Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:19
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Honolulu Intl Arpt HI USA TMY3 WMO#=911820
Simulation Timestamp: 2020-06-03 19:19:10
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:10
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1236.71 | 591.64 | 591.64 |
Net Site Energy | 1236.71 | 591.64 | 591.64 |
Total Source Energy | 3916.66 | 1873.71 | 1873.71 |
Net Source Energy | 3916.66 | 1873.71 | 1873.71 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 446.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 450.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 59.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 92.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 58.57 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1236.71 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 446.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 450.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 59.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 92.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 58.57 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 244.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 286.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 591.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 244.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 286.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 591.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1236.710 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1236.710 | 100.00 |
Total On-Site and Utility Electric Sources | 1236.710 | 100.00 |
Total Electricity End Uses | 1236.710 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 334.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_HI_HONOLULU
| Meter |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:10
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | Honolulu Intl Arpt HI USA TMY3 WMO#=911820 |
Latitude [deg] | 21.32 |
Longitude [deg] | -157.9 |
Elevation [m] | 2.00 |
Time Zone | -10.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.75 | 20.75 | 16.9114 | 11.61 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.37 | 10.37 | 19.7854 | 11.61 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 18.1708 | 11.61 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 18.1708 | 11.61 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 18.1708 | 11.61 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.70 | 20.70 | 11.2173 | 11.61 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 11.2173 | 11.61 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 11.2173 | 11.61 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 11.2173 | 11.61 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.35 | 10.35 | 11.2173 | 11.61 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 14.6187 | 11.61 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 14.6187 | 11.61 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:10
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 03-SEP-14:30 | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 52287.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 29013.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8790.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 6917.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 105068.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 52287.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 29013.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 8790.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 6917.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:10
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1414.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1427.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 188.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 294.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 185.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3916.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 676.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 683.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 90.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 140.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 88.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1873.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 676.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 683.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 90.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 140.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 88.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1873.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:10
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.89 |
SMSTORE1 DIRECT AIR | 1.00 |
SMSTORE2 DIRECT AIR | 1.04 |
SMSTORE3 DIRECT AIR | 1.03 |
SMSTORE4 DIRECT AIR | 1.03 |
LGSTORE2 DIRECT AIR | 1.73 |
SMSTORE5 DIRECT AIR | 0.902030 |
SMSTORE6 DIRECT AIR | 0.896333 |
SMSTORE7 DIRECT AIR | 0.897077 |
SMSTORE8 DIRECT AIR | 1.03 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.89 | 1.89 | 1.89 | 1.89 | 1.89 | 1.89 | 1.00 | 1.00 | 1.89 |
PSZ-AC_2:2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PSZ-AC_3:3 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.00 | 1.000000 | 1.04 |
PSZ-AC_4:4 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.00 | 1.00 | 1.03 |
PSZ-AC_5:5 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.00 | 1.00 | 1.03 |
PSZ-AC_6:6 | 1.73 | 1.73 | 1.73 | 1.73 | 1.73 | 1.73 | 1.00 | 1.00 | 1.73 |
PSZ-AC_7:7 | 0.902030 | 0.902030 | 0.902030 | 0.902030 | 0.902030 | 0.902030 | 1.00 | 1.00 | 0.902030 |
PSZ-AC_8:8 | 0.896333 | 0.896333 | 0.896333 | 0.896333 | 0.896333 | 0.896333 | 1.00 | 1.000000 | 0.896333 |
PSZ-AC_9:9 | 0.897077 | 0.897077 | 0.897077 | 0.897077 | 0.897077 | 0.897077 | 1.00 | 1.00 | 0.897077 |
PSZ-AC_10:10 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.00 | 1.00 | 1.03 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.89 | 0.411453 |
PSZ-AC_2:2_OA_CONTROLLER | 1.00 | 0.205727 |
PSZ-AC_3:3_OA_CONTROLLER | 1.04 | 0.205727 |
PSZ-AC_4:4_OA_CONTROLLER | 1.03 | 0.205727 |
PSZ-AC_5:5_OA_CONTROLLER | 1.03 | 0.205727 |
PSZ-AC_6:6_OA_CONTROLLER | 1.73 | 0.411453 |
PSZ-AC_7:7_OA_CONTROLLER | 0.902030 | 0.205727 |
PSZ-AC_8:8_OA_CONTROLLER | 0.896333 | 0.205727 |
PSZ-AC_9:9_OA_CONTROLLER | 0.897077 | 0.205727 |
PSZ-AC_10:10_OA_CONTROLLER | 1.03 | 0.205727 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.89 | 1.89 | 1.89 | 1.25 | 44096.68 | 45618.71 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.00 | 1.00 | 1.00 | 0.660798 | 23198.11 | 24103.83 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 0.686757 | 24092.37 | 25002.37 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.03 | 1.03 | 1.03 | 0.682759 | 23932.53 | 24863.96 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.03 | 1.03 | 1.03 | 0.680811 | 23928.07 | 25110.56 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.73 | 1.73 | 1.73 | 1.14 | 41256.64 | 41948.12 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.902030 | 0.902030 | 0.902030 | 0.595340 | 21485.38 | 21836.15 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.896333 | 0.896333 | 0.896333 | 0.591580 | 21385.97 | 21944.33 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.897077 | 0.897077 | 0.897077 | 0.592071 | 21399.55 | 21723.68 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.03 | 1.03 | 1.03 | 0.680472 | 23616.56 | 25140.34 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 1.89 | 0.944565 | 1.26 | 41804.11 | 44096.68 | 22048.34 | 22048.34 | 0.691728 | 0.691730 | 0.691730 | 0.691730 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 1.00 | 0.500605 | 0.667473 | 21980.43 | 23198.11 | 11599.06 | 11599.06 | 0.693666 | 0.693670 | 0.693670 | 0.693670 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 1.04 | 0.520270 | 0.693693 | 22826.56 | 24092.37 | 12046.18 | 12046.18 | 0.693852 | 0.693850 | 0.693850 | 0.693850 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 1.03 | 0.517240 | 0.689653 | 22673.70 | 23932.53 | 11966.26 | 11966.26 | 0.694066 | 0.694070 | 0.694070 | 0.694070 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 1.03 | 0.515765 | 0.687687 | 22673.86 | 23928.07 | 11964.03 | 11964.03 | 0.693365 | 0.693370 | 0.693370 | 0.693370 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 1.73 | 0.864275 | 1.15 | 39172.87 | 41256.64 | 20628.32 | 20628.32 | 0.685988 | 0.685990 | 0.685990 | 0.685990 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 0.902030 | 0.451015 | 0.601353 | 20397.28 | 21485.38 | 10742.69 | 10742.69 | 0.686511 | 0.686510 | 0.686510 | 0.686510 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 0.896330 | 0.448165 | 0.597553 | 20305.22 | 21385.97 | 10692.99 | 10692.99 | 0.686077 | 0.686080 | 0.686080 | 0.686080 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 0.897080 | 0.448540 | 0.598053 | 20317.98 | 21399.55 | 10699.77 | 10699.77 | 0.686128 | 0.686130 | 0.686130 | 0.686130 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 1.03 | 0.515510 | 0.687347 | 22360.35 | 23616.56 | 11808.28 | 11808.28 | 0.696694 | 0.696690 | 0.696690 | 0.696690 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.89 | 2021.46 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.00 | 1108.50 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1152.04 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.03 | 1145.34 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.03 | 1142.07 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.73 | 1849.63 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.902030 | 998.69 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.896333 | 992.38 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.897077 | 993.21 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.03 | 1141.50 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | 45618.71 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | 24103.83 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | 25002.37 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | 24863.96 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | 25110.56 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | 41948.12 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | 21836.15 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | 21944.33 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | 21723.68 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | 25140.34 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:10
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:10
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:10
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.20 | 24.80 | 23.70 | 22.50 | 22.80 | 23.20 | 23.80 | 25.20 | 25.90 | 26.90 | 27.10 | 26.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Honolulu Intl Arpt HI USA TMY3 WMO#=911820 | 21.32 | -157.93 | -10.00 | 2.00 | 101301 | 1.2040 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.92 | 4.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.76 | 20.75 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.67 | 10.37 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.43 | 20.70 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.13 | 10.35 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 16.911 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.211 | No |
2 | SMSTORE1 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 19.785 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.085 | No |
3 | SMSTORE2 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.171 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.471 | No |
4 | SMSTORE3 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.171 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.471 | No |
5 | SMSTORE4 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.171 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.471 | No |
6 | LGSTORE2 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 11.217 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.517 | No |
7 | SMSTORE5 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 11.217 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.517 | No |
8 | SMSTORE6 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 11.217 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.517 | No |
9 | SMSTORE7 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 11.217 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.517 | No |
10 | SMSTORE8 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 11.217 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.517 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 3907.969 | 11.217 | 130.283 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3907.969 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 1983.747 | 5.694 | 66.133 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1983.747 |
3 | SMSTORE1_LIGHTS | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1953.984 | 11.217 | 130.283 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1953.984 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1492.505 | 8.568 | 99.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.505 |
5 | SMSTORE2_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 1953.984 | 11.217 | 130.283 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1953.984 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 1211.252 | 6.954 | 80.761 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.252 |
7 | SMSTORE3_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 1953.984 | 11.217 | 130.283 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1953.984 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 1211.252 | 6.954 | 80.761 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.252 |
9 | SMSTORE4_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 1953.984 | 11.217 | 130.283 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1953.984 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 1211.252 | 6.954 | 80.761 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.252 |
11 | LGSTORE2_LIGHTS | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 3907.969 | 11.217 | 130.283 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3907.969 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 1953.984 | 11.217 | 130.283 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1953.984 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 1953.984 | 11.217 | 130.283 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1953.984 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 1953.984 | 11.217 | 130.283 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1953.984 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 1953.984 | 11.217 | 130.283 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1953.984 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL | 20 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 30 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 31 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1010000 | 2.1010000 | 2.1010000 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
19 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
20 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
21 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
22 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
23 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
24 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
25 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
26 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
27 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
28 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
29 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 29 | 1 | VerySmooth | 3.241 | 0.252 | 0.162 | 0.276 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 30.0 | 0.159 | 4.569E-004 | 2.517E-004 | 0.317 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 15.0 | 4.561E-002 | 2.619E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 30.0 | 9.122E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 15.0 | 0.113 | 6.514E-004 | 3.022E-004 | 0.453 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 21444.70323 | 25733.64388 | 1.57428 | 1.88913 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 31.98700 | 1.43490E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
2 | LGSTORE1 | Heating | 6400.06112 | 7680.07334 | 0.26704 | 0.41145 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 16.20000 | 1.15180E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
3 | SMSTORE1 | Cooling | 11365.17449 | 13638.20939 | 0.83434 | 1.00121 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 32.20000 | 1.43490E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
4 | SMSTORE1 | Heating | 2913.33288 | 3495.99945 | 0.12217 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 16.20000 | 1.15180E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
5 | SMSTORE2 | Cooling | 12142.45852 | 14570.95022 | 0.86712 | 1.04054 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 28.29500 | 1.43490E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
6 | SMSTORE2 | Heating | 2741.87926 | 3290.25511 | 0.11823 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 13:00:00 | 16.20000 | 1.15180E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
7 | SMSTORE3 | Cooling | 12073.99074 | 14488.78889 | 0.86207 | 1.03448 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 28.29500 | 1.43490E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
8 | SMSTORE3 | Heating | 2775.11778 | 3330.14133 | 0.11967 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 13:00:00 | 16.20000 | 1.15180E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
9 | SMSTORE4 | Cooling | 12040.03821 | 14448.04586 | 0.85961 | 1.03153 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 28.29500 | 1.43490E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
10 | SMSTORE4 | Heating | 2883.41128 | 3460.09354 | 0.12434 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 13:00:00 | 16.20000 | 1.15180E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
11 | LGSTORE2 | Cooling | 19622.21540 | 23546.65848 | 1.44046 | 1.72855 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 32.14083 | 1.43490E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
12 | LGSTORE2 | Heating | 6664.85858 | 7997.83030 | 0.27746 | 0.41145 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 16.20000 | 1.15180E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
13 | SMSTORE5 | Cooling | 10239.45708 | 12287.34849 | 0.75169 | 0.90203 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 32.14083 | 1.43490E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
14 | SMSTORE5 | Heating | 3449.17851 | 4139.01421 | 0.14418 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 16.20000 | 1.15180E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
15 | SMSTORE6 | Cooling | 10174.78928 | 12209.74714 | 0.74694 | 0.89633 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 32.14083 | 1.43490E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
16 | SMSTORE6 | Heating | 3456.68784 | 4148.02541 | 0.14449 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 16.20000 | 1.15180E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
17 | SMSTORE7 | Cooling | 10183.23345 | 12219.88014 | 0.74756 | 0.89708 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 32.14083 | 1.43490E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
18 | SMSTORE7 | Heating | 3717.39787 | 4460.87744 | 0.15511 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 16.20000 | 1.15180E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
19 | SMSTORE8 | Cooling | 11705.32395 | 14046.38874 | 0.85918 | 1.03102 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 31.84500 | 1.43490E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
20 | SMSTORE8 | Heating | 4390.74043 | 5268.88852 | 0.18267 | 0.21921 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 16.20000 | 1.15180E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 29443.29 | 1.88913 | 1.88913 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 11847.79 | 0.41145 | 0.41145 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:50:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 15497.02 | 1.00121 | 1.00121 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 5923.90 | 0.20573 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:20:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 15533.72 | 1.04054 | 1.04054 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 5923.90 | 0.20573 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 15576.22 | 1.03448 | 1.03448 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 5923.90 | 0.20573 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 15438.38 | 1.03153 | 1.03153 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 5923.90 | 0.20573 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 08:10:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 27320.18 | 1.72855 | 1.72855 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 11847.79 | 0.41145 | 0.41145 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 14165.54 | 0.90203 | 0.90203 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 5923.90 | 0.20573 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 18:50:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 14089.28 | 0.89633 | 0.89633 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 5923.90 | 0.20573 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:20:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 14097.99 | 0.89708 | 0.89708 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 5923.90 | 0.20573 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 15810.10 | 1.03102 | 1.03102 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 6237.73 | 0.21921 | 0.21921 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.88913 |
2 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.00121 |
3 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.04054 |
4 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.03448 |
5 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.03153 |
6 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.72855 |
7 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.90203 |
8 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.89633 |
9 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.89708 |
10 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.03102 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.88913 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.88913 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.88913 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.88913 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.88913 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.88913 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.00121 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.00121 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.00121 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.00121 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.00121 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.00121 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.04054 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.04054 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.04054 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.04054 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04054 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04054 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.03448 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.03448 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.03448 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.03448 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.03448 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.03448 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.03153 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.03153 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.03153 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.03153 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.03153 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.03153 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.72855 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.72855 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.72855 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.72855 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.72855 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.72855 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.90203 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.90203 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.90203 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.90203 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.90203 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.90203 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.89633 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.89633 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.89633 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.89633 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.89633 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.89633 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.89708 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.89708 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.89708 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.89708 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.89708 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.89708 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.03102 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.03102 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.03102 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.03102 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.03102 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.03102 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.88913 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.00121 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.04054 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.03448 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.03153 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.72855 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.90203 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.89633 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.89708 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.03102 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.88913 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.88913 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.88913 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.88913 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.24683 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.88913 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.94457 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.25942 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 41804.10885 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 44096.68000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 22048.34000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 22048.34000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69173 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69173 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69173 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69173 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 44096.68000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 45618.70893 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
122 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.88913 |
123 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2021.46016 |
124 | Coil:Heating:Fuel | PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 45618.70893 |
125 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.00121 |
126 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.00121 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.00121 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.00121 |
130 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.66080 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.00121 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50061 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66747 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21980.42948 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 23198.11000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11599.05500 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 11599.05500 |
138 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69367 |
139 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69367 |
140 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69367 |
141 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69367 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23198.11000 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24103.82787 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
146 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.00121 |
147 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1108.49719 |
148 | Coil:Heating:Fuel | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 24103.82787 |
149 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04054 |
150 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
151 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04054 |
152 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04054 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04054 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68676 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04054 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52027 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69369 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22826.55567 |
159 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 24092.37000 |
160 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12046.18500 |
161 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 12046.18500 |
162 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69385 |
163 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69385 |
164 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69385 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69385 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24092.37000 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25002.37138 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
170 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04054 |
171 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1152.04334 |
172 | Coil:Heating:Fuel | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 25002.37138 |
173 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.03448 |
174 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.03448 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.03448 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.03448 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68276 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.03448 |
180 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51724 |
181 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.68965 |
182 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22673.70428 |
183 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 23932.53000 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11966.26500 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 11966.26500 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69407 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69407 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69407 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69407 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23932.53000 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24863.95709 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
194 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.03448 |
195 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1145.33797 |
196 | Coil:Heating:Fuel | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 24863.95709 |
197 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.03153 |
198 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.03153 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.03153 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.03153 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68081 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.03153 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51577 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.68769 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22673.85733 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 23928.07000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11964.03500 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 11964.03500 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69337 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69337 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69337 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69337 |
214 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23928.07000 |
215 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25110.55899 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
218 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.03153 |
219 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1142.07022 |
220 | Coil:Heating:Fuel | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 25110.55899 |
221 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.72855 |
222 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.72855 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.72855 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.72855 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.14084 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.72855 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.86428 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.15237 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 39172.87290 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 41256.64000 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 20628.32000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 20628.32000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68599 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68599 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68599 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68599 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 41256.64000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 41948.12499 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
241 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
242 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.72855 |
243 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1849.63035 |
244 | Coil:Heating:Fuel | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 41948.12499 |
245 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.90203 |
246 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.90203 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.90203 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.90203 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.59534 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.90203 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.45102 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.60135 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 20397.27601 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 21485.38000 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10742.69000 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 10742.69000 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68651 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68651 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68651 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68651 |
262 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21485.38000 |
263 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 21836.14735 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
266 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.90203 |
267 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 998.69047 |
268 | Coil:Heating:Fuel | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 21836.14735 |
269 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.89633 |
270 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
271 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.89633 |
272 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.89633 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.89633 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.59158 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.89633 |
276 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.44817 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.59755 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 20305.21877 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 21385.97000 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10692.98500 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 10692.98500 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68608 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68608 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68608 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68608 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21385.97000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 21944.32810 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.89633 |
291 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 992.38284 |
292 | Coil:Heating:Fuel | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 21944.32810 |
293 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.89708 |
294 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.89708 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.89708 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.89708 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.59207 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.89708 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.44854 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.59805 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 20317.98423 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 21399.55000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10699.77500 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 10699.77500 |
306 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68613 |
307 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68613 |
308 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68613 |
309 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68613 |
310 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21399.55000 |
311 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 21723.67574 |
312 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
313 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
314 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.89708 |
315 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 993.20615 |
316 | Coil:Heating:Fuel | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 21723.67574 |
317 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.03102 |
318 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
319 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.03102 |
320 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.03102 |
321 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.03102 |
322 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68047 |
323 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.03102 |
324 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51551 |
325 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.68735 |
326 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22360.34875 |
327 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 23616.56000 |
328 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11808.28000 |
329 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 11808.28000 |
330 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69669 |
331 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69669 |
332 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69669 |
333 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69669 |
334 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23616.56000 |
335 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25140.33841 |
336 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
337 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
338 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.03102 |
339 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1141.50002 |
340 | Coil:Heating:Fuel | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 25140.33841 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 42608.1 | 11.66 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 22409.3 | 34.30 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 23272.6 | 44.84 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 23117.5 | 56.96 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 23115.3 | 68.81 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 39894.0 | 51.15 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 20774.3 | 111.56 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 20679.4 | 123.97 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 20692.4 | 135.77 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 22804.4 | 134.21 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 58.20 | 78.94 | 58.20 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.10 | 39.47 | 29.10 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 58.24 | 78.94 | 58.24 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 7 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 2.5626391567E-002 | 0.1107943357 | Pass | Pass | 7.2636167838E-002 | 0.5362678848 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 2.6258360291E-002 | 0.1282248869 | Pass | Pass | 9.2621494806E-002 | 0.8089801895 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 3.9587032316E-002 | 0.1649712944 | Pass | Pass | 0.5049442707 | 3.3531635938 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.9703473051E-002 | 0.1660551013 | Pass | Pass | 0.4753661294 | 2.9874693877 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.8674872516E-002 | 0.1591590368 | Pass | Pass | 1.4731305148 | 14.9803304122 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 3.9927140452E-002 | 0.1629885276 | Pass | Pass | 0.4462605401 | 3.7034594785 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 3.8981554120E-002 | 0.1595914797 | Pass | Pass | 0.2223677812 | 1.4396375035 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 3.8748692866E-002 | 0.1575391941 | Pass | Pass | 0.2199960524 | 1.4234054943 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 3.8602024102E-002 | 0.1514151086 | Pass | Pass | 0.1841831267 | 1.2681192573 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 4.5119945925E-002 | 0.1586828841 | Pass | Pass | 0.2326476545 | 1.5295845160 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:10
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 16.20 | 0.00 | 16.20 | Wetbulb [C] | 1.90 | 320.00 |
HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 32.20 | 7.10 | 23.30 | Wetbulb [C] | 6.70 | 60.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:10
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 78.94 | 58.20 | 180.00 | 90.00 | S |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.10 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 78.94 | 58.24 | 180.00 | 90.00 | S |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 3.241 | 0.252 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 3.241 | 0.252 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 3.241 | 0.252 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.241 | 0.252 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.252 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
Total or Average | 124.29 | 3.241 | 0.252 | 0.276 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 124.29 | 3.241 | 0.252 | 0.276 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:10
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:10
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | 11.2173 | 348.39 | 3907.97 | LightsWired | TYPE1_LIGHT_SCH | 98.22 | 168.00 | 96.33 | 0.0000 | Y | 70.67 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | 5.6941 | 348.39 | 1983.75 | LightsWired | TYPE1_LIGHT_SCH | 98.22 | 112.00 | 95.26 | 0.0000 | Y | 35.47 |
SMSTORE1_LIGHTS | SMSTORE1 | 11.2173 | 174.19 | 1953.98 | LightsWired | TYPE1_LIGHT_SCH | 98.22 | 168.00 | 96.33 | 0.0000 | Y | 35.33 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | 8.5681 | 174.19 | 1492.50 | LightsWired | TYPE1_LIGHT_SCH | 98.22 | 112.00 | 95.26 | 0.0000 | Y | 26.69 |
SMSTORE2_LIGHTS | SMSTORE2 | 11.2173 | 174.19 | 1953.98 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 74.85 | 0.0000 | Y | 27.46 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | 6.9535 | 174.19 | 1211.25 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.65 |
SMSTORE3_LIGHTS | SMSTORE3 | 11.2173 | 174.19 | 1953.98 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 74.85 | 0.0000 | Y | 27.46 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | 6.9535 | 174.19 | 1211.25 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.65 |
SMSTORE4_LIGHTS | SMSTORE4 | 11.2173 | 174.19 | 1953.98 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 74.85 | 0.0000 | Y | 27.46 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | 6.9535 | 174.19 | 1211.25 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.65 |
LGSTORE2_LIGHTS | LGSTORE2 | 11.2173 | 348.39 | 3907.97 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 68.34 | 0.0000 | Y | 50.13 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | 0.0000 | 348.39 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | 11.2173 | 174.19 | 1953.98 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 68.34 | 0.0000 | Y | 25.07 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | 11.2173 | 174.19 | 1953.98 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 68.34 | 0.0000 | Y | 25.07 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | 11.2173 | 174.19 | 1953.98 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 68.34 | 0.0000 | Y | 25.07 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | 11.2173 | 174.19 | 1953.98 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 68.34 | 0.0000 | Y | 25.07 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 7.3094 | 4180.64 | 30557.82 | 450.89 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 418.40 | AstronomicalClock | - | 41.86 | 41.86 | 3.29 | |
EXTERIOR_LIGHTS_B | 2520.30 | AstronomicalClock | - | 83.86 | 62.86 | 29.74 | |
EXTERIOR_LIGHTS_C | 2520.30 | AstronomicalClock | - | 83.86 | 55.86 | 26.43 | |
Exterior Lighting Total | 5459.01 | 59.45 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:10
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 44096.68 | 30503.00 | 13593.68 | 0.69 | 3.73 | |||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 23198.11 | 16091.83 | 7106.28 | 0.69 | 3.80 | |||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 24092.37 | 16716.49 | 7375.88 | 0.69 | 3.80 | |||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 23932.53 | 16610.85 | 7321.68 | 0.69 | 3.80 | |||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 23928.07 | 16591.01 | 7337.06 | 0.69 | 3.80 | |||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 41256.64 | 28301.64 | 12955.00 | 0.69 | 3.73 | |||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 21485.38 | 14749.93 | 6735.45 | 0.69 | 3.80 | |||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 21385.97 | 14672.49 | 6713.48 | 0.69 | 3.80 | |||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 21399.55 | 14682.87 | 6716.68 | 0.69 | 3.80 | |||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 23616.56 | 16453.42 | 7163.14 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 42608.1 | 11.66 | ||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 22409.3 | 34.30 | ||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 23272.6 | 44.84 | ||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 23117.5 | 56.96 | ||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 23115.3 | 68.81 | ||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 39894.0 | 51.15 | ||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 20774.3 | 111.56 | ||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 20679.4 | 123.97 | ||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 20692.4 | 135.77 | ||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 22804.4 | 134.21 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 45618.71 | 0.80 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 24103.83 | 0.80 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 25002.37 | 0.80 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 24863.96 | 0.80 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 25110.56 | 0.80 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 41948.12 | 0.80 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 21836.15 | 0.80 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 21944.33 | 0.80 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 21723.68 | 0.80 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 25140.34 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.89 | 2021.46 | 1070.05 | 1.00 | 1.32 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.00 | 1108.50 | 1107.16 | 1.00 | 1.40 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1152.04 | 1107.16 | 1.00 | 1.39 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.03 | 1145.34 | 1107.16 | 1.00 | 1.39 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.03 | 1142.07 | 1107.16 | 1.00 | 1.39 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.73 | 1849.63 | 1070.05 | 1.00 | 1.34 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.90 | 998.69 | 1107.16 | 1.00 | 1.43 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.90 | 992.38 | 1107.16 | 1.00 | 1.43 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.90 | 993.21 | 1107.16 | 1.00 | 1.43 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.03 | 1141.50 | 1107.16 | 1.00 | 1.39 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:10
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 21444.70 | 25733.64 | 73.87 | 1.574 | 1.889 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 23.89 | 23.88 | 0.00989 | 31.99 | 0.01435 | 0.411 | 0.00 |
SMSTORE1 | 11365.17 | 13638.21 | 78.29 | 0.834 | 1.001 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 23.89 | 23.88 | 0.00992 | 32.20 | 0.01435 | 0.206 | 0.00 |
SMSTORE2 | 12142.46 | 14570.95 | 83.65 | 0.867 | 1.041 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00934 | 28.30 | 0.01435 | 0.206 | 0.00 |
SMSTORE3 | 12073.99 | 14488.79 | 83.18 | 0.862 | 1.034 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00933 | 28.30 | 0.01435 | 0.206 | 0.00 |
SMSTORE4 | 12040.04 | 14448.05 | 82.94 | 0.860 | 1.032 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00936 | 28.30 | 0.01435 | 0.206 | 0.00 |
LGSTORE2 | 19622.22 | 23546.66 | 67.59 | 1.440 | 1.729 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00997 | 32.14 | 0.01435 | 0.411 | 0.00 |
SMSTORE5 | 10239.46 | 12287.35 | 70.54 | 0.752 | 0.902 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01004 | 32.14 | 0.01435 | 0.206 | 0.00 |
SMSTORE6 | 10174.79 | 12209.75 | 70.09 | 0.747 | 0.896 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01005 | 32.14 | 0.01435 | 0.206 | 0.00 |
SMSTORE7 | 10183.23 | 12219.88 | 70.15 | 0.748 | 0.897 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01005 | 32.14 | 0.01435 | 0.206 | 0.00 |
SMSTORE8 | 11705.32 | 14046.39 | 80.64 | 0.859 | 1.031 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 23.89 | 23.88 | 0.00991 | 31.85 | 0.01435 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 6400.06 | 7680.07 | 22.04 | 0.267 | 0.411 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 21.11 | 21.11 | 0.00919 | 16.20 | 0.01152 | 0.411 | 0.00 |
SMSTORE1 | 2913.33 | 3496.00 | 20.07 | 0.122 | 0.206 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 21.11 | 21.11 | 0.00913 | 16.20 | 0.01152 | 0.206 | 0.00 |
SMSTORE2 | 2741.88 | 3290.26 | 18.89 | 0.118 | 0.206 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 13:00:00 | 21.11 | 21.11 | 0.00992 | 16.20 | 0.01152 | 0.206 | 0.00 |
SMSTORE3 | 2775.12 | 3330.14 | 19.12 | 0.120 | 0.206 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 13:00:00 | 21.11 | 21.11 | 0.00991 | 16.20 | 0.01152 | 0.206 | 0.00 |
SMSTORE4 | 2883.41 | 3460.09 | 19.86 | 0.124 | 0.206 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 13:00:00 | 21.11 | 21.11 | 0.00987 | 16.20 | 0.01152 | 0.206 | 0.00 |
LGSTORE2 | 6664.86 | 7997.83 | 22.96 | 0.277 | 0.411 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 21.11 | 21.11 | 0.00951 | 16.20 | 0.01152 | 0.411 | 0.00 |
SMSTORE5 | 3449.18 | 4139.01 | 23.76 | 0.144 | 0.206 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 21.11 | 21.11 | 0.00953 | 16.20 | 0.01152 | 0.206 | 0.00 |
SMSTORE6 | 3456.69 | 4148.03 | 23.81 | 0.144 | 0.206 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 21.11 | 21.11 | 0.00953 | 16.20 | 0.01152 | 0.206 | 0.00 |
SMSTORE7 | 3717.40 | 4460.88 | 25.61 | 0.155 | 0.206 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 21.11 | 21.11 | 0.00946 | 16.20 | 0.01152 | 0.206 | 0.00 |
