maximum of Months | 0.112352E+10 | 0.47 | 823.45 | 0.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.50 | 0.25 |
February | 0.78 | 0.48 |
March | 0.46 | 0.68 |
April | 0.28 | 0.75 |
May | 0.31 | 0.82 |
June | 0.25 | 1.50 |
July | 0.17 | 1.50 |
August | 0.00 | 0.00 |
September | 0.39 | 0.96 |
October | 0.44 | 0.84 |
November | 0.28 | 0.75 |
December | 0.52 | 1.10 |
Annual Sum or Average | 4.37 | 0.78 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.78 | 1.50 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.94 | 6.48 |
February | 1.25 | 6.83 |
March | 2.00 | 5.19 |
April | 1.94 | 3.86 |
May | 1.75 | 2.83 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.08 | 0.75 |
October | 1.42 | 3.29 |
November | 2.19 | 5.36 |
December | 0.08 | 4.50 |
Annual Sum or Average | 11.67 | 4.66 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.19 | 6.83 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 1.69 | 0.75 |
May | 1.92 | 0.72 |
June | 1.17 | 0.75 |
July | 0.51 | 0.75 |
August | 0.08 | 0.75 |
September | 1.39 | 0.75 |
October | 1.69 | 0.71 |
November | 0.14 | 0.75 |
December | 0.00 | 0.00 |
Annual Sum or Average | 8.59 | 0.74 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.92 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 1.14 | 0.75 |
May | 1.53 | 0.71 |
June | 1.42 | 0.75 |
July | 0.51 | 0.75 |
August | 0.00 | 0.00 |
September | 1.39 | 0.75 |
October | 1.36 | 0.70 |
November | 0.06 | 0.75 |
December | 0.00 | 0.00 |
Annual Sum or Average | 7.39 | 0.73 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.53 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.81 | 0.75 |
May | 1.47 | 0.71 |
June | 1.58 | 0.75 |
July | 0.59 | 0.75 |
August | 0.00 | 0.00 |
September | 1.64 | 0.75 |
October | 1.28 | 0.70 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 7.37 | 0.73 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.64 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.06 | 3.30 |
June | 0.00 | 0.00 |
July | 0.17 | 3.30 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.08 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.31 | 2.42 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.17 | 3.30 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.14 | 1.65 |
June | 0.00 | 0.00 |
July | 0.17 | 1.65 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.08 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.39 | 1.30 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.17 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.08 | 1.65 |
June | 0.00 | 0.00 |
July | 0.17 | 1.65 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.08 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.34 | 1.24 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.17 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.17 | 1.65 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 1.65 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.17 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.31 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.17 | 1.65 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.39 | 0.00 |
Annual Sum or Average | 0.87 | 0.33 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.39 | 1.65 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.140901E+10 | 0.142642E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.126027E+10 | 0.120602E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.135367E+10 | 0.108858E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.125947E+10 | 0.278267E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.124198E+10 | 0.183591E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.147494E+10 | 41105357.31 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.185239E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.189942E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.150945E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.121310E+10 | 0.275537E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.128197E+10 | 0.911682E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.143490E+10 | 0.155172E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.171906E+11 | 0.692592E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.121310E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.189942E+10 | 0.155172E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.131355E+10 | 0.333746E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.118812E+10 | 0.249113E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.133744E+10 | 0.198907E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.152161E+10 | 0.125522E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.162026E+10 | 19533476.71 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.209455E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.255274E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.270821E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.226640E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.148589E+10 | 99522926.19 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.127873E+10 | 0.151621E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.130658E+10 | 0.383367E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.206741E+11 | 0.134121E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.118812E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.270821E+10 | 0.383367E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.158004E+10 | 0.435119E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.143068E+10 | 0.339356E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.161148E+10 | 0.281759E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.155704E+10 | 0.303198E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.161105E+10 | 47418841.39 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.169876E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.177836E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.181819E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.166980E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.158006E+10 | 0.278038E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.153287E+10 | 0.227606E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.157218E+10 | 0.484380E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.194405E+11 | 0.183108E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.143068E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.181819E+10 | 0.484380E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.157289E+10 | 0.469805E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.142421E+10 | 0.368135E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.160419E+10 | 0.311896E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.154878E+10 | 0.412713E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.160161E+10 | 97090366.31 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.168781E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.176662E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.180598E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.165788E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.157290E+10 | 0.411891E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.152594E+10 | 0.259015E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.156507E+10 | 0.517014E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.193339E+11 | 0.201803E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.142421E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.180598E+10 | 0.517014E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.156267E+10 | 0.517119E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.141495E+10 | 0.409800E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.159376E+10 | 0.356818E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.153524E+10 | 0.586631E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.158836E+10 | 0.225564E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.166633E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.174020E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.177689E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.163315E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.156267E+10 | 0.626196E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.151602E+10 | 0.301215E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.155489E+10 | 0.564700E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.191451E+11 | 0.229349E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.141495E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.177689E+10 | 0.564700E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.106257E+10 | 0.131836E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.944520E+09 | 0.108836E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.103393E+10 | 0.104100E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.901476E+09 | 0.326552E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.903137E+09 | 0.239353E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.104267E+10 | 0.124180E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.121103E+10 | 3179272.25 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.129583E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.104429E+10 | 2804964.86 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.901513E+09 | 0.363045E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.971260E+09 | 0.924540E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.107152E+10 | 0.139831E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.123837E+11 | 0.671254E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.901476E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.129583E+10 | 0.139831E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.114759E+10 | 0.616298E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.103933E+10 | 0.501813E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.117234E+10 | 0.468055E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.114143E+10 | 0.122445E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.118080E+10 | 0.835334E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.128699E+10 | 32252350.13 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.150130E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.165644E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.133598E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.114895E+10 | 0.137763E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.111357E+10 | 0.409429E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.114141E+10 | 0.660115E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.148661E+11 | 0.300268E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.103933E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.165644E+10 | 0.660115E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.113357E+10 | 0.629317E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.102663E+10 | 0.514012E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.115802E+10 | 0.480997E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.112598E+10 | 0.131604E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.116468E+10 | 0.922004E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.126376E+10 | 41211608.51 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.146966E+10 | 30290.41 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.161997E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.131017E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.113466E+10 | 0.146741E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.109996E+10 | 0.421584E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.112746E+10 | 0.672110E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.146345E+11 | 0.309269E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.102663E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.161997E+10 | 0.672110E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.111011E+10 | 0.673351E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.100539E+10 | 0.555442E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.113405E+10 | 0.525243E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.109888E+10 | 0.160436E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.113664E+10 | 0.119567E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.121866E+10 | 73632494.89 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.139892E+10 | 3043315.80 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.153161E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.125478E+10 | 1224008.40 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.111064E+10 | 0.174162E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.107720E+10 | 0.459048E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.110413E+10 | 0.715139E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.141810E+11 | 0.339018E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.100539E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.153161E+10 | 0.715139E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.109980E+10 | 0.816084E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.996047E+09 | 0.686624E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.112352E+10 | 0.662413E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.108484E+10 | 0.234385E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.112164E+10 | 0.194737E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.118711E+10 | 0.215236E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.132262E+10 | 28731538.19 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.142495E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.120611E+10 | 25436194.