SMSTORE8 | 4390.74 | 5268.89 | 30.25 | 0.183 | 0.219 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 21.11 | 21.11 | 0.00961 | 16.20 | 0.01152 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.89 | 1.89 | 0.41 | 0.41 | 1.8891 | 1.8891 | 1.8891 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.00 | 1.00 | 0.21 | 0.21 | 1.0012 | 1.0012 | 1.0012 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.04 | 1.04 | 0.21 | 0.21 | 1.0405 | 1.0405 | 1.0405 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.03 | 1.03 | 0.21 | 0.21 | 1.0345 | 1.0345 | 1.0345 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.03 | 1.03 | 0.21 | 0.21 | 1.0315 | 1.0315 | 1.0315 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.73 | 1.73 | 0.41 | 0.41 | 1.7286 | 1.7286 | 1.7286 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 0.90 | 0.90 | 0.21 | 0.21 | 0.9020 | 0.9020 | 0.9020 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 0.90 | 0.90 | 0.21 | 0.21 | 0.8963 | 0.8963 | 0.8963 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 0.90 | 0.90 | 0.21 | 0.21 | 0.8971 | 0.8971 | 0.8971 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.03 | 1.03 | 0.22 | 0.22 | 1.0310 | 1.0310 | 1.0310 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 22048.340 | 0.000 | 1.889130 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 22048.34 | 15543.37 | 1.889130 | 25.70 | 18.88 | 0.01086330 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 21.7800 | 23.88 | 0.00988955 | 53.4816 | 21417.83 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 45618.709 | 45618.709 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:50:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:50:00 | 45618.71 | 45618.71 | 1.889132 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 21.7800 | 21.11 | 0.00919453 | 58.9169 | 2632.98 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 11599.055 | 0.000 | 1.001210 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 11599.06 | 8190.54 | 1.001210 | 25.59 | 18.83 | 0.01083273 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 20.5478 | 23.88 | 0.00992335 | 53.6621 | 11365.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 24103.828 | 24103.828 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:20:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:20:00 | 24103.83 | 24103.83 | 1.001209 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 20.5478 | 21.11 | 0.00912900 | 58.5036 | 1201.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 12046.185 | 0.000 | 1.040540 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 12046.18 | 8510.71 | 1.040540 | 25.59 | 18.82 | 0.01082782 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 19.7711 | 23.89 | 0.00934354 | 50.5693 | 11396.24 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 25002.371 | 25002.371 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 25002.37 | 25002.37 | 1.040540 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 19.7711 | 21.11 | 0.00991806 | 63.4771 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 11966.265 | 0.000 | 1.034480 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 11966.26 | 8459.36 | 1.034480 | 25.58 | 18.81 | 0.01082215 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 19.8870 | 23.89 | 0.00932665 | 50.4787 | 11432.21 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 24863.957 | 24863.957 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 24863.96 | 24863.96 | 1.034484 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 19.8869 | 21.11 | 0.00990834 | 63.4158 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 11964.035 | 0.000 | 1.031530 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 11964.03 | 8441.13 | 1.031530 | 25.60 | 18.84 | 0.01084068 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 19.9438 | 23.89 | 0.00936119 | 50.6636 | 11315.54 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 25110.559 | 25110.559 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 08:10:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 08:10:00 | 25110.56 | 25110.56 | 1.031532 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 19.9438 | 21.11 | 0.00987145 | 63.1833 | 1101.71 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 20628.320 | 0.000 | 1.728550 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 20628.32 | 14321.78 | 1.728550 | 25.86 | 19.06 | 0.01101565 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 23.8034 | 23.89 | 0.00997293 | 53.9250 | 19620.86 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 41948.125 | 41948.125 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 41948.12 | 41948.12 | 1.728550 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 23.8034 | 21.11 | 0.00950956 | 60.9040 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 10742.690 | 0.000 | 0.902030 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 10742.69 | 7435.17 | 0.902030 | 25.78 | 19.04 | 0.01102674 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 22.8071 | 23.88 | 0.01004380 | 54.3029 | 10238.20 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 21836.147 | 21836.147 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 18:50:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 18:50:00 | 21836.15 | 21836.15 | 0.902030 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 22.8071 | 21.11 | 0.00952784 | 61.0190 | 1753.13 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 10692.985 | 0.000 | 0.896330 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 10692.99 | 7391.81 | 0.896330 | 25.79 | 19.05 | 0.01103882 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 22.9521 | 23.88 | 0.01005139 | 54.3433 | 10173.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 21944.328 | 21944.328 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:20:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:20:00 | 21944.33 | 21944.33 | 0.896333 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 22.9520 | 21.11 | 0.00952765 | 61.0177 | 1456.46 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 10699.775 | 0.000 | 0.897080 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 10699.77 | 7397.53 | 0.897080 | 25.79 | 19.05 | 0.01103744 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 22.9329 | 23.88 | 0.01005039 | 54.3380 | 10181.02 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 21723.676 | 21723.676 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 21723.68 | 21723.68 | 0.897077 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 22.9330 | 21.11 | 0.00945788 | 60.5775 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 11808.280 | 0.000 | 1.031020 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 11808.28 | 8360.68 | 1.031020 | 25.47 | 18.76 | 0.01079202 | 12.80 | 12.10 | 0.00850000 | 31.85 | 0.01434902 | 23.20 | 19.9537 | 23.88 | 0.00990534 | 53.5658 | 11705.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 25140.338 | 25140.338 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 25140.34 | 25140.34 | 1.031017 | 16.48 | 16.20 | 0.01140074 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 19.9538 | 21.11 | 0.00961134 | 61.5436 | 4390.74 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:19:10
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22048.340 | 0.000 | 1.889130 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.0343 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 22048.34 | 15543.37 | 1.0000 | 2.27455633 | 1.889130 | 25.70 | 18.88 | 0.01086330 | 53510.0 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22048.34 | 32.20 | 0.01434902 | 23.30 | 0.41145340 | 21.7800 | 23.88 | 0.00989116 | 23.88 | 0.00988955 | 53.4816 | 21417.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 45618.709 | 45618.709 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.889132 | 2.27455830 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:50:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:50:00 | 45618.71 | 45618.71 | 1.0000 | 2.27455830 | 1.889132 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 45618.71 | 16.20 | 0.01151798 | 16.20 | 0.41145340 | 21.7800 | 21.11 | 0.00863764 | 21.11 | 0.00919453 | 58.9169 | 2632.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 11599.055 | 0.000 | 1.001210 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.9775 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 11599.06 | 8190.54 | 1.0000 | 1.20548006 | 1.001210 | 25.59 | 18.83 | 0.01083273 | 53324.6 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11599.06 | 32.20 | 0.01434902 | 23.30 | 0.20572670 | 20.5478 | 23.88 | 0.00992335 | 23.88 | 0.00992335 | 53.6621 | 11365.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24103.828 | 24103.828 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.001209 | 1.20547875 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:20:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:20:00 | 24103.83 | 24103.83 | 1.0000 | 1.20547875 | 1.001209 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24103.83 | 16.20 | 0.01151798 | 16.20 | 0.20572670 | 20.5478 | 21.11 | 0.00881468 | 21.11 | 0.00912900 | 58.5036 | 1201.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12046.185 | 0.000 | 1.040540 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.9684 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 12046.18 | 8510.71 | 1.0000 | 1.25283429 | 1.040540 | 25.59 | 18.82 | 0.01082782 | 53307.3 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12046.18 | 32.20 | 0.01434902 | 23.30 | 0.20572670 | 19.7711 | 23.88 | 0.00992030 | 23.89 | 0.00934354 | 50.5693 | 11396.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25002.371 | 25002.371 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.040540 | 1.25283471 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 25002.37 | 25002.37 | 1.0000 | 1.25283471 | 1.040540 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25002.37 | 16.20 | 0.01151798 | 16.20 | 0.20572670 | 19.7711 | 21.11 | 0.00000000 | 21.11 | 0.00991806 | 63.4771 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 11966.265 | 0.000 | 1.034480 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.9578 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 11966.26 | 8459.36 | 1.0000 | 1.24553791 | 1.034480 | 25.58 | 18.81 | 0.01082215 | 53287.4 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11966.26 | 32.20 | 0.01434902 | 23.30 | 0.20572670 | 19.8870 | 23.88 | 0.00991675 | 23.89 | 0.00932665 | 50.4787 | 11432.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24863.957 | 24863.957 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.034484 | 1.24554269 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 24863.96 | 24863.96 | 1.0000 | 1.24554269 | 1.034484 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24863.96 | 16.20 | 0.01151798 | 16.20 | 0.20572670 | 19.8869 | 21.11 | 0.00000000 | 21.11 | 0.00990834 | 63.4158 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 11964.035 | 0.000 | 1.031530 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.9923 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 11964.03 | 8441.13 | 1.0000 | 1.24198604 | 1.031530 | 25.60 | 18.84 | 0.01084068 | 53352.5 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11964.03 | 32.20 | 0.01434902 | 23.30 | 0.20572670 | 19.9438 | 23.88 | 0.00992834 | 23.89 | 0.00936119 | 50.6636 | 11315.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25110.559 | 25110.559 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.031532 | 1.24198905 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 08:10:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 08:10:00 | 25110.56 | 25110.56 | 1.0000 | 1.24198905 | 1.031532 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25110.56 | 16.20 | 0.01151798 | 16.20 | 0.20572670 | 19.9438 | 20.80 | 0.00164239 | 21.11 | 0.00987145 | 63.1833 | 1101.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20628.320 | 0.000 | 1.728550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.3175 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 20628.32 | 14321.78 | 1.0000 | 2.08121428 | 1.728550 | 25.86 | 19.06 | 0.01101565 | 54068.7 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20628.32 | 32.20 | 0.01434902 | 23.30 | 0.41145340 | 23.8034 | 23.89 | 0.00997423 | 23.89 | 0.00997293 | 53.9250 | 19620.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 41948.125 | 41948.125 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.728550 | 2.08121445 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 41948.12 | 41948.12 | 1.0000 | 2.08121445 | 1.728550 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 41948.12 | 16.20 | 0.01151798 | 16.20 | 0.41145340 | 23.8034 | 21.11 | 0.00000000 | 21.11 | 0.00950956 | 60.9040 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 10742.690 | 0.000 | 0.902030 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.3382 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 10742.69 | 7435.17 | 1.0000 | 1.08606504 | 0.902030 | 25.78 | 19.04 | 0.01102674 | 54011.9 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10742.69 | 32.20 | 0.01434902 | 23.30 | 0.20572670 | 22.8071 | 23.88 | 0.01004501 | 23.88 | 0.01004380 | 54.3029 | 10238.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 21836.147 | 21836.147 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.902030 | 1.08606512 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 18:50:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 18:50:00 | 21836.15 | 21836.15 | 1.0000 | 1.08606512 | 0.902030 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21836.15 | 16.20 | 0.01151798 | 16.20 | 0.20572670 | 22.8071 | 21.11 | 0.01005726 | 21.11 | 0.00952784 | 61.0190 | 1753.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 10692.985 | 0.000 | 0.896330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.3606 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 10692.99 | 7391.81 | 1.0000 | 1.07920211 | 0.896330 | 25.79 | 19.05 | 0.01103882 | 54055.1 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10692.99 | 32.20 | 0.01434902 | 23.30 | 0.20572670 | 22.9521 | 23.88 | 0.01005260 | 23.88 | 0.01005139 | 54.3433 | 10173.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 21944.328 | 21944.328 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.896333 | 1.07920564 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:20:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:20:00 | 21944.33 | 21944.33 | 1.0000 | 1.07920564 | 0.896333 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21944.33 | 16.20 | 0.01151798 | 16.20 | 0.20572670 | 22.9520 | 20.83 | 0.00973800 | 21.11 | 0.00952765 | 61.0177 | 1456.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 10699.775 | 0.000 | 0.897080 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.3580 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 10699.77 | 7397.53 | 1.0000 | 1.08010512 | 0.897080 | 25.79 | 19.05 | 0.01103744 | 54050.1 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10699.77 | 32.20 | 0.01434902 | 23.30 | 0.20572670 | 22.9329 | 23.88 | 0.01005173 | 23.88 | 0.01005039 | 54.3380 | 10181.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 21723.676 | 21723.676 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.897077 | 1.08010098 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 21723.68 | 21723.68 | 1.0000 | 1.08010098 | 0.897077 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21723.68 | 16.20 | 0.01151798 | 16.20 | 0.20572670 | 22.9330 | 21.11 | 0.00000000 | 21.11 | 0.00945788 | 60.5775 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 11808.280 | 0.000 | 1.031020 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.9018 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 11808.28 | 8360.68 | 1.0000 | 1.24137199 | 1.031020 | 25.47 | 18.76 | 0.01079202 | 53099.0 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11808.28 | 31.85 | 0.01434902 | 23.20 | 0.20572670 | 19.9537 | 23.89 | 0.00990534 | 23.88 | 0.00990534 | 53.5658 | 11705.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25140.338 | 25140.338 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.031017 | 1.24136896 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 25140.34 | 25140.34 | 1.0000 | 1.24136896 | 1.031017 | 16.48 | 16.20 | 0.01140074 | 45421.7 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25140.34 | 16.20 | 0.01151798 | 16.20 | 0.20572670 | 19.9538 | 20.75 | 0.00961134 | 21.11 | 0.00961134 | 61.5436 | 4390.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:10
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 5748.17 | 124.67 | 120.17 |
SMSTORE1 | 5645.50 | 61.67 | 58.00 |
SMSTORE2 | 4365.67 | 148.00 | 147.33 |
SMSTORE3 | 4364.00 | 148.50 | 147.83 |
SMSTORE4 | 4359.67 | 165.00 | 164.00 |
LGSTORE2 | 3972.50 | 189.00 | 188.83 |
SMSTORE5 | 3945.83 | 209.17 | 209.00 |
SMSTORE6 | 3941.33 | 216.33 | 216.00 |
SMSTORE7 | 3941.50 | 225.33 | 224.50 |
SMSTORE8 | 3968.00 | 195.17 | 193.17 |
Facility | 5871.83 | 341.83 | 334.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.17 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 0.67 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.33 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 0.33 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 0.17 | 0.00 | 0.00 |
SMSTORE8 | 0.00 | 0.83 | 0.00 | 0.00 |
Facility | 0.00 | 1.17 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:10
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.02 | 30.00 | 1805.20 | 0.842 | 0.352 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.706 | 0.387 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 0.843 | 0.506 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 0.843 | 0.506 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 0.843 | 0.506 | 0.000 | 0.000 |
LGSTORE2 | 13.23 | 30.00 | 1805.20 | 0.843 | 0.474 | 0.000 | 0.000 |
SMSTORE5 | 6.62 | 15.00 | 902.60 | 0.843 | 0.540 | 0.000 | 0.000 |
SMSTORE6 | 6.62 | 15.00 | 902.60 | 0.843 | 0.540 | 0.000 | 0.000 |
SMSTORE7 | 6.62 | 15.00 | 902.60 | 0.843 | 0.540 | 0.000 | 0.000 |
SMSTORE8 | 6.62 | 15.00 | 902.60 | 0.843 | 0.565 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.02 | 30.00 | 1805.20 | 0.826 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.133 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 0.826 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 0.826 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 0.826 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 13.23 | 30.00 | 1805.20 | 0.829 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 6.62 | 15.00 | 902.60 | 0.829 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 6.62 | 15.00 | 902.60 | 0.829 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 6.62 | 15.00 | 902.60 | 0.829 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 6.62 | 15.00 | 902.60 | 0.829 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:10
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:19:10
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1236.71 | 2102.83 | 01-JAN-07:20 | 105068.84 | 03-SEP-14:30 |
Electricity:Building | 579.04 | 891.83 | 01-JAN-00:20 | 37073.46 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 132.39 | 148.64 | 01-JAN-00:20 | 6930.31 | 01-JAN-10:10 |
InteriorLights:Electricity | 450.89 | 450.00 | 01-JAN-00:20 | 29013.96 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 106.14 | 75.00 | 01-JAN-00:20 | 5587.06 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 450.89 | 450.00 | 01-JAN-00:20 | 29013.96 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 75.15 | 74.32 | 01-JAN-00:20 | 3939.90 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 62.02 | 37.50 | 01-JAN-00:20 | 3268.27 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 54.53 | 74.32 | 01-JAN-00:10 | 3678.60 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 44.11 | 37.50 | 01-JAN-00:10 | 3006.97 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 54.53 | 74.32 | 01-JAN-00:10 | 3678.60 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 44.11 | 37.50 | 01-JAN-00:10 | 3006.97 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 54.53 | 74.32 | 01-JAN-00:10 | 3678.60 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 44.11 | 37.50 | 01-JAN-00:10 | 3006.97 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 69.31 | 148.64 | 01-JAN-00:10 | 5055.82 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 50.13 | 75.00 | 01-JAN-00:10 | 3712.57 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 34.65 | 74.32 | 01-JAN-00:10 | 2527.91 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 25.07 | 37.50 | 01-JAN-00:10 | 1856.29 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 34.65 | 74.32 | 01-JAN-00:10 | 2527.91 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 25.07 | 37.50 | 01-JAN-00:10 | 1856.29 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 34.65 | 74.32 | 01-JAN-00:10 | 2527.91 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 25.07 | 37.50 | 01-JAN-00:10 | 1856.29 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 34.65 | 74.32 | 01-JAN-00:10 | 2527.91 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 25.07 | 37.50 | 01-JAN-00:10 | 1856.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
Electricity:Plant | 58.57 | 1211.00 | 18-JUN-08:10 | 11783.50 | 04-JAN-13:50 |
WaterSystems:Electricity | 58.57 | 1211.00 | 18-JUN-08:10 | 11783.50 | 04-JAN-13:50 |
Water Heater:WaterSystems:Electricity | 58.57 | 1211.00 | 18-JUN-08:10 | 11783.50 | 04-JAN-13:50 |
ElectricityPurchased:Facility | 1236.71 | 2102.83 | 01-JAN-07:20 | 105068.84 | 03-SEP-14:30 |
ElectricityPurchased:Plant | 1236.71 | 2102.83 | 01-JAN-07:20 | 105068.84 | 03-SEP-14:30 |
Cogeneration:ElectricityPurchased | 1236.71 | 2102.83 | 01-JAN-07:20 | 105068.84 | 03-SEP-14:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1236.71 | 2102.83 | 01-JAN-07:20 | 105068.84 | 03-SEP-14:30 |
ElectricityNet:Plant | 1236.71 | 2102.83 | 01-JAN-07:20 | 105068.84 | 03-SEP-14:30 |
Cogeneration:ElectricityNet | 1236.71 | 2102.83 | 01-JAN-07:20 | 105068.84 | 03-SEP-14:30 |
Electricity:HVAC | 539.64 | 0.00 | 01-JAN-00:10 | 61974.93 | 03-SEP-13:00 |
Fans:Electricity | 92.90 | 0.00 | 01-JAN-00:10 | 8916.68 | 03-SEP-13:00 |
General:Fans:Electricity | 92.90 | 0.00 | 01-JAN-00:10 | 8916.68 | 03-SEP-13:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 446.74 | 0.00 | 01-JAN-00:10 | 53058.25 | 03-SEP-13:00 |
ExteriorLights:Electricity | 59.45 | 0.00 | 01-JAN-07:20 | 5459.01 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 59.45 | 0.00 | 01-JAN-07:20 | 5459.01 | 01-JAN-06:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Gas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 2811.80 | 0.00 | 01-JAN-00:10 | 313282.14 | 03-SEP-13:00 |
EnergyTransfer:Building | 959.85 | 0.00 | 01-JAN-00:10 | 103505.34 | 11-OCT-13:00 |
EnergyTransfer:Zone:LGSTORE1 | 199.90 | 0.00 | 01-JAN-00:10 | 17813.14 | 03-SEP-16:10 |
Heating:EnergyTransfer | 3.22 | 0.00 | 01-JAN-00:10 | 17189.27 | 03-SEP-16:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.20 | 0.00 | 01-JAN-00:10 | 1676.56 | 09-JUL-07:20 |
Cooling:EnergyTransfer | 956.63 | 0.00 | 01-JAN-00:10 | 103505.34 | 11-OCT-13:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 199.70 | 0.00 | 01-JAN-00:10 | 17813.14 | 03-SEP-16:10 |
EnergyTransfer:Zone:SMSTORE1 | 106.27 | 0.00 | 01-JAN-00:10 | 9212.35 | 01-OCT-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.11 | 0.00 | 01-JAN-00:10 | 849.31 | 30-JUN-07:20 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 106.16 | 0.00 | 01-JAN-00:10 | 9212.35 | 01-OCT-13:00 |
EnergyTransfer:Zone:SMSTORE2 | 81.39 | 0.00 | 01-JAN-00:10 | 9055.71 | 01-OCT-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 0.39 | 0.00 | 01-JAN-00:10 | 1891.99 | 03-SEP-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 81.00 | 0.00 | 01-JAN-00:10 | 9055.71 | 01-OCT-13:00 |
EnergyTransfer:Zone:SMSTORE3 | 81.39 | 0.00 | 01-JAN-00:10 | 9071.52 | 01-OCT-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 0.39 | 0.00 | 01-JAN-00:10 | 1890.42 | 03-SEP-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 81.01 | 0.00 | 01-JAN-00:10 | 9071.52 | 01-OCT-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 79.27 | 0.00 | 01-JAN-00:10 | 8949.83 | 01-OCT-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 0.40 | 0.00 | 01-JAN-00:10 | 1897.44 | 03-SEP-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 78.87 | 0.00 | 01-JAN-00:10 | 8949.83 | 01-OCT-13:00 |
EnergyTransfer:Zone:LGSTORE2 | 130.91 | 0.00 | 01-JAN-00:10 | 15791.90 | 03-SEP-14:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 0.58 | 0.00 | 01-JAN-00:10 | 3848.51 | 03-SEP-16:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 130.33 | 0.00 | 01-JAN-00:10 | 15791.90 | 03-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE5 | 67.69 | 0.00 | 01-JAN-00:10 | 8327.44 | 03-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 0.30 | 0.00 | 01-JAN-00:10 | 1931.41 | 03-SEP-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 67.39 | 0.00 | 01-JAN-00:10 | 8327.44 | 03-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE6 | 67.06 | 0.00 | 01-JAN-00:10 | 8286.88 | 03-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 0.30 | 0.00 | 01-JAN-00:10 | 1933.51 | 03-SEP-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 66.77 | 0.00 | 01-JAN-00:10 | 8286.88 | 03-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE7 | 66.79 | 0.00 | 01-JAN-00:10 | 8342.85 | 03-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 0.30 | 0.00 | 01-JAN-00:10 | 1931.58 | 03-SEP-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 66.49 | 0.00 | 01-JAN-00:10 | 8342.85 | 03-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE8 | 79.18 | 0.00 | 01-JAN-00:10 | 9934.16 | 11-OCT-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 0.27 | 0.00 | 01-JAN-00:10 | 1864.41 | 03-SEP-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 78.91 | 0.00 | 01-JAN-00:10 | 9934.16 | 11-OCT-13:00 |
EnergyTransfer:HVAC | 1851.95 | 0.00 | 01-JAN-00:10 | 215648.08 | 19-AUG-15:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 1851.95 | 0.00 | 01-JAN-00:10 | 215648.08 | 19-AUG-15:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:10
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.200 | -199.697 | 0.000 | 0.000 | 12.382 | 106.140 | 26.249 | 16.173 | 0.000 | 17.150 | 26.215 | 0.000 | -3.332 | 0.000 | -1.481 | -0.001 |
SMSTORE1 | 0.000 | 0.000 | 0.112 | -106.159 | 0.000 | 0.000 | 6.191 | 62.022 | 13.125 | 8.105 | 0.000 | 9.512 | 9.298 | 0.000 | -1.670 | 0.000 | -0.535 | -0.000 |
SMSTORE2 | 0.000 | 0.000 | 0.389 | -80.996 | 0.000 | 0.000 | 3.719 | 44.110 | 10.421 | 8.076 | 0.000 | 9.325 | 7.557 | 0.000 | -1.855 | 0.000 | -0.746 | 0.000 |
SMSTORE3 | 0.000 | 0.000 | 0.385 | -81.007 | 0.000 | 0.000 | 3.719 | 44.110 | 10.421 | 8.076 | 0.000 | 9.324 | 7.582 | 0.000 | -1.860 | 0.000 | -0.749 | 0.000 |
SMSTORE4 | 0.000 | 0.000 | 0.400 | -78.865 | 0.000 | 0.000 | 3.719 | 44.110 | 10.421 | 8.087 | 0.000 | 9.326 | 5.349 | 0.000 | -1.826 | 0.000 | -0.723 | -0.000 |
LGSTORE2 | 0.000 | 0.000 | 0.580 | -130.325 | 0.000 | 0.000 | 12.763 | 50.132 | 19.173 | 16.171 | 0.000 | 16.396 | 19.873 | 0.000 | -3.437 | 0.000 | -1.326 | -0.001 |
SMSTORE5 | 0.000 | 0.000 | 0.296 | -67.388 | 0.000 | 0.000 | 6.382 | 25.066 | 9.586 | 8.102 | 0.000 | 9.337 | 10.974 | 0.000 | -1.678 | 0.000 | -0.677 | -0.000 |
SMSTORE6 | 0.000 | 0.000 | 0.297 | -66.766 | 0.000 | 0.000 | 6.382 | 25.066 | 9.586 | 8.108 | 0.000 | 9.338 | 10.327 | 0.000 | -1.668 | 0.000 | -0.671 | -0.000 |
SMSTORE7 | 0.000 | 0.000 | 0.297 | -66.490 | 0.000 | 0.000 | 6.382 | 25.066 | 9.586 | 8.107 | 0.000 | 9.339 | 10.033 | 0.000 | -1.660 | 0.000 | -0.658 | -0.001 |
SMSTORE8 | 0.000 | 0.000 | 0.267 | -78.913 | 0.000 | 0.000 | 6.381 | 25.066 | 9.586 | 8.021 | 0.000 | 9.730 | 22.799 | 0.000 | -1.664 | 0.000 | -1.273 | 0.000 |
Total Facility | 0.000 | 0.000 | 3.224 | -956.606 | 0.000 | 0.000 | 68.018 | 450.890 | 128.154 | 97.026 | 0.000 | 108.777 | 130.006 | 0.000 | -20.651 | 0.000 | -8.838 | -0.003 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 20-DEC-08:62 | 0.00 | 0.00 | 0.00 | -32810.43 | 0.00 | 0.00 | 96.21 | 75.00 | 74.62 | 1195.70 | 0.00 | 0.00 | 31631.28 | 0.00 | -0.00 | 0.00 | -262.38 | 0.00 |
SMSTORE1 | 25-DEC-08:62 | 0.00 | 0.00 | 0.00 | -17967.21 | 0.00 | 0.00 | 47.17 | 37.50 | 37.31 | 548.79 | 0.00 | 0.00 | 17402.90 | 0.00 | -0.00 | 0.00 | -106.47 | 0.00 |
SMSTORE2 | 25-DEC-08:62 | 0.00 | 0.00 | 0.00 | -17670.09 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 546.60 | 0.00 | 0.00 | 17157.43 | 0.00 | -0.00 | 0.00 | -108.75 | 0.00 |
SMSTORE3 | 25-DEC-08:62 | 0.00 | 0.00 | 0.00 | -17553.28 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 547.00 | 0.00 | 0.00 | 17039.79 | 0.00 | -0.00 | 0.00 | -108.33 | 0.00 |
SMSTORE4 | 25-DEC-08:62 | 0.00 | 0.00 | 0.00 | -17452.43 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 549.27 | 0.00 | 0.00 | 16932.14 | 0.00 | -0.00 | 0.00 | -103.78 | 0.00 |
LGSTORE2 | 20-DEC-08:62 | 0.00 | 0.00 | 0.00 | -30874.12 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 1196.93 | 0.00 | 0.00 | 29764.64 | 0.00 | -0.00 | 0.00 | -236.10 | 0.00 |
SMSTORE5 | 20-DEC-08:62 | 0.00 | 0.00 | 0.00 | -15992.19 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 598.80 | 0.00 | 0.00 | 15447.12 | 0.00 | -0.00 | 0.00 | -128.06 | 0.00 |
SMSTORE6 | 20-DEC-08:62 | 0.00 | 0.00 | 0.00 | -15891.58 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 599.70 | 0.00 | 0.00 | 15344.44 | 0.00 | -0.00 | 0.00 | -126.88 | 0.00 |
SMSTORE7 | 20-DEC-08:62 | 0.00 | 0.00 | 0.00 | -15828.86 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 601.77 | 0.00 | 0.00 | 15275.15 | 0.00 | -0.00 | 0.00 | -122.38 | 0.00 |
SMSTORE8 | 24-DEC-09:02 | 0.00 | 0.00 | 0.00 | -16767.61 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 1274.10 | 0.00 | 0.00 | 15474.91 | 0.00 | -0.00 | 0.00 | -55.72 | 0.00 |
Total Facility | 20-DEC-08:62 | 0.00 | 0.00 | 0.00 | -147720.04 | 0.00 | 0.00 | 300.94 | 450.00 | 1452.23 | 7215.73 | 0.00 | 0.00 | 139816.33 | 0.00 | 0.00 | 0.00 | -1515.20 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 03-SEP-07:06 | 0.00 | 0.00 | 2988.75 | 0.00 | 0.00 | 0.00 | 88.59 | 75.00 | 74.62 | 163.77 | 0.00 | 296.35 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3687.09 |
SMSTORE1 | 03-SEP-07:06 | 0.00 | 0.00 | 1474.07 | 0.00 | 0.00 | 0.00 | 44.27 | 37.50 | 37.31 | 82.35 | 0.00 | 154.52 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1830.02 |
SMSTORE2 | 03-SEP-16:02 | 0.00 | 0.00 | 2293.83 | 0.00 | 0.00 | 0.00 | 52.54 | 1582.62 | 373.13 | 454.81 | 0.00 | 2190.94 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6947.86 |
SMSTORE3 | 03-SEP-16:02 | 0.00 | 0.00 | 2292.63 | 0.00 | 0.00 | 0.00 | 52.54 | 1582.62 | 373.13 | 454.62 | 0.00 | 2190.70 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6946.23 |
SMSTORE4 | 03-SEP-16:02 | 0.00 | 0.00 | 2296.23 | 0.00 | 0.00 | 0.00 | 52.54 | 1582.62 | 373.13 | 455.08 | 0.00 | 2191.89 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6951.48 |
LGSTORE2 | 03-SEP-16:02 | 0.00 | 0.00 | 4602.81 | 0.00 | 0.00 | 0.00 | 231.18 | 1953.98 | 746.25 | 909.09 | 0.00 | 3867.68 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -12311.00 |
SMSTORE5 | 03-SEP-16:02 | 0.00 | 0.00 | 2307.19 | 0.00 | 0.00 | 0.00 | 115.59 | 976.99 | 373.13 | 458.31 | 0.00 | 2199.27 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6430.49 |
SMSTORE6 | 03-SEP-16:02 | 0.00 | 0.00 | 2307.90 | 0.00 | 0.00 | 0.00 | 115.59 | 976.99 | 373.13 | 458.61 | 0.00 | 2199.73 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6431.95 |
SMSTORE7 | 03-SEP-16:02 | 0.00 | 0.00 | 2306.78 | 0.00 | 0.00 | 0.00 | 115.59 | 976.99 | 373.13 | 457.98 | 0.00 | 2199.30 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6429.77 |
SMSTORE8 | 03-SEP-16:02 | 0.00 | 0.00 | 2278.05 | 0.00 | 0.00 | 0.00 | 115.59 | 976.99 | 373.13 | 450.11 | 0.00 | 2263.38 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6457.25 |
Total Facility | 03-SEP-16:02 | -26464.45 | 26464.45 | 20685.42 | -26464.45 | 0.00 | 0.00 | 2742.70 | 19465.13 | 5373.00 | 5476.59 | 0.00 | 25759.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -53037.70 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:10
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.8891 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.8891 | 0.2178 | 1.0000 | 0.4115 | 0.2178 | ||
PSZ-AC_2:2 | 1.0012 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0012 | 0.2055 | 1.0000 | 0.2057 | 0.2055 | ||
PSZ-AC_3:3 | 1.0405 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0405 | 0.1977 | 1.0000 | 0.2057 | 0.1977 | ||
PSZ-AC_4:4 | 1.0345 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0345 | 0.1989 | 1.0000 | 0.2057 | 0.1989 | ||
PSZ-AC_5:5 | 1.0315 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0315 | 0.1994 | 1.0000 | 0.2057 | 0.1994 | ||
PSZ-AC_6:6 | 1.7286 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.7286 | 0.2380 | 1.0000 | 0.4115 | 0.2380 | ||
PSZ-AC_7:7 | 0.9020 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9020 | 0.2281 | 1.0000 | 0.2057 | 0.2281 | ||
PSZ-AC_8:8 | 0.8963 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.8963 | 0.2295 | 1.0000 | 0.2057 | 0.2295 | ||
PSZ-AC_9:9 | 0.8971 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.8971 | 0.2293 | 1.0000 | 0.2057 | 0.2293 | ||
PSZ-AC_10:10 | 1.0310 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0310 | 0.1995 | 1.0000 | 0.2057 | 0.1995 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.8891 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.8891 | 1.0000 | 1.0000 | 0.4115 | 0.2178 | ||
PSZ-AC_2:2 | 1.0012 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0012 | 1.0000 | 1.0000 | 0.2057 | 0.2055 | ||
PSZ-AC_3:3 | 1.0405 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0405 | 1.0000 | 1.0000 | 0.2057 | 0.1977 | ||
PSZ-AC_4:4 | 1.0345 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0345 | 1.0000 | 1.0000 | 0.2057 | 0.1989 | ||
PSZ-AC_5:5 | 1.0315 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0315 | 1.0000 | 1.0000 | 0.2057 | 0.1994 | ||
PSZ-AC_6:6 | 1.7286 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.7286 | 1.0000 | 1.0000 | 0.4115 | 0.2380 | ||
PSZ-AC_7:7 | 0.9020 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9020 | 1.0000 | 1.0000 | 0.2057 | 0.2281 | ||
PSZ-AC_8:8 | 0.8963 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.8963 | 1.0000 | 1.0000 | 0.2057 | 0.2295 | ||
PSZ-AC_9:9 | 0.8971 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.8971 | 1.0000 | 1.0000 | 0.2057 | 0.2293 | ||
PSZ-AC_10:10 | 1.0310 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0310 | 1.0000 | 1.0000 | 0.2057 | 0.1995 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 1.8891 | 1.8891 | 1.8891 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.0012 | 1.0012 | 1.0012 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.0405 | 1.0405 | 1.0405 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.0345 | 1.0345 | 1.0345 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.0315 | 1.0315 | 1.0315 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 1.7286 | 1.7286 | 1.7286 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 0.9020 | 0.9020 | 0.9020 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 0.8963 | 0.8963 | 0.8963 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 0.8971 | 0.8971 | 0.8971 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.0310 | 1.0310 | 1.0310 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.8891 | 1.8891 | 1.8891 | 1.8891 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0012 | 1.0012 | 1.0012 | 1.0012 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0405 | 1.0405 | 1.0405 | 1.0405 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0345 | 1.0345 | 1.0345 | 1.0345 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0315 | 1.0315 | 1.0315 | 1.0315 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.7286 | 1.7286 | 1.7286 | 1.7286 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9020 | 0.9020 | 0.9020 | 0.9020 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.8963 | 0.8963 | 0.8963 | 0.8963 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.8971 | 0.8971 | 0.8971 | 0.8971 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0310 | 1.0310 | 1.0310 | 1.0310 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 1.8891 | 1.8891 | 1.8891 | 0.4115 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.0012 | 1.0012 | 1.0012 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.0405 | 1.0405 | 1.0405 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.0345 | 1.0345 | 1.0345 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.0315 | 1.0315 | 1.0315 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 1.7286 | 1.7286 | 1.7286 | 0.4115 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 0.9020 | 0.9020 | 0.9020 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 0.8963 | 0.8963 | 0.8963 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 0.8971 | 0.8971 | 0.8971 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.0310 | 1.0310 | 1.0310 | 0.2057 | 0.9385 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.8891 | 1.8891 | 1.8891 | 1.8891 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0012 | 1.0012 | 1.0012 | 1.0012 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0405 | 1.0405 | 1.0405 | 1.0405 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0345 | 1.0345 | 1.0345 | 1.0345 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0315 | 1.0315 | 1.0315 | 1.0315 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.7286 | 1.7286 | 1.7286 | 1.7286 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9020 | 0.9020 | 0.9020 | 0.9020 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.8963 | 0.8963 | 0.8963 | 0.8963 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.8971 | 0.8971 | 0.8971 | 0.8971 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0310 | 1.0310 | 1.0310 | 1.0310 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:10
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Honolulu Intl Arpt HI USA TMY3 WMO#=911820 |
Total gross floor area [m2] | 2090.32 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 446.74 | 53058.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 450.89 | 29013.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 59.45 | 5459.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 92.90 | 8916.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 58.57 | 11783.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 1236.71 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1236.71 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 215.70 |
Space Heating | 0.00 |
Space Cooling | 213.72 |
Fans (All) | 44.44 |
Service Water Heating | 28.02 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 591.64 |
Subtotal | 591.64 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 36.46 |
Space Heating | 0.00 |
Space Cooling | 36.12 |
Fans (All) | 7.51 |
Service Water Heating | 4.74 |
Receptacle Equipment | 10.36 |
Miscellaneous | 4.81 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
TYPE1_LIGHT_SCH | 5122. | 8760. |
TYPE2_LIGHT_SCH | 4096. | 8760. |
TYPE3_LIGHT_SCH | 3767. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUALSPSCHED | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Meter
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Meter
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Meter
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_HI_HONOLULU
For: Meter
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143540E+11 | 30134.77 | 12-JAN-08:62 | 22.88 | 18.16 | 0.751639E+09 | 899.02 | 20-JAN-13:00 | 25.00 | 16.56 |
February | 0.133989E+11 | 26575.06 | 13-FEB-08:62 | 23.98 | 19.24 | 0.678489E+09 | 899.03 | 11-FEB-13:50 | 24.08 | 16.32 |
March | 0.150094E+11 | 29470.39 | 19-MAR-07:02 | 21.88 | 17.44 | 0.744847E+09 | 899.00 | 24-MAR-12:00 | 26.10 | 17.93 |
April | 0.144753E+11 | 28316.12 | 06-APR-07:03 | 22.48 | 16.83 | 0.726276E+09 | 899.00 | 02-APR-16:19 | 25.40 | 17.89 |
May | 0.168459E+11 | 28667.56 | 22-MAY-07:02 | 23.77 | 19.39 | 0.747369E+09 | 898.98 | 21-MAY-17:00 | 27.20 | 21.04 |
June | 0.170142E+11 | 28328.92 | 04-JUN-07:02 | 24.67 | 20.27 | 0.722054E+09 | 898.99 | 04-JUN-17:00 | 26.70 | 19.95 |
July | 0.190185E+11 | 26990.36 | 08-JUL-07:02 | 25.37 | 20.63 | 0.753607E+09 | 898.97 | 30-JUL-16:19 | 29.23 | 21.06 |
August | 0.192955E+11 | 27484.54 | 24-AUG-07:02 | 23.27 | 19.94 | 0.743090E+09 | 898.95 | 06-AUG-17:00 | 26.70 | 21.73 |
September | 0.189611E+11 | 27519.05 | 18-SEP-07:02 | 23.35 | 20.65 | 0.728226E+09 | 898.93 | 03-SEP-16:30 | 32.25 | 23.55 |
October | 0.188291E+11 | 28240.23 | 26-OCT-07:03 | 21.23 | 19.48 | 0.751670E+09 | 898.96 | 08-OCT-17:00 | 27.20 | 21.04 |
November | 0.166814E+11 | 29049.62 | 15-NOV-08:62 | 23.98 | 18.53 | 0.726899E+09 | 898.97 | 10-NOV-13:09 | 26.10 | 21.50 |
December | 0.158170E+11 | 32816.27 | 20-DEC-08:62 | 21.28 | 16.29 | 0.755463E+09 | 899.01 | 22-DEC-13:09 | 25.77 | 17.26 |
Annual Sum or Average | 0.199700E+12 | 0.882963E+10 | ||||||||
Minimum of Months | 0.133989E+11 | 26575.06 | 21.23 | 16.29 | 0.678489E+09 | 898.93 | 24.08 | 16.32 | ||
Maximum of Months | 0.192955E+11 | 32816.27 | 25.37 | 20.65 | 0.755463E+09 | 899.03 | 32.25 | 23.55 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.791825E+10 | 17094.40 | 22-JAN-08:62 | 20.78 | 16.89 | 0.375824E+09 | 449.51 | 20-JAN-13:00 | 25.00 | 16.56 |
February | 0.725530E+10 | 15573.21 | 04-FEB-08:62 | 21.97 | 19.50 | 0.339252E+09 | 449.51 | 11-FEB-13:00 | 23.90 | 16.33 |
March | 0.807557E+10 | 16697.97 | 19-MAR-07:02 | 21.88 | 17.44 | 0.372435E+09 | 449.50 | 26-MAR-12:09 | 26.78 | 19.06 |
April | 0.778336E+10 | 16471.41 | 06-APR-07:03 | 22.48 | 16.83 | 0.363141E+09 | 449.50 | 01-APR-12:50 | 25.10 | 17.06 |
May | 0.895883E+10 | 16503.39 | 22-MAY-07:02 | 23.77 | 19.39 | 0.373687E+09 | 449.48 | 29-MAY-16:30 | 26.15 | 21.01 |
June | 0.894609E+10 | 16097.01 | 04-JUN-07:02 | 24.67 | 20.27 | 0.361027E+09 | 449.48 | 18-JUN-16:19 | 29.17 | 21.62 |
July | 0.992826E+10 | 15472.06 | 08-JUL-07:02 | 25.37 | 20.63 | 0.376804E+09 | 449.48 | 02-JUL-16:30 | 29.75 | 21.23 |
August | 0.100366E+11 | 15716.56 | 24-AUG-07:02 | 23.27 | 19.94 | 0.371545E+09 | 449.48 | 06-AUG-16:19 | 28.67 | 22.02 |
September | 0.977336E+10 | 15863.97 | 18-SEP-07:02 | 23.35 | 20.65 | 0.364113E+09 | 449.48 | 17-SEP-16:19 | 28.70 | 21.46 |
October | 0.998335E+10 | 16146.12 | 26-OCT-07:03 | 21.23 | 19.48 | 0.375835E+09 | 449.48 | 08-OCT-16:49 | 29.18 | 21.92 |
November | 0.890294E+10 | 16923.96 | 26-NOV-08:62 | 21.38 | 17.99 | 0.363451E+09 | 449.48 | 12-NOV-17:30 | 25.85 | 20.51 |
December | 0.859969E+10 | 17969.44 | 25-DEC-08:62 | 21.85 | 16.27 | 0.377736E+09 | 449.50 | 22-DEC-13:09 | 25.77 | 17.26 |
Annual Sum or Average | 0.106162E+12 | 0.441485E+10 | ||||||||
Minimum of Months | 0.725530E+10 | 15472.06 | 20.78 | 16.27 | 0.339252E+09 | 449.48 | 23.90 | 16.33 | ||
Maximum of Months | 0.100366E+11 | 17969.44 | 25.37 | 20.65 | 0.377736E+09 | 449.51 | 29.75 | 22.02 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.594519E+10 | 16637.66 | 22-JAN-08:62 | 20.78 | 16.89 | 0.224043E+09 | 449.49 | 21-JAN-13:09 | 25.68 | 17.07 |
February | 0.541536E+10 | 14751.08 | 13-FEB-07:03 | 23.40 | 18.65 | 0.203519E+09 | 449.51 | 11-FEB-13:50 | 24.08 | 16.32 |
March | 0.610498E+10 | 15609.32 | 19-MAR-07:02 | 21.88 | 17.44 | 0.230042E+09 | 449.49 | 25-MAR-12:20 | 26.33 | 17.76 |
April | 0.578537E+10 | 16099.31 | 30-APR-07:03 | 22.15 | 17.80 | 0.218981E+09 | 449.49 | 29-APR-12:39 | 27.20 | 18.28 |
May | 0.684576E+10 | 15751.37 | 31-MAY-06:03 | 22.38 | 17.90 | 0.227200E+09 | 449.45 | 27-MAY-12:09 | 29.60 | 20.63 |
June | 0.689101E+10 | 15024.38 | 04-JUN-07:02 | 24.67 | 20.27 | 0.222358E+09 | 449.43 | 03-JUN-12:09 | 28.25 | 20.83 |
July | 0.759483E+10 | 14347.56 | 04-JUL-07:02 | 25.37 | 20.83 | 0.224090E+09 | 449.46 | 08-JUL-12:09 | 31.20 | 21.97 |
August | 0.788718E+10 | 14644.28 | 24-AUG-06:02 | 21.38 | 19.31 | 0.230275E+09 | 449.43 | 05-AUG-12:00 | 30.00 | 21.62 |
September | 0.748531E+10 | 14653.36 | 19-SEP-06:02 | 22.30 | 20.24 | 0.219250E+09 | 449.39 | 30-SEP-12:09 | 27.38 | 23.55 |
October | 0.772224E+10 | 14962.39 | 18-OCT-06:02 | 20.10 | 18.61 | 0.224334E+09 | 449.38 | 28-OCT-12:09 | 30.18 | 22.21 |
November | 0.684931E+10 | 15875.70 | 09-NOV-07:03 | 18.77 | 17.50 | 0.216605E+09 | 449.42 | 25-NOV-13:09 | 28.30 | 22.38 |
December | 0.647131E+10 | 17673.96 | 25-DEC-08:62 | 21.85 | 16.27 | 0.223843E+09 | 449.48 | 23-DEC-13:09 | 25.77 | 17.78 |
Annual Sum or Average | 0.809979E+11 | 0.266454E+10 | ||||||||
Minimum of Months | 0.541536E+10 | 14347.56 | 18.77 | 16.27 | 0.203519E+09 | 449.38 | 24.08 | 16.32 | ||
Maximum of Months | 0.788718E+10 | 17673.96 | 25.37 | 20.83 | 0.230275E+09 | 449.51 | 31.20 | 23.55 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.591863E+10 | 16520.90 | 22-JAN-08:62 | 20.78 | 16.89 | 0.224039E+09 | 449.49 | 21-JAN-13:09 | 25.68 | 17.07 |
February | 0.539575E+10 | 14636.73 | 13-FEB-07:03 | 23.40 | 18.65 | 0.203515E+09 | 449.51 | 11-FEB-13:50 | 24.08 | 16.32 |
March | 0.608806E+10 | 15528.72 | 19-MAR-07:02 | 21.88 | 17.44 | 0.230038E+09 | 449.49 | 25-MAR-12:20 | 26.33 | 17.76 |
April | 0.576580E+10 | 15834.30 | 06-APR-06:03 | 22.20 | 17.21 | 0.218978E+09 | 449.49 | 29-APR-12:39 | 27.20 | 18.28 |
May | 0.684518E+10 | 15661.32 | 31-MAY-06:03 | 22.38 | 17.90 | 0.227198E+09 | 449.45 | 27-MAY-12:09 | 29.60 | 20.63 |
June | 0.689544E+10 | 14940.06 | 04-JUN-07:02 | 24.67 | 20.27 | 0.222357E+09 | 449.43 | 03-JUN-12:09 | 28.25 | 20.83 |
July | 0.761860E+10 | 14288.73 | 04-JUL-07:02 | 25.37 | 20.83 | 0.224090E+09 | 449.43 | 29-JUL-12:09 | 30.10 | 22.30 |
August | 0.790796E+10 | 14571.04 | 24-AUG-06:02 | 21.38 | 19.31 | 0.230274E+09 | 449.38 | 05-AUG-12:00 | 30.00 | 21.62 |
September | 0.751911E+10 | 14588.06 | 19-SEP-06:02 | 22.30 | 20.24 | 0.219250E+09 | 449.39 | 30-SEP-12:09 | 27.38 | 23.55 |
October | 0.774869E+10 | 14887.38 | 18-OCT-06:02 | 20.10 | 18.61 | 0.224334E+09 | 449.38 | 28-OCT-12:09 | 30.18 | 22.21 |
November | 0.684792E+10 | 15787.22 | 09-NOV-07:03 | 18.77 | 17.50 | 0.216602E+09 | 449.42 | 25-NOV-13:09 | 28.30 | 22.38 |
December | 0.645780E+10 | 17557.10 | 25-DEC-08:62 | 21.85 | 16.27 | 0.223841E+09 | 449.48 | 23-DEC-13:09 | 25.77 | 17.78 |
Annual Sum or Average | 0.810089E+11 | 0.266452E+10 | ||||||||
Minimum of Months | 0.539575E+10 | 14288.73 | 18.77 | 16.27 | 0.203515E+09 | 449.38 | 24.08 | 16.32 | ||
Maximum of Months | 0.790796E+10 | 17557.10 | 25.37 | 20.83 | 0.230274E+09 | 449.51 | 30.18 | 23.55 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.572597E+10 | 15951.10 | 22-JAN-08:62 | 20.78 | 16.89 | 0.224021E+09 | 449.50 | 21-JAN-13:09 | 25.68 | 17.07 |
February | 0.521923E+10 | 14478.76 | 13-FEB-07:03 | 23.40 | 18.65 | 0.203497E+09 | 449.51 | 11-FEB-13:39 | 24.27 | 16.30 |
March | 0.588612E+10 | 15428.64 | 19-MAR-07:02 | 21.88 | 17.44 | 0.230016E+09 | 449.47 | 18-MAR-12:09 | 27.70 | 19.76 |
April | 0.557415E+10 | 15244.06 | 06-APR-06:03 | 22.20 | 17.21 | 0.218960E+09 | 449.48 | 29-APR-12:00 | 27.20 | 18.09 |
May | 0.666175E+10 | 15305.46 | 31-MAY-06:03 | 22.38 | 17.90 | 0.227182E+09 | 449.45 | 27-MAY-12:09 | 29.60 | 20.63 |
June | 0.672266E+10 | 14825.83 | 04-JUN-07:02 | 24.67 | 20.27 | 0.222341E+09 | 449.43 | 03-JUN-12:09 | 28.25 | 20.83 |
July | 0.745436E+10 | 14173.29 | 04-JUL-07:02 | 25.37 | 20.83 | 0.224074E+09 | 449.46 | 08-JUL-12:09 | 31.20 | 21.97 |
August | 0.773298E+10 | 14454.49 | 24-AUG-06:02 | 21.38 | 19.31 | 0.230258E+09 | 449.44 | 05-AUG-12:00 | 30.00 | 21.62 |
September | 0.735694E+10 | 14477.72 | 19-SEP-06:02 | 22.30 | 20.24 | 0.219234E+09 | 449.39 | 30-SEP-12:20 | 27.57 | 23.54 |
October | 0.757755E+10 | 14774.01 | 18-OCT-06:02 | 20.10 | 18.61 | 0.224318E+09 | 449.38 | 28-OCT-12:09 | 30.18 | 22.21 |
November | 0.667917E+10 | 15676.17 | 09-NOV-07:03 | 18.77 | 17.50 | 0.216587E+09 | 449.42 | 25-NOV-13:09 | 28.30 | 22.38 |
December | 0.627609E+10 | 17456.29 | 25-DEC-08:62 | 21.85 | 16.27 | 0.223823E+09 | 449.48 | 23-DEC-13:09 | 25.77 | 17.78 |
Annual Sum or Average | 0.788670E+11 | 0.266431E+10 | ||||||||
Minimum of Months | 0.521923E+10 | 14173.29 | 18.77 | 16.27 | 0.203497E+09 | 449.38 | 24.27 | 16.30 | ||
Maximum of Months | 0.773298E+10 | 17456.29 | 25.37 | 20.83 | 0.230258E+09 | 449.51 | 31.20 | 23.54 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.926967E+10 | 28411.83 | 12-JAN-08:62 | 22.88 | 18.16 | 0.764939E+09 | 1198.63 | 21-JAN-15:09 | 22.98 | 17.97 |
February | 0.847043E+10 | 24609.39 | 13-FEB-08:62 | 23.98 | 19.24 | 0.696515E+09 | 1198.57 | 11-FEB-15:00 | 23.90 | 16.33 |
March | 0.957390E+10 | 26016.00 | 19-MAR-08:62 | 23.27 | 17.70 | 0.788938E+09 | 1198.54 | 25-MAR-14:09 | 26.10 | 17.78 |
April | 0.902914E+10 | 25632.78 | 07-APR-07:03 | 23.07 | 18.56 | 0.751624E+09 | 1198.63 | 29-APR-14:00 | 27.20 | 18.09 |
May | 0.110195E+11 | 26898.75 | 31-MAY-07:03 | 23.58 | 18.09 | 0.777249E+09 | 1198.52 | 06-MAY-14:09 | 30.40 | 21.69 |
June | 0.111733E+11 | 25035.70 | 06-JUN-07:02 | 23.92 | 19.67 | 0.762372E+09 | 1198.47 | 17-JUN-14:00 | 28.90 | 22.16 |
July | 0.124586E+11 | 25241.56 | 18-JUL-07:02 | 26.28 | 19.61 | 0.767045E+09 | 1198.39 | 01-JUL-14:00 | 31.10 | 21.52 |
August | 0.129664E+11 | 25314.46 | 24-AUG-07:02 | 23.27 | 19.94 | 0.789303E+09 | 1198.36 | 05-AUG-14:09 | 31.60 | 22.39 |
September | 0.123066E+11 | 25693.80 | 19-SEP-07:02 | 22.98 | 20.28 | 0.752136E+09 | 1198.41 | 16-SEP-14:20 | 27.77 | 23.42 |
October | 0.126932E+11 | 25525.25 | 26-OCT-07:03 | 21.23 | 19.48 | 0.765577E+09 | 1198.33 | 21-OCT-14:00 | 28.90 | 22.67 |
November | 0.110847E+11 | 27144.43 | 09-NOV-08:62 | 21.75 | 19.08 | 0.736995E+09 | 1198.48 | 25-NOV-15:00 | 26.10 | 20.73 |
December | 0.102822E+11 | 30879.07 | 20-DEC-08:62 | 21.28 | 16.29 | 0.766358E+09 | 1198.64 | 23-DEC-15:20 | 25.13 | 17.44 |
Annual Sum or Average | 0.130328E+12 | 0.911905E+10 | ||||||||
Minimum of Months | 0.847043E+10 | 24609.39 | 21.23 | 16.29 | 0.696515E+09 | 1198.33 | 22.98 | 16.33 | ||
Maximum of Months | 0.129664E+11 | 30879.07 | 26.28 | 20.28 | 0.789303E+09 | 1198.64 | 31.60 | 23.42 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.475300E+10 | 14729.92 | 12-JAN-08:62 | 22.88 | 18.16 | 0.382460E+09 | 599.31 | 21-JAN-15:09 | 22.98 | 17.97 |
February | 0.434673E+10 | 12507.97 | 13-FEB-08:62 | 23.98 | 19.24 | 0.348248E+09 | 599.28 | 11-FEB-15:00 | 23.90 | 16.33 |
March | 0.492114E+10 | 13452.52 | 19-MAR-08:62 | 23.27 | 17.70 | 0.394460E+09 | 599.27 | 25-MAR-14:09 | 26.10 | 17.78 |
April | 0.464730E+10 | 13266.93 | 07-APR-07:03 | 23.07 | 18.56 | 0.375803E+09 | 599.31 | 29-APR-14:00 | 27.20 | 18.09 |
May | 0.570482E+10 | 13460.08 | 31-MAY-07:03 | 23.58 | 18.09 | 0.388614E+09 | 599.25 | 06-MAY-14:30 | 30.00 | 21.62 |
June | 0.577955E+10 | 12971.29 | 06-JUN-07:02 | 23.92 | 19.67 | 0.381174E+09 | 599.23 | 03-JUN-14:00 | 28.30 | 20.42 |
July | 0.647557E+10 | 13075.65 | 18-JUL-07:02 | 26.28 | 19.61 | 0.383505E+09 | 599.19 | 01-JUL-14:00 | 31.10 | 21.52 |
August | 0.674636E+10 | 13112.29 | 24-AUG-07:02 | 23.27 | 19.94 | 0.394635E+09 | 599.17 | 05-AUG-14:09 | 31.60 | 22.39 |
September | 0.638759E+10 | 13327.93 | 19-SEP-07:02 | 22.98 | 20.28 | 0.376050E+09 | 599.19 | 16-SEP-14:20 | 27.77 | 23.42 |
October | 0.660228E+10 | 13214.60 | 26-OCT-07:03 | 21.23 | 19.48 | 0.382772E+09 | 599.16 | 21-OCT-14:00 | 28.90 | 22.67 |
November | 0.572958E+10 | 14059.42 | 09-NOV-08:62 | 21.75 | 19.08 | 0.368487E+09 | 599.24 | 25-NOV-15:00 | 26.10 | 20.73 |
December | 0.529562E+10 | 15994.83 | 20-DEC-08:62 | 21.28 | 16.29 | 0.383167E+09 | 599.31 | 23-DEC-15:09 | 25.27 | 17.49 |
Annual Sum or Average | 0.673895E+11 | 0.455937E+10 | ||||||||
Minimum of Months | 0.434673E+10 | 12507.97 | 21.23 | 16.29 | 0.348248E+09 | 599.16 | 22.98 | 16.33 | ||
Maximum of Months | 0.674636E+10 | 15994.83 | 26.28 | 20.28 | 0.394635E+09 | 599.31 | 31.60 | 23.42 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.469680E+10 | 14632.75 | 12-JAN-08:62 | 22.88 | 18.16 | 0.382457E+09 | 599.31 | 21-JAN-15:09 | 22.98 | 17.97 |
February | 0.429370E+10 | 12017.47 | 13-FEB-08:62 | 23.98 | 19.24 | 0.348244E+09 | 599.28 | 11-FEB-15:00 | 23.90 | 16.33 |
March | 0.486388E+10 | 13370.83 | 19-MAR-08:62 | 23.27 | 17.70 | 0.394456E+09 | 599.27 | 25-MAR-14:09 | 26.10 | 17.78 |
April | 0.459698E+10 | 13127.34 | 11-APR-07:03 | 22.48 | 19.66 | 0.375799E+09 | 599.31 | 29-APR-14:00 | 27.20 | 18.09 |
May | 0.565394E+10 | 13290.70 | 23-MAY-07:03 | 23.27 | 19.89 | 0.388611E+09 | 599.25 | 06-MAY-14:30 | 30.00 | 21.62 |
June | 0.572968E+10 | 12883.44 | 06-JUN-07:02 | 23.92 | 19.67 | 0.381172E+09 | 599.23 | 03-JUN-14:00 | 28.30 | 20.42 |
July | 0.642713E+10 | 12995.03 | 18-JUL-07:02 | 26.28 | 19.61 | 0.383502E+09 | 599.19 | 01-JUL-14:00 | 31.10 | 21.52 |
August | 0.669782E+10 | 13024.83 | 24-AUG-07:02 | 23.27 | 19.94 | 0.394633E+09 | 599.17 | 05-AUG-14:09 | 31.60 | 22.39 |
September | 0.633907E+10 | 13238.70 | 19-SEP-07:02 | 22.98 | 20.28 | 0.376046E+09 | 599.19 | 16-SEP-14:20 | 27.77 | 23.42 |
October | 0.655228E+10 | 13083.27 | 18-OCT-07:03 | 21.15 | 19.35 | 0.382769E+09 | 599.16 | 21-OCT-14:00 | 28.90 | 22.67 |
November | 0.567594E+10 | 13962.47 | 09-NOV-08:62 | 21.75 | 19.08 | 0.368484E+09 | 599.24 | 25-NOV-15:00 | 26.10 | 20.73 |
December | 0.523992E+10 | 15894.21 | 20-DEC-08:62 | 21.28 | 16.29 | 0.383163E+09 | 599.27 | 23-DEC-15:50 | 24.73 | 17.28 |
Annual Sum or Average | 0.667671E+11 | 0.455934E+10 | ||||||||
Minimum of Months | 0.429370E+10 | 12017.47 | 21.15 | 16.29 | 0.348244E+09 | 599.16 | 22.98 | 16.33 | ||
Maximum of Months | 0.669782E+10 | 15894.21 | 26.28 | 20.28 | 0.394633E+09 | 599.31 | 31.60 | 23.42 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.462968E+10 | 14569.28 | 12-JAN-08:62 | 22.88 | 18.16 | 0.382452E+09 | 599.31 | 21-JAN-15:09 | 22.98 | 17.97 |
February | 0.422149E+10 | 11587.20 | 05-FEB-09:02 | 24.50 | 20.72 | 0.348239E+09 | 599.28 | 11-FEB-15:00 | 23.90 | 16.33 |
March | 0.479385E+10 | 13327.92 | 19-MAR-08:62 | 23.27 | 17.70 | 0.394448E+09 | 599.27 | 25-MAR-14:09 | 26.10 | 17.78 |
April | 0.455657E+10 | 12627.93 | 10-APR-07:02 | 23.27 | 19.37 | 0.375796E+09 | 599.31 | 29-APR-14:00 | 27.20 | 18.09 |
May | 0.564675E+10 | 13060.67 | 27-MAY-07:02 | 23.30 | 20.09 | 0.388609E+09 | 599.25 | 06-MAY-14:30 | 30.00 | 21.62 |
June | 0.572834E+10 | 12833.99 | 06-JUN-07:02 | 23.92 | 19.67 | 0.381170E+09 | 599.23 | 03-JUN-14:00 | 28.30 | 20.42 |
July | 0.644368E+10 | 12952.91 | 18-JUL-07:02 | 26.28 | 19.61 | 0.383500E+09 | 599.19 | 01-JUL-14:00 | 31.10 | 21.52 |
August | 0.672648E+10 | 13003.10 | 24-AUG-07:02 | 23.27 | 19.94 | 0.394633E+09 | 599.17 | 05-AUG-14:09 | 31.60 | 22.39 |
September | 0.634911E+10 | 13210.31 | 19-SEP-07:02 | 22.98 | 20.28 | 0.376046E+09 | 599.19 | 16-SEP-14:20 | 27.77 | 23.42 |
October | 0.656220E+10 | 13002.40 | 17-OCT-07:02 | 23.48 | 19.40 | 0.382768E+09 | 599.16 | 21-OCT-14:00 | 28.90 | 22.67 |
November | 0.564488E+10 | 13906.43 | 09-NOV-08:62 | 21.75 | 19.08 | 0.368481E+09 | 599.24 | 25-NOV-15:00 | 26.10 | 20.73 |
December | 0.518873E+10 | 15831.51 | 20-DEC-08:62 | 21.28 | 16.29 | 0.383158E+09 | 599.27 | 23-DEC-15:50 | 24.73 | 17.28 |
Annual Sum or Average | 0.664918E+11 | 0.455930E+10 | ||||||||
Minimum of Months | 0.422149E+10 | 11587.20 | 21.28 | 16.29 | 0.348239E+09 | 599.16 | 22.98 | 16.33 | ||
Maximum of Months | 0.672648E+10 | 15831.51 | 26.28 | 20.72 | 0.394633E+09 | 599.31 | 31.60 | 23.42 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.531056E+10 | 13456.98 | 04-JAN-08:62 | 21.85 | 20.29 | 0.382479E+09 | 599.31 | 21-JAN-15:09 | 22.98 | 17.97 |
February | 0.471743E+10 | 11177.34 | 26-FEB-09:02 | 24.27 | 20.65 | 0.348262E+09 | 599.29 | 11-FEB-15:00 | 23.90 | 16.33 |
March | 0.546118E+10 | 13000.29 | 14-MAR-07:02 | 23.07 | 19.87 | 0.394468E+09 | 599.27 | 25-MAR-14:30 | 26.10 | 17.83 |
April | 0.544587E+10 | 13697.47 | 10-APR-07:02 | 23.27 | 19.37 | 0.375838E+09 | 599.32 | 29-APR-14:00 | 27.20 | 18.09 |
May | 0.689959E+10 | 13957.41 | 30-MAY-07:03 | 24.18 | 18.91 | 0.388658E+09 | 599.25 | 06-MAY-14:39 | 29.80 | 21.58 |
June | 0.697400E+10 | 14238.91 | 04-JUN-08:62 | 25.15 | 20.78 | 0.381213E+09 | 599.23 | 03-JUN-14:00 | 28.30 | 20.42 |
July | 0.786927E+10 | 13856.89 | 04-JUL-08:61 | 27.38 | 20.84 | 0.383570E+09 | 599.18 | 01-JUL-14:00 | 31.10 | 21.52 |
August | 0.829777E+10 | 13616.28 | 24-AUG-07:02 | 23.27 | 19.94 | 0.394688E+09 | 599.16 | 05-AUG-14:09 | 31.60 | 22.39 |
September | 0.753396E+10 | 13998.64 | 19-SEP-07:02 | 22.98 | 20.28 | 0.376112E+09 | 599.19 | 16-SEP-14:30 | 28.05 | 23.49 |
October | 0.791334E+10 | 13824.16 | 27-OCT-07:02 | 22.43 | 19.75 | 0.382831E+09 | 599.15 | 21-OCT-14:00 | 28.90 | 22.67 |
November | 0.654259E+10 | 15203.23 | 15-NOV-08:62 | 23.98 | 18.53 | 0.368515E+09 | 599.24 | 25-NOV-15:00 | 26.10 | 20.73 |
December | 0.594933E+10 | 16771.63 | 24-DEC-09:02 | 23.50 | 17.22 | 0.383190E+09 | 599.32 | 23-DEC-15:09 | 25.27 | 17.49 |
Annual Sum or Average | 0.789149E+11 | 0.455982E+10 | ||||||||
Minimum of Months | 0.471743E+10 | 11177.34 | 21.85 | 17.22 | 0.348262E+09 | 599.15 | 22.98 | 16.33 | ||
Maximum of Months | 0.829777E+10 | 16771.63 | 27.38 | 20.84 | 0.394688E+09 | 599.32 | 31.60 | 23.49 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3707831.84 | 978.55 | 02-JAN-08:06 | 23.48 |
February | 10513920.07 | 1659.27 | 18-FEB-08:06 | 24.60 |
March | 7682610.60 | 1239.39 | 15-MAR-07:05 | 23.68 |
April | 7973707.95 | 1146.94 | 25-APR-07:06 | 24.18 |
May | 23877723.82 | 1994.70 | 09-MAY-07:06 | 25.28 |
June | 28966445.27 | 2363.42 | 18-JUN-07:05 | 26.03 |
July | 28114941.72 | 2531.67 | 18-JUL-07:05 | 26.28 |
August | 25537076.97 | 2467.76 | 27-AUG-07:05 | 26.38 |
September | 21744226.18 | 2989.11 | 03-SEP-07:06 | 27.48 |
October | 14353366.58 | 2257.88 | 06-OCT-07:05 | 25.97 |
November | 17546576.99 | 2374.90 | 06-NOV-08:06 | 26.47 |
December | 9940671.84 | 2252.71 | 03-DEC-08:06 | 26.10 |
Annual Sum or Average | 0.199959E+09 | |||
Minimum of Months | 3707831.84 | 978.55 | 23.48 | |
Maximum of Months | 28966445.27 | 2989.11 | 27.48 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2337570.04 | 538.41 | 02-JAN-08:06 | 23.48 |
February | 5978273.06 | 881.44 | 18-FEB-08:06 | 24.60 |
March | 4519186.27 | 742.34 | 15-MAR-07:05 | 23.68 |
April | 4890489.37 | 638.27 | 07-APR-07:05 | 23.07 |
May | 11890989.39 | 1029.79 | 09-MAY-07:06 | 25.28 |
June | 14616995.55 | 1455.21 | 21-JUN-07:05 | 26.78 |
July | 15003475.49 | 1375.36 | 18-JUL-07:05 | 26.28 |
August | 14564956.80 | 1369.19 | 27-AUG-07:05 | 26.38 |
September | 12555697.42 | 1473.99 | 03-SEP-07:06 | 27.48 |
October | 9247205.88 | 1293.64 | 06-OCT-07:05 | 25.97 |
November | 10615094.65 | 1313.20 | 22-NOV-08:05 | 26.28 |
December | 5762769.72 | 1236.19 | 01-DEC-08:05 | 25.72 |
Annual Sum or Average | 0.111983E+09 | |||
Minimum of Months | 2337570.04 | 538.41 | 23.07 | |
Maximum of Months | 15003475.49 | 1473.99 | 27.48 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3988710.83 | 867.18 | 29-JAN-17:03 | 26.83 |
February | 6201510.32 | 882.16 | 17-FEB-07:06 | 24.40 |
March | 8520431.12 | 935.19 | 12-MAR-16:03 | 27.12 |
April | 12037709.19 | 1160.32 | 09-APR-16:03 | 28.12 |
May | 33738332.64 | 1200.06 | 21-MAY-16:03 | 28.30 |
June | 46472344.58 | 1470.84 | 18-JUN-16:02 | 29.23 |
July | 66694653.90 | 1737.83 | 09-JUL-16:02 | 30.40 |
August | 64184913.44 | 2027.57 | 20-AUG-16:02 | 31.42 |
September | 62911283.91 | 2293.39 | 03-SEP-16:02 | 32.62 |
October | 50965010.38 | 2145.44 | 01-OCT-16:02 | 31.93 |
November | 21041579.39 | 1445.39 | 05-NOV-16:02 | 29.22 |
December | 12351189.52 | 1197.10 | 03-DEC-08:06 | 26.10 |
Annual Sum or Average | 0.389108E+09 | |||
Minimum of Months | 3988710.83 | 867.18 | 24.40 | |
Maximum of Months | 66694653.90 | 2293.39 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3958659.46 | 868.44 | 29-JAN-17:03 | 26.83 |
February | 6176075.14 | 876.02 | 17-FEB-07:06 | 24.40 |
March | 8490532.40 | 936.23 | 12-MAR-16:03 | 27.12 |
April | 11999943.32 | 1160.76 | 09-APR-16:03 | 28.12 |
May | 33432025.22 | 1200.02 | 21-MAY-16:03 | 28.30 |
June | 45941754.95 | 1470.27 | 18-JUN-16:02 | 29.23 |
July | 65688183.65 | 1737.29 | 09-JUL-16:02 | 30.40 |
August | 63309716.82 | 2026.63 | 20-AUG-16:02 | 31.42 |
September | 62570212.19 | 2292.19 | 03-SEP-16:02 | 32.62 |
October | 50384175.22 | 2144.69 | 01-OCT-16:02 | 31.93 |
November | 20824008.17 | 1444.48 | 05-NOV-16:02 | 29.22 |
December | 12246319.73 | 1186.13 | 03-DEC-08:06 | 26.10 |
Annual Sum or Average | 0.385022E+09 | |||
Minimum of Months | 3958659.46 | 868.44 | 24.40 | |
Maximum of Months | 65688183.65 | 2292.19 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4049528.20 | 874.79 | 29-JAN-17:03 | 26.83 |
February | 6561426.97 | 814.95 | 17-FEB-07:06 | 24.40 |
March | 8827185.57 | 942.74 | 12-MAR-16:03 | 27.12 |
April | 12488947.41 | 1166.89 | 09-APR-16:03 | 28.12 |
May | 34615230.46 | 1205.91 | 21-MAY-16:03 | 28.30 |
June | 47433373.13 | 1474.72 | 18-JUN-16:02 | 29.23 |
July | 68288971.44 | 1741.83 | 09-JUL-16:02 | 30.40 |
August | 66388396.20 | 2030.40 | 20-AUG-16:02 | 31.42 |
September | 64104414.81 | 2295.79 | 03-SEP-16:02 | 32.62 |
October | 52432503.98 | 2148.44 | 01-OCT-16:02 | 31.93 |
November | 22050554.36 | 1448.76 | 05-NOV-16:02 | 29.22 |
December | 13106179.17 | 1229.34 | 03-DEC-08:06 | 26.10 |
Annual Sum or Average | 0.400347E+09 | |||
Minimum of Months | 4049528.20 | 814.95 | 24.40 | |
Maximum of Months | 68288971.44 | 2295.79 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10624216.90 | 1757.14 | 29-JAN-17:03 | 26.83 |
February | 17181801.22 | 1543.36 | 18-FEB-08:06 | 24.60 |
March | 20185874.45 | 1895.47 | 12-MAR-16:03 | 27.12 |
April | 27982354.84 | 2351.08 | 09-APR-16:03 | 28.12 |
May | 59684979.37 | 2431.66 | 21-MAY-16:03 | 28.30 |
June | 64431188.50 | 2947.97 | 18-JUN-16:02 | 29.23 |
July | 93646114.66 | 3494.88 | 09-JUL-16:02 | 30.40 |
August | 79526388.26 | 4056.52 | 20-AUG-16:02 | 31.42 |
September | 80425097.46 | 4601.99 | 03-SEP-16:02 | 32.62 |
October | 67488118.83 | 4298.28 | 01-OCT-16:02 | 31.93 |
November | 39624189.44 | 2905.53 | 05-NOV-16:02 | 29.22 |
December | 19105131.68 | 2038.49 | 01-DEC-08:05 | 25.72 |
Annual Sum or Average | 0.579905E+09 | |||
Minimum of Months | 10624216.90 | 1543.36 | 24.60 | |
Maximum of Months | 93646114.66 | 4601.99 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5430589.17 | 889.16 | 29-JAN-17:03 | 26.83 |
February | 9175920.74 | 810.29 | 05-FEB-09:05 | 24.50 |
March | 11053245.25 | 959.06 | 12-MAR-16:03 | 27.12 |
April | 15369244.19 | 1184.98 | 09-APR-16:03 | 28.12 |
May | 29715703.00 | 1224.68 | 21-MAY-16:03 | 28.30 |
June | 31790007.89 | 1483.98 | 18-JUN-16:02 | 29.23 |
July | 46499020.64 | 1754.95 | 09-JUL-16:02 | 30.40 |
August | 40455219.57 | 2036.63 | 20-AUG-16:02 | 31.42 |
September | 41286204.55 | 2306.76 | 03-SEP-16:02 | 32.62 |
October | 35044953.21 | 2156.21 | 01-OCT-16:02 | 31.93 |
November | 19639875.36 | 1460.77 | 05-NOV-16:02 | 29.22 |
December | 10203018.70 | 1087.86 | 01-DEC-08:05 | 25.72 |
Annual Sum or Average | 0.295663E+09 | |||
Minimum of Months | 5430589.17 | 810.29 | 24.50 | |
Maximum of Months | 46499020.64 | 2306.76 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5421559.28 | 890.25 | 29-JAN-17:03 | 26.83 |
February | 9151465.71 | 809.94 | 05-FEB-09:05 | 24.50 |
March | 11102777.98 | 960.13 | 12-MAR-16:03 | 27.12 |
April | 15467296.10 | 1186.11 | 09-APR-16:03 | 28.12 |
May | 29685928.98 | 1225.77 | 21-MAY-16:03 | 28.30 |
June | 31914967.71 | 1484.69 | 18-JUN-16:02 | 29.23 |
July | 46972299.42 | 1755.77 | 09-JUL-16:02 | 30.40 |
August | 40461814.89 | 2037.03 | 20-AUG-16:02 | 31.42 |
September | 41525628.74 | 2307.47 | 03-SEP-16:02 | 32.62 |
October | 35255181.70 | 2156.87 | 01-OCT-16:02 | 31.93 |
November | 20106793.75 | 1461.72 | 05-NOV-16:02 | 29.22 |
December | 10314617.62 | 1082.11 | 01-DEC-08:05 | 25.72 |
Annual Sum or Average | 0.297380E+09 | |||
Minimum of Months | 5421559.28 | 809.94 | 24.50 | |
Maximum of Months | 46972299.42 | 2307.47 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5633232.68 | 892.30 | 29-JAN-17:03 | 26.83 |
February | 9411992.66 | 823.99 | 05-FEB-09:05 | 24.50 |
March | 11208064.73 | 961.78 | 12-MAR-16:03 | 27.12 |
April | 15619296.18 | 1186.84 | 09-APR-16:03 | 28.12 |
May | 29094945.48 | 1225.79 | 21-MAY-16:03 | 28.30 |
June | 32311237.77 | 1484.51 | 18-JUN-16:02 | 29.23 |
July | 46950837.40 | 1755.14 | 09-JUL-16:02 | 30.40 |
August | 40095691.21 | 2035.93 | 20-AUG-16:02 | 31.42 |
September | 41431428.67 | 2306.35 | 03-SEP-16:02 | 32.62 |
October | 35128218.20 | 2156.70 | 01-OCT-16:02 | 31.93 |
November | 19472997.85 | 1461.80 | 05-NOV-16:02 | 29.22 |
December | 10703276.76 | 1116.60 | 01-DEC-08:05 | 25.72 |
Annual Sum or Average | 0.297061E+09 | |||
Minimum of Months | 5633232.68 | 823.99 | 24.50 | |
Maximum of Months | 46950837.40 | 2306.35 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4829026.33 | 891.90 | 29-JAN-17:03 | 26.83 |
February | 9968636.83 | 834.52 | 20-FEB-09:05 | 24.37 |
March | 11256551.51 | 950.53 | 12-MAR-16:03 | 27.12 |
April | 15011650.68 | 1169.45 | 09-APR-16:03 | 28.12 |
May | 26491840.55 | 1204.96 | 21-MAY-16:03 | 28.30 |
June | 26000404.38 | 1468.91 | 18-JUN-16:02 | 29.23 |
July | 39793591.44 | 1728.72 | 09-JUL-16:02 | 30.40 |
August | 35002815.16 | 2014.94 | 20-AUG-16:02 | 31.42 |
September | 38550802.82 | 2277.60 | 03-SEP-16:02 | 32.62 |
October | 33573012.14 | 2137.27 | 01-OCT-16:02 | 31.93 |
November | 16325442.44 | 1493.22 | 23-NOV-09:06 | 27.38 |
December | 9913267.63 | 1206.28 | 01-DEC-08:05 | 25.72 |
Annual Sum or Average | 0.266717E+09 | |||
Minimum of Months | 4829026.33 | 834.52 | 24.37 | |
Maximum of Months | 39793591.44 | 2277.60 | 32.62 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.900155E+10 | 5587.06 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.814396E+10 | 5587.06 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.901902E+10 | 5587.06 | 01-MAR-10:09 | 0.223053E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.873329E+10 | 5587.06 | 01-APR-09:09 | 0.215990E+10 | 1343.25 | 01-APR-09:09 |
May | 0.900155E+10 | 5587.06 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.873302E+10 | 5587.06 | 01-JUN-09:09 | 0.215990E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.901915E+10 | 5587.06 | 01-JUL-09:09 | 0.223053E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.900155E+10 | 5587.06 | 01-AUG-09:09 | 0.222596E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.875049E+10 | 5587.06 | 01-SEP-09:09 | 0.216447E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.900168E+10 | 5587.06 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.869809E+10 | 5587.06 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.903649E+10 | 5587.06 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.106140E+12 | 0.262491E+11 | ||||
Minimum of Months | 0.814396E+10 | 5587.06 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.903649E+10 | 5587.06 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.525997E+10 | 3268.27 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.475885E+10 | 3268.27 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.527019E+10 | 3268.27 | 01-MAR-10:09 | 0.111526E+10 | 671.63 | 01-MAR-10:09 |
April | 0.510323E+10 | 3268.27 | 01-APR-09:09 | 0.107995E+10 | 671.63 | 01-APR-09:09 |
May | 0.525997E+10 | 3268.27 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.510306E+10 | 3268.27 | 01-JUN-09:09 | 0.107995E+10 | 671.63 | 01-JUN-09:09 |
July | 0.527027E+10 | 3268.27 | 01-JUL-09:09 | 0.111526E+10 | 671.63 | 01-JUL-09:09 |
August | 0.525997E+10 | 3268.27 | 01-AUG-09:09 | 0.111298E+10 | 671.63 | 01-AUG-09:09 |
September | 0.511328E+10 | 3268.27 | 01-SEP-09:09 | 0.108223E+10 | 671.63 | 01-SEP-09:09 |
October | 0.526005E+10 | 3268.27 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.508263E+10 | 3268.27 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.528040E+10 | 3268.27 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.620219E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.475885E+10 | 3268.27 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.528040E+10 | 3268.27 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.372206E+10 | 3006.97 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.337152E+10 | 3006.97 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.380758E+10 | 3006.97 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.361234E+10 | 3006.97 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.376482E+10 | 3006.97 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.367648E+10 | 3006.97 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.370068E+10 | 3006.97 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.380758E+10 | 3006.97 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.361234E+10 | 3006.97 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.372206E+10 | 3006.97 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.361234E+10 | 3006.97 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.370068E+10 | 3006.97 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.441105E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.337152E+10 | 3006.97 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.380758E+10 | 3006.97 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.372206E+10 | 3006.97 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.337152E+10 | 3006.97 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.380758E+10 | 3006.97 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.361234E+10 | 3006.97 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.376482E+10 | 3006.97 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.367648E+10 | 3006.97 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.370068E+10 | 3006.97 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.380758E+10 | 3006.97 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.361234E+10 | 3006.97 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.372206E+10 | 3006.97 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.361234E+10 | 3006.97 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.370068E+10 | 3006.97 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.441105E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.337152E+10 | 3006.97 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.380758E+10 | 3006.97 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.372206E+10 | 3006.97 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.337152E+10 | 3006.97 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.380758E+10 | 3006.97 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.361234E+10 | 3006.97 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.376482E+10 | 3006.97 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.367648E+10 | 3006.97 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.370068E+10 | 3006.97 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.380758E+10 | 3006.97 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.361234E+10 | 3006.97 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.372206E+10 | 3006.97 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.361234E+10 | 3006.97 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.370068E+10 | 3006.97 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.441105E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.337152E+10 | 3006.97 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.380758E+10 | 3006.97 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.422804E+10 | 3712.57 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.383070E+10 | 3712.57 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.433280E+10 | 3712.57 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.410432E+10 | 3712.57 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.428042E+10 | 3712.57 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.418290E+10 | 3712.57 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.420185E+10 | 3712.57 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.433280E+10 | 3712.57 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.410432E+10 | 3712.57 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.422804E+10 | 3712.57 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.410432E+10 | 3712.57 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.420185E+10 | 3712.57 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.501324E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.383070E+10 | 3712.57 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.433280E+10 | 3712.57 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.211402E+10 | 1856.29 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.191535E+10 | 1856.29 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.216640E+10 | 1856.29 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.205216E+10 | 1856.29 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.214021E+10 | 1856.29 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.209145E+10 | 1856.29 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.210092E+10 | 1856.29 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.216640E+10 | 1856.29 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.205216E+10 | 1856.29 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.211402E+10 | 1856.29 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.205216E+10 | 1856.29 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.210092E+10 | 1856.29 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.250662E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.191535E+10 | 1856.29 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.216640E+10 | 1856.29 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.211402E+10 | 1856.29 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.191535E+10 | 1856.29 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.216640E+10 | 1856.29 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.205216E+10 | 1856.29 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.214021E+10 | 1856.29 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.209145E+10 | 1856.29 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.210092E+10 | 1856.29 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.216640E+10 | 1856.29 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.205216E+10 | 1856.29 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.211402E+10 | 1856.29 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.205216E+10 | 1856.29 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.210092E+10 | 1856.29 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.250662E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.191535E+10 | 1856.29 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.216640E+10 | 1856.29 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.211402E+10 | 1856.29 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.191535E+10 | 1856.29 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.216640E+10 | 1856.29 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.205216E+10 | 1856.29 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.214021E+10 | 1856.29 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.209145E+10 | 1856.29 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.210092E+10 | 1856.29 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.216640E+10 | 1856.29 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.205216E+10 | 1856.29 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.211402E+10 | 1856.29 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.205216E+10 | 1856.29 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.210092E+10 | 1856.29 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.250662E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.191535E+10 | 1856.29 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.216640E+10 | 1856.29 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.211402E+10 | 1856.29 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.191535E+10 | 1856.29 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.216640E+10 | 1856.29 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.205216E+10 | 1856.29 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.214021E+10 | 1856.29 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.209145E+10 | 1856.29 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.210092E+10 | 1856.29 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.216640E+10 | 1856.29 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.205216E+10 | 1856.29 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.211402E+10 | 1856.29 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.205216E+10 | 1856.29 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.210092E+10 | 1856.29 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.250662E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.191535E+10 | 1856.29 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.216640E+10 | 1856.29 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.180574E+10 | 0.900155E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574149E+09 | 0.346070E+09 |
February | 0.163016E+10 | 0.814396E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624247E+09 | 0.180556E+09 |
March | 0.178954E+10 | 0.901902E+10 | 0.223053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.947820E+09 | 0.183988E+09 |
April | 0.174484E+10 | 0.873329E+10 | 0.215990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103388E+10 | 0.155986E+09 |
May | 0.179537E+10 | 0.900155E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162730E+10 | 87209053.69 |
June | 0.173447E+10 | 0.873302E+10 | 0.215990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159666E+10 | 65734091.39 |
July | 0.181028E+10 | 0.901915E+10 | 0.223053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220523E+10 | 47849181.19 |
August | 0.178501E+10 | 0.900155E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240702E+10 | 42435793.06 |
September | 0.174937E+10 | 0.875049E+10 | 0.216447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199054E+10 | 32709750.59 |
October | 0.180574E+10 | 0.900168E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210652E+10 | 51670070.22 |
November | 0.174613E+10 | 0.869809E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123666E+10 | 0.115243E+09 |
December | 0.181481E+10 | 0.903649E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.800010E+09 | 0.171285E+09 |
Annual Sum or Average | 0.212115E+11 | 0.106140E+12 | 0.262491E+11 | 0.171500E+11 | 0.148074E+10 | ||||
Minimum of Months | 0.163016E+10 | 0.814396E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574149E+09 | 32709750.59 |
Maximum of Months | 0.181481E+10 | 0.903649E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240702E+10 | 0.346070E+09 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.902868E+09 | 0.525997E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321536E+09 | 0.147368E+09 |
February | 0.815075E+09 | 0.475885E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349740E+09 | 69589616.90 |
March | 0.894769E+09 | 0.527019E+10 | 0.111526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529159E+09 | 64295444.01 |
April | 0.872416E+09 | 0.510323E+10 | 0.107995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576200E+09 | 52939451.28 |
May | 0.897684E+09 | 0.525997E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905955E+09 | 26962666.73 |
June | 0.867232E+09 | 0.510306E+10 | 0.107995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.880901E+09 | 20130289.41 |
July | 0.905135E+09 | 0.527027E+10 | 0.111526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121625E+10 | 14614861.98 |
August | 0.892501E+09 | 0.525997E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133119E+10 | 12774453.28 |
September | 0.874683E+09 | 0.511328E+10 | 0.108223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109716E+10 | 9695424.38 |
October | 0.902868E+09 | 0.526005E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117341E+10 | 16085923.80 |
November | 0.873064E+09 | 0.508263E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683977E+09 | 38003775.20 |
December | 0.907403E+09 | 0.528040E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446450E+09 | 62169870.74 |
Annual Sum or Average | 0.106057E+11 | 0.620219E+11 | 0.131245E+11 | 0.951192E+10 | 0.534630E+09 | ||||
Minimum of Months | 0.815075E+09 | 0.475885E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321536E+09 | 9695424.38 |
Maximum of Months | 0.907403E+09 | 0.528040E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133119E+10 | 0.147368E+09 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.372206E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318129E+09 | 0.176058E+09 |
February | 0.487879E+09 | 0.337152E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344629E+09 | 92429350.53 |
March | 0.551374E+09 | 0.380758E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521173E+09 | 86548149.00 |
April | 0.524810E+09 | 0.361234E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566435E+09 | 78683623.41 |
May | 0.544247E+09 | 0.376482E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.889843E+09 | 42367965.58 |
June | 0.532585E+09 | 0.367648E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862365E+09 | 33091476.55 |
July | 0.536472E+09 | 0.370068E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118486E+10 | 25184509.52 |
August | 0.551374E+09 | 0.380758E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130825E+10 | 20045531.20 |
September | 0.524810E+09 | 0.361234E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106834E+10 | 17107853.91 |
October | 0.537120E+09 | 0.372206E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114703E+10 | 25054202.46 |
November | 0.518979E+09 | 0.361234E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671447E+09 | 58268928.14 |
December | 0.536472E+09 | 0.370068E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442421E+09 | 91167576.90 |
Annual Sum or Average | 0.638324E+10 | 0.441105E+11 | 0.104207E+11 | 0.932492E+10 | 0.746007E+09 | ||||
Minimum of Months | 0.487879E+09 | 0.337152E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318129E+09 | 17107853.91 |
Maximum of Months | 0.551374E+09 | 0.380758E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130825E+10 | 0.176058E+09 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.372206E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318134E+09 | 0.175709E+09 |
February | 0.487879E+09 | 0.337152E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344633E+09 | 92256468.55 |
March | 0.551374E+09 | 0.380758E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521181E+09 | 86480384.78 |
April | 0.524810E+09 | 0.361234E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566450E+09 | 78517677.29 |
May | 0.544247E+09 | 0.376482E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.889833E+09 | 42577484.92 |
June | 0.532585E+09 | 0.367648E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862332E+09 | 33574707.54 |
July | 0.536472E+09 | 0.370068E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118468E+10 | 26135243.07 |
August | 0.551374E+09 | 0.380758E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130814E+10 | 20785050.35 |
September | 0.524810E+09 | 0.361234E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106801E+10 | 17981215.34 |
October | 0.537120E+09 | 0.372206E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114692E+10 | 25611908.15 |
November | 0.518979E+09 | 0.361234E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671445E+09 | 58512264.47 |
December | 0.536472E+09 | 0.370068E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442422E+09 | 91097960.73 |
Annual Sum or Average | 0.638324E+10 | 0.441105E+11 | 0.104207E+11 | 0.932419E+10 | 0.749239E+09 | ||||
Minimum of Months | 0.487879E+09 | 0.337152E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318134E+09 | 17981215.34 |
Maximum of Months | 0.551374E+09 | 0.380758E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130814E+10 | 0.175709E+09 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.372206E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318147E+09 | 0.173480E+09 |
February | 0.487879E+09 | 0.337152E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344645E+09 | 90462521.53 |
March | 0.551374E+09 | 0.380758E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521222E+09 | 84409519.41 |
April | 0.524810E+09 | 0.361234E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566526E+09 | 76206596.55 |
May | 0.544247E+09 | 0.376482E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.890021E+09 | 40581595.22 |
June | 0.532585E+09 | 0.367648E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862548E+09 | 30962620.69 |
July | 0.536472E+09 | 0.370068E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118514E+10 | 23361975.14 |
August | 0.551374E+09 | 0.380758E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130845E+10 | 18530223.47 |
September | 0.524810E+09 | 0.361234E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106850E+10 | 15827420.40 |
October | 0.537120E+09 | 0.372206E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114726E+10 | 24036652.47 |
November | 0.518979E+09 | 0.361234E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671522E+09 | 56183954.56 |
December | 0.536472E+09 | 0.370068E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442451E+09 | 88701596.22 |
Annual Sum or Average | 0.638324E+10 | 0.441105E+11 | 0.104207E+11 | 0.932643E+10 | 0.722745E+09 | ||||
Minimum of Months | 0.487879E+09 | 0.337152E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318147E+09 | 15827420.40 |
Maximum of Months | 0.551374E+09 | 0.380758E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130845E+10 | 0.173480E+09 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.183632E+10 | 0.422804E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558418E+09 | 0.318683E+09 |
February | 0.167188E+10 | 0.383070E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604856E+09 | 0.168086E+09 |
March | 0.189386E+10 | 0.433280E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.915496E+09 | 0.159301E+09 |
April | 0.180380E+10 | 0.410432E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.995497E+09 | 0.143598E+09 |
May | 0.186509E+10 | 0.428042E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156418E+10 | 75276868.53 |
June | 0.182945E+10 | 0.418290E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151697E+10 | 53293932.51 |
July | 0.183943E+10 | 0.420185E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208472E+10 | 38334640.11 |
August | 0.189386E+10 | 0.433280E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230200E+10 | 30639523.10 |
September | 0.180380E+10 | 0.410432E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188151E+10 | 25496102.50 |
October | 0.183632E+10 | 0.422804E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201652E+10 | 44135015.88 |
November | 0.176881E+10 | 0.410432E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117968E+10 | 0.103529E+09 |
December | 0.183943E+10 | 0.420185E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776302E+09 | 0.165358E+09 |
Annual Sum or Average | 0.218821E+11 | 0.501324E+11 | 0.191729E+11 | 0.163962E+11 | 0.132573E+10 | ||||
Minimum of Months | 0.167188E+10 | 0.383070E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558418E+09 | 25496102.50 |
Maximum of Months | 0.189386E+10 | 0.433280E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230200E+10 | 0.318683E+09 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.211402E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318247E+09 | 0.170754E+09 |
February | 0.835938E+09 | 0.191535E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344742E+09 | 88115363.76 |
March | 0.946926E+09 | 0.216640E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521565E+09 | 81478727.95 |
April | 0.901896E+09 | 0.205216E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567013E+09 | 72837108.47 |
May | 0.932542E+09 | 0.214021E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.890941E+09 | 36856413.18 |
June | 0.914724E+09 | 0.209145E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.863308E+09 | 25038562.62 |
July | 0.919713E+09 | 0.210092E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118675E+10 | 17524100.43 |
August | 0.946926E+09 | 0.216640E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131055E+10 | 14082763.41 |
September | 0.901896E+09 | 0.205216E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107109E+10 | 11502434.75 |
October | 0.918158E+09 | 0.211402E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114916E+10 | 21477736.30 |
November | 0.884402E+09 | 0.205216E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671297E+09 | 51664746.96 |
December | 0.919713E+09 | 0.210092E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442291E+09 | 85185016.79 |
Annual Sum or Average | 0.109410E+11 | 0.250662E+11 | 0.958644E+10 | 0.933696E+10 | 0.676517E+09 | ||||
Minimum of Months | 0.835938E+09 | 0.191535E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318247E+09 | 11502434.75 |
Maximum of Months | 0.946926E+09 | 0.216640E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131055E+10 | 0.170754E+09 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.211402E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318255E+09 | 0.170148E+09 |
February | 0.835938E+09 | 0.191535E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344749E+09 | 87613993.83 |
March | 0.946926E+09 | 0.216640E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521587E+09 | 80955211.36 |
April | 0.901896E+09 | 0.205216E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567047E+09 | 72293359.21 |
May | 0.932542E+09 | 0.214021E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.891010E+09 | 36433084.79 |
June | 0.914724E+09 | 0.209145E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.863422E+09 | 24538927.40 |
July | 0.919713E+09 | 0.210092E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118697E+10 | 17051817.82 |
August | 0.946926E+09 | 0.216640E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131071E+10 | 13756133.80 |
September | 0.901896E+09 | 0.205216E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107133E+10 | 11167212.34 |
October | 0.918158E+09 | 0.211402E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114931E+10 | 21187546.00 |
November | 0.884402E+09 | 0.205216E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671343E+09 | 51100226.03 |
December | 0.919713E+09 | 0.210092E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442314E+09 | 84548160.18 |
Annual Sum or Average | 0.109410E+11 | 0.250662E+11 | 0.958644E+10 | 0.933805E+10 | 0.670794E+09 | ||||
Minimum of Months | 0.835938E+09 | 0.191535E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318255E+09 | 11167212.34 |
Maximum of Months | 0.946926E+09 | 0.216640E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131071E+10 | 0.170148E+09 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.211402E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318260E+09 | 0.168632E+09 |
February | 0.835938E+09 | 0.191535E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344758E+09 | 86313850.89 |
March | 0.946926E+09 | 0.216640E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521610E+09 | 79680178.00 |
April | 0.901896E+09 | 0.205216E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567070E+09 | 71038880.63 |
May | 0.932542E+09 | 0.214021E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.891051E+09 | 35574529.03 |
June | 0.914724E+09 | 0.209145E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.863526E+09 | 23481719.60 |
July | 0.919713E+09 | 0.210092E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118714E+10 | 16202667.63 |
August | 0.946926E+09 | 0.216640E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131079E+10 | 13224741.73 |
September | 0.901896E+09 | 0.205216E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107144E+10 | 10588717.39 |
October | 0.918158E+09 | 0.211402E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114939E+10 | 20734355.42 |
November | 0.884402E+09 | 0.205216E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671415E+09 | 49845908.19 |
December | 0.919713E+09 | 0.210092E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442371E+09 | 83100245.63 |
Annual Sum or Average | 0.109410E+11 | 0.250662E+11 | 0.958644E+10 | 0.933882E+10 | 0.658418E+09 | ||||
Minimum of Months | 0.835938E+09 | 0.191535E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318260E+09 | 10588717.39 |
Maximum of Months | 0.946926E+09 | 0.216640E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131079E+10 | 0.168632E+09 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.211402E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328078E+09 | 0.261882E+09 |
February | 0.835938E+09 | 0.191535E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355086E+09 | 0.149378E+09 |
March | 0.946926E+09 | 0.216640E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539789E+09 | 0.156711E+09 |
April | 0.901896E+09 | 0.205216E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588143E+09 | 0.144406E+09 |
May | 0.932542E+09 | 0.214021E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.924838E+09 | 82259981.30 |
June | 0.914724E+09 | 0.209145E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905760E+09 | 59367537.50 |
July | 0.919713E+09 | 0.210092E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124345E+10 | 44613302.27 |
August | 0.946926E+09 | 0.216640E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137033E+10 | 37264317.60 |
September | 0.901896E+09 | 0.205216E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112368E+10 | 29770552.56 |
October | 0.918158E+09 | 0.211402E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118980E+10 | 49513682.31 |
November | 0.884402E+09 | 0.205216E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703182E+09 | 0.104390E+09 |
December | 0.919713E+09 | 0.210092E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457742E+09 | 0.153939E+09 |
Annual Sum or Average | 0.109410E+11 | 0.250662E+11 | 0.958644E+10 | 0.972988E+10 | 0.127350E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.191535E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328078E+09 | 29770552.56 |
Maximum of Months | 0.946926E+09 | 0.216640E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137033E+10 | 0.261882E+09 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2159.72 | 01-JAN-13:09 | 5587.06 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2595.01 | 06-JAN-13:00 | 2205.20 | 25-JAN-12:10 |
February | 2159.72 | 03-FEB-13:09 | 5587.06 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2357.71 | 25-FEB-13:00 | 1074.70 | 06-FEB-18:00 |
March | 2159.72 | 03-MAR-13:09 | 5587.06 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2913.11 | 29-MAR-13:00 | 815.96 | 03-MAR-15:00 |
April | 2159.72 | 01-APR-12:09 | 5587.06 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2928.07 | 09-APR-14:00 | 825.50 | 11-APR-14:00 |
May | 2159.72 | 05-MAY-12:09 | 5587.06 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3458.51 | 17-MAY-13:00 | 285.12 | 15-MAY-17:00 |
June | 2159.72 | 02-JUN-12:09 | 5587.06 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3240.11 | 29-JUN-11:10 | 191.95 | 13-JUN-05:00 |
July | 2159.72 | 01-JUL-12:09 | 5587.06 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3937.60 | 09-JUL-12:00 | 196.47 | 13-JUL-06:00 |
August | 2159.72 | 04-AUG-12:09 | 5587.06 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4201.03 | 11-AUG-14:00 | 158.64 | 13-AUG-03:00 |
September | 2159.72 | 01-SEP-12:09 | 5587.06 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4517.85 | 03-SEP-13:00 | 166.39 | 30-SEP-06:00 |
October | 2159.72 | 01-OCT-12:09 | 5587.06 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4429.08 | 01-OCT-13:00 | 284.13 | 19-OCT-07:03 |
November | 2159.72 | 03-NOV-12:09 | 5587.06 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3261.31 | 04-NOV-13:00 | 1082.39 | 25-NOV-18:00 |
December | 2159.72 | 01-DEC-13:09 | 5587.06 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3178.60 | 13-DEC-14:00 | 1005.39 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2159.72 | 5587.06 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2357.71 | 158.64 | |||||
Maximum of Months | 2159.72 | 5587.06 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4517.85 | 2205.20 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 01-JAN-13:09 | 3268.27 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1463.01 | 03-JAN-14:00 | 1242.68 | 25-JAN-12:10 |
February | 1079.86 | 03-FEB-13:09 | 3268.27 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.18 | 25-FEB-13:00 | 602.31 | 06-FEB-18:00 |
March | 1079.86 | 03-MAR-13:09 | 3268.27 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.07 | 29-MAR-13:00 | 457.93 | 03-MAR-15:00 |
April | 1079.86 | 01-APR-12:09 | 3268.27 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1635.94 | 09-APR-14:00 | 464.04 | 11-APR-14:00 |
May | 1079.86 | 05-MAY-12:09 | 3268.27 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1926.43 | 17-MAY-13:00 | 161.08 | 15-MAY-17:00 |
June | 1079.86 | 02-JUN-12:09 | 3268.27 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1801.51 | 29-JUN-11:20 | 58.64 | 13-JUN-05:00 |
July | 1079.86 | 01-JUL-12:09 | 3268.27 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2206.79 | 09-JUL-12:00 | 59.51 | 13-JUL-06:00 |
August | 1079.86 | 04-AUG-12:09 | 3268.27 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2354.41 | 11-AUG-14:00 | 82.40 | 26-AUG-07:02 |
September | 1079.86 | 01-SEP-12:09 | 3268.27 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.18 | 03-SEP-13:00 | 63.10 | 19-SEP-07:02 |
October | 1079.86 | 01-OCT-12:09 | 3268.27 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2482.22 | 01-OCT-13:00 | 154.80 | 19-OCT-07:03 |
November | 1079.86 | 03-NOV-12:09 | 3268.27 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1807.88 | 04-NOV-13:00 | 603.81 | 25-NOV-18:00 |
December | 1079.86 | 01-DEC-13:09 | 3268.27 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1784.18 | 13-DEC-14:00 | 568.92 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3268.27 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.18 | 58.64 | |||||
Maximum of Months | 1079.86 | 3268.27 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.18 | 1242.68 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3006.97 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1462.99 | 03-JAN-14:00 | 1242.68 | 25-JAN-12:10 |
February | 1079.86 | 04-FEB-13:09 | 3006.97 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.20 | 25-FEB-13:00 | 757.10 | 12-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3006.97 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.03 | 29-MAR-13:00 | 686.07 | 05-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 3006.97 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1635.94 | 09-APR-14:00 | 464.07 | 11-APR-14:00 |
May | 1079.86 | 06-MAY-12:09 | 3006.97 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1926.52 | 17-MAY-13:00 | 570.52 | 14-MAY-17:00 |
June | 1079.86 | 03-JUN-12:09 | 3006.97 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1801.53 | 29-JUN-11:10 | 76.17 | 03-JUN-19:00 |
July | 1079.86 | 01-JUL-12:09 | 3006.97 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2206.77 | 09-JUL-12:00 | 76.49 | 22-JUL-18:10 |
August | 1079.86 | 05-AUG-12:09 | 3006.97 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2354.36 | 11-AUG-14:00 | 80.54 | 06-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 3006.97 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.12 | 03-SEP-13:00 | 74.31 | 30-SEP-18:10 |
October | 1079.86 | 07-OCT-12:09 | 3006.97 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2482.16 | 01-OCT-13:00 | 529.00 | 22-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 3006.97 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1807.86 | 04-NOV-13:00 | 732.70 | 26-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3006.97 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1784.15 | 13-DEC-14:00 | 919.25 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3006.97 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.20 | 74.31 | |||||
Maximum of Months | 1079.86 | 3006.97 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.12 | 1242.68 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3006.97 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1462.99 | 03-JAN-14:00 | 1242.68 | 25-JAN-12:10 |
February | 1079.86 | 04-FEB-13:09 | 3006.97 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.20 | 25-FEB-13:00 | 753.12 | 12-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3006.97 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.04 | 29-MAR-13:00 | 683.67 | 05-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 3006.97 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1635.95 | 09-APR-14:00 | 464.07 | 11-APR-14:00 |
May | 1079.86 | 06-MAY-12:09 | 3006.97 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1926.50 | 17-MAY-13:00 | 571.91 | 14-MAY-17:00 |
June | 1079.86 | 03-JUN-12:09 | 3006.97 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1801.51 | 29-JUN-11:10 | 77.45 | 03-JUN-19:00 |
July | 1079.86 | 01-JUL-12:09 | 3006.97 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2206.77 | 09-JUL-12:00 | 77.16 | 22-JUL-18:10 |
August | 1079.86 | 05-AUG-12:09 | 3006.97 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2354.36 | 11-AUG-14:00 | 84.51 | 06-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 3006.97 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.13 | 03-SEP-13:00 | 75.22 | 30-SEP-18:10 |
October | 1079.86 | 07-OCT-12:09 | 3006.97 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2482.16 | 01-OCT-13:00 | 530.19 | 22-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 3006.97 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1807.86 | 04-NOV-13:00 | 729.89 | 26-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3006.97 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1784.15 | 13-DEC-14:00 | 916.32 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3006.97 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.20 | 75.22 | |||||
Maximum of Months | 1079.86 | 3006.97 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.13 | 1242.68 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3006.97 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1462.62 | 03-JAN-14:00 | 1242.68 | 25-JAN-12:10 |
February | 1079.86 | 04-FEB-13:09 | 3006.97 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.19 | 25-FEB-13:00 | 736.28 | 12-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3006.97 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.00 | 29-MAR-13:00 | 667.93 | 05-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 3006.97 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1635.92 | 09-APR-14:00 | 464.09 | 11-APR-14:00 |
May | 1079.86 | 06-MAY-12:09 | 3006.97 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1926.53 | 17-MAY-13:00 | 557.98 | 14-MAY-17:00 |
June | 1079.86 | 03-JUN-12:09 | 3006.97 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1801.58 | 29-JUN-11:10 | 72.21 | 03-JUN-19:00 |
July | 1079.86 | 01-JUL-12:09 | 3006.97 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2206.77 | 09-JUL-12:00 | 73.04 | 22-JUL-18:10 |
August | 1079.86 | 05-AUG-12:09 | 3006.97 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2354.35 | 11-AUG-14:00 | 70.98 | 06-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 3006.97 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.12 | 03-SEP-13:00 | 70.52 | 30-SEP-18:10 |
October | 1079.86 | 07-OCT-12:09 | 3006.97 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2482.15 | 01-OCT-13:00 | 516.25 | 22-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 3006.97 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1807.85 | 04-NOV-13:00 | 714.10 | 26-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3006.97 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1784.14 | 13-DEC-14:00 | 900.28 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3006.97 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.19 | 70.52 | |||||
Maximum of Months | 1079.86 | 3006.97 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.12 | 1242.68 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2879.63 | 07-JAN-15:09 | 3712.57 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2564.36 | 03-JAN-14:00 | 2178.50 | 25-JAN-12:10 |
February | 2879.63 | 04-FEB-15:09 | 3712.57 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2334.55 | 25-FEB-13:00 | 1186.85 | 12-FEB-18:00 |
March | 2879.63 | 04-MAR-15:09 | 3712.57 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2860.62 | 29-MAR-13:00 | 1077.10 | 05-MAR-18:00 |
April | 2879.63 | 01-APR-14:09 | 3712.57 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2871.60 | 09-APR-14:00 | 813.93 | 11-APR-14:00 |
May | 2879.63 | 06-MAY-14:09 | 3712.57 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3383.02 | 17-MAY-13:00 | 904.28 | 14-MAY-17:00 |
June | 2879.63 | 03-JUN-14:09 | 3712.57 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3164.48 | 29-JUN-11:10 | 132.30 | 08-JUN-23:00 |
July | 2879.63 | 01-JUL-14:09 | 3712.57 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3871.65 | 09-JUL-12:00 | 112.88 | 22-JUL-18:10 |
August | 2879.63 | 05-AUG-14:09 | 3712.57 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4130.64 | 11-AUG-14:00 | 170.75 | 06-AUG-07:10 |
September | 2879.63 | 02-SEP-14:09 | 3712.57 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4406.48 | 03-SEP-13:00 | 121.98 | 18-SEP-07:02 |
October | 2879.63 | 07-OCT-14:09 | 3712.57 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4354.84 | 01-OCT-13:00 | 826.71 | 22-OCT-17:00 |
November | 2879.63 | 04-NOV-14:09 | 3712.57 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3176.93 | 04-NOV-13:00 | 1159.01 | 26-NOV-18:00 |
December | 2879.63 | 02-DEC-15:09 | 3712.57 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3129.58 | 13-DEC-14:00 | 1475.25 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2879.63 | 3712.57 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2334.55 | 112.88 | |||||
Maximum of Months | 2879.63 | 3712.57 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4406.48 | 2178.50 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 1856.29 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1463.04 | 03-JAN-14:00 | 1242.68 | 25-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 1856.29 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.24 | 25-FEB-13:00 | 660.34 | 12-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 1856.29 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.11 | 29-MAR-13:00 | 596.41 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 1856.29 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1636.00 | 09-APR-14:00 | 464.12 | 11-APR-14:00 |
May | 1439.81 | 06-MAY-14:09 | 1856.29 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1926.49 | 17-MAY-13:00 | 497.58 | 14-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 1856.29 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1801.57 | 29-JUN-11:20 | 64.38 | 08-JUN-23:00 |
July | 1439.81 | 01-JUL-14:09 | 1856.29 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2206.77 | 09-JUL-12:00 | 55.20 | 22-JUL-18:10 |
August | 1439.81 | 05-AUG-14:09 | 1856.29 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2354.38 | 11-AUG-14:00 | 90.79 | 06-AUG-07:03 |
September | 1439.81 | 02-SEP-14:09 | 1856.29 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.14 | 03-SEP-13:00 | 67.37 | 18-SEP-07:02 |
October | 1439.81 | 07-OCT-14:09 | 1856.29 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2482.17 | 01-OCT-13:00 | 451.97 | 22-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 1856.29 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1807.87 | 04-NOV-13:00 | 640.59 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 1856.29 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1784.20 | 13-DEC-14:00 | 822.99 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.24 | 55.20 | |||||
Maximum of Months | 1439.81 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.14 | 1242.68 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 1856.29 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1463.04 | 03-JAN-14:00 | 1242.68 | 25-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 1856.29 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.24 | 25-FEB-13:00 | 654.62 | 12-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 1856.29 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.11 | 29-MAR-13:00 | 591.56 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 1856.29 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1635.99 | 09-APR-14:00 | 464.12 | 11-APR-14:00 |
May | 1439.81 | 06-MAY-14:09 | 1856.29 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1926.49 | 17-MAY-13:00 | 494.31 | 14-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 1856.29 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1801.57 | 29-JUN-11:20 | 63.94 | 08-JUN-23:00 |
July | 1439.81 | 01-JUL-14:09 | 1856.29 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2206.77 | 09-JUL-12:00 | 54.00 | 22-JUL-18:10 |
August | 1439.81 | 05-AUG-14:09 | 1856.29 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2354.38 | 11-AUG-14:00 | 89.56 | 06-AUG-07:03 |
September | 1439.81 | 02-SEP-14:09 | 1856.29 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.14 | 03-SEP-13:00 | 66.58 | 18-SEP-07:02 |
October | 1439.81 | 07-OCT-14:09 | 1856.29 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2482.17 | 01-OCT-13:00 | 448.32 | 22-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 1856.29 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1807.87 | 04-NOV-13:00 | 635.85 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 1856.29 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1784.20 | 13-DEC-14:00 | 817.84 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.24 | 54.00 | |||||
Maximum of Months | 1439.81 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.14 | 1242.68 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 1856.29 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1463.04 | 03-JAN-14:00 | 1242.68 | 25-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 1856.29 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.24 | 25-FEB-13:00 | 644.24 | 12-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 1856.29 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.10 | 29-MAR-13:00 | 585.91 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 1856.29 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1635.99 | 09-APR-14:00 | 464.12 | 11-APR-14:00 |
May | 1439.81 | 06-MAY-14:09 | 1856.29 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1926.49 | 17-MAY-13:00 | 490.59 | 14-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 1856.29 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1801.83 | 29-JUN-11:10 | 63.13 | 08-JUN-23:00 |
July | 1439.81 | 01-JUL-14:09 | 1856.29 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2206.78 | 09-JUL-12:00 | 53.43 | 22-JUL-18:10 |
August | 1439.81 | 05-AUG-14:09 | 1856.29 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2354.38 | 11-AUG-14:00 | 87.16 | 06-AUG-07:02 |
September | 1439.81 | 02-SEP-14:09 | 1856.29 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.14 | 03-SEP-13:00 | 64.95 | 18-SEP-07:02 |
October | 1439.81 | 07-OCT-14:09 | 1856.29 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2482.17 | 01-OCT-13:00 | 445.60 | 22-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 1856.29 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1807.87 | 04-NOV-13:00 | 628.92 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 1856.29 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1784.20 | 13-DEC-14:00 | 811.92 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.24 | 53.43 | |||||
Maximum of Months | 1439.81 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.14 | 1242.68 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 1856.29 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1494.07 | 06-JAN-13:00 | 1269.32 | 25-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 1856.29 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1355.55 | 25-FEB-13:00 | 681.64 | 12-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 1856.29 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1682.55 | 29-MAR-13:00 | 652.39 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 1856.29 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1692.49 | 09-APR-14:00 | 475.74 | 11-APR-14:00 |
May | 1439.81 | 06-MAY-14:09 | 1856.29 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2002.38 | 17-MAY-13:00 | 574.89 | 14-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 1856.29 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1877.50 | 29-JUN-11:10 | 155.18 | 08-JUN-23:00 |
July | 1439.81 | 01-JUL-14:09 | 1856.29 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2272.68 | 09-JUL-12:00 | 121.05 | 13-JUL-06:00 |
August | 1439.81 | 05-AUG-14:09 | 1856.29 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2424.63 | 11-AUG-14:00 | 124.80 | 06-AUG-07:10 |
September | 1439.81 | 02-SEP-14:09 | 1856.29 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2619.30 | 03-SEP-13:00 | 114.12 | 29-SEP-22:00 |
October | 1439.81 | 07-OCT-14:09 | 1856.29 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2556.23 | 01-OCT-13:00 | 533.70 | 22-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 1856.29 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1892.15 | 04-NOV-13:00 | 674.90 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 1856.29 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1833.20 | 13-DEC-14:00 | 854.35 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1355.55 | 114.12 | |||||
Maximum of Months | 1439.81 | 1856.29 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2619.30 | 1269.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 30134.77 | 12-JAN-08:62 | 899.88 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.94 |