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.109984E+10 | 0.250071E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.106719E+10 | 0.567732E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.109387E+10 | 0.862283E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.138275E+11 | 0.430127E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.996047E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.142495E+10 | 0.862283E+10 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140901E+10 | 0.00 | 0.114113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126027E+10 | 0.00 | 0.964819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135367E+10 | 0.00 | 0.870861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117883E+10 | 0.323868E+09 | 0.222614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.119744E+10 | 0.170007E+09 | 0.146873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113229E+10 | 0.141391E+10 | 32884285.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.117137E+10 | 0.273904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116622E+10 | 0.290729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113382E+10 | 0.151299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121308E+10 | 64536.19 | 0.220429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128197E+10 | 0.00 | 0.729345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143490E+10 | 0.00 | 0.124138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149329E+11 | 0.906718E+10 | 0.554074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.113229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143490E+10 | 0.290729E+10 | 0.124138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.131355E+10 | 10028.10 | 0.266997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118812E+10 | 0.00 | 0.199290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133570E+10 | 6229936.63 | 0.159126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133637E+10 | 0.791552E+09 | 0.100418E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140037E+10 | 0.913815E+09 | 15626781.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144870E+10 | 0.282918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151574E+10 | 0.464004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153487E+10 | 0.529344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144990E+10 | 0.360060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136988E+10 | 0.459124E+09 | 79618340.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127670E+10 | 7285458.76 | 0.121297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130658E+10 | 0.00 | 0.306693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164765E+11 | 0.185413E+11 | 0.107297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153487E+10 | 0.529344E+10 | 0.306693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.158004E+10 | 0.00 | 0.348095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143068E+10 | 0.00 | 0.271484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161148E+10 | 0.00 | 0.225407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153287E+10 | 0.108511E+09 | 0.242558E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159576E+10 | 67274550.24 | 37935073.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155645E+10 | 0.656428E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157218E+10 | 0.934689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161148E+10 | 0.927191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153287E+10 | 0.617812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158004E+10 | 116435.40 | 0.222430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153287E+10 | 0.00 | 0.182085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157218E+10 | 0.00 | 0.387504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187089E+11 | 0.331202E+10 | 0.146487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161148E+10 | 0.934689E+09 | 0.387504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.157289E+10 | 0.00 | 0.375844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142421E+10 | 0.00 | 0.294508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160419E+10 | 0.00 | 0.249517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152594E+10 | 0.102434E+09 | 0.330170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158854E+10 | 57308304.78 | 77672293.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154942E+10 | 0.637164E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156507E+10 | 0.913436E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160419E+10 | 0.904373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152594E+10 | 0.594436E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157289E+10 | 36817.76 | 0.329513E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152594E+10 | 0.00 | 0.207212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156507E+10 | 0.00 | 0.413611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186243E+11 | 0.320919E+10 | 0.161443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160419E+10 | 0.913436E+09 | 0.413611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.156267E+10 | 0.00 | 0.413695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141495E+10 | 0.00 | 0.327840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159376E+10 | 0.00 | 0.285454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151602E+10 | 86014309.09 | 0.469305E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157822E+10 | 44216637.18 | 0.180451E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153934E+10 | 0.580933E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155489E+10 | 0.837072E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159376E+10 | 0.818477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151602E+10 | 0.525271E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156267E+10 | 9282.89 | 0.500957E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151602E+10 | 0.00 | 0.240972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155489E+10 | 0.00 | 0.451760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185032E+11 | 0.289199E+10 | 0.183479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159376E+10 | 0.837072E+09 | 0.451760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.106257E+10 | 0.00 | 0.105469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.944520E+09 | 0.00 | 0.870691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103393E+10 | 0.00 | 0.832802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.870446E+09 | 0.120725E+09 | 0.261242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.889720E+09 | 50335831.03 | 0.191482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.831076E+09 | 0.845844E+09 | 99343922.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.836522E+09 | 0.148704E+10 | 2543417.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.858427E+09 | 0.171808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.815440E+09 | 0.904344E+09 | 2243971.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.901513E+09 | 1621.56 | 0.290436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.971260E+09 | 0.00 | 0.739632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107152E+10 | 0.00 | 0.111864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110869E+11 | 0.512638E+10 | 0.537003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.815440E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.107152E+10 | 0.171808E+10 | 0.111864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.114759E+10 | 0.00 | 0.493038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103933E+10 | 0.00 | 0.401451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117234E+10 | 0.00 | 0.374444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111357E+10 | 0.123930E+09 | 0.979556E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115997E+10 | 89370292.61 | 0.668268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113213E+10 | 0.701989E+09 | 25801880.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.114141E+10 | 0.162099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117234E+10 | 0.217415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111357E+10 | 0.100463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114759E+10 | 5696037.51 | 0.110211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111357E+10 | 0.00 | 0.327543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114141E+10 | 0.00 | 0.528092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135948E+11 | 0.572075E+10 | 0.240214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.117234E+10 | 0.217415E+10 | 0.528092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.113357E+10 | 0.00 | 0.503453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102663E+10 | 0.00 | 0.411210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115802E+10 | 0.00 | 0.384798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109996E+10 | 0.115634E+09 | 0.105283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114580E+10 | 80839987.43 | 0.737603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.111830E+10 | 0.658923E+09 | 32969286.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.112746E+10 | 0.154016E+10 | 24232.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.115802E+10 | 0.207223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.109996E+10 | 0.948779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113357E+10 | 4581224.02 | 0.117393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109996E+10 | 0.00 | 0.337268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112746E+10 | 0.00 | 0.537688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134287E+11 | 0.542115E+10 | 0.247415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.102663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115802E+10 | 0.207223E+10 | 0.537688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.111011E+10 | 0.00 | 0.538681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100539E+10 | 0.00 | 0.444354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113405E+10 | 0.00 | 0.420194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107720E+10 | 96017409.44 | 0.128349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112208E+10 | 61853812.40 | 0.956538E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.109515E+10 | 0.557769E+09 | 58905995.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110413E+10 | 0.132421E+10 | 2434652.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.113405E+10 | 0.177783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107720E+10 | 0.799009E+09 | 979206.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111011E+10 | 2192506.20 | 0.139329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107720E+10 | 0.00 | 0.367238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110413E+10 | 0.00 | 0.572112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131508E+11 | 0.461889E+10 | 0.271214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.100539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.113405E+10 | 0.177783E+10 | 0.572112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.109980E+10 | 0.00 | 0.652867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.996047E+09 | 0.00 | 0.549299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112352E+10 | 0.00 | 0.529930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106719E+10 | 77581809.45 | 0.187508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111166E+10 | 42033508.84 | 0.155790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108498E+10 | 0.459364E+09 | 0.172189E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109387E+10 | 0.102781E+10 | 22985230.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.112352E+10 | 0.134118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.106719E+10 | 0.621963E+09 | 20348955.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109980E+10 | 147363.85 | 0.200057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106719E+10 | 0.00 | 0.454186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109387E+10 | 0.00 | 0.689827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130287E+11 | 0.357008E+10 | 0.344102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.996047E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.112352E+10 | 0.134118E+10 | 0.689827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.140901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117883E+10 | 0.00 | 0.00 | 0.00 | 80635973.83 | 0.00 | 0.278267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.119744E+10 | 0.00 | 0.00 | 0.00 | 44534782.18 | 0.00 | 0.183591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113229E+10 | 0.00 | 0.00 | 0.00 | 0.342654E+09 | 0.00 | 41105357.