February | 26575.06 | 13-FEB-08:62 | 719.91 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.85 |
March | 29470.39 | 19-MAR-07:02 | 899.88 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.21 |
April | 28316.12 | 06-APR-07:03 | 719.91 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.38 |
May | 28667.56 | 22-MAY-07:02 | 899.88 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.66 |
June | 28328.92 | 04-JUN-07:02 | 1079.86 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.28 |
July | 26990.36 | 08-JUL-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 44.85 | 0.00 |
August | 27484.54 | 24-AUG-07:02 | 899.88 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.78 |
September | 27519.05 | 18-SEP-07:02 | 1079.86 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.55 |
October | 28240.23 | 26-OCT-07:03 | 719.91 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.85 |
November | 29049.62 | 15-NOV-08:62 | 1079.86 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.73 |
December | 32816.27 | 20-DEC-08:62 | 899.88 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.38 |
Annual Sum or Average | |||||||||||
Minimum of Months | 26575.06 | 0.00 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32816.27 | 1079.86 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 44.85 | 262.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17094.40 | 22-JAN-08:62 | 359.95 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.25 |
February | 15573.21 | 04-FEB-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.32 |
March | 16697.97 | 19-MAR-07:02 | 449.94 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.49 |
April | 16471.41 | 06-APR-07:03 | 359.95 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.40 |
May | 16503.39 | 22-MAY-07:02 | 449.94 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.16 |
June | 16097.01 | 04-JUN-07:02 | 539.93 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 |
July | 15472.06 | 08-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.96 | 0.00 |
August | 15716.56 | 24-AUG-07:02 | 449.94 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.55 |
September | 15863.97 | 18-SEP-07:02 | 539.93 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.79 |
October | 16146.12 | 26-OCT-07:03 | 359.95 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.80 |
November | 16923.96 | 26-NOV-08:62 | 359.95 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.03 |
December | 17969.44 | 25-DEC-08:62 | 449.94 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.47 |
Annual Sum or Average | |||||||||||
Minimum of Months | 15472.06 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17969.44 | 539.93 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 24.96 | 143.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16637.66 | 22-JAN-08:62 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.55 |
February | 14751.08 | 13-FEB-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.55 |
March | 15609.32 | 19-MAR-07:02 | 0.00 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.18 |
April | 16099.31 | 30-APR-07:03 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.05 |
May | 15751.37 | 31-MAY-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.72 |
June | 15024.38 | 04-JUN-07:02 | 0.00 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.52 |
July | 14347.56 | 04-JUL-07:02 | 0.00 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 | 0.00 |
August | 14644.28 | 24-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.25 |
September | 14653.36 | 19-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 |
October | 14962.39 | 18-OCT-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.43 |
November | 15875.70 | 09-NOV-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.21 |
December | 17673.96 | 25-DEC-08:62 | 0.00 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.75 |
Annual Sum or Average | |||||||||||
Minimum of Months | 14347.56 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17673.96 | 0.00 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 | 144.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16520.90 | 22-JAN-08:62 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.80 |
February | 14636.73 | 13-FEB-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.39 |
March | 15528.72 | 19-MAR-07:02 | 0.00 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.98 |
April | 15834.30 | 06-APR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.42 |
May | 15661.32 | 31-MAY-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.78 |
June | 14940.06 | 04-JUN-07:02 | 0.00 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 |
July | 14288.73 | 04-JUL-07:02 | 0.00 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 | 0.00 |
August | 14571.04 | 24-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.30 |
September | 14588.06 | 19-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 |
October | 14887.38 | 18-OCT-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.47 |
November | 15787.22 | 09-NOV-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.23 |
December | 17557.10 | 25-DEC-08:62 | 0.00 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.33 |
Annual Sum or Average | |||||||||||
Minimum of Months | 14288.73 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17557.10 | 0.00 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 | 143.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15951.10 | 22-JAN-08:62 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.39 |
February | 14478.76 | 13-FEB-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.66 |
March | 15428.64 | 19-MAR-07:02 | 0.00 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.51 |
April | 15244.06 | 06-APR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 |
May | 15305.46 | 31-MAY-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.29 |
June | 14825.83 | 04-JUN-07:02 | 0.00 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 |
July | 14173.29 | 04-JUL-07:02 | 0.00 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 | 0.00 |
August | 14454.49 | 24-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 |
September | 14477.72 | 19-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 |
October | 14774.01 | 18-OCT-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.27 |
November | 15676.17 | 09-NOV-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.09 |
December | 17456.29 | 25-DEC-08:62 | 0.00 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.78 |
Annual Sum or Average | |||||||||||
Minimum of Months | 14173.29 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17456.29 | 0.00 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 | 140.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28411.83 | 12-JAN-08:62 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.57 |
February | 24609.39 | 13-FEB-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.49 |
March | 26016.00 | 19-MAR-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.43 |
April | 25632.78 | 07-APR-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.21 |
May | 26898.75 | 31-MAY-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.31 |
June | 25035.70 | 06-JUN-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.22 |
July | 25241.56 | 18-JUL-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 78.91 | 0.00 |
August | 25314.46 | 24-AUG-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.82 |
September | 25693.80 | 19-SEP-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.84 |
October | 25525.25 | 26-OCT-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.51 |
November | 27144.43 | 09-NOV-08:62 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.14 |
December | 30879.07 | 20-DEC-08:62 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.10 |
Annual Sum or Average | |||||||||||
Minimum of Months | 24609.39 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30879.07 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 78.91 | 236.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14729.92 | 12-JAN-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.94 |
February | 12507.97 | 13-FEB-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 | 0.00 |
March | 13452.52 | 19-MAR-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.51 |
April | 13266.93 | 07-APR-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.84 |
May | 13460.08 | 31-MAY-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.89 |
June | 12971.29 | 06-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.89 |
July | 13075.65 | 18-JUL-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 47.78 | 0.00 |
August | 13112.29 | 24-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.37 |
September | 13327.93 | 19-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.91 |
October | 13214.60 | 26-OCT-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.11 |
November | 14059.42 | 09-NOV-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.75 |
December | 15994.83 | 20-DEC-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.06 |
Annual Sum or Average | |||||||||||
Minimum of Months | 12507.97 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15994.83 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 47.78 | 128.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14632.75 | 12-JAN-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.75 |
February | 12017.47 | 13-FEB-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1.01 | 0.00 |
March | 13370.83 | 19-MAR-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.50 |
April | 13127.34 | 11-APR-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.48 |
May | 13290.70 | 23-MAY-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.29 |
June | 12883.44 | 06-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.13 |
July | 12995.03 | 18-JUL-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 48.50 | 0.00 |
August | 13024.83 | 24-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.51 |
September | 13238.70 | 19-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.16 |
October | 13083.27 | 18-OCT-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.90 |
November | 13962.47 | 09-NOV-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.74 |
December | 15894.21 | 20-DEC-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.88 |
Annual Sum or Average | |||||||||||
Minimum of Months | 12017.47 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15894.21 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 48.50 | 126.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14569.28 | 12-JAN-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.50 |
February | 11587.20 | 05-FEB-09:02 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 23.93 | 0.00 |
March | 13327.92 | 19-MAR-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.43 |
April | 12627.93 | 10-APR-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.71 |
May | 13060.67 | 27-MAY-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.03 |
June | 12833.99 | 06-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 |
July | 12952.91 | 18-JUL-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 51.38 | 0.00 |
August | 13003.10 | 24-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.70 |
September | 13210.31 | 19-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.98 |
October | 13002.40 | 17-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.02 |
November | 13906.43 | 09-NOV-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.40 |
December | 15831.51 | 20-DEC-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.38 |
Annual Sum or Average | |||||||||||
Minimum of Months | 11587.20 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15831.51 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 51.38 | 122.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13456.98 | 04-JAN-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.26 |
February | 11177.34 | 26-FEB-09:02 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 0.00 |
March | 13000.29 | 14-MAR-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.29 |
April | 13697.47 | 10-APR-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.67 |
May | 13957.41 | 30-MAY-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 6.26 | 0.00 |
June | 14238.91 | 04-JUN-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.60 |
July | 13856.89 | 04-JUL-08:61 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 91.25 | 0.00 |
August | 13616.28 | 24-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.44 |
September | 13998.64 | 19-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.25 |
October | 13824.16 | 27-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.76 |
November | 15203.23 | 15-NOV-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.24 |
December | 16771.63 | 24-DEC-09:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.72 |
Annual Sum or Average | |||||||||||
Minimum of Months | 11177.34 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16771.63 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 91.25 | 90.26 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.950739E+11 | 93750.04 | 04-JAN-13:50 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.893279E+11 | 92210.75 | 20-FEB-15:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.983431E+11 | 88268.68 | 13-MAR-15:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.935122E+11 | 85172.02 | 24-APR-13:50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.104398E+12 | 94748.65 | 13-MAY-13:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.103009E+12 | 88918.13 | 29-JUN-12:39 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.111370E+12 | 98088.94 | 15-JUL-13:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.114904E+12 | 102756.70 | 19-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.110505E+12 | 105068.84 | 03-SEP-14:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.113129E+12 | 99886.65 | 15-OCT-13:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.102576E+12 | 96413.55 | 06-NOV-13:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.100560E+12 | 91714.00 | 13-DEC-13:39 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.123671E+13 | 0.00 | ||||
Minimum of Months | 0.893279E+11 | 85172.02 | 0.00 | 0.00 | ||
Maximum of Months | 0.114904E+12 | 105068.84 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.381118E+11 | 0.575607E+10 | 0.108325E+11 | 0.00 | 0.743333E+10 | 0.00 | 0.00 | 0.279227E+11 | 0.00 | 0.00 | 0.00 | 0.501756E+10 | 0.00 |
February | 0.345095E+11 | 0.495506E+10 | 0.980803E+10 | 0.00 | 0.682569E+10 | 0.00 | 0.00 | 0.286975E+11 | 0.00 | 0.00 | 0.00 | 0.453216E+10 | 0.00 |
March | 0.387104E+11 | 0.513047E+10 | 0.110038E+11 | 0.00 | 0.755659E+10 | 0.00 | 0.00 | 0.309118E+11 | 0.00 | 0.00 | 0.00 | 0.503006E+10 | 0.00 |
April | 0.369865E+11 | 0.459379E+10 | 0.105115E+11 | 0.00 | 0.717509E+10 | 0.00 | 0.00 | 0.294276E+11 | 0.00 | 0.00 | 0.00 | 0.481775E+10 | 0.00 |
May | 0.383972E+11 | 0.444263E+10 | 0.109147E+11 | 0.00 | 0.765030E+10 | 0.00 | 0.00 | 0.380363E+11 | 0.00 | 0.00 | 0.00 | 0.495729E+10 | 0.00 |
June | 0.374142E+11 | 0.415489E+10 | 0.106349E+11 | 0.00 | 0.749405E+10 | 0.00 | 0.00 | 0.385210E+11 | 0.00 | 0.00 | 0.00 | 0.478949E+10 | 0.00 |
July | 0.379970E+11 | 0.433454E+10 | 0.107982E+11 | 0.00 | 0.826920E+10 | 0.00 | 0.00 | 0.450652E+11 | 0.00 | 0.00 | 0.00 | 0.490636E+10 | 0.00 |
August | 0.386827E+11 | 0.461623E+10 | 0.109970E+11 | 0.00 | 0.860663E+10 | 0.00 | 0.00 | 0.470547E+11 | 0.00 | 0.00 | 0.00 | 0.494711E+10 | 0.00 |
September | 0.370138E+11 | 0.481324E+10 | 0.105184E+11 | 0.00 | 0.828414E+10 | 0.00 | 0.00 | 0.450946E+11 | 0.00 | 0.00 | 0.00 | 0.478079E+10 | 0.00 |
October | 0.381120E+11 | 0.533027E+10 | 0.108325E+11 | 0.00 | 0.848910E+10 | 0.00 | 0.00 | 0.454042E+11 | 0.00 | 0.00 | 0.00 | 0.496131E+10 | 0.00 |
November | 0.369307E+11 | 0.548470E+10 | 0.104978E+11 | 0.00 | 0.756873E+10 | 0.00 | 0.00 | 0.372651E+11 | 0.00 | 0.00 | 0.00 | 0.482925E+10 | 0.00 |
December | 0.380245E+11 | 0.584123E+10 | 0.108050E+11 | 0.00 | 0.754520E+10 | 0.00 | 0.00 | 0.333393E+11 | 0.00 | 0.00 | 0.00 | 0.500485E+10 | 0.00 |
Annual Sum or Average | 0.450890E+12 | 0.594531E+11 | 0.128154E+12 | 0.928980E+11 | 0.00 | 0.446740E+12 | 0.585740E+11 | ||||||
Minimum of Months | 0.345095E+11 | 0.415489E+10 | 0.980803E+10 | 0.00 | 0.682569E+10 | 0.00 | 0.00 | 0.279227E+11 | 0.00 | 0.00 | 0.00 | 0.453216E+10 | 0.00 |
Maximum of Months | 0.387104E+11 | 0.584123E+10 | 0.110038E+11 | 0.00 | 0.860663E+10 | 0.00 | 0.00 | 0.470547E+11 | 0.00 | 0.00 | 0.00 | 0.503006E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 29013.96 | 01-JAN-11:09 | 5459.01 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 6574.96 | 02-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 29013.96 | 01-FEB-10:09 | 5459.01 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 6901.78 | 19-FEB-13:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 29013.96 | 01-MAR-10:09 | 5459.01 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 6552.43 | 13-MAR-14:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 29013.96 | 01-APR-09:09 | 5459.01 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 6329.12 | 24-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 29013.96 | 01-MAY-09:09 | 5459.01 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 6825.88 | 10-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 29013.96 | 01-JUN-09:09 | 5459.01 | 01-JUN-05:10 | 8059.50 | 01-JUN-09:09 | 0.00 | 6839.00 | 21-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 29013.96 | 01-JUL-09:09 | 5459.01 | 01-JUL-05:10 | 8059.50 | 01-JUL-09:09 | 0.00 | 7823.87 | 15-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 29013.96 | 01-AUG-09:09 | 5459.01 | 01-AUG-05:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 8774.16 | 19-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 29013.96 | 01-SEP-09:09 | 5459.01 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 8916.68 | 03-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 29013.96 | 01-OCT-10:09 | 5459.01 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 8671.20 | 14-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 29013.96 | 01-NOV-09:09 | 5459.01 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 7670.67 | 06-NOV-13:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 29013.96 | 01-DEC-10:09 | 5459.01 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 6985.32 | 13-DEC-13:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 29013.96 | 5459.01 | 8059.50 | 0.00 | 6329.12 | 0.00 | 0.00 | |||||
Maximum of Months | 29013.96 | 5459.01 | 8059.50 | 0.00 | 8916.68 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 38875.77 | 04-JAN-13:00 | 0.00 | 0.00 | 0.00 | 11783.50 | 04-JAN-13:50 | 0.00 |
February | 41113.70 | 19-FEB-13:00 | 0.00 | 0.00 | 0.00 | 10313.08 | 02-FEB-13:30 | 0.00 |
March | 39585.53 | 13-MAR-14:09 | 0.00 | 0.00 | 0.00 | 9662.58 | 30-MAR-13:09 | 0.00 |
April | 36279.91 | 24-APR-13:00 | 0.00 | 0.00 | 0.00 | 9665.54 | 07-APR-12:30 | 0.00 |
May | 41350.11 | 13-MAY-13:00 | 0.00 | 0.00 | 0.00 | 9657.20 | 13-MAY-13:00 | 0.00 |
June | 40119.70 | 29-JUN-12:00 | 0.00 | 0.00 | 0.00 | 9656.05 | 12-JUN-13:30 | 0.00 |
July | 47025.42 | 15-JUL-13:00 | 0.00 | 0.00 | 0.00 | 8776.81 | 22-JUL-15:00 | 0.00 |
August | 51482.75 | 19-AUG-14:00 | 0.00 | 0.00 | 0.00 | 7544.10 | 09-AUG-13:30 | 0.00 |
September | 53058.25 | 03-SEP-12:00 | 0.00 | 0.00 | 0.00 | 7545.24 | 05-SEP-13:09 | 0.00 |
October | 51103.43 | 15-OCT-12:00 | 0.00 | 0.00 | 0.00 | 7550.05 | 19-OCT-12:30 | 0.00 |
November | 45523.81 | 06-NOV-13:00 | 0.00 | 0.00 | 0.00 | 11541.29 | 17-NOV-14:30 | 0.00 |
December | 42398.56 | 13-DEC-13:00 | 0.00 | 0.00 | 0.00 | 7932.49 | 07-DEC-20:00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 36279.91 | 0.00 | 0.00 | 0.00 | 7544.10 | 0.00 | ||
Maximum of Months | 53058.25 | 0.00 | 0.00 | 0.00 | 11783.50 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 93750.04 | 04-JAN-13:50 | 29013.96 | 8059.50 | 0.00 | 0.00 | 6324.20 | 0.00 | 0.00 | 38568.89 | 0.00 |
February | 92210.75 | 20-FEB-15:30 | 29013.96 | 8059.50 | 0.00 | 0.00 | 6662.73 | 0.00 | 0.00 | 39835.97 | 0.00 |
March | 88268.68 | 13-MAR-15:30 | 29013.96 | 8059.50 | 0.00 | 0.00 | 6459.87 | 0.00 | 0.00 | 39167.87 | 0.00 |
April | 85172.02 | 24-APR-13:50 | 29013.96 | 8059.50 | 0.00 | 0.00 | 5704.76 | 0.00 | 0.00 | 35992.96 | 0.00 |
May | 94748.65 | 13-MAY-13:00 | 29013.96 | 8059.50 | 0.00 | 0.00 | 6667.88 | 0.00 | 0.00 | 41350.11 | 0.00 |
June | 88918.13 | 29-JUN-12:39 | 29013.96 | 8059.50 | 0.00 | 0.00 | 6424.49 | 0.00 | 0.00 | 39985.97 | 0.00 |
July | 98088.94 | 15-JUL-13:20 | 29013.96 | 8059.50 | 0.00 | 0.00 | 7564.49 | 0.00 | 0.00 | 45597.51 | 0.00 |
August | 102756.70 | 19-AUG-14:00 | 29013.96 | 8059.50 | 0.00 | 0.00 | 8774.16 | 0.00 | 0.00 | 51482.75 | 0.00 |
September | 105068.84 | 03-SEP-14:30 | 29013.96 | 8059.50 | 0.00 | 0.00 | 8790.37 | 0.00 | 0.00 | 52287.64 | 0.00 |
October | 99886.65 | 15-OCT-13:30 | 29013.96 | 8059.50 | 0.00 | 0.00 | 8471.03 | 0.00 | 0.00 | 50168.75 | 0.00 |
November | 96413.55 | 06-NOV-13:30 | 29013.96 | 8059.50 | 0.00 | 0.00 | 7424.23 | 0.00 | 0.00 | 44364.34 | 0.00 |
December | 91714.00 | 13-DEC-13:39 | 29013.96 | 8059.50 | 0.00 | 0.00 | 6962.32 | 0.00 | 0.00 | 42238.70 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 85172.02 | 29013.96 | 8059.50 | 0.00 | 0.00 | 5704.76 | 0.00 | 0.00 | 35992.96 | 0.00 | |
Maximum of Months | 105068.84 | 29013.96 | 8059.50 | 0.00 | 0.00 | 8790.37 | 0.00 | 0.00 | 52287.64 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.50 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.48 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.67 | 24.49 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.50 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.47 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 24.47 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.47 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.47 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 24.47 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.47 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.46 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.75 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.51 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.51 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.83 | 24.56 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.75 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 23.87 | 464.17 | 23.89 | 0.33 | 23.96 |
February | 45.50 | 23.86 | 432.33 | 23.89 | 43.50 | 23.88 |
March | 15.33 | 23.85 | 474.17 | 23.89 | 13.17 | 23.89 |
April | 0.00 | 0.00 | 468.67 | 23.89 | 0.00 | 0.00 |
May | 3.50 | 23.91 | 495.00 | 23.89 | 3.50 | 23.91 |
June | 1.17 | 23.98 | 480.00 | 23.89 | 1.17 | 23.98 |
July | 13.67 | 23.93 | 496.00 | 23.89 | 13.67 | 23.93 |
August | 7.50 | 23.96 | 496.00 | 23.89 | 7.50 | 23.96 |
September | 23.67 | 23.91 | 480.00 | 23.89 | 23.67 | 23.91 |
October | 3.67 | 23.93 | 495.50 | 23.89 | 3.67 | 23.93 |
November | 5.50 | 23.94 | 479.33 | 23.89 | 5.50 | 23.94 |
December | 4.50 | 23.91 | 487.00 | 23.89 | 4.50 | 23.91 |
Annual Sum or Average | 124.67 | 23.89 | 5748.17 | 23.89 | 120.17 | 23.91 |
Minimum of Months | 0.00 | 0.00 | 432.33 | 23.89 | 0.00 | 0.00 |
Maximum of Months | 45.50 | 23.98 | 496.00 | 23.89 | 43.50 | 23.98 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 23.80 | 442.17 | 23.89 | 0.00 | 0.00 |
February | 28.33 | 23.87 | 416.83 | 23.89 | 26.83 | 23.89 |
March | 10.50 | 23.86 | 454.00 | 23.89 | 8.67 | 23.89 |
April | 0.00 | 0.00 | 444.00 | 23.89 | 0.00 | 0.00 |
May | 0.67 | 23.89 | 490.33 | 23.89 | 0.67 | 23.89 |
June | 0.00 | 0.00 | 479.67 | 23.89 | 0.00 | 0.00 |
July | 6.33 | 23.90 | 496.00 | 23.89 | 6.33 | 23.90 |
August | 0.00 | 0.00 | 496.00 | 23.89 | 0.00 | 0.00 |
September | 11.83 | 23.89 | 480.00 | 23.89 | 11.83 | 23.89 |
October | 0.83 | 23.89 | 494.50 | 23.89 | 0.83 | 23.89 |
November | 0.67 | 23.89 | 474.33 | 23.89 | 0.67 | 23.89 |
December | 2.17 | 23.91 | 477.67 | 23.89 | 2.17 | 23.91 |
Annual Sum or Average | 61.67 | 23.88 | 5645.50 | 23.89 | 58.00 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 416.83 | 23.89 | 0.00 | 0.00 |
Maximum of Months | 28.33 | 23.91 | 496.00 | 23.89 | 26.83 | 23.91 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 24.74 | 359.50 | 24.01 | 2.67 | 24.74 |
February | 51.17 | 24.18 | 329.50 | 24.01 | 50.83 | 24.19 |
March | 14.33 | 24.15 | 370.83 | 24.02 | 14.00 | 24.16 |
April | 1.50 | 24.93 | 357.50 | 24.02 | 1.50 | 24.93 |
May | 6.83 | 24.94 | 375.00 | 24.05 | 6.83 | 24.94 |
June | 1.17 | 27.46 | 366.00 | 24.05 | 1.17 | 27.46 |
July | 13.67 | 25.18 | 369.00 | 24.08 | 13.67 | 25.18 |
August | 7.50 | 26.02 | 379.00 | 24.07 | 7.50 | 26.02 |
September | 26.00 | 24.97 | 360.00 | 24.09 | 26.00 | 24.97 |
October | 12.17 | 25.36 | 371.00 | 24.07 | 12.17 | 25.36 |
November | 4.33 | 25.09 | 360.00 | 24.04 | 4.33 | 25.09 |
December | 6.67 | 24.91 | 368.33 | 24.02 | 6.67 | 24.91 |
Annual Sum or Average | 148.00 | 24.74 | 4365.67 | 24.05 | 147.33 | 24.74 |
Minimum of Months | 1.17 | 24.15 | 329.50 | 24.01 | 1.17 | 24.16 |
Maximum of Months | 51.17 | 27.46 | 379.00 | 24.09 | 50.83 | 27.46 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 24.73 | 359.33 | 24.01 | 2.67 | 24.73 |
February | 51.17 | 24.18 | 329.17 | 24.01 | 50.83 | 24.19 |
March | 14.83 | 24.17 | 370.33 | 24.02 | 14.50 | 24.18 |
April | 1.50 | 24.93 | 357.00 | 24.02 | 1.50 | 24.93 |
May | 7.00 | 24.91 | 375.00 | 24.05 | 7.00 | 24.91 |
June | 1.17 | 27.47 | 366.00 | 24.05 | 1.17 | 27.47 |
July | 14.00 | 25.23 | 369.00 | 24.08 | 14.00 | 25.23 |
August | 7.33 | 26.07 | 379.00 | 24.07 | 7.33 | 26.07 |
September | 25.50 | 25.00 | 360.00 | 24.09 | 25.50 | 25.00 |
October | 12.00 | 25.38 | 371.00 | 24.07 | 12.00 | 25.38 |
November | 4.33 | 25.09 | 360.00 | 24.04 | 4.33 | 25.09 |
December | 7.00 | 24.91 | 368.17 | 24.02 | 7.00 | 24.91 |
Annual Sum or Average | 148.50 | 24.75 | 4364.00 | 24.05 | 147.83 | 24.75 |
Minimum of Months | 1.17 | 24.17 | 329.17 | 24.01 | 1.17 | 24.18 |
Maximum of Months | 51.17 | 27.47 | 379.00 | 24.09 | 50.83 | 27.47 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 24.66 | 358.33 | 24.00 | 2.83 | 24.66 |
February | 55.17 | 24.17 | 328.50 | 24.01 | 54.50 | 24.17 |
March | 16.17 | 24.11 | 369.00 | 24.02 | 15.83 | 24.12 |
April | 1.83 | 24.84 | 356.33 | 24.02 | 1.83 | 24.84 |
May | 7.33 | 24.77 | 375.00 | 24.04 | 7.33 | 24.77 |
June | 1.00 | 26.31 | 366.00 | 24.05 | 1.00 | 26.31 |
July | 14.50 | 25.10 | 369.00 | 24.07 | 14.50 | 25.10 |
August | 8.83 | 25.58 | 379.00 | 24.07 | 8.83 | 25.58 |
September | 28.17 | 24.88 | 360.00 | 24.08 | 28.17 | 24.88 |
October | 14.50 | 25.07 | 371.00 | 24.07 | 14.50 | 25.07 |
November | 5.67 | 24.83 | 360.00 | 24.03 | 5.67 | 24.83 |
December | 9.00 | 24.73 | 367.50 | 24.02 | 9.00 | 24.73 |
Annual Sum or Average | 165.00 | 24.63 | 4359.67 | 24.04 | 164.00 | 24.63 |
Minimum of Months | 1.00 | 24.11 | 328.50 | 24.00 | 1.00 | 24.12 |
Maximum of Months | 55.17 | 26.31 | 379.00 | 24.08 | 54.50 | 26.31 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.17 | 24.43 | 319.83 | 23.93 | 4.17 | 24.43 |
February | 63.67 | 24.01 | 295.33 | 23.93 | 63.67 | 24.01 |
March | 21.00 | 24.07 | 335.17 | 23.93 | 20.83 | 24.07 |
April | 3.17 | 24.43 | 323.67 | 23.94 | 3.17 | 24.43 |
May | 7.17 | 24.46 | 344.00 | 23.95 | 7.17 | 24.46 |
June | 0.67 | 27.08 | 336.00 | 23.94 | 0.67 | 27.08 |
July | 18.33 | 24.53 | 338.00 | 23.97 | 18.33 | 24.53 |
August | 8.67 | 25.11 | 348.00 | 23.95 | 8.67 | 25.11 |
September | 35.00 | 24.48 | 330.00 | 23.97 | 35.00 | 24.48 |
October | 9.67 | 25.43 | 340.00 | 23.96 | 9.67 | 25.43 |
November | 6.17 | 24.46 | 330.00 | 23.94 | 6.17 | 24.46 |
December | 11.33 | 24.54 | 332.50 | 23.94 | 11.33 | 24.54 |
Annual Sum or Average | 189.00 | 24.37 | 3972.50 | 23.95 | 188.83 | 24.37 |
Minimum of Months | 0.67 | 24.01 | 295.33 | 23.93 | 0.67 | 24.01 |
Maximum of Months | 63.67 | 27.08 | 348.00 | 23.97 | 63.67 | 27.08 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.33 | 24.32 | 311.67 | 23.93 | 5.33 | 24.32 |
February | 67.17 | 24.01 | 291.00 | 23.93 | 67.17 | 24.01 |
March | 22.00 | 24.05 | 329.83 | 23.93 | 21.83 | 24.06 |
April | 4.50 | 24.27 | 318.50 | 23.94 | 4.50 | 24.27 |
May | 7.83 | 24.52 | 344.00 | 23.94 | 7.83 | 24.52 |
June | 0.67 | 27.00 | 336.00 | 23.94 | 0.67 | 27.00 |
July | 21.83 | 24.39 | 338.00 | 23.97 | 21.83 | 24.39 |
August | 11.00 | 24.82 | 348.00 | 23.95 | 11.00 | 24.82 |
September | 38.83 | 24.40 | 330.00 | 23.97 | 38.83 | 24.40 |
October | 10.33 | 25.36 | 340.00 | 23.96 | 10.33 | 25.36 |
November | 6.83 | 24.39 | 330.00 | 23.94 | 6.83 | 24.39 |
December | 12.83 | 24.50 | 328.83 | 23.94 | 12.83 | 24.50 |
Annual Sum or Average | 209.17 | 24.32 | 3945.83 | 23.95 | 209.00 | 24.32 |
Minimum of Months | 0.67 | 24.01 | 291.00 | 23.93 | 0.67 | 24.01 |
Maximum of Months | 67.17 | 27.00 | 348.00 | 23.97 | 67.17 | 27.00 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.67 | 24.29 | 310.17 | 23.93 | 5.67 | 24.29 |
February | 69.17 | 24.00 | 290.17 | 23.93 | 69.00 | 24.00 |
March | 22.83 | 24.05 | 329.00 | 23.93 | 22.67 | 24.05 |
April | 5.00 | 24.23 | 317.50 | 23.94 | 5.00 | 24.23 |
May | 8.00 | 24.51 | 344.00 | 23.94 | 8.00 | 24.51 |
June | 0.83 | 26.37 | 336.00 | 23.94 | 0.83 | 26.37 |
July | 22.33 | 24.37 | 338.00 | 23.97 | 22.33 | 24.37 |
August | 11.83 | 24.75 | 348.00 | 23.95 | 11.83 | 24.75 |
September | 39.67 | 24.39 | 330.00 | 23.97 | 39.67 | 24.39 |
October | 11.17 | 25.25 | 340.00 | 23.96 | 11.17 | 25.25 |
November | 6.83 | 24.39 | 330.00 | 23.94 | 6.83 | 24.39 |
December | 13.00 | 24.49 | 328.50 | 23.94 | 13.00 | 24.49 |
Annual Sum or Average | 216.33 | 24.30 | 3941.33 | 23.95 | 216.00 | 24.30 |
Minimum of Months | 0.83 | 24.00 | 290.17 | 23.93 | 0.83 | 24.00 |
Maximum of Months | 69.17 | 26.37 | 348.00 | 23.97 | 69.00 | 26.37 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.17 | 24.20 | 310.33 | 23.93 | 7.17 | 24.20 |
February | 71.50 | 24.00 | 290.00 | 23.93 | 71.33 | 24.00 |
March | 24.17 | 24.03 | 328.67 | 23.93 | 23.50 | 24.04 |
April | 5.00 | 24.22 | 318.17 | 23.94 | 5.00 | 24.22 |
May | 8.33 | 24.48 | 344.00 | 23.94 | 8.33 | 24.48 |
June | 1.00 | 25.95 | 336.00 | 23.94 | 1.00 | 25.95 |
July | 22.33 | 24.37 | 338.00 | 23.97 | 22.33 | 24.37 |
August | 12.00 | 24.74 | 348.00 | 23.95 | 12.00 | 24.74 |
September | 40.33 | 24.40 | 330.00 | 23.97 | 40.33 | 24.40 |
October | 11.50 | 25.21 | 340.00 | 23.96 | 11.50 | 25.21 |
November | 7.33 | 24.35 | 330.00 | 23.94 | 7.33 | 24.35 |
December | 14.67 | 24.41 | 328.33 | 23.93 | 14.67 | 24.41 |
Annual Sum or Average | 225.33 | 24.29 | 3941.50 | 23.95 | 224.50 | 24.29 |
Minimum of Months | 1.00 | 24.00 | 290.00 | 23.93 | 1.00 | 24.00 |
Maximum of Months | 71.50 | 25.95 | 348.00 | 23.97 | 71.33 | 25.95 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.00 | 24.23 | 318.50 | 23.93 | 7.00 | 24.23 |
February | 64.83 | 24.01 | 294.50 | 23.94 | 64.33 | 24.02 |
March | 23.83 | 24.04 | 334.17 | 23.93 | 22.33 | 24.07 |
April | 2.33 | 24.68 | 324.33 | 23.95 | 2.33 | 24.68 |
May | 7.33 | 24.60 | 344.00 | 23.95 | 7.33 | 24.60 |
June | 2.00 | 25.59 | 336.00 | 23.95 | 2.00 | 25.59 |
July | 16.50 | 24.74 | 338.00 | 23.98 | 16.50 | 24.74 |
August | 6.50 | 26.00 | 348.00 | 23.95 | 6.50 | 26.00 |
September | 35.00 | 24.57 | 330.00 | 23.98 | 35.00 | 24.57 |
October | 10.83 | 25.52 | 340.00 | 23.97 | 10.83 | 25.52 |
November | 7.33 | 24.47 | 330.00 | 23.94 | 7.33 | 24.47 |
December | 11.67 | 24.58 | 330.50 | 23.94 | 11.67 | 24.58 |
Annual Sum or Average | 195.17 | 24.43 | 3968.00 | 23.95 | 193.17 | 24.44 |
Minimum of Months | 2.00 | 24.01 | 294.50 | 23.93 | 2.00 | 24.02 |
Maximum of Months | 64.83 | 26.00 | 348.00 | 23.98 | 64.33 | 26.00 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.89310 | 51.07744 | 0.53381 | 11.05355 |
February | 448.00000 | 23.88920 | 55.92159 | 0.57035 | 11.93181 |
March | 496.00000 | 23.89031 | 52.61804 | 0.54682 | 11.35782 |
April | 480.00000 | 23.89224 | 51.63601 | 0.53934 | 11.14940 |
May | 496.00000 | 23.89820 | 54.02250 | -0.2775 | 6.69081 |
June | 480.00000 | 23.90186 | 54.39564 | -0.2607 | 6.48878 |
July | 496.00000 | 23.90384 | 55.60545 | -0.2349 | 6.23148 |
August | 496.00000 | 23.90405 | 55.53155 | -0.2333 | 6.21562 |
September | 480.00000 | 23.90282 | 56.81502 | -0.2152 | 6.06481 |
October | 496.00000 | 23.89968 | 56.03886 | 0.60968 | 12.85453 |
November | 480.00000 | 23.90209 | 54.95918 | 0.59110 | 12.39218 |
December | 496.00000 | 23.89853 | 53.59477 | 0.56748 | 11.83724 |
Annual Sum or Average | 5840.00000 | 23.89805 | 54.33734 | 0.22598 | 9.50800 |
Minimum of Months | 448.00000 | 23.88920 | 51.07744 | -0.2775 | 6.06481 |
Maximum of Months | 496.00000 | 23.90405 | 56.81502 | 0.60968 | 12.85453 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.89470 | 49.13473 | 0.51643 | 10.67281 |
February | 448.00000 | 23.89165 | 53.58171 | 0.54671 | 11.38705 |
March | 496.00000 | 23.89299 | 50.73983 | 0.52508 | 10.87017 |
April | 480.00000 | 23.89344 | 49.83962 | 0.51722 | 10.66649 |
May | 496.00000 | 23.89953 | 52.29221 | -0.3078 | 7.06800 |
June | 480.00000 | 23.90257 | 52.87461 | -0.2938 | 6.87905 |
July | 496.00000 | 23.90417 | 54.06846 | -0.2721 | 6.63232 |
August | 496.00000 | 23.90410 | 54.07554 | -0.2717 | 6.62347 |
September | 480.00000 | 23.90302 | 55.40104 | -0.2562 | 6.46905 |
October | 496.00000 | 23.90038 | 54.23790 | 0.58223 | 12.17552 |
November | 480.00000 | 23.90286 | 53.08881 | 0.56596 | 11.78762 |
December | 496.00000 | 23.90001 | 51.61539 | 0.54627 | 11.34530 |
Annual Sum or Average | 5840.00000 | 23.89916 | 52.56848 | 0.19774 | 9.36964 |
Minimum of Months | 448.00000 | 23.89165 | 49.13473 | -0.3078 | 6.46905 |
Maximum of Months | 496.00000 | 23.90417 | 55.40104 | 0.58223 | 12.17552 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.98221 | 51.16332 | 0.55295 | 11.51713 |
February | 336.00000 | 23.98603 | 56.38724 | 0.58901 | 12.43341 |
March | 379.00000 | 23.99163 | 53.01017 | 0.56244 | 11.77132 |
April | 360.00000 | 23.99496 | 51.97574 | 0.55398 | 11.53975 |
May | 375.00000 | 24.01357 | 54.28979 | -0.2577 | 6.62877 |
June | 366.00000 | 24.01772 | 54.82565 | -0.2439 | 6.48041 |
July | 369.00000 | 24.03468 | 55.93315 | -0.2165 | 6.30503 |
August | 379.00000 | 24.02873 | 55.81951 | -0.2189 | 6.30770 |
September | 360.00000 | 24.04347 | 57.37106 | -0.1980 | 6.22646 |
October | 371.00000 | 24.03253 | 56.30135 | 0.63004 | 13.51424 |
November | 360.00000 | 24.00509 | 55.21796 | 0.60788 | 12.87140 |
December | 369.00000 | 23.99556 | 53.79784 | 0.58629 | 12.33876 |
Annual Sum or Average | 4395.00000 | 24.01067 | 54.65776 | 0.24221 | 9.80271 |
Minimum of Months | 336.00000 | 23.98221 | 51.16332 | -0.2577 | 6.22646 |
Maximum of Months | 379.00000 | 24.04347 | 57.37106 | 0.63004 | 13.51424 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.98145 | 51.20384 | 0.55222 | 11.49956 |
February | 336.00000 | 23.98520 | 56.42623 | 0.58838 | 12.41776 |
March | 379.00000 | 23.99085 | 53.03775 | 0.56193 | 11.75872 |
April | 360.00000 | 23.99435 | 52.00695 | 0.55341 | 11.52570 |
May | 375.00000 | 24.01322 | 54.29521 | -0.2578 | 6.62934 |
June | 366.00000 | 24.01745 | 54.82399 | -0.2438 | 6.47919 |
July | 369.00000 | 24.03463 | 55.90462 | -0.2157 | 6.29899 |
August | 379.00000 | 24.02865 | 55.79806 | -0.2183 | 6.30225 |
September | 360.00000 | 24.04352 | 57.32189 | -0.1969 | 6.21991 |
October | 371.00000 | 24.03248 | 56.26613 | 0.63057 | 13.52894 |
November | 360.00000 | 24.00471 | 55.22556 | 0.60776 | 12.86850 |
December | 369.00000 | 23.99504 | 53.81966 | 0.58590 | 12.32882 |
Annual Sum or Average | 4395.00000 | 24.01029 | 54.66063 | 0.24223 | 9.79640 |
Minimum of Months | 336.00000 | 23.98145 | 51.20384 | -0.2578 | 6.21991 |
Maximum of Months | 379.00000 | 24.04352 | 57.32189 | 0.63057 | 13.52894 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.97802 | 51.44847 | 0.54873 | 11.41527 |
February | 336.00000 | 23.98138 | 56.74592 | 0.58513 | 12.33465 |
March | 379.00000 | 23.98673 | 53.31088 | 0.55817 | 11.66682 |
April | 360.00000 | 23.99104 | 52.26072 | 0.54971 | 11.43496 |
May | 375.00000 | 24.01018 | 54.52774 | -0.2629 | 6.67386 |
June | 366.00000 | 24.01452 | 55.04945 | -0.2486 | 6.51656 |
July | 369.00000 | 24.03185 | 56.10522 | -0.2201 | 6.32534 |
August | 379.00000 | 24.02581 | 56.00811 | -0.2229 | 6.33131 |
September | 360.00000 | 24.04067 | 57.54508 | -0.2012 | 6.24063 |
October | 371.00000 | 24.02959 | 56.48734 | 0.62779 | 13.44807 |
November | 360.00000 | 24.00170 | 55.45989 | 0.60494 | 12.79062 |
December | 369.00000 | 23.99182 | 54.06770 | 0.58281 | 12.24804 |
Annual Sum or Average | 4395.00000 | 24.00710 | 54.90061 | 0.23839 | 9.76091 |
Minimum of Months | 336.00000 | 23.97802 | 51.44847 | -0.2629 | 6.24063 |
Maximum of Months | 379.00000 | 24.04067 | 57.54508 | 0.62779 | 13.44807 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.91896 | 52.56141 | 0.53140 | 11.00093 |
February | 308.00000 | 23.92397 | 58.00307 | 0.56993 | 11.93093 |
March | 348.00000 | 23.92044 | 54.45340 | 0.54032 | 11.21625 |
April | 330.00000 | 23.92963 | 53.34713 | 0.53153 | 10.98814 |
May | 344.00000 | 23.93304 | 55.56888 | -0.2925 | 6.92667 |
June | 336.00000 | 23.93193 | 56.17667 | -0.2780 | 6.73883 |
July | 338.00000 | 23.95464 | 57.16907 | -0.2457 | 6.47055 |
August | 348.00000 | 23.93600 | 56.99852 | -0.2527 | 6.50410 |
September | 330.00000 | 23.95388 | 58.62020 | -0.2274 | 6.34928 |
October | 340.00000 | 23.94810 | 57.39313 | 0.61024 | 12.93574 |
November | 330.00000 | 23.92758 | 56.56883 | 0.58744 | 12.31015 |
December | 338.00000 | 23.92573 | 55.21561 | 0.56536 | 11.79347 |
Annual Sum or Average | 4030.00000 | 23.93368 | 55.98729 | 0.21638 | 9.57415 |
Minimum of Months | 308.00000 | 23.91896 | 52.56141 | -0.2925 | 6.34928 |
Maximum of Months | 348.00000 | 23.95464 | 58.62020 | 0.61024 | 12.93574 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.91837 | 52.72127 | 0.51619 | 10.66208 |
February | 308.00000 | 23.92334 | 58.24349 | 0.55488 | 11.57242 |
March | 348.00000 | 23.91994 | 54.63317 | 0.52489 | 10.86607 |
April | 330.00000 | 23.92905 | 53.49954 | 0.51620 | 10.64823 |
May | 344.00000 | 23.93255 | 55.74759 | -0.3168 | 7.23277 |
June | 336.00000 | 23.93135 | 56.36331 | -0.3033 | 7.04081 |
July | 338.00000 | 23.95386 | 57.35007 | -0.2723 | 6.75352 |
August | 348.00000 | 23.93529 | 57.16334 | -0.2793 | 6.79389 |
September | 330.00000 | 23.95295 | 58.83993 | -0.2544 | 6.61162 |
October | 340.00000 | 23.94733 | 57.58170 | 0.59184 | 12.46528 |
November | 330.00000 | 23.92705 | 56.77048 | 0.57036 | 11.88904 |
December | 338.00000 | 23.92493 | 55.41379 | 0.54927 | 11.41198 |
Annual Sum or Average | 4030.00000 | 23.93302 | 56.17442 | 0.19613 | 9.47547 |
Minimum of Months | 308.00000 | 23.91837 | 52.72127 | -0.3168 | 6.61162 |
Maximum of Months | 348.00000 | 23.95386 | 58.83993 | 0.59184 | 12.46528 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.91803 | 52.79353 | 0.51456 | 10.62627 |
February | 308.00000 | 23.92297 | 58.34209 | 0.55331 | 11.53535 |
March | 348.00000 | 23.91957 | 54.71004 | 0.52324 | 10.82949 |
April | 330.00000 | 23.92874 | 53.56410 | 0.51465 | 10.61389 |
May | 344.00000 | 23.93231 | 55.80570 | -0.3191 | 7.26187 |
June | 336.00000 | 23.93112 | 56.42190 | -0.3056 | 7.06804 |
July | 338.00000 | 23.95356 | 57.40280 | -0.2745 | 6.77656 |
August | 348.00000 | 23.93508 | 57.21229 | -0.2814 | 6.81704 |
September | 330.00000 | 23.95266 | 58.90011 | -0.2566 | 6.63267 |
October | 340.00000 | 23.94705 | 57.63753 | 0.59039 | 12.42808 |
November | 330.00000 | 23.92679 | 56.84127 | 0.56883 | 11.85157 |
December | 338.00000 | 23.92457 | 55.48829 | 0.54769 | 11.37491 |
Annual Sum or Average | 4030.00000 | 23.93273 | 56.24015 | 0.19430 | 9.46474 |
Minimum of Months | 308.00000 | 23.91803 | 52.79353 | -0.3191 | 6.63267 |
Maximum of Months | 348.00000 | 23.95356 | 58.90011 | 0.59039 | 12.42808 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.91756 | 52.91532 | 0.51518 | 10.64022 |
February | 308.00000 | 23.92233 | 58.52018 | 0.55373 | 11.54673 |
March | 348.00000 | 23.91876 | 54.84742 | 0.52373 | 10.84185 |
April | 330.00000 | 23.92843 | 53.64635 | 0.51595 | 10.64234 |
May | 344.00000 | 23.93215 | 55.82875 | -0.3161 | 7.22266 |
June | 336.00000 | 23.93099 | 56.43597 | -0.3024 | 7.02816 |
July | 338.00000 | 23.95350 | 57.38578 | -0.2707 | 6.73313 |
August | 348.00000 | 23.93512 | 57.18005 | -0.2771 | 6.76876 |
September | 330.00000 | 23.95261 | 58.89836 | -0.2531 | 6.59747 |
October | 340.00000 | 23.94698 | 57.63631 | 0.59290 | 12.49137 |
November | 330.00000 | 23.92651 | 56.90876 | 0.57028 | 11.88670 |
December | 338.00000 | 23.92416 | 55.58583 | 0.54871 | 11.39923 |
Annual Sum or Average | 4030.00000 | 23.93245 | 56.29503 | 0.19644 | 9.46307 |
Minimum of Months | 308.00000 | 23.91756 | 52.91532 | -0.3161 | 6.59747 |
Maximum of Months | 348.00000 | 23.95350 | 58.89836 | 0.59290 | 12.49137 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.91989 | 52.47513 | 0.53764 | 11.15469 |
February | 308.00000 | 23.92453 | 58.21897 | 0.57277 | 12.01609 |
March | 348.00000 | 23.92030 | 54.59550 | 0.54675 | 11.37957 |
April | 330.00000 | 23.93237 | 52.95715 | 0.54532 | 11.31118 |
May | 344.00000 | 23.93646 | 54.79517 | -0.2627 | 6.60561 |
June | 336.00000 | 23.93491 | 55.39800 | -0.2491 | 6.44501 |
July | 338.00000 | 23.95966 | 56.27645 | -0.2108 | 6.17274 |
August | 348.00000 | 23.93990 | 55.94483 | -0.2134 | 6.16144 |
September | 330.00000 | 23.95862 | 58.03413 | -0.1996 | 6.14732 |
October | 340.00000 | 23.95253 | 56.54631 | 0.63188 | 13.52705 |
November | 330.00000 | 23.92956 | 56.28484 | 0.59720 | 12.56816 |
December | 338.00000 | 23.92690 | 55.01968 | 0.57214 | 11.96782 |
Annual Sum or Average | 4030.00000 | 23.93634 | 55.52090 | 0.23555 | 9.59682 |
Minimum of Months | 308.00000 | 23.91989 | 52.47513 | -0.2627 | 6.14732 |
Maximum of Months | 348.00000 | 23.95966 | 58.21897 | 0.63188 | 13.52705 |
Report: DXReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.231825E+11 | 0.572291E+10 | 493.36 | 0.158065E+11 | 0.737601E+10 | 0.00 | 1.00 | 01-JAN-08:62 | 0.00 | 01-JAN-00:05 | 47767.37 | 31-JAN-08:62 | 33287.40 | 12-JAN-08:62 | 20370.68 | 31-JAN-08:62 | 10356.18 | 02-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.248336E+11 | 0.595446E+10 | 444.97 | 0.152269E+11 | 0.960672E+10 | 0.00 | 1.00 | 04-FEB-08:62 | 0.00 | 01-FEB-00:05 | 49451.36 | 17-FEB-08:62 | 30625.99 | 13-FEB-08:62 | 25696.76 | 17-FEB-08:62 | 10545.97 | 18-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.260003E+11 | 0.636333E+10 | 491.26 | 0.173780E+11 | 0.862233E+10 | 0.00 | 1.00 | 02-MAR-08:62 | 0.00 | 01-MAR-00:05 | 48237.15 | 03-MAR-08:62 | 32084.67 | 19-MAR-07:02 | 22934.63 | 03-MAR-08:62 | 10326.56 | 15-MAR-07:03 | 0.00 | 01-MAR-00:05 |
April | 0.247874E+11 | 0.613023E+10 | 478.88 | 0.170576E+11 | 0.772982E+10 | 0.00 | 1.00 | 07-APR-07:03 | 0.00 | 01-APR-00:05 | 47246.92 | 25-APR-07:02 | 31416.00 | 10-APR-07:02 | 17643.98 | 24-APR-07:03 | 10394.93 | 25-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.318883E+11 | 0.777699E+10 | 497.34 | 0.211516E+11 | 0.107367E+11 | 0.00 | 1.00 | 01-MAY-07:03 | 0.00 | 01-MAY-00:10 | 48545.05 | 10-MAY-07:02 | 32512.92 | 30-MAY-07:03 | 22052.78 | 10-MAY-07:03 | 10566.04 | 09-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.325194E+11 | 0.788875E+10 | 485.35 | 0.214426E+11 | 0.110768E+11 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 48094.14 | 14-JUN-07:02 | 31839.55 | 04-JUN-07:02 | 19926.18 | 14-JUN-07:02 | 10742.95 | 21-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.382272E+11 | 0.928706E+10 | 502.28 | 0.248529E+11 | 0.133743E+11 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 49394.11 | 20-JUL-07:02 | 31130.56 | 18-JUL-07:02 | 24012.87 | 20-JUL-07:03 | 10757.36 | 20-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.389160E+11 | 0.951937E+10 | 500.15 | 0.254991E+11 | 0.134169E+11 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 48672.13 | 08-AUG-07:02 | 30656.56 | 24-AUG-07:02 | 21541.20 | 08-AUG-07:03 | 10710.31 | 27-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.391689E+11 | 0.940810E+10 | 487.35 | 0.246179E+11 | 0.145510E+11 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 49050.35 | 30-SEP-07:02 | 30506.85 | 27-SEP-07:02 | 23634.22 | 30-SEP-07:03 | 10852.54 | 03-SEP-07:01 | 0.00 | 01-SEP-00:10 |
October | 0.379719E+11 | 0.922618E+10 | 497.91 | 0.244462E+11 | 0.135257E+11 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:05 | 48379.24 | 13-OCT-07:02 | 30982.15 | 26-OCT-07:03 | 20743.17 | 13-OCT-07:03 | 10667.85 | 07-OCT-07:02 | 0.00 | 01-OCT-00:05 |
November | 0.314542E+11 | 0.759636E+10 | 483.02 | 0.202825E+11 | 0.111717E+11 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 48510.51 | 01-NOV-07:02 | 32184.78 | 15-NOV-08:62 | 21486.24 | 01-NOV-07:03 | 10709.57 | 06-NOV-08:61 | 0.00 | 01-NOV-00:10 |
December | 0.284016E+11 | 0.687627E+10 | 498.86 | 0.183853E+11 | 0.100163E+11 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-01:05 | 48787.81 | 03-DEC-08:61 | 35545.16 | 25-DEC-08:62 | 21874.13 | 03-DEC-08:04 | 10696.39 | 03-DEC-08:61 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.377351E+12 | 0.917500E+11 | 5860.73 | 0.246147E+12 | 0.131204E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.231825E+11 | 0.572291E+10 | 444.97 | 0.152269E+11 | 0.737601E+10 | 0.00 | 1.00 | 0.00 | 47246.92 | 30506.85 | 17643.98 | 10326.56 | 0.00 | |||||||
Maximum of Months | 0.391689E+11 | 0.951937E+10 | 502.28 | 0.254991E+11 | 0.145510E+11 | 0.00 | 1.00 | 0.00 | 49451.36 | 35545.16 | 25696.76 | 10852.54 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.124747E+11 | 0.305586E+10 | 494.04 | 0.881098E+10 | 0.366372E+10 | 0.00 | 1.00 | 01-JAN-08:62 | 0.00 | 01-JAN-00:05 | 24619.56 | 31-JAN-08:62 | 18672.00 | 22-JAN-08:62 | 8392.27 | 31-JAN-08:62 | 5306.30 | 02-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.129813E+11 | 0.309951E+10 | 446.79 | 0.828975E+10 | 0.469155E+10 | 0.00 | 1.00 | 04-FEB-08:62 | 0.00 | 01-FEB-00:05 | 25323.84 | 17-FEB-08:62 | 17592.07 | 05-FEB-08:62 | 10698.98 | 17-FEB-08:62 | 5427.70 | 18-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.135798E+11 | 0.330933E+10 | 494.71 | 0.937171E+10 | 0.420804E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 24746.84 | 03-MAR-08:62 | 18233.04 | 19-MAR-07:02 | 9250.23 | 03-MAR-08:62 | 5289.03 | 15-MAR-07:03 | 0.00 | 01-MAR-00:05 |
April | 0.128639E+11 | 0.316929E+10 | 479.33 | 0.913132E+10 | 0.373261E+10 | 0.00 | 1.00 | 07-APR-07:03 | 0.00 | 01-APR-00:05 | 24316.24 | 18-APR-07:03 | 18417.48 | 06-APR-07:03 | 7319.62 | 14-APR-07:03 | 5316.13 | 25-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.161940E+11 | 0.393796E+10 | 498.19 | 0.110645E+11 | 0.512948E+10 | 0.00 | 1.00 | 01-MAY-07:03 | 0.00 | 01-MAY-00:10 | 24952.51 | 10-MAY-07:02 | 18502.76 | 22-MAY-07:02 | 9266.09 | 10-MAY-07:03 | 5421.99 | 09-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.163281E+11 | 0.395352E+10 | 485.49 | 0.110631E+11 | 0.526502E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 24832.47 | 14-JUN-07:02 | 18061.94 | 04-JUN-07:02 | 8556.14 | 14-JUN-07:02 | 5527.51 | 21-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.189765E+11 | 0.460926E+10 | 502.38 | 0.126830E+11 | 0.629343E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 25392.39 | 20-JUL-07:02 | 17778.30 | 08-JUL-07:02 | 10482.38 | 20-JUL-07:03 | 5552.34 | 20-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.193166E+11 | 0.472044E+10 | 500.34 | 0.129873E+11 | 0.632937E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 25066.22 | 08-AUG-07:02 | 17541.70 | 24-AUG-07:02 | 9346.65 | 08-AUG-07:03 | 5507.01 | 08-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.192237E+11 | 0.461891E+10 | 486.47 | 0.124157E+11 | 0.680799E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 25200.84 | 30-SEP-07:02 | 17552.90 | 19-SEP-07:02 | 10088.83 | 30-SEP-07:03 | 5588.01 | 03-SEP-07:01 | 0.00 | 01-SEP-00:10 |
October | 0.191103E+11 | 0.463185E+10 | 498.12 | 0.126718E+11 | 0.643856E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:05 | 24900.60 | 13-OCT-07:02 | 17848.16 | 28-OCT-07:02 | 8858.65 | 13-OCT-07:03 | 5483.83 | 07-OCT-07:02 | 0.00 | 01-OCT-00:05 |
November | 0.160634E+11 | 0.386386E+10 | 482.33 | 0.106936E+11 | 0.536972E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 25004.33 | 01-NOV-07:02 | 18664.43 | 26-NOV-08:62 | 9288.17 | 01-NOV-07:03 | 5510.22 | 22-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.147952E+11 | 0.356384E+10 | 499.23 | 0.993402E+10 | 0.486114E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-01:05 | 25202.84 | 03-DEC-08:61 | 19549.31 | 25-DEC-08:62 | 9669.88 | 03-DEC-08:03 | 5513.69 | 03-DEC-08:61 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.191907E+12 | 0.465336E+11 | 5867.42 | 0.129117E+12 | 0.627906E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.124747E+11 | 0.305586E+10 | 446.79 | 0.828975E+10 | 0.366372E+10 | 0.00 | 1.00 | 0.00 | 24316.24 | 17541.70 | 7319.62 | 5289.03 | 0.00 | |||||||
Maximum of Months | 0.193166E+11 | 0.472044E+10 | 502.38 | 0.129873E+11 | 0.680799E+10 | 0.00 | 1.00 | 0.00 | 25392.39 | 19549.31 | 10698.98 | 5588.01 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.975870E+10 | 0.236932E+10 | 360.63 | 0.673852E+10 | 0.302018E+10 | 0.00 | 1.00 | 01-JAN-08:62 | 0.00 | 01-JAN-00:05 | 26482.29 | 02-JAN-07:02 | 18610.58 | 12-JAN-07:03 | 11996.67 | 01-JAN-08:62 | 5553.04 | 02-JAN-07:02 | 0.00 | 01-JAN-00:05 |
February | 0.102322E+11 | 0.241735E+10 | 324.58 | 0.634880E+10 | 0.388340E+10 | 0.00 | 1.00 | 04-FEB-07:03 | 0.00 | 01-FEB-00:05 | 27257.34 | 18-FEB-07:02 | 17002.40 | 13-FEB-07:03 | 14660.78 | 18-FEB-07:04 | 5651.66 | 17-FEB-07:02 | 0.00 | 01-FEB-00:05 |
March | 0.107669E+11 | 0.260391E+10 | 364.97 | 0.726640E+10 | 0.350051E+10 | 0.00 | 1.00 | 01-MAR-07:03 | 0.00 | 01-MAR-00:05 | 26888.65 | 13-MAR-06:02 | 17187.05 | 19-MAR-07:02 | 13427.57 | 13-MAR-06:02 | 5544.84 | 14-MAR-06:02 | 0.00 | 01-MAR-00:05 |
April | 0.100873E+11 | 0.246755E+10 | 350.25 | 0.700202E+10 | 0.308524E+10 | 0.00 | 1.00 | 01-APR-06:03 | 0.00 | 01-APR-00:05 | 26395.15 | 24-APR-06:03 | 18099.53 | 30-APR-07:03 | 12108.24 | 24-APR-06:03 | 5552.95 | 25-APR-06:02 | 0.00 | 01-APR-00:05 |
May | 0.130774E+11 | 0.315116E+10 | 367.75 | 0.876204E+10 | 0.431534E+10 | 0.00 | 1.00 | 01-MAY-06:03 | 0.00 | 01-MAY-00:10 | 26880.60 | 15-MAY-06:02 | 17782.24 | 31-MAY-06:03 | 13669.16 | 15-MAY-06:02 | 5637.26 | 09-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.133190E+11 | 0.318832E+10 | 361.66 | 0.881324E+10 | 0.450572E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 26430.05 | 18-JUN-07:02 | 17042.71 | 04-JUN-07:02 | 11258.32 | 09-JUN-06:02 | 5736.62 | 21-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.153659E+11 | 0.368793E+10 | 365.89 | 0.100518E+11 | 0.531411E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 27264.50 | 23-JUL-07:01 | 16495.80 | 04-JUL-07:02 | 13814.63 | 23-JUL-07:04 | 5755.31 | 23-JUL-07:04 | 0.00 | 01-JUL-00:05 |
August | 0.159561E+11 | 0.386337E+10 | 375.56 | 0.105467E+11 | 0.540940E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 27006.02 | 20-AUG-07:02 | 16408.15 | 23-AUG-06:02 | 13039.16 | 20-AUG-07:03 | 5760.70 | 27-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.155092E+11 | 0.368144E+10 | 357.77 | 0.979343E+10 | 0.571574E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 27467.04 | 25-SEP-06:02 | 16312.84 | 29-SEP-06:02 | 15115.26 | 25-SEP-06:02 | 5829.49 | 03-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 0.155100E+11 | 0.372082E+10 | 366.26 | 0.100992E+11 | 0.541077E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:05 | 26882.93 | 10-OCT-06:02 | 16278.64 | 28-OCT-06:02 | 13845.03 | 23-OCT-06:02 | 5704.66 | 07-OCT-06:02 | 0.00 | 01-OCT-00:05 |
November | 0.130454E+11 | 0.310481E+10 | 355.32 | 0.849056E+10 | 0.455480E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 26707.69 | 24-NOV-07:02 | 17493.66 | 15-NOV-07:02 | 12695.17 | 24-NOV-07:03 | 5720.33 | 23-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.117263E+11 | 0.279112E+10 | 361.80 | 0.767240E+10 | 0.405391E+10 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 26873.97 | 03-DEC-08:61 | 19343.98 | 25-DEC-08:62 | 12806.46 | 10-DEC-08:62 | 5744.23 | 03-DEC-08:61 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.154354E+12 | 0.370471E+11 | 4312.44 | 0.101585E+12 | 0.527691E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.975870E+10 | 0.236932E+10 | 324.58 | 0.634880E+10 | 0.302018E+10 | 0.00 | 1.00 | 0.00 | 26395.15 | 16278.64 | 11258.32 | 5544.84 | 0.00 | |||||||
Maximum of Months | 0.159561E+11 | 0.386337E+10 | 375.56 | 0.105467E+11 | 0.571574E+10 | 0.00 | 1.00 | 0.00 | 27467.04 | 19343.98 | 15115.26 | 5829.49 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.971819E+10 | 0.235799E+10 | 360.38 | 0.670835E+10 | 0.300984E+10 | 0.00 | 1.00 | 01-JAN-08:62 | 0.00 | 01-JAN-00:05 | 26308.59 | 02-JAN-07:02 | 18479.93 | 12-JAN-07:03 | 11909.00 | 01-JAN-08:62 | 5516.31 | 02-JAN-07:02 | 0.00 | 01-JAN-00:05 |
February | 0.102006E+11 | 0.240814E+10 | 324.54 | 0.632619E+10 | 0.387446E+10 | 0.00 | 1.00 | 04-FEB-07:03 | 0.00 | 01-FEB-00:05 | 27077.66 | 18-FEB-07:02 | 16871.29 | 13-FEB-07:03 | 14575.26 | 18-FEB-07:04 | 5614.17 | 17-FEB-07:02 | 0.00 | 01-FEB-00:05 |
March | 0.107390E+11 | 0.259497E+10 | 364.72 | 0.724587E+10 | 0.349314E+10 | 0.00 | 1.00 | 01-MAR-07:03 | 0.00 | 01-MAR-00:05 | 26712.09 | 13-MAR-06:02 | 17082.03 | 19-MAR-07:02 | 13360.75 | 13-MAR-06:04 | 5508.18 | 14-MAR-06:02 | 0.00 | 01-MAR-00:05 |
April | 0.100560E+11 | 0.245782E+10 | 350.08 | 0.697869E+10 | 0.307728E+10 | 0.00 | 1.00 | 01-APR-06:03 | 0.00 | 01-APR-00:05 | 26219.48 | 24-APR-06:03 | 17808.10 | 06-APR-06:03 | 12034.81 | 24-APR-06:03 | 5516.24 | 25-APR-06:02 | 0.00 | 01-APR-00:05 |
May | 0.130720E+11 | 0.314664E+10 | 367.75 | 0.875885E+10 | 0.431316E+10 | 0.00 | 1.00 | 01-MAY-06:03 | 0.00 | 01-MAY-00:10 | 26705.14 | 15-MAY-06:02 | 17667.11 | 31-MAY-06:03 | 13567.62 | 15-MAY-06:02 | 5600.01 | 09-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.133210E+11 | 0.318554E+10 | 361.85 | 0.881574E+10 | 0.450524E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 26258.55 | 18-JUN-07:02 | 16937.54 | 04-JUN-07:02 | 11190.25 | 09-JUN-06:02 | 5698.67 | 21-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.153960E+11 | 0.369215E+10 | 366.03 | 0.100762E+11 | 0.531974E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 27088.49 | 23-JUL-07:01 | 16410.40 | 04-JUL-07:02 | 13707.26 | 23-JUL-07:04 | 5717.12 | 23-JUL-07:04 | 0.00 | 01-JUL-00:05 |
August | 0.159813E+11 | 0.386641E+10 | 375.51 | 0.105677E+11 | 0.541358E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 26832.66 | 20-AUG-07:02 | 16314.51 | 23-AUG-06:02 | 12930.65 | 20-AUG-07:03 | 5722.51 | 27-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.155536E+11 | 0.368862E+10 | 357.74 | 0.982769E+10 | 0.572589E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 27291.93 | 25-SEP-06:02 | 16214.07 | 29-SEP-06:02 | 14975.13 | 25-SEP-06:02 | 5790.83 | 03-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 0.155435E+11 | 0.372563E+10 | 366.15 | 0.101258E+11 | 0.541774E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:05 | 26711.05 | 10-OCT-06:02 | 16173.91 | 28-OCT-06:02 | 13741.65 | 23-OCT-06:02 | 5666.95 | 07-OCT-06:02 | 0.00 | 01-OCT-00:05 |
November | 0.130393E+11 | 0.310052E+10 | 355.32 | 0.848693E+10 | 0.455233E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 26534.30 | 24-NOV-07:02 | 17375.72 | 15-NOV-07:02 | 12596.74 | 24-NOV-07:03 | 5682.47 | 23-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.117038E+11 | 0.278339E+10 | 361.78 | 0.765578E+10 | 0.404802E+10 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 26697.71 | 03-DEC-08:61 | 19208.65 | 25-DEC-08:62 | 12724.18 | 10-DEC-08:62 | 5706.13 | 03-DEC-08:61 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.154324E+12 | 0.370078E+11 | 4311.84 | 0.101574E+12 | 0.527504E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.971819E+10 | 0.235799E+10 | 324.54 | 0.632619E+10 | 0.300984E+10 | 0.00 | 1.00 | 0.00 | 26219.48 | 16173.91 | 11190.25 | 5508.18 | 0.00 | |||||||