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.117137E+10 | 0.00 | 0.00 | 0.00 | 0.681027E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116622E+10 | 0.00 | 0.00 | 0.00 | 0.733201E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113382E+10 | 0.00 | 0.00 | 0.00 | 0.375629E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121308E+10 | 0.00 | 0.00 | 0.00 | 18190.04 | 0.00 | 0.275537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.911682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149329E+11 | 0.00 | 0.00 | 0.00 | 0.225770E+10 | 0.00 | 0.692592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.113229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143490E+10 | 0.00 | 0.00 | 0.00 | 0.733201E+09 | 0.00 | 0.155172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.131355E+10 | 0.00 | 0.00 | 0.00 | 2827.64 | 0.00 | 0.333746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133570E+10 | 0.00 | 0.00 | 0.00 | 1738229.08 | 0.00 | 0.198907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133637E+10 | 0.00 | 0.00 | 0.00 | 0.185245E+09 | 0.00 | 0.125522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140037E+10 | 0.00 | 0.00 | 0.00 | 0.219890E+09 | 0.00 | 19533476.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144870E+10 | 0.00 | 0.00 | 0.00 | 0.645857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151574E+10 | 0.00 | 0.00 | 0.00 | 0.103700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153487E+10 | 0.00 | 0.00 | 0.00 | 0.117333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144990E+10 | 0.00 | 0.00 | 0.00 | 0.816498E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136988E+10 | 0.00 | 0.00 | 0.00 | 0.116015E+09 | 0.00 | 99522926.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127670E+10 | 0.00 | 0.00 | 0.00 | 2029451.30 | 0.00 | 0.151621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164765E+11 | 0.00 | 0.00 | 0.00 | 0.419761E+10 | 0.00 | 0.134121E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.118812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153487E+10 | 0.00 | 0.00 | 0.00 | 0.117333E+10 | 0.00 | 0.383367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.158004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153287E+10 | 0.00 | 0.00 | 0.00 | 24165611.52 | 0.00 | 0.303198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159576E+10 | 0.00 | 0.00 | 0.00 | 15288028.69 | 0.00 | 47418841.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155645E+10 | 0.00 | 0.00 | 0.00 | 0.142302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157218E+10 | 0.00 | 0.00 | 0.00 | 0.206180E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161148E+10 | 0.00 | 0.00 | 0.00 | 0.206706E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153287E+10 | 0.00 | 0.00 | 0.00 | 0.136924E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158004E+10 | 0.00 | 0.00 | 0.00 | 28571.10 | 0.00 | 0.278038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187089E+11 | 0.00 | 0.00 | 0.00 | 0.731595E+09 | 0.00 | 0.183108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.143068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161148E+10 | 0.00 | 0.00 | 0.00 | 0.206706E+09 | 0.00 | 0.484380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.157289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152594E+10 | 0.00 | 0.00 | 0.00 | 22836847.45 | 0.00 | 0.412713E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158854E+10 | 0.00 | 0.00 | 0.00 | 13068287.02 | 0.00 | 97090366.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154942E+10 | 0.00 | 0.00 | 0.00 | 0.138393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156507E+10 | 0.00 | 0.00 | 0.00 | 0.201553E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160419E+10 | 0.00 | 0.00 | 0.00 | 0.201789E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152594E+10 | 0.00 | 0.00 | 0.00 | 0.131935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157289E+10 | 0.00 | 0.00 | 0.00 | 9078.48 | 0.00 | 0.411891E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186243E+11 | 0.00 | 0.00 | 0.00 | 0.709584E+09 | 0.00 | 0.201803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.142421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160419E+10 | 0.00 | 0.00 | 0.00 | 0.201789E+09 | 0.00 | 0.517014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.156267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151602E+10 | 0.00 | 0.00 | 0.00 | 19215843.60 | 0.00 | 0.586631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157822E+10 | 0.00 | 0.00 | 0.00 | 10139974.18 | 0.00 | 0.225564E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153934E+10 | 0.00 | 0.00 | 0.00 | 0.126984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155489E+10 | 0.00 | 0.00 | 0.00 | 0.185307E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159376E+10 | 0.00 | 0.00 | 0.00 | 0.183126E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151602E+10 | 0.00 | 0.00 | 0.00 | 0.117135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156267E+10 | 0.00 | 0.00 | 0.00 | 2288.62 | 0.00 | 0.626196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185032E+11 | 0.00 | 0.00 | 0.00 | 0.641911E+09 | 0.00 | 0.229349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.141495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159376E+10 | 0.00 | 0.00 | 0.00 | 0.185307E+09 | 0.00 | 0.564700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.106257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.944520E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.870446E+09 | 0.00 | 0.00 | 0.00 | 31030577.46 | 0.00 | 0.326552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.889720E+09 | 0.00 | 0.00 | 0.00 | 13417475.79 | 0.00 | 0.239353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.831076E+09 | 0.00 | 0.00 | 0.00 | 0.211592E+09 | 0.00 | 0.124180E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.836522E+09 | 0.00 | 0.00 | 0.00 | 0.374508E+09 | 0.00 | 3179272.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.858427E+09 | 0.00 | 0.00 | 0.00 | 0.437408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.815440E+09 | 0.00 | 0.00 | 0.00 | 0.228852E+09 | 0.00 | 2804964.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.901513E+09 | 0.00 | 0.00 | 0.00 | 458.35 | 0.00 | 0.363045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.971260E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.924540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110869E+11 | 0.00 | 0.00 | 0.00 | 0.129681E+10 | 0.00 | 0.671254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.815440E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.107152E+10 | 0.00 | 0.00 | 0.00 | 0.437408E+09 | 0.00 | 0.139831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.114759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.616298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111357E+10 | 0.00 | 0.00 | 0.00 | 27857215.37 | 0.00 | 0.122445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115997E+10 | 0.00 | 0.00 | 0.00 | 20831624.14 | 0.00 | 0.835334E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113213E+10 | 0.00 | 0.00 | 0.00 | 0.154861E+09 | 0.00 | 32252350.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.114141E+10 | 0.00 | 0.00 | 0.00 | 0.359895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117234E+10 | 0.00 | 0.00 | 0.00 | 0.484099E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111357E+10 | 0.00 | 0.00 | 0.00 | 0.222415E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114759E+10 | 0.00 | 0.00 | 0.00 | 1351745.65 | 0.00 | 0.137763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.660115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135948E+11 | 0.00 | 0.00 | 0.00 | 0.127131E+10 | 0.00 | 0.300268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.103933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.117234E+10 | 0.00 | 0.00 | 0.00 | 0.484099E+09 | 0.00 | 0.660115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.113357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109996E+10 | 0.00 | 0.00 | 0.00 | 26018236.23 | 0.00 | 0.131604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114580E+10 | 0.00 | 0.00 | 0.00 | 18889181.70 | 0.00 | 0.922004E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.111830E+10 | 0.00 | 0.00 | 0.00 | 0.145462E+09 | 0.00 | 41211608.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.112746E+10 | 0.00 | 0.00 | 0.00 | 0.342198E+09 | 0.00 | 30290.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.115802E+10 | 0.00 | 0.00 | 0.00 | 0.461956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.109996E+10 | 0.00 | 0.00 | 0.00 | 0.210210E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113357E+10 | 0.00 | 0.00 | 0.00 | 1090407.49 | 0.00 | 0.146741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134287E+11 | 0.00 | 0.00 | 0.00 | 0.120582E+10 | 0.00 | 0.309269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.102663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115802E+10 | 0.00 | 0.00 | 0.00 | 0.461956E+09 | 0.00 | 0.672110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.111011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107720E+10 | 0.00 | 0.00 | 0.00 | 21683616.09 | 0.00 | 0.160436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112208E+10 | 0.00 | 0.00 | 0.00 | 14556828.14 | 0.00 | 0.119567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.109515E+10 | 0.00 | 0.00 | 0.00 | 0.123503E+09 | 0.00 | 73632494.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110413E+10 | 0.00 | 0.00 | 0.00 | 0.294787E+09 | 0.00 | 3043315.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.113405E+10 | 0.00 | 0.00 | 0.00 | 0.397561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107720E+10 | 0.00 | 0.00 | 0.00 | 0.177579E+09 | 0.00 | 1224008.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111011E+10 | 0.00 | 0.00 | 0.00 | 528092.26 | 0.00 | 0.174162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131508E+11 | 0.00 | 0.00 | 0.00 | 0.103020E+10 | 0.00 | 0.339018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.100539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.113405E+10 | 0.00 | 0.00 | 0.00 | 0.397561E+09 | 0.00 | 0.715139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.109980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.816084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.996047E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106719E+10 | 0.00 | 0.00 | 0.00 | 17648774.33 | 0.00 | 0.234385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111166E+10 | 0.00 | 0.00 | 0.00 | 9976842.32 | 0.00 | 0.194737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108498E+10 | 0.00 | 0.00 | 0.00 | 0.102134E+09 | 0.00 | 0.215236E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109387E+10 | 0.00 | 0.00 | 0.00 | 0.228746E+09 | 0.00 | 28731538.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.112352E+10 | 0.00 | 0.00 | 0.00 | 0.301431E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.106719E+10 | 0.00 | 0.00 | 0.00 | 0.138919E+09 | 0.00 | 25436194.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109980E+10 | 0.00 | 0.00 | 0.00 | 36076.93 | 0.00 | 0.250071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130287E+11 | 0.00 | 0.00 | 0.00 | 0.798891E+09 | 0.00 | 0.430127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.996047E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.112352E+10 | 0.00 | 0.00 | 0.00 | 0.301431E+09 | 0.00 | 0.862283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.936565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488201E+10 | 0.00 | 0.00 | 0.52 |
February | 0.864788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396913E+10 | 0.00 | 0.00 | 0.53 |
March | 0.890457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356284E+10 | 0.00 | 0.00 | 0.53 |
April | 0.865568E+10 | 0.00 | 0.00 | 1299642.05 | 1734306.60 | 0.264516E+09 | 0.664242E+09 | 0.00 | 0.55 |
May | 0.863909E+10 | 374117.90 | 0.00 | 1163885.11 | 0.00 | 37563223.56 | 0.881108E+09 | 0.00 | 0.55 |
June | 0.511032E+10 | 74217535.69 | 0.00 | 4317692.34 | 0.00 | 0.00 | 0.287432E+10 | 0.00 | 0.60 |
July | 0.199532E+10 | 0.113115E+09 | 0.00 | 10335373.07 | 0.00 | 0.00 | 0.594233E+10 | 0.00 | 0.70 |
August | 0.537228E+09 | 2898708.60 | 0.00 | 13905179.36 | 0.00 | 0.00 | 0.736928E+10 | 0.00 | 0.77 |
September | 0.300680E+10 | 390477.68 | 0.00 | 8150650.38 | 0.00 | 0.00 | 0.525458E+10 | 0.00 | 0.65 |
October | 0.965955E+10 | 0.00 | 0.00 | 90251.22 | 0.00 | 91242581.46 | 0.117074E+09 | 0.00 | 0.53 |
November | 0.913156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255723E+10 | 0.00 | 0.00 | 0.52 |
December | 0.818505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.618990E+10 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.818387E+11 | 0.190996E+09 | 0.00 | 39262673.53 | 1734306.60 | 0.215544E+11 | 0.231029E+11 | 0.00 | 0.58 |
Minimum of Months | 0.537228E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.965955E+10 | 0.113115E+09 | 0.00 | 13905179.36 | 1734306.60 | 0.618990E+10 | 0.736928E+10 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.374896E+10 | 0.00 | 0.00 | 22.79 | 0.00 | 0.139677E+10 | 8505.01 | 0.00 | 0.38 |
February | 0.383562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631440E+09 | 0.00 | 0.00 | 0.39 |
March | 0.408358E+10 | 0.00 | 0.00 | 13413.81 | 0.00 | 0.459577E+09 | 4825850.45 | 0.00 | 0.39 |
April | 0.298074E+10 | 0.00 | 0.00 | 1760442.32 | 190527.08 | 4781669.56 | 0.658834E+09 | 0.00 | 0.40 |
May | 0.286322E+10 | 139964.21 | 0.00 | 2096798.76 | 0.00 | 0.00 | 0.886109E+09 | 0.00 | 0.41 |
June | 0.641161E+09 | 28634708.19 | 0.00 | 5523008.05 | 0.00 | 0.00 | 0.239124E+10 | 0.00 | 0.44 |