Maximum of Months | 0.159813E+11 | 0.386641E+10 | 375.51 | 0.105677E+11 | 0.572589E+10 | 0.00 | 1.00 | 0.00 | 27291.93 | 19208.65 | 14975.13 | 5790.83 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.946612E+10 | 0.230426E+10 | 359.66 | 0.651277E+10 | 0.295335E+10 | 0.00 | 1.00 | 01-JAN-08:62 | 0.00 | 01-JAN-00:05 | 26293.64 | 02-JAN-07:02 | 17528.93 | 12-JAN-07:03 | 11970.57 | 01-JAN-08:62 | 5514.70 | 02-JAN-07:02 | 0.00 | 01-JAN-00:05 |
February | 0.995388E+10 | 0.235629E+10 | 323.24 | 0.614620E+10 | 0.380768E+10 | 0.00 | 1.00 | 04-FEB-07:03 | 0.00 | 01-FEB-00:05 | 27065.36 | 18-FEB-07:02 | 16713.37 | 13-FEB-07:03 | 14678.21 | 18-FEB-07:02 | 5613.11 | 17-FEB-07:02 | 0.00 | 01-FEB-00:05 |
March | 0.104714E+11 | 0.253833E+10 | 362.35 | 0.704121E+10 | 0.343016E+10 | 0.00 | 1.00 | 01-MAR-07:03 | 0.00 | 01-MAR-00:05 | 26695.79 | 13-MAR-06:02 | 16994.21 | 19-MAR-07:02 | 13409.58 | 13-MAR-06:02 | 5506.52 | 14-MAR-06:02 | 0.00 | 01-MAR-00:05 |
April | 0.980559E+10 | 0.240495E+10 | 349.53 | 0.678456E+10 | 0.302102E+10 | 0.00 | 1.00 | 07-APR-06:02 | 0.00 | 01-APR-00:05 | 26202.94 | 24-APR-06:03 | 17107.21 | 06-APR-06:03 | 12116.17 | 24-APR-06:03 | 5514.69 | 25-APR-06:02 | 0.00 | 01-APR-00:05 |
May | 0.128313E+11 | 0.309625E+10 | 368.08 | 0.857050E+10 | 0.426079E+10 | 0.00 | 1.00 | 03-MAY-06:03 | 0.00 | 01-MAY-00:10 | 26690.46 | 15-MAY-06:02 | 17257.85 | 31-MAY-06:03 | 13632.72 | 15-MAY-06:02 | 5598.57 | 09-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.130926E+11 | 0.313798E+10 | 361.69 | 0.863725E+10 | 0.445532E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 26240.10 | 18-JUN-07:02 | 16834.42 | 04-JUN-07:02 | 11293.79 | 09-JUN-06:02 | 5697.09 | 21-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.151756E+11 | 0.364311E+10 | 365.59 | 0.990187E+10 | 0.527377E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 27070.85 | 23-JUL-07:01 | 16310.34 | 04-JUL-07:02 | 13788.26 | 23-JUL-07:04 | 5716.07 | 23-JUL-07:04 | 0.00 | 01-JUL-00:05 |
August | 0.157470E+11 | 0.381381E+10 | 375.06 | 0.103820E+11 | 0.536505E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 26816.72 | 20-AUG-07:02 | 16208.46 | 23-AUG-06:02 | 13005.25 | 20-AUG-07:03 | 5721.34 | 27-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.153328E+11 | 0.364016E+10 | 357.75 | 0.965636E+10 | 0.567642E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 27277.90 | 25-SEP-06:02 | 16108.70 | 29-SEP-06:02 | 15037.00 | 25-SEP-06:02 | 5789.73 | 03-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 0.153139E+11 | 0.367472E+10 | 366.10 | 0.994538E+10 | 0.536854E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:05 | 26698.03 | 10-OCT-06:02 | 16061.40 | 28-OCT-06:02 | 13807.62 | 23-OCT-06:02 | 5665.50 | 07-OCT-06:02 | 0.00 | 01-OCT-00:05 |
November | 0.128132E+11 | 0.305337E+10 | 354.85 | 0.831283E+10 | 0.450041E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 26518.98 | 24-NOV-07:02 | 17267.70 | 15-NOV-07:02 | 12656.34 | 24-NOV-07:03 | 5681.10 | 23-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.114611E+11 | 0.273287E+10 | 361.74 | 0.746972E+10 | 0.399142E+10 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 26679.21 | 03-DEC-08:61 | 19119.32 | 25-DEC-08:62 | 12804.43 | 10-DEC-08:62 | 5704.98 | 03-DEC-08:61 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.151465E+12 | 0.363961E+11 | 4305.65 | 0.993606E+11 | 0.521039E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.946612E+10 | 0.230426E+10 | 323.24 | 0.614620E+10 | 0.295335E+10 | 0.00 | 1.00 | 0.00 | 26202.94 | 16061.40 | 11293.79 | 5506.52 | 0.00 | |||||||
Maximum of Months | 0.157470E+11 | 0.381381E+10 | 375.06 | 0.103820E+11 | 0.567642E+10 | 0.00 | 1.00 | 0.00 | 27277.90 | 19119.32 | 15037.00 | 5789.73 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.160407E+11 | 0.396265E+10 | 350.64 | 0.107454E+11 | 0.529533E+10 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 45372.24 | 01-JAN-09:02 | 31159.92 | 12-JAN-08:62 | 20510.92 | 02-JAN-08:04 | 9861.93 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.170794E+11 | 0.409487E+10 | 317.01 | 0.102077E+11 | 0.687175E+10 | 0.00 | 1.00 | 04-FEB-08:62 | 0.00 | 01-FEB-00:05 | 46322.99 | 18-FEB-08:62 | 28237.47 | 13-FEB-08:62 | 24534.97 | 17-FEB-08:62 | 9867.58 | 18-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.180020E+11 | 0.442269E+10 | 356.91 | 0.117907E+11 | 0.621121E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 45973.84 | 13-MAR-07:02 | 29178.34 | 19-MAR-08:62 | 23571.30 | 13-MAR-07:02 | 9676.32 | 13-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.167377E+11 | 0.415916E+10 | 339.71 | 0.113039E+11 | 0.543377E+10 | 0.00 | 1.00 | 07-APR-07:03 | 0.00 | 01-APR-00:05 | 45223.76 | 24-APR-07:03 | 28794.69 | 07-APR-07:03 | 21348.54 | 24-APR-07:03 | 9763.68 | 09-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.224042E+11 | 0.546820E+10 | 359.70 | 0.146308E+11 | 0.777343E+10 | 0.00 | 1.00 | 01-MAY-07:03 | 0.00 | 01-MAY-00:10 | 46029.35 | 15-MAY-07:02 | 30363.90 | 31-MAY-07:03 | 23682.83 | 15-MAY-07:02 | 10018.01 | 14-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.228875E+11 | 0.554680E+10 | 353.59 | 0.147520E+11 | 0.813554E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 45249.64 | 18-JUN-08:61 | 28292.70 | 27-JUN-07:02 | 19214.97 | 25-JUN-08:03 | 10081.77 | 18-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.267332E+11 | 0.649264E+10 | 354.96 | 0.170796E+11 | 0.965359E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 46742.92 | 23-JUL-08:61 | 29111.35 | 04-JUL-08:61 | 23677.69 | 23-JUL-08:03 | 10151.39 | 23-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.279121E+11 | 0.684355E+10 | 366.66 | 0.180445E+11 | 0.986755E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 46282.16 | 20-AUG-08:61 | 28443.58 | 23-AUG-07:02 | 22224.75 | 20-AUG-08:04 | 10238.54 | 20-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.270186E+11 | 0.649111E+10 | 346.65 | 0.166530E+11 | 0.103655E+11 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 47012.40 | 25-SEP-07:02 | 28327.35 | 19-SEP-07:02 | 26201.30 | 25-SEP-07:02 | 10345.72 | 03-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.271398E+11 | 0.659265E+10 | 355.61 | 0.172629E+11 | 0.987689E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:05 | 46014.49 | 10-OCT-07:02 | 27930.44 | 28-OCT-07:02 | 24027.61 | 23-OCT-07:03 | 10170.11 | 08-OCT-08:62 | 0.00 | 01-OCT-00:05 |
November | 0.223204E+11 | 0.538230E+10 | 346.26 | 0.141225E+11 | 0.819791E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 45818.91 | 24-NOV-08:62 | 29866.41 | 15-NOV-08:62 | 21798.57 | 24-NOV-08:03 | 10125.11 | 23-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.197214E+11 | 0.476191E+10 | 350.66 | 0.124989E+11 | 0.722249E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 46218.15 | 03-DEC-09:01 | 32881.07 | 20-DEC-08:62 | 22446.17 | 03-DEC-09:04 | 10012.63 | 03-DEC-09:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.263997E+12 | 0.642185E+11 | 4198.37 | 0.169092E+12 | 0.949050E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.160407E+11 | 0.396265E+10 | 317.01 | 0.102077E+11 | 0.529533E+10 | 0.00 | 1.00 | 0.00 | 45223.76 | 27930.44 | 19214.97 | 9676.32 | 0.00 | |||||||
Maximum of Months | 0.279121E+11 | 0.684355E+10 | 366.66 | 0.180445E+11 | 0.103655E+11 | 0.00 | 1.00 | 0.00 | 47012.40 | 32881.07 | 26201.30 | 10345.72 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.824843E+10 | 0.200572E+10 | 350.80 | 0.553245E+10 | 0.271598E+10 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 23637.41 | 01-JAN-09:02 | 16264.65 | 12-JAN-08:62 | 10678.55 | 01-JAN-09:02 | 5046.15 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.878277E+10 | 0.207264E+10 | 317.21 | 0.525403E+10 | 0.352874E+10 | 0.00 | 1.00 | 05-FEB-09:02 | 0.00 | 01-FEB-00:05 | 24113.38 | 18-FEB-08:62 | 14433.48 | 13-FEB-08:62 | 12744.24 | 17-FEB-08:62 | 5048.61 | 18-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.926185E+10 | 0.223945E+10 | 356.91 | 0.607159E+10 | 0.319026E+10 | 0.00 | 1.00 | 02-MAR-08:62 | 0.00 | 01-MAR-00:05 | 23963.87 | 13-MAR-07:02 | 15200.76 | 19-MAR-08:62 | 12323.27 | 13-MAR-07:02 | 4951.70 | 13-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.861415E+10 | 0.210670E+10 | 339.91 | 0.582364E+10 | 0.279052E+10 | 0.00 | 1.00 | 07-APR-07:03 | 0.00 | 01-APR-00:05 | 23563.33 | 24-APR-07:03 | 15020.01 | 07-APR-07:03 | 11135.26 | 24-APR-07:03 | 4995.90 | 09-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.115605E+11 | 0.277702E+10 | 360.69 | 0.755520E+10 | 0.400527E+10 | 0.00 | 1.00 | 01-MAY-07:03 | 0.00 | 01-MAY-00:10 | 23994.16 | 15-MAY-07:02 | 15255.71 | 31-MAY-07:03 | 12398.07 | 15-MAY-07:02 | 5125.84 | 14-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.118005E+11 | 0.281525E+10 | 355.38 | 0.761299E+10 | 0.418747E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 23568.43 | 18-JUN-08:61 | 14769.55 | 27-JUN-07:02 | 10020.46 | 25-JUN-08:03 | 5158.38 | 18-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.138190E+11 | 0.330394E+10 | 355.99 | 0.883599E+10 | 0.498305E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 24349.02 | 23-JUL-08:61 | 15148.05 | 04-JUL-08:61 | 12383.57 | 23-JUL-08:03 | 5193.93 | 23-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.144316E+11 | 0.348357E+10 | 367.71 | 0.933717E+10 | 0.509438E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24111.06 | 20-AUG-08:61 | 14831.38 | 23-AUG-07:02 | 11617.72 | 20-AUG-08:04 | 5238.51 | 20-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.139563E+11 | 0.330038E+10 | 347.17 | 0.860935E+10 | 0.534693E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 24513.97 | 25-SEP-07:02 | 14804.84 | 19-SEP-07:02 | 13744.65 | 25-SEP-07:02 | 5293.29 | 03-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.140389E+11 | 0.335663E+10 | 355.88 | 0.893724E+10 | 0.510168E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:05 | 23990.98 | 10-OCT-07:02 | 14584.77 | 28-OCT-07:02 | 12553.50 | 23-OCT-07:03 | 5203.47 | 08-OCT-08:62 | 0.00 | 01-OCT-00:05 |
November | 0.115125E+11 | 0.273264E+10 | 346.60 | 0.729284E+10 | 0.421967E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 23873.75 | 24-NOV-08:62 | 15572.77 | 15-NOV-08:62 | 11390.03 | 24-NOV-08:03 | 5180.25 | 23-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.101589E+11 | 0.241459E+10 | 351.12 | 0.644666E+10 | 0.371229E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 24069.67 | 03-DEC-09:01 | 17164.15 | 20-DEC-08:62 | 11704.81 | 03-DEC-09:04 | 5122.91 | 03-DEC-09:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.136185E+12 | 0.326085E+11 | 4205.38 | 0.873091E+11 | 0.488762E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.824843E+10 | 0.200572E+10 | 317.21 | 0.525403E+10 | 0.271598E+10 | 0.00 | 1.00 | 0.00 | 23563.33 | 14433.48 | 10020.46 | 4951.70 | 0.00 | |||||||
Maximum of Months | 0.144316E+11 | 0.348357E+10 | 367.71 | 0.933717E+10 | 0.534693E+10 | 0.00 | 1.00 | 0.00 | 24513.97 | 17164.15 | 13744.65 | 5293.29 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.817138E+10 | 0.198772E+10 | 350.64 | 0.547229E+10 | 0.269910E+10 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 23526.04 | 01-JAN-09:02 | 16157.03 | 12-JAN-08:62 | 10650.19 | 01-JAN-09:02 | 5022.72 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.870527E+10 | 0.205482E+10 | 316.74 | 0.519726E+10 | 0.350801E+10 | 0.00 | 1.00 | 05-FEB-09:02 | 0.00 | 01-FEB-00:05 | 24003.90 | 18-FEB-08:62 | 13836.40 | 13-FEB-08:62 | 12721.36 | 17-FEB-08:62 | 5025.27 | 18-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.918239E+10 | 0.222078E+10 | 356.74 | 0.601030E+10 | 0.317210E+10 | 0.00 | 1.00 | 02-MAR-08:62 | 0.00 | 01-MAR-00:05 | 23850.32 | 13-MAR-07:02 | 15106.61 | 19-MAR-08:62 | 12287.01 | 13-MAR-07:02 | 4928.69 | 13-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.854560E+10 | 0.209042E+10 | 339.75 | 0.576945E+10 | 0.277614E+10 | 0.00 | 1.00 | 09-APR-08:62 | 0.00 | 01-APR-00:05 | 23452.22 | 24-APR-07:03 | 14769.59 | 16-APR-08:62 | 11104.90 | 24-APR-07:03 | 4972.63 | 09-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.114921E+11 | 0.276064E+10 | 360.67 | 0.750049E+10 | 0.399165E+10 | 0.00 | 1.00 | 04-MAY-07:02 | 0.00 | 01-MAY-00:10 | 23881.11 | 15-MAY-07:02 | 15083.52 | 23-MAY-07:03 | 12360.33 | 15-MAY-07:02 | 5102.08 | 14-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.117331E+11 | 0.279919E+10 | 355.32 | 0.755921E+10 | 0.417389E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 23457.37 | 18-JUN-08:61 | 14671.00 | 27-JUN-07:02 | 9993.52 | 25-JUN-08:03 | 5134.46 | 18-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.137536E+11 | 0.328788E+10 | 355.66 | 0.878316E+10 | 0.497046E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 24235.10 | 23-JUL-08:61 | 15054.15 | 04-JUL-08:61 | 12343.67 | 23-JUL-08:03 | 5169.89 | 23-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.143673E+11 | 0.346762E+10 | 367.82 | 0.928468E+10 | 0.508258E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 23999.12 | 20-AUG-08:61 | 14737.83 | 23-AUG-07:02 | 11576.18 | 20-AUG-08:04 | 5214.28 | 20-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.138896E+11 | 0.328419E+10 | 347.17 | 0.855663E+10 | 0.533299E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 24398.84 | 25-SEP-07:02 | 14704.39 | 19-SEP-07:02 | 13695.10 | 25-SEP-07:02 | 5268.81 | 03-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.139715E+11 | 0.334012E+10 | 355.85 | 0.888304E+10 | 0.508851E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:05 | 23877.96 | 10-OCT-07:02 | 14482.45 | 28-OCT-07:02 | 12512.67 | 23-OCT-07:03 | 5179.40 | 08-OCT-08:62 | 0.00 | 01-OCT-00:05 |
November | 0.114379E+11 | 0.271511E+10 | 346.40 | 0.723473E+10 | 0.420319E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 23761.07 | 24-NOV-08:62 | 15468.80 | 15-NOV-08:62 | 11357.69 | 24-NOV-08:03 | 5156.30 | 23-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.100820E+11 | 0.239676E+10 | 351.03 | 0.638691E+10 | 0.369506E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 23956.87 | 03-DEC-09:01 | 17052.54 | 20-DEC-08:62 | 11667.61 | 03-DEC-09:04 | 5099.21 | 03-DEC-09:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.135332E+12 | 0.324052E+11 | 4203.79 | 0.866382E+11 | 0.486937E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.817138E+10 | 0.198772E+10 | 316.74 | 0.519726E+10 | 0.269910E+10 | 0.00 | 1.00 | 0.00 | 23452.22 | 13836.40 | 9993.52 | 4928.69 | 0.00 | |||||||
Maximum of Months | 0.143673E+11 | 0.346762E+10 | 367.82 | 0.928468E+10 | 0.533299E+10 | 0.00 | 1.00 | 0.00 | 24398.84 | 17052.54 | 13695.10 | 5268.81 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.807566E+10 | 0.196661E+10 | 350.19 | 0.540390E+10 | 0.267176E+10 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 23531.87 | 01-JAN-09:02 | 16115.56 | 12-JAN-08:62 | 10695.57 | 01-JAN-09:02 | 5025.55 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.859571E+10 | 0.203119E+10 | 316.24 | 0.512362E+10 | 0.347209E+10 | 0.00 | 1.00 | 05-FEB-09:02 | 0.00 | 01-FEB-00:05 | 24014.80 | 18-FEB-08:62 | 13651.63 | 05-FEB-09:02 | 12803.14 | 17-FEB-08:62 | 5028.42 | 18-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.908095E+10 | 0.219845E+10 | 355.41 | 0.593959E+10 | 0.314136E+10 | 0.00 | 1.00 | 02-MAR-08:62 | 0.00 | 01-MAR-00:05 | 23858.95 | 13-MAR-07:02 | 15078.49 | 19-MAR-08:62 | 12328.01 | 13-MAR-07:02 | 4931.56 | 13-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.848739E+10 | 0.207751E+10 | 339.58 | 0.572826E+10 | 0.275913E+10 | 0.00 | 1.00 | 09-APR-08:62 | 0.00 | 01-APR-00:05 | 23459.14 | 24-APR-07:03 | 14461.17 | 16-APR-08:62 | 11146.77 | 24-APR-07:03 | 4975.17 | 09-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.114820E+11 | 0.275867E+10 | 360.81 | 0.749423E+10 | 0.398777E+10 | 0.00 | 1.00 | 04-MAY-07:02 | 0.00 | 01-MAY-00:10 | 23889.67 | 15-MAY-07:02 | 14779.78 | 23-MAY-07:03 | 12396.14 | 15-MAY-07:02 | 5105.10 | 14-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.117297E+11 | 0.279869E+10 | 355.30 | 0.755806E+10 | 0.417165E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 23466.44 | 18-JUN-08:61 | 14648.60 | 27-JUN-07:02 | 10023.73 | 25-JUN-08:03 | 5137.58 | 18-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.137756E+11 | 0.329340E+10 | 356.06 | 0.880118E+10 | 0.497439E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 24246.35 | 23-JUL-08:61 | 15037.61 | 04-JUL-08:61 | 12368.34 | 23-JUL-08:03 | 5173.17 | 23-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.144069E+11 | 0.347723E+10 | 368.05 | 0.931569E+10 | 0.509122E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24010.11 | 20-AUG-08:61 | 14719.50 | 23-AUG-07:02 | 11596.48 | 20-AUG-08:04 | 5217.60 | 20-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.139032E+11 | 0.328783E+10 | 347.03 | 0.856787E+10 | 0.533534E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 24410.86 | 25-SEP-07:02 | 14686.37 | 19-SEP-07:02 | 13717.94 | 25-SEP-07:02 | 5272.16 | 03-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.139848E+11 | 0.334366E+10 | 355.95 | 0.889430E+10 | 0.509049E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:05 | 23889.14 | 10-OCT-07:02 | 14461.94 | 28-OCT-07:02 | 12542.89 | 23-OCT-07:03 | 5182.70 | 08-OCT-08:62 | 0.00 | 01-OCT-00:05 |
November | 0.113933E+11 | 0.270615E+10 | 346.85 | 0.720408E+10 | 0.418922E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 23769.17 | 24-NOV-08:62 | 15420.96 | 15-NOV-08:62 | 11391.39 | 24-NOV-08:03 | 5159.37 | 23-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.100080E+11 | 0.238099E+10 | 351.19 | 0.633484E+10 | 0.367315E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 23966.31 | 03-DEC-09:01 | 17010.91 | 20-DEC-08:62 | 11699.51 | 03-DEC-09:04 | 5102.45 | 03-DEC-09:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.134923E+12 | 0.323204E+11 | 4202.64 | 0.863656E+11 | 0.485576E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.807566E+10 | 0.196661E+10 | 316.24 | 0.512362E+10 | 0.267176E+10 | 0.00 | 1.00 | 0.00 | 23459.14 | 13651.63 | 10023.73 | 4931.56 | 0.00 | |||||||
Maximum of Months | 0.144069E+11 | 0.347723E+10 | 368.05 | 0.931569E+10 | 0.533534E+10 | 0.00 | 1.00 | 0.00 | 24410.86 | 17010.91 | 13717.94 | 5272.16 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.899519E+10 | 0.218964E+10 | 351.47 | 0.616736E+10 | 0.282783E+10 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 25945.90 | 02-JAN-08:62 | 15125.41 | 08-JAN-09:02 | 11973.83 | 31-JAN-08:62 | 5545.19 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.931120E+10 | 0.220818E+10 | 315.65 | 0.569361E+10 | 0.361759E+10 | 0.00 | 1.00 | 17-FEB-08:62 | 0.00 | 01-FEB-00:05 | 26887.43 | 18-FEB-08:62 | 13354.96 | 26-FEB-09:02 | 15463.05 | 18-FEB-08:62 | 5548.33 | 18-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.998689E+10 | 0.242058E+10 | 353.83 | 0.669133E+10 | 0.329556E+10 | 0.00 | 1.00 | 02-MAR-08:62 | 0.00 | 01-MAR-00:05 | 26381.28 | 13-MAR-07:02 | 14983.56 | 02-MAR-08:62 | 13696.55 | 13-MAR-07:02 | 5444.37 | 13-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.968753E+10 | 0.236394E+10 | 340.48 | 0.669860E+10 | 0.298894E+10 | 0.00 | 1.00 | 09-APR-08:62 | 0.00 | 01-APR-00:05 | 25496.82 | 09-APR-08:62 | 15632.49 | 10-APR-07:02 | 10298.98 | 24-APR-07:03 | 5500.62 | 09-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.131899E+11 | 0.316275E+10 | 361.59 | 0.884707E+10 | 0.434288E+10 | 0.00 | 1.00 | 04-MAY-07:02 | 0.00 | 01-MAY-00:10 | 26365.02 | 15-MAY-07:02 | 16336.23 | 30-MAY-07:03 | 13528.95 | 15-MAY-07:02 | 5637.04 | 14-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.134658E+11 | 0.320698E+10 | 356.27 | 0.890892E+10 | 0.455683E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 26027.37 | 25-JUN-08:61 | 16263.28 | 04-JUN-08:62 | 11755.38 | 14-JUN-07:02 | 5671.84 | 18-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.157587E+11 | 0.376778E+10 | 356.64 | 0.103469E+11 | 0.541174E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 26922.31 | 23-JUL-08:61 | 16271.21 | 04-JUL-08:61 | 13994.37 | 20-JUL-07:03 | 5708.96 | 23-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.165726E+11 | 0.399938E+10 | 369.03 | 0.110153E+11 | 0.555733E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 26650.46 | 20-AUG-08:61 | 15635.12 | 23-AUG-07:02 | 12784.22 | 20-AUG-08:04 | 5758.29 | 20-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.155848E+11 | 0.369382E+10 | 348.09 | 0.986237E+10 | 0.572241E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 26962.66 | 25-SEP-07:02 | 15859.75 | 19-SEP-07:02 | 15058.77 | 25-SEP-07:02 | 5818.83 | 03-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.158350E+11 | 0.379190E+10 | 356.19 | 0.103605E+11 | 0.547444E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:05 | 26429.67 | 10-OCT-07:02 | 15591.55 | 28-OCT-07:02 | 13624.54 | 10-OCT-07:03 | 5719.66 | 08-OCT-08:03 | 0.00 | 01-OCT-00:05 |
November | 0.126517E+11 | 0.300994E+10 | 348.09 | 0.819449E+10 | 0.445725E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 26291.68 | 24-NOV-08:62 | 17055.82 | 15-NOV-08:62 | 12652.32 | 24-NOV-08:03 | 5704.12 | 23-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.110676E+11 | 0.263754E+10 | 351.36 | 0.718157E+10 | 0.388605E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 26565.41 | 03-DEC-09:01 | 18709.23 | 24-DEC-09:02 | 12974.44 | 03-DEC-09:04 | 5631.06 | 03-DEC-09:03 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.152107E+12 | 0.364524E+11 | 4208.69 | 0.999681E+11 | 0.521388E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.899519E+10 | 0.218964E+10 | 315.65 | 0.569361E+10 | 0.282783E+10 | 0.00 | 1.00 | 0.00 | 25496.82 | 13354.96 | 10298.98 | 5444.37 | 0.00 | |||||||
Maximum of Months | 0.165726E+11 | 0.399938E+10 | 369.03 | 0.110153E+11 | 0.572241E+10 | 0.00 | 1.00 | 0.00 | 26962.66 | 18709.23 | 15463.05 | 5818.83 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.80 | 26.09 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.12 | 24.72 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.17 | 24.31 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.56 | 20.28 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.29 | 14.69 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.76 | 11.32 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.37 | 8.21 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.43 | 9.45 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.96 | 8.51 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.38 | 14.09 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.49 | 16.93 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.64 | 19.96 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.16 | 16.50 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.56 | 8.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.64 | 26.09 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.80 | 26.09 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.12 | 24.72 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.17 | 24.31 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.56 | 20.28 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.29 | 14.69 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.76 | 11.32 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.37 | 8.21 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.43 | 9.45 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.96 | 8.51 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.38 | 14.09 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.49 | 16.93 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.64 | 19.96 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.16 | 16.50 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.56 | 8.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.64 | 26.09 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.80 | 26.09 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.12 | 24.72 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.17 | 24.31 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.56 | 20.28 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.29 | 14.69 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.76 | 11.32 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.37 | 8.21 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.43 | 9.45 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.96 | 8.51 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.38 | 14.09 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.49 | 16.93 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.64 | 19.96 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.16 | 16.50 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.56 | 8.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.64 | 26.09 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.80 | 26.09 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.12 | 24.72 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.17 | 24.31 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.56 | 20.28 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.29 | 14.69 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.76 | 11.32 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.37 | 8.21 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.43 | 9.45 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.96 | 8.51 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.38 | 14.09 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.49 | 16.93 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.64 | 19.96 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.16 | 16.50 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.56 | 8.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.64 | 26.09 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.84 | 57.67 | 34.17 | 148.63 | 31.27 | 0.00 | 0.00 | 744.00 |
February | 77.79 | 41.47 | 36.32 | 123.80 | 29.61 | 0.00 | 0.00 | 672.00 |
March | 56.44 | 19.34 | 37.10 | 86.59 | 29.12 | 0.00 | 0.00 | 744.00 |
April | 36.49 | 3.51 | 32.98 | 53.42 | 24.32 | 0.00 | 0.00 | 720.00 |
May | 30.89 | 0.08 | 30.81 | 54.20 | 17.65 | 0.00 | 0.00 | 744.00 |
June | 30.55 | 0.00 | 30.55 | 53.55 | 13.63 | 0.00 | 0.00 | 720.00 |
July | 29.63 | 0.08 | 29.55 | 57.82 | 9.91 | 0.00 | 0.00 | 744.00 |
August | 32.41 | 1.99 | 30.42 | 61.48 | 11.40 | 0.00 | 0.00 | 744.00 |
September | 48.98 | 11.89 | 37.09 | 84.98 | 10.26 | 0.00 | 0.00 | 720.00 |
October | 69.44 | 33.53 | 35.91 | 123.93 | 16.94 | 0.00 | 0.00 | 744.00 |
November | 87.68 | 50.26 | 37.42 | 149.39 | 20.34 | 0.00 | 0.00 | 720.00 |
December | 94.88 | 61.13 | 33.75 | 156.83 | 23.96 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 57.15 | 23.34 | 33.81 | 96.11 | 19.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.63 | 0.00 | 29.55 | 53.42 | 9.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.88 | 61.13 | 37.42 | 156.83 | 31.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.84 | 57.67 | 34.17 | 148.63 | 31.27 | 0.00 | 0.00 | 744.00 |
February | 77.79 | 41.47 | 36.32 | 123.80 | 29.61 | 0.00 | 0.00 | 672.00 |
March | 56.44 | 19.34 | 37.10 | 86.59 | 29.12 | 0.00 | 0.00 | 744.00 |
April | 36.49 | 3.51 | 32.98 | 53.42 | 24.32 | 0.00 | 0.00 | 720.00 |
May | 30.89 | 0.08 | 30.81 | 54.20 | 17.65 | 0.00 | 0.00 | 744.00 |
June | 30.55 | 0.00 | 30.55 | 53.55 | 13.63 | 0.00 | 0.00 | 720.00 |
July | 29.63 | 0.08 | 29.55 | 57.82 | 9.91 | 0.00 | 0.00 | 744.00 |
August | 32.41 | 1.99 | 30.42 | 61.48 | 11.40 | 0.00 | 0.00 | 744.00 |
September | 48.98 | 11.89 | 37.09 | 84.98 | 10.26 | 0.00 | 0.00 | 720.00 |
October | 69.44 | 33.53 | 35.91 | 123.93 | 16.94 | 0.00 | 0.00 | 744.00 |
November | 87.68 | 50.26 | 37.42 | 149.39 | 20.34 | 0.00 | 0.00 | 720.00 |
December | 94.88 | 61.13 | 33.75 | 156.83 | 23.96 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 57.15 | 23.34 | 33.81 | 96.11 | 19.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.63 | 0.00 | 29.55 | 53.42 | 9.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.88 | 61.13 | 37.42 | 156.83 | 31.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.57 | 26.41 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.00 | 24.97 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.21 | 24.55 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.69 | 20.44 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.58 | 14.75 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 45.12 | 11.25 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.87 | 8.07 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.98 | 9.27 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 71.50 | 8.25 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.63 | 14.06 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.50 | 16.94 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.48 | 20.11 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.34 | 16.55 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.69 | 8.07 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.48 | 26.41 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.57 | 26.41 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.00 | 24.97 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.21 | 24.55 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.69 | 20.44 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.58 | 14.75 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 45.12 | 11.25 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.87 | 8.07 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.98 | 9.27 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 71.50 | 8.25 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.63 | 14.06 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.50 | 16.94 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.48 | 20.11 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.34 | 16.55 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.69 | 8.07 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.48 | 26.41 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.84 | 57.67 | 34.17 | 148.37 | 31.65 | 0.00 | 0.00 | 744.00 |
February | 77.79 | 41.47 | 36.32 | 123.67 | 29.90 | 0.00 | 0.00 | 672.00 |
March | 56.44 | 19.34 | 37.10 | 86.65 | 29.40 | 0.00 | 0.00 | 744.00 |
April | 36.49 | 3.51 | 32.98 | 53.58 | 24.51 | 0.00 | 0.00 | 720.00 |
May | 30.89 | 0.08 | 30.81 | 54.54 | 17.71 | 0.00 | 0.00 | 744.00 |
June | 30.55 | 0.00 | 30.55 | 53.99 | 13.54 | 0.00 | 0.00 | 720.00 |
July | 29.63 | 0.08 | 29.55 | 58.42 | 9.73 | 0.00 | 0.00 | 744.00 |
August | 32.41 | 1.99 | 30.42 | 62.14 | 11.18 | 0.00 | 0.00 | 744.00 |
September | 48.98 | 11.89 | 37.09 | 85.63 | 9.96 | 0.00 | 0.00 | 720.00 |
October | 69.44 | 33.53 | 35.91 | 124.23 | 16.91 | 0.00 | 0.00 | 744.00 |
November | 87.68 | 50.26 | 37.42 | 149.42 | 20.36 | 0.00 | 0.00 | 720.00 |
December | 94.88 | 61.13 | 33.75 | 156.66 | 24.14 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 57.15 | 23.34 | 33.81 | 96.34 | 19.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.63 | 0.00 | 29.55 | 53.58 | 9.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.88 | 61.13 | 37.42 | 156.66 | 31.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.69 | 27.98 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 102.99 | 26.54 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.07 | 26.04 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.63 | 21.97 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.45 | 16.59 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 45.02 | 13.19 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.51 | 10.29 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.78 | 11.45 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.90 | 10.47 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.37 | 16.35 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.59 | 18.92 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.62 | 21.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.21 | 18.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.63 | 10.29 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.62 | 27.98 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.69 | 27.98 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 102.99 | 26.54 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.07 | 26.04 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.63 | 21.97 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.45 | 16.59 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 45.02 | 13.19 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.51 | 10.29 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.78 | 11.45 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.90 | 10.47 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.37 | 16.35 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.59 | 18.92 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.62 | 21.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.21 | 18.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.63 | 10.29 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.62 | 27.98 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 147.69 | 33.29 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 122.99 | 31.56 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 86.02 | 30.97 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 53.21 | 26.15 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 54.09 | 19.75 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 53.57 | 15.73 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 57.68 | 12.28 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 61.57 | 13.66 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 84.47 | 12.50 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 123.26 | 19.49 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 148.70 | 22.54 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 155.96 | 26.14 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 95.66 | 21.96 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 53.21 | 12.28 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 155.96 | 33.29 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.71 | 27.91 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.01 | 26.49 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.09 | 26.01 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.65 | 21.93 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.44 | 16.64 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 45.01 | 13.26 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.48 | 10.44 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.76 | 11.58 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.86 | 10.66 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.34 | 16.50 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.59 | 18.96 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.63 | 21.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.21 | 18.49 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.65 | 10.44 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.63 | 27.91 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.71 | 27.91 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.01 | 26.49 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.09 | 26.01 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.65 | 21.93 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.44 | 16.64 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 45.01 | 13.26 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.48 | 10.44 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.76 | 11.58 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.86 | 10.66 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.34 | 16.50 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.59 | 18.96 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.63 | 21.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.21 | 18.49 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.65 | 10.44 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.63 | 27.91 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 147.72 | 33.21 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 123.01 | 31.50 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 86.03 | 30.94 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 53.23 | 26.10 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 54.09 | 19.81 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 53.56 | 15.81 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 57.65 | 12.46 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 61.54 | 13.82 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 84.42 | 12.72 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 123.22 | 19.66 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 148.69 | 22.59 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 155.97 | 26.13 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 95.66 | 22.02 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 53.23 | 12.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 155.97 | 33.21 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.82 | 27.54 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.14 | 26.11 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.21 | 25.63 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.77 | 21.56 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.56 | 16.30 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 45.13 | 12.93 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.59 | 10.13 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.87 | 11.25 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.96 | 10.33 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.44 | 16.16 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.70 | 18.63 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.74 | 21.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.32 | 18.14 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.77 | 10.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.74 | 27.54 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.82 | 27.54 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.14 | 26.11 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.21 | 25.63 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.77 | 21.56 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.56 | 16.30 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 45.13 | 12.93 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.59 | 10.13 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.87 | 11.25 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.96 | 10.33 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.44 | 16.16 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.70 | 18.63 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.74 | 21.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.32 | 18.14 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.77 | 10.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.74 | 27.54 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 147.86 | 32.78 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 123.17 | 31.06 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 86.18 | 30.48 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 53.38 | 25.66 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 54.23 | 19.41 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 53.71 | 15.42 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 57.78 | 12.09 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 61.67 | 13.42 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 84.55 | 12.34 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 123.34 | 19.27 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 148.83 | 22.20 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 156.11 | 25.72 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 95.80 | 21.61 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 53.38 | 12.09 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 156.11 | 32.78 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.99 | 26.44 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.39 | 25.00 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.42 | 24.50 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.85 | 20.48 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.47 | 15.24 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.95 | 11.86 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.31 | 9.13 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.62 | 10.14 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.82 | 9.35 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.36 | 15.13 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.68 | 17.60 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.83 | 20.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.30 | 17.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.85 | 9.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.83 | 26.44 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.99 | 26.44 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.39 | 25.00 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.42 | 24.50 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.85 | 20.48 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.47 | 15.24 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.95 | 11.86 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.31 | 9.13 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.62 | 10.14 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.82 | 9.35 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.36 | 15.13 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.68 | 17.60 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.83 | 20.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.30 | 17.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.85 | 9.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.83 | 26.44 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.99 | 26.44 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.39 | 25.00 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.42 | 24.50 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.85 | 20.48 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.47 | 15.24 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.95 | 11.86 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.31 | 9.13 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.62 | 10.14 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.82 | 9.35 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.36 | 15.13 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.68 | 17.60 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.83 | 20.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.30 | 17.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.85 | 9.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.83 | 26.44 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.99 | 26.44 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.39 | 25.00 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.42 | 24.50 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.85 | 20.48 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.47 | 15.24 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.95 | 11.86 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.31 | 9.13 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.62 | 10.14 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.82 | 9.35 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.36 | 15.13 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.68 | 17.60 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.83 | 20.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.30 | 17.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.85 | 9.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.83 | 26.44 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 148.07 | 31.47 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 123.46 | 29.74 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 86.44 | 29.14 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 53.49 | 24.38 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 54.14 | 18.15 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 53.52 | 14.15 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 57.47 | 10.90 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 61.40 | 12.11 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 84.39 | 11.17 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 123.26 | 18.04 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 148.81 | 20.99 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 156.22 | 24.45 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 95.78 | 20.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 53.49 | 10.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 156.22 | 31.47 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 148.07 | 31.47 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 123.46 | 29.74 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 86.44 | 29.14 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 53.49 | 24.38 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 54.14 | 18.15 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 53.52 | 14.15 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 57.47 | 10.90 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 61.40 | 12.11 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 84.39 | 11.17 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 123.26 | 18.04 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 148.81 | 20.99 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 156.22 | 24.45 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 95.78 | 20.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 53.49 | 10.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 156.22 | 31.47 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.95 | 26.11 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.38 | 24.65 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.52 | 24.14 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 45.03 | 20.12 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.74 | 14.86 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 45.25 | 11.43 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.67 | 8.69 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.98 | 9.69 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 71.11 | 8.89 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.53 | 14.69 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.72 | 17.17 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.79 | 20.12 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.46 | 16.67 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 45.03 | 8.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.79 | 26.11 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.95 | 26.11 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.38 | 24.65 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.52 | 24.14 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 45.03 | 20.12 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.74 | 14.86 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 45.25 | 11.43 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.67 | 8.69 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.98 | 9.69 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 71.11 | 8.89 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.53 | 14.69 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.72 | 17.17 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.79 | 20.12 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.46 | 16.67 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 45.03 | 8.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.79 | 26.11 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 148.04 | 31.07 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 123.47 | 29.32 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 86.57 | 28.71 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 53.71 | 23.95 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 54.46 | 17.70 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 53.88 | 13.64 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 57.90 | 10.38 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 61.83 | 11.58 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 84.74 | 10.62 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 123.47 | 17.51 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 148.88 | 20.47 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 156.20 | 23.97 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 95.99 | 19.86 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 53.71 | 10.38 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 156.20 | 31.07 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 124.01 | 25.99 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.44 | 24.52 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.57 | 24.02 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 45.08 | 20.01 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.79 | 14.77 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 45.31 | 11.34 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.72 | 8.61 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 52.03 | 9.61 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 71.16 | 8.80 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.58 | 14.59 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.78 | 17.07 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.85 | 20.01 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.52 | 16.57 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 45.08 | 8.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.85 | 25.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 124.01 | 25.99 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.44 | 24.52 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.57 | 24.02 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 45.08 | 20.01 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.79 | 14.77 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 45.31 | 11.34 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.72 | 8.61 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 52.03 | 9.61 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 71.16 | 8.80 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.58 | 14.59 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.78 | 17.07 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.85 | 20.01 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.52 | 16.57 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 45.08 | 8.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.85 | 25.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 148.11 | 30.93 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 123.55 | 29.17 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 86.64 | 28.57 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 53.77 | 23.82 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 54.53 | 17.59 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 53.95 | 13.54 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 57.96 | 10.28 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 61.89 | 11.48 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 84.80 | 10.51 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 123.53 | 17.40 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 148.95 | 20.35 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 156.27 | 23.84 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 96.06 | 19.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 53.77 | 10.28 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 156.27 | 30.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 124.05 | 25.82 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.49 | 24.33 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.60 | 23.85 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 45.08 | 19.88 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.76 | 14.72 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 45.27 | 11.31 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.66 | 8.62 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.95 | 9.64 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 71.10 | 8.82 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.53 | 14.59 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.78 | 16.98 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.88 | 19.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.51 | 16.50 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 45.08 | 8.62 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.88 | 25.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 124.05 | 25.82 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.49 | 24.33 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.60 | 23.85 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 45.08 | 19.88 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 45.76 | 14.72 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 45.27 | 11.31 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 48.66 | 8.62 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 51.95 | 9.64 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 71.10 | 8.82 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 103.53 | 14.59 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.78 | 16.98 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.88 | 19.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 80.51 | 16.50 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 45.08 | 8.62 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.88 | 25.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 148.16 | 30.73 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 123.61 | 28.94 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 86.67 | 28.37 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 53.78 | 23.68 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 54.49 | 17.53 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 53.90 | 13.50 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 57.89 | 10.30 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 61.80 | 11.52 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 84.73 | 10.54 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 123.47 | 17.40 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 148.96 | 20.25 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 156.30 | 23.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 96.04 | 19.66 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 53.78 | 10.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 156.30 | 30.73 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.60 | 25.36 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.13 | 23.79 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.08 | 23.37 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.33 | 19.61 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 44.72 | 14.82 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.20 | 11.52 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 47.44 | 9.07 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 50.64 | 10.19 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.06 | 9.37 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 102.47 | 15.04 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.11 | 17.01 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.34 | 19.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 79.67 | 16.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.20 | 9.07 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.34 | 25.36 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 123.60 | 25.36 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 103.13 | 23.79 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 72.08 | 23.37 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.33 | 19.61 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 44.72 | 14.82 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 44.20 | 11.52 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 47.44 | 9.07 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 50.64 | 10.19 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 70.06 | 9.37 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 102.47 | 15.04 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 124.11 | 17.01 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 130.34 | 19.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 79.67 | 16.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 44.20 | 9.07 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 130.34 | 25.36 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 147.61 | 30.19 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 123.17 | 28.31 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 86.04 | 27.81 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 52.86 | 23.36 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 53.23 | 17.67 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 52.61 | 13.76 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 56.41 | 10.84 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 60.22 | 12.18 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 83.48 | 11.20 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 122.18 | 17.94 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 148.13 | 20.29 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 155.64 | 23.47 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 95.02 | 19.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 52.61 | 10.84 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 155.64 | 30.19 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.331581E+09 | 69871004.38 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.249459E+09 | 59793421.12 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193290E+09 | 65101009.16 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.115501E+09 | 52553393.57 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.121306E+09 | 39355732.17 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116012E+09 | 29334671.10 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.129551E+09 | 21983335.50 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.137745E+09 | 25319083.87 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183917E+09 | 22046738.50 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276889E+09 | 37737887.88 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322685E+09 | 43873386.98 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349911E+09 | 53456211.36 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.252785E+10 | 0.520426E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.115501E+09 | 21983335.50 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349911E+09 | 69871004.38 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.331581E+09 | 69871004.38 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.249459E+09 | 59793421.12 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193290E+09 | 65101009.16 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.115501E+09 | 52553393.57 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.121306E+09 | 39355732.17 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116012E+09 | 29334671.10 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.129551E+09 | 21983335.50 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.137745E+09 | 25319083.87 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183917E+09 | 22046738.50 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276889E+09 | 37737887.88 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322685E+09 | 43873386.98 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349911E+09 | 53456211.36 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.252785E+10 | 0.520426E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.115501E+09 | 21983335.50 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349911E+09 | 69871004.38 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.331581E+09 | 69871004.38 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.249459E+09 | 59793421.12 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193290E+09 | 65101009.16 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.115501E+09 | 52553393.57 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.121306E+09 | 39355732.17 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116012E+09 | 29334671.10 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.129551E+09 | 21983335.50 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.137745E+09 | 25319083.87 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183917E+09 | 22046738.50 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276889E+09 | 37737887.88 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322685E+09 | 43873386.98 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349911E+09 | 53456211.36 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.252785E+10 | 0.520426E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.115501E+09 | 21983335.50 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349911E+09 | 69871004.38 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.331581E+09 | 69871004.38 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.249459E+09 | 59793421.12 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193290E+09 | 65101009.16 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.115501E+09 | 52553393.57 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.121306E+09 | 39355732.17 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116012E+09 | 29334671.10 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.129551E+09 | 21983335.50 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.137745E+09 | 25319083.87 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183917E+09 | 22046738.50 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276889E+09 | 37737887.88 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322685E+09 | 43873386.98 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349911E+09 | 53456211.36 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.252785E+10 | 0.520426E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.115501E+09 | 21983335.50 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349911E+09 | 69871004.38 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.245987E+09 | 0.154472E+09 | 91515107.98 | 0.398093E+09 | 83747640.41 |