July | 0.149797E+09 | 50446435.80 | 0.00 | 7745099.11 | 0.00 | 0.00 | 0.227508E+10 | 0.00 | 0.44 |
August | 15230939.56 | 1227827.42 | 0.00 | 9134952.29 | 0.00 | 0.00 | 0.208325E+10 | 0.00 | 0.45 |
September | 0.233621E+09 | 0.00 | 0.00 | 7581808.48 | 0.00 | 0.00 | 0.255503E+10 | 0.00 | 0.44 |
October | 0.278845E+10 | 0.00 | 0.00 | 1650729.84 | 0.00 | 0.00 | 0.105889E+10 | 0.00 | 0.40 |
November | 0.392872E+10 | 0.00 | 0.00 | 16813.50 | 0.00 | 0.324142E+09 | 5418211.84 | 0.00 | 0.39 |
December | 0.317507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191462E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.284442E+11 | 80448935.61 | 0.00 | 35523088.97 | 190527.08 | 0.473133E+10 | 0.119187E+11 | 0.00 | 0.41 |
Minimum of Months | 15230939.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.408358E+10 | 50446435.80 | 0.00 | 9134952.29 | 190527.08 | 0.191462E+10 | 0.255503E+10 | 0.00 | 0.45 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.325914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215422E+10 | 0.00 | 0.00 | 0.41 |
February | 0.320900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150479E+10 | 0.00 | 0.00 | 0.41 |
March | 0.356982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123063E+10 | 0.00 | 0.00 | 0.42 |
April | 0.318652E+10 | 0.00 | 0.00 | 796759.21 | 550675.12 | 70687183.06 | 0.658783E+09 | 0.00 | 0.49 |
May | 0.314521E+10 | 61803.31 | 0.00 | 954853.65 | 0.00 | 1513666.05 | 0.905188E+09 | 0.00 | 0.50 |
June | 0.109042E+10 | 19584425.24 | 0.00 | 3319072.06 | 9969.53 | 0.00 | 0.283214E+10 | 0.00 | 0.67 |
July | 0.542361E+09 | 38585637.17 | 0.00 | 4952207.33 | 2083445.29 | 0.00 | 0.377627E+10 | 0.00 | 0.86 |
August | 0.349769E+09 | 495551.94 | 0.00 | 6311707.74 | 0.00 | 0.00 | 0.435478E+10 | 0.00 | 1.06 |
September | 0.730432E+09 | 0.00 | 0.00 | 4745319.21 | 0.00 | 0.00 | 0.354001E+10 | 0.00 | 0.81 |
October | 0.311841E+10 | 0.00 | 0.00 | 784370.31 | 0.00 | 13031850.04 | 0.865843E+09 | 0.00 | 0.44 |
November | 0.354506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.907346E+09 | 0.00 | 0.00 | 0.41 |
December | 0.259905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277910E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.283452E+11 | 58727417.67 | 0.00 | 21864289.51 | 2644089.94 | 0.866132E+10 | 0.169330E+11 | 0.00 | 0.58 |
Minimum of Months | 0.349769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.356982E+10 | 38585637.17 | 0.00 | 6311707.74 | 2083445.29 | 0.277910E+10 | 0.435478E+10 | 0.00 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.303766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237402E+10 | 0.00 | 0.00 | 0.41 |
February | 0.293031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178336E+10 | 0.00 | 0.00 | 0.41 |
March | 0.325633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154137E+10 | 0.00 | 0.00 | 0.42 |
April | 0.316929E+10 | 0.00 | 0.00 | 703276.31 | 610861.40 | 0.104556E+09 | 0.574782E+09 | 0.00 | 0.48 |
May | 0.314639E+10 | 50806.30 | 0.00 | 857269.00 | 0.00 | 4715351.02 | 0.819118E+09 | 0.00 | 0.49 |
June | 0.117141E+10 | 19269188.14 | 0.00 | 3027301.20 | 8399.46 | 0.00 | 0.264821E+10 | 0.00 | 0.66 |
July | 0.599400E+09 | 38506088.51 | 0.00 | 4744472.26 | 2091960.27 | 0.00 | 0.364143E+10 | 0.00 | 0.85 |
August | 0.358467E+09 | 475761.02 | 0.00 | 6148216.22 | 0.00 | 0.00 | 0.429234E+10 | 0.00 | 1.05 |
September | 0.788448E+09 | 0.00 | 0.00 | 4534840.75 | 0.00 | 0.00 | 0.339416E+10 | 0.00 | 0.79 |
October | 0.311140E+10 | 0.00 | 0.00 | 666989.02 | 0.00 | 36426688.81 | 0.774093E+09 | 0.00 | 0.44 |
November | 0.330224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114402E+10 | 0.00 | 0.00 | 0.41 |
December | 0.236151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301663E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.272329E+11 | 58301843.96 | 0.00 | 20682364.75 | 2711221.12 | 0.100051E+11 | 0.161441E+11 | 0.00 | 0.57 |
Minimum of Months | 0.358467E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.330224E+10 | 38506088.51 | 0.00 | 6148216.22 | 2091960.27 | 0.301663E+10 | 0.429234E+10 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.269095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272007E+10 | 0.00 | 0.00 | 0.41 |
February | 0.252514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218832E+10 | 0.00 | 0.00 | 0.41 |
March | 0.285818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193697E+10 | 0.00 | 0.00 | 0.42 |
April | 0.311089E+10 | 0.00 | 0.00 | 530753.36 | 784381.49 | 0.169877E+09 | 0.446845E+09 | 0.00 | 0.47 |
May | 0.314706E+10 | 33940.69 | 0.00 | 642008.11 | 0.00 | 18329067.96 | 0.645338E+09 | 0.00 | 0.47 |
June | 0.154042E+10 | 18411414.15 | 0.00 | 2239828.97 | 4384.39 | 0.00 | 0.199048E+10 | 0.00 | 0.62 |
July | 0.718189E+09 | 38195202.15 | 0.00 | 4097981.69 | 2135596.67 | 0.00 | 0.328309E+10 | 0.00 | 0.81 |
August | 0.396697E+09 | 416616.12 | 0.00 | 5595558.73 | 0.00 | 0.00 | 0.407078E+10 | 0.00 | 1.01 |
September | 0.878879E+09 | 0.00 | 0.00 | 3879040.90 | 0.00 | 0.00 | 0.303956E+10 | 0.00 | 0.75 |
October | 0.320046E+10 | 0.00 | 0.00 | 311875.70 | 0.00 | 96795401.60 | 0.487482E+09 | 0.00 | 0.42 |
November | 0.291187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152903E+10 | 0.00 | 0.00 | 0.41 |
December | 0.208474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329345E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.260635E+11 | 57057173.12 | 0.00 | 17297047.46 | 2924362.55 | 0.119528E+11 | 0.139636E+11 | 0.00 | 0.55 |
Minimum of Months | 0.396697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.320046E+10 | 38195202.15 | 0.00 | 5595558.73 | 2135596.67 | 0.329345E+10 | 0.407078E+10 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.301758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697254E+10 | 0.00 | 0.00 | 0.38 |
February | 0.322601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547705E+10 | 0.00 | 0.00 | 0.38 |
March | 0.384640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502206E+10 | 0.00 | 0.00 | 0.39 |
April | 0.550316E+10 | 0.00 | 0.00 | 426910.57 | 1651378.18 | 0.530035E+09 | 0.250927E+09 | 0.00 | 0.39 |
May | 0.598772E+10 | 0.00 | 0.00 | 314973.83 | 0.00 | 0.119409E+09 | 0.268469E+09 | 0.00 | 0.39 |
June | 0.407754E+10 | 29587185.41 | 0.00 | 1664174.12 | 0.00 | 1366832.92 | 0.914031E+09 | 0.00 | 0.43 |
July | 0.179302E+10 | 65801516.17 | 0.00 | 4701769.14 | 4210444.54 | 0.00 | 0.302611E+10 | 0.00 | 0.47 |
August | 0.637089E+09 | 433887.97 | 0.00 | 7609508.04 | 0.00 | 0.00 | 0.433082E+10 | 0.00 | 0.54 |
September | 0.292160E+10 | 0.00 | 0.00 | 3496927.08 | 0.00 | 0.00 | 0.209205E+10 | 0.00 | 0.46 |
October | 0.539949E+10 | 0.00 | 0.00 | 31103.51 | 0.00 | 0.109463E+10 | 42816669.95 | 0.00 | 0.38 |
November | 0.402272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417578E+10 | 0.00 | 0.00 | 0.38 |
December | 0.233401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759571E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.427663E+11 | 95822589.55 | 0.00 | 18245366.29 | 5861822.72 | 0.309886E+11 | 0.109252E+11 | 0.00 | 0.41 |
Minimum of Months | 0.637089E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.598772E+10 | 65801516.17 | 0.00 | 7609508.04 | 4210444.54 | 0.759571E+10 | 0.433082E+10 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370593E+10 | 0.00 | 0.00 | 0.38 |
February | 0.148642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285891E+10 | 0.00 | 0.00 | 0.38 |
March | 0.173594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269173E+10 | 0.00 | 0.00 | 0.39 |
April | 0.262091E+10 | 0.00 | 0.00 | 241003.28 | 710993.27 | 0.376122E+09 | 0.135668E+09 | 0.00 | 0.38 |
May | 0.286729E+10 | 0.00 | 0.00 | 195345.50 | 0.00 | 0.156173E+09 | 0.168723E+09 | 0.00 | 0.38 |
June | 0.201255E+10 | 13103672.14 | 0.00 | 919721.09 | 0.00 | 689735.95 | 0.450130E+09 | 0.00 | 0.39 |
July | 0.764916E+09 | 30318552.33 | 0.00 | 2543551.86 | 1960471.96 | 0.00 | 0.124977E+10 | 0.00 | 0.38 |
August | 0.203152E+09 | 163981.95 | 0.00 | 3987338.11 | 0.00 | 0.00 | 0.161467E+10 | 0.00 | 0.39 |
September | 0.119460E+10 | 0.00 | 0.00 | 2056132.62 | 0.00 | 0.00 | 0.111373E+10 | 0.00 | 0.38 |
October | 0.262427E+10 | 0.00 | 0.00 | 21670.88 | 0.00 | 0.644055E+09 | 25437723.39 | 0.00 | 0.38 |
November | 0.181620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227564E+10 | 0.00 | 0.00 | 0.38 |
December | 0.100564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395159E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.196142E+11 | 43586206.42 | 0.00 | 9964763.33 | 2671465.23 | 0.166608E+11 | 0.475814E+10 | 0.00 | 0.38 |
Minimum of Months | 0.203152E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.286729E+10 | 30318552.33 | 0.00 | 3987338.11 | 1960471.96 | 0.395159E+10 | 0.161467E+10 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381053E+10 | 0.00 | 0.00 | 0.38 |
February | 0.143315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291223E+10 | 0.00 | 0.00 | 0.38 |
March | 0.166490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276268E+10 | 0.00 | 0.00 | 0.39 |
April | 0.258343E+10 | 0.00 | 0.00 | 222376.11 | 742943.18 | 0.417934E+09 | 0.124960E+09 | 0.00 | 0.38 |
May | 0.282291E+10 | 0.00 | 0.00 | 173250.25 | 0.00 | 0.208558E+09 | 0.151437E+09 | 0.00 | 0.38 |
June | 0.203208E+10 | 12775941.28 | 0.00 | 857663.46 | 0.00 | 2424065.76 | 0.412782E+09 | 0.00 | 0.39 |
July | 0.785841E+09 | 30196184.58 | 0.00 | 2421084.36 | 1977294.24 | 0.00 | 0.122567E+10 | 0.00 | 0.38 |
August | 0.226480E+09 | 148898.04 | 0.00 | 3846427.11 | 0.00 | 0.00 | 0.159670E+10 | 0.00 | 0.39 |
September | 0.125499E+10 | 0.00 | 0.00 | 1931995.11 | 0.00 | 0.00 | 0.104667E+10 | 0.00 | 0.38 |
October | 0.258247E+10 | 0.00 | 0.00 | 18198.18 | 0.00 | 0.678156E+09 | 23825454.87 | 0.00 | 0.38 |
November | 0.172778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236407E+10 | 0.00 | 0.00 | 0.38 |
December | 0.899836E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405739E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.191914E+11 | 43121023.90 | 0.00 | 9470994.57 | 2720237.42 | 0.172140E+11 | 0.458205E+10 | 0.00 | 0.38 |
Minimum of Months | 0.226480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.282291E+10 | 30196184.58 | 0.00 | 3846427.11 | 1977294.24 | 0.405739E+10 | 0.159670E+10 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.843645E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414455E+10 | 0.00 | 0.00 | 0.38 |
February | 0.111691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322845E+10 | 0.00 | 0.00 | 0.38 |
March | 0.132497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310265E+10 | 0.00 | 0.00 | 0.39 |
April | 0.241708E+10 | 0.00 | 0.00 | 178055.63 | 846437.72 | 0.596090E+09 | 97244641.31 | 0.00 | 0.38 |
May | 0.260872E+10 | 0.00 | 0.00 | 119295.07 | 0.00 | 0.437908E+09 | 0.108367E+09 | 0.00 | 0.38 |
June | 0.205634E+10 | 12039025.96 | 0.00 | 670204.68 | 0.00 | 8043314.60 | 0.328671E+09 | 0.00 | 0.39 |
July | 0.903282E+09 | 29906155.91 | 0.00 | 2042696.53 | 2019711.46 | 0.00 | 0.109433E+10 | 0.00 | 0.38 |
August | 0.298384E+09 | 113798.82 | 0.00 | 3405995.58 | 0.00 | 0.00 | 0.153881E+10 | 0.00 | 0.39 |
September | 0.146053E+10 | 0.00 | 0.00 | 1557531.15 | 0.00 | 0.00 | 0.807478E+09 | 0.00 | 0.38 |
October | 0.239408E+10 | 0.00 | 0.00 | 9669.27 | 0.00 | 0.848190E+09 | 15895259.65 | 0.00 | 0.38 |
November | 0.142486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266701E+10 | 0.00 | 0.00 | 0.38 |
December | 0.567754E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438952E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.174165E+11 | 42058980.70 | 0.00 | 7983447.91 | 2866149.18 | 0.194224E+11 | 0.399080E+10 | 0.00 | 0.38 |
Minimum of Months | 0.298384E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.260872E+10 | 29906155.91 | 0.00 | 3405995.58 | 2019711.46 | 0.438952E+10 | 0.153881E+10 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.197239E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478725E+10 | 0.00 | 0.00 | 0.38 |
February | 0.102546E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423412E+10 | 0.00 | 0.00 | 0.38 |
March | 0.338396E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408103E+10 | 0.00 | 0.00 | 0.39 |
April | 0.185181E+10 | 0.00 | 0.00 | 132870.40 | 1053962.35 | 0.115544E+10 | 72863139.53 | 0.00 | 0.38 |
May | 0.208920E+10 | 0.00 | 0.00 | 82359.36 | 0.00 | 0.935264E+09 | 74764819.23 | 0.00 | 0.38 |
June | 0.201742E+10 | 11443527.68 | 0.00 | 507140.53 | 247930.40 | 52586216.28 | 0.204308E+09 | 0.00 | 0.39 |
July | 0.108198E+10 | 30190782.72 | 0.00 | 1482749.73 | 2059318.65 | 1960662.56 | 0.864465E+09 | 0.00 | 0.38 |
August | 0.488693E+09 | 43130.20 | 0.00 | 2627995.72 | 9967.95 | 0.00 | 0.133680E+10 | 0.00 | 0.39 |
September | 0.161417E+10 | 0.00 | 0.00 | 1149372.58 | 0.00 | 1511965.42 | 0.554122E+09 | 0.00 | 0.38 |
October | 0.178461E+10 | 0.00 | 0.00 | 2784.38 | 0.00 | 0.141146E+10 | 8827716.09 | 0.00 | 0.38 |
November | 0.610403E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346584E+10 | 0.00 | 0.00 | 0.38 |
December | 24814340.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491711E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.122013E+11 | 41677440.60 | 0.00 | 5985272.70 | 3371179.36 | 0.250436E+11 | 0.311615E+10 | 0.00 | 0.38 |
Minimum of Months | 24814340.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.208920E+10 | 30190782.72 | 0.00 | 2627995.72 | 2059318.65 | 0.491711E+10 | 0.133680E+10 | 0.00 | 0.39 |