February | 0.188197E+09 | 0.100323E+09 | 87874414.35 | 0.299490E+09 | 71631925.28 |
March | 0.151158E+09 | 51789298.46 | 99368896.28 | 0.231923E+09 | 77983865.96 |
April | 94588372.98 | 9109605.43 | 85478767.55 | 0.138452E+09 | 63031909.12 |
May | 82733628.79 | 213615.15 | 82520013.64 | 0.145160E+09 | 47260863.61 |
June | 79197287.84 | 0.00 | 79197287.84 | 0.138812E+09 | 35323751.71 |
July | 79352611.83 | 216935.24 | 79135676.59 | 0.154855E+09 | 26536915.51 |
August | 86805029.55 | 5330716.79 | 81474312.76 | 0.164670E+09 | 30538158.45 |
September | 0.126953E+09 | 30810433.11 | 96142796.74 | 0.220259E+09 | 26606162.47 |
October | 0.185985E+09 | 89814394.78 | 96170710.31 | 0.331922E+09 | 45382235.40 |
November | 0.227268E+09 | 0.130278E+09 | 96989683.65 | 0.387215E+09 | 52731586.59 |
December | 0.254120E+09 | 0.163736E+09 | 90383919.63 | 0.420065E+09 | 64175901.42 |
Annual Sum or Average | 0.180234E+10 | 0.736093E+09 | 0.106625E+10 | 0.303092E+10 | 0.624951E+09 |
Minimum of Months | 79197287.84 | 0.00 | 79135676.59 | 0.138452E+09 | 26536915.51 |
Maximum of Months | 0.254120E+09 | 0.163736E+09 | 99368896.28 | 0.420065E+09 | 83747640.41 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.245987E+09 | 0.154472E+09 | 91515107.98 | 0.398093E+09 | 83747640.41 |
February | 0.188197E+09 | 0.100323E+09 | 87874414.35 | 0.299490E+09 | 71631925.28 |
March | 0.151158E+09 | 51789298.46 | 99368896.28 | 0.231923E+09 | 77983865.96 |
April | 94588372.98 | 9109605.43 | 85478767.55 | 0.138452E+09 | 63031909.12 |
May | 82733628.79 | 213615.15 | 82520013.64 | 0.145160E+09 | 47260863.61 |
June | 79197287.84 | 0.00 | 79197287.84 | 0.138812E+09 | 35323751.71 |
July | 79352611.83 | 216935.24 | 79135676.59 | 0.154855E+09 | 26536915.51 |
August | 86805029.55 | 5330716.79 | 81474312.76 | 0.164670E+09 | 30538158.45 |
September | 0.126953E+09 | 30810433.11 | 96142796.74 | 0.220259E+09 | 26606162.47 |
October | 0.185985E+09 | 89814394.78 | 96170710.31 | 0.331922E+09 | 45382235.40 |
November | 0.227268E+09 | 0.130278E+09 | 96989683.65 | 0.387215E+09 | 52731586.59 |
December | 0.254120E+09 | 0.163736E+09 | 90383919.63 | 0.420065E+09 | 64175901.42 |
Annual Sum or Average | 0.180234E+10 | 0.736093E+09 | 0.106625E+10 | 0.303092E+10 | 0.624951E+09 |
Minimum of Months | 79197287.84 | 0.00 | 79135676.59 | 0.138452E+09 | 26536915.51 |
Maximum of Months | 0.254120E+09 | 0.163736E+09 | 99368896.28 | 0.420065E+09 | 83747640.41 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.330968E+09 | 70738313.97 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.249170E+09 | 60402039.19 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193403E+09 | 65753479.94 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.115848E+09 | 52973935.48 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.122071E+09 | 39517881.85 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116958E+09 | 29154248.87 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.130901E+09 | 21601645.75 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.139220E+09 | 24826519.26 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.185318E+09 | 21395216.87 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.277555E+09 | 37659450.38 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322706E+09 | 43920085.06 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349487E+09 | 53866446.72 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.253360E+10 | 0.521809E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.115848E+09 | 21395216.87 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349487E+09 | 70738313.97 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.330968E+09 | 70738313.97 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.249170E+09 | 60402039.19 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193403E+09 | 65753479.94 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.115848E+09 | 52973935.48 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.122071E+09 | 39517881.85 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116958E+09 | 29154248.87 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.130901E+09 | 21601645.75 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.139220E+09 | 24826519.26 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.185318E+09 | 21395216.87 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.277555E+09 | 37659450.38 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322706E+09 | 43920085.06 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349487E+09 | 53866446.72 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.253360E+10 | 0.521809E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.115848E+09 | 21395216.87 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349487E+09 | 70738313.97 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.245987E+09 | 0.154472E+09 | 91515107.98 | 0.397404E+09 | 84770838.01 |
February | 0.188197E+09 | 0.100323E+09 | 87874414.35 | 0.299181E+09 | 72344712.57 |
March | 0.151158E+09 | 51789298.46 | 99368896.28 | 0.232080E+09 | 78747067.96 |
April | 94588372.98 | 9109605.43 | 85478767.55 | 0.138875E+09 | 63518733.92 |
May | 82733628.79 | 213615.15 | 82520013.64 | 0.146084E+09 | 47443907.35 |
June | 79197287.84 | 0.00 | 79197287.84 | 0.139952E+09 | 35101541.54 |
July | 79352611.83 | 216935.24 | 79135676.59 | 0.156477E+09 | 26071341.27 |
August | 86805029.55 | 5330716.79 | 81474312.76 | 0.166440E+09 | 29941086.44 |
September | 0.126953E+09 | 30810433.11 | 96142796.74 | 0.221951E+09 | 25812082.20 |
October | 0.185985E+09 | 89814394.78 | 96170710.31 | 0.332749E+09 | 45282657.63 |
November | 0.227268E+09 | 0.130278E+09 | 96989683.65 | 0.387286E+09 | 52779280.35 |
December | 0.254120E+09 | 0.163736E+09 | 90383919.63 | 0.419609E+09 | 64656458.92 |
Annual Sum or Average | 0.180234E+10 | 0.736093E+09 | 0.106625E+10 | 0.303809E+10 | 0.626470E+09 |
Minimum of Months | 79197287.84 | 0.00 | 79135676.59 | 0.138875E+09 | 25812082.20 |
Maximum of Months | 0.254120E+09 | 0.163736E+09 | 99368896.28 | 0.419609E+09 | 84770838.01 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.331278E+09 | 74928858.14 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.249156E+09 | 64206870.67 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193041E+09 | 69753710.05 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.115678E+09 | 56945653.81 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.121721E+09 | 44436178.75 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116685E+09 | 34183955.30 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.129939E+09 | 27571699.01 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.138685E+09 | 30666156.96 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183774E+09 | 27149193.79 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276869E+09 | 43798527.74 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322934E+09 | 49029636.96 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349855E+09 | 58802877.13 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.252961E+10 | 0.581473E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.115678E+09 | 27149193.79 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349855E+09 | 74928858.14 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.331278E+09 | 74928858.14 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.249156E+09 | 64206870.67 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193041E+09 | 69753710.05 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.115678E+09 | 56945653.81 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.121721E+09 | 44436178.75 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116685E+09 | 34183955.30 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.129939E+09 | 27571699.01 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.138685E+09 | 30666156.96 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183774E+09 | 27149193.79 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276869E+09 | 43798527.74 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322934E+09 | 49029636.96 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349855E+09 | 58802877.13 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.252961E+10 | 0.581473E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.115678E+09 | 27149193.79 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349855E+09 | 74928858.14 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.395585E+09 | 89152647.87 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.297529E+09 | 76351873.80 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.230389E+09 | 82952849.40 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.137920E+09 | 67777948.76 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.144874E+09 | 52906778.66 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.138861E+09 | 40762810.46 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.154502E+09 | 32897891.55 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.164902E+09 | 36588835.87 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.218955E+09 | 32406741.86 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.330127E+09 | 52200694.90 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.385419E+09 | 58426296.00 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.417730E+09 | 70025620.55 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.301679E+10 | 0.692451E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.137920E+09 | 32406741.86 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.417730E+09 | 89152647.87 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.331339E+09 | 74749013.63 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.249203E+09 | 64091329.87 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193073E+09 | 69676037.94 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.115722E+09 | 56850036.15 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.121715E+09 | 44566289.98 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116663E+09 | 34372863.35 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.129861E+09 | 27964091.30 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.138624E+09 | 31022924.19 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183669E+09 | 27623902.34 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276798E+09 | 44184524.69 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322929E+09 | 49139106.40 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349880E+09 | 58778432.15 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.252948E+10 | 0.583019E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.115722E+09 | 27623902.34 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349880E+09 | 74749013.63 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.331339E+09 | 74749013.63 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.249203E+09 | 64091329.87 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193073E+09 | 69676037.94 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.115722E+09 | 56850036.15 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.121715E+09 | 44566289.98 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116663E+09 | 34372863.35 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.129861E+09 | 27964091.30 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.138624E+09 | 31022924.19 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183669E+09 | 27623902.34 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276798E+09 | 44184524.69 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.322929E+09 | 49139106.40 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349880E+09 | 58778432.15 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.252948E+10 | 0.583019E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.115722E+09 | 27623902.34 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349880E+09 | 74749013.63 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.395658E+09 | 88939282.07 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.297586E+09 | 76214416.76 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.230428E+09 | 82860598.96 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.137973E+09 | 67663837.35 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.144866E+09 | 53061951.78 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.138836E+09 | 40987163.69 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.154408E+09 | 33362483.26 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.164828E+09 | 37011988.05 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.218828E+09 | 32970079.70 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.330043E+09 | 52658717.64 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.385414E+09 | 58556734.63 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.417760E+09 | 69996686.45 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.301663E+10 | 0.694284E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.137973E+09 | 32970079.70 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.417760E+09 | 88939282.07 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.331647E+09 | 73772813.96 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.249515E+09 | 63176682.02 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193410E+09 | 68640203.76 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.116050E+09 | 55883349.51 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.122040E+09 | 43655945.89 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116973E+09 | 33511035.03 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.130155E+09 | 27123748.65 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.138919E+09 | 30124103.48 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183929E+09 | 26785768.09 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.277062E+09 | 43292898.24 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.323212E+09 | 48279192.06 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.350178E+09 | 57836210.99 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.253309E+10 | 0.572082E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.116050E+09 | 26785768.09 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.350178E+09 | 73772813.96 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.331647E+09 | 73772813.96 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.249515E+09 | 63176682.02 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193410E+09 | 68640203.76 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.116050E+09 | 55883349.51 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.122040E+09 | 43655945.89 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116973E+09 | 33511035.03 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.130155E+09 | 27123748.65 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.138919E+09 | 30124103.48 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183929E+09 | 26785768.09 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.277062E+09 | 43292898.24 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.323212E+09 | 48279192.06 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.350178E+09 | 57836210.99 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.253309E+10 | 0.572082E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.116050E+09 | 26785768.09 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.350178E+09 | 73772813.96 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.396032E+09 | 87787013.91 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.297963E+09 | 75136102.89 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.230836E+09 | 81637522.81 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.138369E+09 | 66523275.23 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.145259E+09 | 51988159.70 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.139210E+09 | 39971826.16 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.154763E+09 | 32373918.82 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.165183E+09 | 35952694.18 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.219142E+09 | 31982448.31 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.330363E+09 | 51606377.67 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.385755E+09 | 57542767.71 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.418120E+09 | 68884624.12 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.302100E+10 | 0.681387E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.138369E+09 | 31982448.31 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.418120E+09 | 87787013.91 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.332108E+09 | 70828942.23 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.250110E+09 | 60481997.75 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193975E+09 | 65616279.51 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.116244E+09 | 53072670.92 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.121778E+09 | 40814431.29 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116520E+09 | 30729502.95 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.129404E+09 | 24447977.79 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.138256E+09 | 27167366.80 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183569E+09 | 24246730.14 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276843E+09 | 40530348.24 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.323167E+09 | 45628948.24 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.350421E+09 | 54980238.88 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.253240E+10 | 0.538545E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.116244E+09 | 24246730.14 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.350421E+09 | 70828942.23 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.332108E+09 | 70828942.23 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.250110E+09 | 60481997.75 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193975E+09 | 65616279.51 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.116244E+09 | 53072670.92 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.121778E+09 | 40814431.29 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116520E+09 | 30729502.95 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.129404E+09 | 24447977.79 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.138256E+09 | 27167366.80 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183569E+09 | 24246730.14 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276843E+09 | 40530348.24 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.323167E+09 | 45628948.24 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.350421E+09 | 54980238.88 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.253240E+10 | 0.538545E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.116244E+09 | 24246730.14 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.350421E+09 | 70828942.23 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.332108E+09 | 70828942.23 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.250110E+09 | 60481997.75 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193975E+09 | 65616279.51 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.116244E+09 | 53072670.92 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.121778E+09 | 40814431.29 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116520E+09 | 30729502.95 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.129404E+09 | 24447977.79 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.138256E+09 | 27167366.80 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183569E+09 | 24246730.14 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276843E+09 | 40530348.24 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.323167E+09 | 45628948.24 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.350421E+09 | 54980238.88 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.253240E+10 | 0.538545E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.116244E+09 | 24246730.14 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.350421E+09 | 70828942.23 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.332108E+09 | 70828942.23 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.250110E+09 | 60481997.75 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193975E+09 | 65616279.51 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.116244E+09 | 53072670.92 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.121778E+09 | 40814431.29 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.116520E+09 | 30729502.95 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.129404E+09 | 24447977.79 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.138256E+09 | 27167366.80 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.183569E+09 | 24246730.14 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.276843E+09 | 40530348.24 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.323167E+09 | 45628948.24 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.350421E+09 | 54980238.88 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.253240E+10 | 0.538545E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.116244E+09 | 24246730.14 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.350421E+09 | 70828942.23 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.396591E+09 | 84301218.53 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.298681E+09 | 71944026.05 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.231531E+09 | 78051783.44 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.138637E+09 | 63185892.23 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.144998E+09 | 48619425.15 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.138728E+09 | 36673482.87 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.153934E+09 | 29200968.47 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.164457E+09 | 32442897.31 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.218751E+09 | 28959427.88 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.330129E+09 | 48320647.26 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.385724E+09 | 54398171.97 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.418425E+09 | 65499707.93 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.302059E+10 | 0.641598E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.138637E+09 | 28959427.88 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.418425E+09 | 84301218.53 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.396591E+09 | 84301218.53 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.298681E+09 | 71944026.05 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.231531E+09 | 78051783.44 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.138637E+09 | 63185892.23 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.144998E+09 | 48619425.15 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.138728E+09 | 36673482.87 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.153934E+09 | 29200968.47 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.164457E+09 | 32442897.31 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.218751E+09 | 28959427.88 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.330129E+09 | 48320647.26 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.385724E+09 | 54398171.97 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.418425E+09 | 65499707.93 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.302059E+10 | 0.641598E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.138637E+09 | 28959427.88 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.418425E+09 | 84301218.53 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.331986E+09 | 69923941.43 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.250087E+09 | 59627106.35 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.194229E+09 | 64656774.60 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.116708E+09 | 52144349.93 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.122505E+09 | 39792264.72 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.117284E+09 | 29625611.21 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.130348E+09 | 23274283.55 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.139222E+09 | 25957231.51 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.184304E+09 | 23033053.55 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.277288E+09 | 39332507.13 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.323267E+09 | 44510639.61 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.350315E+09 | 53893468.62 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.253754E+10 | 0.525771E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.116708E+09 | 23033053.55 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.350315E+09 | 69923941.43 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.331986E+09 | 69923941.43 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.250087E+09 | 59627106.35 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.194229E+09 | 64656774.60 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.116708E+09 | 52144349.93 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.122505E+09 | 39792264.72 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.117284E+09 | 29625611.21 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.130348E+09 | 23274283.55 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.139222E+09 | 25957231.51 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.184304E+09 | 23033053.55 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.277288E+09 | 39332507.13 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.323267E+09 | 44510639.61 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.350315E+09 | 53893468.62 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.253754E+10 | 0.525771E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.116708E+09 | 23033053.55 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.350315E+09 | 69923941.43 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.396504E+09 | 83218459.41 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.298701E+09 | 70922090.03 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.231866E+09 | 76905046.31 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.139207E+09 | 62079354.12 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.145877E+09 | 47403527.93 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.139651E+09 | 35366603.51 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.155068E+09 | 27811663.05 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.165611E+09 | 31008541.18 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.219645E+09 | 27520614.82 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.330693E+09 | 46896999.13 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.385892E+09 | 53067564.78 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.418359E+09 | 64203172.42 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.302707E+10 | 0.626404E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.139207E+09 | 27520614.82 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.418359E+09 | 83218459.41 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.332142E+09 | 69615646.01 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.250240E+09 | 59330506.12 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.194382E+09 | 64339176.43 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.116850E+09 | 51870989.43 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.122657E+09 | 39547672.27 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.117435E+09 | 29394997.46 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.130501E+09 | 23048284.77 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.139361E+09 | 25738579.23 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.184440E+09 | 22802398.71 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.277419E+09 | 39086718.44 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.323417E+09 | 44239389.45 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.350472E+09 | 53593504.62 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.253932E+10 | 0.522608E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.116850E+09 | 22802398.71 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.350472E+09 | 69615646.01 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.332142E+09 | 69615646.01 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.250240E+09 | 59330506.12 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.194382E+09 | 64339176.43 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.116850E+09 | 51870989.43 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.122657E+09 | 39547672.27 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.117435E+09 | 29394997.46 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.130501E+09 | 23048284.77 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.139361E+09 | 25738579.23 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.184440E+09 | 22802398.71 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.277419E+09 | 39086718.44 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.323417E+09 | 44239389.45 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.350472E+09 | 53593504.62 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.253932E+10 | 0.522608E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.116850E+09 | 22802398.71 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.350472E+09 | 69615646.01 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.396692E+09 | 82852482.22 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.298887E+09 | 70570181.78 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.232051E+09 | 76527789.75 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.139378E+09 | 61753720.92 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.146060E+09 | 47112648.84 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.139833E+09 | 35092321.38 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.155251E+09 | 27543135.40 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.165778E+09 | 30749042.39 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.219809E+09 | 27246310.98 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.330852E+09 | 46604307.90 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.386073E+09 | 52745066.42 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.418548E+09 | 63846737.99 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.302921E+10 | 0.622644E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.139378E+09 | 27246310.98 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.418548E+09 | 82852482.22 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.332266E+09 | 69154290.03 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.250374E+09 | 58856194.77 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.194459E+09 | 63872864.14 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.116860E+09 | 51541252.78 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.122574E+09 | 39415212.61 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.117338E+09 | 29305561.24 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.130332E+09 | 23075597.00 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.139155E+09 | 25812604.51 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.184283E+09 | 22849726.39 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.277289E+09 | 39084965.60 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.323442E+09 | 44020259.10 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.350548E+09 | 53254625.73 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.253892E+10 | 0.520243E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.116860E+09 | 22849726.39 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.350548E+09 | 69154290.03 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.332266E+09 | 69154290.03 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.250374E+09 | 58856194.77 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.194459E+09 | 63872864.14 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.116860E+09 | 51541252.78 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.122574E+09 | 39415212.61 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.117338E+09 | 29305561.24 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.130332E+09 | 23075597.00 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.139155E+09 | 25812604.51 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.184283E+09 | 22849726.39 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.277289E+09 | 39084965.60 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.323442E+09 | 44020259.10 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.350548E+09 | 53254625.73 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.253892E+10 | 0.520243E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.116860E+09 | 22849726.39 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.350548E+09 | 69154290.03 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.396840E+09 | 82312059.60 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.299047E+09 | 70014384.40 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.232144E+09 | 75982455.69 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.139391E+09 | 61370494.66 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.145959E+09 | 46963172.79 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.139713E+09 | 34995043.06 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.155046E+09 | 27584391.99 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.165529E+09 | 30845808.83 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.219618E+09 | 27311340.85 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.330693E+09 | 46611629.62 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.386100E+09 | 52492513.79 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.418637E+09 | 63451755.00 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.302872E+10 | 0.619935E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.139391E+09 | 27311340.85 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.418637E+09 | 82312059.60 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.331049E+09 | 67927193.07 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.249495E+09 | 57550764.36 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193065E+09 | 62591442.01 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.114903E+09 | 50834129.76 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.119772E+09 | 39705835.35 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.114573E+09 | 29854208.58 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.127058E+09 | 24287193.40 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.135644E+09 | 27293123.21 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.181593E+09 | 24289476.18 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.274456E+09 | 40293586.11 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.321682E+09 | 44099795.56 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349094E+09 | 52754547.09 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.251238E+10 | 0.521481E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.114573E+09 | 24287193.40 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349094E+09 | 67927193.07 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.331049E+09 | 67927193.07 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.249495E+09 | 57550764.36 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.193065E+09 | 62591442.01 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.114903E+09 | 50834129.76 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.119772E+09 | 39705835.35 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.114573E+09 | 29854208.58 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.127058E+09 | 24287193.40 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.135644E+09 | 27293123.21 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.181593E+09 | 24289476.18 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.274456E+09 | 40293586.11 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.321682E+09 | 44099795.56 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.349094E+09 | 52754547.09 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.251238E+10 | 0.521481E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.114573E+09 | 24287193.40 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.349094E+09 | 67927193.07 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.395357E+09 | 80869682.10 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.297977E+09 | 68475934.54 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.230455E+09 | 74475904.87 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.137021E+09 | 60543370.88 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.142571E+09 | 47318946.93 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.136367E+09 | 35654406.61 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.151087E+09 | 29029171.46 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.161282E+09 | 32610618.62 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.216368E+09 | 29029735.64 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.327259E+09 | 48055607.68 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.383963E+09 | 52597403.85 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.416867E+09 | 62870513.28 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.299657E+10 | 0.621531E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.136367E+09 | 29029171.46 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.416867E+09 | 80869682.10 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 792.46 | 166.88 | 488.81 | 306.96 | 181.85 | 0.00 | 0.00 |
February | 660.06 | 158.08 | 414.05 | 220.72 | 193.33 | 0.00 | 0.00 |
March | 461.85 | 155.46 | 300.38 | 102.91 | 197.46 | 0.00 | 0.00 |
April | 285.07 | 129.74 | 194.23 | 18.71 | 175.52 | 0.00 | 0.00 |
May | 289.55 | 94.07 | 164.40 | 0.42 | 163.98 | 0.00 | 0.00 |
June | 286.14 | 72.53 | 162.62 | 0.00 | 162.62 | 0.00 | 0.00 |
July | 309.11 | 52.65 | 157.69 | 0.43 | 157.26 | 0.00 | 0.00 |
August | 328.67 | 60.62 | 172.50 | 10.59 | 161.90 | 0.00 | 0.00 |
September | 453.78 | 54.55 | 260.69 | 63.27 | 197.42 | 0.00 | 0.00 |
October | 661.36 | 90.25 | 369.58 | 178.48 | 191.11 | 0.00 | 0.00 |
November | 796.75 | 108.39 | 466.67 | 267.51 | 199.16 | 0.00 | 0.00 |
December | 836.24 | 127.75 | 504.98 | 325.37 | 179.61 | 0.00 | 0.00 |
Annual Sum or Average | 512.85 | 105.64 | 304.19 | 124.23 | 179.95 | 0.00 | 0.00 |
Minimum of Months | 285.07 | 52.65 | 157.69 | 0.00 | 157.26 | 0.00 | 0.00 |
Maximum of Months | 836.24 | 166.88 | 504.98 | 325.37 | 199.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 395.51 | 84.47 | 244.41 | 153.48 | 90.93 | 0.00 | 0.00 |
February | 329.66 | 79.84 | 207.02 | 110.36 | 96.66 | 0.00 | 0.00 |
March | 231.07 | 78.50 | 150.19 | 51.46 | 98.73 | 0.00 | 0.00 |
April | 142.97 | 65.38 | 97.11 | 9.35 | 87.76 | 0.00 | 0.00 |
May | 145.69 | 47.22 | 82.20 | 0.21 | 81.99 | 0.00 | 0.00 |
June | 144.24 | 36.04 | 81.31 | 0.00 | 81.31 | 0.00 | 0.00 |
July | 156.17 | 25.86 | 78.84 | 0.22 | 78.63 | 0.00 | 0.00 |
August | 166.10 | 29.72 | 86.25 | 5.30 | 80.95 | 0.00 | 0.00 |
September | 228.62 | 26.47 | 130.34 | 31.63 | 98.71 | 0.00 | 0.00 |
October | 331.49 | 45.03 | 184.79 | 89.24 | 95.55 | 0.00 | 0.00 |
November | 398.42 | 54.25 | 233.34 | 133.76 | 99.58 | 0.00 | 0.00 |
December | 417.63 | 64.36 | 252.49 | 162.68 | 89.80 | 0.00 | 0.00 |
Annual Sum or Average | 257.02 | 52.96 | 152.09 | 62.12 | 89.98 | 0.00 | 0.00 |
Minimum of Months | 142.97 | 25.86 | 78.84 | 0.00 | 78.63 | 0.00 | 0.00 |
Maximum of Months | 417.63 | 84.47 | 252.49 | 162.68 | 99.58 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 395.06 | 89.24 | 243.91 | 153.16 | 90.74 | 0.00 | 0.00 |
February | 328.97 | 84.64 | 206.60 | 110.13 | 96.47 | 0.00 | 0.00 |
March | 230.16 | 83.06 | 149.88 | 51.35 | 98.53 | 0.00 | 0.00 |
April | 142.47 | 70.09 | 96.91 | 9.33 | 87.58 | 0.00 | 0.00 |
May | 144.98 | 52.93 | 82.03 | 0.21 | 81.82 | 0.00 | 0.00 |
June | 143.61 | 42.10 | 81.14 | 0.00 | 81.14 | 0.00 | 0.00 |
July | 154.71 | 32.87 | 78.68 | 0.22 | 78.47 | 0.00 | 0.00 |
August | 165.13 | 36.56 | 86.07 | 5.29 | 80.78 | 0.00 | 0.00 |
September | 226.27 | 33.45 | 130.08 | 31.57 | 98.51 | 0.00 | 0.00 |
October | 330.00 | 52.19 | 184.41 | 89.05 | 95.36 | 0.00 | 0.00 |
November | 397.87 | 60.37 | 232.86 | 133.48 | 99.37 | 0.00 | 0.00 |
December | 417.20 | 70.05 | 251.97 | 162.35 | 89.62 | 0.00 | 0.00 |
Annual Sum or Average | 256.09 | 58.83 | 151.78 | 61.99 | 89.79 | 0.00 | 0.00 |
Minimum of Months | 142.47 | 32.87 | 78.68 | 0.00 | 78.47 | 0.00 | 0.00 |
Maximum of Months | 417.20 | 89.24 | 251.97 | 162.35 | 99.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 395.14 | 89.02 | 243.91 | 153.16 | 90.74 | 0.00 | 0.00 |
February | 329.03 | 84.49 | 206.60 | 110.13 | 96.47 | 0.00 | 0.00 |
March | 230.20 | 82.96 | 149.88 | 51.35 | 98.53 | 0.00 | 0.00 |
April | 142.52 | 69.97 | 96.91 | 9.33 | 87.58 | 0.00 | 0.00 |
May | 144.97 | 53.09 | 82.03 | 0.21 | 81.82 | 0.00 | 0.00 |
June | 143.58 | 42.34 | 81.14 | 0.00 | 81.14 | 0.00 | 0.00 |
July | 154.62 | 33.34 | 78.68 | 0.22 | 78.47 | 0.00 | 0.00 |
August | 165.05 | 36.98 | 86.07 | 5.29 | 80.78 | 0.00 | 0.00 |
September | 226.14 | 34.03 | 130.08 | 31.57 | 98.51 | 0.00 | 0.00 |
October | 329.91 | 52.65 | 184.41 | 89.05 | 95.36 | 0.00 | 0.00 |
November | 397.87 | 60.51 | 232.86 | 133.48 | 99.37 | 0.00 | 0.00 |
December | 417.23 | 70.02 | 251.97 | 162.35 | 89.62 | 0.00 | 0.00 |
Annual Sum or Average | 256.07 | 58.99 | 151.78 | 61.99 | 89.79 | 0.00 | 0.00 |
Minimum of Months | 142.52 | 33.34 | 78.68 | 0.00 | 78.47 | 0.00 | 0.00 |
Maximum of Months | 417.23 | 89.02 | 251.97 | 162.35 | 99.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 395.51 | 87.86 | 243.91 | 153.16 | 90.74 | 0.00 | 0.00 |
February | 329.44 | 83.29 | 206.60 | 110.13 | 96.47 | 0.00 | 0.00 |
March | 230.61 | 81.73 | 149.88 | 51.35 | 98.53 | 0.00 | 0.00 |
April | 142.93 | 68.78 | 96.91 | 9.33 | 87.58 | 0.00 | 0.00 |
May | 145.36 | 52.01 | 82.03 | 0.21 | 81.82 | 0.00 | 0.00 |
June | 143.96 | 41.28 | 81.14 | 0.00 | 81.14 | 0.00 | 0.00 |
July | 154.97 | 32.34 | 78.68 | 0.22 | 78.47 | 0.00 | 0.00 |
August | 165.41 | 35.92 | 86.07 | 5.29 | 80.78 | 0.00 | 0.00 |
September | 226.47 | 33.01 | 130.08 | 31.57 | 98.51 | 0.00 | 0.00 |
October | 330.23 | 51.59 | 184.41 | 89.05 | 95.36 | 0.00 | 0.00 |
November | 398.22 | 59.45 | 232.86 | 133.48 | 99.37 | 0.00 | 0.00 |
December | 417.59 | 68.91 | 251.97 | 162.35 | 89.62 | 0.00 | 0.00 |
Annual Sum or Average | 256.44 | 57.89 | 151.78 | 61.99 | 89.79 | 0.00 | 0.00 |
Minimum of Months | 142.93 | 32.34 | 78.68 | 0.00 | 78.47 | 0.00 | 0.00 |
Maximum of Months | 417.59 | 87.86 | 251.97 | 162.35 | 99.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 792.12 | 168.73 | 487.81 | 306.33 | 181.48 | 0.00 | 0.00 |
February | 660.47 | 159.48 | 413.20 | 220.26 | 192.93 | 0.00 | 0.00 |
March | 462.58 | 156.28 | 299.76 | 102.70 | 197.06 | 0.00 | 0.00 |
April | 286.36 | 130.66 | 193.83 | 18.67 | 175.16 | 0.00 | 0.00 |
May | 290.14 | 97.26 | 164.07 | 0.42 | 163.64 | 0.00 | 0.00 |
June | 286.86 | 75.72 | 162.29 | 0.00 | 162.29 | 0.00 | 0.00 |
July | 308.20 | 58.32 | 157.36 | 0.43 | 156.93 | 0.00 | 0.00 |
August | 329.28 | 64.80 | 172.14 | 10.57 | 161.57 | 0.00 | 0.00 |
September | 452.08 | 59.76 | 260.15 | 63.14 | 197.01 | 0.00 | 0.00 |
October | 659.96 | 96.61 | 368.82 | 178.11 | 190.71 | 0.00 | 0.00 |
November | 796.34 | 112.39 | 465.71 | 266.96 | 198.75 | 0.00 | 0.00 |
December | 835.77 | 131.02 | 503.94 | 324.70 | 179.24 | 0.00 | 0.00 |
Annual Sum or Average | 512.77 | 109.00 | 303.56 | 123.98 | 179.58 | 0.00 | 0.00 |
Minimum of Months | 286.36 | 58.32 | 157.36 | 0.00 | 156.93 | 0.00 | 0.00 |
Maximum of Months | 835.77 | 168.73 | 503.94 | 324.70 | 198.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 395.94 | 83.28 | 243.91 | 153.16 | 90.74 | 0.00 | 0.00 |
February | 330.22 | 78.61 | 206.60 | 110.13 | 96.47 | 0.00 | 0.00 |
March | 231.60 | 76.99 | 149.88 | 51.35 | 98.53 | 0.00 | 0.00 |
April | 143.76 | 64.19 | 96.91 | 9.33 | 87.58 | 0.00 | 0.00 |
May | 145.94 | 47.41 | 82.03 | 0.21 | 81.82 | 0.00 | 0.00 |
June | 144.37 | 36.50 | 81.14 | 0.00 | 81.14 | 0.00 | 0.00 |
July | 155.23 | 27.76 | 78.68 | 0.22 | 78.47 | 0.00 | 0.00 |
August | 165.79 | 30.96 | 86.07 | 5.29 | 80.78 | 0.00 | 0.00 |
September | 226.95 | 28.39 | 130.08 | 31.57 | 98.51 | 0.00 | 0.00 |
October | 330.52 | 46.88 | 184.41 | 89.05 | 95.36 | 0.00 | 0.00 |
November | 398.31 | 54.82 | 232.86 | 133.48 | 99.37 | 0.00 | 0.00 |
December | 417.78 | 64.21 | 251.97 | 162.35 | 89.62 | 0.00 | 0.00 |
Annual Sum or Average | 256.92 | 53.21 | 151.78 | 61.99 | 89.79 | 0.00 | 0.00 |
Minimum of Months | 143.76 | 27.76 | 78.68 | 0.00 | 78.47 | 0.00 | 0.00 |
Maximum of Months | 417.78 | 83.28 | 251.97 | 162.35 | 99.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 396.12 | 82.92 | 243.91 | 153.16 | 90.74 | 0.00 | 0.00 |
February | 330.43 | 78.22 | 206.60 | 110.13 | 96.47 | 0.00 | 0.00 |
March | 231.79 | 76.62 | 149.88 | 51.35 | 98.53 | 0.00 | 0.00 |
April | 143.93 | 63.85 | 96.91 | 9.33 | 87.58 | 0.00 | 0.00 |
May | 146.12 | 47.12 | 82.03 | 0.21 | 81.82 | 0.00 | 0.00 |
June | 144.56 | 36.22 | 81.14 | 0.00 | 81.14 | 0.00 | 0.00 |
July | 155.41 | 27.49 | 78.68 | 0.22 | 78.47 | 0.00 | 0.00 |
August | 165.96 | 30.70 | 86.07 | 5.29 | 80.78 | 0.00 | 0.00 |
September | 227.12 | 28.11 | 130.08 | 31.57 | 98.51 | 0.00 | 0.00 |
October | 330.68 | 46.59 | 184.41 | 89.05 | 95.36 | 0.00 | 0.00 |
November | 398.50 | 54.48 | 232.86 | 133.48 | 99.37 | 0.00 | 0.00 |
December | 417.97 | 63.86 | 251.97 | 162.35 | 89.62 | 0.00 | 0.00 |
Annual Sum or Average | 257.10 | 52.89 | 151.78 | 61.99 | 89.79 | 0.00 | 0.00 |
Minimum of Months | 143.93 | 27.49 | 78.68 | 0.00 | 78.47 | 0.00 | 0.00 |
Maximum of Months | 417.97 | 82.92 | 251.97 | 162.35 | 99.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 396.27 | 82.37 | 243.91 | 153.16 | 90.74 | 0.00 | 0.00 |
February | 330.60 | 77.60 | 206.60 | 110.13 | 96.47 | 0.00 | 0.00 |
March | 231.88 | 76.06 | 149.88 | 51.35 | 98.53 | 0.00 | 0.00 |
April | 143.95 | 63.45 | 96.91 | 9.33 | 87.58 | 0.00 | 0.00 |
May | 146.02 | 46.97 | 82.03 | 0.21 | 81.82 | 0.00 | 0.00 |
June | 144.44 | 36.11 | 81.14 | 0.00 | 81.14 | 0.00 | 0.00 |
July | 155.21 | 27.53 | 78.68 | 0.22 | 78.47 | 0.00 | 0.00 |
August | 165.71 | 30.79 | 86.07 | 5.29 | 80.78 | 0.00 | 0.00 |
September | 226.92 | 28.17 | 130.08 | 31.57 | 98.51 | 0.00 | 0.00 |
October | 330.52 | 46.59 | 184.41 | 89.05 | 95.36 | 0.00 | 0.00 |
November | 398.53 | 54.22 | 232.86 | 133.48 | 99.37 | 0.00 | 0.00 |
December | 418.06 | 63.46 | 251.97 | 162.35 | 89.62 | 0.00 | 0.00 |
Annual Sum or Average | 257.06 | 52.65 | 151.78 | 61.99 | 89.79 | 0.00 | 0.00 |
Minimum of Months | 143.95 | 27.53 | 78.68 | 0.00 | 78.47 | 0.00 | 0.00 |
Maximum of Months | 418.06 | 82.37 | 251.97 | 162.35 | 99.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 394.81 | 80.92 | 243.91 | 153.16 | 90.74 | 0.00 | 0.00 |
February | 329.43 | 75.88 | 206.60 | 110.13 | 96.47 | 0.00 | 0.00 |
March | 230.21 | 74.54 | 149.88 | 51.35 | 98.53 | 0.00 | 0.00 |
April | 141.52 | 62.58 | 96.91 | 9.33 | 87.58 | 0.00 | 0.00 |
May | 142.67 | 47.32 | 82.03 | 0.21 | 81.82 | 0.00 | 0.00 |
June | 141.02 | 36.79 | 81.14 | 0.00 | 81.14 | 0.00 | 0.00 |
July | 151.29 | 28.97 | 78.68 | 0.22 | 78.47 | 0.00 | 0.00 |
August | 161.50 | 32.56 | 86.07 | 5.29 | 80.78 | 0.00 | 0.00 |
September | 223.59 | 29.94 | 130.08 | 31.57 | 98.51 | 0.00 | 0.00 |
October | 327.12 | 48.03 | 184.41 | 89.05 | 95.36 | 0.00 | 0.00 |
November | 396.35 | 54.32 | 232.86 | 133.48 | 99.37 | 0.00 | 0.00 |
December | 416.31 | 62.87 | 251.97 | 162.35 | 89.62 | 0.00 | 0.00 |
Annual Sum or Average | 254.36 | 52.78 | 151.78 | 61.99 | 89.79 | 0.00 | 0.00 |
Minimum of Months | 141.02 | 28.97 | 78.68 | 0.00 | 78.47 | 0.00 | 0.00 |
Maximum of Months | 416.31 | 80.92 | 251.97 | 162.35 | 99.37 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.212251E+10 | 0.446979E+09 | 0.130924E+10 | 0.822161E+09 | 0.487080E+09 | 0.00 | 0.00 |
February | 0.159682E+10 | 0.382438E+09 | 0.100166E+10 | 0.533957E+09 | 0.467703E+09 | 0.00 | 0.00 |
March | 0.123701E+10 | 0.416372E+09 | 0.804525E+09 | 0.275644E+09 | 0.528881E+09 | 0.00 | 0.00 |
April | 0.738907E+09 | 0.336277E+09 | 0.503438E+09 | 48485003.77 | 0.454953E+09 | 0.00 | 0.00 |
May | 0.775543E+09 | 0.251944E+09 | 0.440342E+09 | 1136946.20 | 0.439205E+09 | 0.00 | 0.00 |
June | 0.741673E+09 | 0.187985E+09 | 0.421520E+09 | 0.00 | 0.421520E+09 | 0.00 | 0.00 |
July | 0.827912E+09 | 0.141006E+09 | 0.422347E+09 | 1154617.08 | 0.421192E+09 | 0.00 | 0.00 |
August | 0.880317E+09 | 0.162352E+09 | 0.462011E+09 | 28372230.32 | 0.433639E+09 | 0.00 | 0.00 |
September | 0.117619E+10 | 0.141397E+09 | 0.675696E+09 | 0.163986E+09 | 0.511711E+09 | 0.00 | 0.00 |
October | 0.177140E+10 | 0.241715E+09 | 0.989888E+09 | 0.478029E+09 | 0.511859E+09 | 0.00 | 0.00 |
November | 0.206517E+10 | 0.280957E+09 | 0.120961E+10 | 0.693393E+09 | 0.516218E+09 | 0.00 | 0.00 |
December | 0.223978E+10 | 0.342176E+09 | 0.135253E+10 | 0.871468E+09 | 0.481060E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.161732E+11 | 0.333160E+10 | 0.959281E+10 | 0.391779E+10 | 0.567502E+10 | 0.00 | 0.00 |
Minimum of Months | 0.738907E+09 | 0.141006E+09 | 0.421520E+09 | 0.00 | 0.421192E+09 | 0.00 | 0.00 |
Maximum of Months | 0.223978E+10 | 0.446979E+09 | 0.135253E+10 | 0.871468E+09 | 0.528881E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105934E+10 | 0.226247E+09 | 0.654621E+09 | 0.411081E+09 | 0.243540E+09 | 0.00 | 0.00 |
February | 0.797520E+09 | 0.193149E+09 | 0.500830E+09 | 0.266978E+09 | 0.233852E+09 | 0.00 | 0.00 |
March | 0.618886E+09 | 0.210254E+09 | 0.402263E+09 | 0.137822E+09 | 0.264441E+09 | 0.00 | 0.00 |
April | 0.370571E+09 | 0.169466E+09 | 0.251719E+09 | 24242501.89 | 0.227476E+09 | 0.00 | 0.00 |
May | 0.390226E+09 | 0.126480E+09 | 0.220171E+09 | 568473.10 | 0.219602E+09 | 0.00 | 0.00 |
June | 0.373867E+09 | 93409899.51 | 0.210760E+09 | 0.00 | 0.210760E+09 | 0.00 | 0.00 |
July | 0.418277E+09 | 69274249.21 | 0.211173E+09 | 577308.54 | 0.210596E+09 | 0.00 | 0.00 |
August | 0.444880E+09 | 79593687.42 | 0.231006E+09 | 14186115.16 | 0.216820E+09 | 0.00 | 0.00 |
September | 0.592585E+09 | 68602034.47 | 0.337848E+09 | 81992791.92 | 0.255855E+09 | 0.00 | 0.00 |
October | 0.887859E+09 | 0.120601E+09 | 0.494944E+09 | 0.239014E+09 | 0.255930E+09 | 0.00 | 0.00 |
November | 0.103270E+10 | 0.140619E+09 | 0.604806E+09 | 0.346697E+09 | 0.258109E+09 | 0.00 | 0.00 |
December | 0.111858E+10 | 0.172389E+09 | 0.676264E+09 | 0.435734E+09 | 0.240530E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.810529E+10 | 0.167009E+10 | 0.479640E+10 | 0.195889E+10 | 0.283751E+10 | 0.00 | 0.00 |
Minimum of Months | 0.370571E+09 | 68602034.47 | 0.210760E+09 | 0.00 | 0.210596E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111858E+10 | 0.226247E+09 | 0.676264E+09 | 0.435734E+09 | 0.264441E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105814E+10 | 0.239010E+09 | 0.653277E+09 | 0.410236E+09 | 0.243040E+09 | 0.00 | 0.00 |
February | 0.795841E+09 | 0.204766E+09 | 0.499802E+09 | 0.266430E+09 | 0.233371E+09 | 0.00 | 0.00 |
March | 0.616471E+09 | 0.222460E+09 | 0.401437E+09 | 0.137539E+09 | 0.263898E+09 | 0.00 | 0.00 |
April | 0.369276E+09 | 0.181669E+09 | 0.251202E+09 | 24192722.62 | 0.227009E+09 | 0.00 | 0.00 |
May | 0.388316E+09 | 0.141779E+09 | 0.219719E+09 | 567305.80 | 0.219152E+09 | 0.00 | 0.00 |
June | 0.372231E+09 | 0.109131E+09 | 0.210327E+09 | 0.00 | 0.210327E+09 | 0.00 | 0.00 |
July | 0.414379E+09 | 88041155.13 | 0.210740E+09 | 576123.10 | 0.210164E+09 | 0.00 | 0.00 |
August | 0.442273E+09 | 97921098.93 | 0.230531E+09 | 14156985.56 | 0.216374E+09 | 0.00 | 0.00 |
September | 0.586502E+09 | 86704817.47 | 0.337154E+09 | 81824428.90 | 0.255330E+09 | 0.00 | 0.00 |
October | 0.883865E+09 | 0.139798E+09 | 0.493928E+09 | 0.238523E+09 | 0.255404E+09 | 0.00 | 0.00 |
November | 0.103129E+10 | 0.156486E+09 | 0.603564E+09 | 0.345985E+09 | 0.257579E+09 | 0.00 | 0.00 |
December | 0.111744E+10 | 0.187631E+09 | 0.674875E+09 | 0.434839E+09 | 0.240036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.807602E+10 | 0.185540E+10 | 0.478656E+10 | 0.195487E+10 | 0.283168E+10 | 0.00 | 0.00 |
Minimum of Months | 0.369276E+09 | 86704817.47 | 0.210327E+09 | 0.00 | 0.210164E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111744E+10 | 0.239010E+09 | 0.674875E+09 | 0.434839E+09 | 0.263898E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105834E+10 | 0.238437E+09 | 0.653277E+09 | 0.410236E+09 | 0.243040E+09 | 0.00 | 0.00 |
February | 0.795993E+09 | 0.204397E+09 | 0.499802E+09 | 0.266430E+09 | 0.233371E+09 | 0.00 | 0.00 |
March | 0.616574E+09 | 0.222213E+09 | 0.401437E+09 | 0.137539E+09 | 0.263898E+09 | 0.00 | 0.00 |
April | 0.369416E+09 | 0.181364E+09 | 0.251202E+09 | 24192722.62 | 0.227009E+09 | 0.00 | 0.00 |
May | 0.388297E+09 | 0.142194E+09 | 0.219719E+09 | 567305.80 | 0.219152E+09 | 0.00 | 0.00 |
June | 0.372162E+09 | 0.109733E+09 | 0.210327E+09 | 0.00 | 0.210327E+09 | 0.00 | 0.00 |
July | 0.414129E+09 | 89290561.18 | 0.210740E+09 | 576123.10 | 0.210164E+09 | 0.00 | 0.00 |
August | 0.442076E+09 | 99057803.56 | 0.230531E+09 | 14156985.56 | 0.216374E+09 | 0.00 | 0.00 |
September | 0.586166E+09 | 88217643.76 | 0.337154E+09 | 81824428.90 | 0.255330E+09 | 0.00 | 0.00 |
October | 0.883639E+09 | 0.141028E+09 | 0.493928E+09 | 0.238523E+09 | 0.255404E+09 | 0.00 | 0.00 |
November | 0.103127E+10 | 0.156835E+09 | 0.603564E+09 | 0.345985E+09 | 0.257579E+09 | 0.00 | 0.00 |
December | 0.111752E+10 | 0.187553E+09 | 0.674875E+09 | 0.434839E+09 | 0.240036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.807558E+10 | 0.186032E+10 | 0.478656E+10 | 0.195487E+10 | 0.283168E+10 | 0.00 | 0.00 |
Minimum of Months | 0.369416E+09 | 88217643.76 | 0.210327E+09 | 0.00 | 0.210164E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111752E+10 | 0.238437E+09 | 0.674875E+09 | 0.434839E+09 | 0.263898E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105933E+10 | 0.235333E+09 | 0.653277E+09 | 0.410236E+09 | 0.243040E+09 | 0.00 | 0.00 |
February | 0.796993E+09 | 0.201489E+09 | 0.499802E+09 | 0.266430E+09 | 0.233371E+09 | 0.00 | 0.00 |
March | 0.617655E+09 | 0.218918E+09 | 0.401437E+09 | 0.137539E+09 | 0.263898E+09 | 0.00 | 0.00 |
April | 0.370468E+09 | 0.178290E+09 | 0.251202E+09 | 24192722.62 | 0.227009E+09 | 0.00 | 0.00 |
May | 0.389340E+09 | 0.139300E+09 | 0.219719E+09 | 567305.80 | 0.219152E+09 | 0.00 | 0.00 |
June | 0.373157E+09 | 0.106994E+09 | 0.210327E+09 | 0.00 | 0.210327E+09 | 0.00 | 0.00 |
July | 0.415072E+09 | 86621180.08 | 0.210740E+09 | 576123.10 | 0.210164E+09 | 0.00 | 0.00 |
August | 0.443021E+09 | 96200792.03 | 0.230531E+09 | 14156985.56 | 0.216374E+09 | 0.00 | 0.00 |
September | 0.587000E+09 | 85553429.17 | 0.337154E+09 | 81824428.90 | 0.255330E+09 | 0.00 | 0.00 |
October | 0.884487E+09 | 0.138192E+09 | 0.493928E+09 | 0.238523E+09 | 0.255404E+09 | 0.00 | 0.00 |
November | 0.103218E+10 | 0.154101E+09 | 0.603564E+09 | 0.345985E+09 | 0.257579E+09 | 0.00 | 0.00 |
December | 0.111848E+10 | 0.184557E+09 | 0.674875E+09 | 0.434839E+09 | 0.240036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.808717E+10 | 0.182555E+10 | 0.478656E+10 | 0.195487E+10 | 0.283168E+10 | 0.00 | 0.00 |
Minimum of Months | 0.370468E+09 | 85553429.17 | 0.210327E+09 | 0.00 | 0.210164E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111848E+10 | 0.235333E+09 | 0.674875E+09 | 0.434839E+09 | 0.263898E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.212161E+10 | 0.451918E+09 | 0.130655E+10 | 0.820473E+09 | 0.486080E+09 | 0.00 | 0.00 |
February | 0.159780E+10 | 0.385816E+09 | 0.999603E+09 | 0.532861E+09 | 0.466743E+09 | 0.00 | 0.00 |
March | 0.123896E+10 | 0.418569E+09 | 0.802873E+09 | 0.275078E+09 | 0.527795E+09 | 0.00 | 0.00 |
April | 0.742250E+09 | 0.338662E+09 | 0.502404E+09 | 48385445.24 | 0.454018E+09 | 0.00 | 0.00 |
May | 0.777108E+09 | 0.260496E+09 | 0.439438E+09 | 1134611.60 | 0.438303E+09 | 0.00 | 0.00 |
June | 0.743538E+09 | 0.196265E+09 | 0.420654E+09 | 0.00 | 0.420654E+09 | 0.00 | 0.00 |
July | 0.825485E+09 | 0.156193E+09 | 0.421479E+09 | 1152246.21 | 0.420327E+09 | 0.00 | 0.00 |
August | 0.881937E+09 | 0.173555E+09 | 0.461063E+09 | 28313971.12 | 0.432749E+09 | 0.00 | 0.00 |
September | 0.117178E+10 | 0.154904E+09 | 0.674309E+09 | 0.163649E+09 | 0.510660E+09 | 0.00 | 0.00 |
October | 0.176763E+10 | 0.258762E+09 | 0.987855E+09 | 0.477047E+09 | 0.510808E+09 | 0.00 | 0.00 |
November | 0.206412E+10 | 0.291312E+09 | 0.120713E+10 | 0.691970E+09 | 0.515158E+09 | 0.00 | 0.00 |
December | 0.223853E+10 | 0.350920E+09 | 0.134975E+10 | 0.869679E+09 | 0.480072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.161708E+11 | 0.343737E+10 | 0.957311E+10 | 0.390974E+10 | 0.566337E+10 | 0.00 | 0.00 |
Minimum of Months | 0.742250E+09 | 0.154904E+09 | 0.420654E+09 | 0.00 | 0.420327E+09 | 0.00 | 0.00 |
Maximum of Months | 0.223853E+10 | 0.451918E+09 | 0.134975E+10 | 0.869679E+09 | 0.527795E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.106048E+10 | 0.223066E+09 | 0.653277E+09 | 0.410236E+09 | 0.243040E+09 | 0.00 | 0.00 |
February | 0.798875E+09 | 0.190176E+09 | 0.499802E+09 | 0.266430E+09 | 0.233371E+09 | 0.00 | 0.00 |
March | 0.620324E+09 | 0.206219E+09 | 0.401437E+09 | 0.137539E+09 | 0.263898E+09 | 0.00 | 0.00 |
April | 0.372622E+09 | 0.166368E+09 | 0.251202E+09 | 24192722.62 | 0.227009E+09 | 0.00 | 0.00 |
May | 0.390887E+09 | 0.126988E+09 | 0.219719E+09 | 567305.80 | 0.219152E+09 | 0.00 | 0.00 |
June | 0.374219E+09 | 94617825.93 | 0.210327E+09 | 0.00 | 0.210327E+09 | 0.00 | 0.00 |
July | 0.415765E+09 | 74360230.15 | 0.210740E+09 | 576123.10 | 0.210164E+09 | 0.00 | 0.00 |
August | 0.444055E+09 | 82922864.58 | 0.230531E+09 | 14156985.56 | 0.216374E+09 | 0.00 | 0.00 |
September | 0.588254E+09 | 73586623.90 | 0.337154E+09 | 81824428.90 | 0.255330E+09 | 0.00 | 0.00 |
October | 0.885268E+09 | 0.125562E+09 | 0.493928E+09 | 0.238523E+09 | 0.255404E+09 | 0.00 | 0.00 |
November | 0.103243E+10 | 0.142089E+09 | 0.603564E+09 | 0.345985E+09 | 0.257579E+09 | 0.00 | 0.00 |
December | 0.111899E+10 | 0.171990E+09 | 0.674875E+09 | 0.434839E+09 | 0.240036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.810216E+10 | 0.167794E+10 | 0.478656E+10 | 0.195487E+10 | 0.283168E+10 | 0.00 | 0.00 |
Minimum of Months | 0.372622E+09 | 73586623.90 | 0.210327E+09 | 0.00 | 0.210164E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111899E+10 | 0.223066E+09 | 0.674875E+09 | 0.434839E+09 | 0.263898E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.106098E+10 | 0.222084E+09 | 0.653277E+09 | 0.410236E+09 | 0.243040E+09 | 0.00 | 0.00 |
February | 0.799367E+09 | 0.189231E+09 | 0.499802E+09 | 0.266430E+09 | 0.233371E+09 | 0.00 | 0.00 |
March | 0.620815E+09 | 0.205206E+09 | 0.401437E+09 | 0.137539E+09 | 0.263898E+09 | 0.00 | 0.00 |
April | 0.373078E+09 | 0.165496E+09 | 0.251202E+09 | 24192722.62 | 0.227009E+09 | 0.00 | 0.00 |
May | 0.391375E+09 | 0.126208E+09 | 0.219719E+09 | 567305.80 | 0.219152E+09 | 0.00 | 0.00 |
June | 0.374704E+09 | 93882270.56 | 0.210327E+09 | 0.00 | 0.210327E+09 | 0.00 | 0.00 |
July | 0.416252E+09 | 73639644.88 | 0.210740E+09 | 576123.10 | 0.210164E+09 | 0.00 | 0.00 |
August | 0.444501E+09 | 82226200.85 | 0.230531E+09 | 14156985.56 | 0.216374E+09 | 0.00 | 0.00 |
September | 0.588689E+09 | 72851030.26 | 0.337154E+09 | 81824428.90 | 0.255330E+09 | 0.00 | 0.00 |
October | 0.885690E+09 | 0.124777E+09 | 0.493928E+09 | 0.238523E+09 | 0.255404E+09 | 0.00 | 0.00 |
November | 0.103291E+10 | 0.141224E+09 | 0.603564E+09 | 0.345985E+09 | 0.257579E+09 | 0.00 | 0.00 |
December | 0.111949E+10 | 0.171033E+09 | 0.674875E+09 | 0.434839E+09 | 0.240036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.810785E+10 | 0.166786E+10 | 0.478656E+10 | 0.195487E+10 | 0.283168E+10 | 0.00 | 0.00 |
Minimum of Months | 0.373078E+09 | 72851030.26 | 0.210327E+09 | 0.00 | 0.210164E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111949E+10 | 0.222084E+09 | 0.674875E+09 | 0.434839E+09 | 0.263898E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.106137E+10 | 0.220621E+09 | 0.653277E+09 | 0.410236E+09 | 0.243040E+09 | 0.00 | 0.00 |
February | 0.799794E+09 | 0.187727E+09 | 0.499802E+09 | 0.266430E+09 | 0.233371E+09 | 0.00 | 0.00 |
March | 0.621063E+09 | 0.203728E+09 | 0.401437E+09 | 0.137539E+09 | 0.263898E+09 | 0.00 | 0.00 |
April | 0.373111E+09 | 0.164453E+09 | 0.251202E+09 | 24192722.62 | 0.227009E+09 | 0.00 | 0.00 |
May | 0.391108E+09 | 0.125794E+09 | 0.219719E+09 | 567305.80 | 0.219152E+09 | 0.00 | 0.00 |
June | 0.374389E+09 | 93606165.53 | 0.210327E+09 | 0.00 | 0.210327E+09 | 0.00 | 0.00 |
July | 0.415710E+09 | 73735586.00 | 0.210740E+09 | 576123.10 | 0.210164E+09 | 0.00 | 0.00 |
August | 0.443839E+09 | 82470795.06 | 0.230531E+09 | 14156985.56 | 0.216374E+09 | 0.00 | 0.00 |
September | 0.588183E+09 | 73010698.16 | 0.337154E+09 | 81824428.90 | 0.255330E+09 | 0.00 | 0.00 |
October | 0.885270E+09 | 0.124781E+09 | 0.493928E+09 | 0.238523E+09 | 0.255404E+09 | 0.00 | 0.00 |
November | 0.103298E+10 | 0.140533E+09 | 0.603564E+09 | 0.345985E+09 | 0.257579E+09 | 0.00 | 0.00 |
December | 0.111973E+10 | 0.169961E+09 | 0.674875E+09 | 0.434839E+09 | 0.240036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.810656E+10 | 0.166042E+10 | 0.478656E+10 | 0.195487E+10 | 0.283168E+10 | 0.00 | 0.00 |
Minimum of Months | 0.373111E+09 | 73010698.16 | 0.210327E+09 | 0.00 | 0.210164E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111973E+10 | 0.220621E+09 | 0.674875E+09 | 0.434839E+09 | 0.263898E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105746E+10 | 0.216724E+09 | 0.653277E+09 | 0.410236E+09 | 0.243040E+09 | 0.00 | 0.00 |
February | 0.796968E+09 | 0.183577E+09 | 0.499802E+09 | 0.266430E+09 | 0.233371E+09 | 0.00 | 0.00 |
March | 0.616586E+09 | 0.199659E+09 | 0.401437E+09 | 0.137539E+09 | 0.263898E+09 | 0.00 | 0.00 |
April | 0.366827E+09 | 0.162212E+09 | 0.251202E+09 | 24192722.62 | 0.227009E+09 | 0.00 | 0.00 |
May | 0.382115E+09 | 0.126731E+09 | 0.219719E+09 | 567305.80 | 0.219152E+09 | 0.00 | 0.00 |
June | 0.365512E+09 | 95362748.90 | 0.210327E+09 | 0.00 | 0.210327E+09 | 0.00 | 0.00 |
July | 0.405202E+09 | 77603328.02 | 0.210740E+09 | 576123.10 | 0.210164E+09 | 0.00 | 0.00 |
August | 0.432569E+09 | 87196663.93 | 0.230531E+09 | 14156985.56 | 0.216374E+09 | 0.00 | 0.00 |
September | 0.579554E+09 | 77608563.66 | 0.337154E+09 | 81824428.90 | 0.255330E+09 | 0.00 | 0.00 |
October | 0.876171E+09 | 0.128643E+09 | 0.493928E+09 | 0.238523E+09 | 0.255404E+09 | 0.00 | 0.00 |
November | 0.102733E+10 | 0.140797E+09 | 0.603564E+09 | 0.345985E+09 | 0.257579E+09 | 0.00 | 0.00 |
December | 0.111506E+10 | 0.168380E+09 | 0.674875E+09 | 0.434839E+09 | 0.240036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.802134E+10 | 0.166449E+10 | 0.478656E+10 | 0.195487E+10 | 0.283168E+10 | 0.00 | 0.00 |
Minimum of Months | 0.365512E+09 | 77603328.02 | 0.210327E+09 | 0.00 | 0.210164E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111506E+10 | 0.216724E+09 | 0.674875E+09 | 0.434839E+09 | 0.263898E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 22.49 | 18.25 | 15.90 | 4.15 | 13.31 | 59.87 | 181.51 | 0.00 |
February | 22.80 | 19.74 | 18.20 | 3.70 | 14.21 | 74.30 | 182.84 | 0.03 |
March | 23.17 | 18.99 | 16.85 | 4.23 | 14.23 | 89.51 | 186.76 | 0.02 |
April | 23.76 | 19.01 | 16.50 | 4.83 | 14.94 | 95.22 | 199.35 | 0.00 |
May | 25.23 | 20.49 | 18.23 | 4.38 | 17.08 | 98.73 | 213.00 | 0.00 |
June | 25.87 | 20.89 | 18.70 | 5.87 | 17.20 | 99.16 | 227.55 | 0.00 |
July | 26.90 | 21.77 | 19.49 | 5.98 | 18.80 | 89.26 | 241.04 | 0.00 |
August | 27.06 | 21.88 | 19.61 | 5.21 | 18.26 | 83.09 | 253.22 | 0.00 |
September | 26.87 | 22.30 | 20.37 | 5.44 | 18.71 | 93.82 | 214.78 | 0.00 |
October | 26.22 | 21.67 | 19.68 | 3.78 | 17.26 | 74.41 | 199.79 | 0.00 |
November | 24.76 | 20.57 | 18.62 | 5.17 | 16.20 | 67.97 | 175.93 | 0.00 |
December | 23.69 | 19.64 | 17.67 | 4.42 | 14.96 | 56.37 | 177.80 | 0.00 |
Annual Sum or Average | 24.91 | 20.44 | 18.32 | 4.77 | 16.27 | 81.79 | 204.64 | 0.00 |
Minimum of Months | 22.49 | 18.25 | 15.90 | 3.70 | 13.31 | 56.37 | 175.93 | 0.00 |
Maximum of Months | 27.06 | 22.30 | 20.37 | 5.98 | 18.80 | 99.16 | 253.22 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.40 | 03-JAN-12:00 | 22.05 | 18.90 | 3.60 | 19.35 | 145.50 | 575.00 |
February | 28.90 | 19-FEB-10:00 | 22.34 | 19.40 | 3.10 | 18.28 | 204.00 | 595.50 |
March | 30.00 | 29-MAR-12:00 | 20.05 | 15.00 | 6.70 | 20.22 | 350.50 | 543.50 |
April | 30.00 | 09-APR-13:00 | 20.06 | 15.00 | 7.20 | 17.39 | 126.00 | 778.50 |
May | 31.10 | 17-MAY-13:20 | 21.31 | 16.70 | 7.87 | 22.12 | 283.17 | 716.50 |
June | 30.60 | 26-JUN-13:00 | 21.72 | 17.80 | 6.70 | 20.40 | 162.00 | 756.50 |
July | 32.20 | 09-JUL-11:00 | 23.42 | 20.00 | 6.20 | 23.49 | 235.00 | 733.00 |
August | 32.80 | 11-AUG-13:00 | 23.28 | 19.40 | 6.20 | 23.99 | 228.00 | 563.00 |
September | 33.30 | 02-SEP-12:00 | 23.47 | 19.40 | 5.70 | 23.32 | 185.00 | 789.00 |
October | 33.30 | 01-OCT-12:00 | 23.04 | 18.90 | 6.20 | 23.15 | 143.50 | 854.50 |
November | 30.60 | 03-NOV-12:00 | 22.49 | 18.90 | 7.70 | 20.57 | 148.00 | 798.50 |
December | 30.60 | 13-DEC-13:00 | 22.11 | 18.30 | 5.70 | 18.64 | 59.00 | 832.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 20.05 | 15.00 | 3.10 | 17.39 | 59.00 | 543.50 | |
Maximum of Months | 33.30 | 23.47 | 20.00 | 7.87 | 23.99 | 350.50 | 854.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.20 | 07-JAN-06:00 | 15.82 | 15.00 | 1.50 | 3.89 | 0.00 | 0.00 |
February | 13.30 | 12-FEB-06:00 | 12.64 | 12.20 | 3.10 | 0.73 | 0.00 | 0.00 |
March | 15.00 | 08-MAR-03:00 | 13.29 | 12.20 | 0.00 | 1.16 | 0.00 | 0.00 |
April | 17.80 | 22-APR-02:00 | 16.39 | 15.60 | 0.00 | 6.75 | 0.00 | 0.00 |
May | 18.90 | 23-MAY-05:00 | 17.45 | 16.70 | 2.10 | 9.33 | 110.00 | 159.50 |
June | 21.10 | 06-JUN-04:00 | 19.20 | 18.30 | 2.60 | 9.52 | 0.00 | 0.00 |
July | 22.20 | 09-JUL-03:00 | 20.00 | 18.90 | 1.50 | 11.84 | 0.00 | 0.00 |
August | 21.10 | 18-AUG-05:00 | 19.93 | 19.40 | 2.10 | 8.54 | 0.00 | 0.00 |
September | 22.20 | 19-SEP-04:00 | 20.25 | 19.40 | 2.60 | 11.84 | 0.00 | 0.00 |
October | 19.40 | 19-OCT-05:00 | 17.58 | 16.70 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 16.10 | 27-NOV-06:00 | 15.39 | 15.00 | 2.60 | 5.74 | 50.00 | 566.00 |
December | 16.70 | 26-DEC-01:00 | 15.01 | 13.90 | 2.60 | 4.31 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 12.64 | 12.20 | 0.00 | 0.73 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 20.25 | 19.40 | 3.10 | 11.84 | 110.00 | 566.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.03 | 01-JAN-15:00 | 27.80 | 21.10 | 4.10 | 20.92 | 91.00 | 199.00 |
February | 24.57 | 18-FEB-13:00 | 27.80 | 23.30 | 4.10 | 21.44 | 268.00 | 307.00 |
March | 23.81 | 13-MAR-12:00 | 27.80 | 22.20 | 5.70 | 22.47 | 468.50 | 259.00 |
April | 22.82 | 24-APR-11:00 | 28.30 | 20.60 | 4.60 | 19.87 | 357.00 | 446.00 |
May | 23.35 | 08-MAY-15:00 | 28.90 | 21.10 | 6.20 | 22.13 | 182.00 | 323.50 |
June | 23.02 | 20-JUN-13:00 | 28.90 | 20.60 | 7.70 | 21.96 | 370.50 | 346.50 |
July | 24.68 | 20-JUL-13:00 | 26.70 | 23.90 | 8.20 | 25.33 | 309.00 | 14.00 |
August | 25.47 | 19-AUG-14:00 | 31.70 | 23.30 | 5.20 | 25.33 | 229.00 | 409.00 |
September | 25.16 | 23-SEP-14:00 | 27.20 | 24.40 | 4.10 | 23.82 | 288.00 | 450.00 |
October | 24.72 | 15-OCT-13:00 | 31.70 | 22.20 | 5.20 | 22.98 | 151.50 | 527.00 |
November | 23.46 | 02-NOV-09:00 | 29.40 | 21.10 | 6.20 | 20.57 | 236.50 | 546.50 |
December | 23.69 | 03-DEC-10:00 | 26.10 | 22.80 | 6.70 | 24.50 | 251.50 | 3.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.82 | 26.10 | 20.60 | 4.10 | 19.87 | 91.00 | 3.00 | |
Maximum of Months | 25.47 | 31.70 | 24.40 | 8.20 | 25.33 | 468.50 | 546.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 01-JAN-15:00 | 27.80 | 23.03 | 4.10 | 20.92 | 91.00 | 199.00 |
February | 23.30 | 16-FEB-17:00 | 24.40 | 23.65 | 3.10 | 22.98 | 29.50 | 4.00 |
March | 22.20 | 13-MAR-10:00 | 27.20 | 23.57 | 4.60 | 21.78 | 336.00 | 148.00 |
April | 21.10 | 24-APR-23:00 | 22.80 | 21.58 | 1.50 | 18.82 | 0.00 | 0.00 |
May | 22.20 | 09-MAY-23:00 | 24.40 | 22.88 | 1.50 | 22.64 | 0.00 | 0.00 |
June | 20.80 | 09-JUN-00:10 | 22.15 | 21.03 | 3.78 | 18.14 | 0.00 | 0.00 |
July | 23.90 | 20-JUL-13:00 | 26.70 | 24.68 | 8.20 | 25.33 | 309.00 | 14.00 |
August | 23.30 | 19-AUG-14:00 | 31.70 | 25.47 | 5.20 | 25.33 | 229.00 | 409.00 |
September | 24.40 | 23-SEP-14:00 | 27.20 | 25.16 | 4.10 | 23.82 | 288.00 | 450.00 |
October | 22.80 | 24-OCT-12:00 | 26.10 | 23.69 | 4.10 | 19.70 | 259.00 | 474.50 |
November | 21.70 | 29-NOV-17:00 | 26.10 | 22.98 | 3.10 | 22.13 | 0.00 | 0.00 |
December | 22.80 | 03-DEC-10:00 | 26.10 | 23.69 | 6.70 | 24.50 | 251.50 | 3.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.80 | 22.15 | 21.03 | 1.50 | 18.14 | 0.00 | 0.00 | |
Maximum of Months | 24.40 | 31.70 | 25.47 | 8.20 | 25.33 | 336.00 | 474.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 26.59 | 31.34 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 26.78 | 37.09 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 27.35 | 43.34 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 28.17 | 47.38 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.01 | 50.82 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.64 | 52.70 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.90 | 53.08 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.71 | 53.00 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.13 | 48.47 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.31 | 39.62 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.47 | 33.78 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 26.84 | 30.10 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.25 | 43.42 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 26.59 | 30.10 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.90 | 53.08 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.271378E+09 | -159031006.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112347007.1 | 59.00 | 0.00 | 0.00 |
February | 0.245015E+09 | -143585889.2 | 0.00 | 0.00 | 672.00 | 0.00 | -101428641.7 | 58.99 | 0.00 | 0.00 |
March | 0.270923E+09 | -158623005.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112300173.0 | 58.99 | 0.00 | 0.00 |
April | 0.256460E+09 | -147825421.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108634251.6 | 58.99 | 0.00 | 0.00 |
May | 0.260685E+09 | -148725215.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111959682.8 | 58.99 | 0.00 | 0.00 |
June | 0.250388E+09 | -142217367.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108170742.1 | 58.99 | 0.00 | 0.00 |
July | 0.254510E+09 | -142903247.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111606346.3 | 58.99 | 0.00 | 0.00 |
August | 0.258259E+09 | -146662406.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111596377.6 | 58.99 | 0.00 | 0.00 |
September | 0.251251E+09 | -143356801.5 | 0.00 | 0.00 | 720.00 | 0.00 | -107894574.2 | 58.99 | 0.00 | 0.00 |
October | 0.262402E+09 | -150657117.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111744444.7 | 58.99 | 0.00 | 0.00 |
November | 0.257623E+09 | -149370161.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108253229.7 | 58.99 | 0.00 | 0.00 |
December | 0.270109E+09 | -158053806.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112054840.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.310900E+10 | -.179101E+10 | 8760.00 | -.131799E+10 | 58.99 | |||||
Minimum of Months | 0.245015E+09 | -159031006.7 | 0.00 | 0.00 | 672.00 | 0.00 | -112347007.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.271378E+09 | -142217367.1 | 0.00 | 0.00 | 744.00 | 0.00 | -101428641.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.271165E+09 | -159028207.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112136788.7 | 59.00 | 0.00 | 0.00 |
February | 0.244849E+09 | -143582703.8 | 0.00 | 0.00 | 672.00 | 0.00 | -101266667.7 | 58.99 | 0.00 | 0.00 |
March | 0.270736E+09 | -158623013.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112113327.0 | 58.99 | 0.00 | 0.00 |
April | 0.256302E+09 | -147829794.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108471964.5 | 58.99 | 0.00 | 0.00 |
May | 0.260554E+09 | -148731097.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111823302.0 | 58.99 | 0.00 | 0.00 |
June | 0.250290E+09 | -142212909.8 | 0.00 | 0.00 | 720.00 | 0.00 | -108077496.9 | 58.99 | 0.00 | 0.00 |
July | 0.254442E+09 | -142891205.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111550946.2 | 58.99 | 0.00 | 0.00 |
August | 0.258207E+09 | -146663374.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111543152.2 | 58.99 | 0.00 | 0.00 |
September | 0.251221E+09 | -143350685.4 | 0.00 | 0.00 | 720.00 | 0.00 | -107870559.4 | 58.99 | 0.00 | 0.00 |
October | 0.262308E+09 | -150645763.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111661975.8 | 58.99 | 0.00 | 0.00 |
November | 0.257502E+09 | -149368337.4 | 0.00 | 0.00 | 720.00 | 0.00 | -108133301.8 | 58.99 | 0.00 | 0.00 |
December | 0.269948E+09 | -158056844.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111891250.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.310752E+10 | -.179098E+10 | 8760.00 | -.131654E+10 | 58.99 | |||||
Minimum of Months | 0.244849E+09 | -159028207.3 | 0.00 | 0.00 | 672.00 | 0.00 | -112136788.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.271165E+09 | -142212909.8 | 0.00 | 0.00 | 744.00 | 0.00 | -101266667.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.250897E+09 | -139844578.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111052784.1 | 59.00 | 0.00 | 0.00 |
February | 0.226575E+09 | -126374868.4 | 0.00 | 0.00 | 672.00 | 0.00 | -100199854.6 | 58.99 | 0.00 | 0.00 |
March | 0.252600E+09 | -141663901.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110936424.1 | 58.99 | 0.00 | 0.00 |
April | 0.237211E+09 | -129924286.0 | 0.00 | 0.00 | 720.00 | 0.00 | -107286763.1 | 58.99 | 0.00 | 0.00 |
May | 0.242261E+09 | -131891822.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110369475.9 | 58.99 | 0.00 | 0.00 |
June | 0.233383E+09 | -126781919.4 | 0.00 | 0.00 | 720.00 | 0.00 | -106601461.4 | 58.98 | 0.00 | 0.00 |
July | 0.234546E+09 | -124845781.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109699881.0 | 58.99 | 0.00 | 0.00 |
August | 0.240934E+09 | -131115443.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109818919.8 | 58.98 | 0.00 | 0.00 |
September | 0.231861E+09 | -125892330.3 | 0.00 | 0.00 | 720.00 | 0.00 | -105968502.7 | 58.99 | 0.00 | 0.00 |
October | 0.242336E+09 | -132483684.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109852706.5 | 58.99 | 0.00 | 0.00 |
November | 0.238660E+09 | -131897417.2 | 0.00 | 0.00 | 720.00 | 0.00 | -106762479.5 | 58.99 | 0.00 | 0.00 |
December | 0.248574E+09 | -137976201.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110598059.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.287984E+10 | -.158069E+10 | 8760.00 | -.129915E+10 | 58.99 | |||||
Minimum of Months | 0.226575E+09 | -141663901.9 | 0.00 | 0.00 | 672.00 | 0.00 | -111052784.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.252600E+09 | -124845781.5 | 0.00 | 0.00 | 744.00 | 0.00 | -100199854.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.250923E+09 | -139844293.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111078569.1 | 59.00 | 0.00 | 0.00 |
February | 0.226589E+09 | -126373317.3 | 0.00 | 0.00 | 672.00 | 0.00 | -100215693.4 | 58.99 | 0.00 | 0.00 |
March | 0.252610E+09 | -141663216.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110947231.7 | 58.99 | 0.00 | 0.00 |
April | 0.237224E+09 | -129924462.1 | 0.00 | 0.00 | 720.00 | 0.00 | -107299062.1 | 58.99 | 0.00 | 0.00 |
May | 0.242240E+09 | -131889611.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110350252.5 | 58.99 | 0.00 | 0.00 |
June | 0.233354E+09 | -126781077.4 | 0.00 | 0.00 | 720.00 | 0.00 | -106572455.7 | 58.98 | 0.00 | 0.00 |
July | 0.234482E+09 | -124843490.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109638535.2 | 58.99 | 0.00 | 0.00 |
August | 0.240878E+09 | -131102300.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109776054.3 | 58.99 | 0.00 | 0.00 |
September | 0.231785E+09 | -125898082.6 | 0.00 | 0.00 | 720.00 | 0.00 | -105887323.6 | 58.99 | 0.00 | 0.00 |
October | 0.242278E+09 | -132501770.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109776546.5 | 58.99 | 0.00 | 0.00 |
November | 0.238637E+09 | -131887760.6 | 0.00 | 0.00 | 720.00 | 0.00 | -106749569.2 | 58.99 | 0.00 | 0.00 |
December | 0.248581E+09 | -137977059.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110603878.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.287958E+10 | -.158069E+10 | 8760.00 | -.129890E+10 | 58.99 | |||||
Minimum of Months | 0.226589E+09 | -141663216.9 | 0.00 | 0.00 | 672.00 | 0.00 | -111078569.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.252610E+09 | -124843490.0 | 0.00 | 0.00 | 744.00 | 0.00 | -100215693.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.243826E+09 | -132175210.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111650494.3 | 59.00 | 0.00 | 0.00 |
February | 0.220243E+09 | -119501711.5 | 0.00 | 0.00 | 672.00 | 0.00 | -100741448.6 | 58.99 | 0.00 | 0.00 |
March | 0.245627E+09 | -134054226.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111572589.1 | 58.99 | 0.00 | 0.00 |
April | 0.230840E+09 | -122940918.3 | 0.00 | 0.00 | 720.00 | 0.00 | -107899245.3 | 58.99 | 0.00 | 0.00 |
May | 0.235670E+09 | -124725773.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110944208.4 | 58.99 | 0.00 | 0.00 |
June | 0.227091E+09 | -119966912.9 | 0.00 | 0.00 | 720.00 | 0.00 | -107124124.3 | 58.98 | 0.00 | 0.00 |
July | 0.228213E+09 | -118061954.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110151407.3 | 58.99 | 0.00 | 0.00 |
August | 0.234437E+09 | -124036916.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110399852.0 | 58.99 | 0.00 | 0.00 |
September | 0.225573E+09 | -119121836.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106451174.9 | 58.99 | 0.00 | 0.00 |
October | 0.235594E+09 | -125213130.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110381009.4 | 58.99 | 0.00 | 0.00 |
November | 0.231812E+09 | -124562970.8 | 0.00 | 0.00 | 720.00 | 0.00 | -107248998.9 | 58.99 | 0.00 | 0.00 |
December | 0.241626E+09 | -130510657.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111115609.3 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.280055E+10 | -.149487E+10 | 8760.00 | -.130568E+10 | 58.99 | |||||
Minimum of Months | 0.220243E+09 | -134054226.5 | 0.00 | 0.00 | 672.00 | 0.00 | -111650494.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.245627E+09 | -118061954.7 | 0.00 | 0.00 | 744.00 | 0.00 | -100741448.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.243925E+09 | -132179504.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111745045.1 | 59.00 | 0.00 | 0.00 |
February | 0.220340E+09 | -119498555.6 | 0.00 | 0.00 | 672.00 | 0.00 | -100841486.9 | 58.99 | 0.00 | 0.00 |
March | 0.245733E+09 | -134052101.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111680528.3 | 58.99 | 0.00 | 0.00 |
April | 0.230935E+09 | -122959418.1 | 0.00 | 0.00 | 720.00 | 0.00 | -107975214.4 | 58.99 | 0.00 | 0.00 |
May | 0.235784E+09 | -124732995.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111050996.7 | 58.99 | 0.00 | 0.00 |
June | 0.227207E+09 | -119928070.6 | 0.00 | 0.00 | 720.00 | 0.00 | -107278653.7 | 58.99 | 0.00 | 0.00 |
July | 0.228356E+09 | -118084861.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110271102.1 | 58.99 | 0.00 | 0.00 |
August | 0.234562E+09 | -124045567.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110515977.7 | 58.99 | 0.00 | 0.00 |
September | 0.225702E+09 | -119144102.3 | 0.00 | 0.00 | 720.00 | 0.00 | -106557863.6 | 58.99 | 0.00 | 0.00 |
October | 0.235728E+09 | -125206518.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110521013.0 | 59.00 | 0.00 | 0.00 |
November | 0.231932E+09 | -124559193.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107373179.4 | 58.99 | 0.00 | 0.00 |
December | 0.241737E+09 | -130506581.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111230743.2 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.280194E+10 | -.149490E+10 | 8760.00 | -.130704E+10 | 58.99 | |||||
Minimum of Months | 0.220340E+09 | -134052101.3 | 0.00 | 0.00 | 672.00 | 0.00 | -111745045.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.245733E+09 | -118084861.4 | 0.00 | 0.00 | 744.00 | 0.00 | -100841486.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.243969E+09 | -132181403.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111788094.9 | 59.00 | 0.00 | 0.00 |
February | 0.220383E+09 | -119494622.0 | 0.00 | 0.00 | 672.00 | 0.00 | -100888826.2 | 58.99 | 0.00 | 0.00 |
March | 0.245777E+09 | -134048850.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111728237.2 | 58.99 | 0.00 | 0.00 |
April | 0.230970E+09 | -122944739.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108024907.3 | 58.99 | 0.00 | 0.00 |
May | 0.235821E+09 | -124743625.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111077240.6 | 58.98 | 0.00 | 0.00 |
June | 0.227250E+09 | -119923887.8 | 0.00 | 0.00 | 720.00 | 0.00 | -107325981.6 | 59.00 | 0.00 | 0.00 |
July | 0.228385E+09 | -118079894.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110305039.8 | 58.99 | 0.00 | 0.00 |
August | 0.234595E+09 | -124031499.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110563215.1 | 58.99 | 0.00 | 0.00 |
September | 0.225746E+09 | -119125677.3 | 0.00 | 0.00 | 720.00 | 0.00 | -106620717.4 | 58.99 | 0.00 | 0.00 |
October | 0.235763E+09 | -125221246.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110541885.1 | 58.99 | 0.00 | 0.00 |
November | 0.231970E+09 | -124549320.1 | 0.00 | 0.00 | 720.00 | 0.00 | -107421062.3 | 58.99 | 0.00 | 0.00 |
December | 0.241785E+09 | -130480400.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111304475.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.280241E+10 | -.149483E+10 | 8760.00 | -.130759E+10 | 58.99 | |||||
Minimum of Months | 0.220383E+09 | -134048850.2 | 0.00 | 0.00 | 672.00 | 0.00 | -111788094.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.245777E+09 | -118079894.0 | 0.00 | 0.00 | 744.00 | 0.00 | -100888826.2 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 326.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 285.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 336.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 360.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 384.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 392.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 398.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 382.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 346.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 316.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 318.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4207.17 | ||||||||||
Minimum of Months | 285.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 398.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.231825E+11 | 0.158065E+11 | 47767.37 | 31-JAN-08:62 | 27396.69 | 0.00 |
February | 0.00 | 0.00 | 0.248336E+11 | 0.152269E+11 | 49451.36 | 17-FEB-08:62 | 23754.60 | 0.00 |
March | 0.00 | 0.00 | 0.260003E+11 | 0.173780E+11 | 48237.15 | 03-MAR-08:62 | 25302.52 | 0.00 |
April | 0.00 | 0.00 | 0.247874E+11 | 0.170576E+11 | 47246.92 | 25-APR-07:02 | 29647.03 | 0.00 |
May | 0.00 | 0.00 | 0.318883E+11 | 0.211516E+11 | 48545.05 | 10-MAY-07:02 | 26669.96 | 0.00 |
June | 0.00 | 0.00 | 0.325194E+11 | 0.214426E+11 | 48094.14 | 14-JUN-07:02 | 28167.96 | 0.00 |
July | 0.00 | 0.00 | 0.382272E+11 | 0.248529E+11 | 49394.11 | 20-JUL-07:02 | 25482.61 | 0.00 |
August | 0.00 | 0.00 | 0.389160E+11 | 0.254991E+11 | 48672.13 | 08-AUG-07:02 | 27278.30 | 0.00 |
September | 0.00 | 0.00 | 0.391689E+11 | 0.246179E+11 | 49050.35 | 30-SEP-07:02 | 25543.15 | 0.00 |
October | 0.00 | 0.00 | 0.379719E+11 | 0.244462E+11 | 48379.24 | 13-OCT-07:02 | 27813.97 | 0.00 |
November | 0.00 | 0.00 | 0.314542E+11 | 0.202825E+11 | 48510.51 | 01-NOV-07:02 | 27189.92 | 0.00 |
December | 0.00 | 0.00 | 0.284016E+11 | 0.183853E+11 | 48787.81 | 03-DEC-08:61 | 27241.40 | 0.00 |
Annual Sum or Average | 0.377351E+12 | 0.246147E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.231825E+11 | 0.152269E+11 | 47246.92 | 23754.60 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.391689E+11 | 0.254991E+11 | 49451.36 | 29647.03 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.124747E+11 | 0.881098E+10 | 24619.56 | 31-JAN-08:62 | 16227.29 | 0.00 |
February | 0.00 | 0.00 | 0.129813E+11 | 0.828975E+10 | 25323.84 | 17-FEB-08:62 | 14624.86 | 0.00 |
March | 0.00 | 0.00 | 0.135798E+11 | 0.937171E+10 | 24746.84 | 03-MAR-08:62 | 15496.61 | 0.00 |
April | 0.00 | 0.00 | 0.128639E+11 | 0.913132E+10 | 24316.24 | 18-APR-07:03 | 17008.34 | 0.00 |
May | 0.00 | 0.00 | 0.161940E+11 | 0.110645E+11 | 24952.51 | 10-MAY-07:02 | 15893.06 | 0.00 |
June | 0.00 | 0.00 | 0.163281E+11 | 0.110631E+11 | 24832.47 | 14-JUN-07:02 | 16276.33 | 0.00 |
July | 0.00 | 0.00 | 0.189765E+11 | 0.126830E+11 | 25392.39 | 20-JUL-07:02 | 15059.80 | 0.00 |
August | 0.00 | 0.00 | 0.193166E+11 | 0.129873E+11 | 25066.22 | 08-AUG-07:02 | 15886.90 | 0.00 |
September | 0.00 | 0.00 | 0.192237E+11 | 0.124157E+11 | 25200.84 | 30-SEP-07:02 | 15287.76 | 0.00 |
October | 0.00 | 0.00 | 0.191103E+11 | 0.126718E+11 | 24900.60 | 13-OCT-07:02 | 16232.61 | 0.00 |
November | 0.00 | 0.00 | 0.160634E+11 | 0.106936E+11 | 25004.33 | 01-NOV-07:02 | 15899.15 | 0.00 |
December | 0.00 | 0.00 | 0.147952E+11 | 0.993402E+10 | 25202.84 | 03-DEC-08:61 | 15674.31 | 0.00 |
Annual Sum or Average | 0.191907E+12 | 0.129117E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.124747E+11 | 0.828975E+10 | 24316.24 | 14624.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.193166E+11 | 0.129873E+11 | 25392.39 | 17008.34 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.975870E+10 | 0.673852E+10 | 26482.29 | 02-JAN-07:02 | 14711.95 | 0.00 |
February | 0.00 | 0.00 | 0.102322E+11 | 0.634880E+10 | 27257.34 | 18-FEB-07:02 | 12607.68 | 0.00 |
March | 0.00 | 0.00 | 0.107669E+11 | 0.726640E+10 | 26888.65 | 13-MAR-06:02 | 13461.08 | 0.00 |
April | 0.00 | 0.00 | 0.100873E+11 | 0.700202E+10 | 26395.15 | 24-APR-06:03 | 14286.92 | 0.00 |
May | 0.00 | 0.00 | 0.130774E+11 | 0.876204E+10 | 26880.60 | 15-MAY-06:02 | 13211.43 | 0.00 |
June | 0.00 | 0.00 | 0.133190E+11 | 0.881324E+10 | 26430.05 | 18-JUN-07:02 | 15567.67 | 0.00 |
July | 0.00 | 0.00 | 0.153659E+11 | 0.100518E+11 | 27264.50 | 23-JUL-07:01 | 13482.46 | 0.00 |
August | 0.00 | 0.00 | 0.159561E+11 | 0.105467E+11 | 27006.02 | 20-AUG-07:02 | 14006.74 | 0.00 |
September | 0.00 | 0.00 | 0.155092E+11 | 0.979343E+10 | 27467.04 | 25-SEP-06:02 | 12351.77 | 0.00 |
October | 0.00 | 0.00 | 0.155100E+11 | 0.100992E+11 | 26882.93 | 10-OCT-06:02 | 13367.83 | 0.00 |
November | 0.00 | 0.00 | 0.130454E+11 | 0.849056E+10 | 26707.69 | 24-NOV-07:02 | 14068.05 | 0.00 |
December | 0.00 | 0.00 | 0.117263E+11 | 0.767240E+10 | 26873.97 | 03-DEC-08:61 | 14485.43 | 0.00 |
Annual Sum or Average | 0.154354E+12 | 0.101585E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.975870E+10 | 0.634880E+10 | 26395.15 | 12351.77 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.159561E+11 | 0.105467E+11 | 27467.04 | 15567.67 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.971819E+10 | 0.670835E+10 | 26308.59 | 02-JAN-07:02 | 14626.50 | 0.00 |
February | 0.00 | 0.00 | 0.102006E+11 | 0.632619E+10 | 27077.66 | 18-FEB-07:02 | 12512.89 | 0.00 |
March | 0.00 | 0.00 | 0.107390E+11 | 0.724587E+10 | 26712.09 | 13-MAR-06:02 | 13379.11 | 0.00 |
April | 0.00 | 0.00 | 0.100560E+11 | 0.697869E+10 | 26219.48 | 24-APR-06:03 | 14184.67 | 0.00 |
May | 0.00 | 0.00 | 0.130720E+11 | 0.875885E+10 | 26705.14 | 15-MAY-06:02 | 13137.53 | 0.00 |
June | 0.00 | 0.00 | 0.133210E+11 | 0.881574E+10 | 26258.55 | 18-JUN-07:02 | 15484.75 | 0.00 |
July | 0.00 | 0.00 | 0.153960E+11 | 0.100762E+11 | 27088.49 | 23-JUL-07:01 | 13416.86 | 0.00 |
August | 0.00 | 0.00 | 0.159813E+11 | 0.105677E+11 | 26832.66 | 20-AUG-07:02 | 13943.45 | 0.00 |
September | 0.00 | 0.00 | 0.155536E+11 | 0.982769E+10 | 27291.93 | 25-SEP-06:02 | 12316.80 | 0.00 |
October | 0.00 | 0.00 | 0.155435E+11 | 0.101258E+11 | 26711.05 | 10-OCT-06:02 | 13321.38 | 0.00 |
November | 0.00 | 0.00 | 0.130393E+11 | 0.848693E+10 | 26534.30 | 24-NOV-07:02 | 13993.24 | 0.00 |
December | 0.00 | 0.00 | 0.117038E+11 | 0.765578E+10 | 26697.71 | 03-DEC-08:61 | 14397.64 | 0.00 |
Annual Sum or Average | 0.154324E+12 | 0.101574E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.971819E+10 | 0.632619E+10 | 26219.48 | 12316.80 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.159813E+11 | 0.105677E+11 | 27291.93 | 15484.75 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.946612E+10 | 0.651277E+10 | 26293.64 | 02-JAN-07:02 | 14548.30 | 0.00 |
February | 0.00 | 0.00 | 0.995388E+10 | 0.614620E+10 | 27065.36 | 18-FEB-07:02 | 12387.15 | 0.00 |
March | 0.00 | 0.00 | 0.104714E+11 | 0.704121E+10 | 26695.79 | 13-MAR-06:02 | 13286.21 | 0.00 |
April | 0.00 | 0.00 | 0.980559E+10 | 0.678456E+10 | 26202.94 | 24-APR-06:03 | 14086.77 | 0.00 |
May | 0.00 | 0.00 | 0.128313E+11 | 0.857050E+10 | 26690.46 | 15-MAY-06:02 | 13057.74 | 0.00 |
June | 0.00 | 0.00 | 0.130926E+11 | 0.863725E+10 | 26240.10 | 18-JUN-07:02 | 15386.61 | 0.00 |
July | 0.00 | 0.00 | 0.151756E+11 | 0.990187E+10 | 27070.85 | 23-JUL-07:01 | 13312.02 | 0.00 |
August | 0.00 | 0.00 | 0.157470E+11 | 0.103820E+11 | 26816.72 | 20-AUG-07:02 | 13846.21 | 0.00 |
September | 0.00 | 0.00 | 0.153328E+11 | 0.965636E+10 | 27277.90 | 25-SEP-06:02 | 12240.91 | 0.00 |
October | 0.00 | 0.00 | 0.153139E+11 | 0.994538E+10 | 26698.03 | 10-OCT-06:02 | 13253.93 | 0.00 |
November | 0.00 | 0.00 | 0.128132E+11 | 0.831283E+10 | 26518.98 | 24-NOV-07:02 | 13912.78 | 0.00 |
December | 0.00 | 0.00 | 0.114611E+11 | 0.746972E+10 | 26679.21 | 03-DEC-08:61 | 14295.88 | 0.00 |
Annual Sum or Average | 0.151465E+12 | 0.993606E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.946612E+10 | 0.614620E+10 | 26202.94 | 12240.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.157470E+11 | 0.103820E+11 | 27277.90 | 15386.61 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.160407E+11 | 0.107454E+11 | 45372.24 | 01-JAN-09:02 | 24905.88 | 0.00 |
February | 0.00 | 0.00 | 0.170794E+11 | 0.102077E+11 | 46322.99 | 18-FEB-08:62 | 21951.97 | 0.00 |
March | 0.00 | 0.00 | 0.180020E+11 | 0.117907E+11 | 45973.84 | 13-MAR-07:02 | 22402.54 | 0.00 |
April | 0.00 | 0.00 | 0.167377E+11 | 0.113039E+11 | 45223.76 | 24-APR-07:03 | 23875.22 | 0.00 |
May | 0.00 | 0.00 | 0.224042E+11 | 0.146308E+11 | 46029.35 | 15-MAY-07:02 | 22346.52 | 0.00 |
June | 0.00 | 0.00 | 0.228875E+11 | 0.147520E+11 | 45249.64 | 18-JUN-08:61 | 26543.62 | 0.00 |
July | 0.00 | 0.00 | 0.267332E+11 | 0.170796E+11 | 46742.92 | 23-JUL-08:61 | 23078.04 | 0.00 |
August | 0.00 | 0.00 | 0.279121E+11 | 0.180445E+11 | 46282.16 | 20-AUG-08:61 | 24118.66 | 0.00 |
September | 0.00 | 0.00 | 0.270186E+11 | 0.166530E+11 | 47012.40 | 25-SEP-07:02 | 20811.10 | 0.00 |
October | 0.00 | 0.00 | 0.271398E+11 | 0.172629E+11 | 46014.49 | 10-OCT-07:02 | 22541.16 | 0.00 |
November | 0.00 | 0.00 | 0.223204E+11 | 0.141225E+11 | 45818.91 | 24-NOV-08:62 | 24094.94 | 0.00 |
December | 0.00 | 0.00 | 0.197214E+11 | 0.124989E+11 | 46218.15 | 03-DEC-09:01 | 23911.89 | 0.00 |
Annual Sum or Average | 0.263997E+12 | 0.169092E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.160407E+11 | 0.102077E+11 | 45223.76 | 20811.10 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.279121E+11 | 0.180445E+11 | 47012.40 | 26543.62 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.824843E+10 | 0.553245E+10 | 23637.41 | 01-JAN-09:02 | 12958.86 | 0.00 |
February | 0.00 | 0.00 | 0.878277E+10 | 0.525403E+10 | 24113.38 | 18-FEB-08:62 | 11460.92 | 0.00 |
March | 0.00 | 0.00 | 0.926185E+10 | 0.607159E+10 | 23963.87 | 13-MAR-07:02 | 11640.60 | 0.00 |
April | 0.00 | 0.00 | 0.861415E+10 | 0.582364E+10 | 23563.33 | 24-APR-07:03 | 12428.08 | 0.00 |
May | 0.00 | 0.00 | 0.115605E+11 | 0.755520E+10 | 23994.16 | 15-MAY-07:02 | 11596.09 | 0.00 |
June | 0.00 | 0.00 | 0.118005E+11 | 0.761299E+10 | 23568.43 | 18-JUN-08:61 | 13799.90 | 0.00 |
July | 0.00 | 0.00 | 0.138190E+11 | 0.883599E+10 | 24349.02 | 23-JUL-08:61 | 11968.91 | 0.00 |
August | 0.00 | 0.00 | 0.144316E+11 | 0.933717E+10 | 24111.06 | 20-AUG-08:61 | 12517.39 | 0.00 |
September | 0.00 | 0.00 | 0.139563E+11 | 0.860935E+10 | 24513.97 | 25-SEP-07:02 | 10769.32 | 0.00 |
October | 0.00 | 0.00 | 0.140389E+11 | 0.893724E+10 | 23990.98 | 10-OCT-07:02 | 11703.78 | 0.00 |
November | 0.00 | 0.00 | 0.115125E+11 | 0.729284E+10 | 23873.75 | 24-NOV-08:62 | 12522.03 | 0.00 |
December | 0.00 | 0.00 | 0.101589E+11 | 0.644666E+10 | 24069.67 | 03-DEC-09:01 | 12433.23 | 0.00 |
Annual Sum or Average | 0.136185E+12 | 0.873091E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.824843E+10 | 0.525403E+10 | 23563.33 | 10769.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.144316E+11 | 0.933717E+10 | 24513.97 | 13799.90 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.817138E+10 | 0.547229E+10 | 23526.04 | 01-JAN-09:02 | 12875.84 | 0.00 |
February | 0.00 | 0.00 | 0.870527E+10 | 0.519726E+10 | 24003.90 | 18-FEB-08:62 | 11372.86 | 0.00 |
March | 0.00 | 0.00 | 0.918239E+10 | 0.601030E+10 | 23850.32 | 13-MAR-07:02 | 11563.31 | 0.00 |
April | 0.00 | 0.00 | 0.854560E+10 | 0.576945E+10 | 23452.22 | 24-APR-07:03 | 12347.32 | 0.00 |
May | 0.00 | 0.00 | 0.114921E+11 | 0.750049E+10 | 23881.11 | 15-MAY-07:02 | 11520.78 | 0.00 |
June | 0.00 | 0.00 | 0.117331E+11 | 0.755921E+10 | 23457.37 | 18-JUN-08:61 | 13715.84 | 0.00 |
July | 0.00 | 0.00 | 0.137536E+11 | 0.878316E+10 | 24235.10 | 23-JUL-08:61 | 11893.85 | 0.00 |
August | 0.00 | 0.00 | 0.143673E+11 | 0.928468E+10 | 23999.12 | 20-AUG-08:61 | 12444.78 | 0.00 |
September | 0.00 | 0.00 | 0.138896E+11 | 0.855663E+10 | 24398.84 | 25-SEP-07:02 | 10703.74 | 0.00 |
October | 0.00 | 0.00 | 0.139715E+11 | 0.888304E+10 | 23877.96 | 10-OCT-07:02 | 11630.76 | 0.00 |
November | 0.00 | 0.00 | 0.114379E+11 | 0.723473E+10 | 23761.07 | 24-NOV-08:62 | 12439.99 | 0.00 |
December | 0.00 | 0.00 | 0.100820E+11 | 0.638691E+10 | 23956.87 | 03-DEC-09:01 | 12354.20 | 0.00 |
Annual Sum or Average | 0.135332E+12 | 0.866382E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.817138E+10 | 0.519726E+10 | 23452.22 | 10703.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.143673E+11 | 0.928468E+10 | 24398.84 | 13715.84 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.807566E+10 | 0.540390E+10 | 23531.87 | 01-JAN-09:02 | 12836.30 | 0.00 |
February | 0.00 | 0.00 | 0.859571E+10 | 0.512362E+10 | 24014.80 | 18-FEB-08:62 | 11311.47 | 0.00 |
March | 0.00 | 0.00 | 0.908095E+10 | 0.593959E+10 | 23858.95 | 13-MAR-07:02 | 11530.94 | 0.00 |
April | 0.00 | 0.00 | 0.848739E+10 | 0.572826E+10 | 23459.14 | 24-APR-07:03 | 12312.37 | 0.00 |
May | 0.00 | 0.00 | 0.114820E+11 | 0.749423E+10 | 23889.67 | 15-MAY-07:02 | 11493.53 | 0.00 |
June | 0.00 | 0.00 | 0.117297E+11 | 0.755806E+10 | 23466.44 | 18-JUN-08:61 | 13697.34 | 0.00 |
July | 0.00 | 0.00 | 0.137756E+11 | 0.880118E+10 | 24246.35 | 23-JUL-08:61 | 11880.08 | 0.00 |
August | 0.00 | 0.00 | 0.144069E+11 | 0.931569E+10 | 24010.11 | 20-AUG-08:61 | 12436.81 | 0.00 |
September | 0.00 | 0.00 | 0.139032E+11 | 0.856787E+10 | 24410.86 | 25-SEP-07:02 | 10692.92 | 0.00 |
October | 0.00 | 0.00 | 0.139848E+11 | 0.889430E+10 | 23889.14 | 10-OCT-07:02 | 11619.09 | 0.00 |
November | 0.00 | 0.00 | 0.113933E+11 | 0.720408E+10 | 23769.17 | 24-NOV-08:62 | 12411.25 | 0.00 |
December | 0.00 | 0.00 | 0.100080E+11 | 0.633484E+10 | 23966.31 | 03-DEC-09:01 | 12331.09 | 0.00 |
Annual Sum or Average | 0.134923E+12 | 0.863656E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.807566E+10 | 0.512362E+10 | 23459.14 | 10692.92 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.144069E+11 | 0.931569E+10 | 24410.86 | 13697.34 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.899519E+10 | 0.616736E+10 | 25945.90 | 02-JAN-08:62 | 14273.87 | 0.00 |
February | 0.00 | 0.00 | 0.931120E+10 | 0.569361E+10 | 26887.43 | 18-FEB-08:62 | 11424.38 | 0.00 |
March | 0.00 | 0.00 | 0.998689E+10 | 0.669133E+10 | 26381.28 | 13-MAR-07:02 | 12684.72 | 0.00 |
April | 0.00 | 0.00 | 0.968753E+10 | 0.669860E+10 | 25496.82 | 09-APR-08:62 | 15455.80 | 0.00 |
May | 0.00 | 0.00 | 0.131899E+11 | 0.884707E+10 | 26365.02 | 15-MAY-07:02 | 12836.07 | 0.00 |
June | 0.00 | 0.00 | 0.134658E+11 | 0.890892E+10 | 26027.37 | 25-JUN-08:61 | 15220.72 | 0.00 |
July | 0.00 | 0.00 | 0.157587E+11 | 0.103469E+11 | 26922.31 | 23-JUL-08:61 | 13446.84 | 0.00 |
August | 0.00 | 0.00 | 0.165726E+11 | 0.110153E+11 | 26650.46 | 20-AUG-08:61 | 13909.98 | 0.00 |
September | 0.00 | 0.00 | 0.155848E+11 | 0.986237E+10 | 26962.66 | 25-SEP-07:02 | 11903.89 | 0.00 |
October | 0.00 | 0.00 | 0.158350E+11 | 0.103605E+11 | 26429.67 | 10-OCT-07:02 | 12813.69 | 0.00 |
November | 0.00 | 0.00 | 0.126517E+11 | 0.819449E+10 | 26291.68 | 24-NOV-08:62 | 13679.35 | 0.00 |
December | 0.00 | 0.00 | 0.110676E+11 | 0.718157E+10 | 26565.41 | 03-DEC-09:01 | 13673.96 | 0.00 |
Annual Sum or Average | 0.152107E+12 | 0.999681E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.899519E+10 | 0.569361E+10 | 25496.82 | 11424.38 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.165726E+11 | 0.110153E+11 | 26962.66 | 15455.80 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148132E+10 | 0.36 | 2021.46 | 01-JAN-08:62 | 0.87 |
February | 0.136056E+10 | 0.36 | 2021.46 | 04-FEB-08:62 | 0.87 |
March | 0.148891E+10 | 0.36 | 2021.46 | 02-MAR-08:62 | 0.87 |
April | 0.143023E+10 | 0.36 | 2021.46 | 07-APR-07:03 | 0.87 |
May | 0.151462E+10 | 0.36 | 2021.46 | 01-MAY-07:03 | 0.87 |
June | 0.147862E+10 | 0.36 | 2021.46 | 01-JUN-07:02 | 0.86 |
July | 0.164002E+10 | 0.38 | 2021.46 | 01-JUL-07:02 | 0.87 |
August | 0.167344E+10 | 0.38 | 2021.46 | 01-AUG-07:02 | 0.86 |
September | 0.164257E+10 | 0.39 | 2021.46 | 01-SEP-07:02 | 0.86 |
October | 0.166452E+10 | 0.38 | 2021.46 | 01-OCT-07:02 | 0.86 |
November | 0.149883E+10 | 0.37 | 2021.46 | 01-NOV-07:02 | 0.86 |
December | 0.151144E+10 | 0.36 | 2021.46 | 01-DEC-08:62 | 0.86 |
Annual Sum or Average | 0.183851E+11 | 0.37 | |||
Minimum of Months | 0.136056E+10 | 0.36 | 2021.46 | 0.86 | |
Maximum of Months | 0.167344E+10 | 0.39 | 2021.46 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.716259E+09 | 0.39 | 1108.50 | 01-JAN-08:62 | 0.90 |
February | 0.665853E+09 | 0.39 | 1108.50 | 04-FEB-08:62 | 0.90 |
March | 0.728218E+09 | 0.39 | 1108.50 | 01-MAR-08:62 | 0.90 |
April | 0.694464E+09 | 0.39 | 1108.50 | 07-APR-07:03 | 0.90 |
May | 0.750874E+09 | 0.39 | 1108.50 | 01-MAY-07:03 | 0.90 |
June | 0.735829E+09 | 0.39 | 1108.50 | 01-JUN-07:02 | 0.90 |
July | 0.823708E+09 | 0.40 | 1108.50 | 01-JUL-07:02 | 0.90 |
August | 0.843639E+09 | 0.40 | 1108.50 | 01-AUG-07:02 | 0.90 |
September | 0.827025E+09 | 0.41 | 1108.50 | 01-SEP-07:02 | 0.90 |
October | 0.840415E+09 | 0.40 | 1108.50 | 01-OCT-07:02 | 0.90 |
November | 0.743505E+09 | 0.39 | 1108.50 | 01-NOV-07:02 | 0.90 |
December | 0.740064E+09 | 0.39 | 1108.50 | 01-DEC-08:62 | 0.90 |
Annual Sum or Average | 0.910985E+10 | 0.39 | |||
Minimum of Months | 0.665853E+09 | 0.39 | 1108.50 | 0.90 | |
Maximum of Months | 0.843639E+09 | 0.41 | 1108.50 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.672247E+09 | 0.30 | 1152.04 | 01-JAN-08:62 | 0.89 |
February | 0.615242E+09 | 0.30 | 1152.04 | 04-FEB-07:03 | 0.89 |
March | 0.685221E+09 | 0.30 | 1152.04 | 01-MAR-07:03 | 0.89 |
April | 0.649761E+09 | 0.30 | 1152.04 | 01-APR-06:03 | 0.90 |
May | 0.685736E+09 | 0.30 | 1152.04 | 01-MAY-06:03 | 0.90 |
June | 0.670546E+09 | 0.30 | 1152.04 | 01-JUN-06:02 | 0.90 |
July | 0.726200E+09 | 0.31 | 1152.04 | 01-JUL-06:02 | 0.89 |
August | 0.759589E+09 | 0.32 | 1152.04 | 01-AUG-06:02 | 0.89 |
September | 0.726435E+09 | 0.31 | 1152.04 | 01-SEP-06:02 | 0.89 |
October | 0.747620E+09 | 0.31 | 1152.04 | 01-OCT-07:02 | 0.89 |
November | 0.676454E+09 | 0.30 | 1152.04 | 01-NOV-06:02 | 0.89 |
December | 0.677443E+09 | 0.30 | 1152.04 | 01-DEC-07:02 | 0.89 |
Annual Sum or Average | 0.829249E+10 | 0.30 | |||
Minimum of Months | 0.615242E+09 | 0.30 | 1152.04 | 0.89 | |
Maximum of Months | 0.759589E+09 | 0.32 | 1152.04 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.668618E+09 | 0.30 | 1145.34 | 01-JAN-08:62 | 0.89 |
February | 0.612210E+09 | 0.30 | 1145.34 | 04-FEB-07:03 | 0.89 |
March | 0.681510E+09 | 0.30 | 1145.34 | 01-MAR-07:03 | 0.89 |
April | 0.646003E+09 | 0.30 | 1145.34 | 01-APR-06:03 | 0.90 |
May | 0.682871E+09 | 0.30 | 1145.34 | 01-MAY-06:03 | 0.90 |
June | 0.668123E+09 | 0.30 | 1145.34 | 01-JUN-06:02 | 0.90 |
July | 0.725763E+09 | 0.31 | 1145.34 | 01-JUL-06:02 | 0.89 |
August | 0.759009E+09 | 0.32 | 1145.34 | 01-AUG-06:02 | 0.89 |
September | 0.726474E+09 | 0.32 | 1145.34 | 01-SEP-06:02 | 0.89 |
October | 0.747086E+09 | 0.31 | 1145.34 | 01-OCT-07:02 | 0.89 |
November | 0.674030E+09 | 0.30 | 1145.34 | 01-NOV-06:02 | 0.89 |
December | 0.674252E+09 | 0.30 | 1145.34 | 01-DEC-07:02 | 0.89 |
Annual Sum or Average | 0.826595E+10 | 0.30 | |||
Minimum of Months | 0.612210E+09 | 0.30 | 1145.34 | 0.89 | |
Maximum of Months | 0.759009E+09 | 0.32 | 1145.34 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.665723E+09 | 0.30 | 1142.07 | 01-JAN-08:62 | 0.89 |
February | 0.608852E+09 | 0.30 | 1142.07 | 04-FEB-07:03 | 0.89 |
March | 0.678579E+09 | 0.30 | 1142.07 | 01-MAR-07:03 | 0.89 |
April | 0.643780E+09 | 0.30 | 1142.07 | 07-APR-06:02 | 0.90 |
May | 0.678535E+09 | 0.30 | 1142.07 | 03-MAY-06:03 | 0.90 |
June | 0.663341E+09 | 0.30 | 1142.07 | 01-JUN-06:02 | 0.90 |
July | 0.717754E+09 | 0.31 | 1142.07 | 01-JUL-06:02 | 0.89 |
August | 0.750640E+09 | 0.32 | 1142.07 | 01-AUG-06:02 | 0.89 |
September | 0.718469E+09 | 0.31 | 1142.07 | 01-SEP-06:02 | 0.89 |
October | 0.739316E+09 | 0.31 | 1142.07 | 01-OCT-07:02 | 0.89 |
November | 0.669404E+09 | 0.30 | 1142.07 | 01-NOV-06:02 | 0.89 |
December | 0.670417E+09 | 0.30 | 1142.07 | 01-DEC-07:02 | 0.89 |
Annual Sum or Average | 0.820481E+10 | 0.30 | |||
Minimum of Months | 0.608852E+09 | 0.30 | 1142.07 | 0.89 | |
Maximum of Months | 0.750640E+09 | 0.32 | 1142.07 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.100042E+10 | 0.26 | 1849.63 | 01-JAN-09:02 | 0.86 |
February | 0.918854E+09 | 0.27 | 1849.63 | 04-FEB-08:62 | 0.87 |
March | 0.102058E+10 | 0.27 | 1849.63 | 01-MAR-08:62 | 0.87 |
April | 0.963396E+09 | 0.26 | 1849.63 | 07-APR-07:03 | 0.87 |
May | 0.103120E+10 | 0.27 | 1849.63 | 01-MAY-07:03 | 0.87 |
June | 0.101245E+10 | 0.27 | 1849.63 | 01-JUN-07:02 | 0.87 |
July | 0.112038E+10 | 0.28 | 1849.63 | 01-JUL-07:02 | 0.87 |
August | 0.117482E+10 | 0.29 | 1849.63 | 01-AUG-07:02 | 0.86 |
September | 0.112526E+10 | 0.29 | 1849.63 | 01-SEP-07:02 | 0.86 |
October | 0.115563E+10 | 0.29 | 1849.63 | 01-OCT-08:62 | 0.86 |
November | 0.102434E+10 | 0.27 | 1849.63 | 01-NOV-07:02 | 0.86 |
December | 0.101396E+10 | 0.27 | 1849.63 | 01-DEC-08:62 | 0.86 |
Annual Sum or Average | 0.125613E+11 | 0.27 | |||
Minimum of Months | 0.918854E+09 | 0.26 | 1849.63 | 0.86 | |
Maximum of Months | 0.117482E+10 | 0.29 | 1849.63 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.539860E+09 | 0.27 | 998.69 | 01-JAN-09:02 | 0.89 |
February | 0.495697E+09 | 0.28 | 998.69 | 05-FEB-09:02 | 0.89 |
March | 0.550750E+09 | 0.28 | 998.69 | 02-MAR-08:62 | 0.90 |
April | 0.519918E+09 | 0.27 | 998.69 | 07-APR-07:03 | 0.90 |
May | 0.556506E+09 | 0.28 | 998.69 | 01-MAY-07:03 | 0.90 |
June | 0.546078E+09 | 0.28 | 998.69 | 01-JUN-07:02 | 0.90 |
July | 0.604889E+09 | 0.29 | 998.69 | 01-JUL-07:02 | 0.90 |
August | 0.634884E+09 | 0.30 | 998.69 | 01-AUG-07:02 | 0.89 |
September | 0.606999E+09 | 0.30 | 998.69 | 01-SEP-07:02 | 0.89 |
October | 0.624268E+09 | 0.30 | 998.69 | 01-OCT-08:62 | 0.89 |
November | 0.552532E+09 | 0.28 | 998.69 | 01-NOV-07:02 | 0.89 |
December | 0.546983E+09 | 0.27 | 998.69 | 01-DEC-08:62 | 0.89 |
Annual Sum or Average | 0.677936E+10 | 0.28 | |||
Minimum of Months | 0.495697E+09 | 0.27 | 998.69 | 0.89 | |
Maximum of Months | 0.634884E+09 | 0.30 | 998.69 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.536357E+09 | 0.27 | 992.38 | 01-JAN-09:02 | 0.89 |
February | 0.492431E+09 | 0.28 | 992.38 | 05-FEB-09:02 | 0.89 |
March | 0.547182E+09 | 0.28 | 992.38 | 02-MAR-08:62 | 0.90 |
April | 0.516555E+09 | 0.27 | 992.38 | 09-APR-08:62 | 0.90 |
May | 0.552977E+09 | 0.28 | 992.38 | 04-MAY-07:02 | 0.90 |
June | 0.542632E+09 | 0.28 | 992.38 | 01-JUN-07:02 | 0.90 |
July | 0.601276E+09 | 0.29 | 992.38 | 01-JUL-07:02 | 0.90 |
August | 0.631239E+09 | 0.30 | 992.38 | 01-AUG-07:02 | 0.89 |
September | 0.603372E+09 | 0.30 | 992.38 | 01-SEP-07:02 | 0.89 |
October | 0.620573E+09 | 0.30 | 992.38 | 01-OCT-08:62 | 0.89 |
November | 0.548971E+09 | 0.28 | 992.38 | 01-NOV-07:02 | 0.89 |
December | 0.543436E+09 | 0.27 | 992.38 | 01-DEC-08:62 | 0.89 |
Annual Sum or Average | 0.673700E+10 | 0.28 | |||
Minimum of Months | 0.492431E+09 | 0.27 | 992.38 | 0.89 | |
Maximum of Months | 0.631239E+09 | 0.30 | 992.38 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.536417E+09 | 0.27 | 993.21 | 01-JAN-09:02 | 0.89 |
February | 0.492176E+09 | 0.28 | 993.21 | 05-FEB-09:02 | 0.89 |
March | 0.547249E+09 | 0.28 | 993.21 | 02-MAR-08:62 | 0.90 |
April | 0.516733E+09 | 0.27 | 993.21 | 09-APR-08:62 | 0.90 |
May | 0.553540E+09 | 0.28 | 993.21 | 04-MAY-07:02 | 0.90 |
June | 0.543366E+09 | 0.28 | 993.21 | 01-JUN-07:02 | 0.90 |
July | 0.602707E+09 | 0.29 | 993.21 | 01-JUL-07:02 | 0.90 |
August | 0.633200E+09 | 0.30 | 993.21 | 01-AUG-07:02 | 0.89 |
September | 0.604566E+09 | 0.30 | 993.21 | 01-SEP-07:02 | 0.89 |
October | 0.621883E+09 | 0.30 | 993.21 | 01-OCT-08:62 | 0.89 |
November | 0.549086E+09 | 0.28 | 993.21 | 01-NOV-07:02 | 0.89 |
December | 0.543475E+09 | 0.27 | 993.21 | 01-DEC-08:62 | 0.89 |
Annual Sum or Average | 0.674440E+10 | 0.28 | |||
Minimum of Months | 0.492176E+09 | 0.27 | 993.21 | 0.89 | |
Maximum of Months | 0.633200E+09 | 0.30 | 993.21 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.616110E+09 | 0.27 | 1141.50 | 01-JAN-09:02 | 0.89 |
February | 0.563807E+09 | 0.27 | 1141.50 | 17-FEB-08:62 | 0.89 |
March | 0.628391E+09 | 0.28 | 1141.50 | 02-MAR-08:62 | 0.89 |
April | 0.594243E+09 | 0.27 | 1141.50 | 09-APR-08:62 | 0.89 |
May | 0.643437E+09 | 0.28 | 1141.50 | 04-MAY-07:02 | 0.89 |
June | 0.633058E+09 | 0.28 | 1141.50 | 01-JUN-07:02 | 0.89 |
July | 0.706507E+09 | 0.29 | 1141.50 | 01-JUL-07:02 | 0.89 |
August | 0.746167E+09 | 0.31 | 1141.50 | 01-AUG-07:02 | 0.89 |
September | 0.702969E+09 | 0.30 | 1141.50 | 01-SEP-07:02 | 0.89 |
October | 0.727786E+09 | 0.30 | 1141.50 | 01-OCT-08:62 | 0.89 |
November | 0.631576E+09 | 0.28 | 1141.50 | 01-NOV-07:02 | 0.89 |
December | 0.623730E+09 | 0.27 | 1141.50 | 01-DEC-08:62 | 0.89 |
Annual Sum or Average | 0.781778E+10 | 0.29 | |||
Minimum of Months | 0.563807E+09 | 0.27 | 1141.50 | 0.89 | |
Maximum of Months | 0.746167E+09 | 0.31 | 1141.50 | 0.89 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.08 | 1.50 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 1.72 | 0.00 |
August | 1.75 | 0.00 |
September | 1.81 | 0.00 |
October | 1.44 | 0.00 |
November | 0.58 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 7.39 | 0.02 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.81 | 1.50 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 2.22 | 0.00 |
August | 2.08 | 0.00 |
September | 1.81 | 0.00 |
October | 1.94 | 0.00 |
November | 0.83 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 8.89 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.22 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.31 | 0.75 |
February | 0.36 | 0.75 |
March | 0.51 | 0.75 |
April | 0.89 | 0.75 |
May | 1.97 | 0.75 |
June | 2.53 | 0.75 |
July | 3.68 | 0.75 |
August | 3.41 | 0.75 |
September | 2.23 | 0.75 |
October | 2.67 | 0.75 |
November | 1.48 | 0.75 |
December | 0.88 | 0.75 |
Annual Sum or Average | 20.93 | 0.75 |
Minimum of Months | 0.31 | 0.75 |
Maximum of Months | 3.68 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.31 | 0.75 |
February | 0.36 | 0.75 |
March | 0.51 | 0.75 |
April | 0.81 | 0.75 |
May | 1.92 | 0.75 |
June | 2.53 | 0.75 |
July | 3.68 | 0.75 |
August | 3.41 | 0.75 |
September | 2.23 | 0.75 |
October | 2.67 | 0.75 |
November | 1.39 | 0.75 |
December | 0.88 | 0.75 |
Annual Sum or Average | 20.71 | 0.75 |
Minimum of Months | 0.31 | 0.75 |
Maximum of Months | 3.68 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.06 | 0.75 |
February | 0.36 | 0.75 |
March | 0.43 | 0.75 |
April | 0.73 | 0.75 |
May | 1.75 | 0.75 |
June | 2.53 | 0.75 |
July | 3.68 | 0.75 |
August | 3.41 | 0.75 |
September | 2.18 | 0.75 |
October | 2.67 | 0.75 |
November | 1.23 | 0.75 |
December | 0.71 | 0.75 |
Annual Sum or Average | 19.73 | 0.75 |
Minimum of Months | 0.06 | 0.75 |
Maximum of Months | 3.68 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.08 | 3.30 |
March | 0.18 | 3.30 |
April | 0.59 | 3.30 |
May | 0.57 | 3.30 |
June | 0.74 | 3.30 |
July | 1.52 | 2.94 |
August | 1.34 | 2.75 |
September | 1.38 | 2.24 |
October | 1.17 | 2.12 |
November | 0.55 | 3.30 |
December | 0.12 | 3.30 |
Annual Sum or Average | 8.25 | 2.80 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.52 | 3.30 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.18 | 1.65 |
April | 0.42 | 1.65 |
May | 0.57 | 1.65 |
June | 0.63 | 1.65 |
July | 1.35 | 1.45 |
August | 1.16 | 1.41 |
September | 1.27 | 1.07 |
October | 0.90 | 1.04 |
November | 0.41 | 1.65 |
December | 0.12 | 1.65 |
Annual Sum or Average | 7.03 | 1.39 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.35 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.18 | 1.65 |
April | 0.42 | 1.65 |
May | 0.57 | 1.65 |
June | 0.63 | 1.65 |
July | 1.35 | 1.45 |
August | 1.16 | 1.41 |
September | 1.27 | 1.07 |
October | 0.79 | 1.19 |
November | 0.41 | 1.65 |
December | 0.12 | 1.65 |
Annual Sum or Average | 6.91 | 1.41 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.35 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.18 | 1.65 |
April | 0.42 | 1.65 |
May | 0.52 | 1.65 |
June | 0.63 | 1.65 |
July | 1.35 | 1.45 |
August | 1.16 | 1.41 |
September | 1.27 | 1.07 |
October | 0.79 | 1.19 |
November | 0.41 | 1.65 |
December | 0.12 | 1.65 |
Annual Sum or Average | 6.86 | 1.41 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.35 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.24 | 1.65 |
April | 0.59 | 1.65 |
May | 0.63 | 1.65 |
June | 0.74 | 1.65 |
July | 1.77 | 1.26 |
August | 1.95 | 0.95 |
September | 2.05 | 0.76 |
October | 1.58 | 0.78 |
November | 0.55 | 1.65 |
December | 0.29 | 0.71 |
Annual Sum or Average | 10.39 | 1.12 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.05 | 1.65 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.720423E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.731503E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.785224E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.756047E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.929161E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.936737E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.109271E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.111928E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.110507E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.108907E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.909519E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.838771E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.110135E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.720423E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.111928E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.377212E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.376536E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.403755E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.386375E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.468883E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.468935E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.543297E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.556408E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.544593E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.547227E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.460737E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.430390E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.556435E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.376536E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.556408E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.304157E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.303259E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.328914E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.311731E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.383689E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.385887E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.441413E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.462296E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.440787E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.446844E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.378126E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.346856E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.453396E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.303259E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.462296E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.302661E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.302035E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.327648E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.310382E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.382951E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.385367E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.441791E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.462541E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.441509E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.447271E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.377455E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.345764E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.452738E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.302035E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.462541E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.296998E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.296514E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.321690E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.304873E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.377479E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.380133E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.436086E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.456445E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.435863E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.441404E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.372277E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.340329E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.446009E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.296514E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.456445E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.496307E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.501373E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.544327E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.512255E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.649940E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.655925E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.761303E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.801837E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.761637E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.774827E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.640664E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.577587E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.767798E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.496307E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.801837E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.254558E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.256834E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.279020E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.262662E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.333353E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.336132E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.390883E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.411846E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.390738E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.398090E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.328517E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.296157E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.393879E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.254558E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.411846E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.252408E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.254726E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.276796E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.260697E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.331362E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.334182E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.388916E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.409886E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.388756E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.396070E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.326408E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.294019E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.391422E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.252408E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.409886E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.250303E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.252336E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.274570E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.259424E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.331221E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.334205E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.389610E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.411043E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.389240E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.396555E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.325523E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.292447E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.390648E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.250303E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.411043E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.280575E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.277199E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.304897E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.295818E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.380619E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.384004E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.447429E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.474555E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.439679E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.451969E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.364152E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.326127E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.442702E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.277199E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.474555E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.148132E+10 | 0.231825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136056E+10 | 0.248336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148891E+10 | 0.260003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143023E+10 | 0.247874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151462E+10 | 0.318883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147862E+10 | 0.325194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.164002E+10 | 0.382272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167344E+10 | 0.389160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164257E+10 | 0.391689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166452E+10 | 0.379719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149883E+10 | 0.314542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151144E+10 | 0.284016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183851E+11 | 0.377351E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136056E+10 | 0.231825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167344E+10 | 0.391689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.716259E+09 | 0.124747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.665853E+09 | 0.129813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.728218E+09 | 0.135798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.694464E+09 | 0.128639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.750874E+09 | 0.161940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.735829E+09 | 0.163281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.823708E+09 | 0.189765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.843639E+09 | 0.193166E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.827025E+09 | 0.192237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.840415E+09 | 0.191103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.743505E+09 | 0.160634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.740064E+09 | 0.147952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.910985E+10 | 0.191907E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.665853E+09 | 0.124747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.843639E+09 | 0.193166E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.672247E+09 | 0.975870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.615242E+09 | 0.102322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.685221E+09 | 0.107669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.649761E+09 | 0.100873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.685736E+09 | 0.130774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.670546E+09 | 0.133190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.726200E+09 | 0.153659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.759589E+09 | 0.159561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.726435E+09 | 0.155092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.747620E+09 | 0.155100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.676454E+09 | 0.130454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.677443E+09 | 0.117263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.829249E+10 | 0.154354E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.615242E+09 | 0.975870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.759589E+09 | 0.159561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.668618E+09 | 0.971819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.612210E+09 | 0.102006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.681510E+09 | 0.107390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.646003E+09 | 0.100560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.682871E+09 | 0.130720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.668123E+09 | 0.133210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.725763E+09 | 0.153960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.759009E+09 | 0.159813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.726474E+09 | 0.155536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.747086E+09 | 0.155435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.674030E+09 | 0.130393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.674252E+09 | 0.117038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.826595E+10 | 0.154324E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.612210E+09 | 0.971819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.759009E+09 | 0.159813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.665723E+09 | 0.946612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.608852E+09 | 0.995388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.678579E+09 | 0.104714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.643780E+09 | 0.980559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.678535E+09 | 0.128313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.663341E+09 | 0.130926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.717754E+09 | 0.151756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.750640E+09 | 0.157470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.718469E+09 | 0.153328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.739316E+09 | 0.153139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.669404E+09 | 0.128132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.670417E+09 | 0.114611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.820481E+10 | 0.151465E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.608852E+09 | 0.946612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.750640E+09 | 0.157470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.100042E+10 | 0.160407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.918854E+09 | 0.170794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102058E+10 | 0.180020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.963396E+09 | 0.167377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103120E+10 | 0.224042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.101245E+10 | 0.228875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.112038E+10 | 0.267332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117482E+10 | 0.279121E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.112526E+10 | 0.270186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115563E+10 | 0.271398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102434E+10 | 0.223204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101396E+10 | 0.197214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125613E+11 | 0.263997E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.918854E+09 | 0.160407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.117482E+10 | 0.279121E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.539860E+09 | 0.824843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.495697E+09 | 0.878277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.550750E+09 | 0.926185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.519918E+09 | 0.861415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.556506E+09 | 0.115605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.546078E+09 | 0.118005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.604889E+09 | 0.138190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.634884E+09 | 0.144316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.606999E+09 | 0.139563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.624268E+09 | 0.140389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.552532E+09 | 0.115125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.546983E+09 | 0.101589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.677936E+10 | 0.136185E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.495697E+09 | 0.824843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.634884E+09 | 0.144316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.536357E+09 | 0.817138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.492431E+09 | 0.870527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.547182E+09 | 0.918239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.516555E+09 | 0.854560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.552977E+09 | 0.114921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.542632E+09 | 0.117331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.601276E+09 | 0.137536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.631239E+09 | 0.143673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.603372E+09 | 0.138896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.620573E+09 | 0.139715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.548971E+09 | 0.114379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.543436E+09 | 0.100820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.673700E+10 | 0.135332E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.492431E+09 | 0.817138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.631239E+09 | 0.143673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.536417E+09 | 0.807566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.492176E+09 | 0.859571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.547249E+09 | 0.908095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.516733E+09 | 0.848739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.553540E+09 | 0.114820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.543366E+09 | 0.117297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.602707E+09 | 0.137756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.633200E+09 | 0.144069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.604566E+09 | 0.139032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.621883E+09 | 0.139848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.549086E+09 | 0.113933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.543475E+09 | 0.100080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.674440E+10 | 0.134923E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.492176E+09 | 0.807566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.633200E+09 | 0.144069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.616110E+09 | 0.899519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.563807E+09 | 0.931120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.628391E+09 | 0.998689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.594243E+09 | 0.968753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.643437E+09 | 0.131899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.633058E+09 | 0.134658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.706507E+09 | 0.157587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.746167E+09 | 0.165726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.702969E+09 | 0.155848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.727786E+09 | 0.158350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.631576E+09 | 0.126517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.623730E+09 | 0.110676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.781778E+10 | 0.152107E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.563807E+09 | 0.899519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.746167E+09 | 0.165726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.148132E+10 | 0.00 | 0.00 | 0.00 | 0.572291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136056E+10 | 0.00 | 0.00 | 0.00 | 0.595446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148891E+10 | 0.00 | 0.00 | 0.00 | 0.636333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143023E+10 | 0.00 | 0.00 | 0.00 | 0.613023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151462E+10 | 0.00 | 0.00 | 0.00 | 0.777699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147862E+10 | 0.00 | 0.00 | 0.00 | 0.788875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.164002E+10 | 0.00 | 0.00 | 0.00 | 0.928706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167344E+10 | 0.00 | 0.00 | 0.00 | 0.951937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164257E+10 | 0.00 | 0.00 | 0.00 | 0.940810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166452E+10 | 0.00 | 0.00 | 0.00 | 0.922618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149883E+10 | 0.00 | 0.00 | 0.00 | 0.759636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151144E+10 | 0.00 | 0.00 | 0.00 | 0.687627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183851E+11 | 0.00 | 0.00 | 0.00 | 0.917500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.136056E+10 | 0.00 | 0.00 | 0.00 | 0.572291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167344E+10 | 0.00 | 0.00 | 0.00 | 0.951937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.716259E+09 | 0.00 | 0.00 | 0.00 | 0.305586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.665853E+09 | 0.00 | 0.00 | 0.00 | 0.309951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.728218E+09 | 0.00 | 0.00 | 0.00 | 0.330933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.694464E+09 | 0.00 | 0.00 | 0.00 | 0.316929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.750874E+09 | 0.00 | 0.00 | 0.00 | 0.393796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.735829E+09 | 0.00 | 0.00 | 0.00 | 0.395352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.823708E+09 | 0.00 | 0.00 | 0.00 | 0.460926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.843639E+09 | 0.00 | 0.00 | 0.00 | 0.472044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.827025E+09 | 0.00 | 0.00 | 0.00 | 0.461891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.840415E+09 | 0.00 | 0.00 | 0.00 | 0.463185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.743505E+09 | 0.00 | 0.00 | 0.00 | 0.386386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.740064E+09 | 0.00 | 0.00 | 0.00 | 0.356384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.910985E+10 | 0.00 | 0.00 | 0.00 | 0.465336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.665853E+09 | 0.00 | 0.00 | 0.00 | 0.305586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.843639E+09 | 0.00 | 0.00 | 0.00 | 0.472044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.672247E+09 | 0.00 | 0.00 | 0.00 | 0.236932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.615242E+09 | 0.00 | 0.00 | 0.00 | 0.241735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.685221E+09 | 0.00 | 0.00 | 0.00 | 0.260391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.649761E+09 | 0.00 | 0.00 | 0.00 | 0.246755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.685736E+09 | 0.00 | 0.00 | 0.00 | 0.315116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.670546E+09 | 0.00 | 0.00 | 0.00 | 0.318832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.726200E+09 | 0.00 | 0.00 | 0.00 | 0.368793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.759589E+09 | 0.00 | 0.00 | 0.00 | 0.386337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.726435E+09 | 0.00 | 0.00 | 0.00 | 0.368144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.747620E+09 | 0.00 | 0.00 | 0.00 | 0.372082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.676454E+09 | 0.00 | 0.00 | 0.00 | 0.310481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.677443E+09 | 0.00 | 0.00 | 0.00 | 0.279112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.829249E+10 | 0.00 | 0.00 | 0.00 | 0.370471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.615242E+09 | 0.00 | 0.00 | 0.00 | 0.236932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.759589E+09 | 0.00 | 0.00 | 0.00 | 0.386337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.668618E+09 | 0.00 | 0.00 | 0.00 | 0.235799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.612210E+09 | 0.00 | 0.00 | 0.00 | 0.240814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.681510E+09 | 0.00 | 0.00 | 0.00 | 0.259497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.646003E+09 | 0.00 | 0.00 | 0.00 | 0.245782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.682871E+09 | 0.00 | 0.00 | 0.00 | 0.314664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.668123E+09 | 0.00 | 0.00 | 0.00 | 0.318554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.725763E+09 | 0.00 | 0.00 | 0.00 | 0.369215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.759009E+09 | 0.00 | 0.00 | 0.00 | 0.386641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.726474E+09 | 0.00 | 0.00 | 0.00 | 0.368862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.747086E+09 | 0.00 | 0.00 | 0.00 | 0.372563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.674030E+09 | 0.00 | 0.00 | 0.00 | 0.310052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.674252E+09 | 0.00 | 0.00 | 0.00 | 0.278339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.826595E+10 | 0.00 | 0.00 | 0.00 | 0.370078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.612210E+09 | 0.00 | 0.00 | 0.00 | 0.235799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.759009E+09 | 0.00 | 0.00 | 0.00 | 0.386641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.665723E+09 | 0.00 | 0.00 | 0.00 | 0.230426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.608852E+09 | 0.00 | 0.00 | 0.00 | 0.235629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.678579E+09 | 0.00 | 0.00 | 0.00 | 0.253833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.643780E+09 | 0.00 | 0.00 | 0.00 | 0.240495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.678535E+09 | 0.00 | 0.00 | 0.00 | 0.309625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.663341E+09 | 0.00 | 0.00 | 0.00 | 0.313798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.717754E+09 | 0.00 | 0.00 | 0.00 | 0.364311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.750640E+09 | 0.00 | 0.00 | 0.00 | 0.381381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.718469E+09 | 0.00 | 0.00 | 0.00 | 0.364016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.739316E+09 | 0.00 | 0.00 | 0.00 | 0.367472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.669404E+09 | 0.00 | 0.00 | 0.00 | 0.305337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.670417E+09 | 0.00 | 0.00 | 0.00 | 0.273287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.820481E+10 | 0.00 | 0.00 | 0.00 | 0.363961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.608852E+09 | 0.00 | 0.00 | 0.00 | 0.230426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.750640E+09 | 0.00 | 0.00 | 0.00 | 0.381381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.100042E+10 | 0.00 | 0.00 | 0.00 | 0.396265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.918854E+09 | 0.00 | 0.00 | 0.00 | 0.409487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102058E+10 | 0.00 | 0.00 | 0.00 | 0.442269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.963396E+09 | 0.00 | 0.00 | 0.00 | 0.415916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103120E+10 | 0.00 | 0.00 | 0.00 | 0.546820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.101245E+10 | 0.00 | 0.00 | 0.00 | 0.554680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.112038E+10 | 0.00 | 0.00 | 0.00 | 0.649264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117482E+10 | 0.00 | 0.00 | 0.00 | 0.684355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.112526E+10 | 0.00 | 0.00 | 0.00 | 0.649111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115563E+10 | 0.00 | 0.00 | 0.00 | 0.659265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102434E+10 | 0.00 | 0.00 | 0.00 | 0.538230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101396E+10 | 0.00 | 0.00 | 0.00 | 0.476191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125613E+11 | 0.00 | 0.00 | 0.00 | 0.642185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.918854E+09 | 0.00 | 0.00 | 0.00 | 0.396265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.117482E+10 | 0.00 | 0.00 | 0.00 | 0.684355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.539860E+09 | 0.00 | 0.00 | 0.00 | 0.200572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.495697E+09 | 0.00 | 0.00 | 0.00 | 0.207264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.550750E+09 | 0.00 | 0.00 | 0.00 | 0.223945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.519918E+09 | 0.00 | 0.00 | 0.00 | 0.210670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.556506E+09 | 0.00 | 0.00 | 0.00 | 0.277702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.546078E+09 | 0.00 | 0.00 | 0.00 | 0.281525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.604889E+09 | 0.00 | 0.00 | 0.00 | 0.330394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.634884E+09 | 0.00 | 0.00 | 0.00 | 0.348357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.606999E+09 | 0.00 | 0.00 | 0.00 | 0.330038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.624268E+09 | 0.00 | 0.00 | 0.00 | 0.335663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.552532E+09 | 0.00 | 0.00 | 0.00 | 0.273264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.546983E+09 | 0.00 | 0.00 | 0.00 | 0.241459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.677936E+10 | 0.00 | 0.00 | 0.00 | 0.326085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.495697E+09 | 0.00 | 0.00 | 0.00 | 0.200572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.634884E+09 | 0.00 | 0.00 | 0.00 | 0.348357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.536357E+09 | 0.00 | 0.00 | 0.00 | 0.198772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.492431E+09 | 0.00 | 0.00 | 0.00 | 0.205482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.547182E+09 | 0.00 | 0.00 | 0.00 | 0.222078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.516555E+09 | 0.00 | 0.00 | 0.00 | 0.209042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.552977E+09 | 0.00 | 0.00 | 0.00 | 0.276064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.542632E+09 | 0.00 | 0.00 | 0.00 | 0.279919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.601276E+09 | 0.00 | 0.00 | 0.00 | 0.328788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.631239E+09 | 0.00 | 0.00 | 0.00 | 0.346762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.603372E+09 | 0.00 | 0.00 | 0.00 | 0.328419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.620573E+09 | 0.00 | 0.00 | 0.00 | 0.334012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.548971E+09 | 0.00 | 0.00 | 0.00 | 0.271511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.543436E+09 | 0.00 | 0.00 | 0.00 | 0.239676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.673700E+10 | 0.00 | 0.00 | 0.00 | 0.324052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.492431E+09 | 0.00 | 0.00 | 0.00 | 0.198772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.631239E+09 | 0.00 | 0.00 | 0.00 | 0.346762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.536417E+09 | 0.00 | 0.00 | 0.00 | 0.196661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.492176E+09 | 0.00 | 0.00 | 0.00 | 0.203119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.547249E+09 | 0.00 | 0.00 | 0.00 | 0.219845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.516733E+09 | 0.00 | 0.00 | 0.00 | 0.207751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.553540E+09 | 0.00 | 0.00 | 0.00 | 0.275867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.543366E+09 | 0.00 | 0.00 | 0.00 | 0.279869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.602707E+09 | 0.00 | 0.00 | 0.00 | 0.329340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.633200E+09 | 0.00 | 0.00 | 0.00 | 0.347723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.604566E+09 | 0.00 | 0.00 | 0.00 | 0.328783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.621883E+09 | 0.00 | 0.00 | 0.00 | 0.334366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.549086E+09 | 0.00 | 0.00 | 0.00 | 0.270615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.543475E+09 | 0.00 | 0.00 | 0.00 | 0.238099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.674440E+10 | 0.00 | 0.00 | 0.00 | 0.323204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.492176E+09 | 0.00 | 0.00 | 0.00 | 0.196661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.633200E+09 | 0.00 | 0.00 | 0.00 | 0.347723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.616110E+09 | 0.00 | 0.00 | 0.00 | 0.218964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.563807E+09 | 0.00 | 0.00 | 0.00 | 0.220818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.628391E+09 | 0.00 | 0.00 | 0.00 | 0.242058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.594243E+09 | 0.00 | 0.00 | 0.00 | 0.236394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.643437E+09 | 0.00 | 0.00 | 0.00 | 0.316275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.633058E+09 | 0.00 | 0.00 | 0.00 | 0.320698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.706507E+09 | 0.00 | 0.00 | 0.00 | 0.376778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.746167E+09 | 0.00 | 0.00 | 0.00 | 0.399938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.702969E+09 | 0.00 | 0.00 | 0.00 | 0.369382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.727786E+09 | 0.00 | 0.00 | 0.00 | 0.379190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.631576E+09 | 0.00 | 0.00 | 0.00 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.623730E+09 | 0.00 | 0.00 | 0.00 | 0.263754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.781778E+10 | 0.00 | 0.00 | 0.00 | 0.364524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.563807E+09 | 0.00 | 0.00 | 0.00 | 0.218964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.746167E+09 | 0.00 | 0.00 | 0.00 | 0.399938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 14044388.57 | 0.460436E+10 | 0.00 | 2692701.36 | 39062784.40 | 0.00 | 0.163993E+09 | 0.00 | 0.57 |
February | 16185108.31 | 0.673728E+10 | 0.00 | 1526980.80 | 77228143.93 | 0.00 | 0.131137E+09 | 0.00 | 0.57 |
March | 21077051.96 | 0.630851E+10 | 0.00 | 1170548.68 | 40516586.02 | 0.00 | 81585255.45 | 0.00 | 0.57 |
April | 6167347.00 | 0.597820E+10 | 0.00 | 454141.42 | 56185356.84 | 0.00 | 15742125.93 | 0.00 | 0.57 |
May | 0.00 | 0.962379E+10 | 0.00 | 15261.82 | 89949163.00 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.00 | 0.996034E+10 | 0.00 | 0.00 | 89671447.94 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 175094.07 | 0.127473E+11 | 0.00 | 151645.89 | 82294449.37 | 0.00 | 277463.57 | 0.00 | 0.57 |
August | 0.00 | 0.132220E+11 | 0.00 | 0.00 | 98648958.57 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.135103E+11 | 0.00 | 0.00 | 87222628.87 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 0.00 | 0.127895E+11 | 0.00 | 64300.01 | 99702185.87 | 0.00 | 0.00 | 0.00 | 0.57 |
November | 47782.25 | 0.916313E+10 | 0.00 | 119307.82 | 73337403.88 | 0.00 | 1473252.59 | 0.00 | 0.57 |
December | 1682579.83 | 0.739948E+10 | 0.00 | 603096.49 | 51387610.23 | 0.00 | 15816491.95 | 0.00 | 0.57 |
Annual Sum or Average | 59379352.00 | 0.112044E+12 | 0.00 | 6797984.29 | 0.885207E+09 | 0.00 | 0.410024E+09 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 0.460436E+10 | 0.00 | 0.00 | 39062784.40 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 21077051.96 | 0.135103E+11 | 0.00 | 2692701.36 | 99702185.87 | 0.00 | 0.163993E+09 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2520733.44 | 0.227288E+10 | 0.00 | 973681.17 | 43061060.16 | 0.00 | 31383239.01 | 0.00 | 0.47 |
February | 1516562.99 | 0.315089E+10 | 0.00 | 725158.37 | 66640661.03 | 0.00 | 18636438.54 | 0.00 | 0.48 |
March | 1510298.30 | 0.297497E+10 | 0.00 | 291641.70 | 43975179.45 | 0.00 | 8211351.68 | 0.00 | 0.48 |
April | 1161992.93 | 0.278753E+10 | 0.00 | 99294.31 | 55027012.50 | 0.00 | 2392201.69 | 0.00 | 0.47 |
May | 0.00 | 0.435994E+10 | 0.00 | 0.00 | 69816477.05 | 0.00 | 0.00 | 0.00 | 0.48 |
June | 0.00 | 0.446483E+10 | 0.00 | 0.00 | 67053310.28 | 0.00 | 0.00 | 0.00 | 0.48 |
July | 0.00 | 0.565590E+10 | 0.00 | 0.00 | 67316361.01 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.591149E+10 | 0.00 | 0.00 | 74037050.64 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.593710E+10 | 0.00 | 0.00 | 66081104.45 | 0.00 | 0.00 | 0.00 | 0.49 |
October | 0.00 | 0.574160E+10 | 0.00 | 0.00 | 77658698.11 | 0.00 | 0.00 | 0.00 | 0.49 |
November | 0.00 | 0.420026E+10 | 0.00 | 0.00 | 63514110.65 | 0.00 | 0.00 | 0.00 | 0.48 |
December | 58527.29 | 0.343262E+10 | 0.00 | 90210.99 | 53132104.40 | 0.00 | 727001.41 | 0.00 | 0.47 |
Annual Sum or Average | 6768114.94 | 0.508900E+11 | 0.00 | 2179986.54 | 0.747313E+09 | 0.00 | 61350232.33 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.227288E+10 | 0.00 | 0.00 | 43061060.16 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 2520733.44 | 0.593710E+10 | 0.00 | 973681.17 | 77658698.11 | 0.00 | 31383239.01 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 40354149.59 | 0.189032E+10 | 0.00 | 1108812.66 | 60857575.99 | 0.00 | 74644692.03 | 0.00 | 0.45 |
February | 29196483.87 | 0.256624E+10 | 0.00 | 674168.83 | 0.124774E+09 | 0.00 | 41730062.92 | 0.00 | 0.46 |
March | 28141507.20 | 0.246229E+10 | 0.00 | 641408.96 | 0.105475E+09 | 0.00 | 58784836.72 | 0.00 | 0.46 |
April | 12336011.14 | 0.229657E+10 | 0.00 | 473324.22 | 0.104022E+09 | 0.00 | 25590312.23 | 0.00 | 0.46 |
May | 1319275.61 | 0.362689E+10 | 0.00 | 401960.40 | 0.205331E+09 | 0.00 | 1657999.24 | 0.00 | 0.46 |
June | 0.00 | 0.377821E+10 | 0.00 | 51755.71 | 0.233432E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.467479E+10 | 0.00 | 87564.93 | 0.291539E+09 | 0.00 | 11417.15 | 0.00 | 0.45 |
August | 0.00 | 0.493871E+10 | 0.00 | 189485.79 | 0.309184E+09 | 0.00 | 56949.83 | 0.00 | 0.46 |
September | 7010.44 | 0.476980E+10 | 0.00 | 253215.14 | 0.302605E+09 | 0.00 | 301302.90 | 0.00 | 0.46 |
October | 713983.27 | 0.466538E+10 | 0.00 | 562450.24 | 0.276070E+09 | 0.00 | 2896255.88 | 0.00 | 0.46 |
November | 3269878.26 | 0.354157E+10 | 0.00 | 322587.51 | 0.173581E+09 | 0.00 | 4922022.01 | 0.00 | 0.46 |
December | 8025966.91 | 0.283017E+10 | 0.00 | 700540.81 | 0.136533E+09 | 0.00 | 14556478.53 | 0.00 | 0.45 |
Annual Sum or Average | 0.123364E+09 | 0.420409E+11 | 0.00 | 5467275.21 | 0.232340E+10 | 0.00 | 0.225152E+09 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.189032E+10 | 0.00 | 51755.71 | 60857575.99 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 40354149.59 | 0.493871E+10 | 0.00 | 1108812.66 | 0.309184E+09 | 0.00 | 74644692.03 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 40550244.39 | 0.188544E+10 | 0.00 | 1101733.81 | 60730830.56 | 0.00 | 75782191.30 | 0.00 | 0.45 |
February | 30089221.41 | 0.256163E+10 | 0.00 | 670602.83 | 0.124432E+09 | 0.00 | 41352812.90 | 0.00 | 0.46 |
March | 28717213.16 | 0.245890E+10 | 0.00 | 635503.13 | 0.105234E+09 | 0.00 | 58765897.09 | 0.00 | 0.46 |
April | 12380786.13 | 0.229236E+10 | 0.00 | 467039.67 | 0.103790E+09 | 0.00 | 25906330.67 | 0.00 | 0.46 |
May | 1317445.49 | 0.362650E+10 | 0.00 | 408707.19 | 0.205171E+09 | 0.00 | 1657975.38 | 0.00 | 0.46 |
June | 0.00 | 0.377918E+10 | 0.00 | 55550.69 | 0.232955E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.468371E+10 | 0.00 | 93923.60 | 0.287769E+09 | 0.00 | 12144.13 | 0.00 | 0.45 |
August | 0.00 | 0.494540E+10 | 0.00 | 199186.89 | 0.306477E+09 | 0.00 | 58239.43 | 0.00 | 0.46 |
September | 6309.37 | 0.477949E+10 | 0.00 | 267775.01 | 0.301378E+09 | 0.00 | 302022.84 | 0.00 | 0.46 |
October | 701704.87 | 0.467428E+10 | 0.00 | 583220.48 | 0.273468E+09 | 0.00 | 2866747.26 | 0.00 | 0.46 |
November | 3276556.80 | 0.354133E+10 | 0.00 | 327772.32 | 0.173086E+09 | 0.00 | 5001979.97 | 0.00 | 0.46 |
December | 8042542.54 | 0.282762E+10 | 0.00 | 703066.77 | 0.136053E+09 | 0.00 | 14856679.21 | 0.00 | 0.45 |
Annual Sum or Average | 0.125082E+09 | 0.420558E+11 | 0.00 | 5514082.39 | 0.231054E+10 | 0.00 | 0.226563E+09 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.188544E+10 | 0.00 | 55550.69 | 60730830.56 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 40550244.39 | 0.494540E+10 | 0.00 | 1101733.81 | 0.306477E+09 | 0.00 | 75782191.30 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 41813158.78 | 0.185327E+10 | 0.00 | 1029525.11 | 59405643.22 | 0.00 | 80295126.54 | 0.00 | 0.45 |
February | 34184715.32 | 0.251953E+10 | 0.00 | 638360.94 | 0.123279E+09 | 0.00 | 39508115.95 | 0.00 | 0.46 |
March | 32954558.13 | 0.241985E+10 | 0.00 | 573056.86 | 0.103444E+09 | 0.00 | 57531947.72 | 0.00 | 0.46 |
April | 13211736.47 | 0.225639E+10 | 0.00 | 420990.01 | 0.102855E+09 | 0.00 | 26864909.65 | 0.00 | 0.46 |
May | 1179964.52 | 0.358935E+10 | 0.00 | 363464.17 | 0.204483E+09 | 0.00 | 1811337.65 | 0.00 | 0.46 |
June | 0.00 | 0.374543E+10 | 0.00 | 46222.39 | 0.231189E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.464868E+10 | 0.00 | 83055.32 | 0.290820E+09 | 0.00 | 11461.63 | 0.00 | 0.45 |
August | 0.00 | 0.491063E+10 | 0.00 | 181094.75 | 0.306768E+09 | 0.00 | 56721.03 | 0.00 | 0.46 |
September | 7968.98 | 0.474307E+10 | 0.00 | 247673.18 | 0.302837E+09 | 0.00 | 305503.03 | 0.00 | 0.46 |
October | 747070.44 | 0.463725E+10 | 0.00 | 536063.62 | 0.274778E+09 | 0.00 | 3170959.35 | 0.00 | 0.46 |
November | 3314547.12 | 0.350365E+10 | 0.00 | 295786.97 | 0.174422E+09 | 0.00 | 5245199.66 | 0.00 | 0.46 |
December | 8325393.84 | 0.279070E+10 | 0.00 | 652018.26 | 0.135240E+09 | 0.00 | 16028898.70 | 0.00 | 0.45 |
Annual Sum or Average | 0.135739E+09 | 0.416178E+11 | 0.00 | 5067311.60 | 0.230952E+10 | 0.00 | 0.230830E+09 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.185327E+10 | 0.00 | 46222.39 | 59405643.22 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 41813158.78 | 0.491063E+10 | 0.00 | 1029525.11 | 0.306768E+09 | 0.00 | 80295126.54 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 33559708.27 | 0.339153E+10 | 0.00 | 1544575.10 | 64273580.41 | 0.00 | 0.122471E+09 | 0.00 | 0.42 |
February | 17796103.89 | 0.470540E+10 | 0.00 | 843323.96 | 0.122871E+09 | 0.00 | 61863226.48 | 0.00 | 0.42 |
March | 23846037.63 | 0.453592E+10 | 0.00 | 607991.79 | 89275768.53 | 0.00 | 39368890.69 | 0.00 | 0.43 |
April | 12231034.22 | 0.421330E+10 | 0.00 | 354951.57 | 0.107660E+09 | 0.00 | 18308590.51 | 0.00 | 0.42 |
May | 42702.39 | 0.686372E+10 | 0.00 | 261954.98 | 0.180662E+09 | 0.00 | 636667.62 | 0.00 | 0.42 |
June | 0.00 | 0.711081E+10 | 0.00 | 8236.61 | 0.177419E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 303909.44 | 0.888169E+10 | 0.00 | 146272.55 | 0.250533E+09 | 0.00 | 375729.65 | 0.00 | 0.42 |
August | 0.00 | 0.951875E+10 | 0.00 | 106071.96 | 0.231188E+09 | 0.00 | 1110.52 | 0.00 | 0.43 |
September | 0.00 | 0.907254E+10 | 0.00 | 249147.38 | 0.256909E+09 | 0.00 | 241380.79 | 0.00 | 0.42 |
October | 356045.43 | 0.900819E+10 | 0.00 | 356301.23 | 0.253797E+09 | 0.00 | 847628.27 | 0.00 | 0.42 |
November | 4943127.27 | 0.660797E+10 | 0.00 | 54980.95 | 0.144620E+09 | 0.00 | 1946495.99 | 0.00 | 0.42 |
December | 7859178.48 | 0.522857E+10 | 0.00 | 886534.29 | 0.114304E+09 | 0.00 | 11964641.78 | 0.00 | 0.42 |
Annual Sum or Average | 0.100938E+09 | 0.791384E+11 | 0.00 | 5420342.35 | 0.199351E+10 | 0.00 | 0.258025E+09 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.339153E+10 | 0.00 | 8236.61 | 64273580.41 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 33559708.27 | 0.951875E+10 | 0.00 | 1544575.10 | 0.256909E+09 | 0.00 | 0.122471E+09 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 16784087.23 | 0.167543E+10 | 0.00 | 772760.43 | 30573517.59 | 0.00 | 62823761.93 | 0.00 | 0.42 |
February | 8946354.47 | 0.232396E+10 | 0.00 | 421234.18 | 58676605.16 | 0.00 | 31083276.03 | 0.00 | 0.42 |
March | 12159546.19 | 0.224242E+10 | 0.00 | 296153.36 | 43461759.50 | 0.00 | 19778975.66 | 0.00 | 0.43 |
April | 5531325.52 | 0.208614E+10 | 0.00 | 171811.00 | 52670439.44 | 0.00 | 9868527.56 | 0.00 | 0.42 |
May | 77509.15 | 0.340711E+10 | 0.00 | 125444.24 | 88528706.12 | 0.00 | 293828.87 | 0.00 | 0.42 |
June | 0.00 | 0.353163E+10 | 0.00 | 5011.04 | 86143380.39 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 138533.62 | 0.442018E+10 | 0.00 | 68331.66 | 0.120901E+09 | 0.00 | 172531.36 | 0.00 | 0.42 |
August | 0.00 | 0.473612E+10 | 0.00 | 53097.61 | 0.115159E+09 | 0.00 | 3394.06 | 0.00 | 0.43 |
September | 0.00 | 0.450833E+10 | 0.00 | 125604.76 | 0.126330E+09 | 0.00 | 140064.18 | 0.00 | 0.42 |
October | 234733.41 | 0.447857E+10 | 0.00 | 176064.11 | 0.125378E+09 | 0.00 | 458285.51 | 0.00 | 0.42 |
November | 2586011.62 | 0.327621E+10 | 0.00 | 25597.10 | 72242834.19 | 0.00 | 999957.19 | 0.00 | 0.42 |
December | 4221776.69 | 0.258715E+10 | 0.00 | 423043.00 | 56035370.82 | 0.00 | 5872284.21 | 0.00 | 0.42 |
Annual Sum or Average | 50679877.90 | 0.392732E+11 | 0.00 | 2664152.48 | 0.976100E+09 | 0.00 | 0.131495E+09 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.167543E+10 | 0.00 | 5011.04 | 30573517.59 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 16784087.23 | 0.473612E+10 | 0.00 | 772760.43 | 0.126330E+09 | 0.00 | 62823761.93 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 17004025.22 | 0.166583E+10 | 0.00 | 766516.78 | 30519404.96 | 0.00 | 64311545.71 | 0.00 | 0.42 |
February | 9577709.76 | 0.231090E+10 | 0.00 | 416171.68 | 58250170.80 | 0.00 | 30969006.89 | 0.00 | 0.42 |
March | 12346896.24 | 0.223129E+10 | 0.00 | 286463.15 | 42765856.47 | 0.00 | 20124884.68 | 0.00 | 0.43 |
April | 5607619.70 | 0.207648E+10 | 0.00 | 165580.20 | 52731627.95 | 0.00 | 10098967.33 | 0.00 | 0.42 |
May | 77435.50 | 0.339842E+10 | 0.00 | 122624.76 | 87922584.95 | 0.00 | 292173.25 | 0.00 | 0.42 |
June | 0.00 | 0.352197E+10 | 0.00 | 3888.54 | 86706818.31 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 143632.12 | 0.441164E+10 | 0.00 | 67003.87 | 0.121192E+09 | 0.00 | 179928.28 | 0.00 | 0.42 |
August | 0.00 | 0.472850E+10 | 0.00 | 52490.35 | 0.114765E+09 | 0.00 | 3357.51 | 0.00 | 0.43 |
September | 0.00 | 0.449743E+10 | 0.00 | 123173.93 | 0.128004E+09 | 0.00 | 140832.50 | 0.00 | 0.42 |
October | 245730.20 | 0.446968E+10 | 0.00 | 173573.81 | 0.125362E+09 | 0.00 | 457922.47 | 0.00 | 0.42 |
November | 2597735.51 | 0.326429E+10 | 0.00 | 24530.29 | 73250016.46 | 0.00 | 1026879.76 | 0.00 | 0.42 |
December | 4232574.08 | 0.257589E+10 | 0.00 | 414404.03 | 55817850.84 | 0.00 | 6076792.23 | 0.00 | 0.42 |
Annual Sum or Average | 51833358.33 | 0.391523E+11 | 0.00 | 2616421.38 | 0.977288E+09 | 0.00 | 0.133682E+09 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.166583E+10 | 0.00 | 3888.54 | 30519404.96 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 17004025.22 | 0.472850E+10 | 0.00 | 766516.78 | 0.128004E+09 | 0.00 | 64311545.71 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 18269974.82 | 0.164963E+10 | 0.00 | 743751.69 | 30127201.42 | 0.00 | 66931743.70 | 0.00 | 0.42 |
February | 12188286.72 | 0.228664E+10 | 0.00 | 400456.12 | 57579732.80 | 0.00 | 29480869.68 | 0.00 | 0.42 |
March | 13724292.05 | 0.220888E+10 | 0.00 | 261648.82 | 44104791.78 | 0.00 | 20016291.39 | 0.00 | 0.43 |
April | 6521999.68 | 0.206384E+10 | 0.00 | 155297.95 | 52307000.27 | 0.00 | 9964242.17 | 0.00 | 0.42 |
May | 72976.45 | 0.339493E+10 | 0.00 | 115172.21 | 86796392.46 | 0.00 | 281038.14 | 0.00 | 0.42 |
June | 0.00 | 0.351845E+10 | 0.00 | 1993.59 | 86870529.04 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 182745.26 | 0.440968E+10 | 0.00 | 58753.66 | 0.124632E+09 | 0.00 | 189393.92 | 0.00 | 0.42 |
August | 0.00 | 0.473205E+10 | 0.00 | 50829.87 | 0.115184E+09 | 0.00 | 2871.89 | 0.00 | 0.43 |
September | 0.00 | 0.449725E+10 | 0.00 | 118317.02 | 0.127878E+09 | 0.00 | 139198.98 | 0.00 | 0.42 |
October | 194962.12 | 0.447061E+10 | 0.00 | 164718.32 | 0.123773E+09 | 0.00 | 527230.65 | 0.00 | 0.42 |
November | 2612807.89 | 0.325309E+10 | 0.00 | 22020.86 | 73704193.94 | 0.00 | 1124104.14 | 0.00 | 0.42 |
December | 4219819.21 | 0.256017E+10 | 0.00 | 386001.39 | 55807961.14 | 0.00 | 6622133.55 | 0.00 | 0.42 |
Annual Sum or Average | 57987864.20 | 0.390452E+11 | 0.00 | 2478961.50 | 0.978765E+09 | 0.00 | 0.135279E+09 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.164963E+10 | 0.00 | 1993.59 | 30127201.42 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 18269974.82 | 0.473205E+10 | 0.00 | 743751.69 | 0.127878E+09 | 0.00 | 66931743.70 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 19547113.38 | 0.170752E+10 | 0.00 | 796124.81 | 20816712.14 | 0.00 | 72678343.14 | 0.00 | 0.42 |
February | 17061697.29 | 0.231394E+10 | 0.00 | 383541.46 | 47080183.83 | 0.00 | 30652929.30 | 0.00 | 0.42 |
March | 23292503.99 | 0.223374E+10 | 0.00 | 263509.67 | 35718867.37 | 0.00 | 18382681.67 | 0.00 | 0.43 |
April | 7776955.57 | 0.214810E+10 | 0.00 | 198545.94 | 41710678.13 | 0.00 | 12093074.25 | 0.00 | 0.42 |
May | 65971.20 | 0.353154E+10 | 0.00 | 164126.00 | 72145969.08 | 0.00 | 303882.10 | 0.00 | 0.42 |
June | 0.00 | 0.365231E+10 | 0.00 | 60592.09 | 65900032.94 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 209811.10 | 0.455022E+10 | 0.00 | 155181.94 | 0.104612E+09 | 0.00 | 1482571.28 | 0.00 | 0.42 |
August | 0.00 | 0.488791E+10 | 0.00 | 54430.87 | 99867230.16 | 0.00 | 703.50 | 0.00 | 0.43 |
September | 0.00 | 0.458235E+10 | 0.00 | 167999.99 | 0.116518E+09 | 0.00 | 136674.42 | 0.00 | 0.42 |
October | 240954.89 | 0.460841E+10 | 0.00 | 204665.90 | 0.109211E+09 | 0.00 | 479730.89 | 0.00 | 0.42 |
November | 2693332.13 | 0.332915E+10 | 0.00 | 88159.87 | 55534019.06 | 0.00 | 1605185.93 | 0.00 | 0.42 |
December | 4466351.69 | 0.262769E+10 | 0.00 | 453368.75 | 47012963.96 | 0.00 | 8810389.00 | 0.00 | 0.42 |
Annual Sum or Average | 75354691.25 | 0.401729E+11 | 0.00 | 2990247.29 | 0.816128E+09 | 0.00 | 0.146626E+09 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.170752E+10 | 0.00 | 54430.87 | 20816712.14 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 23292503.99 | 0.488791E+10 | 0.00 | 796124.81 | 0.116518E+09 | 0.00 | 72678343.14 | 0.00 | 0.43 |